Attachment F-Firecheck Inspection Report- ASU.pdf
PDF 2 MB Posted
- Attached to
- Fire Door Assemblies Assessment, Testing, and Corrective Repair Services for the Albuquerque Area IHS
- Solicitation number
- 75H70726Q00088
About this file
This document is an Initial Annual Fire & Smoke Door Inspection Report for the Albuquerque Indian Health Service facility located at 801 Vassar Drive NE, Albuquerque, NM 87106. The inspection, conducted on August 28, 2025, evaluated 19 fire and smoke doors against NFPA 80-2010 for Healthcare standards. The facility's doors are distributed across five floors of the main building, with door openings ranging from 28" x 84" to 48" x 84", constructed primarily of hollow metal or wood materials.
The inspection results indicate that all 19 doors failed compliance, with 15 classified as Critical priority deficiencies requiring urgent corrective action without delay and 4 classified as Immediate priority deficiencies. The predominant failure categories include FC5 (door clearances exceeding specified tolerances), appearing in 14 openings; FC13.F (missing or illegible frame labels), appearing in 14 openings; and FC13.H (missing or illegible hardware labels), appearing in 14 openings. Additional deficiencies include missing self-closing devices (FC6, 4 openings), open holes or breaks in surfaces (FC1, 4 openings), missing parts (FC4, 1 opening), improper signage (FC12, 1 opening), missing door labels (FC13.D, 5 openings), and louvers or transfer grilles in smoke barriers (FC15, 1 opening). The report notes that the owner must remove excess signage and verify ratings of protection plates, electric strikes, power transfer cords, presence sensors, door position/alarm sensors, steel pick guards, door/frame guards, gasketing/perimeter seals, door viewers, and auto door bottoms/sweeps. No deficiencies were repaired on-site during the inspection.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Initial Annual Fire & Smoke Door Inspection
Albuquerque Indian Health Service
Albuquerque Indian Health
801 Vassar Dr Ne
Albuquerque, NM 87106
Inspection No.: SLS384140
Code Edition: NFPA 80 - 2010 for Healthcare
Inspection Initiated: August 28 2025
If the report indicates that deficiencies were found (and were not repaired on-site), please refer to corresponding proposal.
This comprehensive FireCheck® inspection report is based on NFPA 80 (fire) and NFPA 105 (smoke) requirements. This report applies only to door list provided by the Customer.
Code Interpretation Disclaimer: All information provided by DH Pace Inc. represents our interpretation regarding the intent of the standard(s) and/or code(s) applicable to the issue being addressed. By law, the Authority Having Jurisdiction (AHJ) is the only entity with the legal standing and discretionary authority to make a definitive ruling on these matters. As such, DH Pace disclaims any consequential damages that may arise from the use of the information provided, recommendation made, or opinions expressed on this matter.
This document was developed by and is the Exclusive property of DH Pace Company, Inc. Any unauthorized use, reproduction or duplication, in whole or in part, is expressly prohibited. © 2022 DH Pace Company, Inc.
Inspection Rpt. 8/28/2025
Inspection No. SLS384140 Printed 9/5/2025 10:26 AM 1 of 27
Initial Annual Fire & Smoke Door Inspection Summary Name Albuquerque Indian Health Contact Patricio, Patrick
Address 801 Vassar Dr Ne Contact # (505) 290-0260
City, State Zip Albuquerque, NM 87106 Inspection Date 8/28/2025
P/F
Initial
Repaired
Post Repair
Pass 0 0 0
Fail 19 0 19
Total
Priority of Failed Openings
Opening #
Critical 15
Immediate 4
Total Failed
Priority Definitions
Critical - Deficiency requires urgent corrective action without delay
Immediate - Deficiency requires corrective action without delay
Essential - Deficiency requires corrective action, safety concern
Owner to remove excess signage.
Owner to verify rating of protection plates, electric strikes, power transfer cords, presence sensors, door position/alarm sensors, steel pick guards, door/frame guards, gasketing/perimeter seal, door viewers, and auto door bottoms/sweeps.
Name:
Faron Shetter Jr - DSI Signature:
Date:
9/05/2025
Faron Shetter Jr DH Pace Compliance Services
5656 Pasadena Avenue N.E.
Albuquerque, NM 87113
(505) 344-3667
Main: (505) 221-9025
Email: Faron.ShetterJr@dhpace.com
This document was developed by and is the Exclusive property of DH Pace Company, Inc. Any unauthorized use, reproduction or duplication, in whole or in part, is expressly prohibited. © 2022 DH Pace Company, Inc.
Printed 9/5/2025 10:26 AM 2 of 27
Initial Annual Fire & Smoke Door Inspection Criteria Name Albuquerque Indian Health Code Edition:
Address 801 Vassar Dr Ne Albuquerque, NM 87106 NFPA 80 - 2010 for Healthcare
Inspection Date 8/28/2025 Inspection No. SLS384140
Criteria
Components
Description
# Failed Openings
FC1 Frame, Door No open holes or breaks exist in surfaces of either the door or frame. 4
FC2 Frame, Door Glazing, vision light frames, and glazing beads are intact and securely fastened in place, if so equipped. Safety glass is the correct size and type.
FC3 Frame, Door, Hardware The door, frame, hinges, hardware and non-combustible threshold are secured, aligned, and in working order with no signs of visible damage.
FC4 Frame, Door, Hardware No parts are missing or broken. 1
FC5 Top, Bottom, Hinge Edge, Strike Edge
Door clearances do not exceed clearances listed in 4.8.4 and 6.3.1.7. WOOD/PLAM EDGES/TOP not > 1/8", WOOD/PLAM BOTTOM not > 3/4", HM-STEEL EDGES/TOP 1/8" + or - 1/16", HM-STEEL BOTTOM not > 3/4"
FC6 Hardware The self-closing device is operational, that is, the active door completely closes when operated from the full open position.
FC7 Hardware If a coordinator is installed, the inactive leaf closes before the active leaf. 0
FC8 Hardware Where latching hardware is required, it operates and secures the door when it is in the closed position (not required for cross-corridor doors 1-hr Smoke Barriers in Healthcare deemed "Substantial Doors" and not 20-min rated/labeled)
FC9 Hardware Auxiliary items that interfere or prohibit operation are not installed on the door or frame. 0
FC10 Frame, Door, Hardware No field modifications to the door assembly have been performed to void the label. 0
FC11 Frame, Door Gasketing and edge seals, where required, are inspected to verify their presence and integrity.
FC12 Size, Mounting Signage is the correct size and mounted properly. 1
FC13.D Door Labels are present and readily visible on the opening door. 5
FC13.F Frame Labels are present and readily visible on the opening frame. 14
FC13.G Glass Labels are present and readily visible on the opening glass. 0
FC13.H Hardware Labels are present and readily visible on the opening hardware. 14
FC13.P Protection Plate Labels are present and readily visible on the protection plate (when plate is mounted above 16" from bottom of door)
FC14 Hardware Doors installed in pressurized applications have gasketing and a bottom seal (note deficient gasketing on FC11)
FC15 Hardware No louvers or transfer grills in door (when door is in combo fire and smoke barrier or just smoke barrier)
Door Type S - Single UP - Unequal Pair P - Pair DE - Double
Egress B - Bank D - Dutch
This document was developed by and is the Exclusive property of DH Pace Company, Inc. Any unauthorized use, reproduction or duplication, in whole or in part, is expressly prohibited. © 2022 DH Pace Company, Inc.
Printed 9/5/2025 10:26 AM 3 of 27
Initial Annual Fire & Smoke Door Inspection Details Name Albuquerque Indian Health
Address 801 Vassar Dr Ne Albuquerque, NM 87106
Inspection Date 8/28/2025 Project # 384633 Inspection No. SLS384140
Building: MAIN
Floor: 01
Opening
Barcode Door Material
Door Size
Area Frame Material
Inspector Barrier Type
Date Priority
278-415176-001-0001
Failed
MECHANICAL
Shawn Boxer
8/28/2025
Single
Wood
36" x 80"
Hollow Metal Not Filled
1-Hour Smoke Barrier
Immediate
Leaf
Fire Rating
Smoke Label
Failed Fire Criteria
Leaf A
60 mins
N/A
FC5, FC15
278-415176-001-0002
STAIR
Hollow Metal
48" x 84"
Hollow Metal Filled
2-Hour Fire Barrier
Critical
90 mins
FC5, FC13.F, FC13.H
278-415176-001-0004
278-415176-001-0005
FC6
278-415176-001-0006
180 mins
FC1, FC4
Floor: 02
278-415176-001-0007
FC1, FC5, FC13.F, FC13.H
278-415176-001-0008
278-415176-001-0009
36" x 84"
FC5
278-415176-001-0010
1-Hour Fire Barrier
FC13.D, FC13.F, FC13.H
This document was developed by and is the Exclusive property of DH Pace Company, Inc. Any unauthorized use, reproduction or duplication, in whole or in part, is expressly prohibited. © 2022 DH Pace Company, Inc.
Printed 9/5/2025 10:26 AM 4 of 27
Floor: 02
278-415176-001-0011
FC1, FC5, FC13.D, FC13.F, FC13.H
Floor: 03
278-415176-001-0012
278-415176-001-0014
278-415176-001-0015
46" (3'10") x 84"
FC5, FC13.H
Floor: 04
278-415176-001-0016
278-415176-001-0017
28" x 84"
Label Missing
FC5, FC6, FC12, FC13.D, FC13.F
278-415176-001-0018
278-415176-001-0019
This document was developed by and is the Exclusive property of DH Pace Company, Inc. Any unauthorized use, reproduction or duplication, in whole or in part, is expressly prohibited. © 2022 DH Pace Company, Inc.
Printed 9/5/2025 10:26 AM 5 of 27
Floor: 05
278-415176-001-0020
STORAGE
FC1, FC6, FC13.D, FC13.F, FC13.H
278-415176-001-0021
FC6, FC13.D, FC13.F, FC13.H
This document was developed by and is the Exclusive property of DH Pace Company, Inc. Any unauthorized use, reproduction or duplication, in whole or in part, is expressly prohibited. © 2022 DH Pace Company, Inc.
Printed 9/5/2025 10:26 AM 6 of 27
Initial Annual Fire & Smoke Inspection Door Details
Building: MAIN Floor: 01 Opening: 0001
Fire / Smoke
278-415176-001-0001
Yes / No
60 mins
Failed Notes
General Notes
Compliant Repaired
WD/PLAM strike edge clearance > 1/8"
Strike Edge
No
FC15
No louver or transfer grille installed in door
Hardware
Push
Pull
FC15 - Deficiency
FC5 - Deficiency
This document was developed by and is the Exclusive property of DH Pace Company, Inc. Any unauthorized use, reproduction or duplication, in whole or in part, is expressly prohibited. © 2022 DH Pace Company, Inc.
Printed 9/5/2025 10:26 AM 7 of 27
Building: MAIN Floor: 01 Opening: 0002
278-415176-001-0002
HM strike edge clearance > 3/16" HM top edge clearance > 3/16"
Top, Strike Edge
FC13.F
Missing / illegible frame label
Frame
FC13.H
Missing / illegible fire exit hardware label (cannot label panic hardware, must be fire exit hardware - no mechanical dogging)
Hardware, FC13.F - Deficiency
This document was developed by and is the Exclusive property of DH Pace Company, Inc. Any unauthorized use, reproduction or duplication, in whole or in part, is expressly prohibited. © 2022 DH Pace Company, Inc.
Printed 9/5/2025 10:26 AM 8 of 27
Building: MAIN Floor: 01 Opening: 0004
278-415176-001-0004
This document was developed by and is the Exclusive property of DH Pace Company, Inc. Any unauthorized use, reproduction or duplication, in whole or in part, is expressly prohibited. © 2022 DH Pace Company, Inc.
Printed 9/5/2025 10:26 AM 9 of 27
Building: MAIN Floor: 01 Opening: 0005
278-415176-001-0005
Missing / damaged closer
FC6 - Deficiency
This document was developed by and is the Exclusive property of DH Pace Company, Inc. Any unauthorized use, reproduction or duplication, in whole or in part, is expressly prohibited. © 2022 DH Pace Company, Inc.
Printed 9/5/2025 10:26 AM 10 of 27
Building: MAIN Floor: 01 Opening: 0006
278-415176-001-0006
180 mins
FC1
Missing hardware leaving hole in frame / door
Door
FC4
Lock/latch fire exit hardware missing part
FC1 - Deficiency
FC4 - Deficiency
This document was developed by and is the Exclusive property of DH Pace Company, Inc. Any unauthorized use, reproduction or duplication, in whole or in part, is expressly prohibited. © 2022 DH Pace Company, Inc.
Printed 9/5/2025 10:26 AM 11 of 27
Building: MAIN Floor: 02 Opening: 0007
278-415176-001-0007
This document was developed by and is the Exclusive property of DH Pace Company, Inc. Any unauthorized use, reproduction or duplication, in whole or in part, is expressly prohibited. © 2022 DH Pace Company, Inc.
Printed 9/5/2025 10:26 AM 12 of 27
Building: MAIN Floor: 02 Opening: 0008
278-415176-001-0008
This document was developed by and is the Exclusive property of DH Pace Company, Inc. Any unauthorized use, reproduction or duplication, in whole or in part, is expressly prohibited. © 2022 DH Pace Company, Inc.
Printed 9/5/2025 10:26 AM 13 of 27
Building: MAIN Floor: 02 Opening: 0009
278-415176-001-0009
No / No
WD/PLAM top edge clearance > 1/8"
Top
This document was developed by and is the Exclusive property of DH Pace Company, Inc. Any unauthorized use, reproduction or duplication, in whole or in part, is expressly prohibited. © 2022 DH Pace Company, Inc.
Printed 9/5/2025 10:26 AM 14 of 27
Building: MAIN Floor: 02 Opening: 0010
278-415176-001-0010
FC13.D
Missing / illegible door label (double-check top of door)
FC13.D - Deficiency
This document was developed by and is the Exclusive property of DH Pace Company, Inc. Any unauthorized use, reproduction or duplication, in whole or in part, is expressly prohibited. © 2022 DH Pace Company, Inc.
Printed 9/5/2025 10:26 AM 15 of 27
Building: MAIN Floor: 02 Opening: 0011
278-415176-001-0011
FC5 - Repaired Deficiency
This document was developed by and is the Exclusive property of DH Pace Company, Inc. Any unauthorized use, reproduction or duplication, in whole or in part, is expressly prohibited. © 2022 DH Pace Company, Inc.
Printed 9/5/2025 10:26 AM 16 of 27
Building: MAIN Floor: 03 Opening: 0012
278-415176-001-0012
Bottom clearance for HM and WD/PLAM > 3/4"
Top, Bottom, Deficiency
This document was developed by and is the Exclusive property of DH Pace Company, Inc. Any unauthorized use, reproduction or duplication, in whole or in part, is expressly prohibited. © 2022 DH Pace Company, Inc.
Printed 9/5/2025 10:26 AM 17 of 27
Building: MAIN Floor: 03 Opening: 0014
278-415176-001-0014
This document was developed by and is the Exclusive property of DH Pace Company, Inc. Any unauthorized use, reproduction or duplication, in whole or in part, is expressly prohibited. © 2022 DH Pace Company, Inc.
Printed 9/5/2025 10:26 AM 18 of 27
Building: MAIN Floor: 03 Opening: 0015
278-415176-001-0015
46" (3'10") x 84"
This document was developed by and is the Exclusive property of DH Pace Company, Inc. Any unauthorized use, reproduction or duplication, in whole or in part, is expressly prohibited. © 2022 DH Pace Company, Inc.
Printed 9/5/2025 10:26 AM 19 of 27
Building: MAIN Floor: 04 Opening: 0016
278-415176-001-0016
This document was developed by and is the Exclusive property of DH Pace Company, Inc. Any unauthorized use, reproduction or duplication, in whole or in part, is expressly prohibited. © 2022 DH Pace Company, Inc.
Printed 9/5/2025 10:26 AM 20 of 27
Building: MAIN Floor: 04 Opening: 0017
278-415176-001-0017
28" x 84"
WD/PLAM top edge clearance > 1/8" Bottom clearance for HM and WD/PLAM > 3/4"
Top, Bottom
FC12
Signage > 5%
Size
FC12 - Deficiency
This document was developed by and is the Exclusive property of DH Pace Company, Inc. Any unauthorized use, reproduction or duplication, in whole or in part, is expressly prohibited. © 2022 DH Pace Company, Inc.
Printed 9/5/2025 10:26 AM 21 of 27
Building: MAIN Floor: 04 Opening: 0017
This document was developed by and is the Exclusive property of DH Pace Company, Inc. Any unauthorized use, reproduction or duplication, in whole or in part, is expressly prohibited. © 2022 DH Pace Company, Inc.
Printed 9/5/2025 10:26 AM 22 of 27
Building: MAIN Floor: 04 Opening: 0018
278-415176-001-0018
Top
This document was developed by and is the Exclusive property of DH Pace Company, Inc. Any unauthorized use, reproduction or duplication, in whole or in part, is expressly prohibited. © 2022 DH Pace Company, Inc.
Printed 9/5/2025 10:26 AM 23 of 27
Building: MAIN Floor: 04 Opening: 0019
278-415176-001-0019
This document was developed by and is the Exclusive property of DH Pace Company, Inc. Any unauthorized use, reproduction or duplication, in whole or in part, is expressly prohibited. © 2022 DH Pace Company, Inc.
Printed 9/5/2025 10:26 AM 24 of 27
Building: MAIN Floor: 05 Opening: 0020
278-415176-001-0020
STORAGE
Missing 'F' stamp on latch that designates rated lockset
FC13.H - Deficiency
This document was developed by and is the Exclusive property of DH Pace Company, Inc. Any unauthorized use, reproduction or duplication, in whole or in part, is expressly prohibited. © 2022 DH Pace Company, Inc.
Printed 9/5/2025 10:26 AM 25 of 27
Building: MAIN Floor: 05 Opening: 0021
278-415176-001-0021
Missing 'F' stamp on latch that designates rated lockset
FC13.H - Deficiency
This document was developed by and is the Exclusive property of DH Pace Company, Inc. Any unauthorized use, reproduction or duplication, in whole or in part, is expressly prohibited. © 2022 DH Pace Company, Inc.
Printed 9/5/2025 10:26 AM 26 of 27
--- End of Report ---
Albuquerque Indian Health Service
Albuquerque Indian Health
801 Vassar Dr Ne
Albuquerque, NM 87106
Inspection No.:
SLS384140
Code Edition: NFPA 80 - 2010 for Healthcare
Inspection Initiated: August 28 2025
If the report indicates that deficiencies were found (and were not repaired on-site), please refer to corresponding proposal.
This comprehensive FireCheck® inspection report is based on NFPA 80 (fire) and NFPA 105 (smoke) requirements. This report applies only to door list provided by the Customer.
Code Interpretation Disclaimer: All information provided by DH Pace Inc. represents our interpretation regarding the intent of the standard(s) and/or code(s) applicable to the issue being addressed. By law, the Authority Having Jurisdiction (AHJ) is the only entity with the legal standing and discretionary authority to make a definitive ruling on these matters. As such, DH Pace disclaims any consequential damages that may arise from the use of the information provided, recommendation made, or opinions expressed on this matter.
This document was developed by and is the Exclusive property of DH Pace Company, Inc. Any unauthorized use, reproduction or duplication, in whole or in part, is expressly prohibited. © 2022 DH Pace Company, Inc.
Printed 9/5/2025 10:26 AM 27 of 27