This document is Attachment C to a federal solicitation for the P691 Phase I, Aircraft Development and Maintenance Facility project. The solicitation is for site development and construction services of a Sonobuoy Storage Building and an Air Ops Storage Building, with an option for a Hazmat building. The project also includes a Furniture, Fixtures, and Equipment (FF&E) Option CLIN. This opportunity is restricted to the ten (10) small businesses participating in the NAVFAC WASHINGTON Gold Small Business Multiple Award Construction Contract (GOLD SB MACC). The solicitation number is 6007134, and the agency is the Department of the Navy Naval Facilities Engineering Command.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
S Y
S T
E M
S C
O M
M A
N D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D W
A S
H
IN
G T
O N
W A
S H
IN
G
T O
N N
A V
Y Y
A R
D
D .C
AS NOTED
3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092
W A
S H
IN
G
T O
N D
C C
O R
E
N A
V A
L A
IR
S
T A
T
IO
N P
A T
U X
E N
T R
IV
E
R S
T . M
A R
Y 'S
C O
U N
T Y
, M D
F Y
M
IL
C O
N P
1737036
CONTROLLED UNCLASSIFIED INFORMATION
C O
N T
R O
L L E
D U
N C
L A
S S
IF
IE
D I
N F
O R
M A
T
IO
N
CONTROLLED UNCLASSIFIED INFORMATION
C O
N T
R O
L L E
D U
N C
L A
S S
IF
IE
D I
N F
O R
M A
T
IO
N
PM/CN
TC
SS
04/04/2024
GR
/3
/2
:1 :5
A
M
C U s e rs
\e ri n
.a d a m s o n \O n e D ri v e
M ic h a e l B a k e r
In te rn a ti o n a l\ D o c u m e n ts
\B L D
G -P
-1
-G
V
E ri n
.A d a m s o n
.r v t
V2 G-000
P R
O
JE
C T
C O
V E
R S
H E
E T
JH
13150095
EMA EMA
G -0
100% FINAL SUBMITAL
PROJECT COVER SHEET
NAVAL AIR STATION PATUXENT RIVER, MARYLAND
100% FINAL SUBMITTAL
29 SEPTEMBER 2023
DEPARTMENT OF THE NAVY
NAVAL FACILITIES ENGINEERING SYSTEMS COMMAND
VOLUME 2 - AIR OPS BUILDING
Controlled By: PEO (A) / PMA 271 CUI Catergory(ies): CUI/SP-CTI Limited Dissemination Control: FEDCON POC: Facility LEM PMA-271
(301) 757-0335
V O
LU
M
E
A
IR
O
P S
B U
IL
D
IN
G
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
Erin.Adamson Snapshot
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
S Y
S T
E M
S C
O M
M A
N D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D W
A S
H
IN
G T
O N
W A
S H
IN
G
T O
N N
A V
Y Y
A R
D
D .C
AS NOTED
3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092
W A
S H
IN
G
T O
N D
C C
O R
E
N A
V A
L A
IR
S
T A
T
IO
N P
A T
U X
E N
T R
IV
E
R S
T . M
A R
Y 'S
C O
U N
T Y
, M D
F Y
M
IL
C O
N P
1737036
CONTROLLED UNCLASSIFIED INFORMATION
C O
N T
R O
L L E
D U
N C
L A
S S
IF
IE
D I
N F
O R
M A
T
IO
N
CONTROLLED UNCLASSIFIED INFORMATION
C O
N T
R O
L L E
D U
N C
L A
S S
IF
IE
D I
N F
O R
M A
T
IO
N
PM/CN
TC
SS
04/04/2024
GR
/3
/2
:1 :5
A
M
C U s e rs
\e ri n
.a d a m s o n \O n e D ri v e
M ic h a e l B a k e r
In te rn a ti o n a l\ D o c u m e n ts
\B L D
G -P
-1
-G
V
E ri n
.A d a m s o n
.r v t
V2 G-001
A
IR
O P
S B
U
IL
D
IN
G C
O V
E R
S H
E E
T
V O
LU
M
E
JH
13150096
EMA EMA
G -0
100% FINAL SUBMITAL
VOLUME 2 - AIR OPS BUILDING
NAVAL AIR STATION PATUXENT RIVER, MARYLAND
VICINITY MAP
LOCATION MAP
DEPARTMENT OF THE NAVY
NAVAL FACILITIES ENGINEERING SYSTEMS COMMAND
PROJECT LOCATION(S)
PROJECT LOCATION
V O
LU
M
E
A
IR
O
P S
B U
IL
D
IN
G
Controlled By: PEO (A) / PMA 271 CUI Catergory(ies): CUI/SP-CTI Limited Dissemination Control: FEDCON POC: Facility LEM PMA-271
(301) 757-0335
100% FINAL SUBMITTAL
29 SEPTEMBER 2023
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
S Y
S T
E M
S C
O M
M A
N D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D W
A S
H
IN
G T
O N
W A
S H
IN
G
T O
N N
A V
Y Y
A R
D
D .C
AS NOTED
3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092
W A
S H
IN
G
T O
N D
C C
O R
E
N A
V A
L A
IR
S
T A
T
IO
N P
A T
U X
E N
T R
IV
E
R S
T . M
A R
Y 'S
C O
U N
T Y
, M D
F Y
M
IL
C O
N P
1737036
CONTROLLED UNCLASSIFIED INFORMATION
C O
N T
R O
L L E
D U
N C
L A
S S
IF
IE
D I
N F
O R
M A
T
IO
N
CONTROLLED UNCLASSIFIED INFORMATION
C O
N T
R O
L L E
D U
N C
L A
S S
IF
IE
D I
N F
O R
M A
T
IO
N
PM/CN
TC
SS
04/04/2024
GR
/3
/2
:1 :5
A
M
C U s e rs
\e ri n
.a d a m s o n \O n e D ri v e
M ic h a e l B a k e r
In te rn a ti o n a l\ D o c u m e n ts
\B L D
G -P
-1
-G
V
E ri n
.A d a m s o n
.r v t
V2 G-002
D R
A W
IN
G
IN
D
E X
JH
13150097
EMA EMA
G -0
100% FINAL SUBMITAL
SHEET INDEX
SHEET
NO.
NAVFAC
DRAWING
NO.
SHEET INFORMATION
NUMBER NAME
GENERAL
1 13150095 G-000 PROJECT COVER SHEET
2 13150096 G-001 AIR OPS BUILDING COVER SHEET - VOLUME 2
3 13150097 G-002 DRAWING INDEX
SHEET INDEX - VOLUME 2
SHEET
NO.
NAVFAC
DRAWING
NO.
SHEET INFORMATION
NUMBER NAME
GENERAL
4 13150098 GI001 BUILDING CODE ANALYSIS
5 13150099 GI100 LIFE SAFETY - CODE COMPLIANCE PLAN
6 13150100 GI101 LIFE SAFETY - 1ST FLOOR PLAN
STRUCTURAL
7 13150101 S-001 DESIGN CRITERIA AND GENERAL NOTES
8 13150102 S-002 GENERAL NOTES, ABBREVIATIONS AND SYMBOLS
9 13150103 S-101 FOUNDATION PLAN
10 13150104 S-301 FOUNDATION SECTIONS
11 13150105 S-501 FOUNDATION AND SLAB TYPICAL DETAILS
12 13150106 S-502 FOUNDATION AND SLAB TYPICAL DETAILS
13 13150107 S-601 STRUCTURAL SCHEDULES
14 13150108 S-602 PIER SCHEDULES AND DETAILS
ARCHITECTURE
15 13150109 AE001 ARCHITECTURAL NOTES AND SYMBOLS
16 13150110 AE002 TYPICAL ABA DETAILS & MOUNTING HEIGHTS
17 13150111 AE101 FIRST FLOOR PLAN
18 13150112 AE105 FIRST FLOOR REFLECTED CEILING PLAN
19 13150113 AE109 ROOF PLAN
20 13150114 AE201 NORTH AND SOUTH EXTERIOR ELEVATIONS
21 13150115 AE202 EAST AND WEST EXTERIOR ELEVATIONS
22 13150116 AE301 BUILDING SECTIONS
23 13150117 AE311 WALL SECTIONS
24 13150118 AE501 EXTERIOR DETAILS
25 13150119 AE601 DOOR SCHEDULE AND LOUVER TYPES
26 13150120 AE602 DOOR DETAILS
INTERIORS
27 13150121 IN001 INTERIOR - FINISH, FURNITURE, SIGNAGE SCHEDULES AND NOTES
28 13150122 IN101 INTERIOR - FINISH, FURNITURE AND SIGNAGE PLAN AND LEGENDS
ELECTRICAL
29 13150123 E-001 ELECTRICAL - NOTES, SYMBOLS, AND ABBREVIATIONS
30 13150124 ES101 ELECTRICAL - SITE UTILITY PLAN
31 13150125 ES501 ELECTRICAL - SITE DETAILS
32 13150126 ES502 ELECTRICAL - SITE DETAILS
33 13150127 ES503 ELECTRICAL - SITE DETAILS
34 13150128 EG101 ELECTRICAL - GROUNDING PLAN
35 13150129 EG501 ELECTRICAL - GROUNDING DETAILS
36 13150130 EL101 LIGHTING - 1ST FLOOR PLAN
37 13150131 EP101 POWER - 1ST FLOOR PLAN
38 13150132 E-501 ELECTRICAL - LIGHTING CONTROL DETAILS
39 13150133 E-502 ELECTRICAL - LIGHT FIXTURE DETAILS
40 13150134 E-601 ELECTRICAL - LIGHTING FIXTURE SCHEDULE
41 13150135 E-602 ELECTRICAL - SINGLE LINE DIAGRAM AND PANEL SCHEDULES
TELECOMMUNICATIONS
42 13150136 T-001 TELECOMMUNICATIONS SYMBOLS, SCHEDULES, & NOTES
43 13150137 TS101 TELECOMMUNICATIONS - SITE UTILITY PLAN
44 13150138 T-101 TELECOMMUNICATIONS - 1ST FLOOR PLAN
45 13150139 T-501 TELECOMMUNICATIONS - DETAILS
46 13150140 T-601 TELECOMMUNICATIONS - DIAGRAMS
V O
LU
M
E
A
IR
O
P S
B U
IL
D
IN
G
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
FIRE PROTECTION/LIFE SAFETY CODE SUBMITTAL
1. PROJECT NAME
P691 AIRCRAFT HANGAR AND OUTBUILDINGS - AIRCRAFT OPERATIONS STORAGE BUILDING
2. PROJECT DESCRIPTION
THE SINGLE STORY BUILDING CONSISTS OF STORAGE.
THE FACILITY HAS BEEN ANALYZED FOR LIFE SAFETY AND FIRE PROTECTION REQUIREMENTS USING THE CODES AND STANDARDS LISTED BELOW. THE IBC WILL BE USED FOR FIRE RESISTANCE REQUIREMENTS, ALLOWABLE FLOOR AREA, BUILDING HEIGHT LIMITATIONS, BUILDING SEPARATION DISTANCE REQUIREMENTS, BUILDING CONSTRUCTION TYPE, AND OCCUPANCY SEPARATION REQUIREMENTS. THE APPLICABLE NFPA CODES AND STANDARDS WILL BE USED FOR DETERMINING BUILDING CONSTRUCTION RELATED TO EGRESS AND SAFETY TO LIFE AS WELL AS FIRE RESISTANCE RATINGS OF NON-BEARING PARTITIONS. OCCUPANCY DEFINITIONS OF NFPA WILL BE USED TO
DETERMINE MEANS OF EGRESS REQUIREMENTS.
3. APPLICABLE CODES AND STANDARDS
• UFC 1-200-01 - DOD BUILDING CODE, 01 SEPTEMBER 2022 WITH CHANGE 1, 24 FEBRUARY 2023
• UFC 3-600-01 - FIRE PROTECTION ENGINEERING FOR FACILITIES, 8 AUGUST 2016 WITH CHANGE 6, 6 MAY 2021
• UFC 4-010-01 - DOD MINIMUM ANTITERRORISM STANDARDS FOR BUILDINGS, 12 DECEMBER 2018 WITH CHANGE 1, 19 AUGUST 2020
• FC 1-300-09N - NAVY AND MARINE CORPS DESIGN PROCEDURES WITH CHANGE 6, 9 JULY 2021
• NFPA 1 - 2021 EDITION - FIRE CODE
• NFPA 101 - 2021 EDITION - LIFE SAFETY CODE
• NFPA 291 - 2022 EDITION - RECOMMENDED PRACTICE FOR FIRE FLOW TESTING AND MARKING OF HYDRANTS
• IBC 2021 EDITION - INTERNATIONAL BUILDING CODE
4. OCCUPANCY CLASSIFICATION
5. CONSTRUCTION TYPE (IBC SECTION 602.2)
ALL NEW CONSTRUCTION WILL BE OF TYPE II-B.
6. BUILDING AREA LIMITATIONS (IBC TABLE 506.2)
NOTES:
1. ACTUAL BUILDING SQUARE FOOTAGE IS LESS THAN THE ALLOWABLE AREA FOR THE MOST RESTRICTIVE OCCUPANCY PRIOR TO
THE ADDITION OF THE FRONTAGE ALLOWANCE INCREASE, THEREFORE, THE FRONTAGE ALLOWANCE INCREASE IS NOT REQUIRED.
7. BUILDING HEIGHT LIMITATIONS (IBC TABLES 504.3, 504.4)
THE BUILDING HEIGHT IS 24'-6" AND 1 STORY.
8. MIXED USE AND OCCUPANCY SEPARATIONS (IBC SECTION 508)
THE FACILITY IS CLASSIFIED AS SINGLE OCCUPANCY.
9. FIRE RESISTIVE REQUIREMENTS (IBC TABLES 601, 602)
PRIMARY STRUCTURAL FRAME 0 HOUR RATING
EXTERIOR BEARING WALLS 0 HOUR RATING*
INTERIOR BEARING WALLS 0 HOUR RATING
EXTERIOR NON-BEARING WALLS AND PARTITIONS 0 HOUR RATING*
INTERIOR NON-BEARING WALLS AND PARTITIONS 0 HOUR RATING
FLOOR CONSTRUCTION AND SECONDARY MEMBERS 0 HOUR RATING
ROOF CONSTRUCTION AND SECONDARY MEMBERS 0 HOUR RATING
*TAKES INTO ACCOUNT THE FIRE SEPARATION DISTANCE REQUIREMENT OF TABLE 602. THERE IS GREATER THAN 20 FEET OF SEPARATION
BETWEEN THE AIR OPS FACILITY AND THE NEAREST FACILITY.
10. INTERIOR FINISH CLASSIFICATION LIMITS (NFPA 101 A.10.2.2)
NOTES:
1. IN CONCEALED SPACES, SURFACE MATERIALS SHALL HAVE A FLAME SPREAD INDEX OF 0-25 OR HAVE BEEN DEMONSTRATED NOT
TO PROPOGATE FIRE MORE THAN 10.5 FEET WHEN TESTED IN ACCORDANCE WITH ASTM E84 OR COMPLY WITH THE REQUIREMENTS
OF ASTM 2768.
11. INSULATION REQUIREMENTS (UFC 3-600-01 SECTION 8-3, IBC SECTION 2603)
THERMAL AND ACOUSTICAL INSULATION WITH A FLAME SPREAD RATING NOT HIGHER THAN 75 AND A SMOKE DEVELOPED RATING NOT HIGHER THAN 150 WILL BE USED WHEN TESTED IN ACCORDANCE WITH ASTM E84 UNLESS EXCEPTIONS OF UFC 3-600-01 SECTION 8-3.2 ARE
MET.
FOAM PLASTIC INSULATION MUST MEET THE REQUIREMENTS OF IBC SECTION 2603.
16. MEANS OF EGRESS (NFPA 101)
MEANS OF EGRESS LIMITATIONS WILL BE IN ACCORDANCE WITH NFPA 101 TABLE A.7.6.
EXITS WILL BE DESIGNED TO MEET NFPA 101. ALL DOORS AND CORRIDORS BE SIZED AT 0.2 INCHES PER OCCUPANT USING
THE EXIT IN ACCORDANCE WITH TABLE 7.3.3.1.
EXITS SHALL BE PROVIDED SUCH THAT EXITS ARE AT LEAST 1/2 THE DIAGONAL DISTANCE OF THE BUILDING APART PER
SECTION 7.5.1.3.2.
17. OCCUPANT LOAD CALCULATION
THE OCCUPANT LOAD CALCULATION ABOVE IS NOT TO BE USED FOR THE PURPOSES OF DETERMINING ATFP OCCUPANCY. THE
BUILDING IS CONSIDERED "LOW OCCUPANCY" FOR ATFP PURPOSES.
18. DISCHARGE FROM EXITS AND EGRESS CAPACITY CALCULATION (NFPA 101)
BUILDING EXITS SHALL TERMINATE DIRECTLY AT A PUBLIC WAY IN ACCORDANCE WITH SECTION 7.7.
BASED ON AN OCCUPANT LOAD OF 9 PERSONS, 2 EXITS HAVING A MINIMUM CLEAR WIDTH OF 32 INCHES ARE REQUIRED FOR THE FACILITY PER NFPA 101 SECTIONS 42.2.4 AND 7.11.4. TWO EXITS WITH A MINIMUM CLEAR WIDTH OF 34 INCHES EACH ARE
PROVIDED.
19. ILLUMINATION OF MEANS OF EGRESS (NFPA 101)
MEANS OF EGRESS WILL BE ILLUMINATED IN ACCORDANCE WITH SECTION 7.8.1.2 THROUGH 7.8.1.5.
20. EMERGENCY LIGHTING (NFPA 101)
EMERGENCY LIGHTING MUST BE PROVIDED IN ACCORDANCE WITH SECTION 7.9. EMERGENCY ILLUMINATION MUST BE PROVIDED FOR A MINIMUM OF 1 ½ HOURS IN THE EVENT OF FAILURE OF NORMAL LIGHTING. THE EMERGENCY LIGHTING SYSTEM MUST BE ARRANGED TO PROVIDE THE REQUIRED ILLUMINATION AUTOMATICALLY IN THE EVENT OF ANY
INTERRUPTION OF NORMAL LIGHTING.
21. PORTABLE FIRE EXTINGUISHERS (UFC 3-600-01, NFPA 101)
PORTABLE FIRE EXTINGUISHERS ARE NOT REQUIRED IN ACCORDANCE WITH NFPA 101.
22. AUTOMATIC SPRINKLERS (UFC 3-600-01, NFPA 13)
THE BUILDING IS NOT REQUIRED TO BE PROVIDED WITH A SPRINKLER SYSTEM IN ACCORDANCE WITH UFC 3-600-01 SECTION 9-7.2.1.
23. FIRE ALARM & VOICE EVACUATION SYSTEM (UFC 3-600-01, UFC 4-021-01, AND NFPA 72) THE BUILDING IS NOT REQUIRED TO BE PROVIDED WITH A FIRE ALARM SYSTEM IN ACCORDANCE WITH UFC 3-600-01 SECTION 9-18.1.
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
S Y
S T
E M
S C
O M
M A
N D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D W
A S
H
IN
G T
O N
W A
S H
IN
G
T O
N N
A V
Y Y
A R
D
D .C
AS NOTED
3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092
W A
S H
IN
G
T O
N D
C C
O R
E
N A
V A
L A
IR
S
T A
T
IO
N P
A T
U X
E N
T R
IV
E
R S
T . M
A R
Y 'S
C O
U N
T Y
, M D
F Y
M
IL
C O
N P
1737036
CONTROLLED UNCLASSIFIED INFORMATION
C O
N T
R O
L L E
D U
N C
L A
S S
IF
IE
D I
N F
O R
M A
T
IO
N
CONTROLLED UNCLASSIFIED INFORMATION
C O
N T
R O
L L E
D U
N C
L A
S S
IF
IE
D I
N F
O R
M A
T
IO
N
PM/CN
TC
SS
04/04/2024
GR
/4
/2
:3
:5
P M
C U s e rs
\d m c c u tc h e o n \D o c u m e n ts
\B L D
G -P
-A
O P
-1
-F b a k e r.
rv t
V2 GI001
B U
IL
D
IN
G
C O
D E
A N
A
LY
S
IS
KAB
13150098
TGW DAM
V O
LU
M
E
A
IR
O
P S
B U
IL
D
IN
G
G I0
100% FINAL SUBMITTAL
MODERATE HAZARD STORAGE GROUP S-1 (SECTION 311.2) STORAGE (CHAPTER 42)
IBC NFPA 101
TOTAL AREA (SQ. FT) 4,116
STORAGE S-1 17,500 SEE NOTE 1 17,500 4,116
OCCUPANCY TYPE
BASE ALLOWABLE
AREA
(NON-SPRINKLERED,
SINGLE STORY, SQ.
FT)
FRONTAGE
ALLOWANCE
INCREASE (SQ. FT)
TOTAL BUILDING
AREA PERMITTED
(SQ. FT)
ACTUAL FIRST
FLOOR AREA (SQ.
FT)
ALLOWABLE AREA CALCULATIONS FOR CONSTRUCTION TYPE II-B
CLASS A INTERIOR WALL AND CEILING FINISH - FLAME SPREAD INDEX 0-25, SMOKE DEVELOPED INDEX 0-450 CLASS B INTERIOR WALL AND CEILING FINISH - FLAME SPREAD INDEX 26-75, SMOKE DEVELOPED INDEX 0-450 CLASS C INTERIOR WALL AND CEILING FINISH - FLAME SPREAD INDEX 76-200, SMOKE DEVELOPED INDEX 0-450 CLASS I INTERIOR FLOOR FINISH - CRITICAL RADIANT FLUX NOT LESS THAN 0.45 W/(SQ. CM) CLASS II INTERIOR FLOOR FINISH - CRITICAL RADIANT FLUX NOT MORE THAN 0.22 W/(SQ. CM) BUT LESS THAN
0.45 W/(SQ. CM)
CLASS I OR II NO REQUIREMENT N/A
STORAGE
CLASS A OR B CLASS A, B, OR C CLASS A, B, OR C
OCCUPANCY
EXIT ENCLOSURES AND
EXIT PASSAGEWAYS
CORRIDORS
ROOMS AND ENCLOSED
SPACES
INTERIOR FINISH CLASSIFICATION (NFPA 101, TABLE A.10.2.2)
STORAGE 50 50 200
OCCUPANCY DEAD END (FT) COMMON PATH (FT) TRAVEL DISTANCE (FT)
EGRESS LIMITATIONS: NON SPRINKLERED FACILITY
(NFPA 101 TABLE A.7.6)
TOTALS: 4,116 9
STORAGE 500 (GROSS) 4,116 9
USE
OCCUPANT LOAD FACTOR
(SQ. FT/PERSON)
AREA (SQ. FT) OCCUPANT LOAD
P-691 AIR OPS FACILITY OCCUPANCY LOAD:
UFC 3-600-01 TABLE 10-1 AND NFPA 101 TABLE 7.3.1.2
E-2 32 34 170
E-1 32 34 170
FIRST FLOOR
EXIT NUMBER
MINIMUM REQUIRED CLEAR
WIDTH (INCHES)
ACTUAL CLEAR WIDTH
(INCHES)
CALCULATED OCCUPANT
CAPACITY (PERSONS)
P-691 AIR OPS FACILITY EXIT CAPACITY CALCULATION
NPFA 101 SECTION 7.2.1.2.3 AND TABLE 7.3.3.1
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
T
33' ATFP SETBACK
280'
1/
23' - 6 11/16"
31' - 6"
3 2
10 312'
10 312'
SITE LOCATION
1. REFER TO SHEET GI001 FOR BUILDING AND LIFE SAFETY CODE ANALYSIS.
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
S Y
S T
E M
S C
O M
M A
N D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D W
A S
H
IN
G T
O N
W A
S H
IN
G
T O
N N
A V
Y Y
A R
D
D .C
AS NOTED
3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092
W A
S H
IN
G
T O
N D
C C
O R
E
N A
V A
L A
IR
S
T A
T
IO
N P
A T
U X
E N
T R
IV
E
R S
T . M
A R
Y 'S
C O
U N
T Y
, M D
F Y
M
IL
C O
N P
1737036
CONTROLLED UNCLASSIFIED INFORMATION
C O
N T
R O
L L E
D U
N C
L A
S S
IF
IE
D I
N F
O R
M A
T
IO
N
CONTROLLED UNCLASSIFIED INFORMATION
C O
N T
R O
L L E
D U
N C
L A
S S
IF
IE
D I
N F
O R
M A
T
IO
N
PM/CN
TC
SS
04/04/2024
GR
/4
/2
:3
:5
P M
C U s e rs
\d m c c u tc h e o n \D o c u m e n ts
\B L D
G -P
-A
O P
-1
-F b a k e r.
rv t
V2 GI100
LI
F
E S
A F
E T
Y
C O
D E
C O
M P
LI
A
N C
E P
LA
N
KAB
13150099
TGW DAM
V O
LU
M
E
A
IR
O
P S
B U
IL
D
IN
G
G I1
100% FINAL SUBMITTAL
PLAN
NORTH
GENERAL SHEET NOTES
GRAPHIC SCALE(S)
KEY PLAN
SHEET KEYNOTES#
1" = 30'-0"
LIFE SAFETY - CODE COMPLIANCE PLAN
1" = 30' 0 30' 120'60'
1 ATFP SETBACK
2 BUILDING PERIMETER
3 EXIT DISCHARGE PATH
4 FIRE DEPARTMENT MAIN ENTRANCE
5 LINE OF ENCROACHMENT
6 FIRE DEPARTMENT ACCESS LANE
7 FIRE DEPARTMENT ACCESS LANE WIDTH
8 FIRE DEPARTMENT ACCESS LANE TURNING RADIUS
9 EXISTING FIRE HYDRANT
10 DISTANCE ALONG FIRE DEPARTMENT ACCESS ROAD FOR HYDRANT
SPACING
11 KNOX BOX
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
K
K
1. REFER TO SHEET GI001 FOR BUILDING AND LIFE SAFETY CODE ANALYSIS.
2. EXIT SIGNS ARE SHOWN FOR INFORMATION ONLY. REFER TO ELECTRICAL
DRAWINGS FOR ACTUAL LOCATION.
LEGEND
DESCRIPTION SYMBOL
OCCUPANCY
LOAD
EXIT SIGN
TRAVEL
DISTANCE
COMMON PATH
OF TRAVEL
DEAD END
OCCUPANT LOAD
FACTOR
[X/Y]
PERSONS/SQUARE FEET
E-X/IRE-X
X
X
X
EXIT COMPONENT
CLEAR WIDTH
CALCULATED CAPACITY
ACTUAL USE
OCCUPANCY
CLASSIFICATION
EXIT LEGEND
0'
0'
0'
KNOX BOX
S-1
[ ]1/500
78'
E-2
E-1
STORAGE
1 2 3 4 5 6
D
C
B
A
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
S Y
S T
E M
S C
O M
M A
N D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D W
A S
H
IN
G T
O N
W A
S H
IN
G
T O
N N
A V
Y Y
A R
D
D .C
AS NOTED
3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092
W A
S H
IN
G
T O
N D
C C
O R
E
N A
V A
L A
IR
S
T A
T
IO
N P
A T
U X
E N
T R
IV
E
R S
T . M
A R
Y 'S
C O
U N
T Y
, M D
F Y
M
IL
C O
N P
1737036
CONTROLLED UNCLASSIFIED INFORMATION
C O
N T
R O
L L E
D U
N C
L A
S S
IF
IE
D I
N F
O R
M A
T
IO
N
CONTROLLED UNCLASSIFIED INFORMATION
C O
N T
R O
L L E
D U
N C
L A
S S
IF
IE
D I
N F
O R
M A
T
IO
N
PM/CN
TC
SS
04/04/2024
GR
/4
/2
:3
:5
P M
C U s e rs
\d m c c u tc h e o n \D o c u m e n ts
\B L D
G -P
-A
O P
-1
-F b a k e r.
rv t
V2 GI101
LI
F
E S
A F
E
TY
1S
T F
LO
O
R P
LA
N
KAB
13150100
TGW DAM
V O
LU
M
E
A
IR
O
P S
B U
IL
D
IN
G
G I1
100% FINAL SUBMITTAL
PLAN
NORTH
GENERAL SHEET NOTES
GRAPHIC SCALE(S)
1/8" = 1' - 0" 0 5' 10' 15' 30'
1/8" = 1'-0"
LIFE SAFETY - FIRST FLOOR PLAN
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
S Y
S T
E M
S C
O M
M A
N D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D W
A S
H
IN
G T
O N
W A
S H
IN
G
T O
N N
A V
Y Y
A R
D
D .C
AS NOTED
3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092
W A
S H
IN
G
T O
N D
C C
O R
E
N A
V A
L A
IR
S
T A
T
IO
N P
A T
U X
E N
T R
IV
E
R S
T . M
A R
Y 'S
C O
U N
T Y
, M D
F Y
M
IL
C O
N P
1737036
CONTROLLED UNCLASSIFIED INFORMATION
C O
N T
R O
L L E
D U
N C
L A
S S
IF
IE
D I N
F O
R M
A T
IO
N
CONTROLLED UNCLASSIFIED INFORMATION
C O
N T
R O
L L E
D U
N C
L A
S S
IF
IE
D I N
F O
R M
A T
IO
N
PM/CN
TC
SS
03/15/2024
GR
/3
/2
:1
:1
P M
C U s e rs
\j a m e s .c u m m in g s \D o c u m e n ts \B
L D
G -P
-A O
P -1
-S
J a m e s .C u m m in g s B
B Z
R A
.r v t
V2 S-001
D E
S
IG
N C
R
IT
E R
IA
A
N D
G E
N E
R A
L N
O
TE
S
DRB
13150101
JDZ JAC
V O
LU
M
E
A
IR
O
P S
B U
IL
D
IN
G
S -0
100% FINAL SUBMITTAL
DESIGN CRITERIA
DC-1 BUILDING CODE: INTERNATIONAL BUILDING CODE (IBC) 2021,
AS AMENDED BY UFC 1-200-01 AND UFC 3-301-01
DC-2 LATERAL LOAD DESIGN CRITERIA
A. RISK CATEGORY II
B. WIND DESIGN CRITERIA
1. BASIC DESIGN WIND SPEED (V) 115 MPH
2. ALLOWABLE DESIGN WIND SPEED (Vasd) 90 MPH
3. EXPOSURE CATEGORY C
4. INTERNAL PRESSURE COEFFICIENT +/- 0.18
C. SEISMIC DESIGN CRITERIA
1. SEISMIC IMPORTANCE FACTOR (Ie) 1.0
2. SITE CLASS D
3. SHORT PERIOD SPECTRAL ACCELERATION (SS) 0.114g
4. ONE SECOND SPECTRAL ACCELERATION (S1) 0.041g
5. SHORT PERIOD RESPONSE ACCELERATION (SDS) 0.122g
6. ONE SECOND RESPONSE ACCELERATION (SD1) 0.066g
7. SEISMIC DESIGN CATEGORY A
8. SEISMIC RESPONSE COEFFICIENT (CS) 0.04
9. SEISMIC DESIGN BASE SHEAR PER MFR
10. SEISMIC RESISTING SYSTEM:
STRUCTURAL STEEL SYSTEMS NOT SPECIFICALLY DETAILED FOR
SEISMIC RESISTANCE (R =3.0)
11. ANALYSIS METHOD: EQUIVALENT LATERAL FORCE PROCEDURE
DC-3 GRAVITY LOADS
A. DEAD LOADS
1. BUILDING SELF WEIGHT + 5 PSF COLLATERAL
A. MINIMUM (FOR UPLIFT) 3 PSF
B. LIVE LOADS
1. ROOF 20 PSF MIN
2. TYPICAL (STORAGE) 250 PSF
C. VEHICLE LOADS
1. UFC FORKLIFT CATEGORY II 15 KIP MAX AXLE LOAD
D. SNOW LOADS
1. GROUND SNOW LOAD (Pg) 20 PSF
2. MINIMUM SNOW LOAD (Pm) 20 PSF
3. FLAT-ROOF SNOW LOAD(Pf) 16.8 PSF
4. SLOPED ROOF SNOW LOAD (Ps) 16.8 PSF
5. SNOW IMPORTANCE FACTOR (Is) 1.0
6. SNOW EXPOSURE FACTOR (Ce) 1.0
7. THERMAL FACTOR (Ct) 1.2
8. ADD'L UNBALANCED SNOW LOAD AS PER APPLICABLE BLDG CODE
E. CONSTRUCTION LOADS
1. NOT TO EXCEED THE DESIGN LIVE LOADS.
DC-4 FOUNDATION DESIGN CRITERIA
A. FOUNDATION DESIGN IS BASED UPON THE FOLLOWING SOIL
PARAMETERS:
1. NET ALLOWABLE SOIL BEARING PRESSURE:
A. SPREAD FOOTINGS: 2000 PSF
B. CONTINUOUS FOOTINGS: 2000 PSF
B. ASSUMED LATERAL EARTH PRESSURE PARAMETERS:
1. SOIL DENSITY = 100 PCF
2. COEFFICIENT OF ACTIVE PRESSURE (Ka) = 0.45
3. COEFFICIENT OF AT-REST PRESSURE (Ko) = 0.60
4. COEFFICIENT OF PASSIVE EARTH PRESSURE (Kp) = 3.00
5. ANGLE OF INTERNAL FRICTION (phi) = 28 DEGREES
6. COEFFICIENT OF FRICTION (u) = 0.35
7. MODULUS OF SUB-GRADE REACTION (ks) = 100 PCI
C. FROST DEPTH: 26 INCHES
D. MINIMUM BEARING DEPTH: 26 INCHES
DC-5 ANTI-TERRORISM CRITERIA
A. THIS FACILITY HAS BEEN DESIGNED IN ACCORDANCE WITH THE ANTI-
TERRORISM (AT) REQUIREMENTS SET FORTH IN UFC 4-010-01, DATED
30 JULY 2022. BUILDING ANTI-TERRORISM DESIGN CRITERIA ARE AS
FOLLOWS:
B. AT FACILITY CRITERIA
1. BUILDING SITE LOCATION WITHIN INSTALLATION PERIMETER
2. BUILDING CATEGORY UNINHABITED
3. BUILDING STANDOFF DISTANCE > 50 FT TO PERIMETER
4. UNOBSTRUCTED SPACE 33 FT
5. PROGRESSIVE COLLAPSE N/A
6. STRUCTURAL ISOLATION N/A
GENERAL
G-1 METHODS, PROCEDURES AND SEQUENCES OF CONSTRUCTION ARE
THE RESPONSIBILITY OF THE CONTRACTOR. THE CONTRACTOR IS
RESPONSIBLE FOR IDENTIFYING AND IMPLEMENTING THE
NECESSARY PRECAUTIONS TO MAINTAIN AND ENSURE THE
INTEGRITY OF THE STRUCTURE AT EACH STAGE OF CONSTRUCTION.
G-2 TEMPORARY BRACING, SHEETING, SHORING, ETC, REQUIRED TO
ENSURE THE STRUCTURAL INTEGRITY/STABILITY OF THE EXISTING
BUILDINGS, SIDEWALKS, UTILITIES, ETC, DURING CONSTRUCTION IS
THE RESPONSIBILITY OF THE CONTRACTOR AND MUST BE DESIGNED
BY A REGISTERED PROFESSIONAL ENGINEER EMPLOYED BY THE
CONTRACTOR.
G-3 IMPLEMENTATION OF JOB SITE SAFETY IS THE SOLE RESPONSIBILITY
OF THE CONTRACTOR.
G-4 WHEN NOT SPECIFICALLY INDICATED ON THE STRUCTURAL
DRAWINGS, THE CONTRACTOR IS RESPONSIBLE FOR DETERMINING
SLEEVE AND BLOCK-OUT REQUIREMENTS FOR PENETRATIONS PRIOR
TO FABRICATION OR ERECTION OF THE STRUCTURE. PENETRATIONS
OF STRUCTURAL MEMBERS ARE SUBJECT TO APPROVAL BY THE
CONTRACTING OFFICER. THE CONTRACTOR IS ALSO RESPONSIBLE
FOR DETERMINING ANCHORAGE AND HANGER REQUIREMENTS
REQUIRED FOR SUPPORTING EQUIPMENT, FINISHES, UTILITIES
ETCETERA NOT INDICATED ON THE STRUCTURAL DRAWINGS.
G-5 DO NOT SCALE DRAWINGS.
G-6 THE CONTRACTOR IS RESPONSIBLE FOR DETERMINING AND
COORDINATING DIMENSIONS AND INSTALLATION DETAILS OF
PURCHASED EQUIPMENT WITH THE SUPPORTING
STRUCTURE. CONFLICTS BETWEEN THESE ITEMS AND THE BUILDING
STRUCTURE MUST BE BROUGHT TO THE ATTENTION OF THE
CONTRACTING OFFICER FOR RESOLUTION.
G-7 THE STRUCTURAL DRAWINGS GOVERN THE WORK FOR STRUCTURAL
FEATURES, UNLESS OTHERWISE NOTED. DIMENSIONS SHOWN ON
PLANS AND DETAILS ARE TO GOVERN THE STRUCTURAL WORK. THE
CONTRACTOR IS TO REFER TO THE ARCHITECTURAL DRAWINGS FOR
DIMENSIONS AND DETAILS NOT PROVIDED. DIMENSIONAL CONFLICTS
IN THE DOCUMENTS MUST BE BROUGHT TO THE ATTENTION OF THE
CONTRACTING OFFICER.
G-8 IN CASE OF CONFLICT BETWEEN THE GENERAL NOTES,
SPECIFICATIONS, DRAWINGS, OR WITHIN THESE DOCUMENTS, THE
MOST STRINGENT REQUIREMENTS AS DETERMINED BY THE
CONTRACTING OFFICER WILL GOVERN.
G-9 WORK NOT INDICATED ON A PART OF THE DRAWINGS, BUT
REASONABLY IMPLIED TO BE SIMILAR TO THAT SHOWN AT
CORRESPONDING LOCATIONS, IS TO BE REPEATED.
FOUNDATIONS
F-1 FOUNDATIONS HAVE BEEN DESIGNED IN ACCORDANCE WITH
CRITERIA ESTABLISHED BY TERRACON IN THEIR GEOTECHNICAL
REPORT PREPARED FOR THIS PROJECT DATED FEBRUARY 5, 2024.
F-2 FOUNDATIONS MUST BE PLACED ON COMPACTED SOIL MEETING THE
REQUIREMENTS OF STRUCTURAL FILL OR ON LEAN CONCRETE
BACKFILL.
F-3 THE CONTRACTOR IS TO RETAIN THE SERVICES OF A PROFESSIONAL
GEOTECHNICAL ENGINEER, SUBJECT TO THE APPROVAL OF THE
OWNER, TO VERIFY THAT THE MATERIAL ON WHICH FOUNDATIONS
BEAR HAS AT LEAST THE CAPACITY AS NOTED IN THE DESIGN
CRITERIA. THE GEOTECHNICAL ENGINEER IS TO MAKE
RECOMMENDATIONS FOR IMPROVING AREAS THAT DO NOT MEET
THE DESIGN CRITERIA.
F-4 EXTERIOR FOOTINGS ARE TO BEAR A MINIMUM OF 26 INCHES BELOW
FINISHED GRADE. ELEVATIONS SHOWN ON THE DRAWINGS AT WHICH
FOUNDATIONS BEAR ARE APPROXIMATE AND MAY VARY TO SUIT
SUBSURFACE SOIL CONDITIONS. STEP-IN FOOTING LOCATIONS
SHOWN ON THE DRAWINGS MUST BE FIELD VERIFIED AND ADJUSTED
SO THAT FOUNDATIONS BEAR ON MATERIAL OF AT LEAST THE
CAPACITY NOTED ABOVE.
F-5 PRIOR TO PLACING CONCRETE, WATER PRESENT MUST BE PUMPED
OUT FROM THE BOTTOM OF EXCAVATIONS.
F-6 CONCRETE SLABS-ON-GRADE HAVE BEEN DESIGNED TO BEAR ON
COMPACTED SUB-GRADE SOILS. THE DRAINAGE BASE COURSE
MATERIAL BENEATH THE SLAB-ON-GRADE IS TO BE FREE-DRAINING
(LESS THAN 5% PASSING THE US NO. 200 SIEVE) AND BE COMPACTED
TO AT LEAST 95% OF ASTM D 1557.
F-7 NO BACKFILLING AGAINST WALLS IS ALLOWED UNTIL THE SLABS AT
THE TOP AND BOTTOM HAVE BEEN PLACED OR ADEQUATE SHORING
HAS BEEN PROVIDED. WALLS AND GRADE BEAMS HAVING BACKFILL
AGAINST BOTH SIDES ARE TO HAVE BACKFILL PLACED ON BOTH
SIDES UNIFORMLY SO AS NOT TO EXCEED AN 8” DIFFERENTIAL.
F-8 EQUIPMENT AND/OR MATERIALS WITH WEIGHT GREATER THAN THE
DESIGN SURCHARGE MUST MAINTAIN A SAFE HORIZONTAL CLEAR
DISTANCE FROM BASEMENT AND RETAINING WALLS. A SAFE
HORIZONTAL CLEAR DISTANCE IS DEFINED AS THE DISTANCE FROM
THE BASE OF THE RETAINING WALL TO THE TOP OF FINISHED GRADE.
DESIGN SURCHARGE EQUALS 100 PSF.
F-9 THE FOUNDATION SYSTEM HAS BEEN DESIGNED TO SUPPORT A PRE-
ENGINEERED BUILDING BASED UPON A DESIGN ANALYSIS
PERFORMED BY THE STRUCTURAL ENGINEER. THE FOLLOWING
CONCRETE REQUIREMENTS FOR PRE-ENGINEERED BUILDING APPLY:
A. THE FOUNDATION MUST BE SQUARE AND LEVEL. OUT OF LEVEL
TOLERANCE FOR TOP OF CONCRETE PIERS AND WALLS IS +/-1/8"
IN 20'-0" AND +/-1/4" IN OVERALL LENGTH. TOLERANCE BETWEEN
CENTERLINES OF COLUMN ANCHOR BOLT CLUSTERS IS +/-1/8" IN
20'-0" AND +/-1/4" OVERALL.
B. ADJUST THE ELEVATION OF THE TOP OF PIERS IN ACCORDANCE
WITH BUILDING MANUFACTURER'S STANDARD. TROWEL FINISH
TOP OF CONCRETE AT COLUMN BASES.
C. ADJUST DIMENSIONS OF CONCRETE PIERS GIVEN TO PROVIDE A
MINIMUM OF 2" BEYOND EACH SIDE OF THE COLUMN BASE PLATE.
NOTE: PIER SIZE GIVEN IS MINIMUM, REVISIONS TO PIER SIZES
SHOWN ON THE DRAWINGS MUST BE PROVIDED TO THE
ENGINEER FOR REVIEW.
D. ANCHOR RODS MUST BE SET BY MEANS OF A TEMPLATE. (DO
NOT HAND SET)
E. MISCELLANEOUS JAMB POSTS MUST BE ANCHORED TO
FOUNDATION BY MEANS OF POST-INSTALLED ANCHORS AS PER
BUILDING MANUFACTURER'S DRAWINGS.
REINFORCED CONCRETE
C-1 REINFORCED CONCRETE WORK MUST BE IN ACCORDANCE WITH THE
AMERICAN CONCRETE INSTITUTE (ACI) "BUILDING CODE
REQUIREMENTS FOR STRUCTURAL CONCRETE - ACI 318" (LATEST
EDITION) AND THE “SPECIFICATIONS FOR STRUCTURAL CONCRETE
FOR BUILDINGS- ACI 301” (LATEST EDITION).
C-2 PRIOR TO CONCRETE PLACEMENT, THE CONTRACTOR MUST SUBMIT
CONCRETE MIX DESIGNS FOR EACH TYPE OF CONCRETE TO BE
USED, PREPARED IN ACCORDANCE WITH THE PROJECT
SPECIFICATIONS, TO THE CONTRACTING OFFICER FOR REVIEW.
C-3 CAST-IN-PLACE CONCRETE MUST HAVE A MINIMUM 28 DAY
COMPRESSIVE STRENGTH (f'c) AS INDICATED ON THE CONCRETE
MATERIALS SCHEDULE ON DRAWING S-601.
C-4 REINFORCEMENT:
A. DEFORMED BARS: ASTM A 615/A 615M, GRADE 60
B. WELDED WIRE REINFORCEMENT: ASTM A 1064
C-5 SPLICES (LAPS) OF REINFORCING BARS MUST BE CLASS ‘B’ TENSION
LAPS PER ACI 318 (LATEST EDITION) UNLESS NOTED OTHERWISE.
REFER TO THE MINIMUM LAP SPLICES OF REINFORCING BARS IN
TENSION SCHEDULE ON DRAWING S-601.
C-6 PROVIDE ADEQUATE CONCRETE COVER IN ACCORDANCE WITH THE
REQUIREMENTS AS SET FORTH BY ACI 318. REFER TO THE
CONCRETE COVER SCHEDULE ON DRAWING S-601.
C-7 CONTINUOUS REINFORCING BARS MUST BE TURNED AND LAPPED AT
CORNERS AND INTERSECTIONS OF WALLS AND FOOTINGS. HOOKED
BARS TO HAVE STANDARD ACI HOOKS UNLESS NOTED OTHERWISE.
C-8 CONTINUOUS TOP BARS MUST BE SPLICED AT MID-SPAN.
CONTINUOUS BOTTOM BARS MUST BE SPLICED AT CENTERLINE OF
SUPPORTS (OR AS SHOWN ON DETAILS).
C-9 WELDED WIRE REINFORCEMENT MUST BE SUPPLIED IN FLAT SHEETS
ONLY. LAP WELDED WIRE REINFORCEMENT TWO FULL MESH
LENGTHS AT SPLICES AND WIRE TOGETHER. PLACE WELDED WIRE
REINFORCEMENT WITHIN THE SLAB THICKNESS PER THE TYPICAL
DETAILS.
C-10 CONCRETE SLABS MUST BE CURED BY METHOD COMPATIBLE WITH
SPECIFIED FLOOR FINISH. WHERE ACCEPTABLE USE A LIQUID
MEMBRANE-CURING COMPOUND AT THE MANUFACTURERS
RECOMMENDED COVERAGE.
C-11 SLOPE SLABS-ON-GRADE TO DRAIN. MAINTAIN MINIMUM DESIGN
THICKNESS INDICATED.
C-12 DIVIDE FLOOR SLABS-ON-GRADE INTO SEGMENTS BY MEANS OF
ISOLATION, CONTROL AND CONSTRUCTION JOINTS AS INDICATED ON
THE DRAWINGS. SAW JOINTS MUST BE CUT AS SOON AS POSSIBLE
WITHOUT RAVELING THE SURFACE. POSITION OF CONSTRUCTION
JOINTS OTHER THAN THOSE SHOWN ON THE DRAWINGS MUST BE
SUBMITTED TO THE CONTRACTING OFFICER FOR APPROVAL.
C-13 SLAB-ON-GRADE CONTROL JOINTS MUST BE PLACED ON COLUMN
CENTERLINES UNO. CONTROL JOINTS MUST BE PLACED AT EQUAL
INTERVALS IN EACH DIRECTION AS INDICATED ON THE PLANS. ADAPT
CONTROL JOINT LOCATION AT ODD BAYS. CONSTRUCTION JOINTS
MUST BE PLACED AT CONTROL JOINT LOCATIONS AT CONTRACTOR’S
DISCRETION UNO ON PLAN.
C-14 SLEEVES, INSERTS, MECHANICAL OPENINGS, CONDUITS, PIPES,
RECESSES, DEPRESSIONS, CURBS AND OTHER EMBEDDED ITEMS
MUST BE PROVIDED AS SHOWN ON THE ARCHITECTURAL,
MECHANICAL, FIRE PROTECTION, PLUMBING AND ELECTRICAL
DRAWINGS AND BY EQUIPMENT MANUFACTURERS. INSTALLATION OF
THESE ITEMS MUST BE COORDINATED AND PROVIDED FOR PRIOR TO
PLACING CONCRETE.
C-15 OPENINGS IN CONCRETE SLABS AND/OR CONCRETE WALLS MUST
HAVE ADDITIONAL REINFORCEMENT PER THE TYPICAL DETAILS. NO
PENETRATIONS ARE PERMITTED THROUGH ANY CONCRETE
BEAM, JOIST, COLUMN, PIER OR JAMB WITHOUT THE ENGINEER’S
WRITTEN APPROVAL. PENETRATIONS MUST BE RE-ROUTED AS
REQUIRED AT THESE LOCATIONS.
C-16 PENETRATIONS THROUGH CONCRETE SLABS AND/OR CONCRETE
WALLS MUST BE PLACED DURING CONSTRUCTION OF THE WALL WITH
THE APPROPRIATE SLEEVE.
C-17 ANCHOR RODS TO BE ASTM F 1554 Fy = 36 KSI MINIMUM, UNLESS
NOTED OTHERWISE. DIAMETER AND LOCATIONS MUST BE AS
INDICATED ON THE PRE-ENGINEERED METAL BUILDING DRAWINGS
(BY OTHERS). ANCHOR ROD EMBEDMENT MUST BE AS INDICATED ON
THESE STRUCTURAL DRAWINGS.
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
04/04/2024
ABBREVIATIONS
RO ROUGH OPENING
RTU ROOF TOP UNIT
S SOUTH
SC SLIP CRITICAL
SCHED SCHEDULE
SDI STEEL DECK INSTITUTE
SECT SECTION
SF SQUARE FOOT
SHT SHEET
SIM SIMILAR
SL SLOPE, SLOPED OR SLOPING
SLV SLEEVE
SOG SLAB ON GRADE
SP SPACE, SPACES OR SPACING
SPEC SPECIFY, SPECIFIED OR SPECIFICATIONS
SQ SQUARE
SQ FT SQUARE FOOT
SS STAINLESS STEEL
STD STANDARD
STIFF STIFFENER
STL STEEL
STRUCT STRUCTURAL
SUSP SUSPEND, SUSPENDED OR SUSPENSION
T&B TOP & BOTTOM
T/ TOP OF
T/C TOP OF CURB
TEMP TEMPORARY
TERM TERMINATE OR TERMINAL
THD THREAD OR THREADED
THK THICK OR THICKNESS
THRESH THRESHOLD
TRANS TRANSVERSE
TRTD TREATED
TSF TONS PER SQUARE FEET
TYP TYPICAL
UNO UNLESS NOTED OTHERWISE
VERT VERTICAL
VIF VERIFY IN FIELD
W WEST
WDH WIDTH
W/ WITH
W/O WITHOUT
WL WIND LOAD
WP WORKING POINT
WT WEIGHT
WWR WELDED WIRE REINFORCEMENT
A/E ARCHITECT/ENGINEER
AB ANCHOR BOLT
ABV ABOVE
ACI AMERICAN CONCRETE INSTITUTE
ADDL ADDITIONAL
ADJ ADJACENT
ADJBL ADJUSTABLE
AFF ABOVE FINISHED FLOOR
AHU AIR HANDLING UNIT
AISC AMERICAN INSTITUTE OF STEEL CONSTRUCTION
ALT ALTERNATE
APPROX APPROXIMATE OR APPROXIMATELY
ARCH ARCHITECT OR ARCHITECTURAL
ASTM AMERICAN SOCIETY FOR TESTING MATERIAL
AVG AVERAGE
B PL BASE PLATE OR BEARING PLATE
B/ BOTTOM OF
B/C BOTTOM OF CURB
BD BOARD
BF BOTH FACES
BFF BELOW FINISHED FLOOR
BIT BITUMINOUS
BLDG BUILDING
BLK BLOCK
BLKG BLOCKING
BLW BELOW
BMK BENCH MARK
BM BEAM
BOT BOTTOM
BR BRICK
BRG BEARING
BRKT BRACKET
BS BOTH SIDES
BSMT BASEMENT
BT BENT
BTWN BETWEEN
CB CATCH BASIN
CC CENTER TO CENTER
CEM PL CEMENT PLASTER
CF CUBIC FOOT OR CUBIC FEET
CHAM CHAMFER
CIP CAST IN PLACE
CJ CONTROL JOINT
CL CENTERLINE
CLR CLEAR
CMU CONCRETE MASONRY UNIT
CO CLEAN OUT
COL COLUMN
CONC CONCRETE
CONN CONNECTION
CONST CONSTRUCTION
CONT CONTINUOUS
CONTR CONTRACTOR
COOR COORDINATE
CORR CORRIDOR
CRSE COURSE
CRSI CONCRETE REINFORCING STEEL INSTITUTE
CY CUBIC YARD
db BAR DIAMETER
DBL DOUBLE
DIA DIAMETER
DIAG DIAGONAL
DIM DIMENSION
DL DEAD LOAD
DN DOWN
DTL DETAIL
DWG DRAWING
DWL DOWEL
E EAST
EA EACH
EF EACH FACE
EIFS EXTERIOR INSULATION FINISH SYSTEM
EJ EXPANSION JOINT
ELE ELEVATOR
ELEC ELECTRICAL
ELEV ELEVATION
EMBED EMBED, EMBEDED OR EMBEDMENT
ENCL ENCLOSE OR ENCLOSURE
ENGR ENGINEER
EOS EDGE OF SLAB
EQ EQUAL
EQUIP EQUIPMENT
EST ESTIMATE OR ESTIMATED
EW EACH WAY
EXC EXCAVATE OR EXCAVATION
EXCL EXCLUDE OR EXCLUDING
EXIST EXISTING
EXP EXPANSION
EXP BLT EXPANSION BOLT
EXT EXTERIOR
F/F FACE TO FACE
FD FLOOR DRAIN
FDN FOUNDATION
FF FAR FACE
FIN FINISH OR FINISHED
FL FLOOR
FPRF FIREPROOF OR FIREPROOFING
FS FAR SIDE
FT FOOT OR FEET
FTG FOOTING
GA GAUGE/GAGE
GALV GALVANIZED
GB GRADE BEAM
GC GENERAL CONTRACTOR
GD GRADE(ING)
GRAV GRAVEL
GRD GROUND
GRT GROUT
HM HOLLOW METAL
HORIZ HORIZONTAL
HP HIGH POINT
HT HEIGHT
ID INSIDE DIAMETER
IN INCH(ES)
INCL INCLUDE
INFO INFORMATION
INT INTERIOR
ISO JT ISOLATION JOINT
JB JAMB
JST JOIST
JT JOINT
K KIP(S)
KB KNEE BRACE
KCF KIPS PER CUBIC FEET
KLF KIPS PER LINEAR FOOT
KSF KIPS PER SQUARE FEET
KSI KIPS PER SQUARE INCH
L LENGTH
LB POUND
ld DEVELOPMENT LENGTH
LF LINEAR FOOT
LG LONG
LL LIVE LOAD
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LONG LONGITUDINAL
LP LOW POINT
LTL LINTEL
MEP MECHANICAL, ELECTRICAL & PLUMBING
MAS MASONRY
MATL MATERIAL
MAX MAXIMUM
MCJ MASONRY CONTROL JOINT
MECH MECHANICAL
MEMB MEMBRANE
MEZZ MEZZANINE
MFR MANUFACTURE(R)
MH MANHOLE
MID MIDDLE
MIN MINIMUM
MISC MISCELLANEOUS
MLTP MULTIPLE
MO MASONRY OPENING
MP MASONRY PIER
MTL METAL
N NORTH
NF NEAR FACE
NIC NOT IN CONTRACT
NM NORMAL
No. NUMBER
NOM NOMINAL
NS NEAR SIDE
NTS NOT TO SCALE
OC ON CENTER
OD OUTSIDE DIAMETER
OPNG OPENING
OPH OPPOSITE HAND
OZ OUNCE
PART PARTITION
PCF POUNDS PER CUBIC FOOT
PCI POUNDS PER CUBIC INCH
PEMB PRE-ENGINEERED METAL BUILDING
PERF PERFORATED
PERM PERIMETER
PL PLATE
PLF POUNDS PER LINEAR FOOT
PLYWD PLYWOOD
PRCST PRECAST
PREFAB PREFABRICATED
PREMLD PREMOLDED
PROP PROPERTY
PROT PROTECT(ED)(ION)
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PSIG POUNDS PER SQUARE INCH GAUGE
PT POINT
PVMT PAVEMENT
QTY QUANTITY
RAD RADIUS OR RADII
RD ROOF DRAIN
RE: REFER TO
REC RECESSED
REINF REINFORCE, REINFORCING OR REINFORCEMENT
REQ'D REQUIRED
REV REVISE OR REVISION
RF ROOF
SYMBOLS
CL
PL
S( ) L( ) C( )
LL( )
HSS( )
MC( )
WT( )
W( )
EQUAL
STRUCTURAL TEE
WIDE FLANGE
PLATE
ANGLE
HOLLOW STRUCTURAL SECTION
MISCELLANEOUS CHANNEL
DOUBLE ANGLE
CHANNEL
AMERICAN STANDARD SHAPE
PERPENDICULAR
PERCENT
PARALLEL
NUMBER
DIAMETER
ELEVATION
DEGREE
AT
CENTERLINE
ANGLE
K( ) OPEN WEB STEEL JOIST
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
S Y
S T
E M
S C
O M
M A
N D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D W
A S
H
IN
G T
O N
W A
S H
IN
G
T O
N N
A V
Y Y
A R
D
D .C
AS NOTED
3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092
W A
S H
IN
G
T O
N D
C C
O R
E
N A
V A
L A
IR
S
T A
T
IO
N P
A T
U X
E N
T R
IV
E
R S
T . M
A R
Y 'S
C O
U N
T Y
, M D
F Y
M
IL
C O
N P
1737036
CONTROLLED UNCLASSIFIED INFORMATION
C O
N T
R O
L L E
D U
N C
L A
S S
IF
IE
D I N
F O
R M
A T
IO
N
CONTROLLED UNCLASSIFIED INFORMATION
C O
N T
R O
L L E
D U
N C
L A
S S
IF
IE
D I N
F O
R M
A T
IO
N
PM/CN
TC
SS
03/15/2024
GR
/3
/2
:1
:1
P M
C U s e rs
\j a m e s .c u m m in g s \D o c u m e n ts \B
L D
G -P
-A O
P -1
-S
J a m e s .C u m m in g s B
B Z
R A
.r v t
V2 S-002
G E
N E
R A
L N
O T
E S
, A B
B R
E V
IA
TI
O N
S A
N D
S Y
M B
O
LS
DRB
13150102
JDZ JAC
V O
LU
M
E
A
IR
O
P S
B U
IL
D
IN
G
S -0
100% FINAL SUBMITTAL
METAL BUILDING SYSTEMS
MB-1 DESIGN, FABRICATION AND ERECTION OF THE PRE-ENGINEERED METAL BUILDING SYSTEM MUST
BE SUFFICIENT TO WITHSTAND LOADS FROM WIND, SNOW, GRAVITY, STRUCTURAL MOVEMENT
AND SEISMIC ACTION WITHOUT EXCEEDING ALLOWABLE STRESSES AND MUST BE IN
ACCORDANCE WITH THE LATEST EDITIONS OF THE FOLLOWING CODES:
A. METAL BUILDING MANUFACTURERS ASSOCIATION (MBMA) “METAL BUILDING SYSTEMS
MANUAL” (LATEST EDITION).
B. AMERICAN INSTITUTE OF STEEL CONSTRUCTION (AISC) “SPECIFICATIONS FOR STRUCTURAL
STEEL BUILDINGS” AND STEEL DESIGN GUIDE SERIES 3: “SERVICEABILITY DESIGN
CONSIDERATIONS FOR LOW-RISE BUILDINGS”.
C. IRON AND STEEL INSTITUTE (AISI) “NORTH AMERICAN SPECIFICATION FOR THE DESIGN OF
COLD FORMED STEEL STRUCTURAL MEMBERS” (LATEST EDITION).
D. AMERICAN WELDING SOCIETY (AWS) “STRUCTURAL WELDING CODE STEEL AWS D1.1/D1.1M”.
E. UNITED FACILITIES CRITERIA, UFC 3-301-01, “STRUCTURAL ENGINEERING”.
MB-2 DEFORMATIONS OF THE PRE-ENGINEERED BUILDING (INCLUDING BUT NOT LIMITED TO LATERAL DRIFT, RACKING OF FRAMES, AND HORIZONTAL AND OR VERTICAL DEFLECTION OF STRUCTURAL
ELEMENTS, CLADDING OR OTHER SUPPORTED ELEMENTS), IS TO BE LIMITED BY THE
RECOMMENDATIONS SET FORTH IN AISC’S STEEL DESIGN GUIDE SERIES 3: “SERVICEABILITY
DESIGN CONSIDERATIONS FOR LOW-RISE BUILDINGS,” AND AS FOLLOWS:
A. LATERAL SWAY OF MAIN FRAMES AT EAVE HEIGHT H/240 MAX
B. LATERAL SWAY OF MAIN FRAMES AT TOP OF MASONRY WALL H/240 OR 1-1/2” MAX
C. HORIZ DEFLECTION OF GIRTS SUPPORTING MASONRY WALL L/240 or 1-1/2” MAX
D. HORIZ DEFLECTION OF GIRTS SUPPORTING METAL SIDING L/120 OR 2” MAX
E. VERTICAL DEFLECTION OF MAIN FRAME L/240 OR 6” MAX
F. VERTICAL DEFLECTION OF PURLINS L/240 OR 1-1/2” MAX
G. RACKING OF MAIN FRAME H/500 (H=EAVE HT)
H. RACKING OF END WALLS H/500 (H=EAVE HT)
I. LATERAL MOVEMENT OF ELEMENTS SUPPORTING DRYWALL
PARTITIONS (H= PARTITION HT) H/500
MB-3 WIND FORCES USED FOR COMPUTATION OF MEMBER STRESSES ARE TO BE BASED ON THE
BASIC WIND SPEED PER ASCE 7. COMPUTE DRIFT DUE TO WIND BASED ON A WIND SPEED WITH A
10 YEAR MEAN RECURRENCE INTERVAL (MRI).
MB-4 PRIOR TO FABRICATION, CONTRACTOR IS TO SUBMIT THE FOLLOWING ITEMS TO THE
CONTRACTING OFFICER FOR REVIEW. SUBMITTED ITEMS MUST BE PREPARED BY, OR UNDER
THE SUPERVISION OF, A PROFESSIONAL ENGINEER REGISTERED IN THE STATE THAT THE
PROJECT WILL BE CONSTRUCTED AND BEAR THE SEAL OF THAT PROFESSIONAL ENGINEER.
A. SUBMIT ERECTION DRAWINGS TO INCLUDE DETAILS SHOWING ERECTION AND ASSEMBLY OF
THE METAL BUILDING SYSTEM INCLUDING SIDE WALL, END WALL, ROOF CANOPY AND ROOF
FRAMING. INCLUDE BUILDING TRANSVERSE AND CROSS SECTIONS WITH WIND AND SEISMIC
BRACING PRESENT FOR THE BUILDING SYSTEM.
B. SUBMIT ANCHOR ROD PLACEMENT DRAWING TO SHOW ANCHOR ROD LOCATIONS. INCLUDE
CALCULATED FOUNDATION LOADS AT THE BASE OF COLUMNS.
C. SUBMIT PANEL LAYOUTS ON WALLS, ROOF CANOPIES AND ROOFS. DETAILS OF SUPPORTS
ANCHORAGES AND SPECIAL CONDITIONS. INCLUDE DETAILS OF PANEL PROFILES.
MB-5 CONTRACTOR IS TO ENGAGE AN EXPERIENCED INSTALLER TO ERECT THE PRE-ENGINEERED
METAL BUILDING WHO IS EXPERIENCED IN THE ERECTION OF METAL BUILDINGS AND WHO IS
CERTIFIED IN WRITING BY THE METAL BUILDING SYSTEM MANUFACTURER AS QUALIFIED FOR
ERECTION OF THE MANUFACTURER’S PRODUCTS.
MB-6 FABRICATE FRAMING COMPONENTS IN THE SHOP TO THE GREATEST EXTENT POSSIBLE. IN
GENERAL, SHOP WELD AND FIELD BOLT CONNECTIONS.
MB-7 EXERCISE CARE IN DELIVERING, UNLOADING, STORING AND ERECTING BUILDING MEMBERS, WALL AND ROOF COVERING PANELS AND OTHER BUILDING COMPONENTS TO PREVENT BENDING, WARPING, TWISTING AND SURFACE DAMAGE.
MB-8 ERECT FRAMING TRUE TO LINE, LEVEL AND PLUMB. LEVEL BASE PLATES TO A TRUE PLANE WITH
FULL BEARING TO SUPPORTING STRUCTURE; USE A NON-SHRINKING GROUT TO OBTAIN
UNIFORM BEARING AND TO MAINTAIN A LEVEL BASE LINE ELEVATION.
MB-9 PROVIDE LATERAL LOAD RESISTING SYSTEMS TO RESIST THE INDICATED WIND AND SEISMIC
LOADS IN ROOF AND SIDE WALLS. WHERE OVERHEAD DOORS INTERFERE WITH DIAGONAL
BRACING, PROVIDE STRUCTURAL WIND FRAMES. PROVIDE SAG RODS TO MAINTAIN VERTICAL
ALIGNMENT OF WALL GIRTS. REFERENCE THE PLAN DRAWINGS FOR PERIMETER BRACING AND
FRAME LOCATIONS.
MB-10 PROVIDE FRAMED DOOR AND WINDOW OPENINGS OF DESIGN AND SIZE TO ACCOMMODATE
FINISHED UNITS AND TO TRANSMIT ALL LOADS TO THE BUILDING STRUCTURE.
MB-11 THE FOUNDATION DESIGN ON THESE CONTRACT DRAWINGS IS PRELIMINARY AND BASED UPON
ASSUMED COLUMN BASE REACTIONS CALCULATED BY A STRUCTURAL ENGINEER. THESE
REACTIONS ARE INDICATED IN A TABLE ON DRAWING S-602. UPON FINAL BUILDING DESIGN, THE
ACTUAL COLUMN BASE REACTIONS ARE TO BE COMPARED TO THE PRELIMINARY FOUNDATION
DESIGN LOADS BY THE GENERAL CONTRACTOR. IF THE ACTUAL REACTIONS EXCEED THE
PRELIMINARY DESIGN LOADS, THE FOUNDATION DESIGN PROVIDED IS VOID AND A REGISTERED
PROFESSIONAL ENGINEER MUST BE EMPLOYED BY THE GENERAL CONTRACTOR TO COMPLETE
A FOUNDATION DESIGN BASED UPON THE ACTUAL REACTIONS.
A. COLUMN BASES ARE TO BE PINNED. FIXED BASES ARE NOT PERMITTED.
B. ANCHOR ROD DIAMETERS, AND SPACINGS ARE TO BE PROVIDED FOR BY THE PEMB
MANUFACTURER AND COMPLY WITH THE FOOTING AND DETAILS REFERENCED.
MB-13 THE GENERAL CONTRACTOR IS TO COORDINATE WITH THE PEMB MANUFACTURER AND
MECHANICAL SUBCONTRACTORS TO PROVIDE SUPPORT FOR SUSPENDED EQUIPMENT, PIPING,
DUCTWORK AND UTILITIES IDENTIFIED ON THESE STRUCTURAL DRAWINGS, MEP DRAWINGS, FIRE
PROTECTION DRAWINGS, ARCHITECTURAL DRAWINGS, OR OTHERWISE NOTED OR REQUIRED.
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
A
2 3 4 5 6
B
C
D
98'-0"
19'-0" 20'-0" 20'-0" 20'-0" 19'-0"
'-0
'-0
'-0
'-0
C J
S L S L
SL
SL
C
J
C J
C J
CJ
CJ
TYP. UNO
S8
C1 S-301
TYP
C1 S-301
TYP
C1
S-301
TYP
C1 S-301
TYP
A1
S-301
C4
S-301C4
S-301
1'-4" 1'-4"
C2
S-301
TYP AT
COL
C2 S-301
TYP AT
COL
WF2.8 (TYP)
F7.0
P3AF5.5
P1A
F5.5
P4
F5.5
P4
F5.5
P4A
F5.5
P4A
F7.0
P3A
F8.0
P3A
F8.0
P3A F5.5
P2A
F7.0
P3
F7.0
P3
F8.0
P3
F8.0
P3
F5.5
P2
F5.5
P1 W
F 2.
(T
Y P
WF2.8 (TYP)
W F
2.
(T Y
P
AT OH DOOR
AT MANDOOR
1. RE: DRAWING S-001 & S-002 FOR GENERAL NOTES AND DESIGN CRITERIA.
2. TOP OF SLAB ELEVATION = RE: CIVIL. THIS ELEVATION IS THE DATUM
ELEVATION = 0'-0". ALL ELEVATIONS ARE REFERENCED FROM
THIS ELEVATION.
3. COORDINATE DIMENSIONS, WALL OPENINGS ELEVATIONS, SECTIONS AND
DETAILS WITH ARCHITECTURAL DRAWINGS.
4. COORDINATE LOCATIONS OF ALL FLOOR PENETRATIONS WITH M/E/P
DRAWINGS.
5. RE: DRAWINGS S-501 & S-502 FOR TYPICAL FOUNDATION AND SLAB DETAILS.
6. TOP OF CONCRETE PIER ELEVATION = -0'-8" (TYP UNO)
7. TOP OF CONCRETE FOOTING ELEVATION = -2'-8" (TYP UNO)
SPREAD FTG
MARK
T/FTG ELEV.
PIER MARK
WALL FTG MARK
WFX
FX
GRID
GRID
NOTE:
1. RE: STRUCTURAL FOUNDATION AND PIER SCHEDULES ON S-601 AND
S-602 FOR MARK TYPES.
PX ( )
T/PIER ELEV.
SLAB-ON-GRADE TYPE
RE: SCHEDULE ON S-601
S#
PEMB COLUMN
SL
S L
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
S Y
S T
E M
S C
O M
M A
N D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D W
A S
H
IN
G T
O N
W A
S H
IN
G
T O
N N
A V
Y Y
A R
D
D .C
AS NOTED
3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092
W A
S H
IN
G
T O
N D
C C
O R
E
N A
V A
L A
IR
S
T A
T
IO
N P
A T
U X
E N
T R
IV
E
R S
T . M
A R
Y 'S
C O
U N
T Y
, M D
F Y
M
IL
C O
N P
1737036
CONTROLLED UNCLASSIFIED INFORMATION
C O
N T
R O
L L E
D U
N C
L A
S S
IF
IE
D I N
F O
R M
A T
IO
N
CONTROLLED UNCLASSIFIED INFORMATION
C O
N T
R O
L L E
D U
N C
L A
S S
IF
IE
D I N
F O
R M
A T
IO
N
PM/CN
TC
SS
03/15/2024
GR
/3
/2
:1
:1
P M
C U s e rs
\j a m e s .c u m m in g s \D o c u m e n ts \B
L D
G -P
-A O
P -1
-S
J a m e s .C u m m in g s B
B Z
R A
.r v t
V2 S-101
F O
U N
D A
T
IO
N P
LA
N
DRB
13150103
JDZ JAC
V O
LU
M
E
A
IR
O
P S
B U
IL
D
IN
G
S -1
100% FINAL SUBMITTAL
SCALE: 1/8" = 1'-0"
FOUNDATION PLAN
FOUNDATION PLAN NOTES
SHEET KEYNOTES
SYMBOLS LEGEND
2 BOLLARD, TYP. RE: A1/S-501
11 PROVIDE SLAB ISOLATION JOINT AT ALL COLUMNS, RE: C4/S-501.
12 PROVIDE ADDITIONAL SLAB REINFORCEMENT AT ALL RE-ENTRANT
CORNERS AND DISCONTINUOUS SLAB JOINTS, RE: B3/S-501.
40 ASSUMED BRACED FRAME LOCATION
CJ SLAB CONTROL JOINT. SPACE CONTROL JOINTS AT COLUMNS AND
EQUALLY BETWEEN COLUMNS AS SHOWN AT A SPACING NOT
EXCEEDING 20'-0" WITH A LENGTH TO WIDTH RATIO NO GREATER
THAN 1:25:1.00. RE: C1/S-501.
SL STEEL LINE
PLAN
NORTH
1/8" = 1' - 0" 0 5' 10' 15' 30'
GRAPHIC SCALE(S)
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
FIN GRADE
RE: CIVIL
T/FTG
RE: PLAN
T/SLAB
RE: PLAN
ATTACHMENT BY PEMB
MFR @ 3'-0" MAX
R E
: N O
T E
2'
M
IN
#5 @ 16" OC, EW
FOOTING
RE: PLAN & SCHED
1/2" ISOLATION JOINT
RE: C2/S-501
SLAB-ON-GRADE
RE: PLAN
6" MAX
2" MIN
3/4" CHAMFER
D
A
CONT. 8" CIP WALL
STEEL LINE
T/WALL
EL = 1'-4"
8" CEE GIRT BY
PEMB MFR
NOTE: FOR SLOPING GROUND, MINIMUM
EMBEDMENT DEPTH APPLIES TO THE LOWEST
EXTERIOR GRADE WITHIN 5 HORIZONTAL FEET OF
THE STRUCTURE.
EQ 8" EQ
MASONRY VENEER
RE: ARCH
GROUT SOLID
BELOW GRADE
FIN GRADE
RE: CIVIL
T/FTG
RE: PLAN
T/SLAB
RE: PLAN
T/PIER
RE: PLAN
COL & BASE PLATE
BY PEMB MFR
1/2" EXP JT
SLAB-ON-GRADE
RE: PLAN
ISOLATION POUR
RE: C4/S-501
NON-SHRINK
GROUT
FOOTING
RE: PLAN & SCHED
ATTACHMENT
RE: C1/S-301
CONTINUE WALL REINF
THROUGH PIER, TYP
8" CEE GIRT BY
PEMB MFR
EQ
D
A
8"
FACE OF PEMB
FRAMESTEEL LINE
T/WALL
EL = 1'-4"
R E
: N O
T E
2'
M
IN
MASONRY VENEER
RE: ARCH
GROUT SOLID
BELOW GRADE
NOTE: FOR SLOPING GROUND,
MINIMUM EMBEDMENT DEPTH APPLIES
TO THE LOWEST EXTERIOR GRADE
WITHIN 5 HORIZONTAL FEET OF THE
STRUCTURE.
EQ
FIN GRADE
RE: CIVIL
T/FTG
RE: PLAN
WALL AND GIRT
BEYOND
1/2" EXP JT
#5 DOWEL @ 12" OC
SLAB-ON-GRADE
RE: PLAN
RE-ENTRANT BAR
RE: PLAN
PAVING
RE: CIVIL
T/SLAB
RE: PLAN
#5 @ 16" OC, EW
FOOTING
RE: PLAN & SCHED
CONT. 8" CIP WALL
EQ 8" EQ
MASONRY VENEER
RE: ARCH
GROUT SOLID
BELOW GRADE
FIN GRADE
RE: CIVIL
T/FTG
RE: PLAN
1/2" EXP JT
#5 DOWEL @ 12" OC
SLAB-ON-GRADE
RE: PLAN
RE-ENTRANT BAR
RE: PLAN
PAVING
RE: CIVIL
1/ 2"
8"
DOWEL @ 12" OC
RE: C1/S-501 #5 @ 16" OC, EW
FOOTING
RE: PLAN & SCHED
CONT. 8" CIP WALL
T/SLAB
RE: PLAN
EQ 8" EQ
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
S Y
S T
E M
S C
O M
M A
N D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D W
A S
H
IN
G T
O N
W A
S H
IN
G
T O
N N
A V
Y Y
A R
D
D .C
AS NOTED
3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092
W A
S H
IN
G
T O
N D
C C
O R
E
N A
V A
L A
IR
S
T A
T
IO
N P
A T
U X
E N
T R
IV
E
R S
T . M
A R
Y 'S
C O
U N
T Y
, M D
F Y
M
IL
C O
N P
1737036
CONTROLLED UNCLASSIFIED INFORMATION
C O
N T
R O
L L E
D U
N C
L A
S S
IF
IE
D I N
F O
R M
A T
IO
N
CONTROLLED UNCLASSIFIED INFORMATION
C O
N T
R O
L L E
D U
N C
L A
S S
IF
IE
D I N
F O
R M
A T
IO
N
PM/CN
TC
SS
03/15/2024
GR
/3
/2
:1
:1
P M
C U s e rs
\j a m e s .c u m m in g s \D o c u m e n ts \B
L D
G -P
-A O
P -1
-S
J a m e s .C u m m in g s B
B Z
R A
.r v t
V2 S-301
F O
U N
D A
TI
O
N S
E C
T
IO
N S
DRB
13150104
JDZ JAC
V O
LU
M
E
A
IR
O
P S
B U
IL
D
IN
G
S -3
100% FINAL SUBMITTAL
SCALE: 3/4" = 1'-0"
TYP EXTERIOR WALL SECTION
C1
SCALE: 3/4" = 1'-0"
EXTERIOR WALL SECTION AT COLUMN
C2
SCALE: 3/4" = 1'-0"
EXTERIOR WALL SECTION AT MANDOOR
C4
SCALE: 3/4" = 1'-0"
EXTERIOR WALL SECTION AT OVERHEAD DOOR
A1
SCALE:
1'-0" 2'-0" 4'-0"
0'-0 3/4" = 1'-0"
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
T/SLAB
RE: PLAN
T/FTG
RE: PLAN
T/PAD
T/SLAB-ON-GRADE
RE: PLAN
1/2" EXPANSION JOINT
MATERIAL SEAL JOINT WITH
JOINT SEALER (1/2" DEEP)
CHAIR
PER SPECIFICATIONS
REINF CONC
SLAB-ON-GRADE
RE: PLAN
WALL, PIER, GRADE BEAM OR
EQUIPMENT FOUNDATION
RE: PLAN
COL COL
COL
COL
ISOLATION JOINT
RE: C2/S-501
(T
YP)
3" C
LR
PIER OR
BASE PLATE
EDGE OF SLAB
ON GRADE
(T
YP)
3" C
LR
(T
YP)
3" C
LR
CONTROL OR
CONST JT
ISOLATION POUR
TO TOP OF FOUNDATION
PIER OR
BASE PLATE
PIER OR
BASE PLATE
NOTE: REFER TO PLANS FOR ALTERNATE JOINT CONFIGURATIONS AND ACTUAL COLUMN SHAPES
ISOLATION POUR TO TOP
OF FOUNDATION
ISOLATION JOINT
RE: C2/S-501
A
COLUMN AT CORNER
B
COLUMN AT EXTERIOR
C
COLUMN AT INTERIOR
(T
YP)2'-
0"
(TYP)
4"
A AT DOOR
WALLS (MASONRY OR CONCRETE),
PIERS AND/OR COLUMNS WHICH
PENETRATE THE FLOOR SLAB
(1) #4 IN TOP 1/3
OF SLAB, EA SIDE
(TYP)
EDGE OF SLAB
OR JOINT
(1) #4 x 4'-0" LONG IN
TOP 1/3 OF SLAB (TYP)
(1) #4 x 4'-0" LONG IN
TOP 1/3 OF SLAB (TYP)
CONTROL
JOINT
(TYP)
4"
4"
B AT CORNER C AT DISCONTINUOUS JOINT
A
CONSTRUCTION JOINT
SAWCUT 1/4" WIDE x T/4
DEEP W/ EPOXY JOINT
FILLER
CHAIRS
PER SPECIFICATIONS
VAPOR RETARDER
COMPACTED
GRANULAR FILL
APPLY BOND BREAKER
A615 SMOOTH EPOXY COATED
1" DIA DOWEL x 1'-4" LONG @
12" OC, GREASE OR WRAP ONE
END W/POLYETHYLENE
T /2
STOP REINF 2" EA
SIDE OF JOINT CHAIRS
PER SPECIFICATIONS
VAPOR RETARDER
COMPACTED
GRANULAR FILL
T /2
STOP REINF 2" EA
SIDE OF JOINT
SAWCUT 1/4" WIDE x T/4
DEEP W/ EPOXY JOINT
FILLER
A615 SMOOTH EPOXY COATED
1" DIA DOWEL x 1'-4" LONG @
12" OC, GREASE OR WRAP ONE
END W/POLYETHYLENE
B
CONTROL JOINT
6"
4' -6
4'
-0
(T Y
P
12"x1"x1'-0" BASE PLATE W/ (4) 3/4"ø ANCHOR
RODS @ 9" GAGE EW
DRILL & ADHESIVE
GROUT (6" EMBED)(TYP)
1/4"
8"
STRUCTURAL SLAB
ROUNDED CONC
@ TOP (TYP)
6"ø STD PIPE (TYP)
FILL W/ CONC
1/2" EXP JT MATL
ISOLATION
JOINT
3"
3" 3"
#3
2"
(TYP)
1'-6" ø
(4) #5 VERT
CONC
ENCASEMENT
REINF CONC
SLAB-ON-GRADE
RE: PLAN
PROVIDE ADDITIONAL
SLAB REINFORCEMENT
RE: B3/S-501 (TYP)
SLOPE AWAY FROM
BOLLARD (TYP)
FOOTING
RE: PLAN
NOTES:
1. COORDINATE WITH CIVIL FOR BOLLARDS
NOT IMMEDIATELY ADJACENT TO, OR
INTERIOR OF, BUILDING STRUCTURES.
2. RE: ARCH FOR FINISH REQUIREMENTS.
A
AT STRUCTURAL SLAB
C
AT FOOTING
B
AT SLAB-ON-GRADE OR PAVEMENT
R E
: P
LA
N
#4 @ 8" OC EW
ROUGHEN SURFACE TO 3/4"
AMPLITUDE, ROVIDE BONDING
AGENT PRIOR TO PACING
NEW CONCRETE
TYP
4" MIN
PROVIDE EPOXY BASED ADHESIVE
GROUTED ANCHORS W/ STD
EMBED. QTY AND DIA AS REQD BY
EQUIP MFR
#4 DOWELS @ 12" OC (4 MIN)
ADHESIVE GROUT INTO EXIST
SLAB (3" EMBED)
NOTES:
1. COORDINATE SIZE & LOCATION WITH EQUIPMENT
REQUIREMENTS & MEP DRAWINGS.
2. CHAMFER ALL EDGES 1" TYPICAL.
M
IN 4"
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
CONSTR. CONTR. NO.
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
EPROJECT NO.:
D E
P A
R T
M E
N T
O F
T H
E N
A V
Y N
A V
A L
F A
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
S Y
S T
E M
S C
O M
M A
N D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
N A
V A
L F
A C
IL
IT
IE
S
E N
G
IN
E E
R
IN
G S
Y S
T E
M S
C O
M M
A N
D W
A S
H
IN
G T
O N
W A
S H
IN
G
T O
N N
A V
Y Y
A R
D
D .C
AS NOTED
3500 Parkway Lane, Suite 500 Peachtree Corners, GA 30092
W A
S H
IN
G
T O
N D
C C
O R
E
N A
V A
L A
IR
S
T A
T
IO
N P
A T
U X
E N
T R
IV
E
R S
T . M
A R
Y 'S
C O
U N
T Y
, M D
F Y
M
IL
C O
N P
1737036
CONTROLLED UNCLASSIFIED INFORMATION
C O
N T
R O
L L E
D U
N C
L A
S S
IF
IE
D I N
F O
R M
A T
IO
N
CONTROLLED UNCLASSIFIED INFORMATION
C O
N T
R O
L L E
D U
N C
L A
S S
IF
IE
D I N
F O
R M
A T
IO
N
PM/CN
TC
SS
03/15/2024
GR
/3
/2
:1
:1
P M
C U s e rs
\j a m e s .c u m m in g s \D o c u m e n ts \B
L D
G -P
-A O
P -1
-S
J a m e s .C u m m in g s B
B Z
R A
.r v t
V2 S-501
F O
U N
D A
TI
O
N A
N D
S
LA
B T
Y P
IC
A
L D
E
TA
IL
S
DRB
13150105
JDZ JAC
V O
LU
M
E
A
IR
O
P S
B U
IL
D
IN
G
S -5
100% FINAL SUBMITTAL
SCALE:NTS
TYP ISOLATION JOINT AT GRADE
C2
SCALE:NTS
TYP COLUMN/SLAB ISOLATION JOINTS
C4
SCALE:NTS
TYP RE-ENTRANT CORNER
B3
SCALE:NTS
TYP SLAB-ON-GRADE JOINTS
C1
SCALE:NTS
TYP BOLLARD 6"ø A1
SCALE:NTS
TYP EQUIPMENT PAD ON CONCRETE SLAB DETAIL
A4
S Y
M D
E S
C R
IP
T
IO
N
D A
T E
A P
P R
T/FTG
EA SIDE
1'-0" MIN
STEM
WALL
FOOTING
PROVIDE PIPE SLEEVE
PER M/E/P/FP/C DRAWINGS
UTILITY LINE, RE: OTHERS FILL PIPE TRENCH W/ CONC TO
BOTTOM OF FOOTING USING
LEAN MIX CONCRETE- 2000 PSI
X
4" MIN
(ALL AROUND, TYP)
NOTES:
1. IF X < 1/2 PIPE SLEEVE ø, RE: C2/S-502.
2. IF 1/2 PIPE SLEEVE ø < X, USE THIS DETAIL.
3. IF X ≥ 3FT PIPE DOES NOT REQ'R INTEGRATION W/ FOOTING.
STEM WALL
FOOTING
PROVIDE PIPE SLEEVE
PER M/E/P/FP/C DRAWINGS
STEP WALL FOOTING DOWN
BELOW PIPE ELEVATION
MATCH FOOTING REINF
M
IN
T /2
T
T
MIN
1'-0"
MULTIPLE BARS
4" TYP FOR
TYP
2" CLR
MULTIPLE BARS
4" TYP FOR
TYP
2" CLR
TYP
2" CLR
ADDL (1)-#5 BAR EA
FACE, ABOVE & BELOW
OPNGS. EXTEND BARS
2'-0" PAST OPNGS ON
EA SIDE
SLEEVE AT ALL PIPE
PENETRATIONS PER
M/E/P/FP/C DRAWINGS
ADDL (1)-#5 x 4'-0"
LONG DIAG BAR AT EA
CORNER AND EA FACE
MAX OPENING SIZE IS 3'-0" IN
EITHER DIRECTION
ADDL FULL HEIGHT VERT REINF (FULL LENGTH
MAIN…