View the file

Other files

File Type Posted
Solicitation W911S822R0002 Fire Suppression Maintenance and Repair Questions and Responses (1 June 2022).pdf PDF
PWS_Fire Alarm and Suppression ITM_3-19-2022.pdf PDF
W911S822R0002 Amendment 0005.pdf PDF
W911S822R0002 Amendment 0005 (Conformed Copy).pdf PDF
Solicitation W911S822R0002 Fire Suppression Maintenance and Repair Questions and Answers 28 May 2022 V2.pdf PDF
PWS_Fire Alarm and Suppression ITM_19 May 2022.pdf PDF
TE-4 Device Count - By Device.pdf PDF
W911S822R0002 AMENDMENT 4 v5.pdf PDF
W911S822R0002 AMENDMENT 4 (CONFORMED COPY) v4.pdf PDF
TE-3 Device Count - Number of Devices.pdf PDF
W911S822R0002 Amendment 0003.pdf PDF
W911S822R0002 Amendment 0002.pdf PDF
W911S8-22-R-0002 Amendment 0001.pdf PDF
Attachment A1 - Fire Alarm Continuation Form.pdf PDF
Attachment 2 - PAST PERFORMANCE SPECIFIC RELEVANT CONTRACTS SHEET.pdf PDF
Attachment 1 - PWS_Fire Alarm and Suppression ITM_28 March 2022.pdf PDF
WD-1 Wage Determination 2015-5539 (REV-20) 15MAR2022.pdf PDF
TE-1 2022 JBLM and YTC Facilities Listing.pdf PDF
W911S822R0002 FIRE SUPRESSION.pdf PDF
Attachment 3 - PAST PERFORMANCE QUESTIONAIRE.pdf PDF
WD-2 Wage Determination 2015-5543 (REV-16) 15MAR2022.pdf PDF
Attachment D - Fire Pump Test Form.pdf PDF
TE-2 2022 Kitchen Hood Listing.pdf PDF
Attachment C - Sprinkler System Test Form.pdf PDF
Attachment A - Fire Alarm Inspection Testing form.pdf PDF
Attachment 4 - Consent Letter.pdf PDF
Show all 26

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Joint Base Lewis-McChord

RANGE HOOD SYSTEM

Acceptance and Semi-Annual Certification

Facility Name: DATE:

Building Number: Address:

Procedure Upon completion of the work, inspection and tests shall be made by the contractor’s representative and witnessed by an owner’s representative. All defects shall be corrected and system left in service before contractor’s personnel finally leave the job.

A certificate shall be filled out and signed by both representatives. Copies shall be prepared for approving authorities, owners and contractor. It is understood the owner’s representative’s signature in no way prejudices any claim against contractor for faulty material, poor workmanship, or failure to comply with approving authority’s requirements or local ordinances.

General Information

System Number of

System Manufacture;

Type of System: Wet Chemical Dry Chemical CO2….. H20

System is free of any prior discharge, damage or tampering Yes No Problems Found;

Cylinder

Pressure gauge or weight is at acceptable level. Yes No Date of last hydrostatic test of cylinder. Date;

Last date pressurized dry chemical system had chemical examined. Date;

Expellant gas cartridge; C02 psi Nitrogen pounds

Nozzles Nozzles are in proper positions Yes No

Nozzles are covered by blow-off caps Yes No

Pipe and Fittings All piping and conduit is immobilized with proper hangers and brackets Date fusible links last changed (Required Annually)

Yes No

Operation System operated properly from most remote fusible link Yes No

System operated properly from all manual actuators Yes No

Automatic shut down of fuel / power operated properly Yes No

EXHAUST SYSTEM Exhaust system ON/ Return OFF at time of activation Yes No

Final Inspection

Is system alarmed Yes No

All cooking surfaces are protected Yes No

Inspection and service tag on system cylinder Yes No

Is the hood and duct free from grease and sludge accumulation Yes No

System is now fully operational and free from obstructions Yes No

Corrections Made

This range hood system has been evaluated in accordance with manufacturer’s recommendations and NFPA standards: 96, 17 & 17A

Performance Evaluation . Name Date

Agency: Certification Number:

Address: Phone #

Signature Signature

IAW NFPA 96,17 &17A