Attachment B - Kitchen Hood Suppression Form.pdf
PDF 133 KB Posted
- Solicitation number
- W911S822R0002
View the file
Other files
Show all 26
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Joint Base Lewis-McChord
RANGE HOOD SYSTEM
Acceptance and Semi-Annual Certification
Facility Name: DATE:
Building Number: Address:
Procedure Upon completion of the work, inspection and tests shall be made by the contractor’s representative and witnessed by an owner’s representative. All defects shall be corrected and system left in service before contractor’s personnel finally leave the job.
A certificate shall be filled out and signed by both representatives. Copies shall be prepared for approving authorities, owners and contractor. It is understood the owner’s representative’s signature in no way prejudices any claim against contractor for faulty material, poor workmanship, or failure to comply with approving authority’s requirements or local ordinances.
General Information
System Number of
System Manufacture;
Type of System: Wet Chemical Dry Chemical CO2….. H20
System is free of any prior discharge, damage or tampering Yes No Problems Found;
Cylinder
Pressure gauge or weight is at acceptable level. Yes No Date of last hydrostatic test of cylinder. Date;
Last date pressurized dry chemical system had chemical examined. Date;
Expellant gas cartridge; C02 psi Nitrogen pounds
Nozzles Nozzles are in proper positions Yes No
Nozzles are covered by blow-off caps Yes No
Pipe and Fittings All piping and conduit is immobilized with proper hangers and brackets Date fusible links last changed (Required Annually)
Yes No
Operation System operated properly from most remote fusible link Yes No
System operated properly from all manual actuators Yes No
Automatic shut down of fuel / power operated properly Yes No
EXHAUST SYSTEM Exhaust system ON/ Return OFF at time of activation Yes No
Final Inspection
Is system alarmed Yes No
All cooking surfaces are protected Yes No
Inspection and service tag on system cylinder Yes No
Is the hood and duct free from grease and sludge accumulation Yes No
System is now fully operational and free from obstructions Yes No
Corrections Made
This range hood system has been evaluated in accordance with manufacturer’s recommendations and NFPA standards: 96, 17 & 17A
Performance Evaluation . Name Date
Agency: Certification Number:
Address: Phone #
Signature Signature
IAW NFPA 96,17 &17A