Attachment_F_P919__Volume_5_of_15.pdf

PDF 748 KB Posted

Attached to
P919 - Phase I, Bulk Fuel Tank Farm Improvements, Naval Station Rota, Spain
Solicitation number
N6247026R0006
Issued by

About this file

This document is a Fire Alarm System design specification for the Naval Facilities Engineering System Command's P-919 Bulk Tank Farm Improvements, Phase 1 project. The specification details a new addressable fire alarm system for the Injector Building, requiring compliance with multiple codes including UFC 1-200-01 DOD Building Code, NFPA 70, and NFPA 72. Key technical requirements include Class B signaling circuits, UL-listed devices, red-painted junction boxes, stranded copper wiring, wall-mounted alarm notification devices between 80-96 inches high, and a secondary power supply with 48-hour standby and 15-minute alarm capabilities. The system must be compatible with the existing basewide reporting system and include synchronous visual notification appliances with white housings marked "ALERT".

The documents include a fire alarm riser diagram, sequence of operations, antenna detail, and a floor plan showing device placement in the Equipment Room and Electrical Room. Installation specifications mandate strict adherence to National Electrical Code (NEC), with 25% spare capacity on power supplies, dedicated battery cabinets mounted no more than 3 feet from the floor, and an antenna mounted on the north side of the facility control room. The specification provides comprehensive guidelines for device placement, wiring, mounting, labeling, and overall system functionality to ensure a fully compliant and operational fire alarm system.

View the file

Other files

File Type Posted
N6247026R0006 Amendment 0009.pdf PDF
N6247026R0006 Amendment 0008.pdf PDF
Amendment 0008 Revised Specifications_Section 01.pdf PDF
P919 - Amendment 0007.pdf PDF
N6247026R0006 Amendment 0007.pdf PDF
Amendment 0006_Revised Specifications P919.pdf PDF
Amendment 0006_Revised Specifications F76 Pier 3.pdf PDF
Attachment M - F76 6_PIER3_REFERENCE-DRAWINGS_SET_6-OF-6.pdf PDF
Attachment M - F76 5_PIER3-FINAL_SUBMITTAL-PGS-130-149_SET_5-OF-6.pdf PDF
Amendment 0006_Revised Tank DWGs Prime.pdf PDF
Attachment M - F76 3_PIER3-FINAL_SUBMITTAL-PGS-62-99_SET_3-OF-6.pdf PDF
Amendment 0006_Revised F76 Pier 3 Mech Dwgs.pdf PDF
Attachment M - F76 4_PIER3-FINAL_SUBMITTAL-PGS-100-129_SET_4-OF-6.pdf PDF
Amendment 0006_Revised P-919 Dwgs_Pipeline Dwgs.pdf PDF
N6247026R0006 Amendment 0006.pdf PDF
Attachment M - F76 2_PIER3-FINAL_SUBMITTAL-PGS-35-70_SET_2-OF-6.pdf PDF
Attachment M - F76 1_PIER3-FINAL-REV1_SUBMITTAL-PGS-1-34_SET_1-OF-6.pdf PDF
Amendment 0006_Revised 01 30 00.pdf PDF
Amendment 0006_Revised F76 Pier 3 Civil Dwgs.pdf PDF
P919 - Amendment 0006.pdf PDF
Amendment 0006_Revised EC502P CATHODIC PROTECTION DETAILS.pdf PDF
Amendment 0006_Revised 01 45 00.pdf PDF
Amendment 0006_Revised 01 35 26.pdf PDF
Attachment G - Certificate of Classification Revised.pdf PDF
P-919 - Amendment 0005.pdf PDF
N6247026R0006 Amendment 0005.pdf PDF
Attachment P - Photos.pdf PDF
N6247026R0006 Amendment 0004.pdf PDF
N6247026R0006 Amendment 0003.pdf PDF
P919 Amendment 0002.pdf PDF
Site Visit Log (Attachment O).pdf PDF
N6247026R0006 Amendment 0002.pdf PDF
Attachment B - Bid Schedule Revised.pdf PDF
N6247026R0006 Amedment 0001.pdf PDF
Attachment N - Specifications -Replace Fuel Pipeline Pier 3 Rota.pdf PDF
Attachment M - F74 4_PIER3-FINAL_SUBMITTAL-PGS-100-129_SET_4-OF-6.pdf PDF
Attachment M - F74 5_PIER3-FINAL_SUBMITTAL-PGS-130-149_SET_5-OF-6.pdf PDF
Attachment M - F74 6_PIER3_REFERENCE-DRAWINGS_SET_6-OF-6.pdf PDF
Attachment M - F74 2_PIER3-FINAL_SUBMITTAL-PGS-35-70_SET_2-OF-6.pdf PDF
Attachment M - F74 3_PIER3-FINAL_SUBMITTAL-PGS-62-99_SET_3-OF-6.pdf PDF
Attachment M - F74 1_PIER3-FINAL-REV1_SUBMITTAL-PGS-1-34_SET_1-OF-6.pdf PDF
Attachment_F_P919__Volume_12_of_15.pdf PDF
Attachment_F_P919__Volume_2_of_15.pdf PDF
Attachment_F_P919__Volume_9_of_15.pdf PDF
Attachment_F_P919__Volume_1_of_15.pdf PDF
Attachment L - Certificate Insurance Form.pdf PDF
Attachment_F_P919__Volume_7_of_15.pdf PDF
Attachment G - Certificates of Classifications.pdf PDF
Attachment_F_P919__Volume_14_of_15.pdf PDF
Attachment D - Construction Experience Project Data Sheet.pdf PDF
Show 40 more

Latest 50 of 67 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

FA001T

FIRE ALARM SYSTEM GENERAL NOTES:

PFACP

FIRST FLOOR

CONCEPTUAL RISER DIAGRAM NOTES:

1. THE RISER DIAGRAM IS CONCEPTUAL IN NATURE. IT IS NOT INTERNED TO REPRESENT ACTUAL NUMBER OF DEVICES, CIRCUITS, OR APPLIANCES; OR ACTUAL WIRING AND RACEWAY INSTALLATION. ALL CONDUCTORS AND WIRING SHALL BE INSTALLED ACCORDING TO MANUFACTURER'S RECOMMENDATIONS, NFPA 72-2019 EDITION, AND NFPA 70-2017 EDITION.

2. THE CONTRACTOR SHALL FURNISH AND INSTALL REMOTE NOTIFICATION APPLIANCE CIRCUIT POWER SUPPLIES AS NECESSARY. A SMOKE DETECTOR SHALL BE INSTALLED IN THE VICINITY OF EACH REMOTE POWER SUPPLY. EACH REMOTE

POWER SUPPLY SHALL BE INSTALLED IN AN ACCESSIBLE LOCATION.

3. THE NUMBER OF CIRCUITS AND/OR CONDUCTORS SHALL BE DETERMINED BY THE FIRE ALARM SYSTEM CONTRACTOR UPON DETERMINING THE REQUIRED QUANTITY AND LOCATIONS OF REMOTE POWER SUPPLIES NECESSARY FOR THE FIRE ALARM

SYSTEM TO OPERATE AS DESCRIBED IN SPECIFICATIONS.

RAT

110 110

ACTIVATE AUDIBLE

FIR

E ALA

RM EVACUATIO

N THROUGHOUT BUILD

IN

G

MANUAL PULL STATION

FIRE ALARM INPUT

OPERATIO

N

AREA SMOKE DETECTOR OR HEAT DETECTOR

ACTIVATE C

LE

AR STOBES

ALA

RM C

ONDITIO

N AT FACP

TRANSMIT ALA

RM SIG

NAL T

O FIR

E D

EPT.

TRANSMIT TROUBLE

SIG

NAL T

O FIR

E D

EPT.

TROUBLE

C

ONDITIO

N AT FACP

FACP CIRCUIT FAULT (OPEN, GROUND, SHORT)

OTHER TROUBLE CONDITION

1. GENERAL SCOPE - PROVIDE NEW ADDRESSABLE FIRE ALARM SYSTEM THROUGHOUT THE

INJECTOR BUILDING IN COMPLIANCE WITH THE APPLICABLE CODES. THE NEW FIRE ALARM

SYSTEM SHALL BE COMPATIBLE WITH THE EXISTING BASEWIDE REPORTING SYSTEM.

2. APPLICABLE CODES:

UFC 1-200-01 DOD BUILDING CODE, 1 OCT 2020

UFC 3-600-01 FIRE PROTECTION ENGINEERING FOR FACILITIES, 6 MAY 2021

NFPA 70 NATIONAL ELECTRICAL CODE (NEC), 2020.

NFPA 72 NATIONAL FIRE ALARM AND SIGNALING CODE, 2019

3. NEW DEVICES SHALL BE UL LISTED.

4. SIGNALING LINE, INITIATING DEVICE, AND NOTIFICATION APPLIANCE CIRCUITS SHALL BE CLASS B.

5. ALL NEW JUNCTION BOXES AND COVERS SHALL BE PAINTED RED IN UNFINISHED AREAS. IN

FINISHED AREAS, CONDUIT AND JUNCTION BOXES SHALL BE PAINTED TO MATCH THE ROOM

FINISH. ALL NEW JUNCTION BOXES SHALL HAVE A PERMANENT, MACHINE PRINTED LABEL

READING "FIRE ALARM CIRCUIT" ON THE INSIDE COVER. ALL FIRE ALARM CONDUITS IN FINISHED AREAS SHALL BE MARKED WITH 3/4-IN RED BANDS EVERY 10 FEET, AT EACH SIDE OF A FLOOR, WALL, OR CEILING PENETRATION.

6. ALL SYSTEM POWER AND GROUND CIRCUITS SHALL BE TYPE "THHN" STRANDED OR SOLID

COPPER SIZED ACCORDING TO THE MANUFACTURER'S RECOMMENDATIONS AND THE APPLICABLE

CODES AND BE INSTALLED IN EMT TYPE CONDUIT. ALL FIRE ALARM CIRCUITS SHALL BE

STRANDED.

7. ALL WIRING, CABLES, BOXES, TROUGHS AND OTHER RELATED EQUIPMENT SHALL BE INSTALLED IN

STRICT COMPLIANCE WITH THE NATIONAL ELECTRICAL CODE (NEC).

8. MANUAL FIRE ALARM STATIONS SHALL BE DOUBLE-ACTION TYPE AND SEMI-FLUSH MOUNTED IN

FINISHED SPACES.

9. WALL-MOUNTED VISIBLE AND AUDIBLE/VISIBLE ALARM NOTIFICATION APPLIANCES SHALL BE

MOUNTED BETWEEN 80 AND 96-INCHES ABOVE THE FINISHED FLOOR MEASURED TO THE BOTTOM

OF THE LENDS. THE 96-INCH MEASUREMENT SHALL NOT BE EXCEEDED.

10. VISUAL FIRE ALARM APPLIANCES SHALL HAVE A WHITE HOUSING AND BE MARKED "ALERT."

11. SYNCHRONIZE ALL VISIBLE NOTIFICATION APPLIANCES WITHIN A COMMON VIEWING AREA IN

ACCORDANCE WITH NFPA 72.

12. 25% SPARE CAPACITY SHALL BE PROVIDED ON POWER SUPPLIES AND INDIVIDUAL CIRCUITS.

13. SECONDARY POWER SUPPLY SHALL BE VIA SEALED LEAD ACID BATTERY CAPABLE OF OPERATING

THE FIRE ALARM SYSTEM ON STANDBY FOR 48 HOURS FOLLOWED BY 15 MINUTES IN ALARM.

CHARGING AND METERING SHALL BE PROVIDED IN ACCORDANCE WITH NFPA 72.

14. ALL DRAWINGS ARE CONCEPTUAL IN NATURE, THEY DO NOT SHOW THE EXACT LOCATIONS OF

COMPONENTS NOR SHOW ALL SYSTEM COMPONENTS. CONTRACTOR SHALL PROVIDE ADDITIONAL

COMPONENTS FOR A PROPERLY INSTALLED AND FUNCTIONAL SYSTEM IN ACCORDANCE WITH ALL

APPLICABLE CODES.

15. DEDICATED BATTERY CABINETS SHALL BE MOUNTED NO MORE THAN 3 FEET FROM THE FINISHED

FLOOR.

16. MOUNT ANTENNA ON THE NORTH SIDE OF THE FACILITY CONTROL ROOM. THE ANTENNA SHALL

CLEAR THE ROOF BY THREE FEET (INCLUDING GROUND PLANES).

SCALE: NOT TO SCALE

FIRE ALARM SEQUENCE OF OPERATIONS

SCALE: NOT TO SCALE

FIRE ALARM RISER DIAGRAM

FIRE ALARM LEGEND

FIRE ALARM CONTROL PANEL

RADIO ALARM TRANSMITTER

WALL MOUNTED COMBINATION HORN/CLEAR STROBE

(SUPERSCRIPT INDICATES CANDELA RATING)

MANUAL PULL STATION

CD

P

RAT

FACP

AREA SMOKE DETECTOR

HEAT DETECTOR

WEATHERPROOF

SEAL

GROUND PLANE

1 1/4" RIGID STEEL

PIPE MAST

COAXIAL LIGHTNING ARRESTOR

IN RAINTIGHT ENCLOSURE

WEATHERHEAD

COXIAL CABLE

#6 GROUND WIRE

BUILDING COUNTERPOISE

STAND OFF PIPE BRACKETS

SIZED TO CLEAR RAKE TRIM 16 GAUGE, 12" BY 12" STEEL

SUPPORT PLATES MOUNTED

TO BOTH SIDES OF METAL

WALL, PAINT TO MATCH

SCALE: NOT TO SCALE

FIRE ALARM ANTENNA DETAIL

ELOR

ELOR

CD WALL MOUNTED CLEAR STROBE

(SUPERSCRIPT INDICATES CANDELA RATING)

ESCALA: SIN ESCALA

DETALLE DE ANTENA DE ALARMAS DE INCENDIOS

CONJUNTO DE CABLE DE PUESTA

A TIERRA DEL EDIFICIO #6

CABLE COAXIAL

DIAGRAMA UNIFILAR DE ALARMAS DE INCENDIOS

CABEZAL PARA INTEMPERIE

PARARRAYOS COAXIAL EN ENVOLVENTE

ESTANCA A LA LLUVIA

ABRAZADERAS SEPARADADAS

PARA TUBOS DIMENSIONADAS

PARA MANTENER LAS

DISTANCIASEN EL RASTRILLO

SELLADO RESISTENTE A

INTEMPERIE

PLANO DE TIERRA

MÁSTIL CON TUBO DE

ACERO RÍGIDO 1 1

4 "

PANEL DE CONTROL DE ALARMAS DE INCENDIOS

RADIO TRANSMISOR DE ALARMAS

COMBINACIÓN DE BOCINA / LUZ ESTROBOSCÓPICA TRANSPARENTE

MONTADA EN PARED (EL SUBÍNDICE INDICA EL GRADO DE CANDELAS)

PULSADOR MANUAL

LUZ ESTROBOSCÓPICA TRANSPARENTE MONTADA EN PARED

(EL SUBÍNDICE INDICA ELGRADO DE CANDELAS)

DETECTOR DE HUMO DE ZONA

DETECTOR DE CALOR

PLACAS DE SOPORTE DE ACERO 12"

POR 12", GALGA 16, MONTADA A

AMBOS LADOS DE LA PARED

METÁLICA, PINTAR PARA IGUALAR.

LEYENDA DE ALARMAS DE INCENDIOS

ESCALA: SIN ESCALA

PRIMERA PLANTA

NOTAS CONCEPTUALES DEL DIAGRAMA UNIFILAR:

1. EL DIAGRAMA UNIFILAR ES DE NATURALEZA CONCEPTUAL. NO REPRESENTA EL NÚMERO REAL DE DISPOSITIVOS, CIRCUITOS O APARATOS, NI LA INSTALACIÓN REAL DE CABLEADO Y CONDUCTOS. TODOS LOS CONDUCTORES Y EL CABLEADO SE INSTALARÁN DE ACUERDO CON LAS RECOMENDACIONES DEL FABRICANTE, LA NFPA 72- EDICIÓN 2019 Y

LA NFPA 70- EDICIÓN 2017.

2.

3.

EL CONTRATISTA SUMINISTRARÁ E INSTALARÁ LAS FUENTES DE ALIMENTACIÓN DE LOS CIRCUITOS DE LOS APARATOS DE NOTIFICACIÓN REMOTA QUE SEAN NECESARIAS. SE INSTALARÁ UN DETECTOR DE HUMO CERCA DE CADA FUENTE DE ALIMENTACIÓN REMOTA. CADA FUENTE DE ALIMENTACIÓN REMOTA SE INSTALARÁ EN UN LUGAR ACCESIBLE.

EL NÚMERO DE CIRCUITOS Y/O CONDUCTORES DEBERÁ SER DETERMINADO POR EL CONTRATISTA DEL SISTEMA DE ALARMA CONTRA INCENDIOS UNA VEZ DETERMINADA LA CANTIDAD REQUERIDA Y LAS UBICACIONES DE LAS FUENTES DE ALIMENTACIÓN REMOTAS NECESARIAS PARA QUE EL SISTEMA DE ALARMA CONTRA INCENDIOS FUNCIONE TAL COMO

SE DESCRIBE EN LAS ESPECIFICACIONES.

NOTAS GENERALES DEL SISTEMA DE ALARMAS DE INCENDIOS:

1. ALCANCE GENERAL - PROVEER UN NUEVO SISTEMA DE ALARMA DE INCENDIOS DIRECCIONABLE EN TODO EL

EDIFICIO DEL INYECTOR EN CUMPLIMIENTO CON LAS NORMAS APLICABLES. EL NUEVO SISTEMA DE ALARMA CONTRA INCENDIOS DEBERÁ SER COMPATIBLE CON EL SISTEMA DE NOTIFICACIÓN EXISTENTE EN LA BASE.

2. NORMAS APLICABLES:

UFC 1-200-01 DOD BUILDING CODE, 1 OCT 2020

UFC 3-600-01 FIRE PROTECTION ENGINEERING FOR FACILITIES, 6 MAY 2021

NFPA 70 NATIONAL ELECTRICAL CODE (NEC), 2020.

NFPA 72 NATIONAL FIRE ALARM AND SIGNALING CODE, 2019

3. LOS NUEVOS DISPOSITIVOS ESTARÁN LISTADOS UL.

4. LOS CIRCUITOS DE LA LÍNEA DE SEÑALIZACIÓN, DEL DISPOSITIVO DE INICIACIÓN Y DE LOS APARATOS DE

NOTIFICACIÓN SERÁN CLASE B.

5. TODAS LAS CAJAS DE EMPALMES Y TAPAS NUEVAS SE PINTARÁN DE ROJO EN LAS ZONAS NO ACABADAS. EN LAS ZONAS ACABADAS, LOS CONDUCTOS Y LAS CAJAS DE EMPALME SE PINTARÁN PARA QUE COINCIDAN CON EL ACABADO DEL CUARTO. TODAS LAS CAJAS DE EMPALME NUEVAS TENDRÁN UNA ETIQUETA PERMANENTE IMPRESA A MÁQUINA EN LA QUE SE LEA "CIRCUITO DE ALARMA CONTRA INCENDIOS" EN LA TAPA INTERIOR. TODOS LOS CONDUCTOS DE ALARMA CONTRA INCENDIOS EN LAS ZONAS ACABADAS SE MARCARÁN CON BANDAS ROJAS DE 3/4 DE PULGADA CADA 10 PIES, A CADA LADO DE UNA PENETRACIÓN EN EL SUELO, LA PARED O EL TECHO.

6. TODOS LOS CIRCUITOS DE FUERZA Y PUESTA A TIERRA DEL SISTEMA SERÁN DE COBRE TRENZADO O SÓLIDO TIPO "THHN", DIMENSIONADOS DE ACUERDO CON LAS RECOMENDACIONES DEL FABRICANTE Y LAS NORMAS APLICABLES, Y SE INSTALARÁN EN CONDUCTOS TIPO EMT. TODOS LOS CIRCUITOS DE ALARMA CONTRA INCENDIOS

SERÁN TRENZADOS.

7. TODO EL CABLEADO, CABLES, CAJAS, CANALETAS Y OTROS EQUIPOS RELACIONADOS SE INSTALARÁN EN ESTRICTO

CUMPLIMIENTO DEL CÓDIGO ELÉCTRICO NACIONAL (NEC).

8. LAS ESTACIONES MANUALES DE ALARMA CONTRA INCENDIOS SERÁN DEL TIPO DE DOBLE ACCIÓN Y SE MONTARÁN

SEMIEMPOTRADAS EN ESPACIOS ACABADOS.

9. LOS DISPOSITIVOS DE NOTIFICACIÓN DE ALARMAS VISIBLES Y ACÚSTICAS/VISIBLES MONTADOS EN PARED SE MONTARÁN ENTRE 80 Y 96 PULGADAS POR ENCIMA DEL SUELO ACABADO, MEDIDO HASTA LA PARTE INFERIOR DE

LAS PRESILLAS. LA MEDIDA DE 96 PULGADAS NO DEBE SER EXCEDIDA.

10. LOS DISPOSITIVOS VISUALES DE ALARMA CONTRA INCENDIOS TENDRÁN UNA CARCASA BLANCA Y LLEVARÁN LA

INSCRIPCIÓN "ALERTA".

11. SINCRONIZAR TODOS LOS APARATOS DE NOTIFICACIÓN VISIBLES DENTRO DE UN ÁREA DE VISIÓN COMÚN DE

ACUERDO CON LA NFPA 72.

12. LAS FUENTES DE ALIMENTACIÓN Y LOS CIRCUITOS INDIVIDUALES TENDRÁN UNA CAPACIDAD DE RESERVA DEL 25%.

13. LA ALIMENTACIÓN ELÉCTRICA SECUNDARIA SE REALIZARÁ A TRAVÉS DE UNA BATERÍA DE PLOMO-ÁCIDO SELLADA CAPAZ DE HACER FUNCIONAR EL SISTEMA DE ALARMA CONTRA INCENDIOS EN MODO DE ESPERA DURANTE 48 HORAS SEGUIDAS DE 15 MINUTOS EN MODO DE ALARMA. LA CARGA Y LA MEDICIÓN SE REALIZARÁN DE ACUERDO

CON LA NFPA 72.

14. TODOS LOS PLANOS SON DE NATURALEZA CONCEPTUAL, NO MUESTRAN LAS UBICACIONES EXACTAS DE LOS COMPONENTES NI MUESTRAN TODOS LOS COMPONENTES DEL SISTEMA. EL CONTRATISTA DEBERÁ PROVEER COMPONENTES ADICIONALES PARA UN SISTEMA CORRECTAMENTE INSTALADO Y FUNCIONAL DE ACUERDO CON

TODAS LAS NORMAS APLICABLES.

15. LOS ARMARIOS PARA BATERÍAS DEDICADAS SE MONTARÁN A NO MÁS DE 3 PIES DEL SUELO ACABADO.

16. MONTAR LA ANTENA EN EL LADO NORTE DEL CUARTO DE CONTROL DEL EDIFICIO. LA ANTENA DEBERÁ

SOBRESALIR UN METRO DE LA CUBIERTA (INCLUIDOS LOS PLANOS DE TIERRA).

SECUENCIA DE OPERACIONES DE ALARMA DE INCENDIOS

ESCALA: SIN ESCALA

/ ENTRADAS DE ALARMAS DE INCENDIOS

/ PULSADOR MANUAL

/ DETECTOR DE HUMO DE ZONA O DETECTOR DE

CALOR

/ CONDICIÓN PARA OTRO PROBLEMA

/ FALLO DE CIRCUITO FACP (ABIERTO, TIERRA,

CORTO)

/ FUNCIONAMIENTO

/ ACTIVAR LU

CES ESTROBOSCÓPICAS TRANSPARENTES

/ C

ONDICIÓN DE ALARMA EN EL F

ACP

/ TRANSMITIR SEÑAL D

E ALARMA AL D

EPARTAMENTO DE BOMBEROS

/ TRANSMITIR SEÑAL D

E PROBLEMA AL D

EPARTAMENTO DE BOMBEROS

/ ACTIVAR ALARMA DE IN

CENDIOS ACÚSTICA PARA EVACUACIÓN EN TODO EL E

DIFICIO

/ C

ONDICIÓN DE PROBLEMA EN EL F

ACP

N A

V A

L

FA

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

S Y

S

TE

M C

O M

M A

N D

A

TL

A

N

TI

C

P-

BU

LK

T

AN

K

FA

RM

IM

PR

O

VE

M

EN

TS

, P

H

AS

E

Lic. No. 037705

ALISON WAKELINCO

M M

ON

WE

ALTH-OF-VIRGIN

IA

PROFESSIONAL-ENG

IN

EE

R

FA101T

INJECTOR BUILDING FIRE ALARM PLAN / PLANTA DE ALARMAS DE INCENDIOS EDIFICIO DEL INYECTOR

N A

V A

L

FA

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

S Y

S

TE

M C

O M

M A

N D

A

TL

A

N

TI

C

P-

BU

LK

T

AN

K

FA

RM

IM

PR

O

VE

M

EN

TS

, P

H

AS

E

Lic. No. 037705

ALISON WAKELINCO

M M

ON

WE

ALTH-OF-VIRGIN

IA

PROFESSIONAL-ENG

IN

EE

R

Sheets and Views
FA001T
FA101T

2024-07-15T14:53:57-0400

2024-07-15T14:54:10-0400

2024-07-15T14:59:21-0400

2024-07-15T15:00:19-0400

2025-01-23T06:58:48-0500
FORBES.WILLIAM.BAHRANDT.1049879608
I am approving this document.
2025-01-23T06:58:54-0500
FORBES.WILLIAM.BAHRANDT.1049879608
I am approving this document.

File details come from the government source that posted it. Updated .