B08_Attachment_2_Drawings_Electrical.pdf
PDF 40 MB Posted
- Solicitation number
- 140P8525R0015
About this file
This file is a comprehensive set of electrical design drawings for the Lehman Caves Lighting, Electrical, and Telecommunications Upgrades project at Great Basin National Park in Nevada. The electrical drawings detail a complete renovation of the cave's lighting and electrical infrastructure, including new lighting fixtures, electrical panels, conduit routing, and technology systems across multiple cave areas such as the Entrance Tunnel, Gothic Palace, Trellis Room, Tom Tom Room, Lodge Room, Inscription Room, Rocky Road, Cypress Swamp, Grand Palace, and Exit Tunnel.
The project involves replacing existing electrical systems with new LED lighting fixtures, installing multiple switchbanks and electrical panels, routing new power and technology conduits, and implementing a low-voltage phone system. The design emphasizes minimal impact on the cave environment, with specific requirements for mounting fixtures, concealing wiring, and preserving the cave's natural features. Key components include stainless steel mounting hardware, NEMA 4X enclosures, surge protection devices, and specialized lighting designed to highlight cave formations while minimizing resource damage. The project is associated with Solicitation Number 140P8525R0015 and is being executed by the Department of the Interior National Park Service Northeast Region.
View the file
Other files
Show all 16
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
V.C. HQ.
ADMINISTRATIVE
AREA
GRANITE
PEAK
LINCOLN
PEAK
MT.
WASHINGTON
PYRAMID
PEAK
BAKER
PEAK
WHEELER
PEAK
BALD
MOUNTAIN
LEXINGTON CREEKNORTH FORK
SOUTH F
ORK
BIG WASH
NORTH FORK
SOUTH FORK
J O
H N
S W
A S
H
DEAD
LAKE
JOHNSON
LAKE
BAKER
LAKE
BAKER
CREEK
LEHMAN
CREEK
OSCEOLA
D
IT
C H
UPPER
LEHMAN
CREEK
WHEELER
PEAK
LOWER
LEHMAN
CREEK
LEHMAN
CAVES
BAKER CREEK
TERESA
LAKE
STELLA
LAKE
BUCK
MOUNTAIN
GLACIER
BROWN
LAKE
MILL
CREEK
STRAWBERRY
C R
E E
K
SPRING CREEK
SNAKE CREEK
SNAKE CREEK TO
LEXINGTON ARCH
HUMBOLDT
NATIONAL
FOREST
HUMBOLDT
NATIONAL
FOREST
HUMBOLDT
NATIONAL
FOREST
JEFF DAVIS
PEAK
D E
C A
T H
O N
C A
N Y
O N
SHINGLE CREEK
P
IN
E
CREEK
CREEK
RIDGE
10,842 FEET
BAKER
50 6
TO
ELY
TO
MILFORD,
UTAH
ALT
BAKER
WENDOVER
McGILLEUREKA
PRESTON
N E
V A
D A
U T
A H
ELKO
WELLS
N E
V A
D A
U T
A H
DELTA
TOOELE
MILFORD
CEDAR
CITY
GREAT BASIN
NATIONAL PARK
ELY
SALT
LAKE
CITY
PROVOGREAT
SALT
LAKE
DESERT
GREAT
SALT
LAKE
HQ.
V.C.
LEGEND
CREEK
VEHICLE DUMP STATION
INFORMATION CENTER
PARK HEADQUARTERS
CAMPGROUND
PICNIC AREA
RANGER STATION
VISITOR CENTER
UNPAVED ROAD
TRAIL
PAVED ROAD
STATE LINE
PARK BOUNDARY
BASIC DATA: BOUNDARY MAPS
NATIONAL PARK SERVICE
DENVER SERVICE CENTER
OF
SHEET
DEPARTMENT OF THE INTERIOR
UNITED STATES
STATEREGION COUNTY
LOCATION WITHIN PARK
NAME OF PARK
TITLE OF DRAWING DRAWING NO.
PMIS/PKG NO.
QUALITY DESIGN CERTIFICATION
Prepared in Accordance with design
Development (Title I)
Drawing No.
Variance from Design Delevlopment (Title I)
Approved by Superintendent on
Date
OR
Construction Drawing Not Preceded by
Design Delevlopment (Title I)
OR
Project Manager Date
InitialDateREVISIONSheetMark
LEHMAN CAVE
GREAT BASIN NATIONAL PARK
NEVADASOUTHWEST WHITE PINE
150220
349463
FINAL UPDATED CDs - DRAWINGS
ANDERSON HALLAS ARCHITECTS, PC
STRUCTURAL:
JVA, INCORPORATED
BOULDER, CO 80302
ARCHITECT:
ANDERSON
HALLAS, PC
GOLDEN, CO 80401
- 140P2019D0016
PMIS
ELECTRICAL:
AE DESIGN
DENVER, CO 80202
2022 PMIS/PKG. NO: 311595
FINAL UPDATED DRAWINGS 03/28/2025
3/
/2
:2 1:
A
M C
:\U se rs \a w al te r\
D oc um en ts \5
0.
N P
S G
R B
A L eh m an C av e
Li gh tin g_
C en tr al
_a w al te r3 G
2X 6.
rv t
NPS Lehman Cave
1 27
349463GREAT BASIN NATIONAL PARK
SHEET LIST
SEQUENCE
NUMBER
SHEET
NUMBER DESCRIPTION
1 0.00 COVER SHEET, SITE MAP, AND SHEET INDEX
2 E0.1 ELECTRICAL LEGEND & NOTES
3 E0.2 ELECTRICAL GROUNDING DETAILS
4 E0.3 CAVE OVERALL PLAN
E0.4 CONSTRUCTION LAY DOWN PLAN
6 E0.5 CAVE POWER CONDUIT ROUTING PLAN
7 E0.6 CAVE TECHNOLOGY CONDUIT ROUTING PLAN
8 E0.7 CONDUIT ROUTING PHOTOS
9 E1.0 ELECTRICAL PLAN - ENTRANCE TUNNEL
10 E1.1 ELECTRICAL PLAN - GOTHIC PALACE
11 E1.2 ELECTRICAL PLAN - TRELLIS ROOM
12 E1.3 ELECTRICAL PLAN - TOM TOM ROOM
13 E1.4 ELECTRICAL PLAN - LODGE ROOM
14 E1.5 ELECTRICAL PLAN - INSCRIPTION ROOM
15 E1.6 ELECTRICAL PLAN - ROCKY ROAD
16 E1.7 ELECTRICAL PLAN - CYPRESS SWAMP
17 E1.8 ELECTRICAL PLAN - GRAND PALACE
18 E1.9 ELECTRICAL PLAN - EXIT TUNNEL
19 E2.1 ELECTRICAL ONE-LINE DIAGRAMS
20 E2.2 LOW-VOLTAGE PHONE SYSTEM RISER DIAGRAM
21 E3.1 ELECTRICAL LIGHTING SCHEDULES
22 E3.2 ELECTRICAL PANEL SCHEDULES
23 E4.0 ELECTRICAL DETAILS
24 E4.1 SWITCHBANK DETAILS
25 S0.1 GENERAL NOTES
26 S1.0 FRAME LOCATION KEY
27 S1.1 UNISTRUT AND MOUNTING DETAILS03/28/2025
12/31/2026
MDC
D
TO
TC
J
M
T
SYSTEMS
DISTRIBUTION AND RACEWAY
LIGHTING FIXTURES
WIRING DEVICES
ABBREVIATIONS AND SYMBOLS
J
J
SR
x x x x x
A AMPERE(S)
AC ABOVE COUNTER
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AHJ AUTHORITY HAVING JURISDICTION
AIC AMPERES INTERRUPTING CAPACITY
BFE BASE FLOOD ELEVATION
BFF BELOW FINISHED FLOOR
C CONDUIT
CB CIRCUIT BREAKER
CT CURRENT TRANSFORMER
DISC DISCONNECT
DWG(S) DRAWING(S)
(E) EXISTING TO REMAIN
EC ELECTRICAL CONTRACTOR
EF EXHAUST FAN
(ER) EXISTING TO BE RELOCATED
EM EMERGENCY
EPO EMERGENCY POWER OFF
EWC ELECTRIC WATER COOLER
F FUSE
FLA FULL LOAD AMPS
GD GARBAGE DISPOSAL
G GROUND
GC GENERAL CONTRACTOR
GFI GROUND FAULT CIRCUIT INTERRUPTER
HP HORSEPOWER
IDF INTERMEDIATE DISTRIBUTION FACILITY
ISC SHORT CIRCUIT CURRENT
KVA KILOVOLT AMPERE(S)
KW KILOWATT(S)
LTG LIGHTING
MCA MINIMUM CIRCUIT AMPERE(S)
MCB MAIN CIRCUIT BREAKER
MDP MAIN DISTRIBUTION CENTER
MDF MAIN DISTRIBUTION FACILITY
MLO MAIN LUGS ONLY
MW MICROWAVE
NC NORMALLY CLOSED
NL NIGHT LIGHT - SEE GENERAL NOTES
NO NORMALLY OPEN
OAE OR APPROVED EQUAL
P POLE
PH PHASE
RCPT RECEPTACLE
REF REFRIGERATOR
(RL) RELOCATED
SPD SURGE PROTECTION DEVICE
UC UNDER COUNTER/CABINET
UG UNDERGROUND
UON UNLESS OTHERWISE NOTED
V VOLT(S)
W WATT(S) OR WIRE
WG WIRE GUARD
WP WEATHERPROOF
XFMR TRANSFORMER
MECHANICAL EQUIPMENT SCHEDULE NOTATION
DETAIL NOTE
DELTA REVISION NOTE
ELECTRICAL WIRE SIZE
MAIN DISTRIBUTION CENTER (MDC)
SURFACE MTD PANELBOARD
TRANSFORMER
CONDUIT CONCEALED IN FLOOR
OR UNDERGROUND
CONDUIT EXPOSED OR CONCEALED IN WALL
OR CEILING
RACEWAY UP
RACEWAY DOWN
CAPPED CONDUIT
CURRENT TRANSFORMER
CIRCUIT BREAKER SWITCH
FUSED SWITCH
GROUNDING ELECTRODE CONDUCTOR
METER
TTB, MDF OR IDF SYSTEM BACKBOARD
TELECOMMUNICATION OUTLET. PROVIDE DATA
(#D) AND VOICE (#V) DROPS AS INDICATED IN
TAG. PROVIDE CAT6A TERMINATED AT WALL
PLATE ON 8P8C JACK.
CLOSED CIRCUIT TELEVISION CAMERA
TRAIL LUMINAIRE
DUPLEX RECEPTACLE
FOUR PLEX RECEPTACLE
SPECIAL PURPOSE RECEPTACLE
FLOOR MOUNTED RECEPTACLE DUPLEX/QUAD
SURFACE RACEWAY
JUNCTION BOX
WALL MOUNTED J-BOX
FLOOR MOUNTED JUNCTION BOX
NON-FUSED DISCONNECT SWITCH
FUSED DISCONNECT SWITCH
TIME CLOCK
THERMAL OVERLOAD SWITCH
SINGLE POLE SWITCH
3-WAY SWITCH
4-WAY SWITCH
DIMMER SWITCH
S
S
S
S
S x LIGHTING CONTROL DEVICE SCHEDULE NOTATION
PANIC BUTTON
(R) EXISTING TO BE REMOVED
P
WAP WIRELESS ACCESS POINT. DEVICE BY C.O.
CONTRACTOR TO PROVIDE 1 CAT6A DROP
ABOVE/AT CLG.
MTTB MAIN TELEPHONE TERMINAL BOARD
CLG CEILING
#D/#V
FF FINISHED FLOOR
FEATURE LUMINAIRE
ax AIMING DETAIL NOTE
(R)T EXISTING TRAIL LIGHT TO BE REMOVED
(R)F EXISTING FEATURE LIGHT TO BE REMOVED
WALL-MOUNTED LUMINAIRE
SURFACE-MOUNTED LUMINAIRE
TITLE OF SHEETSUB SHEET NO.DESIGNED:
TECH REVIEW:
DATE:
DRAWING NO.
PMIS/PKG NO.
SHEET
OF3/
/2
:2 1:
A
M C
:\U se rs \a w al te r\
D oc um en ts \5
0.
N P
S G
R B
A L eh m an C av e
Li gh tin g_
C en tr al
_a w al te r3 G
2X 6.
rv t
E0.1
AE DESIGN
LEHMAN CAVE
GREAT BASIN NATIONAL PARK
150220
349463
AE DESIGN
MRS/JEB
03/28/2025 2 27
ELECTRICAL LEGEND
& NOTES
COVERSHEET NOTES
1 THE CONTRACTOR SHALL PROVIDE ALL LABOR AND MATERIAL NECESSARY FOR A COMPLETE AND
FUNCTIONING ELECTRICAL SYSTEM.
2 MATERIALS AND INSTALLATION SHALL COMPLY WITH CODES, LAWS AND ORDINANCES OF
FEDERAL, STATE AND LOCAL GOVERNING BODIES HAVING JURISDICTION.
3 MATERIALS AND EQUIPMENT SHALL BE LISTED AND/OR LABELED BY U.L., ETL, CSA OR ANOTHER
RECOGNIZED TESTING LAB.
4 ALL WORK REQUIRED FOR THE INSTALLATION AS SHOWN ON DRAWINGS INCLUDING LABOR,
EQUIPMENT AND MATERIALS SHALL BE IN STRICT COMPLIANCE WITH THE PROJECT STANDARDS, EXCEPT AS NOTED OTHERWISE.
5 THE CONTRACTOR SHALL SECURE AND PAY FOR ALL PERMITS, GOVERNMENTAL FEES, TAXES
AND LICENSES NECESSARY FOR THE PROPER EXECUTION AND COMPLETION OF THE ELECTRICAL
WORK.
6 THE CONTRACTOR SHALL PREPARE AND SUBMIT SHOP DRAWINGS TO GOVERNMENTAL AGENCIES
, WHICH ARE REQUIRED BY THESE AGENCIES, FOR THEIR APPROVAL.
7 INITIAL DEMOLITION WORK SHALL BE COMPLETED BY THE NATIONAL PARK SERVICE AHEAD OF
CONTRACTOR'S DEMOLITION SCOPE OF WORK. PARK SHALL PROVIDE FLAGGING/MARKING OF
INTENDED EXISTING LOCATIONS TO BE REUSED (IDENTIFIED AS EXISTING IN THESE DOCUMENTS)
AND ENTRY/EXIT LOCATIONS OR PULL STRINGS FOR RACEWAY TO BE REUSED. PARK SERVICE
SHALL REMOVE LOOSE-LAID ELECTRICAL CABLING WITHIN CAVE (APPROXIMATELY 80% OF
CABLING). CONTRACTOR SHALL OBSERVE PARK SERVICE DEMOLITION OF EXISTING WIRING
LOCATIONS. CONTRACTOR SHALL 'TRACE' EXISTING PATHWAY USING STRING TO TRACK
PATHWAY FOR FUTURE INSTALLATION OF NEW CABLING. ENCAPSULATED WIRING WITHIN CAVE
'GUNITE' PATHWAYS SHALL BE ABANDONED IN PLACE. ALL DEMOLITION WORK OUTSIDE OF THE
CAVE SHALL BE BY CONTRACTOR.
8 ALL MATERIALS, AND EQUIPMENT SHALL BE ERECTED, INSTALLED, CONNECTED, CLEANED,
ADJUSTED, TESTED, CONDITIONED, AND PLACED IN SERVICE IN ACCORDANCE WITH THE
MANUFACTURER'S DIRECTIONS AND RECOMMENDATIONS.
9 ALL CUTTING, DRILLING AND PATCHING OF MASONRY, STEEL OR IRON WORK BELONGING TO THE
CAVE SYSTEM MUST BE DONE BY THIS CONTRACTOR IN ORDER THAT HIS WORK MAY BE
PROPERLY INSTALLED, BUT UNDER NO CONDITIONS MAY STRUCTURAL WORK OR CAVE
RESOURCE BE CUT, EXCEPT AT THE DIRECTION OF THE CONTRACTING OFFICER. CONTRACTOR
SHALL INCLUDE 10% ADDITIONAL PATHWAY LENGTHS IN BID PRICING FOR BOTH TELECOM AND
POWER TO SUPPORT NECESSARY CONDUIT ROUTING ADJUSTMENTS DURING INSTALLATION.
10 ALL MATERIAL, EQUIPMENT, WIRING DEVICES, ETC. SHALL BE NEW, UNLESS SPECIFICALLY
INDICATED AS EXISTING TO BE REUSED.
11 THE CONTRACTOR SHALL PROVIDE NEW LAMINATED TYPE WRITTEN PANEL DIRECTORIES FOR
ALL PANELS. PANELBOARD SHALL BE MARKED WHERE THE SOURCE OF POWER SUPPLY
ORIGINATES, AND THEIR LISTED VOLTAGE AND AMPERE RATING.
12 DO NOT SHARE NEUTRAL CONDUCTORS FOR MULTIWIRE BRANCH CIRCUITS. WHERE THE EC
PROPOSES THE USE OF SHARED NEUTRAL CONDUCTORS OR SHARED NEUTRAL CONDUCTORS
REQUIRE THAT HANDLE TIES SHALL BE PROVIDED ON THE CIRCUIT BREAKERS, WITH SHARED
NEUTRALS, SUCH THAT IT WILL SIMULTANEOUSLY DISCONNECT ALL UNGROUNDED CONDUCTORS.
ALL HANDLE TIES ARE REQUIRED TO BE INDICATED ON THE PANELBOARD SHOP DRAWINGS.
13 SHOULD ACTUAL FIELD CONDITIONS REQUIRE INDICATED CIRCUIT DESIGNATIONS TO VARY, INDICATE THE CIRCUIT NUMBER USED ON THE "AS-BUILT" DRAWINGS.
14 ALL SERVICE EQUIPMENT SHALL BE LEGIBLY MARKED IN THE FIELD BY THE ELECTRICAL
CONTRACTOR WITH THE MAXIMUM AVAILABLE FAULT CURRENT AS INDICATED WITHIN THESE
DOCUMENTS. THE FIELD MARKING(S) SHALL COMPLY WITH ELECTRICAL SPECIFICATIONS FOR
READABILITY AND DURABILITY.
15 ALL NEW CIRCUITS SHALL HAVE A GROUND WIRE INSTALLED. IF ANY EXISTING CIRCUITS ARE
FOUND WITHOUT A GROUND WIRE, A NEW EQUIPMENT GROUND WIRE SHALL BE INSTALLED.
16 ALL EXPOSED CABLING SHALL BE CONCEALED TO THE GREATEST EXTENT POSSIBLE, AND SHALL BE INSTALLED PARALLEL TO EXISTING PATHWAYS. CONCEALMENT METHOD SHALL BE VIA GUNITE
MATERIAL OR NATURAL ROCKS AS CONSISTENT WITH CAVE CONDITIONS. FINAL ROUTING AND
CONCEALMENT METHODS SHALL BE CONFIRMED IN FIELD WITH CONTRACTING OFFICER.
17 THE POWER AND CONTROL REQUIREMENTS FOR ALL EQUIPMENT CONNECTIONS SHALL BE
CONFIRMED WITH APPROVED SHOP DRAWINGS PRIOR TO ELECTRICAL ROUGH-IN. FINAL POWER
REQUIREMENTS, DIMENSIONED ROUGH-IN LOCATIONS, LOW VOLTAGE SYSTEM CONNECTIONS,
ETC. SHALL BE CONFIRMED AND MODIFIED AS REQUIRED.
18 ALL EXISTING ELECTRICAL SERVICES NOT SPECIFICALLY INDICATED TO BE REMOVED OR
ALTERED SHALL REMAIN AS THEY PRESENTLY EXIST.
19 ALL EQUIPMENT SHALL BE LISTED AND LABELED FOR THE INTENDED USE.
20 ROUTING OF ALL NEW CONDUIT AND CABLING ALONG EXISTING SURFACES, WALLS, CEILINGS, STRUCTURES, ETC. SHALL BE COORDINATED AND APPROVED BY CONTRACTING OFFICER PRIOR
TO ROUGH-IN TO PRESERVE THE FABRIC AND FEATURES OF THE CAVE RESOURCE. WHERE
POSSIBLE, ALL ROUTING AND PATHWAYS SHALL BE ROUTED ALONG EXISTING PATHWAYS. ALL
FASTENERS AND ATTACHMENTS TO THE RESOURCE SMALL BE MINIMIZED TO THE EXTENT
POSSIBLE AND COORDINATE WITH THE CONTRACTING OFFICER PRIOR TO ANY CUTTING,
DRILLING, ADHESION, OR ATTACHMENT.
21 ALL NEW CIRCUITS AND MAJOR CABLING RUNS SHALL BE WELL DOCUMENTED WITHIN THE
AS-BUILT DOCUMENTATION CREATED BY THE CONTRACTOR. THIS SHALL INCLUDE PHOTO
DOCUMENTATION AND REDLINES OF CONSTRUCTION DOCUMENTS. CONCEALMENT METHODS
SHALL BE COORDINATED WITH THE CONTRACTING OFFICER ON A LOCATIONAL BASIS – MOST
LOCATIONS ARE ANTICIPATED TO BE DIRECT BURIAL SIMILAR TO EXISTING CONDITIONS WHERE
ROUTED ADJACENT TO PAVED PATH.
22 ALL CIRCUIT CONDUCTORS SHALL BE LABELED WITH TYPED ADHESIVE LABELS FOR FUTURE
REFERENCE. LABELS SHALL BE SUITABLE FOR USE IN HUMID AND CORROSIVE ENVIRONMENTS.
23 ALL EQUIPMENT SHALL BE RATED A MINIMUM OF NEMA 4X, STAINLESS STEEL OR PVC AS
INDICATED.
24 ELECTRICAL SYSTEM LAYOUTS INDICATED ON DRAWINGS ARE GENERALLY DIAGRAMMATIC BUT
SHALL BE FOLLOWED AS CLOSELY AS ACTUAL CONSTRUCTION AND WORK OF OTHER TRADES
WILL PERMIT. GOVERN EXACT ROUTING OF RACEWAYS AND LOCATIONS OF OUTLETS BY
STRUCTURE AND EQUIPMENT SERVED.
25 AVOID CUTTING AND BORING HOLES THROUGH CAVE WHEREVER POSSIBLE. OBTAIN PRIOR
APPROVAL OF CONTRACTING OFFICER WHEN CUTTING OR BORING IS NECESSARY AND
PERMITTED. EXISTING LOCATIONS, APPROVED FLOOR AREA LOCATION,STAIR STRUCTURES, OR
HANDRAILS SHALL BE USED OVER NEW LOCATIONS WHERE POSSIBLE.
26 ALL MATERIAL TO BE INSTALLED INSIDE THE CAVE SYSTEM SHALL REQUIRE APPROVAL FROM
CONTRACTING OFFICER PRIOR TO INSTALLATION.
27 CONTRACTORS WORKING WITHIN THE CAVE SYSTEM SHALL MAINTAIN A CLEAN ENVIRONMENT
DURING CONSTRUCTION TO PRESERVE THE MICROCLIMATES.
ELECTRICAL VARIANCE AND WAIVERS
1 CODE INTENT: NEC 300.50 - TO PROTECT THE CABLE FROM DAMAGE
UNDERGROUND DIRECT BURRIED 0-600B CONDUCTORS SHALL BE INSTALLED
WITH MINIMUM COVER OF 24 INCHES.
WAIVER: 120V AND 240V CABLES SHALL BE ROUTED ON THE FLOOR THROUGH
THE CAVE AND WILL NOT BE BURIED IN THE CAVE OR ATTACHED TO THE CAVE
TO LIMIT RESOURCE DAMAGE. REFER TO SPECIFICATIONS DOCUMENT FOR
MORE INFORMATION.
CODE INTENT: TO ENSURE THAT LUMINAIRES ARE SERVICEABLE AND DO NOT
FALL AND HARM THE PUBLIC, NEC 410.3
WAIVER: THE LIGHT FIXTURES WILL BE SECURED WITH NON-METALLIC
JUNCTION BOXES AT THE BASE, AND AFFIXED TO THE RESOURCE UTILIZING
EXISTING HOLES FOR FASTENERS/HARDWARE TO THE EXTENT POSSIBLE AT
APPROVED LOCATIONS TO LIMIT RESOURCE DAMAGE. REFER TO
SPECIFICATIONS FOR MORE INFORMATION.
3 CODE INTENT: NFPA 101 - TO PROVIDE EMERGENCY LIGHTING TO A MINIMUM OF
1.0 AVERAGE FOOT-CANDLES ALONG THE PATH OF EGRESS, AND NO LOWER
THAN 0.1 FOOT-CANDLES ALONG THE PATH OF EGRESS. PROVIDE ILLUMININATED
EXIT SIGNAGE TO MARK PATH OF EGRESS
WAIVER: PARK RANGERS ARE EQUIPPED WITH FLASH LIGHTS TO ASSIST IN THE
EVACUATION OF VISITORS OUT OF THE CAVE IN THE CASE OF A POWER FAILURE
OR EMERGENCY SITUATION. REFER TO SPECIFICATIONS DOCUMENT FOR MORE
INFORMATION.
4 CODE INTENT: NEC 250 REQUIRES GROUND RESISTANCE TO BE ON THE ORDER OF
5-25 OHMS, WITH ADDITIONAL GROUND RODS/PLATES INSTALLED IF THIS LEVEL OF
GROUNDING IS NOT ACHIEVED IN ORDER TO PROVIDE A PATH TO GROUND WITH THE
LOWEST RESISTANCE POSSIBLE TO PROVIDE A FAST RESPONSE TO THE
OVERCURRENT PROTECTIVE DEVICES.
WAIVER: DUE TO THE NATURE OF THE WAY THAT THE CAVE DEVELOPED, THE CAVE
FLOOR IS ESSENTIALLY RUBBLE WITH A HIGH RESISTANCE. AS A RESULT,
CONNECTING ELECTRICAL EQUIPMENT TO A GROUND OF ANY NATURE PLACED
WITHIN THE CAVE IS NOT VERY EFFECTIVE. IN ADDITION, STANDARD METHODS FOR
REDUCING GROUND RESISTANCE INCLUDE CHEMICAL GROUNDS, GROUND RODS, OR
OTHER METHODS THAT WOULD DAMAGE OR COMPROMISE THE CAVE RESOURCE OR
ENVIRONMENT. WHILE THE GROUND RESISTANCE MAY NOT MATCH THAT OF
STANDARD BUILDING CONSTRUCTION, THE GROUNDING SYSTEM PROVIDED WILL BE A
GREAT IMPROVEMENT OVER THE EXISTING GROUNDING SYSTEM.
5 CODE INTENT: NEC 110.13 REQUIRES ELECTRICAL EQUIPMENT TO BE FIRMLY
SECURED TO A SURFACE ON WHICH IT'S MOUNTED SUCH THAT IT IS SERVICEABLE
AND WILL NOT FALL AND HARM THE PUBLIC.
WAIVER: LIGHTING ENCLOSURES MAY BE PLACED OFF TRAIL AND EQUIPMENT WILL
BE LOCATED OFF TRAIL WHERE THE PUBLIC IS NOT PERMITTED AND THE STAFF IS
AWARE OF THE HAZARD, SIMILAR CONDITION TO THE EXISTING CONDITION. REFER TO
THE SPECIFICATIONS DOCUMENT FOR MORE INFORMATION.
6 CODE INTENT: THE INTENT OF NEC 300.5 AND 300.50 - UNDERGROUND RACEWAYS
SHALL BE BURIED TO A MINIMUM DEPTH TO PROVIDE SUFFICIENT PROTECTION TO
BURIED RACEWAYS.
WAIVER: THE EXISTING 120V CABLE CONDITION IS ROUTED ON THE SURFACE OF THE
CAVE FLOOR, OFF TRAIL WHERE THE PUBLIC IS NOT PERMITTED AND CAVE
PERSONNEL RECEIVES TRAINING ON WHERE THE CABLES ARE AND HOW TO
PROTECT THE CABLES WHEN OFF TRAIL. REFER TO SPECIFICATIONS DOCUMENT FOR
MORE INFORMATION.
7 CODE INTENT: THE INTENT OF NEC 720.11 - LOW VOLTAGE CABLING SHALL BE BURIED
TO A MINIMUM DEPTH TO PROVIDE SUFFICIENT PROTECTION TO BURIED CABLING.
WAIVER: THE EXISTING CABLING CONDITION IS ROUTED ON THE SURFACE OF THE
CAVE FLOOR, OFF TRAIL WHERE THE PUBLIC IS NOT PERMITTED AND CAVE
PERSONNEL RECEIVES TRAINING ON WHERE THE CABLES ARE AND HOW TO PROTECT
THE CABLES WHEN OFF TRAIL. REFER TO SPECIFICATIONS DOCUMENT FOR MORE
INFORMATION.
03/28/2025
GENERAL GROUNDING NOTES
A ALL CABLES TO BE TERMINATED ONTO BUS BAR WITH TWO
HOLE COMPRESSION LUGS AND ATTACHED TO BUS BAR WITH
TAB COMPRESSION BELLEVILLE WASHERS AND TORK BOLT
ASSEMBLY.
B ALL GROUND CONNECTORS SHALL BE SOLID.
C ALL BUS BARS SHALL BE ATTACHED TO SURFACE WITH NON-
CONDUCTIVE STAND-OFFS.
D GROUND BUS BAR AND GROUNDING SYSTEM SHALL BE UL
LISTED AND COMPLY WITH MANUFACTURERS INSTALLATION
INSTRUCTIONS.
E ALL ELECTRICALLY CONDUCTIVE MATERIALS AND EQUIPMENT
SHALL BE BONDED TO THE ELECTRICAL GROUND SYSTEM
WITH A COPPER #6 AWG MINIMUM, INCLUDING PANELBOARDS,
ENCLOSURES, MOUNTING SUPPORTS, WALKING BRIDGES,
STAIR STRUCTURES, HAND RAILS, ETC.
GROUNDING DETAIL NOTES
1 DEDICATED GROUND WIRE SHALL BE PROVIDED FOR EACH
LIGHTING CIRCUIT AND TERMINATE AT PANELBOARD GROUND
BUSSING.
TO NEXT
LIGHT FIXTURE
LIGHT FIXTURE
NOTE 2
2 AT EACH JUNCTION BOX, CIRCUIT GROUND WIRE SPLICES
SHALL BE MADE WITH HEAVY DUTY HEAT SHRINK 3-WAY TYPE
CONNECTORS. WIRE NUT CONNECTION OF GROUND WIRE IS
NOT PERMITTED.
JUNCTION BOX
NOTE 2
3 WHERE PRESENT, BOND ELECTRICALLY CONDUCTIVE
WALKING BRIDGES AND STAIR STRUCTURES TO LIGHTING
CIRCUIT EQUIPMENT GROUNDING CONDUCTOR PER NEC
250.4(A)(4).
NOTE 3
PRINCIPAL GROUND POINT (PGP)
CU GROUND BAR
INTERNAL TO PANEL
1#6,3/4"C
GROUND
ROD
(SEE NOTES)
NOTE 1
GROUND WIRE FOR
TYPICAL LIGHTING
BRANCH CIRCUIT
1#6,3/4"C
GROUND
PLATE
(SEE NOTES)
GROUNDING ELECTRODE SYSTEMS NOTES
C
D
EC SHALL UTILIZE GROUND ENCHACEMENT MATERIAL AS
PART OF GROUND ROD / PLATE BACKFILL.
A MINIMUM OF (2) GROUND RODS / PLATES SHALL BE
PROVIDED AND INSTALLED PER NEC SPACING AND
BONDING REQUIREMENTS. EC SHALL PERFORM
RESISTANCE TO EARTH TESTING TO VERIFY READING LESS
THAN 25 OHMS. EC SHALL NOTIFY CONTRACTING OFFICER
AND ENGINEER OF RECORD OF TEST RESULTS.
A GROUND ROD - ROD IS TO BE 8FT IN LENGTH AND SHALL
BE MADE OF IRON OR STEEL AT LEAST 5/8" DIAMETER.
INSTALLATION METHODS FOR GROUND ROD SHALL BE IN
COMPLIANCE WITH THE NEC SUCH THAT AT LEAST 8' OF
LENGTH IS IN CONTACT WITH THE EARTH.
B ALTERNATE: PROVIDE SEPARATE LINE ITEM PRICING FOR
INSTALLATION OF GROUND PLATE ELECTRODES.
INSTALLATION METHODS FOR GROUND PLATES SHALL BE
IN COMPLIANCE WITH NEC.
THIS SERVICE GROUNDING METHOD SHALL BE USED
INSTEAD OF GROUND RODS IN THE EVENT DRIVING
GROUND RODS INTO THE CAVE FLOOR IS NOT POSSIBLE.
TITLE OF SHEETSUB SHEET NO.DESIGNED:
TECH REVIEW:
DATE:
DRAWING NO.
PMIS/PKG NO.
SHEET
OF3/
/2
:2 1:
A
M C
:\U se rs \a w al te r\
D oc um en ts \5
0.
N P
S G
R B
A L eh m an C av e
Li gh tin g_
C en tr al
_a w al te r3 G
2X 6.
rv t
E0.2
AE DESIGN
LEHMAN CAVE
GREAT BASIN NATIONAL PARK
150220
349463
AE DESIGN
MRS/JEB
03/28/2025 3 27
ELECTRICAL
GROUNDING DETAILS
E0.2
1 ELECTRICAL GROUNDING DETAIL AND NOTES
ENTRANCE TUNNEL
EXIT TUNNEL
NATURAL ENTRANCEGOTHIC
PALACE
CIVIL DEFENSE
PASSAGE
TRELLIS
ROOM
MUSIC ROOM
TOM TOM ROOM
LODGE ROOM
CRYSTAL
PALACE
INSCRIPTION
ROOM
ROCKY ROAD
WEST ROOM
VISITOR CENTER
(E) PROPANE TANK
(N) DISC.
& SUB-METER
(E) SERVICE
TRANSFORMER
(E) CT/METER
& TRANSFORMER
LAKE
ROOM
CYPRESS
SWAMP
GRAND
PALACE
SUNKEN
GARDENS
ROYAL
GORGE
E1.0 E1.1
E1.2
E1.3
E1.4
E1.5
E1.6
E1.7
E1.8
E1.9
APPROXIMATE LOCATION OF
TELECOM CLOSET
'GIANTS
EAR'
'CIVIL
DEFENSE'
'LAKE
ROOM'
(E) VISITOR CENTER
DISTRIBUTION
(E) GENERATOR
M
S1
S2
TITLE OF SHEETSUB SHEET NO.DESIGNED:
TECH REVIEW:
DATE:
DRAWING NO.
PMIS/PKG NO.
SHEET
OF3/
/2
:2 1:
A
M C
:\U se rs \a w al te r\
D oc um en ts \5
0.
N P
S G
R B
A L eh m an C av e
Li gh tin g_
C en tr al
_a w al te r3 G
2X 6.
rv t
E0.3
AE DESIGN
LEHMAN CAVE
GREAT BASIN NATIONAL PARK
150220
349463
AE DESIGN
MRS/JEB
03/28/2025 4 27
CAVE OVERALL PLAN
SCALE OF FEET
024 4824
NORTH
E0.3
1 CAVE KEY PLAN
KEYNOTE LEGEND
KEY
VALUE KEYNOTE TEXT
S1 EXISTING METER AND TRANSFORMER CABINET SHALL BE ABANDONED IN
PLACE. REFER TO ONE-LINE FOR ADDITIONAL INFORMATION.
S2 EXISTING CAVE DISCONNECT SHALL BE REPLACED WITH NEW DISCONNECT AND
SUB-METER. REFER TO ONE-LINE FOR ADDITIONAL INFORMATION. PROVIDE
UNISTRUT MOUNTING TO SUPPORT INSTALLATION OF NEW EQUIPMENT.
L
LAYDOWN AREA
VISITOR CENTER
TITLE OF SHEETSUB SHEET NO.DESIGNED:
TECH REVIEW:
DATE:
DRAWING NO.
PMIS/PKG NO.
SHEET
OF3/
/2
:2 1:
A
M C
:\U se rs \a w al te r\
D oc um en ts \5
0.
N P
S G
R B
A L eh m an C av e
Li gh tin g_
C en tr al
_a w al te r3 G
2X 6.
rv t
E0.4
AE DESIGN
LEHMAN CAVE
GREAT BASIN NATIONAL PARK
150220
349463
AE DESIGN
MRS/JEB
03/28/2025 5 27
CONSTRUCTION LAY
DOWN PLAN
E0.4
1 CONSTRUCTION LAYDOWN PLAN
STAGING GENERAL NOTES
A. CONTRACTOR PRIMARY CONSTRUCTION LAYDOWN AREA AND
TRAILER LOCATION SHALL UTILIZE THE FACILITIES GRAVEL PIT AREA
INDICATED. COORDINATE POSITIONING FOR TRAILERS AND LAYDOWN
EQUIPMENT WITH CONTRACTING OFFICER PRIOR TO MOBILIZATION.
SPACE AND ACCESS FOR SNOWPLOW AND CULVERTS SHALL BE
MAINTAINED. FINAL BOUNDARY SHALL BE FIELD VERIFIED WITH
CONTRACTING OFFICER FOR FINAL APPROVAL. FENCING SHALL BE
PROVIDED AS REQUIRED.
B. GENERATORS SHALL BE UTLIZED AT GRAVEL PIT LOCATION TO
SUPPORT CONSTRUCTION POWER NEEDS.
C. TEMPORARY POWER FOR CONSTRUCTION MAY BE ESTABLISHED
OUTSIDE THE CAVE EXIT TUNNEL ADJACENT TO THE OTHER SERVICE
EQUIPMENT, HOWEVER POWER TO VISITOR CENTER MUST BE
MAINTAINED. REFER TO SPECIFICATIONS FOR ADDITIONAL
REQUIREMENTS AND INFORMATION.
D. TOOLS WITHIN THE CAVE SHALL UTILIZE BATTERY POWER AS
PRIMARY SOURCE. REFER TO SPECIFICATIONS FOR ADDITIONAL
REQUIREMENTS AND INFORMATION.
E. EXIT TUNNEL AND ENTRANCE DOORS SHALL REMAIN NORMALLY
CLOSED AND MAY NOT BE PROPPED OR OPEN SIMULTANEOUSLY.
THIS IS TO MAINAIN THE CAVE CLIMATE AT ALL TIMES DURING
CONSTRUCTION.
NATURAL ENTRANCEGOTHIC
PALACE
CIVIL DEFENSE
PASSAGE
TRELLIS
ROOM
MUSIC ROOM
TOM TOM ROOM
LODGE ROOM
CRYSTAL
PALACE
INSCRIPTION
ROOM
ROCKY ROAD
WEST
ROOM
VISITOR CENTER
LAKE
ROOM
CYPRESS
SWAMP
GRAND
PALACE
SUNKEN
GARDENS
ROYAL
GORGE
APPROXIMATE LOCATION OF
TELECOM CLOSET
'GIANTS
EAR'
'CIVIL
DEFENSE'
'LAKE
ROOM'
X1
X2
X3
X3
X7
X5
(E) PROPANE TANK
(E) SERVICE
TRANSFORMER
(E) VISITOR CENTER
DISTRIBUTION
S3
(N) DISC.
& SUB-METER
(E) CT/METER
& TRANSFORMER
(E) VISITOR CENTER
DISTRIBUTION
(E) GENERATOR
M
S5
S5
S5
S5
S5
S5
S5
S5
X4X5
X5X5
X5
X4
X4
X2
X16
TITLE OF SHEETSUB SHEET NO.DESIGNED:
TECH REVIEW:
DATE:
DRAWING NO.
PMIS/PKG NO.
SHEET
OF3/
/2
:2 1:
A
M C
:\U se rs \a w al te r\
D oc um en ts \5
0.
N P
S G
R B
A L eh m an C av e
Li gh tin g_
C en tr al
_a w al te r3 G
2X 6.
rv t
E0.5
AE DESIGN
LEHMAN CAVE
GREAT BASIN NATIONAL PARK
150220
349463
AE DESIGN
MRS/JEB
03/28/2025 6 27
CAVE POWER
CONDUIT ROUTING
PLAN
E0.5
1 CAVE CONDUIT ROUTING PLAN
KEYNOTE LEGEND
KEY
VALUE KEYNOTE TEXT
S3 FEEDER LENGTH FROM EXIT DOOR TO EXTERIOR DISTRIBUTION IS APPROXIMATELY 220
FEET.
S5 PROVIDE IN-GRADE PULL BOX EVERY 250-FT MAXIMUM AND 270-DEG OF BENDS TO
FACILITATE PULLING OF ELECTRICAL FEEDERS. MINIMUM SIZE 12" X 12" WITH FINAL
SIZING PER NEC 314.28 REQUIREMENTS.
X1 EXISTING ROUTING IN EXIT TUNNEL WITHIN CONCRETE / GROUT. ANTICIPATING NEW
CONDUIT WILL BE ROUTED ALONG WALL (FOLLOWING SIMILAR PATH). RE: #3/E0.7.
X2 EXISTING ROUTING WITHIN WALL. ANTICIPATING NEW ROUTING WILL BE ALONG BASE
OF WALL.
X3 EXISTING ROUTING BEHIND STONE WALL. ANTICIPATING PARK WILL CAREFULLY
REMOVE STONE. NEW RACEWAY TO BE PROVIDED, AND NPS WILL REINSTALL STONE.
X4 CROSSOVER OCCURS WITHIN PATH (SAWCUT THROUGH). SAWCUTS FOR NEW
ROUTING SHALL BE CONSOLIDATED TO THESE LOCATIONS WHERE POSSIBLE, GROUPED
TOGETHER TO LIMIT CUTS AND DUST CONSIDERATIONS. SOME AREAS MAY REQUIRE
ABANDONING EXISTING IN PLACE. WHERE PATH CROSSING OCCURS. BACKFILL/PAVING
SHALL BE PROVIDED TO MATCH SURFACE OF PATHWAY AND LIMIT TRIP HAZARDS.
COORDINATE EXACT REQUIREMENTS WITH CONTRACTING OFFICER PRIOR TO SAWCUT
AND REPAVING.
X5 MOUNTED TO UNDERSIDE OF STAIR. THIS WILL BE CONSISTENT APPROACH FOR NEW
RACEWAYS.
X7 EXISTING PATHWAY IN THIS AREA IS WITHIN PORTIONS OF THE PATH. SAWCUTS FOR
NEW ROUTING SHALL BE CONSOLIDATED TO THESE LOCATIONS WHERE POSSIBLE,
GROUPED TOGETHER TO LIMIT CUTS AND DUST CONSIDERATIONS. SOME AREAS MAY
REQUIRE ABANDONING EXISTING IN PLACE.
X16 CONTRACTOR SHALL FOLLOW EXISTING POWER FEEDER PATHWAY INTO THE CAVE EXIT
TUNNEL FOR NEW CAVE SERVICE FEEDER TO THE EXTENT POSSIBLE. RE: #1/E0.7.
GENERAL NOTES
A ROUTING NOTATIONS HAVE BEEN MADE BASED ON EXISTING
CONDITIONS FOR SCHEMATIC CONSIDERATIONS FOR ROUTING.
DETAILED ROUTING SHALL BE FURTHER DEVELOPED BASED
UPON COORDINATION WITH THE NPS FOR COMPELTE
ANTICIPATED ROUTING PLAN. BASIS OF DESIGN ANTICIPATES ALL
NEW ROUTING AND SELECT RACEWAY CONDITIONS. ANTICIPATE
RACEWAY SHALL BE UTILIZED FOR MAIN FEEDERS BETWEEN
DISTRIBUTION PANELS AND SERVICE ENTRANCE. BRANCH
CIRCUITS ARE ANTICIPATED TO BE ROUTED EXTERNAL TO
RACEWAY, WITH THE EXCEPTION OF WHERE CUTS ARE MADE
ACROSS PATHWAY FOR CROSSINGS OR OTHERWISE DEFINED BY
THE KEYNOTES INDICATED.
SCALE OF FEET
024 4824
NORTH
B TO MINIMIZE IMPACT TO THE CAVE RESOURCE, ALL TRAIL
CROSSINGS AND ANY TRENCHING WITHIN THE CAVE SHALL BE
FIELD LOCATED AND COORDINATED WITH THE CONTRACTING
OFFICER PRIOR TO START OF WORK.
C CONDUIT AND CABLING ROUTED ALONG ENTRY AND EXIT
TUNNELS AND OTHER SELECT LOCATIONS DESIGNATED BY
CONTRACTING OFFICER SHALL BE CONCEALED WITH GUNITE OR
SIMILAR CONCRETE MATERIAL.
NATURAL ENTRANCEGOTHIC
PALACE
CIVIL DEFENSE
PASSAGE
TRELLIS
ROOM
MUSIC ROOM
TOM TOM ROOM
LODGE ROOM
CRYSTAL
PALACE
INSCRIPTION
ROOM
ROCKY ROAD
WEST
ROOM
VISITOR CENTER
LAKE
ROOM
CYPRESS
SWAMP
GRAND
PALACE
SUNKEN
GARDENS
ROYAL
GORGE
APPROXIMATE LOCATION OF
TELECOM CLOSET
'GIANTS
EAR'
'CIVIL
DEFENSE'
'LAKE
ROOM'
X8
X17
X10
APPROXIMATE
TELEPHONE
LOCATION
350'
APPROXIMATE
TELEPHONE
LOCATION
850'
APPROXIMATE
TELEPHONE
LOCATION
1025'
APPROXIMATE
TELEPHONE
LOCATION
1500'X4
X3
X3
X4 X4
X5
X5
X5 X5
X4
X4
X4
X9
S8
S8
S8 S8
S8
S8
S8 S8
S8
S8
S8
S8
S8
S8
S8
S8
S8
S8
S8
S8
TITLE OF SHEETSUB SHEET NO.DESIGNED:
TECH REVIEW:
DATE:
DRAWING NO.
PMIS/PKG NO.
SHEET
OF3/
/2
:2 1:
A
M C
:\U se rs \a w al te r\
D oc um en ts \5
0.
N P
S G
R B
A L eh m an C av e
Li gh tin g_
C en tr al
_a w al te r3 G
2X 6.
rv t
E0.6
AE DESIGN
LEHMAN CAVE
GREAT BASIN NATIONAL PARK
150220
349463
AE DESIGN
MRS/JEB
03/28/2025 7 27
CAVE TECHNOLOGY
CONDUIT ROUTING
PLAN
E0.6
1 CAVE TECHNOLOGY CONDUIT ROUTING PLAN
KEYNOTE LEGEND
KEY
VALUE KEYNOTE TEXT
X9 ROUTE NEW TECHNOLOGY CABLING AND CONDUIT ADJACENT TO EXISTING POWER
ROUTE ON THE LEFT OF THE TUNNEL.
X10 ALTERNATE ROUTE FOR TELEPHONE CABLING. ALTERNATE ROUTE SHALL BE REVIEWED
AND EVALUATED WITH CONTRACTING OFFICER. PROVIDE PRICING ALTERNATE FOR
ROUTING THROUGH SENSITIVE AREA TO REDUCE LENGTH. ROUTE THROUGH THIS AREA
IS A SMALL CRAWLWAY THAT IS ALREADY UTILIZED FOR SOME PATHWAY IN EXISTING
CONDITION.
X17 PROPOSED PATHWAY FOR NEW TECHNOLOGY CONDUIT. CONDUIT SHALL BE ROUTED
ALONG EXTERIOR OF CANOPY AS INDICATED, FROM THE BUILDING TO THE STONE WALL
OUTSIDE THE ENTRANCE DOOR, CONCEALED TO THE EXTENT POSSIBLE. REFER TO THE
DETAILS ON SHEET E0.7 FOR SPECIFIC ROUTING REQUIREMENTS.
KEYNOTE LEGEND
KEY
VALUE KEYNOTE TEXT
S8 PROVIDE PULL BOX EVERY 100-FT MAXIMUM OR 180-DEG OF BENDS TO FACILITATE
PULLING OF TECHNOLOGY CABLING. FIELD VERIFY FINAL LOCATIONS AND QUANTITIES
WITH CONTRACTING OFFICER PRIOR TO ROUGH-IN.
X3 EXISTING ROUTING BEHIND STONE WALL. ANTICIPATING PARK WILL CAREFULLY
REMOVE STONE. NEW RACEWAY TO BE PROVIDED, AND NPS WILL REINSTALL STONE.
X4 CROSSOVER OCCURS WITHIN PATH (SAWCUT THROUGH). SAWCUTS FOR NEW
ROUTING SHALL BE CONSOLIDATED TO THESE LOCATIONS WHERE POSSIBLE, GROUPED
TOGETHER TO LIMIT CUTS AND DUST CONSIDERATIONS. SOME AREAS MAY REQUIRE
ABANDONING EXISTING IN PLACE. WHERE PATH CROSSING OCCURS. BACKFILL/PAVING
SHALL BE PROVIDED TO MATCH SURFACE OF PATHWAY AND LIMIT TRIP HAZARDS.
COORDINATE EXACT REQUIREMENTS WITH CONTRACTING OFFICER PRIOR TO SAWCUT
AND REPAVING.
X5 MOUNTED TO UNDERSIDE OF STAIR. THIS WILL BE CONSISTENT APPROACH FOR NEW
RACEWAYS.
X8 ENTER BUILDING AT SATELLITE CONNECTION. ROUTE NEW TECHNOLOGY CABLING AND
CONDUIT ABOVE CEILING TO EXISTING TELECOM ROOM WITHIN VISITOR'S CENTER.
FOLLOW ROUTING FROM HEAD END ABOVE CEILING TO CORNER OF STORAGE CLOSET
TO POKE OUT OF BUILDING (FOLLOWING EXISTING CABLING) AND SURFACE MOUNT OUT
TO CANOPY. REFER TO DETAIL ON E0.7.
GENERAL NOTES
A ROUTING NOTATIONS HAVE BEEN MADE BASED ON EXISTING
CONDITIONS FOR SCHEMATIC CONSIDERATIONS FOR ROUTING.
DETAILED ROUTING SHALL BE FURTHER DEVELOPED BASED
UPON COORDINATION WITH THE NPS FOR COMPELTE
ANTICIPATED ROUTING PLAN. BASIS OF DESIGN ANTICIPATES ALL
NEW ROUTING AND SELECT RACEWAY CONDITIONS.
SCALE OF FEET
024 4824
NORTH
X16
X21X19
X18
X22
X23
X24
X25
X26 X27
X28
TITLE OF SHEETSUB SHEET NO.DESIGNED:
TECH REVIEW:
DATE:
DRAWING NO.
PMIS/PKG NO.
SHEET
OF3/
/2
:2 1:
A
M C
:\U se rs \a w al te r\
D oc um en ts \5
0.
N P
S G
R B
A L eh m an C av e
Li gh tin g_
C en tr al
_a w al te r3 G
2X 6.
rv t
E0.7
AE DESIGN
LEHMAN CAVE
GREAT BASIN NATIONAL PARK
150220
349463
AE DESIGN
MRS/JEB
03/28/2025 8 27
CONDUIT ROUTING
PHOTOS
E0.7
1 ELECTRICAL CONDUIT ROUTING AT CAVE EXIT TUNNEL
E0.7
2 TECHNOLOGY CONDUIT ROUTING AT CAVE ENTRY TUNNEL
KEYNOTE LEGEND
KEY
VALUE KEYNOTE TEXT
X16 CONTRACTOR SHALL FOLLOW EXISTING POWER FEEDER PATHWAY INTO THE
CAVE EXIT TUNNEL FOR NEW CAVE SERVICE FEEDER TO THE EXTENT
POSSIBLE. RE: #1/E0.7.
X18 CONDUIT SHALL TURN DOWN WALL, CONTINUING SURFACE MOUNT
CONDITION BEHIND EXISTING LANDSCAPING TO CONCEAL FROM VIEW.
COORDINATE EXACT TURN DOWN LOCATION OF CONDUIT WITH
CONTRACTING OFFICER.
X19 PROVIDE 4X4 SQUARE JUNCTION BOX FOR CABLE PULLING ALONG SECTION
OF WALL, WITH OPENING ACCESSIBLE, BUT CONCEALED TO THE EXTENT
POSSIBLE FROM VIEW BELOW CANOPY.
X21 AT END OF CANOPY, CONDUIT SHALL CROSS AND BE MOUNTED ALONG
SURFACE OF WALL (CONCEALED FROM DIRECT VIEW) AND ROUTED ALONG
WALL AS INDICATED.
X22 AT BASE OF WALL, PROVIDE SMARTLB 1-1/4" PVC CONDUIT BODY
(SOUTHWIRE #KBLB121 OR APPROVED EQUAL) FOR ACCESSIBLE PULL POINT.
X23 AT BASE OF WALL, TO TURN CORNER, PROVIDE SMARTLB 1-1/4" PVC CONDUIT
BODY (SOUTHWIRE #KBLB121 OR APPROVED EQUAL) FOR ACCESSIBLE PULL
POINT.
X24 FOLLOW BASE OF WALL AND POKE THROUGH WOOD MATERIAL ADJACENT TO
DOOR. SEAL AROUND PENETRATIONS TO PREVENT PEST INTRUSION.
X25 EXIT BUILDING IN CONDUIT FROM SAME APPROXIMATE LOCATION AS
EXISTING CABLING (INTERIOR LOCATION IS STORAGE ROOM).
X26 PROVIDE 4X4 SQUARE JUNCTION BOX FOR CABLE PULLING ALONG SECTION
OF WALL ADJACENT TO OTHER CONDUIT.
X27 ROUTE 1-1/4" CONDUIT ALONG CANOPY FOLLOWING SIMILAR ROUTE AS
EXISTING CONDUIT.
X28 LOW VOLTAGE 1-1/4" CONDUIT SHALL PENETRATE THROUGH WOOD
MATERIAL ADJACENT TO DOOR. SEAL AROUND PENETRATIONS AND CABLES
TO PREVENT PEST INTRUSION. CABLE SHALL BE EXPOSED FROM THIS POINT
INTO THE CAVE.
E0.7
3 CONDUIT ROUTING AT CAVE EXIT TUNNEL - INTERIOR
E0.7
4 TECHNOLOGY CONDUIT ROUTING FROM VISITORS CENTER
E0.7
5 TECHNOLOGY CONDUIT THROUGH CAVE DOOR
A1-W1
A
A2-W1 A3-W1A4-F20
A6-S1
ENTRY TUNNEL
NATURAL ENTRANCE
A7-S1
A10-F20
A8-S1
A5-F20
A9-S1A13-S1
A12-S1
A17-F20
A15-F20
A14-S1
A16-S1
A18-F20
A19-F20
A20-F20
AB
SB1
SB2
R
E F
R E
N C
E
E
.1
R
E F
R E
N C
E
E
.1
WP
A21-F20
L3 P2
WP
P2
WPP2
WP
P2
B20-F20
B21-F20 B19-F20
B18-F20
B10-F20 B17-F20
B9-F20
B11-F20
B8-F20
B7-F20
Bd4-F20
L4 A22-F20
CD-4
CD-4
CD-4
CD-4
Bd5-F20
C38-F20
X14
X14X15
X14
C B
TITLE OF SHEETSUB SHEET NO.DESIGNED:
TECH REVIEW:
DATE:
DRAWING NO.
PMIS/PKG NO.
SHEET
OF3/
/2
:2 1:
A
M C
:\U se rs \a w al te r\
D oc um en ts \5
0.
N P
S G
R B
A L eh m an C av e
Li gh tin g_
C en tr al
_a w al te r3 G
2X 6.
rv t
E1.0
AE DESIGN
LEHMAN CAVE
GREAT BASIN NATIONAL PARK
150220
349463
AE DESIGN
MRS/JEB
03/28/2025 9 27
ELECTRICAL PLAN -
ENTRANCE TUNNEL
KEYNOTE LEGEND
KEY
VALUE KEYNOTE TEXT
L3 LIGHTING CONTROL SHALL BE STANDARD 20A, 120V, TOGGLE SWITCH WITHIN A RATED
NEMA 4X, NON-METALLIC BACKBOX AND COVER. PROVIDE 3-WAY AND 4-WAY TYPE
WHERE INDICATED. PROVIDE LEVITON 'FDBX#-GY' AND 'COVER-GS' FOR BACKBOX AND
COVER, OR APPROVED EQUAL. ELECTRICAL CONTRACTOR SHALL PROVIDE A CLEAR,
WEATHERPROOF- WHILE-IN-USE COVER OVER SWITCH TO DETER PUBLIC TAMPERING.
L4 NEW 'SB2' LOCATION SHALL BE MOUNTED ON CONCRETE, NOT ATTACHED TO CAVE
RESOURCE.
P2 NEW WP RECEPTACLE WITH WHILE-IN-USE COVER.
X14 LOCATION OF EXISTING PATH CROSSING.
X15 LOCATION OF EXISTING NON-SKID SURFACE, DO NOT CROSS.
SCALE OF FEET
010 10 20
NORTH
E1.0
1 ENTRANCE
LIGHTING FIXTURE DESIGNATION SCHEDULE - SWITCHLEG A
SWITCH ID &
NUMBER
LIGHT FIXTURE
TYPE AIMING INTENT
MOUNTING
INFORMATION MOUNTING LOCATION
A14 S1 GENERAL TRAIL ILLUMINATION -
NO AIMING REQUIRED
REUSE EXISTING
MOUNTING LOCATION
RECESSED IN CAVE WALL
A15 F20 AIM AT FORMATION PLUG REUSE EXISTING
MOUNTING LOCATION
LOCATED ON LEFT-HAND
SIDE OF PASSAGE
A16 S1 GENERAL TRAIL ILLUMINATION -
NO AIMING REQUIRED
REUSE EXISTING
MOUNTING LOCATION
RECESSED IN CAVE WALL
A17 F20 AIM UP TO HISTORIC STAIRS NEW MOUNTING
LOCATION
LOCATED AGAINST THE
RIGHT-HAND WALL ON THE
RIGHT EDGE OF THE OLD
TRAIL
A18 F20 AIM DOWN AND ACROSS TRAIL NEW MOUNTING
LOCATION
LOCATED ON THE
RIGHT-HAND SIDE OF THE
TRAIL ON THE LEFT-HAND
SIDE OF THE ENTRANCE
STAIRS PASSAGE
A19 F20 AIM DOWN AND ACROSS TRAIL NEW MOUNTING
LOCATION
LOCATED ON THE
LEFT-HAND SIDE OF THE
TRAIL IN A SLOT NEXT TO
THE BREAKDOWN BLOCK
A20 F20 AIM DOWN AND ACROSS
PLATFORM
NEW MOUNTING
LOCATION
LOCATED ON THE
RIGHT-HAND CORNER OF
THE PLATFORM IN THE
GOTHIC PALACE
A21 F20 AIM DOWN AND ACROSS
PLATFORM
NEW MOUNTING
LOCATION
LOCATED ON THE
LEFT-HAND SIDE OF THE
PLATFORM IN GOTHIC
PALACE UNDER SWITCH
PEDESTAL LOCATION
A22 F20 AIM UP TO CEILING NEW MOUNTING
LOCATION
LOCATED AGAINST THE
RIGHT-HAND WALL ON THE
RIGHT EDGE OF THE OLD
TRAIL
LIGHTING FIXTURE DESIGNATION SCHEDULE - SWITCHLEG A
SWITCH ID &
NUMBER
LIGHT FIXTURE
TYPE AIMING INTENT
MOUNTING
INFORMATION MOUNTING LOCATION
A1 W1 GENERAL TUNNEL
ILLUMINATION -
NO AIMING REQUIRED
REUSE EXISTING
MOUNTING LOCATION
LOCATED ABOVE ENTRANCE
DOOR
A2 W1 GENERAL TUNNEL
ILLUMINATION -
NO AIMING REQUIRED
REUSE EXISTING
MOUNTING LOCATION
LOCATED ABOVE AIR LOCK
DOOR
A3 W1 GENERAL TUNNEL
ILLUMINATION -
NO AIMING REQUIRED
REUSE EXISTING
MOUNTING LOCATION
LOCATED ABOVE AIR LOCK
DOOR, JUST OUTSIDE OF
AIRLOCK
A4 F20 TRAIL ILLUMINATION - AIM
FIXTURE DOWN TOWARDS
TRAIL
NEW MOUNTING
LOCATION
LOCATED TO THE LEFT-HAND
SIDE OF THE TRAIL IN AN
ALCOVE
A5 F20 TRAIL ILLUMINATION - AIM
FIXTURE DOWN TOWARDS
TRAIL
REUSE EXISTING
MOUNTING LOCATION
LOCATED TO THE
RIGHT-HAND SIDE OF THE
TRAIL AT FLOOR LEVEL
A6 S1 GENERAL TRAIL ILLUMINATION -
NO AIMING REQUIRED
REUSE EXISTING
MOUNTING LOCATION
RECESSED IN CAVE WALL
A7 S1 GENERAL TRAIL ILLUMINATION -
NO AIMING REQUIRED
REUSE EXISTING
MOUNTING LOCATION
RECESSED IN CAVE WALL
A8 S1 GENERAL TRAIL ILLUMINATION -
NO AIMING REQUIRED
REUSE EXISTING
MOUNTING LOCATION
RECESSED IN CAVE WALL
A9 S1 GENERAL TRAIL ILLUMINATION -
NO AIMING REQUIRED
NEW MOUNTING
LOCATION
RECESSED IN CAVE WALL
A10 F20 USE A LADDER TO AIM
VERTICALLY UP WALL TO THE
SILHOUETTE AND HIGHLIGHT
THE UNDERSIDE OF THE
OVERHANGING STALACTITE
REUSE EXISTING
MOUNTING LOCATION
LOCATED BEHIND
STALAGMITE SEVEN FEET
ABOVE THE LEFT SIDE OF
THE TRAIL
A12 S1 GENERAL TRAIL ILLUMINATION -
NO AIMING REQUIRED
REUSE EXISTING
MOUNTING LOCATION
RECESSED IN CAVE WALL
A13 S1 GENERAL TRAIL ILLUMINATION -
NO AIMING REQUIRED
REUSE EXISTING
MOUNTING LOCATION
RECESSED IN CAVE WALL
CIRCUITING TABLE
SWITCHLEG
GENERAL NOTES
A
B
ALL FIXTURE LOCATIONS HAVE BEEN SHOWN PER INFORMATION COORDINATED WITH
THE DESIGN TEAM AND PREVIOUS SITE VISITS DURING MARCH 2022, AND IS
UNDERSTOOD TO BE THE BEST INFORMATION CURRENTLY AVAILABLE.
EC SHALL REUSE EXISTING CABLING PATHWAYS TO THE GREATEST EXTENT
POSSIBLE TO ROUTE NEW BRANCH CIRCUIT MULTICONDUCTOR CABLING TO
SWITCHES, LIGHT FIXTURES, AND RECEPTACLES. ADDTIONALLY, ROUTING
ADJUSTMENTS SHALL BE MADE FOR BETTER CONCEALMENT FROM DIRECT VIEW OF
WALKING TRAIL. ALL ROUTING ADJUSTMENTS AND MOUNTING POSITIONS SHALL BE
COORDINATED WITH CONTRACTING OFFICER.
CONDUCTOR SIZING FOR LIGHTING CIRCUITS:
THE FIRST WIRING SEGMENT FROM PANELBOARD TO SWITCHES SHALL BE 2#X, 1#XG,
WHERE "X" IS THE WIRE SIZE INDICATED IN THE CIRCUITING TABLE ON EACH PLAN
SHEET. FOR 3-WAY SWITCHING, PROVIDE 3#X,1#XG BETWEEN SWITCHES TO
ACCOUNT FOR THE TRAVELER WIRE. SOME SIZES INCREASED TO ACCOUNT FOR
VOLTAGE DROP. ALL DOWNSTREAM WIRING FROM SWITCHES TO LIGHT FIXTURES
SHALL BE 2#12,1#12G.
CONDUCTOR SIZING FOR RECEPTACLE CIRCUITS:
PROVIDE 2#8,1#8G TO ACCOUNT FOR VOLTAGE DROP.
EC SHALL PROVIDE PIGTAIL / PIN REDUCER CONNECTORS AND SPLICE BOX AS
REQUIRED FOR PROPER TERMINATION OF CONDUCTORS AT SWITCHES AND
RECEPTACLES.
EC SHALL PROVIDE 2' OF CONDUCTOR SLACK AT EACH LIGHTING FIXTURE LOCATION
FOR FLEXIBILITY OF MINOR LOCATION ADJUSTMENTS IN THE FUTURE BY THE PARK.
D
CIRCUIT #
A CD-1
B CD-2
Ba CD-2
Bb CD-2
Bc CD-2
Bd CD-2
IN GENERAL, TO AVOID SIGNIFICANT RE-WORK OF EXISTING NON-SKID SURFACES
THESE LOCATIONS ARE SHOWN ON PLAN. IF POSSIBLE, TRENCHING SHALL AVOID
EXISTING NON-SKID PATHWAYS.
E
SWITCHLEG
WIRE SIZE
#8
#12
#12
#12
#12
#12
C
FOR IN-CAVE ENVIRONMENT SPLICES, USE HEAVY DUTY HEAT SHRINK TYPE
COMPRESSION CONNECTORS. WIRE NUT CONNECTION OF CONDUCTORS IS NOT
PERMITTED.
F
AB
B7-F20
B8-F20
B11-F20
Bd4-F20
Bc3-F20
Be6-F20
Bb2-F20 B6-F20
Ba1-F20
B12-F20
B9-F20
B10-F20
B18-F20
B19-F20
B15-F20
B16-F20
B13-F20
B20-F20 B21-F20
B17-F20
B
C
SB2
SB3
T1
WP
P1
P2'CIVIL
DEFENSE'
O6
Ba BbBc Bd Be
R
E F
R E
N C
E
E
.0
R
E F
R E
N C
E
E
.0
/REFRENCE: 1 E1.2
P2
WP
P2
WP
L3
L3
P4
C11-F20
C4-F20
C10-F20 C9-F20
C5-F20 C3-F20
C2-F20
C1-F20
A20-F20
A19-F20
P8
A21-F20 L4
Bd5-F20
C38-F20
CD-4
CD-4
CD-4
C39-F20
X15
X14
X15
X14 X14
X14
TITLE OF SHEETSUB SHEET NO.DESIGNED:
TECH REVIEW:
DATE:
DRAWING NO.
PMIS/PKG NO.
SHEET
OF3/
/2
:2 1:
A
M C
:\U se rs \a w al te r\
D oc um en ts \5
0.
N P
S G
R B
A L eh m an C av e
Li gh tin g_
C en tr al
_a w al te r3 G
2X 6.
rv t
E1.1
AE DESIGN
LEHMAN CAVE
GREAT BASIN NATIONAL PARK
150220
349463
AE DESIGN
MRS/JEB
03/28/2025 10 27
ELECTRICAL PLAN -
GOTHIC PALACE
KEYNOTE LEGEND
KEY
VALUE KEYNOTE TEXT
L3 LIGHTING CONTROL SHALL BE STANDARD 20A, 120V, TOGGLE SWITCH WITHIN A RATED
NEMA 4X, NON-METALLIC BACKBOX AND COVER. PROVIDE 3-WAY AND 4-WAY TYPE
WHERE INDICATED. PROVIDE LEVITON 'FDBX#-GY' AND 'COVER-GS' FOR BACKBOX AND
COVER, OR APPROVED EQUAL. ELECTRICAL CONTRACTOR SHALL PROVIDE A CLEAR,
WEATHERPROOF- WHILE-IN-USE COVER OVER SWITCH TO DETER PUBLIC TAMPERING.
L4 NEW 'SB2' LOCATION SHALL BE MOUNTED ON CONCRETE, NOT ATTACHED TO CAVE
RESOURCE.
O6 PROVIDE UL 1449 LISTED EXTERNAL SURGE PROTECTION DEVICE (SPD) WITH 100KVA
PER PHASE MINIMUM FOR TYPE 1 AND 2 APPLICATIONS, CURRENT TECHNOLOGY
#CGP-060-120/240-2G, OR APPROVED EQUIVALENT. PROVIDE BREAKER SIZE AND
WIRING AS COORDINATED WITH MANUFACTURER'S INSTALLATION INSTRUCTIONS.
P1 NEW ELECTRICAL PANEL MOUNTED ON EXISTING H-FRAME.
P2 NEW WP RECEPTACLE WITH WHILE-IN-USE COVER.
P4 PROVIDE (3) TIMER SWITCHES, LEVITON 'VPT24' (OR APPROVED EQUAL) FOR AREA
OVERRIDE CONTROL. TIMER SWITCHES SHALL BE INSTALLED WITHIN 16"X12"X8" NEMA
4X ENCLOSURE MOUNTED ADJACENT TO POWER PANEL ON H-FRAME.
P8 EC SHALL ANTICIPATE TEMPORARY POWER PROVISIONS DURING CONSTRUCTION.
'SPIDER BOX' OR SIMILAR SHALL BE UTILIZED FROM EXISTING EQUIPMENT LOCATIONS
AS NEEDED DURING CONSTRUCTION UNTIL WHICH TIME THE NEW SYSTEMS ARE IN
PLACE.
T1 NEW PHONE LOCATION.
X14 LOCATION OF EXISTING PATH CROSSING.
X15 LOCATION OF EXISTING NON-SKID SURFACE, DO NOT CROSS.
GENERAL NOTES
A REFER TO GENERAL NOTES ON SHEET E1.0.
SCALE OF FEET
010 10 20
NORTH
LIGHTING FIXTURE DESIGNATION SCHEDULE - SWITCHLEG B
SWITCH ID &
NUMBER
LIGHT FIXTURE
TYPE AIMING INTENT
MOUNTING
INFORMATION MOUNTING LOCATION
B17 F20 AIM DOWN AND ACROSS TRAIL TO
REFLECT LIGHT UP TO LOW CEILING
REUSE EXISTING
MOUNTING
LOCATION
LOCATED ON THE
LEFT-HAND SIDE OF
TRAIL AT THE EXISTING
TRAIL LIGHT LOCATION
B18 F20 AIM DOWN AND ACROSS TRAIL TO
REFLECT LIGHT UP TO LOW CEILING
REUSE EXISTING
MOUNTING
LOCATION
LOCATED BEHIND ROSE
TRELLIS
B19 F20 AIM AT BACK AND RIGHT-HAND WALL REUSE EXISTING
MOUNTING
LOCATION
LOCATED IN ALCOVE
AROUND THE CORNER
B20 F20 AIM DOWN SIDE PASSAGE WITH PACK
RAT NEST
REUSE EXISTING
MOUNTING
LOCATION
LOCATED BEHIND
STAGMITE 4' FROM
EDGE OF PLATFORM
B21 F20 AIM UP INTO POCKET BETWEEN TWO
COLUMNS
NEW MOUNTING
LOCATION
LOCATED BEHIND
COLUMN
Ba1 F20 AIM VERTICALLY AT THE LARGE SHIELD NEW MOUNTING
LOCATION
LOCATED BEHIND THE
STALAGMITES UNDER
THE SHIELD 7' AWAY
FROM THE SWITCHBACK
IN THE TRAIL
Bb2 F20 AIM UP TO THE TOP PLATE OF A
SHIELD ON THE CEILING ABOVE THE
PLATFORM
NEW MOUNTING
LOCATION
LOCATED NEXT TO B6 4'
FROM THE EDGE OF THE
PLATFORM, IN-BETWEEN
A TALL STALAGMITE AND
A COLUMN
Bc3 F20 AIM UP AT THE POLE CANYON
LIMESTONE CEILING
REUSE EXISTING
MOUNTING
LOCATION
LOCATED BEHIND THE
BREAKDOWN BLOCK IN
THE MIDDLE OF THE
SIDE PASSAGE
Bd4 F20 AIM UP AT THE STALACTITE-COVERED
CEILING
REUSE EXISTING
MOUNTING
LOCATION
LOCATED BEHIND THE
DRAPERY COLUMN IN
THE RIGHT HAND SIDE
OF THE SIDE PASSAGE
Bd5 F20 AIM IN OPPOSITE DIRECTION AS Bd4 TO
STALACTITES OVERHEAD OF
PLATFORM.
REUSE EXISTING
MOUNTING
LOCATION
LOCATED BEHIND THE
DRAPERY COLUMN IN
THE RIGHT HAND SIDE
OF THE SIDE PASSAGE
Be6 F20 AIM VERTICALLY UP AT THE CLUSTER
OF STALS
NEW MOUNTING
LOCATION
LOCATED BEHIND THE 3'
HIGH STALAGMITE, 4'
FROM THE EDGE OF THE
PLATFORM ALONG THE
EDGE OF A LEDGE
LIGHTING FIXTURE DESIGNATION SCHEDULE - SWITCHLEG B
SWITCH ID &
NUMBER
LIGHT FIXTURE
TYPE AIMING INTENT
MOUNTING
INFORMATION MOUNTING LOCATION
B6 F20 AIM VERTICALLY AT THE BIG COLUMN
AND GROUP OF STALS
NEW MOUNTING
LOCATION
LOCATED NEXT TO B2
BEHIND THE
STALAGMITES 2' FROM
EDGE OF THE
PLATFORM
B7 F20 AIM UP AT DRAPERIES TO SILHOUETTE
BRIDGE
REUSE EXISTING
MOUNTING
LOCATION
LOCATED BEHIND
FORMATION COVERED
BRIDGE ON RIGHT-HAND
SIDE
B8 F20 AIM UP AND TO THE LEFT AT THE
DRAPERY COLUMNS
NEW MOUNTING
LOCATION
LOCATED NEXT TO B11
BEHIND THE
STALAGMITE AT THE
BASE OF THE DRAPERY
WALL
B9 F20 AIM UP TO THE ROW OF COLUMNS REUSE EXISTING
MOUNTING
LOCATION
LOCATED ON 4' HIGH
SHELF BEHIND DOUBLE
STALAGMITE
B10 F20 AIM UP TO THE UPPER PART OF THE
DRAPERIES OVER THE TRAIL
NEW MOUNTING
LOCATION
LOCATED BEHIND TALL
COLUMN
B11 F20 AIM UP AT ROWS OF SODA STRAWS ON
CEILING
REUSE EXISTING
MOUNTING
LOCATION
LOCATED NEXT TO B8
BEHIND STALAGMITE
B12 F20 AIM UP TO THE DRAPERIES AND SODA
STRAWS NEAR BACK WALL
REUSE EXISTING
MOUNTING
LOCATION
LOCATED BEHIND
BREAKDOWN BLOCK
AND SMALL
STALAGMITES ON SLOPE
B13 F20 AIM VERTICALLY AT STALS IN CEILING NEW MOUNTING
LOCATION
LOCATED ON SLOPE
BELOW SWITCHBACK
B15 F20 AIM UP AT LARGE DRAPERY COLUMN REUSE EXISTING
MOUNTING
LOCATION
LOCATED NEXT TO B16
BEHIND BREAKDOWN
BLOCK
B16 F20 AIM UP TO UPPER PORTION OF LARGE
DRAPERY COLUMN AND ROWS OF
STALS
NEW MOUNTING
LOCATION
LOCATED NEXT TO B15
BEHIND BREAKDOWN
BLOCK
E1.1
1 GOTHIC PALACE
CIRCUITING TABLE
SWITCHLEG CIRCUIT #
A CD-1
B CD-2
C CD-3
Ba CD-2
Bb CD-2
Bc CD-2
Bd CD-2
SWITCHLEG
WIRE SIZE
#8
#12
#12
#12
#12
#12
#10
B
C
C1-F20
C2-F20
C3-F20
C6-F20 C7-F20
C8-F20
C5-F20
C12-F20
C4-F20
C9-F20
C10-F20
C11-F20
C13-F20
C14-F20
C17-F20
C15-F20
C18-F20
C16-F20
C19-F20 C20-F20
C21-F20
C23-F20C24-F20 C28-F20 C27-F20
C25-F20
C26-F20
C30-F20 C29-F20C31-F20
TRELLIS ROOM
CIVIL DEFENSE
PASSAGE
MUSIC ROOM
SB3
C22-F20
/REFRENCE: 1 E1.1 /REFRENCE: 1 E1.1
/REFRENCE: 1 E1.3
WP
P2
P2
L3
WP
D2-F20
B18-F20
B19-F20
B20-F20
B21-F20
C39-F20
CD-4
CD-4
D1-F20
X14
X14
'CIVIL
DEFENSE'
X14
TITLE OF SHEETSUB SHEET NO.DESIGNED:
TECH REVIEW:
DATE:
DRAWING NO.
PMIS/PKG NO.
SHEET
OF3/
/2
:2 1:
A
M C
:\U se rs \a w al te r\
D oc um en ts \5
0.
N P
S G
R B
A L eh m an C av e
Li gh tin g_
C en tr al
_a w al te r3 G
2X 6.
rv t
E1.2
AE DESIGN
LEHMAN CAVE
GREAT BASIN NATIONAL PARK
150220
349463
AE DESIGN
MRS/JEB
03/28/2025 11 27
ELECTRICAL PLAN -
TRELLIS ROOM
KEYNOTE LEGEND
KEY
VALUE KEYNOTE TEXT
L3 LIGHTING CONTROL SHALL BE STANDARD 20A, 120V, TOGGLE SWITCH WITHIN A RATED NEMA 4X, NON-METALLIC BACKBOX AND COVER. PROVIDE 3-WAY AND 4-WAY TYPE WHERE INDICATED. PROVIDE LEVITON 'FDBX#-GY' AND 'COVER-GS' FOR BACKBOX AND COVER, OR APPROVED EQUAL. ELECTRICAL CONTRACTOR SHALL PROVIDE A CLEAR, WEATHERPROOF- WHILE-IN-USE COVER OVER SWITCH TO
DETER PUBLIC TAMPERING.
P2 NEW WP RECEPTACLE WITH WHILE-IN-USE COVER.
X14 LOCATION OF EXISTING PATH CROSSING.
SCALE OF FEET
010 10 20
NORTH
LIGHTING FIXTURE DESIGNATION SCHEDULE - SWITCHLEG C
SWITCH
ID &
NUMBER
LIGHT
FIXTURE
TYPE AIMING INTENT MOUNTING INFORMATION MOUNTING LOCATION
C30 F20 AIM NEAR VERTICALLY TO THE
SHIELDS AND DRAPERIES OVER THE
TRAIL.
NEW MOUNTING LOCATION LOCATED NEXT TO C29.
C31 F20 AIM VERTICALLY THE STALLS AND
DRAPERIES IN THE CEILING CRACK.
REUSE EXISTING
MOUNTING LOCATION
LOCATED BEHIND THE DRAPERY COLUMN
18-FEET ABOVE THE RIGHT-HAND EDGE
OF THE TRAIL.
C32 F20 AIM UP TO THE LARGE COLUMN. NEW MOUNTING LOCATION LOCATED BELOW THE BOTTOM STEP ON
THE LEFT-HANDSIDE OF THE TRAIL.
C33 F20 AIM UP LEFT-HAND WALL. NEW MOUNTING LOCATION LOCATED UNDER THE LEFT-HAND EDGE
OF THE STAIRS BELOW THE 2ND STEP.
C34 F20 AIM VERTICALLY AT THE STALS AND
SHIELDS.
NEW MOUNTING LOCATION LOCATED BEHIND THE COLUMNS ON A
SHELF ABOVE THE 3RD STEP.
C35 F20 AIM VERTICALLY UP THE DRAPERIES
ON THE RIGHT-HAND WALL.
NEW MOUNTING LOCATION LOCATED UNDER THE RIGHT-HAND SIDE
OF THE STAIRS BELOW THE 5TH STEP.
C36 F20 AIM DOWN AND ACROSS TRAIL. NEW MOUNTING LOCATION LOCATED ON THE RIGHT-HAND EDGE OF
THE TRAIL.
C37 F20 AIM DOWN AND ACROSS TRAIL. REUSE EXISTING
MOUNTING LOCATION
LOCATED AT EXISTING TRAIL LIGHT
LOCATION ON THE RIGHT-HAND EDGE OF
THE TRAIL.
C38 F20 AIM ACROSS THE PLATFORM. NEW MOUNTING LOCATION LOCATED ON THE FLOOR.
C39 F20 AIM UP AND ACROSS TRAIL AT ROWS
OF TALL COLUMNS
NEW MOUNTING LOCATION LOCATED ON SLOPING SHELF 7' ABOVE
RIGHT-HAND SIDE OF TRAIL
LIGHTING FIXTURE DESIGNATION SCHEDULE - SWITCHLEG C
SWITCH
ID &
NUMBER
LIGHT
FIXTURE
TYPE AIMING INTENT MOUNTING INFORMATION MOUNTING LOCATION
C1 F20 AIM VERTICALLY UP POPCORN
COVERED DRAPERIES TO
SILHOUETTE STALS
NEW MOUNTING LOCATION LOCATED BEHIND LOW STALAGMITE
MOUNT AND UNDER STALS
C2 F20 AIM UP AND ACROSS TRAIL AT ROWS
OF TALL COLUMNS
NEW MOUNTING LOCATION LOCATED ON SLOPING SHELF 7' ABOVE
RIGHT-HAND SIDE OF TRAIL
C3 F20 AIM UP AND ACROSS THE TRAIL TO
UPPER PORTION OF THE LARGE
COLUMN
REUSE EXISTING
MOUNTING LOCATION
LOCATED ON BACK SIDE OF SMALL
BREAKDOWN BRIDGE, 6' ABOVE THE
RIGHT-HAND SIDE OF THE TRAIL AT THE
ENTRANCE OF DOWN-SLOPING TUBE IN
THE LARGE BREAKDOWN BLOCK. MOUNT
TO THE BACKSIDE OF THE BRIDGE
C4 F20 AIM AT RIMSTONE DAMS AND THE
RIGHT-HAND WALL
REUSE EXISTING
MOUNTING LOCATION
LOCATED ON THE FLOOR OUT OF SIGHT
IN THE SIDE PASSAGE WITH RIMSTONE
DAMS
C5 F20 AIM DOWN AND ACROSS TRAIL NEW MOUNTING LOCATION LOCATED IN SMALL FLOOR LEVEL ALCOVE
C6 F20 AIM TOWARDS BACK WALL TO
SILHOUETTE DRAPERY STALS
REUSE EXISTING
MOUNTING LOCATION
LOCATED OUT OF SIGHT IN FLOOR LEVEL
SIDE PASSAGE BEHIND DRAPERY STALS
C7 F20 AUN BACK AND UP TO UPPER
PORTION OF LARGE COLUMN
REUSE EXISTING
MOUNTING LOCATION
LOCATED 7' ABOVE THE LEFT-HAND EDGE
OF THE TRAIL BEHIND DRAPERY COLUMN
C8 F20 AIM VERTICALLY UP TO STALS REUSE EXISTING
MOUNTING LOCATION
LOCATED 6'-6" ABOVE LEFT-HAND EDGE
OF THE TRAIL ON A FLOWSTONE LEDGE
C9 F20 AIM AT ROW OF COLUMNS AND
VERTICAL SHIELF
NEW MOUNTING LOCATION LOCATED BEHIND COLUMN ON FLOOR
C10 F20 AIM BACK AND UP TO STALS ON
CEILING OVER TRAIL
NEW MOUNTING LOCATION LOCATED ON LEDGE 7' FROM RIGHT-HAND
SIDE OF TRAIL
C11 F20 AIM UP TO THE STALS AND
DRAPERIES HANGING FROM SHIELD
REUSE EXISTING
MOUNTING LOCATION
LOCATED ON BACK SIDE OF PILLAR AT
THE TOP OF THE FLOWSTONE SLOPE
C12 F20 AIM VERTICALLY AT UPPER PORTION
OF STALS AND DRAPERIES ON
LEFT-HAND WALL
NEW MOUNTING LOCATION LOCATED IN SLOT 4'-6" ABOUT LEFT-HAND
EDGE OF TRAIL
C13 F20 AIM VERTICALLY AT SALS AND
DRAPERIES HANGING FROM SHIELD
ON THE CEILING. BEST TO ACCESS
FROM GOTHIC PALACE.
REUSE EXISTING
MOUNTING LOCATION
LOCATED ON TOP OF LEDGE 15' ABOVE
THE RIGHT-HAND EDGE OF THE TRAIL
C14 F20 AIM BACK AND OVER TRAIL AT
CEILING TO BRING OUT THE
TEXTURE AND COLORS. BEST TO
ACCESS FROM GOTHIC PALACE.
REUSE EXISTING
MOUNTING LOCATION
LOCATED TO THE LEFT OF THE SHIELD ON
THE CEILING THAT IS HIGHLIGHTED BY
C13
C15 F20 AIM UP TO STALAGMITE, COLUMNS,
AND SHIELDS ON THE LEFT-HAND
SIDE OF THE SIDE PASSAGE
REUSE EXISTING
MOUNTING LOCATION
LOCATED BEHIND SMALL STALAGMITE ON
FLOWSTONE SLOPE 7' FROM THE
RIGHT-HAND EDGE OF THE TRAIL
C16 F20 AIM UP AT DOUBLE STALAGMITES REUSE EXISTING
MOUNTING LOCATION
LOCATED BEHIND VERTICAL SHIELD ON
THE FLOOR IN THE SIDE PASSAGE
C17 F20 AIM UP AND ACROSS THE TRAIL AT
THE UPPER PORTION OF THE STALS
OVER THE TRAIL.
NEW MOUNTING LOCATION LOCATED ON THE FLOOR OF THE SIDE
PASSAGE ALONG THE RIGHT-HAND WALL 8
FEET FROM THE RIGHT-HAND
EDGE OF THE TRAIL.
C18 F20 AIM DOWN ALONG THE LOWER
LEFT-HAND WALL.
NEW MOUNTING LOCATION LOCATED BEHIND CLUSTER OF SMALL
COLUMNS AT THE CORNER OF THE TRAIL.
C19 F20 AIM DOWN AND BACK ACROSS THE
SIDE PASSAGE TO SHIELD AND
DRAPERY COLUMN ON THE
LEFT-HAND SIDE OF THE PASSAGE.
REUSE EXISTING
MOUNTING LOCATION
LOCATED OUT-OF-SIGHT IN THE SMALL
SIDE PASSAGE, JUST PAST THE
RIGHT-HAND WALL OF THE PASSAGE.
C20 F20 AIM VERTICALLY TO THE STALS AND
DRAPERIES.
NEW MOUNTING LOCATION LOCATED BEHIND THE COLUMN ON THE
RIGHTHAND SIDE OF THE TRAIL AT THE
CORNER OF THE WALL.
C21 F20 AIM VERTICALLY AT THE
DRAPERY-COVERED WALLS.
NEW MOUNTING LOCATION LOCATED ON THE RIGHT-HAND SIDE OF
THE SIDE PASSAGE, 13-FEET ABOVE THE
RIGHT-HAND EDGE OF THE TRAIL.
C22 F20 AIM DOWN AND ACROSS THE TRAIL. REUSE EXISTING
MOUNTING LOCATION
LOCATED AT EXISTING TRAIL LIGHT
LOCATION IN THE FLOOR ALCOVE ALONG
THE LEFT-HAND EDGE OF THE TRAIL.
C23 F20 AIM DOWN AND ACROSS THE TRAIL. NEW MOUNTING LOCATION LOCATED NEAR C24 ON THE LEDGE
14-FEET ABOVE THE RIGHT-HAND SIDE OF
THE TRAIL IN AN ALCOVE.
C24 F20 AIM UP TO STALS ABOVE TRAIL. NEW MOUNTING LOCATION LOCATED NEAR C23 ON A LEDGE 14-FEET
ABOVE THE RIGHT-HAND SIDE OF THE
TRAIL.
C25 F20 AIM UP AND ACROSS
DRAPERY-COVERED WALL.
NEW MOUNTING LOCATION LOCATED ON A LEDGE 7-FEET ABOVE THE
RIGHT-HAND EDGE OF THE TRAIL NEXT TO
C26.
C26 F20 AIM ACROSS TRAIL AT DRAPERY
WALL WITH STALS AND COLUMNS.
NEW MOUNTING LOCATION LOCATED NEXT TO C25.
C27 F20 USE LADDER TO AIM UP AND
ACROSS THE TRAIL TO THE UPPER
PART OF THE DRAPERY-COVERED
WALL.
REUSE EXISTING
MOUNTING LOCATION
LOCATED IN ALCOVE 20-FEET ABOVE THE
RIGHT-HANDSIDE OF THE TRAIL NEXT TO
C28.
C28 F20 USE LADDER TO AIM UP TO STALS
OVER THE TRAIL AT THE TOP OF THE
MUSIC ROOM.
REUSE EXISTING
MOUNTING LOCATION
LOCATED NEAR C27.
C29 F20 AIM UP TO DRAPERIES ON THE
LEFT-HAND WALL.
REUSE EXISTING
MOUNTING LOCATION
LOCATED IN ALCOVE 22-FEET ABOVE THE
RIGHT-HAND EDGE OF THE TRAIL NEAR
C30.
E1.2
1 TRELLIS ROOM
CIRCUITING TABLE
SWITCHLEG CIRCUIT #
B CD-2
C CD-3
SWITCHLEG
WIRE SIZE
#12
#10
GENERAL NOTES
A REFER TO GENERAL NOTES ON SHEET E1.0.
D2-F20D3-F20
D
C
D1-F20
D6-F20
D5-F20
D4-F20
D7-F20
D8-F20
D10-F20
D9-F20
D12-F20
D13-F20
D11-F20
D14-F20
D16-F20
D17-F20
D15-F20
D19-F20
D18-F20
D20-F20
D22-F20
D23-F20
D25-F20
D24-F20
D21-F20
D26-F20D27-F20
D28-F20
D29-F20
D30-F20
D32-F20
D31-F20
D33-F20
D34-F20
D35-F20
D39-F20
D38-F20
D37-F20
D40-F20
D41-F20 D42-F20
D43-F20 D46-F20
D45-F20
D44-F20
D47-F20
D48-F20 D49-F20
D51-F20
D53-F20D50-F20
D52-F20
D36-F20
SB4
L1
/REFRENCE: 1 E1.2
/REFRENCE: 1 E1.4/REFRENCE: 1 E1.4
WP
P2
L3
G9-F20
C31-F20
C30-F20
C29-F20
C28-F20
C27-F20
X12
C32-F20 C33-F20
C34-F20
C35-F20
C36-F20
C37-F20 CD-4
X14
X14
X15 X14
X14
X14
X14
X15
X15
TITLE OF SHEETSUB SHEET NO.DESIGNED:
TECH REVIEW:
DATE:
DRAWING NO.
PMIS/PKG NO.
SHEET
OF3/
/2
:2 2:
A
M C
:\U se rs \a w al te r\
D oc um en ts \5
0.
N P
S G
R B
A L eh m an C av e
Li gh tin g_
C en tr al
_a w al te r3 G
2X 6.
rv t
E1.3
AE DESIGN
LEHMAN CAVE
GREAT BASIN NATIONAL PARK
150220
349463
AE DESIGN
MRS/JEB
03/28/2025 12 27
ELECTRICAL PLAN -
TOM TOM ROOM
KEYNOTE LEGEND
KEY
VALUE KEYNOTE TEXT
L1 NEW 'SB4' SWITCHBANK SHALL BE MOUNTED TO THE EXISTING STAIR RAILING NEAR THE
TOP STEP.
L3 LIGHTING CONTROL SHALL BE STANDARD 20A, 120V, TOGGLE SWITCH WITHIN A RATED
NEMA 4X, NON-METALLIC BACKBOX AND COVER. PROVIDE 3-WAY AND 4-WAY TYPE WHERE
INDICATED. PROVIDE LEVITON 'FDBX#-GY' AND 'COVER-GS' FOR BACKBOX AND COVER, OR
APPROVED EQUAL. ELECTRICAL CONTRACTOR SHALL PROVIDE A CLEAR,
WEATHERPROOF- WHILE-IN-USE COVER OVER SWITCH TO DETER PUBLIC TAMPERING.
P2 NEW WP RECEPTACLE WITH WHILE-IN-USE COVER.
X12 CABLING AT THIS LOCATION SHALL BE BURIED WITH NO EXPOSED WIRING.
X14 LOCATION OF EXISTING PATH CROSSING.
X15 LOCATION OF EXISTING NON-SKID SURFACE, DO NOT CROSS.
SCALE OF FEET
010 10 20
NORTH
LIGHTING FIXTURE DESIGNATION SCHEDULE - SWITCHLEG D
SWITCH ID &
NUMBER
LIGHT FIXTURE
TYPE AIMING INTENT
MOUNTING
INFORMATION…