Attachment Combined Existing As-Builts.pdf

PDF 25 MB Posted

Attached to
Z2DA--Install Sinks Outpatient Surgery Project No. 593-26-305 VAMC Las Vegas, NV
Solicitation number
36C26126R0020_2
Issued by

About this file

This is an architectural drawing document that provides comprehensive partition type specifications and construction details for the New VA Medical Center Phase IV Building in North Las Vegas, Nevada. The drawing, dated June 5, 2008, establishes standardized partition classifications (Types A through U) with corresponding construction requirements including stud sizes, gypsum board specifications, fire ratings, sound transmission ratings (STC), and material compositions. The document specifies partition priorities based on functional requirements, such as Priority 1 partitions for wet wall areas with plumbing fixtures requiring moisture-resistant materials, Priority 2 for toilet rooms and utility closets, and progressively lower priorities for standard construction areas. Key construction standards include metal stud framing at minimum 18 gauge with 16-inch on-center spacing, various gypsum board configurations ranging from single to triple layers, fire-sealant requirements for rated partitions, and specialized materials such as lead-lined gypsum board for radiation protection areas and abuse-resistant gypsum board for high-security areas including seclusion rooms.

The document includes detailed partition intersection guidance, plumbing chase schedules, and cross-bracing specifications, along with references to complementary drawing sheets (AE-5105, AE-5410, GI-0321 through GI-3028) for typical head wall, sill, and shaft wall details. Fire-rated partitions are designated with UL assembly numbers such as UL#U419, UL#U415, and UL#U493, with ratings ranging from 1-hour to 2-hour fire resistance. Specific notations address construction conditions in exam rooms, treatment areas, restrooms, patient rooms, staff lounges, and conference rooms, with requirements for sound attenuation blankets in designated spaces. The document was prepared by SYSKA HENNESSY GROUP in collaboration with multiple consulting firms including RTKL, LaSalle Engineering, Degenkolb Engineering, and others, with construction managed by G.C. Wallace, Inc. in Las Vegas.

View the file

Other files

Show all 23

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

erik.tuomy Text Box Record Drawings erik.tuomy

02/20/13

| | | | | | | | |42 3 5 6 7 8 9

PARTITION TYPES PARTITION NOTES WALL LEGEND

STRUCT STRUCT STRUCT STRUCT STRUCT STRUCT STRUCT STRUCT STRUCT STRUCTC I

X I I

LEAKAGE)CLG SIDE OF METAL STUDSEACH

CLG CLG CLG CLG CLG CLG CLG CLG4" MTL STUDS @ 16"

i +CONTANGLEXF B PARTITION U.N.O.TYPEHCO 11-2"—a— 5/8" GYP BD.(2) LAYERS 5/8" GYP BD. 14----- (2) LAYERS 5/8" CMU*EA. SIDE GYP BD.

1 I —------ 4" MASONRY

H 2 LAYERS2 HOUR FIREVENEERT'SHAFT LINER 1" SHAFT LINER 4 5/8 [5 5/8 1/4' 5/8" GYP. BD. 5/8” GYPSUM BOARD atiiA AL A y SIDE OF METAL STUDSo EACHZZZ II3 । ।r=II RESESSED BASE AT

B PARTITION U.N.O.SECURITY WALLS* A TYPEX’X(O LI ’ XFIRE SEALANT FIRE SEALANTL 1 I-FLR FLR FLR FLR FLR FLR FLR. FLR FLR. 1 HR FIREL- 4-

CLG 7

1 HR SHAFTWALL 04 E8 MISC FURRING G4A4 B4 2HR SHAFTWALL D4 H4 J4 K4TYPICAL 2HR RATED LEAD LINED LEAD LINED LEAD LINED 2 HR SMOKE A4WALL WALL WALLA. NON-RATED STC: 40 (49 W/ 3" SAB) A. NON-RATED STC: 43 (56 W/ 3" SAB) 7NON-RATED —X

PARTITION "A"8 1 HR FIRE .CHASESr-o 1/4" TYPICAL DEFAULT

TYPE A PARTITION U.N.O.PARTITIONyA. NON-RATEDCL FLR PARTITION "FLAG" LEGEND EXAMPLE FLOOR PLAN - PARTITION IDENTIFICATION7 I

O 3 1/8" 1 1/2" 1 LAYER1 HOUR FIREO 3. PROVIDE DEFLECTION TRACKS OR CLIPS FOR ALL PARTITIONS ABUTTING STRUCTURE ABOVE.

F8 5/8” GYPSUM BOARD atCMUH

SIDE OF METAL STUDS4. EACH

A PARTITION U.N.O.TYPE

INTERIOR METAL STUD PARTITIONS ARE DIMENSIONED FROM FACE OF STUD UNLESS NOTED OTHERWISE.5.

6. WALLS TO RECEIVE SOUND ATTENUATION BLANKETS (SAB-3") ARE IDENTIFIED ON THE PLANS WITH APROVIDE SOUNDoO

B B(O

C GA B D E F H J K 7. SIDE OF METAL STUDSEACH

A PARTITION U.N.O.TYPE8. PRIORITY 5CO-09N

9. CONSTRUCT ALL RATED CORRIDOR WALLS TO RESIST THE PASSAGE OF SMOKE. I.E., TO BE SMOKE TIGHT.

1 LAYERFULL HEIGHT

10. REFER TO PLUMBING CHASE SCHEDULE THIS SHEET FOR DEFAULT CHASE WIDTH DIMENSIONS.STUD SIZE SUFFIX / WIDTH CHART STUD SIZE SUFFIX / WIDTH CHART STUD SIZE SUFFIX I WIDTH CHART STUD SIZE SUFFIX I WIDTH CHART STUD SIZE SUFFIX / WIDTH CHART STUD SIZE SUFFIX / WIDTH CHART STUD SIZE SUFFIX / WIDTH CHART STUD SIZE SUFFIX I WIDTH CHART STUD SIZE SUFFIX I WIDTH CHART STUD SIZE SUFFIX I WIDTH CHART

11. REFER TO GYPSUM BOARD SCHEDULE THIS SHEET AND SUBSTITUTE OTHER BOARD MATERIALS WHERE NOTED.

SUFFIX STUD SIZE TOTAL WIDTH SUFFIX STUD SIZE TOTAL WIDTH SUFFIX STUD SIZE TOTAL WIDTH SUFFIX STUD SIZE TOTAL WIDTH SUFFIX STUD SIZE TOTAL WIDTH SUFFIX STUD SIZE TOTAL WIDTH SUFFIX STUD SIZE TOTAL WIDTH SUFFIX STUD SIZE TOTAL WIDTH SUFFIX STUD SIZE TOTAL WIDTHSUFFIX BLOCK WIDTH 12.

DEFAULT PARTITIONE8 PRIORITY 6 TYPE A PARTITION U.N.O.

13. PROVIDE DOUBLE STUDS @ EACH DOOR & WINDOW JAMB. STUD GAUGE AND SIZE TO MATCH WALL STUD GAUGE AND SIZE.

C2 2 1/2" 3 1/8" D2 2 1/2" 3 1/4" G2 2 1/2" 3 1/8"O

14. METAL STUD FRAMING: MIN. 18 GAUGE @ 16" O.C., U.N.O.

II

A3 4 7/8" B3 61/8" C4 DEFAULT PARTITION D4 DEFAULT PARTITION F8 DEFAULT PARTITION G33 5/8" 3 5/8" 3 5/8" 4 1/4" 15. BLOCKING: PROVIDE 16 GAUGE SHEET METAL STRAP BLOCKING FOR ALL WALL MOUNTED ITEMS, U.N.O.

O 16.DEFAULT PARTITION DEFAULT PARTITION DEFAULT PARTITIONDEFAULT PARTITION DEFAULT PARTITION C6 6" 6 5/8" D6 6" 7 1/4" G4A4 B4 H4 J4 DEFAULT PARTITION K4 o A6 6" 7 1/4" B6 6" 81/2" G6 H6 6" SEE P.R. J6 6" SEE P.R. K6 6" SEE P.R.6" 6 5/8" 17. PRIORITY 7 TYPE M PARTITION U.N.O.O

9 1/4" 10 1/2" SEE P.R. SEE P.R. SEE P.R.A8 8" B8 8" H8 8" J8 8" K8 8" 18. UL DESIGN NUMBERS REFER TO THE UNDERWRITERS LABORATORIES FIRE RESISTANCE DIRECTORY - 2006 ADDITIONo

C STRUCT STRUCT STRUCT STRUCT STRUCT STRUCT STRUCT STRUCT STRUCT STRUCT 177 c19.- .3 IE* W WP W W W W ) (WT T

FIRE1 “'I 20.

21. REFER TO SHEET AE-5105 FOR TYPICAL SHAFT WALL DETAILS.4" MTL STUDS @16"CLG CLG CLGCONT ANGLE CONT ANGLE CONT ANGLE CONTANGLE

X ■ —o ----or.---- —O.C.------------ 22. REFER TO SHEET AE-5401 FOR TYPICAL HEAD WALL AND SILL DETAILS.CO co co

5/8" GYP BD. EA. SIDEO I J

—— (3) LAYERS 5/8" GYP BD. 5/8" GYP BD. EA. SIDE *

INDICATESEXTERIOR STUDEA. SIDE>II 1 X-I— LEAD LINED GYP BD. II

16" ‘k_X sk5/8" GYP. BD. 5/8" GYP. BD. 5/8" GYP. BD. 5/8" GYP. BD.A L2NX R k XAI0)

. V VV

FIRE SEALANT

FLR. FLR FLR FLR FLR

CLG CLG CLG CLG -o T_ X04L4 M4 N4 — - X U4TYPICAL TYPICAL TYPICALLEAD LINED TYPICAL

WALL XGROUTED CMU GROUTED CMU GROUTED CMU

V X GROUTED CMU7 5/8'III 1'-21/4"A. NON-RATED STC: 55

A. NON-RATED A. NON-RATEDD D6$ $

CL FLR FLR FLR FLR$

FLR

OO 3 1/8"Q8 S8R8 T8CMU CMU CMU CMUP8CMUO

O

C.1 HR RATED UL #U493 STC: 55

II

O

1 5/8" ABUSE RESISTANT GYP BOARD

O

0 Q SL M N P R T UOO

o

\CO-09N

STUD SIZE SUFFIX / WIDTH CHART STUD SIZE SUFFIX / WIDTH CHART STUD SIZE SUFFIX I WIDTH CHART STUD SIZE SUFFIX I WIDTH CHART STUD SIZE SUFFIX I WIDTH CHART STUD SIZE SUFFIX / WIDTH CHART STUD SIZE SUFFIX / WIDTH CHART STUD SIZE SUFFIX I WIDTH CHART STUD SIZE SUFFIX I WIDTH CHART STUD SIZE SUFFIX I WIDTH CHART

] SUFFIX STUD SIZE TOTAL WIDTH SUFFIX STUD SIZE TOTAL WIDTH SUFFIX STUD SIZE TOTAL WIDTH SUFFIX STUD SIZE TOTAL WIDTH SUFFIX STUD SIZE TOTAL WIDTH SUFFIX SUFFIX STUD SIZE TOTAL WIDTH SUFFIX STUD SIZE TOTAL WIDTH SUFFIX STUD SIZE TOTAL WIDTHSUFFIX BLOCK WIDTH BLOCK WIDTH(O 5/8" ]- O

E ]O

(O ]

II

] DEFAULT PARTITIONM3 4 7/8" N3 8 1/2" 03 4 7/8" P8 DEFAULT PARTITION Q8 DEFAULT PARTITION R8 DEFAULT PARTITION S8 DEFAULT PARTITION T8 DEFAULT PARTITION U43 5/8" 3 5/8" 3 5/8"

COO ]

DEFAULT PARTITIONL4 M4 N4 04 R12 12"DEFAULT PARTITION DEFAULT PARTITION DEFAULT PARTITION

BASE DETAILL6 6" SEE P.R. M6 6" 7 1/4" N6 6" 13 1/4" 06 6" 7 1/4"] CO-09N1] 6”=T-O”SEE P.R. 9 1/4" 08 9 1/4"L8 8" M8 8" 8" o

GYP BOARD SCHEDULE PARTITION INTERSECTIONSPLUMBING CHASE SCHEDULE

--------a—— —----------------------------- I WAED A Ac LEGENDWATER CLOSETS URINALS LAVATORIES EWC 5/8" TYPE "X" ALL PARTITIONS U.N.O. BELOW OR SHOWN OTHERWISE 5/8" TYPE "X" ALL PARTITIONS U.N.O. BELOW OR SHOWN OTHERWISE

5/8" ABUSE RESISTANT (CATEGORY 3) PRIORITY 7

CLG 8" 1-2" 1-8" 1-10" T-2" 8" T-2"Q (O -TH +— 1F i

5/8" ABUSE RESISTANT (CATEGORY 4)CROSS BRACINGc I I I FIII 4 4 i c \CO-09N fl

PRIORITY 1

PRIORITY 244 1/2" FIBER CEMENTO Io

I I CONTRACT DOCUMENTSFIRE SEALANT

—__ L FULLY SPR PRIORITY 6INKLERED

O

Project TitleARCHITECT/ENGINEERSKEY PLANC CONSULTANTS New VA Medical CenterII ■

Phase IV Building NumberScitO o .osteRe07% Management.O, Approved: Project Director Drawing Number:73 Z.:.1550O

J M A ARCHITECTURE ) Sc

GI-0311 E.= to 07/08/11 CheckedDate DrawnSYSKA HENNESSY GROUP, 425 CALIFORNIA STREET, SUITE 700, SAN FRANCISCO, CA 94104 A Joint VentureO

O CC June 5, 2008 RE Dwg. 255 of 2149O JR o

VA FORM 08-6201, OCT 1978

I I I I I I I I2 3 4 5 6 7 8 9

Office of Facilities

Department of Veterans Affairs

VENEER

ANCHORS

PRIORITY 1: PARTITIONS EXPOSED DIRECTLY TO RUNNING WATER ALSO SCHEDULED

TO RECEIVE TILE SUCH AS CART WASH, BATHTUBS, SHOWERS, HYDROTHERAPY, ETC

0) — O

RESESSED BASE AT

SECURITY WALLS*

RESESSED BASE AT

‘SECURITY WALLS*

C.1HR RATED UL#U419

STC: 40 (49 W/3" SAB)

ROOM

NAME

I XXXX I

C.1HR RATED UL#U419

STC: 40 (49 W/3" SAB)

FIRE SEALANT

BOTH SIDES (NO

AIR LEAKAGE)

4" CH STUDS

C. 2HR RATED UL#U419

STC: 43 (56 W/3" SAB)

SINGLE

SIDE

FLOOR

MOUNTED

B. NON-RATED SMOKE

RESISTANT STC: 55

FIRE SEALANT

BOTH SIDES (NO

AIR LEAKAGE)

4" CH STUDS

FIRE SEALANT -

TYP. (NO AIR

ROOM

NAME

| xxxx |

ROOM

NAME

I xxxx

ROOM

NAME

I xxxx |

C.1 HR RATED UL#U419

STC: 40 (49 W/ 3" SAB)

ROOM

NAME

xxxx |

MORTAR

JOINT

T. Csk D.

O Q

2 1/2" HAT

CHANNELS

MORTAR

JOINT

PRIORITY 2: USE AT ALL TOILET ROOMS, HOUSEKEEPING/JANITOR CLOSETS,

SOILED UTILITY ROOMS. NOTE THAT MWFA RESISTANT GYPSUM BOARD AND/OR

FIBER CEMENT TAKE PRECEDENT OVER MOISTURE RESISTANT (GREEN ROCK)

C.2HR RATED UL#U419

STC: 43 (56 W/3" SAB)

ROOM

NAME

I xxxx |

"FLAGGED

PARTITION

TYPE SYMBOLo

O

O o o O

DOUBLE

SIDE

FLOOR

MOUNTED

MORTAR

JOINT

PAINTED WOOD BASE (MATCH DOOR FRAMES),

SCREWED TO BACKING AND METAL STUDS

o O

MASONRY

VENEER

Location North Las Vegas, NV

0) Q

SEALANT

(NO AIR

LEAKAGE)

MORTAR

JOINT

c c

O O

O O

CO-09N (Mental Health Unit Revisions) Amendment 0001 Revisions:

CORRIDOR

SIDE

5/8" MOLD, WATER, FIRE &

ABUSE (MWFA) RESISTANT

GYPSUM BOARD

MORTAR

JOINT

FIRE SEALANT

(NO AIR LEAKAGE)

O O

LU

Q

LU

Q i i i i I I

I I

I I

5/8" ABUSE RESISTANT

GYPSUM BOARD

5/8" ABUSE & FIRE

RESISTANT GYPSUM BOARD

FIRE

SEALANT

FIRE

SEALANT

I I

I I I I

I I I I

I I I I

SINGLE

SIDE

WALL

MOUNTED

FIRE

SEALANT

DOUBLE

SIDE

WALL

MOUNTED

FIRE

SEALANT

2-1/2" STUDS

@16"0.C.

Q

LU

FIRE

SEALANT

0) O

HIGHEST

ADJ. CLG _

FIRE

SEALANT

MISC FURRING AT NON-RATED

CHASESAND FURROUTS

FIRE

SEALANT

Q

LU

I I

LA

I

8" METAL

STUDS

1/2" EXTERIOR

GYPSUM

BOARD

O

LU

WALL

MOUNTED

WALL

MOUNTED

Q

LU

8” METAL STUDS with 1

LAYER 5/8” GYPSUM BOARD

ot INTERIOR SIDE

NOTE: HIGHER PRIORITY PARTITIONS TAKE PRECEDENCE OVER PARTITIONS WITH A LOWER

PRIORITY.

I I I I

WALL

MOUNTED

D. SEE PHYSICISTS REPORT FOR

LEAD THICKNESS

D. SEE PHYSICISTS REPORT FOR

LEAD THICKNESS

NON-RATED PARTITIONS SHALL HAVE SEALANTS AT THE HEAD, SILL, THROUGH PENETRATIONS, OPENINGS AND

JUNCTURES WITH DISSIMILAR MATERIALS

FIRE/SMOKE SEALANTAS REQUIRED

FOR UL WALL ASSEMBLY

O O

WALL

MOUNTED

D. SEE PHYSICISTS REPORT FOR

LEAD THICKNESS

C. EXPANDED MTL SHALL BE

SPOT WELDED EVERY 6" TO

VERTICAL AND HORIZONTAL

MTL SUPPORTS

BATT INSULATION

WHERE OCCURS

TYPICAL

3/4"x9GA. EXPANDED

MTL MESH @ PUBLIC

CORRIDOR SIDE

FIRE SEALANT

ATTENUATION BLANKETS IN ALL EXAM AND TREAMENT ROOM, ALL RESTROOMS, ALL PATIENT ROOMS, STAFF LOUNGES, AND ALL CONFERENCE ROOMS.

WHERE THICKNESS VARIES BETWEEN TWO PARTITIONS IN AN UNINTERRUPTED CONTINUOUS WALL PLANE - OFFSET

STUDS AND ALIGN FACE OF PARTITIONS. REF. TO PARTITION INTERSECTIONS.

NOTE THAT ONLY PARTITIONS

OTHER THAN TYPE M4 OR THAT

VARY FROM THE GRAPHICAL

DEFAULT PARTITIONS ARE

FLAGGED

6" FLAT-STRAP BACKING, ATTACH ABOVE

BASE IN ORDER TO MINIMIZE WARPING OF BASE

3 1/16" TALL PREFORMED EXTRUDED

ALUMINUM WALL BASE. SOFTFORMS

SWB-300-8 OR COMPARABLE

Q O

C. SEE PHYSICISTS REPORT FOR

LEAD THICKNESS

BATT INSULATION

WHERE

OCCURS-TYPICAL

* NOTE: PROVIDE CATEGORY #3, NO TEXTURE,

IMPACT RESIST GYP BOARD AT LVL 2 HIGH

SECURITY AREAS. REFER TO SHEETS AD-1102E-R

AND AD-1102H-R FOR LOCATIONS, EXCEPT AT THE

FOLLOWING LOCATIONS PROVIDE CATEGORY #4;

SECLUSION ROOMS (2E201,202,203,204,205,206)

A. 1 HR RATED UL#U415

SYSTEM A STC: 43 (56 W/3"

SAB)

A.2HRRATED UL #U415

SYSTEM B STC: 43 (56 W/3"

SAB)

5/8" MOISTURE RESISTANT

(GREEN ROCK)

USE TO A HEIGHT OF 4 FEET A.F.F. IN DIETETICS, CANTEEN SERVERY, AND WAREHOUSE. NOTE THAT

ABUSE AND FIRE RESISTANT GYPSUM BOARD AND/OR MWFA RESISTANT GYPSUM BOARD WHERE

INDICATED OR NECESSARY TO MEET REQUIRED RATING OR INSTALLATION CONDITIONS TAKE

PRECEDENT OVER ABUSE RESISTANT GYPSUM BOARD.

USE WHERE INDICATED OR NECESSARY TO MEET REQUIRED RATING OF

WALL OR INSTALLION CONDITIONS.

2. LINE OF "STRUCTURE" AS SHOWN AT PARTITION TYPE HEAD CONDITIONS IS DIAGRAMMATIC ONLY AND DOES NOT INDICATE EXACT CONSTRUCTION CONDITIONS. OFFSET PARTITION CONSTRUCTION AS NECESSARY TO EXTEND WALL TO DECK ABOVE

& SEAL AS SHOWN.

FIRE RATED PARTITIONS SHALL HAVE FIRESTOP SEALANTS AT THE HEAD, SILL, THROUGH PENETRATIONS, OPENINGS AND

JUNCTURES WITH DISSIMILAR MATERIALS

REFER TO SHEETS GI-0321 THRU GI-3028 FOR TYPICAL HEAD WALL DETAILS (RATED & NON-RATED). SEE SHEET AE-5410 FOR

ADDITIONAL WALL HEAD DETAILS.

SMOKE PARTITION - 1 LAYER

5/8” GYPSUM BOARD at

(2) LAYERS 5/8" GYP BD.

EA. SIDE

07-08-08 Date

B. NON-RATED SMOKE

RESISTANT STC: 43 (56 W/ 3" SAB)

A. CLASS III BALLISTIC LEVEL RATED

UL STANDARD 752

UL #905 &#415

STC: 48

PRIORITY 1: PROVIDE BEHIND ALL "WET WALL" PARTITIONS WITH PLUMBING

FIXTURES (EWC'S, TOILETS, LAVATORIES, URINALS, ETC) TO A HEIGHT OF 4

FEET A.F.F. & EXTEND 4 FEET FROM EACH SIDE OF THE FIXTURE (8' TOTAL WIDTH)

A. CLASS III BALLISTIC

LEVEL RATED UL STANDARD

752 UL#910&#493 STC: 48

A. NON-RATED STC: 43 (56

W/3"SAB)

B. CLASS III BALLISTIC LEVEL RATED

UL STANDARD 752 UL #910 & #493

STC: 48

USE 4" 18 GAUGE STUDS FOR TYPICAL FLOORS. USE 4" 16 GAUGE STUDS FOR 21'-0" FLOOR TO FLOOR SPANS AND 21'-4"

FLOOR TO FLOOR SPANS AT THE BASEMENT AND 4TH FLOOR RESPECTIVELY.

TYPICAL WALL - 1 LAYER

5/8” GYPSUM BOARD at

EACH SIDE OF METAL STUDS

TO 6” ABOVE HIGHEST

ADJACENT CEILING

* NOTE: PROVIDE CATEGORY #3, NO TEXTURE,

IMPACT RESIST GYP BOARD AT LVL 2 HIGH

SECURITY AREAS. REFER TO SHEETS AD-1102E-R

AND AD-1102H-R FOR LOCATIONS, EXCEPT AT THE

FOLLOWING LOCATIONS PROVIDE CATEGORY #4;

SECLUSION ROOMS (2E201,202,203, 204,205, 206)

ONE SIDE (SEE

PHYSICIST REPORT FOR

LEAD THICKNESS)

* NOTE: PROVIDE CATEGORY #3, NO TEXTURE,

IMPACT RESIST GYP BOARD AT LVL 2 HIGH

SECURITY AREAS. REFER TO SHEETS AD1102E-R

AND AD-1102H-R FOR LOCATIONS, EXCEPT AT THE

FOLLOWING LOCATIONS PROVIDE CATEGORY #4;

SECLUSION ROOMS (2E201,202,203, 204,205, 206)

G.C. WALLACE, INC., 1555 RAINBOW BLVD., LAS VEGAS, NV 89146

SYSKA HENNESSY GROUP, 11500 W. OLYMPIC BLVD. SUITE 680, LOS ANGELES, CA 90064

LASALLE ENGINEERING, LLC, 630 FITZWATERTOWN RD. SUITE AI, WILLOW GROVE, PA 19090

RTKL HEALTHCARE TECHNOLOGIES, 1250 CONNECTICUT AVE., NW, WASHINGTON, DC 20036

DEGENKOLB ENGINEERING, 235 MONGOMERY STREET., SUITE 500, SAN FRANCISCO, CA 94104

CULINARY ADVISORS, 3734 CROSSBOW CT., ELLICOTT CITY, MD 21042

NINYO AND MOORE, 3155 E. PATRICK LANE, SUITE 12, LAS VEGAS, NV 89120

RTKL SPECIAL SYSTEMS GROUP, 1250 CONNECTICUT AVE., NW, WASHINGTON, DC 20036

5/8" GYP BD. EA.

SIDE

A. CLASS III BALLISTIC

LEVEL RATED UL STANDARD

752 UL#910&#493 STC: 48

A. CLASS III BALLISTIC LEVEL RATED

UL STANDARD 752

STC: 48

B. NON-RATED SMOKE

RESISTANT STC: 40 (49 W/ 3"SAB)

(2) LAYERS 5/8" GYP

BD. EA. SIDE

LEAD LINED GYP BD.

EA. SIDE (SEE

PHYSICIST REPORT

FOR LEAD THICKNESS)

USE UP TO CEILING LEVEL AT LOCATIONS INDICATED ON SHEETS AD-1102E-R AND AD-1102H-R THAT

HAVE GYP BOARD CEILINGS AND 4" BELOW ANY LAY-IN TYPE CEILINGS. PERFORMANCE LEVEL

DEFINED BY USG TESTING; ABRASION = 100 CYCLES, INDENTATION = .1 IN., HARD BODY IMPACT = 80

FT-LBS, SOFT BODY IMPACT = 210 FT-LBS.

B. NON-RATED SMOKE

RESISTANT STC: 40 (49 W/ 3" SAB)

5/8" GYP BD.

FIRE

SEALANT-

IDENTIFY ALL RATED PARTITIONS WITH LABELS LOCATED 6" ABOVE THE CEILING AT MAX. 10'-O" O.C. WITH 1 1/2" HIGH LETTERS, CLEARLY LEGIBLE & BRIGHTLY INDICATED AGAINST A CONTRASTING BACKGROUND.

CMU WALL - 8x8x16 OR 4x8x16 VENEER

B. NON-RATED SMOKE

RESISTANT STC: 43 (56 W/ 3" SAB)

B. 1HR RATED FIRE/SMOKE BARRIER

UL#U419STC: 40 (49 W/3" SAB)

GI-0311

A. CLASS III BALLISTIC LEVEL RATED

UL STANDARD 752

STC: 48

USE UP TO CEILING LEVEL AT LOCATIONS INDICATED ON THIS SHEET AS A NOTE FOR WALL TYPES A, B AND M. (INDICATED WITH AN ‘ DESIGNATION). PERFORMANCE LEVEL DEFINED BY USG TESTING;

ABRASION = 500 CYCLES, INDENTATION = .08 IN., HARD BODY IMPACT = 110 FT-LBS, SOFT BODY

IMPACT = 300 FT-LBS.

B. NON-RATED SMOKE

RESISTANT STC: 43 (56 W/ 3" SAB)

LEAD LINED GYP BD.

EA. SIDE (SEE

PHYSICIST REPORT

FOR LEAD THICKNESS)

PROVIDE THE PROPER PROTECTION FOR ALL PENTRATIONS THRU RATED PARTITIONS. REFER TO UL ASSEMBLIES BEGINNING

ON SHEET GI-0321.

EXTEND RATED PARTITIONS THROUGH THE INTERIOR FACE OF EXTERIOR WALL GYPSUM BOARD AND SEAL TO THE INSIDE FACE OF THE EXTERIOR BUILDING WALL SHEATHING. REFER ALSO TO PARTITION INTERSECTION DRAWING BELOW. REFER

ALSO TO 10/AE 5104.

2 HOUR SMOKE - 2 LAYERS

5/8” GYPSUM BOARD at

5/8” GYPSUM BOARD at

EACH SIDE OF METAL STUDS

TO UNDERSIDE OF

STRUCTURE ABOVE

GI-0311

FIRE SEALANT (NO AIR

LEAKAGE)

7/8" HAT

CHANNELS @16"

O.C.

O.C.

(2) LAYERS 5/8" GYP

BD.

LEAD LINED GYP BD.

ONE SIDE (SEE

PHYSICIST REPORT

FOR LEAD THICKNESS)

1 HOUR SMOKE BARRIER -

1 LAYER 5/8” GYPSUM

BOARD at EACH SIDE OF

METAL STUDS

NON RATED

STC: 52 W/3" SAB

FIRE SEALANT

(NO AIR

LEAKAGE)

Drawing Title

Partition Types

SUFFIX "4" -

(STUD SIZE)

A. CLASS III BALLISTIC LEVEL RATED

UL#U905

STC: 48

FIRE SEALANT

(NO AIR

LEAKAGE)

Q

LU

2HR FIRE-RATED

UL#420

STC: 52 W/ 3" SAB

GI-0311

FIRE SEALANT

(NO AIR

LEAKAGE)

Q

LU

A. NON-RATED STC: 43 (56

W/ 3" SAB)

2HR FIRE-RATED

UL#420

STC: 52 W/3" SAB

4" MTL STUDS @16"

O.C.

4" MTL STUDS @

O.C.

A. NON-RATED STC: 40 (49

W/ 3" SAB)

A. NON-RATED STC: 40 (49

W/ 3" SAB)

-FIRE SEALANT

(NO AIR

LEAKAGE)

4" MTL STUDS @16"

OT.

3) LAYERS 5/8" GYP BD.

EA. SIDE

A. NON-RATED STC: 40 (49

W/ 3"SAB)

FIRE SEALANT

BOTH SIDES (NO

AIR LEAKAGE)

4" MTL STUDS @16"

O.C.

FIRE SEALANT

(NO AIR

LEAKAGE)

4" MTL STUDS @16"

FIRE SEALANT

(NO AIR

LEAKAGE)

FIRE SEALANT

(NO AIR

LEAKAGE)

7/8" HAT

CHANNELS @ 16"

O.C.

7/8" HAT

CHANNELS @16"

or

FIRE SEALANT

(NO AIR

LEAKAGE)

FIRE SEALANT

BOTH SIDES (NO

AIR LEAKAGE)

4" MTL STUDS @@16"

O.C.

FIRE SEALANT

(NO AIR

LEAKAGE)

FIRE SEALANT

(NO AIR

LEAKAGE)

7/8" HAT

CHANNELS @16"

O.C.

CIVIL:

MEP:

LIFE SAFETY:

MEDICAL EQUIP. PLANNING:

STRUCTURAL:

FOOD SERVICE:

GEOTECHNICAL:

TELECOM/SECURITY:

VERTICAL TRANSPORTATION/

MATERIALS MANAGEMENT:

o o

7/8" HAT

CHANNELS @16"

O.C.

GROUTED CMU

VARIES

SEE SCHEDULE

O C o

1. FOR ALL PARTITIONS SHOWN ON FLOOR PLANS WITHOUT "FLAG" SYMBOLS OR GRAPHICALLY INDICATED, ASSUME TO BE TYPE M4 PARTITION - REFER TO "PLAN GRAPHIC" ON THE PARTITION TYPES LEGEND, THIS SHEET, FOR RATED PARTITIONS

GRAPHICALLY INDICATED.

Project Number

593-202

K

O

HIGHEST

ADJ. CLG

5/8" GYP BD. EA. SIDE

II

N

II

Scale:

As shown

L

P

. XK X K

I I

I I i

T I I I I

T I I I I

T I I I I

T I I I

O

V . V

O C O

1-2" n

T l l I

V ■

FIRE SEALANT

(NO AIR

LEAKAGE)

4" MTL STUDS @16"

----or----------

O C o

PRIORITY 1

UL

#415/419

—— 7/8" HAT

_ CHANNELS @ 16"

O.C.

T.

Lx

PRIORITY 4

UL

#415/419

PRIORITY 3

UL

#415/419

U S s!

c V O

5 OT

C

PRIORITY 2

UL

#415/419

O c o U V

OT

C o

I I

M C

I I

“WcaECG-onN!"

T I I I

T.

Li F I

T I I I I

—4— 5/8" GYP BD.

ONE SIDE

RTKL

FIRE SEALANT

(NO AIR

LEAKAGE)

4" MTL STUDS @16"

----- or.-------------

GROUTED CMU

9 1/8"

MORTAR JOINT

—4"x16 GA. MTL STUDS @16" or

£36 1/2

C.

5/8" GYP BD. EA. SIDE *

10 3/4"

LaLd

I

I

I

I erik.tuomy Text Box Record Drawings erik.tuomy

02/20/13

VHALASKentoW Contractor

VHALASKentoW Contractor Typical for Exam room Doors

GI-0301 Project I
AE-1102 C
AE-1102 F
AE-1103 C
AE-1103 F
AE-1203C
AE-1203F
593.2202.1AF-1102C
593.2202.1AF-1102F
593.2202.1AF-1103C
593.2202.1AF-1103F
EP-1103 C
EP-1103 F
GI-0311 Partition
PL-605 H
PL-605 J
PL-606 H
PL-606 J
PL-1103 C
PL-1103 F
PP-1103 C
PP-1103 F
FA-103C
TH-0001
TH-1103C
TH-1103F
Door Hardware Set