26-008-ITB_Backup_AOC_Construction_-_Drawings.pdf

PDF 17 MB Posted

Attached to
Backup Airport Operations Center (AOC) Construction
Solicitation number
26-008-ITB
Issued by
Bell County, Kentucky

About this file

This document comprises electrical construction drawings and specifications prepared by Emboss Design, P.S.C., for the Backup Airport Operations Center (AOC) Interior Modifications at Cincinnati/Northern Kentucky International Airport's South ARFF Fire Station, located at 2100 Tower Drive, Hebron, Kentucky. The project involves comprehensive electrical modifications including demolition of existing systems, installation of new power distribution, lighting control systems, data and voice cabling infrastructure, fire alarm integration, access control devices, and audio/visual system support. Key project elements include the installation of a new 8 kVA UPS system, transformer specifications (75 kVA units designated TX-2 and TR-1), new isolated ground bars, cable tray systems beneath raised flooring platforms, conduit routing through multiple building levels, and coordination with existing Honeywell systems and network infrastructure. The drawings indicate that a pre-bid meeting and site visit are scheduled for Thursday, February 26, 2026, at 1:00 pm at the South ARFF Station, with questions due by Monday, March 9, 2026, and answers posted by Thursday, March 12, 2026. Bids must be received by Thursday, March 19, 2026, at 2:00 pm.

The electrical work is designated with a responsibility matrix identifying items as Contractor Furnished/Contractor Installed (CFCI), Contractor Furnished/Owner Installed (CFOI), Owner Furnished/Owner Installed (OFOI), and Owner Furnished/Contractor Installed (OFCI). The project requires strict adherence to the National Electrical Code (NEC), NFPA standards, and local building codes, with all equipment to be listed and labeled by Underwriter's Laboratories. Installation specifications include maximum three branch circuits per homerun with dedicated neutral conductors, proper grounding protocols, and comprehensive labeling of all electrical equipment and panels. The contractor is responsible for coordination with all trades, provision of detailed shop drawings prior to installation, and four hours of training for each system. All materials and work are guaranteed for one full calendar year from substantial completion. The drawings also specify requirements for cable tray installation, fixture support details, occupancy sensor integration, emergency lighting controls with UL924 devices, and coordination with existing electrical infrastructure to maintain continuity of critical circuits during demolition and new work phases.

View the file

Other files

File Type Posted
Backup_Airport_Operations_Center_(AOC)_Construction_(Addendum_#2_Revision).pdf PDF
26-008-ITB_Backup_AOC_Construction_-_Tech_Specs_-_Addendum_2_-_03.09.26.pdf PDF
26-008-ITB_Backup_AOC_Construction_-_Drawings_Addendum_1_03.03.26.pdf PDF
26-008-ITB_Pre-Bid_Sign_In_Sheets.pdf PDF
26-008-ITB_Pre-Bid_Meeting_Agenda.pdf PDF
Backup_Airport_Operations_Center_(AOC)_Construction.pdf PDF
26-008-ITB_Backup_AOC_Construction_-_Ad.pdf PDF
26-008-ITB_Backup_AOC_Construction_-_Exhibit_B_-_Contract_&_Bonds.pdf PDF
26-008-ITB_Backup_AOC_Construction_-_Exhibit_A_-_Proposal_Forms.pdf PDF
26-008-ITB_Backup_AOC_Construction_-_Technical_Specifications.pdf PDF
BACKUP_AOC_IFB_DRAWINGS.pdf PDF
BACKUP_AOC_IFB_SPECS.pdf PDF
Q1_2026_-_Business_Case_-_Backup_AOC_Facility_Construction_-_signed.pdf PDF
BACKUP_AOC_SOUTH_ARFF_ESTIMATE_OF_PROBABLE_COST_2025.11.24.pdf PDF
Affirmative_Action_Certification.docx DOCX document
Disclosure_of_Lobbying_Activities_Certification.docx DOCX document
EEO_Certification.docx DOCX document
NonSegregated_Facilities_Certification.docx DOCX document
Certification_of_Offeror-Bidder_Regarding_Tax_Delinquency_and_Felony_Convictions.docx DOCX document
Non_Debarment_or_Suspension_Certification.docx DOCX document
Buy_American_Certification-Equipment-Building_Projects.docx DOCX document
Buy_American_Certification-Construction_Projects.docx DOCX document
Show all 22

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SD

UON

EM

CFOI

OFOI

CFCI

OFCI

J

DESCRIPTION

S

OS

POWER SUPPLY/CONTROL FOR AUDIO/VISUAL DEVICES

SLASH THROUGH ANY DEVICE INDICATES MOUNTING

ABOVE COUNTERTOP 2" ABOVE BACKSPLASH, OR AT

48" WHERE NO COUNTER IS PRESENT

VS

LV

FILLED CENTER BAR INDICATES INTEGRAL GROUND

FAULT PROTECTION (GFCI)

NON-REVERSING MOTOR STARTER SNAP SWITCH

CONTRACTOR FURNISHED OWNER INSTALLED

CONTRACTOR FURNISHED CONTRACTOR INSTALLED

OWNER FURNISHED OWNER INSTALLED

OWNER FURNISHED CONTRACTOR INSTALLED

PHOTO-ELECTRIC SMOKE DETECTOR

MAIN CONTROL PANEL CENTRAL PROCESSING

UNIT (CPU)

LIGHT SWITCH:GENERAL PURPOSE

AS NOTED

6'-6'' TO

TOP

UNLESS OTHERWISE NOTED

INDICATES EMERGENCY POWER

46"

ABBREVIATIONS

POWER OUTLETS

DUPLEX RECEPTACLE

QUADRUPLEX RECEPTACLE

JUNCTION BOX, CEILING OR WALL

OCCUPANCY OR VACANCY SENSOR, CEILING MOUNT

LOW VOLTAGE SWITCH ON OFF WITH ZONES

CLG

46"

46"

1'-6"

1'-6"

1'-6"

CLG

S

S M

M O

U N

T

IN

G H

E

IG

H T

(T O

C E

N T

E R

O F

B O

X

D R

A W

IN

G

S

Y M

B O

L

ADDRESSABLE RELAY MODULE R

CONDUIT CONCEALED IN WALLS OR IN CEILING

SPACE: ARROW(S) INDICATE(S) HOME RUN & #

OF CIRCUITS: HASHMARKS INDICATE # OF

CONDUCTORS. DASHED LINE INDICATES

CONDUIT BELOW FLOOR.

PANELBOARD, SURFACE OR FLUSH MOUNTED,

HATCHING INDICATES EMERGENCY

EQUIPMENT TAG, REFER TO EQUIPMENT SCHEDULE

AS NOTED

MISCELLANEOUS

DISCONNECT SWITCH

TRANSFORMER

TAGGED NOTE

CONDUIT PATH

5'-0"

6'-6'' TO TOP

C A

B L

IN

G C

O N

D U

C T

O R

S

O F

O I

C A

B L

IN

G

C O

N D

U C

T O

R S

O

F C

I

C O

N D

U

IT

R

O U

G H

-I N

O

F O

I

IT

E

M U

S E

D O

N P

R O

J E

C T

D E

V

IC

E S

O

F C

I

D E

V

IC

E S

C

F C

I

SYSTEM D

E

V

IC

E S

O

F O

I

SYSTEM

RESPONSIBILITY

MATRIX

DATA

SYSTEM RESPONSIBILITY GENERAL NOTES:

A. CMTA IS NOT RESPONSIBILE FOR ASSIGNING SCOPE(S) OR WORK. THE INTENT OF

CONTRACTOR IN THIS MATRIX IS TO SEPERATE OWNER PROVIDED ITEMS FROM THE

GENERAL CONTRACTOR / CONSTRUCTION MANAGER. THE GC OR CM SHALL BE

RESPONSIBLE FOR A COMPLETE SCOPE OF WORK.

B. REFER TO VENDOR DRAWINGS FOR COMPLETE SCOPE OF WORK RELATING TO

VENDOR-FURNISHED EQUIPMENT. ALL WORK INDICATED ON VENDOR DRAWINGS SHALL

BE INCLUDED BY THE CONTRACTOR.

C. REFER TO ARCHITECTURAL DOOR HARDWARE SPECIFICATIONS FOR ACCESS CONTROL

DEVICE SPECIFICATIONS AND FURTHER REQUIREMENTS.

D. PROVIDE BACKBOXES AND CONDUIT WITH PULL-STRINGS FOR ALL SYSTEMS.

CONTRACTOR SHALL VERIFY BACKBOX SIZES, CONDUIT, ETC. AND EXACT

INSTALLATION LOCATIONS/REQUIREMENTS WITH SUCCESSFUL VENDORS OF ALL

SYSTEMS PRIOR TO CONSTRUCTION.

E. AT ALL SYSTEMS EQUIPMENT CABINET/TERMINAL BOARD LOCATIONS, CONTRACTOR

SHALL PROVIDE SIZE AND NUMBER OF CONDUIT STUB-OUTS TO CABLE PATHS AS

REQUIRED BY SYSTEM VENDORS, TERMINATE CONDUITS AT CABINETS/ON

BACKBOARDS AS REQUIRED. COORDINATE EXACT REQUIREMENTS WITH APPROPRIATE

VENDORS PRIOR TO CONSTRUCTION.

F. REFER TO SPECIFICATIONS FOR REQUIREMENTS APPLICABLE TO ALL SYSTEMS

INCLUDING CABLING, CABLE MANAGEMENT, INSTALLATION, GROUNDING, TESTING,

LABELING, ETC.

G. WHERE INDICATED AS CFCI, THE CONTRACTOR SHALL PROVIDE THE SYSTEM

COMPLETE, INCLUDING ALL ROUGH-INS, CABLING, DEVICES, POWER, ETC. THE

CONTRACTOR SHALL CONTACT THE LISTED VENDOR FOR PRICING PRIOR TO BID. ALL

SYSTEMS SHALL MATCH EXISTING FACILITY STANDARDS AND BE FULLY COMPATIBLE

WITH ANY EXISTING SYSTEMS. ALL SYSTEM VENDORS SHALL COORDINATE EXACT

SYSTEM REQUIREMENTS WITH OWNER PRIOR TO BID. NEW COMPONENTS SHALL BE

INTERCONNECTED WITH EXISTING SYSTEMS WHERE POSSIBLE. ALL NEW SYSTEM

DESIGNS AND PROGRAMMING SHALL BE COORDINATED WITH THE OWNER PRIOR TO

ORDERING. ALL PROGRAMMING SHALL BE INCLUDED AS REQUIRED BY THE OWNER.

PROVIDE 4 HOURS OF TRAINING FOR EACH SYSTEM.

SWITCHES

FIRE ALARM

E,EMINDICATES EMERGENCY POWER

NAC

FACP

AS SHOWNSOLID BOTTOM CABLE TRAY, SIZE AS NOTED

EQUIP-1

GROUND

NEUTRAL

PHASE

, J

#D/#V

#D

INTERMEDIATE DISTRIBUTION FRAME - REFERENCE

DATA SYSTEM SCHEMATICS AND DETAILS FOR

ADDITIONAL REQUIREMENTS

MAIN DISTRIBUTION FRAME - REFERENCE DATA

SYSTEM SCHEMATICS AND DETAILS FOR ADDITIONAL

REQUIREMENTS

WIRELESS ACCESS POINT WITH PROVISIONS FOR (1

DATA OUTLET FOR ANTENNA. PROVIDE A COMPLETE

DATA OUTLET WITH FACEPLATE ABOVE CEILING,

MOUNTED AT AN ACCESSIBLE HEIGHT NO MORE THAN

24" ABOVE CEILING. AT EACH OUTLET, PROVIDE A 20'

COIL OF CABLE AHEAD OF THE OUTLET FOR

ADJUSTMENT OF FINAL OUTLET LOCATION. THE

CONTRACTOR SHALL COORDINATE EXACT LOCATIONS

WITH THE OWNER AND ADJUST OUTLET LOCATIONS AT

SUBSTANTIAL COMPLETION TO ACCOMMODATE

OWNER'S WAP LOCATIONS. WAP'S ARE OWNER-

FURNISHED, OWNER-INSTALLED

WAP

DATA OUTLET : NUMBER BESIDE OUTLET

INDICATES NUMBER OF DATA JACKS

VOICE OUTLET : NUMBER BESIDE OUTLET

INDICATES NUMBER OF VOICE JACKS

COMBINATION OUTLET : NUMBER BESIDE OUTLET

INDICATES NUMBER OF DATA/VOICE JACKS

DATA / VOICE

1'-6"

1'-6"

1'-6"

#V

MDF

IDF

GROUND BUS BAR ON INSULATED STANDOFFS 2'-0''

DESCRIPTION M

O

U N

T

IN

G H

E

IG

H T

(T O

C E

N T

E R

O F

B O

X

D R

A W

M

B O

L

DESCRIPTION M

O

U N

T

IN

G H

E

IG

H T

(T O

C E

N T

E R

O F

B O

X

D R

A W

M

B O

L

DESCRIPTION

LV#S,

W H

IT

E

DEVICE

WALL SWITCHES

DEVICE COLOR

MATRIX

RECEPTACLE (NORMAL)

DEVICE COLOR GENERAL NOTES:

A. DEVICE PLATE TO MATCH DEVICE UNLESS NOTED OTHERWISE.

B. NOT ALL DEVICES MAYBE USED THAT ARE SHOWN.

C. IF DEVICE COLOR NOT DEFINED REFER TO SPECIFICATIONS.

DESCRIPTION

IV

O

R Y

R E

D

O R

A N

G E

B L

U E

Y E

L L O

W

C U

S T

O M

S T

A

IN

L E

S S

S T

E E

L

LEGEND

INDICATES SELECTED COLOR

INDICATES COLOR NOT AVAILABLE

INDICATES COLOR NOT SELECTED

LEGEND

INDICATES SELECTED SYSTEM

INDICATES NOT AVAILALBE

INDICATES NOT SELECTED

C O

N D

U

IT

R

O U

G H

-I N

O

F C

I

C O

N D

U

IT

R

O U

G H

-I N

C

F C

I

C A

B L

IN

G

C O

N D

U C

T O

R S

C

F C

I

P R

O G

R A

M M

IN

G

S

E T

U P

O

F O

I

P R

O G

R A

M M

IN

G

S

E T

U P

O

F C

I

P R

O G

R A

M M

IN

G

S

E T

U P

C

F C

I

ST

SECURITY: ACCESS CONTROL

CONDUIT PATH UNDERNEATH RAISED FLOOR

FIRE ALARM

HONEYWELL SYSTEM

PUSHBUTTON STATION 46"

RECEPTACLE (UPS)

RECEPTACLE (ISOLATED GROUND)

T E

R M

IN

A

T

IO

N S

O

F C

I

T E

R M

IN

A

T

IO

N S

C

F C

I

T E

R M

IN

A

T

IO

N S

O

F O

I

2025-048

Cincinnati/Northern Kentucky International Airport

BACKUP AOC

Interior Modifications

South ARFF Fire Station 2100 Tower Dr.

TH

IS

D O

C U M

EN

T, A N

D T

H E

ID

EA

S A N

D D

ES

IG

N S

IN

C O

R

PO

R A

TE

D H

ER

EI

N , A

S A N

I N

ST

R U M

EN

T

O F

PR

O

FE

SS

IO

N

A L

SE

R V

IC

E, I S

TH

E

PR

O

PE

R

TY

O F

EM

BO

SS

D

ES

IG

N , P

.S .C

A N

D I S

N O

T

TO

B E

U

SE

D I N

W H

O

LE

O R I N

P A R T

FO

R A

N Y

O

TH

ER

P

R O

JE

C T, W

IT

H O

U T

TH

E

W R

IT

TE

N

A U

TH

O R

IZ

A

TI

O N

O F

EM

BO

SS

D

ES

IG

N , P

.S .C

C O

PY

R

IG

H T

-2

5:

E

M

BO

SS

D

ES

IG

N , P

.S .C

A

LL

R

IG

H

TS

R

ES

ER

V

ED

15141312 161110987654321

A

D

B

C

E

F

G

H

J

K

L

M

15141312 161110987654321

A

D

B

C

E

F

G

H

J

K

L

M

IS

SU

E DATE DESCRIPTION

9/3/25 60% REVIEW

NO.

P

\P

R

-0

-B

A C

K U

P A

O C

-S O

U T

H A

R F

F \0

-D

R A

W

IN

G S

10/16/25 90% REVIEW

11/20/25 BIDDING & PERMIT

906 Monmouth Street, Newport, KY 41071

EmbossDesign.com (859)431-8612

S y c a m o re S t, S u it e

C in c in n a ti

O H

.4

.4

E 0 0 0

E L E C T R I C A L L E G E N D

ELECTRICAL GENERAL NOTES:

A. EACH CONTRACTOR, PROPOSER, SUPPLIER AND/OR MANUFACTURER SHALL REFER TO ALL DOCUMENTS

PERTAINING TO THIS PROJECT AND COORDINATE ACCORDINGLY SO AS TO ENSURE ADEQUACY OF FIT, COMPLIANCE WITH SPECIFICATIONS, PROPER VOLTAGE AND CURRENT CHARACTERISTICS TO AVOID CONFLICT

WITH ANY OTHER BUILDINGS SYSTEMS. VERIFY SAME WITH SHOP DRAWINGS.

B. ADDITIONAL ELECTRICAL REQUIREMENTS MAY BE SHOWN ON PLANS FROM OTHER DISCIPLINES IN THIS SET. IT IS THE CONTRACTOR’S RESPONSIBILITY TO REVIEW ALL PLANS AND SPECIFICATIONS FOR A COMPLETE

UNDERSTANDING OF THE PROJECT REQUIREMENTS.

C. WORK SHALL BE IN ACCORDANCE WITH THE LATEST EDITION OF ALL LOCAL, STATE, AND NATIONAL CODES.

INCLUDING BUT NOT LIMITED TO NFPA 70 (NEC), NFPA 72, INTERNATIONAL BUILDING CODES, ETC.

D. CONTRACTOR SHALL FOLLOW SEISMIC RESTRAINT AND DESIGN REQUIREMENTS CONTAINED IN LATEST ADOPTED STATE AND INTERNATIONAL BUILDING CODES, WITH ALL AMENDMENTS AS ADOPTED BY THE CURRENT LEGISLATION. REFER TO ELECTRICAL AND STRUCTURAL SPECIFICATIONS FOR ADDITIONAL INFORMATION.

E. ALL OFFSETS, TURNS, FITTINGS, TRIM, DETAIL, ETC. MAY NOT BE INDICATED, BUT SHALL BE PROVIDED AS REQUIRED. ADDITIONAL ALLOWANCES SHALL BE INCLUDED FOR SAME AT EACH PROPOSER’S DISCRETION.

F. INSTALL NO PIPING, CONDUIT, DUCTWORK, ETC. IN A LOCATION OR IN A MANNER WHICH WILL ALLOW FREEZING

OR THE COLLECTION OF CONDENSATION THEREON. IF IN DOUBT, CONTACT THE ENGINEER.

G. ADVISE THE ENGINEER OF ANY CONFLICTS, ERRORS, OMISSIONS, ETC. AT LEAST TEN DAYS PRIOR TO BID DATE, TO ALLOW CLARIFICATION BY WRITTEN ADDENDUM.

H. WHERE CONFLICTS ARE FOUND BETWEEN DRAWINGS, DETAILS, OR SPECIFICATIONS, THE MORE STRINGENT

REQUIREMENT SHALL APPLY. NOTIFY ARCHITECT OF DISCREPANCY IN WRITING.

I. DEVIATION FROM SPECIFICATIONS OR PLANS REQUIRES PRIOR WRITTEN APPROVAL FROM THE ENGINEERS AND

MUST BE SUBMITTED IN WRITING NO LATER THAN TEN DAYS PRIOR TO THE BID DATE.

J. OBSERVE ALL APPLICABLE CODES, RULES AND REGULATIONS THAT MAY APPLY TO THE WORK UNDER THIS CONTRACT. (CITY, COUNTY, LOCAL, STATE, FEDERAL, MUNICIPALITY, UTILITY COMPANY, OSHA, ETC.).

K. MOUNTING HEIGHTS FOR WALL MOUNTED DEVICES INDICATED ABOVE FINISHED FLOOR ARE TO CENTER OF DEVICE UNO. MOUNTING HEIGHTS TO CEILING SUSPENDED DEVICES ARE TO BOTTOM OF DEVICE UNO.

L. INSTALL EQUIPMENT, MATERIALS, ETC. IN STRICT ACCORDANCE WITH MANUFACTURER’S RECOMMENDATIONS AND DIRECTIONS. IF IN CONFLICT WITH THE DESIGN INDICATED IN CONTRACT DOCUMENTS, ADVISE THE

ENGINEER PRIOR TO INSTALLATION FOR CLARIFICATION.

M. DO NOT RECESS PANELBOARD TUBS OR OTHER FLUSH-MOUNTED EQUIPMENT IN WALLS THAT HAVE A FIRE

RATING. NO INSTALLATION SHALL DIMINISH OR VOID FIRE RESISTIVE RATINGS IN ANYWAY.

N. THE PURPOSE AND INTENT OF ALL OF THE DOCUMENTS PERTAINING TO THIS PROJECT IS TO PROVIDE A COMPLETE, FUNCTIONAL, SAFE, LIKE-NEW FACILITY. ANYTHING LESS SHALL BE UNACCEPTABLE.

O. ALL SYSTEMS, EQUIPMENT AND MATERIALS ARE TO BE INSTALLED IN A NEAT AND WORKMANLIKE MANNER.

WORK NOT MEETING THIS CRITERION SHALL BE REMOVED AND REINSTALLED SATISFACTORILY. FINAL DETERMINATION OF THE ACCEPTABILITY OF THE QUALITY OF WORK RESIDES WITH THE ENGINEER

P. ALL WORK, MATERIALS, EQUIPMENT, ETC. SHALL BE FULLY GUARANTEED FOR ONE FULL CALENDAR YEAR FROM THE DATE OF SUBSTANTIAL COMPLETION AS DOCUMENTED BY THE ENGINEER, UNLESS LONGER WARRANTY

PERIODS FOR EQUIPMENT ARE SPECIFIED.

Q. UNLESS OTHERWISE SPECIFIED OR INDICATED, ALL EQUIPMENT AND/OR MATERIALS WITHIN OCCUPIED SPACES OR EXPOSED TO VIEW ON THE BUILDING EXTERIOR SHALL BE PRIMED AND FINISHED SO AS TO COMPLEMENT ADJACENT SURFACE, UNLESS OTHERWISE NOTED. COORDINATE WORK AND COLORS WITH ARCHITECT.

R. COORDINATE WITH ARCHITECTURAL FLOOR PLANS, ELEVATIONS AND CASEWORK DETAILS FOR LOCATION OF

ADDITIONAL RECEPTACLES, UTILITY OUTLETS, ELECTRICAL DEVICES, ETC.

S. CEILING-MOUNTED ELECTRICAL DEVICES SHALL BE CENTERED IN 2'X2' CEILING TILE AND INSTALLED CENTERED ON 2' DIMENSION OF 2'X4' TILE AND ON CENTERLINE OR A QUARTER POINT ON 4' DIMENSION.

T. ANY VIBRATING, OSCILLATING OR OTHER NOISE OR MOTION PRODUCING EQUIPMENT SHALL BE ISOLATED FROM SURROUNDING SYSTEMS IN AN APPROVED MANNER. NOISY OR STRUCTURALLY DAMAGING INSTALLATIONS SHALL BE SATISFACTORILY REPLACED OR REPAIRED AT THE INSTALLING CONTRACTORS' EXPENSE. THE FINAL DECISION ON THE SUITABILITY OF A PARTICULAR INSTALLATION'S ACCEPTABILITY SHALL BE THAT OF THE

ENGINEER.

U. PROVIDE DETAILED SHOP DRAWINGS TO ENGINEER PRIOR TO PURCHASING OR INSTALLING ANY EQUIPMENT V. DEVIATIONS IN SIZES, CAPACITIES, FIT, FINISH, ETC. FOR EQUIPMENT FROM THAT PRIME SPECIFIED SHALL BE

THE RESPONSIBILITY OF THE PURCHASER OF THAT EQUIPMENT. ANY PROVISIONS REQUIRED TO ACCOMMODATE A DEVIATION, WHETHER APPROVED BY THE ENGINEER OR NOT, SHALL BE THE RESPONSIBILITY

OF THE PURCHASER.

W. THE CONSTRUCTION MANAGER, GENERAL CONTRACTOR, OR WHOMEVER HOLDS THE PRIME CONTRACT(S) FOR THIS CONSTRUCTION IS RESPONSIBLE FOR THE COORDINATION, APPEARANCE, SCHEDULING AND TIMELINESS OF THE WORK OF ALL TRADES, CONTRACTORS, SUPPLIERS, INSTALLERS, ETC. POOR OR UNTIMELY WORK ON THE PART OF ANY SUBCONTRACTOR SHALL BE RESOLVED BY THE PARTY WHO ENGAGED THEM ON THIS

PROJECT.

X. WHERE MOUNTING HEIGHTS ARE NOT INDICATED OR ARE IN CONFLICT WITH ANY OTHER BUILDING SYSTEM, CONTACT THE ENGINEER BEFORE AFFECTING INSTALLATION. REFER ALSO TO ARCHITECTURAL INTERIOR AND EXTERIOR ELEVATIONS, CEILING HEIGHTS AND OTHER DETAILS OF THESE DOCUMENTS, AS APPLICABLE.

Y. WHERE FIRE-RATED CEILING ASSEMBLIES ARE NOTED, PROVIDE UL-LISTED FIRE-RATED GYPSUM BOARD OR PRE-MANUFACTURED ENCLOSURES ABOVE LUMINAIRES, CEILING DEVICES, ETC. IN OR ON CEILING, AS

REQUIRED TO MAINTAIN CEILING RATINGS.

Z. COORDINATE THE LOCATION OF DRAINS, ELECTRICAL OUTLETS, GAS OUTLETS, ETC. WITH ALL CASEWORK, KITCHEN EQUIPMENT, MECHANICAL ROOM EQUIPMENT, ETC. PRIOR TO COMMENCING INSTALLATION. WORK NOT SO COORDINATED SHALL BE REMOVED AND PROPERLY INSTALLED AT THE EXPENSE OF THE RESPONSIBLE

CONTRACTOR(S).

AA. ALL ELECTRICAL COMPONENTS OR EQUIPMENT SHALL BE LISTED AND LABELED BY UNDERWRITER'S LABORATORIES OR OTHER APPROVED LISTING AGENCY. APPROVAL AND LABELING OF INDIVIDUAL COMPONENTS ON AN ASSEMBLY IS NOT ACCEPTABLE AS MEETING THIS REQUIREMENT, UNLESS WAIVED BY THE

ENGINEER IN WRITING.

BB. ALL WIRING SYSTEMS SHALL BE INSTALLED WITH A MINIMUM OF SPLICES. CONDUCTORS, WHETHER SINGLE OR MULTI-PAIR, SHALL BE INSTALLED CONTINUOUS INSOFAR AS POSSIBLE FROM TERMINAL POINT TO TERMINAL

POINT.

CC. NO CONDUIT, SUPPORTS, ETC. SHALL BE RUN THROUGH ACCESS CLEARANCES OF EQUIPMENT BY OTHER

TRADES (I.E. VAV BOXES). COORDINATE WITH ALL TRADES PRIOR TO CONSTRUCTION.

DD. ALL CONTRACTORS SHALL EXERCISE EXTREME CARE IN THE COURSE OF THEIR WORK SO AS TO ENSURE THAT THEY DO NOT INTERRUPT ANY EXISTING SERVICE OR SUB-SERVICE FOR SAFETY PURPOSES. PAY PARTICULAR ATTENTION TO THIS PRECAUTION RELATIVE TO NATURAL GAS AND ELECTRICAL LINES. VERIFY THE LOCATION, SIZE, TYPE, ETC. OF EACH UNDERGROUND OR OVERHEAD UTILITY. ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH ALL FEDERAL, STATE AND/OR LOCAL RULES, REGULATIONS, STANDARD AND SAFETY REQUIREMENTS. UTILITIES SHALL BE INSTALLED IN ACCORDANCE WITH THE APPLICABLE MUNICIPALITY OR UTILITY COMPANY STANDARDS. IN ALL CASES, THE MOST STRINGENT REQUIREMENT SHALL APPLY.

EE. ALL SUPPORTS FOR EQUIPMENT, DEVICES OR FIXTURES SHALL BE UNIQUE, DIRECTLY FROM THE BUILDING STRUCTURE. DO NOT SUPPORT WORK FROM OTHER TRADES EQUIPMENT OR SUPPORTS WITHOUT WRITTEN

PERMISSION FROM THE ENGINEER AND CONSENT OF THE OTHER TRADE, IN WRITING.

FF. WHERE INTERRUPTING AN EXISTING UTILITY OR SERVICE DELIBERATELY OR ACCIDENTALLY, THE RESPONSIBLE CONTRACTOR SHALL WORK CONTINUOUSLY AS NEEDED TO RESTORE SAME, PROVIDING PREMIUM TIME AS

NEEDED.

GG. REFER TO ARCHITECTURAL WALL ELEVATIONS (WHERE GIVEN) FOR HEIGHTS AND MOUNTING RELATIONSHIP OF OUTLETS AND EQUIPMENT. IF IN DOUBT, CONTACT ENGINEER FOR DIRECTION PRIOR TO ROUGH IN.

HH. AS APPLICABLE, REFER TO ARCHITECTURAL PHASING PLANS AND PHASING BOUNDARIES ON THESE DRAWINGS FOR SEQUENCING OF WORK, FULL EXTENT OF AREAS INVOLVED, EXTENT OF CEILING WORK, ETC. PROVIDE TEMPORARY CONNECTIONS FOR CIRCUITS AND WORK AS REQUIRED TO MAINTAIN SEQUENCE OF THE WORK

FROM PHASE TO PHASE.

II. THIS CONTRACTOR SHALL BE RESPONSIBLE FOR ALL CUTTING AND PATCHING REQUIRED FOR HIS WORK. ALL CUTTING AND PATCHING SHALL BE IN ACCORDANCE WITH THE ARCHITECT'S STANDARDS FOR SUCH WORK.

JJ. ALL WORK SHALL BE CONCEALED UNLESS SPECIFICALLY INDICATED TO BE EXPOSED, OR REQUIRED TO BE EXPOSED. IF IN DOUBT, CONTACT THE ENGINEER FOR CLARIFICATIONS PRIOR TO INSTALLING ANY SUCH WORK.

KK. WHERE BACKBOXES ARE LOCATED IN THE SAME VERTICAL CHANNEL/STUD SPACE ON OPPOSITE SIDES OF THE SAME WALL, PROVIDE SOUND-INSULATING PUTTY AROUND BOXES AS REQUIRED TO ELIMINATE SOUND

TRANSMISSION FROM ROOM TO ROOM.

LL. JUNCTION BOXES LOCATED ABOVE ACCESSIBLE CEILINGS SHALL BE LOCATED NO MORE THAN 36” ABOVE CEILING LEVEL. LABEL EACH BOX IN AREA OF WORK WITH A PERMANENT MARKER OR IN ACCORDANCE WITH

SPECIFICATIONS, WHICHEVER IS MORE STRINGENT.

MM. ALL MATERIALS FURNISHED AND ALL WORK INSTALLED SHALL COMPLY WITH THE CURRENT EDITION OF THE NATIONAL ELECTRICAL CODES, NATIONAL FIRE CODES OF THE NATIONAL FIRE PROTECTION ASSOCIATION, THE REQUIREMENTS OF LOCAL UTILITY COMPANIES, AND WITH THE REQUIREMENTS OF ALL GOVERNMENTAL AGENCIES OR DEPARTMENTS HAVING JURISDICTION. IF ANY CONFLICTS OR DISCREPANCIES OCCUR THE MOST

STRINGENT SHALL APPLY.

NN. DO NOT SCALE FROM DRAWINGS, AS PRINTING DISTORTS SCALE. WORK SHALL BE LAID OUT FROM

DIMENSIONED DRAWINGS, OR DIMENSIONS SUPPLIED TO THE CONTRACTOR.

OO. NOISY WORK, WORK OUTSIDE CONSTRUCTION BARRIERS, WORK IN OCCUPIED AREAS, ETC. SHALL BE PERFORMED AFTER HOURS OR ON WEEKENDS. COORDINATE EXACT SCHEDULING WITH FACILITY PRIOR TO

CONSTRUCTION.

PP. ALL ITEMS HAVING KEYED LOCKS/OPERATORS SHALL HAVE CORED LOCKS/OPERATORS. ALL KEYING SHALL MATCH THE OWNER'S EXISTING KEY-WAYS. COORDINATE EXACT REQUIREMENTS WITH OWNER PRIOR TO

CONSTRUCTION.

QQ. REFER TO ARCHITECTURAL PLANS FOR PHASING REQUIREMENTS. WORK SHALL BE COMPLETED IN PHASES PER THE PHASING PLAN AND AS COORDINATED WITH OWNER AND GENERAL CONTRACTOR. PROVIDE ALL REQUIRED INCREMENTAL INSPECTIONS, CERTIFICATIONS, ETC. AND ALL TEMPORARY SERVICES AS REQUIRED BY OWNER

TO ACCOMPLISH THE PHASING PLAN.

ELECTRICAL DEMOLITION NOTES:

A. DOTTED LINES INDICATE ITEMS FOR REMOVAL (UON) AND THIN SOLID LINES INDICATE

EXISTING ITEMS TO REMAIN.

B. THE CONTRACTOR SHALL MAINTAIN THE CONTINUITY OF EXISTING CIRCUITS THAT

CONTAIN DEVICES OR EQUIPMENT THAT ARE TO REMAIN. WHEN DEMOLITION OF AN

ELECTRICAL DEVICE (OR CIRCUIT) IS INDICATED ON THE DRAWINGS: THE CONTRACTOR

SHALL ENSURE THAT OTHER DEVICES OR EQUIPMENT "UPSTREAM" OR "DOWNSTREAM"

ON THE CIRCUITS SHALL REMAIN IN "PRE- DEMOLITION" WORKING ORDER. "LEFT-OVER"

CIRCUIT BREAKERS SHALL REMAIN, BE SWITCHED TO OFF POSITION, AND BE LABELED AS

SPARES IN THEIR PANELS. PROVIDE NEW TYPEWRITTEN DIRECTORIES FOR ALL PANELS

AFFECTED.

C. LOCATIONS OF DEVICES, CONNECTIONS, ETC., INDICATED ON THIS DRAWING WERE

TAKEN FROM VARIOUS SOURCES. THEY ARE DIAGRAMMATIC ONLY AND ARE SUBJECT TO

VARIATION FROM EXISTING CONDITIONS. CERTAIN EXISTING ELEMENTS MAY NOT BE

INDICATED AT ALL. THE CONTRACTOR PROPOSING TO DO ANY PART OF THE WORK

INDICATED HEREON SHALL VISIT THIS SITE AND DETERMINE TO HIS SATISFACTION THAT

THEY MAY COMPLETE ALL WORK REQUIRED FOR THE BID WHICH HE PROPOSES.

D. REMOVE ALL ASSOCIATED BACKBOXES, CONDUIT AND CONDUCTORS FOR DEVICES /

FIXTURES / ETC. BEING REMOVED (BACK TO SOURCE), WHETHER INDICATED OR NOT

(UON). CONTRACTOR SHALL PATCH AND REPAIR ANY EXISTING WALLS, FLOORS OR

CEILINGS WHERE DEVICES ARE SHOWN TO BE REMOVED (PATCH AND REPAIR TO

RECEIVE NEW FINISHES - SEE ARCHITECTURAL PLANS).

E. COORDINATE DISPOSAL OF ALL FIXTURES, DEVICES, ETC. (INDICATED FOR DEMOLITION)

WITH OWNER. TURN OVER ITEMS REMOVED TO OWNER AT THEIR OPTION.

F. COORDINATE WITH OTHER TRADES FOR THE REMOVAL AND/OR RELOCATION OF

ELECTRICAL DEVICES AND CONNECTIONS ASSOCIATED WITH THEIR EQUIPMENT.

G. PROVIDE TEMPORARY EMERGENCY EXIT LIGHTS AT CONSTRUCTION BARRIERS AS

REQUIRED.

H. CONTRACTOR SHALL PATCH AND REPAIR ALL EXISTING WALLS / CEILINGS AS REQUIRED

WHERE DEVICES ARE BEING REMOVED OR INSTALLED.

I. UNUSED/ABANDONED CONDUCTORS DISCOVERED ABOVE ACCESSIBLE CEILINGS SHALL

BE REMOVED IN ACCORDANCE WITH NEC REQUIREMENTS.

J. EXISTING ELECTRICAL SYSTEMS IN CONFLICT WITH CONSTRUCTION SHALL BE

RELOCATED TO PERMIT INSTALLATION OF DEVICES AND EQUIPMENT SHOWN ON PLANS.

K. DEVICES INDICATED WITH AN ''R'' SHALL BE RELOCATED. REMOVE, PROTECT, AND

REINSTALL IN NEW LOCATION INDICATED ON NEW WORK PLANS. INTERCEPT AND

EXTEND ALL EXISTING CABLING TO NEW LOCATION. CLEAN AND RE-LAMP RELOCATED

LUMINAIRES.

L. ALL EXISTING PANELS AFFECTED BY THIS CONTRACTOR'S WORK SHALL BE PROVIDED

WITH NEW TYPE-WRITTEN PANEL DIRECTORIES AND INSERT SLEEVES. PANEL

DIRECTORIES SHALL NOT USE ROOM NAMES OR NUMBERS FROM THESE DRAWINGS.

DIRECTORIES SHALL BE DETAILED AND COORDINATED WITH OWNER'S SUITE NUMBERS,

FINAL ROOM NUMBERS, IT RACK NAMES, WORKSTATION DESIGNATIONS, ETC. UNUSED

BREAKERS SHALL BE IN OFF POSITION.

GENERAL NOTES (LIGHTING):

A. REFER TO THE ARCHITECT'S REFLECTED CEILING PLANS, ELEVATIONS, AND CASEWORK

DETAILS FOR EXACT LOCATIONS OF ALL WALL AND CEILING MOUNTED ELECTRICAL

DEVICES.

B. CONTRACTOR SHALL FOLLOW BRANCH CIRCUITING LAY-OUT, AS INDICATED ON THE

FLOOR PLANS, WITH A MAXIMUM OF THREE (3) BRANCH CIRCUITS PER HOMERUN. EACH

BRANCH CIRCUIT SHALL BE PROVIDED WITH A DEDICATED NEUTRAL

CONDUCTOR. DEDICATED NEUTRAL CONDUCTORS SHALL BE CONSIDERED CURRENT

CARRYING. IF ADDITIONAL CONDUCTORS ARE RAN IN THE SAME CONDUIT WITH THOSE

INDICATED, CONTRACTOR SHALL DERATE ALL CURRENT CARRYING CONDUCTORS PER

N.E.C. #310.15(B)(3), AND UPSIZE CONDUIT AS REQUIRED PER N.E.C. #300.17 AND ANNEX C. MULTIWIRE BRANCH CIRCUITS AS DEFINED IN N.E.C #100 / 210.4 (CIRCUITS SHARING A

COMMON NEUTRAL CONDUCTOR) SHALL NOT BE PERMITTED.

C. IDENTIFY THE PANEL AND CIRCUIT NUMBER FOR ALL RECEPTACLES, SWITCHES, ETC. IN

AREA OF CONSTRUCTION. PROVIDE CLEAR ADHESIVE LABELS WITH BLACK LETTERING.

GENERAL NOTES (POWER):

A. REFER TO THE ARCHITECT'S REFLECTED CEILING PLANS, ELEVATIONS, AND CASEWORK

DETAILS FOR EXACT LOCATIONS OF ALL WALL AND CEILING MOUNTED ELECTRICAL

DEVICES.

B. CONTRACTOR SHALL FOLLOW BRANCH CIRCUITING LAY-OUT, AS INDICATED ON THE

FLOOR PLANS, WITH A MAXIMUM OF THREE (3) BRANCH CIRCUITS PER HOMERUN. EACH

BRANCH CIRCUIT SHALL BE PROVIDED WITH A DEDICATED NEUTRAL

CONDUCTOR. DEDICATED NEUTRAL CONDUCTORS SHALL BE CONSIDERED CURRENT

CARRYING. IF ADDITIONAL CONDUCTORS ARE RAN IN THE SAME CONDUIT WITH THOSE

INDICATED, CONTRACTOR SHALL DERATE ALL CURRENT CARRYING CONDUCTORS PER

NEC 310.15(B)(3), AND UPSIZE CONDUIT AS REQUIRED PER NEC 300.17 AND ANNEX

C. MULTIWIRE BRANCH CIRCUITS AS DEFINED IN NEC 100 / 210.4 (CIRCUITS SHARING A

COMMON NEUTRAL CONDUCTOR) SHALL NOT BE PERMITTED.

C. IDENTIFY THE PANEL AND CIRCUIT NUMBER FOR ALL RECEPTACLES, SWITCHES, ETC. IN

AREA OF CONSTRUCTION. PROVIDE CLEAR ADHESIVE LABELS WITH BLACK LETTERING.

MARK INSIDES OF ALL DEVICE BOXES WITH PANEL AND CIRCUIT NUMBER.

D. LOCATIONS OF ELECTRICAL CONNECTIONS AND LOCAL DISCONNECTS SHALL BE

COORDINATED WITH MECHANICAL AND PLUMBING CONTRACTORS TO ENSURE ACCESS

AND WORKING CLEARANCE IS MAINTAINED PER NEC. NOTIFY OTHER TRADES OF

REQUIRED CLEARANCE AREAS TO AVOID ROUTING OF OTHER SYSTEMS IN THESE AREAS.

DO NOT INSTALL ELECTRICAL EQUIPMENT OVER EQUIPMENT NAMEPLATES OR ACCESS

PANELS OR THROUGH ACCESS/MAINTENANCE CLEARANCES OF EQUIPMENT BY OTHER

TRADES.

J

J

J

J

SD

J

GEN ANN PANEL

EXIST

BASEBOARD

HEATER

M

M

EXIST

BASEBOARD

HEATER

EMA #42

CRASH PHONE

EXIST.

DESK/CONSOLES

DE2

DE7

DE6

DE5

DE5

EMA 11

DUPLEX AND IN LINE FAN

EMA-40

SPARE TO ALARM ROOM

DE3

DE11

DE16

DE6

DE14

DE8

DE4

(TYP)

DE9

DE13

R R

R R

R

DE15

MAIN ELEC.

ROOM

IDF ROOM

E001

DE12

2025-048

Cincinnati/Northern Kentucky International Airport

BACKUP AOC

Interior Modifications

South ARFF Fire Station 2100 Tower Dr.

TH

IS

D O

C U M

EN

T, A N

D T

H E

ID

EA

S A N

D D

ES

IG

N S

IN

C O

R

PO

R A

TE

D H

ER

EI

N , A

S A N

I N

ST

R U M

EN

T

O F

PR

O

FE

SS

IO

N

A L

SE

R V

IC

E, I S

TH

E

PR

O

PE

R

TY

O F

EM

BO

SS

D

ES

IG

N , P

.S .C

A N

D I S

N O

T

TO

B E

U

SE

D I N

W H

O

LE

O R I N

P A R T

FO

R A

N Y

O

TH

ER

P

R O

JE

C T, W

IT

H O

U T

TH

E

W R

IT

TE

N

A U

TH

O R

IZ

A

TI

O N

O F

EM

BO

SS

D

ES

IG

N , P

.S .C

C O

PY

R

IG

H T

-2

5:

E

M

BO

SS

D

ES

IG

N , P

.S .C

A

LL

R

IG

H

TS

R

ES

ER

V

ED

15141312 161110987654321

A

D

B

C

E

F

G

H

J

K

L

M

15141312 161110987654321

A

D

B

C

E

F

G

H

J

K

L

M

IS

SU

E DATE DESCRIPTION

9/3/25 60% REVIEW

NO.

P

\P

R

-0

-B

A C

K U

P A

O C

-S O

U T

H A

R F

F \0

-D

R A

W

IN

G S

10/16/25 90% REVIEW

11/20/25 BIDDING & PERMIT

906 Monmouth Street, Newport, KY 41071

EmbossDesign.com (859)431-8612

S y c a m o re S t, S u it e

C in c in n a ti

O H

.4

.4

E 0 0 1

E L E C T R I C A L D E M O L I T I O N P L A N

SCALE:E001 1/2" = 1'-0"

2 CONTROL TOWER ELECTRICAL DEMOLITION PLAN

TAGGED NOTES

DE2 DEMOLISH ALL WIRING ASSOCIATED WITH CRASH PHONE.

COORDINATE WITH CVG COMMUNICATIONS CONSULTANT.

OTHER DEVICES CONNECTED TO SYSTEM MUST REMAIN

OPERATIONAL DURING CONSTRUCTION.

DE3 DEMOLISH EXISTING CONNECTED SMOKE DETECTOR SITTING

ON DESK. PRESERVE WIRING FOR NEW SMOKE DETECTOR IN

NEW WORK PHASE.

DE4 DEMOLISH EXISTING ABANDONED FIRE ALARM PANEL.

REMOVE WIRING BACK TO SOURCE.

DE5 DEMOLISH ALL ELECTRICAL CONNECTIONS AND WIRING TO

EXISTING BASEBOARD HEATER. BASEBOARD HEATERS TO BE

REMOVED BY OWNER'S MECHANICAL CONTRACTOR.

DE6 EXISTING VRF AND INLINE FAN TO REMAIN.

DE7 DEMOLISH PATHWAYS FOR GARAGE DOOR CONTROL WIRING

INSIDE DESK. GARAGE DOOR CONTROLS TO BE RELOCATED IN

NEW WORK PHASE.

DE8 DEMOLISH PLUG MOLD. DEMOLISH WIRING BACK TO STUB OUT

INTO CONTROL TOWER ROOM.

DE9 PROTECT AND REMOVE EXISTING LIGHT FIXTURES. EXISTING

FIXTURES TO BE INSTALLED IN NEW ACT CEILING IN NEW

WORK PHASE. PRESERVE EXISTING WIRING SERVING LIGHT

FIXTURES. FIXTURES TO BE RECONNECTED TO EXISTING

CIRCUIT.

DE11 DEMOLISH ALL ELECTRICAL POWER STRIPS, LOW VOLTAGE

CABLING, AND ELECTRICAL BRANCH WIRING INSIDE EXISTING

DESK CONSOLE.

DE12 EXISTING HONEYWELL IN THIS LOCATION TO BE RELOCATED

TO AOC TOWER. DEMOLISH ANY LOW-VOLTAGE CABLING

ASSOCIATED WITH SYSTEM BACK TO HONEYWELL SWITCH.

DE13 EXISTING GENERATOR ANNUNCIATOR PANEL TO REMAIN.

DE14 PRESERVE ALL CONDUIT AND BRANCH WIRING FROM PANEL

EMA. EMA CIRCUITS TO BE REUSED IN NEW WORK PHASE.

DE15 DEMOLISH DEVICE AND WIRING. PROVIDE COVER PLATE FOR

DEMOLISHED DEVICE LOCATION.

DE16 EXISTING CONDUIT STUBBING UP THROUGH DECK UNDER

RAISED FLOOR TO REMAIN. VERIFY WHETHER EXISTING

CONDUIT CAN BE REUSED FOR NEW LOW VOLTAGE CABLING

FROM IDF AND MDF.

DEMOLISH ALL DEVICES

AND WIRING

INSIDE DESK

CONSOLES.

DEMOLISH POWER

SERVING

POWER STRIPS

INSIDE DESK BACK

TO SOURCE.

DEMOLISH/REWORK ALL EXISTING

WIRING LOCATED UNDERNEATH

EXISTING RAISED WOOD

SHEATHING PLATFORM.

COORDINATE WITH CVG TO

REROUTE ANY ACTIVE WIRING

PRIOR TO DISCONNECTION.

2" C.

SCALE:E001 1" = 30'-0"

1 OVERALL ELECTRICAL DEMOLITION PLAN

SEE SHEET E-101 FOR

ENLARGED VIEW OF AOC

(E)SWBD

EXISTING

HONEYWELL SWITCH

EXISTING MDF

EXISTING IDF

E100

E100

E10

E11

E12 E13

(2) #8 AWG CU &

(1) #10 AWG CU GND IN

3/4" EMT

TO T-AOC

EMA-6

EMA-7

EMA-9

EMA1-33

EMA1-34

EMA1-36

EMA1-38

1-1/2" EMT

EMA1-40

EMA1-42

EMA1-19

EMA1-21

EMA1-31

EMA1-41

1" EMT

(E)EMA1

(E)T-EMA

(E)EMA

(E)EMB

E14

E101

E101

(E)DP-1

E19

E22

E23

MEZZANINE

LEVEL

E1

EXISTING PHONE

EXIST PHONE

E1

2025-048

Cincinnati/Northern Kentucky International Airport

BACKUP AOC

Interior Modifications

South ARFF Fire Station 2100 Tower Dr.

TH

IS

D O

C U M

EN

T, A N

D T

H E

ID

EA

S A N

D D

ES

IG

N S

IN

C O

R

PO

R A

TE

D H

ER

EI

N , A

S A N

I N

ST

R U M

EN

T

O F

PR

O

FE

SS

IO

N

A L

SE

R V

IC

E, I S

TH

E

PR

O

PE

R

TY

O F

EM

BO

SS

D

ES

IG

N , P

.S .C

A N

D I S

N O

T

TO

B E

U

SE

D I N

W H

O

LE

O R I N

P A R T

FO

R A

N Y

O

TH

ER

P

R O

JE

C T, W

IT

H O

U T

TH

E

W R

IT

TE

N

A U

TH

O R

IZ

A

TI

O N

O F

EM

BO

SS

D

ES

IG

N , P

.S .C

C O

PY

R

IG

H T

-2

5:

E

M

BO

SS

D

ES

IG

N , P

.S .C

A

LL

R

IG

H

TS

R

ES

ER

V

ED

15141312 161110987654321

A

D

B

C

E

F

G

H

J

K

L

M

15141312 161110987654321

A

D

B

C

E

F

G

H

J

K

L

M

IS

SU

E DATE DESCRIPTION

9/3/25 60% REVIEW

NO.

P

\P

R

-0

-B

A C

K U

P A

O C

-S O

U T

H A

R F

F \0

-D

R A

W

IN

G S

10/16/25 90% REVIEW

11/20/25 BIDDING & PERMIT

906 Monmouth Street, Newport, KY 41071

EmbossDesign.com (859)431-8612

S y c a m o re S t, S u it e

C in c in n a ti

O H

.4

.4

E 1 0 0

E L E C T R I C A L O V E R A L L P L A N S

TAGGED NOTES

E1 RELOCATE ROLLING DOOR CONTROLS TO NEW LOCATION.

REWORK PATHWAYS AND CABLING FOR WIRING AS NEEDED

TO RECONNECT CONTROL WIRING TO GARAGE DOORS.

VERIFY CABLING TYPE WITH CVG ARFF.

E10 PROVIDE AND INSTALL NEW CONDUIT AND CONDUCTORS

FROM SWBD IN MAIN ELECTRICAL ROOM TO T-AOC IN AOC

TOWER. SEE SINGLE LINE DIAGRAM FOR MORE

INFORMATION.

E11 STUB CONDUITS SERVING AOC THROUGH WALL INTO

UNOCCUPIED SHAFT AND TURN UP TO SECOND FLOOR. SEE

E-101 FOR STUB OUT LOCATION INTO AOC TOWER.

E12 EXISTING HONEYWELL WORKSTATION IN CORRIDOR TO BE

RELOCATED TO AOC TOWER BY OWNER. PULL NEW RED

CAT5 FROM HONEYWELL SWITCH IDF ROOM TO NEW

WORKSTATION LOCATION IN NEW AOC TOWER. VERIFY

WHETHER EXISTING CONDUITS SERVING RAISED FLOOR CAN

BE REUSED FOR AOC TOWER CABLING. VERIFY DATA

CABLING TYPE AND QUANTIY WITH CVG IT DEPARTMENT.

E13 PROVIDE/VERIFY PATHWAY AND DATA CABLING FOR AOC

CPUS FROM EXISTING IDF ROOM UP INTO RAISED SHEATHED

FLOORING SPACE IN AOC. VERIFY WHETHER EXISTING

CONDUITS SERVING RAISED FLOOR CAN BE REUSED. VERIFY

DATA CABLING TYPES AND QUANTITIES WITH CVG IT

DEPARTMENT.

E14 PROVIDE AND INSTALL NEW CONDUIT AND BRANCH WIRING

FROM EMA AND EMA1 TO AOC TOWER. RUN CONDUIT FROM

PANELS IN MEZZANINE AREA DOWN TO ABOVE FIRST FLOOR

CEILING. FOLLOW PATH OF EXISTING EMA CIRCUITS SERVING

AOC TOWER.

E19 PROVIDE AND INSTALL NEW ISOLATED GROUND BAR INSIDE

INSIDE PANEL EMA. PULL #6 IG CONDUCTOR INSIDE EXISTING

CONDUIT FROM NEW GROUND BAR IN PANEL EMA TO

EXISTING GROUND BAR INSIDE TRANSFORMER TX-2.

TERMINATE IG RECEPTACLE CONDUCTORS ON NEW IG

GROUND BUSBAR.

E22 PROPOSED T-AOC FEEDER CONDUIT ROUTING. CONTRACTOR

TO CONFIRM FINAL ROUTING WITH CVG PRIOR TO

INSTALLATION.

E23 CONTRACTOR TO CONFIRM EXISTING LOCATION OF LOW

VOLTAGE CONDUIT SERVING TOWER. REUSE AS NECESSARY.

SCALE:E100 1/16" = 1'-0"

1 OVERALL ELECTRICAL PLAN

SCALE:E100 1/4" = 1'-0"

2 ELECTRICAL ENLARGED PLAN EAST

SCALE:E100 1/4" = 1'-0"

3 ELECTRICAL ENLARGED PLAN WEST

CR

J

J

J

J

FSD

J

J

J

J

KP

OS

OS

ER

GEN ANN PANEL

NEW 8KVA

UPS

M

M

AOC

VRF

IN-LINE OA FAN

E6

T-AOC

D-UPS

E6

E6

E6

60AF

50AT

-21EMA1

-19EMA1

-31EMA1

-40EMA1

-1AOC

-34EMA1

-9EMA

-2AOC

-33EMA1

-6EMA

-4AOC

-36EMA1

-6AOC

-7EMA

-42EMA1

-38EMA1

-3AOC

AOC-6

3/4" EMT.

AOC-2

AOC-4

EMA-6

EMA1-36

EMA1-33

3/4" EMT

3/4" EMT

3/4" EMT

EMA-7

EMA1-42

EMA1-19

EMA1-31

3/4" C.

EMA1-40

EMA1-42

EMA1-19

EMA1-21

EMA1-31

EMA1-41

1" EMT

AOC-1

AOC-2

AOC-3

AOC-4

EMA-6

EMA-9

EMA1-33

EMA1-34

EMA1-36

EMA1-38

2" EMT EMA-6

EMA-7

EMA-9

EMA1-33

EMA1-34

EMA1-36

EMA1-38

1-1/2" EMT

3/4" C.

(3) #8 AWG CU &

(1) #10 AWG CU GND IN

3/4" EMT

E4

E2

E5

E5

E5 E5

E7

E7

E7

E7

(TYP)

E8

(TYP)

E8

(TYP)

E8

E9

E9

E9

ELECTRICAL DEVICE COLOR LEGEND

UPS POWER

ISOLATED GROUND

"SHORE" (UTILITY) POWER

PURPLE LINES DENOTE ACCESS PANELS IN RAISED FLOOR

E16

E17

E17

E17

E18

E20

E20

E20

E21

E21

E21

E24

-41EMA1

E25

(TYP)

E3

LV1AOC

-40EMA

R R R

RR

E15

2025-048

Cincinnati/Northern Kentucky International Airport

BACKUP AOC

Interior Modifications

South ARFF Fire Station 2100 Tower Dr.

TH

IS

D O

C U M

EN

T, A N

D T

H E

ID

EA

S A N

D D

ES

IG

N S

IN

C O

R

PO

R A

TE

D H

ER

EI

N , A

S A N

I N

ST

R U M

EN

T

O F

PR

O

FE

SS

IO

N

A L

SE

R V

IC

E, I S

TH

E

PR

O

PE

R

TY

O F

EM

BO

SS

D

ES

IG

N , P

.S .C

A N

D I S

N O

T

TO

B E

U

SE

D I N

W H

O

LE

O R I N

P A R T

FO

R A

N Y

O

TH

ER

P

R O

JE

C T, W

IT

H O

U T

TH

E

W R

IT

TE

N

A U

TH

O R

IZ

A

TI

O N

O F

EM

BO

SS

D

ES

IG

N , P

.S .C

C O

PY

R

IG

H T

-2

5:

E

M

BO

SS

D

ES

IG

N , P

.S .C

A

LL

R

IG

H

TS

R

ES

ER

V

ED

15141312 161110987654321

A

D

B

C

E

F

G

H

J

K

L

M

15141312 161110987654321

A

D

B

C

E

F

G

H

J

K

L

M

IS

SU

E DATE DESCRIPTION

9/3/25 60% REVIEW

NO.

P

\P

R

-0

-B

A C

K U

P A

O C

-S O

U T

H A

R F

F \0

-D

R A

W

IN

G S

10/16/25 90% REVIEW

11/20/25 BIDDING & PERMIT

906 Monmouth Street, Newport, KY 41071

EmbossDesign.com (859)431-8612

S y c a m o re S t, S u it e

C in c in n a ti

O H

.4

.4

E 1 0 1

B A C K U P A O C E N L A R G E D P L A N S

TAGGED NOTES

E2 VERIFY EXISTING 2" CONDUITS STUBBING THROUGH AOC

ROOM DECK INTO RAISED FLOOR SPACE CAN BE USED AS

PATHWAY FOR AOC LOW VOLTAGE AND DATA CABLING.

E3 CONTRACTOR TO INSTALL OWNER-PROVIDED LIGHT

FIXTURES.

E4 VERIFY BRANCH POWER CONNECTION TYPE FOR

HONEYWELL UNIT WITH OWNER.

E5 PROVIDE 6" WIDE BY 3" DEEP SOLID SINGLE-CHANNEL CABLE

TRAY. RUN CABLE TRAY UNDER RAISED WOOD SHEATHING

PLATFORM AS SHOWN. SEE DETAIL ON E200.

E6 PROVIDE 16"X16" ACCESS PANEL IN RAISED FLOOR.

E7 RUN CONDUIT AS SHOWN TO JUNCTION BOX UNDER RAISED

ACCESS PANEL. SWITCH TO LFMC CONDUIT TO STUB BRANCH

CIRCUITS UP THROUGH RAISED ACCESS PANEL IN FLOOR

AND HOLES IN BOTTOM OF XYBIX CABINET. LAND BRANCH

CIRCUITS ON SURFACE-MOUNT RECEPTACLES INSIDE

CABINET.

E8 MOUNT RECEPTACLES AND GROUND BAR INSIDE CPU

CABINET. SEE OWNER SPECIFICATIONS FOR DEVICE

COLORS. VERIFY EXACT MOUNTING LOCATION FOR EACH

RECEPTACLE INSIDE CPU CABINET WITH OWNER.

E9 REFER TO XYBIX DRAWINGS FOR LOCATIONS AND

DIMENSIONS OF ACCESS HOLES TO BE DRILLED IN THE

BOTTOM OF CPU CABINETS.

E15 PROVIDE EMERGENCY TRANSFER DEVICE FOR FIXTURES.

WHEN NORMAL POWER IS AVAILABLE, TRANSFER DEVICE

SHALL ALLOW LIGHTING CONTROLS TO CONTROL LIGHTING

FIXTURES (WITH FULL DIMMING CONTROL). WHEN NORMAL

POWER IS LOST, EMERGENCY TRANSFER DEVICE SHALL

TURN ON ALL EMERGENCY FIXTURES TO 100% REGARDLESS

OF POSITION OF LOCAL SWITCHING.

E16 STUB CONDUIT FROM UNOCCUPIED SHAFT THROUGH WALL

ABOVE BACKUP AOC CEILING. SEE E-100 FOR CONTINUATION

DOWN TO FIRST FLOOR CEILING

E17 STUB CONDUIT FROM UNOCCUPIED SHAFT THROUGH WALL

BETWEEN DECK AND AOC RAISED FLOOR. CONTINUE

CONDUIT RUN UNDER AOC RAISED FLOOR. SEE E-100 FOR

CONTINUATION DOWN TO FIRST FLOOR CEILING.

E18 SUSPEND TRANSFORMER FROM ROOF STRUCTURE ABOVE.

PROVIDE CEILING SUPPORTS AND TILES COMPLETELY

AROUND TRANSFORMER SUPPORTS TO CONCEAL AS MUCH

AS POSSIBLE. REFER TO DETAIL 3 ON SHEET E201 FOR MORE

INFORMATION.

E20 RUN (2) GROUNDS FOR ISOLATED GROUND RECEPTACLE. AT

RECEPTACLE, TERMINATE NORMAL GROUND ON

RECEPTACLE BOX. TERMINATE IG GROUND ON RECEPTACLE

IG GROUND LUG. SEE OVERALL PLAN ON SHEET E100 FOR IG

CONDUCTOR TERMINATION INSTRUCTIONS AT PANEL.

E21 ELECTRICAL CONTRACTOR TO PROVIDE AND INSTALL

GROUND BAR INSIDE CPU ENCLOSURE. RUN #12 GROUND

FROM GROUND BAR BACK TO GROUND IN AOC PANEL.

GROUND CONNECTIONS TO EQUIPMENT INSIDE CPU CABINET

BY CVG.

E24 NEW LOCATION FOR RELOCATED HONEYWELL STATION. PULL

RED CAT5 CABLE IN CABLE TRAY TO THIS LOCATION. VERIFY

ANY ADDITIONAL REQUIREMENTS WITH OWNER.

E25 CONTRACTOR TO PROVIDE MATRIX KEYPAD CARD READER,

MODEL MX2, WITH CONNECTION BACK TO MATRIX ACCESS

CONTROL SYSTEM IN IDF ROOM. CONFIRM REQUIREMENTS

AND DOOR FUNCTION WITH OWNER PRIOR TO INSTALLATION"

SCALE:E101 1/2" = 1'-0"

1 BACKUP AOC POWER PLAN

SCALE:E101 1/4" = 1'-0"

2 BACKUP AOC LIGHTING PLAN

EXAMPLE CPU CABINET

FIRE ALARM

AUDIO/VISUAL DEVICES

THERMOSTAT

CARBON DIOXIDE/

TEMPERATURE SENSOR

SWITCHES

FIRE ALARM

PULL STATION

TELEPHONE /

DATA OUTLET

RECEPTACLEFINISHED FLOOR

DEVICE MOUNTING DETAIL - GENERAL NOTES:

A. WHERE DEVICES OF ANY DISCIPLINE ARE LOCATED IN THE SAME GENERAL AREA ON THE PLANS AND ARE SHOWN TO BE MOUNTED AT A SIMILAR HEIGHT, ALIGN HORIZONTALLY ALONG TOP OF DEVICE BACKBOX (AS SHOWN IN DETAIL AND DESCRIBED IN KEY NOTE #2).

B. WHERE DEVICES OF ANY DISCIPLINE ARE LOCATED IN THE SAME GENERAL AREA ON THE PLANS AND ARE SHOWN MOUNTED AT DIFFERENT HEIGHTS, ALIGN VERTICALLY

ALONG THE CENTERLINE OF THE DEVICE BACKBOX (AS SHOWN IN DETAIL).

C. FOR ANY WALL OTHER THAN PAINTED GYPSUM BOARD OR CMU, DEVICE LOCATIONS MUST BE FIELD APPROVED BY ENGINEER OR ARCHITECT PRIOR TO INSTALLATION OF

FINISHES.

D. ADA REQUIRES 48" ABOVE FINISH FLOOR FOR FRONT ACCESS. SIDE REACH ACCESS ALLOWS A MAXIMUM OF 54" AND A LOW SIDE REACH OF NO LESS THAN 9" ABOVE FINISH FLOOR. ADA FRONT AND SIDE REACH ACCESS MUST BE MAINTAINED FOR NEW AND EXISTING CONSTRUCTION. NOTIFY ARCHITECT AND ENGINEER OF ANY

DISCREPANCIES.

8"

CARD READER / KEYPAD

DEVICE MOUNTING DETAIL - KEY NOTES:

1. MOUNT VISUAL NOTIFICATION APPLIANCES SO THAT ENTIRE LENS IS BETWEEN 80" AND 96" AFF. IF CEILING IS TOO LOW FOR DEVICE TO BE MOUNTED ABOVE 80", MOUNT

SO THAT THE LENS IS WITHIN 6" OF FINISHED CEILING.

2. ALIGN BACKBOXES OF DEVICES AT THE MOUNTING HEIGHT INDICATED. MEASURE TO THE CENTER OF THE BACKBOX FOR STANDARD OUTLET BOXES. NON-STANDARD BACKBOXES ARE TO BE INSTALLED SUCH THAT THE FINISHED DEVICES ARE ALIGNED ALONG THEIR RESPECTIVE CENTERLINES.

3. MOUNTING HEIGHTS SHOWN ILLUSTRATE DESIGN INTENT AND ARE TO BE FOLLOWED UNLESS CONTRADICTED BY APPLICABLE CODE. WHERE DEVICES ARE SHOWN ADJACENT TO DOOR FRAMES ON PLANS INSTALL 12" FROM FRAME TO AVOID SLUSHED SECTIONS OR BRACING. SPECIFIC DEVICES ARE SHOWN IN RELATIVE ORDER FROM DOOR FRAME; WHERE THESE DEVICES ARE NOT PRESENT AT A PARTICULAR LOCATION, ADJUST LOCATIONS CLOSER TO DOOR ACCORDINGLY.

4. THE CONTRACTOR IS TO COORDINATE ALL ROUGH-INS WITH ANY COUNTERTOPS/BACKSPLASHES/WALL PROTECTION TO AVOID CONFLICT. ALIGN DEVICE BACKBOXES IN THE BOTTOM OF THE NEXT FULL BLOCK ABOVE THE BACKSPLASH AS SHOWN. FOR NON-BLOCK WALLS ALIGN BOTTOM OF DEVICE BACKBOXES 2" ABOVE BACKSPLASH.

COORDINATE WORK WITH CASEWORK AND KITCHEN SHOP DRAWINGS ACCORDINGLY. IF CONFLICT STILL ARISES CONTACT THE ENGINEER FOR DIRECTION ON HOW TO

PROCEED.

X

COUNTERTOP (WHERE

APPLICABLE)

BACKSPLASH (WHERE

APPLICABLE)

CEILING

DOOR FRAME

(WHERE

APPLICABLE)

ADA PUSH PLATE

WALL TELEPHONES

INTERCOM CALL STATION

A/V TOUCH PANEL

F I R E

F I R E

FIRE

CASEWORK / FURNITURE

(WHERE APPLICABLE)

PP

(T O

C E

N T

E R

O F

B O

X

(T O

C E

N T

E R

O

F B

O X

PROVIDE REMOVABLE FIRESTOPPING PILLOW (FSB OR

EQUAL) IN UL LISTED FIRESTOPPING ASSEMBLY TO ALLOW

FOR EASY REMOVAL AND INSTALLATION OF NEW CABLES.

8"+, TO CLEAR

OBSTRUCTIONS

CL

2" EA. SIDE

CEILING

STRUCTURE

LOCATE SO THAT ACCESSIBLE CEILING IS AT EACH SIDE OF

SLEEVES OR PROVIDE ACCESS PANEL.

PROVIDE CAULKING-STYLE FIRESTOPPING BETWEEN

SLEEVE AND WALL MATERIAL TO ANCHOR SLEEVE AND

RESTORE RATING OF WALL PER LOCAL AUTH. HAVING

JURISDICTION.

SIZE CONDUIT SLEEVE (SIZE AS INDICATED) WITH

INSULATED THROAT CONDUIT TERMINATORS ON EACH

END. PROVIDE A THREADED CAP ON EACH END IF NOT

USED FOR WIRING . LINE-UP WITH "CABLE TRAY" OR ''HOOK

PATH'' WHERE APPLICABLE.

FIRE/SMOKE RATED OR UN-RATED PARTITION OF VARIOUS

CONSTRUCTIONS. REFER TO ARCHITECTURAL PLANS OR

FIELD VERIFY TYPE.

GENERAL NOTES:

A. PROVIDE ONE 2" SPARE CONDUIT SLEEVE THROUGH ALL FULL HEIGHT

PARTITIONS FOR FUTURE USE. LABEL AS SPARE FOR OWNER'S USE ONLY.

REFER TO ARCHITECTURAL PLANS FOR FULL HEIGHT PARTITION LOCATIONS.

B. USE AT ALL ''OPEN'' TYPE CABLING PENETRATIONS THROUGH WALLS, FLOORS,

ETC.

NOTE: IF THE SLEEVE SIZE AND NUMBER

INDICATED ON PLANS WILL NOT BE ADEQUATE TO

CONTAIN ALL CABLES AND STILL LEAVE 25%

SPARE CAPACITY, PROVIDE ADD'L SLEEVES AS

NEEDED TO PROVIDE THIS SPARE CAPACITY.

RECESSED MOUNTED

TROFFER

PROVIDE A MINIMUM OF 3

TIGHT TWISTS AT CONNECTION

TO FIXTURE (TYPICAL OF ALL

FOUR CORNERS).

PROVIDE TRAPEZE

SUPPORT WIRE

(TYP)

PROVIDE A MINIMUM OF TWO (2) TIGHT WRAPS

AROUND STRUCTURE ABOVE OR PROVIDE 400LB.

PULLOUT HILTI ANCHORS IN CONCRETE SLAB, TO

SUIT ACTUAL FIELD CONDITIONS (TYPICAL OF ALL

FOUR CORNERS).

STRUCTURE ABOVE

CEILING

GENERAL TROFFER SUPPORT DETAIL NOTES:

A. SUPPORT WIRES SHALL BE GALVANIZED REGULAR COATING, SOFT TEMPER,

0.1055 INCHES IN DIAMETER (12 GAUGE).

B. SUPPORT FIXTURE INDEPENDITLY FROM THE CEILING (GRID) SUPPORT.

C. ALTERNATELY, CONTRACTOR MAY SUPPORT FIXTURES WITH SINGLE WIRE FROM

ALL FOUR CORNERS OF FIXTURE PER SPECIFICATIONS WITH NUMBER OF TWISTS

AT FIXTURE AND NUMBER OF WRAPS AROUND STRUCTURE INDICATED IN THIS

DETAIL.

SUSPENDED CEILING TILE

GENERAL NOTES:

A. NORMAL POWER LABELS SHALL BE BLACK WITH WHITE LETTERS.

B. EMERGENCY POWER LABELS SHALL BE RED WITH WHITE LETTERS. LABEL SHOULD ALSO INCLUDE

THE WORD "EMERGENCY" IN 1/4" LETTERS.

C. EMERGENCY POWER LABELS IN HEALTHCARE APPLICATIONS SHOULD INCLUDE SYSTEM SEVERED

"LIFE SAFETY", "CRITICAL" OR "EQUIPMENT" .

D. UTILIZE SCREW-ON TYPE LAMACOID PLATES.

E. THIS DETAILS APPLIES TO ALL ELECTRICAL EQUIPMENT INCLUDING PANELS, SWITCHGEAR, DISCONNECTS, TRANSFORMERS, MOTOR STARTERS, VARIABLE FREQUENCY DRIVES (VDF'S), SPECIAL DEVICE PLATES, INVERTER, AND SIMILAR MATERIALS SHALL BE CLEARLY MARKED AS TO

THEIR FUNCTION AND USE.

TYPICAL POWER PANEL NAMEPLATE DETAIL

NO SCALE

1/2'' HIGH

LETTERS

1/4'' HIGH

LETTERS

PANEL LXW

120/208V/3PH/4W

FEED: 200 AMPS

(4) #3/0, #6 GND, 2" C.

FED FROM: MDP

NO SCALE

PUMP P-1

208V/3PH/4W

FEED: 600 AMPS

FED FROM: MDP

CKT # 6

TYPICAL EQUIPMENT NAMEPLATE

LAMACOID

NAME PLATE

1/2'' HIGH

LETTERS

1/4'' HIGH

LETTERS

LAMACOID

NAME PLATE

NOTE :

PROVIDE WITH 4" TALL IN-LINE DIVIDER TO DIVIDE

SHARED TRAY BETWEEN DATA-VOICE CABLES AND

ALL OTHER CABLES.

COORDINATE EXACT ROUTING WITH ALL

OTHER TRADES AND OFFSET AS

REQUIRED

BUNDLE/WRAP CABLING AT EACH SIDE OF

SEPARATION

''SOLID'' TYPE CABLE TRAY SHALL BE 4"

DEEP WITH WIDTH AS INDICATED ON

DRAWINGS. CABLE TRAY SHALL HAVE

COVER. B-LINE OR EQUAL.

#6 BARE

GROUND

1" C AT ALL

TELECOM

ROOMS

TO TGB

OR TGMB

#6 BARE BONDED

TO TGB OR TGMB

RAISED WOOD SHEATHING PLATFORM

2025-048

Cincinnati/Northern Kentucky International Airport

BACKUP AOC

Interior Modifications

South ARFF Fire Station 2100 Tower Dr.

TH

IS

D O

C U M

EN

T, A N

D T

H E

ID

EA

S A N

D D

ES

IG

N S

IN

C O

R

PO

R A

TE

D H

ER

EI

N , A

S A N

I N

ST

R U M

EN

T

O F

PR

O

FE

SS

IO

N

A L

SE

R V

IC

E, I S

TH

E

PR

O

PE

R

TY

O F

EM

BO

SS

D

ES

IG

N , P

.S .C

A N

D I S

N O

T

TO

B E

U

SE

D I N

W H

O

LE

O R I N

P A R T

FO

R A

N Y

O

TH

ER

P

R O

JE

C T, W

IT

H O

U T

TH

E

W R

IT

TE

N

A U

TH

O R

IZ

A

TI

O N

O F

EM

BO

SS

D

ES

IG

N , P

.S .C

C O

PY

R

IG

H T

-2

5:

E

M

BO

SS

D

ES

IG

N , P

.S .C

A

LL

R

IG

H

TS

R

ES

ER

V

ED

15141312 161110987654321

A

D

B

C

E

F

G

H

J

K

L

M

15141312 161110987654321

A

D

B

C

E

F

G

H

J

K

L

M

IS

SU

E DATE DESCRIPTION

9/3/25 60% REVIEW

NO.

P

\P

R

-0

-B

A C

K U

P A

O C

-S O

U T

H A

R F

F \0

-D

R A

W

IN

G S

10/16/25 90% REVIEW

11/20/25 BIDDING & PERMIT

906 Monmouth Street, Newport, KY 41071

EmbossDesign.com (859)431-8612

S y c a m o re S t, S u it e

C in c in n a ti

O H

.4

.4

E 2 0 0

E L E C T R I C A L D E T A I L S

NOT TO SCALEE200

TYPICAL WALL DEVICE MOUNTING DETAIL2

NOT TO SCALEE200

CONDUIIT WALL SLEEVE INSTALLATION1

NOT TO SCALEE200

LUMINAIRE SUPPORT DETAIL3

NOT TO SCALEE200

ELECTRICAL EQUIPMENT NAMEPLATE4

NOT TO SCALEE200

CABLE TRAY INSTALLATION DETAIL5

CAT 5 CABLE

NX OCCUPANCY SENSOR

NX OCCUPANCY SENSOR

RED (24VDC)

BLUE (CONTROL)

BLACK

(COMMON)

R J A

D A

P T

E R

CAT 5 CABLE

CAT 5 CABLE

NXRC-1RD

NXRC-UL924-UNV

EMERGENCY

LIGHTING LOAD

G

V

H

N

VIOLET/WHITE

CAP

OFF

VIOLET

GRAY

RED

WHITE

BLUE WIRE

BLUE LOOP FOR USE WITH A

NORMALLY CLOSED

MAINTAINED TEST SWITCH

EMERGENCY

LIGHTING LOAD

G

V

H

N

GRAY

VIOLET

W H

IT

E

R E

D

B L

A C

K

/2

/3

V A

C

W H

IT

E

N

E U

T R

A L

B L

A C

K

/2

/3

V A

C

W H

IT

E

N

E U

T R

A L

ON / OFF

OS CEILING MOUNTED OCCUPANCY SENSOR

A. LOW VOLTAGE CEILING MOUNTED OCCUPANCY SENSOR BASIS OF

DESIGN: nLIGHT nCM SERIES.

B. LIGHTING TO AUTOMATICALLY TURN ON TO 100% WHEN OCCUPANCY IS

DETECTED.

C. WHILE IN UNOCCUPIED MODE NORMAL AND EMERGENCY LIGHTING

SHALL TURN OFF.

D. LIGHTING SHALL HAVE AUTOMATIC SHUT-OFF OF LIGHTING WITHIN 15

MINUTES OF OCCUPANTS LEAVING.

E. WHERE LIFE-SAFETY LIGHTING CIRCUIT(S) ARE PRESENT, PROVIDE

UL924 DEVICE(S) TO REVERT LIGHTS TO 100% UPON FAILURE OF

NORMAL POWER.

ON / OFF

A. LOW VOLTAGE MANUAL CONTROL STATION WITH INDIVIDUAL BUTTONS AS

SHOWN ON DETAIL. BASIS OF DESIGN: nLIGHT nPODMA SERIES.

B. ADDITIONAL CONTROL INPUTS: VACANCY SENSOR, PHOTOCELL. REFER TO

FLOOR PLANS AND SEQUENCE OF OPERATIONS FOR ADDITIONAL CONTROL

REQUIREMENTS.

C. SWITCH REQUIREMENTS:

a. MANUAL ON BUTTON

b. MANUAL OFF BUTTON

c. RAISE BUTTON

d. LOWER BUTTON

$LV1 LOW VOLTAGE ON/OFF, DIMMING CONTROL STATION

A. PROVIDE A STANDALONE LIGHTING CONTROL SYSTEM EQUAL TO nLIGHT BRANDS WITH ROOM

CONTROLLER TECHNOLOGY. REFER TO SPECIFICATIONS FOR ADDITIONAL ACCEPTABLE

MANUFACTURER.

B. PROVIDE FIRE-ALARM CONTROL/RELAY MODULE(S) AS REQUIRED TO MAKE LIGHTING CONTROL SYSTEM BRING ALL LIGHTING ON EGRESS PATHS TO 100% WHEN THE FIRE ALARM SYSTEM IS ACTIVATED.

C. INSTALL CONTROLLERS AND BRIDGES ABOVE ACCESSIBLE CEILING NEAR LUMINAIRE(S) TO BE CONTROLLED. PROVIDE CAD DRAWINGS INDICATING EXACT LOCATION OF CONTROL DEVICES AND

SUBMIT INFORMATION AS SHOP DRAWINGS FOR APPROVAL BY ENGINEER.

D. THE INTENTION IS TO PROVIDE A FULLY WIRED SYSTEM. WIRELESS AND/OR DEVICES THAT REQUIRE A

BATTERY ARE NOT ACCEPTABLE UNLESS SPECIFICALLY APPROVED BY THE ENGINEER.

E. CAT5, 5E, OR 6 NETWORK CABLE. NETWORK CABLE SHALL BE PLENUM RATED IF REQUIRED PER

SPECIFICATIONS AND /OR SITE CONDITIONS. MANIMUN CABLE LENGTH PER ZONE 1500 FEET.

LIGHTING CONTROL GENERAL NOTES:

NETWORK CABLE USED TO

INTERCONNET SWITCH TO

ROOM CONTROLLER

GENERAL NOTES:

A. THIS DETAIL ONLY APPLIES TO DRY-TYPE

TRANSFORMERS UP TO 45 KVA. CASE HARDENED NUTS

WASHERS

DRILL HOLE

3/4" THREADED ROD

2" x 2" x 3/8" ANGLE

1" x 1" x 3/16" ANGLE

1/2" x 4" SQ. VIBRATION

ISOLATION PADS

WELD (TYP.)

NEW STRUCTURE ABOVE TRANSFORMER - SIZE

FRAME APPROPRIATELY

2025-048

Cincinnati/Northern Kentucky International Airport

BACKUP AOC

Interior Modifications

South ARFF Fire Station 2100 Tower Dr.

TH

IS

D O

C U M

EN

T, A N

D T

H E

ID

EA

S A N

D D

ES

IG

N S

IN

C O

R

PO

R A

TE

D H

ER

EI

N , A

S A N

I N

ST

R U M

EN

T

O F

PR

O

FE

SS

IO

N

A L

SE

R V

IC

E, I S

TH

E

PR

O

PE

R

TY

O F

EM

BO

SS

D

ES

IG

N , P

.S .C

A N

D I S

N O

T

TO

B E

U

SE

D I N

W H

O

LE

O R I N

P A R T

FO

R A

N Y

O

TH

ER

P

R O

JE

C T, W

IT

H O

U T

TH

E

W R

IT

TE

N

A U

TH

O R

IZ

A

TI

O N

O F

EM

BO

SS

D

ES

IG

N , P

.S .C

C O

PY

R

IG

H T

-2

5:

E

M

BO

SS

D

ES

IG

N , P

.S .C

A

LL

R

IG

H

TS

R

ES

ER

V

ED

15141312 161110987654321

A

D

B

C

E

F

G

H

J

K

L

M

15141312 161110987654321

A

D

B

C

E

F

G

H

J

K

L

M

IS

SU

E DATE DESCRIPTION

9/3/25 60% REVIEW

NO.

P

\P

R

-0

-B

A C

K U

P A

O C

-S O

U T

H A

R F

F \0

-D

R A

W

IN

G S

10/16/25 90% REVIEW

11/20/25 BIDDING & PERMIT

906 Monmouth Street, Newport, KY 41071

EmbossDesign.com (859)431-8612

S y c a m o re S t, S u it e

C in c in n a ti

O H

.4

.4

E 2 0 1

E L E C T R I C A L D E T A I L S

NOT TO SCALEE201

TYPICAL UL924 CONTROL DIAGRAM1

NOT TO SCALEE201

SUSPENDED DRY-TYPE TRANSFORMER INSTALLATION3

EG8

375KVA

DIESEL

480Y/277V/3Φ/4W

600ASWBD (MAIN ELECTRIC ROOM)

480Y/277V, 3-PHASE, 4-WIRE

600A BUSSING

DISTRIBUTION SECTION(S)

100AT/

100AF

GENERAL POWER RISER NOTES:

A. REFER TO SPECIFICATIONS FOR CONDUCTOR REQUIREMENTS. FEEDERS SHALL

BE COPPER.

B. PROVIDE ENGRAVED LAMACOID LABELS FOR ALL POWER DISTRIBUTION

EQUIPMENT FURNISHED OR MODIFIED IN THIS PROJECT, LABELS PER DETAILS

AND SPECIFICATIONS.

C. SERVICE EQUIPMENT SHALL BE MARKED WITH THE MAXIMUM AVAILABLE FAULT-

CURRENT AT THE EQUIPMENT AND THE DATE THE CALCULATION WAS

PERFORMED. APPLY A TYPE-WRITTEN ADHESIVE LABEL WITH WHITE

BACKGROUND, 1/2'' HIGH BLACK LETTERING.

D. CONTRACTOR SHALL INSTALL SEPARATE CONDUITS, PULL BOXES, ETC. FOR EACH

EMERGENCY POWER BRANCH & NORMAL POWER PER NEC FOR COMPLETE

SEPARATION OF POWER SERVICES.

E. ALL SPARE BREAKERS SHALL BE SO LABELED IN CIRCUIT DIRECTORIES AND

SHALL BE LEFT IN THE OFF POSITION.

F. MINIMUM PANEL MOUNTING SPACE IS NOTED ON DRAWINGS AND SCHEDULES.

ALL MOUNTING SPACE SHALL BE PREPARED TO ACCEPT FUTURE BREAKERS.

G. SEE SPECIFICATIONS FOR POWER STUDY REQUIREMENTS.

H. PROVIDE ELECTRONIC TRIP BREAKERS ON ALL EMERGENCY BRANCH CIRCUITS

WHERE REQUIRED FOR SELECTIVE COORDINATION.

N E

ATS-1

600A

ATS

RTU-1

480Y/277V,3Φ,4W

EMB

PANEL

225A

MCB

TX-2

TRANSFORMER

75 kVA

208Y/120V,3Φ,4W

EMA

PANEL

225A MCB

208Y/120V,3Φ,4W

KP

PANEL

100A

TR-1

TRANSFORMER

75 kVA

225AT/

400AF

208Y/120V,3Φ,4W

LPA

PANEL

225A MLO

120/240V,1Φ,3W

60A MLO

AOC

PANEL

A

A

A

A

A

A

A

A

A

600A600A

(2) SETS OF (4) #350MCM

(1) #1 GND

IN 4" C.

FROM UTILITY

TRANS.

(2) SETS OF (4) #350MCM

(1) #1 GND

IN 4" C.

(4) 4/0 &

(1) #6 GND IN

2-1/2" C.

(4) #1 &

GND IN

1-1/2" C.

(3) #2 &

(1) #8 GND IN

1-1/2" C.

(4) 4/0 &

(1) #6 GND IN

2-1/2" C.

(4) 4/0 &

(1) #6 GND IN

2-1/2" C.

(4) #2 &

(1) #8 GND IN

1-1/2" C.

DP-1

A

A

DP-2

A

SPARE

M

UTILITY METER

# 108 262 173

59.8KW PEAK DEMAND

(4) #1/0 THWN &

(1) #6 GND IN

2-1/2" C.

(3) #2 THWN &

(1) #8 GND IN

1-1/2" C.

A

SINGLE LINE TAGGED NOTES

1. DEMOLISH EXISTING FUSE INSIDE EXISTING BUCKET ON SWITCHBOARD.

PROVIDE AND INSTALL NEW 40A FUSES IN BUCKET.

2. DEMOLISH ANY EXISTING ABANDONED CONDUIT AND CONDUCTORS

CONNECTED TO EXISTING SWITCHBOARD SPACE.

3. PROVIDE AND INSTALL NEW CONDUIT AND CONDUCTORS AND CONNECT TO

REPURPOSED SWITCHBOARD BUCKET.

4. PROVIDE NEW ISOLATED GROUND BAR.

5. PULL #6 IG CONDUCTOR IN EXISTING CONDUIT. CONNECT NEW IG BAR IN PANEL

EMA TO EXISTING GROUND BAR TRANSFORMER TX-2.

SPARE

50AT/

60AF

T-AOC

TRANSFORMER

15 kVA

2CU-40A

3CU-50A

3CU-50A

3CU-50A

208Y/120V,3Φ,4W

EMA1

PANEL

100A

23.3KW

FROM DRAWINGS

50KW

(4) #3 &

GND IN

CU.

23.3KW

20.4 KW

FROM DRAWINGS

42.8KW FROM DRAWINGS

BOD: SQUARE D

BOD: SCHNEIDER APC

SYMMETRA LX

470/277V, 1PH PRIMARY

120/240V, 1PH, 3W SECONDARY

2.2kAFC

A

8KVA UPS

2025-048

Cincinnati/Northern Kentucky International Airport

BACKUP AOC

Interior Modifications

South ARFF Fire Station 2100 Tower Dr.

TH

IS

D O

C U M

EN

T, A N

D T

H E

ID

EA

S A N

D D

ES

IG

N S

IN

C O

R

PO

R A

TE

D H

ER

EI

N , A

S A N

I N

ST

R U M

EN

T

O F

PR

O

FE

SS

IO

N

A L

SE

R V

IC

E, I S

TH

E

PR

O

PE

R

TY

O F

EM

BO

SS

D

ES

IG

N , P

.S .C

A N

D I S

N O

T

TO

B E

U

SE

D I N

W H

O

LE

O R I N

P A R T

FO

R A

N Y

O

TH

ER

P

R O

JE

C T, W

IT

H O

U T

TH

E

W R

IT

TE

N

A U

TH

O R

IZ

A

TI

O N

O F

EM

BO

SS

D

ES

IG

N , P

.S .C

C O

PY

R

IG

H T

-2

5:

E

M

BO

SS

D

ES

IG

N , P

.S .C

A

LL

R

IG

H

TS

R

ES

ER

V

ED

15141312 161110987654321

A

D

B

C

E

F

G

H

J

K

L

M

15141312 161110987654321

A

D

B

C

E

F

G

H

J

K

L

M

IS

SU

E DATE DESCRIPTION

9/3/25 60% REVIEW

NO.

P

\P

R

-0

-B

A C

K U

P A

O C

-S O

U T

H A

R F

F \0

-D

R A

W

IN

G S

10/16/25 90% REVIEW

11/20/25 BIDDING & PERMIT

906 Monmouth Street, Newport, KY 41071

EmbossDesign.com (859)431-8612

S y c a m o re S t, S u it e

C in c in n a ti

O H

.4

.4

E 7 0 0

E L E C T R I C A L S I N G L E L I N E

FEEDER SCHEDULE

Size Type WireSize

2CU-40A 2CU-40A (2) #8 CU & #10 CU GND. IN 3/4"C

3CU-50A 3CU-50A (3) #8 CU & #10 CU GND. IN 3/4"C

2025-048

Cincinnati/Northern Kentucky International Airport

BACKUP AOC

Interior Modifications

South ARFF Fire Station 2100 Tower Dr.

TH

IS

D O

C U M

EN

T, A N

D T

H E

ID

EA

S A N

D D

ES

IG

N S

IN

C O

R

PO

R A

TE

D H

ER

EI

N , A

S A N

I N

ST

R U M

EN

T

O F

PR

O

FE

SS

IO

N

A L

SE

R V

IC

E, I S

TH

E

PR

O

PE

R

TY

O F

EM

BO

SS

D

ES

IG

N , P

.S .C

A N

D I S

N O

T

TO

B E

U

SE

D I N

W H

O

LE

O R I N

P A R T

FO

R A

N Y

O

TH

ER

P

R O

JE

C T, W

IT

H O

U T

TH

E

W R

IT

TE

N

A U

TH

O R

IZ

A

TI

O N

O F

EM

BO

SS

D

ES

IG

N , P

.S .C

C O

PY

R

IG

H T

-2

5:

E

M

BO

SS

D

ES

IG

N , P

.S .C

A

LL

R

IG

H

TS

R

ES

ER

V

ED

15141312 161110987654321

A

D

B

C

E

F

G

H

J

K

L

M

15141312 161110987654321

A

D

B

C

E

F

G

H

J

K

L

M

IS

SU

E DATE DESCRIPTION

9/3/25 60% REVIEW

NO.

P

\P

R

-0

-B

A C

K U

P A

O C

-S O

U T

H A

R F

F \0

-D

R A

W

IN

G S

10/16/25 90% REVIEW

11/20/25 BIDDING & PERMIT

906 Monmouth Street, Newport, KY 41071

EmbossDesign.com (859)431-8612

S y c a m o re S t, S u it e

C in c in n a ti

O H

.4

.4

E 8 0 0

P A N E L S C H E D U L E S

NOTES:

TOTAL EST. DEMAND CURRENT: 8 A

REC 5940 VA 100.00% 5940 VA TOTAL CONN. CURRENT: 8 A

LTNG 145 VA 100.00% 145 VA TOTAL EST. DEMAND: 6 kVA

EQUIP 300 VA 100.00% 300 VA TOTAL CONN. LOAD: 6 kVA

LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS

8 SPACE -- -- -- -- 3 -- -- --

7 E RTU1 -- -- -- -- 3 100 A 100 A 0.0

6 E TR1 -- -- -- -- 3 100 A 100 A 0.0

5 E SPARE -- -- -- -- 3 100 A 100 A 0.0

4 T-AOC 2 100 A 40 A 1.8

3 E DP-2 -- -- -- -- 3 100 A 100 A 0.0

2 E DP-1 -- -- -- -- 3 100 A 100 A 0.0

1 E EMB 3 200 A 125 A 4.6

CKT CIRCUIT DESCRIPTION SETS WIRE GND COND POLES FRAME TRIP LOAD (kVA) REMARKS

AMPERES: 600 A MOUNTING: FLOOR SUPPLY FROM: UTILITY

VOLTAGE: 480Y/277V,3P,4W SPD: No LOCATION: MAIN ELECTRICAL ROOM

SWITCHBOARD: SWBD MAINS TYPE: 600A MCB kAIC RATING: EXISTING

SWITCHBOARD AND WIRING SCHEDULE kAIC VALUE: EXISTING

ADD ISOLATED GROUND BAR TO EXISTING PANEL.

NOTES: WHERE NOT LISTED, WIRE AND CONDUIT SHALL BE BE MINIMUM PER SPECIFICATIONS.

TOTAL ESTIMATED DEMAND CURRENT: 13 A

REC 4140 VA 100.00% 4140 VA TOTAL CONNECTED CURRENT: 13 A

LTNG 145 VA 100.00% 145 VA TOTAL ESTIMATED DEMAND: 4585 VA

EQUIP 300 VA 100.00% 300 VA TOTAL CONNECTED LOAD: 4585 VA

LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND PANEL TOTALS

13 A 18 A 8 A

1.5 kVA 2.1 kVA 1.0 kVA

E SPARE 20 1 41 0.0 0.0 42 1 20 E CORD DROP F-5

E WATER HEATER RR/SHOWER 20 1 39 0.0 0.1 40 1 20 BACKUP AOC TOWER LIGHTS

E F3 LADDER CORD DROP 20 1 37 0.0 0.0 38 1 20 E RADIO BATTERY CHARGERS

E CORD DROP WEST WALL 20 1 35 0.0 0.8 36

E CORD DROP WEST 20 1 33 0.0 1.8 34

E CORD DROP WEST 20 1 31 0.0 1.3 32

3 100 EMA1

29 0.0 0.0 30 1 20 E WEST WALL AND PIDS

27 0.0 0.0 28KP 100 3

25 0.0 0.0 26

2 30 E SHORELINE DISASTER TRAILER

E CORD DROP DOOR F3 20 1 23 0.0 0.0 24

E RADIO 20 1 21 0.0 0.0 22

2 20 E AC-1

E RADIO 20 1 19 0.0 0.0 20

E GATE CAMERA INTERCOM 20 1 17 0.0 0.0 18

2 20

E GENERATOR BATTERY CHARGER BLOCK

HEATER

E OPEN DOOR LIGHT 20 1 15 0.0 0.0 16 1 20 E SPARE

E EF LOUVER 20 1 13 0.0 0.0 14 1 20 E DUPLEX WEST F2 CORD DROP

E DUPLEX ALARM ROOM/INLINE FAN 20 1 11 0.0 0.0 12 1 20 E BAY HEATERS WEST

BACKUP AOC CPU IG DUPLEX 20 1 9 0.2 0.0 10 1 20 E BAY HEATERS WEST

BACKUP AOC CPU IG DUPLEX 20 1 7 0.2 0.0 8 1 20 E CORD DROP BATALLION DOOR

E PAGING SYSTEM 20 1 5 0.0 0.2 6 1 20 BACKUP AOC CPU IG DUPLEX

E FIRE ALARM PANEL 20 1 3 0.0 0.0 4 1 20 E DUPLEX CAPTAIN'S OFFICE

E DUPLEX AT TELEPHONE 20 1 1 0.0 0.0 2 1 20 E EX LOAD

CIRCUIT DESCRIPTION CB... OCP P CKT A B C CKT P OCP CB... CIRCUIT DESCRIPTION

AMPERES: 225 A MOUNTING: SURFACE SUPPLY FROM: T-EMA

VOLTAGE: 208Y/120V,3P,4W SPD: No LOCATION: WEST MEZZANINE

PANEL: EMA MAINS TYPE: 225A MCB PANEL INTERRUPTING RATING: EXISTING

PANELBOARD AND WIRING SCHEDULE AVAILABLE FAULT CURRENT: EXISTING

NOTES: WHERE NOT LISTED, WIRE AND CONDUIT SHALL BE BE MINIMUM PER SPECIFICATIONS.

TOTAL ESTIMATED DEMAND CURRENT: 8 A

TOTAL CONNECTED CURRENT: 8 A

TOTAL ESTIMATED DEMAND: 1800 VA

REC 1800 VA…