This document appears to be an Appendix A to the Statement of Objectives (SOO) for the GRCA 250440 Shuttle Bus Facility solicitation. It provides an update to the Standard Design (SD) for the shuttle bus facilities to include Battery Electric Buses (BEBs).

The key details are: The solicitation number is 140P2024R0028 issued by the National Park Service. The update to the SOO Appendix A details the requirements for incorporating BEBs into the shuttle bus facilities design, including charging infrastructure, parking, and other related specifications. This is likely in response to federal fleet electrification initiatives. No other details on the overall solicitation, such as response dates, award information, or set-asides are provided in this specific document.

View the file

Other files for this federal contract opportunity

Show all 23

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

o o o o o o o o o o o o o o o o

8 6

8 6

.67

3.50

8.47

.2

2.20

2.43

2.2

GRCA Bus Maintenance – SD Update

GRCA Bus SD Update Preferred Alternative – Civil Summary

The following summarizes changes from the original Schematic Design Basis of Design narrative to accommodate Battery Electric Buses (BEBs).

• Increase bus parking paving limits from previous SD layout by approximately 6,220 SF (previous SD layout had 105,590 SF of bus parking area). Total bus parking paving would be approximately

111,810 SF.

o Provide concrete paving at bus parking stalls: 27,220 SF concrete – 8” reinforced concrete at

4500 psi, reinforcement assumed to be #4 @ 18” o.c.

o Provide asphalt paving for bus drive aisles: 84,590 SF asphalt – 6” asphalt over 9” aggregate base course o Providing concrete pavement at bus parking stalls is preferred for pavement longevity due to impacts that asphalt might experience from parked and/or turning buses.

• Maintain bus parking stall widths at 14-feet and add a 2-foot-wide painted island between stalls.

Three stalls would be at a 13-feet width to accommodate column locations.

o Maintaining the 14-foot stall width and adding a 2-foot-wide painted island between stalls would provide clearance around parked buses for staff movement.

• 10 canopy mounted bus charging stations within main bus parking area.

o Bus charging stations are being shown at the north end of the bus parking area to allow for expansion of the bus parking further south if desired in the future.

• 1 bus ground mounted charging station within parallel bus parking area.

• 1 bus charging station within bus maintenance facility building.

• Increase fencing limits from previous SD layout by approximately 190 LF (previous SD layout had

1,520 LF of fencing). Total fencing would be approximately 1,710 LF.

• Expand detention pond along west side of bus parking area for increased pavement area.

• Would result in an additional 15 trees being removed and an additional 7,330 SF of revegetation for expanded pavement limits and fencing.

• Decrease in utility yard paving limits from previous SD layout by approximately 575 SF (previous SD layout had 1,700 SF for utility yard). Total utility yard paving would be approximately 1,125 SF.

• Conduit routing to charging stations:

o Approximately 3610 LF of 1-inch and 3610 LF of 2-inch electrical conduit to proposed charging stations.

o Approximately 5800 LF of 1-inch and 5800 LF of 2-inch electrical conduit placed for future charging stations.

o Total of 9410 LF of 1-inch and 9410 LF of 2-inch electrical conduit.

o Refer to electrical narrative for additional information.

• Provide approximately 600 LF new gas line from the natural gas fueling station to utility yard.

• Refer to structural narrative for information on canopy and piers.

Articulated Bus Counterclockwise Turn

Articulated Bus Clockwise Turn

40-ft Bus Counterclockwise Turn

40-ft Bus Clockwise Turn

Battery Electric Bus Design

It is anticipated that Battery Electric Buses (BEB’s) will be provided to support (2) bus routes along the

Canyon. It is anticipated (10) dedicated charging stations will be provided in the new bus parking lot as well as (1) dedicated charging station located at an alternative location on the site, and (1) located within a bus maintenance bay.

Base Bid:

For the purposes of this project, please anticipate the following which is based on Proterra charging stations and control systems.

The bus charging infrastructure is anticipated to be served by a new pad mount 480V/3PH transformer which will be located in the utility yard on the south side of the Maintenance Building. APS is to provide and install the utility transformer and the incoming primary cable, the EC shall be responsible for all trenching and conduit. EC is to provide and install the pad and all secondary conduit and conductors. APS is to provide the CT Meter, and the EC is to provide the CT Enclosure with meter housing, and all make all connections to the meter.

It is anticipated that (4) parallel runs of 3-1/2” conduit will be provided from the utility transformer to an

800A, 480/277V fused service disconnect. Two of the conduits will be provided with 4#500MCM copper conductors. The disconnect will then feed into a 800A automatic transfer switch (see generator section below) and then into a 800A electrical distribution panel. The electrical distribution panel will feed (1)

30kVA 480:208V step-down transformer and (3) Power Control System (PCS) cabinets which are each capable of controlling (4) bus charging dispensers. The 30kVA transformer will feed a 100A, 120/208V electrical panel which will feed the miscellaneous low voltage electrical loads including receptacles and generator equipment loads. The electrical connection to each PCS is anticipated to be 200A therefore requiring (1) 2-1/2” conduit with 4#3/0 AWG conductors and 1#6AWG grounding conductor. Room will be provided to expand the number of PCS cabinets to a total of (12) to account for potential future expansion of the bus charging dispenser. The electrical distribution panel shall also be equipped with an externally mounted listed surge suppression device.

An additional bus charging station will be provided within one of the maintenance building’s Work Bays. It is anticipated that (1) 75kVA 208:480V step up transformer will be required to provide the required voltage for the charger. This transformer will be fed on the primary side by 3#250MCM conductors and 1#4 ground.

The secondary side will have 4#1AWG conductors and (1) 1#6 ground and will feed a 100A disconnect. This disconnect will then feed into the stand-alone bus charger.

From each PCS location, the contractor shall provide (1) 2” conduit for power and (1) 1” conduit for communications to each charging dispenser location. This alterative includes (10) canopy mounted, pantograph charge dispensers located above each bus and (1) pedestal mounted charging dispenser location for the remote bus charging location. Please refer to Civil drawings for locations of all (11) charging dispensers. Also provide (1) spare 2” conduit and (1) spare 1” conduit from future PCS locations out to each bus parking stall (31 total stalls) to provide infrastructure for future charging dispensers.

The PCS cabinets shall be provided with demand optimization capabilities which limit the number of buses charging at any given time to (5) busses and limit the demand to the electrical grid to 150kW.

Standby Generator:

To provide standby capacity beyond 60-90 minutes, it is anticipated that a 275kW standby generator will be required. Base bid shall consist of a natural gas generator which will require a new underground gas line to the nearby Fueling Station. A bid alternate shall also be provided to provide a diesel generator in lieu of a natural gas generator. A diesel generator would require a 24-hour base tank located beneath the generator and the gas line from the Fueling Station will not be required. The final selection will be made during the DD

Phase of design after further discussion and coordination with NPS staff. Refer to civil drawings for anticipated gas-line routing. The generator shall provide standby power to a 400A automatic transfer switch

(ATS-1) that gets normal power from the 400A utility service disconnect, and ATS-1 shall feed into the electrical distribution panel indicated above. The size of this genset is anticipated to be approximately

175”L x 58”W x 80” high. Three feet, four inches of clearance is required on all sides around the generator.

This is for the standard enclosure, if higher level acoustic ratings are required, the generator will grow in length and height. The average sound pressure level at 7 meters for each generator running at full load can be found in the table below:

Generator Type

Standard dB(A)

Level 1 dB(A)

Level 2 dB(A)

Diesel 84.2 78.1 75.2

Natural Gas

83.2 77.7 74.4

Solar Design

A preliminary investigation of the impact of implementing a solar PV system on the roof of the bus parking canopy, was done using the National Renewable Energy Laboratory (NREL) PV Watts Calculator (simulation) on-line program. The intent of the solar array would be to offset the operating costs of the BEB’s, these would not be used to directly charge the buses due to the fact that they will be out on routes throughout most of the daytime hours. The solar panel canopy footprint for the Preferred Alternative is anticipated to be 478-feet by 70-feet giving a total square footage of 33,460SF. Using an 80”x40” solar panel, an estimate of approximately 1,206 panels can fit on the structure and produce approximately 482.4kW of electricity or

701,483kWh/Year. Calculations were run using a panel lying flat on the roof, a 2” spacing is anticipated to allow for racking hardware, and a clear view of the sky. If actual conditions change, the electrical value of the system (show below) may decrease.

• Variables such as the potential build-up of snow are not accounted for in this initial study. These will impact the total annual production of the system, but further/detailed investigation is required to understand how much.

• Studies have shown that single axis rotation of solar panels provides and increased efficiency of 25 to 35 percent and dual-axis trackers provide an additional 5 to 10 percent. Adding trackers to the system adds anywhere from 40% to 60% to the total cost of the installation.

Electrical infrastructure for this installation is anticipated to consist of microinverters located at each solar panel which will convert DC power to AC power. These will feed back to a combiner panel which will be located on the canopy structure. This combiner panel will then feed back through a PV utility meter to an

800A/3P disconnect and then to an 800A/3P breaker located in the Main Distribution Panel. See attached one-line diagram for additional information.

Based on this study, the initial cost of the system would be on the order of $1,206,000.00 with an annual electrical value of $71,691.00. Payback would be roughly 16.8 years. The annual electrical value is estimated using an average retail electricity rate of 0.102$/kWh. This number may vary depending on actual demand billing, usage, and utility rates.

Arizona does offer some solar PV incentive and rebate programs. This will be investigated as we move further into the design process.

An energy demand analysis was performed by the NPS for the anticipated bus fleet. The analysis was performed with the assumption that (8) buses will be in service on a typical day, two of which will have a consumption of 129kWh per day and six of which will have a consumption of 272kWh per day. These numbers are derived based on route information and the scheduled bus services and have been used as a baseline for determining the anticipated solar offset.

As mentioned above, the annual production of the solar array is anticipated to be 701,483kWh. Using the numbers from the fleet analysis, the yearly consumption for charging the buses is anticipated to be

689,850kWh. This shows that on a typical day, the solar array will be able to produce 102% of the needed load. There will be days where production is lower and utility power is needed however there will also be days where excess energy is provided back to the utility grid. Using a greenhouse gas equivalencies calculator provided by the EPA, an offset of 701,483kWh is equivalent to 497 metric tons of carbon dioxide or 549,468 pounds of coal burned.

Using an average retail electricity rate of 0.102$/kWh, without any solar offset, an average monthly electricity bill would be approximately $5,863. As mentioned above, the electricity rate will vary depending on actual demand billing, usage, and utility rates. This number is to be used for rough pricing only. Per the solar offset numbers stated above, on an average month with a fully sized solar array, the utility bill would be at or near zero with potential for the system to sell power back to the grid.

• Bid Option: An alternate investigation was performed using panels mounted at an optimal 36-degree tilt using a fixed mount system which provided approximately 284kW of electricity or 484,213kWh/Year. In this configuration 711 panels are able to fit on the structure and require a 2’8” gap between panels to avoid shadowing. Additional structural members will be required to achieve a 36-degree tilt, please refer to the structural narrative for more information. On a typical day, this configuration would be able to produce 70% of the needed load. Using a greenhouse gas equivalencies calculator provided by the EPA, an offset of 484,213kWh is equivalent to 343 metric tons of carbon dioxide or 379,282 pounds of coal burned. The initial cost of this system would be on the order of $711,000 with an annual electrical value of $49,487.00 and a payback of roughly 14.4 years.

Please see attached Solar PV calculation, showing the full characteristics and results of the study.

Revision to the Lightning Protection System Section of the Basis of Design Report:

Electrical Contractor to provide add-alternate pricing to provide and install a lightning protection system on both the Maintenance Building and Bus Canopy with an underwriter’s laboratories Master ‘C’ label.

Contractor shall coordinate all ground rod locations on roof with architect while developing submittals.

Submittals shall require full roof plans with all ground rod (and all other equipment) indicated for review prior to submittal approval. Careful consideration shall be made to conceal exposed conductors from public view, to the greatest extent possible.

���� !"#$%&!�!'!(�� )$*+*�,-$.,/0!/-�"), ./,1 )� !"*$)�()�(��,1$2+$%34���*5$ ")(�1, -�"+$ "&,/,"�$ �**�-.� !"*$ �"1

�"),/�� "� ,*$�"1$1!$"!�$/,0(,)�$'�/ �� !"*

2,�6,,"$%3$�,)&"!(!7 ,*$"!/$* �,8*.,) 0 )

)&�/�)�,/ *� )*$,9),.�$�*$/,./,*,"�,1$2+

%34���*5$ ".��*:$;!/$,9�-.(,<$%3$-!1�(,*

6 �&$ 2,��,/$ .,/0!/-�"),$ �/,$ "!�

1 00,/,"� ��,1$6 �& "$%34���*5$0/!-$(,**,/

.,/0!/- "7$-!1�(,*:$=!�&$>?@A$�"1$./ '��, )!-.�" ,*$./!' 1,$-!/,$*!.& *� )��,1$%3

-!1,( "7$�!!(*$B*�)&$�*$�&,$C+*�,-$D1' *!/

E!1,($��$&��.*#FF*�-:"/,(:7!'G$�&��$�((!6$0!/

-!/,$./,) *,$�"1$)!-.(,9$-!1,( "7$!0$%3

H&,$,9.,)�,1$/�"7,$ *$2�*,1$!"$IJ$+,�/*$!0

�)���($6,��&,/$1���$��$�&,$7 ',"$(!)�� !"

�"1$ *$ "�,"1,1$�!$./!' 1,$�"$ "1 )�� !"$!0

�&,$'�/ �� !"$+!�$- 7&�$*,,:$;!/$-!/, "0!/-�� !"<$.(,�*,$/,0,/$�!$�& *$>?@A$/,.!/�#

H&,$@//!/$?,.!/�:

K *)(� -,/#$H&,$%34���*5$E!1,($BLE!1,(LG

*$./!' 1,1$2+$�&,$>�� !"�($?,",6�2(, @",/7+$A�2!/��!/+$BL>?@ALG<$6& )&$ *

!.,/��,1$2+$�&,$D(( �"),$0!/$C�*�� "�2(, @",/7+<$AA�$BLD(( �"),LG$0!/$�&,$M:C:

K,.�/�-,"�$N0$@",/7+$BLKN@LG$�"1$-�+$2,

�*,1$0!/$�"+$.�/.!*,$6&��*!,',/:

H&,$"�-,*$KN@F>?@AFDAAOD>�@$*&�(($"!�

2,$�*,1$ "$�"+$/,./,*,"��� !"<$�1',/� * "7<

.�2( ) �+$!/$!�&,/$-�"",/$6&��*!,',/$�!

,"1!/*,$!/$./!-!�,$�"+$,"� �+$�&��$�1!.�*$!/

�*,*$�&,$E!1,(:$KN@F>?@AFDAAOD>�@$*&�((

"!�$./!' 1, �"+$ *�..!/�<$ )!"*�(� "7<$ �/� " "7$ !/

�** *��"),$!0$�"+$P "1$6 �&$/,7�/1$�!$�&,$�*, !0$�&,$E!1,($!/$�"+$�.1��,*<$/,' * !"*$!/

",6$',/* !"*$!0$�&,$E!1,(:

QNM$ DR?@@$ HN$ O>K@E>O;Q

KN@F>?@AFDAAOD>�@<$D>K$OHC$D;;OAODH@C<

N;;O�@?C<$ DR@>HC<$ D>K$ @E%ANQ@@C

DRDO>CH$ D>Q$ �ADOE$ N?$ K@ED>K<

O>�AMKO>R$ ?@DCN>D=A@$ DHHN?>@QCS

;@@C<$?@ADH@K$HN$QNM?$MC@<$?@AOD>�@<

N?$DKN%HON>$N;$HT@$ENK@A$;N?$D>Q

%M?%NC@$4TDHCN@3@?:$HT@$ENK@A$OC

%?N3OK@K$=Q$KN@F>?@AFDAAOD>�@$LDC$OCL

D>K$ D>Q$ @U%?@CC$ N?$ OE%AO@K

4D??D>HO@C<$ O>�AMKO>R$ =MH$ >NH

AOEOH@K$HN$HT@$OE%AO@K$4D??D>HO@C$N;

E@?�TD>HD=OAOHQ$D>K$;OH>@CC$;N?$D

%D?HO�MAD?$%M?%NC@$D?@$@U%?@CCAQ

KOC�ADOE@K:$ O>$ >N$ @3@>H$ CTDAA

KN@F>?@AFDAAOD>�@$=@$AOD=A@$;N?$D>Q

C%@�ODA<$O>KO?@�H$N?$�N>C@VM@>HODA

KDEDR@C$N?$D>Q$KDEDR@C$4TDHCN@3@?<

O>�AMKO>R$=MH$>NH$AOEOH@K$HN$�ADOEC

DCCN�ODH@K$4OHT$HT@$ANCC$N;$KDHD$N?

%?N;OHC<$4TO�T$EDQ$?@CMAH$;?NE$D>Q

D�HON>$O>$�N>H?D�H<$>@RAOR@>�@$N?

NHT@?$HN?HONMC$�ADOE$HTDH$D?OC@C$NMH

N;$N?$O>$�N>>@�HON>$4OHT$HT@$MC@$N?

%@?;N?ED>�@$N;$HT@$ENK@A:

H&,$,",/7+$!��.��$/�"7,$ *$2�*,1$!"

�"�(+* *$!0$IJ$+,�/*$!0$& *�!/ )�($6,��&,/

1���$0!/$",�/2+$<$�"1$ *$ "�,"1,1$�!$./!' 1, �"$ "1 )�� !"$!0$�&,$.!** 2(,$ "�,/�""��(

'�/ �2 ( �+$ "$7,",/�� !"$0!/$�$; 9,1$B!.,"

/�)PG$%3$*+*�,-$��$�& *$(!)�� !":

WXYZ[\]̂_̀abcdefghijklmj nopqrstuvqwvqtsxotyxz{rt|yust}}~����tqut�������t���twrytorxytzrxytq��pt�u�xq�uz�t

��ª�¢

«��©��¡ ¬ ®̄°±²̄ ®°² ̄

³¦́�©��¡ ®¬µµ ±¶°® µ ±°· ·

���̧� ¬̄±¶ ² °²± ²°±¶

£¹��� ²¬²¶ µ®°º̄ µ°̄̄

��¡ µ¬²̄ º±°®ºº º°² ±

«©�¦ º¬®¶ º±°¶¶ º°²µµ

«©�¡ ²¬µ̄ µ®°® º µ°±±

£©§©»� ²¬¶̄ ²±°®·² ²°̄µ®

�¦¹�¦� ¦́� ¬̄º· ²·°µ²· ²°®·

¼̧ ��́¦� ±¬̄² ·̄°¶µ °̄ ¶

½�¾¦� ¦́� ®¬®º ®µ°̄¶² ®°º®®

¿¦̧¦� ¦́� ¬µ® ®·°ºµ² ®° ̄º

£��©�� ¬̄®® µ¶·°±º® ª�µ·°²·

À�̧������������������Á�¦���Â�̧�����

�¦Ã©¦»�¦��À�̧����� ·���©���¦�Ä©»�����°�Å�����¤��¡��

�¦���¦��¿������©�̧¦ À��°�À��Æ�®²¬¶̄°�Ç·· ¬·± �¶¬®���

À����©�¦ ®²¬¶̄È�½

À��§��©�¦ ·· ¬·±È��

É̈ ��¡»�¦���¹¦̧�Â�̧�����»�ÊËussry��x�Ì

¿¤��¡»�¦����ͦ ±º ¬±���

���©�¦�Ρ¹¦ ��������

£���¡�Ρ¹¦ ³�Ϧ������Â���©��¢

£���¡�Î��� ¶È

£���¡�£Í��©�� ·º¶È

�¡»�¦��À�»»¦» ·±¬¶ºÐ

Á�¾¦��¦��¥ÂÂ�̧�¦�̧¡ ²Ð

¿¤����£¤���ͦ������ ·¬

£¾¦��§¦��¦�����¥�¦̧���̧��¡����¦ ¶¬·¶ �ª����

ɦ�Â�����̧¦��¦���̧»

¤�¹�̧��¡�³�̧��� ·²¬²Ð

Feature

425W | 420W | 415W | 410W

About LG Electronics LG Electronics is a global big player, committed to expanding its operations with the solar market. The company first embarked on a solar energy source research program in 1985, supported by LG Group’s vast experience in the semi-conductor, LCD, chemistry and materials industries. In 2010, LG Solar successfully released its first MonoX® series to the market, which is now available in 32 countries. The NeON® (previous. MonoX® NeON), NeON®2, NeON®2 BiFacial won the “Intersolar AWARD” in 2013, 2015 and 2016, which demonstrates LG Solar’s lead, innovation and commitment to the industry.

KM 564573 BS EN 61215 Photovoltaic Modules

TM

yrs25 Warranty

Enhanced Product warranty

Because of the high quality of LG solar panels, LG provides 25 years product warranty to customers.

Enhanced Performance Warranty

LG NeON® 2 has an enhanced performance warranty. After 25 years, LG NeON® 2 is guar-anteed to perform at minimum 90.1% of initial performance.

The LG NeON® 2 is LG’s best selling solar module, and is one of the powerful and versatile modules on the market today.

Dimensions (mm / inch)

LG425N2W-L5 I LG420N2W-L5 I LG415N2W-L5 I LG410N2W-L5

General Data Cell Properties(Material / Type) Monocrystalline / N-type

Cell Maker LG

Cell Configuration 72 Cells (6 x 12)

Number of Busbars 12EA

Module Dimensions (L x W x H) 2,024mm x 1,024mm x 40 mm

Weight 21.5 kg

Glass(Thickness / Material) 2.8mm / Tempered Glass with AR Coating

Backsheet(Color) White

Frame(Material) Anodized Aluminium

Junction Box(Protection Degree) IP 68 with 3 Bypass Diodes

Cables(Length) 1,200 mm x 2EA

Connector(Type / Maker) MC4 / MC4 Compatible

* First year : 98%, After 1st year : 0.33% annual degradation, 90.1% at 25years

Certifications and Warranty

Certifications

IEC 61215-1/-1-1/2:2016, IEC 61730-

1/2:2016, UL 61730-1/-2:2017

ISO 9001, ISO 14001, ISO 50001

OHSAS 18001

Salt Mist Corrosion Test IEC 61701 : 2011 Severity 6

Ammonia Corrosion Test IEC 62716 : 2013

Module Fire Performance Type 1 (UL 61730)

Fire Rating Class C (UL 790)

Solar Module Product Warranty 25 Years

Solar Module Output Warranty Linear Warranty*

* NMOT (Nominal Module Operating Temperature): Irradiance 800 W/m2, Ambient temperature 20 °C, Wind speed 1 m/s, Spectrum AM 1.5

Temperature Characteristics

NMOT* [ °C ] 42 ± 3

Pmax [%/°C] -0.35

Voc [%/°C] -0.26

Isc [%/°C] 0.025

I-V Curves

* STC (Standard Test Condition): Irradiance 1000 W/m², Cell temperature 25 °C, AM 1.5

** Measure Tolerance of Pmax : ±3%

Electrical Properties (STC*) Model LG425N2W-L5 LG420N2W-L5 LG415N2W-L5 LG410N2W-L5

Maximum Power (Pmax) [W] 425 420 415 410

MPP Voltage (Vmpp) [V] 42.5 42.1 41.8 41.4

MPP Current (Impp) [A] 10.01 9.98 9.94 9.91

Open Circuit Voltage (Voc, ±5%) [V] 49.8 49.7 49.6 49.5

Short Circuit Current (Isc, ±5%) [A] 10.67 10.63 10.59 10.55

Module Efficiency [%] 20.5 20.3 20.0 19.8

Power Tolerance [%] 0 ~ +3

Electrical Properties (NMOT) Model LG425N2W-L5 LG420N2W-L5 LG415N2W-L5 LG410N2W-L5 Maximum Power (Pmax) [W] 319 315 312 308 MPP Voltage (Vmpp) [V] 39.9 39.6 39.3 38.9 MPP Current (Impp) [A] 7.99 7.96 7.93 7.91 Open Circuit Voltage (Voc) [V] 47.0 46.9 46.8 46.7 Short Circuit Current (Isc) [A] 8.57 8.54 8.51 8.48

LG Electronics Inc.

Energy Business Division LG Twin Towers, 128 Yeoui-daero, Yeongdeungpo-gu, Seoul 07336, Korea www.lg-solar.com

Product specifications are subject to change without notice.

DS-L5-72-W-G-F-EN-200708

© 2020 LG Electronics. All rights reserved.

Packaging Configuration Number of Modules per Pallet [EA] 25

Number of Modules per 40ft HQ Container [EA] 550

Packaging Box Dimensions (L x W x H) [mm] 2,080 x 1,120 x 1,226

Packaging Box Gross Weight [kg] 551

Operating Conditions Operating Temperature [°C ] -40 ~ +90

Maximum System Voltage [V] 1,500(UL), 1000(IEC)

Maximum Series Fuse Rating [A] 20

Mechanical Test Load (Front) [Pa / psf] 5,400 / 113 Mechanical Test Load (Rear) [Pa / psf] 3,000 / 63

※Mechanical Test Load 5,400Pa / 3,000Pa based on IEC 61215-2 : 2016 (Test Load = Design Load x Safety Factor(1.5))

(Refer to the table)

Voltage[V]

Cu rr en t[

A

0.0

2.0

4.0

6.0

8.0

10.0

12.0

0.0 10.0 20.0 30.0 40.0 50.0

1000W

800W

600W

400W

200W

RELIABLE

DC FAST CHARGING

FOR FLEETS

The Proterra Industrial Series charging system is designed explicitly for fleet applications.

Available in 60kW, 90kW, 120kW, 150kW and 180kW configurations.

Charge up to 4 vehicles from the same charger with automated, multi-dispenser configurations, including up to 4 single-cable dispensers or 2 dual-cable dispensers.

Dispensers can be sited separately

(up to 500 feet away) from the charging cabinet, enabling greater flexibility in design and configuration for fleets.

Remote monitoring, intelligent diagnostics and a modular design allows for quick issue resolution and efficient field service.

Broad voltage range (up to 1000VDC) ensures compatibility with both today’s and next generation electric vehicles.

• OCPP compliant and 4G enabled

• Small footprint

• Multi-dispenser option

• Supports CCS1 and pantograph options

• 3 Year Standard Warranty with extensions available

CHARGING

SYSTEMS

INDUSTRIAL SERIES

Proterra charging systems are compliant with Federal DOT Buy America requirements.

CHARGING

SYSTEMS

Proterra charging systems are compliant with Federal DOT Buy America requirements.

proterra.com/energy-services

MODEL PC-060-PI PC-090-PI PC-120-PI PC-150-PI PC-180-PI

ELECTRICAL OUTPUT

Continuous DC Output Power 60 kW 90 kW 120 kW 150 kW 180 kW

DC Output Voltage 150-1000 VDC

Continuous DC Output Current 200 A, 500 A Pantograph (Optional) 300 A, 500 A Pantograph (Optional)

ELECTRICAL INPUT

AC Input Power 63 kVA 95 kVA 126 kVA 158 kVA 189 kVA

AC Input Current 76 A 114 A 152 A 190 A 227 A

AC Input Voltage 480V +/- 10%

AC Input Topology 5-wire WYE (3ph + N + GND)

AC Input Frequency 60 Hz

Current THD% at full power <3%

Power Factor >0.99

Efficiency 95%

MECHANICAL

Cooling Integrated air cooling

Weight 825 lbs 880 lbs 935 lbs 990 lbs 1056 lbs

Dimensions (D x W x H) 31.2 in x 39.6 in x 79.2 in | 80 cm x 100 cm x 200 cm

Required side doork clearance None

Required Front and Rear Clearance 1000 mm

ENVIRONMENTAL

Environmental Rating NEMA 3R

Maximum Altitude 3000m | 9800 ft (power derates above 2000m | 6500 ft)

Operating temperature -22°F to 122°F | -30°C to 50°C

Operating Humidity 4-95%

MISC

Approved charger-to-vehicle interfaces CCS1 Industrial dispenser

J3105-1 Infrastructure-Down Pantograph

Approved number of dispensers per power cabinet

Up to 2 Dual Cable Dispensers or Up to 4 Single Cable Dispensers

Sequential Charging Capabilities 1 @ 60 kW 1 @ 90 kW 1 @ 120 kW 1 @ 150 kW 1 @ 180 kW

Simultaneous Charging Capabilities - - 2 @ 60 kW - 3 @ 60 kW

Power Cabinet to dispenser or pantograph control box communications

Modbus TCP via fiber optic

Max Distance between Power Cabinet and Dispenser

500 ft | 152.4 m (fiber optics)

Management Communications OCPP 1.6 control via 4G Cellular (standard)

Supports WiFi, Ethernet (optional)

Certifications UL 2231, UL 2202 (pending)

Warranty 3 year standard, 5 year extended warranty (optional)

S P

E C

C

H G

S Y

S N

B c

Q mkeisler Cross-Out remove mkeisler Cross-Out remove

SG275 | 14.2L | 275 kW

INDUSTRIAL SPARK-IGNITED GENERATOR SET

EPA Certified Stationary Emergency and Non-Emergency

SP

EC

S H

EE

T

DEMAND RESPONSE READY

Standby Power Rating 275 kW, 344 kVA, 60 Hz

Demand Response Rating 275 kW, 344 kVA, 60 Hz

Prime Power Rating 248 kW, 309 kVA, 60 Hz

Codes and Standards Not all codes and standards apply to all configurations. Contact factory for details.

UL2200, UL6200, UL1236, UL489

CSA C22.2

BS5514 and DIN 6271

SAE J1349

NFPA 37, 70, 99, 110

NEC700, 701, 702, 708

ISO 3046, 7637, 8528, 9001

NEMA ICS10, MG1, 250, ICS6, AB1

ANSI C62.41

IBC 2009, CBC 2010, IBC 2012,

ASCE 7-05, ASCE 7-10, ICC-ES AC-

156 (2012)

TM

Powering Ahead Generac ensures superior quality by designing and manufacturing most of its generator components, such as alternators, enclosures, control systems and communications software. Generac also makes its own spark-ignited engines, and you’ll find them on every Generac gaseous-fueled generator. We engineer and manufacture them from the block up — all at our facilities throughout Wisconsin. Applying natural gas and LP-fueled engines to generators requires advanced engineering expertise to ensure reliability, durability and necessary performance. By designing specifically for these dry, hotter-burning fuels, the engines last longer and require less maintenance. Building our own engines also means we control every step of the supply chain and delivery process, so you benefit from single-source responsibility.

Plus, Generac Industrial Power’s distribution network provides all parts and service so you don’t have to deal with third-party suppliers. It all leads to a positive owner experience and higher confidence level. Generac spark-ignited engines give you more options in commercial and industrial generator applications as well as extended run time from utility-supplied natural gas.

*Assembled in the USA using domestic and foreign parts

Image used for illustration purposes only

EPA Certified Stationary Emergency and Non-Emergency

SP

EC

S H

EE

T

DEMAND RESPONSE READY

CONTROL SYSTEM

Power Zone® Pro Sync Controller

Program Functions

• NFPA 110 Level 1 Compliant

• Engine Protective Functions

• Alternator Protective Functions

• Digital Engine Governor Control

• Digital Voltage Regulator

• Multiple Programmable Inputs and Outputs

• Remote Display Capability

• Remote Communication via Modbus® RTU, Modbus TCP/IP, and Ethernet 10/100

• Alarm and Event Logging with Real Time Stamping

• Expandable Analog and Digital Inputs and Outputs

• Remote Wireless Software Update Capable

• Wi-Fi®, Bluetooth®, BMS and Remote Telemetry

• Built-In Programmable Logic Eliminates the Need for External Controllers Under Most Conditions

• Ethernet Based Communications Between Generators

• Programmable I/O Channel Properties

• Built-In Diagnostics

Protections

• Low Oil Pressure

• Low Coolant Level

• High/Low Coolant Temperature

• Sensor Failure

• Oil Temperature

• Over/Under Speed

• Over/Under Voltage

• Over/Under Frequency

• Over/Under Current

• Over Load

• High/Low Battery Voltage

• Battery Charger Current

• Phase to Phase and Phase to Neutral Short Circuits

(I2T Algorithm)

7 Inch Color Touch Screen Display

• Resistive Color Touch Screen

• Sunlight Readable (1400 NITS)

• Easily Identifiable Icons

• Multi-Lingual

• On Screen Editable Parameters

• Key Function Monitoring

• Three Phase Voltage, Amperage, kW, kVA, and kVAr

• Selectable Line to Line or Line to Neutral Measurements

• Frequency

• Engine Speed

• Engine Coolant Temperature

• Engine Oil Pressure

• Engine Oil Temperature

• Battery Voltage

• Hourmeter

• Warning and Alarm Indication

• Diagnostics

• Maintenance Events/Information

ENGINE SYSTEM

• Oil Drain Extension

• Air Cleaner

• Fan Guard (Open Sets Only)

• Stainless Steel Flexible Exhaust Connection

• Factory Filled Oil and Coolant

• Radiator Duct Adapter (Open Set Only)

• Critical Silencer (Enclosed Units Only)

• Oil Temperature Indication and Alarm

Fuel System

• NPT Fuel Connection on Frame

• Primary and Secondary Fuel Shutoff

Cooling System

• Closed Coolant Recovery System

• UV/Ozone Resistant Hoses

• Factory-Installed Radiator

• 50/50 Ethylene Glycol Antifreeze

• Radiator Drain Extension

Electrical System

• Battery Charging Alternator

• Battery Cables

• Battery Tray

• Rubber-Booted Engine Electrical Connections

• Solenoid Activated Starter Motor

ALTERNATOR SYSTEM

• UL2200 GENprotect™

• Class H Insulation Material

• 2/3 Pitch

• Skewed Stator

• Permanent Magnet Excitation

• Sealed Bearing

• Amortisseur Winding

• Full Load Capacity Alternator

GENERATOR SET

• Internal Genset Vibration Isolation

• Separation of Circuits - High/Low Voltage

• Separation of Circuits - Multiple Breakers

• Wrapped Exhaust Piping

• Standard Factory Testing

• 2 Year Limited Warranty (Standby and Demand

Response Rated Units)

• 1 Year Limited Warranty (Prime Rated Units)

• Silencer Mounted in the Discharge Hood

(Enclosed Units Only)

• Ready to Accept Full Load in <10 Seconds

ENCLOSURE (If Selected)

• Rust-Proof Fasteners with Nylon Washers to Protect Finish

• High Performance Sound-Absorbing Material (Sound Attenuated Enclosures)

• Gasketed Doors

• Upward Facing Discharge Hood (Radiator and Exhaust)

• Stainless Steel Lift Off Door Hinges

• Stainless Steel Lockable Handles

• RhinoCoat™ - Textured Polyester Powder Coat

STANDARD FEATURES

EPA Certified Stationary Emergency and Non-Emergency

SP

EC

S H

EE

T

DEMAND RESPONSE READYCONFIGURABLE OPTIONS

ENGINE SYSTEM

○ Engine Coolant Heater

○ Baseframe Cover/Rodent Guard

○ 2 Stage Air Cleaner

○ Oil Heater

○ Air Filter Restriction Indicator

○ Radiator Stone Guard (Open Set Only)

○ Level 1 Fan and Belt Guards (Enclosed Units Only)

FUEL SYSTEM

○ NPT Flexible Fuel Line

ELECTRICAL SYSTEM

○ 10A UL Listed Battery Charger

○ Battery Warmer

ALTERNATOR SYSTEM

○ Alternator Upsizing

○ Anti-Condensation Heater

○ Tropical Coating

CIRCUIT BREAKER OPTIONS

○ Main Line Circuit Breaker

○ 2nd Main Line Circuit Breaker

○ Shunt Trip and Auxiliary Contact

○ Electronic Trip Breakers

GENERATOR SET

○ Demand Response Rating

○ Extended Factory Testing (3-Phase Only)

○ 12 Position Load Center

○ Vapor Recovery Heater

ENCLOSURE

○ Weather Protected Enclosure

○ Level 1 Sound Attenuated

○ Level 2 Sound Attenuated

○ Level 2 Sound Attenuated with Motorized Dampers

○ Level 3 Sound Attenuated (Steel Only)

○ Steel Enclosure

○ Aluminum Enclosure

○ Up to 200 MPH Wind Load Rating (Contact Factory for Availability)

○ AC/DC Enclosure Lighting Kit

○ Enclosure Heaters (with Motorized Dampers Only)

○ IBC Certification

○ Door Open Alarm Switch

CONTROL SYSTEM

○ NFPA 110 Level 1 Compliant 21-Light Remote Annunciator

○ Remote Relay Assembly (8 or 16)

○ Remote E-Stop (Break Glass-Type, Surface Mount)

○ Remote E-Stop (Red Mushroom-Type, Surface Mount)

○ Remote E-Stop (Red Mushroom-Type, Flush Mount)

○ 10A Engine Run Relay

○ Ground Fault Annunciator

○ 100 dB Alarm Horn

○ Damper Alarm Contacts (with Motorized Dampers Only)

○ 120V GFCI and 240V Outlets

WARRANTY (Standby Gensets Only)

○ 2 Year Extended Limited Warranty

○ 5 Year Limited Warranty

○ 5 Year Extended Limited Warranty

○ 7 Year Extended Limited Warranty

○ 10 Year Extended Limited Warranty

ENGINEERED OPTIONS

ENGINE SYSTEM

○ Fluid Containment Pans

CONTROL SYSTEM

○ Battery Disconnect Switch

ALTERNATOR SYSTEM

○ 3rd Main Line Circuit Breaker

○ 4th Breaker System

GENERATOR SET

○ Special Testing

○ Battery Box

EPA Certified Stationary Emergency and Non-Emergency

SP

EC

S H

EE

T

DEMAND RESPONSE READY

General

Make Generac

Cylinder # 6

Type In-line

Displacement - in3 (L) 864.71 (14.2)

Bore - in (mm) 5.31 (135)

Stroke - in (mm) 6.50 (165)

Compression Ratio 9.5:1

Intake Air Method Turbocharged/Aftercooled

Number of Main Bearings 7

Connecting Rods Steel Alloy

Cylinder Head Cast Iron GT250, OHV

Cylinder Liners Ductile Iron

Ignition Electronic

Piston Type Aluminum

Crankshaft Type Ductile Iron

Lifter Type Solid

Intake Valve Material Special Heat-Resistant Steel

Exhaust Valve Material High Temp Steel Alloy

Hardened Valve Seats High Temp Steel Alloy

Engine Governing

Governor Electronic

Frequency Regulation (Steady State) ±0.25%

Lubrication System

Oil Pump Type Gear

Oil Filter Type Full-Flow with Cartridge

Crankcase Capacity - qt (L) 36.2 (34.3)

Cooling System

Cooling System Type Pressurized Closed Recovery

Fan Type Pusher

Fan Speed - RPM 1,894

Fan Diameter - in (mm) 34 (864)

Fuel System

Fuel Type Natural Gas

Carburetor Down Draft

Secondary Fuel Regulator Standard

Fuel Shut Off Solenoid Standard

Operating Fuel Pressure - in H2O (kPa) 7 - 11 (1.7 - 2.7)

Engine Electrical System

System Voltage 24 VDC

Battery Charger Alternator 57.5 A

Battery Size See Battery Index 0161970SBY

Battery Voltage 24 VDC

Ground Polarity Negative

APPLICATION AND ENGINEERING DATA

ENGINE SPECIFICATIONS

ALTERNATOR SPECIFICATIONS

Standard Model K0300124Y21

Poles 4

Field Type Revolving

Insulation Class - Rotor H

Insulation Class - Stator H

Total Harmonic Distortion <5% (3-Phase)

Telephone Interference Factor (TIF) <50

Standard Excitation Permanent Magnet

Bearings Sealed Ball

Coupling Direct via Flexible Disc

Prototype Short Circuit Test Yes

Voltage Regulator Type Full Digital

Number of Sensed Phases All

Regulation Accuracy (Steady State) ±0.25%

EPA Certified Stationary Emergency and Non-Emergency

SP

EC

S H

EE

T

DEMAND RESPONSE READY

** Refer to “Emissions Data Sheet” for maximum bHP for EPA and SCAQMD permitting purposes.

Deration – Operational characteristics consider maximum ambient conditions. Derate factors may apply under atypical site conditions.

Please contact a Generac Power Systems Industrial Dealer for additional details. All performance ratings in accordance with ISO3046, BS5514, ISO8528, and DIN6271 standards.

Standby - See Bulletin 0187500SSB Demand Response - See Bulletin 10000018250 Prime - See Bulletin 0187510SSB

POWER RATINGS - NATURAL GAS

Standby/Demand Response Prime

Three-Phase 120/208 VAC @0.8pf 275 kW/343.8 kVA Amps: 955 248 kW/309.4 kVA Amps: 860

Three-Phase 120/240 VAC @0.8pf 275 kW/343.8 kVA Amps: 828 248 kW/309.4 kVA Amps: 745

Three-Phase 277/480 VAC @0.8pf 275 kW/343.8 kVA Amps: 414 248 kW/309.4 kVA Amps: 373

Three-Phase 346/600 VAC @0.8pf 275 kW/343.8 kVA Amps: 331 248 kW/309.4 kVA Amps: 298

MOTOR STARTING CAPABILITIES (skVA) skVA vs. Voltage Dip

277/480 VAC 30% 277/480 VAC 30%

K0300124Y21 790 K0300124Y21 609

FUEL CONSUMPTION RATES*

Natural Gas – scfh (m3/hr)

Percent Load Standby/Demand Response Prime

25% 1,080 (30.6) 1,020 (28.9)

50% 1,800 (51.0) 1,620 (45.9)

75% 2,640 (74.8) 2,400 (68.0)

100% 3,240 (91.7) 3,000 (84.9)

* Fuel supply installation must accommodate fuel consumption rates at 100% load.

COOLING

Standby/Demand Response Prime

Air Flow (Fan Air Flow Across Radiator) scfm (m3/min) 15,946 (452) 15,946 (452)

Coolant Flow gpm (Lpm) 90 (340.7) 90 (340.7)

Coolant System Capacity gal (L) 15 (54.9) 15 (54.9)

Maximum Operating Ambient Temperature °F (°C) 122 (50) 122 (50)

Maximum Operating Ambient Temperature (Before Derate) See Bulletin No. 0199270SSD

Maximum Radiator Backpressure in H2O (kPa) 0.5 (0.12) 0.5 (0.12)

COMBUSTION AIR REQUIREMENTS

Standby/Demand Response Prime

Flow at Rated Power - scfm (m3/min) 514 (14.6) 480 (13.6)

ENGINE EXHAUST

Standby/Demand

Response Prime

Standby/Demand Response

Prime

Rated Engine Speed RPM 1,800 1,800 Exhaust Flow (Rated Output) scfm (m3/min) 1,985 (56) 1,670 (47)

Horsepower at Rated kW** hp 409 369 Max. Backpressure (Post Silencer) inHg (kPa) 0.75 (2.54) 0.75 (2.54)

Piston Speed ft/min (m/min) 1,950 (594) 1,950 (594) Exhaust Temp (Rated Output - Post Silencer) °F (°C) 1,385 (752) 1,355 (735)

BMEP psi (kPa) 208 (1,433) 187 (1,292)

OPERATING DATA

EPA Certified Stationary Emergency and Non-Emergency

SP

EC

S H

EE

T

DEMAND RESPONSE READY

YOUR FACTORY RECOGNIZED GENERAC INDUSTRIAL DEALER

Specification characteristics may change without notice. Please contact a Generac Power Systems Industrial Dealer for detailed installation drawings.

* All measurements are approximate and for estimation purposes only.

Part No. 10000039025 Rev. B 02/07/2020

Generac Power Systems, Inc. | P.O. Box 8 | Waukesha, WI 53189 P: (262) 544-4811 ©2020 Generac Power Systems, Inc. All rights reserved. All specifications are subject to change without notice.

DIMENSIONS AND WEIGHTS*

OPEN SET (Includes Exhaust Flex) L x W x H - in (mm) 136.0 (3,454) x 57.1 (1,450) x 67.9 (1,725)

Weight - lbs (kg) 6,200 - 6,587 (2,812 - 2,987)

WEATHER PROTECTED ENCLOSURE

L x W x H - in (mm) 174.7 (4,437) x 57.5 (1,461) x 77.8 (1,976)

Weight - lbs (kg) Steel: 7,535 - 7,919 (3,417 - 3,591) Aluminum: 6,978 - 7,359 (3,165 - 3,337)

LEVEL 1 SOUND ATTENUATED ENCLOSURE

L x W x H - in (mm) 200.2 (5,085) x 57.5 (1,461) x 77.8 (1,976)

Weight - lbs (kg) Steel: 7,770 - 8,273 (3,524 - 3,752) Aluminum: 7,176 - 7,625 (3,254 - 3,458)

LEVEL 2 SOUND ATTENUATED ENCLOSURE

L x W x H - in (mm) 180.6 (4,587) x 57.5 (1,461) x 111.3 (2,827)

Weight - lbs (kg) Steel: 8,804 - 9,188 (3,993 - 4,167) Aluminum: 7,423 - 7,870 (3,366 - 3,569)

LEVEL 3 SOUND ATTENUATED ENCLOSURE

L x W x H - in (mm) 207.3 (5,265) x 63.7 (1,618) x 128.9 (3,274)

Weight - lbs (kg) 10,718 - 11,080 (4,861 - 5,025)

L

L

L

L

L

W

W

W

W

W

H

H

H

H

SD275 | 10.3L | 275 kW

INDUSTRIAL DIESEL GENERATOR SET

EPA Certified Stationary Emergency

SP

EC

S

HE

ET

Powering Ahead

For over 60 years, Generac has provided innovative design and superior manufacturing.

Generac ensures superior quality by designing and manufacturing most of its generator components, including alternators, enclosures and base tanks, control systems and communications software.

Generac gensets utilize a wide variety of options, configurations and arrangements, allowing us to meet the standby power needs of practically every application.

Generac searched globally to ensure the most reliable engines power our generators. We choose only engines that have already been proven in heavy-duty industrial applications under adverse conditions.

Generac is committed to ensuring our customers’ service support continues after their generator purchase.

Codes and Standards Not all codes and standards apply to all configurations. Contact factory for details.

UL2200, UL6200, UL1236, UL489,

UL142

CSA C22.2, ULC S601

BS5514 and DIN 6271

SAE J1349

NFPA 37, 70, 99, 110

NEC700, 701, 702, 708

ISO 3046, 7637, 8528, 9001

NEMA ICS10, MG1, 250, ICS6, AB1

ANSI C62.41

IBC 2009, CBC 2010, IBC 2012,

ASCE 7-05, ASCE 7-10, ICC-ES AC-

156 (2012)

TM

Image used for illustration purposes only

Standby Power Rating 275 kW, 344 kVA, 60 Hz

Prime Power Rating* 248 kW, 309 kVA, 60 Hz

*EPA Certified Prime ratings are not available in the US or its Territories

EPA Certified Stationary Emergency

SP

EC

S

HE

ET

CONTROL SYSTEM

Digital H Control Panel- Dual 4x20 Display

Program Functions

• Programmable Crank Limiter

• 7-Day Programmable Exerciser

• Special Applications Programmable Logic Controller

• RS-232/485 Communications

• All Phase Sensing Digital Voltage Regulator

• 2-Wire Start Capability

• Date/Time Fault History (Event Log)

• Isochronous Governor Control

• Waterproof/Sealed Connectors

• Audible Alarms and Shutdowns

• Not in Auto (Flashing Light)

• Auto/Off/Manual Switch

• E-Stop (Red Mushroom-Type)

• NFPA110 Level I and II (Programmable)

• Customizable Alarms, Warnings, and Events

• Modbus® Protocol

• Predictive Maintenance Algorithm

• Sealed Boards

• Password Parameter Adjustment Protection

• Single Point Ground

• 16 Channel Remote Trending

• 0.2 msec High Speed Remote Trending

• Alarm Information Automatically Annunciated on the Display

Full System Status Display

• Power Output (kW)

• Power Factor

• kW Hours, Total, and Last Run

• Real/Reactive/Apparent Power

• All Phase AC Voltage

• All Phase Currents

• Oil Pressure

• Coolant Temperature

• Coolant Level

• Engine Speed

• Battery Voltage

• Frequency

Alarms and Warnings

• Oil Pressure

• Coolant Temperature

• Coolant Level

• Engine Overspeed

• Battery Voltage

• Alarms and Warnings Time and Date Stamped

• Snap Shots of Key Operation Parameters During

Alarms and Warnings

• Alarms and Warnings Spelled Out (No Alarm Codes)

EMERGENCY

STOP

COMMON ALARM

AUTO OFF MAN.

Phase Volts Amps Hz =

SD EMERGENCY STOP Hi SD COOLANT LEVEL Lo Wr*BATTERY VOLTS Hi ACK More (1–3)

A–B

0.0 kW

B–C

C–A

NOT IN

AUTO

ALARM

HOME

MENU

ENTER

ENGINE SYSTEM

• Oil Drain Extension

• Level 1 Fan and Belt Guards (Open Set Only)

• Stainless Steel Flexible Exhaust Connection

• Factory Filled Oil and Coolant

• Radiator Duct Adapter (Open Set Only)

FUEL SYSTEM

• Fuel Lockoff Solenoid

• Primary Fuel Filter

COOLING SYSTEM

• Closed Coolant Recovery System

• UV/Ozone Resistant Hoses

• Factory-Installed Radiator

• Radiator Drain Extension

• 50/50 Ethylene Glycol Antifreeze

• Engine Coolant Heater

ELECTRICAL SYSTEM

• Battery Charging Alternator

• Battery Cables

• Battery Tray

• Rubber-Booted Engine Electrical Connections

• Solenoid Activated Starter Motor

ALTERNATOR SYSTEM

• UL2200 GENprotect™

• 12 Leads (3-Phase, Non 600V)

• Class H Insulation Material

• Vented Rotor

• 2/3 Pitch

• Skewed Stator

• Auxiliary Voltage Regulator Power Winding

• Permanent Magnet Excitation

• Sealed Bearing

• Automated Manufacturing (Winding, Insertion, Lacing, Varnishing)

• Rotor Dynamically Spin Balanced

• Amortisseur Winding

• Full Load Capacity Alternator

• Protective Thermal Switch

GENERATOR SET

• Internal Genset Vibration Isolation

• Separation of Circuits - High/Low Voltage

• Separation of Circuits - Multiple Breakers

• Wrapped Exhaust Piping

• Standard Factory Testing

• 2 Year Limited Warranty (Standby Rated Units)

• 1 Year Limited Warranty (Prime Rated Units)

• Silencer Mounted in the Discharge Hood

(Enclosed Unit Only)

ENCLOSURE (If Selected)

• Rust-Proof Fasteners with Nylon Washers to Protect Finish

• High Performance Sound-Absorbing Material (Sound Attenuated Enclosures)

• Gasketed Doors

• Upward Facing Discharge Hoods (Radiator and Exhaust)

• Stainless Steel Lift Off Door Hinges

• Stainless Steel Lockable Handles

• RhinoCoat™ - Textured Polyester Powder Coat Paint

FUEL TANKS (If Selected)

• UL 142/ULC S601

• Double Wall

• Vents

• Sloped Top

• Sloped Bottom

• Factory Pressure Tested - 2 psi

• Rupture Basin Alarm

• Fuel Level

• Check Valve In Supply and Return Lines

• RhinoCoat™ - Textured Polyester Powder Coat Paint

• Stainless Steel Hardware

STANDARD FEATURES

EPA Certified Stationary Emergency

SP

EC

S

HE

ET

CONFIGURABLE OPTIONS

ENGINE SYSTEM

○ Block Heater

○ Oil Heater

○ Level 1 Fan and Belt Guards (Enclosed Units Only)

○ Heavy Duty Air Cleaner

○ Radiator Stone Guard

○ Air Filter Restriction Indicator

FUEL SYSTEM

○ NPT Flexible Fuel Line

ELECTRICAL SYSTEM

○ 10A UL Listed Battery Charger

○ Battery Warmer

ALTERNATOR SYSTEM

○ Alternator Upsizing

○ Anti-Condensation Heater

○ Tropical Coating

CIRCUIT BREAKER OPTIONS

○ Main Line Circuit Breaker

○ 2nd Main Line Circuit Breaker

○ Shunt Trip and Auxiliary Contact

○ Electronic Trip Breakers

GENERATOR SET

○ Extended Factory Testing

○ IBC Seismic Certification

○ 12 Position Load Center

○ Spring Vibration Isolators

ENCLOSURE

○ Weather Protected Enclosure

○ Level 1 Sound Attenuated

○ Level 2 Sound Attenuated

○ Level 2 Sound Attenuated with Motorized Dampers

○ Steel Enclosure

○ Aluminum Enclosure

○ Door Open Alarm Horn

○ Up to 200 MPH Wind Load Rating (Contact Factory for Availability)

○ AC/DC Enclosure Lighting Kit

○ Enclosure Heater (with Motorized Dampers Only)

FUEL TANKS (Size on Last Page)

○ 8 in (203.2 mm) Fill Extension

○ 13 in (330.2 mm) Fill Extension

○ 19 in (482.6 mm) Fill Extension

CONTROL SYSTEM

○ NFPA 110 Compliant 21-Light Remote Annunciator

○ Remote Relay Assembly (8 or 16)

○ Oil Temperature Sender with Indication Alarm

○ Remote E-Stop (Break Glass-Type, Surface Mount)

○ Remote E-Stop (Red Mushroom-Type, Surface Mount)

○ Remote E-Stop (Red Mushroom-Type, Flush Mount)

○ 100 dB Alarm Horn

○ Ground Fault Annunciator

○ 120 V GFCI and 240 Outlet

○ Flush Mount Annunciator Kit

○ Remote Communication - Modem

○ 10A Engine Run Relay

○ Damper Alarm Contacts (with Motorized

Dampers Only)

WARRANTY

○ 2 Year Extended Limited Warranty

○ 5 Year Limited Warranty

○ 5 Year Extended Limited Warranty

○ 7 Year Extended Limited Warranty

○ 10 Year Extended Limited Warranty

ENGINEERED OPTIONS

ENGINE SYSTEM

○ Coolant Heater Ball Valves

○ Fluid Containment Pan

CONTROL SYSTEM

○ Spare Inputs (x4) / Outputs (x4)

○ Battery Disconnect Switch

ALTERNATOR SYSTEM

○ 3rd Breaker System

GENERATOR SET

○ Special Testing

FUEL TANKS

○ Overfill Protection Valve

○ UL2085 Tank

○ Special Fuel Tanks

○ Vent Extensions

EPA Certified Stationary Emergency

SP

EC

S

HE

ET

General

Make Iveco/FPT

EPA Emissions Compliance Stationary Emergency

EPA Emissions Reference See Emission Data Sheet

Cylinder # 6

Type In-Line

Displacement - in3 (L) 628.54 (10.3)

Bore - in (mm) 4.92 (125)

Stroke - in (mm) 5.51 (140)

Compression Ratio 16.5:1

Intake Air Method Turbocharged/Aftercooled

Cylinder Head 4-Valve

Piston Type Aluminum

Crankshaft Type Dropped Forged Steel

Engine Governing

Governor Electronic Isochronous

Frequency Regulation (Steady State) ±0.25%

Lubrication System

Oil Pump Type Gear

Oil Filter Type Full Flow

Crankcase Capacity - qt (L) 31.68 (30)

Cooling System

Cooling System Type Closed Recovery

Water Pump Type Pre-Lubed, Self Sealing

Fan Type Pusher

Fan Speed - RPM 2,250

Fan Diameter - in (mm) 30 (762)

Fuel System

Fuel Type Ultra Low Sulfur Diesel Fuel #2

Fuel Specifications ASTM

Fuel Filtering (Microns) 5

Fuel Inject Pump Electronic

Fuel Pump Type Engine Driven Gear

Injector Type Common Rail

Engine Type Direct Injection

Fuel Supply Line - in (mm) 0.5 (12.7) NPT

Fuel Return Line - in (mm) 0.5 (12.7) NPT

Engine Electrical System

System Voltage 24 VDC

Battery Charger Alternator Standard

Battery Size See Battery Index 0161970SBY

Battery Voltage (2)-12 VDC

Ground Polarity Negative

APPLICATION AND ENGINEERING DATA

ENGINE SPECIFICATIONS

ALTERNATOR SPECIFICATIONS

Standard Model K0275124Y21

Poles 4

Field Type Revolving

Insulation Class - Rotor H

Insulation Class - Stator H

Total Harmonic Distortion <5%

Telephone Interference Factor (TIF) <50

Standard Excitation Permanent Magnet

Bearings Single Sealed Cartridge

Coupling Direct via Flexible Disc

Prototype Short Circuit Test Yes

Voltage Regulator Type Digital

Number of Sensed Phases All

Regulation Accuracy (Steady State) ±0.25%

EPA Certified Stationary Emergency

SP

EC

S

HE

ET

** Refer to “Emissions Data Sheet” for maximum bHP for EPA and SCAQMD permitting purposes.

Deration – Operational characteristics consider maximum ambient conditions. Derate factors may apply under atypical site conditions.

Please contact a Generac Power Systems Industrial Dealer for additional details. All performance ratings in accordance with ISO3046, BS5514, ISO8528, and DIN6271 standards.

Standby - See Bulletin 10000018933 Prime - See Bulletin 10000018926

POWER RATINGS

Standby

Three-Phase 120/208 VAC @0.8pf 275 kW Amps: 954

Three-Phase 120/240 VAC @0.8pf 275 kW Amps: 827

Three-Phase 277/480 VAC @0.8pf 275 kW Amps: 414

Three-Phase 346/600 VAC @0.8pf 275 kW Amps: 331

MOTOR STARTING CAPABILITIES (skVA)

SkVA vs. Voltage Dip

277/480 VAC 30% 208/240 VAC 30%

K0275124Y21 790 K0275124Y21 609

K0350124Y21 1,001 K0350124Y21 801

K0400124Y21 953 K0400124Y21 717

FUEL CONSUMPTION RATES*

Diesel - gph (Lph)

Fuel Pump Lift - ft (m) Percent Load Standby

3 (1) 25% 6.8 (25.7)

50% 11.7 (44.2)

Total Fuel Pump Flow (Combustion + Return) - gph (Lph) 75% 15.8 (59.8)

31 (117) 100% 19.6 (74.2)

* Fuel supply installation must accommodate fuel consumption rates at 100% load.

COOLING

Standby

Coolant Flow gpm (Lpm) 95 (360)

Coolant System Capacity gal (L) 13.0 (49.2)

Heat Rejection to Coolant BTU/hr (kW) 722,612 (211.8)

Inlet Air cfm (m3/hr) 14,505 (411)

Maximum Operating Radiator Air Temperature °F (°C) 110 (43.3)

Maximum Ambient Temperature (Before Derate) See Bulletin No. 0199280SSD

Maximum Additional Radiator Backpressure in H2O (kPa) 0.5 (0.12)

COMBUSTION AIR REQUIREMENTS

Standby

Flow at Rated Power - cfm (m3/min) 780 (22.1)

ENGINE EXHAUST

Standby Standby

Rated Engine Speed RPM 1,800 Exhaust Flow (Rated Output) cfm (m3/min) 2,050 (58.1)

Horsepower at Rated kW** hp 449 Maximum Allowable Backpressure inHg (kPa) 1.5 (5.1)

Piston Speed ft/min (m/min) 1,654 (504) Exhaust Temperature (Rated Output) °F (°C) 950 (510)

BMEP psi (kPa) 308 (2,124)

OPERATING DATA

EPA Certified Stationary Emergency

SP

EC

S

HE

ET

Part No. 0185610SBY Rev. F 07/13/2021

Generac Power Systems, Inc. | P.O.Box 8 | Waukesha, WI 53189 P: (262) 544-4811 ©2021 Generac Power Systems, Inc. All rights reserved. All specifications are subject to change without notice.

* All measurements are approximate and for estimation purposes only. Specification characteristics may change without notice. Please contact a Generac Power Systems Industrial Dealer for detailed installation drawings.

DIMENSIONS AND WEIGHTS*

OPEN SET

Run Time

- Hours

Usable Capacity

- Gal (L)

L x W x H - in (mm) Weight - lbs (kg)

No Tank - 137.5 (3,493) x 57.6 (1,463) x 67.8 (1,722) 6,121 - 7,457 (2,776 - 3,382)

9 183 (693) 137.5 (3,493) x 57.6 (1,463) x 80.8 (2,052) 7,069 - 8,405 (3,206 - 3,812)

22 438 (1,659) 137.5 (3,493) x 57.6 (1,463) x 92.8 (2,357) 7,381 - 8,717 (3,348 - 3,954)

35 693 (2,624) 137.5 (3,493) x 57.6 (1,463) x 104.8 (2,662) 7,717 - 9,053 (3,500 - 4,106)

48 946 (3,581) 208.3 (5,220) x 57.6 (1,463) x 122.0 (3,100) 9,146 - 10,482 (4,148 - 4,754)

67 1,325 (5,015) 277.8 (7,055) x 57.6 (1,463) x 120.9 (3,072) 10,161 - 11,497 (4,659 - 5,265)

WEATHER PROTECTED ENCLOSURE

Run Time

- Hours

Usable Capacity

- Gal (L)

L x W x H - in (mm) Weight - lbs (kg) Enclosure Only

Steel Aluminum

No Tank - 174.7 (4,437) x 53.0 (1,346) x 77.8 (1,977)

1,521 (690) 727 (330)

9 183 (693) 174.7 (4,437) x 53.0 (1,346) x 90.8 (2,307)

22 438 (1,659) 174.7 (4,437) x 53.0 (1,346) x 102.8 (2,612)

35 693 (2,624) 174.7 (4,437) x 53.0 (1,346) x 114.8 (2,917)

48 946 (3,581) 208.3 (5,220) x 53.0 (1,346) x 132.0 (3,355)

67 1,325 (5,015) 277.8 (7,055) x 53.0 (1,346) x 130.9 (3,327)

LEVEL 1 SOUND ATTENUATED ENCLOSURE

Run Time

- Hours

Usable Capacity

- Gal (L)

L x W x H - in (mm) Weight - lbs (kg) Enclosure Only

Steel Aluminum

No Tank - 200.2 (5,084) x 57.5 (1,460) x 90.8 (2,306)

1,984 (900) 926 (421)

9 183 (693) 200.2 (5,084) x 57.5 (1,460) x 90.8 (2,306)

22 438 (1,659) 200.2 (5,084) x 57.5 (1,460) x 102.8 (2,611)

35 693 (2,624) 200.2 (5,084) x 57.5 (1,460) x 114.8 (2,916)

48 946 (3,581) 200.2 (5,084) x 57.5 (1,460) x 132.0 (3,354)

67 1,325 (5,015) 277.8 (7,055) x 57.5 (1,460) x 130.9 (3,326)

LEVEL 2 SOUND ATTENUATED ENCLOSURE

Run Time

- Hours

Usable Capacity

- Gal (L)

L x W x H - in (mm) Weight - lbs (kg) Enclosure Only

Steel Aluminum

No Tank - 180.7 (4,588) x 57.5 (1,460) x 107.3 (2,725)

2,557 (1,160) 1,173 (531)

9 183 (693) 180.7 (4,588) x 57.5 (1,460) x 120.3 (3,055)

22 438 (1,659) 180.7 (4,588) x 57.5 (1,460) x 132.3 (3,360)

35 693 (2,624) 180.7 (4,588) x 57.5 (1,460) x 144.3 (3,665)

48 946 (3,581) 180.7 (4,588) x 57.5 (1,460) x 161.5 (4,103)

6…