Attachment_F_P919__Volume_5_of_15.pdf
PDF 748 KB Posted
- Solicitation number
- N6247026R0006
About this file
This document is a Fire Alarm System design specification for the Naval Facilities Engineering System Command's P-919 Bulk Tank Farm Improvements, Phase 1 project. The specification details a new addressable fire alarm system for the Injector Building, requiring compliance with multiple codes including UFC 1-200-01 DOD Building Code, NFPA 70, and NFPA 72. Key technical requirements include Class B signaling circuits, UL-listed devices, red-painted junction boxes, stranded copper wiring, wall-mounted alarm notification devices between 80-96 inches high, and a secondary power supply with 48-hour standby and 15-minute alarm capabilities. The system must be compatible with the existing basewide reporting system and include synchronous visual notification appliances with white housings marked "ALERT".
The documents include a fire alarm riser diagram, sequence of operations, antenna detail, and a floor plan showing device placement in the Equipment Room and Electrical Room. Installation specifications mandate strict adherence to National Electrical Code (NEC), with 25% spare capacity on power supplies, dedicated battery cabinets mounted no more than 3 feet from the floor, and an antenna mounted on the north side of the facility control room. The specification provides comprehensive guidelines for device placement, wiring, mounting, labeling, and overall system functionality to ensure a fully compliant and operational fire alarm system.
View the file
Other files
Show 40 more
Latest 50 of 67 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FA001T
FIRE ALARM SYSTEM GENERAL NOTES:
PFACP
FIRST FLOOR
CONCEPTUAL RISER DIAGRAM NOTES:
1. THE RISER DIAGRAM IS CONCEPTUAL IN NATURE. IT IS NOT INTERNED TO REPRESENT ACTUAL NUMBER OF DEVICES, CIRCUITS, OR APPLIANCES; OR ACTUAL WIRING AND RACEWAY INSTALLATION. ALL CONDUCTORS AND WIRING SHALL BE INSTALLED ACCORDING TO MANUFACTURER'S RECOMMENDATIONS, NFPA 72-2019 EDITION, AND NFPA 70-2017 EDITION.
2. THE CONTRACTOR SHALL FURNISH AND INSTALL REMOTE NOTIFICATION APPLIANCE CIRCUIT POWER SUPPLIES AS NECESSARY. A SMOKE DETECTOR SHALL BE INSTALLED IN THE VICINITY OF EACH REMOTE POWER SUPPLY. EACH REMOTE
POWER SUPPLY SHALL BE INSTALLED IN AN ACCESSIBLE LOCATION.
3. THE NUMBER OF CIRCUITS AND/OR CONDUCTORS SHALL BE DETERMINED BY THE FIRE ALARM SYSTEM CONTRACTOR UPON DETERMINING THE REQUIRED QUANTITY AND LOCATIONS OF REMOTE POWER SUPPLIES NECESSARY FOR THE FIRE ALARM
SYSTEM TO OPERATE AS DESCRIBED IN SPECIFICATIONS.
RAT
110 110
ACTIVATE AUDIBLE
FIR
E ALA
RM EVACUATIO
N THROUGHOUT BUILD
IN
G
MANUAL PULL STATION
FIRE ALARM INPUT
OPERATIO
N
AREA SMOKE DETECTOR OR HEAT DETECTOR
ACTIVATE C
LE
AR STOBES
ALA
RM C
ONDITIO
N AT FACP
TRANSMIT ALA
RM SIG
NAL T
O FIR
E D
EPT.
TRANSMIT TROUBLE
SIG
NAL T
O FIR
E D
EPT.
TROUBLE
C
ONDITIO
N AT FACP
FACP CIRCUIT FAULT (OPEN, GROUND, SHORT)
OTHER TROUBLE CONDITION
1. GENERAL SCOPE - PROVIDE NEW ADDRESSABLE FIRE ALARM SYSTEM THROUGHOUT THE
INJECTOR BUILDING IN COMPLIANCE WITH THE APPLICABLE CODES. THE NEW FIRE ALARM
SYSTEM SHALL BE COMPATIBLE WITH THE EXISTING BASEWIDE REPORTING SYSTEM.
2. APPLICABLE CODES:
UFC 1-200-01 DOD BUILDING CODE, 1 OCT 2020
UFC 3-600-01 FIRE PROTECTION ENGINEERING FOR FACILITIES, 6 MAY 2021
NFPA 70 NATIONAL ELECTRICAL CODE (NEC), 2020.
NFPA 72 NATIONAL FIRE ALARM AND SIGNALING CODE, 2019
3. NEW DEVICES SHALL BE UL LISTED.
4. SIGNALING LINE, INITIATING DEVICE, AND NOTIFICATION APPLIANCE CIRCUITS SHALL BE CLASS B.
5. ALL NEW JUNCTION BOXES AND COVERS SHALL BE PAINTED RED IN UNFINISHED AREAS. IN
FINISHED AREAS, CONDUIT AND JUNCTION BOXES SHALL BE PAINTED TO MATCH THE ROOM
FINISH. ALL NEW JUNCTION BOXES SHALL HAVE A PERMANENT, MACHINE PRINTED LABEL
READING "FIRE ALARM CIRCUIT" ON THE INSIDE COVER. ALL FIRE ALARM CONDUITS IN FINISHED AREAS SHALL BE MARKED WITH 3/4-IN RED BANDS EVERY 10 FEET, AT EACH SIDE OF A FLOOR, WALL, OR CEILING PENETRATION.
6. ALL SYSTEM POWER AND GROUND CIRCUITS SHALL BE TYPE "THHN" STRANDED OR SOLID
COPPER SIZED ACCORDING TO THE MANUFACTURER'S RECOMMENDATIONS AND THE APPLICABLE
CODES AND BE INSTALLED IN EMT TYPE CONDUIT. ALL FIRE ALARM CIRCUITS SHALL BE
STRANDED.
7. ALL WIRING, CABLES, BOXES, TROUGHS AND OTHER RELATED EQUIPMENT SHALL BE INSTALLED IN
STRICT COMPLIANCE WITH THE NATIONAL ELECTRICAL CODE (NEC).
8. MANUAL FIRE ALARM STATIONS SHALL BE DOUBLE-ACTION TYPE AND SEMI-FLUSH MOUNTED IN
FINISHED SPACES.
9. WALL-MOUNTED VISIBLE AND AUDIBLE/VISIBLE ALARM NOTIFICATION APPLIANCES SHALL BE
MOUNTED BETWEEN 80 AND 96-INCHES ABOVE THE FINISHED FLOOR MEASURED TO THE BOTTOM
OF THE LENDS. THE 96-INCH MEASUREMENT SHALL NOT BE EXCEEDED.
10. VISUAL FIRE ALARM APPLIANCES SHALL HAVE A WHITE HOUSING AND BE MARKED "ALERT."
11. SYNCHRONIZE ALL VISIBLE NOTIFICATION APPLIANCES WITHIN A COMMON VIEWING AREA IN
ACCORDANCE WITH NFPA 72.
12. 25% SPARE CAPACITY SHALL BE PROVIDED ON POWER SUPPLIES AND INDIVIDUAL CIRCUITS.
13. SECONDARY POWER SUPPLY SHALL BE VIA SEALED LEAD ACID BATTERY CAPABLE OF OPERATING
THE FIRE ALARM SYSTEM ON STANDBY FOR 48 HOURS FOLLOWED BY 15 MINUTES IN ALARM.
CHARGING AND METERING SHALL BE PROVIDED IN ACCORDANCE WITH NFPA 72.
14. ALL DRAWINGS ARE CONCEPTUAL IN NATURE, THEY DO NOT SHOW THE EXACT LOCATIONS OF
COMPONENTS NOR SHOW ALL SYSTEM COMPONENTS. CONTRACTOR SHALL PROVIDE ADDITIONAL
COMPONENTS FOR A PROPERLY INSTALLED AND FUNCTIONAL SYSTEM IN ACCORDANCE WITH ALL
APPLICABLE CODES.
15. DEDICATED BATTERY CABINETS SHALL BE MOUNTED NO MORE THAN 3 FEET FROM THE FINISHED
FLOOR.
16. MOUNT ANTENNA ON THE NORTH SIDE OF THE FACILITY CONTROL ROOM. THE ANTENNA SHALL
CLEAR THE ROOF BY THREE FEET (INCLUDING GROUND PLANES).
SCALE: NOT TO SCALE
FIRE ALARM SEQUENCE OF OPERATIONS
SCALE: NOT TO SCALE
FIRE ALARM RISER DIAGRAM
FIRE ALARM LEGEND
FIRE ALARM CONTROL PANEL
RADIO ALARM TRANSMITTER
WALL MOUNTED COMBINATION HORN/CLEAR STROBE
(SUPERSCRIPT INDICATES CANDELA RATING)
MANUAL PULL STATION
CD
P
RAT
FACP
AREA SMOKE DETECTOR
HEAT DETECTOR
WEATHERPROOF
SEAL
GROUND PLANE
1 1/4" RIGID STEEL
PIPE MAST
COAXIAL LIGHTNING ARRESTOR
IN RAINTIGHT ENCLOSURE
WEATHERHEAD
COXIAL CABLE
#6 GROUND WIRE
BUILDING COUNTERPOISE
STAND OFF PIPE BRACKETS
SIZED TO CLEAR RAKE TRIM 16 GAUGE, 12" BY 12" STEEL
SUPPORT PLATES MOUNTED
TO BOTH SIDES OF METAL
WALL, PAINT TO MATCH
SCALE: NOT TO SCALE
FIRE ALARM ANTENNA DETAIL
ELOR
ELOR
CD WALL MOUNTED CLEAR STROBE
(SUPERSCRIPT INDICATES CANDELA RATING)
ESCALA: SIN ESCALA
DETALLE DE ANTENA DE ALARMAS DE INCENDIOS
CONJUNTO DE CABLE DE PUESTA
A TIERRA DEL EDIFICIO #6
CABLE COAXIAL
DIAGRAMA UNIFILAR DE ALARMAS DE INCENDIOS
CABEZAL PARA INTEMPERIE
PARARRAYOS COAXIAL EN ENVOLVENTE
ESTANCA A LA LLUVIA
ABRAZADERAS SEPARADADAS
PARA TUBOS DIMENSIONADAS
PARA MANTENER LAS
DISTANCIASEN EL RASTRILLO
SELLADO RESISTENTE A
INTEMPERIE
PLANO DE TIERRA
MÁSTIL CON TUBO DE
ACERO RÍGIDO 1 1
4 "
PANEL DE CONTROL DE ALARMAS DE INCENDIOS
RADIO TRANSMISOR DE ALARMAS
COMBINACIÓN DE BOCINA / LUZ ESTROBOSCÓPICA TRANSPARENTE
MONTADA EN PARED (EL SUBÍNDICE INDICA EL GRADO DE CANDELAS)
PULSADOR MANUAL
LUZ ESTROBOSCÓPICA TRANSPARENTE MONTADA EN PARED
(EL SUBÍNDICE INDICA ELGRADO DE CANDELAS)
DETECTOR DE HUMO DE ZONA
DETECTOR DE CALOR
PLACAS DE SOPORTE DE ACERO 12"
POR 12", GALGA 16, MONTADA A
AMBOS LADOS DE LA PARED
METÁLICA, PINTAR PARA IGUALAR.
LEYENDA DE ALARMAS DE INCENDIOS
ESCALA: SIN ESCALA
PRIMERA PLANTA
NOTAS CONCEPTUALES DEL DIAGRAMA UNIFILAR:
1. EL DIAGRAMA UNIFILAR ES DE NATURALEZA CONCEPTUAL. NO REPRESENTA EL NÚMERO REAL DE DISPOSITIVOS, CIRCUITOS O APARATOS, NI LA INSTALACIÓN REAL DE CABLEADO Y CONDUCTOS. TODOS LOS CONDUCTORES Y EL CABLEADO SE INSTALARÁN DE ACUERDO CON LAS RECOMENDACIONES DEL FABRICANTE, LA NFPA 72- EDICIÓN 2019 Y
LA NFPA 70- EDICIÓN 2017.
2.
3.
EL CONTRATISTA SUMINISTRARÁ E INSTALARÁ LAS FUENTES DE ALIMENTACIÓN DE LOS CIRCUITOS DE LOS APARATOS DE NOTIFICACIÓN REMOTA QUE SEAN NECESARIAS. SE INSTALARÁ UN DETECTOR DE HUMO CERCA DE CADA FUENTE DE ALIMENTACIÓN REMOTA. CADA FUENTE DE ALIMENTACIÓN REMOTA SE INSTALARÁ EN UN LUGAR ACCESIBLE.
EL NÚMERO DE CIRCUITOS Y/O CONDUCTORES DEBERÁ SER DETERMINADO POR EL CONTRATISTA DEL SISTEMA DE ALARMA CONTRA INCENDIOS UNA VEZ DETERMINADA LA CANTIDAD REQUERIDA Y LAS UBICACIONES DE LAS FUENTES DE ALIMENTACIÓN REMOTAS NECESARIAS PARA QUE EL SISTEMA DE ALARMA CONTRA INCENDIOS FUNCIONE TAL COMO
SE DESCRIBE EN LAS ESPECIFICACIONES.
NOTAS GENERALES DEL SISTEMA DE ALARMAS DE INCENDIOS:
1. ALCANCE GENERAL - PROVEER UN NUEVO SISTEMA DE ALARMA DE INCENDIOS DIRECCIONABLE EN TODO EL
EDIFICIO DEL INYECTOR EN CUMPLIMIENTO CON LAS NORMAS APLICABLES. EL NUEVO SISTEMA DE ALARMA CONTRA INCENDIOS DEBERÁ SER COMPATIBLE CON EL SISTEMA DE NOTIFICACIÓN EXISTENTE EN LA BASE.
2. NORMAS APLICABLES:
UFC 1-200-01 DOD BUILDING CODE, 1 OCT 2020
UFC 3-600-01 FIRE PROTECTION ENGINEERING FOR FACILITIES, 6 MAY 2021
NFPA 70 NATIONAL ELECTRICAL CODE (NEC), 2020.
NFPA 72 NATIONAL FIRE ALARM AND SIGNALING CODE, 2019
3. LOS NUEVOS DISPOSITIVOS ESTARÁN LISTADOS UL.
4. LOS CIRCUITOS DE LA LÍNEA DE SEÑALIZACIÓN, DEL DISPOSITIVO DE INICIACIÓN Y DE LOS APARATOS DE
NOTIFICACIÓN SERÁN CLASE B.
5. TODAS LAS CAJAS DE EMPALMES Y TAPAS NUEVAS SE PINTARÁN DE ROJO EN LAS ZONAS NO ACABADAS. EN LAS ZONAS ACABADAS, LOS CONDUCTOS Y LAS CAJAS DE EMPALME SE PINTARÁN PARA QUE COINCIDAN CON EL ACABADO DEL CUARTO. TODAS LAS CAJAS DE EMPALME NUEVAS TENDRÁN UNA ETIQUETA PERMANENTE IMPRESA A MÁQUINA EN LA QUE SE LEA "CIRCUITO DE ALARMA CONTRA INCENDIOS" EN LA TAPA INTERIOR. TODOS LOS CONDUCTOS DE ALARMA CONTRA INCENDIOS EN LAS ZONAS ACABADAS SE MARCARÁN CON BANDAS ROJAS DE 3/4 DE PULGADA CADA 10 PIES, A CADA LADO DE UNA PENETRACIÓN EN EL SUELO, LA PARED O EL TECHO.
6. TODOS LOS CIRCUITOS DE FUERZA Y PUESTA A TIERRA DEL SISTEMA SERÁN DE COBRE TRENZADO O SÓLIDO TIPO "THHN", DIMENSIONADOS DE ACUERDO CON LAS RECOMENDACIONES DEL FABRICANTE Y LAS NORMAS APLICABLES, Y SE INSTALARÁN EN CONDUCTOS TIPO EMT. TODOS LOS CIRCUITOS DE ALARMA CONTRA INCENDIOS
SERÁN TRENZADOS.
7. TODO EL CABLEADO, CABLES, CAJAS, CANALETAS Y OTROS EQUIPOS RELACIONADOS SE INSTALARÁN EN ESTRICTO
CUMPLIMIENTO DEL CÓDIGO ELÉCTRICO NACIONAL (NEC).
8. LAS ESTACIONES MANUALES DE ALARMA CONTRA INCENDIOS SERÁN DEL TIPO DE DOBLE ACCIÓN Y SE MONTARÁN
SEMIEMPOTRADAS EN ESPACIOS ACABADOS.
9. LOS DISPOSITIVOS DE NOTIFICACIÓN DE ALARMAS VISIBLES Y ACÚSTICAS/VISIBLES MONTADOS EN PARED SE MONTARÁN ENTRE 80 Y 96 PULGADAS POR ENCIMA DEL SUELO ACABADO, MEDIDO HASTA LA PARTE INFERIOR DE
LAS PRESILLAS. LA MEDIDA DE 96 PULGADAS NO DEBE SER EXCEDIDA.
10. LOS DISPOSITIVOS VISUALES DE ALARMA CONTRA INCENDIOS TENDRÁN UNA CARCASA BLANCA Y LLEVARÁN LA
INSCRIPCIÓN "ALERTA".
11. SINCRONIZAR TODOS LOS APARATOS DE NOTIFICACIÓN VISIBLES DENTRO DE UN ÁREA DE VISIÓN COMÚN DE
ACUERDO CON LA NFPA 72.
12. LAS FUENTES DE ALIMENTACIÓN Y LOS CIRCUITOS INDIVIDUALES TENDRÁN UNA CAPACIDAD DE RESERVA DEL 25%.
13. LA ALIMENTACIÓN ELÉCTRICA SECUNDARIA SE REALIZARÁ A TRAVÉS DE UNA BATERÍA DE PLOMO-ÁCIDO SELLADA CAPAZ DE HACER FUNCIONAR EL SISTEMA DE ALARMA CONTRA INCENDIOS EN MODO DE ESPERA DURANTE 48 HORAS SEGUIDAS DE 15 MINUTOS EN MODO DE ALARMA. LA CARGA Y LA MEDICIÓN SE REALIZARÁN DE ACUERDO
CON LA NFPA 72.
14. TODOS LOS PLANOS SON DE NATURALEZA CONCEPTUAL, NO MUESTRAN LAS UBICACIONES EXACTAS DE LOS COMPONENTES NI MUESTRAN TODOS LOS COMPONENTES DEL SISTEMA. EL CONTRATISTA DEBERÁ PROVEER COMPONENTES ADICIONALES PARA UN SISTEMA CORRECTAMENTE INSTALADO Y FUNCIONAL DE ACUERDO CON
TODAS LAS NORMAS APLICABLES.
15. LOS ARMARIOS PARA BATERÍAS DEDICADAS SE MONTARÁN A NO MÁS DE 3 PIES DEL SUELO ACABADO.
16. MONTAR LA ANTENA EN EL LADO NORTE DEL CUARTO DE CONTROL DEL EDIFICIO. LA ANTENA DEBERÁ
SOBRESALIR UN METRO DE LA CUBIERTA (INCLUIDOS LOS PLANOS DE TIERRA).
SECUENCIA DE OPERACIONES DE ALARMA DE INCENDIOS
ESCALA: SIN ESCALA
/ ENTRADAS DE ALARMAS DE INCENDIOS
/ PULSADOR MANUAL
/ DETECTOR DE HUMO DE ZONA O DETECTOR DE
CALOR
/ CONDICIÓN PARA OTRO PROBLEMA
/ FALLO DE CIRCUITO FACP (ABIERTO, TIERRA,
CORTO)
/ FUNCIONAMIENTO
/ ACTIVAR LU
CES ESTROBOSCÓPICAS TRANSPARENTES
/ C
ONDICIÓN DE ALARMA EN EL F
ACP
/ TRANSMITIR SEÑAL D
E ALARMA AL D
EPARTAMENTO DE BOMBEROS
/ TRANSMITIR SEÑAL D
E PROBLEMA AL D
EPARTAMENTO DE BOMBEROS
/ ACTIVAR ALARMA DE IN
CENDIOS ACÚSTICA PARA EVACUACIÓN EN TODO EL E
DIFICIO
/ C
ONDICIÓN DE PROBLEMA EN EL F
ACP
N A
V A
L
FA
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
S Y
S
TE
M C
O M
M A
N D
A
TL
A
N
TI
C
P-
BU
LK
T
AN
K
FA
RM
IM
PR
O
VE
M
EN
TS
, P
H
AS
E
Lic. No. 037705
ALISON WAKELINCO
M M
ON
WE
ALTH-OF-VIRGIN
IA
PROFESSIONAL-ENG
IN
EE
R
FA101T
INJECTOR BUILDING FIRE ALARM PLAN / PLANTA DE ALARMAS DE INCENDIOS EDIFICIO DEL INYECTOR
N A
V A
L
FA
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
S Y
S
TE
M C
O M
M A
N D
A
TL
A
N
TI
C
P-
BU
LK
T
AN
K
FA
RM
IM
PR
O
VE
M
EN
TS
, P
H
AS
E
Lic. No. 037705
ALISON WAKELINCO
M M
ON
WE
ALTH-OF-VIRGIN
IA
PROFESSIONAL-ENG
IN
EE
R
| Sheets and Views |
| FA001T |
| FA101T |
2024-07-15T14:53:57-0400
2024-07-15T14:54:10-0400
2024-07-15T14:59:21-0400
2024-07-15T15:00:19-0400
| 2025-01-23T06:58:48-0500 | |
| FORBES.WILLIAM.BAHRANDT.1049879608 | |
| I am approving this document. |
| 2025-01-23T06:58:54-0500 | |
| FORBES.WILLIAM.BAHRANDT.1049879608 | |
| I am approving this document. |
File details come from the government source that posted it. Updated .