This file attachment provides drawings related to a federal solicitation for construction services. The Bay Pines VA Medical Center is seeking a general contractor to construct a new Dental Clinic involving general construction work, as well as mechanical, electrical, plumbing and selected site utility installation. The project scope includes demolition of an existing modular building, construction of a gravel parking lot and select concrete walkways, installation of a new generator and permeable pavement parking lot and driveway. Responses to the solicitation are due to the Department of Veterans Affairs Technology Acquisition Center located in Austin, Texas.
View the file
Other files
Show all 19
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
BUILDING
FF EL 11.27
SOLAR PANEL INVERTER
METAL STAIRS
ON CONC PAD
(TYP)
LANDSCAPED
AREA (TYP)
LANDSCAPED
AREA (TYP)
EXISTING
OVERGROWTH
CONC
BASKETBALL
COURT
8" POLE
(TYP)
EXERCISE
AREA
2" METAL
POST
2" METAL PIPE
6" CURB
AROUND PLANTER
4.7'
4.7'
4.
7'
4.
7'
1.2'
4.7'
1.
2'
1.2' 4.
7'
4.
8'
1.
2'4.7'
4.7' 1.
1'
4.
7'
1.1'
4.7'
1.
2'
4.7' 1.
2'
5.1' 1.
2'
1.2'
5.
2'
4.
7'1.2'
4.
7'1.2'
4.7'
1.
2'
1.2'
4.
7'4.
7'1.2'
.2
44.1' 5.
9' 17.1'
.4
65.5'
.2
6.0'
.1
23.4'
.6
81.8'6.
0'
17.3'
.7
45.8'
.0
12"
10"
20" TWIN
14"
24"
20"
10"
12"
38"
12"
8"
10"
9" TWIN
18"
28"
12"
13"
14"
22"
6"
7" 7"
9" TWIN
36"
10"
34"
12"
SOLAR PANEL
SOLAR PANEL
SOLAR PANEL
SOLA
R PANEL
ASPHALT
SOLAR PANEL
EQUIPMENT
4.9'
4.7' 1.2'
4.7' 1.
1'
1.2'
ANOTHER BUILDING
CONC WALK
(TYP)
CONC WALK
(TYP)
COVERED
AREA (TYP)
ASPHALT
DRIVEDROP INLET (TYP)
POST
(TYP)
GROUNDING ROD
(TYP)
16"
18"
9 9
DROP INLET
GRATE EL 7.75
N 8" PVC INV 5.34
NE 15" RCP INV 5.21
S 18" RCP INV 5.22 (DU)
SW 12" PVC INV 5.45
NW 6" PVC INV 5.41
DROP INLET
GRATE EL 8.75
NE 18" RCP INV 4.44 (DU)
W 18" RCP INV 3.75 (DU)
E INV 8.40
W INV 8.51
.0'
9.3' 52.7'
.6'
2.7'
1.9
1.1
4.0'
.9'
75.3'
PROPOSED
DENTAL CLINIC
BUILDING
11,373 SF
FFE: 11.00
.0'
PROPOSED
STORMWATER
POND-1
PROPOSED
TRANSFORMER PAD
(SEE ELEC PLANS)
9.71
9.58
9.75
9.89
9.45
9.53
9.71
8.65 (EX)
8.60 (EX)
8.52 (EX)
8.67
(EX)
9.39
(FC)
9.83
8.15
(LP)
8.39
9.78
9.59
9.12
9.19
9.529.77
(FC)
9.75
(FC)
9.80
(FC)
9.86
9.57
9.65
9.54
9.10
9.04
9.01
8.71
10.78
10.95
10.56
10.39
10.19
9.89
10.66
10.96
(DS)
10.80(TS)
10.30(BS)
10.50
10.50
8.09
10.25
9.15
9.83
8.87
8.91
9.40
9.19
10.75
8.06
8.05
8.38
8.54
8.90
8.00
8.42
8.66
(HP)
8.10
(LP)
8.62
8.84
9.11
9.44
8.92
9.70
9.79
9.32
9.43
(EX)
9.45
(EX)
10.49
(EX)
10.54
(EX)
10.13
9.48
(EX)
9.36
(EX)
9.39
9.23
9.51
9.34
9.20 8.95
9.66 9.84
9.95 9.63
2.
7%
1.
1%
2.2%
3.
5%
3.8%
3.8%
1.7%
1.6%
1.8%
1.8%
1.9%
2.
0%
9.00
10.10
10.95
0.7%
9.16
9.39
9.12
9.42
9.29
9.27
8.71
8.43
8.17
(LP)
3.
9%
1.7%
7.7%
2.
2%
2.4%
2.8%
1.5
1.0
1.2
10.00
9.23
9.62
9.07
9.37
8.74
9.03
8.45
8.82
8.18
8.73
9.13
9.32
9.56
9.76
9.64
9.68
9.41
9.73
9.77
8.95
9.61
8.68
8.76
1.6
1.2
1.0%
1.9%
9.57
9.70
8.80
8.17
9.45
9.34
9.68
9.74
10.90
10.66
2.
1%
2.
6%
0.6%
1.
3%
0.8%
1.3%
1.
5%
0.
2%
0.3%
9.68
9.75
9.52
10.70
9.30
9.22
10.07
9.45
9.21
9.67
9.54
9.81
9.74
9.95 (HP)
9.61
9.67
9.43
9.55
9.17
9.95
(HP)
1.
7%
1.1
10.80(TS)
10.30(BS)
PROPOSED
FLUME (TYP.)
101 LF 18" HDPE
@ 0.005 FT/FT
DMH-2
RIM: 10.25
INV IN 5.10 (S)
INV IN 6.88 (E)
INV IN 5.10 SW (EX)
INV OUT 5.04 N (EX)
CO-2
RIM: 10.40
INV: 7.40
8" ROOF DRAIN
8" ROOF DRAIN
CO-3
RIM: 10.35
INV: 7.05
CO-2
RIM: 10.35
INV: 7.00
EXISTING LEGEND
EXISTING MANHOLES
EXISTING COMMUNICATION, UNDERGROUND
EXISTING NATURAL GAS, UNDERGROUND
EXISTING POWER, UNDERGROUND
EXISTING SANITARY SEWER, UNDERGROUND
EXISTING STORM SEWER, UNDERGROUND
EXISTING STORM SEWER, ROOF DRAIN
EXISTING SOLAR PANEL
EXISTING WATER, UNDERGROUND
EXISTING CURB
EXISTING EDGE OF PAVEMENT
EXISTING MINOR CONTOUR
EXISTING MAJOR CONTOUR
EXISTING TREES
EXISTING BOLLARD
BORING LOCATION
EXISTING SIGN
EXISTING LIGHT
EXISTING UTILITY POLE
EXISTING FENCE
EXISTING BUILDING
EXISTING SPOT ELEVATION100.55
EXISTING STORM SEWER, INLET
EXISTING SANITARY SEWER, CLEAN-OUT
EXISTING JUNCTION BOX
EXISTING WATER STRUCTURES
EXISTING VALVES
EXISTING SIDEWALK
PROJECT BOUNDARY LIMITS
EXISTING ASPHALT DRIVEWAY
EXISTING GRAVEL PAVEMENT
EXISTING OVERHEAD ELECTRIC
EXISTING OVERGROWTH
EXISTING TRANSFORMER
EXISTING SUPPORT POST
EXISTING DIRT DRIVE
PROPOSED LEGEND
PROPOSED CURB LINE
PROPOSED EDGE OF PAVEMENT
PROPOSED BUILDING OUTLINE
PROPOSED SIDEWALK
PROPOSED WATER MAIN
PROPOSED STORM SEWER
PROPOSED SANITARY SEWER
PROPOSED UNDERGROUND ELECTRIC
PROPOSED UNDERGROUND GAS
PROPOSED AREA DRAIN
PROPOSED DRAINAGE INLET
PROPOSED DRAINAGE MANHOLE
PROPOSED SANITARY MANHOLE
PROPOSED MAJOR CONTOUR
PROPOSED MINOR CONTOUR
PROPOSED BUILDING OVERHANG
5.7
4% PROPOSED SLOPE
PROPOSED SPOT ELEVATION
PROPOSED ASPHALT PAVEMENT
PROPOSED CURB STOP
PROPOSED TREE LINE
PROPOSED DETECTABLE WARNING
PROPOSED DRAINAGE PIPE
PROPOSED POROUS ASPHALT PAVEMENT
Revisions DateRevisions Date
VA Project No.
RDC/JPA Project No.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Office of Construction and Facilities Management
CONSTRUCT
DENTAL CLINC
09/06/2022 APJS
516-349
BAY PINES, FL
BUILDING
100% 21001.00
Revisions Date
PENNONI ASSOCIATES INC.
5755 Rio Vista Dr
Clearwater, FL 33760 T 727.451.9561
Florida COA: 7819
1 65% DESIGN 05/24/2022
CONSTRUCTION SET
CG - 151_____________
GRADING AND DRAINAGE PLAN
00 20' 40'
N O
R
TH
SITE INFORMATION:
ADDRESS: 10000 BAY PINES BLVD
BAY PINES, FL 33744
OWNER: U.S. DEPT. OF VETERANS AFFAIRS
10000 BAY PINES BLVD
BAY PINES, PINELLAS COUNTY FL 33744
ENGINEER: PENNONI
JASON SHERIDAN, PE
5755 RIO VISTA DRIVE
CLEARWATER, FL 33760
GRADING NOTES:
1. THE PREPARED SUBGRADE SHALL BE PROOF ROLLED WITH A
SMOOTH-DRUM VIBRATING ROLLER TO DELINEATE SOFT/UNSTABLE
AREAS AND COMPACT SOILS DISTURBED DURING EXCAVATION
OPERATIONS. AREAS WHICH EXHIBIT INSTABILITY SHALL BE UNDERCUT
AND REPLACED WITH LOAD-BEARING FILL.
2. MINIMUM CONCRETE PAVEMENT GRADE SHALL BE 1.0% SLOPE UNLESS
NOTED OTHERWISE.
3. BEDDING REQUIREMENTS SPECIFIED HEREIN ARE TO BE CONSIDERED AS
MINIMUMS FOR RELATIVELY DRY, STABLE EARTH CONDITIONS.
ADDITIONAL BEDDING SHALL BE REQUIRED FOR ROCK TRENCHES AND
WET AREAS. CONTRACTOR SHALL HAVE THE RESPONSIBILITY TO
PROVIDE SUCH ADDITIONAL BEDDING AS MAY BE REQUIRED TO PROPERLY
CONSTRUCT THE WORK.
4. CONTRACTOR TO ENSURE THAT POSITIVE AND ADEQUATE DRAINAGE IS
MAINTAINED AT ALL TIMES WITHIN THE PROJECT LIMITS. THIS MAY
INCLUDE, BUT NOT BE LIMITED TO, REPLACEMENT OR RECONSTRUCTION
OF EXISTING DRAINAGE STRUCTURES THAT HAVE BEEN DAMAGED OR
REMOVED OR REGRADING AS REQUIRED BY THE ENGINEER, NO
SEPARATE PAYMENT WILL BE MADE FOR ANY COSTS INCURRED TO
COMPLY WITH THIS REQUIREMENT.
5. THE CONTRACTOR SHALL PROVIDE ANY AND ALL EXCAVATION AND
MATERIAL SAMPLES NECESSARY TO CONDUCT REQUIRED SOIL TESTS.
ALL ARRANGEMENTS AND SCHEDULING FOR THE TESTING SHALL BE THE
CONTRACTOR'S RESPONSIBILITY.
6. CONTRACTOR SHALL FURNISH AND MAINTAIN ALL NECESSARY
BARRICADES AROUND THE WORK AREA AND SHALL PROVIDE PROTECTION
AGAINST WATER DAMAGE AND SOIL EROSION.
7. DRAINAGE SYSTEM TO BE FLUSHED AFTER CONSTRUCTION.
SOLAR PANEL INVERTER
METAL STAIRS
ON CONC PAD
(TYP)
LANDSCAPED
AREA (TYP)
LANDSCAPED
AREA (TYP)
EXISTING
OVERGROWTH
CONC
BASKETBALL
COURT
8" POLE
(TYP)
EXERCISE
AREA
2" METAL
POST
2" METAL PIPE
5' CHAIN LINK FENCE
AROUND EDGE OF PAVEMENT
6" CURB
AROUND
PLANTER
6" CURB
AROUND PLANTER
4.7'
1.
2'
1.
2'
4.7'
1.
1'
4.7'
4.7'
1.
1'
5.0' 5.2'
1.
2'
4.9'
4.
7'
4.
7'
1.2'
4.7'
1.
2'
1.2' 4.
7'
4.
8'
1.
2'4.7'
4.7' 1.
1'
4.
7'
1.1'
4.7'
1.
2'
4.7' 1.
2'
5.1' 1.
2'
1.2'
5.
2'
4.
7'1.2'
4.
7'1.2'
4.7'
1.
2'
1.2'
4.
7'4.
7'1.2'
.2
18.6'
.6
19.6' 4.
8' 44.1' 5.
9' 17.1'
.4
65.5'
.2
6.0'
.1
23.4'
.6
81.8'6.
0'
17.3'
.7
45.8'
.0
12"
10"
20" TWIN
14"
24"
20"
10"
12"
38"
12"
8"
10"
9" TWIN
18"
28"
12"
13"
14"
22"
6"
7"7"
9" TWIN
10"
19"
12"
36"
10"
34"
12" 12"
17"
SOLAR PANEL
SOLAR PANEL
SOLAR PANEL
SOLA
R PANEL
COVERED
DRIVE THRU
LANES
ASPHALT
SOLAR PANEL
EQUIPMENT
4.9'
4.7' 1.2'
4.7' 1.
1'
1.2'
HALLWAY TO
ANOTHER BUILDING
CONC WALK
(TYP)
CONC WALK
(TYP)
COVERED
AREA (TYP)
ASPHALT
DRIVEDROP INLET (TYP)
POST
(TYP)
GROUNDING ROD
(TYP)
20" 9"16"
10"
12" TRIPLET
14"9"
9" TWIN14"9"15" TWIN
7" TWIN
18"
ASPHALT
PARKING
SIGN
18"
13"
12"
CONC WALK
(TYP)
16"
18"
9 9
DROP INLET
GRATE EL 7.75
N 8" PVC INV 5.34
NE 15" RCP INV 5.21
S 18" RCP INV 5.22 (DU)
SW 12" PVC INV 5.45
NW 6" PVC INV 5.41
RIM EL 10.14
NE 12" PVC INV 5.88
RIM EL 9.89
N 6" VCP INV 6.34
SE 6" PVC INV 6.38
W 6" VCP INV 6.49 (DU)
DROP INLET
GRATE EL 8.75
NE 18" RCP INV 4.44 (DU)
W 18" RCP INV 3.75 (DU)
TOP 18" RCP 7.56 (DU)
6" PVC
E INV 8.40
W INV 8.51
PROJECT LIMITS
PROJECT LIMITS
PROJECT LIMITS
PIV
FDC
540 LF PROPOSED
2.5" PVC (C900)
CHILLED WATER
TIE INTO EXSTING
CHILLED WATER
PROPOSED
GENERATOR
FEED
EXISTING LEGEND
EXISTING MANHOLES
EXISTING COMMUNICATION, UNDERGROUND
EXISTING NATURAL GAS, UNDERGROUND
EXISTING POWER, UNDERGROUND
EXISTING SANITARY SEWER, UNDERGROUND
EXISTING STORM SEWER, UNDERGROUND
EXISTING STORM SEWER, ROOF DRAIN
EXISTING SOLAR PANEL
EXISTING WATER, UNDERGROUND
EXISTING CURB
EXISTING EDGE OF PAVEMENT
EXISTING MINOR CONTOUR
EXISTING MAJOR CONTOUR
EXISTING TREES
EXISTING BOLLARD
BORING LOCATION
EXISTING SIGN
EXISTING LIGHT
EXISTING UTILITY POLE
EXISTING FENCE
EXISTING BUILDING
EXISTING SPOT ELEVATION100.55
EXISTING STORM SEWER, INLET
EXISTING SANITARY SEWER, CLEAN-OUT
EXISTING JUNCTION BOX
EXISTING WATER STRUCTURES
EXISTING VALVES
EXISTING SIDEWALK
PROJECT BOUNDARY LIMITS
EXISTING ASPHALT DRIVEWAY
EXISTING GRAVEL PAVEMENT
EXISTING OVERHEAD ELECTRIC
EXISTING OVERGROWTH
EXISTING TRANSFORMER
EXISTING SUPPORT POST
EXISTING DIRT DRIVE
PROPOSED LEGEND
PROPOSED CURB LINE
PROPOSED EDGE OF PAVEMENT
PROPOSED BUILDING OUTLINE
PROPOSED SIDEWALK
PROPOSED WATER MAIN
PROPOSED STORM SEWER
PROPOSED SANITARY SEWER
PROPOSED UNDERGROUND ELECTRIC
PROPOSED UNDERGROUND GAS
PROPOSED AREA DRAIN
PROPOSED DRAINAGE INLET
PROPOSED DRAINAGE MANHOLE
PROPOSED SANITARY MANHOLE
PROPOSED MAJOR CONTOUR
PROPOSED MINOR CONTOUR
PROPOSED BUILDING OVERHANG
PROPOSED BAHIA SOD
PROPOSED ASPHALT PAVEMENT
PROPOSED CURB STOP
PROPOSED TREELINE
PROPOSED DETECTABLE WARNING
PROPOSED DRAINAGE PIPE
PROPOSED TREES
PROPOSED POROUS ASPHALT PAVEMENT
PROPOSED UNDERGROUND TELECOM
PROPOSED TELECOM MANHOLE
PROPOSED SAND GROWN BAHIA SOD
Revisions DateRevisions Date
VA Project No.
RDC/JPA Project No.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Office of Construction and Facilities Management
CONSTRUCT
DENTAL CLINC
09/06/2022 APJS
516-349
BAY PINES, FL
BUILDING
100% 21001.00
Revisions Date
PENNONI ASSOCIATES INC.
5755 Rio Vista Dr
Clearwater, FL 33760 T 727.451.9561
Florida COA: 7819
1 65% DESIGN 05/24/2022
CONSTRUCTION SET
CS - 170_____________
OVERALL UTILITY PLAN
00 40' 80'
N O
R
TH
SITE INFORMATION:
ADDRESS: 10000 BAY PINES BLVD
BAY PINES, FL 33744
OWNER: U.S. DEPT. OF VETERANS AFFAIRS
10000 BAY PINES BLVD
BAY PINES, PINELLAS COUNTY, FL 33744
ENGINEER: PENNONI
JASON SHERIDAN, PE
5755 RIO VISTA DRIVE
CLEARWATER, FL 33760
UTILITY NOTES:
1. ALL PIPE LENGTHS AND DISTANCES BETWEEN STRUCTURES ARE MEASURED FROM CENTER
OF STRUCTURE TO CENTER OF STRUCTURE ALONG A HORIZONTAL PLANE.
2. ALL STORM DRAINAGE PIPE SHALL BE LAID ON SMOOTH CONTINUOUS GRADES WITH NO
VISIBLE BENDS AT JOINTS.
3. BEDDING REQUIREMENTS SPECIFIED HEREIN ARE TO BE CONSIDERED AS MINIMUMS FOR
RELATIVELY DRY, STABLE EARTH CONDITIONS. ADDITIONAL BEDDING SHALL BE REQUIRED
FOR ROCK TRENCHES AND WET AREAS. CONTRACTOR SHALL HAVE THE RESPONSIBILITY TO
PROVIDE SUCH ADDITIONAL BEDDING AS MAY BE REQUIRED TO PROPERLY CONSTRUCT THE
WORK.
4. COMPACTION OF THE BACKFILL OF ALL TRENCHES SHALL BE COMPACTED TO THE DENSITY
OF 95% OF THEORETICAL MAXIMUM DRY DENSITY (ASTM D698). BACKFILL MATERIAL SHALL BE
FREE FROM ROOTS, STUMPS, OR OTHER FOREIGN DEBRIS AND SHALL BE PLACED IN LIFTS
NOT TO EXCEED 6 INCHES IN COMPACTED FILL THICKNESS. A REPORT FROM A
GEOTECHNICAL ENGINEER MAY BE REQUIRED BY THE PUBLIC WORKS INSPECTOR.
CORRECTION OF ANY TRENCH SETTLEMENT WITHIN A YEAR FROM THE DATE OF APPROVAL
WILL BE THE RESPONSIBILITY OF THE CONTRACTOR.
5. THE CONTRACTOR WILL ENSURE THAT POSITIVE AND ADEQUATE DRAINAGE IS MAINTAINED
AT ALL TIMES WITHIN THE PROJECT LIMITS. THIS MAY INCLUDE, BUT NOT BE LIMITED TO,
REPLACEMENT OR RECONSTRUCTION OF EXISTING DRAINAGE STRUCTURES THAT HAVE
BEEN DAMAGED OR REMOVED OR REGRADING AS REQUIRED BY THE ENGINEER, EXCEPT FOR
THOSE DRAINAGE ITEMS SHOWN AT SPECIFIC LOCATIONS AND HAVING SPECIFIC PAY ITEMS
IN THE DETAILED ESTIMATE. NO SEPARATE PAYMENT WILL BE MADE FOR ANY COSTS
INCURRED TO COMPLY WITH THIS REQUIREMENT.
6. CONTRACTOR IS RESPONSIBLE FOR ALL UTILITY CONNECTION FEES.
7. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO DETERMINE THE LOCATION OF ALL
EXISTING UNDERGROUND UTILITIES AND TO TAKE WHATEVER STEPS NECESSARY TO
PROVIDE FOR THEIR PROTECTION. THE ENGINEER ASSUMES NO RESPONSIBILITY FOR THE
LOCATIONS OF UTILITIES SHOWN OR NOT SHOWN. THE CONTRACTOR SHALL CONTACT THE
UTILITY COMPANIES FOR EXACT LOCATION OF THEIR UTILITIES PRIOR TO STARTING
CONSTRUCTION. IT SHALL BE THE SOLE RESPONSIBILITY OF THE CONTRACTOR TO REPAIR
AND REPLACE ANY AND ALL DAMAGE MADE TO UTILITIES BY THE CONTRACTOR.
8. THE CONTRACTOR SHALL COORDINATE LOCATION AND INSTALLATION OF ALL UNDERGROUND
UTILITIES AND APPURTENANCES TO MINIMIZE DISTURBANCE TO CURBING, PAVING, AND
COMPACTED SUBGRADE.
9. CONTRACTOR SHALL EXCAVATE ONLY AS MUCH TRENCH WHICH PIPE CAN BE INSTALLED AND
TRENCH BACKFILLED BY THE END OF EACH WORK DAY.
10. ALL UNDERGROUND UTILITY TRENCHES SHALL BE BACKFILLED WITH SAFE CLEAN FILL.
11.FLOW PRESSURE TO ALL FIRE HYDRANTS SHALL HAVE MINIMUM 600 GALLONS PER MINUTE AT
A MINIMUM RESIDUAL PRESSURE OF 20 POUNDS PER SQUARE INCH.
12. ALL TRENCHES SHALL BE PROPERLY SECURED AND BRACED.
13. ALL EXISTING CASTING AND INLET TOPS OR GRATES MUST BE ADJUSTED TO THE PROPOSED
GRADE, UNLESS OTHERWISE INDICATED.
14. ALL PROPOSED UTILITIES, INCLUDING ELECTRIC SERVICE, SHALL BE PLACED UNDERGROUND.
15. ALL CONNECTIONS TO EXISTING UTILITIES AND TESTING SHALL BE PERFORMED IN THE
PRESENCE OF UTILITY OWNERS AND PENNONI. CONNECTION LOCATIONS MUST BE
APPROVED IN FIELD AFTER PIPE IS EXPOSED. CONTRACTOR SHALL PROVIDE WRITTEN
REQUEST TO PENNONI WITH PROPOSED TIME AND DATE OF CONNECTION AT LEAST 5
WORKING DAYS IN ADVANCE OF PLANNED CONNECTION. COORDINATE WITH LOCAL
JURISDICTION ON THE CAPPING AND DISCONNECTING REQUIREMENTS FOR
16. ANY EXISTING SERVICES.ALL BUILDINGS CONTAINING KITCHENS / RESTAURANTS REQUIRE
GREASE TRAPS SIZED IN ACCORDANCE WITH THE EPA REGULATIONS WITHIN SANITARY
LATERALS.
17.CONTRACTOR SHALL CALL FOR A 000-SITE DEVELOPMENT MEETING WITH THE ENGINEERING
DEPARTMENT UTILITY CONSTRUCTION INSPECTORS PRIOR TO THE START OF ANY
CONSTRUCTION ACTIVITIES ON SITE.
18.ON SITE SANITARY SEWER IS PRIVATELY OWNED.
19. A SEPARATE PERMIT IS REQUIRED FOR THE SEWER CUT AND CAP. THE CUT AND CAP PERMIT
MUST BE OBTAINED BY A LICENSED PLUMBER, ISSUED, INSPECTED, AND COMPLETED PRIOR
TO THE ISSUANCE OF THE ASSOCIATED DEMOLITION PERMIT.
20.DOGHOUSE MANHOLES ARE NOT PERMITTED FOR SANITARY SEWER MANHOLES.
21.CONTRACTOR SHALL VERIFY MINIMUM SEPARATION BETWEEN THE OUTSIDE DIAMETER OF
WATER, RECLAIMED WATER, STORM SEWER AND SANITARY SEWER SYSTEMS (18" MINIMUM
VERTICAL AND 10' MINIMUM HORIZONTAL SEPARATIONS). UPON COMPLETION OF
CONSTRUCTION, THE CONTRACTOR SHALL PROVIDE WRITTEN VERIFICATION AND PHOTOS
DOCUMENTING THE MINIMUM SEPARATION AS CONSTRUCTED. CONSTRUCTION SHALL
COMPLY WITH 62-555, FAC
22.ALL WATER, WASTEWATER, AND RECLAIMED WATER LINES CROSSING OTHER UTILITY LINES
HAVE AT LEAST 18" VERTICAL CLEARANCE.
23.CONSTRUCTION SHALL MEET THE REQUIREMENTS OF NFPA 1 2013 EDITION CHAPTER 16 FIRE
SPRINKLER PROTECTION. SAFEGUARDING CONSTRUCTION, ALTERATION, AND DEMOLITION
OPERATIONS TO INCLUDE BUT NOT BE LIMITED TO COMPLYING WITH NFPA 241.
24.FIRE WATER SYSTEM PIPING
24.1. FIRE DEPARTMENT ACCESS AND WATER SUPPLY SHALL BE ESTABLISHED BEFORE ANY
VERTICAL CONSTRUCTION BEINGS. THE CONNECTION SHALL MEET THE REQUIREMENTS
OF NFPA 1 2015 EDITION, CHAPTER 18.
24.2. WHERE UNDERGROUND WATER MAINS AND HYDRANTS ARE TO BE INSTALLED, THEY
SHALL BE INSTALLED, COMPLETED AND IN SERVICE PRIOR TO CONSTRUCTION AS PER
NFPA-241.ALL UNDERGROUND FIRE LINES MUST BE INSTALLED PER NFPA-24 2013
EDITION BY A LICENSED CLASS 1, 2, OR 5 FIRE PROTECTION SYSTEM CONTRACTOR
WITH SEPARATE PERMIT AND PLANS.
24.3. POLYVINYL CHLORIDE (PVC):
24.3.1. FOUR (4) INCHES DIAMETER AND GREATER - CLASS 150 PIPE MEETING AWWA C-900
(DR 14). FIRE LINES, BACKFLOW PREVENTION AND APPURTENANCES SHALL COMPLY
WITH NFPA 24 WITH DR 14 PIPE (CLASS 200) AND TESTED AT 200 PSI. FOR 24 HOURS
IN ACCORDANCE WITH NFPA 24.
25.WATER MAIN AND FORCE MAIN SYSTEM TESTING
25.1. THE CONTRACTOR SHALL PUMP THE LINES TO A PRESSURE EQUAL TO OR GREATER
THAN 150 PSI OR 200 PSI (DR 14). SHOULD PRESSURE FALL BELOW 150 PSI DURING THE
TEST PERIOD, IT SHALL BE VOIDED AND RESTARTED. TEST PERIOD SHALL BE TWO (2)
HOURS. ALLOWABLE LEAKAGE SHALL BE COMPUTED IN ACCORDANCE WITH AWWA
MANUAL M23, LATEST REVISION.
26.POTABLE WATER AND FORCE MAIN FITTINGS
26.1. THRUST RESTRAINT:
26.2. ALL POTABLE WATER AND SEWER FORCE MAIN VALVES AND FITTINGS SHALL BE
RESTRAINED AGAINST THRUST FROM 150 PSI TEST PRESSURE BY FLANGED OR
"MEGALUG" TYPE CONNECTORS. ALL PIPE JOINTS LYING WITHIN THE LISTED MINIMUM
DISTANCE OF ANY FITTING OR VALVE SHALL ALSO BE RESTRAINED. WHEN CASINGS
FALL WITHIN THE MINIMUM DISTANCE FROM A FITTING, RESTRAIN ALL JOINTS INSIDE
THE CASING IN ADDITION TO THE REQUIRED MINIMUM LENGTH OF BURIED PIPE. PLEASE
REFERENCE THE RESTRAINT TABLE ON THE UTILITY PLAN WHICH DESCRIBES THE
MINIMUM LENGTH OF PIPE THAT SHALL BE CONTINUOUSLY RESTRAINED ON BOTH SIDES
OF DIFFERENT TYPES AND SIZES OF POTABLE WATER AND FORCE MAIN FITTINGS. RULE
62-555-320(21) (B)
27.NO EXISTING METERS ARE TO BE REMOVE FROM THE SITE.
28.ALL WATER LINES LOCATED AFTER BACKFLOW DEVICES AND METERS ARE CONSIDERED
PRIVATE.
29.A PRE-CONSTRUCTION MEETING SHALL BE SET UP TO DISCUSS THESE AND OTHER ISSUES
RESULTING IN THIS CONSTRUCTION PROJECT. THIS SHALL BE COORDINATED THROUGH THE
CONSTRUCTION SITE PROJECT MANAGER.
30.PRIOR TO ISSUANCE OF CO:
30.1. SUBMIT A MAINTENANCE AGREEMENT OF THE STORMWATER MAINTENANCE SYSTEM
SIGNED AND ACCEPTED BY THE PROJECT’S OWNER.
30.2. SUBMIT FIVE (5) 24”X36” SIGNED AND SEALED SETS OF RECORD DRAWINGS AND ONE (1)
ENGINEER OF RECORD CERTIFICATION LETTER CERTIFYING THAT THE PROJECT
INFRASTRUCTURE WAS CONSTRUCTED IN SUBSTANTIAL CONFORMANCE WITH THE
APPROVED DESIGN AND SPECIFICATIONS AND WILL MEET ALL GOVERNING AGENCIES
APPLICABLE RULES AND REGULATIONS. SHOULD THE RECORD DRAWINGS SHOW
SUBSTANTIAL DEVIATIONS FROM DESIGN CALCULATIONS AND PERMITTED PLANS, A
NARRATIVE IDENTIFYING THE CHANGES SHALL BE INCLUDED AS PART OF THE
CERTIFICATION LETTER.
30.3. PASS FINAL STORMWATER INSPECTION.
31.THE CONTRACTOR SHALL BE APPROVED FOR UTILITY SHUTDOWN REQUEST PRIOR TO START
OF UTILITY WORK. THE VA SHALL BE PRESENT AT POWER MAIN TIE IN.
SOLAR PANEL INVERTER
METAL STAIRS
ON CONC PAD
(TYP)
LANDSCAPED
AREA (TYP)
LANDSCAPED
AREA (TYP)
EXISTING
OVERGROWTH
CONC
BASKETBALL
COURT
8" POLE
(TYP)
EXERCISE
AREA
2" METAL
POST
2" METAL PIPE
6" CURB
AROUND PLANTER
4.7'
1.
2'
1.
2'
4.7'
4.
7'
4.
7'
1.2'
4.7'
1.
2'
1.2' 4.
7'
4.
8'
1.
2'4.7'
4.7' 1.
1'
4.
7'
1.1'
4.7'
1.
2'
4.7' 1.
2'
5.1' 1.
2'
1.2'
5.
2'
4.
7'1.2'
4.
7'1.2'
4.7' 1.
2'
1.2' 4.
7'4.
7'1.2'
.2
18.6'
.6
19.6' 4.
8' 44.1' 5.
9' 17.1'
.4
65.5'
.2
6.0'
.1
23.4'
.6
81.8'6.
0'
17.3'
.7
45.8'
.0
12"
10"
20" TWIN
14"
24"
20"
10"
12"
38"
12"
8"
10"
9" TWIN
18"
28"
12"
13"
14"
22"
6"
7" 7"
9" TWIN
36"
10"
34"
12" 12"
SOLAR PANEL
SOLAR PANEL
SOLAR PANEL
SOLA
R PANEL
SOLAR PANEL
EQUIPMENT
4.9'
4.7' 1.2'
4.7' 1.
1'
1.2'
HALLWAY TO
ANOTHER BUILDING
CONC WALK
(TYP)
CONC WALK
(TYP)
COVERED
AREA (TYP)
ASPHALT
DRIVEDROP INLET (TYP)
POST
(TYP)
GROUNDING ROD
(TYP)
16"
18"
DROP INLET
GRATE EL 7.75
N 8" PVC INV 5.34
NE 15" RCP INV 5.21
S 18" RCP INV 5.22 (DU)
SW 12" PVC INV 5.45
NW 6" PVC INV 5.41
RIM EL 9.89
N 6" VCP INV 6.34
SE 6" PVC INV 6.38
W 6" VCP INV 6.49 (DU)
DROP INLET
GRATE EL 8.75
NE 18" RCP INV 4.44 (DU)
W 18" RCP INV 3.75 (DU)
6" PVC
E INV 8.40
W INV 8.51
PROJECT LIMITS
PROJECT LIMITS
PROPOSED
STORMWATER
POND-1
PROPOSED
TRANSFORMER PAD
(SEE ELEC PLANS)
PROJECT LIMITS
TIE INTO EXISTING
SANITARY LINE,
INV. = 6.32' (FIELD
VERIFY INVERT)
46 LF OF 4" PVC @ 0.5%
PROPOSED 4" PVC
SANITARY
INV. = 4.06'
204 LF PVC
SANITARY FORCE
MAIN RELOCATION
TIE INTO
EXISTING
FORCE MAIN
TIE INTO
EXISTING
FORCE MAIN
TIE INTO
EXISTING
WATER MAIN
14 LF 2" PVC
DOMESTIC
SERVICE
PROPOSED 4"
CHILLED WATER
SERVICE
45 DEGREE BEND (MJ)
PROPOSED
FIRE HYDRANT
AND GATE
VALVE
50 LF 9" DIP WATER
MAIN RELOCATION
(RESTRAINED)
2" RPZ
BACKFLOW
PREVENTOR
9" X 2" TEE (MJ)
45° BEND (MJ)
45° BEND (MJ)
135 LF 6" PVC (DR-14)
FIRE SERVICE (RESTRAINED)
9" X 6" TEE (MJ)
PROPOSED 2"
GAS SERVICE
& METER
TIE INTO EXISTING
CHILLED WATER
LINE ADJACENT
TO BLDG 102
N1263804.56, E405399.39
N1263788.68, E405408.98
N1263631.92, E405381.72
TO EX MH-207A
(SEE ELEC PLANS)
PIV
PROPOSED 4"
FIRE SERVICE
(149 LF DR-14 PVC)
9" X 4" TEE (MJ)
FDC
TIE INTO EXISTING
6" WATER MAIN
AND VERTICAL
ADJUSTMENT
N1263604.77, E405353.44
N1263602.47, E405365.81
PROPOSED
UTILITY POLE
PROPOSED 1.5"
GAS SERVICE
TO GENERATOR
PROPOSED
COMMUNICATION
DUCT BANK (SEE
DRAWING TS100)
PROPOSED
FLUME (TYP.)
101 LF 18" HDPE
@ 0.005 FT/FT
DMH-2
RIM: 10.25
INV IN 5.10 (S)
INV IN 6.88 (E)
INV IN 5.10 SW (EX)
INV OUT 5.04 N (EX)
CO-2
RIM: 10.40
INV: 7.40
8" ROOF DRAIN
8" ROOF DRAIN
CO-3
RIM: 10.35
INV: 7.05
CO-2
RIM: 10.35
INV: 7.00
EXISTING LEGEND
EXISTING MANHOLES
EXISTING COMMUNICATION, UNDERGROUND
EXISTING NATURAL GAS, UNDERGROUND
EXISTING POWER, UNDERGROUND
EXISTING SANITARY SEWER, UNDERGROUND
EXISTING STORM SEWER, UNDERGROUND
EXISTING STORM SEWER, ROOF DRAIN
EXISTING SOLAR PANEL
EXISTING WATER, UNDERGROUND
EXISTING CURB
EXISTING EDGE OF PAVEMENT
EXISTING MINOR CONTOUR
EXISTING MAJOR CONTOUR
EXISTING TREES
EXISTING BOLLARD
BORING LOCATION
EXISTING SIGN
EXISTING LIGHT
EXISTING UTILITY POLE
EXISTING FENCE
EXISTING BUILDING
EXISTING SPOT ELEVATION100.55
EXISTING STORM SEWER, INLET
EXISTING SANITARY SEWER, CLEAN-OUT
EXISTING JUNCTION BOX
EXISTING WATER STRUCTURES
EXISTING VALVES
EXISTING SIDEWALK
PROJECT BOUNDARY LIMITS
EXISTING ASPHALT DRIVEWAY
EXISTING GRAVEL PAVEMENT
EXISTING OVERHEAD ELECTRIC
EXISTING OVERGROWTH
EXISTING TRANSFORMER
EXISTING SUPPORT POST
EXISTING DIRT DRIVE
PROPOSED LEGEND
PROPOSED CURB LINE
PROPOSED EDGE OF PAVEMENT
PROPOSED BUILDING OUTLINE
PROPOSED SIDEWALK
PROPOSED WATER MAIN
PROPOSED STORM SEWER
PROPOSED SANITARY SEWER
PROPOSED UNDERGROUND ELECTRIC
PROPOSED UNDERGROUND GAS
PROPOSED AREA DRAIN
PROPOSED DRAINAGE INLET
PROPOSED DRAINAGE MANHOLE
PROPOSED SANITARY MANHOLE
PROPOSED MAJOR CONTOUR
PROPOSED MINOR CONTOUR
PROPOSED BUILDING OVERHANG
PROPOSED BAHIA SOD
PROPOSED ASPHALT PAVEMENT
PROPOSED CURB STOP
PROPOSED TREELINE
PROPOSED DETECTABLE WARNING
PROPOSED DRAINAGE PIPE
PROPOSED TREES
PROPOSED POROUS ASPHALT PAVEMENT
PROPOSED UNDERGROUND TELECOM
PROPOSED TELECOM MANHOLE
PROPOSED SAND GROWN BAHIA SOD
Revisions DateRevisions Date
VA Project No.
RDC/JPA Project No.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Office of Construction and Facilities Management
CONSTRUCT
DENTAL CLINC
09/06/2022 APJS
516-349
BAY PINES, FL
BUILDING
100% 21001.00
Revisions Date
PENNONI ASSOCIATES INC.
5755 Rio Vista Dr
Clearwater, FL 33760 T 727.451.9561
Florida COA: 7819
1 65% DESIGN 05/24/2022
CONSTRUCTION SET
CS - 171_____________
UTILITY PLAN
00 20' 40'
N O
R
TH
SITE INFORMATION:
ADDRESS: 10000 BAY PINES BLVD
BAY PINES, FL 33744
OWNER: U.S. DEPT. OF VETERANS AFFAIRS
10000 BAY PINES BLVD
BAY PINES, PINELLAS COUNTY, FL 33744
ENGINEER: PENNONI
JASON SHERIDAN, PE
5755 RIO VISTA DRIVE
CLEARWATER, FL 33760
UTILITY NOTES:
1. ALL PIPE LENGTHS AND DISTANCES BETWEEN STRUCTURES ARE MEASURED FROM CENTER
OF STRUCTURE TO CENTER OF STRUCTURE ALONG A HORIZONTAL PLANE.
2. ALL STORM DRAINAGE PIPE SHALL BE LAID ON SMOOTH CONTINUOUS GRADES WITH NO
VISIBLE BENDS AT JOINTS.
3. BEDDING REQUIREMENTS SPECIFIED HEREIN ARE TO BE CONSIDERED AS MINIMUMS FOR
RELATIVELY DRY, STABLE EARTH CONDITIONS. ADDITIONAL BEDDING SHALL BE REQUIRED
FOR ROCK TRENCHES AND WET AREAS. CONTRACTOR SHALL HAVE THE RESPONSIBILITY TO
PROVIDE SUCH ADDITIONAL BEDDING AS MAY BE REQUIRED TO PROPERLY CONSTRUCT THE
WORK.
4. COMPACTION OF THE BACKFILL OF ALL TRENCHES SHALL BE COMPACTED TO THE DENSITY
OF 95% OF THEORETICAL MAXIMUM DRY DENSITY (ASTM D698). BACKFILL MATERIAL SHALL BE
FREE FROM ROOTS, STUMPS, OR OTHER FOREIGN DEBRIS AND SHALL BE PLACED IN LIFTS
NOT TO EXCEED 6 INCHES IN COMPACTED FILL THICKNESS. A REPORT FROM A
GEOTECHNICAL ENGINEER MAY BE REQUIRED BY THE PUBLIC WORKS INSPECTOR.
CORRECTION OF ANY TRENCH SETTLEMENT WITHIN A YEAR FROM THE DATE OF APPROVAL
WILL BE THE RESPONSIBILITY OF THE CONTRACTOR.
5. THE CONTRACTOR WILL ENSURE THAT POSITIVE AND ADEQUATE DRAINAGE IS MAINTAINED
AT ALL TIMES WITHIN THE PROJECT LIMITS. THIS MAY INCLUDE, BUT NOT BE LIMITED TO,
REPLACEMENT OR RECONSTRUCTION OF EXISTING DRAINAGE STRUCTURES THAT HAVE
BEEN DAMAGED OR REMOVED OR REGRADING AS REQUIRED BY THE ENGINEER, EXCEPT FOR
THOSE DRAINAGE ITEMS SHOWN AT SPECIFIC LOCATIONS AND HAVING SPECIFIC PAY ITEMS
IN THE DETAILED ESTIMATE. NO SEPARATE PAYMENT WILL BE MADE FOR ANY COSTS
INCURRED TO COMPLY WITH THIS REQUIREMENT.
6. CONTRACTOR IS RESPONSIBLE FOR ALL UTILITY CONNECTION FEES.
7. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO DETERMINE THE LOCATION OF ALL
EXISTING UNDERGROUND UTILITIES AND TO TAKE WHATEVER STEPS NECESSARY TO
PROVIDE FOR THEIR PROTECTION. THE ENGINEER ASSUMES NO RESPONSIBILITY FOR THE
LOCATIONS OF UTILITIES SHOWN OR NOT SHOWN. THE CONTRACTOR SHALL CONTACT THE
UTILITY COMPANIES FOR EXACT LOCATION OF THEIR UTILITIES PRIOR TO STARTING
CONSTRUCTION. IT SHALL BE THE SOLE RESPONSIBILITY OF THE CONTRACTOR TO REPAIR
AND REPLACE ANY AND ALL DAMAGE MADE TO UTILITIES BY THE CONTRACTOR.
8. THE CONTRACTOR SHALL COORDINATE LOCATION AND INSTALLATION OF ALL UNDERGROUND
UTILITIES AND APPURTENANCES TO MINIMIZE DISTURBANCE TO CURBING, PAVING, AND
COMPACTED SUBGRADE.
9. CONTRACTOR SHALL EXCAVATE ONLY AS MUCH TRENCH WHICH PIPE CAN BE INSTALLED AND
TRENCH BACKFILLED BY THE END OF EACH WORK DAY.
10. ALL UNDERGROUND UTILITY TRENCHES SHALL BE BACKFILLED WITH SAFE CLEAN FILL.
11.FLOW PRESSURE TO ALL FIRE HYDRANTS SHALL HAVE MINIMUM 600 GALLONS PER MINUTE AT
A MINIMUM RESIDUAL PRESSURE OF 20 POUNDS PER SQUARE INCH.
12. ALL TRENCHES SHALL BE PROPERLY SECURED AND BRACED.
13. ALL EXISTING CASTING AND INLET TOPS OR GRATES MUST BE ADJUSTED TO THE PROPOSED
GRADE, UNLESS OTHERWISE INDICATED.
14. ALL PROPOSED UTILITIES, INCLUDING ELECTRIC SERVICE, SHALL BE PLACED UNDERGROUND.
15. ALL CONNECTIONS TO EXISTING UTILITIES AND TESTING SHALL BE PERFORMED IN THE
PRESENCE OF UTILITY OWNERS AND PENNONI. CONNECTION LOCATIONS MUST BE
APPROVED IN FIELD AFTER PIPE IS EXPOSED. CONTRACTOR SHALL PROVIDE WRITTEN
REQUEST TO PENNONI WITH PROPOSED TIME AND DATE OF CONNECTION AT LEAST 5
WORKING DAYS IN ADVANCE OF PLANNED CONNECTION. COORDINATE WITH LOCAL
JURISDICTION ON THE CAPPING AND DISCONNECTING REQUIREMENTS FOR
16. ANY EXISTING SERVICES.ALL BUILDINGS CONTAINING KITCHENS / RESTAURANTS REQUIRE
GREASE TRAPS SIZED IN ACCORDANCE WITH THE EPA REGULATIONS WITHIN SANITARY
LATERALS.
17.CONTRACTOR SHALL CALL FOR A 000-SITE DEVELOPMENT MEETING WITH THE ENGINEERING
DEPARTMENT UTILITY CONSTRUCTION INSPECTORS PRIOR TO THE START OF ANY
CONSTRUCTION ACTIVITIES ON SITE.
18.ON SITE SANITARY SEWER IS PRIVATELY OWNED.
19. A SEPARATE PERMIT IS REQUIRED FOR THE SEWER CUT AND CAP. THE CUT AND CAP PERMIT
MUST BE OBTAINED BY A LICENSED PLUMBER, ISSUED, INSPECTED, AND COMPLETED PRIOR
TO THE ISSUANCE OF THE ASSOCIATED DEMOLITION PERMIT.
20.DOGHOUSE MANHOLES ARE NOT PERMITTED FOR SANITARY SEWER MANHOLES.
21.CONTRACTOR SHALL VERIFY MINIMUM SEPARATION BETWEEN THE OUTSIDE DIAMETER OF
WATER, RECLAIMED WATER, STORM SEWER AND SANITARY SEWER SYSTEMS (18" MINIMUM
VERTICAL AND 10' MINIMUM HORIZONTAL SEPARATIONS). UPON COMPLETION OF
CONSTRUCTION, THE CONTRACTOR SHALL PROVIDE WRITTEN VERIFICATION AND PHOTOS
DOCUMENTING THE MINIMUM SEPARATION AS CONSTRUCTED. CONSTRUCTION SHALL
COMPLY WITH 62-555, FAC
22.ALL WATER, WASTEWATER, AND RECLAIMED WATER LINES CROSSING OTHER UTILITY LINES
HAVE AT LEAST 18" VERTICAL CLEARANCE.
23.CONSTRUCTION SHALL MEET THE REQUIREMENTS OF NFPA 1 2013 EDITION CHAPTER 16 FIRE
SPRINKLER PROTECTION. SAFEGUARDING CONSTRUCTION, ALTERATION, AND DEMOLITION
OPERATIONS TO INCLUDE BUT NOT BE LIMITED TO COMPLYING WITH NFPA 241.
24.FIRE WATER SYSTEM PIPING
24.1. FIRE DEPARTMENT ACCESS AND WATER SUPPLY SHALL BE ESTABLISHED BEFORE ANY
VERTICAL CONSTRUCTION BEINGS. THE CONNECTION SHALL MEET THE REQUIREMENTS
OF NFPA 1 2015 EDITION, CHAPTER 18.
24.2. WHERE UNDERGROUND WATER MAINS AND HYDRANTS ARE TO BE INSTALLED, THEY
SHALL BE INSTALLED, COMPLETED AND IN SERVICE PRIOR TO CONSTRUCTION AS PER
NFPA-241.ALL UNDERGROUND FIRE LINES MUST BE INSTALLED PER NFPA-24 2013
EDITION BY A LICENSED CLASS 1, 2, OR 5 FIRE PROTECTION SYSTEM CONTRACTOR
WITH SEPARATE PERMIT AND PLANS.
24.3. POLYVINYL CHLORIDE (PVC):
24.3.1. FOUR (4) INCHES DIAMETER AND GREATER - CLASS 150 PIPE MEETING AWWA C-900
(DR 14). FIRE LINES, BACKFLOW PREVENTION AND APPURTENANCES SHALL COMPLY
WITH NFPA 24 WITH DR 14 PIPE (CLASS 200) AND TESTED AT 200 PSI. FOR 24 HOURS
IN ACCORDANCE WITH NFPA 24.
25.WATER MAIN AND FORCE MAIN SYSTEM TESTING
25.1. THE CONTRACTOR SHALL PUMP THE LINES TO A PRESSURE EQUAL TO OR GREATER
THAN 150 PSI OR 200 PSI (DR 14). SHOULD PRESSURE FALL BELOW 150 PSI DURING THE
TEST PERIOD, IT SHALL BE VOIDED AND RESTARTED. TEST PERIOD SHALL BE TWO (2)
HOURS. ALLOWABLE LEAKAGE SHALL BE COMPUTED IN ACCORDANCE WITH AWWA
MANUAL M23, LATEST REVISION.
26.POTABLE WATER AND FORCE MAIN FITTINGS
26.1. THRUST RESTRAINT:
26.2. ALL POTABLE WATER AND SEWER FORCE MAIN VALVES AND FITTINGS SHALL BE
RESTRAINED AGAINST THRUST FROM 150 PSI TEST PRESSURE BY FLANGED OR
"MEGALUG" TYPE CONNECTORS. ALL PIPE JOINTS LYING WITHIN THE LISTED MINIMUM
DISTANCE OF ANY FITTING OR VALVE SHALL ALSO BE RESTRAINED. WHEN CASINGS
FALL WITHIN THE MINIMUM DISTANCE FROM A FITTING, RESTRAIN ALL JOINTS INSIDE
THE CASING IN ADDITION TO THE REQUIRED MINIMUM LENGTH OF BURIED PIPE. PLEASE
REFERENCE THE RESTRAINT TABLE ON THE UTILITY PLAN WHICH DESCRIBES THE
MINIMUM LENGTH OF PIPE THAT SHALL BE CONTINUOUSLY RESTRAINED ON BOTH SIDES
OF DIFFERENT TYPES AND SIZES OF POTABLE WATER AND FORCE MAIN FITTINGS. RULE
62-555-320(21) (B)
27.NO EXISTING METERS ARE TO BE REMOVE FROM THE SITE.
28.ALL WATER LINES LOCATED AFTER BACKFLOW DEVICES AND METERS ARE CONSIDERED
PRIVATE.
29.A PRE-CONSTRUCTION MEETING SHALL BE SET UP TO DISCUSS THESE AND OTHER ISSUES
RESULTING IN THIS CONSTRUCTION PROJECT. THIS SHALL BE COORDINATED THROUGH THE
CONSTRUCTION SITE PROJECT MANAGER.
30.PRIOR TO ISSUANCE OF CO:
30.1. SUBMIT A MAINTENANCE AGREEMENT OF THE STORMWATER MAINTENANCE SYSTEM
SIGNED AND ACCEPTED BY THE PROJECT’S OWNER.
30.2. SUBMIT FIVE (5) 24”X36” SIGNED AND SEALED SETS OF RECORD DRAWINGS AND ONE (1)
ENGINEER OF RECORD CERTIFICATION LETTER CERTIFYING THAT THE PROJECT
INFRASTRUCTURE WAS CONSTRUCTED IN SUBSTANTIAL CONFORMANCE WITH THE
APPROVED DESIGN AND SPECIFICATIONS AND WILL MEET ALL GOVERNING AGENCIES
APPLICABLE RULES AND REGULATIONS. SHOULD THE RECORD DRAWINGS SHOW
SUBSTANTIAL DEVIATIONS FROM DESIGN CALCULATIONS AND PERMITTED PLANS, A
NARRATIVE IDENTIFYING THE CHANGES SHALL BE INCLUDED AS PART OF THE
CERTIFICATION LETTER.
30.3. PASS FINAL STORMWATER INSPECTION.
31.THE CONTRACTOR SHALL BE APPROVED FOR UTILITY SHUTDOWN REQUEST PRIOR TO START
OF UTILITY WORK. THE VA SHALL BE PRESENT AT POWER MAIN TIE IN.
32. UTILITY METERS SHALL BE IN ACCORDANCE WITH THE VA "ADVANCED UTILITY METERING
SYSTEM" SPECIFICATION (SECTION 25 10 10)
SOLAR PANEL INVERTER
METAL STAIRS
ON CONC PAD
(TYP)
LANDSCAPED
AREA (TYP)
LANDSCAPED
AREA (TYP)
EXISTING
OVERGROWTH
CONC
BASKETBALL
COURT
8" POLE
(TYP)
EXERCISE
AREA
2" METAL
POST
2" METAL PIPE
6" CURB
AROUND PLANTER
4.7'
1.
2'
1.
2'
4.7'
4.
7'
4.
7'
1.2'
4.7'
1.
2'
1.2' 4.
7'
4.
8'
1.
2'4.7'
4.7' 1.
1'
4.
7'
1.1'
4.7'
1.
2'
4.7' 1.
2'
5.1' 1.
2'
1.2'
5.
2'
4.
7'1.2'
4.
7'1.2'
4.7'
1.
2'
1.2'
4.
7'4.
7'1.2'
.2
18.6'
19.6' 4.
8' 44.1' 5.
9' 17.1'
.4
65.5'
.2
6.0'
.1
23.4'
.6
81.8'6.
0'
17.3'
.7
45.8'
.0
12"
10"
20" TWIN
14"
24"
20"
10"
12"
38"
12"
8"
10"
9" TWIN
18"
28"
12"
13"
14"
22"
6"
7" 7"
9" TWIN
36"
10"
34"
12" 12"
SOLAR PANEL
SOLAR PANEL
SOLAR PANEL
SOLA
R PANEL
ASPHALT
SOLAR PANEL
EQUIPMENT
4.9'
4.7' 1.2'
4.7' 1.
1'
1.2'
HALLWAY TO
ANOTHER BUILDING
CONC WALK
(TYP)
CONC WALK
(TYP)
COVERED
AREA (TYP)
ASPHALT
DRIVEDROP INLET (TYP)
POST
(TYP)
GROUNDING ROD
(TYP)
16"
18"
PIV
FDC
PROJECT LIMITS
PROJECT LIMITS
.0'
9.3' 52.7'
.6'
2.7'
1.9
1.1
4.0'
.9'
75.3'
PROPOSED
DENTAL CLINIC
BUILDING
11,373 SF
FFE: 11.00
.0'
PROPOSED
STORMWATER
POND-1
PROJECT LIMITS
EXISTING LEGEND
EXISTING MANHOLES
EXISTING COMMUNICATION, UNDERGROUND
EXISTING NATURAL GAS, UNDERGROUND
EXISTING POWER, UNDERGROUND
EXISTING SANITARY SEWER, UNDERGROUND
EXISTING STORM SEWER, UNDERGROUND
EXISTING STORM SEWER, ROOF DRAIN
EXISTING SOLAR PANEL
EXISTING WATER, UNDERGROUND
EXISTING CURB
EXISTING EDGE OF PAVEMENT
EXISTING MINOR CONTOUR
EXISTING MAJOR CONTOUR
EXISTING TREES
EXISTING BOLLARD
BORING LOCATION
EXISTING SIGN
EXISTING LIGHT
EXISTING UTILITY POLE
EXISTING FENCE
EXISTING BUILDING
EXISTING SPOT ELEVATION100.55
EXISTING STORM SEWER, INLET
EXISTING SANITARY SEWER, CLEAN-OUT
EXISTING JUNCTION BOX
EXISTING WATER STRUCTURES
EXISTING VALVES
EXISTING SIDEWALK
PROJECT BOUNDARY LIMITS
EXISTING ASPHALT DRIVEWAY
EXISTING GRAVEL PAVEMENT
EXISTING OVERHEAD ELECTRIC
EXISTING OVERGROWTH
EXISTING TRANSFORMER
EXISTING SUPPORT POST
EXISTING DIRT DRIVE
PROPOSED LEGEND
PROPOSED CURB LINE
PROPOSED EDGE OF PAVEMENT
PROPOSED BUILDING OUTLINE
PROPOSED SIDEWALK
PROPOSED WATER MAIN
PROPOSED STORM SEWER
PROPOSED SANITARY SEWER
PROPOSED UNDERGROUND ELECTRIC
PROPOSED UNDERGROUND GAS
PROPOSED AREA DRAIN
PROPOSED DRAINAGE INLET
PROPOSED DRAINAGE MANHOLE
PROPOSED SANITARY MANHOLE
PROPOSED MAJOR CONTOUR
PROPOSED MINOR CONTOUR
PROPOSED BUILDING OVERHANG
PROPOSED BAHIA SOD
PROPOSED ASPHALT PAVEMENT
PROPOSED CURB STOP
PROPOSED TREELINE
PROPOSED DETECTABLE WARNING
PROPOSED DRAINAGE PIPE
PROPOSED TREES
PROPOSED POROUS ASPHALT PAVEMENT
PROPOSED UNDERGROUND TELECOM
PROPOSED TELECOM MANHOLE
PROPOSED TELECOM HANDHOLE
PROPOSED SAND GROWN BAHIA SOD
TREE REMOVABLE TABLE
TYPE
ORNAMENTAL TREE
ORNAMENTAL TREE
ORNAMENTAL TREE
PINE TREE
PINE TREE
PINE TREE
PINE TREE
PINE TREE
OAK TREE
OAK TREE
OAK TREE
OAK TREE
PINE TREE
PINE TREE
SIZE (IN.)
17"
14"
12"
6"
20"
20"
26"
24"
8"
28"
20"
12"
10"
12"
TOTAL REMOVED 229 INCHES
Revisions DateRevisions Date
VA Project No.
RDC/JPA Project No.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Office of Construction and Facilities Management
CONSTRUCT
DENTAL CLINC
09/06/2022 APJS
516-349
BAY PINES, FL
BUILDING
100% 21001.00
Revisions Date
PENNONI ASSOCIATES INC.
5755 Rio Vista Dr
Clearwater, FL 33760 T 727.451.9561
Florida COA: 7819
1 65% DESIGN 05/24/2022
CONSTRUCTION SET
LS - 401_____________
LANDSCAPE PLAN
00 20' 40'
N O
R
TH
1. EACH CANOPY, ACCENT TREE, PALM TREE, AND SHRUBS ARE REQUIRED TO HAVE
A 2-INCH LAYER OF ORGANIC MULCH NO LESS THAN 36-INCHES BEYOND ITS TRUNK
IN ALL DIRECTIONS
2. CANOPY TREES PLANTED WITHIN 7 FEET OF ANY ROADWAY, SIDEWALK, OR PUBLIC
UTILITY MUST HAVE A 24" ROOT BARRIER MATERIAL INSTALLED
3. ROOT BARRIER TO BE INSTALLED ON TREES MARKED (RB)
4. SOD ALL AREAS DISTURBED BY CONSTRUCTION NOT OTHERWISE PAVED OR
PLANTED. RESTORE AND SOD ALL RIGHT OF WAY AREAS DISTURBED BY
CONSTRUCTION.
LANDSCAPE NOTES:
KEY QTY SCIENTIFIC NAME COMMON NAME MIN. INITIAL SIZE MAXIMUM HEIGHT ESTIMATED CROWN (20-YEAR) NOTES
CANOPY TREES
SO 3 QUERCUS VIRGINIANA SOUTHERN OAK 39" CALIPER 80' 60' MIN. NATIVE, AVERAGE 30" DBH AT MATURITY
RM 6 ACER RUBRUM RED MAPLE 38" CALIPER 80' 25' MIN. NATIVE, AVERAGE 24" DBH AT MATURITY
REPLACEMENT TREE DBH AT
MATURITY 324" > 229"
PLANTING SCHEDULE
SO
RM
RM
RM
RM
RM
POND-1
HORIZONTAL SCALE: 1" = 20'
VERTICAL SCALE: 1" = 2'
-0+25 0+00 1+00 2+00 2+25
OS-1 TO DMH-EX
HORIZONTAL SCALE: 1" = 20'
VERTICAL SCALE: 1" = 2'
-0+25 0+00 1+00 2+00
PROPOSED SURFACE
PROPOSED SURFACE
PROPOSED
SURFACE
EXISTING
SURFACE
EXISTING SURFACE
I-2 DMH-1
HORIZONTAL SCALE: 1" = 20'
VERTICAL SCALE: 1" = 2'
-0+25 0+00 1+00
EXISTING
SURFACE
EXISTING 4" PVC SANITARY
FORCEMAIN TO BE ADJUSTED
(INV. 2.02)
EXISTING 9" DIP WATER
LINE TO BE ADJUSTED
(INV. 3.35)
EXISTING 9" DIP WATER
LINE TO BE ADJUSTED
(INV. 3.78)
POND-1
POND-1
38"
14"
22" 16"
18" A-3
DRI-1
PROPOSED
STORMWATER
POND-1
8.15
(LP)
8.39
8.06
8.05
8.38
8.54
8.90
8.00
8.42
8.66
(HP)
8.10
(LP)
9.23
9.51
9.34
9.20 8.95
2.
7%
1.
1%
2.2%
3.
5%
3.8%
3.8%
1.8%
2.
0%
9.12
9.42
9.29
8.71
8.43
8.17
(LP)
3.
9%
7.7%
2.
2%
10.00
9.23
9.62
PROPOSED
FLUME (TYP.)
Revisions DateRevisions Date
VA Project No.
RDC/JPA Project No.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Office of Construction and Facilities Management
CONSTRUCT
DENTAL CLINC
09/06/2022 APJS
516-349
BAY PINES, FL
BUILDING
100% 21001.00
Revisions Date
PENNONI ASSOCIATES INC.
5755 Rio Vista Dr
Clearwater, FL 33760 T 727.451.9561
Florida COA: 7819
1 65% DESIGN 05/24/2022
CONSTRUCTION SET
CS - 401_____________
STORM SEWER PROFILES
00 20' 40'
N O
R
TH
PROPOSED SANITARY FORCE MAIN ADJUSTMENT
HORIZONTAL SCALE: 1" = 20'
VERTICAL SCALE: 1" = 2'
-0+25 0+00 1+00 2+00 2+25
EXISTING 15" RCP
DRAINAGE (INV. 5.10)
PROPOSED 2"
PVC WATER
(INV. 3.60)
EXISTING 2.25"
DIP WATER
(INV. 7.37)
EXISTING 9" DIP WATER
LINE TO BE ADJUSTED
(INV. 3.35)
PROPOSED 15" RCP
DRAINAGE (INV. 5.44)
PROPOSED WATER LINE ADJUSTMENT
HORIZONTAL SCALE: 1" = 20'
VERTICAL SCALE: 1" = 2'
-0+50 0+00 1+00 2+00 2+50
PROPOSED 15" RCP
DRAINAGE (INV. 5.53)
EXISTING 4" SANITARY
FORCE MAIN TO BE
ADJUSTED (INV. 2.02)
EXISTING 2.25" DIP WATER
(INV. 7.37)
EXISTING 4" SANITARY
FORCE MAIN TO BE
ADJUSTED (INV. 2.02)
EXISTING 18" RCP
DRAINAGE (INV. 5.04)
" M
IN
" M
IN
" M
IN
" M
IN
PROPOSED 15" RCP
DRAINAGE (INV. 5.10)
PROPOSED
SURFACE
PROPOSED
SURFACE
EXISTING SURFACE EXISTING SURFACE
PROPOSED 2.75"
ADJUSTMENT FOR
EXISTING 4 " PVC
FORCE MAIN (127 LF)
PROPOSED 2.85"
ADJUSTMENT FOR
EXISTING 9 " PVC PIPE
(197 LF)
3' MINIMUM
EXISTING 9" DIP WATER
LINE TO BE ADJUSTED
(INV. 3.35)
" M
IN
PROPOSED 2.5"
CHILLED WATER
SERVICE
(INV. 8.05)
PROPOSED 2.5"
CHILLED WATER
SERVICE
(INV. 8.05)
Revisions DateRevisions Date
VA Project No.
RDC/JPA Project No.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Office of Construction and Facilities Management
CONSTRUCT
DENTAL CLINC
09/06/2022 APJS
516-349
BAY PINES, FL
BUILDING
100% 21001.00
Revisions Date
PENNONI ASSOCIATES INC.
5755 Rio Vista Dr
Clearwater, FL 33760 T 727.451.9561
Florida COA: 7819
1 65% DESIGN 05/24/2022
CONSTRUCTION SET
CS - 402_____________
STORM SEWER PROFILES
00 20' 40'
SANITARY FORCE MAIN CONFLICT TABLE
CONFLICT
NUMBER CONFLICT NOTES PIPE ELEVATIONS
SANITARY SEWER SERVICE TO PASS
UNDER WATER LINE A 12" MINIMUM
CLEARANCE.
WATER LINE BOTT.: 3.35
SANITARY FORCE MAIN TOP:
2.35
2 SANITARY SEWER SERVICE TO PASS
UNDER 15" EXISTING DRAINAGE LINE.
STORM DRAINAGE BOTT.:
5.10
SANITARY FORCE MAIN TOP:
2.35
3 SANITARY SEWER SERVICE TO PASS
UNDER 18" EXISTING DRAINAGE LINE.
STORM DRAINAGE BOTT.:
5.04
SANITARY FORCE MAIN TOP:
2.35
SANITARY SEWER SERVICE TO PASS
UNDER WATER LINE WITH A 12" MINIMUM
CLEARANCE.
WATER LINE BOTT.: 3.35
SANITARY FORCE MAIN TOP:
2.35
5 SANITARY SEWER SERVICE TO PASS
UNDER WATER LINE.
WATER LINE BOTT.: 3.60
SANITARY FORCE MAIN TOP:
2.35
6 SANITARY SEWER SERVICE TO PASS
UNDER WATER LINE.
WATER LINE BOTT.: 7.37
SANITARY FORCE MAIN TOP:
2.35
7 SANITARY SEWER SERVICE TO PASS
UNDER 15" PROPOSED DRAINAGE LINE.
STORM DRAINAGE BOTT.:
5.44
SANITARY FORCE MAIN TOP:
2.35
WATER LINE CONFLICT TABLE
CONFLICT
NUMBER CONFLICT NOTES PIPE ELEVATIONS
WATER LINE TO PASS OVER SANITARY
FORCE MAIN WITH A 12" MINIMUM
CLEARANCE.
WATER MAIN BOTT.: 3.35
SANITARY FORCE MAIN TOP:
2.35
2 WATER LINE TO PASS UNDER 15" EXISTING
DRAINAGE LINE.
STORM DRAINAGE BOTT.:
5.10
WATER LINE TOP: 4.10
3 WATER LINE TO PASS UNDER CHILLED
WATER SERVICE.
CHILLED WATER SERVICE
BOTT.: 8.05
WATER LINE TOP: 4.10
WATER LINE TO PASS OVER SANITARY
FORCE MAIN WITH A 12" MINIMUM
CLEARANCE.
WATER MAIN BOTT.: 3.35
SANITARY FORCE MAIN TOP:
2.35
5 WATER LINE TO PASS UNDER DIP WATER
LINE.
DIP WATER LINE BOTT.: 7.37
WATER LINE TOP: 4.10
6 WATER LINE TO PASS UNDER 15"
PROPOSED DRAINAGE LINE.
STORM DRAINAGE BOTT.:
5.53
WATER LINE TOP: 4.10
Revisions DateRevisions Date
VA Project No.
RDC/JPA Project No.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Office of Construction and Facilities Management
CONSTRUCT
DENTAL CLINC
09/06/2022 APJS
516-349
BAY PINES, FL
BUILDING
100% 21001.00
Revisions Date
PENNONI ASSOCIATES INC.
5755 Rio Vista Dr
Clearwater, FL 33760 T 727.451.9561
Florida COA: 7819
1 65% DESIGN 05/24/2022
CONSTRUCTION SET
CK - 601_____________
SITE DETAILS
DETAIL- POND 1
N.T.S.
DETAIL-
N.T.S.
ELEV: 8.00
6" 6"2'
6" 6"
3" 6" 6"
6" 16"
6" 6"
2'
" 3"
3" 18"
6"2'8'5' (MIN)
1' 2'
1'
CONCRETE FLUME
N.T.S.
DETAIL-
NOTE:
1. PAVING CONCRETE SHALL HAVE A MINIMUM
COMPRESSIVE STRENGTH OF 4,000 PSI AT
28-DAYS, ASTM C-94, AND:
A.) CONCRETE COMPRESSIVE STRENGTH; 4,000 PSI.
DESIGN FOR AVERAGE 4,475 PSI; 1" COARSE
AGGREGATE.
B.) CONCRETE FELXURAL STRENGTH; 575 PSI. DESIGN
FOR AVERAGE 620 PSI.
C.) CONCRETE SHALL CONTAIN MACRO-STYLE
SYNTHETIC FIBER REINFORCEMENT AT A RATE OF 1.5
LBS/CY OF MIX. FIBER LENGTH SHALL BE 12"-2 14" IN
LENGTH.
SYNTHETIC FIBERS SHALL COMPLY WITH ASTM C1116.
C.1) CONCRETE SLUMP - 3 INCHES
C.2) WATER/CEMENTITIOUS MATERIAL RATIO - 0.48
(FLYASH 20% MAXIMUM BY TOTAL WEIGHT)
C.3) AIR CONTENT - 5%
C.4) WATER REDUCER, RETARDER, TYPE D
DETAIL- WHEEL STOPS - REINFORCED CONCRETE
N.T.S.
DETAIL-
N.T.S.
DETAIL- DOUBLE CHECK DETECTOR VALVE ASSEMBLYDETAIL-
N.T.S.
DETAIL- DOMESTIC RPZ ASSEMBLYDETAIL-
N.T.S.
ELEV: 5.00
DETAIL- SANITARY MANHOLE DETAILDETAIL-
N.T.S.
DETAIL- PC DOG HOUSE MANHOLE DETAILDETAIL-
N.T.S.
10. UTILITY METERS SHALL BE IN ACCORDANCE WITH
THE VA "ADVANCED UTILITY METERING SYSTEM"
SPECIFICATION (SECTION 25 10 10)
| RDCJP21001 -VA Bay Pines Dental Clinic Structural V20 100% Bid Set S&S |
| S001 - STRUCTURAL GENERAL NOTES |
| S002 - WIND TABLES & SCHEDULES |
| SB100 - FOUNDATION PLAN |
| Bay Pines VA Dental Clinic - 100% Construction Set - Civil Plans |
| VF-041 |
| GC-051 - Layout1 |
| GC-052 - Layout1 |
| GC-053 - Layout1 |
| CD-071 - Layout1 |
| GK-072 - Layout1 |
| CS-100 - Layout1 |
| CS-101 - Layout1 |
| CS-151 - Layout1 |
| CS-170 - CS-171 |
| CS-171 - Layout1 |
| LS-401 - LANDSCAPE PLAN |
| CS-401 - Layout1 |
| CS-402 - Layout1 |
| CK-601 - Layout1 |
| CK-602 - Layout1 |