B08_Solicitation-Specifications_Drawings.pdf
PDF 30 MB Posted
- Attached to
- INDU Fire and Intrusion Alarm Replacement Federal contract opportunity
- Solicitation number
- 140P6425B0006
About this file
This document is a detailed construction specification for replacing fire and intrusion alarm systems across multiple facilities at Indiana Dunes National Park. The project involves comprehensive alarm system upgrades for numerous buildings including the Portage Lakefront Pavilion, Dunes Learning Center, Douglas Center, Chellberg Farm, multiple restroom facilities, and campground buildings. The specifications outline ten bid options covering different building groups, with specific requirements for fire alarm and intrusion detection systems, including door contacts, motion detectors, glass break detectors, and audible alarms.
The project is structured with a base scope of intrusion detection systems and optional bid packages for additional access control and fire alarm coverage. Key technical requirements include utilizing existing network infrastructure where possible, installing wireless or existing service-compatible devices, and ensuring compatibility with National Park Service standards. The work must be conducted with sensitivity to the historical significance of sites like the Chellberg Farm, following the Secretary of the Interior's Standards for the Treatment of Historic Properties. The project is set to be awarded in early summer 2025, with performance beginning in the same season, and is set aside 100% for small businesses with a total project magnitude estimated between $1 million and $5 million.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Questions_and_Answers_0002.pdf | ||
| B11_Site_Visit_Sign-In_Sheet_0002.pdf | ||
| Sol_140P6425B0006_Amd_0002.pdf | ||
| Sol_140P6425B0006_Amd_0001.pdf | ||
| B08_Solicitation-Notice_to_Contractors.pdf | ||
| B08_Solicitation-Construction_Contract_Administration.pdf | ||
| Sol_140P6425B0006.pdf | ||
| B08_Solicitation-Specifications.pdf | ||
| B08_Solicitation-Bid_Schedule.xlsx | XLSX spreadsheet | |
| B08_Solicitation-Wage_Determination.pdf | ||
| B08_Solicitation-Limitations_on_Subcontracting_Report.xlsx | XLSX spreadsheet | |
| B08_Solicitation-NPS_SubmittalList.xlsx | XLSX spreadsheet | |
| B08_Solicitation-Bid_Schedule.pdf |
Show all 13
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
CONSTRUCTION DOCUMENTS 100% REPLACE FIRE AND INTRUSION ALARM SYSTEMS
SEVERAL PARK FACILITIES
Mark Sheet REVISION Date Initial QUALITY DESIGN CERTIFICATION
Prepared in Accordance with Design
Development (Title I)
Variance from Design Development (Title I)
Approved by Superintendent on
Construction Drawing Not Preceded by Design Development (Title I)
OR
OR
Project Manager Date
Drawing No.
Date
0 100 % CD 02/03/25 __
A/E FIRM
PRIME:
BAILEY EDWARD,
CHICAGO, IL
SUB:
IMEG
CHICAGO, IL
MULTIPLE
225 W WASHINGTON STREET
SUITE 2700
CHICAGO, IL 60606
P: 312.294.0501 F: 312.294.0003 www.imegcorp.com
Illinois Design Firm Registration #184008976-0014
IMEG RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO
THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING
AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG AND SHALL NOT
BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE
EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG.
©2024 IMEG CONSULTANTS CORP.
REF. SCALE IN INCHES
0 1 2 3
PROJECT #22005370.07
100% CD - Rev. 11 02/13/25G0.2 LK
LK
2 100% CD - Rev 2E7.1, E8.1 E8.2 04/14/25
A
AFF ABOVE FINISHED FLOOR
APPROX APPROXIMATE
B
BSMT BASEMENT
BTTM/ BOTTOM OF
C
C/C CENTER TO CENTER
CLG CEILING
CLR CLEAR
CO CONTRACTING OFFICER
COL COLUMN
COR CONTRACTING OFFICER REPRESENTATIVE
D
DBL DOUBLE
DEMO DEMOLISH
DIA DIMENSIONS
DN DOWN
DO DITTO
DTL DETAIL
DWG DRAWING
E
E EXISTING
EA EACH
EL ELEVATION
ELEC ELECTRICAL
ELEV ELEVATOR / ELEVATION
EQ EQUAL
EXIST OR (E) EXISTING
EXT EXTERIOR
F
FE FIRE EXTINGUISHER
FEC FIRE EXTINGUISHER CABINET
FFE FINISHED FLOOR ELEVATION
FIN FINISH
FLR FLOOR
FND FOUNDATION
FO FACE OF
FTG FOOTING
I
INT INTERIOR
M
MATL MATERIAL
MAX MAXIMUM
MECH MECHANICAL
MFR MANUFACTURER
MIN MINIMUM
N
N NEW
NIC NOT IN CONTRACT
NO NUMBER
NOM NOMINAL
O
OC ON CENTER
OH OPPOSITE HAND
P
PARK THE NATIONAL PARK SERVICE UNIT
PNT PAINTED/PAINT
PT PRESSURE TREATED
R
R RADIUS
RCP REFLECTED CEILING PLAN
RD ROOF DRAIN
REQD REQUIRED
RM ROOM
S
SF SQUARE FOOT
SIM SIMILAR
SPEC SPECIFIED OR SPECIFICATION
SQ SQUARE
STRUC STRUCTURAL
T
T/ TOP OF
TOC TOP OF CONCRETE
TOS TOP OF STRUCTURE/STEEL
TOW TOP OF WALL
TYP TYPICAL
U
UNO UNLESS NOTED OTHERWISE
V
VIF VERIFY IN FIELD
VP VISION PANEL
W
W/ WITH
WD WOOD
ABBREVIATIONS
THIS PROJECT IS DESIGNED TO MEET THE CODES APPLICABLE
TO THE NATIONAL PARK SERVICE.
1. RM 58 NPS STRUCTURAL FIRE HANDBOOK
2. NPS CABLING STANDARD V1.4
3. NPS FP SYSTEMS INSTALLATION
4. ITM GUIDANCE, FIRE PROTECTION FOR HISTORIC
STRUCTURES
5. IFC 2021, WITH APPENDICES AND APPLICABLE NFPA
STANDARDS
6. IEBC 2024, WITH APPENDICES
7. IECC 2021
8. IMC 2021
9. IPC 2021
10. IFGC 2018
11. NESC 2017
12. NFPA 70 : NEC 2023
13. ABAAS
14. ABA STANDARDS 2015
15. ASHRAE 90.1 2016
16. ASHRAE/IES 90.1 2016
17. IBC 2024 FOR EXIT AND EGRESS LIGHTING
BUILDING CODES
SHEET INDEX
SHEET NO.
Sheet
Number
Sheet Title
1 - COVER
2 G0.1 GENERAL INFORMATION AND INDEX
3 G0.2 GENERAL NOTES
4 E0.0 ELECTRICAL COVER SHEET
5 E0.1 ELECTRICAL DETAILS
6 T0.0 TECHNOLOGY COVER SHEET
PMIS PROJECT TITLE
325487
PORTAGE LAKEFRONT PAVILION & DUNES
LEARNING CENTER
SHEET NO.
Sheet
Number
Sheet Title
7 C1.1
PORTAGE LAKEFRONT PAVILION
LOGISTIC PLAN
8 E1.1
PORTAGE LAKEFRONT PAVILION
FIRST FLOOR PLAN - ELECTRICAL
SYSTEMS
9 T1.1
PORTAGE LAKEFRONT PAVILION -
FIRST FLOOR PLAN - TECHNOLOGY
10 C2.0
DUNES LEARNING CENTER (DLC)
LOGISTIC PLAN
11 E2.1
DLC DINING HALL-
FIRST FLOOR PLAN - ELECTRICAL
SYSTEMS
12 T2.1
DLC DINING HALL - FIRST FLOOR PLAN -
TECHNOLOGY
13 E2.2
COWLES LODGE CABIN - FIRST FLOOR
PLAN - ELECTRICAL SYSTEMS
14 T.2.2
COWLES LODGE CABIN - FIRST FLOOR
PLAN - TECHNOLOGY
15 T2.3
DLC DINING HALL TECHNOLOGY DETAILS
AND DIAGRAMS
16 T2.4
DLC DINING HALL TECHNOLOGY
SCHEDULES
PMIS PROJECT TITLE
325489
DOUGLAS CENTER AND DUNEWOOD
CAMPGROUND BUILDINGS
SHEET NO.
Sheet
Number
Sheet Title
17 C3.0 DOUGLAS CENTER LOGISTIC PLAN
18 ED3.0
DOUGLAS CENTER - LOWER LEVEL
FLOOR PLAN - ELECTRICAL SYSTEMS
19 ED3.1
DOUGLAS CENTER - FIRST FLOOR FLOOR
PLAN - ELECTRICAL SYSTEMS
20 E3.0
DOUGLAS CENTER - LOWER LEVEL PLAN -
ELECTRICAL SYSTEMS
21 E3.1
DOUGLAS CENTER - FIRST FLOOR PLAN -
ELECTRICAL SYSTEMS
22 T3.0
DOUGLAS CENTER - LOWER LEVEL PLAN -
TECHNOLOGY
23 T3.1
DOUGLAS CENTER - FIRST FLOOR PLAN
- TECHNOLOGY
24 T3.2
DOUGLAS CENTER TECHNOLOGY
SCHEDULES
25 C4.0
DUNEWOOD CAMPGROUND
LOGISTIC PLAN
26 E4.1
REGISTRATION BUILDING - FIRST FLOOR
PLAN - ELECTRICAL SYSTEMS
27 T4.1
REGISTRATION BUILDING
- FIRST FLOOR PLAN - TECHNOLOGY- BID
OPTION 3
28 T4.2
REGISTRATION BUILDING TECHNOLOGY
SCHEDULES
29 E5.1
MATHER LOOP RESTROOM - FIRST FLOOR
PLAN - ELECTRICAL SYSTEMS
30 E6.1
DOUGLAS LOOP RESTROOM - FIRST
FLOOR PLAN - ELECTRICAL SYSTEMS
PMIS PROJECT TITLE
334528C CHELLBERG FARM
SHEET NO.
Sheet
Number
Sheet Title
31 C7.0 CHELLBERG FARM LOGISTIC PLAN
32 ED7.1
CHELLBERG FARM HOUSE - FIRST,
SECOND, AND CELLAR FLOOR PLAN -
ELECTRICAL SYSTEMS
33 E7.1
CHELLBERG FARM HOUSE - FIRST,
SECOND, AND CELLAR FLOOR PLAN -
ELECTRICAL SYSTEMS
34 TD7.1
CHELLBERG FARM HOUSE
FIRST, SECOND, AND CELLAR FLOOR
PLAN - TECHNOLOGY
35 T7.1
CHELLBERG FARM HOUSE - FIRST,
SECOND, AND CELLAR FLOOR PLAN -
TECHNOLOGY
36 T7.2
CHELLBERG FARM HOUSE TECHNOLOGY
SCHEDULES
37 E8.1
CHELLBERG BARN - FIRST FLOOR PLAN -
ELECTRICAL SYSTEMS
38 E8.2
CHELLBERG FARM OUTBUILDINGS - FIRST
FLOOR PLAN - ELECTRICAL SYSTEMS
OPTION PMIS PROJECT TITLE
325494 SEVERAL PARK RESTROOM FACILITIES
SHEET NO.
Sheet
Number
Sheet Title
39 C9.0 WEST BEACH LOGISTICS PLAN
40 E9.1
WEST BEACH CONTACT STATION - FIRST
FLOOR PLAN - ELECTRICAL SYSTEMS -
BID OPTION
41 E10.1
WEST BEACH PICNIC RESTROOMS - FIRST
FLOOR PLAN - ELECTRICAL SYSTEMS -
BID OPTION
42 C11.0
WEST BEACH FEE COLLECTION BUILDING
LOGISTIC PLAN
43 E11.1
WEST BEACH FEE COLLECTION BUILDING
- FIRST FLOOR PLAN - ELECTRICAL
SYSTEMS - BID OPTION
44 T11.1
WEST BEACH FEE COLLECTION BUILDING
- FIRST FLOOR PLAN - TECHNOLOGY- BID
OPTION
45 T11.2
WEST BEACH FEE COLLECTION BUILDING
TECHNOLOGY SCHEDULES - BID OPTION
46 C12.0
CALUMET DUNE RESTROOM AND
PUMPHOUSE LOGISTIC PLAN
47 E12.1
CALUMET DUNE RESTROOM +
PUMPHOUSE - ELECTRICAL SYSTEMS -
BID OPTION
48 C13.0
BAILLY CHELLBERG (BC) CONTACT
STATION LOGISTIC PLAN
49 ED13.1
BC CONTACT STATION - FIRST FLOOR
PLAN - ELECTRICAL SYSTEMS - BID
OPTION
50 E13.1
BC CONTACT STATION - FIRST FLOOR
PLAN - ELECTRICAL SYSTEMS - BID
OPTION
51 C14.0 GLENWOOD DUNES LOGISTIC PLAN
52 E14.1
GLENWOOD DUNES RESTROOM - FIRST
FLOOR PLANS - ELECTRICAL SYSTEMS -
BID OPTION
DATE:
DESIGNED:
TECH. REVIEW:
SUB SHEET NO.
PMIS/PKG NO.
DRAWING NO.
SHEET
TITLE OF SHEETA/E FIRM
SUBCONTRACTOR
PRIME:
AND INDEX
MULTIPLE
2 6602/03/25 INDIANA DUNES NATIONAL PARK (INDU)
MULTIPLEG0.1
CHICAGO, IL
IMEG
CHICAGO, IL
BAILEY EDWARD
REPLACE FIRE AND INTRUSION ALARMS
GENERAL INFORMATION
EXP: 12/31/25
PMIS PROJECT TITLE
325495 BEACH RESTROOM FACILITIES
SHEET NO.
Sheet
Number
Sheet Title
53 C15.0
CENTRAL RESTROOM
LOGISTIC PLAN
54 E15.1
CENTRAL RESTROOM - FIRST FLOOR
PLAN - ELECTRICAL SYSTEMS - BID
OPTION
55 C16.0 TREMONT RESTROOM LOGISTIC PLAN
56 E16.1
TREMONT RESTROOM - FIRST
FLOOR PLAN - ELECTRICAL SYSTEMS -
BID OPTION
57 C17.0
MOUNT BALDY RESTROOM LOGISTIC
PLAN
58 E17.1
MOUNT BALDY RESTROOM - FIRST FLOOR
PLAN - ELECTRICAL SYSTEMS - BID
OPTION
59 C18.0 KEMIL RESTROOM LOGISTIC PLAN
60 E18.1
KEMIL RESTROOM - FIRST FLOOR PLAN -
ELECTRICAL SYSTEMS - BID OPTION
61 C19.0
PORTER BEACH RESTROOM LOGISTIC
PLAN
62 E19.1
PORTER BEACH RESTROOM - FIRST
FLOOR PLAN - ELECTRICAL SYSTEMS -
BID OPTION
63 C20.0 DUNBAR RESTROOM LOGISTIC PLAN
64 E20.1
DUNBAR RESTROOM - FIRST FLOOR PLAN
- ELECTRICAL SYSTEMS - BID OPTION
65 C21.0 LAKEVIEW RESTROOM LOGISTIC PLAN
66 E21.1
LAKEVIEW RESTROOM - FIRST FLOOR
PLAN - ELECTRICAL SYSTEMS - BID
OPTION
HISTORICAL SIGNIFICANCE
1. THE INDIANA DUNES WERE THE SUBJECT OF A 50-YEAR FIGHT
TO SAVE THEM FROM INDUSTRIALIZATION. IN 1926, AFTER A
TEN-YEAR PETITION BY THE STATE OF INDIANA TO PRESERVE
THE DUNES, THE INDIANA DUNES STATE PARK OPENED TO THE
PUBLIC. PUBLIC LAW 89-761, PASSED ON NOVEMBER 5, 1966,
DESIGNATED THE PARK AS THE INDIANA DUNES NATIONAL
LAKESHORE. THE 1966 AUTHORIZING LEGISLATION INITIALLY
INCLUDED ONLY 8,330 ACRES OF LAND AND WATER. FOUR
SUBSEQUENT EXPANSION BILLS FOR THE PARK (1976, 1980,
1986, AND 1992) HAVE INCREASED THE SIZE OF THE PARK TO
MORE THAN 15,000 ACRES. ON FEBRUARY 15, 2019, CONGRESS
AUTHORIZED THE NAME CHANGE FROM INDIANA DUNES
NATIONAL LAKESHORE TO INDIANA DUNES NATIONAL PARK -
THE NATION'S 61ST NATIONAL PARK.
2. THE INDIANA DUNES INCLUDE HISTORICAL SITES SUCH AS THE
BAILLY HOMESTEAD (1822) AND THE CHELLBERG FARM (1872).
DESIGN INTENT STATEMENT
WORK OF THIS SECTION SHALL BE GOVERNED BY THE
CONTRACT DOCUMENTS. PROVIDE MATERIALS, LABOR,
EQUIPMENT, AND SERVICES NECESSARY TO FURNISH, DELIVER,
AND INSTALL THE WORK OF THIS SECTION AS SHOWN ON THE
DRAWINGS, AS SPECIFIED HEREIN, AND/OR AS REQUIRED BY
JOB CONDITIONS.
THIS PROJECT INCLUDES REPLACEMENT OF ALL FIRE AND
INTRUSION ALARM SYSTEM IN MULTIPLE PARK BUILDINGS THAT
ARE NOT PROPOSED FOR A MAJOR REHABILITATION IN THE
NEXT 5 YEARS. AS MOST PARK ALARM SYSTEMS ARE NO
LONGER FUNCTIONAL, MANY PARK STRUCTURES ARE
VULNERABLE TO DAMAGE BY FIRE OR BREAK-INS. THIS
PROJECT INCLUDES THE REMOVAL OF THESE EXISTING
NON-FUNCTIONING FIRE AND INTRUSION ALARM SYSTEMS.
PROJECT ADDRESS:
MULTIPLE LOCATIONS AT INDIANA DUNES NATIONAL PARK, LAKE,
LAPORTE, AND PORTER COUNTY, IN
BASE SERVICES:
NOTE: WHERE APPLICABLE - WHERE FORMER ALARM SYSTEMS
HAVE BEEN REMOVED, PATCHING AND REPAIR OF DRYWALL
AND WALL FINISHES SHALL MATCH EXISTING ADJACENT
SURFACES. IF A SEAMLESS MATCH CANNOT BE ACHIEVED
THROUGH TOUCH-UP PAINTING, THE ENTIRE WALL SHALL BE
REPAINTED.
1. GROUP A: PORTAGE LAKEFRONT PAVILION AND DUNES
LEARNING CENTER - PMIS 325487
1.1. PORTAGE LAKEFRONT PAVILION
- FIRE ALARM COVERAGE
- INTRUSION COVERAGE:
-- CONTACTS AT ALL EXTERIOR DOORS, ROLLER
DOOR, AND SLIDING WINDOWS.
-- MOTION DETECTION IN MAIN CORRIDOR, GLASS
BREAK DETECTOR IN CLASSROOM.
-- CONTACT AT ROOF HATCH.
1.2 DUNES LEARNING CENTER
1.2.1 DUNES LEARNING CENTER DINING HALL
- FIRE ALARM COVERAGE
- INTRUSION COVERAGE
1.2.2 COWLES LODGE
- FIRE ALARM COVERAGE
- INTRUSION COVERAGE:
-- CONTACTS AT ALL EXTERIOR DOORS.
-- MOTION DETECTION IN HALLWAYS AND
CAFETERIA.
-- DOOR CONTACTS AT TWO INTERIOR OFFICES;
CONTACTS AT SE OFFICE WINDOWS,
EVALUATION OF GLASS BREAK DETECTION.
1.2.3 (10) STUDENT CABINS: FIRE ALARM COVERAGE
BID OPTIONS:
1. BID OPTION #1: GROUP B - DOUGLAS CENTER AND
DUNEWOOD CAMPGROUND BUILDING - PMIS 325489
1.1 DOUGLAS CENTER
- FIRE ALARM COVERAGE
- INTRUSION COVERAGE TO INCLUDE:
-- CONTACTS AT ALL EXTERIOR DOORS (INCLUDE
LOWER LEVEL EXTERIOR DOOR); CONTACTS ON
ENVIRONMENTAL CONTROL WINDOWS TIED TO
HVAC (WALKWAY, MAIN LOBBY, AND ACTIVITY
ROOMS)
-- MOTION DETECTION IN MAIN CORRIDORS AND
ALL CLASSROOMS
-- INTERIOR DOOR CONTACTS AT MECHANICAL /
ELECTRICAL ROOM AND SUPERVISOR OFFICE
1.2 CAMPGROUND REGISTRATION BUILDING
- FIRE ALARM COVERAGE
1.3 MATHER LOOP RESTROOMS
- FIRE ALARM COVERAGE
1.4 DOUGLAS LOOP RESTROOMS
- FIRE ALARM COVERAGE
2. BID OPTION #2: GROUP C - CHELLBERG FARM - PMIS 334528C
2.1 CHELLBERG FARM - MAIN HOUSE
- FIRE ALARM COVERAGE
- INTRUSION ALARM COVERAGE TO INCLUDE:
-- CONTACTS AT ALL EXTERIOR DOORS AND
BASEMENT HATCH.
-- MOTION DETECTORS IN LIVING ROOM AND
UPPER LEVEL.
2.2 CHELLBERG FARM OUTBUILDINGS
2.2.1 BARN
- FIRE ALARM COVERAGE
2.2.2 SUGAR SHACK
- FIRE ALARM COVERAGE
2.2.3 CHELLBERG FARM CHICKEN COOP
- FIRE ALARM COVERAGE
2.2.4 CHELLBERG FARM STORAGE SHED
- FIRE ALARM COVERAGE
3. BID OPTION #3: GROUP A - PORTAGE LAKEFRONT PAVILION -
PMIS 325487
3.1 PORTAGE LAKEFRONT PAVILION
- ACCESS CONTROL (UNLOCKING DOORS)
4. BID OPTION #4: GROUP A - DLC CABIN INTRUSION- PMIS
325487
4.1 DUNES LEARNING CENTER - (10) STUDENT CABINS
- EXTERIOR DOOR CONTACTS
5. BID OPTION #5: GROUP A - COWLES LODGE ACCESS
CONTROL- PMIS 325487
5.1 COWLES LODGE
- ACCESS CONTROL (UNLOCKING DOORS)
6. BID OPTION #6: CAMPGROUND REGISTRATION INTRUSION -
PMIS 325489
6.1 CAMPGROUND REGISTRATION BUILDING
- CONTACTS AT ALL EXTERIOR DOORS AND ALL
EXTERIOR WINDOWS
- MOTION DETECTOR IN MAIN CORRIDOR
7. BID OPTION #7: DOUGLAS CENTER ACCESS CONTROL - PMIS
325489
7.1 DOUGLAS CENTER
- ACCESS CONTROL (UNLOCKING DOORS)
8. BID OPTION #8: GROUP D - PARK RESTROOM FACILITIES -
PMIS 325494
8.1. WEST BEACH CONTACT STATION
- FIRE ALARM COVERAGE
8.2. WEST BEACH PICNIC RESTROOMS
- FIRE ALARM COVERAGE
8.3. WEST BEACH FEE COLLECTION FACILITY
- FIRE ALARM COVERAGE
- INTRUSION COVERAGE TO INCLUDE:
-- CONTACTS AT ALL EXTERIOR DOORS AND ALL
EXTERIOR WINDOWS.
-- PANIC BUTTONS.
-- MOTION DETECTOR IN MAIN CORRIDOR.
8.4. CALUMET DUNE RESTROOM AND PUMPHOUSE
- FIRE ALARM COVERAGE
8.5. BAILLY/CHELLBERG CONTACT STATION
- FIRE ALARM COVERAGE
8.6. GLENWOOD DUNES RESTROOM
- FIRE ALARM COVERAGE
9. BID OPTION #9: GROUP E - BEACH RESTROOM FACILITIES -
PMIS 325495
9.1 CENTRAL RESTROOM
- FIRE ALARM COVERAGE
9.2. TREMONT RESTROOM
- FIRE ALARM COVERAGE
9.3 MOUNT BALDY RESTROOM
- FIRE ALARM COVERAGE
9.4. KEMIL RESTROOM
- FIRE ALARM COVERAGE
9.5. PORTER BEACH RESTROOM
- FIRE ALARM COVERAGE
9.6. DUNBAR RESTROOM
- FIRE ALARM COVERAGE
9.7. LAKEVIEW RESTROOM
- FIRE ALARM COVERAGE
10. BID OPTION #10: GROUP D - PARK RESTROOM FACILITIES
ACCESS- PMIS 325494
10.1 WEST BEACH FEE COLLECTION FACILITY
- ACCESS CONTROL (UNLOCKING DOORS)
PHASING
1. VERIFY THAT EXISTING CONDITIONS ARE AS INDICATED ON
THE DRAWINGS. NOTIFY THE CONTRACTING OFFICER
IMMEDIATELY OF VARIATIONS OR DISCREPANCIES THAT
HAVE THE POTENTIAL TO AFFECT THE WORK. DO NOT
PROCEED WITH AFFECTED WORK UNTIL VARIATIONS OR
DISCREPANCIES ARE FULLY RESOLVED IN CONSULTATION
WITH THE CONTRACTING OFFICER.
1.1. VISIT THE SITE TO DETERMINE BY INSPECTION ALL
EXISTING CONDITIONS, INCLUDING ACCESS TO THE
SITE, THE NATURE OF STRUCTURES, OBJECTS AND
MATERIALS TO BE ENCOUNTERED, AND ALL OTHER
FACTS CONCERNING OR AFFECTING THE WORK.
INFORMATION AS DRAWN SHOWS EXISTING
CONDITIONS FOR INFORMATION ONLY AND DOES NOT
CONSTITUTE A GUARANTEE THAT OTHER ITEMS MAY
NOT BE FOUND OR ENCOUNTERED.
1.2. BEFORE STARTING WORK, MAKE A THOROUGH
EXAMINATION OF THOSE PORTIONS OF THE SITE IN
WHICH THE WORK IS TO BE PERFORMED. REPORT TO
THE CONTRACTING OFFICER ANY AND ALL CONDITIONS
WHICH MAY INTERFERE WITH OR OTHERWISE AFFECT
OR PREVENT THE PROPER EXECUTION AND
COMPLETION OF THE WORK. DO NOT START THE WORK
UNTIL SUCH CONDITIONS HAVE BEEN EXAMINED
AND A COURSE OF ACTION MUTUALLY AGREED UPON.
1.3. CONFLICTS BETWEEN VARIOUS ELEMENTS OF THE
DRAWINGS, SPECIFICATIONS, NOTES AND DETAILS
SHALL BE BROUGHT TO THE ATTENTION OF THE
CONTRACTING OFFICER AND RESOLVED BEFORE
PROCEEDING WITH WORK.
1.4. THE EXECUTION OF WORK CONSTITUTES ACCEPTANCE
OF THE CONDITIONS. LATER CLAIMS WILL NOT
CONSTITUTE RELIEF FROM THE REQUIREMENTS OF THE
SPECIFICATIONS UNDER THIS SECTION, NOR WILL
EXTRA COMPENSATION BE PAID.
2. THE NEW SYSTEMS WILL UTILIZE THE EXISTING NETWORK
VIA NP DIALER WHERE AVAILABLE. IN BUILIDNGS WITHOUT
NETWORK ACCESS, CELULLAR DIALERS WILL BE USED.
PARK IS TO ENSURE THAT ELECTRICAL POWER AND
CIRCUITS ARE AVAILABLE AND CODE COMPLIANT WITHIN
EXISTING PANELS TO SUPPORT THE REQUIREMENTS OF
THIS PROJECT.
3. THE CONTRACTOR SHALL RECOGNIZE THAT ALL ASPECTS
AND ELEMENTS OF THE PROPERTY MAY POTENTIALLY
CONTRIBUTE TO THE SIGNIFICANCE, AND THE
CONTRACTOR SHALL NOT BE THE JUDGE OF THE RELATIVE
SIGNIFICANCE OF ANY FEATURE. THIS JUDGMENT IS
ENTIRELY THE RESPONSIBILITY OF THE CONTRACTING
OFFICER. CONSEQUENTLY, NO ELEMENT SHALL BE
ALTERED, REMOVED, REFUSED OR TAKEN FROM THE
PREMISES WITHOUT THE APPROVAL OF THE CONTRACTING
OFFICER AS BEING CONSISTENT WITH THE REQUIREMENTS
OF THE CONTRACT DOCUMENTS.
3.1. ACTIVITIES THAT INVOLVE DEMOLITION, DISASSEMBLY,
OR SELECTIVE REMOVAL OF MATERIAL CAN RESULT IN
PERMANENT LOSS IF CARE IS NOT TAKEN TO AVOID
SUCH DAMAGE. APPROPRIATE PROCEDURES AND
TECHNIQUES FOR STORAGE OF DISASSEMBLED ITEMS
MUST BE TAKEN INTO ACCOUNT AS SPECIFIED BEFORE
THE WORK COMMENCES..
3.2. HVAC, PLUMBING, AND FIRE PROTECTION (SPRINKLER
SYSTEM) ARE NOT INCLUDED IN THE SCOPE OF THIS
PROJECT.
4. PROTECT AND PREVENT DAMAGE TO ALL BUILDING AND
SITE RESOURCES. NOTIFY CONTRACTING OFFICER
IMMEDIATELY IF ACCESS, TRANSPORT OF MATERIALS, OR
ANY ASPECT OF THE WORK HAS THE POTENTIAL TO CAUSE
DAMAGE TO RESOURCES. DO NOT PROCEED WITH
AFFECTED WORK UNTIL POTENTIALLY-DAMAGING ACTIONS
ARE FULLY RESOLVED IN CONSULTATION WITH THE
CONTRACTING OFFICER.
5. PERFORM ALL CONSTRUCTION AND INSTALLATION WORK
SHOWN IN ACCORDANCE WITH ALL APPLICABLE LAWS,
CODES AND ORDINANCES. USE METHODS AS REQUIRED TO
COMPLETE WORK WITHIN LIMITATIONS OF ALL PREVAILING
CODES AND LAWS.
6. DO NOT SCALE DRAWINGS: USE DIMENSIONS SHOWN.
VERIFY ALL DIMENSIONS IN THE FIELD.
7. SAFETY MEASURES: AT ALL TIMES THE CONTRACTOR SHALL
BE SOLELY RESPONSIBLE FOR THE CONDITIONS AT THE JOB
SITE, INCLUDING SAFETY OF PEOPLE AND PROPERTY.
8. INSTALL MANUFACTURED MATERIALS AND EQUIPMENT PER
MANUFACTURER'S RECOMMENDATIONS AND
INSTRUCTIONS, UNLESS OTHERWISE INSTRUCTED.
9. ALL WASTE GENERATED BY THE WORK SHALL BE REMOVED
FROM THE PREMISES AND LEGALLY DISPOSED OF BY THE
CONTRACTOR INCLUDING HAZARDOUS MATERIALS.
HAZARDOUS MATERIAL DISPOSAL MUST BE DOCUMENTED
AND LEGAL DISPOSAL PERMITS SUBMITTED FOR RECORD.
THE PREMISES SHALL BE LEFT CLEAR AND CLEAN TO THE
SATISFACTION OF THE CONTRACTING OFFICER.
10. APPLICATION OF FINISH: SURFACES PREVIOUSLY
PREPARED OR INSTALLED BY ANOTHER TRADE SHALL BE
INSPECTED CAREFULLY BY THE CONTRACTOR BEFORE
APPLYING SUBSEQUENT MATERIALS OR FINISHES. IF
SURFACES ARE NOT ACCEPTABLE, IMMEDIATELY NOTIFY
THE CONTRACTING OFFICER SO THAT CORRECTIONS MAY
BE MADE. DO NOT APPLY FINISHES TO SUBSTRATES THAT
ARE NOT ACCEPTABLE.
11. INSTALL WORK PLUMB, LEVEL AND STRAIGHT, OR AS
REQUIRED TO ALIGN WITH EXISTING SURFACES TO REMAIN.
12. DETAILS SHOWN SHALL BE INCORPORATED INTO THE
PROJECT AT ALL APPROPRIATE LOCATIONS WHETHER
SPECIFICALLY CALLED OUT OR NOT.
13. THE CONTRACTING OFFICER IS TO HOLD A TOUR OF THE
PROPERTY PRIOR TO DEMOLITION FOR ALL PROJECT
MANAGERS, SUPERVISORS, SUPERINTENDENTS, OR
FOREMEN (PLUS ANY INTERESTED WORKERS) OF EACH
CONTRACTOR AND SUBCONTRACTOR.
14. THE CONTRACTOR WILL COMPLY WITH ALL SECURITY
RULES AND POLICIES OF THE PARK AND CONTRACTING
OFFICER AND SHALL INCLUDE ALL COSTS ASSOCIATED
WITH COMPLIANCE.
15. ALL ON-SITE PERSONNEL ARE EXPECTED TO CONDUCT
THEIR OPERATIONS IN A PROFESSIONAL MANNER AND BE
COURTEOUS AND POLITE TO ALL VISITORS.
16. WORKMANSHIP - EMPLOY ONLY COMPETENT WORKERS
THOROUGHLY SKILLED IN THEIR RESPECTIVE TRADES TO
PERFORM THE WORK. THE WORK SHALL BE PERFORMED
BY COMPETENT WORKERS EXPERIENCED IN THIS KIND OF
WORK AND SHALL BE CARRIED THROUGH TO COMPLETION.
17. PERFORM THE WORK IN ACCORDANCE WITH THE HIGHEST
STANDARDS AND ESTABLISHED PRACTICES IN THE TRADE,
AND CONFORM TO ALL THE RULES AND REGULATIONS OF
ALL CITY, STATE AND FEDERAL AUTHORITIES HAVING
JURISDICTION OVER THIS WORK
18. CONTRACTOR TO PROTECT GROUND SURFACES ADJACENT
TO WORK. REPAIR TURF AND ADJACENT SURFACES TO
PRE-PROJECT CONDITIONS.
HISTORIC TREATMENT STANDARD
1. THE CHELLBERG FARM MAINHOUSE AND OUTBUILDINGS
ARE THE ONLY HISTORIC STRUCTURES INCLUDED IN THIS
FIRE AND INTRUSION ALARM SYSTEM REPLACEMENT
PROJECT, ALL REPAIRS TO HISTORIC FINISHES AFFECTED
BY THIS WORK MUST BE PERFORMED USING APPROPRIATE
PRESERVATION TREATMENTS.
2. THE WORK OF THIS PROJECT IS TO BE CONDUCTED IN A
MANNER CONSISTENT WITH "THE SECRETARY OF THE
INTERIOR'S STANDARDS FOR THE TREATMENT OF HISTORIC
PROPERTIES."
3. PRESERVATION IS THE TREATMENT STANDARD TO BE
APPLIED TO THE WORK OF THIS PROJECT.
1. NEW FIRE AND INTRUSION ALARM SYSTEMS ARE TO BE
INSTALLED, TESTED, AND COMMISSIONED PRIOR TO
THE DEMOLITION OF ANY EXISTING OPERABLE
SYSTEMS.
2. EXISTING NON-OPERABLE ALARM SYSTEMS, ARE TO BE
REMOVED PRIOR TO THE INSTALLATION OF THE NEW
ALARM SYSTEMS AT THE FOLLOWING SITES:
2.1. PMIS 325489
- CAMPGROUND REGISTRATION BUILDING
2.1. PMIS 325494
- WEST BEACH CONTACT STATION
- CALUMET DUNES RESTROOM
- BAILLY CHELLBERG CONTACT STATION
- GLENWOOD DUNES RESTROOM
2.1. PMIS 325495
- CENTRAL RESTROOM
- TREMONT RESTROOM
- MOUNT BALDY RESTROOM
- KEMIL RESTROOM
- PORTER BEACH RESTROOM
- DUNBAR RESTROOM
- LAKEVIEW RESTROOM
DATE:
DESIGNED:
TECH. REVIEW:
SUB SHEET NO.
PMIS/PKG NO.
DRAWING NO.
SHEET
TITLE OF SHEETA/E FIRM
SUBCONTRACTOR
PRIME: 626
MULTIPLE
3 66
EN
EN
LK
02/03/25 INDIANA DUNES NATIONAL PARK (INDU)
MULTIPLEG0.2
CHICAGO, IL
IMEG
CHICAGO, IL
BAILEY EDWARD
REPLACE FIRE AND INTRUSION ALARMS
GENERAL NOTES
GENERAL NOTES
ELECTRICAL ABBREVIATION KEY
AFF ABOVE FINISHED FLOOR
C CONDUIT (BRANCH CIRCUIT OR FEEDER CONTEXT)
CO CONDUIT AND BOX ROUGH-IN ONLY (ROUGH-IN ONLY)
EG EQUIPMENT GROUND
ABBR: DESCRIPTION:
EGC EQUIPMENT GROUNDING CONDUCTOR
AFG ABOVE FINISHED GRADE
EOL END OF LINE
BC BELOW COUNTER
ASR ARCHITECTURAL SURFACE RACEWAY
ABV ABOVE
AFC ABOVE FINISHED CEILING
EPO EMERGENCY POWER OFF
GFR GROUND FAULT REMOTE
HOA HAND/OFF/AUTO
ITR IT RACK MOUNTED RECEPTACLE
NC NORMALLY CLOSED
NEMA # NEMA RATING
NIC NOT IN CONTRACTED SCOPE
NO NORMALLY OPEN
ROOF EQUIPMENT LOCATED ON ROOF ABOVE
SM SURFACE MOUNTED
TYP TYPICAL
UG UNDERGROUND
UON UNLESS OTHERWISE NOTED
1. THE COMPLETE INSTALLATION SHALL BE IN ACCORDANCE WITH THE ADA STANDARDS FOR
ACCESSIBLE DESIGN. REFER TO THE ADA GUIDELINES FOR ALL CONFIGURATION DETAILS ON
THIS PAGE FOR ADDITIONAL INFORMATION.
2. CIRCUIT NUMBERS ARE SHOWN FOR CIRCUIT IDENTIFICATION. CIRCUITING SHALL AGREE
WITH NUMBERING ON THE PANEL PROVIDED. COMMON NEUTRALS MAY NOT BE USED FOR
BRANCH CIRCUITS. BALANCE THE LOAD ON PANEL AS EVENLY AS POSSIBLE BETWEEN EACH
PHASE.
3. ALL MATERIALS USED TO SEAL PENETRATIONS OF FIRE RATED WALLS AND FLOORS SHALL
BE TESTED AND CERTIFIED AS A SYSTEM PER ASTM E814 STANDARDS FOR FIRE TESTS OF
THROUGH-PENETRATION FIRESTOPS. REFER TO 27 05 03 AND 28 05 03 FOR ADDITIONAL
INFORMATION AND REQUIREMENTS SPECIFIC TO FIRESTOPPING.
4. MOUNT ALL FIRE ALARM PULL STATIONS AT +42" FROM FLOOR (CENTERLINE DIMENSION)
EXCEPT WHERE OTHERWISE NOTED.
5. INSTALL ALL WALL MOUNTED FIRE ALARM NOTIFICATION DEVICES AT 90" ABOVE FINISHED
FLOOR OR 6" BELOW THE CEILING, WHICHEVER IS LOWER, EXCEPT WHERE OTHERWISE
NOTED. HEIGHT SHALL BE MEASURED TO THE TOP OF THE DEVICE.
6. CONTRACTOR SHALL COORDINATE THE LOCATION OF ALL CEILING MOUNTED DEVICES AND
EQUIPMENT WITH LUMINAIRES, SPRINKLER, AND CEILING DIFFUSERS. CENTER ALL DEVICES
IN CEILING TILE PATTERN. SMOKE DETECTORS,CARBON MONOXIDE DETECTORS, AND
OCCUPANCY/VACANCY SENSORS SHALL BE LOCATED NO CLOSER THAN 3 FEET TO AN AIR
SUPPLY DIFFUSER OR RETURN GRILLE. CARBON MONOXIDE DETECTORS SHALL BE LOCATED
10 PLUS FT FROM FIRE PLACES, COOKING, AND SIMILAR FUEL-BURNING APPLIANCES.
7. ELECTRICAL AND TECHNOLOGY EQUIPMENT SHALL BE MOUNTED TO AVOID IMPEDANCE OF,
OPERATION OF, AND/OR ACCESS TO ELECTRICAL AND MECHANICAL EQUIPMENT. ALL
MOUNTING OF ELECTRICAL AND TELECOMMUNICATIONS EQUIPMENT, ON EQUIPMENT
SUPPLIED BY ANOTHER CONTRACTOR, SHALL BE APPROVED IN ADVANCE BY THE OTHER
CONTRACTOR.
8. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL OPENINGS REQUIRED IN WALLS. ALL
OPENINGS SHALL BE REPAIRED TO MATCH EXISTING AT THE EXPENSE OF THIS
CONTRACTOR. ALL CONDUITS THROUGH WALLS SHALL BE GROUTED OR SEALED INTO
OPENINGS.
9. CONTRACTOR IS RESPONSIBLE FOR DAMAGE CAUSED BY THEIR ACTIONS TO THE WALLS,
FLOORS, CEILINGS, AND ROOFS. THE CONTRACTOR WHOSE WORK CAUSES DAMAGE IS
RESPONSIBLE FOR PATCHING TO MATCH ORIGINAL CONSTRUCTION, FIRE RATING, AND
FINISH.
10. REFER TO ARCHITECTURAL REFLECTED CEILING PLAN, TECHNOLOGY AUDIO/VISUAL, AND
OTHER ELECTRICAL PLANS FOR EXACT LOCATIONS OF ALL CEILING MOUNTED DEVICES
ELECTRICAL INSTALLATION NOTES:
1. EXISTING CONDITIONS ARE SHOWN BASED ON INFORMATION OBTAINED FROM FIELD
SURVEYS, EXISTING BUILDING DOCUMENTS. CONTRACTOR SHALL REVIEW EXISTING
CONDITIONS AND REPORT CONFLICTS.
2. NOT ALL EXISTING EQUIPMENT, LUMINAIRES, AND CONDUIT ARE SHOWN. CONTRACTOR
SHALL REVIEW EXISTING CONDITIONS AND REPORT CONFLICTS.
3. CONTRACTOR SHALL REVIEW EXISTING CONDITIONS PRIOR TO FABRICATION OF CABLE
TRAY, CONDUIT RACKS, AND OTHER SYSTEMS. RISES AND DROPS MAY BE NECESSARY
BECAUSE OF EXISTING FIELD CONDITIONS.
4. ELECTRICAL CONTRACTOR SHALL REVIEW EXISTING CONDITIONS TO VERIFY ACCESSIBILITY
TO THE AREAS OF THEIR WORK INCLUDING WALLS, FLOOR, CEILINGS, CEILING TILES/GRID,
AND ROOF. ELECTRICAL CONTRACTOR IS RESPONSIBLE TO PROVIDE CUTTING, REMOVAL,
PATCHING, AND REINSTALLATION OF AFFECTED AREAS ASSOCIATED WITH THEIR WORK BY
COORDINATING WITH THE GENERAL CONTRACTOR OR QUALIFIED CONTRACTOR.
5. WHERE EXISTING ELECTRICAL SYSTEMS ARE LOCATED IN AREAS THAT CONFLICT WITH NEW
EQUIPMENT, PIPING, OR DUCTWORK TO BE INSTALLED, EACH CONTRACTOR SHALL EITHER
ARRANGE NEW EQUIPMENT, CONDUIT, OR DUCTWORK IN SUCH A FASHION THAT IT DOES
NOT CONFLICT WITH EXISTING SYSTEMS, OR REWORK EXISTING ELECTRICAL SYSTEMS TO
ALLOW FOR INSTALLATION OF NEW EQUIPMENT, PIPING, OR DUCTWORK.
ELECTRICAL RENOVATION NOTES:
THESE NOTES APPLY TO ALL ELECTRICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED
TO, FIRE ALARM, AND OTHER LOW VOLTAGE SYSTEMS.
PLAN OR DETAIL NUMBER
PLAN OR DETAIL NAME
PLAN OR DETAIL SCALE
DETAIL REFERRED TO BY SECTION CUT
SHEET DETAIL IS LOCATED ON
NAME
VIEW NAME
1/8" = 1'-0"
M101
SIMSIM
INDICATES SIMILAR DETAIL REFERENCED
IN MULTIPLE LOCATIONS
LEVEL NAME
10'-0" HEIGHT ABOVE
PROJECT 0'-0"
1 KEYNOTE: INDICATES NOTE USED TO
DESCRIBE ADDITIONAL INFORMATION
ABOUT WORK REQUIRED, SPECIFIC
TO THE SHEET AND/OR DETAIL
N O R
HT
INDICATES DIRECTION OF TRUE NORTH
VIEW KEY
LINE TYPE AND TAG KEY:
NEW WORK BY THIS CONTRACTOR (WIDE LINE)
NEW
EXISTING TO BE REMOVED (SHORT DASHED PATTERN)
NEW UNDERFLOOR OR UNDERGROUND (LONG DASHED PATTERN)
EXISTING TO REMAIN OR WORK BY OTHERS (NARROW LINE)
EXISTING
EXISTING TO BE REMOVED BY OTHERS (SHORT DASHED PATTERN)
EXISTING UNDERFLOOR OR UNDERGROUND (LONG DASHED PATTERN)
HALFTONING DOES NOT MODIFY SCOPE.
'TAG'-E TAGS WITH DASH 'E' INDICATES THE REFERENCED OBJECT IS EXISTING
TAG-1 UNDERLINED TAG INDICATES OBJECT IS IN-SCOPE. IF NEW, ADDITIONAL
INFORMATION IS AVAILABLE IN A SCHEDULE, MATERIAL LIST, OR SYMBOL LIST
INDICATES AN EXISTING SYSTEM'S POINT OF CONNECTION/REMOVAL
T101
TEMPERATURE CONTROLS CONTRACTORT.C.C.
SECURITY CONTRACTORS.C.
AUDIO/VISUAL CONTRACTORA.V.C.
NURSE CALL CONTRACTORN.C.C.
CIVIL CONTRACTORC.C.
ASBESTOS ABATEMENT CONTRACTOR
FIRE PROTECTION CONTRACTORF.P.C.
HEATING CONTRACTORH.C.
PLUMBING CONTRACTORP.C.
GENERAL CONTRACTORG.C.
MECHANICAL CONTRACTORM.C.
VENTILATION CONTRACTORV.C.
ELECTRICAL CONTRACTORE.C.
A.C.
CONTRACTOR ABBREVIATION KEY
ABBR: DESCRIPTION:
TECHNOLOGY CONTRACTORT.C.
CONSTRUCTION MANAGERC.M.
FOOD SERVICE CONTRACTORF.S.C.
ELECTRICAL SYMBOL LIST
SYMBOL: TAG: SPEC
SECTION:
DESCRIPTION:
COMMON AND
SEQUENCE OF
OPERATION
SUBSCRIPTS
SUBSCRIPTS: TYPE / PROGRAMMING
WG = WIRE GUARD IS REQUIRED
W = WEATHERPROOF
A = ATRIUM
CA = CLEAN AGENT SYSTEM
CR = COMPUTER ROOM
E = ELEVATOR RECALL
D = HVAC CONTROL
DH = DOOR HOLD RELEASE
DIPS = DUAL INTERLOCK PREACTION SYS
FD = FIRE DOOR RELEASE
MP = MEDICAL PROCEDURE
S = SLEEPING / PATIENT ROOM
SW = STAIRWELL
# = 15, 30, 75, 110, 177 CANDELA RATING
CD = CANDELA RATING SELECTED BY NICET
DESIGNER
S
FA-120 28 31 00 FIRE ALARM SMOKE DETECTOR,
CEILING OR WALL MOUNT
BLANK - PHOTOELECTRIC
AT = ATTIC (LOCATED IN)
BR = BEAM RECEIVER
BT = BEAM TRANSMITTER
CO = COMBINATION SMOKE / CARBON
MONOXIDE
COH = COMBINATION SMOKE /
CARBON MONOXIDE / HEAT
COS = COMBINATION SMOKE /
CARBON MONOXIDE / STROBE
H = COMBINATION SMOKE / HEAT
DETECTOR
ION = IONIZATION TYPE
ID = IN DUCT DETECTOR
LF = LOW FREQUENCY
SA = STAND ALONE WITH SOUNDER
SB = SOUNDER BASE
SV = STAND ALONE WITH SOUNDER
AND 177 CANDELA STROBE
S
H
H
FA-140 28 31 00 FIRE ALARM HEAT DETECTOR
BLANK = COMBINATION RATE OF RISE
/ FIXED TEMP
AT = ATTIC (LOCATED IN)
F = FIXED TEMP
RC = RATE COMPENSATED
X - EXPLOSION PROOF
FA-130 28 31 00 FIRE ALARM MANUAL PULL STATIONF
F
F
FA-210 28 31 00 AUDIO HORN/CHIME ALARM DEVICE, CEILING
OR WALL MOUNTED
M = MINI-HORN
S = SLEEPING / PATIENT ROOM
FA-211 28 31 00 COMBINATION AUDIO HORN/CHIME AND
VISUAL ALARM DEVICE, CEILING OR WALL
MOUNTED
# = CANDELA RATING
CD = CANDELA RATING SELECTED BY NICET
DESIGNER
AN
DERSO RN
LLI
P R
O
FESS IONAL ENGIN
E E
R
WI
SNo.
PE11800750
ANAIDNI
D
ERETSI
G
E
R
STATE OF
DATE:
DESIGNED:
TECH. REVIEW:
SUB SHEET NO.
PMIS/PKG NO.
DRAWING NO.
SHEET
TITLE OF SHEETA/E FIRM
SUBCONTRACTOR
PRIME:
OF
BAILEY EDWARD
INDIANA DUNES NATIONAL PARK (INDU)
MULTIPLE
CHICAGO, IL
IMEG
CHICAGO, IL
REPLACE FIRE AND INTRUSION ALARMS
MULTIPLE
/3
/2
:0
:1
A
M
E0.0
ELECTRICAL COVER SHEET
BRIAN S.
ELI S.
MEGHAN M.
P ro je c t
N a m e P ro je c t
N u m b e r
402/03/25
DIGITAL
COMMUNICATOR
DEDICATED PHONE LINE
AND IP DATA LINE
J
NACCI
C I
C I
C I
C I
SIGNAL LINE CIRCUIT
(SLC)
NOTIFICATION APPLIANCE CIRCUIT (NAC)
EVACUATION - SIGNALING ZONE #
NOTIFICATION APPLIANCE CIRCUIT (NAC)
FACP-#
CIRCUIT INTEGRITY WIRING (TYP)
H
2 3
F
F
F
F
F
F
S
#F FT
MM
NOTES:
1. THE RISER DIAGRAM IS INTENDED TO CONVEY THE TYPES OF
FIRE ALARM CONNECTIONS AND SPECIFICALLY DOES NOT
INDICATE QUANTITIES, NUMBER OF CIRCUITS REQUIRED OR
DISTANCES.
2. THE COMPLETE FIRE ALARM SYSTEM SHALL MEET ALL
APPLICABLE CODES AND MANUFACTURER'S
RECOMMENDATIONS.
3. CONTRACTOR SHALL COORDINATE ALL WIRE SIZES, TYPES AND
REQUIREMENTS WITH THE VENDOR PRIOR TO BID. REFER TO
SPECIFICATIONS TO DETERMINE CIRCUIT STYLES AND IF
CONDUIT IS REQUIRED OR PLENUM RATED CABLE IS
ACCEPTABLE.
4. ALL +120VAC WIRING REQUIRED FOR OPERATION OF THE SYSTEM
AS DESCRIBED IN THE CONSTRUCTION DOCUMENTS SHALL BE
PROVIDED BY THE ELECTRICAL CONTRACTOR.
5. ALL NECESSARY RELAYS MAY NOT BE SHOWN ON THIS PLAN, BUT
WHERE REQUIRED FOR PROPER OPERATION OF THE SYSTEM
THEY SHALL BE PROVIDED BY THE CONTRACTOR.
6. PARTIAL EVACUATION OR RELOCATION OF OCCUPANTS IS THE
STANDARD OPERATING PROCEDURE FOR THIS FACILITY IN THE
EVENT OF AN ALARM. THEREFORE, ALL NOTIFICATION APPLIANCE
CIRCUITS MUST BE INSTALLED AND PROTECTED IN ACCORDANCE
WITH THE CIRCUIT SURVIVABILITY REQUIREMENTS DESCRIBED IN
NFPA 72. SEE SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.
7. BASIS OF DESIGN: NOTIFIER CLSS HORIZON PANEL.
KEYNOTES:
1. REFER TO SPECIFICATION FOR REQUIREMENTS OF EACH
INITIATION LOOP AND WIRING STYLE. REFER TO FLOOR PLANS
FOR DEVICES AND THEIR LOCATIONS.
2. REFER TO SPECIFICATION FOR REQUIREMENTS OF EACH
NOTIFICATION APPLIANCE CIRCUIT AND WIRING STYLE. REFER TO
FLOOR PLANS FOR DEVICES AND THEIR LOCATIONS.
3. PROVIDE NOTIFICATION APPLIANCE EXTENDER PANELS AS
REQUIRED. DETERMINATION OF NEED TO BE MADE BY FIRE
ALARM VENDOR. REFER TO SPECIFICATIONS FOR REQUIREMENTS
AND ACCEPTABLE MOUNTING LOCATIONS.
NO SCALE1
FIRE ALARM RISER
AN
DERSO RN
LLI
P R
O
FESS IONAL ENGIN
E E
R
WI
SNo.
PE11800750
ANAIDNI
D
ERETSI
G
E
R
STATE OF
DATE:
DESIGNED:
TECH. REVIEW:
SUB SHEET NO.
PMIS/PKG NO.
DRAWING NO.
SHEET
TITLE OF SHEETA/E FIRM
SUBCONTRACTOR
PRIME:
OF
BAILEY EDWARD
INDIANA DUNES NATIONAL PARK (INDU)
MULTIPLE
CHICAGO, IL
IMEG
CHICAGO, IL
REPLACE FIRE AND INTRUSION ALARMS
MULTIPLE
/3
/2
:0
:1
A
M
E0.1
ELECTRICAL DETAILS
BRIAN S.
ELI S.
MEGHAN M.
P ro je c t
N a m e P ro je c t
N u m b e r
502/03/25
TECHNOLOGY SYMBOL LIST
SYMBOL: DESCRIPTION: NOTE:
EQUIPMENT
LIST ABBREV.:
CONTROLLED SECURITY SCHEME SCHEDULE
IDENTIFIER
SECURITY DURESS BUTTON (WALL)AC-DB#-W .
N/A
1.SECURITY CREDENTIAL READER (WALL)AC-R#-WR#
CSS
B
K# SECURITY KEYPAD (WALL) .ID-KP#-W
READER WITH KEYPADAC-RK-W 1.RK
RK
DB#
SECURITY CREDENTIAL READER (WALL) -
EXISTING/DEMO
N/ARE
KE SECURITY KEYPAD (WALL) - EXISTING/DEMO .N/A
M
M
G .INTRUSION DETECTION GLASS BREAK (CEILING)ID-GB#-C
.INTRUSION DETECTION MOTION DETECTOR (WALL)ID-MD#-W
.INTRUSION DETECTION MOTION DETECTOR (CEILING)ID-MD#-C
A .INTRUSION DETECTION AUDIBLE ALARM (WALL)ID-AL#-W
D .INTRUSION DETECTION DOOR CONTACTID-DC#
AL#
DC#
GB#
MD#
MD#
TECHNOLOGY ABBREVIATION KEY
ABOVE FINISHED FLOORAFF
BELOW FINISHED CEILINGBFC
CONDUITC
SIMILARSIM
TYPICALTYP
MOUNTING HEIGHT ABOVE FINISHED FLOOR+#
JUNCTION BOXJ-BOX
ABBR: DESCRIPTION:
UNLESS OTHERWISE NOTEDUON
FIELD OF VIEWFOV
DOUBLE POLE DOUBLE THROWDPDT
PAN TILT ZOOMPTZ
POWER OVER ETHERNETPOE
ABOVE FINISHED GRADEAFG
DELAYED EGRESSDE
TECHNOLOGY GENERAL NOTES:
1. ##-###-# INDICATES TECHNOLOGY EQUIPMENT SCHEDULE ITEM LABELED AS "EQUIPMENT
LIST ABBREVIATION"
2. REFER TO TECHNOLOGY EQUIPMENT SCHEDULE AND SPECIFICATIONS FOR FULL
DESCRIPTIONS AND MANUFACTURERS OF ALL DEVICES.
A SLASH IS USED BETWEEN TWO SUBSCRIPTS, E.G., A/H.
1. THE COMPLETE INSTALLATION SHALL BE IN ACCORDANCE WITH THE ABA/ABAAS
STANDARDS FOR ACCESSIBLE DESIGN. REFER TO THE ADA GUIDELINES FOR ALL
CONFIGURATION DETAILS ON THIS PAGE FOR ADDITIONAL INFORMATION.
2. CONCEAL ALL CONDUIT IN WALLS, PARTITIONS, ABOVE CEILING, IN FLOOR SLAB, ETC.
UNLESS OTHERWISE INDICATED ON THE PLANS OR IN THE SPECIFICATIONS. CONDUIT IN
MECHANICAL ROOMS AND STORAGE ROOMS WITHOUT CEILINGS MAY BE EXPOSED ON
BUILDING STRUCTURE.
3. BOXES LOCATED ON OPPOSITE SIDES OF NON-RATED WALLS SHALL BE OFFSET A MINIMUM
OF 6" HORIZONTALLY. BOXES ON OPPOSITE SIDES OF FIRE RATED WALLS SHALL BE
OFFSET A MINIMUM OF 24" HORIZONTALLY. "THRU-THE-WALL" BOXES SHALL NOT BE
ALLOWED WITHOUT PRIOR WRITTEN APPROVAL OF THE ARCHITECT/ENGINEER.
4. SECURITY EQUIPMENT SHALL BE MOUNTED TO ALLOW ACCESS TO ELECTRICAL AND
MECHANICAL EQUIPMENT. ALL MOUNTING OF SECURTIY DEVICES ON EQUIPMENT SUPPLIED
BY ANOTHER CONTRACTOR SHALL BE APPROVED IN ADVANCE BY THE OTHER
CONTRACTOR.
5. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL OPENINGS REQUIRED IN WALLS. ALL
OPENINGS SHALL BE REPAIRED TO MATCH EXISTING BY A QUALIFIED CONTRACTOR AT THE
EXPENSE OF THIS CONTRACTOR. ALL CONDUITS THROUGH WALLS SHALL BE GROUTED OR
SEALED INTO OPENINGS.
6. ALL MATERIALS USED TO SEAL PENETRATIONS OF FIRE RATED WALLS AND FLOORS SHALL
BE TESTED AND CERTIFIED AS A SYSTEM PER ASTM E814 STANDARDS FOR FIRE TESTS OF
THROUGH-PENETRATION FIRESTOPS. REFER TO 28 05 03 AND 26 05 03 FOR ADDITIONAL
INFORMATION AND REQUIREMENTS SPECIFIC TO FIRESTOPPING.
7. THE SECURITY CONTRACTOR IS RESPONSIBLE FOR REMOVAL AND REPLACEMENT OF THE
CEILINGS, CEILING TILES, AND CEILING GRID ASSOCIATED WITH THE AREAS OF WORK BY
ALL CONTRACTORS. NOTIFY THE GENERAL CONTRACTOR OF AFFECTED AREAS PRIOR TO
BIDDING.
8. EACH CONTRACTOR IS RESPONSIBLE FOR DAMAGE CAUSED BY THEIR ACTIONS TO THE
WALLS, FLOORS, CEILINGS, AND ROOFS. THE CONTRACTOR WHOSE WORK CAUSES
DAMAGE IS RESPONSIBLE FOR PATCHING TO MATCH ORIGINAL CONSTRUCTION, FIRE
RATING, AND FINISH.
TECHNOLOGY INSTALLATION NOTES:
1. ALL SYMBOLS AND ABBREVIATIONS LISTED MAY NOT BE APPLICABLE TO THIS PROJECT.
REFER TO THE TECHNOLOGY EQUIPMENT SCHEDULE FOR MORE COMPLETE DESCRIPTION
AND ITEMS.
2. ALL SYMBOLS AND ABBREVIATIONS REFER TO TECHNOLOGY SHEETS ONLY AS DEFINED ON
THE SHEET INDEX. REFER TO THE GENERAL TECHNOLOGY NOTES FOR ADDITIONAL
INFORMATION.
3. ALL SYMBOLS LISTED ABOVE ARE FOR REFERENCE ONLY. REFER TO PLANS AND LINE TYPE
KEY FOR NEW, EXISTING TO REMAIN AND TO BE REMOVED ITEMS FOR ADDITIONAL
INFORMATION.
4. REFER TO RISER ON SHEET: T2.3.
CABLE TRAY, CHANNEL TRAY, BASKET
TRAY
LADDER RACK
WIDTH X HEIGHT
WIDTH X HEIGHT
DIAMETERø C CONDUIT
CONDUIT DOWN
CONDUIT UP OR UP/DOWN
CONDUIT SLEEVE
CONTINUATION
1. REFER TO CONTROLLED SECURITY SCHEME (CSS) TYPE SCHEDULE (ESS) ON T2.4 FOR
ADDITIONAL INFORMATION.
GENERAL NOTES:
TECHNOLOGY SYMBOL NOTES:
PLAN OR DETAIL NUMBER
PLAN OR DETAIL NAME
PLAN OR DETAIL SCALE
DETAIL REFERRED TO BY SECTION CUT
SHEET DETAIL IS LOCATED ON
NAME
VIEW NAME
1/8" = 1'-0"
M101
SIMSIM
INDICATES SIMILAR DETAIL REFERENCED
IN MULTIPLE LOCATIONS
LEVEL NAME
10'-0" HEIGHT ABOVE
PROJECT 0'-0"
1 KEYNOTE: INDICATES NOTE USED TO
DESCRIBE ADDITIONAL INFORMATION
ABOUT WORK REQUIRED, SPECIFIC
TO THE SHEET AND/OR DETAIL
N
O R HT
INDICATES DIRECTION OF TRUE NORTH
VIEW KEY
LINE TYPE AND TAG KEY:
NEW WORK BY THIS CONTRACTOR (WIDE LINE)
NEW
EXISTING TO BE REMOVED (SHORT DASHED PATTERN)
NEW UNDERFLOOR OR UNDERGROUND (LONG DASHED PATTERN)
EXISTING TO REMAIN OR WORK BY OTHERS (NARROW LINE)
EXISTING
EXISTING TO BE REMOVED BY OTHERS (SHORT DASHED PATTERN)
EXISTING UNDERFLOOR OR UNDERGROUND (LONG DASHED PATTERN)
HALFTONING DOES NOT MODIFY SCOPE.
'TAG'-E TAGS WITH DASH 'E' INDICATES THE REFERENCED OBJECT IS EXISTING
TAG-1 UNDERLINED TAG INDICATES OBJECT IS IN-SCOPE. IF NEW, ADDITIONAL
INFORMATION IS AVAILABLE IN A SCHEDULE, MATERIAL LIST, OR SYMBOL LIST
INDICATES AN EXISTING SYSTEM'S POINT OF CONNECTION/REMOVAL
T101
TEMPERATURE CONTROLS CONTRACTORT.C.C.
SECURITY CONTRACTORS.C.
AUDIO/VISUAL CONTRACTORA.V.C.
NURSE CALL CONTRACTORN.C.C.
CIVIL CONTRACTORC.C.
ASBESTOS ABATEMENT CONTRACTOR
FIRE PROTECTION CONTRACTORF.P.C.
HEATING CONTRACTORH.C.
PLUMBING CONTRACTORP.C.
GENERAL CONTRACTORG.C.
MECHANICAL CONTRACTORM.C.
VENTILATION CONTRACTORV.C.
ELECTRICAL CONTRACTORE.C.
A.C.
CONTRACTOR ABBREVIATION KEY
ABBR: DESCRIPTION:
TECHNOLOGY CONTRACTORT.C.
CONSTRUCTION MANAGERC.M.
FOOD SERVICE CONTRACTORF.S.C.
1. THE DRAWINGS INDICATE EXISTING ITEMS TO BE REMOVED. THE DRAWINGS ARE
INTENDED TO INDICATE THE SCOPE OF WORK REQUIRED AND DO NOT INDICATE EVERY
BOX, CONDUIT, OR WIRE THAT MUST BE REMOVED.
2. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE DISPOSAL OF MATERIAL THE
OWNER DOES NOT WANT TO REUSE OR RETAIN. (i.e., FOR MAINTENANCE PURPOSES).
3. EXISTING TO REMAIN DEVICES WITHIN OR ADJACENT TO THE PATH OF CONSTRUCTION
SHALL BE PROTECTED IN PLACE. DEVICES THAT MUST BE REMOVED SHALL BE TESTED
PRIOR TO REMOVAL, PROTECTED FROM DAMAGE, AND RE-INSTALLED IN ITS ORIGINAL
LOCATION DURING THE NEW CONSTRUCTION PHASE OF THE PROJECT.
4. OBTAIN APPROVAL FROM THE OWNER BEFORE TURNING OFF THE POWER TO
EQUIPMENT, SYSTEMS, PANELS, ETC. COORDINATE ALL OUTAGES WITH OWNER.
CONDUIT CONCEALED IN WALL CONSTRUCTION MAY BE ABANDONED IN PLACE IF NOT
AFFECTED BY OTHER CONSTRUCTION.
5. ALL CONDUIT SHALL BE REMOVED WHERE WALLS ARE BEING REMOVED. WHERE
CONDUIT IS IN THE CONCRETE SLAB, CUT OFF FLUSH, PULL OUT WIRE, AND PLUG.
WHERE CONDUIT IS RUN EXPOSED, ALL ASSOCIATED CLAMPS, SUPPORTS, HANGERS,
ETC., SHALL ALSO BE REMOVED.
6. COORDINATE ALL WORK WITH OTHER CONTRACTORS AT THE JOB SITE BEFORE
REMOVING EXISTING EQUIPMENT AND INSTALLING NEW ITEMS.
7. EXISTING CONDUIT IN GOOD CONDITION, MAY BE REUSED IN PLACE. RELOCATING
EXISTING CONDUIT SHALL NOT BE ALLOWED. BONDING CONDUCTORS SHALL BE
INSTALLED IN ALL REUSED CONDUIT TO ASSURE PROPER GROUND PATH.
8. EQUIPMENT REMOVAL IN CERTAIN LOCATIONS MAY REQUIRE THE INSTALLATION OF A
JUNCTION BOX TO RECONNECT CIRCUITS THAT REMAIN IN OPERATION. EXTEND
CONDUIT AND WIRING AS REQUIRED TO MAINTAIN POWER TO REMAINING EQUIPMENT.
9. DEVICES TO BE REMOVED SHALL HAVE ALL CONNECTED WIRING REMOVED TO THE
SOURCE.
10. DEVICES NOT TO BE REMOVED SHALL BE PROTECTED FROM THE ENVIRONMENT, AND
ALL ASSOCIATED CABLE/RACEWAYS ARE TO REMAIN AND BE PROTECTED. S.C. SHALL BE
RESPONSIBLE FOR REPAIR OF ANY INTERRUPTIONS TO PROTECTED DEVICES.
TECHNOLOGY DEMOLITION NOTES
M
A X
20" MAX.
M
A X
20"-25" MAX.
M
A X
M
IN
. 4
M
A X
M
A X
10" MAX. 10"-24" MAX.
ABA/ABAAS GUIDELINES - FRONT ACCESS
ABA/ABAAS STANDARDS FOR ACCESSIBLE DESIGN
INSTALL ABOVE COUNTER
DEVICE AT 44" ABOVE
FINISHED FLOOR.
INSTALL ABOVE COUNTER
DEVICE AT 40" ABOVE
FINISHED FLOOR.
INSTALL DEVICE AT 18"
ABOVE FINISHED FLOOR.
ABA/ABAAS GUIDELINES - SIDE ACCESS
INSTALL DEVICE AT 44"
ABOVE FINISHED FLOOR.
INSTALL DEVICE AT 42"
ABOVE FINISHED FLOOR.
AN
DERSO RN
LLI
P R
O
FESS IONAL ENGIN
E E
R
WI
SNo.
PE11800750
ANAIDNI
D
ERETSI
G
E
R
STATE OF
DATE:
DESIGNED:
TECH. REVIEW:
SUB SHEET NO.
PMIS/PKG NO.
DRAWING NO.
SHEET
TITLE OF SHEETA/E FIRM
SUBCONTRACTOR
PRIME:
OF
BAILEY EDWARD
INDIANA DUNES NATIONAL PARK (INDU)
MULTIPLE
CHICAGO, IL
IMEG
CHICAGO, IL
REPLACE FIRE AND INTRUSION ALARMS
MULTIPLE
/3
/2
:0
:1
A
M
T0.0
TECHNOLOGY COVER SHEET
PHIL N.
YASSINE D.
MEGHAN M.
P ro je c t
N a m e P ro je c t
N u m b e r
SUGGESTED MATRIX OF RESPONSIBILITY
ITEM: SHOWN ON:
FURNISHED
BY:
INSTALLED
BY: NOTES:
SECURITY ROUGH-IN, REFER TO
TECHNOLOGY EQUIPMENT SCHEDULE
AND SPECIFICATIONS FOR DEFINITION
T-SERIES E.C. E.C. 3. 4.
CONDUIT SLEEVES (WHEN SHOWN ON
DRAWINGS)
T-SERIES E.C. E.C.
CONDUIT SLEEVES (NOT SHOWN BUT
REQUIRED FOR PROPER INSTALLATION
OF SYSTEM)
N/A S.C. S.C. 2. 4.
SECURITY SYSTEMS ROUGH-IN T-SERIES S.C. S.C. 1.
SECURITY EQUIPMENT, CABLING, AND
TERMINATIONS
T-SERIES S.C. S.C.
GROUNDING LUGS ON SECURITY
EQUIPMENT
T-SERIES S.C. E.C. 6.
LINE VOLTAGE POWER (+120V OR
GREATER)
E-SERIES E.C. E.C.
LINE VOLTAGE POWER (NOT SHOWN
BUT REQUIRED FOR PROPER
INSTALLATION OF SYSTEM)
N/A S.C. E.C. 2. 4.
LINE VOLTAGE POWER FOR DOOR
HARDWARE POWER SUPPLIES
ARCH SPEC E.C. E.C.
LOW VOLTAGE CABLING FOR SECURITY
SYSTEMS
T-SERIES S.C. S.C.
CABLE HANGERS AND SUPPORTS OR
OTHER CABLE ROUTING METHODS
(OTHER THAN CONDUIT AND CABLE
TRAY)
T-SERIES S.C. S.C. 5.
SUGGESTED MATRIX OF RESPONSIBILITY NOTES
1. LOCATIONS OF SECURITY ROUGH-INS SHALL BE INDICATED BY THE INFORMATION OUTLET
SYMBOLS ON THE DRAWINGS. REFER TO THE TECHNOLOGY SYMBOL LIST FOR ADDITIONAL
INFORMATION.
2. BASED ON THE INHERENT DIFFERENCES IN PRODUCTS FROM VARIOUS MANUFACTURERS, ALL
REQUIRED EQUIPMENT MAY NOT BE SHOWN ON THE DRAWINGS FOR ALL ACCEPTABLE
MANUFACTURERS.
3. INCLUDES BACKBOXES AND CONDUIT REQUIRED FOR THE SYSTEMS INSTALLATION. THE E.C.
SHALL BASE THE BID ON THE BASIS OF DESIGN SHOWN ON THE CONTRACT DOCUMENTS.
4. ALL CHANGES TO THE SLEEVES, BACKBOXES, CONDUITS, AND POWER REQUIRED BECAUSE OF
THE T.C.'S SELECTION OF AN ALTERNATE ACCEPTABLE MANUFACTURER OR FROM SYSTEM
CONFIGURATIONS THAT ARE LEFT TO THE CHOICE OF THE CONTRACTOR SHALL BE INCLUDED
IN THE S.C.'S BID. THIS BID SHALL INCLUDE INSTALLATION BY A LICENSED ELECTRICIAN.
5. UNLESS TRADE RULES DICTATE OTHERWISE.
6. FURNISHED AS PART OF THE EQUIPMENT WHEN POSSIBLE, OR FURNISHED TO THE E.C. FOR
INSTALLATION IN THE FIELD.
602/03/25
PORTAGE LAKEFRONT
PAVILION
100 RIVERWALK DR
PORTAGE, IN 46368
R I V
E R
W A
L K
D
R
PORTAGE DUNE
CONTRACTOR STAGING AND
PARKING LIMITED TO THIS
AREA. APPROXIMATELY 4
PARKING SPACES (720SF).
BUILDING ENTRANCE
SITE PLAN LEGEND - LOGISTIC PLAN
PROPOSED CONTRACTOR STAGING
DATE:
DESIGNED:
TECH. REVIEW:
SUB SHEET NO.
PMIS/PKG NO.
DRAWING NO.
SHEET
TITLE OF SHEETA/E FIRM
SUBCONTRACTOR
PRIME:
LOGISTIC PLAN
80055
7 66
EN
WZ, LP
LK
02/03/25 INDIANA DUNES NATIONAL PARK (INDU)
325487C1.1
CHICAGO, IL
IMEG
CHICAGO, IL
BAILEY EDWARD
REPLACE FIRE AND INTRUSION ALARMS
PORTAGE LAKEFRONT PAVILION
SCALE: 1/64" = 1'-0"
0 32' 64' 128'
GENERAL SITE NOTES
1. GENERAL CONTRACTOR TO COORDINATE WORK
SCHEDULE WITH PARK STAFF TO MINIMIZE
DISRUPTION DURING PEAK VISITOR SEASON.
2. GENERAL CONTRACTOR SHALL REPAIR ALL EXISTING
LAWN AREAS, LANDSCAPE MATERIALS, CURBS AND
PAVING, WALKS, AND OTHER SITE ITEMS, CUT OR
DAMAGED DURING CONSTRUCTION OPERATIONS.
3. CONTRACTOR TO DETERMINE APPROPRIATE SECURE
STORAGE METHODS FOR EACH SITE AND MUST
IDENTIFY FENCING, LOCKING MECHANISM, SIGNAGE,
AND CONES AS NEEDED. STORAGE METHODS WILL BE
SUBJECT TO CO/COR APPROVAL.
4. DO NOT BEGIN DEMOLITION OPERATIONS UNTIL
MATERIALS TO IMMEDIATELY BEGIN RECONSTRUCTION
ARE ON SITE.
5. CONTRACTOR TO SUBMIT STAGING AND STORAGE PLAN
FOR CO/COR APPROVAL.
SITE ACCESS AND PROTECTION NOTES
1. DELIVERIES
A. DO NOT BLOCK DRIVEWAYS OR PATHS FOR
DELIVERIES
B. MAY USE PARK DRIVE FOR DELIVERIES.
2. CONTRACTOR PARKING
A. DO NOT DRIVE ON GRASS
B. DO NOT PARK ON THE GRASS OR UNDER THE
DRIP ZONES OF TREES.
C. NO DOUBLE PARKING OR OVERTAKING.
COORDINATE VEHICLE PARKING PATTERNS.
D. KEEP PATHS OPEN FOR BIKES AND STROLLERS
3' MIN.
E. VEHICLES MAY ONLY BE TWO AXLES
F. CONTRACTOR TO OBTAIN PARKING / ACCESS
PERMITS FROM PARK.
3. CONTRACTOR TO PROTECT AND MAINTAIN ACCESS
TO BUILDINGS AT ALL TIMES.
4. DESIGNATED STAGING AREA. CO/COR WILL REVIEW
AND APPROVE CONTRACTOR STORAGE PLANS.
REFER TO SPECIFICATION SECTION 01 10 00 3.4.
5. CO/COR WILL APPROVE CONTRACTOR SIGNAGE FOR
BUILDING. PARK WILL PROVIDE GATE CLOSURES
WHEN NEEDED.
A. TEMPORARY SIGNAGE TO BE COORDINATED
WITH SITE SUPERVISOR.
B. WHEN TEMPORARY SIGNS ARE NOT INDICATED
TO BE MOUNTED ON FENCING OR TEMPORARY
PARTITIONS, SIGNS MUST HAVE SELF
SUPPORTING PORTABLE STANDS THAT DO NOT
DAMAGE THE EXISTING FABRIC OF THE
BUILDING AND MUST NOT PRESENT A HAZARD
TO THE PUBLIC.
C. TEMPORARY SIGNS MUST BE MAINTAINED AND
LEGIBLE DURING THE ENTIRE DURATION OF THE
WORK.
N
O
R
H
T
1/64" = 1'-0"
PORTAGE LAKEFRONT PAVILION - LOGISTIC PLAN
EXP: 12/31/25
BASE BID
100 100 B
100 A
107A
102A
001A
MEETING/CLASSROOM
STORAGE
GALLERY
STORAGE
CONCESSION
COATS
ALCOVE
STORAGE
WOMEN
COURT
TRASH
RECYCLE
COVERED DECK
FIRE
EQUIPMENT
ALCOVE
MEN MECH
B
A
R28641R1 2 5 73
F T
F T
FT
F T
F T
S
F
F
S
F 7
F
S S
H
S
S
S
H H
S
S
S
S S
S
F 1
F 1
FT
100 100 B
100 A
107A
102A
001A
MEETING/CLASSROOM
STORAGE
GALLERY
STORAGE
CONCESSION
COATS
ALCOVE
STORAGE
WOMEN
COURT
TRASH
RECYCLE
COVERED DECK
FIRE
EQUIPMENT
ALCOVE
MEN MECH
B
A
R28641R1 2 5 73
F F
FT
FT
F F
S
S
F
F
S
S
F
F
S S
S
S
S
H H
H
FAA PANEL
FACP
EXISTING PANEL.
FACP PANEL
FA PANEL
AN
DERSO RN
LLI
P R
O
FESS IONAL ENGIN
E E
R
WI
S
No.
PE11800750
ANAIDNI
D
ERETSI
G
E
R
STATE OF
DATE:
DESIGNED:
TECH. REVIEW:
SUB SHEET NO.
PMIS/PKG NO.
DRAWING NO.
SHEET
TITLE OF SHEETA/E FIRM
SUBCONTRACTOR
PRIME:
OF
BAILEY EDWARD
INDIANA DUNES NATIONAL PARK (INDU)CHICAGO, IL
IMEG
CHICAGO, IL
REPLACE FIRE AND INTRUSION ALARMS
325487
80055
/3
/2
:1
:2
A
M
E1.1
ELECTRICAL SYSTEMS
BRIAN S.
ELI S.
MEGHAN M.
P ro je c t
N a m e P ro je c t
N u m b e r N
O R
HT
1/8" = 1'-0"2
PORTAGE LAKEFRONT PAVILION FLOOR PLAN - ELECTRICAL SYSTEMS
N O R
HT
1/8" = 1'-0"1
PORTAGE LAKEFRONT PAVILION DEMOLITION PLAN - ELECTRICAL SYSTEMS
SHEET NOTE:
1. ELECTRICAL CONTRACTOR SHALL
REUSE ELECTRICAL CIRCUIT
SERVING EXISTING FIRE ALARM
PANEL AND REUSE, EXTEND AND,IF
NEEDED, MATCH EXISTING
CONDITIONS OF ALL CONDUIT AND
WIRING TO NEW FIRE ALARM
PANEL.
2. IN CASE OF EMERGENCY, FIRE
ALARM CONTROL PANEL SHALL
REPORT BACK TO PARK'S
HEADQUARTERS. ELECTRICAL
CONTRACTOR SHALL VISIT
PROJECT SITE TO DETERMINE
DISTANCES PRIOR TO BID. BASIS
OF DESIGN: NOTIFIER CLSS
HORIZON PANEL.
3. PROVIDE DEDICATED 20A/120V
CIRCUIT TO NEW ACCESS
CONTROL PANEL AND INTRUSION
PANEL.REFER TO "T" DRAWINDS
FOR LOCATION OF PANELS
ELECTRICAL CONTRACTOR SHALL
PROVIDE CIRCUIT WITH 2#12 AND 1
#12GND WITHIN 3/4" CONDUIT.
4. FIRE ALARM PANEL, ACCESS
CONTROL PANEL AND INTRUSION
DETECTION PANEL SHALL BE
PROVIDED WITH SEPARATE 20A
CIRCUITS
5. NEW DEVICES SHALL BE
INSTALLED FLUSH IN EXISTING
WALL WITH CONDUIT CONCEALED.
CUT, PATCH, AND REPAIR WALL AS
REQUIRED TO MATCH ADJACENT
CONDITIONS.
PORTAGE LAKEFRONT PAVILION
FIRST FLOOR PLAN
KEYNOTES:
1. ELECTRICIAN SHALL FIELD
COORDINATE PANEL LOCATION.
02/03/25
100 100 B
100 A
107A
102A
001A
MEETING/CLASSROOM
STORAGE
GALLERY
STORAGE
CONCESSION
COATS
ALCOVE
STORAGE
WOMEN
COURT
TRASH
RECYCLE
COVERED DECK
FIRE
EQUIPMENT
ALCOVE
MEN MECH
B
A
R28641R1 2 5 73
M
D D
D D
D D
K
D C
S S
C S
S
D D
M
A
G G
GG
M
G
G
M
A
C S
S
CSS
C S
S
CSSCSS
CSS D
100 100 B
100 A
107A
102A
001A
MEETING/CLASSROOM
STORAGE
GALLERY
STORAGE
CONCESSION
COATS
ALCOVE
STORAGE
WOMEN
COURT
TRASH
RECYCLE
COVERED DECK
FIRE
EQUIPMENT
ALCOVE
MEN MECH
B
A
R28641R1 2 5 73
R E
R E
KE
ID-CP
DC1
DC1
22 23
DC1 DC1
DC1 DC1
15 16
AC-SCP-1
EXISTING
NETWORK SWITCH
DC1
DC1
DC1
GB1
GB1
GB1
GB1
MD1
GB1
GB1
MD1
AL1
R K
RK
R K
RK
R K
R K
+96"
+54"
+48"
+48"
RK
AN
DERSO RN
LLI
P R
O
FESS IONAL ENGIN
E E
R
WI
S
No.
PE11800750
ANAIDNI
D
ERETSI
G
E
R
STATE OF
DATE:
DESIGNED:
TECH. REVIEW:
SUB SHEET NO.
PMIS/PKG NO.
DRAWING NO.
SHEET
TITLE OF SHEETA/E FIRM
SUBCONTRACTOR
PRIME:
OF
BAILEY EDWARD
INDIANA DUNES NATIONAL PARK (INDU)CHICAGO, IL
IMEG
CHICAGO, IL
REPLACE FIRE AND INTRUSION ALARMS
325487
80055
/3
/2
:1
:2
A
M
T1.1
TECHNOLOGY
PHIL N.
YASSINE D.
MEGHAN M.
P ro je c t
N a m e P ro je c t
N u m b e r
N O R
HT
1/8" = 1'-0"2
PORTAGE LAKEFRONT PAVILION FLOOR PLAN - TECHNOLOGY
N O R
HT
1/8" = 1'-0"1
PORTAGE LAKEFRONT PAVILION DEMOLITION PLAN - TECHNOLOGY
PORTAGE LAKEFRONT PAVILION
FIRST FLOOR PLAN
BASE SCOPE:
BASE SCOPE SHALL BE
INTRUSION DETECTION SYSTEM
ONLY. REFER TO SYMBOLS LIST
FOR ADDITIONAL INFORMATION.
BID OPTION
PROVIDE BID OPTION COST TO
INCLUDE ACCESS CONTROL
SCOPE.
3:
BUILDING ENTRANCE
SITE PLAN LEGEND - LOGISTIC PLAN
PROPOSED CONTRACTOR STAGING
COWLES LODGE
700 HOWE RD
PORTER, IN 46304
STORAGE
STUDENT CABINS (10)
CONTRACTOR STAGING LIMITED TO THIS AREA.
APPROXIMATELY 4 PARKING SPACES (720SF).
TO HOWE RD
ELECTRIC LINE
SITE PLAN LEGEND - UTILITY PLAN
E
GAS LINEG
SEWER LINESS
DATA LINETV
WATER LINEW
FIRE HYDRANT
MANHOLE
FIRE DEPT CONECTION
GAS METER
SHUT-OFF VALVE
ELEVATED POLE LIGHT
DATE:
DESIGNED:
TECH. REVIEW:
SUB SHEET NO.
PMIS/PKG NO.
DRAWING NO.
SHEET
TITLE OF SHEETA/E FIRM
SUBCONTRACTOR
PRIME:
LOGISTIC PLAN
80055
10 66
EN
WZ, LP
LK
02/03/25 INDIANA DUNES NATIONAL PARK (INDU)
325487C2.0
CHICAGO, IL
IMEG
CHICAGO, IL
BAILEY EDWARD
REPLACE FIRE AND INTRUSION ALARMS
DUNES LEARNING CENTER
GENERAL SITE NOTES
1. GENERAL CONTRACTOR TO COORDINATE WORK
SCHEDULE WITH PARK STAFF TO MINIMIZE
DISRUPTION DURING PEAK VISITOR SEASON.
2. GENERAL CONTRACTOR SHALL REPAIR ALL EXISTING
LAWN AREAS, LANDSCAPE MATERIALS, CURBS AND
PAVING, WALKS, AND OTHER SITE ITEMS, CUT OR
DAMAGED DURING CONSTRUCTION OPERATIONS.
3. CONTRACTOR TO DETERMINE APPROPRIATE SECURE
STORAGE METHODS FOR EACH SITE AND MUST
IDENTIFY FENCING, LOCKING MECHANISM, SIGNAGE,
AND CONES AS NEEDED. STORAGE METHODS WILL BE
SUBJECT TO CO/COR APPROVAL.
4. DO NOT BEGIN DEMOLITION OPERATIONS UNTIL
MATERIALS TO IMMEDIATELY BEGIN RECONSTRUCTION
ARE ON SITE.
5. CONTRACTOR TO SUBMIT STAGING AND STORAGE PLAN
FOR CO/COR APPROVAL.
SITE ACCESS AND PROTECTION NOTES
1. DELIVERIES
A. DO NOT BLOCK DRIVEWAYS OR PATHS FOR
DELIVERIES
B. MAY USE PARK DRIVE FOR DELIVERIES.
2. CONTRACTOR PARKING
A. DO NOT DRIVE ON GRASS
B. DO NOT PARK ON THE GRASS OR UNDER THE
DRIP ZONES OF TREES.
C. NO DOUBLE PARKING OR OVERTAKING.
COORDINATE VEHICLE PARKING PATTERNS.
D. KEEP PATHS OPEN FOR BIKES AND STROLLERS
3' MIN.
E. VEHICLES MAY ONLY BE TWO AXLES
F. CONTRACTOR TO OBTAIN PARKING / ACCESS
PERMITS FROM PARK.
3. CONTRACTOR TO PROTECT AND MAINTAIN ACCESS
TO BUILDINGS AT ALL TIMES.
4. DESIGNATED STAGING AREA. CO/COR WILL REVIEW
AND APPROVE CONTRACTOR STORAGE PLANS.
REFER TO SPECIFICATION SECTION 01 10 00 3.4.
5. CO/COR WILL APPROVE CONTRACTOR SIGNAGE FOR
BUILDING. PARK WILL PROVIDE GATE CLOSURES
WHEN NEEDED.
A. TEMPORARY SIGNAGE TO BE COORDINATED
WITH SITE SUPERVISOR.
B. WHEN TEMPORARY SIGNS ARE NOT INDICATED
TO BE MOUNTED ON FENCING OR TEMPORARY
PARTITIONS, SIGNS MUST HAVE SELF
SUPPORTING PORTABLE STANDS THAT DO NOT
DAMAGE THE EXISTING FABRIC OF THE
BUILDING AND MUST NOT PRESENT A HAZARD
TO THE PUBLIC.
C. TEMPORARY SIGNS MUST BE MAINTAINED AND
LEGIBLE DURING THE ENTIRE DURATION OF THE
WORK.
SCALE: 1/64" = 1'-0"
0 32' 64' 128'
N O R HT
1/64" = 1'-0"1 DUNES LEARNING CENTER - LOGISTIC PLAN
SCALE: 1/64" = 1'-0"
0 32' 64' 128'
N O R HT
1/64" = 1'-0"2 DUNES LEARNING CENTER - EXISTING UTILITIES
6. CONTRACTOR TO FIELD VERIFY ADEQUATE
THE PROJECT. CONTRACTOR TO CONDUCT TESTING OF
THE EXISTING PATHWAYS AND CABLING TO EACH CABIN,
AND REFER TO NPS FOR VIABLE REUSE.
UTILITIES FOR
NOTE: CONTRACTOR TO FIELD-VERIFY EXISTING UTILITIES
UTILITIES FOR
106 107 108 109
RESTROOM
MECH.
FIRST AID
DINING HALL
KITCHEN
MECH.
STOR.
STORAGE
STOR. RESTROOMOFFICEJANITOR
COVERED PORCH
MECH
S
SS
H
H H
F T
FT FT FT FT
F T
FTFTFT
S H
S
S
S
S
S
S H
S S
SS
S S
F
F
5 1
106 107 108 109
RESTROOM
MECH.
FIRST AID
DINING HALL
KITCHEN
MECH.
STOR.
STORAGE
STOR. RESTROOMOFFICEJANITOR
COVERED PORCH
MECH
S
SS
H
H H
H
F
F F F F
F
F
FFF
NAC PANEL
FACP
EXISTING PANEL.
FIRE + INTRUSION
PANEL
NAC PANEL
AN
DERSO RN
LLI
P R
O
FESS IONAL ENGIN
E E
R
WI
S
No.
PE11800750
ANAIDNI
D
ERETSI
G
E
R
STATE OF
DATE:
DESIGNED:
TECH. REVIEW:
SUB SHEET NO.
PMIS/PKG NO.
DRAWING NO.
SHEET
TITLE OF SHEETA/E FIRM
SUBCONTRACTOR
PRIME:
OF
BAILEY EDWARD
INDIANA DUNES NATIONAL PARK (INDU)CHICAGO, IL
IMEG
CHICAGO, IL
REPLACE FIRE AND INTRUSION ALARMS
325487
80055
/3
/2
:1
:2
A
M
E2.1
ELECTRICAL SYSTEMS
BRIAN S.
ELI S.
MEGHAN M.
P ro je c t
N a m e P ro je c t
N u m b e r
N O R
HT
1/8" = 1'-0"2
DUNES LEARNING CENTER
DINING HALL FLOOR PLAN -
ELECTRICAL SYSTEMS
N O R
HT
1/8" = 1'-0"1
DUNES LEARNING CENTER
DINING HALL DEMOLITION PLAN
- ELECTRICAL SYSTEMS
SHEET NOTES:
1. CONTRACTOR IS RESPONSIBLE FOR PATCHING ALL OPENING AND MATCH TO EXISTING
CONDITIONS.
2. EXISTING SYSTEM SHALL REMAIN OPERATIONAL DURING ALL NEW WORK.
3. ELECTRICAL CONTRACTOR SHALL REUSE ELECTRICAL CIRCUIT SERVING EXISTING FIRE ALARM
PANEL AND REUSE, EXTEND AND MATCH EXISTING CONDITIONS OF ALL CONDUITS AND WIRING TO
NEW FIRE ALARM PANEL.
4. ELECTRICAL CONTRACTOR SHALL TEST ALL EXISTING WIRING AND PATHWAYS TO EACH CABIN FROM THE MAIN BUILDING AND REPORT THE RESULTS AND THE VIABILITY OF REUSE FOR…
This is the start of the file's text. The full file is on GovTribe.