This is an architectural drawing document that provides comprehensive partition type specifications and construction details for the New VA Medical Center Phase IV Building in North Las Vegas, Nevada. The drawing, dated June 5, 2008, establishes standardized partition classifications (Types A through U) with corresponding construction requirements including stud sizes, gypsum board specifications, fire ratings, sound transmission ratings (STC), and material compositions. The document specifies partition priorities based on functional requirements, such as Priority 1 partitions for wet wall areas with plumbing fixtures requiring moisture-resistant materials, Priority 2 for toilet rooms and utility closets, and progressively lower priorities for standard construction areas. Key construction standards include metal stud framing at minimum 18 gauge with 16-inch on-center spacing, various gypsum board configurations ranging from single to triple layers, fire-sealant requirements for rated partitions, and specialized materials such as lead-lined gypsum board for radiation protection areas and abuse-resistant gypsum board for high-security areas including seclusion rooms.
The document includes detailed partition intersection guidance, plumbing chase schedules, and cross-bracing specifications, along with references to complementary drawing sheets (AE-5105, AE-5410, GI-0321 through GI-3028) for typical head wall, sill, and shaft wall details. Fire-rated partitions are designated with UL assembly numbers such as UL#U419, UL#U415, and UL#U493, with ratings ranging from 1-hour to 2-hour fire resistance. Specific notations address construction conditions in exam rooms, treatment areas, restrooms, patient rooms, staff lounges, and conference rooms, with requirements for sound attenuation blankets in designated spaces. The document was prepared by SYSKA HENNESSY GROUP in collaboration with multiple consulting firms including RTKL, LaSalle Engineering, Degenkolb Engineering, and others, with construction managed by G.C. Wallace, Inc. in Las Vegas.
View the file
Other files
Show all 23
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
erik.tuomy Text Box Record Drawings erik.tuomy
02/20/13
| | | | | | | | |42 3 5 6 7 8 9
PARTITION TYPES PARTITION NOTES WALL LEGEND
STRUCT STRUCT STRUCT STRUCT STRUCT STRUCT STRUCT STRUCT STRUCT STRUCTC I
X I I
LEAKAGE)CLG SIDE OF METAL STUDSEACH
CLG CLG CLG CLG CLG CLG CLG CLG4" MTL STUDS @ 16"
i +CONTANGLEXF B PARTITION U.N.O.TYPEHCO 11-2"—a— 5/8" GYP BD.(2) LAYERS 5/8" GYP BD. 14----- (2) LAYERS 5/8" CMU*EA. SIDE GYP BD.
1 I —------ 4" MASONRY
H 2 LAYERS2 HOUR FIREVENEERT'SHAFT LINER 1" SHAFT LINER 4 5/8 [5 5/8 1/4' 5/8" GYP. BD. 5/8” GYPSUM BOARD atiiA AL A y SIDE OF METAL STUDSo EACHZZZ II3 । ।r=II RESESSED BASE AT
B PARTITION U.N.O.SECURITY WALLS* A TYPEX’X(O LI ’ XFIRE SEALANT FIRE SEALANTL 1 I-FLR FLR FLR FLR FLR FLR FLR. FLR FLR. 1 HR FIREL- 4-
CLG 7
1 HR SHAFTWALL 04 E8 MISC FURRING G4A4 B4 2HR SHAFTWALL D4 H4 J4 K4TYPICAL 2HR RATED LEAD LINED LEAD LINED LEAD LINED 2 HR SMOKE A4WALL WALL WALLA. NON-RATED STC: 40 (49 W/ 3" SAB) A. NON-RATED STC: 43 (56 W/ 3" SAB) 7NON-RATED —X
PARTITION "A"8 1 HR FIRE .CHASESr-o 1/4" TYPICAL DEFAULT
TYPE A PARTITION U.N.O.PARTITIONyA. NON-RATEDCL FLR PARTITION "FLAG" LEGEND EXAMPLE FLOOR PLAN - PARTITION IDENTIFICATION7 I
O 3 1/8" 1 1/2" 1 LAYER1 HOUR FIREO 3. PROVIDE DEFLECTION TRACKS OR CLIPS FOR ALL PARTITIONS ABUTTING STRUCTURE ABOVE.
F8 5/8” GYPSUM BOARD atCMUH
SIDE OF METAL STUDS4. EACH
A PARTITION U.N.O.TYPE
INTERIOR METAL STUD PARTITIONS ARE DIMENSIONED FROM FACE OF STUD UNLESS NOTED OTHERWISE.5.
6. WALLS TO RECEIVE SOUND ATTENUATION BLANKETS (SAB-3") ARE IDENTIFIED ON THE PLANS WITH APROVIDE SOUNDoO
B B(O
C GA B D E F H J K 7. SIDE OF METAL STUDSEACH
A PARTITION U.N.O.TYPE8. PRIORITY 5CO-09N
9. CONSTRUCT ALL RATED CORRIDOR WALLS TO RESIST THE PASSAGE OF SMOKE. I.E., TO BE SMOKE TIGHT.
1 LAYERFULL HEIGHT
10. REFER TO PLUMBING CHASE SCHEDULE THIS SHEET FOR DEFAULT CHASE WIDTH DIMENSIONS.STUD SIZE SUFFIX / WIDTH CHART STUD SIZE SUFFIX / WIDTH CHART STUD SIZE SUFFIX I WIDTH CHART STUD SIZE SUFFIX I WIDTH CHART STUD SIZE SUFFIX / WIDTH CHART STUD SIZE SUFFIX / WIDTH CHART STUD SIZE SUFFIX / WIDTH CHART STUD SIZE SUFFIX I WIDTH CHART STUD SIZE SUFFIX I WIDTH CHART STUD SIZE SUFFIX I WIDTH CHART
11. REFER TO GYPSUM BOARD SCHEDULE THIS SHEET AND SUBSTITUTE OTHER BOARD MATERIALS WHERE NOTED.
SUFFIX STUD SIZE TOTAL WIDTH SUFFIX STUD SIZE TOTAL WIDTH SUFFIX STUD SIZE TOTAL WIDTH SUFFIX STUD SIZE TOTAL WIDTH SUFFIX STUD SIZE TOTAL WIDTH SUFFIX STUD SIZE TOTAL WIDTH SUFFIX STUD SIZE TOTAL WIDTH SUFFIX STUD SIZE TOTAL WIDTH SUFFIX STUD SIZE TOTAL WIDTHSUFFIX BLOCK WIDTH 12.
DEFAULT PARTITIONE8 PRIORITY 6 TYPE A PARTITION U.N.O.
13. PROVIDE DOUBLE STUDS @ EACH DOOR & WINDOW JAMB. STUD GAUGE AND SIZE TO MATCH WALL STUD GAUGE AND SIZE.
C2 2 1/2" 3 1/8" D2 2 1/2" 3 1/4" G2 2 1/2" 3 1/8"O
14. METAL STUD FRAMING: MIN. 18 GAUGE @ 16" O.C., U.N.O.
II
A3 4 7/8" B3 61/8" C4 DEFAULT PARTITION D4 DEFAULT PARTITION F8 DEFAULT PARTITION G33 5/8" 3 5/8" 3 5/8" 4 1/4" 15. BLOCKING: PROVIDE 16 GAUGE SHEET METAL STRAP BLOCKING FOR ALL WALL MOUNTED ITEMS, U.N.O.
O 16.DEFAULT PARTITION DEFAULT PARTITION DEFAULT PARTITIONDEFAULT PARTITION DEFAULT PARTITION C6 6" 6 5/8" D6 6" 7 1/4" G4A4 B4 H4 J4 DEFAULT PARTITION K4 o A6 6" 7 1/4" B6 6" 81/2" G6 H6 6" SEE P.R. J6 6" SEE P.R. K6 6" SEE P.R.6" 6 5/8" 17. PRIORITY 7 TYPE M PARTITION U.N.O.O
9 1/4" 10 1/2" SEE P.R. SEE P.R. SEE P.R.A8 8" B8 8" H8 8" J8 8" K8 8" 18. UL DESIGN NUMBERS REFER TO THE UNDERWRITERS LABORATORIES FIRE RESISTANCE DIRECTORY - 2006 ADDITIONo
C STRUCT STRUCT STRUCT STRUCT STRUCT STRUCT STRUCT STRUCT STRUCT STRUCT 177 c19.- .3 IE* W WP W W W W ) (WT T
FIRE1 “'I 20.
21. REFER TO SHEET AE-5105 FOR TYPICAL SHAFT WALL DETAILS.4" MTL STUDS @16"CLG CLG CLGCONT ANGLE CONT ANGLE CONT ANGLE CONTANGLE
X ■ —o ----or.---- —O.C.------------ 22. REFER TO SHEET AE-5401 FOR TYPICAL HEAD WALL AND SILL DETAILS.CO co co
5/8" GYP BD. EA. SIDEO I J
—— (3) LAYERS 5/8" GYP BD. 5/8" GYP BD. EA. SIDE *
INDICATESEXTERIOR STUDEA. SIDE>II 1 X-I— LEAD LINED GYP BD. II
16" ‘k_X sk5/8" GYP. BD. 5/8" GYP. BD. 5/8" GYP. BD. 5/8" GYP. BD.A L2NX R k XAI0)
. V VV
FIRE SEALANT
FLR. FLR FLR FLR FLR
CLG CLG CLG CLG -o T_ X04L4 M4 N4 — - X U4TYPICAL TYPICAL TYPICALLEAD LINED TYPICAL
WALL XGROUTED CMU GROUTED CMU GROUTED CMU
V X GROUTED CMU7 5/8'III 1'-21/4"A. NON-RATED STC: 55
A. NON-RATED A. NON-RATEDD D6$ $
CL FLR FLR FLR FLR$
FLR
OO 3 1/8"Q8 S8R8 T8CMU CMU CMU CMUP8CMUO
O
C.1 HR RATED UL #U493 STC: 55
II
O
1 5/8" ABUSE RESISTANT GYP BOARD
O
0 Q SL M N P R T UOO
o
\CO-09N
STUD SIZE SUFFIX / WIDTH CHART STUD SIZE SUFFIX / WIDTH CHART STUD SIZE SUFFIX I WIDTH CHART STUD SIZE SUFFIX I WIDTH CHART STUD SIZE SUFFIX I WIDTH CHART STUD SIZE SUFFIX / WIDTH CHART STUD SIZE SUFFIX / WIDTH CHART STUD SIZE SUFFIX I WIDTH CHART STUD SIZE SUFFIX I WIDTH CHART STUD SIZE SUFFIX I WIDTH CHART
] SUFFIX STUD SIZE TOTAL WIDTH SUFFIX STUD SIZE TOTAL WIDTH SUFFIX STUD SIZE TOTAL WIDTH SUFFIX STUD SIZE TOTAL WIDTH SUFFIX STUD SIZE TOTAL WIDTH SUFFIX SUFFIX STUD SIZE TOTAL WIDTH SUFFIX STUD SIZE TOTAL WIDTH SUFFIX STUD SIZE TOTAL WIDTHSUFFIX BLOCK WIDTH BLOCK WIDTH(O 5/8" ]- O
E ]O
(O ]
II
] DEFAULT PARTITIONM3 4 7/8" N3 8 1/2" 03 4 7/8" P8 DEFAULT PARTITION Q8 DEFAULT PARTITION R8 DEFAULT PARTITION S8 DEFAULT PARTITION T8 DEFAULT PARTITION U43 5/8" 3 5/8" 3 5/8"
COO ]
DEFAULT PARTITIONL4 M4 N4 04 R12 12"DEFAULT PARTITION DEFAULT PARTITION DEFAULT PARTITION
BASE DETAILL6 6" SEE P.R. M6 6" 7 1/4" N6 6" 13 1/4" 06 6" 7 1/4"] CO-09N1] 6”=T-O”SEE P.R. 9 1/4" 08 9 1/4"L8 8" M8 8" 8" o
GYP BOARD SCHEDULE PARTITION INTERSECTIONSPLUMBING CHASE SCHEDULE
--------a—— —----------------------------- I WAED A Ac LEGENDWATER CLOSETS URINALS LAVATORIES EWC 5/8" TYPE "X" ALL PARTITIONS U.N.O. BELOW OR SHOWN OTHERWISE 5/8" TYPE "X" ALL PARTITIONS U.N.O. BELOW OR SHOWN OTHERWISE
5/8" ABUSE RESISTANT (CATEGORY 3) PRIORITY 7
CLG 8" 1-2" 1-8" 1-10" T-2" 8" T-2"Q (O -TH +— 1F i
5/8" ABUSE RESISTANT (CATEGORY 4)CROSS BRACINGc I I I FIII 4 4 i c \CO-09N fl
PRIORITY 1
PRIORITY 244 1/2" FIBER CEMENTO Io
I I CONTRACT DOCUMENTSFIRE SEALANT
—__ L FULLY SPR PRIORITY 6INKLERED
O
Project TitleARCHITECT/ENGINEERSKEY PLANC CONSULTANTS New VA Medical CenterII ■
Phase IV Building NumberScitO o .osteRe07% Management.O, Approved: Project Director Drawing Number:73 Z.:.1550O
J M A ARCHITECTURE ) Sc
GI-0311 E.= to 07/08/11 CheckedDate DrawnSYSKA HENNESSY GROUP, 425 CALIFORNIA STREET, SUITE 700, SAN FRANCISCO, CA 94104 A Joint VentureO
O CC June 5, 2008 RE Dwg. 255 of 2149O JR o
VA FORM 08-6201, OCT 1978
I I I I I I I I2 3 4 5 6 7 8 9
Office of Facilities
Department of Veterans Affairs
VENEER
ANCHORS
PRIORITY 1: PARTITIONS EXPOSED DIRECTLY TO RUNNING WATER ALSO SCHEDULED
TO RECEIVE TILE SUCH AS CART WASH, BATHTUBS, SHOWERS, HYDROTHERAPY, ETC
0) — O
RESESSED BASE AT
SECURITY WALLS*
RESESSED BASE AT
‘SECURITY WALLS*
C.1HR RATED UL#U419
STC: 40 (49 W/3" SAB)
ROOM
NAME
I XXXX I
C.1HR RATED UL#U419
STC: 40 (49 W/3" SAB)
FIRE SEALANT
BOTH SIDES (NO
AIR LEAKAGE)
4" CH STUDS
C. 2HR RATED UL#U419
STC: 43 (56 W/3" SAB)
SINGLE
SIDE
FLOOR
MOUNTED
B. NON-RATED SMOKE
RESISTANT STC: 55
FIRE SEALANT
BOTH SIDES (NO
AIR LEAKAGE)
4" CH STUDS
FIRE SEALANT -
TYP. (NO AIR
ROOM
NAME
| xxxx |
ROOM
NAME
I xxxx
ROOM
NAME
I xxxx |
C.1 HR RATED UL#U419
STC: 40 (49 W/ 3" SAB)
ROOM
NAME
xxxx |
MORTAR
JOINT
T. Csk D.
O Q
2 1/2" HAT
CHANNELS
MORTAR
JOINT
PRIORITY 2: USE AT ALL TOILET ROOMS, HOUSEKEEPING/JANITOR CLOSETS,
SOILED UTILITY ROOMS. NOTE THAT MWFA RESISTANT GYPSUM BOARD AND/OR
FIBER CEMENT TAKE PRECEDENT OVER MOISTURE RESISTANT (GREEN ROCK)
C.2HR RATED UL#U419
STC: 43 (56 W/3" SAB)
ROOM
NAME
I xxxx |
"FLAGGED
PARTITION
TYPE SYMBOLo
O
O o o O
DOUBLE
SIDE
FLOOR
MOUNTED
MORTAR
JOINT
PAINTED WOOD BASE (MATCH DOOR FRAMES),
SCREWED TO BACKING AND METAL STUDS
o O
MASONRY
VENEER
Location North Las Vegas, NV
0) Q
SEALANT
(NO AIR
LEAKAGE)
MORTAR
JOINT
c c
O O
O O
CO-09N (Mental Health Unit Revisions) Amendment 0001 Revisions:
CORRIDOR
SIDE
5/8" MOLD, WATER, FIRE &
ABUSE (MWFA) RESISTANT
GYPSUM BOARD
MORTAR
JOINT
FIRE SEALANT
(NO AIR LEAKAGE)
O O
LU
Q
LU
Q i i i i I I
I I
I I
5/8" ABUSE RESISTANT
GYPSUM BOARD
5/8" ABUSE & FIRE
RESISTANT GYPSUM BOARD
FIRE
SEALANT
FIRE
SEALANT
I I
I I I I
I I I I
I I I I
SINGLE
SIDE
WALL
MOUNTED
FIRE
SEALANT
DOUBLE
SIDE
WALL
MOUNTED
FIRE
SEALANT
2-1/2" STUDS
@16"0.C.
Q
LU
FIRE
SEALANT
0) O
HIGHEST
ADJ. CLG _
FIRE
SEALANT
MISC FURRING AT NON-RATED
CHASESAND FURROUTS
FIRE
SEALANT
Q
LU
I I
LA
I
8" METAL
STUDS
1/2" EXTERIOR
GYPSUM
BOARD
O
LU
WALL
MOUNTED
WALL
MOUNTED
Q
LU
8” METAL STUDS with 1
LAYER 5/8” GYPSUM BOARD
ot INTERIOR SIDE
NOTE: HIGHER PRIORITY PARTITIONS TAKE PRECEDENCE OVER PARTITIONS WITH A LOWER
PRIORITY.
I I I I
WALL
MOUNTED
D. SEE PHYSICISTS REPORT FOR
LEAD THICKNESS
D. SEE PHYSICISTS REPORT FOR
LEAD THICKNESS
NON-RATED PARTITIONS SHALL HAVE SEALANTS AT THE HEAD, SILL, THROUGH PENETRATIONS, OPENINGS AND
JUNCTURES WITH DISSIMILAR MATERIALS
FIRE/SMOKE SEALANTAS REQUIRED
FOR UL WALL ASSEMBLY
O O
WALL
MOUNTED
D. SEE PHYSICISTS REPORT FOR
LEAD THICKNESS
C. EXPANDED MTL SHALL BE
SPOT WELDED EVERY 6" TO
VERTICAL AND HORIZONTAL
MTL SUPPORTS
BATT INSULATION
WHERE OCCURS
TYPICAL
3/4"x9GA. EXPANDED
MTL MESH @ PUBLIC
CORRIDOR SIDE
FIRE SEALANT
ATTENUATION BLANKETS IN ALL EXAM AND TREAMENT ROOM, ALL RESTROOMS, ALL PATIENT ROOMS, STAFF LOUNGES, AND ALL CONFERENCE ROOMS.
WHERE THICKNESS VARIES BETWEEN TWO PARTITIONS IN AN UNINTERRUPTED CONTINUOUS WALL PLANE - OFFSET
STUDS AND ALIGN FACE OF PARTITIONS. REF. TO PARTITION INTERSECTIONS.
NOTE THAT ONLY PARTITIONS
OTHER THAN TYPE M4 OR THAT
VARY FROM THE GRAPHICAL
DEFAULT PARTITIONS ARE
FLAGGED
6" FLAT-STRAP BACKING, ATTACH ABOVE
BASE IN ORDER TO MINIMIZE WARPING OF BASE
3 1/16" TALL PREFORMED EXTRUDED
ALUMINUM WALL BASE. SOFTFORMS
SWB-300-8 OR COMPARABLE
Q O
C. SEE PHYSICISTS REPORT FOR
LEAD THICKNESS
BATT INSULATION
WHERE
OCCURS-TYPICAL
* NOTE: PROVIDE CATEGORY #3, NO TEXTURE,
IMPACT RESIST GYP BOARD AT LVL 2 HIGH
SECURITY AREAS. REFER TO SHEETS AD-1102E-R
AND AD-1102H-R FOR LOCATIONS, EXCEPT AT THE
FOLLOWING LOCATIONS PROVIDE CATEGORY #4;
SECLUSION ROOMS (2E201,202,203,204,205,206)
A. 1 HR RATED UL#U415
SYSTEM A STC: 43 (56 W/3"
SAB)
A.2HRRATED UL #U415
SYSTEM B STC: 43 (56 W/3"
SAB)
5/8" MOISTURE RESISTANT
(GREEN ROCK)
USE TO A HEIGHT OF 4 FEET A.F.F. IN DIETETICS, CANTEEN SERVERY, AND WAREHOUSE. NOTE THAT
ABUSE AND FIRE RESISTANT GYPSUM BOARD AND/OR MWFA RESISTANT GYPSUM BOARD WHERE
INDICATED OR NECESSARY TO MEET REQUIRED RATING OR INSTALLATION CONDITIONS TAKE
PRECEDENT OVER ABUSE RESISTANT GYPSUM BOARD.
USE WHERE INDICATED OR NECESSARY TO MEET REQUIRED RATING OF
WALL OR INSTALLION CONDITIONS.
2. LINE OF "STRUCTURE" AS SHOWN AT PARTITION TYPE HEAD CONDITIONS IS DIAGRAMMATIC ONLY AND DOES NOT INDICATE EXACT CONSTRUCTION CONDITIONS. OFFSET PARTITION CONSTRUCTION AS NECESSARY TO EXTEND WALL TO DECK ABOVE
& SEAL AS SHOWN.
FIRE RATED PARTITIONS SHALL HAVE FIRESTOP SEALANTS AT THE HEAD, SILL, THROUGH PENETRATIONS, OPENINGS AND
JUNCTURES WITH DISSIMILAR MATERIALS
REFER TO SHEETS GI-0321 THRU GI-3028 FOR TYPICAL HEAD WALL DETAILS (RATED & NON-RATED). SEE SHEET AE-5410 FOR
ADDITIONAL WALL HEAD DETAILS.
SMOKE PARTITION - 1 LAYER
5/8” GYPSUM BOARD at
(2) LAYERS 5/8" GYP BD.
EA. SIDE
07-08-08 Date
B. NON-RATED SMOKE
RESISTANT STC: 43 (56 W/ 3" SAB)
A. CLASS III BALLISTIC LEVEL RATED
UL STANDARD 752
UL #905 Ɵ
STC: 48
PRIORITY 1: PROVIDE BEHIND ALL "WET WALL" PARTITIONS WITH PLUMBING
FIXTURES (EWC'S, TOILETS, LAVATORIES, URINALS, ETC) TO A HEIGHT OF 4
FEET A.F.F. & EXTEND 4 FEET FROM EACH SIDE OF THE FIXTURE (8' TOTAL WIDTH)
A. CLASS III BALLISTIC
LEVEL RATED UL STANDARD
752 UL#910ǭ STC: 48
A. NON-RATED STC: 43 (56
W/3"SAB)
B. CLASS III BALLISTIC LEVEL RATED
UL STANDARD 752 UL #910 & #493
STC: 48
USE 4" 18 GAUGE STUDS FOR TYPICAL FLOORS. USE 4" 16 GAUGE STUDS FOR 21'-0" FLOOR TO FLOOR SPANS AND 21'-4"
FLOOR TO FLOOR SPANS AT THE BASEMENT AND 4TH FLOOR RESPECTIVELY.
TYPICAL WALL - 1 LAYER
5/8” GYPSUM BOARD at
EACH SIDE OF METAL STUDS
TO 6” ABOVE HIGHEST
ADJACENT CEILING
* NOTE: PROVIDE CATEGORY #3, NO TEXTURE,
IMPACT RESIST GYP BOARD AT LVL 2 HIGH
SECURITY AREAS. REFER TO SHEETS AD-1102E-R
AND AD-1102H-R FOR LOCATIONS, EXCEPT AT THE
FOLLOWING LOCATIONS PROVIDE CATEGORY #4;
SECLUSION ROOMS (2E201,202,203, 204,205, 206)
ONE SIDE (SEE
PHYSICIST REPORT FOR
LEAD THICKNESS)
* NOTE: PROVIDE CATEGORY #3, NO TEXTURE,
IMPACT RESIST GYP BOARD AT LVL 2 HIGH
SECURITY AREAS. REFER TO SHEETS AD1102E-R
AND AD-1102H-R FOR LOCATIONS, EXCEPT AT THE
FOLLOWING LOCATIONS PROVIDE CATEGORY #4;
SECLUSION ROOMS (2E201,202,203, 204,205, 206)
G.C. WALLACE, INC., 1555 RAINBOW BLVD., LAS VEGAS, NV 89146
SYSKA HENNESSY GROUP, 11500 W. OLYMPIC BLVD. SUITE 680, LOS ANGELES, CA 90064
LASALLE ENGINEERING, LLC, 630 FITZWATERTOWN RD. SUITE AI, WILLOW GROVE, PA 19090
RTKL HEALTHCARE TECHNOLOGIES, 1250 CONNECTICUT AVE., NW, WASHINGTON, DC 20036
DEGENKOLB ENGINEERING, 235 MONGOMERY STREET., SUITE 500, SAN FRANCISCO, CA 94104
CULINARY ADVISORS, 3734 CROSSBOW CT., ELLICOTT CITY, MD 21042
NINYO AND MOORE, 3155 E. PATRICK LANE, SUITE 12, LAS VEGAS, NV 89120
RTKL SPECIAL SYSTEMS GROUP, 1250 CONNECTICUT AVE., NW, WASHINGTON, DC 20036
5/8" GYP BD. EA.
SIDE
A. CLASS III BALLISTIC
LEVEL RATED UL STANDARD
752 UL#910ǭ STC: 48
A. CLASS III BALLISTIC LEVEL RATED
UL STANDARD 752
STC: 48
B. NON-RATED SMOKE
RESISTANT STC: 40 (49 W/ 3"SAB)
(2) LAYERS 5/8" GYP
BD. EA. SIDE
LEAD LINED GYP BD.
EA. SIDE (SEE
PHYSICIST REPORT
FOR LEAD THICKNESS)
USE UP TO CEILING LEVEL AT LOCATIONS INDICATED ON SHEETS AD-1102E-R AND AD-1102H-R THAT
HAVE GYP BOARD CEILINGS AND 4" BELOW ANY LAY-IN TYPE CEILINGS. PERFORMANCE LEVEL
DEFINED BY USG TESTING; ABRASION = 100 CYCLES, INDENTATION = .1 IN., HARD BODY IMPACT = 80
FT-LBS, SOFT BODY IMPACT = 210 FT-LBS.
B. NON-RATED SMOKE
RESISTANT STC: 40 (49 W/ 3" SAB)
5/8" GYP BD.
FIRE
SEALANT-
IDENTIFY ALL RATED PARTITIONS WITH LABELS LOCATED 6" ABOVE THE CEILING AT MAX. 10'-O" O.C. WITH 1 1/2" HIGH LETTERS, CLEARLY LEGIBLE & BRIGHTLY INDICATED AGAINST A CONTRASTING BACKGROUND.
CMU WALL - 8x8x16 OR 4x8x16 VENEER
B. NON-RATED SMOKE
RESISTANT STC: 43 (56 W/ 3" SAB)
B. 1HR RATED FIRE/SMOKE BARRIER
UL#U419STC: 40 (49 W/3" SAB)
GI-0311
A. CLASS III BALLISTIC LEVEL RATED
UL STANDARD 752
STC: 48
USE UP TO CEILING LEVEL AT LOCATIONS INDICATED ON THIS SHEET AS A NOTE FOR WALL TYPES A, B AND M. (INDICATED WITH AN ‘ DESIGNATION). PERFORMANCE LEVEL DEFINED BY USG TESTING;
ABRASION = 500 CYCLES, INDENTATION = .08 IN., HARD BODY IMPACT = 110 FT-LBS, SOFT BODY
IMPACT = 300 FT-LBS.
B. NON-RATED SMOKE
RESISTANT STC: 43 (56 W/ 3" SAB)
LEAD LINED GYP BD.
EA. SIDE (SEE
PHYSICIST REPORT
FOR LEAD THICKNESS)
PROVIDE THE PROPER PROTECTION FOR ALL PENTRATIONS THRU RATED PARTITIONS. REFER TO UL ASSEMBLIES BEGINNING
ON SHEET GI-0321.
EXTEND RATED PARTITIONS THROUGH THE INTERIOR FACE OF EXTERIOR WALL GYPSUM BOARD AND SEAL TO THE INSIDE FACE OF THE EXTERIOR BUILDING WALL SHEATHING. REFER ALSO TO PARTITION INTERSECTION DRAWING BELOW. REFER
ALSO TO 10/AE 5104.
2 HOUR SMOKE - 2 LAYERS
5/8” GYPSUM BOARD at
5/8” GYPSUM BOARD at
EACH SIDE OF METAL STUDS
TO UNDERSIDE OF
STRUCTURE ABOVE
GI-0311
FIRE SEALANT (NO AIR
LEAKAGE)
7/8" HAT
CHANNELS @16"
O.C.
O.C.
(2) LAYERS 5/8" GYP
BD.
LEAD LINED GYP BD.
ONE SIDE (SEE
PHYSICIST REPORT
FOR LEAD THICKNESS)
1 HOUR SMOKE BARRIER -
1 LAYER 5/8” GYPSUM
BOARD at EACH SIDE OF
METAL STUDS
NON RATED
STC: 52 W/3" SAB
FIRE SEALANT
(NO AIR
LEAKAGE)
Drawing Title
Partition Types
SUFFIX "4" -
(STUD SIZE)
A. CLASS III BALLISTIC LEVEL RATED
UL#U905
STC: 48
FIRE SEALANT
(NO AIR
LEAKAGE)
Q
LU
2HR FIRE-RATED
UL#420
STC: 52 W/ 3" SAB
GI-0311
FIRE SEALANT
(NO AIR
LEAKAGE)
Q
LU
A. NON-RATED STC: 43 (56
W/ 3" SAB)
2HR FIRE-RATED
UL#420
STC: 52 W/3" SAB
4" MTL STUDS @16"
O.C.
4" MTL STUDS @
O.C.
A. NON-RATED STC: 40 (49
W/ 3" SAB)
A. NON-RATED STC: 40 (49
W/ 3" SAB)
-FIRE SEALANT
(NO AIR
LEAKAGE)
4" MTL STUDS @16"
OT.
3) LAYERS 5/8" GYP BD.
EA. SIDE
A. NON-RATED STC: 40 (49
W/ 3"SAB)
FIRE SEALANT
BOTH SIDES (NO
AIR LEAKAGE)
4" MTL STUDS @16"
O.C.
FIRE SEALANT
(NO AIR
LEAKAGE)
4" MTL STUDS @16"
FIRE SEALANT
(NO AIR
LEAKAGE)
FIRE SEALANT
(NO AIR
LEAKAGE)
7/8" HAT
CHANNELS @ 16"
O.C.
7/8" HAT
CHANNELS @16"
or
FIRE SEALANT
(NO AIR
LEAKAGE)
FIRE SEALANT
BOTH SIDES (NO
AIR LEAKAGE)
4" MTL STUDS @@16"
O.C.
FIRE SEALANT
(NO AIR
LEAKAGE)
FIRE SEALANT
(NO AIR
LEAKAGE)
7/8" HAT
CHANNELS @16"
O.C.
CIVIL:
MEP:
LIFE SAFETY:
MEDICAL EQUIP. PLANNING:
STRUCTURAL:
FOOD SERVICE:
GEOTECHNICAL:
TELECOM/SECURITY:
VERTICAL TRANSPORTATION/
MATERIALS MANAGEMENT:
o o
7/8" HAT
CHANNELS @16"
O.C.
GROUTED CMU
VARIES
SEE SCHEDULE
O C o
1. FOR ALL PARTITIONS SHOWN ON FLOOR PLANS WITHOUT "FLAG" SYMBOLS OR GRAPHICALLY INDICATED, ASSUME TO BE TYPE M4 PARTITION - REFER TO "PLAN GRAPHIC" ON THE PARTITION TYPES LEGEND, THIS SHEET, FOR RATED PARTITIONS
GRAPHICALLY INDICATED.
Project Number
593-202
K
O
HIGHEST
ADJ. CLG
5/8" GYP BD. EA. SIDE
II
N
II
Scale:
As shown
L
P
. XK X K
I I
I I i
T I I I I
T I I I I
T I I I I
T I I I
O
V . V
O C O
1-2" n
T l l I
V ■
FIRE SEALANT
(NO AIR
LEAKAGE)
4" MTL STUDS @16"
----or----------
O C o
PRIORITY 1
UL
#415/419
—— 7/8" HAT
_ CHANNELS @ 16"
O.C.
T.
Lx
PRIORITY 4
UL
#415/419
PRIORITY 3
UL
#415/419
U S s!
c V O
5 OT
C
PRIORITY 2
UL
#415/419
O c o U V
OT
C o
I I
M C
I I
“WcaECG-onN!"
T I I I
T.
Li F I
T I I I I
—4— 5/8" GYP BD.
ONE SIDE
RTKL
FIRE SEALANT
(NO AIR
LEAKAGE)
4" MTL STUDS @16"
----- or.-------------
GROUTED CMU
9 1/8"
MORTAR JOINT
—4"x16 GA. MTL STUDS @16" or
£36 1/2
C.
5/8" GYP BD. EA. SIDE *
10 3/4"
LaLd
I
I
I
I erik.tuomy Text Box Record Drawings erik.tuomy
02/20/13
VHALASKentoW Contractor
VHALASKentoW Contractor Typical for Exam room Doors
| GI-0301 Project I |
| AE-1102 C |
| AE-1102 F |
| AE-1103 C |
| AE-1103 F |
| AE-1203C |
| AE-1203F |
| 593.2202.1AF-1102C |
| 593.2202.1AF-1102F |
| 593.2202.1AF-1103C |
| 593.2202.1AF-1103F |
| EP-1103 C |
| EP-1103 F |
| GI-0311 Partition |
| PL-605 H |
| PL-605 J |
| PL-606 H |
| PL-606 J |
| PL-1103 C |
| PL-1103 F |
| PP-1103 C |
| PP-1103 F |
| FA-103C |
| TH-0001 |
| TH-1103C |
| TH-1103F |
| Door Hardware Set |