Attachment_8_Fire_supression.pdf

PDF 2 MB Posted

Attached to
SLOAN CANYON CONTACT STATION CONSTRUCTION & DELEGA
Solicitation number
140L0624R0026
Issued by

About this file

This document is a request for an alternate method approval related to a federal contract opportunity for construction of the Sloan Canyon Contact Station. The Bureau of Land Management Southern Nevada District Office is seeking to reduce the required fire flow for the 3,000 square foot facility from 1,500 gallons per minute for 2 hours as specified in the 2018 International Fire Code, to 1,500 gallons per minute for 13 minutes (19,500 gallons total) in accordance with NFPA 1142 based on an analysis classifying the occupancy hazard level 4 and construction type V-B with no exposures. Short Elliott Hendrickson Inc. as the delegated designer recommends approval due to the provision of an automatic sprinkler system designed to NFPA 13 standards to provide 300 gallons per minute for 30 minutes (9,000 gallons), along with a fire pump and over 28,500 gallon water tank to supply both the sprinkler system and a hydrant for fire department use.

View the file

Other files

File Type Posted
Attachment_2C_Additive_Details_20240422_0003.pdf PDF
Sol_140L0624R0026_Amd_0003.pdf PDF
Attachment_14_Final_EA_July2021_0003.pdf PDF
Attachment_11A_Questions_and_Answers_2_0003.pdf PDF
SF30_Continuation_Pages_Amend_3_0003.pdf PDF
Sol_140L0624R0026_Amd_0002.pdf PDF
Attachment_13_Consulting_Firms_Tortoise_0001.pdf PDF
Attachment_11_Questions_Answers_1_26_20240402_0001.pdf PDF
Attachment_2C_Additives_Details_20240328_0001.pdf PDF
Attachment_1_SOW_Amendment_1_20240328_0001.pdf PDF
Attachment_12_Site_Visit_Sign_In_20240401_0001.pdf PDF
SF1442_Continuation_Pages_Amend_1_0001.pdf PDF
Sol_140L0624R0026_Amd_0001.pdf PDF
Attachment_10_SF1442_Completion_Instructions.pdf PDF
Attachment_3C_Amended_Sewer_Specifications.pdf PDF
Attachment_6_Price_Breakout.pdf PDF
Attachment_3A_Construction_Specifications_1.pdf PDF
Attachment_2A_Contsruction_Drawings_Compressed.pdf PDF
Attachment_7_Drainage_Report.pdf PDF
Attachment_9_Lim_on_SubK_Breakout.xlsx XLSX spreadsheet
Attachment_3B_Construction_Specifications_2.pdf PDF
Attachment_2B_Amended_Sewer_Drawings.pdf PDF
Attachment_5_Wage_Determination_NV20240038.pdf PDF
Attachment_4_Delegated_Water_Service_Design_Info.pdf PDF
Sol_140L0624R0026.pdf PDF
Attachment_1_SOW_240110.pdf PDF
Show all 26

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

City of Henderson Building and Fire Safety Department

240 Water Street P.O. Box 95050 Henderson, Nevada 89009-5050

Bldg (702) 267-3650 FS (702) 267-3630 Fax (702) 267-3603

REQUEST FOR ALTERNATE METHODS

Building & Fire Safety Rev 07/07

BFSE 0400

04/08

BAMM T200

PROVIDES EQUIVALENCY

Date:

Project Name:

Project Address:

Owners Name:

Owners Address:

INTRODUCTION:

Type of Construction: Occupancy Classification:

Number of Stories: Size of Building: square feet Sprinkler - Hazard Classification: Design Density:

Permit Number(s) to be referenced:

REQUEST:

Code and Code Section Affected:

Code Edition: Code Title:

Section Number: Section Title:

Code Requirement:

Alternate Being Requested:

APPROVED DISAPPROVED

14 January 2021 Sloan Visitor Contact Station

U.S. Government; Bureau of Land Management BLM - Southern Nevada District Office, 4701 North Torrey Pines Drive, LV, NV 89130

V-B, 000 A-3, 3,0031

Light Light; 0.1/1500 N/A

2018 IFC International Fire Code B105 FireFlow Requirements for bldgs

The minimum fire-flow and flow duration for buildings other than one- and two-family dwellings, Group R-3 and

B105.1(2). Per Table B105.1(2) Column V-B row 0-3,600 sq.ft. the required fire flow is 1,500 gpm for a 2-hours duration.

Instead of using the 2018 IFC appendix B to determine the fire flow use the 2017 edition of NFPA 1142.

NFPA 1142 is the Standard on Water Supplies for Suburban and Rural Fire Fighting. The facility has been analyzed per NFPA 1142 section 4.1.1 as follows: Occupancy hazard 4 Exhibition Halls, Construction type 000 (V-B); dimensions 81’ length 44’ width and 16’ height; with no exposures. The water supply to be provided is an underground water tank with a fire pump to 1 hydrant with a minimum fire flow of 1,500 gpm for at least 13 minutes duration (19,500 gallons).

mark.sandusky@cityofhenderson.com Text Box

BOTH2021137357

mark.sandusky@cityofhenderson.com Ellipse

REQUEST FOR ALTERNATE METHODS

BFSE 0400

Rev 07/07

JUSTIFICATION: (Provide supporting data, technical reports, data sheets, modeling, calculations, sketches, drawings, etc. Attach as separate sheets as necessary)

SUBMITTED BY: (If prepared by a registered professional provide a “wet seal”)

Signature Date

Name Title Company Name:

Company Address:

Company Telephone: Fax:

Owner’s (Authorized Representative) acknowledgement of this request:

Signature Date

Name Title Company Name:

Company Address:

Company Telephone: Fax:

DETERMINATION: (Mark check box on page one)

Reviewed By:

Name Title Date

Conditions of approval

MITTETETETTETETETETETETETETTETETTETTTETTTTTTTETETTTTTTETETETETETTTTETTTTTETETTTTTETTTTETETETTETTTETETETTETETETTTTETETETTETTETTETETTTTETTTETTTTTTETTTTTTEETTTTETETTTTEEETTTTTEEETTTTTEETTTTEEETTTTETTTEEETTTTTEETTTEEETTETTTETTTTEETTTEETEEETTTTEEEEEETTTTTEEEEETTTTEEEEEETTTTTEEEEETTTEEEDDDDDDDDDDDDDDDDDDDDDDDDD BY: (I((((((((( f prepared atttttttttttttttttttttttttttttttttttttttttttttttttttttuuuuuururururuuuuuuururuuuuuuruuuuuuuruuuuuuuuuuuuuuuuuuuuuuuuuuuuuuuuuuuuuuuuuuuuuuuuuuuuuuuuuuuuuuuuuuuuuuuuuuuuuuuuuuuuuuuuuuuuuuuuuuuuuuuuuuuuuuuuuuuuuu e l provide a “wet seal”) e

This building is not required by code to be provided with an automatic fire sprinkler system. The owner has elected to provide an automatic fire sprinkler system designed in accordance with NFPA 13. The required fire flow is allowed to be reduced when a building is provided with an automatic sprinkler system. This system mitigates the required fire flow and provides life and property protection to the facility, assisting the firefighters.

The sprinkler system will be designed to provide 300 gpm for 30 minutes (9,000 gallons). The overall system will include a single tank with more than 28,500 gallon capacity and a pump system for fire flow to the hydrant and sprinkler flow to the building.

Short Elliott Hendrickson, Inc.

2000 S Colorado Blvd Colorado Tower 1 Ste 6000 Denver CO 80222

720.540.6800

James D. Hayson, PE Senior Professional Engineer II

04/07/2021

Raymond Tsui District Civil Engineer

Bureau of Land Management, Southern Nevada District Office 4701 North Torrey Pines Drive, Las Vegas, NV 89130

(702) 515-5039

April 7, 2021 mark.sandusky@cityofhenderson.com Fire Approval - 2 mark.sandusky@cityofhenderson.com Text Box Mark R Sandusky mark.sandusky@cityofhenderson.com Text Box Senior Fire Safety Plans Examiner