B08_Att_4_Appendix_A_SD_Update_Add_BEBs.pdf
PDF 18 MB Posted
- Attached to
- GRCA 250440 Shuttle Bus Facility Federal contract opportunity
- Solicitation number
- 140P2024R0028
About this file
This document appears to be an Appendix A to the Statement of Objectives (SOO) for the GRCA 250440 Shuttle Bus Facility solicitation. It provides an update to the Standard Design (SD) for the shuttle bus facilities to include Battery Electric Buses (BEBs).
The key details are: The solicitation number is 140P2024R0028 issued by the National Park Service. The update to the SOO Appendix A details the requirements for incorporating BEBs into the shuttle bus facilities design, including charging infrastructure, parking, and other related specifications. This is likely in response to federal fleet electrification initiatives. No other details on the overall solicitation, such as response dates, award information, or set-asides are provided in this specific document.
View the file
Other files for this federal contract opportunity
Show all 23
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
o o o o o o o o o o o o o o o o
8 6
8 6
.67
3.50
8.47
.2
2.20
2.43
2.2
GRCA Bus Maintenance – SD Update
GRCA Bus SD Update Preferred Alternative – Civil Summary
The following summarizes changes from the original Schematic Design Basis of Design narrative to accommodate Battery Electric Buses (BEBs).
• Increase bus parking paving limits from previous SD layout by approximately 6,220 SF (previous SD layout had 105,590 SF of bus parking area). Total bus parking paving would be approximately
111,810 SF.
o Provide concrete paving at bus parking stalls: 27,220 SF concrete – 8” reinforced concrete at
4500 psi, reinforcement assumed to be #4 @ 18” o.c.
o Provide asphalt paving for bus drive aisles: 84,590 SF asphalt – 6” asphalt over 9” aggregate base course o Providing concrete pavement at bus parking stalls is preferred for pavement longevity due to impacts that asphalt might experience from parked and/or turning buses.
• Maintain bus parking stall widths at 14-feet and add a 2-foot-wide painted island between stalls.
Three stalls would be at a 13-feet width to accommodate column locations.
o Maintaining the 14-foot stall width and adding a 2-foot-wide painted island between stalls would provide clearance around parked buses for staff movement.
• 10 canopy mounted bus charging stations within main bus parking area.
o Bus charging stations are being shown at the north end of the bus parking area to allow for expansion of the bus parking further south if desired in the future.
• 1 bus ground mounted charging station within parallel bus parking area.
• 1 bus charging station within bus maintenance facility building.
• Increase fencing limits from previous SD layout by approximately 190 LF (previous SD layout had
1,520 LF of fencing). Total fencing would be approximately 1,710 LF.
• Expand detention pond along west side of bus parking area for increased pavement area.
• Would result in an additional 15 trees being removed and an additional 7,330 SF of revegetation for expanded pavement limits and fencing.
• Decrease in utility yard paving limits from previous SD layout by approximately 575 SF (previous SD layout had 1,700 SF for utility yard). Total utility yard paving would be approximately 1,125 SF.
• Conduit routing to charging stations:
o Approximately 3610 LF of 1-inch and 3610 LF of 2-inch electrical conduit to proposed charging stations.
o Approximately 5800 LF of 1-inch and 5800 LF of 2-inch electrical conduit placed for future charging stations.
o Total of 9410 LF of 1-inch and 9410 LF of 2-inch electrical conduit.
o Refer to electrical narrative for additional information.
• Provide approximately 600 LF new gas line from the natural gas fueling station to utility yard.
• Refer to structural narrative for information on canopy and piers.
Articulated Bus Counterclockwise Turn
Articulated Bus Clockwise Turn
40-ft Bus Counterclockwise Turn
40-ft Bus Clockwise Turn
Battery Electric Bus Design
It is anticipated that Battery Electric Buses (BEB’s) will be provided to support (2) bus routes along the
Canyon. It is anticipated (10) dedicated charging stations will be provided in the new bus parking lot as well as (1) dedicated charging station located at an alternative location on the site, and (1) located within a bus maintenance bay.
Base Bid:
For the purposes of this project, please anticipate the following which is based on Proterra charging stations and control systems.
The bus charging infrastructure is anticipated to be served by a new pad mount 480V/3PH transformer which will be located in the utility yard on the south side of the Maintenance Building. APS is to provide and install the utility transformer and the incoming primary cable, the EC shall be responsible for all trenching and conduit. EC is to provide and install the pad and all secondary conduit and conductors. APS is to provide the CT Meter, and the EC is to provide the CT Enclosure with meter housing, and all make all connections to the meter.
It is anticipated that (4) parallel runs of 3-1/2” conduit will be provided from the utility transformer to an
800A, 480/277V fused service disconnect. Two of the conduits will be provided with 4#500MCM copper conductors. The disconnect will then feed into a 800A automatic transfer switch (see generator section below) and then into a 800A electrical distribution panel. The electrical distribution panel will feed (1)
30kVA 480:208V step-down transformer and (3) Power Control System (PCS) cabinets which are each capable of controlling (4) bus charging dispensers. The 30kVA transformer will feed a 100A, 120/208V electrical panel which will feed the miscellaneous low voltage electrical loads including receptacles and generator equipment loads. The electrical connection to each PCS is anticipated to be 200A therefore requiring (1) 2-1/2” conduit with 4#3/0 AWG conductors and 1#6AWG grounding conductor. Room will be provided to expand the number of PCS cabinets to a total of (12) to account for potential future expansion of the bus charging dispenser. The electrical distribution panel shall also be equipped with an externally mounted listed surge suppression device.
An additional bus charging station will be provided within one of the maintenance building’s Work Bays. It is anticipated that (1) 75kVA 208:480V step up transformer will be required to provide the required voltage for the charger. This transformer will be fed on the primary side by 3#250MCM conductors and 1#4 ground.
The secondary side will have 4#1AWG conductors and (1) 1#6 ground and will feed a 100A disconnect. This disconnect will then feed into the stand-alone bus charger.
From each PCS location, the contractor shall provide (1) 2” conduit for power and (1) 1” conduit for communications to each charging dispenser location. This alterative includes (10) canopy mounted, pantograph charge dispensers located above each bus and (1) pedestal mounted charging dispenser location for the remote bus charging location. Please refer to Civil drawings for locations of all (11) charging dispensers. Also provide (1) spare 2” conduit and (1) spare 1” conduit from future PCS locations out to each bus parking stall (31 total stalls) to provide infrastructure for future charging dispensers.
The PCS cabinets shall be provided with demand optimization capabilities which limit the number of buses charging at any given time to (5) busses and limit the demand to the electrical grid to 150kW.
Standby Generator:
To provide standby capacity beyond 60-90 minutes, it is anticipated that a 275kW standby generator will be required. Base bid shall consist of a natural gas generator which will require a new underground gas line to the nearby Fueling Station. A bid alternate shall also be provided to provide a diesel generator in lieu of a natural gas generator. A diesel generator would require a 24-hour base tank located beneath the generator and the gas line from the Fueling Station will not be required. The final selection will be made during the DD
Phase of design after further discussion and coordination with NPS staff. Refer to civil drawings for anticipated gas-line routing. The generator shall provide standby power to a 400A automatic transfer switch
(ATS-1) that gets normal power from the 400A utility service disconnect, and ATS-1 shall feed into the electrical distribution panel indicated above. The size of this genset is anticipated to be approximately
175”L x 58”W x 80” high. Three feet, four inches of clearance is required on all sides around the generator.
This is for the standard enclosure, if higher level acoustic ratings are required, the generator will grow in length and height. The average sound pressure level at 7 meters for each generator running at full load can be found in the table below:
Generator Type
Standard dB(A)
Level 1 dB(A)
Level 2 dB(A)
Diesel 84.2 78.1 75.2
Natural Gas
83.2 77.7 74.4
Solar Design
A preliminary investigation of the impact of implementing a solar PV system on the roof of the bus parking canopy, was done using the National Renewable Energy Laboratory (NREL) PV Watts Calculator (simulation) on-line program. The intent of the solar array would be to offset the operating costs of the BEB’s, these would not be used to directly charge the buses due to the fact that they will be out on routes throughout most of the daytime hours. The solar panel canopy footprint for the Preferred Alternative is anticipated to be 478-feet by 70-feet giving a total square footage of 33,460SF. Using an 80”x40” solar panel, an estimate of approximately 1,206 panels can fit on the structure and produce approximately 482.4kW of electricity or
701,483kWh/Year. Calculations were run using a panel lying flat on the roof, a 2” spacing is anticipated to allow for racking hardware, and a clear view of the sky. If actual conditions change, the electrical value of the system (show below) may decrease.
• Variables such as the potential build-up of snow are not accounted for in this initial study. These will impact the total annual production of the system, but further/detailed investigation is required to understand how much.
• Studies have shown that single axis rotation of solar panels provides and increased efficiency of 25 to 35 percent and dual-axis trackers provide an additional 5 to 10 percent. Adding trackers to the system adds anywhere from 40% to 60% to the total cost of the installation.
Electrical infrastructure for this installation is anticipated to consist of microinverters located at each solar panel which will convert DC power to AC power. These will feed back to a combiner panel which will be located on the canopy structure. This combiner panel will then feed back through a PV utility meter to an
800A/3P disconnect and then to an 800A/3P breaker located in the Main Distribution Panel. See attached one-line diagram for additional information.
Based on this study, the initial cost of the system would be on the order of $1,206,000.00 with an annual electrical value of $71,691.00. Payback would be roughly 16.8 years. The annual electrical value is estimated using an average retail electricity rate of 0.102$/kWh. This number may vary depending on actual demand billing, usage, and utility rates.
Arizona does offer some solar PV incentive and rebate programs. This will be investigated as we move further into the design process.
An energy demand analysis was performed by the NPS for the anticipated bus fleet. The analysis was performed with the assumption that (8) buses will be in service on a typical day, two of which will have a consumption of 129kWh per day and six of which will have a consumption of 272kWh per day. These numbers are derived based on route information and the scheduled bus services and have been used as a baseline for determining the anticipated solar offset.
As mentioned above, the annual production of the solar array is anticipated to be 701,483kWh. Using the numbers from the fleet analysis, the yearly consumption for charging the buses is anticipated to be
689,850kWh. This shows that on a typical day, the solar array will be able to produce 102% of the needed load. There will be days where production is lower and utility power is needed however there will also be days where excess energy is provided back to the utility grid. Using a greenhouse gas equivalencies calculator provided by the EPA, an offset of 701,483kWh is equivalent to 497 metric tons of carbon dioxide or 549,468 pounds of coal burned.
Using an average retail electricity rate of 0.102$/kWh, without any solar offset, an average monthly electricity bill would be approximately $5,863. As mentioned above, the electricity rate will vary depending on actual demand billing, usage, and utility rates. This number is to be used for rough pricing only. Per the solar offset numbers stated above, on an average month with a fully sized solar array, the utility bill would be at or near zero with potential for the system to sell power back to the grid.
• Bid Option: An alternate investigation was performed using panels mounted at an optimal 36-degree tilt using a fixed mount system which provided approximately 284kW of electricity or 484,213kWh/Year. In this configuration 711 panels are able to fit on the structure and require a 2’8” gap between panels to avoid shadowing. Additional structural members will be required to achieve a 36-degree tilt, please refer to the structural narrative for more information. On a typical day, this configuration would be able to produce 70% of the needed load. Using a greenhouse gas equivalencies calculator provided by the EPA, an offset of 484,213kWh is equivalent to 343 metric tons of carbon dioxide or 379,282 pounds of coal burned. The initial cost of this system would be on the order of $711,000 with an annual electrical value of $49,487.00 and a payback of roughly 14.4 years.
Please see attached Solar PV calculation, showing the full characteristics and results of the study.
Revision to the Lightning Protection System Section of the Basis of Design Report:
Electrical Contractor to provide add-alternate pricing to provide and install a lightning protection system on both the Maintenance Building and Bus Canopy with an underwriter’s laboratories Master ‘C’ label.
Contractor shall coordinate all ground rod locations on roof with architect while developing submittals.
Submittals shall require full roof plans with all ground rod (and all other equipment) indicated for review prior to submittal approval. Careful consideration shall be made to conceal exposed conductors from public view, to the greatest extent possible.
���� !"#$%&!�!'!(�� )$*+*�,-$.,/0!/-�"), ./,1 )� !"*$)�()�(��,1$2+$%34���*5$ ")(�1, -�"+$ "&,/,"�$ �**�-.� !"*$ �"1
�"),/�� "� ,*$�"1$1!$"!�$/,0(,)�$'�/ �� !"*
2,�6,,"$%3$�,)&"!(!7 ,*$"!/$* �,8*.,) 0 )
)&�/�)�,/ *� )*$,9),.�$�*$/,./,*,"�,1$2+
%34���*5$ ".��*:$;!/$,9�-.(,<$%3$-!1�(,*
6 �&$ 2,��,/$ .,/0!/-�"),$ �/,$ "!�
1 00,/,"� ��,1$6 �& "$%34���*5$0/!-$(,**,/
.,/0!/- "7$-!1�(,*:$=!�&$>?@A$�"1$./ '��, )!-.�" ,*$./!' 1,$-!/,$*!.& *� )��,1$%3
-!1,( "7$�!!(*$B*�)&$�*$�&,$C+*�,-$D1' *!/
E!1,($��$&��.*#FF*�-:"/,(:7!'G$�&��$�((!6$0!/
-!/,$./,) *,$�"1$)!-.(,9$-!1,( "7$!0$%3
H&,$,9.,)�,1$/�"7,$ *$2�*,1$!"$IJ$+,�/*$!0
�)���($6,��&,/$1���$��$�&,$7 ',"$(!)�� !"
�"1$ *$ "�,"1,1$�!$./!' 1,$�"$ "1 )�� !"$!0
�&,$'�/ �� !"$+!�$- 7&�$*,,:$;!/$-!/, "0!/-�� !"<$.(,�*,$/,0,/$�!$�& *$>?@A$/,.!/�#
H&,$@//!/$?,.!/�:
K *)(� -,/#$H&,$%34���*5$E!1,($BLE!1,(LG
*$./!' 1,1$2+$�&,$>�� !"�($?,",6�2(, @",/7+$A�2!/��!/+$BL>?@ALG<$6& )&$ *
!.,/��,1$2+$�&,$D(( �"),$0!/$C�*�� "�2(, @",/7+<$AA�$BLD(( �"),LG$0!/$�&,$M:C:
K,.�/�-,"�$N0$@",/7+$BLKN@LG$�"1$-�+$2,
�*,1$0!/$�"+$.�/.!*,$6&��*!,',/:
H&,$"�-,*$KN@F>?@AFDAAOD>�@$*&�(($"!�
2,$�*,1$ "$�"+$/,./,*,"��� !"<$�1',/� * "7<
.�2( ) �+$!/$!�&,/$-�"",/$6&��*!,',/$�!
,"1!/*,$!/$./!-!�,$�"+$,"� �+$�&��$�1!.�*$!/
�*,*$�&,$E!1,(:$KN@F>?@AFDAAOD>�@$*&�((
"!�$./!' 1, �"+$ *�..!/�<$ )!"*�(� "7<$ �/� " "7$ !/
�** *��"),$!0$�"+$P "1$6 �&$/,7�/1$�!$�&,$�*, !0$�&,$E!1,($!/$�"+$�.1��,*<$/,' * !"*$!/
",6$',/* !"*$!0$�&,$E!1,(:
QNM$ DR?@@$ HN$ O>K@E>O;Q
KN@F>?@AFDAAOD>�@<$D>K$OHC$D;;OAODH@C<
N;;O�@?C<$ DR@>HC<$ D>K$ @E%ANQ@@C
DRDO>CH$ D>Q$ �ADOE$ N?$ K@ED>K<
O>�AMKO>R$ ?@DCN>D=A@$ DHHN?>@QCS
;@@C<$?@ADH@K$HN$QNM?$MC@<$?@AOD>�@<
N?$DKN%HON>$N;$HT@$ENK@A$;N?$D>Q
%M?%NC@$4TDHCN@3@?:$HT@$ENK@A$OC
%?N3OK@K$=Q$KN@F>?@AFDAAOD>�@$LDC$OCL
D>K$ D>Q$ @U%?@CC$ N?$ OE%AO@K
4D??D>HO@C<$ O>�AMKO>R$ =MH$ >NH
AOEOH@K$HN$HT@$OE%AO@K$4D??D>HO@C$N;
E@?�TD>HD=OAOHQ$D>K$;OH>@CC$;N?$D
%D?HO�MAD?$%M?%NC@$D?@$@U%?@CCAQ
KOC�ADOE@K:$ O>$ >N$ @3@>H$ CTDAA
KN@F>?@AFDAAOD>�@$=@$AOD=A@$;N?$D>Q
C%@�ODA<$O>KO?@�H$N?$�N>C@VM@>HODA
KDEDR@C$N?$D>Q$KDEDR@C$4TDHCN@3@?<
O>�AMKO>R$=MH$>NH$AOEOH@K$HN$�ADOEC
DCCN�ODH@K$4OHT$HT@$ANCC$N;$KDHD$N?
%?N;OHC<$4TO�T$EDQ$?@CMAH$;?NE$D>Q
D�HON>$O>$�N>H?D�H<$>@RAOR@>�@$N?
NHT@?$HN?HONMC$�ADOE$HTDH$D?OC@C$NMH
N;$N?$O>$�N>>@�HON>$4OHT$HT@$MC@$N?
%@?;N?ED>�@$N;$HT@$ENK@A:
H&,$,",/7+$!��.��$/�"7,$ *$2�*,1$!"
�"�(+* *$!0$IJ$+,�/*$!0$& *�!/ )�($6,��&,/
1���$0!/$",�/2+$<$�"1$ *$ "�,"1,1$�!$./!' 1, �"$ "1 )�� !"$!0$�&,$.!** 2(,$ "�,/�""��(
'�/ �2 ( �+$ "$7,",/�� !"$0!/$�$; 9,1$B!.,"
/�)PG$%3$*+*�,-$��$�& *$(!)�� !":
WXYZ[\]̂_̀abcdefghijklmj nopqrstuvqwvqtsxotyxz{rt|yust}}~����tqut�������t���twrytorxytzrxytq��pt�u�xq�uz�t
��ª�¢
«��©��¡ ¬ ®̄°±²̄ ®°² ̄
³¦́�©��¡ ®¬µµ ±¶°® µ ±°· ·
���̧� ¬̄±¶ ² °²± ²°±¶
£¹��� ²¬²¶ µ®°º̄ µ°̄̄
��¡ µ¬²̄ º±°®ºº º°² ±
«©�¦ º¬®¶ º±°¶¶ º°²µµ
«©�¡ ²¬µ̄ µ®°® º µ°±±
£©§©»� ²¬¶̄ ²±°®·² ²°̄µ®
�¦¹�¦� ¦́� ¬̄º· ²·°µ²· ²°®·
¼̧ ��́¦� ±¬̄² ·̄°¶µ °̄ ¶
½�¾¦� ¦́� ®¬®º ®µ°̄¶² ®°º®®
¿¦̧¦� ¦́� ¬µ® ®·°ºµ² ®° ̄º
£��©�� ¬̄®® µ¶·°±º® ª�µ·°²·
À�̧������������������Á�¦���Â�̧�����
�¦Ã©¦»�¦��À�̧����� ·���©���¦�Ä©»�����°�Å�����¤��¡��
�¦���¦��¿������©�̧¦ À��°�À��Æ�®²¬¶̄°�Ç·· ¬·± �¶¬®���
À����©�¦ ®²¬¶̄È�½
À��§��©�¦ ·· ¬·±È��
É̈ ��¡»�¦���¹¦̧�Â�̧�����»�ÊËussry��x�Ì
¿¤��¡»�¦����ͦ ±º ¬±���
���©�¦�Ρ¹¦ ��������
£���¡�Ρ¹¦ ³�Ϧ������Â���©��¢
£���¡�Î��� ¶È
£���¡�£Í��©�� ·º¶È
�¡»�¦��À�»»¦» ·±¬¶ºÐ
Á�¾¦��¦��¥ÂÂ�̧�¦�̧¡ ²Ð
¿¤����£¤���ͦ������ ·¬
£¾¦��§¦��¦�����¥�¦̧���̧��¡����¦ ¶¬·¶ �ª����
ɦ�Â�����̧¦��¦���̧»
¤�¹�̧��¡�³�̧��� ·²¬²Ð
Feature
425W | 420W | 415W | 410W
About LG Electronics LG Electronics is a global big player, committed to expanding its operations with the solar market. The company first embarked on a solar energy source research program in 1985, supported by LG Group’s vast experience in the semi-conductor, LCD, chemistry and materials industries. In 2010, LG Solar successfully released its first MonoX® series to the market, which is now available in 32 countries. The NeON® (previous. MonoX® NeON), NeON®2, NeON®2 BiFacial won the “Intersolar AWARD” in 2013, 2015 and 2016, which demonstrates LG Solar’s lead, innovation and commitment to the industry.
KM 564573 BS EN 61215 Photovoltaic Modules
TM
yrs25 Warranty
Enhanced Product warranty
Because of the high quality of LG solar panels, LG provides 25 years product warranty to customers.
Enhanced Performance Warranty
LG NeON® 2 has an enhanced performance warranty. After 25 years, LG NeON® 2 is guar-anteed to perform at minimum 90.1% of initial performance.
The LG NeON® 2 is LG’s best selling solar module, and is one of the powerful and versatile modules on the market today.
Dimensions (mm / inch)
LG425N2W-L5 I LG420N2W-L5 I LG415N2W-L5 I LG410N2W-L5
General Data Cell Properties(Material / Type) Monocrystalline / N-type
Cell Maker LG
Cell Configuration 72 Cells (6 x 12)
Number of Busbars 12EA
Module Dimensions (L x W x H) 2,024mm x 1,024mm x 40 mm
Weight 21.5 kg
Glass(Thickness / Material) 2.8mm / Tempered Glass with AR Coating
Backsheet(Color) White
Frame(Material) Anodized Aluminium
Junction Box(Protection Degree) IP 68 with 3 Bypass Diodes
Cables(Length) 1,200 mm x 2EA
Connector(Type / Maker) MC4 / MC4 Compatible
* First year : 98%, After 1st year : 0.33% annual degradation, 90.1% at 25years
Certifications and Warranty
Certifications
IEC 61215-1/-1-1/2:2016, IEC 61730-
1/2:2016, UL 61730-1/-2:2017
ISO 9001, ISO 14001, ISO 50001
OHSAS 18001
Salt Mist Corrosion Test IEC 61701 : 2011 Severity 6
Ammonia Corrosion Test IEC 62716 : 2013
Module Fire Performance Type 1 (UL 61730)
Fire Rating Class C (UL 790)
Solar Module Product Warranty 25 Years
Solar Module Output Warranty Linear Warranty*
* NMOT (Nominal Module Operating Temperature): Irradiance 800 W/m2, Ambient temperature 20 °C, Wind speed 1 m/s, Spectrum AM 1.5
Temperature Characteristics
NMOT* [ °C ] 42 ± 3
Pmax [%/°C] -0.35
Voc [%/°C] -0.26
Isc [%/°C] 0.025
I-V Curves
* STC (Standard Test Condition): Irradiance 1000 W/m², Cell temperature 25 °C, AM 1.5
** Measure Tolerance of Pmax : ±3%
Electrical Properties (STC*) Model LG425N2W-L5 LG420N2W-L5 LG415N2W-L5 LG410N2W-L5
Maximum Power (Pmax) [W] 425 420 415 410
MPP Voltage (Vmpp) [V] 42.5 42.1 41.8 41.4
MPP Current (Impp) [A] 10.01 9.98 9.94 9.91
Open Circuit Voltage (Voc, ±5%) [V] 49.8 49.7 49.6 49.5
Short Circuit Current (Isc, ±5%) [A] 10.67 10.63 10.59 10.55
Module Efficiency [%] 20.5 20.3 20.0 19.8
Power Tolerance [%] 0 ~ +3
Electrical Properties (NMOT) Model LG425N2W-L5 LG420N2W-L5 LG415N2W-L5 LG410N2W-L5 Maximum Power (Pmax) [W] 319 315 312 308 MPP Voltage (Vmpp) [V] 39.9 39.6 39.3 38.9 MPP Current (Impp) [A] 7.99 7.96 7.93 7.91 Open Circuit Voltage (Voc) [V] 47.0 46.9 46.8 46.7 Short Circuit Current (Isc) [A] 8.57 8.54 8.51 8.48
LG Electronics Inc.
Energy Business Division LG Twin Towers, 128 Yeoui-daero, Yeongdeungpo-gu, Seoul 07336, Korea www.lg-solar.com
Product specifications are subject to change without notice.
DS-L5-72-W-G-F-EN-200708
© 2020 LG Electronics. All rights reserved.
Packaging Configuration Number of Modules per Pallet [EA] 25
Number of Modules per 40ft HQ Container [EA] 550
Packaging Box Dimensions (L x W x H) [mm] 2,080 x 1,120 x 1,226
Packaging Box Gross Weight [kg] 551
Operating Conditions Operating Temperature [°C ] -40 ~ +90
Maximum System Voltage [V] 1,500(UL), 1000(IEC)
Maximum Series Fuse Rating [A] 20
Mechanical Test Load (Front) [Pa / psf] 5,400 / 113 Mechanical Test Load (Rear) [Pa / psf] 3,000 / 63
※Mechanical Test Load 5,400Pa / 3,000Pa based on IEC 61215-2 : 2016 (Test Load = Design Load x Safety Factor(1.5))
(Refer to the table)
Voltage[V]
Cu rr en t[
A
0.0
2.0
4.0
6.0
8.0
10.0
12.0
0.0 10.0 20.0 30.0 40.0 50.0
1000W
800W
600W
400W
200W
RELIABLE
DC FAST CHARGING
FOR FLEETS
The Proterra Industrial Series charging system is designed explicitly for fleet applications.
Available in 60kW, 90kW, 120kW, 150kW and 180kW configurations.
Charge up to 4 vehicles from the same charger with automated, multi-dispenser configurations, including up to 4 single-cable dispensers or 2 dual-cable dispensers.
Dispensers can be sited separately
(up to 500 feet away) from the charging cabinet, enabling greater flexibility in design and configuration for fleets.
Remote monitoring, intelligent diagnostics and a modular design allows for quick issue resolution and efficient field service.
Broad voltage range (up to 1000VDC) ensures compatibility with both today’s and next generation electric vehicles.
• OCPP compliant and 4G enabled
• Small footprint
• Multi-dispenser option
• Supports CCS1 and pantograph options
• 3 Year Standard Warranty with extensions available
CHARGING
SYSTEMS
INDUSTRIAL SERIES
Proterra charging systems are compliant with Federal DOT Buy America requirements.
CHARGING
SYSTEMS
Proterra charging systems are compliant with Federal DOT Buy America requirements.
proterra.com/energy-services
MODEL PC-060-PI PC-090-PI PC-120-PI PC-150-PI PC-180-PI
ELECTRICAL OUTPUT
Continuous DC Output Power 60 kW 90 kW 120 kW 150 kW 180 kW
DC Output Voltage 150-1000 VDC
Continuous DC Output Current 200 A, 500 A Pantograph (Optional) 300 A, 500 A Pantograph (Optional)
ELECTRICAL INPUT
AC Input Power 63 kVA 95 kVA 126 kVA 158 kVA 189 kVA
AC Input Current 76 A 114 A 152 A 190 A 227 A
AC Input Voltage 480V +/- 10%
AC Input Topology 5-wire WYE (3ph + N + GND)
AC Input Frequency 60 Hz
Current THD% at full power <3%
Power Factor >0.99
Efficiency 95%
MECHANICAL
Cooling Integrated air cooling
Weight 825 lbs 880 lbs 935 lbs 990 lbs 1056 lbs
Dimensions (D x W x H) 31.2 in x 39.6 in x 79.2 in | 80 cm x 100 cm x 200 cm
Required side doork clearance None
Required Front and Rear Clearance 1000 mm
ENVIRONMENTAL
Environmental Rating NEMA 3R
Maximum Altitude 3000m | 9800 ft (power derates above 2000m | 6500 ft)
Operating temperature -22°F to 122°F | -30°C to 50°C
Operating Humidity 4-95%
MISC
Approved charger-to-vehicle interfaces CCS1 Industrial dispenser
J3105-1 Infrastructure-Down Pantograph
Approved number of dispensers per power cabinet
Up to 2 Dual Cable Dispensers or Up to 4 Single Cable Dispensers
Sequential Charging Capabilities 1 @ 60 kW 1 @ 90 kW 1 @ 120 kW 1 @ 150 kW 1 @ 180 kW
Simultaneous Charging Capabilities - - 2 @ 60 kW - 3 @ 60 kW
Power Cabinet to dispenser or pantograph control box communications
Modbus TCP via fiber optic
Max Distance between Power Cabinet and Dispenser
500 ft | 152.4 m (fiber optics)
Management Communications OCPP 1.6 control via 4G Cellular (standard)
Supports WiFi, Ethernet (optional)
Certifications UL 2231, UL 2202 (pending)
Warranty 3 year standard, 5 year extended warranty (optional)
S P
E C
C
H G
S Y
S N
B c
Q mkeisler Cross-Out remove mkeisler Cross-Out remove
SG275 | 14.2L | 275 kW
INDUSTRIAL SPARK-IGNITED GENERATOR SET
EPA Certified Stationary Emergency and Non-Emergency
SP
EC
S H
EE
T
DEMAND RESPONSE READY
Standby Power Rating 275 kW, 344 kVA, 60 Hz
Demand Response Rating 275 kW, 344 kVA, 60 Hz
Prime Power Rating 248 kW, 309 kVA, 60 Hz
Codes and Standards Not all codes and standards apply to all configurations. Contact factory for details.
UL2200, UL6200, UL1236, UL489
CSA C22.2
BS5514 and DIN 6271
SAE J1349
NFPA 37, 70, 99, 110
NEC700, 701, 702, 708
ISO 3046, 7637, 8528, 9001
NEMA ICS10, MG1, 250, ICS6, AB1
ANSI C62.41
IBC 2009, CBC 2010, IBC 2012,
ASCE 7-05, ASCE 7-10, ICC-ES AC-
156 (2012)
TM
Powering Ahead Generac ensures superior quality by designing and manufacturing most of its generator components, such as alternators, enclosures, control systems and communications software. Generac also makes its own spark-ignited engines, and you’ll find them on every Generac gaseous-fueled generator. We engineer and manufacture them from the block up — all at our facilities throughout Wisconsin. Applying natural gas and LP-fueled engines to generators requires advanced engineering expertise to ensure reliability, durability and necessary performance. By designing specifically for these dry, hotter-burning fuels, the engines last longer and require less maintenance. Building our own engines also means we control every step of the supply chain and delivery process, so you benefit from single-source responsibility.
Plus, Generac Industrial Power’s distribution network provides all parts and service so you don’t have to deal with third-party suppliers. It all leads to a positive owner experience and higher confidence level. Generac spark-ignited engines give you more options in commercial and industrial generator applications as well as extended run time from utility-supplied natural gas.
*Assembled in the USA using domestic and foreign parts
Image used for illustration purposes only
EPA Certified Stationary Emergency and Non-Emergency
SP
EC
S H
EE
T
DEMAND RESPONSE READY
CONTROL SYSTEM
Power Zone® Pro Sync Controller
Program Functions
• NFPA 110 Level 1 Compliant
• Engine Protective Functions
• Alternator Protective Functions
• Digital Engine Governor Control
• Digital Voltage Regulator
• Multiple Programmable Inputs and Outputs
• Remote Display Capability
• Remote Communication via Modbus® RTU, Modbus TCP/IP, and Ethernet 10/100
• Alarm and Event Logging with Real Time Stamping
• Expandable Analog and Digital Inputs and Outputs
• Remote Wireless Software Update Capable
• Wi-Fi®, Bluetooth®, BMS and Remote Telemetry
• Built-In Programmable Logic Eliminates the Need for External Controllers Under Most Conditions
• Ethernet Based Communications Between Generators
• Programmable I/O Channel Properties
• Built-In Diagnostics
Protections
• Low Oil Pressure
• Low Coolant Level
• High/Low Coolant Temperature
• Sensor Failure
• Oil Temperature
• Over/Under Speed
• Over/Under Voltage
• Over/Under Frequency
• Over/Under Current
• Over Load
• High/Low Battery Voltage
• Battery Charger Current
• Phase to Phase and Phase to Neutral Short Circuits
(I2T Algorithm)
7 Inch Color Touch Screen Display
• Resistive Color Touch Screen
• Sunlight Readable (1400 NITS)
• Easily Identifiable Icons
• Multi-Lingual
• On Screen Editable Parameters
• Key Function Monitoring
• Three Phase Voltage, Amperage, kW, kVA, and kVAr
• Selectable Line to Line or Line to Neutral Measurements
• Frequency
• Engine Speed
• Engine Coolant Temperature
• Engine Oil Pressure
• Engine Oil Temperature
• Battery Voltage
• Hourmeter
• Warning and Alarm Indication
• Diagnostics
• Maintenance Events/Information
ENGINE SYSTEM
• Oil Drain Extension
• Air Cleaner
• Fan Guard (Open Sets Only)
• Stainless Steel Flexible Exhaust Connection
• Factory Filled Oil and Coolant
• Radiator Duct Adapter (Open Set Only)
• Critical Silencer (Enclosed Units Only)
• Oil Temperature Indication and Alarm
Fuel System
• NPT Fuel Connection on Frame
• Primary and Secondary Fuel Shutoff
Cooling System
• Closed Coolant Recovery System
• UV/Ozone Resistant Hoses
• Factory-Installed Radiator
• 50/50 Ethylene Glycol Antifreeze
• Radiator Drain Extension
Electrical System
• Battery Charging Alternator
• Battery Cables
• Battery Tray
• Rubber-Booted Engine Electrical Connections
• Solenoid Activated Starter Motor
ALTERNATOR SYSTEM
• UL2200 GENprotect™
• Class H Insulation Material
• 2/3 Pitch
• Skewed Stator
• Permanent Magnet Excitation
• Sealed Bearing
• Amortisseur Winding
• Full Load Capacity Alternator
GENERATOR SET
• Internal Genset Vibration Isolation
• Separation of Circuits - High/Low Voltage
• Separation of Circuits - Multiple Breakers
• Wrapped Exhaust Piping
• Standard Factory Testing
• 2 Year Limited Warranty (Standby and Demand
Response Rated Units)
• 1 Year Limited Warranty (Prime Rated Units)
• Silencer Mounted in the Discharge Hood
(Enclosed Units Only)
• Ready to Accept Full Load in <10 Seconds
ENCLOSURE (If Selected)
• Rust-Proof Fasteners with Nylon Washers to Protect Finish
• High Performance Sound-Absorbing Material (Sound Attenuated Enclosures)
• Gasketed Doors
• Upward Facing Discharge Hood (Radiator and Exhaust)
• Stainless Steel Lift Off Door Hinges
• Stainless Steel Lockable Handles
• RhinoCoat™ - Textured Polyester Powder Coat
STANDARD FEATURES
EPA Certified Stationary Emergency and Non-Emergency
SP
EC
S H
EE
T
DEMAND RESPONSE READYCONFIGURABLE OPTIONS
ENGINE SYSTEM
○ Engine Coolant Heater
○ Baseframe Cover/Rodent Guard
○ 2 Stage Air Cleaner
○ Oil Heater
○ Air Filter Restriction Indicator
○ Radiator Stone Guard (Open Set Only)
○ Level 1 Fan and Belt Guards (Enclosed Units Only)
FUEL SYSTEM
○ NPT Flexible Fuel Line
ELECTRICAL SYSTEM
○ 10A UL Listed Battery Charger
○ Battery Warmer
ALTERNATOR SYSTEM
○ Alternator Upsizing
○ Anti-Condensation Heater
○ Tropical Coating
CIRCUIT BREAKER OPTIONS
○ Main Line Circuit Breaker
○ 2nd Main Line Circuit Breaker
○ Shunt Trip and Auxiliary Contact
○ Electronic Trip Breakers
GENERATOR SET
○ Demand Response Rating
○ Extended Factory Testing (3-Phase Only)
○ 12 Position Load Center
○ Vapor Recovery Heater
ENCLOSURE
○ Weather Protected Enclosure
○ Level 1 Sound Attenuated
○ Level 2 Sound Attenuated
○ Level 2 Sound Attenuated with Motorized Dampers
○ Level 3 Sound Attenuated (Steel Only)
○ Steel Enclosure
○ Aluminum Enclosure
○ Up to 200 MPH Wind Load Rating (Contact Factory for Availability)
○ AC/DC Enclosure Lighting Kit
○ Enclosure Heaters (with Motorized Dampers Only)
○ IBC Certification
○ Door Open Alarm Switch
CONTROL SYSTEM
○ NFPA 110 Level 1 Compliant 21-Light Remote Annunciator
○ Remote Relay Assembly (8 or 16)
○ Remote E-Stop (Break Glass-Type, Surface Mount)
○ Remote E-Stop (Red Mushroom-Type, Surface Mount)
○ Remote E-Stop (Red Mushroom-Type, Flush Mount)
○ 10A Engine Run Relay
○ Ground Fault Annunciator
○ 100 dB Alarm Horn
○ Damper Alarm Contacts (with Motorized Dampers Only)
○ 120V GFCI and 240V Outlets
WARRANTY (Standby Gensets Only)
○ 2 Year Extended Limited Warranty
○ 5 Year Limited Warranty
○ 5 Year Extended Limited Warranty
○ 7 Year Extended Limited Warranty
○ 10 Year Extended Limited Warranty
ENGINEERED OPTIONS
ENGINE SYSTEM
○ Fluid Containment Pans
CONTROL SYSTEM
○ Battery Disconnect Switch
ALTERNATOR SYSTEM
○ 3rd Main Line Circuit Breaker
○ 4th Breaker System
GENERATOR SET
○ Special Testing
○ Battery Box
EPA Certified Stationary Emergency and Non-Emergency
SP
EC
S H
EE
T
DEMAND RESPONSE READY
General
Make Generac
Cylinder # 6
Type In-line
Displacement - in3 (L) 864.71 (14.2)
Bore - in (mm) 5.31 (135)
Stroke - in (mm) 6.50 (165)
Compression Ratio 9.5:1
Intake Air Method Turbocharged/Aftercooled
Number of Main Bearings 7
Connecting Rods Steel Alloy
Cylinder Head Cast Iron GT250, OHV
Cylinder Liners Ductile Iron
Ignition Electronic
Piston Type Aluminum
Crankshaft Type Ductile Iron
Lifter Type Solid
Intake Valve Material Special Heat-Resistant Steel
Exhaust Valve Material High Temp Steel Alloy
Hardened Valve Seats High Temp Steel Alloy
Engine Governing
Governor Electronic
Frequency Regulation (Steady State) ±0.25%
Lubrication System
Oil Pump Type Gear
Oil Filter Type Full-Flow with Cartridge
Crankcase Capacity - qt (L) 36.2 (34.3)
Cooling System
Cooling System Type Pressurized Closed Recovery
Fan Type Pusher
Fan Speed - RPM 1,894
Fan Diameter - in (mm) 34 (864)
Fuel System
Fuel Type Natural Gas
Carburetor Down Draft
Secondary Fuel Regulator Standard
Fuel Shut Off Solenoid Standard
Operating Fuel Pressure - in H2O (kPa) 7 - 11 (1.7 - 2.7)
Engine Electrical System
System Voltage 24 VDC
Battery Charger Alternator 57.5 A
Battery Size See Battery Index 0161970SBY
Battery Voltage 24 VDC
Ground Polarity Negative
APPLICATION AND ENGINEERING DATA
ENGINE SPECIFICATIONS
ALTERNATOR SPECIFICATIONS
Standard Model K0300124Y21
Poles 4
Field Type Revolving
Insulation Class - Rotor H
Insulation Class - Stator H
Total Harmonic Distortion <5% (3-Phase)
Telephone Interference Factor (TIF) <50
Standard Excitation Permanent Magnet
Bearings Sealed Ball
Coupling Direct via Flexible Disc
Prototype Short Circuit Test Yes
Voltage Regulator Type Full Digital
Number of Sensed Phases All
Regulation Accuracy (Steady State) ±0.25%
EPA Certified Stationary Emergency and Non-Emergency
SP
EC
S H
EE
T
DEMAND RESPONSE READY
** Refer to “Emissions Data Sheet” for maximum bHP for EPA and SCAQMD permitting purposes.
Deration – Operational characteristics consider maximum ambient conditions. Derate factors may apply under atypical site conditions.
Please contact a Generac Power Systems Industrial Dealer for additional details. All performance ratings in accordance with ISO3046, BS5514, ISO8528, and DIN6271 standards.
Standby - See Bulletin 0187500SSB Demand Response - See Bulletin 10000018250 Prime - See Bulletin 0187510SSB
POWER RATINGS - NATURAL GAS
Standby/Demand Response Prime
Three-Phase 120/208 VAC @0.8pf 275 kW/343.8 kVA Amps: 955 248 kW/309.4 kVA Amps: 860
Three-Phase 120/240 VAC @0.8pf 275 kW/343.8 kVA Amps: 828 248 kW/309.4 kVA Amps: 745
Three-Phase 277/480 VAC @0.8pf 275 kW/343.8 kVA Amps: 414 248 kW/309.4 kVA Amps: 373
Three-Phase 346/600 VAC @0.8pf 275 kW/343.8 kVA Amps: 331 248 kW/309.4 kVA Amps: 298
MOTOR STARTING CAPABILITIES (skVA) skVA vs. Voltage Dip
277/480 VAC 30% 277/480 VAC 30%
K0300124Y21 790 K0300124Y21 609
FUEL CONSUMPTION RATES*
Natural Gas – scfh (m3/hr)
Percent Load Standby/Demand Response Prime
25% 1,080 (30.6) 1,020 (28.9)
50% 1,800 (51.0) 1,620 (45.9)
75% 2,640 (74.8) 2,400 (68.0)
100% 3,240 (91.7) 3,000 (84.9)
* Fuel supply installation must accommodate fuel consumption rates at 100% load.
COOLING
Standby/Demand Response Prime
Air Flow (Fan Air Flow Across Radiator) scfm (m3/min) 15,946 (452) 15,946 (452)
Coolant Flow gpm (Lpm) 90 (340.7) 90 (340.7)
Coolant System Capacity gal (L) 15 (54.9) 15 (54.9)
Maximum Operating Ambient Temperature °F (°C) 122 (50) 122 (50)
Maximum Operating Ambient Temperature (Before Derate) See Bulletin No. 0199270SSD
Maximum Radiator Backpressure in H2O (kPa) 0.5 (0.12) 0.5 (0.12)
COMBUSTION AIR REQUIREMENTS
Standby/Demand Response Prime
Flow at Rated Power - scfm (m3/min) 514 (14.6) 480 (13.6)
ENGINE EXHAUST
Standby/Demand
Response Prime
Standby/Demand Response
Prime
Rated Engine Speed RPM 1,800 1,800 Exhaust Flow (Rated Output) scfm (m3/min) 1,985 (56) 1,670 (47)
Horsepower at Rated kW** hp 409 369 Max. Backpressure (Post Silencer) inHg (kPa) 0.75 (2.54) 0.75 (2.54)
Piston Speed ft/min (m/min) 1,950 (594) 1,950 (594) Exhaust Temp (Rated Output - Post Silencer) °F (°C) 1,385 (752) 1,355 (735)
BMEP psi (kPa) 208 (1,433) 187 (1,292)
OPERATING DATA
EPA Certified Stationary Emergency and Non-Emergency
SP
EC
S H
EE
T
DEMAND RESPONSE READY
YOUR FACTORY RECOGNIZED GENERAC INDUSTRIAL DEALER
Specification characteristics may change without notice. Please contact a Generac Power Systems Industrial Dealer for detailed installation drawings.
* All measurements are approximate and for estimation purposes only.
Part No. 10000039025 Rev. B 02/07/2020
Generac Power Systems, Inc. | P.O. Box 8 | Waukesha, WI 53189 P: (262) 544-4811 ©2020 Generac Power Systems, Inc. All rights reserved. All specifications are subject to change without notice.
DIMENSIONS AND WEIGHTS*
OPEN SET (Includes Exhaust Flex) L x W x H - in (mm) 136.0 (3,454) x 57.1 (1,450) x 67.9 (1,725)
Weight - lbs (kg) 6,200 - 6,587 (2,812 - 2,987)
WEATHER PROTECTED ENCLOSURE
L x W x H - in (mm) 174.7 (4,437) x 57.5 (1,461) x 77.8 (1,976)
Weight - lbs (kg) Steel: 7,535 - 7,919 (3,417 - 3,591) Aluminum: 6,978 - 7,359 (3,165 - 3,337)
LEVEL 1 SOUND ATTENUATED ENCLOSURE
L x W x H - in (mm) 200.2 (5,085) x 57.5 (1,461) x 77.8 (1,976)
Weight - lbs (kg) Steel: 7,770 - 8,273 (3,524 - 3,752) Aluminum: 7,176 - 7,625 (3,254 - 3,458)
LEVEL 2 SOUND ATTENUATED ENCLOSURE
L x W x H - in (mm) 180.6 (4,587) x 57.5 (1,461) x 111.3 (2,827)
Weight - lbs (kg) Steel: 8,804 - 9,188 (3,993 - 4,167) Aluminum: 7,423 - 7,870 (3,366 - 3,569)
LEVEL 3 SOUND ATTENUATED ENCLOSURE
L x W x H - in (mm) 207.3 (5,265) x 63.7 (1,618) x 128.9 (3,274)
Weight - lbs (kg) 10,718 - 11,080 (4,861 - 5,025)
L
L
L
L
L
W
W
W
W
W
H
H
H
H
SD275 | 10.3L | 275 kW
INDUSTRIAL DIESEL GENERATOR SET
EPA Certified Stationary Emergency
SP
EC
S
HE
ET
Powering Ahead
For over 60 years, Generac has provided innovative design and superior manufacturing.
Generac ensures superior quality by designing and manufacturing most of its generator components, including alternators, enclosures and base tanks, control systems and communications software.
Generac gensets utilize a wide variety of options, configurations and arrangements, allowing us to meet the standby power needs of practically every application.
Generac searched globally to ensure the most reliable engines power our generators. We choose only engines that have already been proven in heavy-duty industrial applications under adverse conditions.
Generac is committed to ensuring our customers’ service support continues after their generator purchase.
Codes and Standards Not all codes and standards apply to all configurations. Contact factory for details.
UL2200, UL6200, UL1236, UL489,
UL142
CSA C22.2, ULC S601
BS5514 and DIN 6271
SAE J1349
NFPA 37, 70, 99, 110
NEC700, 701, 702, 708
ISO 3046, 7637, 8528, 9001
NEMA ICS10, MG1, 250, ICS6, AB1
ANSI C62.41
IBC 2009, CBC 2010, IBC 2012,
ASCE 7-05, ASCE 7-10, ICC-ES AC-
156 (2012)
TM
Image used for illustration purposes only
Standby Power Rating 275 kW, 344 kVA, 60 Hz
Prime Power Rating* 248 kW, 309 kVA, 60 Hz
*EPA Certified Prime ratings are not available in the US or its Territories
EPA Certified Stationary Emergency
SP
EC
S
HE
ET
CONTROL SYSTEM
Digital H Control Panel- Dual 4x20 Display
Program Functions
• Programmable Crank Limiter
• 7-Day Programmable Exerciser
• Special Applications Programmable Logic Controller
• RS-232/485 Communications
• All Phase Sensing Digital Voltage Regulator
• 2-Wire Start Capability
• Date/Time Fault History (Event Log)
• Isochronous Governor Control
• Waterproof/Sealed Connectors
• Audible Alarms and Shutdowns
• Not in Auto (Flashing Light)
• Auto/Off/Manual Switch
• E-Stop (Red Mushroom-Type)
• NFPA110 Level I and II (Programmable)
• Customizable Alarms, Warnings, and Events
• Modbus® Protocol
• Predictive Maintenance Algorithm
• Sealed Boards
• Password Parameter Adjustment Protection
• Single Point Ground
• 16 Channel Remote Trending
• 0.2 msec High Speed Remote Trending
• Alarm Information Automatically Annunciated on the Display
Full System Status Display
• Power Output (kW)
• Power Factor
• kW Hours, Total, and Last Run
• Real/Reactive/Apparent Power
• All Phase AC Voltage
• All Phase Currents
• Oil Pressure
• Coolant Temperature
• Coolant Level
• Engine Speed
• Battery Voltage
• Frequency
Alarms and Warnings
• Oil Pressure
• Coolant Temperature
• Coolant Level
• Engine Overspeed
• Battery Voltage
• Alarms and Warnings Time and Date Stamped
• Snap Shots of Key Operation Parameters During
Alarms and Warnings
• Alarms and Warnings Spelled Out (No Alarm Codes)
EMERGENCY
STOP
COMMON ALARM
AUTO OFF MAN.
Phase Volts Amps Hz =
SD EMERGENCY STOP Hi SD COOLANT LEVEL Lo Wr*BATTERY VOLTS Hi ACK More (1–3)
A–B
0.0 kW
B–C
C–A
NOT IN
AUTO
ALARM
HOME
MENU
ENTER
ENGINE SYSTEM
• Oil Drain Extension
• Level 1 Fan and Belt Guards (Open Set Only)
• Stainless Steel Flexible Exhaust Connection
• Factory Filled Oil and Coolant
• Radiator Duct Adapter (Open Set Only)
FUEL SYSTEM
• Fuel Lockoff Solenoid
• Primary Fuel Filter
COOLING SYSTEM
• Closed Coolant Recovery System
• UV/Ozone Resistant Hoses
• Factory-Installed Radiator
• Radiator Drain Extension
• 50/50 Ethylene Glycol Antifreeze
• Engine Coolant Heater
ELECTRICAL SYSTEM
• Battery Charging Alternator
• Battery Cables
• Battery Tray
• Rubber-Booted Engine Electrical Connections
• Solenoid Activated Starter Motor
ALTERNATOR SYSTEM
• UL2200 GENprotect™
• 12 Leads (3-Phase, Non 600V)
• Class H Insulation Material
• Vented Rotor
• 2/3 Pitch
• Skewed Stator
• Auxiliary Voltage Regulator Power Winding
• Permanent Magnet Excitation
• Sealed Bearing
• Automated Manufacturing (Winding, Insertion, Lacing, Varnishing)
• Rotor Dynamically Spin Balanced
• Amortisseur Winding
• Full Load Capacity Alternator
• Protective Thermal Switch
GENERATOR SET
• Internal Genset Vibration Isolation
• Separation of Circuits - High/Low Voltage
• Separation of Circuits - Multiple Breakers
• Wrapped Exhaust Piping
• Standard Factory Testing
• 2 Year Limited Warranty (Standby Rated Units)
• 1 Year Limited Warranty (Prime Rated Units)
• Silencer Mounted in the Discharge Hood
(Enclosed Unit Only)
ENCLOSURE (If Selected)
• Rust-Proof Fasteners with Nylon Washers to Protect Finish
• High Performance Sound-Absorbing Material (Sound Attenuated Enclosures)
• Gasketed Doors
• Upward Facing Discharge Hoods (Radiator and Exhaust)
• Stainless Steel Lift Off Door Hinges
• Stainless Steel Lockable Handles
• RhinoCoat™ - Textured Polyester Powder Coat Paint
FUEL TANKS (If Selected)
• UL 142/ULC S601
• Double Wall
• Vents
• Sloped Top
• Sloped Bottom
• Factory Pressure Tested - 2 psi
• Rupture Basin Alarm
• Fuel Level
• Check Valve In Supply and Return Lines
• RhinoCoat™ - Textured Polyester Powder Coat Paint
• Stainless Steel Hardware
STANDARD FEATURES
EPA Certified Stationary Emergency
SP
EC
S
HE
ET
CONFIGURABLE OPTIONS
ENGINE SYSTEM
○ Block Heater
○ Oil Heater
○ Level 1 Fan and Belt Guards (Enclosed Units Only)
○ Heavy Duty Air Cleaner
○ Radiator Stone Guard
○ Air Filter Restriction Indicator
FUEL SYSTEM
○ NPT Flexible Fuel Line
ELECTRICAL SYSTEM
○ 10A UL Listed Battery Charger
○ Battery Warmer
ALTERNATOR SYSTEM
○ Alternator Upsizing
○ Anti-Condensation Heater
○ Tropical Coating
CIRCUIT BREAKER OPTIONS
○ Main Line Circuit Breaker
○ 2nd Main Line Circuit Breaker
○ Shunt Trip and Auxiliary Contact
○ Electronic Trip Breakers
GENERATOR SET
○ Extended Factory Testing
○ IBC Seismic Certification
○ 12 Position Load Center
○ Spring Vibration Isolators
ENCLOSURE
○ Weather Protected Enclosure
○ Level 1 Sound Attenuated
○ Level 2 Sound Attenuated
○ Level 2 Sound Attenuated with Motorized Dampers
○ Steel Enclosure
○ Aluminum Enclosure
○ Door Open Alarm Horn
○ Up to 200 MPH Wind Load Rating (Contact Factory for Availability)
○ AC/DC Enclosure Lighting Kit
○ Enclosure Heater (with Motorized Dampers Only)
FUEL TANKS (Size on Last Page)
○ 8 in (203.2 mm) Fill Extension
○ 13 in (330.2 mm) Fill Extension
○ 19 in (482.6 mm) Fill Extension
CONTROL SYSTEM
○ NFPA 110 Compliant 21-Light Remote Annunciator
○ Remote Relay Assembly (8 or 16)
○ Oil Temperature Sender with Indication Alarm
○ Remote E-Stop (Break Glass-Type, Surface Mount)
○ Remote E-Stop (Red Mushroom-Type, Surface Mount)
○ Remote E-Stop (Red Mushroom-Type, Flush Mount)
○ 100 dB Alarm Horn
○ Ground Fault Annunciator
○ 120 V GFCI and 240 Outlet
○ Flush Mount Annunciator Kit
○ Remote Communication - Modem
○ 10A Engine Run Relay
○ Damper Alarm Contacts (with Motorized
Dampers Only)
WARRANTY
○ 2 Year Extended Limited Warranty
○ 5 Year Limited Warranty
○ 5 Year Extended Limited Warranty
○ 7 Year Extended Limited Warranty
○ 10 Year Extended Limited Warranty
ENGINEERED OPTIONS
ENGINE SYSTEM
○ Coolant Heater Ball Valves
○ Fluid Containment Pan
CONTROL SYSTEM
○ Spare Inputs (x4) / Outputs (x4)
○ Battery Disconnect Switch
ALTERNATOR SYSTEM
○ 3rd Breaker System
GENERATOR SET
○ Special Testing
FUEL TANKS
○ Overfill Protection Valve
○ UL2085 Tank
○ Special Fuel Tanks
○ Vent Extensions
EPA Certified Stationary Emergency
SP
EC
S
HE
ET
General
Make Iveco/FPT
EPA Emissions Compliance Stationary Emergency
EPA Emissions Reference See Emission Data Sheet
Cylinder # 6
Type In-Line
Displacement - in3 (L) 628.54 (10.3)
Bore - in (mm) 4.92 (125)
Stroke - in (mm) 5.51 (140)
Compression Ratio 16.5:1
Intake Air Method Turbocharged/Aftercooled
Cylinder Head 4-Valve
Piston Type Aluminum
Crankshaft Type Dropped Forged Steel
Engine Governing
Governor Electronic Isochronous
Frequency Regulation (Steady State) ±0.25%
Lubrication System
Oil Pump Type Gear
Oil Filter Type Full Flow
Crankcase Capacity - qt (L) 31.68 (30)
Cooling System
Cooling System Type Closed Recovery
Water Pump Type Pre-Lubed, Self Sealing
Fan Type Pusher
Fan Speed - RPM 2,250
Fan Diameter - in (mm) 30 (762)
Fuel System
Fuel Type Ultra Low Sulfur Diesel Fuel #2
Fuel Specifications ASTM
Fuel Filtering (Microns) 5
Fuel Inject Pump Electronic
Fuel Pump Type Engine Driven Gear
Injector Type Common Rail
Engine Type Direct Injection
Fuel Supply Line - in (mm) 0.5 (12.7) NPT
Fuel Return Line - in (mm) 0.5 (12.7) NPT
Engine Electrical System
System Voltage 24 VDC
Battery Charger Alternator Standard
Battery Size See Battery Index 0161970SBY
Battery Voltage (2)-12 VDC
Ground Polarity Negative
APPLICATION AND ENGINEERING DATA
ENGINE SPECIFICATIONS
ALTERNATOR SPECIFICATIONS
Standard Model K0275124Y21
Poles 4
Field Type Revolving
Insulation Class - Rotor H
Insulation Class - Stator H
Total Harmonic Distortion <5%
Telephone Interference Factor (TIF) <50
Standard Excitation Permanent Magnet
Bearings Single Sealed Cartridge
Coupling Direct via Flexible Disc
Prototype Short Circuit Test Yes
Voltage Regulator Type Digital
Number of Sensed Phases All
Regulation Accuracy (Steady State) ±0.25%
EPA Certified Stationary Emergency
SP
EC
S
HE
ET
** Refer to “Emissions Data Sheet” for maximum bHP for EPA and SCAQMD permitting purposes.
Deration – Operational characteristics consider maximum ambient conditions. Derate factors may apply under atypical site conditions.
Please contact a Generac Power Systems Industrial Dealer for additional details. All performance ratings in accordance with ISO3046, BS5514, ISO8528, and DIN6271 standards.
Standby - See Bulletin 10000018933 Prime - See Bulletin 10000018926
POWER RATINGS
Standby
Three-Phase 120/208 VAC @0.8pf 275 kW Amps: 954
Three-Phase 120/240 VAC @0.8pf 275 kW Amps: 827
Three-Phase 277/480 VAC @0.8pf 275 kW Amps: 414
Three-Phase 346/600 VAC @0.8pf 275 kW Amps: 331
MOTOR STARTING CAPABILITIES (skVA)
SkVA vs. Voltage Dip
277/480 VAC 30% 208/240 VAC 30%
K0275124Y21 790 K0275124Y21 609
K0350124Y21 1,001 K0350124Y21 801
K0400124Y21 953 K0400124Y21 717
FUEL CONSUMPTION RATES*
Diesel - gph (Lph)
Fuel Pump Lift - ft (m) Percent Load Standby
3 (1) 25% 6.8 (25.7)
50% 11.7 (44.2)
Total Fuel Pump Flow (Combustion + Return) - gph (Lph) 75% 15.8 (59.8)
31 (117) 100% 19.6 (74.2)
* Fuel supply installation must accommodate fuel consumption rates at 100% load.
COOLING
Standby
Coolant Flow gpm (Lpm) 95 (360)
Coolant System Capacity gal (L) 13.0 (49.2)
Heat Rejection to Coolant BTU/hr (kW) 722,612 (211.8)
Inlet Air cfm (m3/hr) 14,505 (411)
Maximum Operating Radiator Air Temperature °F (°C) 110 (43.3)
Maximum Ambient Temperature (Before Derate) See Bulletin No. 0199280SSD
Maximum Additional Radiator Backpressure in H2O (kPa) 0.5 (0.12)
COMBUSTION AIR REQUIREMENTS
Standby
Flow at Rated Power - cfm (m3/min) 780 (22.1)
ENGINE EXHAUST
Standby Standby
Rated Engine Speed RPM 1,800 Exhaust Flow (Rated Output) cfm (m3/min) 2,050 (58.1)
Horsepower at Rated kW** hp 449 Maximum Allowable Backpressure inHg (kPa) 1.5 (5.1)
Piston Speed ft/min (m/min) 1,654 (504) Exhaust Temperature (Rated Output) °F (°C) 950 (510)
BMEP psi (kPa) 308 (2,124)
OPERATING DATA
EPA Certified Stationary Emergency
SP
EC
S
HE
ET
Part No. 0185610SBY Rev. F 07/13/2021
Generac Power Systems, Inc. | P.O.Box 8 | Waukesha, WI 53189 P: (262) 544-4811 ©2021 Generac Power Systems, Inc. All rights reserved. All specifications are subject to change without notice.
* All measurements are approximate and for estimation purposes only. Specification characteristics may change without notice. Please contact a Generac Power Systems Industrial Dealer for detailed installation drawings.
DIMENSIONS AND WEIGHTS*
OPEN SET
Run Time
- Hours
Usable Capacity
- Gal (L)
L x W x H - in (mm) Weight - lbs (kg)
No Tank - 137.5 (3,493) x 57.6 (1,463) x 67.8 (1,722) 6,121 - 7,457 (2,776 - 3,382)
9 183 (693) 137.5 (3,493) x 57.6 (1,463) x 80.8 (2,052) 7,069 - 8,405 (3,206 - 3,812)
22 438 (1,659) 137.5 (3,493) x 57.6 (1,463) x 92.8 (2,357) 7,381 - 8,717 (3,348 - 3,954)
35 693 (2,624) 137.5 (3,493) x 57.6 (1,463) x 104.8 (2,662) 7,717 - 9,053 (3,500 - 4,106)
48 946 (3,581) 208.3 (5,220) x 57.6 (1,463) x 122.0 (3,100) 9,146 - 10,482 (4,148 - 4,754)
67 1,325 (5,015) 277.8 (7,055) x 57.6 (1,463) x 120.9 (3,072) 10,161 - 11,497 (4,659 - 5,265)
WEATHER PROTECTED ENCLOSURE
Run Time
- Hours
Usable Capacity
- Gal (L)
L x W x H - in (mm) Weight - lbs (kg) Enclosure Only
Steel Aluminum
No Tank - 174.7 (4,437) x 53.0 (1,346) x 77.8 (1,977)
1,521 (690) 727 (330)
9 183 (693) 174.7 (4,437) x 53.0 (1,346) x 90.8 (2,307)
22 438 (1,659) 174.7 (4,437) x 53.0 (1,346) x 102.8 (2,612)
35 693 (2,624) 174.7 (4,437) x 53.0 (1,346) x 114.8 (2,917)
48 946 (3,581) 208.3 (5,220) x 53.0 (1,346) x 132.0 (3,355)
67 1,325 (5,015) 277.8 (7,055) x 53.0 (1,346) x 130.9 (3,327)
LEVEL 1 SOUND ATTENUATED ENCLOSURE
Run Time
- Hours
Usable Capacity
- Gal (L)
L x W x H - in (mm) Weight - lbs (kg) Enclosure Only
Steel Aluminum
No Tank - 200.2 (5,084) x 57.5 (1,460) x 90.8 (2,306)
1,984 (900) 926 (421)
9 183 (693) 200.2 (5,084) x 57.5 (1,460) x 90.8 (2,306)
22 438 (1,659) 200.2 (5,084) x 57.5 (1,460) x 102.8 (2,611)
35 693 (2,624) 200.2 (5,084) x 57.5 (1,460) x 114.8 (2,916)
48 946 (3,581) 200.2 (5,084) x 57.5 (1,460) x 132.0 (3,354)
67 1,325 (5,015) 277.8 (7,055) x 57.5 (1,460) x 130.9 (3,326)
LEVEL 2 SOUND ATTENUATED ENCLOSURE
Run Time
- Hours
Usable Capacity
- Gal (L)
L x W x H - in (mm) Weight - lbs (kg) Enclosure Only
Steel Aluminum
No Tank - 180.7 (4,588) x 57.5 (1,460) x 107.3 (2,725)
2,557 (1,160) 1,173 (531)
9 183 (693) 180.7 (4,588) x 57.5 (1,460) x 120.3 (3,055)
22 438 (1,659) 180.7 (4,588) x 57.5 (1,460) x 132.3 (3,360)
35 693 (2,624) 180.7 (4,588) x 57.5 (1,460) x 144.3 (3,665)
48 946 (3,581) 180.7 (4,588) x 57.5 (1,460) x 161.5 (4,103)
6…