This solicitation is for construction services to perform upgrades to the EHRM server room and site communication infrastructure at the VA Greater Los Angeles Healthcare System. The work includes general construction, alterations, mechanical, electrical and utility systems work. All work must be performed in accordance with the terms, conditions, specifications and drawings of the solicitation and applicable building codes. This is a 100% set-aside for Service-Disabled Veteran-Owned Small Businesses listed as verified on VIP database. The point of contact for questions is Steven J. Covell, Contracting Specialist, via email at steve.covell@va.gov.

View the file

Other files for this federal contract opportunity

Show all 22

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

J

120VAC

4 3

J

J

W.257.E-401

ELECTRICAL ENLARGED PLAN -

TR ROOM, 135

0' 2' 4' 12'

SCALE: 1/4" = 1'-0"

Project Number

Campus / Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

A

F i l e

P a t h

U.S. Department of Veterans Affairs

B

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Project Director

Revisions: Date:

Key Plan

Upgrade Server Room and Site Communication Infrastructure

11301 WILSHIRE BOULEVARD,

WEST LOS ANGELES, CA 90073

691-20-152FINAL CONSTRUCTION

DOCUMENTS

JULY 13, 2021 PM EW/JB

FULLY SPRINKLERED

A

GENERAL NOTES

ARCHITECT/ENGINEER OF RECORD

C

D

17075 Via Del Campo, San Diego, CA 92127

Phone: 858.946.0333

20801.11 20-SCE-06

GENERAL NOTE

FIRE PROTECTION

1. DO NOT MAKE ANY ATTACHMENTS OR MODIFICATIONS TO

ANY FIREPROOFED COMPONENTS.

SYMBOLS LIST

2 HOUR FIRE BARRIER

1 HOUR FIRE BARRIER

2 HOUR FIRE/SMOKE BARRIER

SMOKE BARRIER

SMOKE PARTITION

1 HOUR FIRE/SMOKE BARRIER

3 HOUR FIRE BARRIER

KEY NOTES

NEW HIRSCH ACCESS CONTROL PANEL.

NEW PIV READER. SEE E-503 FOR CONDUIT

REQUIREMENT.

3/4''C- 2 #12 + 1 #12EG

CONNECT TO EXISTING CIRCUIT IN TR ROOM.

TO HIRSCH ACCESS CONTROL PANEL. SEE

KEYNOTE 1 & ACCESS CONTROL RISER

DIAGRAM ON T-600 SERIES DRAWING.

SCALE: 1/4" = 1' - 0"

NORTH

TR ROOM

B

SCALE: 1/4" = 1' - 0"

NORTH

TR ROOM

1.

2.

SCALE: 1/4" = 1' - 0"

NORTH

TR ROOM

120VAC

J

J

J

J

J

J

J

J

W.258.E-401

Project Number

Campus / Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

A

F i t h

U.S. Department of Veterans Affairs

B

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Project Director

Revisions: Date:

Upgrade Server Room and Site Communication Infrastructure

11301 WILSHIRE BOULEVARD,

WEST LOS ANGELES, CA 90073

691-20-152FINAL CONSTRUCTION

DOCUMENTS

JULY 13, 2021 PM EW/JB

FULLY SPRINKLERED

A

GENERAL NOTES

ARCHITECT/ENGINEER OF RECORD

C

D

17075 Via Del Campo, San Diego, CA 92127

Phone: 858.946.0333

20801.11 20-SCE-06

GENERAL NOTE

FIRE PROTECTION

1. DO NOT MAKE ANY ATTACHMENTS OR MODIFICATIONS TO

ANY FIREPROOFED COMPONENTS.

SYMBOLS LIST

2 HOUR FIRE BARRIER

1 HOUR FIRE BARRIER

2 HOUR FIRE/SMOKE BARRIER

SMOKE BARRIER

SMOKE PARTITION

1 HOUR FIRE/SMOKE BARRIER

3 HOUR FIRE BARRIER

0' 2' 4' 12'

SCALE: 1/4" = 1'-0"

SCALE: 1/4" = 1' - 0"

NORTH

SCALE: 1/4" = 1' - 0"

NORTH

TR ROOM 105

TR ROOM 136A

SCALE: 1/4" = 1' - 0"

NORTH

SCALE: 1/4" = 1' - 0"

NORTH

TR ROOM 210A

TR ROOM 215

KEY NOTES

NEW HIRSCH ACCESS CONTROL PANEL.

NEW PIV READER. SEE E-503 FOR CONDUIT

REQUIREMENT.

3/4''C- 2 #12 + 1 #12EG

CONNECT TO EXISTING CIRCUIT IN TR ROOM.

TO HIRSCH ACCESS CONTROL PANEL. SEE

KEYNOTE 1 & ACCESS CONTROL RISER

DIAGRAM ON T-600 SERIES DRAWING.

1.

2.

TR ROOM 120

TR ROOM 104A

SCALE: 1/4" = 1' - 0"

NORTH

TR ROOM 404

SCALE: 1/4" = 1' - 0"

NORTH

TR ROOM 335

120VAC

J

SCALE: 1/4" = 1' - 0"

NORTH

W.259.E-401

ELECTRICAL ENLARGED PLAN -

TR ROOM

0' 2' 4' 12'

SCALE: 1/4" = 1'-0"

Project Number

Campus / Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

A

F i t h U.S. Department of Veterans Affairs

B

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Project Director

Revisions: Date:

Key Plan

Upgrade Server Room and Site Communication Infrastructure

11301 WILSHIRE BOULEVARD,

WEST LOS ANGELES, CA 90073

691-20-152FINAL CONSTRUCTION

DOCUMENTS

JULY 13, 2021 PM EW/JB

FULLY SPRINKLERED

A

GENERAL NOTES

ARCHITECT/ENGINEER OF RECORD

C

D

17075 Via Del Campo, San Diego, CA 92127

Phone: 858.946.0333

20801.11 20-SCE-06

GENERAL NOTE

FIRE PROTECTION

1. DO NOT MAKE ANY ATTACHMENTS OR MODIFICATIONS TO

ANY FIREPROOFED COMPONENTS.

SYMBOLS LIST

2 HOUR FIRE BARRIER

1 HOUR FIRE BARRIER

2 HOUR FIRE/SMOKE BARRIER

SMOKE BARRIER

SMOKE PARTITION

1 HOUR FIRE/SMOKE BARRIER

3 HOUR FIRE BARRIER

KEY NOTES

NEW DOOR AND WALL

NEW HIRSCH ACCESS CONTROL PANEL.

NEW PIV READER. SEE E-503 FOR CONDUIT

REQUIREMENT.

3/4''C- 2 #12 + 1 #12EG

CONNECT TO EXISTING CIRCUIT IN TR ROOM.

TO HIRSCH ACCESS CONTROL PANEL. SEE

KEYNOTE 1 & ACCESS CONTROL RISER

DIAGRAM ON T-600 SERIES DRAWING.

1.

2.

UP

SCALE: 1/4" = 1' - 0"

NORTH

W.295.E-401

ELECTRICAL ENLARGED PLAN -

TR ROOM

0' 2' 4' 12'

SCALE: 1/4" = 1'-0"

Project Number

Campus / Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

A

F i t h

U.S. Department of Veterans Affairs

B

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Project Director

Revisions: Date:

Key Plan

Upgrade Server Room and Site Communication Infrastructure

11301 WILSHIRE BOULEVARD,

WEST LOS ANGELES, CA 90073

691-20-152FINAL CONSTRUCTION

DOCUMENTS

JULY 13, 2021 PM EW/JB

FULLY SPRINKLERED

A

GENERAL NOTES

ARCHITECT/ENGINEER OF RECORD

C

D

17075 Via Del Campo, San Diego, CA 92127

Phone: 858.946.0333

20801.11 20-SCE-06

GENERAL NOTE

FIRE PROTECTION

1. DO NOT MAKE ANY ATTACHMENTS OR MODIFICATIONS TO

ANY FIREPROOFED COMPONENTS.

SYMBOLS LIST

2 HOUR FIRE BARRIER

1 HOUR FIRE BARRIER

2 HOUR FIRE/SMOKE BARRIER

SMOKE BARRIER

SMOKE PARTITION

1 HOUR FIRE/SMOKE BARRIER

3 HOUR FIRE BARRIER

NEW FIBER TERMINAL DISTRIBUTION UNIT TDU.

TERMINATE FIBER ON FIBER PATCH PANEL.

KEY NOTES

1 120VAC

J

5 2

SCALE: 1/4" = 1' - 0"

NORTH

W.297.E-401

ELECTRICAL ENLARGED PLAN -

TR ROOM

0' 2' 4' 12'

SCALE: 1/4" = 1'-0"

Project Number

Campus / Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

A

F i t h

U.S. Department of Veterans Affairs

B

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Project Director

Revisions: Date:

Key Plan

Upgrade Server Room and Site Communication Infrastructure

11301 WILSHIRE BOULEVARD,

WEST LOS ANGELES, CA 90073

691-20-152FINAL CONSTRUCTION

DOCUMENTS

JULY 13, 2021 PM EW/JB

FULLY SPRINKLERED

A

GENERAL NOTES

ARCHITECT/ENGINEER OF RECORD

C

D

17075 Via Del Campo, San Diego, CA 92127

Phone: 858.946.0333

20801.11 20-SCE-06

GENERAL NOTE

FIRE PROTECTION

1. DO NOT MAKE ANY ATTACHMENTS OR MODIFICATIONS TO

ANY FIREPROOFED COMPONENTS.

SYMBOLS LIST

2 HOUR FIRE BARRIER

1 HOUR FIRE BARRIER

2 HOUR FIRE/SMOKE BARRIER

SMOKE BARRIER

SMOKE PARTITION

1 HOUR FIRE/SMOKE BARRIER

3 HOUR FIRE BARRIER

KEY NOTES

NEW HIRSCH ACCESS CONTROL PANEL.

3/4''C- 2 #12 + 1 #12EG

CONNECT TO EXISTING CIRCUIT IN TR ROOM.

TO HIRSCH ACCESS CONTROL PANEL. SEE

KEYNOTE 1 & ACCESS CONTROL RISER

DIAGRAM ON T-600 SERIES DRAWING.

1.

120VAC

J

W.300.E-401

ELECTRICAL ENLARGED PLAN -

TR ROOM 106 AND 206B

0' 2' 4' 12'

SCALE: 1/4" = 1'-0"

Project Number

Campus / Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

A

F i t h

U.S. Department of Veterans Affairs

B

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Project Director

Revisions: Date:

Key Plan

Upgrade Server Room and Site Communication Infrastructure

11301 WILSHIRE BOULEVARD,

WEST LOS ANGELES, CA 90073

691-20-152FINAL CONSTRUCTION

DOCUMENTS

JULY 13, 2021 PM EW/JB

FULLY SPRINKLERED

A

GENERAL NOTES

ARCHITECT/ENGINEER OF RECORD

C

D

17075 Via Del Campo, San Diego, CA 92127

Phone: 858.946.0333

20801.11 20-SCE-06

GENERAL NOTE

FIRE PROTECTION

1. DO NOT MAKE ANY ATTACHMENTS OR MODIFICATIONS TO

ANY FIREPROOFED COMPONENTS.

SYMBOLS LIST

2 HOUR FIRE BARRIER

1 HOUR FIRE BARRIER

2 HOUR FIRE/SMOKE BARRIER

SMOKE BARRIER

SMOKE PARTITION

1 HOUR FIRE/SMOKE BARRIER

3 HOUR FIRE BARRIER

KEY NOTES

SCALE: 1/4" = 1' - 0"

NORTH

TR ROOM

SCALE: 1/4" = 1' - 0"

NORTH

TR ROOM

206-B

NEW HIRSCH ACCESS CONTROL PANEL.

NEW PIV READER. SEE E-503 FOR CONDUIT

REQUIREMENT.

3/4''C- 2 #12 + 1 #12EG

CONNECT TO EXISTING CIRCUIT IN TR ROOM.

TO HIRSCH ACCESS CONTROL PANEL. SEE

KEYNOTE 1 & ACCESS CONTROL RISER

DIAGRAM ON T-600 SERIES DRAWING.

1.

FROM NEW

TELEPHONE

MANHOLE

OUTDOOR

TELEPHONE

CABINET

TO OLD

SIGNAL

MANHOLE

34 2

11 12

16 7

POST COLUMN

TO REMAIN

OFFICE

CONFERENCE ROOM

MAIN TELECOM

DISTRIBUTION HUB

NIC

OFFICE

OFFICE

CONFERENCE ROOM

NIC

LOUNGE

OFFICE

NIC

RESTROOM 1

NIC

OFFICE

NIC

RESTROOM 2

DN

SCALE: 1/4" = 1' - 0" NORTH

W.301.E-401

1 FAPP-301 NETWORK FIBER LOOP 2 & FIREWORK NETWORK TO REMAIN

FAPP-301 NETWORK FIBER LOOP 3 & FIREWORK NETWORK TO REMAIN

FAPP-301 NETWORK FIBER LOOP 4 & FIREWORK NETWORK TO REMAIN

VIDEO SURVEILLANCE EQUIPMENT RACK TO REMAIN BUT RELOCATED

EXISTING LADDER RACK TO REMAIN

EXISTING ABANDONED PNEUMATIC SYSTEM CABINET & ASSOCIATED TUBE

COMING UP FROM U/G CONDUIT TO BE REMOVED AND PULLED OUT TO

MAKE ROOM FOR NEW FIBER.

EXISTING PANEL 301 100A 208/120V TO REMAIN

EXISTING SUB PANEL TO BE REMOVED. REMOVE CIRCUIT BREAKERS &

TURN IT OVER TO VA ELECTRICAL SHOP BEFORE DISPOSING OFF PANEL.

EXISTING WALL TO BE DEMOLITION.

EXISTING 110 BLOCK FOR PATCHING DATA CABLE TO BE REPLACED WITH

PATCH PANEL

EXISTING 110 RACK TO REMAIN.

EXISTING ABANDONED DUKANE SOUND SYSTEM CABINET TO BE

DISCONNECTED AND REMOVED

EXISTING CEILING MOUNTED FCU UNIT TO BE ELECTRICALLY

DISCONNECTED FOR SAFE REMOVED BY MECHANICAL CONTRACTOR.

EXISTING OUTDOOR CONDENSING UNIT TO BE ELECTRICALLY

DISCONNECTED FOR SAFE REMOVAL BY MECHANICAL CONTRACTOR.

EXISTING RACK WITH FIBER PATCH PANEL TO BE REMOVED AFTER NEW

FIBER SYSTEM IS IN PLACED AND COMMISSIONED. ALL EXISTING FIBER TO

BE PULLED OUT ALL THE WAY TO THE MANHOLE.

EXISTING SURFACE MOUNTED FIXTURES TO BE DISCONNECTED AND

REMOVED AND REPLACED.

EXISTING POWER SUPPLY RACK TO BE DISCONNECTED AND REMOVED.

KEY NOTES

Project Number

Campus / Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

A

F i t h

U.S. Department of Veterans Affairs

B

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Project Director

Revisions: Date:

Key Plan

Upgrade Server Room and Site Communication Infrastructure

11301 WILSHIRE BOULEVARD,

WEST LOS ANGELES, CA 90073

691-20-152FINAL CONSTRUCTION

DOCUMENTS

JULY 13, 2021 PM EW/JB

FULLY SPRINKLERED

A

GENERAL NOTES

ARCHITECT/ENGINEER OF RECORD

C

D

17075 Via Del Campo, San Diego, CA 92127

Phone: 858.946.0333

20801.11 20-SCE-06

GENERAL NOTE

FIRE PROTECTION

1. DO NOT MAKE ANY ATTACHMENTS OR MODIFICATIONS TO

ANY FIREPROOFED COMPONENTS.

SYMBOLS LIST

2 HOUR FIRE BARRIER

1 HOUR FIRE BARRIER

2 HOUR FIRE/SMOKE BARRIER

SMOKE BARRIER

SMOKE PARTITION

1 HOUR FIRE/SMOKE BARRIER

3 HOUR FIRE BARRIER

W.301.E-402

Project Number

Campus / Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

A

F i t h U.S. Department of Veterans Affairs

B

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Project Director

Revisions: Date:

Upgrade Server Room and Site Communication Infrastructure

11301 WILSHIRE BOULEVARD,

WEST LOS ANGELES, CA 90073

691-20-152FINAL CONSTRUCTION

DOCUMENTS

JULY 13, 2021 PM EW/JB

FULLY SPRINKLERED

A

ARCHITECT/ENGINEER OF RECORD

C

D

17075 Via Del Campo, San Diego, CA 92127

Phone: 858.946.0333

20801.11 20-SCE-06

SCALE: NONE SCALE: NONESCALE: NONE SCALE: NONE SCALE: NONE SCALE: NONE

SCALE: NONE SCALE: NONE SCALE: NONE SCALE: NONE SCALE: NONE SCALE: NONE

SCALE: NONE SCALE: NONE SCALE: NONE SCALE: NONE SCALE: NONE

CONFERENCE ROOM

MAIN TELECOM

DISTRIBUTION HUB

CONFERENCE ROOM

NIC

LOUNGE

OFFICE

NIC

RESTROOM 1

NIC

OFFICE

NIC

RESTROOM 2

DN

FROM NEW

TELEPHONE

MANHOLE

OUTDOOR

TELEPHONE

CABINET

TO OLD

SIGNAL

MANHOLE

34 2

3 12

120VAC

J 14

UPSA-1

12 12

CU

B301 COND1

T-301-14,16,18

T-301-12

WP

GFI

CRAC

B301 VRAC1DB 301 PL

CONFERENCE ROOM

MAIN TELECOM

DISTRIBUTION HUB

CONFERENCE ROOM

NIC

LOUNGE

OFFICE

NIC

RESTROOM 1

NIC

OFFICE

NIC

RESTROOM 2

DN

J

CONFERENCE ROOM

MAIN TELECOM

DISTRIBUTION HUB

CONFERENCE ROOM

NIC

LOUNGE

OFFICE

NIC

RESTROOM 1

NIC

OFFICE

NIC

RESTROOM 2

DN

UPB-1,3

UPA-1,3

RACK1 RACK 2

UPB-10,12

UPA-10,12

UP

B-

6,8

UP

A-

6,8

RACK 3 RACK 4 RACK 5 RACK 6

UP

B-

2,4

UP

A-

2,4

UPA-9,11

UPB-9,11

UPB-5,7

UPA-5,7

26 TYPICAL FOR 12

SCALE: 1/4" = 1' - 0" NORTH

W.301.E-403

Project Number

Campus / Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

A

F i t h

U.S. Department of Veterans Affairs

B

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Project Director

Revisions: Date:

Upgrade Server Room and Site Communication Infrastructure

11301 WILSHIRE BOULEVARD,

WEST LOS ANGELES, CA 90073

691-20-152FINAL CONSTRUCTION

DOCUMENTS

JULY 13, 2021 PM EW/JB

FULLY SPRINKLERED

A

GENERAL NOTES

ARCHITECT/ENGINEER OF RECORD

C

D

17075 Via Del Campo, San Diego, CA 92127

Phone: 858.946.0333

20801.11 20-SCE-06

GENERAL NOTE

FIRE PROTECTION

1. DO NOT MAKE ANY ATTACHMENTS OR MODIFICATIONS TO

ANY FIREPROOFED COMPONENTS.

SYMBOLS LIST

2 HOUR FIRE BARRIER

1 HOUR FIRE BARRIER

2 HOUR FIRE/SMOKE BARRIER

SMOKE BARRIER

SMOKE PARTITION

1 HOUR FIRE/SMOKE BARRIER

3 HOUR FIRE BARRIER

FAPP-301 NETWORK FIBER LOOP 2 & FIREWORK

NETWORK TO REMAIN.

FAPP-301 NETWORK FIBER LOOP 3 & FIREWORK

NETWORK TO REMAIN.

FAPP-301 NETWORK FIBER LOOP 4 & FIREWORK

NETWORK TO REMAIN.

EXISTING VIDEO SURVEILLANCE EQUIPMENT

RACK AT NEW LOCATION.

NOT USED.

NEW 40KVA UPS 208/120V 3P 4W W/ BYPASS &

BATTERY CABINET.

EXISTING PANEL T-301 100A 208/120V TO

REMAIN.

EXISTING 110 RACK TO REMAIN.

NEW 4 POST RACK.

NEW 18"W X 1 1/2" H LADDER RACK BLACK.

NEW HIRSCH ACCESS CONTROL PANEL.

NEW PIV READER. SEE E-503 FOR CONDUIT

REQUIREMENT.

3/4''C- 2 #12 + 1 #12EG.

TO HIRSCH ACCESS CONTROL PANEL. SEE

KEYNOTE 1 & ACCESS CONTROL RISER

DIAGRAM ON T-700 SERIES DRAWING.

NEW 100A/ 3P FUSED DISCONNECT.

1''C- 3 #4 + 1 #8EG.

NEW 30A/ 3P FUSED DISCONNECT NEMA 3R.

3/4''C- 3 #12 + 1 #12EG.

3/4''C- 2 #12 + 1 #12EG.

NEW PANEL UPA 100A 208/120V.

NEW PANEL UPB 100A 208/120V.

NEW 1 1/ 4''C- 4 #2 + 1 #8EG.

NEW 3/4''C- 3 #12 + 1 #12EG.

EXISTING FIXTURE TO BE REPLACED WITH

TYPE E .

EXISTING CRITICAL DISTRIBUTION BOARD 301

PL 800A 208/120V.

L21-20R MOUNTED ON SIDE OF LADDER RACK.

0' 2' 4' 8'

SCALE: 1/4" = 1'-0"

ALL CIRCUIT BREAKERS WILL BE TURNED

OVER TO VA ELECTRICAL SHOP

BEFORE DISPOSING OFF ELECTRICAL PANELS.

1.

2.

KEY NOTES

SCALE: 1/4" = 1' - 0" NORTH

SCALE: 1/4" = 1' - 0" NORTH

SCALE: NONE

3.

4.

OFFICE

CONFERENCE ROOM

MAIN TELECOM

DISTRIBUTION HUB

NIC

OFFICE

OFFICE

CONFERENCE ROOM

NIC

LOUNGE

OFFICE

NIC

RESTROOM 1

NIC

OFFICE

NIC

RESTROOM 2

DN

2 2

SCALE: 1/4" = 1' - 0" NORTH

W.301.E-404

1 NEW PENDANT MOUNTED LIGHTING FIXTURE.

EXISTING FIXTURE RE-CONFIGURED BOTH IN TERMS OF

PLACEMENT AND SWITCHING.

CONNECT TO EXISTING CIRCUIT.

UNSWITCHED NIGHT LIGHT.

Project Number

Campus / Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

A

F i t h

U.S. Department of Veterans Affairs

B

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Project Director

Revisions: Date:

Key Plan

Upgrade Server Room and Site Communication Infrastructure

11301 WILSHIRE BOULEVARD,

WEST LOS ANGELES, CA 90073

691-20-152FINAL CONSTRUCTION

DOCUMENTS

JULY 13, 2021 PM EW/JB

FULLY SPRINKLERED

A

GENERAL NOTES

ARCHITECT/ENGINEER OF RECORD

C

D

17075 Via Del Campo, San Diego, CA 92127

Phone: 858.946.0333

20801.11 20-SCE-06

GENERAL NOTE

FIRE PROTECTION

1. DO NOT MAKE ANY ATTACHMENTS OR MODIFICATIONS TO

ANY FIREPROOFED COMPONENTS.

SYMBOLS LIST

2 HOUR FIRE BARRIER

1 HOUR FIRE BARRIER

2 HOUR FIRE/SMOKE BARRIER

SMOKE BARRIER

SMOKE PARTITION

1 HOUR FIRE/SMOKE BARRIER

3 HOUR FIRE BARRIER

0' 2' 4' 12'

SCALE: 1/4" = 1'-0"

KEY NOTES

120VAC

J

J

J

J

J

SCALE: 1/4" = 1' - 0"

NORTH

W.304.E-401

0' 2' 4' 12'

SCALE: 1/4" = 1'-0"

TR ROOM

2-2

Project Number

Campus / Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

A

F i t h

U.S. Department of Veterans Affairs

B

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Project Director

Revisions: Date:

Upgrade Server Room and Site Communication Infrastructure

11301 WILSHIRE BOULEVARD,

WEST LOS ANGELES, CA 90073

691-20-152FINAL CONSTRUCTION

DOCUMENTS

JULY 13, 2021 PM EW/JB

FULLY SPRINKLERED

A

GENERAL NOTES

ARCHITECT/ENGINEER OF RECORD

C

D

17075 Via Del Campo, San Diego, CA 92127

Phone: 858.946.0333

20801.11 20-SCE-06

GENERAL NOTE

FIRE PROTECTION

1. DO NOT MAKE ANY ATTACHMENTS OR MODIFICATIONS TO

ANY FIREPROOFED COMPONENTS.

SYMBOLS LIST

2 HOUR FIRE BARRIER

1 HOUR FIRE BARRIER

2 HOUR FIRE/SMOKE BARRIER

SMOKE BARRIER

SMOKE PARTITION

1 HOUR FIRE/SMOKE BARRIER

3 HOUR FIRE BARRIER

KEY NOTES

SCALE: 1/4" = 1' - 0"

NORTH

TR ROOM

2-106B

SCALE: 1/4" = 1' - 0"

NORTH

TR ROOM

3-223A

SCALE: 1/4" = 1' - 0"

NORTH

TR ROOM

NEW HIRSCH ACCESS CONTROL PANEL.

NEW PIV READER. SEE E-503 FOR CONDUIT

REQUIREMENT.

3/4''C- 2 #12 + 1 #12EG

CONNECT TO EXISTING CIRCUIT IN TR ROOM.

TO HIRSCH ACCESS CONTROL PANEL. SEE

KEYNOTE 1 & ACCESS CONTROL RISER

DIAGRAM ON T-600 SERIES DRAWING.

1.

120VAC

J

W.305.E-401

ELECTRICAL ENLARGED PLAN -

TR ROOM LADIES LOUNGE

0' 2' 4' 12'

SCALE: 1/4" = 1'-0"

Project Number

Campus / Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

A

F i t h U.S. Department of Veterans Affairs

B

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Project Director

Revisions: Date:

Key Plan

Upgrade Server Room and Site Communication Infrastructure

11301 WILSHIRE BOULEVARD,

WEST LOS ANGELES, CA 90073

691-20-152FINAL CONSTRUCTION

DOCUMENTS

JULY 13, 2021 PM EW/JB

FULLY SPRINKLERED

A

GENERAL NOTES

ARCHITECT/ENGINEER OF RECORD

C

D

17075 Via Del Campo, San Diego, CA 92127

Phone: 858.946.0333

20801.11 20-SCE-06

GENERAL NOTE

FIRE PROTECTION

1. DO NOT MAKE ANY ATTACHMENTS OR MODIFICATIONS TO

ANY FIREPROOFED COMPONENTS.

SYMBOLS LIST

2 HOUR FIRE BARRIER

1 HOUR FIRE BARRIER

2 HOUR FIRE/SMOKE BARRIER

SMOKE BARRIER

SMOKE PARTITION

1 HOUR FIRE/SMOKE BARRIER

3 HOUR FIRE BARRIER

SCALE: 1/4" = 1' - 0"

NORTH

KEY NOTES

NEW HIRSCH ACCESS CONTROL PANEL.

NEW PIV READER. SEE E-503 FOR CONDUIT

REQUIREMENT.

3/4''C- 2 #12 + 1 #12EG

CONNECT TO EXISTING CIRCUIT IN TR ROOM.

TO HIRSCH ACCESS CONTROL PANEL. SEE

KEYNOTE 1 & ACCESS CONTROL RISER

DIAGRAM ON T-600 SERIES DRAWING.

1.

120VAC

J

SCALE: 1/4" = 1' - 0"

NORTH

W.306.E-401

ELECTRICAL ENLARGED PLAN -

TR ROOM

0' 2' 4' 12'

SCALE: 1/4" = 1'-0"

TR ROOM

Project Number

Campus / Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

A

F i t h

U.S. Department of Veterans Affairs

B

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Project Director

Revisions: Date:

Upgrade Server Room and Site Communication Infrastructure

11301 WILSHIRE BOULEVARD,

WEST LOS ANGELES, CA 90073

691-20-152FINAL CONSTRUCTION

DOCUMENTS

JULY 13, 2021 PM EW/JB

FULLY SPRINKLERED

A

GENERAL NOTES

ARCHITECT/ENGINEER OF RECORD

C

D

17075 Via Del Campo, San Diego, CA 92127

Phone: 858.946.0333

20801.11 20-SCE-06

GENERAL NOTE

FIRE PROTECTION

1. DO NOT MAKE ANY ATTACHMENTS OR MODIFICATIONS TO

ANY FIREPROOFED COMPONENTS.

SYMBOLS LIST

2 HOUR FIRE BARRIER

1 HOUR FIRE BARRIER

2 HOUR FIRE/SMOKE BARRIER

SMOKE BARRIER

SMOKE PARTITION

1 HOUR FIRE/SMOKE BARRIER

3 HOUR FIRE BARRIER

KEY NOTES

NEW HIRSCH ACCESS CONTROL PANEL.

NEW PIV READER. SEE E-503 FOR CONDUIT

REQUIREMENT.

3/4''C- 2 #12 + 1 #12EG

CONNECT TO EXISTING CIRCUIT IN TR ROOM.

TO HIRSCH ACCESS CONTROL PANEL. SEE

KEYNOTE 1 & ACCESS CONTROL RISER

DIAGRAM ON T-600 SERIES DRAWING.

1.

120VAC

J5

SCALE: 1/4" = 1' - 0"

NORTH

W.337.E-401

ELECTRICAL ENLARGED PLAN -

TR ROOM C1-5

0' 2' 4' 12'

SCALE: 1/4" = 1'-0"

Project Number

Campus / Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

A

F i t h U.S. Department of Veterans Affairs

B

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Project Director

Revisions: Date:

Upgrade Server Room and Site Communication Infrastructure

11301 WILSHIRE BOULEVARD,

WEST LOS ANGELES, CA 90073

691-20-152FINAL CONSTRUCTION

DOCUMENTS

JULY 13, 2021 PM EW/JB

FULLY SPRINKLERED

A

GENERAL NOTES

ARCHITECT/ENGINEER OF RECORD

C

D

17075 Via Del Campo, San Diego, CA 92127

Phone: 858.946.0333

20801.11 20-SCE-06

GENERAL NOTE

FIRE PROTECTION

1. DO NOT MAKE ANY ATTACHMENTS OR MODIFICATIONS TO

ANY FIREPROOFED COMPONENTS.

SYMBOLS LIST

2 HOUR FIRE BARRIER

1 HOUR FIRE BARRIER

2 HOUR FIRE/SMOKE BARRIER

SMOKE BARRIER

SMOKE PARTITION

1 HOUR FIRE/SMOKE BARRIER

3 HOUR FIRE BARRIER

TR ROOM

C1-5

KEY NOTES

NEW HIRSCH ACCESS CONTROL PANEL.

NEW PIV READER. SEE E-503 FOR CONDUIT

REQUIREMENT.

3/4''C- 2 #12 + 1 #12EG

CONNECT TO EXISTING CIRCUIT IN TR ROOM.

TO HIRSCH ACCESS CONTROL PANEL. SEE

KEYNOTE 1 & ACCESS CONTROL RISER

DIAGRAM ON T-600 SERIES DRAWING.

1.

1LM-28

120VAC

J

SCALE: 1/4" = 1' - 0"

NORTH

W.345.E-401

ELECTRICAL ENLARGED PLAN -

TR ROOM 29 AND 39A

0' 2' 4' 12'

SCALE: 1/4" = 1'-0"

TR ROOM

Project Number

Campus / Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

A

F i t h U.S. Department of Veterans Affairs

B

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Project Director

Revisions: Date:

Key Plan

Upgrade Server Room and Site Communication Infrastructure

11301 WILSHIRE BOULEVARD,

WEST LOS ANGELES, CA 90073

691-20-152FINAL CONSTRUCTION

DOCUMENTS

JULY 13, 2021 PM EW/JB

FULLY SPRINKLERED

A

GENERAL NOTES

ARCHITECT/ENGINEER OF RECORD

C

D

17075 Via Del Campo, San Diego, CA 92127

Phone: 858.946.0333

20801.11 20-SCE-06

GENERAL NOTE

FIRE PROTECTION

1. DO NOT MAKE ANY ATTACHMENTS OR MODIFICATIONS TO

ANY FIREPROOFED COMPONENTS.

SYMBOLS LIST

2 HOUR FIRE BARRIER

1 HOUR FIRE BARRIER

2 HOUR FIRE/SMOKE BARRIER

SMOKE BARRIER

SMOKE PARTITION

1 HOUR FIRE/SMOKE BARRIER

3 HOUR FIRE BARRIER

KEY NOTES

SCALE: 1/4" = 1' - 0"

NORTH

TR ROOM

39A

NEW HIRSCH ACCESS CONTROL PANEL.

NEW PIV READER. SEE E-503 FOR CONDUIT

REQUIREMENT.

3/4''C- 2 #12 + 1 #12EG

CONNECT TO EXISTING CIRCUIT IN TR ROOM.

TO HIRSCH ACCESS CONTROL PANEL. SEE

KEYNOTE 1 & ACCESS CONTROL RISER

DIAGRAM ON T-600 SERIES DRAWING.

1.

J

J

SCALE: 1/4" = 1' - 0"

NORTH

W.401.E-401

Project Number

Campus / Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

A

F i t h U.S. Department of Veterans Affairs

B

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Project Director

Revisions: Date:

Upgrade Server Room and Site Communication Infrastructure

11301 WILSHIRE BOULEVARD,

WEST LOS ANGELES, CA 90073

691-20-152FINAL CONSTRUCTION

DOCUMENTS

JULY 13, 2021 PM EW/JB

FULLY SPRINKLERED

A

GENERAL NOTES

ARCHITECT/ENGINEER OF RECORD

C

D

17075 Via Del Campo, San Diego, CA 92127

Phone: 858.946.0333

20801.11 20-SCE-06

GENERAL NOTE

FIRE PROTECTION

1. DO NOT MAKE ANY ATTACHMENTS OR MODIFICATIONS TO

ANY FIREPROOFED COMPONENTS.

SYMBOLS LIST

2 HOUR FIRE BARRIER

1 HOUR FIRE BARRIER

2 HOUR FIRE/SMOKE BARRIER

SMOKE BARRIER

SMOKE PARTITION

1 HOUR FIRE/SMOKE BARRIER

3 HOUR FIRE BARRIER

0' 2' 4' 12'

SCALE: 1/4" = 1'-0"

SCALE: 1/4" = 1' - 0"

NORTH

TR ROOM

TR ROOM

KEY NOTES

NEW HIRSCH ACCESS CONTROL PANEL.

NEW PIV READER. SEE E-503 FOR CONDUIT

REQUIREMENT.

3/4''C- 2 #12 + 1 #12EG

CONNECT TO EXISTING CIRCUIT IN TR ROOM.

TO HIRSCH ACCESS CONTROL PANEL. SEE

KEYNOTE 1 & ACCESS CONTROL RISER

DIAGRAM ON T-600 SERIES DRAWING.

1.

2.

A239

A100G

J 64

J 6

W.402.E-401

Project Number

Campus / Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

A

F i t h U.S. Department of Veterans Affairs

B

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Project Director

Revisions: Date:

Key Plan

Upgrade Server Room and Site Communication Infrastructure

11301 WILSHIRE BOULEVARD,

WEST LOS ANGELES, CA 90073

691-20-152FINAL CONSTRUCTION

DOCUMENTS

JULY 13, 2021 PM EW/JB

FULLY SPRINKLERED

A

GENERAL NOTES

ARCHITECT/ENGINEER OF RECORD

C

D

17075 Via Del Campo, San Diego, CA 92127

Phone: 858.946.0333

20801.11 20-SCE-06

GENERAL NOTE

FIRE PROTECTION

1. DO NOT MAKE ANY ATTACHMENTS OR MODIFICATIONS TO

ANY FIREPROOFED COMPONENTS.

SYMBOLS LIST

2 HOUR FIRE BARRIER

1 HOUR FIRE BARRIER

2 HOUR FIRE/SMOKE BARRIER

SMOKE BARRIER

SMOKE PARTITION

1 HOUR FIRE/SMOKE BARRIER

3 HOUR FIRE BARRIER

0' 2' 4' 12'

SCALE: 1/4" = 1'-0"

KEY NOTES

NEW HIRSCH ACCESS CONTROL PANEL.

NEW PIV READER. SEE E-503 FOR CONDUIT

REQUIREMENT.

3/4''C- 2 #12 + 1 #12EG

CONNECT TO EXISTING CIRCUIT IN TR ROOM.

TO HIRSCH ACCESS CONTROL PANEL. SEE

KEYNOTE 1 & ACCESS CONTROL RISER

DIAGRAM ON T-600 SERIES DRAWING.

NEW J-BOX ABOVE DOOR. SEE DETAIL 7

DRAWING 503.

SCALE: 1/4" = 1' - 0"

NORTH

TR ROOM

SCALE: 1/4" = 1' - 0"

NORTH

TR ROOM

1.

2.

RAMP UP

(EX)

GCR3

(EX)

GCR

(EX)

GXE-A

(EX)

GXE-B

(EX)

GXE A

(EX)

GXE UPS2

(EX)

GXE-B

DATA RACK

TO REMAIN

SECURITY

PANEL TO

REMIAN

6 5.1 5 4.2 4.1 4 3 2.1

K

X.G

X.H

L

X.J

X.K

L.1

M

N

N.1

SCALE: 1/4" = 1' - 0"

NORTH

W.500.E-401

Project Number

Campus / Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

A

F i t h

U.S. Department of Veterans Affairs

B

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Project Director

Revisions: Date:

Key Plan

Upgrade Server Room and Site Communication Infrastructure

11301 WILSHIRE BOULEVARD,

WEST LOS ANGELES, CA 90073

691-20-152FINAL CONSTRUCTION

DOCUMENTS

JULY 13, 2021 PM EW/JB

FULLY SPRINKLERED

A

GENERAL NOTES

KEY NOTES

ARCHITECT/ENGINEER OF RECORD

C

D

17075 Via Del Campo, San Diego, CA 92127

Phone: 858.946.0333

20801.11 20-SCE-06

GENERAL NOTE

FIRE PROTECTION

1. DO NOT MAKE ANY ATTACHMENTS OR MODIFICATIONS TO

ANY FIREPROOFED COMPONENTS.

SYMBOLS LIST

2 HOUR FIRE BARRIER

1 HOUR FIRE BARRIER

2 HOUR FIRE/SMOKE BARRIER

SMOKE BARRIER

SMOKE PARTITION

1 HOUR FIRE/SMOKE BARRIER

3 HOUR FIRE BARRIER

0' 2' 4' 8'

SCALE: 1/4" = 1'-0"

EXISTING 80KVA UPS WITH BATTERY CABINETS TO

BE DISCONNECTED AND REMOVED AFTER NEW UPS

AND MCR IS COMMISSIONED.

EXISTING ELECTRICAL PANEL TO BE

DISCONNECTED AND REMOVED AFTER NEW UPS

AND MCR IS COMMISSIONED. REMOVE CIRCUIT

BREAKERS FROM EACH PANEL & TURN IT OVER

TO VA ELECTRICAL SHOP BEFORE DISPOSING

OFF PANEL.

EXISTING POWER (RECEPTACLES) TO IT RACKES TO

BE DISCONNECTED AND REMOVED AFTER NEW UPS

AND MCR IS COMMISSIONED. REMOVE EXISTING

BRANCH CIRCUIT ALL THE WAY TO ELECTRICAL

PANEL.

EXISTING POWER (RECEPTACLES) TO SERVER

CABINET TO BE DISCONNECTED AND REMOVED

AFTER NEW UPS AND MCR IS COMMISSIONED.

REMOVE EXISTING BRANCH CIRCUIT ALL THE WAY

TO ELECTRICAL PANEL.

ALL EXISTING ACTIVE EQUIPMENT SUCH AS

CISCO SWITCHES, SERVER, FIBER PATCH PANEL

WILL BE REMOVED/RELOCATED BY VA/OIT

DEPARTMENT.

ALL PATCH PANEL TO BE REMOVED OFFSITE BY IT

CABLING CONTRACTOR.

1.

2.

SCALE: NO SCALE

SCALE: NO SCALE

ELECTRICAL PANELS TO BE REMOVED

SCALE: NO SCALE

ELECTRICAL PANEL/ CONDUIT/ SO CORD

TO BE REMOVED

SCALE: NO SCALE

ELECTRICAL PANELS TO BE REMOVED

SCALE: NO SCALE

ELECTRICAL PANEL & SO CORD TO

RACKS TO BE REMOVED

SCALE: NO SCALE

TYPE SO CORDS TO DATA RACK TO BE

REMOVED

DN

5.1 5 4.2 4.1 4 3 2.1 2

K

X.G

X.H

L

X.J

X.K

L.1

M

N

N.1

SCALE: 1/4" = 1' - 0" NORTH

W.500.E-402

Project Number

Campus / Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

A

F i t h

U.S. Department of Veterans Affairs

B

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Project Director

Revisions: Date:

Upgrade Server Room and Site Communication Infrastructure

11301 WILSHIRE BOULEVARD,

WEST LOS ANGELES, CA 90073

691-20-152FINAL CONSTRUCTION

DOCUMENTS

JULY 13, 2021 PM EW/JB

FULLY SPRINKLERED

A

GENERAL NOTES

KEY NOTES

ARCHITECT/ENGINEER OF RECORD

C

D

17075 Via Del Campo, San Diego, CA 92127

Phone: 858.946.0333

20801.11 20-SCE-06

GENERAL NOTE

FIRE PROTECTION

1. DO NOT MAKE ANY ATTACHMENTS OR MODIFICATIONS TO

ANY FIREPROOFED COMPONENTS.

SYMBOLS LIST

2 HOUR FIRE BARRIER

1 HOUR FIRE BARRIER

2 HOUR FIRE/SMOKE BARRIER

SMOKE BARRIER

SMOKE PARTITION

1 HOUR FIRE/SMOKE BARRIER

3 HOUR FIRE BARRIER

0' 2' 4' 8'

SCALE: 1/4" = 1'-0"

EXISTING FIXTURES (LOWER CEILING) TO BE DISCONNECTED

AND REMOVED. REMOVE EXISTING CIRCUIT ALL THE WAY TO

SOURCE PANEL.

EXISTING FIXTURES (HIGH BAY) TO BE DISCONNECTED AND

REMOVED. REMOVE CIRCUIT WIRE AND WIREWAY TO THE

CLOSEST HOMERUN J-BOX. ALL ASSOCIATED UNISTRUT

SUPPORT AND WIREWAY TO BE REMOVED. SEE PHOTO A.

INDICATES EXISTING CIRCUIT GLD1-19 AND SWITCH LEG “h”.

INDICATES EXISTING CIRCUIT GLD1-3 AND SWITCH LEG “g”.

WIREWAY WITH CIRCUIT GLD1-19 TO BE REMOVED.

WIREWAY WITH CIRCUIT GLD1-3 TO BE REMOVED.

EXISTING FIXTURES TO REMAIN AND RECONNECTED TO

CLOSEST EXISTING CIRCUIT GLD1-3g.

EXISTING FIXTURE TO REMAIN.

EXISTING LIGHT SWITCH Sg AND Sh TO REMAIN OPERATIVE.

REWIRE AS NECESSARY TO KEEP ACTIVE FIXTURES (TO

REMAIN) ON SWITCH LEG g AND h.

SCALE: NONE

GENERAL NOTES FOR PHOTO A

KEY NOTES FOR PHOTO A

DOWN STREAM FIXTURE TO BE RECONNECTED SO CIRCUITS TO

REMAINING FIXTURE IS RE-STORED.

A TYPICAL FIXTURE TO BE DISCONNECTED AND REMOVED IN THE

AREA SHOWN IN DETAIL 1 .

TYPICAL UNISTRUT SUPPORT TO BE REMOVED IN AREA

SHOWN.

TYPICAL WIRE GUTTER TO BE REMOVED ALONG WITH BRANCH

CIRCUIT WIRE IN AREA SHOWN.

B

C

C

A

B

DN

6 5.1 5 4.2 4.1 4 3 2.1

K

X.G

X.H

L

X.J

X.K

L.1

M

N

N.1

SCALE: 1/4" = 1' - 0" NORTH

W.500.E-403

Project Number

Campus / Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

A

F i t h

U.S. Department of Veterans Affairs

B

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Project Director

Revisions: Date:

Key Plan

Upgrade Server Room and Site Communication Infrastructure

11301 WILSHIRE BOULEVARD,

WEST LOS ANGELES, CA 90073

691-20-152FINAL CONSTRUCTION

DOCUMENTS

JULY 13, 2021 PM EW/JB

FULLY SPRINKLERED

A

GENERAL NOTES

KEY NOTES

ARCHITECT/ENGINEER OF RECORD

C

D

17075 Via Del Campo, San Diego, CA 92127

Phone: 858.946.0333

20801.11 20-SCE-06

GENERAL NOTE

FIRE PROTECTION

1. DO NOT MAKE ANY ATTACHMENTS OR MODIFICATIONS TO

ANY FIREPROOFED COMPONENTS.

SYMBOLS LIST

2 HOUR FIRE BARRIER

1 HOUR FIRE BARRIER

2 HOUR FIRE/SMOKE BARRIER

SMOKE BARRIER

SMOKE PARTITION

1 HOUR FIRE/SMOKE BARRIER

3 HOUR FIRE BARRIER

0' 2' 4' 8'

SCALE: 1/4" = 1'-0"

EXISTING TWO STACKED CABLE TRAY TO BE REMOVED AFTER

ALL EXISTING COPPER, FIBER & POWER CABLES HAVE BEEN

REMOVED ONCE NEW MCR IS COMMISSIONED.

MBC(BATTERY)(UPS)

EXISTING

SLAB

PDU

DN

C R

C

U

N I T

DATA RACK

TO REMAIN

(CCTV)

SECURITY

PANEL

TO

REMIAN

C R

I T

U P

S

A

B A

T

P D

U

COLUMN

HDAHDA

HDAHDA

HDA HDA

C R

I T

C R

I T

RPMCRE-1

RPMCRE-3

RPMCRE-3

RPMCRE-3

RPMCRE-3

RPMCRE-1

UST 2

UST 3

UST 2

UST 3

MBC

U P

S

B

B A

T

P D

U

A-1

A-2A-3A-4A-5A-6A-7A-8A-9A-10A-11

A-12

B-1

B-2B-3B-4B-5B-6B-7B-8B-9B-10B-11

B-12

C-1C-2C-3C-4C-5C-6C-7C-8C-9C-10C-11

PB PB

FUTURE

BATTERY

CABINET

MBC

FUTURE

BATTERY

CABINET

RPMCRE-7

RPMCRE-5

6 4

URPMCRA-2,4,6

URPMCREA-5

URPMCRA-9

NEW HIRSCH PANEL FOR

TR ROOM SW RISER

3/4''C- 2 #12 + 1

#12EG

3/4''C- 2 #12 +

1 # 12 EG

RPMCRA-14,16,18

RPMCRA-8,10,12

EDBMCR-B-3

EDBMCR-A-3EDBMCR-A-3

EDBMCR-B-1

RPMCRE-8

0240C

MCR

0240D

NEW UPS ROOM

0240B

OIT

OFFICE

OIT OFFICE

ELECTRICAL

ROOM

OFFICE SUPPLY

WAREHOUSE

0262B

SPD

WAREHOUSE

0262E

MATERIALS

MANAGMENT

WAREHOUSE

VIEWVING

ROOM

0243A

MATERIALS

MANAGMENT

OFFICE

(LOGISTICS)

MATERIALS

MANAGMENT

OFFICE

(LOGISTICS)

0243B

URPMCRB-5

URPMCR A-11

URPMCRA-15

URPMCRB-1

URPMCRB-3

URPMCRA-13

URPMCRA-17

URPMCRB-7

URPMCRA-11

URPMCRA-11

URPMCRB-7

URPMCRB-4

URPMCRB-2

RPMCRE-10,12

RPMCRE-5

RPMCRE-9

RPMCRE-7

RPMCRE-5RPMCRE-9

T

6 5.1 5 4.2 4.1 4 3 2.1

K

X.G

X.H

L

X.J

X.K

L.1

M

N

N.1

W.500.E-404

SCALE: 1/2'' = 1'-0''

NEW 800A 480/277V ATS WITH BYPASS 4 POLE SYSTEM A.

NEW 800A 480/277V ATS WITH MANUAL BYPASS 4 POLE

SYSTEM B.

NEW 800A 480/277V EMERGENCY DISTRIBUTION BOARD

SYSTEM A EDBMCR-A.

NEW 800A 480/277V EMERGENCY DISTRIBUTION BOARD

SYSTEM B EDBMCR-B.

NEW 225A 480/277V EMERGENCY PANEL LMCRE.

NEW 75KVA 480-208/120V TRANSFORMER T-RPMCRE.

NEW 225A 208/120V EMERGENCY PANEL RPMCRE.

NEW 4 POST IT RACKS.

NEW SERVER CABINETS CHATSWORTH CAT#

FFIN-IICC-E72B. WITH EXHAUST RISER.

NEW 150 KVA 480V IN, 480V OUT UPS WITH BATTERY

CABINET SYSTEM A. (LITHIUM ION BATTERY)

NEW 150 KVA 480V IN, 480V OUT UPS WITH BATTERY

CABINET SYSTEM B. (LITHIUM ION BATTERY)

PLUG IN BUS DUCT SYSTEM A 200A 208/120V 3P 4W.

(STARLINE OR EQUAL).

PLUG IN BUS DUCT SYSTEM B 200A 208/120 3P 4W.

(STARLINE OR EQUAL).

TELECOMMUNICATIONS MAIN GROUND BUS. SEE DETAILS

ON E-501.

SERVER CABINET ROW SIGN ''A''.

SERVER CABINET ROW SIGN ''B''.

MDA DATA RACKS ROW SIGN ''C''.

3/4''C - 3 #12 H + 3 #12 N + 1 #12 EG.

UPS SYSTEM A PANEL URPMCRA 100A 208/120.

UPS SYSTEM B PANEL URPMCRB 100A 208/120.

NEW FIRE RATED TELEPHONE BACKBOARD 8'-0" HIGH. DO

NOT PAINT.

NEW HIRSCH ACCESS CONTROL PANEL.

NEW PIV READER. SEE E-503 FOR CONDUIT

REQUIREMENTS.

NEW 3/4''C- 2 # 12 + 1 # 12 EG.

TO NEW HIRSCH ACCESS CONTROL PANEL IN TR

ROOM SHOWN ON T-616 RISER DIAGRAM.

NEW J-BOX ABOVE DOOR SEE DETAIL 7 DRAWING

E-503.

NEW 3/4''C W/ PULL STRING BY ELECTRICAL

CONTRACTOR (INSTALLED ABOVE CEILING)

DOOR CONTROL CABLE BY SECURITY

CONTRACTOR.

NEW 100A/3P 480V DISCONNECT.

NEW 1 1/ 4''C- 3 # 2 + 1 #8EG.

NEW 3/ 4''C - 3 # 2 + 1 #12EG.

NEW 30A/3P DISCONNECT.

SCALE: 1/4" = 1' - 0" NORTH

0' 2' 4' 8'

SCALE: 1/4" = 1'-0"

Project Number

Campus / Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

A

F i t h U.S. Department of Veterans Affairs

B

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Project Director

Revisions: Date:

Upgrade Server Room and Site Communication Infrastructure

11301 WILSHIRE BOULEVARD,

WEST LOS ANGELES, CA 90073

691-20-152FINAL CONSTRUCTION

DOCUMENTS

JULY 13, 2021 PM EW/JB

FULLY SPRINKLERED

A

GENERAL NOTES

ARCHITECT/ENGINEER OF RECORD

C

D

17075 Via Del Campo, San Diego, CA 92127

Phone: 858.946.0333

20801.11 20-SCE-06

GENERAL NOTE

FIRE PROTECTION

1. DO NOT MAKE ANY ATTACHMENTS OR MODIFICATIONS TO

ANY FIREPROOFED COMPONENTS.

SYMBOLS LIST

2 HOUR FIRE BARRIER

1 HOUR FIRE BARRIER

2 HOUR FIRE/SMOKE BARRIER

SMOKE BARRIER

SMOKE PARTITION

1 HOUR FIRE/SMOKE BARRIER

3 HOUR FIRE BARRIER

KEY NOTES

MAIN GROUND BUS. CONNECT TO

BUILDING GROUND BUS/ROD AT

UST 2 AND UST 3 ON BASEMENT

LEVEL. USE 1 # 4/0 BARE COPPER

CONDUCTOR. SEE DETAIL PN

E-502.

FOR SINGLE LINE SEE E-600 SERIES DRAWINGS.

FOR PANEL SCHEDULE SEE E-800 SERIES

DRAWINGS.

FOR PANEL LOCATION SEE. RESPECTIVE

OVERALL FLOOR PLAN.

ALL EXISTING LIGHTING FIXTURES TO BE

REMOVED AND REPLACED WITH NEW PER PLANS.

EXISTING CIRCUIT REPLACE EXISTING SWITCH

WITH WALL MOUNTED OCCUPANCY SENSOR TO

BE REUSED AND EXTEND TO NEW LIGHTS.

CONNECT NEW SMOKE DETECTOR TO EXISTING

FA SYSTEM.

CONTRACTOR SHALL TRACE EXISTING

RECEPTACLE IN EACH TR ROOM TO PANEL &

CIRCUIT NUMBER. INSTALL NEW SS COVER WITH

ENGRAVED GEN PANEL/ CIRCUIT NUMBER.

PROVIDE 120VAC TO NEW DDC I/O PANEL FROM

EXISTING 120VAC RECEPTACLE CIRCUIT IN TR.

COORDINATE WITH MECHANICAL CONTRACTOR

ON THE EXACT LOCATION OF DDC I/O PANEL.

1.

2.

3.

4.

5.

6.

7.

MCR

NEW UPS

ROOM

COLUMN

LMCRE-5

a b a b a b a

LMCRE-1

LMCRE-5

b

LMCRE-1

LMCRE-3

LMCRE-5

LMCRE-5

LMCRE-5

LMCRE-5

0240C

MCR

OIT OFFICE

0240A

ELECTRICAL

ROOM

0262B

SPD

WAREHOUSE

0262E

MATERIALS

MANAGMENT

WAREHOUSE

VIEWVING

ROOM

0243A

MATERIALS

MANAGMENT

OFFICE

(LOGISTICS)

MATERIALS

MANAGMENT

OFFICE

(LOGISTICS)

0243B

LMCRE-5

LMCRE-3

LMCRE-5

LMCRE-7

LMCRE-5

LMCRE-5

LMCRE-5

LMCRE-5

LMCRE-5

LMCRE-5

LMCRE-5

0240B

OIT

OFFICE

OFFICE SUPPLY

WAREHOUSE

6 5.1 5 4.2 4.1 4 3 2.1

K

X.G

X.H

L

X.J

X.K

L.1

M

N

N.1

W.500.E-405

SCALE: 1/4" = 1' - 0" NORTH

0' 2' 4' 8'

SCALE: 1/4" = 1'-0"

Project Number

Campus / Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

A

F i t h

U.S. Department of Veterans Affairs

B

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Project Director

Revisions: Date:

Key Plan

Upgrade Server Room and Site Communication Infrastructure

11301 WILSHIRE BOULEVARD,

WEST LOS ANGELES, CA 90073

691-20-152FINAL CONSTRUCTION

DOCUMENTS

JULY 13, 2021 PM EW/JB

FULLY SPRINKLERED

A

GENERAL NOTES

KEY NOTES

ARCHITECT/ENGINEER OF RECORD

C

D

17075 Via Del Campo, San Diego, CA 92127

Phone: 858.946.0333

20801.11 20-SCE-06

GENERAL NOTE

FIRE PROTECTION

1. DO NOT MAKE ANY ATTACHMENTS OR MODIFICATIONS TO

ANY FIREPROOFED COMPONENTS.

SYMBOLS LIST

2 HOUR FIRE BARRIER

1 HOUR FIRE BARRIER

2 HOUR FIRE/SMOKE BARRIER

SMOKE BARRIER

SMOKE PARTITION

1 HOUR FIRE/SMOKE BARRIER

3 HOUR FIRE BARRIER

NEW EMERGENCY PANEL LMCRE 225A 480/277V

COLUMN

CT WALL SUPPORT

BRACK (TYP)

0240C

MCR

OIT OFFICE

0240A

ELECTRICAL

ROOM

0262B

SPD

WAREHOUSE

0262E

MATERIALS

MANAGMENT

WAREHOUSE

VIEWVING

ROOM

0243A

MATERIALS

MANAGMENT

OFFICE

(LOGISTICS)

MATERIALS

MANAGMENT

OFFICE

(LOGISTICS)

0243B

CABLE RISES TO INTERSTITIAL

LEVEL CABLE TRAY

0240B

OIT

OFFICE

OFFICE SUPPLY

WAREHOUSE

6 5.1 5 4.2 4.1 4 3 2.1

K

X.G

X.H

L

X.J

X.K

L.1

M

N

N.1

W.500.E-406

0' 2' 4' 8'

SCALE: 1/4" = 1'-0"

Project Number

Campus / Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

A

F i t h

U.S. Department of Veterans Affairs

B

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Project Director

Revisions: Date:

Upgrade Server Room and Site Communication Infrastructure

11301 WILSHIRE BOULEVARD,

WEST LOS ANGELES, CA 90073

691-20-152FINAL CONSTRUCTION

DOCUMENTS

JULY 13, 2021 PM EW/JB

FULLY SPRINKLERED

A

GENERAL NOTES

KEY NOTES

ARCHITECT/ENGINEER OF RECORD

C

D

17075 Via Del Campo, San Diego, CA 92127

Phone: 858.946.0333

20801.11 20-SCE-06

GENERAL NOTE

FIRE PROTECTION

1. DO NOT MAKE ANY ATTACHMENTS OR MODIFICATIONS TO

ANY FIREPROOFED COMPONENTS.

SYMBOLS LIST

2 HOUR FIRE BARRIER

1 HOUR FIRE BARRIER

2 HOUR FIRE/SMOKE BARRIER

SMOKE BARRIER

SMOKE PARTITION

1 HOUR FIRE/SMOKE BARRIER

3 HOUR FIRE BARRIER

SCALE: 1/4" = 1' - 0" NORTH

UPPER TIER NEW 18" X 6" BASKET TYPE CABLE

TRAY FOR PHILIPS MM(OM4) FIBER & LOWER

TIER FOR FIBER TO TR ROOMS UNDER ANOTHER

PROJECT.

TWO NEW 18" W X 6" BASKET TYPE CABLE

TRACK STACKED. LOWER STAYS IN MCR AND

OIT ROOM. UPPER CONNECTS TO CABLE TRAY

AT INTERSTITIAL LEVEL.

TWO 12''W X 6''H BASKET TYPE CABLE TRAY

STACKED & STAGGERED. SEE SECTION

DETAIL 1 T-505.

TWO 12''W X 6''H BASKET TYPE CABLE TRAY

STACKED.

18'' X 6''H BASKET CABLE TRAY 10'-0'' TO

BOTTOM.

FIRE RATED TELEPHONE BACKBOARD 8'-0'' HIGH.

GAE-14

120VAC

GAE-16

120VAC

120VAC

GBE-14

W.500.E-407

ELECTRICAL ENLARGED PLAN -

TR ROOM 10SJ, 10SO, 10SA, 10IN,

10IS

0' 2' 4' 12'

SCALE: 1/4" = 1'-0"

Project Number

Campus / Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

A

F i t h

U.S. Department of Veterans Affairs

B

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Project Director

Revisions: Date:

Key Plan

Upgrade Server Room and Site Communication Infrastructure

11301 WILSHIRE BOULEVARD,

WEST LOS ANGELES, CA 90073

691-20-152FINAL CONSTRUCTION

DOCUMENTS

JULY 13, 2021 PM EW/JB

FULLY SPRINKLERED

A

GENERAL NOTES

KEY NOTES

ARCHITECT/ENGINEER OF RECORD

C

D

17075 Via Del Campo, San Diego, CA 92127

Phone: 858.946.0333

20801.11 20-SCE-06

GENERAL NOTE

FIRE PROTECTION

1. DO NOT MAKE ANY ATTACHMENTS OR MODIFICATIONS TO

ANY FIREPROOFED COMPONENTS.

SYMBOLS LIST

2 HOUR FIRE BARRIER

1 HOUR FIRE BARRIER

2 HOUR FIRE/SMOKE BARRIER

SMOKE BARRIER

SMOKE PARTITION

1 HOUR FIRE/SMOKE BARRIER

3 HOUR FIRE BARRIER

NEW HIRSCH ACCESS CONTROL PANEL.

NEW PIV READER. SEE E-503 FOR CONDUIT

REQUIREMENTS.

NEW 3/4''C- 2 # 12 + 1 # 12 EG.

TO NEW HIRSCH ACCESS CONTROL PANEL IN

TR ROOM SHOWN ON T-616 RISER DIAGRAM.

NEW J-BOX ABOVE DOOR SEE DETAIL 7

DRAWING E-503.

NEW 3/4''C W/ PULL STRING BY ELECTRICAL

CONTRACTOR (INSTALLED ABOVE CEILING)

DOOR CONTROL CABLE BY SECURITY

CONTRACTOR.

SCALE: 1/4" = 1' - 0"

NORTH

ELECTRICAL

ENLARGED PLAN - ROOM 10SJ

SCALE: 1/4" = 1' - 0"

NORTH

ELECTRICAL

ENLARGED PLAN - ROOM 10SO

SCALE: 1/4" = 1' - 0"

NORTH

ELECTRICAL

ENLARGED PLAN - ROOM 10SA

SCALE: 1/4" = 1' - 0"

NORTH

ELECTRICAL

ENLARGED PLAN - ROOM 10IS

TR ROOM

10IS

SCALE: 1/4" = 1' - 0"

NORTH

ELECTRICAL

ENLARGED PLAN - ROOM 10IN

TR ROOM

10IN

TR ROOM

10 SJTR ROOM

10 SO

TR ROOM

10 SA

1.

STAIR

W.500.E-408

ELECTRICAL ENLARGED PLAN -

TR ROOM 11SH, 11SO, 11SN,

11SE, 11IN, 11IS

0' 2' 4' 12'

SCALE: 1/4" = 1'-0"

SCALE: 1/4" = 1' - 0"

NORTH

ELECTRICAL

ENLARGED PLAN - ROOM 11SH

Project Number

Campus / Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

A

F i t h

U.S. Department of Veterans Affairs

B

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Project Director

Revisions: Date:

Key Plan

Upgrade Server Room and Site Communication Infrastructure

11301 WILSHIRE BOULEVARD,

WEST LOS ANGELES, CA 90073

691-20-152FINAL CONSTRUCTION

DOCUMENTS

JULY 13, 2021 PM EW/JB

FULLY SPRINKLERED

A

GENERAL NOTES

KEY NOTES

ARCHITECT/ENGINEER OF RECORD

C

D

17075 Via Del Campo, San Diego, CA 92127

Phone: 858.946.0333

20801.11 20-SCE-06

GENERAL NOTE

FIRE PROTECTION

1. DO NOT MAKE ANY ATTACHMENTS OR MODIFICATIONS TO

ANY FIREPROOFED COMPONENTS.

SYMBOLS LIST

2 HOUR FIRE BARRIER

1 HOUR FIRE BARRIER

2 HOUR FIRE/SMOKE BARRIER

SMOKE BARRIER

SMOKE PARTITION

1 HOUR FIRE/SMOKE BARRIER

3 HOUR FIRE BARRIER

SCALE: 1/4" = 1' - 0"

NORTH

ELECTRICAL

ENLARGED PLAN - ROOM 11SO

SCALE: 1/4" = 1' - 0"

NORTH

ELECTRICAL

ENLARGED PLAN - ROOM 11SN

SCALE: 1/4" = 1' - 0"

NORTH

ELECTRICAL

ENLARGED PLAN - ROOM 11IS

TR ROOM

11IS

SCALE: 1/4" = 1' - 0"

NORTH

ELECTRICAL

ENLARGED PLAN - ROOM 11IN

TR ROOM

1444A

TR ROOM

1603A

TR ROOM

11 SO

TR ROOM

1444A

SCALE: 1/4" = 1' - 0"

NORTH

ELECTRICAL

ENLARGED PLAN - ROOM 11SE

TR ROOM

1.

NEW HIRSCH ACCESS CONTROL PANEL.

NEW PIV READER. SEE E-503 FOR CONDUIT

REQUIREMENTS.

NEW 3/4''C- 2 # 12 + 1 # 12 EG.

TO NEW HIRSCH ACCESS CONTROL PANEL IN

TR ROOM SHOWN ON T-616 RISER DIAGRAM.

NEW J-BOX ABOVE DOOR SEE DETAIL 7

DRAWING E-503.

NEW 3/4''C W/ PULL STRING BY ELECTRICAL

CONTRACTOR (INSTALLED ABOVE CEILING)

DOOR CONTROL CABLE BY SECURITY

CONTRACTOR.

STAIR

W.500.E-409

ELECTRICAL ENLARGED PLAN -

TR ROOM 12SE, 12SA, 12IN, 12IS

0' 2' 4' 12'

SCALE: 1/4" = 1'-0"

Project Number

Campus / Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

A

F i t h

U.S. Department of Veterans Affairs

B

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Project Director

Revisions: Date:

Key Plan

Upgrade Server Room and Site Communication Infrastructure

11301 WILSHIRE BOULEVARD,

WEST LOS ANGELES, CA 90073

691-20-152FINAL CONSTRUCTION

DOCUMENTS

JULY 13, 2021 PM EW/JB

FULLY SPRINKLERED

A

GENERAL NOTES

KEY NOTES

ARCHITECT/ENGINEER OF RECORD

C

D

17075 Via Del Campo, San Diego, CA 92127

Phone: 858.946.0333

20801.11 20-SCE-06

GENERAL NOTE

FIRE PROTECTION

1. DO NOT MAKE ANY ATTACHMENTS OR MODIFICATIONS TO

ANY FIREPROOFED COMPONENTS.

SYMBOLS LIST

2 HOUR FIRE BARRIER

1 HOUR FIRE BARRIER

2 HOUR FIRE/SMOKE BARRIER

SMOKE BARRIER

SMOKE PARTITION

1 HOUR FIRE/SMOKE BARRIER

3 HOUR FIRE BARRIER

SCALE: 1/4" = 1' - 0"

NORTH

ELECTRICAL

ENLARGED PLAN - ROOM 12IS

TR ROOM

12IS

SCALE: 1/4" = 1' - 0"

NORTH

ELECTRICAL

ENLARGED PLAN - ROOM 12IN

TR ROOM

12IN

SCALE: 1/4" = 1' - 0"

NORTH

ELECTRICAL

ENLARGED PLAN - ROOM 12SA

TR ROOM

12SA

SCALE: 1/4" = 1' - 0"

NORTH

ELECTRICAL

ENLARGED PLAN - ROOM 12SE

TR ROOM

12SE

1.

NEW HIRSCH ACCESS CONTROL PANEL.

NEW PIV READER. SEE E-503 FOR CONDUIT

REQUIREMENTS.

NEW 3/4''C- 2 # 12 + 1 # 12 EG.

TO NEW HIRSCH ACCESS CONTROL PANEL IN

TR ROOM SHOWN ON T-616 RISER DIAGRAM.

NEW J-BOX ABOVE DOOR SEE DETAIL 7

DRAWING E-503.

NEW 3/4''C W/ PULL STRING BY ELECTRICAL

CONTRACTOR (INSTALLED ABOVE CEILING)

DOOR CONTROL CABLE BY SECURITY

CONTRACTOR.

5 6

W.500.E-410

ELECTRICAL ENLARGED PLAN -

TR ROOM 13SE, 13SA, 13IN, 13IS

0' 2' 4' 12'

SCALE: 1/4" = 1'-0"

Project Number

Campus / Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

A

F i t h

U.S. Department of Veterans Affairs

B

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Project Director

Revisions: Date:

Key Plan

Upgrade Server Room and Site Communication Infrastructure

11301 WILSHIRE BOULEVARD,

WEST LOS ANGELES, CA 90073

691-20-152FINAL CONSTRUCTION

DOCUMENTS

JULY 13, 2021 PM EW/JB

FULLY SPRINKLERED

A

GENERAL NOTES

KEY NOTES

ARCHITECT/ENGINEER OF RECORD

C

D

17075 Via Del Campo, San Diego, CA 92127

Phone: 858.946.0333

20801.11 20-SCE-06

GENERAL NOTE

FIRE PROTECTION

1. DO NOT MAKE ANY ATTACHMENTS OR MODIFICATIONS TO

ANY FIREPROOFED COMPONENTS.

SYMBOLS LIST

2 HOUR FIRE BARRIER

1 HOUR FIRE BARRIER

2 HOUR FIRE/SMOKE BARRIER

SMOKE BARRIER

SMOKE PARTITION

1 HOUR FIRE/SMOKE BARRIER

3 HOUR FIRE BARRIER

SCALE: 1/4" = 1' - 0"

NORTH

ELECTRICAL

ENLARGED PLAN - ROOM 13IS

TR ROOM

13IS

SCALE: 1/4" = 1' - 0"

NORTH

ELECTRICAL

ENLARGED PLAN - ROOM 13IN

TR ROOM

13IN

SCALE: 1/4" = 1' - 0"

NORTH

ELECTRICAL

ENLARGED PLAN - ROOM 13SA

TR ROOM

13SA

SCALE: 1/4" = 1' - 0"

NORTH

ELECTRICAL

ENLARGED PLAN - ROOM 13SE

TR ROOM

13SE

1.

NEW HIRSCH ACCESS CONTROL PANEL.

NEW PIV READER. SEE E-503 FOR CONDUIT

REQUIREMENTS.

NEW 3/4''C- 2 # 12 + 1 # 12 EG.

TO NEW HIRSCH ACCESS CONTROL PANEL IN

TR ROOM SHOWN ON T-616 RISER DIAGRAM.

NEW J-BOX ABOVE DOOR SEE DETAIL 7

DRAWING E-503.

NEW 3/4''C W/ PULL STRING BY ELECTRICAL

CONTRACTOR (INSTALLED ABOVE CEILING)

DOOR CONTROL CABLE BY SECURITY

CONTRACTOR.

120VAC

4CE-25

120VAC

3 5

64AE-21

W.500.E-411

ELECTRICAL ENLARGED PLAN -

TR ROOM 14SE, 14SA, 14IN, 14IS

0' 2' 4' 12'

SCALE: 1/4" = 1'-0"

Project Number

Campus / Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

A

F i t h

U.S. Department of Veterans Affairs

B

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Project Director

Revisions: Date:

Key Plan

Upgrade Server Room and Site Communication Infrastructure

11301 WILSHIRE BOULEVARD,

WEST LOS ANGELES, CA 90073

691-20-152FINAL CONSTRUCTION

DOCUMENTS

JULY 13, 2021 PM EW/JB

FULLY SPRINKLERED

A

GENERAL NOTES

KEY NOTES

ARCHITECT/ENGINEER OF RECORD

C

D

17075 Via Del Campo, San Diego, CA 92127

Phone: 858.946.0333

20801.11 20-SCE-06

GENERAL NOTE

FIRE PROTECTION

1. DO NOT MAKE ANY ATTACHMENTS OR MODIFICATIONS TO

ANY FIREPROOFED COMPONENTS.

SYMBOLS LIST

2 HOUR FIRE BARRIER

1 HOUR FIRE BARRIER

2 HOUR FIRE/SMOKE BARRIER

SMOKE BARRIER

SMOKE PARTITION

1 HOUR FIRE/SMOKE BARRIER

3 HOUR FIRE BARRIER

SCALE: 1/4" = 1' - 0"

NORTH

ELECTRICAL

ENLARGED PLAN - ROOM 14IS

TR ROOM

14IS

SCALE: 1/4" = 1' - 0"

NORTH

ELECTRICAL

ENLARGED PLAN - ROOM 14IN

SCALE: 1/4" = 1' - 0"

NORTH

ELECTRICAL

ENLARGED PLAN - ROOM 14SA

TR ROOM

14SA

SCALE: 1/4" = 1' - 0"

NORTH

ELECTRICAL

ENLARGED PLAN - ROOM 14SE

TR ROOM

14SE

TR ROOM

14IN

1.

NEW HIRSCH ACCESS CONTROL PANEL.

NEW PIV READER. SEE E-503 FOR CONDUIT

REQUIREMENTS.

NEW 3/4''C- 2 # 12 + 1 # 12 EG.

TO NEW HIRSCH ACCESS CONTROL PANEL IN

TR ROOM SHOWN ON T-616 RISER DIAGRAM.

NEW J-BOX ABOVE DOOR SEE DETAIL 7

DRAWING E-503.

NEW 3/4''C W/ PULL STRING BY ELECTRICAL

CONTRACTOR (INSTALLED ABOVE CEILING)

DOOR CONTROL CABLE BY SECURITY

CONTRACTOR.

W.500.E-412

ELECTRICAL ENLARGED PLAN -

TR ROOM 15SE, 15SA, 15IN, 15IS

0' 2' 4' 12'

SCALE: 1/4" = 1'-0"

SCALE: 1/4" = 1' - 0"

NORTH

ELECTRICAL

ENLARGED PLAN - ROOM 15IS

TR ROOM

15IS

Project Number

Campus / Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

A

F i t h U.S. Department of Veterans Affairs

B

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Project Director

Revisions: Date:

Key Plan

Upgrade Server Room and Site Communication Infrastructure

11301 WILSHIRE BOULEVARD,

WEST LOS ANGELES, CA 90073

691-20-152FINAL CONSTRUCTION

DOCUMENTS

JULY 13, 2021 PM EW/JB

FULLY SPRINKLERED

A

GENERAL NOTES

KEY NOTES

ARCHITECT/ENGINEER OF RECORD

C

D

17075 Via Del Campo, San Diego, CA 92127

Phone: 858.946.0333

20801.11 20-SCE-06

GENERAL NOTE

FIRE PROTECTION

1. DO NOT MAKE ANY ATTACHMENTS OR MODIFICATIONS TO

ANY FIREPROOFED COMPONENTS.

SYMBOLS LIST

2 HOUR FIRE BARRIER

1 HOUR FIRE BARRIER

2 HOUR FIRE/SMOKE BARRIER

SMOKE BARRIER

SMOKE PARTITION

1 HOUR FIRE/SMOKE BARRIER

3 HOUR FIRE BARRIER

SCALE: 1/4" = 1' - 0"

NORTH

ELECTRICAL

ENLARGED PLAN - ROOM 15IN

TR ROOM

15IN

SCALE: 1/4" = 1' - 0"

NORTH

ELECTRICAL ENLARGED PLAN -

ROOM 15SA

TR ROOM

15SA

SCALE: 1/4" = 1' - 0"

NORTH

ELECTRICAL

ENLARGED PLAN - ROOM 15SE

TR ROOM

15SE

1.

NEW HIRSCH ACCESS CONTROL PANEL.

NEW PIV READER. SEE E-503 FOR CONDUIT

REQUIREMENTS.

NEW 3/4''C- 2 # 12 + 1 # 12 EG.

TO NEW HIRSCH ACCESS CONTROL PANEL IN

TR ROOM SHOWN ON T-616 RISER DIAGRAM.

NEW J-BOX ABOVE DOOR SEE DETAIL 7

DRAWING E-503.

NEW 3/4''C W/ PULL STRING BY ELECTRICAL

CONTRACTOR (INSTALLED ABOVE CEILING)

DOOR CONTROL CABLE BY SECURITY

CONTRACTOR.

STAIR

W.500.E-413

ELECTRICAL ENLARGED PLAN -

TR ROOM 16SA, 16SE, 16IN, 16IS

AND E2

0' 2' 4' 12'

SCALE: 1/4" = 1'-0"

SCALE: 1/4" = 1' - 0"

NORTH

ELECTRICAL

ENLARGED PLAN - ROOM 16IS

TR ROOM

16IS

Project Number

Campus / Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

A

F i t h U.S. Department of Veterans Affairs

B

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Project Director

Revisions: Date:

Key Plan

Upgrade Server Room and Site Communication Infrastructure

11301 WILSHIRE BOULEVARD,

WEST LOS ANGELES, CA 90073

691-20-152FINAL CONSTRUCTION

DOCUMENTS

JULY 13, 2021 PM EW/JB

FULLY SPRINKLERED

A

GENERAL NOTES

KEY NOTES

ARCHITECT/ENGINEER OF RECORD

C

D

17075 Via Del Campo, San Diego, CA 92127

Phone: 858.946.0333

20801.11 20-SCE-06

GENERAL NOTE

FIRE PROTECTION

1. DO NOT MAKE ANY ATTACHMENTS OR MODIFICATIONS TO

ANY FIREPROOFED COMPONENTS.

SYMBOLS LIST

2 HOUR FIRE BARRIER

1 HOUR FIRE BARRIER

2 HOUR FIRE/SMOKE BARRIER

SMOKE BARRIER

SMOKE PARTITION

1 HOUR FIRE/SMOKE BARRIER

3 HOUR FIRE BARRIER

SCALE: 1/4" = 1' - 0"

NORTH

ELECTRICAL

ENLARGED PLAN - ROOM 16IN

TR ROOM

16IN

SCALE: 1/4" = 1' - 0"

NORTH

ELECTRICAL

ENLARGED PLAN - ROOM 16SA

TELECOM

RM 16SA

SCALE: 1/4" = 1' - 0"

NORTH

ELECTRICAL

ENLARGED PLAN - ROOM 16SE

TR ROOM

16SE

1.

SCALE: 1/4" = 1' - 0"

NORTH

ELECTRICAL ENLARGED PLAN -

PENTHOUSE TR ROOM E2

NEW HIRSCH ACCESS CONTROL PANEL.

NEW PIV READER. SEE E-503 FOR CONDUIT

REQUIREMENTS.

NEW 3/4''C- 2 # 12 + 1 # 12 EG.

TO NEW HIRSCH ACCESS CONTROL PANEL IN

TR ROOM SHOWN ON T-616 RISER DIAGRAM.

NEW J-BOX ABOVE DOOR SEE DETAIL 7

DRAWING E-503.

NEW 3/4''C W/ PULL STRING BY ELECTRICAL

CONTRACTOR (INSTALLED ABOVE CEILING)

DOOR CONTROL CABLE BY SECURITY

CONTRACTOR.

ROOF

COND

0240C MCR COND4

COND

0240C MCR COND3

COND

0240C MCR COND1

COND

0240C MCR COND2

COND

0240C UPS COND5

2 2 2

2 2

WP

GFIRPMCR-7

SCALE: 1/4" = 1' - 0"

NORTH

W.500.E-414

Project Number

Campus / Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

A

F i t h

U.S. Department of Veterans Affairs

B

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Project Director

Revisions: Date:

Key Plan

Upgrade Server Room and Site Communication Infrastructure

11301 WILSHIRE BOULEVARD,

WEST LOS ANGELES, CA 90073

691-20-152FINAL CONSTRUCTION

DOCUMENTS

JULY 13, 2021 PM EW/JB

FULLY SPRINKLERED

A

GENERAL NOTES

KEY NOTES

ARCHITECT/ENGINEER OF RECORD

C

D

17075 Via Del Campo, San Diego, CA 92127

Phone: 858.946.0333

20801.11 20-SCE-06

GENERAL NOTE

FIRE PROTECTION

1. DO NOT MAKE ANY ATTACHMENTS OR MODIFICATIONS TO

ANY FIREPROOFED COMPONENTS.

SYMBOLS LIST

2 HOUR FIRE BARRIER

1 HOUR FIRE BARRIER

2 HOUR FIRE/SMOKE BARRIER

SMOKE BARRIER

SMOKE PARTITION

1 HOUR FIRE/SMOKE BARRIER

3 HOUR FIRE BARRIER

0' 2' 4' 12'

SCALE: 1/4" = 1'-0"

30A/ 3P 480V NEMA 3R FUSED DISCONNECT.

NEW 3/ 4''C - 3 # 12 + 1 # 12 EG.

PANEL ELMCRA-ROOF 100A 480V 3P 3W

NEMA 3R.

UNISTRUT RACK SEE DETAIL THIS SHEET.

NEW 3/4''C - 2 # 12 + 1 # 12 EG.

PANEL ELMCRB-ROOF 100A 480V 3P 3W NEMA 3R.

3/8'' DIA. KWIK BOLT 3 (2 1/2'' EMBEDMENT) 4 PER LEG

FITTING UNISTRUT CONNECTOR.

1/4'' DIA. BOLT.

(ESR 1917).

KEY NOTES FOR ELEVATION DETAIL:

NEW DISCONNECT.

POST BASE (P2073 UNISTRUT).

(1 5/8 x 1 5/8'') (P1001) (UNISTRUT).

(P1000 UNISTRUT).2

SCALE: NO SCALE

1. THE TWO FEEDER CONDUITS FOR THE TWO

PANELS & ONE BRANCH CIRCUIT CONDUIT SHALL

BE GROUPED TOGETHER & ROUTED WITH

MECHANICAL PIPES THROUGH NEW DOG HOUSE

FOR ROOF PENETRATION.

120VAC

SCALE: 1/4" = 1' - 0"

NORTH

W.506.E-401

ELECTRICAL ENLARGED PLAN -

ROOM 133

0' 2' 4' 12'

SCALE: 1/4" = 1'-0"

Project Number

Campus / Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

A

F i t h U.S. Department of Veterans Affairs

B

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Project Director

Revisions: Date:

Key Plan

Upgrade Server Room and Site Communication Infrastructure

11301 WILSHIRE BOULEVARD,

WEST LOS ANGELES, CA 90073

691-20-152FINAL CONSTRUCTION

DOCUMENTS

JULY 13, 2021 PM EW/JB

FULLY SPRINKLERED

A

GENERAL NOTES

ARCHITECT/ENGINEER OF RECORD

C

D

17075 Via Del Campo, San Diego, CA 92127

Phone: 858.946.0333

20801.11 20-SCE-06

GENERAL NOTE

FIRE PROTECTION

1. DO NOT MAKE ANY ATTACHMENTS OR MODIFICATIONS TO

ANY FIREPROOFED COMPONENTS.

SYMBOLS LIST

2 HOUR FIRE BARRIER

1 HOUR FIRE BARRIER

2 HOUR FIRE/SMOKE BARRIER

SMOKE BARRIER

SMOKE PARTITION

1 HOUR FIRE/SMOKE BARRIER

3 HOUR FIRE BARRIER

KEY NOTES

NEW HIRSCH ACCESS CONTROL PANEL.

NEW PIV READER. SEE E-503 FOR CONDUIT

REQUIREMENT.

3/4''C- 2 #12 + 1 #12EG

CONNECT TO EXISTING CIRCUIT IN TR ROOM.

120VAC

SCALE: 1/4" = 1' - 0"

NORTH

W.507.E-401

ELECTRICAL ENLARGED PLAN -

TR ROOM 102

0' 2' 4' 12'

SCALE: 1/4" = 1'-0"

Project Number

Campus / Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

A

F i t h

U.S. Department of Veterans Affairs

B

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

STAMPCONSULTANT

321 4 5 6 7 8 9 10

Project Director

Revisions:…