This file attachment relates to a federal solicitation to construct a dental clinic at the Bay Pines VA Medical Center. The solicitation seeks a general contractor to provide all labor, materials, equipment and supervision necessary to construct a new dental clinic building. The project scope includes general construction, mechanical, electrical and plumbing work, demolition of an existing modular building, select site utilities and concrete work, a gravel parking lot with permeable pavement, and select landscaping including trees. In addition to construction of the new clinic building, the project also involves installation of a new backup generator and driveway. The soliciting agency is the Department of Veterans Affairs Technology Acquisition Center located in Austin, Texas. The solicitation number is 36C77623B0029.
View the file
Other files
Show all 19
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
A2
A3
B8B7
AHU-1
B-1 & 2
4" FD-B
PROVIDE FD WITH INTEGRAL
BACKWATER VALVE
CP-1
P-801
P-804
2" V
ET-1
GWH-1
2" V. REFER TO 1/PJ111
FOR CONTINUATION
2" V. REFER TO 1/PJ111
FOR CONTINUATION
1 1/4" HW, 1" HWR, & 2"
CW. REFER TO 1/PK111
FOR CONTINUATION
1 1/4" HW
1 1/4" HWR
1 1/2" CW
2 1/2" CW
2" CW
REFER TO 1/PK111
FOR CONTINUATION
1" G. REFER TO 1/PG111
FOR CONTINUATION
4" ST DN
68.4 GPM
4" ST & STO
UP TO RD
4" ST DN
64.6 GPM
4" STO
68.4 GPM
6" STO
133 GPM
1 1/4" G
4" FD-B
PROVIDE FD WITH INTEGRAL
BACKWATER VALVE
4" FD-M
REFER TO 1/PG111
FOR CONTINUATION
REFER TO 1/PG111
FOR CONTINUATION
1 1/2" G
1 1/2" G
1 1/4" G
1" G
1" G
1" HWR
3/4" HWR
2" V DN
2" V DN
2" V
TMV-1
TP-1
2 1/2" CW U/G
1 1/2" G U/G
2" CW
6" STO. REFER TO
1/PJ111 FOR
CONTINUATION
1" G. REFER TO 1/PG111
FOR CONTINUATION
1 1/4" HW & 3/4" HWR. REFER TO
1/PK111 FOR CONTINUATION
1 1/4" HW
2" CW. REFER TO 1/PK111
FOR CONTINUATION
Mechanical
A.5
A1
A1.5
B8
VP-1
2" V DN
2" V. REFER TO 1/PJ111
FOR CONTINUATION
3/4" CW. REFER TO 1/PK111
FOR CONTINUATION
1 1/4" DA. REFER TO
1/PG111 FOR
CONTINUATION
1" MV
1 1/4" DA
3" FD-B
4" FD-B
PROVIDE FLOOR DRAIN WITH
INTEGRAL BACKWATER VALVE
4" AIR COMPRESSOR INTAKE.
REFER TO 1/PJ111 FOR
CONTINUATION.
3" DV. REFER TO 1/PG111
FOR CONTINUATION
3" DV. PROVIDE A REDUCER AFTER 2" 45° ELBOW
DOWN. TURN 1 1/2" PIPING HORIZONTAL WITH A 45°
ELBOW. ROUTE 1 1/2" DV UP WITH A 45° ELBOW UP.
PIPE VACUUM PIPE UP TO AMALGAM SEPERATOR.
1 1/2" DV TANDEM INTAKE MANIFOLD. CONNECT
DV TO MANIFOLD AND CONNECT TO VACUUM
PUMPS. PIPE VACUUM PIPE CONNECTIONS PER
MANUFACTURER'S RECOMENDATIONS.
4" FD-W
Medical Mechanical
AC-115
3" DV U/G
7 7VP-2 VP-3
1" MV. REFER TO
1/PG111 FOR
CONTINUATION
TP-2
DC-1
2" V DN
3/4" CW
3/4" HW, 1 1/2" CW, 3/4"
HWR. REFER TO 1/PK111
FOR CONTINUATION
P-103 P-103
P-418
P-418
BALANCING VALVE. SET TO 1.0 GPM
3/4" HW
1 1/2" CW
3/4" HWR
Staff Toilet
133A Staff Toilet
135A
1/2" CW
1/2" HW
1/2" CW, 1/2" HW.
REFER TO 1/PK111
FOR CONTINUATION
A.5
A1
A1.5
A2
A3
B8B7
TP-2
TP-1
(3)1/2" CW LINES UP
TO TRAP PRIMER
(3)1/2" CW LINES UP
TO TRAP PRIMER
Mechanical
Medical Mechanical
Corridor
C-4
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
FULLY SPRINKLERED
B
IM
/0
B a y P in e s V
A D e n ta l C lin ic
/0
B a y P in e s V
A D e n ta l C lin ic
R
D iv
.r v t
/2
/2
:4
:3
A
M
PX401
PLUMBING ENLARGED PLANS CONSTRUCT DENTAL CLINIC
BAY PINES VAMC
516-349
AMBER MILTON
02/03/2023 ADL AJZ
MICHAEL R. KNOTT, P.E.
FL License #91858
100% CONSTRUCTION SET
CODED NOTES:
2 1/2" CW DN. REFER TO DETAIL FOR WATER ENTRY.
1 1/2" CW, 3/4" HWR, 1 1/2" HW, & G TO GWH-1. ROUTE HW THROUGH TMV. 3" INTAKE AND EXHAUST
ROUTED THROUGH A CONCENTRIC VENT KIT THROUGH THE ROOF. REFER TO DETAIL.
3/4" CW TO HOSE BIBB
3/4" CW TO TP. 1/2" CW FROM TP TO FLOOR DRAINS
1 1/4" G DN TO BOILERS. REFER TO DETAIL. REFER TO MECHANICAL DETAIL FOR CONNECTION
LOCATION.
3" VACUUM PUMP EXHAUST PIPE UP TO ROOF. PROVIDE 2 45° TEES TO CONNECT EACH VACUUM
PUMP TO EXHAUST. PROVIDE A DRIP LEG BELOW ALL CONNECTIONS AND ROUTE DRIP LEG TO
FLOOD DRAIN BEHIND VACUUM PUMPS. PIPE VACUUM PIPE CONNECTIONS PER MANUFACTURER'S
RECOMENDATIONS.
DENTAL VACUUM PUMPS. CONNECT DRAIN, EXHAUST, AND DENTAL VACUUM INTAKE PER
MANUFACTURER'S RECOMENDATIONS. ROUTE ALL DRAINS AND DRIP LEGS TO HUB DRAIN.
1 1/4" HW LOOP, 3/4" CW DN. 1/2" HW TO TMV-2. 1/2" CW & HW TO LAV/SINK.
AMALGAM SEPERATOR, DESIGN BASIS SOLMETEX NXT HG5 HIGH VOLUME (PART NUMBER NXT-HG5- HV). ROUTE VACUUM PIPING FROM AMALGAM SEPERATOR TO DENTAL VACUUM PUMPS. INSTALL ALL
CONNECTIONS PER MANUFACTURER'S RECOMENDATIONS. MOUNT AMALGAM SEPERATOR TO WALL
ABOVE VACUUM PUMP INLET AND DRAIN CONNECTION. WALL MOUNTING TO BE CAPABLE OF
SUPPORTING 100 LBS.
1 1/2" CW DN. 1 1/4" CW TO WC
2" VACUUM PUMP EXHAUST PIPE UP TO ROOF
SET PRV TO 12" WC. REFER TO DETAIL 12/PY502.
SET PRV TO 12" WC. REFER TO DETAIL 12/PY502. PROVIDE A DOUBLE SHUTOFF VALVE WITH
ELECTRICAL PROOF OF CLOSURE PER NFPA 85. INTERLOCK WITH THE BOILER.
GAS METER WITH PRV. COORDINATE INSTALLATION OF GAS METER WITH TECO. COORDINATE
INSTALLATION OF A PRV AND A SHUTOFF VALVE BEFORE THE GAS METER WITH TECO. COORDINATE PRV TO BE SET TO 2 PSI. AFTER THE METER, PROVIDE TWO GAS SUPPLY PIPES. ONE GAS SUPPLY TO BUILDING. THE SECOND GAS SUPPLY TO THE EMERGENCY GENERATOR. PROVIDE EACH SUPPLY LINE WITH A GAS SHUTOFF VALVE. REFER TO NFPA 110 SECTION 7.9.7 & 7.9.8 FOR MORE INFORMATION ON THE GAS SHUTOFF VALVE LABELING. COORDINATE INCOMING PIPE SIZE WITH CIVIL CONTRACTOR.
4" AIR INTAKE AND 1" DA TO AIR COMPRESSOR. REFER TO DETAIL 4 / PY501 FOR.
1/2" CW FROM TRAP PRIMER TO FLOOR DRAIN.
1/2" DA DN TO DUST COLLECTOR. CONFIRM EXACT CONNECTION SIZE AND LOCATION WITH FINAL
EQUIPMENT SELECTION..
2" ST TO SCUPPER DRAIN ON CANOPY. REFER TO PJ121 FOR CONTINUATION.
2" ST DN. PROVIDE A WCO BEFORE PIPING DROPS BFF.
PROVIDE A 24V SOLENOID VALVE. INTERLOCK WITH EMERGENCY PUSH BUTTON (EPO) AND FIRE ALARM SYSTEM. COORDINATE EPO LOCATION WITH ELECTRICAL CONTRACTOR AND VA. EPO TO BE
PROVIDED BY ELECTRICAL CONTRACTOR. COORDINATE ALL WIRING WITH ELECTRICAL
CONTRACTOR.
DRAWING NOTES:
1. SLOPE VENT PIPING TO SANITARY MAIN.
2. DESIGN BASIS AIR COMPRESSOR CAN DELIVER A MAX PRESSURE OF 120 PSIG. SYSTEM IS
CURRENTLY DESIGNED TO DELIVER 80 PSIG AFTER PRV. COORDINATE FINAL PRESSURE WITH FINAL EQUIPMENT SELECTIONS. IF A HIGHER PRESSURE (ABOVE 120 PSI) IS NEEDED NOTIFY ENGINEER OF
RECORD.
3. SLOPE ALL CW PIPING FROM TRAP PRIMER TO FLOOR DRAIN. REFER TO DETAIL.
1/2" = 1'-0"PX401
1 MECHANICAL ROOM ENLARGED PLAN - PLUMBING
1/2" = 1'-0"PX401
2 MEDICAL MECHANICAL ROOM ENLARGED PLAN - PLUMBING
1/2" = 1'-0"PX401
3 STAFF RESTROOMS ENLARGED PLAN - PRESSURE
N
0 4' 8' 16' 24'
1/8" = 1'-0"
1/8" = 1'-0"PX401
4 PLUMBING TRAP PRIMER PLAN - NEW WORK
0 1' 2' 4' 6'
1/2" = 1'-0"
Revisions Date
M C
H
A
O T
T
P R
O F
E S
S
IO N A L EN
G I N
E E
R
LICENSE
F
LO R I D A
STATE OF
No. 91858
I
E L
R K
N
AICH RD
WALL HYDRANT
SLEEVE THRU
EXTERIOR WALL
AND CAULK
SLEEVE FOUNDATION
WALL
COLD WATER SUPPLY
MIN. 2'-0" BELOW
FINISHED GRADE
MAIN SHUT-OFF
GATE VALVE
CW TO BLDG
3/4"
3/4" CW
TEE W/ PLUG
BALL VALVE
PRESSURE GAUGE
W/ 1/4" SHUT-OFF
CHECK
VALVE
BALL VALVE
BALL VALVE
CHECK VALVE
CHECK VALVE
CHECK VALVE
BALL VALVE
CHECK VALVE
CHECK VALVE BALL VALVE
BALL VALVE
BALL VALVEBALL VALVE
4" HOUSEKEEPING PAD
EXPANSION TANK,
REFER TO SCHEDULES FOR SIZEFLOOR DRAIN
FF
DRIP PAN
TEMPERATURE &
PRESSURE RELIEF
VALVE BLOWOFF PIPED
FULL SIZE TO FLOOR
DRAIN
GAS FIRED
WATER HEATER
DIRT LEG
GAS SHUT
OFF VALVE
GAS
SUPPLY
2" DIAL
THERMOMETER
3" CPVC INTAKE
AND EXHAUST
COLD WATER
SUPPLY
2" DIAL
THERMOMETER
140 °F HOT WATER
SUPPLY
HEAT TRAP
27" DROP (MIN.)
BALL
VALVE
TMV
2" DIAL
THERMOMETER
CIRCULATING PUMP
WIRE CIRCULATING
PUMP TO TIMER
(UNDER ELECTRICAL DIVISION)
PROGRAMMABLE
7 DAY TIMER
HOT WATER
TO FIXTURES.
HWR PIPING CAN ALSO BE
PIPED DIRECTLY TO WH THAT
HAS A HWR CONNECTION
COLD WATER
MIN 10'-0" FROM PARAPET, WALLS, AND STRUCTURE
CONCENTRIC VENT TERMINATION KIT
HWR
NC TMV
BYPASS
VALVE FOR
THERMAL
ERADICATION
OR CATCH BASIN
TO STORM DRAIN
CAST IRON BACKWATER VALVE
W/PVC FLAPPER AND O-RING
SEAL EQUAL TO ZURN-Z-1090
GRADE
10" DIAMETER CAST IRON COVER
MARKED 'BACKWATER VALVE',
EQUAL TO BROOKS 3-RT SERIES
PRECAST CONCRETE BODY
PROVIDE EXTENSIONS AS
REQUIRED
UNDERGROUND CONDESATE DRAIN
PIPING, SEE PLAN FOR SIZE
1/2" CD DRAIN
O U
T
LE
T S
ID
E
IN
T
A K
E S
ID
E
4" HOUSEKEEPING PAD
FLOOR SLAB
NOTES:
1. ALL PIPING SHALL BE HAND DRAWN SEAMLESS TYPE "K" OR "L" COPPER TUBING CONFORMING TO ASTM B-819.
2. FIELD ROUTE ALL CONDENSATE DRAINS TO NEAREST FLOOR DRAIN.
3. THIS DIAGRAM ONLY SHOWS INTENT AND FINAL INSTALLATION LOCATIONS MAY VARY.
ZERO
AIR-LOSS
VALVE
PRESSURE REGULATING VALVE
SET AT 80 PSIG WITH BYPASS LINE
MEDICAL AIR OIL-FREE SCROLL DUPLEX
COMPRESSOR, WITH INTEGRATED SINGLE STAGE AIR-
COOLED COMPRESSOR MOTORS, INLINE INLET AIR
FILTER, AIR RECIEVER, DESICCANT DRYERS, FILTER,
REGULATOR SYSTEM, AND CONTROL SYSTEM
HIGH-LOW PRESSURE SWITCH
MAIN SHUTOFF VALVE
MAIN PRESSURE GAUGE
PRESSURE GAUGE
MIN 24"
FULL LINE INTAKE WITH
GOOSENECK INLET WITH
MESH SCREEN OVER OPENING
PRE-FAB CURB
ROOF
REFER TO MANUFACTURER'S
INSTALLATION REQUIRMENTS
FOR INTAKE PIPE SIZING
2" MINIMUM AIR
GAP (SEE NOTE)
CAST IRON
FLOOR SINK
DRAIN (FS-1)DRAIN LINE
TO "P" TRAP
FINISHED FLOOR
REMOVABLE GRATE
SUPPORT PIPING
EVERY 4'-0"
INDIRECT WASTE
LINE
NOTE:
THE AIR GAP BETWEEN THE INDIRECT WASTE PIPEAND THE FLOOD LEVEL RIM OF THE WASTE RECEPTOR SHALL BE A
MINIMUM OF TWICE THE EFFECTIVEOPENING OF THE INDIRECT WASTE PIPE.
4' -0
FLOOR DRAIN
P-TRAP
TO
FLOOR DRAINS
BALL VALVE
3/4" COLD WATER
FINISH FLOOR
1/2" TYPE "K" SOFT SEAMLESS COPPER
WITH NO JOINTS BELOW FLOOR SLAB.
SLOPE AT 1/8" PER FOOT MINIMUM TO
FLOOR DRAIN CONNECTION.
120/1/60 ELECTRICAL
CONNECTION
ELECTRONIC TRAP PRIMING MANIFOLD SUITABLE FOR 4 TO 30
FLOOR DRAINS. COMPLETE WITH CIRCUIT BREAKER, TIMER,
BALL VALVE, SOLENOID VALVE & VACUUM BREAKER
COMPLETLY MOUNTED IN STEEL CABINET ENCLOSURE.
(PRECISION PLUMBING PRODUCTS PT-4 THRU PT-30)
SOLENOID VALVE
24-HOUR TIME CLOCK
WITH TEST AND
OVERRIDE BUTTONS.
VACUUM BREAKER
GALVANIZED STEEL
CABINET
CAP EXTRA
LINES IN WALL
PAVEMENTGRADE
CAST IRON CLEANOUT COLLAR
W/HEAVY DUTY COVER
PAVEMENT
18" SQ x 4" DEEP
CONC. PAD
CLEAN-OUT COVER
IN VEHICULAR
TRAFFIC AREAS
SHALL BE DUCTILE IRON
TWO-WAY
C.O. FTG.
1'-0"
PIPE HANGER (SEE
SPECIFICATIONS 22 05 11)
GALVANIZED SHEETMETAL
PIPE SADDLE W/FLARED ENDS
INSULATED PIPE
PIPE HANGER (SEE
SPECIFICATIONS 22 05 11)
VACUUM PUMP
NOTES:
1. PROVIDE ALL ITEMS INDICATED THAT ARE
NOT INCLUDED IN PACKAGED EQUIPMENT.
2. PROVIDE INERTIA BASE IF EQUIPMENT IS
NOT MOUNTED ON GROUND FLOOR.
MIN 24"
4" RAISE HOUSEKEEPING PAD
ASME GALVANIZED
RECEIVER
VACUUM PUMP
FLEXIBLE CONNECTION(TYP)
VACUUM GAUGE(TYP)
CONTROL PANEL IN
NEMA 12 CABINET
CHECK
VALVE (TYP)
EXHAUST MUFFLER
FULL LINE EXHAUST WITH
GOOSENECK DISCHARGE WITH
MESH SCREEN OVER OPENING
PRE-FAB CURB
TANK DRAIN LINE
WITH VALVE
DRIP LEG, PIPE
TO FLOOR DRAIN
FROM LAB
ROOF
NEOPRENE VIBRATION PAD EQUAL
TO MASON MODEL WM (TYP. OF 4)
SECURE PUMP FRAME AND
ISOLATION PAD TO CONCRETE SLAB
FLOOR DRAIN
BALL VALVE
(TYP)
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
FULLY SPRINKLERED
B
IM
/0
B a y P in e s V
A D e n ta l C lin ic
/0
B a y P in e s V
A D e n ta l C lin ic
R
D iv
.r v t
/2
/2
:4
:3
A
M
PY501
PLUMBING DETAILS CONSTRUCT DENTAL CLINIC
BAY PINES VAMC
516-349
AMBER MILTON
02/03/2023 ADL AJZ
MICHAEL R. KNOTT, P.E.
FL License #91858
100% CONSTRUCTION SET
N.T.S.
DOMESTIC WATER SERVICE ENTRY DETAIL
N.T.S.
GAS FIRED WATER HEATER DETAIL
N.T.S.
BACKWATER VALVE
3N.T.S.
COMPRESSED AIR SCHEMATIC DETAIL
N.T.S.
CONDENSATE FLOOR DRAIN DETAIL
N.T.S.
ELECTRONIC TRAP PRIMER
N.T.S.
EXTERIOR CLEAN OUT (TWO WAY) DETAIL
N.T.S.
INSULATED PIPE HANGAR DETAIL
N.T.S.
LAB VACUUM PUMP
Revisions Date
M C
H
A
O T
T
P R
O F
E S
S
IO N A L EN
G I N
E E
R
LICENSE
F
LO R I D A
STATE OF
No. 91858
I
E L
R K
DETAIL NOTES:
A.
B.
C.
REFER TO FLOOR PLANS FOR ANY DEVIATIONS TO PIPING LAYOUT SHOWN.
EXTEND PIPING AS REQUIRED WITHIN CASEWORK TO SINK. PROVIDE PROPER
PIPE SUPPORTS.
INSTALL PIPING TO MAXIMIZE SPACE AVAILABLE BELOW SINK.
SAN
S A
N
FINISHED
FLOOR
REFER TO FLOOR PLANS FOR PIPE
SIZES AND ADDITIONAL INFORMATION.
FAUCET
SINK
SAN PIPING
S A
N
WALL/CHASE
BEHIND SINK
T
TEMPERING
VALVE TMV-2
SPOUT BRACE
SPOUT WITH HOSE
END & PAILHOOK
3" DIA. P-TRAP
36"
DRAIN
ROUGH CHROME PLATED
SERVICE FAUCET WITH
VACUUM BREAKER
H C
VARIES
30'' HOSE
HOSE BRACKET
4" x 3" x 4"
WELD TO 5"
EXTRA HEAVY RISER
CLAMP-BOLT TO 4"L
LEG AGAINST WALL
PIPE
"Ø BOLTS
FINISHED FLOOR
FOR FIXTURE HEIGHT
SEE ARCHITECTURAL
DRAWINGS
1" [25mm] STOP
[56mm]
2 1/4"
[69mm]
2 3/4"
[119mm]
4 3/4"
[2 m m
/2
[6 3m m
1/
2"
NOTE:
FURNISH 24 VOLT TRANSFORMER
C/L OF FIXTURE
FINISHED WALL
MANUAL OVER-RIDE
BUTTON
SENSOR
ELECTRICAL BOXES
[4 m m
[200mm]
8"
[8 m m
F
O R
F
IX
T U
R E
H E
IG
H
T S
S E
E
A R
C H
IT
E
C T
U R
A L
D R
A W
IN
G
S
FAUCET SEE SPECIFICATIONS
NOTE:
PROVIDE COVER FOR EXPOSED PIPING
OFFSET WASTE
LAMINAR FLOW
CONTROL DEVICE
LOOSE KEY STOP
ESCUTCHEON
FINISHED FLOOR
TRAP PARALLEL TO WALL
[2 m m
/4
NOTE:
1. PROVIDE 20 GAGE STUDS WHEN HEIGHT EXCEEDS
12'-0" [3600mm]
[9 m m
T
O F
LO
O
R
3' -3
PLAN
1/4" [6mm]∅ MOLLY BOLT HOLLOW
WALL ANCHOR (1 EA. SIDE OF LAV)
FOR FIXTURE HEIGHT SEE
ARCHITECTURA DRAWINGS
V A
R
IE
S
MINIMUM 16 GAGE GALVANIZED
STEEL PLATE 12"x48" [300x1200mm]
MIN. SECURED TO A MIN. 4 STUDS
PER LAVATORY
MIN. 5 1/4" [131mm]∅
GALV. MACHINE BOLTS
WELDED TO PLATE
MIN. (3) 1/4" [6mm]
MACHINE BOLTS
W/DOUBLE LOCK
NUTS ON BACK SIDE
A
STEEL HANGER
BY LAV MFGR
SECTION A
STEEL WALL
PLATE
WALL ANCHOR
STUDS
TYP. 1/8"
TYP. [3mm]
1/4"
[6mm]
POLISHED BRONCE TOP
CONCRETE SLAB
PROVIDE ADJUSTABLE FLOOR CLEANOUT,
CAST IRON BODY WITH GAS & WATER
TIGHT ABS TAPERED THREAD PLUG &
ROUND SECURED TOP FOR ADJUSTMENT
SLIP JOINT
SAME SIZE AS SEWER
SHORT SWEEP
ELBOW
NOTE: SECURE CLEANOUT COVER WITH SCREWS
3/4" SUPPLY
3/4" CHROMIUM PLATED
W/ VANDAL PROOF
VACUUM BEAKER
METAL WHEEL OR LOOSE
KEY TYPE HANDLE-SEE
PIPING SCHEDULE FOR
MOUNTING HGT &
HANDLE TYPE
3/4" FLANGED FEMALE INLET
HB & 3/4" HOSE THREAD ON
OUTLET, CHROME PLATED
W/ VACUUM BREAKER
TEST TEE
THREADED
CLEANOUT PLUG ACCESS COVER AND FRAME
FINISHED WALL SURFACE
RECESSED ALARM PANEL (AP) WITH
CONTINUOUS DIGITAL DISPLAY OF ALL
MEDICAL GASES AND VACUUM
PROVIDE ZONE
IDENTIFICATION SIGN
120V/1Ø POWER SUPPLY BY
ELECTRICAL
CONTRACTOR,COORDINATE
EXACT LOCATION BEFORE
CONSTRUCTION
SIGNAL WIRING
IN CONDUIT
FROM PRESSURE
SWITCHES
MEDICAL GAS MAINS
MEDICAL GAS ZONE PIPING
DOWN IN WALL,SEE PLANS
FOR EXACT SIZE AND
LOCATION
RECESSED MEDICAL GAS ZONE VALVE BOX (MGV) WITH
SHUT-OFF VALVES, PRESSURE/VACUUM GAUGES,
PRESSURE AND VACUUM SWITCHES, AND REMOVABLE
WINDOW WITH PULL RING. MOUNT TOP OF BOX 66" AFF.
CONNECT TO CAPPED PIPE
EXTENSION (TYPICAL)
CONDUIT WITH SIGNAL WIRING FROM PRESSURE/VACUUM
SWITCH TO AREA ALARM PANEL (AP) BY ELECTRICAL
CONTRACTOR, COORDINATE EXACT LOCATION BEFORE
CONSTRUCTION.
PRESSURE/VACUUM
SWITCH (TYPICAL)
PROVIDE UNIVERSAL QUICK-CONNECT
FITTING FOR IN-LINE PRESSURE/
VACUUM SWITCH (TYPICAL)
PROVIDE LOCKABLE
SHUTOFF VALVES.
LOCK VALVES IN THE
OPEN POSITION (TYP)
STRUCTURAL STEEL
MEMBER
FINISHED
FLOOR
FULL SIZE 6" LONG
DIRT LEG WITH CAP
SEE PLANS FOR
PIPE SIZES
FOR PRV INDOORS PROVIDE VENT
PIPING THRU ROOF, TERMINATE WITH
GOOSENECK AT 1'-0" ABOVE AND PLACE
AN INSECT SCREEN OVER OPENING
DOWNSTREAM
CONTROL LINE
GAS PRESSURE REGULATOR. REFER
TO FLOOR PLANS FOR SET POINT
GAS MAIN
APPROVED GAS BALL VALVE
GAS FIRED
EQUIPMENT
UNION
APPROVED GAS BALL VALVE FOR
INDIVIDUAL EQUIPMENT SHUTDOWN
TEST TEE
AT LEAST 10 PIPE DIAMETERS
STRUCTURAL STEEL
MEMBER
SEE PLANS FOR
PIPE SIZES
FOR PRV INDOORS PROVIDE VENT
PIPING THRU ROOF, TERMINATE WITH
GOOSENECK AT 1'-0" ABOVE AND PLACE
AN INSECT SCREEN OVER OPENING
DOWNSTREAM
CONTROL LINE
GAS PRESSURE REGULATOR. REFER
TO FLOOR PLANS FOR SET POINT
2 PSI GAS MAIN
APPROVED GAS BALL VALVE
TEST TEE
AT LEAST 10 PIPE DIAMETERS
CONTINUED LOW
PRESSURE GAS
PIPING TO
OUTLETS
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
FULLY SPRINKLERED
B
IM
/0
B a y P in e s V
A D e n ta l C lin ic
/0
B a y P in e s V
A D e n ta l C lin ic
R
D iv
.r v t
/2
/2
:4
:3
A
M
PY502
PLUMBING DETAILS CONSTRUCT DENTAL CLINIC
BAY PINES VAMC
516-349
AMBER MILTON
02/03/2023 ADL AJZ
MICHAEL R. KNOTT, P.E.
FL License #91858
100% CONSTRUCTION SET
N.T.S.
MIXING VALVE UNDER SINK DETAIL
N.T.S.
MOP SINK DETAIL
N.T.S.
PIPE ANCHOR TO VERTICAL DETAIL
N.T.S.
WATER CLOSET P-103 DETAIL - SENSOR OPERATED
N.T.S.
TYPICAL WHEELCHAIR LAVATORY DETAIL
N.T.S.
LAVATORY MOUNTING DETAIL
N.T.S.
FLOOR CLEANOUT (FCO) DETAIL
N.T.S.
HOSE BIBB DETAIL
N.T.S.
WALL CLEANOUT
N.T.S.
MEDICAL GAS ZONE VALVE / ALARM PANEL DETAIL
N.T.S.
GAS EQUIPMENT CONNECTION DETAIL
6N.T.S.
GAS PRV STATION DETAIL
Revisions Date
M C
H
A
O T
T
P R
O F
E S
S
IO N A L EN
G I N
E E
R
LICENSE
F
LO R I D A
STATE OF
No. 91858
I
E L
R K
DETAIL NOTES:
A.
B.
C.
PROVIDE FINAL CONNECTION TO
GENERATOR. FLEX CONNECTOR
TO BE FURNISHED BY DIVISION
26 PROVIDE REDUCER AFTER VALVE
IF REQUIRED.
2' -6
1'
-6
M
IN
IM
U
M
ANODELESS RISER ASSEMBLY
MATCH PIPE SIZE AND BURIAL DEPTH
GRADE
TRACER WIRE
GAS VALVE. PROVIDE TEMPORARY
PLUG UNTIL FINAL CONNECTION
IS MADE.
POLYETHYLENE GAS SERVICE.
PIPING MUST BE MARKED PER ASTM D2513.
PROVIDE AN ANODELESS RISER AT EACH LOCATION WHERE THE GAS PIPING
PENETRATES THE SURFACE. EXTEND TRACER TO THE SURFACE AT EACH RISER.
COORDINATE PIPE AND CONDUIT ROUTING TO MINIMIZE TRENCHING.
PAINT ALL EXTERIOR GAS PIPING WITH ONE(1) PRIMER AND TWO(2) FINISH
COATS OF COLOR SELECTED, AS SPECIFIED.
EMERGENCY GENERATOR
TRACER WIRE - 10 AWG, SOLID, THHN
BLACK INSULATION, COIL APPROX. 1'-0"
AT EACH END. WIRE SHALL BE
CONTINUOUS, SOLDERED OR CRIMPED
JOINTS ONLY, WIRE NUTS ARE NOT
ALLOWED. DEDICATED TRACER WIRE
IS NOT REQUIRED IF IT IS PROVIDED
AS PART OF LOCATOR TAPE.
COORDINATE GAS RISER LOCATION
WITH GAS CONNECTION ON
GENERATOR.
VERIFY LOCATION WITH DIVISION 26.
LOCATOR TAPE - YELLOW PLASTIC, WITH
LETTERING: "CAUTION, BURIED GAS LINE BELOW"
6" WIDE x 4 MILS THICK, IF TRACER WIRE
IS PROVIDED WITH TAPE TERMINATE
ABOVEGROUND AS SHOWN IN DETAIL.
TRACER SHALL BE 10 AWG STRANDED,
COATED,
PVC SLEEVE, SCHEDULE 40, 1'-6" LONG
(MINIMUM)DIAMETER SIZED TO FIT OVER
RISER
6"
6"
DIRT LEG
SLOPE
INSULATE UNDERSIDE ROOF
SUMP & HORIZONTAL RAIN
LEADERS
INSULATION
PIPE SUPPORT (TYP)
ROOF DRAIN
ROOF DECK
ZURN #Z-199 DOWNSPOUT NOZZLE
SECONDARY STORM PIPING, SEE FLOOR
PLANS FOR SIZE AND LOCATIONS
EXTERIOR WALL
FINISHED FLOOR
18"-24"MAX
SPLASH BLOCK
EXAMPLES OF ACCEPTABLE FITTINGS EXAMPLES OF UNACCEPTABLE FITTINGS
ACCEPTABLE WAY TO CONNECT
MAIN DENTAL VACUUM LINES
ACCEPTABLE WAY TO CONNECT A BRANCH
TO A MAIN DENTAL VACUUM LINE
ACCEPTABLE WAY TO RISE TO
FINAL OUTLET/CHAIR CONNECTION
ACCEPTABLE WAY TO RISE MAIN DENTAL
VACUUM PIPE TO DENTAL VACUUM PUMP
CANOPY. REFER TO
ARCHITECTURAL PLANS
FOR DETAIL ON CANOPY.
EXTEND PIPING TO BELOW
FINISHED FLOOR AND
CONNECT TO THE STORM MAIN.
PROVIDE A WALL CLEANOUT IN
AN ACCESSIBLE LOCATION
ABOVE FINISHED FLOOR.
STRUCTURAL ELEMENT. COORDINATE SCUPPER
DRAIN INSTALLATION SO THAT PIPING IS ABOVE
STRUCTURAL. IF DESIGN BASIS DRAIN IS NOT
SELECTED, COORDINATE INSTALLATION AND
FIELD VERIFY THAT DRAIN AND PIPING WILL NOT
CONFLICT WITH STRUCTURAL ELEMENT.
COORDINATE DRAIN INSTALLATION TO
PROVIDE ROOM FOR DRAIN BODY TO
ENSURE THAT DRAIN BODY WILL NOT
CONFLICT WITH STRUCTURAL ELEMENT.
SCUPPER DRAIN. DESIGN
BASIS WATTS RD-270-6
EXTERIOR WALL. REFER TO
ARCHITECTURAL PLANS.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
FULLY SPRINKLERED
B
IM
/0
B a y P in e s V
A D e n ta l C lin ic
/0
B a y P in e s V
A D e n ta l C lin ic
R
D iv
.r v t
/2
/2
:4
:4
A
M
PY503
PLUMBING DETAILS CONSTRUCT DENTAL CLINIC
BAY PINES VAMC
516-349
AMBER MILTON
02/03/2023 ADL AJZ
MICHAEL R. KNOTT, P.E.
FL License #91858
100% CONSTRUCTION SET
N.T.S.
GENERATOR, EXTERIOR - NATURAL GAS PIPING DETAIL
N.T.S.
ROOF DRAIN - INSULATED
N.T.S.
OVERFLOW NOZZLE DETAIL
N.T.S.
DENTAL PIPING DETAILS
N.T.S.
SCUPPER ROOF DRAIN DETAIL
Revisions Date
M C
H
A
O T
T
P R
O F
E S
S
IO N A L EN
G I N
E E
R
LICENSE
F
LO R I D A
STATE OF
No. 91858
I
E L
R K
4" FCO
4" FCO
4" FCO
4" TWO-WAY ECO
4" FCO
4" FCO
2" FCO
P-608
P-413
P-413
P-413
P-413
P-413
P-413
P-413
P-413
P-413
P-413
P-413
P-413
P-413
P-413
P-414
P-414
P-418
P-103
P-103
P-418
P-413
P-413
P-413
P-413
P-413
P-413
P-413
P-413
P-413
P-413
P-413
P-413
P-413
P-413
P-413
P-413
P-103
P-418
P-528
P-414
P-502
WCO
P-103
P-418
P-418
P-514
P-514
P-520
P-520
P-520
P-520
4" FD-M
4" VTR
4" VTR
4" VTR
2" V. REFER TO
PY602 FOR
CONTINUATION.
2" V. REFER TO
PY602 FOR
CONTINUATION.
2" V. REFER TO
PY602 FOR
CONTINUATION.
4" SAN
2" SAN
2" SAN
2" SAN
2" SAN
2" SAN
2" SAN
2" SAN
2" SAN
2" SAN
4" SAN
4" SAN
4" SAN
4" SAN
4" SAN
4" SAN
4" SAN
4" SAN
4" SAN
4" SAN
2" SAN
4" SAN
4" SAN
2" SAN
2" SAN
3" SAN
2" SAN
4" SAN
4" SAN
2" SAN
2" SAN
2" SAN
4" SAN
4" SAN
4" SAN
2" SAN
2" SAN
2" SAN
2" SAN
2" SAN
2" SAN
2" V
1 1/2" V
3" V
1 1/2" V
1 1/2" V
1 1/2" V
1 1/2" V
3" V
3" V
3" V
1 1/2" V
3" V 1 1/2" V
2" V
2" V
1 1/2" V
1 1/2" V
2" V
2" V
1 1/2" V
1 1/2" V
1 1/2" V
2" V
3" V
2" V
1 1/2" V
1 1/2" V
1 1/2" V
1 1/2" V
1 1/2" V
1 1/2" V
2" V
1 1/2" V
1 1/2" V
1 1/2" V
1 1/2" V
1 1/2" V
1 1/2" V
2" V
1 1/2" V
1 1/2" V
2" V
3" V
3" V
3" V
3" V
2" V
2" V
1 1/2" V
2" V
2" V
3" V
1 1/2" V
2" V
2" V
2" V
2" V
2" V
1 1/2" V
2" V
2" V
2" V
2" V
4" SAN
3" SAN
2" V 2" V
4" FD-W
3" FD-B
2" SAN
2" SAN
WCO
P-103
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
FULLY SPRINKLERED
B
IM
/0
B a y P in e s V
A D e n ta l C lin ic
/0
B a y P in e s V
A D e n ta l C lin ic
R
D iv
.r v t
/2
/2
:4
:4
A
M
PY601
PLUMBING GRAVITY ISOMETRICS CONSTRUCT DENTAL CLINIC
BAY PINES VAMC
516-349
AMBER MILTON
02/03/2023 ADL AJZ
MICHAEL R. KNOTT, P.E.
FL License #91858
100% CONSTRUCTION SET
DRAWING NOTES:
1. ISOMETRICS ARE PROVIDED FOR REFERENCE ONLY. REFER TO FLOOR PLANS FOR MORE
INFORMATION.
N.T.S.PY601
1 PLUMBING GRAVITY ISOMETRIC
Revisions Date
M C
H
A
O T
T
P R
O F
E S
S
IO N A L EN
G I N
E E
R
LICENSE
F
LO R I D A
STATE OF
No. 91858
I
E L
R K
WCO
WCO
WCO
WCO
BACKWATER VALVE
6" FCO
BACKWATER VALVE
6" FCO
6" FCO
4" RD-A
85.9 GPM
3" RD-A
26.7 GPM
3" RD-A
37.5 GPM
4" RD-A
86.2 GPM
4" RD-A
73.5 GPM
4" RD-A
74.7 GPM
4" RD-A
64.6 GPM
4" RD-A
68.4 GPM
3" STO
37.5 GPM
4" STO
64.2 GPM
6" STO
236.3 GPM
6" STO
172.1 GPM
4" STO
85.9 GPM
4" STO
86.2 GPM
DOWNSPOUT
DOWNSPOUT
3" ST
37.5 GPM
4" ST
64.2 GPM
6" ST
266.8 GPM
4" ST
85.9 GPM
4" ST
74.7 GPM
6" ST
317.4 GPM
4" ST
84.2 GPM
4" ST
68.4 GPM
4" ST
64.6 GPM
4" STO
74.7 GPM
6" STO
148.2 GPM
4" STO
68.4 GPM
6" STO
133 GPM
6" STO
281.2 GPM
2" V
2" V
2" V
4" CD
4" CD
4" CD
2" V. REFER TO
PY601 FOR
CONTINUATION
2" V. REFER TO
PY601 FOR
CONTINUATION
2" V. REFER TO
PY601 FOR
CONTINUATION
4" FD-B
4" FD-B
4" FD-B
2" ST
15.9 GPM
2" RD-B
15.9 GPM
2" RD-B
11.2 GPM
2" RD-B
9.3 GPM
4" FCO
2" RD-B
9.6 GPM
2" RD-B
9.6 GPM
2" RD-B
11.4 GPM
WCO
WCO
WCO
WCO
WCO
WCO
WCO
4" ST
86.2 GPM
2" ST
30.6 GPM
6" ST
116.8 GPM
2" ST
11.4 GPM
6" ST
2" ST
20.5 GPM
2" ST
11.2 GPM
4" ST
20.4 GPM
4" ST
95.1 GPM
6" ST
222.3 GPM
2" ST
21.0 GPM
2" ST
9.6 GPM
6" ST
148.8 GPM
4" ST
73.5 GPM
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
FULLY SPRINKLERED
B
IM
/0
B a y P in e s V
A D e n ta l C lin ic
/0
B a y P in e s V
A D e n ta l C lin ic
R
D iv
.r v t
/2
/2
:4
:4
A
M
PY602
PLUMBING STORM ISOMETRICS CONSTRUCT DENTAL CLINIC
BAY PINES VAMC
516-349
AMBER MILTON
02/03/2023 ADL AJZ
MICHAEL R. KNOTT, P.E.
FL License #91858
100% CONSTRUCTION SET
DRAWING NOTES:
1. ISOMETRICS ARE PROVIDED FOR REFERENCE ONLY. REFER TO FLOOR PLANS FOR MORE
INFORMATION.
N.T.S.PY602
1 PLUMBING STORM ISOMETRIC
Revisions Date
M C
H
A
O T
T
P R
O F
E S
S
IO N A L EN
G I N
E E
R
LICENSE
F
LO R I D A
STATE OF
No. 91858
I
E L
R K
P-413
P-413
P-413
P-413
P-413
P-413
P-413
P-413
P-413
P-502
P-413
P-413 P-413
P-413 P-413
P-413 P-413
P-413
P-413
P-413 P-413
P-413
P-413
P-413
P-103
P-418
P-103 P-418
P-608
P-414
P-414
P-103
P-418
P-528
P-520 P-708
P-520
P-520 P-708
P-520
P-103
P-103
P-418
P-514 P-708
GWH-1
ET-1
TP-1
TP-2
P-801
CP-1
TMV-1
P-804
BALANCING VALVE
2 1/2" CW
2" CW
2" CW
1 1/2" CW
1 1/4" CW
1 1/4" CW 1/2" CW
1/2" CW
3/4" HW
3/4" HW 3/4" CW
3/4" HW
3/4" HW 3/4" CW
3/4" HW
3/4" HW 3/4" CW
3/4" HW
3/4" HW 3/4" CW
3/4" HW
3/4" HW 3/4" CW
1" HW
1" HW
3/4" CW
1" HW
1" HW
3/4" CW
1" HW
1" HW
1 1/4" CW
1/2" CW
1" HW
1" HW
1/2" CW
1" HW
1" HW
3/4" HW
3/4" CW
1/2" CW
1 1/4" HW
1 1/4" HW
1 1/4" HW
1 1/4" HW
3/4" CW
1/2" CW
3/4" HW
1 1/2" CW
3/4" HWR
BALANCING VALVE
3/4" HWR
3/4" HWR
1 1/4" HW
1 1/4" HW
1" HWR
1 1/4" HWR
1 1/2" HW
3/4" HWR
1" HW
3/4" HWR
2" CW
1/2" CW
1/2" HW
2" CW
1 1/2" CW
1 1/2" CW
1/2" CW
1/2" CW
1 1/4" CW
1/2" CW
1 1/4" CW
3/4" HW
3/4" HW
3/4" HW
3/4" HW
1/2" CW 3/4" HW
3/4" HW
1/2" CW
3/4" CW
3/4" HW
3/4" HW
3/4" HW
3/4" HW
3/4" CW
3/4" CW
1" HW
1" HW
3/4" CW
1" HW
1" HW
3/4" CW
1" HW
1" HW
1" HW
1" HW
1/2" CW
3/4" HW
3/4" HW
3/4" HW
3/4" HW
1/2" CW
3/4" HW
1/2" CW
3/4" HW
3/4" HW
3/4" CW
2 1/2" CW
1 1/2" CW
1 1/2" CW
1 1/2" CW
3/4" CW
1 1/2" CW
3/4" HW
3/4" HW
1/2" CW
P-514 P-708
1/2" HW
1/2" CW
P-414
P-413
P-413
P-413
P-413
P-413
P-413
P-413
CAP 2" CW, 1" HW, & 3/4"
HWR FOR FUTURE
EXPANSION CONNECTIONS.
2" CW
1" HW
3/4" HWR
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
FULLY SPRINKLERED
B
IM
/0
B a y P in e s V
A D e n ta l C lin ic
/0
B a y P in e s V
A D e n ta l C lin ic
R
D iv
.r v t
/2
/2
:4
:4
A
M
PY603
PLUMBING PRESSURE
ISOMETRICS
CONSTRUCT DENTAL CLINIC
BAY PINES VAMC
516-349
AMBER MILTON
02/03/2023 ADL AJZ
MICHAEL R. KNOTT, P.E.
FL License #91858
100% CONSTRUCTION SET
DRAWING NOTES:
1. ISOMETRICS ARE PROVIDED FOR REFERENCE ONLY. REFER TO FLOOR PLANS FOR MORE
INFORMATION.
N.T.S.PY603
1 PLUMBING PRESSURE ISOMETRIC
Revisions Date
M C
H
A
O T
T
P R
O F
E S
S
IO N A L EN
G I N
E E
R
LICENSE
F
LO R I D A
STATE OF
No. 91858
I
E L
R K
ZVB-2
(2)AREA ALARM PANELS
ZVB-1
AC-1
VP-1
AMALGAM
SEPERATOR
1" MV
1 1/4" DA
1" MV
1" DA
CAP 1" DA & MV FOR
CONNECTION TO
FUTURE EXPANSION
3/4" MV1" DA
3/4" MV
1" DA
3/4" MV
1" DA
3/4" DA U/G
1/2" DA U/G
1/2" DA U/G
1/2" DA U/G
1" DV U/G
(TYP ALL TREATMENT ROOMS)
1/2" DA U/G
GO-2
GO-3
GO-2
GO-3
GO-2
GO-3 GO-2
GO-3
GO-4
GO-4
1" DA
1" DA U/G
3/4" DA U/G
1/2" DA U/G
3/4" DA U/G
1" DV U/G
1" DV U/G
1/2" DA U/G
(TYP ALL TREATMENT ROOMS)
(TYP ALL SURGERY ROOMS)
3/4" MV
3/4" MV
3/4" MV
3/4" MV
3/4" MV U/G
3" DV U/G
3" DV U/G
2" DV U/G
1 1/2" DV U/G
1 1/2" DV U/G
1 1/2" DV U/G
1 1/2" DV U/G
3/4" DA U/G
2" DV U/G
1 1/2" DV U/G
1 1/2" DV U/G
VP-3
VP-2
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
FULLY SPRINKLERED
B
IM
/0
B a y P in e s V
A D e n ta l C lin ic
/0
B a y P in e s V
A D e n ta l C lin ic
R
D iv
.r v t
/2
/2
:4
:5
A
M
PY604
PLUMBING MED GAS ISOMETRICS CONSTRUCT DENTAL CLINIC
BAY PINES VAMC
516-349
AMBER MILTON
02/03/2023 ADL AJZ
MICHAEL R. KNOTT, P.E.
FL License #91858
100% CONSTRUCTION SET
CODED NOTES:
1/2" DA & 1" DV UP TO FLOOR MOUNTED UTILITY CENTER.
3/4" DA & 1" DV UP TO FLOOR MOUNTED UTILITY CENTER.
OPTIONAL DV FLOOR CLEAN OUT LOCATION. COORDINATE WITH VA IS CLEANOUT IS DESIRED. CAP
PIPING BFF IF NO CLEANOUT IS PROVIDED.
DRAWING NOTES:
1. ISOMETRICS ARE PROVIDED FOR REFERENCE ONLY. REFER TO FLOOR PLANS FOR MORE
INFORMATION.
2. COORDINATE INSTALLATION OF ALL DENTAL AIR, MEDICAL VAC, AND DENTAL VAC EQUIPMENT AND
PIPING WITH MANUFACTUER'S RECOMMENDATIONS.
3. COORDINATE LOCATION OF INTAKE FOR AIR COMPRESSORS WITH ALL VTR, VACUUM PUMP EXHAUST, WATER HEATER CONCENTRIC VENT, MECHANICAL INTAKES, AND MECHANICAL EXHAUST. INTAKES
SHALL MAINTAIN A 25'-0" CLEARANCE FROM EXHAUST.
N.T.S.PY604
1 PLUMBING MED GAS ISOMETRIC
3" DENTAL VACUUM
PUMP EXHAUST
2" MEDICAL VACUUM
PUMP EXHAUST
4" DENTAL AIR
COMPRESSOR INTAKE
Revisions Date
M C
H
A
O T
T
P R
O F
E S
S
IO N A L EN
G I N
E E
R
LICENSE
F
LO R I D A
STATE OF
No. 91858
I
E L
R K
1 1/2" G
2000 MBH
1 1/2" G
2941.8 MBH
1 1/2" G
941.8 MBH
GAS SHUTOFF VALVE
GWH-1
B-1 & B-2
1" G
100 MBH
1 1/4" G
511.8 MBH
3/4" G
120 MBH
GO-1
GO-1
GO-1
GO-1
GO-1
GO-1
GO-1
GO-1
GO-1 GO-1
3/4" G
10 MBH
3/4" G
20 MBH
3/4" G
30 MBH
3/4" G
10 MBH
(TYP ALL TREATMENT ROOMS)
3/4" G
40 MBH
3/4" G
50 MBH
3/4" G
60 MBH
3/4" G
70 MBH
1" G
80 MBH
1" G
100 MBH
3/4" G
20 MBH
1" G
100 MBH
3/4" G
10 MBH
GO-1
GO-1
GO-1
GO-1
GO-1
GO-1
GO-1
GO-1
GO-1
GO-1
GO-1
3/4" G
20 MBH
3/4" G
30 MBH
3/4" G
40 MBH
3/4" G
50 MBH
3/4" G
60 MBH
3/4" G
70 MBH
1" G
110 MBH
3/4" G
40 MBH
1" G
210 MBH
1 1/4" G
330 MBH
1 1/4" G
841.8 MBH
CAP 1" G PIPING FOR FUTURE
EXPANSION CONNECTION.
ESTIMATED LOAD OF 100 MBH.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
FULLY SPRINKLERED
B
IM
/0
B a y P in e s V
A D e n ta l C lin ic
/0
B a y P in e s V
A D e n ta l C lin ic
R
D iv
.r v t
/2
/2
:4
:5
A
M
PY605
PLUMBING NATURAL GAS
ISOMETRICS
CONSTRUCT DENTAL CLINIC
BAY PINES VAMC
516-349
AMBER MILTON
02/03/2023 ADL AJZ
MICHAEL R. KNOTT, P.E.
FL License #91858
100% CONSTRUCTION SET
CODED NOTES:
GAS METER WITH PRV. COORDINATE INSTALLATION OF GAS METER WITH TECO. COORDINATE
INSTALLATION OF A PRV AND A SHUTOFF VALVE BEFORE THE GAS METER WITH TECO. COORDINATE PRV TO BE SET TO 2 PSI. AFTER THE METER, PROVIDE TWO GAS SUPPLY PIPES. ONE GAS SUPPLY TO BUILDING. THE SECOND GAS SUPPLY TO THE EMERGENCY GENERATOR. PROVIDE EACH SUPPLY LINE WITH A GAS SHUTOFF VALVE. REFER TO NFPA 110 SECTION 7.9.7 & 7.9.8 FOR MORE INFORMATION ON THE GAS SHUTOFF VALVE LABELING. COORDINATE INCOMING PIPE SIZE WITH CIVIL CONTRACTOR.
1 1/2" G LINE FOR EMERGENCY GENERATOR. PROVIDE A SHUTOFF VALVE AND A PRV SET AT 10" WC
BEFORE CONNECTION TO GENERATOR. PROVIDE A DOUBLE SHUTOFF VALVE WITH ELECTRICAL
PROOF OF CLOSURE PER NFPA 85. INTERLOCK WITH THE GENERATOR.
SET PRV TO 12" WC. REFER TO DETAIL 12/PY502 FOR VENTING REQUIRMENTS.
PROVIDE A 24V SOLENOID VALVE. INTERLOCK WITH EMERGENCY PUSH BUTTON (EPO) AND FIRE ALARM SYSTEM. COORDINATE EPO LOCATION WITH ELECTRICAL CONTRACTOR AND VA. EPO TO BE
PROVIDED BY ELECTRICAL CONTRACTOR. COORDINATE ALL WIRING WITH ELECTRICAL
CONTRACTOR.
DRAWING NOTES:
1. ISOMETRICS ARE PROVIDED FOR REFERENCE ONLY. REFER TO FLOOR PLANS FOR MORE
INFORMATION.
2. FOR NATURAL GAS PIPING OVER 2 PSI INSIDE THE BUILDING, NATURAL GAS CALCULATIONS ARE BASED ON THE 2021 NFPA 54 TABLE 6.2.1(e), SCHEDULE 40 METALLIC PIPE WITH AN INLET PRESSURE
2.0 PSI WITH AN ALLOWABLE PRESSURE DROP OF 1 PSI. MAX CAPACITY OF 2941.8 MBH AND A MAX
LENGTH OF 143 FT.
3. FOR NATURAL GAS PIPING OVER 2 PSI TO THE GENERATOR, NATURAL GAS CALCULATIONS ARE BASED ON THE 2021 NFPA 54 TABLE 6.2.1(v), POLYETHLENE PLASTIC PIPE WITH AN INLET PRESSURE
2.0 PSI WITH AN ALLOWABLE PRESSURE DROP OF 1 PSI. MAX CAPACITY OF 2941.8 MBH AND A MAX
LENGTH OF 63 FT.
4. FOR NATURAL GAS PIPING UNDER 2 PSI, NATURAL GAS CALCULATIONS ARE BASED ON THE 2021 NFPA 54 TABLE 6.2.1(b),SCHEDULE 40 METALLIC PIPE WITH AN INLET PRESSURE LESS THAN 2.0 PSI WITH AN ALLOWABLE PRESSURE DROP OF 0.5" W.C. MAX CAPACITY OF 110 MBH AND A MAX LENGTH
OF 154 FT.
N.T.S.PY605
1 PLUMBING NATURAL GAS ISOMETRIC
Revisions Date
M C
H
A
O T
T
P R
O F
E S
S
IO N A L EN
G I N
E E
R
LICENSE
F
LO R I D A
STATE OF
No. 91858
I
E L
R K
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10 www.abovegroupinc.com COA/CA Lic. No. 31120
305 East Dr., Suite H, Melbourne, Florida 32904
PH: 321.345.9026
FULLY SPRINKLERED
B
IM
/0
B a y P in e s V
A D e n ta l C lin ic
/0
B a y P in e s V
A D e n ta l C lin ic
R
D iv
.r v t
/2
/2
:4
:5
A
M
PY801
PLUMBING SCHEDULES CONSTRUCT DENTAL CLINIC
BAY PINES VAMC
516-349
AMBER MILTON
02/03/2023 ADL AJZ
MICHAEL R. KNOTT, P.E.
FL License #91858
100% CONSTRUCTION SET
GAS WATER HEATER SCHEDULE
MARK MANUFACTURER MODEL NO. GAS CONNECTION BTUH THERMAL EFFICIENCY
RECOVERY (GPH)
@90°F STORAGE (GALLONS) STORAGE TEMP (°F) SIZE (D"xH") VOLTS/PHASE/HERTZ OPERATING WEIGHT (LBS)
GWH-1 AO SMITH BTH-120 3/4" 120,000 95% 197 60 140 27-3/4" x 55-1/2" 120/1/60 961
THERMOSTATIC MIXING VALVE SCHEDULE
LOCATION MANUFACTURER MODEL NO. OUTLET/TEMPERATURE INLET/OUTLET SIZE MIN. FLOW RATE LOCATION NOTES
TMV-1 BRADLEY S59-3045 130°F 3/4" / 1" 1.5 MASTER @ WATER HEATER 1,2
TMV-2 WATTS LFUSG-B 110°F 1/2" / 1/2" 0.25 @ HAND SINKS/LAVS 1,2
TMV-3 BRADLEY S59-4016 110°F 3/4" / 3/4" 0.5 @ PLUMBING FIXTURES 1,2
TMV-4 BRADLEY S19-2010 110°F / 85°F 1/2" / 1/2" 0.2 / 1.5 @ HAND SINKS WITH EYEWASHES 1,2,3
EXPANSION TANK SCHEDULE
MARK
BASIS OF DESIGN
MANUFACTURER
BASIS OF DESIGN
MODEL NUMBER
TANK VOLUME
(GAL)
ACCEPTANCE
VOLUME (GAL) SIZE (D" x H") CONNECTION SIZE WEIGHT (LBS)
ET-1 TACO PAX25-150 6.6 4 12" x 20-5/8" 3/4" 52
VACUUM PUMP SCHEDULE
MARK MAKE MODEL NO. TYPE
MOTOR QT. /
HP V/PH/HZ SYSTEM FLA SYSTEM
RECIEVER
(GAL) SCFM WEIGHT
VP-1 BEACONMEDAES VHV02D-060H-D DUPLEX 2 / 2.0 208/3/60 14.6 SURGICAL
VACUUM
60 16 @ 19" HG 1634
VP-2 A-DEC DV10 SIMPLEX 1 / 3.4 208/1/60 17.0 DENTAL VACUUM - 74 @ 10" HG 191
VP-3 A-DEC DV10 SIMPLEX 1 / 3.4 208/1/60 17.0 DENTAL VACUUM - 74 @ 10" HG 191
AIR COMPRESSOR SCHEDULE
MARK MAKE MODEL NO. TYPE
MOTOR
QTY. / HP
RECIEVER
(GAL)
CAPACITY
(SCFM) V/P/HZ SYSTEM FLA WEIGHT (LBS)
AC-1 AMICO A-SCD-D-200P-SS-N-150 DUPLEX 2/15 200 48 @ 120 PSI 208/3/60 71.3 2715
NOTES:
1. AIR COMPRESSOR AND ALL ASSOCIATED COMPONENTS SHALL BE PIPED PER MANUFACTURER RECOMMENDATIONS.
2. AIR COMPRESSOR SHALL BE PLACED ON A 4" RAISED CONCRETE PAD.
3. ROUTE CONDENSATE THROUGH A CONDENSATE NEUTRALIZATION KIT TO FLOOR DRAIN.
4. PROVIDED WITH INTEGRAL AIR INLET FILTER, TWO AIR COMPRESSOR ELEMENTS, TWO DRIVE MOTORS, AFTERCOOLER, DECICCANT DRYER, AIR RECEIVER, AND CONTROL SYSTEM
THAT MONITORS DEW POINT AND CO2 IN THE SYSTEM.
5. PROVIDE A HIGH EFFICIENCY COALESCIN PREFILTER RATED FOR 0.01 MICRON WITH AUTOMATIC DRAIN AND ELEMENT CHANGE INDICATOR AND A FULLY DUPLEXED FINAL LINE
PARTICLE FILTERS RATED FOR 1 MICRON WITH ELEMENT CHANGE INDICATOR WITH THE DRYER.
6. PROVIDE SINGLE POINT ELECTRICAL CONNECTION. DISCONNECT PROVIDED BY ELECTRICAL. REFER TO ELECTRICAL DRAWINGS.
NOTES:
1. ALL VACUUM PUMPS AND ALL ASSOCIATED COMPONENTS SHALL BE INSTALLED PER MANUFACTURER RECOMMENDATIONS.
2. ALL VACUUM PUMPS SHALL BE PLACED ON A 4" RAISED CONCRETE PAD.
3. ROUTE EXHAUST CONDENSATE DRIP LEG THROUGH A CONDENSATE NEUTRALIZATION KIT TO FLOOR DRAIN.
4. ROUTE TANK DISCHARGE THROUGH A CONDENSATE NEUTRALIZATION KIT AND DISCHARCE TO A FLOOR DRAIN.
5. PROVIDE SINGLE POINT ELECTRICAL CONNECTION. DISCONNECT PROVIDED BY ELECTRICAL. REFER TO ELECTRICAL DRAWINGS.
NOTES:
1. WATER HEATER AND ALL ASSOCIATED COMPONENTS SHALL BE PIPED PER MANUFACTURER RECOMMENDATIONS.
2. ROUTE T&P VALVE AND INDIRECT DISCHARGE TO FLOOR DRAIN.
3. OUTLET TEMPERATURE SHALL BE SET TO 140°F ON WATER HEATER.
4. WATER HEATER SHALL BE PLACED ON A 4" RAISED CONCRETE PAD.
5. WATER HEATER TO BE CAPABLE OF HEATING WATER TO 180°F. PROVIDE A BYPASS AROUND THE THERMOSTATIC MIXING VALVE FOR THERMAL ERADICATION PURPOSES.
6. ROUTE EXHAUST CONDENSATE DRAIN THROUGH A CONDENSATE NEUTRALIZATION KIT AND DISCHARCE TO A FLOOR DRAIN.
7. PROVIDE INTAKE AND EXHAUST WITH CONCENTRIC VENT KIT.
NOTES:
1. THERMOSTATIC MIXING VALVE SHALL BE PIPED PER MANUFACTURER RECOMMENDATIONS.
2. PROVIDE WITH INLET AND OUTLET SHUT-OFF VALVES.
3. PROVIDE 105°F WATER TO FAUCET AND 85°F WATER TO EYEWASH. MIN FLOW RATE FOR FAUCET IS 0.2 GPM AND MIN FLOW RATE FOR EYEWASH IS 1.5 GPM.
HOT WATER RECIRC. PUMP SCHEDULE
MARK MANUFACTURER MODEL NO. TYPE CAPACITY (GPM) HEAD (FEET) MOTOR (HP) V/PH/HZ
CP-1 BELL & GOSSETT ECOCIRC XL 55-45 INLINE 7.5 38.0 1/2 208/1/60
NOTES:
1. RECIRC PUMP SHALL BE PIPED PER MANUFACTURER RECOMMENDATIONS
2. BALANCING VALVES SHALL BE PROVIDED FOR ALL CIRCULATING SYSTEMS, VALVES SHALL BE SET TO FLOW RATES SHOWN UNLESS NOTED
OTHERWISE.
3. PROVIDE AUTOMATIC TIMER KIT TC-1 AND AQUASTAT AQS-1/2 FOR EACH PUMP LOCATION.
4. PROVIDE SINGLE POINT ELECTRICAL CONNECTION. DISCONNECT PROVIDED BY ELECTRICAL. REFER TO ELECTRICAL DRAWINGS.
PLUMBING FIXTURE SCHEDULE
MARK FIXTURE
BASIS OF DESIGN
MIXING VALVE NO.
CONNECTION SIZES FIXTURE UNITS FLUSH VALVE / FAUCET TYPE
FIXTURE FLUSH VALVE/FAUCET
WASTE PIPE
(INCHES)
VENT PIPE
(INCHES)
COLD WATER
(INCHES)
HOT WATER
(INCHES)
WASTE FIXTURE
UNITS
WATER FIXTURE
UNITS
COLD WATER
FIXTURE UNITS
HOT WATER
FIXTURE UNITS MANUAL
HARD WIRED
SENSOR BATTERY SENSOR FOOT PEDAL
P-103 WATER CLOSET (WALL HUNG, FLUSH VALVE, ADA) ZURN : Z5615-BWL-AM SLOAN : ROYAL 111 ESS-1.28 - 4" 2" 1-1/4" - 4 10 10 - - YES - -
P-413 TREATMENT SINKS ZURN : Z5128 ZURN : Z831B4-XL-28F TMV-2 1-1/2" 1-1/2" 1/2" 1/2" 1 2 1.5 1.5 YES - - -
P-414 HAND SINK ZURN : Z5318 ZURN : Z831B4-XL-28F TMV-2 1-1/2" 1-1/2" 1/2" 1/2" 1 2 1.5 1.5 YES - - -
P-418 LAVATORY ZURN : Z5311 ZURN : Z6920-XL-CWB-HW6-N TMV-2 1-1/2" 1-1/2" 1/2" 1/2" 1 2 1.5 1.5 - YES - -
P-502 MOP SINK FIAT PRODUCTS : TSB3000 FIAT PRODUCTS : 830AA TMV-3 3" 2" 3/4" 3/4" 2 4 3 3 YES - - -
P-514 LAB SINK ELKAY : ILGR4322 ZURN Z871B4-XL-18F TMV-2 / TMV-4 1-1/2" 1-1/2" 1/2" 1/2" 3 2 1.5 1.5 YES - - -
P-520 ORAL SURGERY SINK ELKAY : DLSR272210 ZURN : Z6920-XL-CWB-HW6-J TMV-2 / TMV-4 1-1/2" 1-1/2" 3/4" 3/4" 3 2 1.5 1.5 - YES - -
P-528 KITCHEN SINK ELKAY : LRADQ222265 DELTA : 9113-DST TMV-3 1-1/2" 1-1/2" 3/4" 3/4" 3 2 1.5 1.5 YES - - -
P-608 ELECTRIC WATER COOLER ELKAY : LZSTL8WSLP - - 1-1/2" 1-1/2" 1/2" - 0.5 0.25 0.25 - YES - - -
P-708 EMERGENCY EYE AND FACE WASH BRADLEY : S19274E - TMV-4 - - 3/4" TEMPERED - - - - - YES - - -
P-801 WALL HYDRANT ZURN : Z1320XL - - - - 3/4" - - - - - YES - - -
P-804 HOSE BIBB ZURN : Z1341 - - - - 3/4" - - - - - YES - - -
NOTES:
1. REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION
ELECTRONIC TRAP PRIMER SCHEDULE
MARK BASIS OF DESIGN MANUFACTURER
BASIS OF DESIGN
MODEL NUMBER CW INLET CW OUTLET SIZE
MAX NUMBER OF
DRAINS SERVED
DIMENSIONS (L" x W" x H")
ELECTRICAL
(V/P/HZ)
TP-1 PRECISION PLUMBING PRODUCTS PT-6 3/4" 1/2" 6 16" x 14" x 3-3/8" 120/1/60
TP-2 PRECISION PLUMBING PRODUCTS PT-6 3/4" 1/2" 6 16" x 14" x 3-3/8" 120/1/60
NOTES:
1. PROVIDE WITH INTEGRAL DISCONNECT.
PLUMBING MEDICAL GAS OUTLET
MARK
BASIS OF DESIGN
MANUFACTURER
BASIS OF DESIGN
MODEL NO. DESCRIPTION MOUNTING SERVICE
GO-1 CHICAGO FAUCETS LGN1-A11C-50 GAS OUTLET WALL NATURAL GAS
GO-2 CHICAGO FAUCETS LGN1-A11B-50 GAS OUTLET WALL VACUUM (LAB)
GO-3 CHICAGO FAUCETS LGN1-A11A-50 GAS OUTLET WALL COMPRESSED AIR (LAB)
GO-4 AMICO O-FXNC-DI-U-VAC GAS OUTLET WALL VACUUM (SURGERY)
PLUMBING MEDICAL GAS VALVE BOX
MARK
BASIS OF DESIGN
MANUFACTURER
BASIS OF DESIGN
MODEL NO. DESCRIPTION MOUNTING SERVICE LOCATION
ELECTRICAL
(V/PH/HZ)
ZVB-1 AMICO AVU-3A2V ZONE VALVE BOX WALL MA & DV CORRIDOR C-1 120/1/60
ZVB-2 AMICO AVU-3A2V ZONE VALVE BOX WALL MA & DV CORRIDOR C-2 120/1/60
NOTES:
1. PROVIDE EACH ZONE VALVE BOX WITH A LOCAL ALARM PANEL, DESIGN BASIS AMICO A3AR-U-AV. REFER TO FLOOR PLANS FOR LOCAL ALARM LOCATION.
2. PROVIDE PRESSURE SWITCHES AND LOCATE PRESSURE SWITCHES INSIDE ZONE VALVE BOX. WIRE PRESSURE SWITCHES BACK TO LOCAL ALARM PANEL.
3. WIRE LOCAL ALARM PANELS BACK TO BOTH MASTER ALARM PANEL LOCATIONS.
4. MEDICAL AIR WILL BE USED FOR MEDICAL AIR TO THE PATIENTS. INSTRUMENT AIR WILL BE USED FOR DENTAL AIR FOR TOOLS.
GAS LOAD SCHEDULE
MARK DESCRIPTION QTY
GAS CONNECTION
SIZE BTUH TOTAL BTUH
ROOM OUTLETS 21 1/2" 10,000 210,000
ASSUMED EXPANSION
GAS LOAD
1 100,000 100,000
B-1,2 BOILER 2 1-1/4" 255,900 511,800
GENERATOR EMERGENCY
GENERATOR
1 1-1/2" 2,000,000 2,000,000
GWH-1 WATER HEATER 1 3/4" 120,000 120,000
TOTAL BTUH: 2,941,800
TOTAL MBH: 2941.8
Revisions Date
M C
H
A
O T
T
P R
O F
E S
S
IO N A L EN
G I N
E E
R
LICENSE
F
LO R I D A
STATE OF
No. 91858
I
E L
R K
-SPIN-IN TAKE-OFF
-RECTANGLE-TO-ROUND TAKE-OFF
DNUP
-TRANSITION, SQUARE TO ROUND
-CEILING EXHAUST
-CEILING RETURN
-STANDARD BRANCH TAKE-OFF
-RADIUS ELBOW
-TRANSITION, ECCENTRIC
-FLEXIBLE DUCT
-CHANGE OF ELEVATION
-TRANSITION, CONCENTRIC
-SQUARE THROAT ELBOW
W/TURNING VANES
-RECTANGULAR/ROUND BRANCH TAKE-
OFF
OR ROUND/ROUND BRANCH TAKE-OFF
-SQUARE THROAT TEE
-RADIUS TEE
-SUPPLY REGISTER OR GRILLE
-RETURN/EXHAUST REGISTER OR GRILLE
(VERTICAL MOUNT, SIDEWALL)
(VERTICAL MOUNT, SIDEWALL)
-CEILING DIFFUSER, ROUND NECK
(CEILING DIFFUSERS ARE 4-WAY THROW UNO)
-CEILING DIFFUSER, RECTANGULAR OR
SQUARE NECK (CEILING DIFFUSERS
ARE 4-WAY THROW UNO)
-AIRFLOW SENSORAFS-X
ECC-X -ENGINEERING CONTROL CENTER
HVAC ABBREVIATIONSHVAC SYMBOL LEGEND
SYMBOL DESCRIPTIONSYMBOL DESCRIPTIONSYMBOL DESCRIPTION SYMBOL DESCRIPTION SYMBOL DESCRIPTION
-CONDENSATE
-CHILLED WATER RETURN
-CONDENSER WATER SUPPLY
-CHILLED WATER SUPPLY
-CONDENSER WATER RETURN
PIPING LEGEND
SYMBOL DESCRIPTIONSYMBOL DESCRIPTION
CWS
CWR
CHWS
CHWR
CD
-HOT WATER RETURN
-HOT WATER SUPPLYHWS
HWR
-WATER METER
-FLOW METER
-PRESSURE GAUGE
-ELBOW, TURNED DOWN
-CONNECTION, BOTTOM
-INLINE PUMP
-CAP
-INLINE PUMP
-ELBOW, 90°
-CONNECTION, TOP
-ELBOW, TURNED UP
-TEE, OUTLET DOWN
FM
M
-ELBOW, 45°
-TEE, OUTLET UP
-45° PIPE RISE (R)/DROP (D)
-PIPE ANCHORS
-CONCENTRIC REDUCER
-ECCENTRIC REDUCER
R R
-FLANGES
-FLEXIBLE CONNECTOR
-Y-TPE STRAINER
-MALE HOSE CONNECTION
-PIPE CONNECTION
-CONTROL VALVE
-BUTTERFLY VALVE
-FLOW DIRECTION
-CALIBRATING BALANCING VALVE
-BALL VALVE
-STRAINER
-UNION
-THERMOMETER
-SLOPE DIRECTION (DOWN)
-PSI REG.
-FLOW SWITCH
-CHECK VALVE
-THREE-WAY CONTROL VALVE
-FLEX CONNECTION (DOUBLE SPHERE FOR
PIPES 6" AND LARGER; SINGLE SPHERE FOR
PIPES 4" AND SMALLER
-RELIEF VALVE
-VALVE ON RISER
-TEST PLUG
-GLOBE VALVE
-PSI REG.
-MANUAL VENT
EQUIP. -P-TRAP
-DUCT SMOKE DETECTOR
-DIGITAL OUTPUT FROM DDC CONTROLLER
-DIGITAL INPUT TO DDC CONTROLLER
-STARTER
-CURRENT SENSING STATUS SWITCH
-DRY CONTACT
-ANALOG OUTPUT FROM DDC CONTROLLER
-ANALOG INPUT TO DDC CONTROLLER
CS
A -ALARM
-COM OUTPUT FROM DDC CONTROLLER
-COM INPUT TO DDC CONTROLLER
S
-HARD-WIRED INTERLOCKi
-24VAC POWER
-IMMERSION TEMPERATURE
P
-FLOW SWITCH
R -REFRIGERANT SENSOR
T -THERMOSTAT
XFM -TRANSFORMER
-EMERGENCY PUSHBUTTON
-DIFF. PRESSURE SWITCH DIGITAL
TRANSMITTER W/ THERMOWELL
CO -SPACE CARBON DIOXIDE
DPS
SENSOR/TRANSMITTER
-FLOW METER
-SPACE PUSH-BUTTON OVER-RIDE SWITCH
-AIR FLOW SENSOR
-DUCT MOUNTED TEMPERATURE SENSOR
-2-WAY VALVE W / 24VAC OR 120VAC
-SPACE TEMPERATURE SENSOR
-SPACE RH SENSOR
24VAC
24VAC
F
-ACTUATOR AS INDICATED
-ACTUATOR W / 24VAC OR 120VAC
ACTUATOR AS INDICATED
-INDICATES AVERAGING ELEMENT SENSOR
-VARIABLE FREQUENCY DRIVEVFD
-DIFF. PRESSURE
INDICATING TRANSMITTER
-MAGNEHELIC DIFFERENTIAL
-OPPOSED BLADE DAMPER
-PARALLEL BLADE DAMPER
DPIT
-STATIC PRESSURE SENSORSP
PRESSURE GAUGE
-PARTICULATE TRANSMITTERPT
-INDICATES PROBE SENSOR
SYMBOL DESCRIPTION SYMBOL DESCRIPTION
CONTROLS LEGEND
-CALIBRATED BALANCING VALVE
-SOLENOID VALVE (2-POSTION W/ ACTUATOR)
-FLOW SWITCH
PRESSURE SWITCH
-AUTOMATIC AIR VENT
BASIC MATERIALS
-CURRENT SENSORCS-X
-MANUAL BALANCING DAMPER
-MOTOR OPERATED CONTROL DAMPER
(MOD)
-FLEXIBLE CONNECTION
-ACCESS DOORS, VERTICAL OR
HORIZONTAL
-DOOR GRILLE
-UNDERCUT DOOR
-DUCT ELBOW, NEGATIVE PRESSURE,
RETURN
-DUCT ELBOW, EXHAUST
-DUCT ELBOW, POSITIVE PRESSURE
(SUPPLY)
-NEW DUCTWORK, FIRST DIMENSION IS
SIDE SHOWN
-TEMPERATURE SENSOR
-MOTORIZED CONTROL DAMPER
-HUMIDISTAT/HUMIDITY SENSOR
-THERMOSTAT/TEMPERATURE SENSOR
-STATIC PRESSURE SENSOR
-DUCT SMOKE DETECTOR
-BACKDRAFT DAMPER
-CEILING MOUNTED ACCESS DOOR
-RECTANGULAR DUCT SECTION UP,
EXHAUST
-RECTANGULAR DUCT SECTION UP,
NEGATIVE PRESSURE, RETURN
-RECTANGULAR DUCT SECTION UP,
POSITIVE PRESSURE, SUPPLY OR
OUTSIDE AIR
-ROUND DUCT SECTION UP
T
H
DOWN UP W/IN FLOOR
UC
M
T
SP
BD
M
-CONNECT TO EXISTING
-DEMOLISH TO POINT INDICATED
-HUMIDITY SENSOR (DUCT MOUNTED)H
-CARBON DIOXIDE SENSOR (DUCT MOUNTED)CO2
-CARBON DIOXIDE SENSORCO2
-SMOKE (WITH ACCESS PANEL)
-FIRE DAMPER (WITH ACCESS PANEL)
EXISTING TO BE REMOVED (HEAVY, DASHED LINE)
EXISTING TO REMAIN (THIN, HALFTONED, SOLID LINE)
NEW (HEAVY, SOLID LINE)
-STATIC PRESSURE SENSOR
-DIFFERENTIAL PRESSURE SENSORDPS-X
-DAMPERD-X
T-X
-ROOM THERMOSTAT/TEMPERATURE
SENSOR
DDC -DIRECT DIGITAL CONTROLS
PRS -PRESSURE REDUCING STATION
SP -STATIC PRESSURE
-CFM (CUBIC FEET PER MINUTE)
CV -CONSTANT AIR VOLUME
-ROOFTOP AIR HANDLING UNITRTU
RS/L -REFRIGERANT SUCTION & LIQUID LINES
C
-OUTSIDE AIR TEMPERATUREOAT
-VARIABLE AIR VOLUMEVAV
-SUPPLY AIRSA
-ROOFTOP HEAT PUMPRHP
-REHEAT COILRHC
-REVOLUTIONS PER MINUTERPM
-RETURN AIRRA
-POLYVINYL CHLORIDE PIPEPVC
-PSI GAUGEPSIG
-POUNDS PER SQUARE INCHPSI
-PRESSURE REDUCING VALVEPRV
-OUTSIDE AIROA
-NOT TO SCALENTS
-NORMALLY OPENNO
-NORMALLY CLOSEDNC
-LINEAR DIFFUSERLD
-LEAVING WATER TEMPERATURELWT
-LEAVING AIR TEMPERATURELAT
-GALLONS PER MINUTEGPM
-FEET PER MINUTE
-FIRE DAMPER
-FIRE ALARM SYSTEM
-ENTERING WATER TEMPERATURE
-ENTERING AIR TEMPERATURE
-DOWN
-CONDENSING UNIT
-CUBIC FEET PER MINUTE
-COOLING TOWER
-CONDENSATE
-CENTER LINE
-BRITISH THERMAL UNIT
-BRAKE HORSEPOWER
-BOTTOM OF PIPE
-ACCESS PANEL
-ABOVE FINISHED FLOOR
FPM
FD
FAS
EWT
EAT
DN
CU
CFM
CT
CD
BTU
BOP
BHP
AP
AFF
-AIR HANDLING UNITAHU
MBH -THOUSAND BTUs PER HOUR
ESP -EXTERNAL STATIC PRESSURE
KW -KILOWATT
MCA -MINIMUM CIRCUIT AMPS
MOCP -MAXIMUM OVER CURRENT PROTECTION
TSP
TEFC -TOTALLY ENCLOSED FAN COOLED
-VOLTS/PHASEV/PH
VFD -VARIABLE FREQUENCY DRIVE
-TOTAL STATIC PRESSURE
FLA -FULL LOAD AMPS
MOD -MOTOR OPERATED CONTROL DAMPER (MOD)
-PACKAGED TERMINAL AIR CONDITIONERPTAC
-ABOVE FINISHED ROOFAFR
-BUTTERFLY VALVEBFV
c
L
-EXHAUST AIREA
-CLEAN OUTCO
TS-X -TEMPERATURE SENSOR
SPS-X -STATIC PRESSURE SENSOR
H-X -HUMIDITY SENSOR
-CARBON DIOXIDE SENSORCO2-X
V-X
-VALVE (CHILLED WATER/HEATING HOT
WATER)
WFM-X -WATER FLOW METER
2-AHU-3-1
26-TU-I-I
VIEW NUMBER
DRAWING NUMBER WHERE SHOWN
SECTIONLETTER
TYPICAL UNIT NUMBER; AHU NO. 1, LOCATED ON LEVEL 3, LOCATED IN BLDG. 2
BUILDING NO. WHERE EQUIPMENT IS LOCATED.
AHU NUMBER
EQUIPMENT ABBREVIATION. AN "(E)" SHOWN IN FRONT OF EQUIPMENT TAGS NOTIFIES
THAT EQUIPMENT IS EXISTING
ITEM NUMBER (TERMINAL UNIT NO. 1)
ITEM (TERMINAL UNIT SHOWN)
SERVED BY AIR HANDLER UNIT NO. 1
BUILDING NO. WHERE EQUIPMENT IS LOCATED
H4
H7
A
SHEET NUMBER
A 200
DEVICE MARK
DEVICE FLOW RATE (CFM)
12X10 SA
DUCT DIMENSION (INCHES)
TYPICAL AIR DISTRIBUTION DEVICE TAG
TYPICAL DUCTWORK TAG
SYSTEM TYPE (SA = SUPPLY AIR , RA = RETURN
AIR, OA = OUTSIDE AIR, EA = EXHAUST AIR,
SS EA = STAINLESS-STEEL EXHAUST)
LEVEL EQUIPMENT LOCATED ON / LEVEL IT SERVES
DRAWING SYMBOLS
REVISION REFERENCEXX
SHEET NOTE CALLOUTXX
-EQUIPMENT WITH CLEARANCE
CLEARANCE
EQUIPMENT
1. CONNECTION TO EQUIPMENT SHALL BE VERIFIED WITH MANUFACTURER'S CERTIFIED DRAWINGS.
TRANSITIONS TO ALL EQUIPMENT SHALL BE VERIFIED AND PROVIDED FOR EQUIPMENT FURNISHED.
2. DIMENSIONS SHALL BE FIELD-VERIFIED AND COORDINATED PRIOR TO PROCUREMENT OR
FABRICATION. COORDINATE THE WORK WITH OTHER TRADES INVOLVED. FIELD MODIFICATIONS SUCH
AS OFFSETS IN PIPING OR DUCTWORK (INCLUDING DIVIDED DUCTWORK) NEEDED DUE TO
OBSTRUCTIONS OR INTERFERENCES SHALL BE PROVIDED AT NO ADDITIONAL COST.
3. DUCT CONSTRUCTION SHALL BE IN ACCORDANCE WITH THE LATEST EDITION OF THE SMACNA HVAC
DUCT CONSTRUCTION STANDARD.
4. INSTALL ALL FIRE DAMPERS, SMOKE DAMPERS AND COMBINATION FIRE/SMOKE DAMPERS IN
ACCORDANCE WITH MANUFACTURE'S INSTALLATION DIRECTIONS. PROVIDE ACCESS DOORS TO
ALLOW COMPLETE INSPECTION AND MAINTENANCE OF ALL DEVICES.
5. PROVIDE 1.5R ELBOWS IN DUCTWORK AS INDICATED. IF 1.5R ELBOWS DO NOT FIT, PROVIDE 1.0R ELBOWS. IF 1.0R ELBOWS DO NOT FIT, PROVIDE 90 DEGREE RECTANGULAR DUCT ELBOWS WITH
TURNING VANES.
6. DUCT SIZES AND ALL OPENINGS THROUGH BUILDING CONSTRUCTION SHALL SUIT EQUIPMENT
FURNISHED.
7. COORDINATE DIFFUSER, GRILLE AND REGISTER LOCATIONS WITH ARCHITECTURAL REFLECTED
CEILING PLANS AND EQUIPMENT OF ALL TRADES.
8. LOCATE THERMOSTATS, TEMPERATURE SENSORS, HUMIDISTATS, AND HUMIDITY SENSORS AT 48"
ABOVE FINISHED FLOOR UNLESS NOTED OTHERWISE. COORDINATE LOCATIONS WITH OTHER
EQUIPMENT, FURNITURE, AND DOOR SWINGS.
9. ALL EQUIPMENT, DUCTWORK, ETC., SHALL BE SUPPORTED AS DETAILED AND/OR SPECIFIED. PROVIDE
ADDITIONAL SUPPORTS AS REQUIRED TO PROVIDE A VIBRATION-FREE, RIGID INSTALLATION.
10. ALL DUCT SIZES SHOWN ARE INSIDE CLEAR DIMENSIONS.
11. DAMPERS AND INSIDES OF DUCTS VISIBLE THROUGH GRILLES, REGISTERS AND DIFFUSERS SHALL BE
PAINTED FLAT BLACK.
12. REFER TO TYPICAL DETAILS FOR PIPING AND INSTALLATION OF EQUIPMENT.
13. TRAPPED CONDENSATE DRAINS FROM ALL MECHANICAL EQUIPMENT SHALL BE PROVIDED FOR
PROPER DRAINAGE TO SUIT EQUIPMENT FURNISHED.
14. ACCESS PANELS IN DUCTWORK AND CEILINGS SHALL BE PROVIDED WHERE REQUIRED FOR
OPERATION, BALANCING OR MAINTENANCE OF ALL MECHANICAL EQUIPMENT.
15. ALL DUCTWORK AND PIPING IS SHOWN SCHEMATICALLY. PROVIDE ALL TRANSITIONS, TURNING VANES, ELBOWS, FITTINGS, ETC., TO ALLOW SMOOTH FLOWS. ALL SPLIT DUCT FITTINGS SHALL TRANSITION TO
FULL SIZE OF THE SUM OF BOTH BRANCHES, UPSTREAM OF SPLIT.
16. COORDINATE SIZE REQUIREMENTS OF ALL CONCRETE HOUSEKEEPING PADS UNDER ALL FLOOR-
MOUNTED EQUIPMENT. SEE STRUCTURAL DRAWINGS FOR PAD DETAILS AND SPECIFICATIONS.
17. VERIFY FINISH WITH ARCHITECT PRIOR TO PURCHASING GRILLES, REGISTERS, DIFFUSERS, LOUVERS
AND OTHER AIR DISTRIBUTION DEVICES.
18. PROVIDE FLEXIBLE DUCT CONNECTIONS ON ALL DUCTWORK CONNECTING TO FANS, AIR HANDLING
UNITS, AND FAN COIL UNITS.
19. PROVIDE TRANSITIONS AT DIFFUSER NECKS AS REQUIRED TO MATCH SIZES OF FLEX DUCTS TO BE
CONNECTED.
20. SLEEVE AND SEAL ALL PIPING PENETRATIONS THROUGH BUILDING PARTITIONS.
21. MAINTAIN CLEARANCE OF A MINIMUM OF 6" BETWEEN DUCTWORK, PIPING, EQUIPMENT, ETC., AND ALL FIRE RATED AND FIRE/SMOKE RATED PARTITIONS, TO ALLOW FOR INSPECTIONS OF RATED WALLS.
22. LOCATE ALL OUTSIDE AIR INTAKES A MINIMUM OF 25'-0" CLEAR FROM ALL PLUMBING VENTS AND EXHAUST AIR DISCHARGE LOCATIONS. LOWEST POINT OF EACH OUTSIDE AIR INTAKE ON ROOF SHALL
BE A MINIMUM OF 24" ABOVE ROOF.
23. DUCT RUNOUTS TO DIFFUSERS SHALL MATCH THE SIZE OF THE DIFFUSER NECK.
24. UNLESS OTHERWISE NOTED, ALL EQUIPMENT AND VALVE DRAINS SHALL BE INDEPENDENTLY PIPED
FULL SIZE TO THE NEAREST PLUMBING DRAIN.
GENERAL NOTES
SUSTAINABLE DESIGN REQUIREMENTS
1.0 GENERAL:
A. REQUIREMENTS BELOW ARE BASED ON THE VA SUSTAINABLE DESIGN MANUAL - 2014: REV1 2017.
2.0 ENERGY AND ATMOSPHERE
A. FUNDAMENTAL AND ENHANCED COMMISSIONING (Cx) AND VERIFICATION
1. PROVIDE COMMISSIONING SERVICES FOR MECHANICAL, ELECTRICAL, AND PLUMBING PER
THE VA COMMISSIONING SPECIFICATION SECTIONS FOR EACH DISCIPLINE.
B. MINIMUM ENERGY PERFORMANCE
1. EQUIPMENT EFFICIENCY VALUES SHALL COMPLY WITH ASHRAE STANDARD 90.1-2013.
2. TOTAL BUILDING PERFORMANCE SHALL BE IN ACCORDANCE WITH CRITERIA INDICATED IN
THE SUBMITTED DESIGN NARRATIVE FOR MECHANICAL, ELECTRICAL, AND PLUMBING.
C. BUILDING-LEVEL ENERGY METERING AND ADVANCED ENERGY METERING
1. INSTALL NEW BUILDING-LEVEL ENERGY METERS, OR SUBMETERS THAT CAN BE
AGGRE…