Attachment J01 Lame Deer Construction Plans.pdf
PDF 6 MB Posted
- Attached to
- Lame Deer Heliport Reconstruction
- Solicitation number
- 75H70125R00066
About this file
These construction documents detail the Lame Deer Clinic Heliport Reconstruction project for the Indian Health Service (IHS), located in the Billings Area Office in Montana. The project involves reconstructing a heliport with specific design requirements based on Federal Aviation Administration (FAA) standards, including a Final Approach and Takeoff Area (FATO), Touchdown and Liftoff Area (TLOF), and associated safety areas. The design is optimized for helicopter models Eurocopter EC-135 and Bell Helicopter 407, with precise dimensional specifications for the helipad's layout and safety zones.
The comprehensive set of documents includes civil, electrical, structural, and mechanical plans covering site preparation, removals, grading, lighting, electrical infrastructure, foundation work, and detailed construction specifications. Key elements include installing a 12" structural concrete heliport surface, perimeter lighting, a wind sock, navigation lights, a 6' high chainlink fence with gate, and various site improvements. The project is scheduled for construction documents completion on March 7, 2025, with Short Elliott Hendrickson Inc. (SEH) serving as the engineering design firm for the Indian Health Service's Division of Engineering Services.
View the file
Other files
Show all 16
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
R
SEH Project Checked By Drawn By
Project Status Issue Date
This drawing is an instrument of service and shall remain the property of Short Elliott Hendrickson, Inc.
(SEH). This drawing, concepts and ideas contained herein shall not be used, reproduced, revised, or retained without the express written approval of SEH.
Submission or distribution of this drawing to meet official or regulatory requirements or for purposes in connection with the project is not be construed as publication in derogation of any of the rights of SEH. Sh or t E llio tt H en dr ick so n, Inc
Al l R igh ts Re se rve d
CO
PY
RI
GH
T
PROJECT OWNER
INDIAN HEALTH SERVICE (IHS)
DEPARTMENT OF HEALTH AND HUMAN
SERVICES
DIVISION OF ENGINEERING SERVICES
701 FIFTH AVENUE, MS 24, SUITE 1600
SEATTLE, WASHINGTON 98104-7304
CIVIL / MEP / STRUCTURAL
SHORT ELLIOTT HENDRICKSON INC.
2000 SOUTH COLORADO BLVD.
TOWER TWO, SUITE 1200
DENVER, CO. 80222
720.540.6800
LA
ME
D
EE
R
CL
IN
IC
H
EL
IP
OR
T
RE
CO
NS
TR
UC
TI
ON
BI
LL
IN
GS
A
RE
A
OF
FI
CE
1 F
IF
TH
A
VE
NU
E, M S
, S
UI
TE
SE
AT
TL
E, W
AS
HI
NG
TO
N
4-
180991
JH
AG
IN
DI
AN
H
EA
LT
H
SE
RV
IC
E
CONSTRUCTION DOCUMENTS 03.07.2025
REVISION SCHEDULE
REV. # DESCRIPTION DATE
COVER SHEET
G001
INDIAN HEALTH SERVICE - BILLINGS AREA
LAME DEER CLINIC HELIPORT RECONSTRUCTION
701 FIFTH AVENUE, MS 24, SUITE 1600
SEATTLE, WASHINGTON 98104-7304
CIVIL
G001 COVER SHEET
G002 GENERAL NOTES
C001 LAME DEER EXISTING CONDITIONS
C101 LAME DEER REMOVALS PLAN
C201 LAME DEER SITE PLAN
C301 LAME DEER GRADING PLAN
C401 DETAILS
C402 DETAILS
C403 DETAILS
C404 STRIPING DETAILS
ELECTRICAL
E001 ELECTRICAL TITLE SHEET
E051 LAME DEER ELECTRICAL SITE PLAN
E101 LAME DEER ENLARGED LIGHTING AND POWER PLAN
E501 LAME DEER ONE-LINE DIAGRAM
E601 LAME DEER SCHEDULES AND DETAILS
STRUCTURAL
S001 GENERAL STRUCTURAL ABBREVIATIONS, SYMBOLS AND TABLES
S002 GENERAL STRUCTURAL NOTES
S101 FOUNDATION PLANS
S114 FLOOR FRAMING PLANS
S501 CONCRETE DETAILS
S502 CONCRETE DETAILS
S531 STEEL DETAILS
MECHANICAL
MP001A MECHANICAL SYMBOLS AND ABBREVIATIONS
M101 CRAWL SPACE PLAN
DRAWING INDEXVICINITY MAP PROJECT DIRECTORY
OWNER
INDIAN HEALTH SERVICE (IHS)
DEPARTMENT OF HEALTH AND HUMAN SERVICES
DIVISION OF ENGINEERING SERVICES
701 FIFTH AVENUE, MS 24, SUITE 1600
SEATTLE, WASHINGTON 98104-7307
CIVIL / MEP / STRUCTURAL
SHORT ELLIOTT HENDRICKSON, INC. (SEH, INC.)
2000 SOUTH COLORADO BOULEVARD
SUITE 1200, COLORADO CENTER TOWER TWO
DENVER, COLORADO 80222
720.540.6800
LOCATION MAP
LAME DEER, MT
LAME DEER, MT
CONSTRUCTION DOCUMENTS
jhayson eSeal_MT_Hayson_Dynamic
LEGEND
GAS LINE
STORM LINE
SANITARY LINE
BURIED TV CABLE
RIGHT OF WAY
BURIED PHONE CABLE
PROPERTY LINE
BURIED ELECTRIC
S
DECIDUOUS TREE
MANHOLE
HAND HOLE
SOIL BORING
LIGHT STRUCTURE
HORIZONTAL CONTROL POINT
P-BUR
TV-BUR TV-BUR
T-BUR T-BUR
G
P
HH
SIGN POST
BOLLARD
CABLE FENCEO O
CULVERT
CONCRETE PAVEMENT
BUILDING
ROCK LANDSCAPE
FO FO BURIED FIBER OPTIC CABLE
SAFETY AREA
ASPHALT MAT
UNIDENTIFIED PEDESTAL
ROCK LANDSCAPE
CONCRETE SAWCUT (4 IN)
ASPHALT SAWCUT (2 IN)
REMOVAL OF CURB AND GUTTER
REMOVAL OF CONCRETE
REMOVAL OF ASPHALT
REMOVAL OF LANDSCAPE
WIND SOCK NAVIGATION LIGHT
XC CHAINLINK FENCE
SWALE
PERIMETER LIGHTS
J JUNCTION BOX
ELECTRICAL TRANSFORMER
E
R
SEH Project Checked By Drawn By
Project Status Issue Date
This drawing is an instrument of service and shall remain the property of Short Elliott Hendrickson, Inc.
(SEH). This drawing, concepts and ideas contained herein shall not be used, reproduced, revised, or retained without the express written approval of SEH.
Submission or distribution of this drawing to meet official or regulatory requirements or for purposes in connection with the project is not be construed as publication in derogation of any of the rights of SEH. Sh or t E llio tt H en dr ick so n, Inc
Al l R igh ts Re se rve d
CO
PY
RI
GH
T
PROJECT OWNER
INDIAN HEALTH SERVICE (IHS)
DEPARTMENT OF HEALTH AND HUMAN
SERVICES
DIVISION OF ENGINEERING SERVICES
701 FIFTH AVENUE, MS 24, SUITE 1600
SEATTLE, WASHINGTON 98104-7304
CIVIL / MEP / STRUCTURAL
SHORT ELLIOTT HENDRICKSON INC.
2000 SOUTH COLORADO BLVD.
TOWER TWO, SUITE 1200
DENVER, CO. 80222
720.540.6800
LA
ME
D
EE
R
CL
IN
IC
H
EL
IP
OR
T
RE
CO
NS
TR
UC
TI
ON
BI
LL
IN
GS
A
RE
A
OF
FI
CE
1 F
IF
TH
A
VE
NU
E, M S
, S
UI
TE
SE
AT
TL
E, W
AS
HI
NG
TO
N
4-
180991
JH
AG
IN
DI
AN
H
EA
LT
H
SE
RV
IC
E
CONSTRUCTION DOCUMENTS 03.07.2025
REVISION SCHEDULE
REV. # DESCRIPTION DATE
GENERAL NOTES
G002
GENERAL NOTES
1. ALL REFERENCES TO ANY PUBLISHED STANDARDS OR CODES SHALL REFER TO THE LATEST LOCALLY ADOPTED EDITION OF SAID STANDARD OR CODE, UNLESS SPECIFICALLY STATED OTHERWISE. THE
GOVERNMENT WILL RESOLVE ANY DISCREPANCIES BETWEEN THE CONTRACT DOCUMENTS IN THE
FOLLOWING ORDER OF PRECEDENCE:
A. CONTRACT CHANGE ORDERS AND REQUEST FOR INFORMATION RESPONSES
B. PROJECT SPECIFICATIONS
C. STAMPED AND APPROVED CONSTRUCTION DRAWINGS
D. REVIEWED, ACCEPTED, AND STAMPED WORKING DRAWINGS
E. 3D ENGINEERED MODELS AND SUPPLEMENTAL DATA
F. STANDARD DRAWINGS
G. ALL OTHER CONTRACT DOCUMENTS NOT LISTED ABOVE
2. THE CONTRACTOR SHALL HAVE A STAMPED AGENCY APPROVED SET OF PLANS AND SPECIFICATIONS AT THE WORK SITE DURING CONSTRUCTION. CONSTRUCTION SHALL NOT PROCEED UNTIL THIS SET OF DOCUMENTS IS ISSUED WITH INCLUDED REVISIONS AND COMMENTS MADE BY THE APPLICABLE
AGENCIES.
3. THE CONTRACTOR SHALL BE RESPONSIBLE FOR RECORDING AS-CONSTRUCTED INFORMATION ON A
SET OF RECORD DRAWINGS KEPT ON THE CONSTRUCTION SITE.
4. THE CONTRACTOR SHALL VERIFY, IN THE FIELD, ALL ELEVATIONS, DIMENSIONS, EXISTING
CONDITIONS, AND POINTS OF CONNECTION WITH EXISTING ROADWAYS AND UTILITIES. ANY
DISCREPANCIES SHALL BE CALLED TO THE ATTENTION OF THE GOVERNMENT BEFORE PROCEEDING WITH THE WORK. IF THE CONTRACTOR CHOOSES TO PROCEED, THE WORK WILL BE CONDUCTED AT CONTRACTOR'S RISK AND INCUR ALL COSTS, IF ANY, TO RESOLVE THE ISSUE TO THE SATISFACTION
OF THE GOVERNMENT.
5. THE CONTRACTOR SHALL CONTACT UTILITY NOTIFICATION CENTER (MONTANA 811 CALL BEFORE YOU DIG) AT 811 OR 800-424-5555 AT LEAST 2 WORKING DAYS, BUT NOT MORE THAN 14 CALENDAR
DAYS, PRIOR TO THE START OF WORK.
6. EXISTING UTILITIES SHALL BE EXPOSED TO VERIFY THEIR VERTICAL AND HORIZONTAL LOCATIONS. AT A MINIMUM, LOCATIONS SHOULD BE AT PROPOSED UTILITY IMPROVEMENT CROSSINGS OR WHERE
EXCAVATION IS EXPECTED TO EXCEED 24 INCHES ABOVE THE UTILITY.
7. THE LOCATION AND DESCRIPTION OF THE NEAREST SURVEY MONUMENTATION FOR THE PROJECT, THE BASIS OF BEARING AND PROJECT DATUM ARE PROVIDED ON ASSOCIATED SITE EXISTING
CONDITIONS SHEET.
8. THE CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING ALL NECESSARY PERMITS FROM
APPLICABLE AGENCIES. ANY EARTH DISTURBING ACTIVITY OR CONSTRUCTION ON ANY AND ALL
PUBLIC IMPROVEMENTS WILL NOT BEGIN UNTIL ALL PERMITS HAVE BEEN APPROVED.
9. THE CONTRACTOR IS RESPONSIBLE FOR ALL ASPECTS OF SAFETY INCLUDING, BUT NOT LIMITED TO, EXCAVATION, TRENCHING, SHORING, TRAFFIC CONTROL AND SECURITY.
10. DIMENSIONS FOR LAYOUT AND CONSTRUCTION ARE NOT TO BE SCALED FROM ANY DRAWING. IF PERTINENT DIMENSIONS ARE NOT SHOWN, CONTACT THE GOVERNMENT FOR CLARIFICATION, AND
ANNOTATE THE DIMENSION ON THE AS-BUILT DRAWINGS.
11. ALL EXISTING STRUCTURES, FENCES, SIGNS, AND IMPROVEMENTS DESTROYED, DAMAGED, OR REMOVED DUE TO THE CONSTRUCTION OF THE PROJECT SHALL BE REPLACED OR RESTORED IN LIKE
KIND AT THE CONTRACTOR'S EXPENSE, UNLESS OTHERWISE SHOWN ON THE PLANS.
12. THE CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING A DISPOSAL SITE FOR ALL UNUSABLE MATERIAL REMOVED FROM THE PROJECT. THE DISPOSAL SITE SHALL BE AN ESTABLISHED LANDFILL
OR AS OTHERWISE ALLOWED BY FEDERAL, STATE AND LOCAL REGULATIONS.
13. EXCAVATIONS SHALL BE PROTECTED FROM ENCROACHMENT BY PERSONS AS REQUIRED IN THE SPECIFICATIONS. PROTECTION SHALL BE PLACED AT THE END OF THE WORKING DAY OR WHEN NO
ONE IS PRESENT ON SITE.
14. THERE IS LIMITED EXISTING TOPSOIL ANTICIPATED WITHIN THE LIMITS OF CONSTRUCTION. AREAS TO
BE RESEEDED SHALL HAVE A MINIMUM OF 4 INCHES OF SUITABLE TOPSOIL PLACED PRIOR TO
SEEDING.
15. FINAL CONNECTIONS TO EQUIPMENT SHALL BE AS PER MANUFACTURER'S WIRING DIAGRAMS, DETAILS AND INSTRUCTIONS. CONTRACTOR SHALL BE RESPONSIBLE TO PROVIDE MATERIALS AND
EQUIPMENT COMPATIBLE WITH EQUIPMENT ACTUALLY SUPPLIED.
16. WORK REQUIRED TO INSTALL THE FACILITIES, SYSTEMS, AND OTHER ITEMS SHOWN ON THE PLANS SHALL INCLUDE ALL EQUIPMENT, APPURTENANCES, AND INCIDENTALS NECESSARY TO PROVIDE A
COMPLETE AND FUNCTIONAL RESULT, REGARDLESS IS SPECIFICALLY NOTED OR NOT.
17. ALL COMPONENTS INCLUDED AND CONCEALED WITHIN THE CONDUCTIVE CONCRETE SECTION SHALL
BE CONSIDERED INCIDENTAL AND SHALL NOT BE MEASURED OR PAID FOR SEPARATELY.
DEMOLITION NOTES
1. THE EXTENT OF DEMOLITION WORK IS INCLUDED IN THE PLANS AND INCLUDES, BUT IS NOT LIMITED TO, THE REMOVAL OF UTILITIES OVERHEAD AND UNDERGROUND, PAVING, VEGETATION, AND OTHER
SITE FEATURES WHICH CONFLICT WITH THE CONSTRUCTION OF THE NEW FACILITIES, OR ARE
INDICATED TO BE REMOVED. THE LIMITS OF DEMOLITION SHOULD BE VERIFIED IN THE FIELD BY THE
CONTRACTOR.
2. ENSURE SAFE PASSAGE OF PERSONS AND VEHICLES AROUND AREAS OF DEMOLITION. REMOVE
FROM SITE ALL DEBRIS, RUBBISH, AND OTHER MATERIALS RESULTING FROM DEMOLITION.
3. THE CONTRACTOR SHALL IMMEDIATELY NOTIFY THE GOVERNMENT OF ANY ITEMS ENCOUNTERED IN THE FIELD THAT ARE NOT SHOWN ON THE PLANS, WHICH REQUIRE DEMOLITION OR RELOCATION.
4. IT IS THE CONTRACTOR'S RESPONSIBILITY TO REMOVE ALL EXISTING SERVICES AND
APPURTENANCES REQUIRED TO DEMOLISH EXISTING FACILITIES OR CONSTRUCT NEW FACILITIES.
ALL UTILITIES SHALL BE CAPPED, TERMINATED, OR REMOVED AS REQUIRED BY THE UTILITY OR AS INDICATED IN THE PLANS AND SPECIFICATIONS. THE CONTRACTOR SHALL NOTIFY THE GOVERNMENT IMMEDIATELY IF QUESTIONS ARISE AS TO THE VIABILITY OR CONDITION OF THE EXISTING UTILITY TO
ALLOW FOR CAPPING OR PROPER TERMINATION.
LAYOUT NOTES
1. ALL DIMENSIONS ARE FROM EDGE OF DRIVING SURFACE, FACE OF BUILDING, CENTERLINE OF UTILITY
LINE, CENTER OF STRUCTURE, PROPERTY LINE, OR POINT OF TANGENCY UNLESS OTHERWISE
NOTED.
2. GRADES ARE TO TOP OF FINISHED SURFACE, UNLESS OTHERWISE NOTED.
UTILITY NOTES
1. THE LOCATION OF PUBLIC OR PRIVATE UTILITIES SHOWN ON THE PLANS ARE APPROXIMATE AND THE GOVERNMENT DOES NOT GUARANTEE THEIR ACCURACY. THE CONTRACTOR SHALL BE REQUIRED TO ASCERTAIN THE EXACT LOCATION OF SUCH UTILITIES AND EXERCISE CARE DURING CONSTRUCTION
OPERATIONS SO AS NOT TO DAMAGE THEM.
2. EXCAVATION IN THE VICINITY OF EXISTING STRUCTURES, PIPES, CABLES, OR OTHER ITEMS SHALL BE
PERFORMED BY HAND.
3. POWER AND COMMUNICATIONS UTILITY TRENCHING SHALL BE COMPLETED IN ACCORDANCE WITH
PLANS AND SPECIFICATIONS FROM APPLICABLE UTILITY COMPANIES.
4. CONTRACTOR SHALL MAINTAIN THE FOLLOWING SEPARATION, UNLESS OTHERWISE SHOWN,
BETWEEN:
A. WATER AND SEWER (HORIZONTAL) = 10 FEET MINIMUM
B. WATER AND SEWER (VERTICAL) = 18 INCHES MINIMUM WITH WATER ABOVE SEWER
C. WATER AND POWER (VERTICAL) = 12 INCHES MINIMUM
D. WATER AND GAS (VERTICAL) = 12 INCHES MINIMUM
E. ALL OTHER UTILITIES AND SEWER (VERTICAL) = 12 INCHES MINIMUM
5. ALL CONNECTIONS TO EXISTING UTILITY PIPES SHALL BE CUT IN TO A CLEAN LINE AND MADE WITH A MANUFACTURED FITTING. INTERRUPTIONS IN SITE UTILITY SERVICE SHALL BE COORDINATED WITH
THE GOVERNMENT.
6. UTILITIES CROSSING EXISTING PAVED AREAS SHALL BE INSTALLED BY CUTTING THE PAVEMENT TO A CLEAN LINE AND TRENCHING. TRAFFIC CONTROL SHALL BE IN PLACE PRIOR TO REMOVING SAW CUT
PAVEMENT.
EROSION CONTROL NOTES
1. THE CONTRACTOR IS RESPONSIBLE FOR OBTAINING, IMPLEMENTING AND MAINTAINING A NATIONAL
POLLUTION DISCHARGE ELIMINATION SYSTEM (NPDES) GENERAL PERMIT FOR CONSTRUCTION
ACTIVITIES.
2. THE CONTRACTOR SHALL UTILIZE STORM WATER QUALITY BEST MANAGEMENT PRACTICES TO
MINIMIZE SOIL EROSION, SEDIMENTATION, INCREASED POLLUTANT LOADS AND CHANGED WATER FLOW CHARACTERISTICS RESULTING FROM LAND DISTURBING ACTIVITY, TO THE MAXIMUM EXTENT
PRACTICABLE, SO AS TO MINIMIZE POLLUTION OF RECEIVING WATERS.
3. EROSION AND SEDIMENT CONTROL MEASURES SHALL BE IN PLACE AND MAINTAINED AT ALL TIMES BEFORE, DURING, AND AFTER CONSTRUCTION UNTIL THE SITE IS STABILIZED AS REQUIRED BY THE
GENERAL PERMIT FOR CONSTRUCTION ACTIVITIES.
4. NATURAL, EXISTING VEGETATION SHALL BE RETAINED AND PROTECTED WHERE SHOWN ON THE PLANS AND TO THE MAXIMUM EXTENT POSSIBLE. AREAS OUTSIDE THE GRADING LIMITS SHOWN ON
THE PLANS SHALL NOT BE DISTURBED WITHOUT WRITTEN PERMISSION FROM THE GOVERNMENT.
5. ACCESS TO AREAS NOT CONTIGUOUS TO AREAS ALREADY GRADED SHALL BE ROUTED TO MINIMIZE DAMAGE TO EXISTING VEGETATION AND EXISTING ROADS OR OTHER VISIBLE ACCESS ROUTES SHALL
BE USED.
6. SILT FENCE SHALL BE PLACED WITHIN 10 FEET OF AND ON THE DOWNSTREAM SIDE OF ANY
STOCKPILE.
DEFINITIONS:
· FINAL APPROACH AND TAKEOFF AREA (FATO)
· TOUCHDOWN AND LIFTOFF AREA (TLOF)
· CONTROLLING DIMENSION (D) - THE GREATER OF HELICOPTER OVERALL LENGTH AND OVERALL WIDTH
· SAFETY AREA - A DEFINED AREA ON A HELIPORT SURROUNDING THE FATO INTENDED TO REDUCE THE
RISK OF DAMAGE TO HELICOPTERS ACCIDENTALLY DIVERGING FROM FATO. NO VERTICAL
OBSTRUCTIONS IN THIS AREA.
TLOF/FATO/SAFETY AREA RELATIONSHIPS AND MINIMUM DIMENSIONS:
HELIPORT DESIGN BASED ON FEDERAL AVIATION ADMINISTRATION STANDARD AC 150/5390 - 2D
DESIGN MODELS: EUROCOPTER EC-135 (D = 40) AND BELL HELICOPTER 407 (D = 41.4)
A = 0.83D F = 0.34D = 0.83(41.4) = 0.34(41.4)
= 34.36 LF =14.08 LF
B = 0.83D G = 0.28D = 0.83(41.4) = 0.28(41.4)
= 34.36 LF = 11.59 LF
C = 1.50D = 1.50(41.4)
= 62.10 LF
E = 1.50D = 1.50(41.4)
= 62.10 LF
G
C
E
F
B
A
SAFETY AREA
FATO
TLOF
P-BUR
P-BUR
P-BUR
P-BU
R
P-BU
R
P-BU
R
P-BU
R
S
ST
STST
3316 33 17 33 18 33
SANITARY MANHOLE
RIM ELEV =3320.91
INV IN=3310.79 (E)
INV OUT=3310.75 (W)
STORM MANHOLE
RIM ELEV =3322.28
(UNABLE TO ACCESS)
WIND SOCK
NAVIGATION LIGHT
SAND/OIL SEPARATOR
RIM ELEV =3322.35
SAND/OIL SEPARATOR
RIM ELEV =3322.34
BUILDING OVERHANG
OVERHANG COLUMN
UTILITY PEDESTAL
PERIMETER ENHANCEMENT LIGHT
(TYP. 8 EACH)
LIGHT POLE
GROUND SIGN
(TYP.)
HEALTH
CENTER
18" RCP CULVERT
INV ELEV= 3313.96
18" RCP CULVERT
INV ELEV= 3317.16
18" RCP CULVERT
INV ELEV= 3312.79
10" PVC @ 1.65%
8" PVC @ 1.45%
POINT TABLE
POINT NO. DESCRIPTION ELEVATION NORTHING EASTING
50* CTRL RPC REBAR 3321.154 516205.813 2691912.408
51* CTRL SPIKE 3319.864 516175.636 2691859.632
60 CTRL RPC REBAR 3321.807 516025.867 2692031.276
61 CTRL SPIKE 3321.273 516006.577 2691872.723
62 CTRL RPC REBAR 3317.371 516006.28 2691768.589
R
SEH Project Checked By Drawn By
Project Status Issue Date
This drawing is an instrument of service and shall remain the property of Short Elliott Hendrickson, Inc.
(SEH). This drawing, concepts and ideas contained herein shall not be used, reproduced, revised, or retained without the express written approval of SEH.
Submission or distribution of this drawing to meet official or regulatory requirements or for purposes in connection with the project is not be construed as publication in derogation of any of the rights of SEH. Sh or t E llio tt H en dr ick so n, Inc
Al l R igh ts Re se rve d
CO
PY
RI
GH
T
PROJECT OWNER
INDIAN HEALTH SERVICE (IHS)
DEPARTMENT OF HEALTH AND HUMAN
SERVICES
DIVISION OF ENGINEERING SERVICES
701 FIFTH AVENUE, MS 24, SUITE 1600
SEATTLE, WASHINGTON 98104-7304
CIVIL / MEP / STRUCTURAL
SHORT ELLIOTT HENDRICKSON INC.
2000 SOUTH COLORADO BLVD.
TOWER TWO, SUITE 1200
DENVER, CO. 80222
720.540.6800
LA
ME
D
EE
R
CL
IN
IC
H
EL
IP
OR
T
RE
CO
NS
TR
UC
TI
ON
BI
LL
IN
GS
A
RE
A
OF
FI
CE
1 F
IF
TH
A
VE
NU
E, M S
, S
UI
TE
SE
AT
TL
E, W
AS
HI
NG
TO
N
4-
180991
JH
AG
IN
DI
AN
H
EA
LT
H
SE
RV
IC
E
CONSTRUCTION DOCUMENTS 03.07.2025
REVISION SCHEDULE
REV. # DESCRIPTION DATE
feetscale
10 2010
LAME DEER EXISTING
CONDITIONS
C001
CONTROL STATEMENT
NAD83(2011) MT STATE PLANE ZONE 2500
PROJECT LOCATION (AT CONTROL POINT 50):
LAT: N45°37'47.59525"
LON: W106°40'14.99182"
HEIGHT: 3271.804 FT
VERTICAL DATUM: NAVD88 (OPUS DERIVED, GEOID18)
COMBINED SCALE FACTOR: 1.0004761464
SCALED TO GROUND AT CONTROL POINT 50, UNITS OF INTERNATIONAL FEET
*OUTSIDE OF VIEWPORT LIMITS
P-BUR
P-BUR
P-BUR
P-BU
R
P-BU
R
P-BU
R
P-BU
R
S
ST
STST
HEALTH
CENTER
18 33
REMOVAL OF 4"
CONCRETE SIDEWALK
(62 SY)
REMOVAL OF 8" REINFORCED
CONCRETE PAVEMENT AND 6"
AGGREGATE BASE (171 SY)
REMOVAL OF PERIMETER
ENHANCEMENT LIGHT AND
ASSOCIATED CONDUIT/WIRING
(TYP. 8 EACH)
REMOVAL AND REPLACE SANITARY MANHOLE
REMOVAL AND REPLACE 5 LF OF PIPE ON
INLET AND OUTLET SIDES
PROTECT WIND SOCK
NAVIGATION LIGHT
N=515992.80 E=2691868.90
BEGIN ASPHALT SAWCUT
N=516032.17 E=2691884.13
END REMOVAL OF
CURB AND GUTTER
N=515991.62 E=2691907.70
END REMOVAL OF
CURB AND GUTTER
N=516032.78 E=2691896.14
BEGIN REMOVAL OF
CURB AND GUTTER
N=515988.43 E=2691909.73
END ASPHALT SAWCUT
N=515995.57 E=2691871.64
BEGIN REMOVAL OF
CURB AND GUTTER
N=516011.67 E=2691951.79
BEGIN CONCRETE SAWCUT
N=516009.06 E=2691956.70
END CONCRETE SAWCUT
REMOVAL OF 2" ASPHALT
PAVEMENT (61 SY)
N=516052.83 E=2691956.46
BEGIN CONCRETE SAWCUT
N=516055.91 E=2691960.91
END CONCRETE SAWCUT
PROTECT
OVERHANG COLUMN
N=516124.60 E=2691914.68
BEGIN ASPHALT SAWCUT
N=516056.72 E=2691962.07
END ASPHALT SAWCUT
REMOVAL OF 4" CONCRETE
SIDEWALK (49 SY)
REMOVAL OF 2" ASPHALT
PAVEMENT (10 SY)
18" RCP
INV ELEV= 3317.16
REMOVAL OF END
SECTION
REMOVE UTILITY
CONDUIT
X X
X X
X
XXXXXXXXXX
X
X X
X X
X X
X X
X X
X X
X X
X X
X
X X
N=515991.14 E=2691933.39
BEGIN CONCRETE SAWCUT
N=515963.98 E=2691934.47
END CONCRETE SAWCUT
R
SEH Project Checked By Drawn By
Project Status Issue Date
This drawing is an instrument of service and shall remain the property of Short Elliott Hendrickson, Inc.
(SEH). This drawing, concepts and ideas contained herein shall not be used, reproduced, revised, or retained without the express written approval of SEH.
Submission or distribution of this drawing to meet official or regulatory requirements or for purposes in connection with the project is not be construed as publication in derogation of any of the rights of SEH. Sh or t E llio tt H en dr ick so n, Inc
Al l R igh ts Re se rve d
CO
PY
RI
GH
T
PROJECT OWNER
INDIAN HEALTH SERVICE (IHS)
DEPARTMENT OF HEALTH AND HUMAN
SERVICES
DIVISION OF ENGINEERING SERVICES
701 FIFTH AVENUE, MS 24, SUITE 1600
SEATTLE, WASHINGTON 98104-7304
CIVIL / MEP / STRUCTURAL
SHORT ELLIOTT HENDRICKSON INC.
2000 SOUTH COLORADO BLVD.
TOWER TWO, SUITE 1200
DENVER, CO. 80222
720.540.6800
LA
ME
D
EE
R
CL
IN
IC
H
EL
IP
OR
T
RE
CO
NS
TR
UC
TI
ON
BI
LL
IN
GS
A
RE
A
OF
FI
CE
1 F
IF
TH
A
VE
NU
E, M S
, S
UI
TE
SE
AT
TL
E, W
AS
HI
NG
TO
N
4-
180991
JH
AG
IN
DI
AN
H
EA
LT
H
SE
RV
IC
E
CONSTRUCTION DOCUMENTS 03.07.2025
REVISION SCHEDULE
REV. # DESCRIPTION DATE
LAME DEER REMOVALS PLAN
C101 feetscale
10 2010
ST
STST
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
S J
SAFETY AREA
N=515992.80 E=2691868.90
BEGIN ASPHALT PATCH N=515988.43
E=2691909.73
END ASPHALT PATCH
N=516011.67 E=2691951.79
END CONCRETE AND CURB
N=516009.06 E=2691956.70
END CONCRETE AND CURB
INSTALL CONCRETE PAVEMENT (77 SY)
SEE SHEET C402 FOR TYPICAL SECTION
INSTALL12" STRUCTURAL
CONCRETE (711 SY)
SEE SHEET C402 FOR
HELIPORT DETAIL
PROTECT WIND SOCK
NAVIGATION LIGHT
HEALTH
CENTER
FATO
TLOF
80.0'
80.0'
40.0'
40.0'
20.0'
12.0'
8.0'
INSTALL STEEL CABLE AND
POST FENCE (411 LF)
SEE SHEET C401 FOR DETAIL
N=516124.60 E=2691914.68
BEGIN ASPHALT PATCH
N=516056.72 E=2691962.07
END ASPHALT PATCH
N=515995.57 E=2691871.64
BEGIN CURB AND GUTTER
N=516013.33 E=2691876.68
N=516035.86 E=2691909.12
N=516040.42 E=2691915.69
N=516011.67 E=2691935.66
N=515998.06 E=2691935.38
N=516058.97 E=2691942.39
N=516063.98 E=2691914.56
N=516041.17 E=2691881.70
N=516079.04 E=2691831.05
N=516074.02 E=2691858.88
N=516096.84 E=2691891.74
N=516124.67 E=2691896.76
SEE SHEET C404 FOR
MARKING DETAIL
N=516123.84 E=2691913.61
BEGIN CURB
N=516055.97 E=2691960.99
END CURB
N=515991.62 E=2691907.66
END CURB AND GUTTER
N=516133.73 E=2691879.32
INSTALL 18" RCP
FLARED END SECTION
19 LF 18" RCP
ROOF OVERHANG
6.2' SWALE
6' HIGH CHAINLINK FENCE WITH
42" WIDE GATE ACCESS (53 LF)
N=515993.56 E=2691935.53
BEGIN CURB
N=515994.41 E=2691957.37
END CURB
OVERHANG COLUMN
N=516063.17 E=2691870.69
RIM ELEV=3323.08
INV IN=3310.82(W)
INV OUT=3310.75(E)
INSTALL LOAD BEARING MANHOLE
SEE SHEET C405 FOR DETAIL 8.6'
2.4'
5 LF 8" PVC
5 LF 10" PVC
N=515963.97 E=2691934.26
N=515991.14 E=2691933.39
N=515994.07 E=2691948.03
N=515964.55 E=2691949.00
R
SEH Project Checked By Drawn By
Project Status Issue Date
This drawing is an instrument of service and shall remain the property of Short Elliott Hendrickson, Inc.
(SEH). This drawing, concepts and ideas contained herein shall not be used, reproduced, revised, or retained without the express written approval of SEH.
Submission or distribution of this drawing to meet official or regulatory requirements or for purposes in connection with the project is not be construed as publication in derogation of any of the rights of SEH. Sh or t E llio tt H en dr ick so n, Inc
Al l R igh ts Re se rve d
CO
PY
RI
GH
T
PROJECT OWNER
INDIAN HEALTH SERVICE (IHS)
DEPARTMENT OF HEALTH AND HUMAN
SERVICES
DIVISION OF ENGINEERING SERVICES
701 FIFTH AVENUE, MS 24, SUITE 1600
SEATTLE, WASHINGTON 98104-7304
CIVIL / MEP / STRUCTURAL
SHORT ELLIOTT HENDRICKSON INC.
2000 SOUTH COLORADO BLVD.
TOWER TWO, SUITE 1200
DENVER, CO. 80222
720.540.6800
LA
ME
D
EE
R
CL
IN
IC
H
EL
IP
OR
T
RE
CO
NS
TR
UC
TI
ON
BI
LL
IN
GS
A
RE
A
OF
FI
CE
1 F
IF
TH
A
VE
NU
E, M S
, S
UI
TE
SE
AT
TL
E, W
AS
HI
NG
TO
N
4-
180991
JH
AG
IN
DI
AN
H
EA
LT
H
SE
RV
IC
E
CONSTRUCTION DOCUMENTS 03.07.2025
REVISION SCHEDULE
REV. # DESCRIPTION DATE
feetscale
10 2010
LAME DEER SITE PLAN
C201
NOTES:
1. ELECTRICAL INFRASTRUCTURE SHOWN FOR
REFERENCE ONLY. REFER TO ELECTRICAL PLANS FOR
FURTHER DETAIL.
ST
STST
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O
O O
O
O
O
S J
3316 33
18 33
3316 33 17 33
18 33
SAFETY AREA
HEALTH
CENTER
FATO
TLOF
3317 3318 3319 3321
0.53%
1.07%
1.60%
1.
0.46%
0.50% 0.45%
0.
0.
1.03%
0.60%
0.75%
0.75%
0.76%
0.75%
0.75%
0.75%
0.75%
0.75%
0.75%
0.76%
0.75%
0.
0.75%
0.53%
0.00%
0.00%
0.00%
0.00%
0.00%
0.00%
0.00%
0.00%
0.75% 0.75%
0.75%
0.75%
34.28%
31.21%
31.73%
15.89% 1.03%
2.79%
N=515998.06 E=2691935.38
ELEV=3322.62
N=516011.67 E=2691935.66
ELEV=3322.54
N=516040.42 E=2691915.69
ELEV=3322.90
N=516035.86 E=2691909.12
ELEV=3322.90
N=516011.67 E=2691951.79
MATCH EX. ELEV=3322.62
N=516009.06 E=2691956.70
MATCH EX. ELEV=3322.65
N=516013.33 E=2691876.68
ELEV=3322.90
N=516079.04 E=2691831.05
ELEV=3322.90
N=516074.02 E=2691858.88
ELEV=3323.05
N=516096.84 E=2691891.74
ELEV=3323.05
N=516124.67 E=2691896.76
ELEV=3322.90
N=516058.97 E=2691942.39
ELEV=3322.90
N=516063.98 E=2691914.56
ELEV=3323.05
N=516041.17 E=2691881.70
ELEV=3323.05
N=516133.73 E=2691879.32
INV ELEV=3317.04
STORM OUTLET
N=515988.43 E=2691909.73
MATCH EX. ELEV=3321.98
END ASPHALT PATCH
N=515991.62 E=2691907.66
MATCH EX. ELEV=3321.70
END CURB AND GUTTER
N=515995.57 E=2691871.64
MATCH EX. ELEV=3320.93
BEGIN CURB AND GUTTER
N=515992.80 E=2691868.90
MATCH EX. ELEV=3321.04
BEGIN ASPHALT PATCH
N=516056.72 E=2691962.07
MATCH EX. ELEV=3322.23
END ASPHALT PATCH
N=516124.60 E=2691914.68
MATCH EX. ELEV=3322.07
BEGIN ASPHALT PATCH
N=516123.84 E=2691913.61
MATCH EX. ELEV=3322.02
BEGIN CURB
N=516055.97 E=2691960.99
ELEV=3322.24
END CURB
1.
42.23%
8.
.7
9% N=515994.43 E=2691957.37
MATCH EX. ELEV=3322.76
N=515994.07 E=2691948.03
MATCH EX. ELEV=3322.80
N=515993.65 E=2691935.50
ELEV=3322.54
SWALE
0.60%
1.03%
11.70%
5.33%
13.90%
18.14%
0.53%
0.
N=516063.17 E=2691870.69
RIM ELEV=3323.08
N=516069.00 E=2691886.72
ELEV=3323.20
N=516062.60 E=2691947.57
ELEV=3322.36
N=516129.65 E=2691900.77
ELEV=3321.57
N=515963.97 E=2691934.26
MATCH EX. ELEV=3322.84
N=515991.14 E=2691933.45
MATCH EX. ELEV=3322.82
R
SEH Project Checked By Drawn By
Project Status Issue Date
This drawing is an instrument of service and shall remain the property of Short Elliott Hendrickson, Inc.
(SEH). This drawing, concepts and ideas contained herein shall not be used, reproduced, revised, or retained without the express written approval of SEH.
Submission or distribution of this drawing to meet official or regulatory requirements or for purposes in connection with the project is not be construed as publication in derogation of any of the rights of SEH. Sh or t E llio tt H en dr ick so n, Inc
Al l R igh ts Re se rve d
CO
PY
RI
GH
T
PROJECT OWNER
INDIAN HEALTH SERVICE (IHS)
DEPARTMENT OF HEALTH AND HUMAN
SERVICES
DIVISION OF ENGINEERING SERVICES
701 FIFTH AVENUE, MS 24, SUITE 1600
SEATTLE, WASHINGTON 98104-7304
CIVIL / MEP / STRUCTURAL
SHORT ELLIOTT HENDRICKSON INC.
2000 SOUTH COLORADO BLVD.
TOWER TWO, SUITE 1200
DENVER, CO. 80222
720.540.6800
LA
ME
D
EE
R
CL
IN
IC
H
EL
IP
OR
T
RE
CO
NS
TR
UC
TI
ON
BI
LL
IN
GS
A
RE
A
OF
FI
CE
1 F
IF
TH
A
VE
NU
E, M S
, S
UI
TE
SE
AT
TL
E, W
AS
HI
NG
TO
N
4-
180991
JH
AG
IN
DI
AN
H
EA
LT
H
SE
RV
IC
E
CONSTRUCTION DOCUMENTS 03.07.2025
REVISION SCHEDULE
REV. # DESCRIPTION DATE
feetscale
10 2010
C301
DETAILS
C401
R
SEH Project Checked By Drawn By
Project Status Issue Date
This drawing is an instrument of service and shall remain the property of Short Elliott Hendrickson, Inc.
(SEH). This drawing, concepts and ideas contained herein shall not be used, reproduced, revised, or retained without the express written approval of SEH.
Submission or distribution of this drawing to meet official or regulatory requirements or for purposes in connection with the project is not be construed as publication in derogation of any of the rights of SEH. Sh or t E llio tt H en dr ick so n, Inc
Al l R igh ts Re se rve d
CO
PY
RI
GH
T
PROJECT OWNER
INDIAN HEALTH SERVICE (IHS)
DEPARTMENT OF HEALTH AND HUMAN
SERVICES
DIVISION OF ENGINEERING SERVICES
701 FIFTH AVENUE, MS 24, SUITE 1600
SEATTLE, WASHINGTON 98104-7304
CIVIL / MEP / STRUCTURAL
SHORT ELLIOTT HENDRICKSON INC.
2000 SOUTH COLORADO BLVD.
TOWER TWO, SUITE 1200
DENVER, CO. 80222
720.540.6800
LA
ME
D
EE
R
CL
IN
IC
H
EL
IP
OR
T
RE
CO
NS
TR
UC
TI
ON
BI
LL
IN
GS
A
RE
A
OF
FI
CE
1 F
IF
TH
A
VE
NU
E, M S
, S
UI
TE
SE
AT
TL
E, W
AS
HI
NG
TO
N
4-
180991
JH
AG
IN
DI
AN
H
EA
LT
H
SE
RV
IC
E
CONSTRUCTION DOCUMENTS 03.07.2025
REVISION SCHEDULE
REV. # DESCRIPTION DATE
L-810 OBSTRUCTION LIGHT
OPERATED BY DUSK-TO-DAWN PHOTO SENSOR
TUBULAR ALUMINUM WIND CONE SUPPORT
SIZE I WIND SOCK
DAY-GLO BLAZE ORANGE NYLON
FABRIC WIND CONE GROMMETS -
BOTTOM SIDE FOR DRAINAGE
INTERNAL LIGHTING ASSEMBLY
SEALED BEARING
SEALED BEARING
ALUMINUM MAST
BASEPLATE AND GASKET
FRANGIBLE COUPLING
SUPPLEMENTAL WIND CONE - TYPE L-806
NTS
L-867 BASE
POST AND CABLE FENCE
NTS
2'
4,000PSI CONCRETE
3.5'
6"
4" Ø SCH 80 STEEL
POWDER COATED (BROWN/RUST)
3/4" DIA. - 3 X 7 WIRE ROPE
1" Ø HOLE
ROUND CAP
15"
6"
3/4" Ø
3/4" WASHER
3/4" HEX NUT
FLATTEN FOR WRENCH CABLE END
(CAST STEEL OR MALL IRON)
3/4" Ø CABLE
3/4" SQ. NUT
CABLE WEDGE
7 1/2" R.H.
2 1/4" R.H.
1 1/4" R.H.
5/8"
(TYP.)
CABLE END ASSEMBLY
*R.H. = RIGHT HAND
NOTES:
1. WIRE ROPE AND CONNECTING HARDWARE ARE TO CONFORM
TO THE REQUIREMENTS OF AASHTO M30 TYPE 1 CLASS A,
3/4" ROPE. CONNECTING HARDWARE MUST DEVELOP THE
FULL STRENGTH OF A SINGLE CABLE (25,000 LB). CAST STEEL
COMPONENTS ARE TO THE REQUIREMENTS OF AASHTO M103
(ASTM A27). MALLEABLE IRON CASTINGS ARE TO CONFORM
TO THE REQUIREMENTS OF ASTM A47.
2. AT ALL LOCATIONS WHERE THE CABLE IS CONNECTED TO A
CABLE SOCKET WITH A WEDGE TYPE CONNECTION, CRIMP
ONE WIRE OF THE CABLE OVER THE BASE OF THE WEDGE TO
HOLD IT FIRMLY IN PLACE.
3. DESIGN SOCKET BASKETS FOR USE WITH THE WEDGE
DETAILED IN THIS DRAWING.
4. ALTERNATE HARDWARE DESIGNS WILL BE CONSIDERED FOR
APPROVAL PROVIDED THEIR CONNECTION DETAILS, FOR THE
PURPOSE OF MAINTENANCE SUBSTITUTIONS, ARE
COMPATIBLE WITH THE DETAILS OF THIS DRAWING AND
THEIR OPERATING CHARACTERISTICS ARE SIMILAR TO
THOSE OF THE HARDWARE IN THIS DRAWING.
CABLE WEDGE
1.844"
0.843" 0.562"
0.437"
0.125"
0.203"R (TYP.) CAST STEEL
OR MALL IRON
5°
3/4" DIA. CABLE
3/4" Ø - 3 X 7 WIRE ROPE
LOW - TENSION CABLE GUARDRAIL HARDWARE
NTS
MDT CURB AND GUTTER
NTS
24"
6"
12"
2"
P
9 1/2"P = AREA TO BE PAINTED, WHEN
PAINTED CURB IS REQUIRED (102
SQ. FT. PER 100 FT. OF CURB)
6"
4"R FLOWLINE
2% SLOPE
4% ± SLOPE
1" DEEP CONTRACTION JOINT
PLACED AT 10' MAXIMUM
INTERVALS. GROOVES ARE
CONTINUOUS ON THE TOP
EXPOSED SURFACE FOR THE
WIDTH OF CURB AND GUTTER.
3"R
6" FACE OF
CURB
CURB SECTION
NTS
6"
6"
HEAD HEIGHT
1"R
12"
FLOWLINE
C402
R
SEH Project Checked By Drawn By
Project Status Issue Date
This drawing is an instrument of service and shall remain the property of Short Elliott Hendrickson, Inc.
(SEH). This drawing, concepts and ideas contained herein shall not be used, reproduced, revised, or retained without the express written approval of SEH.
Submission or distribution of this drawing to meet official or regulatory requirements or for purposes in connection with the project is not be construed as publication in derogation of any of the rights of SEH. Sh or t E llio tt H en dr ick so n, Inc
Al l R igh ts Re se rve d
CO
PY
RI
GH
T
PROJECT OWNER
INDIAN HEALTH SERVICE (IHS)
DEPARTMENT OF HEALTH AND HUMAN
SERVICES
DIVISION OF ENGINEERING SERVICES
701 FIFTH AVENUE, MS 24, SUITE 1600
SEATTLE, WASHINGTON 98104-7304
CIVIL / MEP / STRUCTURAL
SHORT ELLIOTT HENDRICKSON INC.
2000 SOUTH COLORADO BLVD.
TOWER TWO, SUITE 1200
DENVER, CO. 80222
720.540.6800
LA
ME
D
EE
R
CL
IN
IC
H
EL
IP
OR
T
RE
CO
NS
TR
UC
TI
ON
BI
LL
IN
GS
A
RE
A
OF
FI
CE
1 F
IF
TH
A
VE
NU
E, M S
, S
UI
TE
SE
AT
TL
E, W
AS
HI
NG
TO
N
4-
180991
JH
AG
IN
DI
AN
H
EA
LT
H
SE
RV
IC
E
CONSTRUCTION DOCUMENTS 03.07.2025
REVISION SCHEDULE
REV. # DESCRIPTION DATE
SIDEWALK PAVEMENT SECTION
NTS
HELIPORT PAVEMENT SECTION
NTS
#6 @ 18" EACH WAY
TOP AND BOTTOM
12" DEEP CONCRETE CURB
AROUND OUTER PERIMETER
LANDSCAPE AREA
STAINLESS STEEL COVER BOLTS
APPLY ANTI-SIEZE COMPOUND TO
THREADS, TYP
SILICA SAND FILL TOPPED WITH
EPOXY SEALANT
LOAD BEARING BLANK PLATE W/ RECESSED BOLT
HEADS SET FLUSH WITH PAVEMENT
SPACER RINGS AS REQUIRED
FLUSH MOUNT BASE CAN - TYPE L-868
NTS
SEE LIGHT BASE EDGE
EPOXY DETAIL BELOW
HELISTOP LED PERIMETER INSET LIGHT (GREEN
WITH IR EMITTER). CONNECT TO RADIO
RECEIVER/DECODER (L-854).
4" THREADED HUBS
(90° APART)
8"
STRUCTURAL FILL
CONDUIT
NO DRAIN HOLE
LIGHT BASE EDGE EPOXY
NTS
SILICA SAND
3"
1"
FULL
FLUSH
EPOXY SEALANT
INSTALLATION NOTES:
1. USE MANUFACTURER'S SETTING JIG (OR OTHER APPROVED DEVICE) FOR PROPERLY SETTING THE LIGHTING BASES. SECURE JIG TO PREVENT MOVEMENT DURING
CONCRETE FOOTING PLACEMENT.
2. PLACE CONCRETE FOOTING AND CONFIRM HEIGHT/LOCATION/TILT OF LIGHT FIXTURE BASE BEFORE CONCRETE SETS. OPENINGS IN BASE TO BE GROMMETED TO PREVENT
CONCRETE FROM ENTERING BASE OR CONDUIT. TOP OF BASE TO MATCH SLOPE OF PAVEMENT.
3. DURING PLACEMENT OF CONCRETE PAVEMENT, WHILE CONCRETE IS STILL WET, USE TEMPORARY 'MUDRING' AND PUSH IT DOWN TO 1" INSIDE MUDRING AND CLEAN
EXPOSED METAL SURFACES. FINISH THE CONCRETE AROUND THE MUDRING WITH A CURVES RADIUS TROWEL. USE CAUTION TO AVOID AGGREGATE SEPARATION DURING THIS WORK. COORDINATE THICKNESS OF MUDRING TO ALLOW FOR INSTALLATION OF FLANGE RING.
4. AFTER CONCRETE PAVEMENT HAS SET, REMOVE TEMPORARY MUDRING AND MUDPLATE. INSTALL FLANGE RING AND LOAD-BEARING BLANK COVER PLATE WITH RECESSED BOLT HEADS. TOP OF COVER PLATE TO BE LEVEL TO WITHIN +/- 1/2 DEGREE AND FLUSH WITHIN +0",-1/16" FROM SURFACE. CONTRACTOR SHALL FINISH AND INSTALL
SPACER RINGS IN QUANTITY AND THICKNESS AS REQUIRED TO MEET HEIGHT TOLERANCES.
5. SEAL AROUND FLANGE RING, EXTENSION RINGS AND TOP COVER PLATE WITH P-606 SEALANT. MAXIMIM FILL SPACE (LEFT BY MUDRING REMOVAL TO BE 3/4" WIDE.)
6. INSTALLATION MUST COMPLY WITH HEIGHT TOLERANCES GIVEN ON DETAILS. UNITS THAT ARE UP TO 1/8" TO HIGH SHALL B DISASSEMBLED AND THE BASE TIP RING MILLED
DOWN USING A MILLING MACHINE. UNITS THAT ARE SET GREATER THAN 1/8" TOO HIGH SHALL BE REMOVED IN THEIR ENTIRETY BY SAWCUTTING A 4' X 4' OPENING AND REPLACING PAVEMENT BY DOWELING INTO ADJACENT PAVEMENT, ALL AS DIRECTED BY THE ENGINEER. ALL CORRECTIVE OPERATIONS SHALL BE AT THE CONTRACTORS
EXPENSE.
PVC CAP AT BOTTOM OF POST
CONSTRUCTION JOINT DETAIL
NTS
1/4"
SILICONE SEALANT RECESS 1/4"
FROM PAVEMENT SURFACE
1/2" EXPANSION JOINT MATERIAL
FORM NON-CONDUCTIVE HEAT
SHRINK TUBING AROUND PVC CAP
shalewski Image shalewski Image shalewski Text Box 3.7.2025 shalewski Cloud
C403
R
SEH Project Checked By Drawn By
Project Status Issue Date
This drawing is an instrument of service and shall remain the property of Short Elliott Hendrickson, Inc.
(SEH). This drawing, concepts and ideas contained herein shall not be used, reproduced, revised, or retained without the express written approval of SEH.
Submission or distribution of this drawing to meet official or regulatory requirements or for purposes in connection with the project is not be construed as publication in derogation of any of the rights of SEH. Sh or t E llio tt H en dr ick so n, Inc
Al l R igh ts Re se rve d
CO
PY
RI
GH
T
PROJECT OWNER
INDIAN HEALTH SERVICE (IHS)
DEPARTMENT OF HEALTH AND HUMAN
SERVICES
DIVISION OF ENGINEERING SERVICES
701 FIFTH AVENUE, MS 24, SUITE 1600
SEATTLE, WASHINGTON 98104-7304
CIVIL / MEP / STRUCTURAL
SHORT ELLIOTT HENDRICKSON INC.
2000 SOUTH COLORADO BLVD.
TOWER TWO, SUITE 1200
DENVER, CO. 80222
720.540.6800
LA
ME
D
EE
R
CL
IN
IC
H
EL
IP
OR
T
RE
CO
NS
TR
UC
TI
ON
BI
LL
IN
GS
A
RE
A
OF
FI
CE
1 F
IF
TH
A
VE
NU
E, M S
, S
UI
TE
SE
AT
TL
E, W
AS
HI
NG
TO
N
4-
180991
JH
AG
IN
DI
AN
H
EA
LT
H
SE
RV
IC
E
CONSTRUCTION DOCUMENTS 03.07.2025
REVISION SCHEDULE
REV. # DESCRIPTION DATE
SLOPE 4%
CONCRETE BASE
TO BE POURED IN
FIELD OR PRECAST
0.5 Ø
OF PIPE
MDT TYPE 3 SECTION B-B
MDT TYPE 3 SECTION A-A
MODIFIED MDT TYPE 3 MANHOLE
6"
SHELF
CHANNEL
SHELF
ROOF SLAB
AS REQUIRED
0.5 DIA.
OF PIPE
B
B
REINFORCED CONCRETE
PIPE BARREL
A A
K
6" 24" MIN.
COVER DIAMETER
#4 BARS @ 12"
O.C. EACH WAY
6" FOR UP TO 78" DIA.
8" FOR 84" AND 90" DIA.
10" FOR 96" AND 102" DIA.
T 1"
MDT TYPE 3 MANHOLE ROOF SLAB
PIPE DIA.
(IN)
SLAB DIA.
(IN)
T
(IN)
K
(IN) BOTTOM BARS TOP BARS
48 58 8 9 #4 @ 6" -
54 65 8 9 #4 @ 6" -
60 72 8 9 #4 @ 6" #3 @ 6"
66 79 8 9 #4 @ 6" #3 @ 6"
72 86 8 9 #4 @ 6" #3 @ 6"
78 93 8 9 #4 @ 4" #4 @ 4"
84 100 8 9 #4 @ 4" #4 @ 4"
90 107 8 9 #5 @ 4" #4 @ 4"
96 114 8 9 #5 @ 4" #4 @ 4"
102 121 8 9 #5 @ 4" #4 @ 4"
NOTES:
1. CONTRACTOR SHALL VERIFY ALL EXISTING PIPES, INLETS, MANHOLES INVERTS AND ALL OTHER ELEVATIONS FOR TIE IN
TO PROPOSED CONDITIONS.
2. STRUCTURES SHALL BE PRECAST CONCRETE CONFORMING TO REQUIREMENTS OF ITEM D-751, AC 150/5370-10H AND
ASTM C858; STANDARD SPECIFICATION FOR UNDERGROUND PRECAST CONCRETE UTILITY STRUCTURES.
REINFORCEMENT SHOWN IS ILLUSTRATIVE ONLY.
3. STRUCTURES AND CASTING FRAMES SHALL MEET ALL REQUIRED AIRPORT AIRCRAFT DESIGN LOADS
4. SHOP DRAWING SUBMITTALS SHALL BE FURNISHED WITH SEALED ENGINEERING CALCULATIONS BY AN ENGINEER
LICENSED TO PRACTICE IN THE STATE OF MONTANA.
5. FRAME AND COVER UNIT SHALL BE PROVIDED WITH FASTENING MEMBERS TO PREVENT IT FROM BEING DISLODGED BY
TRAFFIC BUT WHICH WILL ALLOW EASY REMOVAL FOR ACCESS TO THE STRUCTURE.
6. ALL CASTINGS SHALL BE THOROUGHLY CLEANED. AFTER FABRICATION, STRUCTURAL STEEL UNITS SHALL BE GALVANIZED
TO MEET THE REQUIREMENTS OF ASTM A123.
7. USE MANHOLE STEPS THAT ARE MALLEABLE CAST IRON OR GALVANIZED STEEL.
NEENAH CASTING R-3492 OR
EQUAL (SEALED CASTING)
12"
16"
SHELF
CHANNEL
ADJUST RING AS NEEDED
(SEE MDT DWG. NO. 621-00)
SURROUND CONCRETE COLLAR
38 1/2"
6" MIN.
CONCRETE
SANITARY MANHOLE LID
104.0' SAFETY AREA
4.
0' S
AF
ET
Y
AR
EA
.0
' F
AT
O
40.0' TLOF
.0
' T
LO
F
80.0' FATO
10.0' 10.0' 10.0'4.0'
1.0'
4.0'
Ø20.7' 1.5'
2.0'
2.
0'
TOUCHDOWN/POSITION
CIRCLE WIDE YELLOW STRIPE
FATO EDGE MARKING
OR RETROREFLECTIVE
MARKERS
TLOF EDGE RETROREFLECTIVE
WHITE STRIPE
5.
0'
0.
5'
5.0'
3.0'
5.0'
5.
0'
2.
5'
5.0'
0.
4'
0.5' 0.5' 0.5'
1.0'
.0
2.
0'
6.7'
1.
5'
0.4'
1.0'
0.2'
0.8'
1.
5' 0.2'
1.0'
0.2'
0.2'
1.
2'
1.
5'
0.6'
1.
5'
1.
0'
0.
8'
0.8'
0.2'
R
SEH Project Checked By Drawn By
Project Status Issue Date
This drawing is an instrument of service and shall remain the property of Short Elliott Hendrickson, Inc.
(SEH). This drawing, concepts and ideas contained herein shall not be used, reproduced, revised, or retained without the express written approval of SEH.
Submission or distribution of this drawing to meet official or regulatory requirements or for purposes in connection with the project is not be construed as publication in derogation of any of the rights of SEH. Sh or t E llio tt H en dr ick so n, Inc
Al l R igh ts Re se rve d
CO
PY
RI
GH
T
PROJECT OWNER
INDIAN HEALTH SERVICE (IHS)
DEPARTMENT OF HEALTH AND HUMAN
SERVICES
DIVISION OF ENGINEERING SERVICES
701 FIFTH AVENUE, MS 24, SUITE 1600
SEATTLE, WASHINGTON 98104-7304
CIVIL / MEP / STRUCTURAL
SHORT ELLIOTT HENDRICKSON INC.
2000 SOUTH COLORADO BLVD.
TOWER TWO, SUITE 1200
DENVER, CO. 80222
720.540.6800
LA
ME
D
EE
R
CL
IN
IC
H
EL
IP
OR
T
RE
CO
NS
TR
UC
TI
ON
BI
LL
IN
GS
A
RE
A
OF
FI
CE
1 F
IF
TH
A
VE
NU
E, M S
, S
UI
TE
SE
AT
TL
E, W
AS
HI
NG
TO
N
4-
180991
JH
AG
IN
DI
AN
H
EA
LT
H
SE
RV
IC
E
CONSTRUCTION DOCUMENTS 03.07.2025
REVISION SCHEDULE
REV. # DESCRIPTION DATE
STRIPING DETAILS
C404
BLACK PAINT
TLOF SIZE / WEIGHT LIMITATION MARKING
RED PAINT
HELISTOP IDENTIFICATION SYMBOL
BLACK PAINT
VERTICAL STROKE OF 2.5"
HORIZONTAL STROKE OF 6"
TLOF SIZE / WEIGHT NUMBERS
NOTES:
1. ALL WHITE MARKINGS SHALL BE OUTLINED WITH A
6" BLACK STRIPE.
2. THE "H" SHOULD BE LOCATED IN THE CENTER OF
THE TLOF AND ORIENTED ON THE AXIS OF THE
PREFERRED APPROACH/DEPARTURE PATH.
1P 1 POLE (2P, 3P, 4P, ETC.)
A AMPERE
AC ABOVE COUNTER OR AIR
CONDITIONER
ACLG ABOVE CEILING
ADO AUTOMATIC DOOR OPENER
AF AMP FRAME
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AFI ARC FAULT CIRCUIT
INTERRUPTER
AHU AIR HANDLING UNIT
AL ALUMINUM
ALT ALTERNATE
AMP AMPERE
AMPL AMPLIFIER
ANNUN ANNUNCIATOR
APPROX APPROXIMATELY
AQ-STAT AQUASTAT
ARCH ARCHITECT, ARCHITECTURAL
AS AMP SWITCH
AT AMP TRIP
ATS AUTOMATIC TRANSFER SWITCH
AUTO AUTOMATIC
AUX AUXILIARY
AV AUDIO VISUAL
AWG AMERICAN WIRE GAUGE
BATT BATTERY
BD BOARD
BLDG BUILDING
BMS BUILDING MANAGEMENT SYSTEM
C CONDUIT
CAB CABINET
CAT CATALOG
CATV CABLE TELEVISION
CB CIRCUIT BREAKER
CCTV CLOSED CIRCUIT TELEVISION
CKT CIRCUIT
CLG CEILING
COMB COMBINATION
CMPR COMPRESSOR
CONN CONNECTION
CONST CONSTRUCTION
CONT CONTINUATION OR CONTINUOUS
CONTR CONTRACTOR
CONV CONVECTOR
CP CIRCULATING PUMP
CRT CATHODE-RAY TUBE
CT CURRENT TRANSFORMER
CTR CENTER
CU COPPER
DCP DOMESTIC WATER CIRCULATING PUMP
DEPT DEPARTMENT
DET DETAIL
DIA DIAMETER
DISC DISCONNECT
DIST DISTRIBUTION
DN DOWN
DPR DAMPER
DS SAFETY DISCONNECT SWITCH
DT DOUBLE THROW
DWG DRAWING
EC ELECTRICAL CONTRACTOR
ELEC ELECTRIC, ELECTRICAL
ELEV ELEVATOR
EM EMERGENCY
EMS ENERGY MANAGEMENT SYSTEM
EMT ELECTRICAL METALLIC TUBING
EP ELECTRIC PNEUMATIC
EQUIP EQUIPMENT
EWC ELECTRIC WATER COOLER
EXIST EXISTING
EXH EXHAUST
EXP EXPLOSION PROOF
FA FIRE ALARM
FABP FIRE ALARM BOOSTER POWER
SUPPLY PANEL
FACP FIRE ALARM CONTROL PANEL
FCU FAN COIL UNIT
FIXT FIXTURE
FLR FLOOR
FLUOR FLUORESCENT
FU FUSE
FUDS FUSED SAFETY DISCONNECT SWITCH
GA GAUGE
GAL GALLON
GALV GALVANIZED
GC GENERAL CONTRACTOR
GEN GENERATOR
GFI GROUND FAULT CIRCUIT INTERRUPTER
GFP GROUND FAULT PROTECTOR
GND GROUND
GRS GALVANIZED RIGID STEEL (CONDUIT)
GYP BD GYPSUM BOARD
HOA HANDS-OFF-AUTOMATIC SWITCH
HORIZ HORIZONTAL
HP HORSEPOWER
HPF HIGH POWER FACTOR
HT HEIGHT
HTG HEATING
HTR HEATER
HV HIGH VOLTAGE
HVAC HEATING, VENTILATING AND AIR
CONDITIONING
HWP HYDRONIC WATER PUMP
IC INTERRUPTING CAPACITY
IG ISOLATED GROUND
IMC INTERMEDIATE METAL CONDUIT
INCAND INCANDESCENT
IR INFRARED
I/W INTERLOCK WITH
J-BOX JUNCTION BOX
KV KILOVOLT
KVA KILOVOLT-AMPERE
KVAR KILOVOLT-AMPERE REACTIVE
KW KILOWATT
KWH KILOWATT HOUR
LOC LOCATE OR LOCATION
LT LIGHT
LTG LIGHTING
LTNG LIGHTNING
LV LOW VOLTAGE
MAX MAXIMUM
MAG.S MAGNETIC STARTER
M/C MOMENTARY CONTACT
MC MECHANICAL CONTRACTOR
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MDC MAIN DISTRIBUTION CENTER
MDP MAIN DISTRIBUTION PANEL
MFR MANUFACTURER
MFS MAIN FUSED DISCONNECT SWITCH
MH MANHOLE
MIC MICROPHONE
MIN MINIMUM
MISC MISCELLANEOUS
MLO MAIN LUGS ONLY
MMS MANUAL MOTOR STARTER
MOA MULTIOUTLET ASSEMBLY
MSP MOTOR STARTER PANELBOARD
MSBD MAIN SWITCHBOARD
MT MOUNT
MT.C EMPTY CONDUIT
MTS MANUAL TRANSFER SWITCH
MTR MOTOR, MOTORIZED
N.C. NORMALLY CLOSED
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECTRICAL
MANUFACTURER'S ASSOCIATION
NFDS NON-FUSED SAFETY DISCONNECT
SWITCH
NIC NOT IN CONTRACT
NL NIGHT LIGHT
N.O. NORMALLY OPEN
NPF NORMAL POWER FACTOR
NTS NOT TO SCALE
OH OVERHEAD
OL OVERLOADS
PA PUBLIC ADDRESS
PB PULL BOX OR PUSHBUTTON
PE PNEUMATIC ELECTRIC
PED PEDESTAL
PF POWER FACTOR
PH PHASE
PIV POST INDICATING VALVE
PNL PANEL
PP POWER POLE
PR PAIR
PRI PRIMARY
PROJ PROJECTION
PRV POWER ROOF VENTILATOR
PT POTENTIAL TRANSFORMER
PVC POLYVINYL CHLORIDE (CONDUIT)
PWR POWER
QUAN QUANTITY
RCPT RECEPTACLE
REQD REQUIRED
RM ROOM
RSC RIGID STEEL CONDUIT
RTU ROOF TOP UNIT
SC SURFACE CONDUIT
SEC SECONDARY
SHT SHEET
SIM SIMILAR
S/N SOLID NEUTRAL
SPEC SPECIFICATION
SPKR SPEAKER
SP SPARE
SR SURFACE RACEWAY
SS STAINLESS STEEL
SSW SELECTOR SWITCH
S/S STOP/START PUSHBUTTONS
STA STATION
STD STANDARD
SURF SURFACE MOUNTED
SW SWITCH
ELECTRICAL ABBREVIATIONS LIST
SWBD SWITCHBOARD
SYM SYMMETRICAL
SYS SYSTEM
TEL TELEPHONE
TEL/DATA TELEPHONE/DATA
TERM TERMINAL
TL TWIST LOCK
TR TAMPER RESISTANT
T-STAT THERMOSTAT
TTC TELEPHONE TERMINAL CABINET
TV TELEVISION
TVTC TELEVISION TERMINAL CABINET
TYP TYPICAL
UC UNDER COUNTER
UE UNDERGROUND ELECTRICAL
UG UNDERGROUND
UH UNIT HEATER
UT UNDERGROUND TELEPHONE
UTIL UTILITY
UV UNIT VENTILATOR OR
ULTRAVIOLET
V VOLT
VA VOLT-AMPERES
VDT VIDEO DISPLAY TERMINAL
VERT VERTICAL
VFD VARIABLE FREQUENCY DRIVE
VOL VOLUME
W WATT
W/ WITH
WG WIRE GUARD
WH WATER HEATER
W/O WITHOUT
WP WEATHERPROOF
XFMR TRANSFORMER
XFR TRANSFER
∠ ANGLE
@ AT
▲ DELTA
' FEET
" INCHES
# NUMBER
Ø PHASE
C CENTER LINE
P PLATE
A2
E d
ELECTRICAL SYMBOL NOTES
b
FIXTURE TYPE
SWITCH DESIGNATION
CIRCUIT NUMBER
FIXTURE TYPE
CHEVRON DIRECTION
SHADE = EXIT FACE
CIRCUIT NUMBER
CIRCUIT NUMBER
SWITCH IDENTIFICATION
SYMBOLSYMBOL SYMBOL
ELECTRICAL SYMBOL LEGEND
J
2 POLE SINGLE THROW SW.
SINGLE POLE SW.
DIMMER SWITCH
MOMENTARY CONTACT SWITCH
OCCUPANCY SENSOR SWITCH
SINGLE RECEPT.
TIME DELAY SWITCH
SPLIT DUPLEX RECEPT.
QUADPLEX RECEPT.
DUPLEX RECEPT.
RECEPT ON EMERGENCY CKT (DUPLEX SHOWN)
ISOLATED GROUND RECEPT (DUPLEX SHOWN)
RECEPT ON DROP CORD (DUPLEX SHOWN)
RECEPT ON CORD REEL (DUPLEX SHOWN)
FLOOR RECEPT. (DUPLEX SHOWN)
KEYED SW.
SW. W/PILOT
3-WAY SW.
4-WAY SW.
DESCRIPTION
WALL MOUNTED FLOODLIGHT (TYPE DENOTED)
POLE MOUNTED LIGHT (TYPE DENOTED)
RECESSED LIGHT (TYPE DENOTED)
SURFACE LIGHT (TYPE DENOTED)
EXIT SIGN (TYPE DENOTED)
SUSPENDED OR PENDANT LIGHT (TYPE DENOTED)
TRACK AND TRACK LIGHT (TYPES DENOTED)
SURFACE LINEAR LIGHT (TYPE DENOTED)
STRIP LIGHT (TYPE DENOTED)
EMERGENCY BATTERY LIGHT (TYPE DENOTED)
RECESSED LINEAR LIGHT (TYPE DENOTED)
POLE MOUNTED FLOODLIGHT (TYPE DENOTED)
QUADRAPLEX PLEX RECEPTACLE
ON EMERGENCY CIRCUIT
LIGHT FIXTURE ON EMERGENCY CIRCUIT
CIRCUIT BREAKER PANEL
DASHED SYMBOL INDICATES REMOVED
HALFTONE SYMBOL INDICATES EXISTING
LIGHT LEVEL SENSOR - TYPE DENOTED
PHOTOCELL
SAFETY DISC. SW. (FUSED)
SAFETY DISC. SW. (NON-FUSED)
COMB. MOTOR STARTER (FUSED)
POWER OR DISTRIBUTION PANEL
MOTOR (SEE SCHEDULE)
TRANSFORMER (TYPE DENOTED)
STATIC GROUND RECEPTACLE (TYPE DENOTED)
SPECIAL RECEPT. OR CONN. (SEE SCHEDULE)
JUNCTION BOX (FLOOR MOUNTED)
GROUND ROD (PLAN VIEW)
LIGHTNING PROTECTION AIR TERMINAL
CLOCK (TYPE DENOTED)
POWER POLE (OPEN OFFICE STYLE)
MULTIOUTLET ASSEMBLY (TYPE DENOTED)
DESCRIPTION
UTILITY SERVICE POWER POLE (SITE)
OCCUPANCY SENSOR - TYPE DENOTED
COMBINATION TELEPHONE/DATA OUTLET
INFORMATION OUTLET (TYPE DENOTED)
TELEPHONE OUTLET (TYPE DENOTED)
DESCRIPTION
WIRELESS ACCESS POINT
CARD READER
SECURITY
SYSTEMS
FIRE ALARM
JUNCTION BOX (WALL MOUNTED)
CR
C
POWERLIGHTING
SYMBOL
TELEPHONE OUTLET (TYPE DENOTED)
DESCRIPTION
SYSTEMS
SYMBOL DESCRIPTIONSYMBOL DESCRIPTION
INSTRUMENTATION
MANUAL MOTOR STARTER SWITCH
WEATHER PROOF SWITCH
TIMER SWITCH
D P
K
OS
M
W P
MC
T
TD
OS
LS
P
WAP
DOOR CONTACTDC
MOTION DETECTORMD
CCTV
CCTV-PTZ
* = * FACP (FIRE ALARM CONTROL PANEL)
FAA (FIRE ALARM ANNUNCIATOR)
FAGM (FIRE ALARM GRAPHIC MAP)
PACP (PRE-ACTION CONTROL PANEL)
* =* F (MANUAL PULL STATION)
FD (FIRE DAMPER)
F/S (FIRE/SMOKE DAMPER)
SD (SMOKE DAMPER)
M (MAGNETIC DOOR HOLDER)
RT (REMOTE TEST STATION & PILOT LIGHT)
V (VISUAL)
I OR Z (INDIVIDUAL ADDRESSABLE MODULE)
WHERE X:
C (CONTROL TYPE)
M (MONITOR TYPE)
S (SUPERVISORY)
* =* F (FLOW SWITCH)
T (TAMPER SWITCH)
P/V (POST INDICATOR VALVE)
* =* A (AUDIBLE)
H (HORN)
AV (AUDIBLE & VISUAL)
WHERE X:
X (CANDELA RATING)
* = D (DUCT DETECTOR)
H (HEAT)
S (SMOKE)
F (FLAME DETECTOR)
IR (INFRA-RED)
MF (MULTI SPECTRUM FLAME)
S (SMOKE DETECTOR)
I (IONIZATION)
P (PHOTOELECTRIC)
H (HEAT DETECTOR)
R (RATE OF RISE)
F (FIXED TEMPERATURE)
WIRING AND GROUNDING
XX =XX PS (PRESSURE SWITCH)
SV (SOLENOID VALVE)
LS (LIMIT SWITCH)
L (FLOAT SWITCH)
FS (FLOW SWITCH)
FD (FLOOR FLOOD FLOAT SWITCH)
T (THERMOSTAT)
MV (MOTORIZED VALVE)
XX =XX PT (PRESSURE TRANSMITTER)
LT (LEVEL TRANSMITTER)
LE (LEVEL ELEMENT)
FT (FLOW TRANSMITTER)
FM (FLOW METER ELEMENT)
TT (TEMPERATURE TRANSMITTER)
AT (ANALYZER)
MV (MODULATING MOTORIZED VALVE)
AE (ANALYZER ELEMENT)
CONDUIT EXPOSED
CONDUIT CONCEALED
CONDUIT CAPPED
CONDUIT CONTINUED
GROUND CONDUCTOR
OH OVERHEAD ELECTRICAL LINE
EE DIRECT BURIED CONDUIT
XX-1
P
P
J
J
J
SYSTEM
DESIGNATION
EQUIPMENT
DESIGNATION
EMERGENCY
UNINTERRUPTIBLE POWER SOURCE
NORMAL
U
LPE-102
E
(BLANK)
PANEL NUMBER
FLOOR OF STRUCTURE
3Ø4W. 208Y/120V
3Ø4W, 480Y/277V
EQUIPMENT DESIGNATION
SYSTEMS DESIGNATION
LP
PP
CODE
CODE
P3Ø3W. 480
L1Ø3W. 240/120V
PANELBOARD IDENTIFICATION
CURRENT TRANSFORMER
SELECTOR SWITCH
STARTER, CONTACTOR OR RELAY COIL
FLOAT SWITCH (OPENING ON RISING LEVEL)
FLOAT SWITCH (CLOSING ON RISING LEVEL)
TEMPERATURE SWITCH (OPENING ON RISING LEVEL)
TEMPERATURE SWITCH (CLOSING ON RISING LEVEL)
NORMALLY CLOSED PUSH-BUTTON
NORMALLY OPEN PUSH-BUTTON
NORMALLY OPEN CONTACTS
NORMALLY CLOSED CONTACTS
NORMALLY OPEN LIMIT SWITCH
SWITCH
SOLENOID
FUSE
GROUND
CONNECTION POINT
SURGE SUPPRESSION
THERMAL OVERLOAD RELAY
PILOT LIGHT
TRANSFORMER
MAGNETIC STARTER
FUSED DISCONNECT
POTENTIAL TRANSFORMER
NORMALLY CLOSED LIMIT SWITCH
MUSHROOM HEAD PUSH-BUTTON
FIXED CAPACITOR
CIRCUIT BREAKER
MOTOR- NUMBER DENOTES HORSEPOWER
EXTERNAL CONNECTION POINT
KEY INTERLOCK
P
P
SWITCH (OPENING ON INCREASE)
P=PRESSURE
V=VACCUM
DP=DIFFERENTIAL PRESSURE
SWITCH (CLOSING ON INCREASE)
P=PRESSURE
V=VACCUM
DP=DIFFERENTIAL PRESSURE
ON TIME DELAY SWITCH
(TIME DELAY AFTER COIL IS ENERGIZED)
OFF TIME DELAY SWITCH
(TIME DELAY BEFORE COIL IS ENERGIZED)
AT PLC (SCHEMATIC DEVICE LOCATION)
AT MOTOR (SCHEMATIC DEVICE LOCATION)
FLOW SWITCH (CLOSING ON INCREASE IN FLOW)
FLOW SWITCH (OPENING ON INCREASE IN FLOW)
TORQUE SWITCH (NORMALLY CLOSED)
TORQUE SWITCH (NORMALLY OPEN)
METERING DEVICE
ENGINE DRIVEN GENERATOR
ALARM HORN
ANTENNA
POTENTIOMETER
OCCUPANCY SENSOR, CEIL MOUNT
OCCUPANCY SENSOR, WALL MOUNT
DRAWOUT CIRCUIT BREAKER
SCHEMATIC SYMBOLS
AT MFR CP (SCHEMATIC DEVICE LOCATION)
R1
G
K
OS
OS
L A
M E
D E
E R
C L
IN
IC
H E
L
IP
O R
T R
E C
O N
S T
R U
C T
IO
N
B
IL
L
IN
G S
A R
E A
O F
F
IC
E
F
IF
T
H A
V E
N U
E , M
S
4, S
U
IT
E
S E
A T
T
LE
, W A
S H
IN
G
T O
N
-7
180991
JS
NS/JS
IN
D
IA
N
H E
A
LT
H S
E R
V
IC
E
CONSTRUCTION DOCUMENTS 03.07.2025
REVISION SCHEDULE
REV. # DESCRIPTION DATE
R
SEH Project
Checked By
Drawn By
Project Status Issue Date
This drawing is an instrument of service and shall remain the property of Short Elliott Hendrickson, Inc.
(SEH). This drawing, concepts and ideas contained herein shall not be used, reproduced, revised, or retained without the express written approval of SEH.
Submission or distribution of this drawing to meet official or regulatory requirements or for purposes in connection with the project is not be construed as publication in derogation of any of the rights of SEH. S ho rt E lli ot t H en dr ic ks on
, I nc
A ll
R ig ht s
R es er ve d
C O
P Y
R
IG
H T
PROJECT OWNER
INDIAN HEALTH SERVICE (IHS)
DEPARTMENT OF HEALTH AND HUMAN
SERVICES
DIVISION OF ENGINEERING SERVICES
701 FIFTH AVENUE, MS 24, SUITE 1600
SEATTLE, WASHINGTON 98104-7304
CIVIL, MEP, STRUCTURAL
SHORT ELLIOTT HENDRICKSON INC.
2000 SOUTH COLORADO BLVD.
SUITE 1200, COLORADO CENTER TOWER TWO
DENVER, CO. 80222
720.540.6800
ELECTRICAL TITLE SHEET
E001
INDEX OF ELECTRICAL DRAWINGS
E001 ELECTRICAL TITLE SHEET
E051 LAME DEER ELECTRICAL SITE PLAN
E101 LAME DEER ENLARGED LIGHTING AND POWER PLAN
E501 LAME DEER ONE-LINE DIAGRAM
E601 LAME DEER ELECTRICAL SCHEDULES AND DETAILS
03/07/2025
T
J
KEYNOTES
1. APPROXIMATE LOCATION OF ELECTRICAL ROOM CONTAINING PANEL P3.
X
SITE GENERAL NOTES
A. ALL WORK SHALL COMPLY WITH THE 2023 NATIONAL ELECTRIC CODE, NATIONAL,
STATE, AND LOCAL CODES.
B. COORDINATE ALL EQUIPMENT LOCATIONS AND REQUIREMENTS PRIOR TO ROUGH IN.
C. ALL CONDUIT ROUTING SHOWN IS APPROXIMATE. IT IS THE ELECTRICAL
CONTRACTOR'S RESPONSIBILITY TO COORDINATE WITH ALL OTHER TRADES AND
UTILITIES TO AVOID CONFLICTS WITH NEW WORK AND EXISTING CONDITIONS PRIOR
TO INSTALLATION.
D. ALL EXTERIOR CIRCUITS SHALL BE #10 AWG CONDUCTORS AT A MINIMUM FOR THE
ENTIRE LENGTH OF THE CIRCUIT.
E. CIRCUIT NUMBERS AT HOMERUNS CORRESPOND TO PANELBOARD BREAKERS (SEE
PANELBOARD SCHEDULES). BRANCH CIRCUITS CONDUCTORS SHALL BE SIZED
ACCORDING TO THE CIRCUIT BREAKER RATING UNLESS OTHERWISE INDICATED ON
THE EQUIPMENT SCHEDULES(S).
F. ALL LIGHTING AND POWER CONDUCTORS SHALL BE INSTALLED BETWEEN 24"
(MINIMUM) AND 36" (MAXIMUM) BELOW FINISHED GRADE.
L A
M E
D E
E R
C L
IN
IC
H E
L
IP
O R
T R
E C
O N
S T
R U
C T
IO
N
B
IL
L
IN
G S
A R
E A
O F
F
IC
E
F
IF
T
H A
V E
N U
E , M
S
4, S
U
IT
E
S E
A T
T
LE
, W A
S H
IN
G
T O
N
-7
180991
JS
NS/JS
IN
D
IA
N
H E
A
LT
H S
E R
V
IC
E
CONSTRUCTION DOCUMENTS 03.07.2025
REVISION SCHEDULE
REV. # DESCRIPTION DATE
R
SEH Project
Checked By
Drawn By
Project Status Issue Date
This drawing is an instrument of service and shall remain the property of Short Elliott Hendrickson, Inc.
(SEH). This drawing, concepts and ideas contained herein shall not be used, reproduced, revised, or retained without the express written approval of SEH.
Submission or distribution of this drawing to meet official or regulatory requirements or for purposes in connection with the project is not be construed as publication in derogation of any of the rights of SEH. S ho rt E lli ot t H en dr ic ks on
, I nc
A ll
R ig ht s
R es er ve d
C O
P Y
R
IG
H T
PROJECT OWNER
INDIAN HEALTH SERVICE (IHS)
DEPARTMENT OF HEALTH AND HUMAN
SERVICES
DIVISION OF ENGINEERING SERVICES
701 FIFTH AVENUE, MS 24, SUITE 1600
SEATTLE, WASHINGTON 98104-7304
CIVIL, MEP, STRUCTURAL
SHORT ELLIOTT HENDRICKSON INC.
2000 SOUTH COLORADO BLVD.
SUITE 1200, COLORADO CENTER TOWER TWO
DENVER, CO. 80222
720.540.6800
LAME DEER ELECTRICAL
SITE PLAN
E051 1/32" = 1'-0"
LAME DEER ELECTRICAL SITE PLAN
0 24' 48' 72'
J
GENERAL NOTES
A. ALL WORK SHALL COMPLY WITH THE 2023 NATIONAL ELECTRIC CODE, NATIONAL,
STATE AND LOCAL CODES.
B. COORDINATE ALL FIXTURE AND CONTROL DEVICE LOCATIONS WITH MECHANICAL
PIPING, DUCTWORK, ECT., TO AVOID CONFLICT PRIOR TO ROUGH IN.
C. COOORDINATE ALL EQUIPMENT LOCATIONS AND REQUIREMENTS PRIOR TO ROUGH IN.
D. ALL EXTERIOR CIRCUITS SHALL BE #10 AWG CONDUCTORS AT A MINIMUM FOR THE
ENTIRE LENGTH OF THE CIRCUIT.
E. ALL LIGHTING AND POWER CONDUCTORS SHALL BE INSTALLED BETWEEN
24"(MINIMUM) AND 36"(MAXIMUM) BELOW FINISHED GRADE.
F. ALL RECEPTACLES LABELED WP SHALL BE PROTECTED WITH AN IN-USE TYPE
WEATHERPROOF ENCLOSURE.
G. LOWERCASE LETTERS AT FIXTURES CORRESPOND TO TEH SWITCH AND/OR CONTROL
DEVICE IDENTIFICATION.
H. ALL LIGHT SWITCHES ARE MOUNTED 48" ABOVE FINISHED FLOOOR, UNLESS
OTHERWISE INDICATED ON THE DRAWINGS.
I. FOR ALL 20A CIRCUITS EXCEEDING 120' FROM THE PANEL TO THE FIXTURE, PROVIDE #
10 AWG CONDUCTORS FOR VOLTAGE DROP.
J. WIRE COUNTS FOR CIRCUIT CONDUCTORS ARE NOT SHOWN. PROVIDE PROPER
NUMBER OF CONDUCTORS TO ACHIEVE CIRCUIT AND SWITCHING CONNECTIONS
SHOWN.
K. CIRCUIT NUMBERS AT HOMERUN CORRESPOND TO PANELBOARD BREAKERS (SEE
PANELBOARD SCHEDULE(S)). BRANCH CIRCUITS SHALL BE SIZED ACCORDING TO THE
CIRCUIT BREAKER RATING, UNLESS INDICATED OTHERWISE ON TEH EQUIPMENT
SCHEDULE(S).
L. NO METALLIC MATERIALS SHOULD BE IN DIRECT CONTACT WITH CONDUCTIVE
CONCRETE. METAL OBJECTS MUST BE INSULATED FROM CONDUCTIVE CONCRETE
WITH PLASTIC SHEATHS, EPOXY COATING OR SEALANT, OR ENCASED IN STANDARD
CONCRETE. SPECIFIC METAL OBJECTS INCLUDE, BUT NOT LIMITED TO: LIGHTING
CONDUCTORS AND FIXTURES.
KEYNOTES
1. EXISTING WIND SOCK. DISCONNECT FROM EXISTING CIRCUIT AND RECONNECT TO
NEW HELIPAD LIGHTING CIRCUIT P3-56. CONTROL FOR WIND SOCK LIGHTING
ASSEMBLY SHALL BE CONNECTED TO EXISTING LIGHT SWITCH FOR HELIPAD LIGHTING.
2. L-852H BASIS OF DESIGN: "FLIGHT LIGHT HL-392 G IR LPUL". LIGHT FIXTURE TO BE
INSTALLED IN LOAD BEARING LIGHT BASE L-868 SIZE A. FIXTURE BASE L-868 BASIS OF
DESIGN: "FLIGHT LIGHT: 30-L868AH-2QD". CONNECT TO EXISTING LIGHT SWITCH FOR
HELIPAD LIGHTS. TYP.
3. APPROXIMATE LOCATION OF EXISTING LIGHT SWITCH FOR HELIPAD LIGHTS. EXISTING
LIGHT…