This is a product specification document for the MARK Architectural Lighting SLOT 4 Wall Indirect/Direct Pattern LED fixture, produced by Acuity Brands Lighting, Inc. (Document dated 03/13/23).
The SLOT 4 is a linear LED wall fixture available in configurable lengths from 2 to 4 feet (individual units) or custom lengths up to 100 total feet per order line, with maximum lumen outputs ranging from 600 to 3000 lumens per foot. The fixture provides both direct and indirect light distributions with independently selectable lumen packages for each channel: direct options of 300LMF to 1500LMF and indirect options of 300LMF to 1500LMF, achieving up to 166 lumens per watt in indirect mode. Available color temperatures include 2700K, 3000K, 3500K, 4000K, and 5000K with 80 or 90 CRI options. The fixture offers multiple dimming configurations (no dimming, 1% minimum, 10% minimum, or 0.1% constant current dimming), control options including 0-10V, nLight wired, nLight Air 2 wireless, DALI, or Lutron EcoSystem Digital Driver, and optional integrated occupancy sensors (daylight dimming and passive infrared or dual technology options). Shielding includes three direct lens options (flush lens, edge glow lens, or top glow lens) and indirect options (dust cover, frosted dust cover, or top glow lens). Additional features include single or dual circuit switching, emergency battery pack options (E10WLCP integral battery), emergency circuits (EC), remote generator transfer device (GTD), voltage options (multi-volt 120-277V, 120V, 277V, or 347V), and finish options (white, black, or silver satin). The fixture is CSA certified (UL1598 and UL8750), suitable for damp indoor locations, operates between -20°C to +25°C, weighs approximately 1 lb per foot, and includes a 5-year limited warranty. Buy American Act compliance is available. The document provides comprehensive ordering nomenclature guidance, pattern configuration examples for closed, open, rectangular, and square patterns with corner options (40° to 160° in 1° increments), dimensional drawings, and sensor zone layout specifications for integrated control systems.
View the file
Other files
Show all 21
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
marklighting.com | 800-705-SERV (7378) | © 2022-2023 Acuity Brands Lighting, Inc. All Rights Reserved. We reserve the right to change design, materials and finish in any way that will not alter installed appearance or reduce function and performance.
S P E C I F I C AT I O N S TYPE:
PROJECT:
S4WIDMP WALL PATTERN 03/13/23
SLOT 4
WALL INDIRECT/DIRECT PAT TERN
• 600 to 3000 total lumens per foot
• 300 to 1500 lumens per foot Direct or Indirect
• Up to 166 Lumens per Watt
• Integrated control with optional nLight or nLight Air for system networking
• Driver options for Dim to Dark, 1% or 10% minimum dimming
• White, black or silver paint with satin finish
• Declare listed
HIGHLIGHTS
DIFFUSERS/SHIELDING
DIMENSIONS
See page 5 for additional details.
Flush Lens
(FLL)
RUN LAYOUT
ORDERED LENGTH
4FT
5FT
6FT
7FT
8FT
"A1" O.A.L.
4'- 0 1/4"
5'- 0 1/4"
6'- 0 1/4"
7'- 0 1/4"
8'- 0 1/4"
"A2" O.A.L.
4'-0"
5'-0"
6'-0"
7'-0"
8'-0"
"B" "D"
1'- 0"
"C" FROM END APPROX. WEIGHT
LBS
LBS
LBS
LBS
LBS
"C" "B" "C"
"A"
INDIVIDUAL FIXTURES
ORDERED LENGTH
2FT
3FT
4FT
5FT
6FT
7FT
8FT
"A" O.A.L.
2'- 0 9/16"
3'- 0 9/16"
4'- 0 9/16"
5'- 0 9/16"
6'- 0 9/16"
7'- 0 9/16"
8'- 0 9/16"
"B" O.C. "C" FROM END
6 1/4"
APPROX. WEIGHT
LBS
LBS
LBS
LBS
LBS
LBS
LBS
Left (L) Intermediate (I)
"C"
Right (R)
"A1" "A1"
"B" "B" "B"
"A2"
"C""D" "D"
6 1/4"
6 1/4"
6 1/4"
6 1/4"
6 1/4"
6 1/4"
1'- 0"
2'- 0"
3'- 0"
4'- 0"
5'- 0"
6'- 0"
7'- 0"
1'- 0"
1'- 0"
1'- 0"
1'- 0"
3'- 0"
4'- 0"
5'- 0"
6'- 0"
7'- 0"
6 1/4"
6 1/4"
6 1/4"
6 1/4"
6 1/4"
2" 1
2"
4"
2"
BIDIRECT
*INTERNAL NOTE: TABLE DIFFERS SLIGHTLY FROM BIDIRECT AND DIRECT/INDIRECT
Edge View Lens
(EGLD)
FIXTURE PERFORMANCE
Top Glow
(TGLD)
SM
DIRECT DISTRIBUTION
INDIRECT DISTRIBUTION
Lambertian (No Optic)
Lambertian (No Optic)
Direct
Nominal Lumens/Foot 300LMF 400LMF 600LMF 800LMF 1000LMF 1200LMF 1400LMF 1500LMF
Delivered Lumens/Foot 292 394 575 791 973 1192 1352 1442
Input Watts/Foot 2.39 3.14 4.68 6.33 7.96 10.00 11.93 13.01
Lumens/Watt 122 126 123 125 122 119 113 111
Indirect
Nominal Lumens/Foot 300LMF 400LMF 600LMF 800LMF 1000LMF 1200LMF 1400LMF 1500LMF
Delivered Lumens/Foot 325 405 610 797 1027 1225 1484 1580
Input Watts/Foot 1.95 2.55 3.82 4.85 6.19 7.54 8.98 9.78
Lumens/Watt 166 159 160 164 166 163 165 162
Based on a 4ft 35K fixture with standard lambertian distribution http://marklighting.com https://declare.living-future.org/search?query=acuity https://www.acuitybrands.com/resources/buy-american
S4WIDMP WALL PATTERN 03/13/23 marklighting.com | 800-705-SERV (7378) | © 2022-2023 Acuity Brands Lighting, Inc. All Rights Reserved. We reserve the right to change design, materials and finish in any way that will not alter installed appearance or reduce function and performance.
MARK
ARCHITECTURAL
LIGHTING TM
SLOT 4
Wall Indirect/Direct Pattern
Series Linear Plan Fixture Dimensions Connectors Direct Light Source
Color Rendering Direct LED
Color Temp Direct Lumen Output
S4WIDMP Slot 4 Wall Indirect/ Direct Master Pattern (Formerly S4LWIDP)
CPP Closed Pattern Plan OPP Open Pattern Plan RPP Rectangular Pattern Plan SPP Square Pattern Plan
_FT Specify pattern in total linear feet.
Unit length may affect available options.
90IC 90 Degree Horizontal Inside Corner
90OC 90 Degree Horizontal Outside Corner
Corner angles available from 40° - 160°. Replace the 90 with the appropriate corner degree to specify. For more information, see page x.
80CRI 80 CRI
90CRI 90 CRI
27K 2700K 30K 3000K 35K 3500K 40K 4000K 50K 5000K
300LMF 300 Lumens per Foot 400LMF 400 Lumens per Foot 600LMF 600 Lumens per Foot 800LMF 800 Lumens per Foot 1000LMF 1000 Lumens per Foot 1200LMF 1200 Lumens per Foot 1400LMF 1400 Lumens per Foot 1500LMF 1500 Lumens per Foot _LMF Specify Lumens between
300LMF - 1500LMF in 50LMF increments
Indirect Light Source Color
Rendering Indirect LED Color Temp Indirect Lumen Output Switching
Minimum Dimming Level Direct Shielding Indirect Shielding
I80CRI 80CRI
I90CRI 90CRI
I27K 2700K I30K 3000K I35K 3500K I40K 4000K I50K 5000K
I300 LMF 300 Lumens per FT I400 LMF 400 Lumens per FT I600LMF 600 Lumens per FT I800LMF 800 Lumens per FT I1000LMF 1000 Lumens per FT I1200LMF 1200 Lumens per FT I1400LMF 1400 Lumens per FT I1500LMF 1500 Lumens per FT _LMF Specify Lumens between
300LMF - 1500LMF in 50LMF increments
SCT Single Circuit/ Single switching
DCT 1 Dual Circuit/Dual Switching
1. DCT is not available with sensors or NLTAIR2. Not available on fixtures under 4'. DCT with E10WLCP is not available in units under 5'.
NODIM 1 no dimming MIN1 Constant current dimming to 1% DARK Constant current dimming to 0.1% MIN10 2 Constant Current
Dimming to 10%
1. Not available with Control Input options.
2. MIN10 is not available with DALI, ECOD or ECOD2.
FLL Flush Lens EGLD 1 Edge Glow Direct Lens
(edgeview)
1. EGLD is not available with E10WLCP, NLTAIR2 or sensors. Only available in whole foot increments.
TGLD 1 Top Glow Lens DC Clear Dust Cover DCF Frosted Dust Cover 1.TGLD is only available in whole foot increments. It's not available with E10WLCP or NLTAIR2.
Voltage Finish Emergency Options Control Input Primary Sensor Secondary Sensor
MVOLT Multi-Volt, 120-277
120 120V 277 277V 347 1 347V ( in every fixture step down transformer)
1. 347 & DCT are not available under 4'. 347 is only available with ZT.
347 is not available with emergency options or sensors.
WHTT White, Satin BLKT Black, Satin SLVT Silver, Satin RALTBD 1 RAL paint finishes RALTBD is for pricing only.
Replace with applicable RAL number & finish when placing order.
(blank) No Emergency Option _E10WLCP 1 Emergency Battery
Pack WEC 2 Emergency circuit for entire run _EC # of Emergency Circuits GTD 3 Generator Transfer
Device (remote) Battery packs are not available in connectors. For more information on the emergency options, see page x.
1. E10WLCP is not available in units under 7'.
2. WEC is not available with NLIGHT, NLTAIR2 or sensors.
3. GTD is remote mounted. GTD is not available with MVOLT or 347.
(blank) Non-Dimming
ZT 0-10V
NLIGHT nLight Wired NLTAIR2 1 nLight Air 2 Wireless Enabled
DALI 2 DALI
ECOD 3 Lutron EcoSystem Digital Driver For additional ordering assistance consult "Intelligent Luminaire Technology Guide" on page 7
1. NLTAIR2 can be used as a normal power sensing device for nLight Air devices and luminaires with EM emergency options. It is not available with NODIM or DCT with EC or BGTD.
Not available on units under 4'.
2. DALI is only available with DARK. DALI is not available with sensors.
3. ECOD is only available with MIN1. It is not available with E10WLCP & sensors. It is only available with 300LMF, 600LMF, 1000LMF or 1500LMF.
(blank) No sensors NS_ Primary Zone with No
Sensor (Specify length in feet)
ADC 1 Daylight Dimming Sensor PDT 1 Dual Technology
Occupancy Sensor, PIR and Microphonics Sensor
APIR 2 Passive Infrared Occupancy and Daylight Dimming Sensor
APDT 2 Dual Technology Occupancy and Daylight Dimming Sensor
Sensors are only available with FLL and fixtures 4' and above. Sensors are not available in connectors. For more information, see page 6.
1. ADC & PDT are available with ZT or
NLIGHT
2. APIR & APDT are available with ZT, NLIGHT or NLTAIR2.
(blank) No Sensors or Secondary Zone SNS_ Secondary Zone with No Sensor
(Specify length in feet) SADC 1 Daylight Dimming Sensor, Secondary Zone SPDT 1 Dual Technology Occupancy
Sensor, PIR and Microphonics Sensor, Secondary Zone
SAPIR 2 Passive Infrared Occupancy and Daylight Dimming Sensor, Secondary Zone
SAPDT 2 Dual Technology Occupancy and Daylight Dimming Sensor, Secondary Zone
Sensors are only available with FLL and fixtures 4' and above. Sensors are not available in connectors. For more information, see page 6.
1. ADC & PDT are available with ZT or NLIGHT
2. APIR & APDT are available with ZT, NLIGHT or NLTAIR2.
Tertiary Zone Options
(blank) No Tertiary Zone TNS_ Tertiary Zone
(Specify length in feet)
(blank) No Options BAA Manufactured in US
ORDERING Example: S4WIDMP OPP 32FT 290IC 90CRI 35K 800LMF I90CRI I35K I1200LMF DARK FLL SCT MVOLT WHTT ZT
Note: Unit length and lumen outputs may affect available options.
http://marklighting.com https://marklighting.acuitybrands.com/-/media/abl/acuitybrands/files/resources/customer-tools/paint-colors/architectural-ral-color-brochure.pdf?forceBehavior=open https://marklighting.acuitybrands.com/-/media/abl/acuitybrands/files/resources/customer-tools/paint-colors/architectural-ral-color-brochure.pdf?forceBehavior=open bascot Highlight bascot Highlight bascot Highlight bascot Highlight bascot Highlight bascot Highlight bascot Highlight bascot Highlight bascot Highlight bascot Highlight bascot Highlight bascot Highlight bascot Highlight bascot Highlight bascot Highlight bascot Highlight bascot Highlight
S4WIDMP WALL PATTERN 03/13/23 marklighting.com | 800-705-SERV (7378) | © 2022-2023 Acuity Brands Lighting, Inc. All Rights Reserved. We reserve the right to change design, materials and finish in any way that will not alter installed appearance or reduce function and performance.
MARK
ARCHITECTURAL
LIGHTING TM
SLOT 4
Wall Indirect/Direct Pattern
PATTERN ORDERING GUIDE
Slot 4 LED patterns can be configured in 1" increments with illuminated corners, X & T connectors. Corners are available between 40° and 160° in 1° increments. For custom angles, corners of junction lengths, consult factory.
• 4 corners are required for SPP & RPP plans.
• The system will only price a maximum of 6 of each type of connector on one order line and up to 100 total feet. Please consult with quotations to determine pricing if over limits.
• Total Run Length = all sides of the pattern
10’
14’
8’
12’
8’
15’
8’
7’
9’
17’
14’
14’
Total run length = 24FT 190IC or 90IC = (1) 90° inside corner Nomenclature:
S4WIDMP OPP 24FT 190IC 90CRI 30K
600LMF I90CRI I30K I800LMF SCT DARK
MVOLT WHT ZT
LAYOUT SKETCH
Please draw and configure your pattern plan below.
4’
4’
Total run length = 40FT 490IC = (4) 90° inside corners Nomenclature:
S4WIDMP RPP 40FT 490IC 90CRI 30K
600LMF I90CRI I30K I800LMF SCT MIN1
MVOLT WHT ZT
10’
14’
8’
12’
8’
15’
8’
7’
9’
17’
14’
14’
Total Run length = 64FT 590IC = (5) 90° inside corners 190OC = (1) 90° outside corner Nomenclature:
S4WIDMP CPP 64FT 590IC 190OC 90CRI 30K
600LMF I90CRI I30K I800LMF SCT MIN1
MVOLT WHT ZT
10’
14’
8’
12’
8’
15’
8’
7’
9’
17’
14’
14’ http://marklighting.com
S4WIDMP WALL PATTERN 03/13/23 marklighting.com | 800-705-SERV (7378) | © 2022-2023 Acuity Brands Lighting, Inc. All Rights Reserved. We reserve the right to change design, materials and finish in any way that will not alter installed appearance or reduce function and performance.
MARK
ARCHITECTURAL
LIGHTING TM
SLOT 4
Wall Indirect/Direct Pattern
Run Patterns, Corners and Junction Patterns can be configured in 1" increments with illuminated L connectors with standard 2’ corner. L connectors are available in 40-160 degrees in 1 degree increments.
For custom angles, corner or junction lengths, consult factory.
4"
4"
4" 40°-160°
40°-160°
SLOT 4 CORNERS (S4WD, S4WI, S4WID)
Inside Corner (IC)
SHIELDING, OPTICS & CONNECTORS
Direct Shielding
Indirect Shielding
Outside Corner (OC)
DUST COVER TOP GLOW INDIRECT BATWING INDIRECT ASYMMETRIC
4" 51
4" 53 8"
4"
4"
4"
2"
2"
2"
2"
2"
2"
1/2" DROP LENS
CO-EXTRUDED LENS LOUVER EDGE GLOW LENS
1" DROP LENS
1-1/2" DROP LENS
4"
2"
1" 2"
2"
4"
2"
8"
2"
4"
2"
4"
SHIELDING
INDIRECT OPTICS
BIDIRECT
8"
8"
DUST COVER TOP GLOW INDIRECT BATWING INDIRECT ASYMMETRIC
4" 51
4" 53 8"
4"
4"
4"
2"
2"
2"
2"
2"
2"
1/2" DROP LENS
CO-EXTRUDED LENS LOUVER EDGE GLOW LENS
1" DROP LENS
1-1/2" DROP LENS
4"
2"
1" 2"
2"
4"
2"
8"
2"
4"
2"
4"
SHIELDING
INDIRECT OPTICS
BIDIRECT
8"
8"
EDGE GLOW LENS
DUST COVER TOP GLOW
S4WIDMP WALL PATTERN 03/13/23 marklighting.com | 800-705-SERV (7378) | © 2022-2023 Acuity Brands Lighting, Inc. All Rights Reserved. We reserve the right to change design, materials and finish in any way that will not alter installed appearance or reduce function and performance.
MARK
ARCHITECTURAL
LIGHTING TM
SLOT 4
Wall Indirect/Direct Pattern
Choose nomenclature from these columns
D riv er C on fig ur at io ns
Minimum Dimming Level Control Input Dimming
Range Notes
NO DIM + (blank) - No 0-10V leads from the driver.
MIN10 + ZT 100 to 10%
MIN1 + ZT 100 to 1%
MIN1 + NLIGHT 100 to 1%
MIN1 ECOD 100 to 1% Lutron Hi-lume 1% EcoSystem LED Driver with Soft-on, Fade-to-Black (model LDE1)
DARK ZT 100 to 0.1%
DARK NLIGHT 100 to 0.1%
DARK DALI 100 to 0.1% "Compatible with DALI. Formerly (EDB & EDAB) nomenclature." Logarithmic dimming
INTELLIGENT LUMINAIRE TECHNOLOGY GUIDE
Choose nomenclature from these columns
Co nt ro l /
S en so r C on fig ur at io ns
Control Input Sensor Sensor Notes
ZT + ADC = MSD ADC Automatic dimming control integral photocell.
ZT + PDT = MSD PDT 7 Dual technology integral occupany sensor.
ZT + APIR = MSD 7 ADC PIR integral occupancy sensor with automatic dimming control photocell.
ZT + APDT = MSD PDT 7 ADC Dual technology integral occupany sensor with automatic dimming control photocell.
NLIGHT + (blank) = nIO EZ PH nLight enabled only. No onboard sensor.
NLIGHT + ADC = nIO EZ PH + nES ADCX Automatic dimming control integral photocell. nLight enabled.
NLIGHT + PDT = nIO EZ PH + nES PDT 7 360° Dual technology integral occupany sensor. nLight enabled.
NLIGHT + APIR = nIO EZ PH + nES 7 ADCX 360° PIR integral occupancy sensor with automatic dimming control photocell. nLight enabled.
NLIGHT + APDT = nIO EZ PH + nES PDT 7 ADCX 360° Dual technology integral occupany sensor with automatic dimming control photocell. nLight enabled.
NLTAIR2 + (blank) = RIO EZDL EXT900 ACWH 90D G2 nLight AIR enabled only. No onboard sensor.
NLTAIR2 + APIR = RES7 EXT900 ACWH 90D G2 PIR integral occupancy sensor with automatic dimming control photocell. nLight AIR enabled.
NLTAIR2 + APDT = RES7 PDT EXT900 ACWH 90D G2 Dual technology integral occupany sensor with automatic dimming control photocell. nLight AIR enabled.
For more information, please consult our technical guides for nLight or nLight Air.
UL924 Sequence of Operation
The below information applies to all nLight AIR devices with an EM option.
• EM devices will remain at their high-end trim and ignore wireless lighting control commands, unless a normal-power-sensed (NPS) broadcast is received at least every 8 seconds.
• Using the CLAIRITY+ mobile app, EM devices must be associated with a group that includes a normal power sensing device to receive NPS broadcasts.
• Only non-emergency rPP20, rLSXR, rSBOR, rSDGR, and nLight AIR luminaires with version 3.4 or later firmware can provide normal power sensing for EM devices. See specification sheets for control devices and luminaires for more information on options that support normal power sensing.
nLight ® Wired Control Accessories Order as separate catalog number
Wall Switches Model Number
On/Off single pole nPODMA (color)
On/Off two pole nPODMA 2P (color)
On/Off single pole, dimming nPODMA DX (color)
On/Off two pole, dimming nPODMA 2P DX (color)
On/Off, two level nPODMA 2L (color)
Graphic touchscreen nPOD TOUCH (color)
For more information see nPOD and nPOD TOUCH spec sheets nLight AIR ® Control Accessories Order as separate catalog number
Wall Switches Model Number
On/Off single pole rPODBA (color)
On/Off two pole rPODBA 2P (color)
On/Off single pole, dimming rPODBA DX (color)
On/Off two pole, dimming rPODBA 2P DX (color)
On/Off, 4 scene control rPODBA 4S (color)
For more information see rPOD spec sheets http://marklighting.com https://img.acuitybrands.com/public-assets/catalog/1252937/nl_1008400_nlight-wired-architectural-ambient-tech-guide_0122_002.pdf?abl_version=09%2f23%2f2022+17:41:51&DOC_Type=Technical_Bulletins https://img.acuitybrands.com/public-assets/catalog/1252937/nltair2-architectural-ambient-tech-guide.pdf?abl_version=09%2f12%2f2022+21:15:29&DOC_Type=Technical_Bulletins https://img.acuitybrands.com/public-assets/catalog/982001/npodma.pdf?abl_version=03%2f16%2f2022+23:32:37&DOC_Type=SPEC_SHEET%0D https://img.acuitybrands.com/public-assets/catalog/982001/npodma.pdf?abl_version=03%2f16%2f2022+23:32:37&DOC_Type=SPEC_SHEET%0D https://img.acuitybrands.com/public-assets/catalog/982001/npodma.pdf?abl_version=03%2f16%2f2022+23:32:37&DOC_Type=SPEC_SHEET%0D https://img.acuitybrands.com/public-assets/catalog/982001/npodma.pdf?abl_version=03%2f16%2f2022+23:32:37&DOC_Type=SPEC_SHEET%0D https://img.acuitybrands.com/public-assets/catalog/982001/npodma.pdf?abl_version=03%2f16%2f2022+23:32:37&DOC_Type=SPEC_SHEET%0D https://img.acuitybrands.com/public-assets/catalog/981468/npod-touch.pdf?abl_version=12%2f03%2f2020+18:45:12&DOC_Type=SPEC_SHEET https://img.acuitybrands.com/public-assets/catalog/982001/npodma.pdf?abl_version=03%2f16%2f2022+23:32:37&DOC_Type=SPEC_SHEET%0D https://img.acuitybrands.com/public-assets/catalog/981468/npod-touch.pdf?abl_version=12%2f03%2f2020+18:45:12&DOC_Type=SPEC_SHEET https://img.acuitybrands.com/public-assets/catalog/982003/rpodba.pdf?abl_version=10%2f12%2f2022+13:29:20&DOC_Type=SPEC_SHEET https://img.acuitybrands.com/public-assets/catalog/982003/rpodba.pdf?abl_version=10%2f12%2f2022+13:29:20&DOC_Type=SPEC_SHEET https://img.acuitybrands.com/public-assets/catalog/982003/rpodba.pdf?abl_version=10%2f12%2f2022+13:29:20&DOC_Type=SPEC_SHEET https://img.acuitybrands.com/public-assets/catalog/982003/rpodba.pdf?abl_version=10%2f12%2f2022+13:29:20&DOC_Type=SPEC_SHEET https://img.acuitybrands.com/public-assets/catalog/982003/rpodba.pdf?abl_version=10%2f12%2f2022+13:29:20&DOC_Type=SPEC_SHEET https://img.acuitybrands.com/public-assets/catalog/982003/rpodba.pdf?abl_version=10%2f12%2f2022+13:29:20&DOC_Type=SPEC_SHEET
S4WIDMP WALL PATTERN 03/13/23 marklighting.com | 800-705-SERV (7378) | © 2022-2023 Acuity Brands Lighting, Inc. All Rights Reserved. We reserve the right to change design, materials and finish in any way that will not alter installed appearance or reduce function and performance.
MARK
ARCHITECTURAL
LIGHTING TM
SLOT 4
Wall Indirect/Direct Pattern
Integrated Controls Optional nLight® integrated controls make Slot LED luminaires addressable- allowing them to digitally communicate with other nLight enabled controls such as dimmers, switches, occupancy sensors and photocontrols. Simply connect all the nLight enabled control devices using standard CAT5 Cabling (included).
Occupancy Sensor and/or Photocell
3 1/2"
SENSOR (FOR ALL) ANTENNA (SURFACE) ANTENNA (PENDANT DIRECT)
ANTENNA (PENDANT
INDIRECT AND BIDIRECT)
ANTENNA (WALL DIRECT) ANTENNA (WALL
INDIRECT AND BIDIRECT)
32FT
8FT 8FT 8FT 8FT
32FT MSL8 RUN WITH 2 SENSORS WITH PRIMARY ZONE 24FT AND SECONDARY ZONE 8FT -- PDT24 SADC8
PRIMARY ZONE:
PDT24 (DUAL TECH SENSOR, 24FT ZONE)
32FT
8FT 8FT 8FT 8FT
32FT MSL8 RUN WITH 1 SENSOR ALL ONE ZONE -- ADC
PRIMARY ZONE:
ADC (DAYLIGHT SENSOR). SINCE THERE IS NO NUMBER AFTER THE ADC SENSOR NOMENCLATURE, THE SENSOR WILL CONTROL THE ENTIRE RUN.
32FT
8FT 8FT 8FT 8FT
32FT MSL8 RUN WITH 1 SENSOR ALL ONE ZONE -- PDT16
DOES NOT WORK BECAUSE THE LENGTH OF THE ZONE SPECIFIED (16FT),
DOES NOT MATCH THE ENTIRE RUN (32FT)
32FT
8FT 8FT 8FT 8FT
32FT MSL8 RUN WITH 2 SENSORS WITH PRIMARY ZONE 20FT AND SECONDARY ZONE 12FT -- PDT20 SADC12
INCORRECT:
NOTE: IF THERE IS ONLY ONE ZONE, LEAVE THE NUMBERS AFTER THE SENSOR NOMENCLATURE BLANK. EXAMPLE: NO PDT16, USE PDT
DOES NOT WORK BECAUSE THE LENGTH OF THE ZONES SPECIFIED (20FT AND 12FT),
DOES NOT WORK FOR 8FT FIXTURE SECTIONS, ZONES CANNOT SPLIT A FIXTURE SECTION
PRIMARY ZONE: 20FT
SECONDARY ZONE: 12FT
Notes:
• Only one sensor per zone
• At the most, the entire run can only have 2 sensors (thus 2 sensors zones at the most)
• Sensor zone can not split fixture sections
• No overlapping zones
CORRECT:
SECONDARY ZONE:
SADC (DAYLIGHT SENSOR, 8FT ZONE)
Total Run Length to Order
Total Run Length to Order
INTEGRATED SENSOR LAYOUT
For runs longer than 8FT:
ALWAYS order the run by the TOTAL RUN LENGTH. Ordering the sections individually will not provide the correct joining hardware to allow connection in the field.
At the 7.5 ft (2.9 m) hanging height of a typical pendant mount fixture the sensor provides 10 ft (3.05 m) radial detection of small motion. At a 9 ft (2.74 m) hanging height the radius is 12 ft (3.66
m) for small motion.
Adequate for walking motion detection from mounting heights between 7.5 ft (2.29 m) and 20 ft (6.10 m).
Initial detection will occur earlier when walking across sensor’s field of view than when walking directly at sensor.
Initial detection of walking motion into long coverage segment will occur at distances of 2x the mounting height up to 15 ft (4.57
m) and 1.75x up to 20 ft (6.10 m). Lens assembly rotates 15° to enable adjustment in order to line up long segments.
Lens rotates 15° to enable adjustment
12.5
2.5
0 ft
2.5
12.5
4.5
3.8
2.5
1.5
0.75
0 m
0.75
1.5
2.5
3.8
4.5
OCCUPANCY DETECTION COVERAGE
nLight Air Wireless Antenna Location Note: Antenna will be shipped separately and will need to be attached to the coax connector.
32FT
8FT 8FT 8FT 8FT
32FT MSL8 RUN WITH 2 SENSORS WITH PRIMARY ZONE 24FT AND SECONDARY ZONE 8FT -- PDT24 SADC8
PRIMARY ZONE:
PDT24 (DUAL TECH SENSOR, 24FT ZONE)
32FT
8FT 8FT 8FT 8FT
32FT MSL8 RUN WITH 1 SENSOR ALL ONE ZONE -- ADC
PRIMARY ZONE:
ADC (DAYLIGHT SENSOR). SINCE THERE IS NO NUMBER AFTER THE ADC SENSOR NOMENCLATURE, THE SENSOR WILL CONTROL THE ENTIRE RUN.
32FT
8FT 8FT 8FT 8FT
32FT MSL8 RUN WITH 1 SENSOR ALL ONE ZONE -- PDT16
DOES NOT WORK BECAUSE THE LENGTH OF THE ZONE SPECIFIED (16FT),
DOES NOT MATCH THE ENTIRE RUN (32FT)
32FT
8FT 8FT 8FT 8FT
32FT MSL8 RUN WITH 2 SENSORS WITH PRIMARY ZONE 20FT AND SECONDARY ZONE 12FT -- PDT20 SADC12
INCORRECT:
NOTE: IF THERE IS ONLY ONE ZONE, LEAVE THE NUMBERS AFTER THE SENSOR NOMENCLATURE BLANK. EXAMPLE: NO PDT16, USE PDT
DOES NOT WORK BECAUSE THE LENGTH OF THE ZONES SPECIFIED (20FT AND 12FT),
DOES NOT WORK FOR 8FT FIXTURE SECTIONS, ZONES CANNOT SPLIT A FIXTURE SECTION
PRIMARY ZONE: 20FT
SECONDARY ZONE: 12FT
Notes:
• Only one sensor per zone
• At the most, the entire run can only have 2 sensors (thus 2 sensors zones at the most)
• Sensor zone can not split fixture sections
• No overlapping zones
CORRECT:
SECONDARY ZONE:
SADC (DAYLIGHT SENSOR, 8FT ZONE)
Total Run Length to Order
Total Run Length to Order
32FT MSL8 RUN WITH 2 SENSORS WITH PRIMARY ZONE 16FT, SECONDARY ZONE 8FT,
AND TERTIARY ZONE 8FT-- ADC16 SPDT8 TNS8
8FT 8FT
PRIMARY ZONE:
ADC (DAYLIGHT SENSOR, 16FT ZONE)
32FT
Total Run Length to Order
8FT 8FT
TERTIARY ZONE:
TNS (NO SENSOR, 8FT ZONE)
SECONDARY ZONE:
SPDT8 (DUAL TECH SENSOR, 8FT ZONE)
S4WIDMP WALL PATTERN 03/13/23 marklighting.com | 800-705-SERV (7378) | © 2022-2023 Acuity Brands Lighting, Inc. All Rights Reserved. We reserve the right to change design, materials and finish in any way that will not alter installed appearance or reduce function and performance.
MARK
ARCHITECTURAL
LIGHTING TM
SLOT 4
Wall Indirect/Direct Pattern
Remote GTD Mounting Option Recessed in ceiling. Consult factory for other ceiling types or canopy options.
6 foot flexible conduit included, GTD option should be mounted within 6 feet of junction box above fixture.
Accessible Ceiling
EMERGENCY OPTIONS
How to Estimate Delivered Lumens in Emergency Mode Use the formula below to estimate the delivered lumens in emergency mode Delivered Lumens = 1.25 x P x LPW P = 10W for PS1055LCP LPW = Lumen per watt rating of the luminaire This information is available on page 1 of this spec sheet or appropriate IES file.
(By Acuity) (By others)
Section Length E10WLCP EC
U2 None Entire unit
U3 None Entire unit
U4 Entire unit Entire unit
U5 Last 3' Entire unit
U6 Last 3' Entire unit
U7 Last 4' Entire unit
U8 Last 4' Entire unit
Emergency Circuits
EC
Multiple EC
WEC
Note: Whole run on emergency circuit nltAIR2/nLight PP in second fixture
WEC
WEC
Note: Whole run on emergency circuit nltAIR2/nLight PP in first fixture
Note: Whole run on emergency circuit0% 0% 0%
0% 0%
0% 0%
0%
0% 0% E10WLCP/R 0%
0% 0% 0% 100%0%
0% 0% 0%
0% 0%
0% 0%
0%
0% 100% EC
0% 0% 100%0% 100%
100%
0% 0% 0%
0% 0%
0% 100% EC
0% 100%0% 100%
100%100% EC
100%100%
100%
0% 0% 0%
0% 0%
0% 0%
0%
0% 0% E10WLCP/R 0%
0% 0% 100%0%
E10WLCP/R
100%
100% EC
100%100%
100%100% EC
100%100%
100%100% EC
100%100%
100%100% EC
100%100%
100%
EC
MULTIPLE EC
E10WLCP
MULTIPLE E10WLCP
EMERGENCY, S2WID/S4WID
WEC
(WHOLE RUN ON EMERGENCY CIRCUIT)
WEC
(WHOLE RUN ON EMERGENCY CIRCUIT
NLTAIR2/NLIGHT PP IN FIRST FIXTURE)
WEC
(WHOLE RUN ON EMERGENCY CIRCUIT
NLTAIR2/NLIGHT PP IN SECOND FIXTURE)
100%
100%100%
100%100%
100%100%
100%100%
100%100%
100%100% EC
100%100%
100%
100%
100%100%
100%100%
100%100%
100%100% EC
100%100%
100%100%
100%100%
100%
0% 0% 0%
0% 0%
0% 0%
0%
0% 0% E10WLCP/R 0%
0% 0% 0% 100%0%
0% 0% 0%
0% 0%
0% 0%
0%
0% 100% EC
0% 0% 100%0% 100%
100%
0% 0% 0%
0% 0%
0% 100% EC
0% 100%0% 100%
100%100% EC
100%100%
100%
0% 0% 0%
0% 0%
0% 0%
0%
0% 0% E10WLCP/R 0%
0% 0% 100%0%
E10WLCP/R
100%
100% EC
100%100%
100%100% EC
100%100%
100%100% EC
100%100%
100%100% EC
100%100%
100%
EC
MULTIPLE EC
E10WLCP
MULTIPLE E10WLCP
EMERGENCY, S2WID/S4WID
WEC
(WHOLE RUN ON EMERGENCY CIRCUIT)
WEC
(WHOLE RUN ON EMERGENCY CIRCUIT
NLTAIR2/NLIGHT PP IN FIRST FIXTURE)
WEC
(WHOLE RUN ON EMERGENCY CIRCUIT
NLTAIR2/NLIGHT PP IN SECOND FIXTURE)
100%
100%100%
100%100%
100%100%
100%100%
100%100%
100%100% EC
100%100%
100%
100%
100%100%
100%100%
100%100%
100%100% EC
100%100%
100%100%
100%100%
100%
0% 0% 0%
0% 0%
0% 0%
0%
0% 0% E10WLCP/R 0%
0% 0% 0% 100%0%
0% 0% 0%
0% 0%
0% 0%
0%
0% 100% EC
0% 0% 100%0% 100%
100%
0% 0% 0%
0% 0%
0% 100% EC
0% 100%0% 100%
100%100% EC
100%100%
100%
0% 0% 0%
0% 0%
0% 0%
0%
0% 0% E10WLCP/R 0%
0% 0% 100%0%
E10WLCP/R
100%
100% EC
100%100%
100%100% EC
100%100%
100%100% EC
100%100%
100%100% EC
100%100%
100%
EC
MULTIPLE EC
E10WLCP
MULTIPLE E10WLCP
EMERGENCY, S2WID/S4WID
WEC
(WHOLE RUN ON EMERGENCY CIRCUIT)
WEC
(WHOLE RUN ON EMERGENCY CIRCUIT
NLTAIR2/NLIGHT PP IN FIRST FIXTURE)
WEC
(WHOLE RUN ON EMERGENCY CIRCUIT
NLTAIR2/NLIGHT PP IN SECOND FIXTURE)
100%
100%100%
100%100%
100%100%
100%100%
100%100%
100%100% EC
100%100%
100%
100%
100%100%
100%100%
100%100%
100%100% EC
100%100%
100%100%
100%100%
100%
0% 0% 0%
0% 0%
0% 0%
0%
0% 0% E10WLCP/R 0%
0% 0% 0% 100%0%
0% 0% 0%
0% 0%
0% 0%
0%
0% 100% EC
0% 0% 100%0% 100%
100%
0% 0% 0%
0% 0%
0% 100% EC
0% 100%0% 100%
100%100% EC
100%100%
100%
0% 0% 0%
0% 0%
0% 0%
0%
0% 0% E10WLCP/R 0%
0% 0% 100%0%
E10WLCP/R
100%
100% EC
100%100%
100%100% EC
100%100%
100%100% EC
100%100%
100%100% EC
100%100%
100%
EC
MULTIPLE EC
E10WLCP
MULTIPLE E10WLCP
EMERGENCY, S2WID/S4WID
WEC
(WHOLE RUN ON EMERGENCY CIRCUIT)
WEC
(WHOLE RUN ON EMERGENCY CIRCUIT
NLTAIR2/NLIGHT PP IN FIRST FIXTURE)
WEC
(WHOLE RUN ON EMERGENCY CIRCUIT
NLTAIR2/NLIGHT PP IN SECOND FIXTURE)
100%
100%100%
100%100%
100%100%
100%100%
100%100%
100%100% EC
100%100%
100%
100%
100%100%
100%100%
100%100%
100%100% EC
100%100%
100%100%
100%100%
100%
0% 0% 0%
0% 0%
0% 0%
0%
0% 0% E10WLCP/R 0%
0% 0% 0% 100%0%
0% 0% 0%
0% 0%
0% 0%
0%
0% 100% EC
0% 0% 100%0% 100%
100%
0% 0% 0%
0% 0%
0% 100% EC
0% 100%0% 100%
100%100% EC
100%100%
100%
0% 0% 0%
0% 0%
0% 0%
0%
0% 0% E10WLCP/R 0%
0% 0% 100%0%
E10WLCP/R
100%
100% EC
100%100%
100%100% EC
100%100%
100%100% EC
100%100%
100%100% EC
100%100%
100%
EC
MULTIPLE EC
E10WLCP
MULTIPLE E10WLCP
EMERGENCY, S2WID/S4WID
WEC
(WHOLE RUN ON EMERGENCY CIRCUIT)
WEC
(WHOLE RUN ON EMERGENCY CIRCUIT
NLTAIR2/NLIGHT PP IN FIRST FIXTURE)
WEC
(WHOLE RUN ON EMERGENCY CIRCUIT
NLTAIR2/NLIGHT PP IN SECOND FIXTURE)
100%
100%100%
100%100%
100%100%
100%100%
100%100%
100%100% EC
100%100%
100%
100%
100%100%
100%100%
100%100%
100%100% EC
100%100%
100%100%
100%100%
100%
Emergency Battery Packs The PS1055LCP battery is integral to the fixture and comes standard with a remote test switch and self-diagnostics.
Only direct light portion operated by emergency, as indicated below. Battery packs cannot be placed in the connectors.
E10WLCP
Multiple E10WLCP
0% 0% 0%
0% 0%
0% 0%
0%
0% 0% E10WLCP/R 0%
0% 0% 0% 100%0%
0% 0% 0%
0% 0%
0% 0%
0%
0% 100% EC
0% 0% 100%0% 100%
100%
0% 0% 0%
0% 0%
0% 100% EC
0% 100%0% 100%
100%100% EC
100%100%
100%
0% 0% 0%
0% 0%
0% 0%
0%
0% 0% E10WLCP/R 0%
0% 0% 100%0%
E10WLCP/R
100%
100% EC
100%100%
100%100% EC
100%100%
100%100% EC
100%100%
100%100% EC
100%100%
100%
EC
MULTIPLE EC
E10WLCP
MULTIPLE E10WLCP
EMERGENCY, S2WID/S4WID
WEC
(WHOLE RUN ON EMERGENCY CIRCUIT)
WEC
(WHOLE RUN ON EMERGENCY CIRCUIT
NLTAIR2/NLIGHT PP IN FIRST FIXTURE)
WEC
(WHOLE RUN ON EMERGENCY CIRCUIT
NLTAIR2/NLIGHT PP IN SECOND FIXTURE)
100%
100%100%
100%100%
100%100%
100%100%
100%100%
100%100% EC
100%100%
100%
100%
100%100%
100%100%
100%100%
100%100% EC
100%100%
100%100%
100%100%
100% https://img.acuitybrands.com/public-assets/catalog/755258/ps1055lcp_ps1555lcp_ps1555mcp.pdf?abl_version=01%2f24%2f2022+16:57:20&DOC_Type=SPEC_SHEET
S4WIDMP WALL PATTERN 03/13/23 marklighting.com | 800-705-SERV (7378) | © 2022-2023 Acuity Brands Lighting, Inc. All Rights Reserved. We reserve the right to change design, materials and finish in any way that will not alter installed appearance or reduce function and performance.
MARK
ARCHITECTURAL
LIGHTING TM
SLOT 4
Wall Indirect/Direct Pattern
SPECIFICATIONS
Housing One-piece extruded aluminum housing
Finish Standard colors for fixtures and end caps are polyester powder coated white, black, or silver with satin sheen. Consult factory for custom colors and RAL color options.
Lenses/Shielding Indirect: Clear acrylic, dust cover (DC), frosted, acrylic dust cover (DCF), Extruded acrylic top glow lens (TGLD).
Direct: Extruded acrylic lens (FLL) and edge glow lens (EGLD).
LED Components Multiple lumen packages available with 2700K, 3000K, 3500K, 4000K and 5000K CCT. The Acuity Brands circuit boards for the linear LED components use a precise binning algorithm which creates a consistent color temperature from board to board. The color a variation of no greater than a 2.5 Step MacAdam (2.55DECM) along the black body locus from board to board.
Electrical Long-life LEDs, coupled with high-efficiency drivers, provide superior quantity and quality of illumination for extended service life. 90% LED lumen maintenance at 60,000 hours (L90/60,000).
Circuits Single and dual switching options available. Dual switching offered with shared neutral.
Controls System Networking Options Optional integrated nLight® controls make each fixture addressable - allowing it to digitally communicate with other nLight enabled controls such as dimmers, switches, occupancy sensors, and photocontrols. Connection to nLight is simple. It can be accomplished with remote nLight AIR wireless or through standard Cat-5 cabling. (cabling “by others") nLight offers unique plug-and-play convenience as devices and luminaires automatically discover each other, while nLight AIR is commissioned easily through an intuitive mobile app.
Emergency Battery (Optional) Integral emergency battery (E10WLCP) for 90 minutes of operation. Emergency battery pack, 10W, Linear Constant Power Certified in CA Title 20 MAEDBS.
Remote generator transfer device (GTD) works in conjunction with an auxiliary generator or a central inverter system to power fixtures for safe egress lighting.
Dimming Drivers Factory tuned constant current electronic dimming driver is standard.
Flicker free dimming available down to <1%. LED drivers perform within the recommended operating areas for flicker as a function of frequency and modulation (%) IEEE Standard 1789-2015 (IEEE Recommended Practices for Modulating Current in High-Brightness LEDs for Mitigating Health Risks to Viewers), in typical operating conditions at representative dimming levels.
Electrical specifications at maximum driver load: PF > 0.9 and THD <20%. Meets FCC Title 47 Class A or Class B. Other available drivers include Lutron and DALI protocol drivers. All drivers are RoHS compliant.
Environment Suitable for damp location. Indoor use only.
Certification CSA certified to meet U.S. and Canadian standards (UL1598 and UL8750).
Ambient Operating Temperature -20°C (-4° F) to +25°C (+77°F).
Buy American Act Product with the BAA option is assembled in the USA and meets the Buy America(n) government procurement requirements under FAR, DFARS and DOT regulations. Please refer to www.acuitybrands.com/buy-american for additional information.
Fixture Weight 1 lb per foot, less packaging.
Warranty 5-year limited warranty. This is the only warranty provided and no other statements in this specification sheet create any warranty of any kind. All other express and implied warranties are disclaimed. Complete warranty terms located at: www.acuitybrands.com/support/warranty/terms-and-conditions
Note: Actual performance may differ as a result of end-user environment and application.
All values are design or typical values, measured under laboratory conditions at 25 °C.
Specifications subject to change without notice.
http://marklighting.com https://www.acuitybrands.com/resources/buy-american https://www.acuitybrands.com/support/warranty/terms-and-conditions
| Text Field 177: |
| Page 1: |
| Text Field 178: |
| Page 1: |
| Text Field 212: |
| Text Field 213: |
| Text Field 214: |
| Text Field 215: |
| Text Field 216: |
| Text Field 217: |
| Text Field 218: |
| Text Field 220: |
| Text Field 221: |
| Text Field 222: |
| Text Field 223: |
| Text Field 224: |
| Text Field 225: |
| Text Field 226: |
| Text Field 228: |
| Text Field 201: |
| Text Field 202: |
| Text Field 203: |
| Text Field 205: |
| Text Field 206: |
| Text Field 207: |
| Text Field 208: |
File details come from the government source that posted it. Updated .