Attachment A2 -EX-10-ES00012 Rev 4 Technical Specification for a 90 Degree Extended Ver. and Shortened Ver. Utility Tray.pdf
PDF 4 MB Posted
- Attached to
- Utility Tray
- Solicitation number
- 494232
- Issued by
-
Department of Energy
About this file
This is a Technical Specification document for the design, fabrication, assembly, testing, and delivery of utility trays in three versions for Oak Ridge National Laboratory (ORNL). The specification establishes requirements for systems that provide electrical service, cooling water, and compressed gases to production equipment.
The specification details three utility tray configurations: a 90-Degree Version (37" wide × 203" along first leg × 180" along second leg), an Extended Version configured as a modified "U" shape (37" wide × 231" along first leg × 318" along width), and a Shortened Version configured as a modified "V" with 60-degree angles (37" wide × 175" along first leg × 118" along second leg). All three versions are approximately 9.5 inches tall. The 90D and Shortened versions consist of three sub-assemblies each (Source End, transition assembly, and Collection End), while the Extended version comprises six sub-assemblies. Electrical services include multiple circuits ranging from 120/208V at 100-125 amps to 480V at 40 amps, with distribution through Panel D and various receptacles. Fluid systems deliver cooling water at 60-80 PSIG (20-25 GPM nominal), primary and auxiliary compressed air at 90-100 PSIG, nitrogen and argon gases, and vacuum pump exhaust. Construction must comply with ASME B31.3 piping code, AWS welding standards, UL-508A electrical panel standards, and OSHA/NEC regulations. Materials include AISI 304 stainless steel framing, copper Type L tubing for water, and 316 stainless steel tubing for gases. Acceptance testing requires electrical continuity and voltage verification, static pressure testing of fluid systems up to 150 PSIG for water and 110 PSIG for gases, and comprehensive cleaning and flushing of cooling water lines. The seller must provide fabrication drawings, as-built drawings, material certificates, welding documentation, inspection and test procedures, a cleaning and flushing plan, and test reports prior to shipment. All fabricated elements carry a 24-month warranty against material and manufacturing defects, and the completed trays must be crated and shipped in an enclosed trailer to ORNL.
View the file
Other files
Show all 18
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Technical Specification for a 90 Degree, Extended Version, and Shortened Version Utility Tray
Doc Number: EX-10-ES00012
Revision: 04
AUTHOR:
Date
REVIEWERS:
UCNI Reviewing Official
APPROVER:
Technical Specification Number: EX-10-ES00012, Rev 4 Issued: See Approval Dates
90 Degree, Extended Version and Shortened Version Utility Tray
CHANGE HISTORY
REV. DESCRIPTION
REVISION
TYPE
Major Minor
01 Initial Issue ☐ ☐
02 Updated to reflect change in scope activities and new references. No rev bar shown.
03 Updated to reflect needed changes in testing requirements and specifications and the addition of the extended length version of the
Utility Tray.
04 Updated to reflect the addition of a shortened length version of the
Utility Tray.
PREVIOUS REVISION (2) AUTHORS AND APPROVERS
Author: Anna Strickland
Reviewers: Shane Carr
Darryl Dowling (UCNI RO)
Approver: Seth Wilder
PREVIOUS REVISION (3) AUTHORS AND APPROVERS
Author: Darryl Dowling
Reviewers: Shane Carr
Darryl Dowling (UCNI RO)
Approver: Seth Wilder
CONTENTS
1. INTRODUCTION
2. REFERENCE DOCUMENTS
3. ACRONYMS AND DEFINITIONS
4. GENERAL
4.1 Requirements
4.2 Design
5. DESCRIPTION
5.1 Utility Tray Source End Assembly
5.2 Utility Tray 45 Degree Assembly
5.3. Utility Tray Collection End Assembly
5.4 Extended Utility Tray Source End Assembly ……………………………………………………...18
5.5 Extended Utility Tray Removable Section Assembly ……………………………………………..22
5.6 Extended Utility Tray 1st 45 Degree Assembly ……………………………………………………22
5.7 Extended Utility Tray Mid Collection Area Assembly ……………………………………………23
5.8 Extended Utility Tray 2nd 45 Degree Assembly …………………………………………………...24
5.9 Extended Utility Tray Collection End Assembly ………………………………………………….25
5.10 Shortened Utility Tray Source End Assembly ……………………………………………………. 30
5.11 Shortened Utility Tray 30 Degree Assembly ……………………………………………………... 33
5.12 Shortened Utility Tray Collection End Assembly ………………………………………………... 34
6. UTILITES AND SERVICE DROPS
7. EQUIPMENT AND COMPONENT SUBSTITUTIONS
8. DOCUMENTATION
9. QUALITY ASSURANCE
10. INSPECTIONS AND TESTS
11. CLEANING & FLUSHING
12. WARRANTY
13. PACKING AND SHIPPING
14. DOCUMENT LIST
1. INTRODUCTION
This Specification defines the requirements for the design, procurement, materials, fabrication, assembly, testing, and shipment of a Utility Tray that will provide electrical service, cooling water, and compressed gases. The Utility Tray is designed as an integral part of a system used for production at the Oak Ridge National Laboratory (ORNL), hereafter referred to as the Company. The
Utility Tray design has three versions, a “90D Version”, an “Extended Version” and a “Shortened
Version”. The term “Utility Tray” is used to generically refer to each of the versions and the 90D
Version is the basic version, whereas the term “Extended Utility Tray” and “Shortened Utility Tray” details the requirements for those specific versions only.
2. REFERENCE DOCUMENTS
The Utility Tray fabrication shall conform to the requirements in the following documents.
Additional requirements are located in the General Project Specification, EX-00-ES00086. In the event of a conflict between the General Specification, Technical Specification, Statement of Work, or between either of these documents and a requirement in a specified code or standard, the Seller shall notify the Company’s TPO and PO. The TPO and PO will determine which document takes precedence and advise the Seller accordingly. Failure to notify the Company of any such conflict shall not relieve the Seller of any responsibility to meet all requirements.
Codes & Standards
• Applicable OSHA Standards and Regulations
• National Electric Code NFPA No 70-2020
• UL508A Edition 3 Industrial Control Panels
• ASME Building Services Piping Code B31.3-2020
• AWS Structural Welding Code - Steel AWS D1.1/D1.1M:2020
• AWS Structural Welding Code - Stainless Steel AWS D1.6/D1.6M:2017
• IPC/WHMA-A-620D Requirements and Acceptance for Cable and Wire Harness Assemblies
• ASME Section IX -2021 Welding, Brazing and Fusing Qualifications
• ASNT SNT-TC-1A Personnel Qualification and Certification in Nondestructive Testing
Project Documents
• EX-00-ES00086 General Project Specification
• See Section 14
3. ACRONYMS AND DEFINITIONS
ACRONYMS, ABBREVIATIONS, AND INITIALISMS
AISI American Iron and Steel Institute
ANSI American National Standards Institute
ASME American Society of Mechanical Engineers
ASNT American Society For Nondestructive Testing
AWS American Welding Society
BOM Bill of Materials
CAT Category
ACRONYMS, ABBREVIATIONS, AND INITIALISMS
EMT Electrical Metallic Tubing
ID Inside Diameter
IEEE Institute of Electrical and Electronics Engineers
IPC Institute for Printed Circuits
HV High Voltage
NEC National Electric Code
NEMA National Electrical Manufacturers Association
NFPA National Fire Protection Association
NPT National Pipe Thread
NRTL Nationally Recognized Testing Laboratory
OD Outside Diameter
ORNL Oak Ridge National Laboratory
OSHA Occupational Health and Safety Administration
P&ID Piping and Instrumentation Diagram
PDF Portable Document Format
PO Procurement Officer
POC Point of Contact
TPO Technical Project Officer
UL Underwriter Laboratories
WHMA Wiring Harness Manufacturer's Association
DEFINITIONS
COMPANY Oak Ridge National Laboratory
SELLER Provider of Goods or Services under this Contract (includes Seller contracted sub-suppliers)
4. GENERAL
4.1 Requirements
4.1.1 This document is technical in nature; all legal and procedural matters governing proposals and contract awards are covered in separate purchasing contracts and documents, as well as an accompanying Statement of Work document.
4.1.2 All drawings prepared by the Seller detailing modifications to Company provided drawings or to provide details omitted in the Company’s design drawings shall be reviewed and approved by the Company prior to fabrication.
4.1.3 The Seller shall fabricate, assemble, inspect, test, and ship the completed Utility Tray to the
Company’s facility.
4.1.4 Final acceptance of the Utility Tray shall occur after successful completion of all acceptance test as defined in the listed Specifications.
4.2 Design
The Company has designed the Utility Tray to provide the specific fit, form and function required to integrate with the system as defined in this Specification, design drawings and solid models.
All original drawings, as-built drawings, models, Bill of Materials (BOM) and related documents are the sole property of the Company and shall not be disseminated for reasons other than the fabrication, assembly, and testing of the Utility Tray. All changes in scope, fit, form or function must be submitted to the Company for approval in accordance with Section 5.2 of the General
Specification and documented on as-built drawings.
4.2.1 Solid models, drawings, schematics, etc. containing the assembly, sub-assemblies and individual components of the Utility Tray have been generated by the Company and will be provided to the Seller in zip file format. The 90D Utility Tray file is named UTILITY TRAY
90D.7z. The Extended Utility Tray file is named EXTENDED UTILITY TRAY 90D.7z.
The Shortened Utility Tray File is named SHORTENED UTILITY TRAY 60D.7z.
4.2.2 The top-level assembly and drawing defining the 90D Utility Tray design is EX-10-90000_90D
MASTER FACILITY TO MACHINE UTILITIES. The Extended Utility Tray design is
DX-10-90000_DEMIS MASTER FACILITY TO MACHINE UTILITIES. The Shortened
Utility Tray design is EX-10-60000_60D MASTER FACILITY TO MACHINE
UTILITIES. The assembly model and drawings were developed using SOLIDWORKS 2020
3D Design Software.
4.2.3 Bill of Materials are contained within the assembly and sub-assembly drawings for modeled components, with an additional BOM in an Excel spreadsheet format which includes
Instrumentation and Control or other components not modeled. In the event that a BOM item and the prints/solid models are discrepant with each other, the Seller is to notify the Company for resolution. The BOM for the 90D Utility Tray Panel D assembly file name is EX-10-
ES00029 Supplement – Panel D Bill of Materials. The BOM for the Extended Utility Tray
Panel D assembly file name is DX-10-ES00099 ES Supplement - DX Panel D Bill of
Materials. The BOM for the Shortened Utility Tray Panel D assembly file name is E1-10-
ES00102 ES Supplement – E1 Panel D Bill of Materials.
4.2.4 PDF instances of the drawings required to fabricate the Utility Tray and components, along with single line P&ID schematics of the electrical components, cooling water lines, and compressed gas lines, will be provided in an electronic drawing binder within the zip file referenced in Section 4.2.1. The name of the 90D Utility Tray file is EX-10-90000_MASTER
FACILITY TO MACHINE UTILITIES-DRAWINGS AND SCHEMATICS.pdf. The name of the Extended Utility Tray file is DX-10-00000_DEMIS MASTER FACILITY TO
MACHINE UTILITIES-DRAWINGS AND SCHEMATICS.pdf. The name of the
Shortened Utility Tray file is EX-10-60000_60D MASTER FACILITY TO MACHINE
UTILITIES-DRAWINGS AND SCHEMATICS.pdf.
4.3 Fabrication
4.3.1 The Utility Tray shall be fabricated according to this Specification and as detailed in the accompanying documents mentioned in Section 4.2.
4.3.2 Commercially procured equipment and components shall be selected and sized so that specifications of the original equipment manufacturer are not exceeded during normal operating conditions and shall be installed according to manufacturer’s recommendations.
4.3.3 All equipment provided by the Seller shall conform to applicable Occupational, Safety, and
Health Administration (OSHA) and National Electric Code (NEC) regulations which are in force at the time the contract is signed. Equipment must have a NRTL certification to U.S.
standards.
4.3.4 Bolting, threads, fasteners, piping, and electrical connectors shall be manufactured to applicable standards of the American National Standards Institute (ANSI), and shall, wherever possible, permit the use of ordinarily available tools. All specialty tools shall be provided by the Seller.
4.3.5 All fasteners shall be metric 18-8 stainless steel or metric grade 8.8 of medium-carbon steel unless otherwise specified in the drawing or spreadsheet BOM’s, using course thread specifications. Fasteners which are not specified in a drawing or spreadsheet BOM shall be metric 18-8 stainless steel and sized according to the mounting holes of the component it is supporting. All fasteners are required to have an appropriate anti-seize coating applied prior to assembly.
4.3.6 All piping connections shall be national pipe tapered (NPT) threaded fittings. Stainless steel tubing connections shall be imperial pipe size Swagelok stainless steel tube fittings. Copper water and compressed air lines shall utilize solder/braze connections except when connecting to other threaded components, in which case the joints shall be NPT threaded. In all cases, NPT threaded joints require suitable thread sealant in the form of tape and/or paste.
4.3.7 All solder/brazed joints shall be cleaned externally to remove any residual flux. Internal surfaces of solder/braze joints shall be cleaned & flushed per Seller provided plan as detailed in
Section 11 of this Specification.
4.3.8 Tubing shall be purchased, stored, and transported with end caps in place to exclude foreign matter and objects from the interior of the tubing. All tubing cuts shall be deburred and reamed to clean the cut surface and restore nominal ID to the tubing. This applies to both copper and stainless steel tubing.
4.3.9 Electrical cables shall not be spliced, including by in-line splices or by setting additional electrical boxes, enclosures, or terminal lugs beyond those called for in the drawing and schematic packages.
4.3.10 Conduits are specified as EMT. All conduit and cable tray cuts shall be deburred and cleaned.
5. DESCRIPTION
The 90D Utility Tray is designed as an integral part of the system, configured in a modified “L” 90-degree arrangement to closely mate with and provide electrical service, cooling water, and compressed gases to the system. The Utility Tray overall dimensions are approximately 37 inches wide X 203 inches along the first leg of the “L” and 180 inches along the second leg of the “L”, with a height of 9.5 inches over a majority of the tray surface. The Utility Tray is designed such that it can be fabricated off-site at the Seller’s facility in three primary sub-assemblies and transported to the
Company’s facility for installation. The three subassemblies are named Utility Tray Source End
Assembly, Utility Tray 45 Deg Assembly, and Utility Tray Collection End Assembly. Figures 1, 2 and 3 show the overall layout of the entire Utility Tray with general labeling of components.
The Extended Utility Tray is designed as an integral part of the system, configured in a modified “U” double 90-degree arrangement to closely mate with and provide electrical service, cooling water, and compressed gases to the system. The Utility Tray overall dimensions are approximately 37 inches wide x 231 inches along the first leg of the “U” and 318 inches along the width of the “U”, with a height of 9.5 inches over a majority of the tray surface. The Utility Tray is designed such that it can be fabricated off-site at the Seller’s facility in six primary sub-assemblies and transported to the
Company’s facility for installation. The six subassemblies are named Utility Tray Source End
Assembly, Utility Tray Removable Section Assembly, Utility Tray 1st 45 Deg Assembly, Utility Tray
Mid Collection Area Assembly, Utility Tray 2nd 45 Deg Assembly, and Utility Tray Collection End
Assembly. Figures 4, 5 and 6 show the overall layout of the entire Extended Utility Tray with general labeling of components.
The Shortened Utility Tray is designed as an integral part of the system, configured in a modified “V”
60-degree arrangement to closely mate with and provide electrical service, cooling water, and compressed gases to the system. The Utility Tray overall dimensions are approximately 37 inches wide X 175 inches along the first leg of the “V” and 118 inches along the second leg of the “V”, with a height of 9.5 inches over a majority of the tray surface. The Utility Tray is designed such that it can be fabricated off-site at the Seller’s facility in three primary sub-assemblies and transported to the
Company’s facility for installation. The three subassemblies are named Utility Tray Source End
Assembly, Utility Tray 30 Deg Assembly, and Utility Tray Collection End Assembly. Figures 7, 8 and 9 show the overall layout of the entire Utility Tray with general labeling of components.
Figure 1: 90D Utility Tray Isometric View
Figure 2: 90D Utility Tray with Services Noted, View 1
Figure 3: 90D Utility Tray with Services Noted, View 2
Figure 4: Extended Utility Tray Isometric View
Figure 5: Extended Utility Tray with Services Noted, View 1
Figure 6: Extended Utility Tray with Services Noted, View 2
Figure 7: Shortened Utility Tray Isometric View
Figure 8: Shortened Utility Tray with Services Noted, View 1
Figure 9: Shortened Utility Tray with Services Noted, View 2
Figure 10: 90D Utility Tray Source End Assembly
5.1 90D Utility Tray Source End Assembly
The 90D Utility Tray Source End Assembly, detailed in solid model and drawings EX-10-
90025_UTILITY TRAY, SOURCE END ASSEMBLY and shown in Figures 10, 11, 12 and 13 is the interface point between the entire Utility Tray Assembly and the facility utilities infrastructure where all the utility drops occur. This assembly has 7 major components consisting of a Platform
Frame, a pump tray, an assembly of three fused disconnects, an electrical enclosure named “Panel
D”, two receptacle assemblies and a Flow Switch Manifold Assembly. The overall assembly measures nominally 37 inches wide x 139 inches long with a 22.5° angle on one end and is designed as a 10 ft tall unit which is to be extended both in structure and utility functions to tie to the facility structure and facility utilities. The assembly includes removable fiberglass bar grates.
5.1.1 The Platform Frame is a welded assembly constructed of AISI 304 stainless steel and it supports the conduits, tubing, and fused disconnects to bring the electrical service, ethernet and fiber optic networks, cooling water, primary compressed air, auxiliary compressed air, nitrogen gas, argon gas and connection to the vacuum pump exhaust from the facility to the components.
It also supports the utility runs, the Flow Switch Manifold Assembly, and removable fiberglass bar grates.
5.1.2 The Pump Tray is a welded assembly constructed of AISI 304 stainless steel and it will support dry-type or oil-based vacuum pumps. The pump tray is free standing but located within the envelope of the Utility Tray Platform Frame. The vacuum pumps are not in the scope of this
Specification. The Pump Tray incorporates a lip and a drain feature to act as retention in case of an oil leak on a vacuum pump.
5.1.3 The Flow Switch Manifold Assembly provides supply and return cooling water manifolds with ten outlet ports each, shut off valves, and flow switches for connections to equipment. It also provides auxiliary compressed air capability via a manifold, pressure regulator, and quick disconnects.
5.1.4 Electrical Services consist of two circuits of 120/208V 100 amp 3 phase 4 wire, one circuit of
277/480V 40 amp 3 phase 4 wire, one circuit of 480V 40 amp 3 phase delta 3 wire, electrical enclosure Panel D, various electrical receptacles and a ground bar system.
5.1.4.1 All the line and load side wiring and connections, with the exception of Panel D and its load side circuits, will be installed by the Company and is outside the scope of this specification.
5.1.4.2 One 120/208V 3 phase circuit is routed to a fused disconnect and the load side is routed to
Panel D, with wiring installation included in the Utility Tray fabrication and testing. The final fused disconnect line side wiring installation will occur on-site by the Company, while the fused disconnect load side wiring, Panel D internal wiring and Panel D load side wiring to receptacles should be completed by Seller’s to facilitate testing.
5.1.4.3 Panel D is used as the distribution hub for all 120V and 208V electrical services along the entire Utility Tray. Wiring from Panel D is routed through the cable trays in the Utility Tray to corresponding receptacles. The layout, assembly and wiring of Panel D is detailed in drawings EX-10-00000_PANEL D ASSEMBLY and wiring schematic “EX-10-D00018
Single Line - Panel D and Utility Tray”. A supplemental Bill of Materials for Panel D components is detailed in “EX-10-ES00029 ES Supplement - Panel D Bill of Materials”.
5.1.4.4 The receptacle assemblies from Panel D provide access to 120V 20 amp circuits, 208V 15 amp single phase circuits, a 208V 30 amp single phase circuit, 208V 20 amp 3 phase circuits, and 208V 20/30 amp 3 phase circuits. All 208V circuit wiring within Panel D and run through the Utility Tray to receptacles is to be rated for 30A. All 208 V receptacles are standardized to 30A versions, though some breaker sizes are lower than this. This is to allow for easier updating of individual circuit amperage in the future if/as needed. Receptacle types and locations along the Utility Tray are found in wiring schematic “EX-10-D00018 Single
Line Diagrams – Panel D and Utility Tray”.
5.1.4.5 The ground bar system is provided as a means of grounding equipment and structures along the length of the Utility Tray that are not grounded by other means. The ground bar system extends to all three primary Utility Tray sub-assemblies.
5.1.5 Though not a part of this Specification, signal and communication cables are also routed through the primary cable tray and small channel trays to equipment which will be installed adjacent to the Utility Tray.
5.1.6 Fluid Services consist of distilled cooling water supply and return at up to 80 psig, primary compressed air at up to 100 psig, auxiliary compressed air at up to 100 psig, nitrogen gas at up to 100 psig, argon gas at up to 10 psig, and vacuum pump exhaust at slightly negative pressure relative to atmospheric.
Figure 11: 90D Utility Tray Source End Utility Drop Identification View 1
Figure 12: 90D Utility Tray Source End Utility Drop Identification View 2
Figure 13: 90D Utility Tray Source End Utility Drop Identification View 3
Figure 14: 90D Utility Tray 45 Degree Assembly
5.2 90D Utility Tray 45 Degree Assembly
The 90D Utility Tray 45 Degree Assembly, detailed in solid model and drawings EX-10-
90024_UTILITY TRAY, 45 DEGREE ASSEMBLY and shown in Figure 14, provides the structure to route utilities from the Utility Tray Source End Assembly through a 90 degree bend to the Utility Tray Collection End Assembly and to support a Magnet Electronics Rack. This assembly has three major components consisting of the 45 Degree Platform Frame, the Dipole
Water Manifold Assembly, and an Electronics Rack Support Plate. The Magnet Electronics Rack is outside the scope of this Specification. The overall assembly measures nominally 37 inches wide x 89 inches long with a 22.5° angle on each end. The assembly also includes removable fiberglass bar grates.
5.2.1. Platform Frame: See Section 5.1.1 for a general description.
5.2.2. The Flow Switch Manifold Assembly includes supply and return cooling water manifolds with three outlet ports each, shut off valves, and flow switches for connections to equipment.
5.2.3. The Electronics Rack Support Plate provides a base for supporting the Magnet Electronics
Rack.
5.2.4. Electrical Services to receptacles and all fluid services are continued from the Utility Tray
Source End to the Utility Tray Collection End. Though not a part of this Specification, signal and communication cables are also routed through the primary cable tray and small channel trays to equipment which will be installed adjacent to the Utility Tray by the Company.
Figure 15: 90D Utility Tray Collection End Assembly
5.3. 90D Utility Tray Collection End Assembly
The 90D Utility Tray Collection End Assembly, detailed in solid model and drawings EX-10-
90026_UTILITY TRAY, COLLECTION END ASSEMBLY and shown in Figure 15, provides the structure to route utilities from the Utility Tray 45 Degree to the final locations on the
Collection End Assembly. This assembly has five major components consisting of the Collection
End Platform Frame, a pump tray, the Collector Water Manifold Assembly, and two receptacle assemblies. The overall assembly measures nominally 37 inches wide x 116 inches long with a
22.5° angle on one end. The assembly also includes removable fiberglass bar grates.
5.3.1 Platform Frame: See Section 5.1.1 for a general description.
5.3.2 Pump Tray: See Section 5.1.2 for a general description.
5.3.3 Flow Switch Manifold Assembly: See Section 5.1.3 for a general description.
5.3.4 Electrical Services to receptacles and all fluid services are continued from the 45 Degree Utility
Tray Source Assembly to the utility termination locations. Though not a part of this
Specification, signal and communication cables are also routed through the primary cable tray and small cross trays to equipment which will be installed adjacent to the Utility Tray by the
Company.
Figure 16: Extended Utility Tray Source End Assembly
5.4 Extended Utility Tray Source End Assembly
The Extended Utility Tray Source End Assembly, detailed in solid model and drawings DX-10-
00025_UTILITY TRAY, SOURCE END ASSEMBLY and shown in Figures 16, 17, 18 and 19 is the interface point between the entire Utility Tray Assembly and the facility utilities infrastructure where all the utility drops occur. This assembly has 7 major components consisting of a Platform
Frame, a pump tray, assemblies of three fused disconnects, an electrical enclosure named “Panel
D”, two receptacle assemblies and a Flow Switch Manifold Assembly. The overall assembly measures nominally 37 inches wide x 139 inches long with a 22.5° angle on one end and is designed as a 10 ft tall unit which is to be extended both in structure and utility functions to tie to the facility structure and facility utilities. The assembly includes removable fiberglass bar grates.
5.4.1 Platform Frame: See Section 5.1.1 for a general description.
5.4.2 Pump Tray: See Section 5.1.2 for a general description.
5.4.3 Flow Switch Manifold Assembly: See Section 5.1.3 for a general description.
5.4.4 Electrical Services consist of one circuit of 120/208V 125 amp 3 phase 4 wire, one circuit of
120/208V 100 amp 3 phase 4 wire, two circuits of 277/480V 40 amp 3 phase 4 wire, one circuit of 480V 40 amp 3 phase delta 3 wire, electrical enclosure Panel D, various electrical receptacles and a ground bar system.
5.4.4.1 All the line and load side wiring and connections, with the exception of Panel D and its load side circuits, will be installed by the Company and is outside the scope of this specification.
5.4.4.2 The 120/208V 125A 3 phase circuit is routed to a 200A capacity, 125A fused disconnect and the load side is routed to Panel D, with wiring installation included in the Utility Tray fabrication and testing. The final fused disconnect line side wiring installation will occur on-site by the Company, while the fused disconnect load side wiring, Panel D internal wiring and
Panel D load side wiring to receptacles should be completed by Seller’s to facilitate testing.
5.4.4.3 Panel D is used as the distribution hub for all 120V and 208V electrical services along the entire Utility Tray. Wiring from Panel D is routed through the cable trays in the Utility Tray to corresponding receptacles. The layout, assembly and wiring of Panel D on the Extended
Utility Tray is detailed in drawings DX-10-00000_PANEL D ASSEMBLY and wiring schematic “DX-10-D00092-00 Electrical Single Line Diagrams - Panel D and Utility Tray”.
A supplemental Bill of Materials for Panel D components is detailed in “DX-10-ES00099 ES
Supplement - DX Panel D Bill of Materials”.
5.4.4.4 Receptacle Assemblies from Panel D: See Section 5.1.4.4 for a general description.
Receptacle types and locations along the Extended Utility Tray are found in wiring schematic
“DX-10-D00092-00 Electrical Single Line Diagrams - Panel D and Utility Tray”.
5.4.4.5 Ground Bar System: See Section 5.1.4.5 for a general description. The ground bar system extends to all six primary Utility Tray sub-assemblies.
5.4.5 Signal and Communication Cables: See Section 5.1.5 for a general description.
5.4.6 Fluid Services: See Section 5.1.6 for a general description.
Figure 17: Extended Utility Tray Source End Utility Drop Identification View 1
Figure 18: Extended Utility Tray Source End Utility Drop Identification View 2
Figure 19: Extended Utility Tray Source End Utility Drop Identification View 3
Figure 20: Extended Utility Tray Removable Section Assembly
5.5 Extended Utility Tray Removable Section Assembly
The Extended Utility Tray Removable Section Assembly, detailed in solid model and drawings
DX-10-00076_UTILITY TRAY, REMOVABLE SECTION ASSEMBLY and shown in Figure
20, provides the structure to route utilities from the Utility Tray Source End Assembly to the
Utility Tray 1st 45 Deg Assembly through a short straight path. This assembly has one major component consisting of the Removable Section Platform Frame. The overall assembly measures nominally 37 inches wide x 43 inches long with a 22.5° angle on each end. The angled ends of the Platform Frame are parallel. The assembly also includes removable fiberglass bar grates.
5.5.1. Platform Frame: See Section 5.1.1 for a general description.
5.5.2. Electrical Services to receptacles and all fluid services are continued from the Utility Tray
Source End to the Utility Tray 1st 45 Deg Assembly. Though not a part of this Specification, signal and communication cables are also routed through the primary cable tray and small channel trays to equipment which will be installed adjacent to the Utility Tray by the Company.
Figure 21: Extended Utility Tray 1st 45 Degree Assembly
5.6 Extended Utility Tray 1st 45 Degree Assembly
The Utility Tray 1st 45 Degree Assembly, detailed in solid model and drawings DX-10-
00029_UTILITY TRAY, 1st 45 DEGREE ASSEMBLY and shown in Figure 21, provides the structure to route utilities from the Utility Tray Removable Section Assembly through a 90 degree bend to the Utility Tray Mid Collection Area Assembly. This assembly has two major components consisting of the 1st 45 Degree Platform Frame and the Dipole Water Manifold
Assembly. The overall assembly measures nominally 37 inches wide x 63 inches long with a
22.5° angle on each end. The assembly also includes removable fiberglass bar grates.
5.6.1. Platform Frame: See Section 5.1.1 for a general description.
5.6.2. Flow Switch Manifold Assembly: See Section 5.2.2 for a general description.
5.6.3. Electrical Services to receptacles and all fluid services are continued from the Utility Tray
Removable Section Assembly to the Utility Tray Mid Collection Area. Though not a part of this Specification, signal and communication cables are also routed through the primary cable tray and small channel trays to equipment which will be installed adjacent to the Utility Tray by the Company.
Figure 22: Extended Utility Tray Mid Collection Area Assembly
5.7. Extended Utility Tray Mid Collection Area Assembly
The Extended Utility Tray Mid Collection Area Assembly, detailed in solid model and drawings
DX-10-00026_UTILITY TRAY, MID COLLECTION AREA ASSEMBLY and shown in Figure
22, provides the structure to route utilities from the 1st Utility Tray 45 Degree Assembly to the 2nd
Utility Tray 45 Degree Assembly and to provide utility drops on the assembly. This assembly has five major components consisting of the Mid Collection Area Platform Frame, a pump tray, the Mid Collection Area Water Manifold Assembly, and two receptacle assemblies. The overall assembly measures nominally 37 inches wide x 190 inches long with a 22.5° angle on one each end. The assembly also includes removable fiberglass bar grates.
5.7.1 Platform Frame: See Section 5.1.1 for a general description.
5.7.2 Pump Tray: See Section 5.1.2 for a general description.
5.7.3 Flow Switch Manifold Assembly: See Section 5.1.3 for a general description.
5.7.4 Electrical Services to receptacles and all fluid services are continued from the 1st 45 Degree
Utility Tray to the 2nd 45 degree Utility Tray and to the utility termination locations. Though not a part of this Specification, signal and communication cables are also routed through the primary cable tray and small cross trays to equipment which will be installed adjacent to the
Utility Tray by the Company.
Figure 23: Extended Utility Tray 2ndt 45 Degree Assembly
5.8 Extended Utility Tray 2nd 45 Degree Assembly
The Utility Tray 2nd 45 Degree Assembly, detailed in solid model and drawings DX-10-
00028_UTILITY TRAY, 2nd 45 DEGREE ASSEMBLY and shown in Figure 23, provides the structure to route utilities from the Utility Tray Collection Area Assembly through a 90 degree bend to the Utility Tray Collection End Assembly. This assembly has three major components consisting of the 2nd 45 Degree Platform Frame, the Dipole Water Manifold Assembly, and an
Electronics Rack Support Plate. The Electronics Rack is outside the scope of this Specification.
The overall assembly measures nominally 37 inches wide x 89 inches long with a 22.5° angle on each end. The assembly also includes removable fiberglass bar grates.
5.8.1. Platform Frame: See Section 5.1.1 for a general description.
5.8.2. Flow Switch Manifold Assembly: See Section 5.2.2 for a general description.
5.8.3. Electronics Rack Support Plate: See Section 5.2.3 for a general description.
5.8.4. Electrical Services to receptacles and all fluid services are continued from the Utility Tray Mid
Collection Area Assembly to the Utility Tray Collection End Assembly. Though not a part of this Specification, signal and communication cables are also routed through the primary cable tray and small channel trays to equipment which will be installed adjacent to the Utility Tray by the Company.
Figure 24: Extended Utility Tray Collection End Assembly
5.9. Extended Utility Tray Collection End Assembly
The Utility Tray Collection End Assembly, detailed in solid model and drawings DX-10-
00019_UTILITY TRAY, COLLECTION END ASSEMBLY and shown in Figure 24, provides the structure to route utilities from the 2nd Utility Tray 45 Degree Assembly to the final locations on the Collection End Assembly. This assembly has five major components consisting of the
Collection End Platform Frame, a pump tray, the Collector End Water Manifold Assembly, and two receptacle assemblies. The overall assembly measures nominally 37 inches wide x 134 inches long with a 22.5° angle on one end. The assembly also includes removable fiberglass bar grates.
5.9.1 Platform Frame: See Section 5.1.1 for a general description.
5.9.2 Pump Tray: See Section 5.1.2 for a general description.
5.9.3 Flow Switch Manifold Assembly: See Section 5.1.3 for a general description.
5.9.4 Electrical Services to receptacles and all fluid services are continued from the 2nd 45 Degree
Utility Tray Assembly to the utility termination locations. Though not a part of this
Specification, signal and communication cables are also routed through the primary cable tray
Figure 25: Shortened Utility Tray Source End Assembly
5.10 Shortened Utility Tray Source End Assembly
The Shortened Utility Tray Source End Assembly, detailed in solid model and drawings EX-10-
60025_UTILITY TRAY, SOURCE END ASSEMBLY and shown in Figures 25, 26, 27 and 28 is the interface point between the entire Utility Tray Assembly and the facility utilities infrastructure where all the utility drops occur. This assembly has 8 major components consisting of a Platform
Frame, a pump tray, assemblies of three fused disconnects, an electrical enclosure named “Panel
D”, two receptacle assemblies and two Flow Switch Manifold Assemblies. The overall assembly measures nominally 37 inches wide x 151 inches long with a 15° angle on one end and is designed as a 9 ft tall unit which is to be extended both in structure and utility functions to tie to the facility structure and facility utilities. The assembly includes removable fiberglass bar grates.
5.10.1 Platform Frame: See Section 5.1.1 for a general description.
5.10.2 Pump Tray: See Section 5.1.2 for a general description.
5.10.3 Flow Switch Manifold Assembly: See Section 5.1.3 for a general description.
5.10.4 Electrical Services consist of two circuits of 120/208V 100 amp 3 phase 4 wire, one circuit of
277/480V 30 amp 3 phase 4 wire, one circuit of 480V 40 amp 3 phase delta 3 wire, electrical enclosure Panel D, various electrical receptacles and a ground bar system.
5.10.4.1 All the line and load side wiring and connections, with the exception of Panel D and its load side circuits, will be installed by the Company and is outside the scope of this specification.
5.10.4.2 One of the 120/208V 100A 3 phase circuits is routed to a 100A capacity, 100A fused disconnect and the load side is routed to Panel D, with wiring installation included in the
Utility Tray fabrication and testing. The final fused disconnect line side wiring installation will occur on-site by the Company, while the fused disconnect load side wiring, Panel D internal wiring and Panel D load side wiring to receptacles should be completed by the Seller to facilitate testing.
5.10.4.3 Panel D is used as the distribution hub for all 120V and 208V electrical services along the entire Utility Tray. Wiring from Panel D is routed through the cable trays in the Utility Tray to corresponding receptacles. The layout, assembly and wiring of Panel D on the Shortened
Utility Tray is detailed in drawings EX-10-00000_PANEL D ASSEMBLY and wiring schematic “E1-10-D00100 EMIS E1 PANEL-D AND UTILITY TRAY ELECTRICAL
SINGLE LINE DIAGRAMS ”. A supplemental Bill of Materials for Panel D components is detailed in “E1-10-ES00102 ES Supplement – E1 Panel D Bill of Materials”.
5.10.4.4 Receptacle Assemblies from Panel D: See Section 5.1.4.4 for a general description.
Receptacle types and locations along the Shortened Utility Tray are found in wiring schematic “E1-10-D00100 EMIS E1 PANEL-D AND UTILITY TRAY ELECTRICAL
SINGLE LINE DIAGRAMS”.
5.10.4.5 Ground Bar System: See Section 5.1.4.5 for a general description. The ground bar system extends to all three primary Utility Tray sub-assemblies.
5.10.5 Signal and Communication Cables: See Section 5.1.5 for a general description.
5.10.6 Fluid Services: See Section 5.1.6 for a general description.
Figure 26: Shortened Utility Tray Source End Utility Drop Identification View 1
Figure 27: Shortened Utility Tray Source End Utility Drop Identification View 2
Figure 28: Shortened Utility Tray Source End Utility Drop Identification View 3
Figure 29: Shortened Utility Tray 30 Degree Assembly
5.11 Shortened Utility Tray 30 Degree Assembly
The Shortened Utility Tray 30 Degree Assembly, detailed in solid model and drawings EX-10-
60024_UTILITY TRAY, 30 DEGREE ASSEMBLY and shown in Figure 29, provides the structure to route utilities from the Utility Tray Source End Assembly through a 60° bend to the
Utility Tray Collection End Assembly and to support a Magnet Electronics Rack. This assembly has three major components consisting of the 30 Degree Platform Frame, the Dipole Water
Manifold Assembly, and an Electronics Rack Support Plate. The Magnet Electronics Rack is outside the scope of this Specification. The overall assembly measures nominally 37 inches wide x 56 inches long with a 15° angle on each end. The assembly also includes removable fiberglass bar grates.
5.11.1. Platform Frame: See Section 5.1.1 for a general description.
5.11.2. The Flow Switch Manifold Assembly includes supply and return cooling water manifolds with three outlet ports each, shut off valves, and flow switches for connections to equipment.
5.11.3. The Electronics Rack Support Plate provides a base for supporting the Magnet Electronics
Rack.
5.11.4. Electrical Services to receptacles and all fluid services are continued from the Utility Tray
Source End to the Utility Tray Collection End. Though not a part of this Specification, signal and communication cables are also routed through the primary cable tray and small channel trays to equipment which will be installed adjacent to the Utility Tray by the Company.
Figure 30: Shortened Utility Tray Collection End Assembly
5.12. Shortened Utility Tray Collection End Assembly
The Shortened Utility Tray Collection End Assembly, detailed in solid model and drawings EX-
10-60026_UTILITY TRAY, COLLECTION END ASSEMBLY and shown in Figure 30, provides the structure to route utilities from the Utility Tray 30 Degree Assembly to the final locations on the Collection End Assembly. This assembly has five major components consisting of the Collection End Platform Frame, a pump tray, the Collector Water Manifold Assembly, and two receptacle assemblies. The overall assembly measures nominally 37 inches wide x 92 inches long with a 15° angle on one end. The assembly also includes removable fiberglass bar grates.
5.12.1 Platform Frame: See Section 5.1.1 for a general description.
5.12.2 Pump Tray: See Section 5.1.2 for a general description.
5.12.3 Flow Switch Manifold Assembly: See Section 5.1.3 for a general description.
5.12.4 Electrical Services to receptacles and all fluid services are continued from the 30 Degree Utility
Tray Source Assembly to the utility termination locations. Though not a part of this
Specification, signal and communication cables are also routed through the primary cable tray
6. UTILITES AND SERVICE DROPS
General information regarding the electrical and fluid utility and service drops are detailed in Table 1 and Table 2. Specific utility service locations in the Utility Tray, receptacle locations, flow switch locations, etc. are provided in the drawing packages.
UTILITY TRAY DROP GENERAL INFORMATION
UTILITY DROP TYPE CONDUIT OR
TUBE SIZE
DESCRIPTION
Power Supply Receptacle EMT 3/4 277/480V 40A 3Ph 4W
[277/480V 30A 3Ph 4W] HV Transformer Disconnect, Line and Load EMT 3/4 480V 40A 3Ph Delta 3W
Cabinet Power Disconnect, Line and Load EMT 1-1/4 120/208V 100A 3Ph 4W
Panel "D" Disconnect, Line and
Load EMT 1-1/4 (1-1/2) [1-1/4] 120/208V 100A 3Ph 4W
(120/208V 125A 3Ph 4W)
[120/208V 100A 3Ph 4W]
CAT-6A Cable EMT 3/4 Ethernet Cable, Qty 2 cables for
VOIP & ORNL LAN
Fiber Optic Cable EMT 3/4 Fiber Optic OM4-12 Fiber for
Control System
Ground Cable EMT 3/4 1” Copper/Tinned Flat Braid
FTCB 1550 w/ PB50 Lugs
Cooling Water Supply and
Return Copper Type L 2" Nom OD x .07 Wall 60 - 80 psig supply, 20 gpm nom, 30 gpm max
(25 gpm nom, 30 gpm max)
[20 gpm nom, 30 gpm max]
Primary Compressed Air 316 SS Tubing .50 OD x .049 Wall 90-100 psig, regulated to 80 psig, 10 SCFM max
Auxiliary Compressed Air Copper Type L 1" Nom OD x .05 Wall 90 - 100 psig, 50 SCFM max
Argon Gas 316 SS Tubing .50 OD x .049 Wall 5 psig nom, 10 psig max,
1.5 SCFM (40,000 SCCM) max
Nitrogen Gas 316 SS Tubing .50 OD x .049 Wall 60 psig nom, 100 psig max, 2 SCFM max
Vacuum Pump Exhaust Wire Reinforced PVC
Flex Tubing
2.00 ID x .2 Wall Atmospheric Discharge to
Toxic Exhaust System
Table 1: Utility Tray Drop General Information - Extended Utility Tray Specific Requirements provided in parenthesis (); Shortened Utility Tray Specific Requirements provided in brackets []
ELECTRICAL CIRCUIT GENERAL INFORMATION
UTILITY DROP QTY RECEPTACLE /
DISC SPECS
SERVICE
Power Supply Receptacle 1
(2)
[1]
Meltric
DSN60 63-64043-375-843
(480V 60A 3P, G)
[Meltric
DSN30 63-34043-375-843
(480V 30A 3P, G)]
277/480V 40A 3Ph 3W
[277/480V 30A 3Ph 3W]
HV Transformer Disconnect, Line and Load 1 Fusible 600V 60A 3P SN disconnect switch, Square D H362N
480V 40A 3Ph Delta 3W
Cabinet Power Disconnect, Line and Load 1 Fusible 240V 100A 3P SN disconnect switch, Square D H323N
120/208V 100A 3Ph 4W
Panel "D" Disconnect, Line and
Load 1 Fusible 240V 100A (200A) 3P SN disconnect switch, Square D H323N (VH324N)
120/208V 100A 3Ph 4W
(120/208V 125A 3Ph 4W)
Convenience Receptacles 12
(18)
[14]
NEMA 5-20R 120V 20 Amp
Power Receptacles 13
(22)
[17]
NEMA L6-30R (2P, G) 208V 1Ph 15/30 Amp
Power Receptacles 2
(1)
[1]
NEMA L15-30R (3P, G) 208V 3 Ph 30 Amp
Power Receptacles 7
(9)
[5]
Meltric
DSN30 63-34163-375-843
(208V 30A 3P, G)
208V 3 Ph 15/20 Amp
Table 2: Utility Tray Electrical Circuit General Information – Extended Utility Tray Specific
Requirements provided in parenthesis (); Shortened Utility Tray Specific Requirements provided in brackets []
7. EQUIPMENT AND COMPONENT SUBSTITUTIONS
Equipment, components, and materials have been chosen for specific fit, form, and function to ensure performance and interface with components within the Utility Tray and to the overall System. In many cases, a specific vendor or manufacturer’s item can be substituted if the substitute item has the same fit, form and function along with performance parameter. Allowances and restrictions for substitution of components are detailed in Table 3. All substitutions which require Company approval shall be requested from the Company’s POC or designee in writing, either hard copy or email, by requesting a seller deviation using form ORNL-313. See the GS for additional instructions.
7.1 Substitution of equipment and components for items detailed in Table 3 as “No Restriction” may be performed without Company approval and must be documented in as-built BOM.
7.2 Substitution of all equipment and components for items detailed in Table 3 as “Upon Approval” must be approved in writing by the Company.
7.3 Substitution of all equipment and components for items detailed in Table 3 as “No Substitution” will not be approved by the Company unless there are severe supply chain or design/safety issues which can’t be reasonably overcome.
7.4 Substitution of any equipment or component other than bolts and fasteners shall occur across all
Utility Tray builds which are occurring under a single contract and must be documented by the
Seller on as-built drawings and/or BOM’s. Sales sheets or cut sheets shall be provided to the
Company for items which require Company approval.
Table 3: Equipment and Component Substitution Allowances
7.5 Tubing, fittings, and valves for the water system and manifold assemblies are configured into tight assembly and operating spaces so substitution for these items must be performed with careful consideration of component dimensions.
EQUIPMENT AND COMPONENT SUBSTITUTION ALLOWANCES
Manufacturer/Vendor Item Class Substitution Restrictions
B-Line Framing Channels, Channel Nuts, Hardware
Company Approval
Burger and Brown
Engineering
Fluid Manifold No Substitution
Corning Fiber Optic Cassette Housing No Substitution
DW: Dwyer Flowmeter No Substitution
Eaton Cable Tray Company Approval
Hilti Anchors No Restrictions
LK: Kurt Lesker Vacuum Equipment No Restrictions
Meltric Power Receptacles No Substitution
NG: Norgren Pressure Regulator No Restrictions
MC: McMaster Carr Bar Grating Company Approval
MC: McMaster Carr Hose Quick Disconnects No Substitution
MC: McMaster Carr Valves, Tube Fittings Company Approval
MC: McMaster Carr All Others No Restrictions, any vendor or manufacturer
MSC: MSC Industrial Brass Valves Any Vendor, but Manufacturer or model change requires Company Approval
SCE: Electrical Enclosure No Substitution
SMC: SMC Corp Flow Switches No Substitution
SQD: Square D Disconnect Switch Company Approval
SP: Storm Power Insulators, Stand-offs No Substitution
SW: Swagelok Valves, Quick Disconnects, Tube and
Pipe Fittings
No Substitution
SW: Swagelok 1" and 2" Braided Flex Hose Company Approval
SW: Swagelok Tubing Company Approval, 304SST or 316SST
Acceptable
UNI-Unistrut Framing Channels, Channel Nuts, Hardware
Company Approval
8. DOCUMENTATION
8.1 The Seller shall provide the following documentation for approval by the Company as defined in the Submittal Schedule included with the SOW. All documentation shall be provided in English.
The submittal schedule summarizes all required documentation and identifies the referenced specification section which can provide details on what is expected. It also provides information regarding document format, when the document is needed, & if approval to proceed is required.
Additional information and documentation submittal requirements can be found in the General
Project Specification, EX-00-ES00086.
• Fabrication drawings used by the Seller to fabricate the Utility Tray
• All As-built drawings prepared by the Seller
• Any additional design drawings and solid models required for fabrication and assembly of the system
• Dimensional Inspection Plan
• Material Certificates for all fabricated steel components and all weld material
• Wiring Schematics / Detailed Electrical Drawings
• Bill of Material
• Specification Sheets of major component parts (as defined by the BOM)
• Welding Documentation
• Inspection & Test Procedures
• Cleaning & Flushing Plan
• Inspection & Test Reports
• Shipping Plan
8.2 Modifications required to the Utility Tray shall be submitted in writing for Company approval prior to modifications being implemented, and as-built drawings shall be provided (red-lines of
Company drawings are acceptable).
8.3 Substitutions of equipment and components which require Company approval according to
Section 7.0 shall be approved by the Company in writing prior to substitutions being implemented. The Seller shall provide a copy of the manufacturer’s documentation, including mechanical drawings, manuals, schematics and parts lists, to enable Company evaluation of the substitution request. Components will be identified by manufacturer, part number and quantity on applicable prints. U.S. domestic parts are recommended.
9. QUALITY ASSURANCE
The Seller shall assure the quality of this equipment by complying fully with all the requirements of this specification, related drawings, and those defined in the General Project Specification.
9.1 All electrical components must be listed by a Nationally Recognized Testing Laboratory (NRTL) or be inspected and certified by a trained electrical inspector. The Seller shall submit a plan for certification of non-listed electrical equipment to the Company for review and approval. The
Seller shall include the cost of obtaining this certification in the cost of the Utility Tray.
9.2 All panels shall be assembled to the UL-508A standard and appropriately marked/labeled with a
NRTL certification. All wiring/cables shall be labeled in accordance with UL-508A and include
“FROM/TO” designation. Each outlet shall be labeled with feed breaker “CB-xx”. Cables routing from Panel D to outlets along tray shall be labeled at 3ft intervals.
9.3 All tubing runs shall be labeled according to applicable ASME Process Piping Code B31.3 using standard color schemes and label sizes.
9.4 All cabling and piping routing shall be performed as close to modeled and drawings as possible, which maximizes area for personnel accessing various components. No sharp edges should be exposed, especially where cabling could come in contact. No adhesive zip tie mounts are permitted.
10. INSPECTIONS AND TESTS
Acceptance tests shall include verification of each of the following items, at a minimum, as per respective parameters listed elsewhere in this equipment specification. Test and Inspection procedures shall be provided to the Company for review and approval prior to performance of the test or inspection. The Seller shall provide the power supplies and any other ancillary items needed for testing at the Seller’s facility.
10.1 Electrical component and circuit testing shall include verification of screw lug tightness and circuit continuity checks for each circuit phase leg, neutral and ground connection of receptacles.
Additional verifications after connection to power feeds shall include appropriate voltage readings line to line, line to neutral, neutral to ground, and line to ground for all receptacles on a breaker-by-breaker basis, with results of all measurements and breaker size observation supplied in table format. Phase rotation checks shall be performed for all 3 phase outlets as well.
10.2 Cooling water supply and return line testing shall include static pressurization using distilled water according to the conditions set forth in Table 4.
This is the start of the file's text. The full file is on GovTribe.