This structural drawing package outlines the design and construction of a dental clinic addition at the Bay Pines VA Medical Center. The project involves demolishing an existing modular building and constructing a new clinic structure, along with associated site work including a permeable pavement parking lot and walkways. The structural steel, concrete, and masonry design is presented, along with specifications for materials and construction methods. Foundation systems, floor and roof framing, and building enclosure details are provided. The package appears to provide the necessary information for contractors to prepare bids for the clinic construction in accordance with the design.
View the file
Other files
Show all 19
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
NOTE: REFER TO MANUFACTURERS SHOP
DRAWINGS FOR ACTUAL SIZE & DIMENSIONS
2'-6"
3' -0
PLAN
SECTION A-A
31"
31"
Revisions DateRevisions Date
VA Project No.
RDC/JPA Project No.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Office of Construction and Facilities Management
CONSTRUCT
DENTAL CLINC
09/06/2022 APJS
516-349
BAY PINES, FL
BUILDING
100% 21001.00
Revisions Date
PENNONI ASSOCIATES INC.
5755 Rio Vista Dr
Clearwater, FL 33760 T 727.451.9561
Florida COA: 7819
1 65% DESIGN 05/24/2022
CONSTRUCTION SET
CK - 602_____________
SITE DETAILS
DETAIL- OUTLET STRUCTURE OS-1DETAIL-
N.T.S.
DETAIL- UTILITY CROSSING DETAILDETAIL-
N.T.S.
DETAIL- DISABLED PARKING/SIGNING
N.T.S.
DETAIL-
N.T.S.
AA
SECTION A - A
METAL POST
SIGN DETAIL
FINE
$250 MAX
DETAIL- ADA PARKING/PAVEMENT MARKINGS TYPICAL DETAILS
N.T.S.
DETAIL-
N.T.S.
NOTES:
MANDATORY
DETAIL- POROUS PAVEMENT
N.T.S.
DETAIL-
N.T.S.
FRICTION COURSE AGGREGATE
GRADATION
U.S. STANDARD
SIEVE SIZE
PERCENT PASSING BY
WEIGHT
5/8" 100%
1/2" 95-100%
3/8" 70-95%
#4 20-40%
#8 10-20%
#40 0-8%
#200 0-3%
TYPE D CURB 4" POROUS PAVEMENT
FRICTION COURSE
RIBBON CURB
LEVEL SPREADER
6" AASHTO # 57
AGGREGATE
(CLEAN WASHED)
NON-WOVEN
GEOTEXTILE FABRIC
(ALL SIDES)
12" MIN OVERLAP
This item has been digitally signed and sealed by Eglantina Vrusho on the date adjacent to the seal. Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies.
NO. 79006
STATE OF
LORIDAF
P R
O
FESS IONAL ENGINEE
R
L ICENSEEG
LANT INA VRUSHO
Florida P.E. 79006
(727) 536-8772
Eglantina Vrusho, P.E.
Pennoni Project No. RDCJP21001
Florida Coa 7819
Clearwater, FL. 33760-3137 5755 Rio Vista Drive
VA Project No.
RDC/JPA Project No.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
STRUCTURAL
DOCUMENTSU.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Office of Construction and Facilities Management
EV NM
/3
/2
:5
:2
P
M
CONSTRUCT DENTAL CLINIC
02/03/2023
STRUCTURAL GENERAL NOTES
S001
516-349
BAY PINES VAMC
AMBER MILTON
21005.00100% Construction Set
STRUCTURAL SPECIFICATIONS
MISCELLANEOUS
1. THESE ABBREVIATED DRAWING SPECIFICATIONS ARE WRITTEN TO MATCH THE BOOK SPECIFICATIONS.
IF THERE ARE ANY ITEMS THAT DO NOT CORRESPOND EXACTLY AS WRITTEN, THE MORE STRINGENT WILL
TAKE PRECEDENCE.
2. THE STRUCTURAL SYSTEM IS UNSTABLE UNTIL ALL CONNECTIONS HAVE BEEN MADE AND ALL CONCRETE HAS REACHED ITS MINIMUM DESIGN STRENGTH, AS SHOWN IN THE STRUCTURAL DOCUMENTS.
3. CONTRACTOR IS RESPONSIBLE FOR MEANS AND METHODS OF CONSTRUCTION TO ENSURE THE
SAFETY OF THE BUILDING UNTIL STRUCTURAL SYSTEM IS COMPLETED. THIS INCLUDES, BUT IS NOT LIMITED
TO, THE ADDITION OF WHATEVER TEMPORARY BRACING, SHORING, GUYS OR TIE-DOWNS THAT MAY BE
NECESSARY. SUCH MATERIAL SHALL BE REMOVED AND SHALL REMAIN THE PROPERTY OF THE
CONTRACTOR AFTER COMPLETION OF THE PROJECT.
4. CONTRACTOR TO SUPPORT, BRACE AND SECURE EXISTING STRUCTURE AS REQUIRED. CONTRACTOR
IS SOLELY RESPONSIBLE FOR THE SAFETY OF THE BUILDING DURING CONSTRUCTION.
5. APPLICABLE BUILDING CODE: 7TH EDITION (2020) FLORIDA BUILDING CODE.
6. GRAVITY DESIGN LOADS:
SUPERIMPOSED SUPERIMPOSED
AREA LIVE LOAD DEAD LOAD
ROOF 20 PSF 20 PSF
7. WIND DESIGN CRITERIA:
ULTIMATE WIND SPEED: VULT =146 MPH (3 SECOND GUST)
EQUIVALENT NOMINAL BASIC WIND SPEED VASD = 113 MPH (3 SECOND GUST)
RISK CATEGORY = II
EXPOSURE CATEGORY = C
ENCLOSED BUILDING INTERNAL PRESSURE COEFFICIENT, GCPI= +/-0.18
WIND BORNE DEBRIS REGION
8. ALL MATERIALS AND WORKMANSHIP SHALL BE IN ACCORDANCE WITH THE REFERENCED BUILDING
CODE.
9. COORDINATE ALL DIMENSIONS AND ELEVATIONS WITH THE ARCHITECTURAL DRAWINGS. DO NOT
SCALE DRAWINGS.
10. CONTACT ENGINEER WITH ANY QUESTIONS OR DISCREPANCIES FOUND ON
DRAWINGS.
11. SECTIONS AND DETAILS ARE REFERENCED IN TYPICAL LOCATIONS BUT ALSO APPLY TO ALL OTHER
SIMILAR CONDITIONS.
12. CONTRACTOR TO VERIFY ALL EXISTING DIMENSIONS, ELEVATIONS, AND CONDITIONS PRIOR TO
BEGINNING CONSTRUCTION.
13. SUBMIT SHOP DRAWINGS AS REQUIRED HEREIN. ALLOW FOR TWO WEEKS REVIEW TIME AFTER RECEIPT OF SUBMITTALS BY THIS FIRM. ALL SUBMITTALS SHALL BE CHECKED AND SIGNED BY THE GENERAL CONTRACTOR AND SIGNED/SEALED BY THE DELEGATED ENGINEER, WHERE SPECIFIED HEREIN.
14. CONTRACTOR SHALL NOT BE RELIEVED FROM RESPONSIBILITY FOR ERRORS OR OMISSIONS IN SHOP
DRAWINGS OR MIX DESIGNS BY THE ENGINEER'S REVIEW THEREOF.
15. ANY CHANGES TO THE STRUCTURE SHALL HAVE BEEN REVIEWED AND APPROVED IN WRITING BY THE
ENGINEER PRIOR TO COMMENCING WORK ON ITEMS AFFECTED.
16. CONTRACTOR SHALL NOTIFY THIS OFFICE WHEN THE STRUCTURAL SYSTEM IS SUBSTANTIALLY
COMPLETED, AND BEFORE SHEATHING, CEILINGS, OR ROOFING IS INSTALLED.
HAND RAILS
1. AN ENGINEER REGISTERED IN THE STATE OF FLORIDA SHALL DESIGN RAILING SYSTEM AND
CONNECTION OF IT TO THIS STRUCTURE.
2. SUBMIT SHOP DRAWINGS BEARING THE EMBOSSED SEAL AND THE SIGNATURE OF THE ENGINEER FOR
REVIEW PRIOR TO FABRICATION.
3. THE CONFIGURATION OF THE RAILING SYSTEM SHALL BE AS SHOWN ON THE ARCHITECTURAL
DRAWINGS.
4. RAILING SYSTEM AND CONNECTIONS SHALL BE DESIGNED FOR APPLICABLE LOADS AS INDICATED ON THE PLANS AND IN THE BUILDING CODE. THE LOADS SHALL BE CLEARLY INDICATED ON SHOP DRAWINGS.
5. SHOP DRAWINGS SHALL SHOW AND SPECIFY CONNECTIONS UTILIZED WITHIN THE RAILING SYSTEM AS WELL AS CONNECTIONS TO AND LOADS IMPOSED UPON THE STRUCTURAL SYSTEM SHOWN ON THESE
PLANS.
GLAZED CURTAIN WALL, STOREFRONT, WINDOW AND DOOR SYSTEMS
1. EXTERIOR GLAZED OPENINGS SHALL BE DESIGNED IN ACCORDANCE WITH ACCEPTED ENGINEERING
PRINCIPLES AND GOVERNING CODES.
2. THIS BUILDING HAS BEEN DESIGNED AS "ENCLOSED". REFER TO THE STRUCTURAL DRAWINGS FOR
COMPONENTS AND CLADDING MINIMUM DESIGN WIND PRESSURES.
3. IF THIS SITE IS LOCATED WITHIN A WIND BORNE DEBRIS REGION, AS SHOWN IN FIGURE 1609 OF THE FLORIDA BUILDING CODE, ALL EXTERIOR GLAZED OPENINGS SHALL BE DESIGNED AND TESTED FOR MISSILE
IMPACT OR PROTECTED BY APPROVED SCREENS OR SHUTTERS.
4. A LICENSED PROFESSIONAL ENGINEER SHALL DESIGN THE EXTERIOR GLAZED SYSTEMS, SHOP
DRAWINGS, AND OVERSEE ANY LOAD TESTING.
5. SIGNED AND SEALED SHOP DRAWINGS, NOTICE OF ACCEPTANCE (NOA), OR FLORIDA PRODUCT
APPROVAL DOCUMENTATION SHALL BE SUBMITTED IN ACCORDANCE WITH THE ARCHITECT'S
REQUIREMENTS.
6. GLAZING AND WINDOW SYSTEMS SHALL BE DESIGNED TO RESIST BLAST LOADING AND PROVIDE THE LEVEL OF PROTECTION AS SPECIFIED ON THESE DRAWINGS. SEE BLAST DESIGN CRITERIA ON S002.
THRESHOLD BUILDINGS
1. IF THE BUILDING DEPARTMENT CLASSIFIES THIS PROJECT AS A THRESHOLD BUILDING, A SPECIAL
INSPECTOR SHALL BE RETAINED IN ACCORDANCE WITH FLORIDA STATUTES.
2. THE SPECIAL INSPECTOR SHALL BE LICENSED BY THE FLORIDA BOARD OF PROFESSIONAL ENGINEERS AND SHALL STRICTLY FOLLOW THE "STRUCTURAL INSPECTION PLAN", PREPARED BY THIS OFFICE.
3. RESUMES OF THE SPECIAL INSPECTOR AND ANY OF HIS AUTHORIZED REPRESENTATIVES SHALL BE SUBMITTED TO THIS OFFICE FOR REVIEW. MCCARTHY RESERVES THE RIGHT TO REJECT ANY INSPECTOR
THAT DOES NOT MEET OUR QUALIFICATIONS.
DELEGATED ENGINEER
1. WHERE NOTED HEREIN, A LICENSED PROFESSIONAL (DELEGATED) ENGINEER SHALL BE RETAINED TO
DESIGN THE PRODUCT OR ASSEMBLY.
2. THE DELEGATED ENGINEER SHALL BE EXPERIENCED IN THE DESIGN OF THE REFERENCED PRODUCT
OR ASSEMBLY.
3. THE DELEGATED ENGINEER MUST BE PROVIDED WITH A COPY OF THESE DRAWINGS AND
SPECIFICATIONS.
4. IT IS THE DELEGATED ENGINEER'S RESPONSIBILITY TO REVIEW THE ENGINEER OF RECORD'S WRITTEN ENGINEERING REQUIREMENTS AND AUTHORIZATION FOR THE DELEGATED ENGINEERING DOCUMENT TO
DETERMINE THE APPROPRIATE SCOPE OF ENGINEERING.
5. THE DELEGATED ENGINEERING DOCUMENT SHALL COMPLY WITH THE WRITTEN ENGINEERING
REQUIREMENTS RECEIVED FROM THE ENGINEER OF RECORD. THEY SHALL INCLUDE THE PROJECT IDENTIFICATION AND THE CRITERIA USED AS A BASIS FOR ITS PREPARATION. IF A DELEGATED ENGINEER DETERMINES THERE ARE DETAILS, FEATURES OR UNANTICIPATED PROJECT LIMITS WHICH CONFLICT WITH THE WRITTEN ENGINEERING REQUIREMENTS PROVIDED BY THE ENGINEER OF RECORD, THE DELEGATED ENGINEER SHALL TIMELY CONTACT THE ENGINEER OF RECORD FOR RESOLUTION OF CONFLICTS.
6. THE DELEGATED ENGINEER SHALL FORWARD THE DELEGATED ENGINEERING DOCUMENT TO THE ENGINEER OF RECORD FOR REVIEW. ALL FINAL DELEGATED ENGINEERING DOCUMENTS REQUIRE THE
IMPRESSED SEAL AND SIGNATURE OF THE DELEGATED ENGINEER AND INCLUDE:
A) DRAWINGS INTRODUCING ENGINEERING INPUT SUCH AS DEFINING THE CONFIGURATION OR
STRUCTURAL CAPACITY OF STRUCTURAL COMPONENTS AND/OR THEIR ASSEMBLY INTO
STRUCTURAL SYSTEMS.
B) CALCULATIONS.
SITE WORK
1. A SUBSURFACE INVESTIGATION HAS BEEN COMPLETED AT THE PROJECT SITE BY TERRACON
CONSULTANTS,INC.. SOIL BORING LOGS AND SITE PREPARATION PROCEDURES ARE INCLUDED IN THE PROJECT SOILS REPORT, DATED JULY 22,2021, WHICH IS AN INTEGRAL PART OF THESE CONTRACT
DOCUMENTS.
2. SITE WORK SHALL BE DONE IN STRICT ACCORDANCE WITH THE PROJECT SOILS REPORT.
3. CONTRACTOR SHALL REVIEW THE SOILS REPORT AND VERIFY THAT TEST BORINGS HAVE BEEN DONE
UNDER ALL BUILDING(S) PRIOR TO BEGINNING EARTHWORK.
INDEX OF DRAWINGS
SHEET NUMBER SHEET NAME Discipline
S001 STRUCTURAL GENERAL NOTES STRUCTURE
S002 WIND TABLES & SCHEDULES STRUCTURE
SB100 FOUNDATION PLAN STRUCTURE
SF100 ROOF FRAMING PLAN STRUCTURE
SF101 ALTERNATIVE ROOF FRAMING
SJ501 FOUNDATION DETAILS STRUCTURE
SJ502 DETAILS STRUCTURE
SJ510 FRAMING DETAILS STRUCTURE
SJ601 WALL SECTIONS STRUCTURE
SJ602 WALL SECTIONS STRUCTURE
SJ901 ISOMETRIC VIEW STRUCTURE
4. INFORMATION FROM GEOTECHNICAL REPORT:
A) DESIGN SOIL BEARING PRESSURE = 2000 PSF.
B) ESTIMATED MAXIMUM SETTLEMENT = 1 INCH.
C) ESTIMATED DIFFERENTIAL SETTLEMENT =1/2 INCH.
5. A QUALIFIED TESTING LABORATORY SHALL BE RETAINED TO PERFORM THE FOLLOWING MINIMUM
TESTS. REFER TO SOILS REPORT FOR ANY ADDITIONAL TESTING.
A) ONE DENSITY TEST FOR EACH 2,000 SQUARE FEET OF COMPACTED SUBGRADE AND
COMPACTED FILL.
B) ONE DENSITY TEST AT EACH COLUMN FOOTING.
C) ONE DENSITY TEST PER 50 FEET OF WALL FOOTING.
6. ONE COPY OF ALL TEST REPORTS SHALL BE SENT DIRECTLY TO OWNER, ARCHITECT, STRUCTURAL
ENGINEER, AND GENERAL CONTRACTOR.
7. FOUNDATION WALLS THAT RETAIN EARTH SHALL BE BRACED AGAINST BACKFILLING PRESSURES UNTIL
FLOOR SLABS AT TOP AND BOTTOM ARE IN PLACE.
8. THE SIDES OF FOOTINGS MAY BE EARTH-FORMED IF THE EXCAVATION CAN BE KEPT VERTICAL, CLEAN, AND STABLE, OTHERWISE, PLYWOOD FORMS MUST BE USED.
9. EXERCISE CARE WHEN COMPACTING NEAR ADJACENT STRUCTURES. FOLLOW THE
RECOMMENDATIONS IN THE SOILS REPORT AND DOCUMENT EXISTING CONDITIONS WITH
PHOTOGRAPHS PRIOR TO STARTING WORK.
10. PRIOR TO CONSTRUCTION, CONTRACTOR SHALL LOCATE ALL EXISTING UNDERGROUND UTILITY LINES, TANKS, ETC. WITHIN THE CONSTRUCTION AREA AND RELOCATE THEM AS DIRECTED BY THE CIVIL
ENGINEER.
CAST IN PLACE CONCRETE
1. ALL CAST-IN-PLACE CONCRETE WORK INCLUDES REINFORCING STEEL AND RELATED WORK SHOWN INCLUDING FORMWORK, SETTING ANCHOR BOLTS, PLATES, FRAMES, DOWELS FOR MASONRY OR OTHER
ITEMS EMBEDDED IN CONCRETE.
2. APPLICABLE STANDARDS
ACI NUMBER TITLE
117 STANDARD SPECIFICATIONS FOR TOLERANCES FOR CONCRETE CONSTRUCTION
226 GROUND GRANULATED BLAST-FURNACE SLAG
301 STANDARD SPECIFICATIONS FOR STRUCTURAL CONCRETE FOR BUILDINGS
302 GUIDE FOR CONCRETE FLOOR AND SLAB CONSTRUCTION
304 GUIDE FOR MEASURING MIXING, TRANSPORTING AND PLACING CONCRETE
304.2R PLACING CONCRETE BY PUMPING METHODS.
305R HOT WEATHER CONCRETING
306R COLD WEATHER CONCRETING
308 STANDARD PRACTICE FOR CURING CONCRETE
309R GUIDE FOR CONSOLIDATION OF CONCRETE
315 MANUAL OF STANDARD PRACTICE FOR DETAILING CONCRETE STRUCTURES
318 BUILDING CODE REQUIREMENTS FOR REINFORCED CONCRETE
347 RECOMMENDED PRACTICE FOR CONCRETE FORMWORK
CRSI NUMBER TITLE
63 RECOMMENDED PRACTICE FOR PLACING REINFORCING BARS
3. CONCRETE MATERIALS
A) PORTLAND CEMENT - ASTM C 150, TYPE I
B) AGGREGATES - NORMAL WEIGHT CONCRETE, COARSE AND FINE, ASTM C33. STRUCTURAL LIGHT
WEIGHT ASTM C330.
C) AIR-ENTRAINING - ASTM C260
D) WATER REDUCING - ASTM C494, TYPE A
E) WATER - FRESH, CLEAN AND POTABLE
F) NO ACCELERATORS, RETARDERS OR ADMIXTURES CONTAINING CHLORIDES WILL BE PERMITTED G) FLY-ASH - ASTM C618, CLASS F, 20% MAXIMUM OF CEMENTITIOUS MATERIAL BY WEIGHT. DO NOT
USE FOR EXPOSED SLABS OR ARCHITECTURAL CONCRETE.
H) SUPER PLASTICIZER - ASTM C494, TYPE F OR G, WHERE AUTHORIZED BY THE ENGINEER.
I) GROUND GRANULATED BLAST-FURNACE SLAG CEMENT – ASTM C989, 50% MAXIMUM BY WEIGHT.
J) MAXIMUM AGGREGATE SIZE - FOOTINGS = #57, OTHERS #67
4. REINFORCING MATERIALS
A) DEFORMED BARS - ASTM A615, GRADE 60
B) SMOOTH DOWELS - ASTM A615, PLAIN BARS, MINIMUM YIELD STRENGTH OF 60,000 PSI.
C) CORROSION RESISTANT UNCOATED STEEL (MMFX-2) – ASTM A615, GRADE 75 AND ASTM A1035 LOW-
CARBON (8% MINIMUM) CHROMIUM BY MMFX OR EQUAL.
D) WELDED WIRE FABRIC - ASTM A1064, PLAIN WIRE FABRIC IN FLAT SHEETS ONLY.
E) ACCESSORIES TO CONFORM TO ACI 315.
F) WHERE CONCRETE SURFACES ARE EXPOSED, MAKE THOSE PORTIONS OF ALL ACCESSORIES IN
CONTACT WITH THE CONCRETE SURFACE OR WITHIN 1/2 INCH THEREOF, OF PLASTIC OR STAINLESS STEEL.
5. PROVIDE THE FOLLOWING MINIMUM CONCRETE STRENGTHS AT 28 DAYS:
A) FOOTINGS, SLAB-ON-GRADE--------------------3000 PSI
B) REGULAR FILL ON METAL DECK-----------------3000 PSI
C) MASONRY WALL BEAMS, TIE COLUMNS------------3000 PSI
D) FORMED COLUMNS, WALLS, BEAMS & SLABS-------4000 PSI
6. CONCRETE MUST BE BATCHED, MIXED AND TRANSPORTED IN ACCORDANCE WITH THE SPECIFICATIONS
FOR READY-MIXED CONCRETE ASTM C94.
7. REQUIRED SLUMP = 4 PLUS OR MINUS ONE INCH.
8. CONCRETE MUST BE PLACED WITHIN 90 MINUTES OF BATCH TIME. WHEN AIR TEMPERATURE IS BETWEEN 85 AND 90 DEGREES F, REDUCE MIXING AND DELIVERY TIME TO 75 MINUTES. WHEN AIR TEMPERATURE IS HIGHER THAN 90 DEGREES F, REDUCE MIXING AND DELIVERY TIME TO 60 MINUTES.
9. DO NOT ADD WATER AT THE JOB SITE WITHOUT APPROVAL OF THE PROJECT SUPERINTENDENT. DO NOT EXCEED THE SLUMP LIMITATION. USE ONLY COLD WATER FROM THE TRUCK TANK. ANY ADDED WATER MUST BE INDICATED ON THE DELIVERY TICKET PLUS THE NAME OF THE PERSON AUTHORIZING.
TEST CYLINDERS SHALL BE TAKEN AFTER THE ADDITION OF WATER.
10. LAP SPLICE REINFORCING PER CONCRETE LAP SCHEDULE MINIMUM UNLESS OTHERWISE SHOWN OR
NOTED.
11. PROVIDE CORNER BARS AT ALL WALL FOOTING, WALL AND BEAM CORNERS. SIZE AND NUMBER TO
MATCH HORIZONTAL BARS.
12. PROVIDE FOUNDATION DOWELS TO MATCH SIZE AND NUMBER OF VERTICAL BARS. EMBED DOWELS TO:
A) 3" ABOVE BOTTOM OF FOOTINGS
13. REINFORCEMENT SHALL BE FASTENED AND SECURED TOGETHER TO PREVENT DISPLACEMENT BY
CONSTRUCTION LOADS OR THE PLACING OF CONCRETE.
14. REINFORCING BAR COVER
A) FOOTINGS 2" (TOP), 3" (SIDES AND BOTTOM)
B) COLUMNS AND BEAMS 1-1/2"
C) SLABS 3/4" (INTERIOR), 1-1/2" (EXTERIOR)
15. WHERE BAR LENGTHS ARE GIVEN ON THE DRAWINGS, LENGTH OF HOOK, IF REQUIRED, IS NOT
INCLUDED.
16. SELECT PROPORTIONS IN ACCORDANCE WITH ACI 301 TO PROVIDE CONCRETE CAPABLE OF BEING PLACED WITHOUT EXCESSIVE SEGREGATION AND WITH ACCEPTABLE FINISHING PROPERTIES, DURABILITY, SURFACE HARDENERS, APPEARANCE, AND STRENGTH REQUIREMENTS REQUIRED BY THESE
SPECIFICATIONS.
17. CHAIR WELDED WIRE FABRIC REINFORCING AT 3'-0" ON CENTER MAXIMUM IN EACH DIRECTION.
18. MAXIMUM WATER TO CEMENT RATIO WHEN NO BACK-UP DATA IS AVAILABLE:
A) 4000 PSI, 28-DAY COMPRESSIVE STRENGTH; W/C RATIO, 0.44 MAXIMUM (NON-AIR-ENTRAINED), 0.36
MAXIMUM (AIR-ENTRAINED).
B) 3000 PSI, 28-DAY COMPRESSIVE STRENGTH; W/C RATIO, 0.58 MAXIMUM (NON-AIR-ENTRAINED), 0.47
MAXIMUM (AIR-ENTRAINED).
19. DATA TO BE SUBMITTED:
A) INTENDED USAGE AND LOCATION FOR EACH TYPE
B) MIX DESIGN FOR EACH TYPE
C) CEMENT CONTENT IN POUNDS-PER-CUBIC YARD
D) COARSE AND FINE AGGREGATE IN POUNDS/CUBIC YARD
E) WATER CEMENT RATIO BY WEIGHT
F) CEMENT TYPE AND MANUFACTURER
G) SLUMP RANGE
H) AIR CONTENT
I) ADMIXTURE TYPE AND MANUFACTURER
J) PERCENT ADMIXTURE BY WEIGHT
K) STRENGTH TEST DATA REQUIRED TO ESTABLISH MIX DESIGN.
L) COMPLETE DETAIL AND PLACING SHOP DRAWINGS FOR ALL REINFORCING STEEL INCLUDING
ACCESSORIES THAT HAVE BEEN REVIEWED AND STAMPED BY THE GENERAL CONTRACTOR.
INCLUDE ALL REQUIRED DIMENSIONS AND ELEVATIONS (IE. TOP OF CONCRETE)
20. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR PROVIDING THE CONSTRUCTION OF FORMWORK, SHORING AND RE-SHORING IN ACCORDANCE WITH ACI 347.
A) FORM AND SHORING DESIGN BY A P.E. REGISTERED IN THE STATE OF FLORIDA.
21. SUBMIT FORM WORK AND SHORING DRAWINGS TO LOCAL BUILDING DEPARTMENT WHEN REQUIRED BY
FLORIDA THRESHOLD LAW.
22. CONSTRUCTION JOINTS NOT SHOWN ON THE DRAWINGS MUST BE MADE AND LOCATED TO LEAST
IMPAIR THE STRENGTH OF THE STRUCTURE.
A) NO HORIZONTAL CONSTRUCTION JOINTS WILL BE PERMITTED IN BEAMS, GIRDERS AND SLABS.
B) LOCATION OF ANY CONSTRUCTION JOINT NOT SHOWN IS SUBJECT TO REVIEW AND
ACCEPTANCE BY ENGINEER.
23. INTERNAL VIBRATION, PROPERLY APPLIED IS THE REQUIRED METHOD OF CONSOLIDATING PLASTIC
CONCRETE.
24. PROVIDE 3/4" CHAMFER ON ALL EXPOSED CORNERS OF COLUMNS, BEAMS AND WALLS UNLESS
OTHERWISE NOTED ON ARCHITECTURAL DRAWINGS
25. CONTRACTOR SHALL VERIFY LOCATIONS OF ALL OPENINGS, SLEEVES, AND SLAB RECESSES AS REQUIRED BY OTHER TRADES BEFORE CONCRETE IS PLACED. NO SLEEVE, OPENINGS, OR INSERT MAY BE
PLACED IN BEAMS, JOISTS, OR COLUMN UNLESS APPROVED BY THE ENGINEER.
26. CONTRACTOR SHALL VERIFY EMBEDDED ITEMS INCLUDING, BUT NOT LIMITED TO, ANCHOR BOLTS, BOLT CLUSTERS, WELD PLATES, ETC., BEFORE PLACING CONCRETE. NOTIFY ENGINEER OF ANY CONFLICTS WITH
REBAR.
27. ALL EXPOSED CONCRETE SURFACES TO BE IN ACCORDANCE WITH ACI 301 SECTION 5.3.3.(C), INCLUDING SURFACE TOLERANCE CLASS A AS SPECIFIED IN ACI 117.U.N.O.
28. SEE ARCHITECTURAL DRAWINGS FOR REQUIRED CONCRETE FINISHES.
29. SLOPE WALKWAYS AND BALCONIES TO DRAIN AWAY FROM THE BUILDING.
30. BUILDING FLOOR AND SITE SLABS-ON-GRADE SHALL BE 4" MINIMUM THICKNESS, UNLESS NOTED
OTHERWISE.
A) REINFORCED WITH 6X6 - W1.4 X W1.4 W.W.F.
B) PLACED ON 10 MIL POLYETHYLENE VAPOR RETARDER. LAP 6" AND TAPE ALL JOINTS.
C) SAW-CUT CONTROL JOINTS @ LESS THAN OR EQUAL TO 15'-0" EACH WAY.
D) PROVIDE HOUSEKEEPING PADS AS REQUIRED.
E) SEE DRAWINGS FOR ANY ADDITIONAL CONDITIONS.
31. TESTING
A) A QUALIFIED TESTING LAB SHALL BE RETAINED TO PERFORM QUALITY CONTROL WORK AND ON-
SITE TESTING.
B) SLUMP TEST - ASTM 143
C) MOLD AND CURE TEST CYLINDERS (ASTM C-31) AND TEST CYLINDERS FOR STRENGTH (ASTM
C39). TAKE ONE TEST - THREE CYLINDERS FOR EACH DAYS POUR OF 100 CUBIC YARDS, OR
FRACTION THEREOF. TEST ONE CYLINDER AT 7 DAYS, TWO AT 28 DAYS. TEST CYLINDER SAMPLES
SHALL BE TAKEN AT THE POINT OF DISCHARGE WHEN USING A PUMP.
D) ONE COPY OF ALL TEST REPORTS SHALL BE SENT DIRECTLY TO THE OWNER, ENGINEER,
ARCHITECT AND GENERAL CONTRACTOR.
32. CONTRACTOR SHALL PROVIDE FLATNESS AND LEVELNESS IN CONCRETE SLABS PER ACI 302.1R, FIG.
10.7 MINIMUM REQUIRED "F" NUMBERS FOR TYPE OF SLAB USE. REFER TO ACI 117 FOR FLOOR
TOLERANCES.
33. REPAIR ANY CRACKS OR DEFECTIVE AREAS THAT WILL RESTORE THE AFFECTED SURFACE OR AREAS TO THEIR FULL DESIGN STRENGTH AND APPEARANCE. CONTACT THE STRUCTURAL ENGINEER FOR ADVICE
AND EVALUATION.
34. ACCEPTANCE OF THE STRUCTURE WILL BE MADE IN CONFORMANCE WITH ACI 301.
35. ALL CAST-IN-PLACE CONCRETE MUST BE MAINTAINED WITH MINIMAL MOISTURE LOSS AT A RELATIVELY CONSTANT TEMPERATURE FOR A MINIMUM OF 7 DAYS FOLLOWING THE PLACING OF THE CONCRETE BY THE USE OF A WATER SPRAY, WATER SATURATED FABRIC, MOISTURE RETAINING MEMBRANE OR LIQUID
CURING COMPOUND.
36. CURE SLABS-ON-GRADE FOR THE FIRST 72 HOURS BY THE USE OF:
A) FOG SPRAYING
B) PONDING
C) SPRINKLING
D) CONTINUOUSLY WET ABSORPTIVE MATS OR FABRIC
E) CONTINUE CURING BY USE OF MOISTURE RETAINING COVER UNTIL CONCRETE HAS OBTAINED ITS
SPECIFIED 28 DAY COMPRESSIVE STRENGTH.
F) OR LIQUID CURING COMPOUND AFTER FINISHING PROCESS IS COMPLETED.
G) CONCRETE WET CURE TIME TO BE 7 DAYS MINIMUM AT 50 DEGREES MINIMUM TEMPERATURE.
37. SUBMIT MATERIALS AND METHOD OF CURING FOR REVIEW.
38. DO NOT USE MOISTURE RETAINING CURING COMPOUNDS FOR CURING SURFACES TO RECEIVE CARPET, FLEXIBLE FLOORING, CERAMIC TILED FLOORS OR OTHER SPECIFIED FLOOR SYSTEMS, UNLESS IT
HAS BEEN DEMONSTRATED THAT SUCH COMPOUNDS WILL NOT PREVENT BOND.
39. DO NOT PERMIT CONCRETE NOT FULLY CURED TO BE EXPOSED TO EXCESSIVE TEMPERATURE
CHANGES OR HIGH WINDS.
40. POUR ALL GROUND SLABS ON 10 MIL MINIMUM VAPOR RETARDER IN COMPLIANCE WITH ASTM E1745, LAPPED 6" MINIMUM AND FULLY TAPED.
41. EQUIPMENT MADE OF ALUMINUM OR ALUMINUM ALLOYS, SHALL NOT BE USED FOR PUMP LINES, TREMIES, OR CHUTES OTHER THAN SHORT CHUTES SUCH AS THOSE USED TO CONVEY CONCRETE FROM A
TRUCK MIXER.
42. THE CODE PROHIBITS THE USE OF ALUMINUM (CONDUIT, PIPES, ETC.) IN STRUCTURAL CONCRETE
UNLESS IT IS EFFECTIVELY COATED OR COVERED.
FIBROUS REINFORCING (ALTERNATE TO W.W.F. IN SLAB-ON-GRADE)
1. REINFORCING FIBERS TO BE VIRGIN 100% MICRO SYNTHETIC POLYPROPYLENE FIBERS, SPECIFICALLY MANUFACTURED FOR USE IN CONCRETE, CONTAINING NO REPROCESSED OLEFIN MATERIALS, WITH THE
FOLLOWING MINIMUM PHYSICAL CHARACTERISTICS:
A) SPECIFIED GRAVITY: 0.91
B) YOUNG'S MODULUS 0.5 (3.5KN/MM2)
C) TENSILE STRENGTH: 45-60 KSI
D) LENGTH: 3/4" MAXIMUM, MULTI GRADATION DESIGN
2. REINFORCING FIBERS TO BE SUPPLIED BY THE FOLLOWING APPROVED MANUFACTURERS:
A) "FIBERSTRAND 100", EUCLID CHEMICAL COMPANY
B) "FIBERMESH 150 OR 300, PROPEX CONCRETE SOLUTIONS
C) "FORTA ECONO-NET", FORTA CORPORATION
D) "NYCON SUPER FIBERS", NYCON, INC.
3. FIBERS TO BE ADDED IN MANUFACTURER'S APPROVED AMOUNT WITH A MINIMUM OF 1.5 LBS PER CUBIC
YARD FOR POLY AND NYLON.
4. CONCRETE TO BE MIXED IN ACCORDANCE WITH FIBER MANUFACTURER'S RECOMMENDATIONS FOR UNIFORM AND COMPLETE DISPERSION OF FIBER BUNDLES INTO SINGLE MONOFILAMENTS WITHIN
CONCRETE.
5. REINFORCING FIBERS ONLY TO BE USED IN CONCRETE SLAB-ON-GRADES, AND NOT IN PRECAST PLANK
OR METAL DECK TOPPING SLABS.
6. FOR A "NON-HAIRY" FINISH, USE A MONOFILAMENT FIBER. MORE DEMANDING APPLICATIONS, USE A
COLLATED FIBRILLATED FIBER, WHICH WILL WEAR AWAY OVER TIME
PRECAST CONCRETE U-LINTELS AND SILLS
1. UNITS SHALL BE FABRICATED BY A FIRM ENGAGED IN THE MANUFACTURING OF PRECAST AND PRE- STRESSED CONCRETE U-LINTELS AND SILLS FOR A MINIMUM OF 5 YEARS. FABRICATOR SHALL HAVE A
QUALITY ASSURANCE PROGRAM THAT COMPLIES WITH THE PROCEDURES OF MANUAL 116 BY THE
PRECAST/PRE-STRESSED CONCRETE INSTITUTE PCI).
2. PLANT RECORDS OF PRODUCTION AND QUALITY CONTROL SHALL BE KEPT IN ACCORDANCE WITH PCI
RECOMMENDATIONS AND MADE AVAILABLE UPON REQUEST FOR THE ARCHITECT/ENGINEER.
3. CODES AND STANDARDS:
A) AMERICAN SOCIETY FOR TESTING AND MATERIALS(ASTM)
1) C33 – SPECIFICATION FOR CONCRETE AGGREGATES
2) C150 – SPECIFICATION FOR PORTLAND CEMENT
B) PRECAST/PRE-STRESSED CONCRETE INSTITUTE (PCI) STANDARDS: MANUAL FOR QUALITY
CONTROL FOR PRECAST AND PRE-STRESSED CONCRETE MNL-116.
C) AMERICAN CONCRETE INSTITUTE: BUILDING CODE REQUIREMENTS FOR STRUCTURAL
CONCRETE (ACI 318)
D) AMERICAN CONCRETE INSTITUTE: BUILDING CODE REQUIREMENTS FOR MASONRY
STRUCTURES (ACI 530)
4. CONCRETE MATERIALS:
A) PORTLAND CEMENT: ASTM C150 TYPE I OR III, GRAY COLOR
B) AGGREGATES: ASTM C33
C) WATER: POTABLE
D) ADMIXTURES: SHALL NOT CONTAIN CALCIUM CHLORIDE OR CHLORIDE IONS
5. REINFORCING
A) DEFORMED REINFORCEMENT: ASTM A615 GRADE 40 OR 60.
B) PRE-STRESSING STRAND: ASTM A416 270 KSI LL.
6. U-LINTEL UNITS 14 FEET IN OVERALL LENGTH AND SHORTER SHALL BE MADE OF CONCRETE WITH A
MINIMUM STRENGTH OF 3500 PSI AT 28 DAYS.
7. U-LINTEL UNITS EXCEEDING 14 FEET IN OVERALL LENGTH SHALL BE MADE OF CONCRETE WITH A
MINIMUM STRENGTH OF 6000 PSI AT 28 DAYS AND SHALL BE PRE-STRESSED CONCRETE.
8. SILL UNITS SHALL BE MADE OF CONCRETE WITH A MINIMUM STRENGTH OF 3000 PSI AT 28 DAYS.
9 UNITS SHALL BE SAND BLOCK FINISH EXCEPT PRE-STRESSED, 6" WIDE, AND 12" WIDE U-LINTELS SHALL
BE SMOOTH FORM FINISHED.
10. PRECAST CONCRETE U-LINTELS SHALL BE DESIGNED BY A LICENSED DELEGATED ENGINEER.
11. SUBMITTALS
A) PROVIDE MANUFACTURER'S CATALOG ENGINEERING DATA.
B) MANUFACTURER SHALL RATE U-LINTEL UNITS FOR GRAVITY, UPLIFT, AND LATERAL LOADS IN
UNITS OF POUNDS PER LINEAR FOOT.
MASONRY
1. HOLLOW LOAD BEARING UNITS SHALL CONFORM TO ASTM C90, NORMAL WEIGHT, TYPE II. MINIMUM NET COMPRESSIVE UNIT STRENGTH = 2000 PSI. (NET AREA COMPRESSIVE MASONRY STRENGTH F'M = 2000 PSI).
2. MORTAR SHALL BE TYPE S AND CONFORM TO ASTM C270 (PROPORTION OR PROPERTY SPECIFICATION).
3. COARSE GROUT SHALL CONFORM TO ASTM C476:
A) 2500 PSI AT 28 DAYS.
B) 1/4" MAXIMUM AGGREGATE.
C) 8" - 11" SLUMP.
4. CODES AND STANDARDS:
A) SPECIFICATIONS FOR MASONRY STRUCTURES - ACI 530.1/ASCE 6/ TMS 602 IS INCLUDED BY
REFERENCE IN ITS ENTIRETY.
B) BUILDING CODE REQUIREMENTS FOR MASONRY STRUCTURES – ACI 530/ ASCE 5/TMS 402.
5. A REINFORCED TIE BEAM SHALL BE PROVIDED IN ALL WALLS SHOWN ON THE STRUCTURAL DRAWINGS AT THE ROOF, AND AT TOP OF ANY PARAPET WALL. USE GALVANIZED MESH-TYPE CELL CAPS. PROVIDE
CORNER BARS AT ALL BEAM CORNERS TO MATCH HORIZONTAL BARS.
6. UNLESS NOTED OTHERWISE, TIE BEAMS SHALL BE AS FOLLOWS:
A) ROOF LEVEL: DOUBLE COURSE OF KNOCK-OUT BLOCKS WITH (1) #5 IN EACH COURSE.
B) TOP OF PARAPET: (1) #5 BAR IN GROUTED KNOCK-OUT BLOCKS.
7. VERTICAL BARS SHALL BE HELD IN POSITION AT THE TOP AND BOTTOM OF BAR AND AT 8'-0" O.C.
MAXIMUM WITH A MINIMUM CLEARANCE OF 1/2" FROM MASONRY. THE CLEAR DISTANCE BETWEEN BARS
SHALL NOT EXCEED ONE BAR DIAMETER, OR MORE THAN 1". CENTER BARS IN WALLS U.N.O.
8. VERTICAL REINFORCING SHALL BE AS SHOWN ON THE DRAWINGS. FILLCELLS WITH COARSE GROUT AS SPECIFIED. PROVIDE ACI 90 DEGREE STANDARD HOOKS INTO FOOTING AND ROOF TIE BEAM. LAP SPLICE VERTICAL REINFORCEMENT ABOVE FOOTING AND ABOVE EACH FLOOR LEVEL UNLESS NOTED OTHERWISE.
MAINTAIN VERTICAL REINFORCING SHOWN ON PLANS ABOVE AND BELOW MASONRY OPENINGS. CONTINUE
FOUNDATION DOWELS BELOW ALL MASONRY OPENINGS.
9. REINFORCED FILL CELLS ARE TO BE CLEAN AND FREE OF ANY FOREIGN MATERIAL OR DEBRIS.
REMOVE ANY INSULATING MATERIAL FROM CELLS, INCLUDING POLYSTYRENE INSULATING INSERTS, PRIOR
TO GROUT POUR.
10. REINFORCING BARS SHALL BE STRAIGHT EXCEPT FOR BENDS AROUND CORNERS AND WHERE BENDS
OR HOOKS ARE DETAILED ON THE PLANS.
11. REINFORCING BARS SHALL BE LAPPED PER MASONRY LAP SCHEDULE MINIMUM (UNLESS OTHERWISE
NOTED) WHERE SPLICED AND SHALL BE WIRED TOGETHER.
12. WHEN A FOUNDATION DOWEL DOES NOT LINE UP WITH A VERTICAL CORE, IT SHALL NOT BE SLOPED MORE THAN ONE HORIZONTAL IN SIX VERTICALS. DOWELS SHALL BE GROUTED INTO A CORE IN VERTICAL ALIGNMENT, EVEN THOUGH IT IS IN AN ADJACENT CELL TO THE VERTICAL WALL REINFORCEMENT.
13. PROVIDE HORIZONTAL WALL REINFORCING (9 GA.) HOT DIPPED GALVANIZED LADDER TYPE DUR-O-WALL
(OR EQUIVALENT) AT 16" O.C. JOINT REINFORCING SHALL CONFORM TO ASTM A-951.
14. PROVIDE HORIZONTAL JOINT REINFORCEMENT AT DOORS AND WINDOWS FOR FIRST AND SECOND BLOCK COURSE ABOVE AND BELOW APERTURES. RUN REINFORCING CONTINUOUS OR EXTEND TWO FEET
FROM APERTURE EDGE.
15. WIRE REINFORCEMENT SHALL BE LAPPED AT LEAST 6" AT SPLICES AND SHALL CONTAIN AT LEAST ONE
CROSS WIRE OF EACH PIECE OF REINFORCEMENT IN THE LAPPED DISTANCE.
16. CLEANOUTS SHALL BE PROVIDED IN THE BOTTOM COURSE OF MASONRY IN EACH GROUT POUR WHEN
THE POUR HEIGHT EXCEEDS 5'. CLEANOUTS TO BE SAW-CUT 4" X 4".
17. GROUT POUR HEIGHT SHALL NOT EXCEED 24'. PLACE GROUT IN 5' MAX. LIFTS HEIGHTS.
18. CONSOLIDATE GROUT POURS AT THE TIME OF PLACEMENT BY MECHANICAL MEANS AND
RECONSOLIDATE AFTER INITIAL WATER LOSS AND SETTLEMENT.
19. ALL MASONRY FOUNDATION STEMWALLS AND RETAINING WALLS SHALL BE FULLY GROUTED.
20. STORE BLOCKS ON PALLETS AND COVER WITH PLASTIC SHEETING.
21. PLACE MASONRY IN RUNNING BOND WITH 3/8" MORTAR JOINTS. PROVIDE COMPLETE COVERAGE FACE SHELL MORTAR BEDDING, HORIZONTAL AND VERTICAL. FULLY MORTAR WEBS IN ALL COURSES OF PIERS, COLUMNS, AND PILASTERS AND ADJACENT TO GROUTED CELLS.
22. SEE DRAWINGS FOR MASONRY CONTROL JOINT LOCATIONS. SPACE AT 26'-0" O.C. AT EXTERIOR WALLS, 32'-0" O.C. AT INTERIOR WALLS UNLESS NOTED OTHERWISE.
23. SUBMITTALS:
A) SUBMIT PROPOSED GROUT MIX DESIGN PRIOR TO CONSTRUCTION.
B) SUBMIT PROPOSED MORTAR MIX DESIGN PRIOR TO CONSTRUCTION.
C) SUBMIT DETAILED SHOP DRAWINGS OF REINFORCING BARS SHOWING NUMBER, SIZE, AND
LOCATION. INCLUDE BAR LISTS AND BEND DIAGRAMS. INCLUDE ALL REQUIRED DIMENSIONS AND
ELEVATIONS.
D) SUBMIT COMPRESSIVE STRENGTH TESTS OF PROPOSED MASONRY UNITS PRIOR TO
CONSTRUCTION. MASONRY UNITS ARE TO BE TESTED IN ACCORDANCE WITH ASTM C140.
24. A QUALIFIED TESTING LABORATORY SHALL BE RETAINED TO PERFORM THE FOLLOWING TESTS:
A) SAMPLE AND TEST GROUT IN ACCORDANCE WITH ASTM C1019 FOR EACH 5000 SQ. FT. OF
MASONRY.
B) SLUMP TESTS - ASTM C143.
C) MASONRY PRISM TEST IN ACCORDANCE WITH ASTM C1314. PROVIDE ONE SET OF 3 PRISMS
PRIOR TO CONSTRUCTION AND DURING CONSTRUCTION FOR EACH 5000 SQ. FT. OF WALL.
25. PROVIDE 8" DEEP PRECAST REINFORCED CONCRETE LINTELS OVER ALL MASONRY OPENINGS NOT SHOWN TO HAVE A STRUCTURAL BEAM. MINIMUM END BEARING = 8". LINTEL WIDTH TO MATCH MASONRY
WIDTH.
26. TOPS OF PARTIALLY CONSTRUCTED WALLS SHALL BE COVERED WITH VISQUEEN WHENEVER RAIN
OCCURS AND AT THE END OF THE WORK DAY.
DRILL-IN BOLTS, SCREWS AND DOWELS
1. ADHESIVE DOWELING RODS/BOLTS SHALL BE CARBON STEEL THREADED ROD CONFORMING TO ISO 898
5.8 WITH A MINIMUM TENSILE STRENGTH OF 72.5 KSI (500MPa) AND A MINIMUM YIELD OF 58 KSI (400MPa).
THREADED RODS WITH NUTS AND WASHERS INSTALLED IN ACCORDANCE WITH MANUFACTURER'S
INSTRUCTIONS.
2. ANCHORING ADHESIVE SHALL BE A TWO-COMPONENT SYSTEM SUPPLIED IN MANUFACTURER'S
STANDARD SIDE-BY-SIDE FOIL PACKAGE AND DISPENSED THROUGH A STATIC-MIXING NOZZLE SUPPLIED BY
THE MANUFACTURER. ADHESIVE SHALL BE TESTED AND APPROVED TO MEET THE MINIMUM
REQUIREMENTS OF ACI 355.4 FOR CRACKED AND UNCRACKED CONCRETE RECOGNITION. PROVIDE HILTI HY 200 SAFE SET (ESR 3187) OR RE 500 V3 (ESR 3814) ANCHORS BY HILTI OR EQUAL (E.G. SIMPSON SET-XP, ATC
ULTRABOND 365CC)UNLESS SPECIFIED OTHERWISE IN THE STRUCTURAL DOCUMENT.
3. DRILL-IN REBAR DOWELS SHALL BE SET USING A TWO-PART ADHESIVE AS DESCRIBED ABOVE.
4. EXPANSION BOLTS SHALL BE HILTI KB TZ (ESR 1917) OR EQUAL. BOLT SHALL MEET DUCTILITY
REQUIREMENTS OF ACI 318 SECTION D1.
5. EXPANSION BOLTS SHALL HAVE CARBON STEEL ANCHOR BODY AND NUT AND WASHER SHALL BE ELECTROPLATED ZINC COATING CONFORMING TO ASTM B633 TO A MINIMUM OF 5µM. THE STAINLESS STEEL ANCHOR BODY, NUT AND WASHER, AND EXPANSION SLEEVE SHALL CONFORM TO TYPE 316 STAINLESS STEEL. EXPANSION ANCHORS SHALL MEET THE MINIMUM REQUIREMENTS OF ACI 355.2 FOR CRACKED AND
UNCRACKED CONCRETE. INSTALL IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS.
6. MASONRY SCREWS SHALL BE 1/4" DIAMETER WITH 1-5/8" MINIMUM EMBEDMENT INSTALLED IN DRILLED
HOLES USING AN APPROPRIATE BIT DIAMETER.
7. SCREWS SHALL HAVE A BODY MADE OF CARBON STEEL AND SHALL BE HEAT TREATED AND SHALL HAVE 8µM ZINC COATING IN ACORDANCE WITH EN ISO 4042. PROVIDE HUS EZ (ESR 3027) SCREWS BY HILTI
OR EQUAL.
8. HEAVY-DUTY CONCRETE AND MASONRY SCREWS SHALL BE TESTED AND APPROVED TO MEET THE MINIMUM REQUIREMENTS OF ACI 355.2. HILTI KWICK HUS EZ (ESR-3027 FOR CONCRETE, ESR-3056 FOR
GROUT FILLED MASONRY). HEAVY DUTY SCREWS BY HILTI OR EQUAL.
9. THE CONTRACTOR SHALL ARRANGE FOR AN ANCHOR MANUFACTURER’S REPRESENTATIVE TO
PROVIDE ONSITE INSTALLATION TRAINING FOR ALL OF THE ANCHORING PRODUCTS SPECIFIED. PENNONI TO RECEIVE DOCUMENTED CONFIRMATION THAT ALL OF THE CONTRACTOR’S PERSONNEL WHO ARE TO
INSTALL ANCHORS ARE TRAINED PRIOR TO THE COMMENCEMENT OF INSTALLATION.
STRUCTURAL STEEL
1. STRUCTURAL STEEL SHALL CONFORM TO THE AISC "SPECIFICATION FOR BUILDINGS", LATEST EDITION.
2. WELDED CONNECTIONS SHALL CONFORM TO THE LATEST REVISED CODE OF THE AMERICAN WELDING SOCIETY, AWS D1.1. ALL WELDING SHALL BE PERFORMED USING E70XX, LOW HYDROGEN ELECTRODES.
ELECTRODES ARE TO BE PROTECTED FROM MOISTURE.
3. CONNECTIONS TO BE DOUBLE ANGLE FRAMED BEAM CONNECTION PER AISC UNLESS NOTED
OTHERWISE. ALL BOLTS TO BE 3/4" DIAMETER UNLESS NOTED OTHERWISE. SHOP CONNECTIONS MAY BE WELDED OR BOLTED. WELDS ARE TO BE EQUAL IN STRENGTH TO BOLTS. ALL FIELD CONNECTIONS ARE TO BE BOLTED WITH ASTM A325N OR A490 BOLTS (BEARING TYPE BOLTS WITH THREADS IN THE SHEAR PLANE) INCLUDING SUITABLE NUTS AND PLAIN HARDENED WASHERS. ALL BOLTS SHALL BE TIGHTENED SNUG TIGHT UNLESS OTHERWISE NOTED. DESIGN CONNECTIONS FOR THE LARGER OF EITHER THE SHEAR SHOWN ON THE DRAWINGS, (INDICATED AS "V =K" AT ENDS OF MEMBER) OR 55% OF THE MAXIMUM LOAD(IN KIPS) LISTED IN THE TABLES FOR "MINIMUM TOTAL FACTORED UNIFORM LOADS IN KIPS FOR BRACED, SIMPLE SPAN BEAMS BENT ABOUT THE STRONG AXIS” OF THE LATEST EDITION OF THE AISC "MANUAL OF
STEEL CONSTRUCTION".
4. SIZE AND USE OF HOLES: SEE AISC TABLE J3.3.
A) LARGER HOLES ARE PERMITTED IN STANDARD COLUMN BASE PLATES. MAXIMUM HOLE
DIAMETER = BOLT DIAMETER + 3/8". HARDENED WASHERS, TO COVER THE LARGER HOLE, SHALL BE
PROVIDED.
B) LARGER HOLES ARE NOT PERMITTED IN WIND FRAME COLUMN BASE PLATES. MAXIMUM HOLE
DIAMETER = BOLT DIAMETER + 1/16".
C) SLOTTED HOLES: A PLATE WASHERS OR A CONTINUOUS BAR WITHSTANDARD HOLES, HAVING A SIZE SUFFICIENT TO COMPLETELY COVER THE SLOT AFTER INSTALLATION, AND A MIN. OF 5/16"
THICK SHALL BE PROVIDED. TACK WELD NUT TO BOLT AFTER ERECTION.
5. STEEL BEAMS SHALL BE FABRICATED WITH THE NATURAL CAMBER (WITHIN THE MILL TOLERANCE)
LOCATED ABOVE THE HORIZONTAL CENTERLINE BETWEEN THE END CONNECTIONS.
6. VERIFY THE EXACT SIZE AND LOCATION OF ALL FLOOR AND ROOF OPENINGS FOR MECHANICAL
EQUIPMENT WITH THE MECHANICAL CONTRACTOR PRIOR TO FABRICATION OF MATERIALS.
7. SHOP PRIME STEEL SURFACES EXCEPT THE FOLLOWING:
A) SURFACES EMBEDDED IN CONCRETE OR MORTAR. EXTEND PRIMING OF PARTIALLY EMBEDDED
MEMBERS TO A DEPTH OF 2 INCHES.
B) SURFACES TO BE FIELD WELDED.
C) SURFACES TO BE HIGH-STRENGTH BOLTED WITH SLIP-CRITICAL CONNECTIONS.
D) SURFACES TO RECEIVE SPRAYED FIRE-RESISTIVE MATERIALS.
E) GALVANIZED SURFACES.
8. SURFACE PREPARATION: CLEAN SURFACES TO BE PAINTED. REMOVE LOOSE RUST AND MILL SCALE
AND SPATTER, SLAG, OR FLUX DEPOSITS. PREPARE SURFACES ACCORDING TO THE FOLLOWING
SPECIFICATIONS AND STANDARDS.
9. PRIMING: IMMEDIATELY AFTER SURFACE PREPARATION, APPLY PRIMER ACCORDING TO
MANUFACTURER’S WRITTEN INSTRUCTIONS AND AT RATE RECOMMENDED BY SSPC TO PROVIDE A DRY FILM THICKNESS OF NOT LESS THAN 1.5 MILS. USE PRIMING METHODS THAT RESULT IN FULL COVERAGE
OF JOINTS, CORNERS, EDGES, AND EXPOSED SURFACES.
A) STRIPE PAINT CORNERS, CREVICES, BOLTS, WELDS, AND SHARP EDGES.
B) APPLY TWO COATS OF SHOP PAINT TO INACCESSIBLE SURFACES AFTER ASSEMBLY OR
ERECTION. CHANGE COLOR OF SECOND COAT TO DISTINGUISH IT FROM FIRST.
10. PRIME AND PAINT ALL FIELD WELDS AFTER INSPECTION.
11. A QUALIFIED TESTING LABORATORY SHALL BE RETAINED TO PERFORM THE FOLLOWING TESTS.
A) VISUALLY INSPECT ALL STEEL MEMBERS AND CONNECTIONS.
B) TEST 50 PERCENT OF FULL PENETRATION WELDS.
12. ONE COPY OF ALL TEST REPORTS SHALL BE SENT DIRECTLY TO OWNER, ARCHITECT, STRUCTURAL
ENGINEER, AND GENERAL CONTRACTOR.
13. STEEL SHALL CONFORM TO:
WIDE FLANGE (WF)(WT)------ASTM A992 (50 KSI)
SHAPES (S, L, C, MC)---------ASTM A36
HOLLOW STRUCTURAL SECTIONS (HSS)---ASTM A500 GRADE C (RECTANGULAR 50 KSI; ROUND 46
KSI)
STEEL PIPE----------------ASTM A53
ANCHOR RODS---------------ASTM F1554 (55 KSI W/S1 SUPPLEMENT)
ANCHOR BOLTS--------------ASTM A307
FRAMING BOLTS-------------ASTM A325N OR A490N
SHEAR STUDS---------------ASTM A108
WELDING ELECTRODES--------E70XX
14. FASTENERS AND MATERIALS USED FOR WELDING OR OTHERWISE SECURING COMPONENTS ONE TO ANOTHER SHALL BE OF DOMESTIC (USA MADE) MANUFACTURE. SIMILARLY, ALL MATERIALS USED IN THE
MANUFACTURING PROCESS SHALL BE FROM A DOMESTIC SOURCE.
15. OPENINGS THROUGH STEEL BEAMS SHALL BE PROVIDED AS DETAILED ON THE DRAWINGS. ALL SUCH OPENINGS SHALL BE MACHINE CUT IN THE SHOP. ALL RECTANGULAR OPENINGS SHALL HAVE A CORNER
RADIUS OF 2 TIMES THE WEB THICKNESS, 1/2" MINIMUM.
16. SHOP AND FIELD WELDS SHALL BE DONE BY A.W.S. CERTIFIED WELDERS. PROVIDE CURRENT
CERTIFICATES UPON REQUEST.
17. NO SPLICES SHALL BE PERMITTED IN ANY STRUCTURAL STEEL MEMBER UNLESS SHOWN ON APPROVED
SHOP DRAWINGS.
18. STEEL STAIRS AND/OR LADDERS SHALL BE DESIGNED FOR 100 PSF LIVE LOAD BY A LICENSED DELEGATED ENGINEER, WHO SHALL SUBMIT SIGNED AND SEALED SHOP DRAWINGS. SHOP DRAWINGS
SHALL SPECIFY ALL DESIGN LOADS.
19. SUBMITTALS: CONTRACTOR SHALL SUBMIT DETAILED SHOP DRAWINGS SHOWING ALL STRUCTURAL STEEL LAYOUTS AND DETAILS, SIZES OF MEMBERS, TYPE OF STEEL, CONNECTION DETAILS, WELDS, BOLTS, ETC., AS REQUIRED TO FABRICATE AND ERECT ALL STRUCTURAL STEEL FRAMING. ALL CONNECTIONS NOT SHOWN ON THE STRUCTURAL DRAWINGS SHALL BE DESIGNED BY THE DETAILER AND SUBMITTED ON SHOP
DRAWINGS, SIGNED AND SEALED BY A REGISTERED FLORIDA DELEGATED ENGINEER.
20. NON-SHRINK GROUT SHALL BE: NONMETALLIC SHRINKAGE-RESISTANT GROUT, PREMIXED, NON- CORROSIVE, NON-STAINING PRODUCT CONTAINING SELECTED SILICA SANDS, PORTLAND CEMENT, SHRINKAGE COMPENSATING AGENTS, PLASTICIZING AND WATER-REDUCING AGENTS, COMPLYING WITH
CRD-C621, CORPS OF ENGINEERS.
21. IF NOT SPECIFIED ON THE DRAWINGS, THE THROAT SIZE OF ANY FILLET WELD SHALL BE EQUAL TO 1/16"
LESS THAN THE THINNEST CONNECTION COMPONENT.
22. NO FIELD WELDING OF GALVANIZED MEMBERS IS PERMITTED.
23. MINIMUM EMBEDMENT DEPTH OF ANCHOR BOLTS:
A) BEAMS, COLUMNS, WALLS = 6"
B) FOOTINGS = 3" FROM BOTTOM
C) PILE CAPS = 6" FROM BOTTOM
24. ERECTION
A) BEFORE ERECTION, THE CONTRACTOR IS TO REMOVE ALL MUD, DIRT OR OTHER FOREIGN
MATTER, WHICH ACCUMULATES DURING HANDLING AND STORAGE.
B) DRIFTING TO ENLARGE UNFAIR HOLES WILL NOT BE PERMITTED. DRILL SUCH HOLES TO
ACCOMMODATE THE NEXT LARGER SIZE FASTENER, WHERE POSSIBLE.
C) AFTER ERECTION, CLEAN FIELD WELDS, BOLTED CONNECTIONS, AND ABRADED AREAS WHERE SHOP COAT HAS BEEN DAMAGED. SPOT AND PRIME AREAS USING SAME MATERIAL AS SHOP COAT.
D) SET ALL MEMBERS SO THAT, IN THEIR FINAL LOCATION, LEVEL, PLUMBNESS AND ALIGNMENT
ARE WITHIN THE TOLERANCES PRESCRIBED BY AISC CODE.
E) DOUBLE CONNECTIONS THROUGH COLUMN WEBS OR AT BEAMS THAT FRAME OVER THE TOPS OF COLUMNS MUST BE DESIGNED TO HAVE AT LEAST ONE INSTALLED BOLT REMAIN IN PLACE TO SUPPORT THE FIRST BEAM WHILE THE SECOND BEAM IS BEING ERECTED. ALTERNATIVELY, THE FABRICATOR MUST
SUPPLY A SEAT OR EQUIVALENT .
METAL DECKING
1. METAL DECK WORK SHALL CONFORM TO THE REQUIREMENTS OF THE STEEL DECK INSTITUTE.
2. FASTEN DECK AS INDICATED ON PLANS.
3. METAL ROOF DECK SHALL BE 1 1/2" DEEP, 18 GAUGE GALVANIZED TYPE "B" INSTALLED 3 SAPN MIN..
(VULCRAFT 1.5B OR EQUIVALENT.)
4. FASTEN DECK W/ (7) 5/8" DIA. PUDDLE WELDPATTERN AT EACH SUPPORT AND (12)#12 TEK SCREW SIDELAP FASTENERS FOR 36" WIDE DECKING PUDDLE WELD @ 6" O.C. AT ALL PERIMETER SUPPORTS .
5. MINIMUM FASTENING AT BUILDING PERIMETER OF DECK SHALL BE 5/8" DIAMETER PUDDLE WELDS AT 6" O.C.
6. METAL DECK AND SHEET METAL COATING DESIGNATION:
A. WITH STRUCTURAL CONCRETE OR INSULATING CONCRETE TOPPING – G90
B. WITHOUT STRUCTURAL CONCRETE OR INSULATING CONCRETE TOPPING – G60
7. INSTALL ALL DECKING 3 SPAN CONTINUOUS.
8. USE WELD WASHERS FOR ALL DECKING 24 GA. AND THINNER.
9. DO NOT HANG OR ATTACH DUCTWORK, CONDUIT, PIPING, EQUIPMENT, CEILINGS, ETC. FROM METAL
DECKING.
10. PRIME AND PAINT ALL FIELD WELDS AFTER INSPECTION WITH A GALVANIZED TOUCH-UP PAINT. (SEE NOTE
BELOW)
11. SUBMITTALS: CONTRACTOR SHALL SUBMIT DETAILED SHOP DRAWINGS SHOWING LAYOUT OF DECK, TYPE OF DECK, ALL CONNECTIONS INCLUDING END WELDS, SEAM WELDS, INTERMEDIATE WELDS, AND ALL
ACCESSORY MATERIAL SUCH AS CLOSURES, SUMPS FOR DRAINS, ETC.
12. A QUALIFIED TESTING LABORATORY SHALL BE RETAINED TO VISUALLY INSPECT ALL DECK WELDS AND
FASTENERS.
COLD-FORM STEEL FRAMING
1. STEEL FRAMING SHALL CONFORM TO THE A.I.S.I. "SPECIFICATION FOR THE DESIGN OF COLD-FORMED
STEEL STRUCTURAL MEMBERS".
2. COLD-FORMED STEEL FRAMING SYSTEM, INCLUDING STUDS, TRUSSES, CONNECTIONS, AND ALL ACCESSORIES, SHALL BE DESIGNED BY A DELEGATED ENGINEER WHO SHALL PREPARE CALCULATIONS AND
SUPERVISE THE PREPARATION OF SHOP DRAWINGS.
3. WELDED CONNECTIONS SHALL CONFORM TO "CODE FOR WELDING IN BUILDING CONSTRUCTION, AWS D1.3".
4. ASTM A-568 STANDARD SPECIFICATION FOR GENERAL REQUIREMENTS FOR STEEL, CARBON AND HIGH
STRENGTH LOW-ALLOY HOT ROLLED SHEET AND COLD ROLLED SHEET.
5. ALL STEEL FRAMING SHALL BE INSTALLED BY PERSONNEL EXPERIENCED IN LIGHT GAUGE STEEL FRAMING
INSTALLATION.
6. WHERE STEEL FRAMING MEMBERS ARE COMPONENTS OF ASSEMBLIES INDICATED FOR A FIRE-RESISTANCE
RATING, INCLUDING THOSE REQUIRED FOR COMPLIANCE WITH GOVERNING REGULATIONS, PROVIDE MEMBERS
WHICH HAVE BEEN APPROVED BY GOVERNING AUTHORITIES HAVING JURISDICTION.
7. PROTECT LIGHT GAUGE STEEL FRAMING MEMBERS FROM RUSTING AND DAMAGE. DELIVER TO PROJECT SITE IN BUNDLES, FULLY IDENTIFIED WITH NAME, BRAND, TYPE AND GRADE. STORE OFF GROUND IN A DRY
VENTILATED SPACE OR PROTECT WITH SUITABLE WATERPROOF COVERINGS.
8. WITH EACH TYPE OF STEEL FRAMING REQUIRED, PROVIDE MANUFACTURER'S STANDARD STEEL RUNNERS (TRACKS), BLOCKING, LINTELS, CLIP ANGLES, BRACING, REINFORCEMENTS, FASTENERS, AND ACCESSORIES AS RECOMMENDED BY MANUFACTURER FOR APPLICATIONS INDICATED, AS NEEDED TO PROVIDE A COMPLETE
STEEL FRAMING SYSTEM.
9. FABRICATE METAL FRAMING COMPONENTS OF STRUCTURAL QUALITY SHEET STEEL WITH A MINIMUM YIELD
POINT OF 50,000 PSI U.N.O; ASTM A653.
10. PROVIDE GALVANIZED FINISH TO METAL FRAMING COMPONENTS COMPLYING WITH ASTM A525 WITH A MIN.
G90 COATING.
11. PROVIDE MANUFACTURER'S STANDARD STRUCTURAL "CEE" SHAPED STEEL STUDS OF SIZE, SHAPE, AND
GAUGE INDICATED.
12. FRAMING COMPONENTS MAY BE PREFABRICATED INTO PANELS PRIOR TO ERECTION. FABRICATE PANELS PLUMB, SQUARE, TRUE TO LINE AND BRACED AGAINST RACKING WITH JOINTS WELDED. PERFORM LIFTING OF
PREFABRICATED PANELS IN A MANNER TO PREVENT DAMAGE OR DISTORTION.
13. INSTALL METAL FRAMING SYSTEMS IN ACCORDANCE WITH REVIEWED SHOP DRAWINGS.
14. INSTALL CONTINUOUS TRACKS SIZED TO MATCH STUD DEPTH. ALIGN TRACKS ACCURATELY TO LAYOUT AT BASE AND TOPS OF STUDS. SECURE TRACKS AS RECOMMENDED BY STUD MANUFACTURER FOR TYPE OF
CONSTRUCTION INVOLVED, EXCEPT DO NOT EXCEED 24" O.C. SPACING FOR NAIL OR POWDER-DRIVEN
FASTENERS, OR 16" O.C., FOR OTHER TYPES OF ATTACHMENT. PROVIDE FASTENERS AT CORNERS AND ENDS
OF TRACKS.
15. FRAME BOTH SIDES OF EXPANSION AND CONTROL JOINTS, AS SHOWN FOR THE WALL SYSTEM, WITH
SEPARATE STUDS AND DO NOT BRIDGE THE JOINT WITH COMPONENTS OF THE STUD SYSTEM.
16. WHERE REQUIRED, TEMPORARY BRACING SHALL BE PROVIDED UNTIL ERECTION IS COMPLETED.
17. RESISTANCE TO BENDING AND ROTATION ABOUT THE MINOR AXIS SHALL BE PROVIDED BY MECHANICAL
LATERAL BRACING WHERE REQUIRED.
18. ATTACHMENTS OF SIMILAR COMPONENTS SHALL BE DONE BY WELDING, SCREW ATTACHMENT, OR
BOLTING. WIRE TYING OF FRAMING COMPONENTS SHALL NOT BE PERMITTED.
19. WELDING OF MEMBERS LIGHTER THAN 18 GAUGE SHALL NOT BE PERMITTED.
20. SPLICES SHALL NOT BE PERMITTED.
21. MINIMUM NUMBERS OF EQUALLY SPACED JOIST BRIDGING FOR THE SPANS SHOWN:
UP TO 14' - 1 ROW
14' TO 20' - 2 ROWS
20' TO 26' - 3 ROWS
26' TO 32' - 4 ROWS
OVER 32' - AT 8' CENTERS
22. PROVIDE HORIZONTAL BLOCKING BETWEEN EACH STUD AT 4'-0" ON CENTER MAXIMUM OR AT EACH
SHEATHING JOINT.
23. CONTRACTOR TO SUBMIT THE FOLLOWING:
A) SUBMIT DETAILED SHOP DRAWINGS FOR STEEL FRAMING SHOWING THE TYPE AND SPACING OF ALL
MEMBERS. ALL ATTACHMENTS SHALL BE CLEARLY DETAILED ON THE DRAWINGS. INDICATED
SUPPLEMENTAL STRAPPING, BRACING, CLIPS, AND OTHER ACCESSORIES REQUIRED FOR PROPER
INSTALLATION.
B) SUBMIT CERTIFICATION OF MATERIALS FROM THE MANUFACTURER TO SHOW COMPLIANCE WITH
THESE SPECIFICATIONS AND RELATED DRAWINGS.
24. SUBMITTED SHOP DRAWINGS MUST BE CHECKED AND SIGNED BY THE GENERAL CONTRACTOR.
25. COLD FORMED STEEL FRAMING FORMING PART OF THE EXTERIOR SHELL OF THE BUILDING SHALL BE DESIGNED TO RESIST BLAST LOADING AND PROVIDE THE LEVEL OF PROTECTION AS SPECIFIED ON THESE
DRAWINGS. SEE BLAST DESIGN CRITERIA ON S002.
Revisions Date
ULTIMATE
WIND PRESSURES ( PSF)
ROOFING MATERIALS
JOISTS
COMPONENTS
AND CLADDING
JOISTS
ROOF ZONECOMPONENTS
SUCTION (psf)
AND CLADDING
PRESSURE (psf)
1 2 3
ROOF ZONECOMPONENTS
SUCTION (psf)
AND CLADDING
PRESSURE (psf)
1 2 3
PRESSURE
EXTERIOR DOORS, WINDOWS, WALLS
251 TO 500
501 + ABOVE
101 TO 150
151 TO 250
51 TO 100
21 TO 50
1 TO 20
AREA (ft )
EFFECTIVE ZONE 4
PRESSURE
SUCTION SUCTION
ZONE 5
46.9
DOORS, WINDOWS AND WALLS
a 4 a a a
44.7
42.0
40.0
38.8
37.3
35.2
-50.8
-48.6
-45.9
-43.9
-42.7
-41.2
-39.1
-62.6
-58.1
-52.8
-48.7
-46.3
-43.2
-58.4
16.5
-77.8 -87.0
-100.4 -119.8 -129.0
GROSS ULTIMATE
WIND LOADS
MAIN ROOF
NET ULTIMATE
WIND LOADS
MAIN ROOF
NET ULTIMATE
WIND LOADS
OVERHANGS AND CANOPIES
1. a= 7'-6"
2. THIS BUILDING IS DESIGNED AS AN ENCLOSED STRUCTURE.
ALL EXTERIOR COMPONENTS (DOORS, WINDOWS, ETC.)
MUST BE DESIGNED TO WITHSTAND THE WIND LOADINGS
SPECIFIED FOR THE DESIGN OF COMPONENTS AND
CLADDING IN THE TABLES. IN ADDITION, ALL AREAS OF
EXTERIOR GLAZING MUST BE CERTIFIED FOR MISSILE
IMPACT OR PROTECTED BY WIND-BORNE DEBRIS BY A
SCREEN BARRIER.
3. TO CONVERT THE (ASCE 7-16) ULTIMATE WIND PRESSURES
IN THE TABLES ABOVE TO (ASD) WIND PRESSURES,
MULTIPLY EACH VALUE BY 0.6.
ROOF ZONE
PRESSURE (psf)
1 2 3
20.9
SUCTION (psf) -81.7 -108.0 -147.0
20.9 20.9
16.5 16.5
16.5 16.5 16.5
-39.1
46.9
44.7
42.0
40.0
38.8
37.3
35.2
COMPONENT AND CLADDING LOADING DIAGRAMS
1'
-79.6
16.5
1'
-46.9
20.9
1'
-37.6
16.5
FLAT ROOF
2 1
1 2 a a
(0 7 DEG)_
1'
0.6h
0.6h
0.
6h
0.
6h
0.2h a a a
1\
STIRRUP SPACING
OPEN
SEE SCHEDULE FOR
#3 STIRRUPS
2"
1/
2"
1/
1/
4"
2/3 1/3
1\ " C
LR
EQ. EQ.
TENSION SPLICE
SEE SCHEDULE
6"
FULL BRG ON COLUMN
EXCEPT 16" MIN. ON
PARALLEL WALL
CONST. JOINT
AS REQ'D.
WHERE NECESSARY.SPLICE TOP
STL. @ MIDSPAN
EXTEND BOT. BARS 6" INTO
SUPPORT UNLESS BARS ARE
CONTINUOUS (SPLICE PER
SCHEDULE)
C O
N S
TR
. J
T.
C
O N
S
TR
. J T.
90^ STD ACI HOOK @ ENDS
OF BM.
1\
STIRRUP SPACING
OPEN
SEE SCHEDULE FOR
#3 STIRRUPS
2"
1/
2"
1/
1/
4"
2/3 1/3
1\ " C
LR
EQ. EQ.
TENSION SPLICE
SEE SCHEDULE
6"
FULL BRG ON COLUMN
EXCEPT 16" MIN. ON
PARALLEL WALL
CONST. JOINT
AS REQ'D.
WHERE NECESSARY.SPLICE TOP
STL. @ MIDSPAN
EXTEND BOT. BARS 6" INTO
SUPPORT UNLESS BARS ARE
CONTINUOUS (SPLICE PER
SCHEDULE)
C O
N S
TR
. J
T.
C
O N
S
TR
. J T.
90^ STD ACI HOOK @ ENDS
OF BM.
CONCRETE BEAM TENSION LAP
43"
81"
LOCATION
SIZE
BAR
3,000 PSI
29"
37"
47"
36"
56"
OTHER BARS
TOP BARS
CONCRETE STRENGTH
32" 29"
70"
48"
37"
31"
25"
40"
33"
63"
43"
28"
36"
22"
4,000 PSI 5,000 PSI
CONCRETE BEAM TENSION
LAP SPLICE SCHEDULE
81"
118"
105"
72"
93"
63"
70"
102"
91"
80"
62"
54"
63"
91"
81"
72"
55"
49"
# 4
# 5
# 6
# 7
# 8
# 9
# 10 91" 79" 70"
OTHER BARS
TOP BARS
OTHER BARS
TOP BARS
OTHER BARS
TOP BARS
OTHER BARS
TOP BARS
OTHER BARS
TOP BARS
OTHER BARS
TOP BARS
# 10
# 9
# 8
81"
91"
72"
70"
79"
62"
63"
70"
55"
VERTICAL REINFORCEMENT
BAR LAP SCHEDULE
3,000 PSI
# 6
# 7
# 5
63"
43"
36"
BAR
SIZE
54"
37"
31"
49"
33"
28"
CLASS "B" TENSION LAP
4,000 PSI 5,000 PSI
NOTES:
1. BASED ON NORMAL WEIGHT CONCRETE & GRADE 60 REINFORCING BARS.
2. TOP BARS ARE HORIZONTAL BARS WITH MORE THAN 12 INCHES OF
CONCRETE CAST BELOW THE BARS.
3. FOR LIGHTWEIGHT AGGREGATE, MULTIPLY ABOVE VALUES BY 1.3.
SPLICE SCHEDULE
VERTICAL REINFORCEMENT BAR
LAP SCHEDULE - CONCRETE
NOTES:
1. BASED ON NORMAL WEIGHT CONCRETE & GRADE 60 REINFORCING BARS.
30"
42"
36"
BAR SIZE LAP LENGTH
#7 BAR
#6 BAR
#5 BAR
24"#4 BAR
18"#3 BAR
MASONRY REINF.
LAP SCHEDULE
VERTICAL REINFORCEMENT BAR
LAP SCHEDULE - MASONRY
NOTE:
1. LAPS BASED ON 48 BAR DIAMETERS
2. BAR STRESSES DO NOT EXCEED 80%
CONCRETE BEAM SCHEDULE
CB1224 12"x24"
MARK
CB816 8"x16"
DEPTH
WIDTH x
(2) # 6(2) # 6 # 3 @ 10" O.C.
REMARKSSTIRRUPS
(2) # 5(2) # 5
TOP BOT.
# 3 @ 6" O.C.
REINFORCING
TYPE A
TYPE A
CB1230 12"x30" (2) # 6(2) # 6 # 3 @ 12" O.C. TYPE B
TYPE A TYPE B
1 1/2" CLR.
1 1/2" CLR.
(1)#6 E.F.
CB1220 12"x20" (2) # 6(2) # 6 # 3 @ 12" O.C. TYPE A
NOTE: FOR CONTINUES LINTEL AND BOND BEAMS, PROVIDE FULL TENSION
SPLICE (CONTINUOUS STEEL FULL LENGTH, BOTH FACE)
CB824 8"x24" (2) # 6(2) # 6 # 3 @ 12" O.C. TYPE B
CONCRETE BEAM SCHEDULE
CB1224 12"x24"
MARK
CB816 8"x16"
DEPTH
WIDTH x
(2) # 6(2) # 6 # 3 @ 10" O.C.
REMARKSSTIRRUPS
(2) # 5(2) # 5
TOP BOT.
# 3 @ 6" O.C.
REINFORCING
TYPE A
TYPE A
CB1230 12"x30" (2) # 6(2) # 6 # 3 @ 12" O.C. TYPE B
TYPE A TYPE B
1 1/2" CLR.
1 1/2" CLR.
(1)#6 E.F.
CB1220 12"x20" (2) # 6(2) # 6 # 3 @ 12" O.C. TYPE A
NOTE: FOR CONTINUES LINTEL AND BOND BEAMS, PROVIDE FULL TENSION
SPLICE (CONTINUOUS STEEL FULL LENGTH, BOTH FACE)
CB824 8"x24" (2) # 6(2) # 6 # 3 @ 12" O.C. TYPE B
This item has been digitally signed and sealed by Eglantina Vrusho on the date adjacent to the seal. Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies.
NO. 79006
STATE OF
LORIDAF
P R
O
FESS IONAL ENGINEE
R
L ICENSEEG
LANT INA VRUSHO
Florida P.E. 79006
(727) 536-8772
Eglantina Vrusho, P.E.
Pennoni Project No. RDCJP21001
Florida Coa 7819
Clearwater, FL. 33760-3137 5755 Rio Vista Drive
VA Project No.
RDC/JPA Project No.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
STRUCTURAL
DOCUMENTSU.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Office of Construction and Facilities Management
EV NM
/3
/2
:5
:2
P
M
CONSTRUCT DENTAL CLINIC
02/03/2023
WIND TABLES & SCHEDULES
S002
516-349
BAY PINES VAMC
AMBER MILTON
21005.00100% Construction Set
BLAST DESIGN CRITERIA AND REQUIREMENTS
1. THIS BUILDING IS DESIGNATED AS A LIFE SAFETY PROTECTED FACILITY IN ACCORDANCE WITH THE PHYSICAL SECURITY AND RESILIENCY DESIGN MANUAL PUBLISHED BY THE U.S. DEPARTMENT OF VETERANS
AFFAIRS.
2. THE BLAST DESIGN FOR THE MAIN BUILDING FRAMING MEMBERS AND COMPONENTS HAS BEEN PREFORMED BY A SPECIALTY DELEGATE ENGINEER, AND DESIGN RESULTS HAVE BEEN INCORPORATED INTO THE DESIGN
DOCUMENTS DRAWINGS. SIGNED AND SEALED CALCULATIONS BY THE DELEGATE ENGINEER,
FROM 'PROTECTION ENGINEERING CONSULTANTS' ALDO E. McKAY PE, PMP WITH LICENSE #84402, DATED FEBRUARY 1, 2023 ARE INCLUDED IN THE DESIGN CALCULATIONS PACKAGE AS AN INTEGRAL PART OF THESE
DESIGN DOCUMENTS.
3. THE DESIGN OF EXTERIOR LOAD BEARING AND NON-LOAD BEARING WALLS AND THEIR CONNECTIONS, GLAZED AND NON-GLAZED DOORS, WINDOWS AND GLAZING SYSTEMS IN THE EXTERIOR WALLS, AND AIR INTAKES AND EXHAUSTS SERVICING CRITICAL EQUIPMENT SHALL BE IN ACCORDANCE WITH THE FOLLOWING
STANDARDS:
A) THE PHYSICAL SECURITY AND RESILIENCY DESIGN MANUAL (OCTOBER 1, 2020 – REVISED APRIL 1, 2021)
B) ASCE 59-11, BLAST PROTECTION OF BUILDINGS
3. THE DESIGN BLAST LOAD CRITERIA FOR NON-LOAD BEARING WALLS, DOORS, GLAZING SYSTEMS AND
OTHER PARTS OF THE EXTERIOR FAÇADE EXCEPT LOAD BEARING WALLS ARE AS FOLLOWS:
A) DESIGN LEVEL THREAT EXPLOSIVE WEIGHT: W1
B) STANDOFF DISTANCE: 25 FT.
C) PEAK PRESSURE AND IMPULSE LOAD: GP1
D) EFFECTS OF REBOUND: NOT CONSIDERED
5. THE DESIGN BLAST LOAD CRITERIA FOR LOAD BEARING WALLS AND OTHER STRUCTURAL ELEMENTS
REQUIRED FOR STRUCTURAL STABILITY ARE AS FOLLOWS:
A) DESIGN LEVEL THREAT EXPLOSIVE WEIGHT: W1
B) STANDOFF DISTANCE: 25 FT.
6. THE MAGNITUDES OF THE DESIGN LEVEL THREAT AND PEAK PRESSURE AND IMPULSE ARE DEFINED IN THE PHYSICAL SECURITY AND RESILIENCY DESIGN STANDARDS DATA DEFINITIONS. AUTHORIZED CONTRACTORS CAN CONTACT THE VA OFFICE OF CONSTRUCTION AND FACILITIES MANAGEMENT (CFM) TO REQUEST THIS
DOCUMENT.
7. BUILDING COMPONENT RESPONSE UNDER BLAST LOADING SHALL NOT EXCEED THE MAXIMUM RESPONSE
LIMITS FOR SDOF ANALYSIS…