This file attachment relates to a federal solicitation to construct a dental clinic at the Bay Pines VA Medical Center. The solicitation seeks a general contractor to provide all labor, materials, equipment and supervision necessary to construct a new dental clinic building. The project scope includes general construction, mechanical, electrical and plumbing work, demolition of an existing modular building, select site utilities and concrete work, a gravel parking lot with permeable pavement, and select landscaping including trees. In addition to construction of the new clinic building, the project also involves installation of a new backup generator and driveway. The soliciting agency is the Department of Veterans Affairs Technology Acquisition Center located in Austin, Texas. The solicitation number is 36C77623B0029.

View the file

Other files

Show all 19

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

A2

A3

B8B7

AHU-1

B-1 & 2

4" FD-B

PROVIDE FD WITH INTEGRAL

BACKWATER VALVE

CP-1

P-801

P-804

2" V

ET-1

GWH-1

2" V. REFER TO 1/PJ111

FOR CONTINUATION

2" V. REFER TO 1/PJ111

FOR CONTINUATION

1 1/4" HW, 1" HWR, & 2"

CW. REFER TO 1/PK111

FOR CONTINUATION

1 1/4" HW

1 1/4" HWR

1 1/2" CW

2 1/2" CW

2" CW

REFER TO 1/PK111

FOR CONTINUATION

1" G. REFER TO 1/PG111

FOR CONTINUATION

4" ST DN

68.4 GPM

4" ST & STO

UP TO RD

4" ST DN

64.6 GPM

4" STO

68.4 GPM

6" STO

133 GPM

1 1/4" G

4" FD-B

PROVIDE FD WITH INTEGRAL

BACKWATER VALVE

4" FD-M

REFER TO 1/PG111

FOR CONTINUATION

REFER TO 1/PG111

FOR CONTINUATION

1 1/2" G

1 1/2" G

1 1/4" G

1" G

1" G

1" HWR

3/4" HWR

2" V DN

2" V DN

2" V

TMV-1

TP-1

2 1/2" CW U/G

1 1/2" G U/G

2" CW

6" STO. REFER TO

1/PJ111 FOR

CONTINUATION

1" G. REFER TO 1/PG111

FOR CONTINUATION

1 1/4" HW & 3/4" HWR. REFER TO

1/PK111 FOR CONTINUATION

1 1/4" HW

2" CW. REFER TO 1/PK111

FOR CONTINUATION

Mechanical

A.5

A1

A1.5

B8

VP-1

2" V DN

2" V. REFER TO 1/PJ111

FOR CONTINUATION

3/4" CW. REFER TO 1/PK111

FOR CONTINUATION

1 1/4" DA. REFER TO

1/PG111 FOR

CONTINUATION

1" MV

1 1/4" DA

3" FD-B

4" FD-B

PROVIDE FLOOR DRAIN WITH

INTEGRAL BACKWATER VALVE

4" AIR COMPRESSOR INTAKE.

REFER TO 1/PJ111 FOR

CONTINUATION.

3" DV. REFER TO 1/PG111

FOR CONTINUATION

3" DV. PROVIDE A REDUCER AFTER 2" 45° ELBOW

DOWN. TURN 1 1/2" PIPING HORIZONTAL WITH A 45°

ELBOW. ROUTE 1 1/2" DV UP WITH A 45° ELBOW UP.

PIPE VACUUM PIPE UP TO AMALGAM SEPERATOR.

1 1/2" DV TANDEM INTAKE MANIFOLD. CONNECT

DV TO MANIFOLD AND CONNECT TO VACUUM

PUMPS. PIPE VACUUM PIPE CONNECTIONS PER

MANUFACTURER'S RECOMENDATIONS.

4" FD-W

Medical Mechanical

AC-115

3" DV U/G

7 7VP-2 VP-3

1" MV. REFER TO

1/PG111 FOR

CONTINUATION

TP-2

DC-1

2" V DN

3/4" CW

3/4" HW, 1 1/2" CW, 3/4"

HWR. REFER TO 1/PK111

FOR CONTINUATION

P-103 P-103

P-418

P-418

BALANCING VALVE. SET TO 1.0 GPM

3/4" HW

1 1/2" CW

3/4" HWR

Staff Toilet

133A Staff Toilet

135A

1/2" CW

1/2" HW

1/2" CW, 1/2" HW.

REFER TO 1/PK111

FOR CONTINUATION

A.5

A1

A1.5

A2

A3

B8B7

TP-2

TP-1

(3)1/2" CW LINES UP

TO TRAP PRIMER

(3)1/2" CW LINES UP

TO TRAP PRIMER

Mechanical

Medical Mechanical

Corridor

C-4

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120

305 East Dr., Suite H, Melbourne, Florida 32904

PH: 321.345.9026

FULLY SPRINKLERED

B

IM

/0

B a y P in e s V

A D e n ta l C lin ic

/0

B a y P in e s V

A D e n ta l C lin ic

R

D iv

.r v t

/2

/2

:4

:3

A

M

PX401

PLUMBING ENLARGED PLANS CONSTRUCT DENTAL CLINIC

BAY PINES VAMC

516-349

AMBER MILTON

02/03/2023 ADL AJZ

MICHAEL R. KNOTT, P.E.

FL License #91858

100% CONSTRUCTION SET

CODED NOTES:

2 1/2" CW DN. REFER TO DETAIL FOR WATER ENTRY.

1 1/2" CW, 3/4" HWR, 1 1/2" HW, & G TO GWH-1. ROUTE HW THROUGH TMV. 3" INTAKE AND EXHAUST

ROUTED THROUGH A CONCENTRIC VENT KIT THROUGH THE ROOF. REFER TO DETAIL.

3/4" CW TO HOSE BIBB

3/4" CW TO TP. 1/2" CW FROM TP TO FLOOR DRAINS

1 1/4" G DN TO BOILERS. REFER TO DETAIL. REFER TO MECHANICAL DETAIL FOR CONNECTION

LOCATION.

3" VACUUM PUMP EXHAUST PIPE UP TO ROOF. PROVIDE 2 45° TEES TO CONNECT EACH VACUUM

PUMP TO EXHAUST. PROVIDE A DRIP LEG BELOW ALL CONNECTIONS AND ROUTE DRIP LEG TO

FLOOD DRAIN BEHIND VACUUM PUMPS. PIPE VACUUM PIPE CONNECTIONS PER MANUFACTURER'S

RECOMENDATIONS.

DENTAL VACUUM PUMPS. CONNECT DRAIN, EXHAUST, AND DENTAL VACUUM INTAKE PER

MANUFACTURER'S RECOMENDATIONS. ROUTE ALL DRAINS AND DRIP LEGS TO HUB DRAIN.

1 1/4" HW LOOP, 3/4" CW DN. 1/2" HW TO TMV-2. 1/2" CW & HW TO LAV/SINK.

AMALGAM SEPERATOR, DESIGN BASIS SOLMETEX NXT HG5 HIGH VOLUME (PART NUMBER NXT-HG5- HV). ROUTE VACUUM PIPING FROM AMALGAM SEPERATOR TO DENTAL VACUUM PUMPS. INSTALL ALL

CONNECTIONS PER MANUFACTURER'S RECOMENDATIONS. MOUNT AMALGAM SEPERATOR TO WALL

ABOVE VACUUM PUMP INLET AND DRAIN CONNECTION. WALL MOUNTING TO BE CAPABLE OF

SUPPORTING 100 LBS.

1 1/2" CW DN. 1 1/4" CW TO WC

2" VACUUM PUMP EXHAUST PIPE UP TO ROOF

SET PRV TO 12" WC. REFER TO DETAIL 12/PY502.

SET PRV TO 12" WC. REFER TO DETAIL 12/PY502. PROVIDE A DOUBLE SHUTOFF VALVE WITH

ELECTRICAL PROOF OF CLOSURE PER NFPA 85. INTERLOCK WITH THE BOILER.

GAS METER WITH PRV. COORDINATE INSTALLATION OF GAS METER WITH TECO. COORDINATE

INSTALLATION OF A PRV AND A SHUTOFF VALVE BEFORE THE GAS METER WITH TECO. COORDINATE PRV TO BE SET TO 2 PSI. AFTER THE METER, PROVIDE TWO GAS SUPPLY PIPES. ONE GAS SUPPLY TO BUILDING. THE SECOND GAS SUPPLY TO THE EMERGENCY GENERATOR. PROVIDE EACH SUPPLY LINE WITH A GAS SHUTOFF VALVE. REFER TO NFPA 110 SECTION 7.9.7 & 7.9.8 FOR MORE INFORMATION ON THE GAS SHUTOFF VALVE LABELING. COORDINATE INCOMING PIPE SIZE WITH CIVIL CONTRACTOR.

4" AIR INTAKE AND 1" DA TO AIR COMPRESSOR. REFER TO DETAIL 4 / PY501 FOR.

1/2" CW FROM TRAP PRIMER TO FLOOR DRAIN.

1/2" DA DN TO DUST COLLECTOR. CONFIRM EXACT CONNECTION SIZE AND LOCATION WITH FINAL

EQUIPMENT SELECTION..

2" ST TO SCUPPER DRAIN ON CANOPY. REFER TO PJ121 FOR CONTINUATION.

2" ST DN. PROVIDE A WCO BEFORE PIPING DROPS BFF.

PROVIDE A 24V SOLENOID VALVE. INTERLOCK WITH EMERGENCY PUSH BUTTON (EPO) AND FIRE ALARM SYSTEM. COORDINATE EPO LOCATION WITH ELECTRICAL CONTRACTOR AND VA. EPO TO BE

PROVIDED BY ELECTRICAL CONTRACTOR. COORDINATE ALL WIRING WITH ELECTRICAL

CONTRACTOR.

DRAWING NOTES:

1. SLOPE VENT PIPING TO SANITARY MAIN.

2. DESIGN BASIS AIR COMPRESSOR CAN DELIVER A MAX PRESSURE OF 120 PSIG. SYSTEM IS

CURRENTLY DESIGNED TO DELIVER 80 PSIG AFTER PRV. COORDINATE FINAL PRESSURE WITH FINAL EQUIPMENT SELECTIONS. IF A HIGHER PRESSURE (ABOVE 120 PSI) IS NEEDED NOTIFY ENGINEER OF

RECORD.

3. SLOPE ALL CW PIPING FROM TRAP PRIMER TO FLOOR DRAIN. REFER TO DETAIL.

1/2" = 1'-0"PX401

1 MECHANICAL ROOM ENLARGED PLAN - PLUMBING

1/2" = 1'-0"PX401

2 MEDICAL MECHANICAL ROOM ENLARGED PLAN - PLUMBING

1/2" = 1'-0"PX401

3 STAFF RESTROOMS ENLARGED PLAN - PRESSURE

N

0 4' 8' 16' 24'

1/8" = 1'-0"

1/8" = 1'-0"PX401

4 PLUMBING TRAP PRIMER PLAN - NEW WORK

0 1' 2' 4' 6'

1/2" = 1'-0"

Revisions Date

M C

H

A

O T

T

P R

O F

E S

S

IO N A L EN

G I N

E E

R

LICENSE

F

LO R I D A

STATE OF

No. 91858

I

E L

R K

N

AICH RD

WALL HYDRANT

SLEEVE THRU

EXTERIOR WALL

AND CAULK

SLEEVE FOUNDATION

WALL

COLD WATER SUPPLY

MIN. 2'-0" BELOW

FINISHED GRADE

MAIN SHUT-OFF

GATE VALVE

CW TO BLDG

3/4"

3/4" CW

TEE W/ PLUG

BALL VALVE

PRESSURE GAUGE

W/ 1/4" SHUT-OFF

CHECK

VALVE

BALL VALVE

BALL VALVE

CHECK VALVE

CHECK VALVE

CHECK VALVE

BALL VALVE

CHECK VALVE

CHECK VALVE BALL VALVE

BALL VALVE

BALL VALVEBALL VALVE

4" HOUSEKEEPING PAD

EXPANSION TANK,

REFER TO SCHEDULES FOR SIZEFLOOR DRAIN

FF

DRIP PAN

TEMPERATURE &

PRESSURE RELIEF

VALVE BLOWOFF PIPED

FULL SIZE TO FLOOR

DRAIN

GAS FIRED

WATER HEATER

DIRT LEG

GAS SHUT

OFF VALVE

GAS

SUPPLY

2" DIAL

THERMOMETER

3" CPVC INTAKE

AND EXHAUST

COLD WATER

SUPPLY

2" DIAL

THERMOMETER

140 °F HOT WATER

SUPPLY

HEAT TRAP

27" DROP (MIN.)

BALL

VALVE

TMV

2" DIAL

THERMOMETER

CIRCULATING PUMP

WIRE CIRCULATING

PUMP TO TIMER

(UNDER ELECTRICAL DIVISION)

PROGRAMMABLE

7 DAY TIMER

HOT WATER

TO FIXTURES.

HWR PIPING CAN ALSO BE

PIPED DIRECTLY TO WH THAT

HAS A HWR CONNECTION

COLD WATER

MIN 10'-0" FROM PARAPET, WALLS, AND STRUCTURE

CONCENTRIC VENT TERMINATION KIT

HWR

NC TMV

BYPASS

VALVE FOR

THERMAL

ERADICATION

OR CATCH BASIN

TO STORM DRAIN

CAST IRON BACKWATER VALVE

W/PVC FLAPPER AND O-RING

SEAL EQUAL TO ZURN-Z-1090

GRADE

10" DIAMETER CAST IRON COVER

MARKED 'BACKWATER VALVE',

EQUAL TO BROOKS 3-RT SERIES

PRECAST CONCRETE BODY

PROVIDE EXTENSIONS AS

REQUIRED

UNDERGROUND CONDESATE DRAIN

PIPING, SEE PLAN FOR SIZE

1/2" CD DRAIN

O U

T

LE

T S

ID

E

IN

T

A K

E S

ID

E

4" HOUSEKEEPING PAD

FLOOR SLAB

NOTES:

1. ALL PIPING SHALL BE HAND DRAWN SEAMLESS TYPE "K" OR "L" COPPER TUBING CONFORMING TO ASTM B-819.

2. FIELD ROUTE ALL CONDENSATE DRAINS TO NEAREST FLOOR DRAIN.

3. THIS DIAGRAM ONLY SHOWS INTENT AND FINAL INSTALLATION LOCATIONS MAY VARY.

ZERO

AIR-LOSS

VALVE

PRESSURE REGULATING VALVE

SET AT 80 PSIG WITH BYPASS LINE

MEDICAL AIR OIL-FREE SCROLL DUPLEX

COMPRESSOR, WITH INTEGRATED SINGLE STAGE AIR-

COOLED COMPRESSOR MOTORS, INLINE INLET AIR

FILTER, AIR RECIEVER, DESICCANT DRYERS, FILTER,

REGULATOR SYSTEM, AND CONTROL SYSTEM

HIGH-LOW PRESSURE SWITCH

MAIN SHUTOFF VALVE

MAIN PRESSURE GAUGE

PRESSURE GAUGE

MIN 24"

FULL LINE INTAKE WITH

GOOSENECK INLET WITH

MESH SCREEN OVER OPENING

PRE-FAB CURB

ROOF

REFER TO MANUFACTURER'S

INSTALLATION REQUIRMENTS

FOR INTAKE PIPE SIZING

2" MINIMUM AIR

GAP (SEE NOTE)

CAST IRON

FLOOR SINK

DRAIN (FS-1)DRAIN LINE

TO "P" TRAP

FINISHED FLOOR

REMOVABLE GRATE

SUPPORT PIPING

EVERY 4'-0"

INDIRECT WASTE

LINE

NOTE:

THE AIR GAP BETWEEN THE INDIRECT WASTE PIPEAND THE FLOOD LEVEL RIM OF THE WASTE RECEPTOR SHALL BE A

MINIMUM OF TWICE THE EFFECTIVEOPENING OF THE INDIRECT WASTE PIPE.

4' -0

FLOOR DRAIN

P-TRAP

TO

FLOOR DRAINS

BALL VALVE

3/4" COLD WATER

FINISH FLOOR

1/2" TYPE "K" SOFT SEAMLESS COPPER

WITH NO JOINTS BELOW FLOOR SLAB.

SLOPE AT 1/8" PER FOOT MINIMUM TO

FLOOR DRAIN CONNECTION.

120/1/60 ELECTRICAL

CONNECTION

ELECTRONIC TRAP PRIMING MANIFOLD SUITABLE FOR 4 TO 30

FLOOR DRAINS. COMPLETE WITH CIRCUIT BREAKER, TIMER,

BALL VALVE, SOLENOID VALVE & VACUUM BREAKER

COMPLETLY MOUNTED IN STEEL CABINET ENCLOSURE.

(PRECISION PLUMBING PRODUCTS PT-4 THRU PT-30)

SOLENOID VALVE

24-HOUR TIME CLOCK

WITH TEST AND

OVERRIDE BUTTONS.

VACUUM BREAKER

GALVANIZED STEEL

CABINET

CAP EXTRA

LINES IN WALL

PAVEMENTGRADE

CAST IRON CLEANOUT COLLAR

W/HEAVY DUTY COVER

PAVEMENT

18" SQ x 4" DEEP

CONC. PAD

CLEAN-OUT COVER

IN VEHICULAR

TRAFFIC AREAS

SHALL BE DUCTILE IRON

TWO-WAY

C.O. FTG.

1'-0"

PIPE HANGER (SEE

SPECIFICATIONS 22 05 11)

GALVANIZED SHEETMETAL

PIPE SADDLE W/FLARED ENDS

INSULATED PIPE

PIPE HANGER (SEE

SPECIFICATIONS 22 05 11)

VACUUM PUMP

NOTES:

1. PROVIDE ALL ITEMS INDICATED THAT ARE

NOT INCLUDED IN PACKAGED EQUIPMENT.

2. PROVIDE INERTIA BASE IF EQUIPMENT IS

NOT MOUNTED ON GROUND FLOOR.

MIN 24"

4" RAISE HOUSEKEEPING PAD

ASME GALVANIZED

RECEIVER

VACUUM PUMP

FLEXIBLE CONNECTION(TYP)

VACUUM GAUGE(TYP)

CONTROL PANEL IN

NEMA 12 CABINET

CHECK

VALVE (TYP)

EXHAUST MUFFLER

FULL LINE EXHAUST WITH

GOOSENECK DISCHARGE WITH

MESH SCREEN OVER OPENING

PRE-FAB CURB

TANK DRAIN LINE

WITH VALVE

DRIP LEG, PIPE

TO FLOOR DRAIN

FROM LAB

ROOF

NEOPRENE VIBRATION PAD EQUAL

TO MASON MODEL WM (TYP. OF 4)

SECURE PUMP FRAME AND

ISOLATION PAD TO CONCRETE SLAB

FLOOR DRAIN

BALL VALVE

(TYP)

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120

305 East Dr., Suite H, Melbourne, Florida 32904

PH: 321.345.9026

FULLY SPRINKLERED

B

IM

/0

B a y P in e s V

A D e n ta l C lin ic

/0

B a y P in e s V

A D e n ta l C lin ic

R

D iv

.r v t

/2

/2

:4

:3

A

M

PY501

PLUMBING DETAILS CONSTRUCT DENTAL CLINIC

BAY PINES VAMC

516-349

AMBER MILTON

02/03/2023 ADL AJZ

MICHAEL R. KNOTT, P.E.

FL License #91858

100% CONSTRUCTION SET

N.T.S.

DOMESTIC WATER SERVICE ENTRY DETAIL

N.T.S.

GAS FIRED WATER HEATER DETAIL

N.T.S.

BACKWATER VALVE

3N.T.S.

COMPRESSED AIR SCHEMATIC DETAIL

N.T.S.

CONDENSATE FLOOR DRAIN DETAIL

N.T.S.

ELECTRONIC TRAP PRIMER

N.T.S.

EXTERIOR CLEAN OUT (TWO WAY) DETAIL

N.T.S.

INSULATED PIPE HANGAR DETAIL

N.T.S.

LAB VACUUM PUMP

Revisions Date

M C

H

A

O T

T

P R

O F

E S

S

IO N A L EN

G I N

E E

R

LICENSE

F

LO R I D A

STATE OF

No. 91858

I

E L

R K

DETAIL NOTES:

A.

B.

C.

REFER TO FLOOR PLANS FOR ANY DEVIATIONS TO PIPING LAYOUT SHOWN.

EXTEND PIPING AS REQUIRED WITHIN CASEWORK TO SINK. PROVIDE PROPER

PIPE SUPPORTS.

INSTALL PIPING TO MAXIMIZE SPACE AVAILABLE BELOW SINK.

SAN

S A

N

FINISHED

FLOOR

REFER TO FLOOR PLANS FOR PIPE

SIZES AND ADDITIONAL INFORMATION.

FAUCET

SINK

SAN PIPING

S A

N

WALL/CHASE

BEHIND SINK

T

TEMPERING

VALVE TMV-2

SPOUT BRACE

SPOUT WITH HOSE

END & PAILHOOK

3" DIA. P-TRAP

36"

DRAIN

ROUGH CHROME PLATED

SERVICE FAUCET WITH

VACUUM BREAKER

H C

VARIES

30'' HOSE

HOSE BRACKET

4" x 3" x 4"

WELD TO 5"

EXTRA HEAVY RISER

CLAMP-BOLT TO 4"L

LEG AGAINST WALL

PIPE

"Ø BOLTS

FINISHED FLOOR

FOR FIXTURE HEIGHT

SEE ARCHITECTURAL

DRAWINGS

1" [25mm] STOP

[56mm]

2 1/4"

[69mm]

2 3/4"

[119mm]

4 3/4"

[2 m m

/2

[6 3m m

1/

2"

NOTE:

FURNISH 24 VOLT TRANSFORMER

C/L OF FIXTURE

FINISHED WALL

MANUAL OVER-RIDE

BUTTON

SENSOR

ELECTRICAL BOXES

[4 m m

[200mm]

8"

[8 m m

F

O R

F

IX

T U

R E

H E

IG

H

T S

S E

E

A R

C H

IT

E

C T

U R

A L

D R

A W

IN

G

S

FAUCET SEE SPECIFICATIONS

NOTE:

PROVIDE COVER FOR EXPOSED PIPING

OFFSET WASTE

LAMINAR FLOW

CONTROL DEVICE

LOOSE KEY STOP

ESCUTCHEON

FINISHED FLOOR

TRAP PARALLEL TO WALL

[2 m m

/4

NOTE:

1. PROVIDE 20 GAGE STUDS WHEN HEIGHT EXCEEDS

12'-0" [3600mm]

[9 m m

T

O F

LO

O

R

3' -3

PLAN

1/4" [6mm]∅ MOLLY BOLT HOLLOW

WALL ANCHOR (1 EA. SIDE OF LAV)

FOR FIXTURE HEIGHT SEE

ARCHITECTURA DRAWINGS

V A

R

IE

S

MINIMUM 16 GAGE GALVANIZED

STEEL PLATE 12"x48" [300x1200mm]

MIN. SECURED TO A MIN. 4 STUDS

PER LAVATORY

MIN. 5 1/4" [131mm]∅

GALV. MACHINE BOLTS

WELDED TO PLATE

MIN. (3) 1/4" [6mm]

MACHINE BOLTS

W/DOUBLE LOCK

NUTS ON BACK SIDE

A

STEEL HANGER

BY LAV MFGR

SECTION A

STEEL WALL

PLATE

WALL ANCHOR

STUDS

TYP. 1/8"

TYP. [3mm]

1/4"

[6mm]

POLISHED BRONCE TOP

CONCRETE SLAB

PROVIDE ADJUSTABLE FLOOR CLEANOUT,

CAST IRON BODY WITH GAS & WATER

TIGHT ABS TAPERED THREAD PLUG &

ROUND SECURED TOP FOR ADJUSTMENT

SLIP JOINT

SAME SIZE AS SEWER

SHORT SWEEP

ELBOW

NOTE: SECURE CLEANOUT COVER WITH SCREWS

3/4" SUPPLY

3/4" CHROMIUM PLATED

W/ VANDAL PROOF

VACUUM BEAKER

METAL WHEEL OR LOOSE

KEY TYPE HANDLE-SEE

PIPING SCHEDULE FOR

MOUNTING HGT &

HANDLE TYPE

3/4" FLANGED FEMALE INLET

HB & 3/4" HOSE THREAD ON

OUTLET, CHROME PLATED

W/ VACUUM BREAKER

TEST TEE

THREADED

CLEANOUT PLUG ACCESS COVER AND FRAME

FINISHED WALL SURFACE

RECESSED ALARM PANEL (AP) WITH

CONTINUOUS DIGITAL DISPLAY OF ALL

MEDICAL GASES AND VACUUM

PROVIDE ZONE

IDENTIFICATION SIGN

120V/1Ø POWER SUPPLY BY

ELECTRICAL

CONTRACTOR,COORDINATE

EXACT LOCATION BEFORE

CONSTRUCTION

SIGNAL WIRING

IN CONDUIT

FROM PRESSURE

SWITCHES

MEDICAL GAS MAINS

MEDICAL GAS ZONE PIPING

DOWN IN WALL,SEE PLANS

FOR EXACT SIZE AND

LOCATION

RECESSED MEDICAL GAS ZONE VALVE BOX (MGV) WITH

SHUT-OFF VALVES, PRESSURE/VACUUM GAUGES,

PRESSURE AND VACUUM SWITCHES, AND REMOVABLE

WINDOW WITH PULL RING. MOUNT TOP OF BOX 66" AFF.

CONNECT TO CAPPED PIPE

EXTENSION (TYPICAL)

CONDUIT WITH SIGNAL WIRING FROM PRESSURE/VACUUM

SWITCH TO AREA ALARM PANEL (AP) BY ELECTRICAL

CONTRACTOR, COORDINATE EXACT LOCATION BEFORE

CONSTRUCTION.

PRESSURE/VACUUM

SWITCH (TYPICAL)

PROVIDE UNIVERSAL QUICK-CONNECT

FITTING FOR IN-LINE PRESSURE/

VACUUM SWITCH (TYPICAL)

PROVIDE LOCKABLE

SHUTOFF VALVES.

LOCK VALVES IN THE

OPEN POSITION (TYP)

STRUCTURAL STEEL

MEMBER

FINISHED

FLOOR

FULL SIZE 6" LONG

DIRT LEG WITH CAP

SEE PLANS FOR

PIPE SIZES

FOR PRV INDOORS PROVIDE VENT

PIPING THRU ROOF, TERMINATE WITH

GOOSENECK AT 1'-0" ABOVE AND PLACE

AN INSECT SCREEN OVER OPENING

DOWNSTREAM

CONTROL LINE

GAS PRESSURE REGULATOR. REFER

TO FLOOR PLANS FOR SET POINT

GAS MAIN

APPROVED GAS BALL VALVE

GAS FIRED

EQUIPMENT

UNION

APPROVED GAS BALL VALVE FOR

INDIVIDUAL EQUIPMENT SHUTDOWN

TEST TEE

AT LEAST 10 PIPE DIAMETERS

STRUCTURAL STEEL

MEMBER

SEE PLANS FOR

PIPE SIZES

FOR PRV INDOORS PROVIDE VENT

PIPING THRU ROOF, TERMINATE WITH

GOOSENECK AT 1'-0" ABOVE AND PLACE

AN INSECT SCREEN OVER OPENING

DOWNSTREAM

CONTROL LINE

GAS PRESSURE REGULATOR. REFER

TO FLOOR PLANS FOR SET POINT

2 PSI GAS MAIN

APPROVED GAS BALL VALVE

TEST TEE

AT LEAST 10 PIPE DIAMETERS

CONTINUED LOW

PRESSURE GAS

PIPING TO

OUTLETS

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120

305 East Dr., Suite H, Melbourne, Florida 32904

PH: 321.345.9026

FULLY SPRINKLERED

B

IM

/0

B a y P in e s V

A D e n ta l C lin ic

/0

B a y P in e s V

A D e n ta l C lin ic

R

D iv

.r v t

/2

/2

:4

:3

A

M

PY502

PLUMBING DETAILS CONSTRUCT DENTAL CLINIC

BAY PINES VAMC

516-349

AMBER MILTON

02/03/2023 ADL AJZ

MICHAEL R. KNOTT, P.E.

FL License #91858

100% CONSTRUCTION SET

N.T.S.

MIXING VALVE UNDER SINK DETAIL

N.T.S.

MOP SINK DETAIL

N.T.S.

PIPE ANCHOR TO VERTICAL DETAIL

N.T.S.

WATER CLOSET P-103 DETAIL - SENSOR OPERATED

N.T.S.

TYPICAL WHEELCHAIR LAVATORY DETAIL

N.T.S.

LAVATORY MOUNTING DETAIL

N.T.S.

FLOOR CLEANOUT (FCO) DETAIL

N.T.S.

HOSE BIBB DETAIL

N.T.S.

WALL CLEANOUT

N.T.S.

MEDICAL GAS ZONE VALVE / ALARM PANEL DETAIL

N.T.S.

GAS EQUIPMENT CONNECTION DETAIL

6N.T.S.

GAS PRV STATION DETAIL

Revisions Date

M C

H

A

O T

T

P R

O F

E S

S

IO N A L EN

G I N

E E

R

LICENSE

F

LO R I D A

STATE OF

No. 91858

I

E L

R K

DETAIL NOTES:

A.

B.

C.

PROVIDE FINAL CONNECTION TO

GENERATOR. FLEX CONNECTOR

TO BE FURNISHED BY DIVISION

26 PROVIDE REDUCER AFTER VALVE

IF REQUIRED.

2' -6

1'

-6

M

IN

IM

U

M

ANODELESS RISER ASSEMBLY

MATCH PIPE SIZE AND BURIAL DEPTH

GRADE

TRACER WIRE

GAS VALVE. PROVIDE TEMPORARY

PLUG UNTIL FINAL CONNECTION

IS MADE.

POLYETHYLENE GAS SERVICE.

PIPING MUST BE MARKED PER ASTM D2513.

PROVIDE AN ANODELESS RISER AT EACH LOCATION WHERE THE GAS PIPING

PENETRATES THE SURFACE. EXTEND TRACER TO THE SURFACE AT EACH RISER.

COORDINATE PIPE AND CONDUIT ROUTING TO MINIMIZE TRENCHING.

PAINT ALL EXTERIOR GAS PIPING WITH ONE(1) PRIMER AND TWO(2) FINISH

COATS OF COLOR SELECTED, AS SPECIFIED.

EMERGENCY GENERATOR

TRACER WIRE - 10 AWG, SOLID, THHN

BLACK INSULATION, COIL APPROX. 1'-0"

AT EACH END. WIRE SHALL BE

CONTINUOUS, SOLDERED OR CRIMPED

JOINTS ONLY, WIRE NUTS ARE NOT

ALLOWED. DEDICATED TRACER WIRE

IS NOT REQUIRED IF IT IS PROVIDED

AS PART OF LOCATOR TAPE.

COORDINATE GAS RISER LOCATION

WITH GAS CONNECTION ON

GENERATOR.

VERIFY LOCATION WITH DIVISION 26.

LOCATOR TAPE - YELLOW PLASTIC, WITH

LETTERING: "CAUTION, BURIED GAS LINE BELOW"

6" WIDE x 4 MILS THICK, IF TRACER WIRE

IS PROVIDED WITH TAPE TERMINATE

ABOVEGROUND AS SHOWN IN DETAIL.

TRACER SHALL BE 10 AWG STRANDED,

COATED,

PVC SLEEVE, SCHEDULE 40, 1'-6" LONG

(MINIMUM)DIAMETER SIZED TO FIT OVER

RISER

6"

6"

DIRT LEG

SLOPE

INSULATE UNDERSIDE ROOF

SUMP & HORIZONTAL RAIN

LEADERS

INSULATION

PIPE SUPPORT (TYP)

ROOF DRAIN

ROOF DECK

ZURN #Z-199 DOWNSPOUT NOZZLE

SECONDARY STORM PIPING, SEE FLOOR

PLANS FOR SIZE AND LOCATIONS

EXTERIOR WALL

FINISHED FLOOR

18"-24"MAX

SPLASH BLOCK

EXAMPLES OF ACCEPTABLE FITTINGS EXAMPLES OF UNACCEPTABLE FITTINGS

ACCEPTABLE WAY TO CONNECT

MAIN DENTAL VACUUM LINES

ACCEPTABLE WAY TO CONNECT A BRANCH

TO A MAIN DENTAL VACUUM LINE

ACCEPTABLE WAY TO RISE TO

FINAL OUTLET/CHAIR CONNECTION

ACCEPTABLE WAY TO RISE MAIN DENTAL

VACUUM PIPE TO DENTAL VACUUM PUMP

CANOPY. REFER TO

ARCHITECTURAL PLANS

FOR DETAIL ON CANOPY.

EXTEND PIPING TO BELOW

FINISHED FLOOR AND

CONNECT TO THE STORM MAIN.

PROVIDE A WALL CLEANOUT IN

AN ACCESSIBLE LOCATION

ABOVE FINISHED FLOOR.

STRUCTURAL ELEMENT. COORDINATE SCUPPER

DRAIN INSTALLATION SO THAT PIPING IS ABOVE

STRUCTURAL. IF DESIGN BASIS DRAIN IS NOT

SELECTED, COORDINATE INSTALLATION AND

FIELD VERIFY THAT DRAIN AND PIPING WILL NOT

CONFLICT WITH STRUCTURAL ELEMENT.

COORDINATE DRAIN INSTALLATION TO

PROVIDE ROOM FOR DRAIN BODY TO

ENSURE THAT DRAIN BODY WILL NOT

CONFLICT WITH STRUCTURAL ELEMENT.

SCUPPER DRAIN. DESIGN

BASIS WATTS RD-270-6

EXTERIOR WALL. REFER TO

ARCHITECTURAL PLANS.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120

305 East Dr., Suite H, Melbourne, Florida 32904

PH: 321.345.9026

FULLY SPRINKLERED

B

IM

/0

B a y P in e s V

A D e n ta l C lin ic

/0

B a y P in e s V

A D e n ta l C lin ic

R

D iv

.r v t

/2

/2

:4

:4

A

M

PY503

PLUMBING DETAILS CONSTRUCT DENTAL CLINIC

BAY PINES VAMC

516-349

AMBER MILTON

02/03/2023 ADL AJZ

MICHAEL R. KNOTT, P.E.

FL License #91858

100% CONSTRUCTION SET

N.T.S.

GENERATOR, EXTERIOR - NATURAL GAS PIPING DETAIL

N.T.S.

ROOF DRAIN - INSULATED

N.T.S.

OVERFLOW NOZZLE DETAIL

N.T.S.

DENTAL PIPING DETAILS

N.T.S.

SCUPPER ROOF DRAIN DETAIL

Revisions Date

M C

H

A

O T

T

P R

O F

E S

S

IO N A L EN

G I N

E E

R

LICENSE

F

LO R I D A

STATE OF

No. 91858

I

E L

R K

4" FCO

4" FCO

4" FCO

4" TWO-WAY ECO

4" FCO

4" FCO

2" FCO

P-608

P-413

P-413

P-413

P-413

P-413

P-413

P-413

P-413

P-413

P-413

P-413

P-413

P-413

P-413

P-414

P-414

P-418

P-103

P-103

P-418

P-413

P-413

P-413

P-413

P-413

P-413

P-413

P-413

P-413

P-413

P-413

P-413

P-413

P-413

P-413

P-413

P-103

P-418

P-528

P-414

P-502

WCO

P-103

P-418

P-418

P-514

P-514

P-520

P-520

P-520

P-520

4" FD-M

4" VTR

4" VTR

4" VTR

2" V. REFER TO

PY602 FOR

CONTINUATION.

2" V. REFER TO

PY602 FOR

CONTINUATION.

2" V. REFER TO

PY602 FOR

CONTINUATION.

4" SAN

2" SAN

2" SAN

2" SAN

2" SAN

2" SAN

2" SAN

2" SAN

2" SAN

2" SAN

4" SAN

4" SAN

4" SAN

4" SAN

4" SAN

4" SAN

4" SAN

4" SAN

4" SAN

4" SAN

2" SAN

4" SAN

4" SAN

2" SAN

2" SAN

3" SAN

2" SAN

4" SAN

4" SAN

2" SAN

2" SAN

2" SAN

4" SAN

4" SAN

4" SAN

2" SAN

2" SAN

2" SAN

2" SAN

2" SAN

2" SAN

2" V

1 1/2" V

3" V

1 1/2" V

1 1/2" V

1 1/2" V

1 1/2" V

3" V

3" V

3" V

1 1/2" V

3" V 1 1/2" V

2" V

2" V

1 1/2" V

1 1/2" V

2" V

2" V

1 1/2" V

1 1/2" V

1 1/2" V

2" V

3" V

2" V

1 1/2" V

1 1/2" V

1 1/2" V

1 1/2" V

1 1/2" V

1 1/2" V

2" V

1 1/2" V

1 1/2" V

1 1/2" V

1 1/2" V

1 1/2" V

1 1/2" V

2" V

1 1/2" V

1 1/2" V

2" V

3" V

3" V

3" V

3" V

2" V

2" V

1 1/2" V

2" V

2" V

3" V

1 1/2" V

2" V

2" V

2" V

2" V

2" V

1 1/2" V

2" V

2" V

2" V

2" V

4" SAN

3" SAN

2" V 2" V

4" FD-W

3" FD-B

2" SAN

2" SAN

WCO

P-103

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120

305 East Dr., Suite H, Melbourne, Florida 32904

PH: 321.345.9026

FULLY SPRINKLERED

B

IM

/0

B a y P in e s V

A D e n ta l C lin ic

/0

B a y P in e s V

A D e n ta l C lin ic

R

D iv

.r v t

/2

/2

:4

:4

A

M

PY601

PLUMBING GRAVITY ISOMETRICS CONSTRUCT DENTAL CLINIC

BAY PINES VAMC

516-349

AMBER MILTON

02/03/2023 ADL AJZ

MICHAEL R. KNOTT, P.E.

FL License #91858

100% CONSTRUCTION SET

DRAWING NOTES:

1. ISOMETRICS ARE PROVIDED FOR REFERENCE ONLY. REFER TO FLOOR PLANS FOR MORE

INFORMATION.

N.T.S.PY601

1 PLUMBING GRAVITY ISOMETRIC

Revisions Date

M C

H

A

O T

T

P R

O F

E S

S

IO N A L EN

G I N

E E

R

LICENSE

F

LO R I D A

STATE OF

No. 91858

I

E L

R K

WCO

WCO

WCO

WCO

BACKWATER VALVE

6" FCO

BACKWATER VALVE

6" FCO

6" FCO

4" RD-A

85.9 GPM

3" RD-A

26.7 GPM

3" RD-A

37.5 GPM

4" RD-A

86.2 GPM

4" RD-A

73.5 GPM

4" RD-A

74.7 GPM

4" RD-A

64.6 GPM

4" RD-A

68.4 GPM

3" STO

37.5 GPM

4" STO

64.2 GPM

6" STO

236.3 GPM

6" STO

172.1 GPM

4" STO

85.9 GPM

4" STO

86.2 GPM

DOWNSPOUT

DOWNSPOUT

3" ST

37.5 GPM

4" ST

64.2 GPM

6" ST

266.8 GPM

4" ST

85.9 GPM

4" ST

74.7 GPM

6" ST

317.4 GPM

4" ST

84.2 GPM

4" ST

68.4 GPM

4" ST

64.6 GPM

4" STO

74.7 GPM

6" STO

148.2 GPM

4" STO

68.4 GPM

6" STO

133 GPM

6" STO

281.2 GPM

2" V

2" V

2" V

4" CD

4" CD

4" CD

2" V. REFER TO

PY601 FOR

CONTINUATION

2" V. REFER TO

PY601 FOR

CONTINUATION

2" V. REFER TO

PY601 FOR

CONTINUATION

4" FD-B

4" FD-B

4" FD-B

2" ST

15.9 GPM

2" RD-B

15.9 GPM

2" RD-B

11.2 GPM

2" RD-B

9.3 GPM

4" FCO

2" RD-B

9.6 GPM

2" RD-B

9.6 GPM

2" RD-B

11.4 GPM

WCO

WCO

WCO

WCO

WCO

WCO

WCO

4" ST

86.2 GPM

2" ST

30.6 GPM

6" ST

116.8 GPM

2" ST

11.4 GPM

6" ST

2" ST

20.5 GPM

2" ST

11.2 GPM

4" ST

20.4 GPM

4" ST

95.1 GPM

6" ST

222.3 GPM

2" ST

21.0 GPM

2" ST

9.6 GPM

6" ST

148.8 GPM

4" ST

73.5 GPM

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120

305 East Dr., Suite H, Melbourne, Florida 32904

PH: 321.345.9026

FULLY SPRINKLERED

B

IM

/0

B a y P in e s V

A D e n ta l C lin ic

/0

B a y P in e s V

A D e n ta l C lin ic

R

D iv

.r v t

/2

/2

:4

:4

A

M

PY602

PLUMBING STORM ISOMETRICS CONSTRUCT DENTAL CLINIC

BAY PINES VAMC

516-349

AMBER MILTON

02/03/2023 ADL AJZ

MICHAEL R. KNOTT, P.E.

FL License #91858

100% CONSTRUCTION SET

DRAWING NOTES:

1. ISOMETRICS ARE PROVIDED FOR REFERENCE ONLY. REFER TO FLOOR PLANS FOR MORE

INFORMATION.

N.T.S.PY602

1 PLUMBING STORM ISOMETRIC

Revisions Date

M C

H

A

O T

T

P R

O F

E S

S

IO N A L EN

G I N

E E

R

LICENSE

F

LO R I D A

STATE OF

No. 91858

I

E L

R K

P-413

P-413

P-413

P-413

P-413

P-413

P-413

P-413

P-413

P-502

P-413

P-413 P-413

P-413 P-413

P-413 P-413

P-413

P-413

P-413 P-413

P-413

P-413

P-413

P-103

P-418

P-103 P-418

P-608

P-414

P-414

P-103

P-418

P-528

P-520 P-708

P-520

P-520 P-708

P-520

P-103

P-103

P-418

P-514 P-708

GWH-1

ET-1

TP-1

TP-2

P-801

CP-1

TMV-1

P-804

BALANCING VALVE

2 1/2" CW

2" CW

2" CW

1 1/2" CW

1 1/4" CW

1 1/4" CW 1/2" CW

1/2" CW

3/4" HW

3/4" HW 3/4" CW

3/4" HW

3/4" HW 3/4" CW

3/4" HW

3/4" HW 3/4" CW

3/4" HW

3/4" HW 3/4" CW

3/4" HW

3/4" HW 3/4" CW

1" HW

1" HW

3/4" CW

1" HW

1" HW

3/4" CW

1" HW

1" HW

1 1/4" CW

1/2" CW

1" HW

1" HW

1/2" CW

1" HW

1" HW

3/4" HW

3/4" CW

1/2" CW

1 1/4" HW

1 1/4" HW

1 1/4" HW

1 1/4" HW

3/4" CW

1/2" CW

3/4" HW

1 1/2" CW

3/4" HWR

BALANCING VALVE

3/4" HWR

3/4" HWR

1 1/4" HW

1 1/4" HW

1" HWR

1 1/4" HWR

1 1/2" HW

3/4" HWR

1" HW

3/4" HWR

2" CW

1/2" CW

1/2" HW

2" CW

1 1/2" CW

1 1/2" CW

1/2" CW

1/2" CW

1 1/4" CW

1/2" CW

1 1/4" CW

3/4" HW

3/4" HW

3/4" HW

3/4" HW

1/2" CW 3/4" HW

3/4" HW

1/2" CW

3/4" CW

3/4" HW

3/4" HW

3/4" HW

3/4" HW

3/4" CW

3/4" CW

1" HW

1" HW

3/4" CW

1" HW

1" HW

3/4" CW

1" HW

1" HW

1" HW

1" HW

1/2" CW

3/4" HW

3/4" HW

3/4" HW

3/4" HW

1/2" CW

3/4" HW

1/2" CW

3/4" HW

3/4" HW

3/4" CW

2 1/2" CW

1 1/2" CW

1 1/2" CW

1 1/2" CW

3/4" CW

1 1/2" CW

3/4" HW

3/4" HW

1/2" CW

P-514 P-708

1/2" HW

1/2" CW

P-414

P-413

P-413

P-413

P-413

P-413

P-413

P-413

CAP 2" CW, 1" HW, & 3/4"

HWR FOR FUTURE

EXPANSION CONNECTIONS.

2" CW

1" HW

3/4" HWR

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120

305 East Dr., Suite H, Melbourne, Florida 32904

PH: 321.345.9026

FULLY SPRINKLERED

B

IM

/0

B a y P in e s V

A D e n ta l C lin ic

/0

B a y P in e s V

A D e n ta l C lin ic

R

D iv

.r v t

/2

/2

:4

:4

A

M

PY603

PLUMBING PRESSURE

ISOMETRICS

CONSTRUCT DENTAL CLINIC

BAY PINES VAMC

516-349

AMBER MILTON

02/03/2023 ADL AJZ

MICHAEL R. KNOTT, P.E.

FL License #91858

100% CONSTRUCTION SET

DRAWING NOTES:

1. ISOMETRICS ARE PROVIDED FOR REFERENCE ONLY. REFER TO FLOOR PLANS FOR MORE

INFORMATION.

N.T.S.PY603

1 PLUMBING PRESSURE ISOMETRIC

Revisions Date

M C

H

A

O T

T

P R

O F

E S

S

IO N A L EN

G I N

E E

R

LICENSE

F

LO R I D A

STATE OF

No. 91858

I

E L

R K

ZVB-2

(2)AREA ALARM PANELS

ZVB-1

AC-1

VP-1

AMALGAM

SEPERATOR

1" MV

1 1/4" DA

1" MV

1" DA

CAP 1" DA & MV FOR

CONNECTION TO

FUTURE EXPANSION

3/4" MV1" DA

3/4" MV

1" DA

3/4" MV

1" DA

3/4" DA U/G

1/2" DA U/G

1/2" DA U/G

1/2" DA U/G

1" DV U/G

(TYP ALL TREATMENT ROOMS)

1/2" DA U/G

GO-2

GO-3

GO-2

GO-3

GO-2

GO-3 GO-2

GO-3

GO-4

GO-4

1" DA

1" DA U/G

3/4" DA U/G

1/2" DA U/G

3/4" DA U/G

1" DV U/G

1" DV U/G

1/2" DA U/G

(TYP ALL TREATMENT ROOMS)

(TYP ALL SURGERY ROOMS)

3/4" MV

3/4" MV

3/4" MV

3/4" MV

3/4" MV U/G

3" DV U/G

3" DV U/G

2" DV U/G

1 1/2" DV U/G

1 1/2" DV U/G

1 1/2" DV U/G

1 1/2" DV U/G

3/4" DA U/G

2" DV U/G

1 1/2" DV U/G

1 1/2" DV U/G

VP-3

VP-2

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120

305 East Dr., Suite H, Melbourne, Florida 32904

PH: 321.345.9026

FULLY SPRINKLERED

B

IM

/0

B a y P in e s V

A D e n ta l C lin ic

/0

B a y P in e s V

A D e n ta l C lin ic

R

D iv

.r v t

/2

/2

:4

:5

A

M

PY604

PLUMBING MED GAS ISOMETRICS CONSTRUCT DENTAL CLINIC

BAY PINES VAMC

516-349

AMBER MILTON

02/03/2023 ADL AJZ

MICHAEL R. KNOTT, P.E.

FL License #91858

100% CONSTRUCTION SET

CODED NOTES:

1/2" DA & 1" DV UP TO FLOOR MOUNTED UTILITY CENTER.

3/4" DA & 1" DV UP TO FLOOR MOUNTED UTILITY CENTER.

OPTIONAL DV FLOOR CLEAN OUT LOCATION. COORDINATE WITH VA IS CLEANOUT IS DESIRED. CAP

PIPING BFF IF NO CLEANOUT IS PROVIDED.

DRAWING NOTES:

1. ISOMETRICS ARE PROVIDED FOR REFERENCE ONLY. REFER TO FLOOR PLANS FOR MORE

INFORMATION.

2. COORDINATE INSTALLATION OF ALL DENTAL AIR, MEDICAL VAC, AND DENTAL VAC EQUIPMENT AND

PIPING WITH MANUFACTUER'S RECOMMENDATIONS.

3. COORDINATE LOCATION OF INTAKE FOR AIR COMPRESSORS WITH ALL VTR, VACUUM PUMP EXHAUST, WATER HEATER CONCENTRIC VENT, MECHANICAL INTAKES, AND MECHANICAL EXHAUST. INTAKES

SHALL MAINTAIN A 25'-0" CLEARANCE FROM EXHAUST.

N.T.S.PY604

1 PLUMBING MED GAS ISOMETRIC

3" DENTAL VACUUM

PUMP EXHAUST

2" MEDICAL VACUUM

PUMP EXHAUST

4" DENTAL AIR

COMPRESSOR INTAKE

Revisions Date

M C

H

A

O T

T

P R

O F

E S

S

IO N A L EN

G I N

E E

R

LICENSE

F

LO R I D A

STATE OF

No. 91858

I

E L

R K

1 1/2" G

2000 MBH

1 1/2" G

2941.8 MBH

1 1/2" G

941.8 MBH

GAS SHUTOFF VALVE

GWH-1

B-1 & B-2

1" G

100 MBH

1 1/4" G

511.8 MBH

3/4" G

120 MBH

GO-1

GO-1

GO-1

GO-1

GO-1

GO-1

GO-1

GO-1

GO-1 GO-1

3/4" G

10 MBH

3/4" G

20 MBH

3/4" G

30 MBH

3/4" G

10 MBH

(TYP ALL TREATMENT ROOMS)

3/4" G

40 MBH

3/4" G

50 MBH

3/4" G

60 MBH

3/4" G

70 MBH

1" G

80 MBH

1" G

100 MBH

3/4" G

20 MBH

1" G

100 MBH

3/4" G

10 MBH

GO-1

GO-1

GO-1

GO-1

GO-1

GO-1

GO-1

GO-1

GO-1

GO-1

GO-1

3/4" G

20 MBH

3/4" G

30 MBH

3/4" G

40 MBH

3/4" G

50 MBH

3/4" G

60 MBH

3/4" G

70 MBH

1" G

110 MBH

3/4" G

40 MBH

1" G

210 MBH

1 1/4" G

330 MBH

1 1/4" G

841.8 MBH

CAP 1" G PIPING FOR FUTURE

EXPANSION CONNECTION.

ESTIMATED LOAD OF 100 MBH.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120

305 East Dr., Suite H, Melbourne, Florida 32904

PH: 321.345.9026

FULLY SPRINKLERED

B

IM

/0

B a y P in e s V

A D e n ta l C lin ic

/0

B a y P in e s V

A D e n ta l C lin ic

R

D iv

.r v t

/2

/2

:4

:5

A

M

PY605

PLUMBING NATURAL GAS

ISOMETRICS

CONSTRUCT DENTAL CLINIC

BAY PINES VAMC

516-349

AMBER MILTON

02/03/2023 ADL AJZ

MICHAEL R. KNOTT, P.E.

FL License #91858

100% CONSTRUCTION SET

CODED NOTES:

GAS METER WITH PRV. COORDINATE INSTALLATION OF GAS METER WITH TECO. COORDINATE

INSTALLATION OF A PRV AND A SHUTOFF VALVE BEFORE THE GAS METER WITH TECO. COORDINATE PRV TO BE SET TO 2 PSI. AFTER THE METER, PROVIDE TWO GAS SUPPLY PIPES. ONE GAS SUPPLY TO BUILDING. THE SECOND GAS SUPPLY TO THE EMERGENCY GENERATOR. PROVIDE EACH SUPPLY LINE WITH A GAS SHUTOFF VALVE. REFER TO NFPA 110 SECTION 7.9.7 & 7.9.8 FOR MORE INFORMATION ON THE GAS SHUTOFF VALVE LABELING. COORDINATE INCOMING PIPE SIZE WITH CIVIL CONTRACTOR.

1 1/2" G LINE FOR EMERGENCY GENERATOR. PROVIDE A SHUTOFF VALVE AND A PRV SET AT 10" WC

BEFORE CONNECTION TO GENERATOR. PROVIDE A DOUBLE SHUTOFF VALVE WITH ELECTRICAL

PROOF OF CLOSURE PER NFPA 85. INTERLOCK WITH THE GENERATOR.

SET PRV TO 12" WC. REFER TO DETAIL 12/PY502 FOR VENTING REQUIRMENTS.

PROVIDE A 24V SOLENOID VALVE. INTERLOCK WITH EMERGENCY PUSH BUTTON (EPO) AND FIRE ALARM SYSTEM. COORDINATE EPO LOCATION WITH ELECTRICAL CONTRACTOR AND VA. EPO TO BE

PROVIDED BY ELECTRICAL CONTRACTOR. COORDINATE ALL WIRING WITH ELECTRICAL

CONTRACTOR.

DRAWING NOTES:

1. ISOMETRICS ARE PROVIDED FOR REFERENCE ONLY. REFER TO FLOOR PLANS FOR MORE

INFORMATION.

2. FOR NATURAL GAS PIPING OVER 2 PSI INSIDE THE BUILDING, NATURAL GAS CALCULATIONS ARE BASED ON THE 2021 NFPA 54 TABLE 6.2.1(e), SCHEDULE 40 METALLIC PIPE WITH AN INLET PRESSURE

2.0 PSI WITH AN ALLOWABLE PRESSURE DROP OF 1 PSI. MAX CAPACITY OF 2941.8 MBH AND A MAX

LENGTH OF 143 FT.

3. FOR NATURAL GAS PIPING OVER 2 PSI TO THE GENERATOR, NATURAL GAS CALCULATIONS ARE BASED ON THE 2021 NFPA 54 TABLE 6.2.1(v), POLYETHLENE PLASTIC PIPE WITH AN INLET PRESSURE

2.0 PSI WITH AN ALLOWABLE PRESSURE DROP OF 1 PSI. MAX CAPACITY OF 2941.8 MBH AND A MAX

LENGTH OF 63 FT.

4. FOR NATURAL GAS PIPING UNDER 2 PSI, NATURAL GAS CALCULATIONS ARE BASED ON THE 2021 NFPA 54 TABLE 6.2.1(b),SCHEDULE 40 METALLIC PIPE WITH AN INLET PRESSURE LESS THAN 2.0 PSI WITH AN ALLOWABLE PRESSURE DROP OF 0.5" W.C. MAX CAPACITY OF 110 MBH AND A MAX LENGTH

OF 154 FT.

N.T.S.PY605

1 PLUMBING NATURAL GAS ISOMETRIC

Revisions Date

M C

H

A

O T

T

P R

O F

E S

S

IO N A L EN

G I N

E E

R

LICENSE

F

LO R I D A

STATE OF

No. 91858

I

E L

R K

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120

305 East Dr., Suite H, Melbourne, Florida 32904

PH: 321.345.9026

FULLY SPRINKLERED

B

IM

/0

B a y P in e s V

A D e n ta l C lin ic

/0

B a y P in e s V

A D e n ta l C lin ic

R

D iv

.r v t

/2

/2

:4

:5

A

M

PY801

PLUMBING SCHEDULES CONSTRUCT DENTAL CLINIC

BAY PINES VAMC

516-349

AMBER MILTON

02/03/2023 ADL AJZ

MICHAEL R. KNOTT, P.E.

FL License #91858

100% CONSTRUCTION SET

GAS WATER HEATER SCHEDULE

MARK MANUFACTURER MODEL NO. GAS CONNECTION BTUH THERMAL EFFICIENCY

RECOVERY (GPH)

@90°F STORAGE (GALLONS) STORAGE TEMP (°F) SIZE (D"xH") VOLTS/PHASE/HERTZ OPERATING WEIGHT (LBS)

GWH-1 AO SMITH BTH-120 3/4" 120,000 95% 197 60 140 27-3/4" x 55-1/2" 120/1/60 961

THERMOSTATIC MIXING VALVE SCHEDULE

LOCATION MANUFACTURER MODEL NO. OUTLET/TEMPERATURE INLET/OUTLET SIZE MIN. FLOW RATE LOCATION NOTES

TMV-1 BRADLEY S59-3045 130°F 3/4" / 1" 1.5 MASTER @ WATER HEATER 1,2

TMV-2 WATTS LFUSG-B 110°F 1/2" / 1/2" 0.25 @ HAND SINKS/LAVS 1,2

TMV-3 BRADLEY S59-4016 110°F 3/4" / 3/4" 0.5 @ PLUMBING FIXTURES 1,2

TMV-4 BRADLEY S19-2010 110°F / 85°F 1/2" / 1/2" 0.2 / 1.5 @ HAND SINKS WITH EYEWASHES 1,2,3

EXPANSION TANK SCHEDULE

MARK

BASIS OF DESIGN

MANUFACTURER

BASIS OF DESIGN

MODEL NUMBER

TANK VOLUME

(GAL)

ACCEPTANCE

VOLUME (GAL) SIZE (D" x H") CONNECTION SIZE WEIGHT (LBS)

ET-1 TACO PAX25-150 6.6 4 12" x 20-5/8" 3/4" 52

VACUUM PUMP SCHEDULE

MARK MAKE MODEL NO. TYPE

MOTOR QT. /

HP V/PH/HZ SYSTEM FLA SYSTEM

RECIEVER

(GAL) SCFM WEIGHT

VP-1 BEACONMEDAES VHV02D-060H-D DUPLEX 2 / 2.0 208/3/60 14.6 SURGICAL

VACUUM

60 16 @ 19" HG 1634

VP-2 A-DEC DV10 SIMPLEX 1 / 3.4 208/1/60 17.0 DENTAL VACUUM - 74 @ 10" HG 191

VP-3 A-DEC DV10 SIMPLEX 1 / 3.4 208/1/60 17.0 DENTAL VACUUM - 74 @ 10" HG 191

AIR COMPRESSOR SCHEDULE

MARK MAKE MODEL NO. TYPE

MOTOR

QTY. / HP

RECIEVER

(GAL)

CAPACITY

(SCFM) V/P/HZ SYSTEM FLA WEIGHT (LBS)

AC-1 AMICO A-SCD-D-200P-SS-N-150 DUPLEX 2/15 200 48 @ 120 PSI 208/3/60 71.3 2715

NOTES:

1. AIR COMPRESSOR AND ALL ASSOCIATED COMPONENTS SHALL BE PIPED PER MANUFACTURER RECOMMENDATIONS.

2. AIR COMPRESSOR SHALL BE PLACED ON A 4" RAISED CONCRETE PAD.

3. ROUTE CONDENSATE THROUGH A CONDENSATE NEUTRALIZATION KIT TO FLOOR DRAIN.

4. PROVIDED WITH INTEGRAL AIR INLET FILTER, TWO AIR COMPRESSOR ELEMENTS, TWO DRIVE MOTORS, AFTERCOOLER, DECICCANT DRYER, AIR RECEIVER, AND CONTROL SYSTEM

THAT MONITORS DEW POINT AND CO2 IN THE SYSTEM.

5. PROVIDE A HIGH EFFICIENCY COALESCIN PREFILTER RATED FOR 0.01 MICRON WITH AUTOMATIC DRAIN AND ELEMENT CHANGE INDICATOR AND A FULLY DUPLEXED FINAL LINE

PARTICLE FILTERS RATED FOR 1 MICRON WITH ELEMENT CHANGE INDICATOR WITH THE DRYER.

6. PROVIDE SINGLE POINT ELECTRICAL CONNECTION. DISCONNECT PROVIDED BY ELECTRICAL. REFER TO ELECTRICAL DRAWINGS.

NOTES:

1. ALL VACUUM PUMPS AND ALL ASSOCIATED COMPONENTS SHALL BE INSTALLED PER MANUFACTURER RECOMMENDATIONS.

2. ALL VACUUM PUMPS SHALL BE PLACED ON A 4" RAISED CONCRETE PAD.

3. ROUTE EXHAUST CONDENSATE DRIP LEG THROUGH A CONDENSATE NEUTRALIZATION KIT TO FLOOR DRAIN.

4. ROUTE TANK DISCHARGE THROUGH A CONDENSATE NEUTRALIZATION KIT AND DISCHARCE TO A FLOOR DRAIN.

5. PROVIDE SINGLE POINT ELECTRICAL CONNECTION. DISCONNECT PROVIDED BY ELECTRICAL. REFER TO ELECTRICAL DRAWINGS.

NOTES:

1. WATER HEATER AND ALL ASSOCIATED COMPONENTS SHALL BE PIPED PER MANUFACTURER RECOMMENDATIONS.

2. ROUTE T&P VALVE AND INDIRECT DISCHARGE TO FLOOR DRAIN.

3. OUTLET TEMPERATURE SHALL BE SET TO 140°F ON WATER HEATER.

4. WATER HEATER SHALL BE PLACED ON A 4" RAISED CONCRETE PAD.

5. WATER HEATER TO BE CAPABLE OF HEATING WATER TO 180°F. PROVIDE A BYPASS AROUND THE THERMOSTATIC MIXING VALVE FOR THERMAL ERADICATION PURPOSES.

6. ROUTE EXHAUST CONDENSATE DRAIN THROUGH A CONDENSATE NEUTRALIZATION KIT AND DISCHARCE TO A FLOOR DRAIN.

7. PROVIDE INTAKE AND EXHAUST WITH CONCENTRIC VENT KIT.

NOTES:

1. THERMOSTATIC MIXING VALVE SHALL BE PIPED PER MANUFACTURER RECOMMENDATIONS.

2. PROVIDE WITH INLET AND OUTLET SHUT-OFF VALVES.

3. PROVIDE 105°F WATER TO FAUCET AND 85°F WATER TO EYEWASH. MIN FLOW RATE FOR FAUCET IS 0.2 GPM AND MIN FLOW RATE FOR EYEWASH IS 1.5 GPM.

HOT WATER RECIRC. PUMP SCHEDULE

MARK MANUFACTURER MODEL NO. TYPE CAPACITY (GPM) HEAD (FEET) MOTOR (HP) V/PH/HZ

CP-1 BELL & GOSSETT ECOCIRC XL 55-45 INLINE 7.5 38.0 1/2 208/1/60

NOTES:

1. RECIRC PUMP SHALL BE PIPED PER MANUFACTURER RECOMMENDATIONS

2. BALANCING VALVES SHALL BE PROVIDED FOR ALL CIRCULATING SYSTEMS, VALVES SHALL BE SET TO FLOW RATES SHOWN UNLESS NOTED

OTHERWISE.

3. PROVIDE AUTOMATIC TIMER KIT TC-1 AND AQUASTAT AQS-1/2 FOR EACH PUMP LOCATION.

4. PROVIDE SINGLE POINT ELECTRICAL CONNECTION. DISCONNECT PROVIDED BY ELECTRICAL. REFER TO ELECTRICAL DRAWINGS.

PLUMBING FIXTURE SCHEDULE

MARK FIXTURE

BASIS OF DESIGN

MIXING VALVE NO.

CONNECTION SIZES FIXTURE UNITS FLUSH VALVE / FAUCET TYPE

FIXTURE FLUSH VALVE/FAUCET

WASTE PIPE

(INCHES)

VENT PIPE

(INCHES)

COLD WATER

(INCHES)

HOT WATER

(INCHES)

WASTE FIXTURE

UNITS

WATER FIXTURE

UNITS

COLD WATER

FIXTURE UNITS

HOT WATER

FIXTURE UNITS MANUAL

HARD WIRED

SENSOR BATTERY SENSOR FOOT PEDAL

P-103 WATER CLOSET (WALL HUNG, FLUSH VALVE, ADA) ZURN : Z5615-BWL-AM SLOAN : ROYAL 111 ESS-1.28 - 4" 2" 1-1/4" - 4 10 10 - - YES - -

P-413 TREATMENT SINKS ZURN : Z5128 ZURN : Z831B4-XL-28F TMV-2 1-1/2" 1-1/2" 1/2" 1/2" 1 2 1.5 1.5 YES - - -

P-414 HAND SINK ZURN : Z5318 ZURN : Z831B4-XL-28F TMV-2 1-1/2" 1-1/2" 1/2" 1/2" 1 2 1.5 1.5 YES - - -

P-418 LAVATORY ZURN : Z5311 ZURN : Z6920-XL-CWB-HW6-N TMV-2 1-1/2" 1-1/2" 1/2" 1/2" 1 2 1.5 1.5 - YES - -

P-502 MOP SINK FIAT PRODUCTS : TSB3000 FIAT PRODUCTS : 830AA TMV-3 3" 2" 3/4" 3/4" 2 4 3 3 YES - - -

P-514 LAB SINK ELKAY : ILGR4322 ZURN Z871B4-XL-18F TMV-2 / TMV-4 1-1/2" 1-1/2" 1/2" 1/2" 3 2 1.5 1.5 YES - - -

P-520 ORAL SURGERY SINK ELKAY : DLSR272210 ZURN : Z6920-XL-CWB-HW6-J TMV-2 / TMV-4 1-1/2" 1-1/2" 3/4" 3/4" 3 2 1.5 1.5 - YES - -

P-528 KITCHEN SINK ELKAY : LRADQ222265 DELTA : 9113-DST TMV-3 1-1/2" 1-1/2" 3/4" 3/4" 3 2 1.5 1.5 YES - - -

P-608 ELECTRIC WATER COOLER ELKAY : LZSTL8WSLP - - 1-1/2" 1-1/2" 1/2" - 0.5 0.25 0.25 - YES - - -

P-708 EMERGENCY EYE AND FACE WASH BRADLEY : S19274E - TMV-4 - - 3/4" TEMPERED - - - - - YES - - -

P-801 WALL HYDRANT ZURN : Z1320XL - - - - 3/4" - - - - - YES - - -

P-804 HOSE BIBB ZURN : Z1341 - - - - 3/4" - - - - - YES - - -

NOTES:

1. REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION

ELECTRONIC TRAP PRIMER SCHEDULE

MARK BASIS OF DESIGN MANUFACTURER

BASIS OF DESIGN

MODEL NUMBER CW INLET CW OUTLET SIZE

MAX NUMBER OF

DRAINS SERVED

DIMENSIONS (L" x W" x H")

ELECTRICAL

(V/P/HZ)

TP-1 PRECISION PLUMBING PRODUCTS PT-6 3/4" 1/2" 6 16" x 14" x 3-3/8" 120/1/60

TP-2 PRECISION PLUMBING PRODUCTS PT-6 3/4" 1/2" 6 16" x 14" x 3-3/8" 120/1/60

NOTES:

1. PROVIDE WITH INTEGRAL DISCONNECT.

PLUMBING MEDICAL GAS OUTLET

MARK

BASIS OF DESIGN

MANUFACTURER

BASIS OF DESIGN

MODEL NO. DESCRIPTION MOUNTING SERVICE

GO-1 CHICAGO FAUCETS LGN1-A11C-50 GAS OUTLET WALL NATURAL GAS

GO-2 CHICAGO FAUCETS LGN1-A11B-50 GAS OUTLET WALL VACUUM (LAB)

GO-3 CHICAGO FAUCETS LGN1-A11A-50 GAS OUTLET WALL COMPRESSED AIR (LAB)

GO-4 AMICO O-FXNC-DI-U-VAC GAS OUTLET WALL VACUUM (SURGERY)

PLUMBING MEDICAL GAS VALVE BOX

MARK

BASIS OF DESIGN

MANUFACTURER

BASIS OF DESIGN

MODEL NO. DESCRIPTION MOUNTING SERVICE LOCATION

ELECTRICAL

(V/PH/HZ)

ZVB-1 AMICO AVU-3A2V ZONE VALVE BOX WALL MA & DV CORRIDOR C-1 120/1/60

ZVB-2 AMICO AVU-3A2V ZONE VALVE BOX WALL MA & DV CORRIDOR C-2 120/1/60

NOTES:

1. PROVIDE EACH ZONE VALVE BOX WITH A LOCAL ALARM PANEL, DESIGN BASIS AMICO A3AR-U-AV. REFER TO FLOOR PLANS FOR LOCAL ALARM LOCATION.

2. PROVIDE PRESSURE SWITCHES AND LOCATE PRESSURE SWITCHES INSIDE ZONE VALVE BOX. WIRE PRESSURE SWITCHES BACK TO LOCAL ALARM PANEL.

3. WIRE LOCAL ALARM PANELS BACK TO BOTH MASTER ALARM PANEL LOCATIONS.

4. MEDICAL AIR WILL BE USED FOR MEDICAL AIR TO THE PATIENTS. INSTRUMENT AIR WILL BE USED FOR DENTAL AIR FOR TOOLS.

GAS LOAD SCHEDULE

MARK DESCRIPTION QTY

GAS CONNECTION

SIZE BTUH TOTAL BTUH

ROOM OUTLETS 21 1/2" 10,000 210,000

ASSUMED EXPANSION

GAS LOAD

1 100,000 100,000

B-1,2 BOILER 2 1-1/4" 255,900 511,800

GENERATOR EMERGENCY

GENERATOR

1 1-1/2" 2,000,000 2,000,000

GWH-1 WATER HEATER 1 3/4" 120,000 120,000

TOTAL BTUH: 2,941,800

TOTAL MBH: 2941.8

Revisions Date

M C

H

A

O T

T

P R

O F

E S

S

IO N A L EN

G I N

E E

R

LICENSE

F

LO R I D A

STATE OF

No. 91858

I

E L

R K

-SPIN-IN TAKE-OFF

-RECTANGLE-TO-ROUND TAKE-OFF

DNUP

-TRANSITION, SQUARE TO ROUND

-CEILING EXHAUST

-CEILING RETURN

-STANDARD BRANCH TAKE-OFF

-RADIUS ELBOW

-TRANSITION, ECCENTRIC

-FLEXIBLE DUCT

-CHANGE OF ELEVATION

-TRANSITION, CONCENTRIC

-SQUARE THROAT ELBOW

W/TURNING VANES

-RECTANGULAR/ROUND BRANCH TAKE-

OFF

OR ROUND/ROUND BRANCH TAKE-OFF

-SQUARE THROAT TEE

-RADIUS TEE

-SUPPLY REGISTER OR GRILLE

-RETURN/EXHAUST REGISTER OR GRILLE

(VERTICAL MOUNT, SIDEWALL)

(VERTICAL MOUNT, SIDEWALL)

-CEILING DIFFUSER, ROUND NECK

(CEILING DIFFUSERS ARE 4-WAY THROW UNO)

-CEILING DIFFUSER, RECTANGULAR OR

SQUARE NECK (CEILING DIFFUSERS

ARE 4-WAY THROW UNO)

-AIRFLOW SENSORAFS-X

ECC-X -ENGINEERING CONTROL CENTER

HVAC ABBREVIATIONSHVAC SYMBOL LEGEND

SYMBOL DESCRIPTIONSYMBOL DESCRIPTIONSYMBOL DESCRIPTION SYMBOL DESCRIPTION SYMBOL DESCRIPTION

-CONDENSATE

-CHILLED WATER RETURN

-CONDENSER WATER SUPPLY

-CHILLED WATER SUPPLY

-CONDENSER WATER RETURN

PIPING LEGEND

SYMBOL DESCRIPTIONSYMBOL DESCRIPTION

CWS

CWR

CHWS

CHWR

CD

-HOT WATER RETURN

-HOT WATER SUPPLYHWS

HWR

-WATER METER

-FLOW METER

-PRESSURE GAUGE

-ELBOW, TURNED DOWN

-CONNECTION, BOTTOM

-INLINE PUMP

-CAP

-INLINE PUMP

-ELBOW, 90°

-CONNECTION, TOP

-ELBOW, TURNED UP

-TEE, OUTLET DOWN

FM

M

-ELBOW, 45°

-TEE, OUTLET UP

-45° PIPE RISE (R)/DROP (D)

-PIPE ANCHORS

-CONCENTRIC REDUCER

-ECCENTRIC REDUCER

R R

-FLANGES

-FLEXIBLE CONNECTOR

-Y-TPE STRAINER

-MALE HOSE CONNECTION

-PIPE CONNECTION

-CONTROL VALVE

-BUTTERFLY VALVE

-FLOW DIRECTION

-CALIBRATING BALANCING VALVE

-BALL VALVE

-STRAINER

-UNION

-THERMOMETER

-SLOPE DIRECTION (DOWN)

-PSI REG.

-FLOW SWITCH

-CHECK VALVE

-THREE-WAY CONTROL VALVE

-FLEX CONNECTION (DOUBLE SPHERE FOR

PIPES 6" AND LARGER; SINGLE SPHERE FOR

PIPES 4" AND SMALLER

-RELIEF VALVE

-VALVE ON RISER

-TEST PLUG

-GLOBE VALVE

-PSI REG.

-MANUAL VENT

EQUIP. -P-TRAP

-DUCT SMOKE DETECTOR

-DIGITAL OUTPUT FROM DDC CONTROLLER

-DIGITAL INPUT TO DDC CONTROLLER

-STARTER

-CURRENT SENSING STATUS SWITCH

-DRY CONTACT

-ANALOG OUTPUT FROM DDC CONTROLLER

-ANALOG INPUT TO DDC CONTROLLER

CS

A -ALARM

-COM OUTPUT FROM DDC CONTROLLER

-COM INPUT TO DDC CONTROLLER

S

-HARD-WIRED INTERLOCKi

-24VAC POWER

-IMMERSION TEMPERATURE

P

-FLOW SWITCH

R -REFRIGERANT SENSOR

T -THERMOSTAT

XFM -TRANSFORMER

-EMERGENCY PUSHBUTTON

-DIFF. PRESSURE SWITCH DIGITAL

TRANSMITTER W/ THERMOWELL

CO -SPACE CARBON DIOXIDE

DPS

SENSOR/TRANSMITTER

-FLOW METER

-SPACE PUSH-BUTTON OVER-RIDE SWITCH

-AIR FLOW SENSOR

-DUCT MOUNTED TEMPERATURE SENSOR

-2-WAY VALVE W / 24VAC OR 120VAC

-SPACE TEMPERATURE SENSOR

-SPACE RH SENSOR

24VAC

24VAC

F

-ACTUATOR AS INDICATED

-ACTUATOR W / 24VAC OR 120VAC

ACTUATOR AS INDICATED

-INDICATES AVERAGING ELEMENT SENSOR

-VARIABLE FREQUENCY DRIVEVFD

-DIFF. PRESSURE

INDICATING TRANSMITTER

-MAGNEHELIC DIFFERENTIAL

-OPPOSED BLADE DAMPER

-PARALLEL BLADE DAMPER

DPIT

-STATIC PRESSURE SENSORSP

PRESSURE GAUGE

-PARTICULATE TRANSMITTERPT

-INDICATES PROBE SENSOR

SYMBOL DESCRIPTION SYMBOL DESCRIPTION

CONTROLS LEGEND

-CALIBRATED BALANCING VALVE

-SOLENOID VALVE (2-POSTION W/ ACTUATOR)

-FLOW SWITCH

PRESSURE SWITCH

-AUTOMATIC AIR VENT

BASIC MATERIALS

-CURRENT SENSORCS-X

-MANUAL BALANCING DAMPER

-MOTOR OPERATED CONTROL DAMPER

(MOD)

-FLEXIBLE CONNECTION

-ACCESS DOORS, VERTICAL OR

HORIZONTAL

-DOOR GRILLE

-UNDERCUT DOOR

-DUCT ELBOW, NEGATIVE PRESSURE,

RETURN

-DUCT ELBOW, EXHAUST

-DUCT ELBOW, POSITIVE PRESSURE

(SUPPLY)

-NEW DUCTWORK, FIRST DIMENSION IS

SIDE SHOWN

-TEMPERATURE SENSOR

-MOTORIZED CONTROL DAMPER

-HUMIDISTAT/HUMIDITY SENSOR

-THERMOSTAT/TEMPERATURE SENSOR

-STATIC PRESSURE SENSOR

-DUCT SMOKE DETECTOR

-BACKDRAFT DAMPER

-CEILING MOUNTED ACCESS DOOR

-RECTANGULAR DUCT SECTION UP,

EXHAUST

-RECTANGULAR DUCT SECTION UP,

NEGATIVE PRESSURE, RETURN

-RECTANGULAR DUCT SECTION UP,

POSITIVE PRESSURE, SUPPLY OR

OUTSIDE AIR

-ROUND DUCT SECTION UP

T

H

DOWN UP W/IN FLOOR

UC

M

T

SP

BD

M

-CONNECT TO EXISTING

-DEMOLISH TO POINT INDICATED

-HUMIDITY SENSOR (DUCT MOUNTED)H

-CARBON DIOXIDE SENSOR (DUCT MOUNTED)CO2

-CARBON DIOXIDE SENSORCO2

-SMOKE (WITH ACCESS PANEL)

-FIRE DAMPER (WITH ACCESS PANEL)

EXISTING TO BE REMOVED (HEAVY, DASHED LINE)

EXISTING TO REMAIN (THIN, HALFTONED, SOLID LINE)

NEW (HEAVY, SOLID LINE)

-STATIC PRESSURE SENSOR

-DIFFERENTIAL PRESSURE SENSORDPS-X

-DAMPERD-X

T-X

-ROOM THERMOSTAT/TEMPERATURE

SENSOR

DDC -DIRECT DIGITAL CONTROLS

PRS -PRESSURE REDUCING STATION

SP -STATIC PRESSURE

-CFM (CUBIC FEET PER MINUTE)

CV -CONSTANT AIR VOLUME

-ROOFTOP AIR HANDLING UNITRTU

RS/L -REFRIGERANT SUCTION & LIQUID LINES

C

-OUTSIDE AIR TEMPERATUREOAT

-VARIABLE AIR VOLUMEVAV

-SUPPLY AIRSA

-ROOFTOP HEAT PUMPRHP

-REHEAT COILRHC

-REVOLUTIONS PER MINUTERPM

-RETURN AIRRA

-POLYVINYL CHLORIDE PIPEPVC

-PSI GAUGEPSIG

-POUNDS PER SQUARE INCHPSI

-PRESSURE REDUCING VALVEPRV

-OUTSIDE AIROA

-NOT TO SCALENTS

-NORMALLY OPENNO

-NORMALLY CLOSEDNC

-LINEAR DIFFUSERLD

-LEAVING WATER TEMPERATURELWT

-LEAVING AIR TEMPERATURELAT

-GALLONS PER MINUTEGPM

-FEET PER MINUTE

-FIRE DAMPER

-FIRE ALARM SYSTEM

-ENTERING WATER TEMPERATURE

-ENTERING AIR TEMPERATURE

-DOWN

-CONDENSING UNIT

-CUBIC FEET PER MINUTE

-COOLING TOWER

-CONDENSATE

-CENTER LINE

-BRITISH THERMAL UNIT

-BRAKE HORSEPOWER

-BOTTOM OF PIPE

-ACCESS PANEL

-ABOVE FINISHED FLOOR

FPM

FD

FAS

EWT

EAT

DN

CU

CFM

CT

CD

BTU

BOP

BHP

AP

AFF

-AIR HANDLING UNITAHU

MBH -THOUSAND BTUs PER HOUR

ESP -EXTERNAL STATIC PRESSURE

KW -KILOWATT

MCA -MINIMUM CIRCUIT AMPS

MOCP -MAXIMUM OVER CURRENT PROTECTION

TSP

TEFC -TOTALLY ENCLOSED FAN COOLED

-VOLTS/PHASEV/PH

VFD -VARIABLE FREQUENCY DRIVE

-TOTAL STATIC PRESSURE

FLA -FULL LOAD AMPS

MOD -MOTOR OPERATED CONTROL DAMPER (MOD)

-PACKAGED TERMINAL AIR CONDITIONERPTAC

-ABOVE FINISHED ROOFAFR

-BUTTERFLY VALVEBFV

c

L

-EXHAUST AIREA

-CLEAN OUTCO

TS-X -TEMPERATURE SENSOR

SPS-X -STATIC PRESSURE SENSOR

H-X -HUMIDITY SENSOR

-CARBON DIOXIDE SENSORCO2-X

V-X

-VALVE (CHILLED WATER/HEATING HOT

WATER)

WFM-X -WATER FLOW METER

2-AHU-3-1

26-TU-I-I

VIEW NUMBER

DRAWING NUMBER WHERE SHOWN

SECTIONLETTER

TYPICAL UNIT NUMBER; AHU NO. 1, LOCATED ON LEVEL 3, LOCATED IN BLDG. 2

BUILDING NO. WHERE EQUIPMENT IS LOCATED.

AHU NUMBER

EQUIPMENT ABBREVIATION. AN "(E)" SHOWN IN FRONT OF EQUIPMENT TAGS NOTIFIES

THAT EQUIPMENT IS EXISTING

ITEM NUMBER (TERMINAL UNIT NO. 1)

ITEM (TERMINAL UNIT SHOWN)

SERVED BY AIR HANDLER UNIT NO. 1

BUILDING NO. WHERE EQUIPMENT IS LOCATED

H4

H7

A

SHEET NUMBER

A 200

DEVICE MARK

DEVICE FLOW RATE (CFM)

12X10 SA

DUCT DIMENSION (INCHES)

TYPICAL AIR DISTRIBUTION DEVICE TAG

TYPICAL DUCTWORK TAG

SYSTEM TYPE (SA = SUPPLY AIR , RA = RETURN

AIR, OA = OUTSIDE AIR, EA = EXHAUST AIR,

SS EA = STAINLESS-STEEL EXHAUST)

LEVEL EQUIPMENT LOCATED ON / LEVEL IT SERVES

DRAWING SYMBOLS

REVISION REFERENCEXX

SHEET NOTE CALLOUTXX

-EQUIPMENT WITH CLEARANCE

CLEARANCE

EQUIPMENT

1. CONNECTION TO EQUIPMENT SHALL BE VERIFIED WITH MANUFACTURER'S CERTIFIED DRAWINGS.

TRANSITIONS TO ALL EQUIPMENT SHALL BE VERIFIED AND PROVIDED FOR EQUIPMENT FURNISHED.

2. DIMENSIONS SHALL BE FIELD-VERIFIED AND COORDINATED PRIOR TO PROCUREMENT OR

FABRICATION. COORDINATE THE WORK WITH OTHER TRADES INVOLVED. FIELD MODIFICATIONS SUCH

AS OFFSETS IN PIPING OR DUCTWORK (INCLUDING DIVIDED DUCTWORK) NEEDED DUE TO

OBSTRUCTIONS OR INTERFERENCES SHALL BE PROVIDED AT NO ADDITIONAL COST.

3. DUCT CONSTRUCTION SHALL BE IN ACCORDANCE WITH THE LATEST EDITION OF THE SMACNA HVAC

DUCT CONSTRUCTION STANDARD.

4. INSTALL ALL FIRE DAMPERS, SMOKE DAMPERS AND COMBINATION FIRE/SMOKE DAMPERS IN

ACCORDANCE WITH MANUFACTURE'S INSTALLATION DIRECTIONS. PROVIDE ACCESS DOORS TO

ALLOW COMPLETE INSPECTION AND MAINTENANCE OF ALL DEVICES.

5. PROVIDE 1.5R ELBOWS IN DUCTWORK AS INDICATED. IF 1.5R ELBOWS DO NOT FIT, PROVIDE 1.0R ELBOWS. IF 1.0R ELBOWS DO NOT FIT, PROVIDE 90 DEGREE RECTANGULAR DUCT ELBOWS WITH

TURNING VANES.

6. DUCT SIZES AND ALL OPENINGS THROUGH BUILDING CONSTRUCTION SHALL SUIT EQUIPMENT

FURNISHED.

7. COORDINATE DIFFUSER, GRILLE AND REGISTER LOCATIONS WITH ARCHITECTURAL REFLECTED

CEILING PLANS AND EQUIPMENT OF ALL TRADES.

8. LOCATE THERMOSTATS, TEMPERATURE SENSORS, HUMIDISTATS, AND HUMIDITY SENSORS AT 48"

ABOVE FINISHED FLOOR UNLESS NOTED OTHERWISE. COORDINATE LOCATIONS WITH OTHER

EQUIPMENT, FURNITURE, AND DOOR SWINGS.

9. ALL EQUIPMENT, DUCTWORK, ETC., SHALL BE SUPPORTED AS DETAILED AND/OR SPECIFIED. PROVIDE

ADDITIONAL SUPPORTS AS REQUIRED TO PROVIDE A VIBRATION-FREE, RIGID INSTALLATION.

10. ALL DUCT SIZES SHOWN ARE INSIDE CLEAR DIMENSIONS.

11. DAMPERS AND INSIDES OF DUCTS VISIBLE THROUGH GRILLES, REGISTERS AND DIFFUSERS SHALL BE

PAINTED FLAT BLACK.

12. REFER TO TYPICAL DETAILS FOR PIPING AND INSTALLATION OF EQUIPMENT.

13. TRAPPED CONDENSATE DRAINS FROM ALL MECHANICAL EQUIPMENT SHALL BE PROVIDED FOR

PROPER DRAINAGE TO SUIT EQUIPMENT FURNISHED.

14. ACCESS PANELS IN DUCTWORK AND CEILINGS SHALL BE PROVIDED WHERE REQUIRED FOR

OPERATION, BALANCING OR MAINTENANCE OF ALL MECHANICAL EQUIPMENT.

15. ALL DUCTWORK AND PIPING IS SHOWN SCHEMATICALLY. PROVIDE ALL TRANSITIONS, TURNING VANES, ELBOWS, FITTINGS, ETC., TO ALLOW SMOOTH FLOWS. ALL SPLIT DUCT FITTINGS SHALL TRANSITION TO

FULL SIZE OF THE SUM OF BOTH BRANCHES, UPSTREAM OF SPLIT.

16. COORDINATE SIZE REQUIREMENTS OF ALL CONCRETE HOUSEKEEPING PADS UNDER ALL FLOOR-

MOUNTED EQUIPMENT. SEE STRUCTURAL DRAWINGS FOR PAD DETAILS AND SPECIFICATIONS.

17. VERIFY FINISH WITH ARCHITECT PRIOR TO PURCHASING GRILLES, REGISTERS, DIFFUSERS, LOUVERS

AND OTHER AIR DISTRIBUTION DEVICES.

18. PROVIDE FLEXIBLE DUCT CONNECTIONS ON ALL DUCTWORK CONNECTING TO FANS, AIR HANDLING

UNITS, AND FAN COIL UNITS.

19. PROVIDE TRANSITIONS AT DIFFUSER NECKS AS REQUIRED TO MATCH SIZES OF FLEX DUCTS TO BE

CONNECTED.

20. SLEEVE AND SEAL ALL PIPING PENETRATIONS THROUGH BUILDING PARTITIONS.

21. MAINTAIN CLEARANCE OF A MINIMUM OF 6" BETWEEN DUCTWORK, PIPING, EQUIPMENT, ETC., AND ALL FIRE RATED AND FIRE/SMOKE RATED PARTITIONS, TO ALLOW FOR INSPECTIONS OF RATED WALLS.

22. LOCATE ALL OUTSIDE AIR INTAKES A MINIMUM OF 25'-0" CLEAR FROM ALL PLUMBING VENTS AND EXHAUST AIR DISCHARGE LOCATIONS. LOWEST POINT OF EACH OUTSIDE AIR INTAKE ON ROOF SHALL

BE A MINIMUM OF 24" ABOVE ROOF.

23. DUCT RUNOUTS TO DIFFUSERS SHALL MATCH THE SIZE OF THE DIFFUSER NECK.

24. UNLESS OTHERWISE NOTED, ALL EQUIPMENT AND VALVE DRAINS SHALL BE INDEPENDENTLY PIPED

FULL SIZE TO THE NEAREST PLUMBING DRAIN.

GENERAL NOTES

SUSTAINABLE DESIGN REQUIREMENTS

1.0 GENERAL:

A. REQUIREMENTS BELOW ARE BASED ON THE VA SUSTAINABLE DESIGN MANUAL - 2014: REV1 2017.

2.0 ENERGY AND ATMOSPHERE

A. FUNDAMENTAL AND ENHANCED COMMISSIONING (Cx) AND VERIFICATION

1. PROVIDE COMMISSIONING SERVICES FOR MECHANICAL, ELECTRICAL, AND PLUMBING PER

THE VA COMMISSIONING SPECIFICATION SECTIONS FOR EACH DISCIPLINE.

B. MINIMUM ENERGY PERFORMANCE

1. EQUIPMENT EFFICIENCY VALUES SHALL COMPLY WITH ASHRAE STANDARD 90.1-2013.

2. TOTAL BUILDING PERFORMANCE SHALL BE IN ACCORDANCE WITH CRITERIA INDICATED IN

THE SUBMITTED DESIGN NARRATIVE FOR MECHANICAL, ELECTRICAL, AND PLUMBING.

C. BUILDING-LEVEL ENERGY METERING AND ADVANCED ENERGY METERING

1. INSTALL NEW BUILDING-LEVEL ENERGY METERS, OR SUBMETERS THAT CAN BE

AGGRE…