Attachment 8 - Drawings FINAL.pdf
PDF 16 MB Posted
- Attached to
- Z1DA--619A4-23-106 Correct the Mechanical/Fixtures & Piping for Buildings 2, 4 & 4A (VA-26-00016382)
- Solicitation number
- 36C24726R0070
About this file
This document is a set of construction drawings for a federal contract to install dual parallel piping for domestic water and fire protection systems in Buildings 2, 4, and 4A at the Central Alabama Veteran's Health Care System East Campus in Tuskegee, Alabama. The contract number is 36C24723C0066, and the project number is 619A4-23-106. The drawings constitute the final submission dated November 6, 2023, and include comprehensive plumbing and fire protection designs with multiple sheets covering demolition plans, new work installations, details, schedules, and hazardous materials abatement plans.
The project scope includes installing new 4-inch reduced pressure principle backflow preventers (BFP-2, BFP-4, and BFP-4A) in service rooms across the three buildings, with new 4-inch cold water piping and associated drainage systems. Double check valve backflow preventers (DCV-2, DCV-4, and DCV-4A) are specified for fire protection systems in the building attics and upper floors. The drawings detail pipe support installations, fire-rated wall penetrations using 3M firestop systems, and modifications to existing dry pipe external resetting valves. Asbestos and lead-based paint abatement work is required in identified areas within the basements and attics, with sampling locations marked on separate hazardous materials abatement plans. The construction must comply with infection control protocols during renovation, operate after hours and weekends, and include seismic bracing for all piping 2.5 inches in diameter and larger, as well as proper vibration isolation for new equipment.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C24726R0070 0003.docx | DOCX document | |
| Attachment 10 - Revised RFI Answers.docx | DOCX document | |
| Attachment 11 - Hazmat Survey Report.pdf | ||
| Attachment 10 - RFI Answers.docx | DOCX document | |
| 36C24726R0070 0002.docx | DOCX document | |
| 36C24726R0070 0001.docx | DOCX document | |
| Attachment 9 - Site Visit Attend.pdf | ||
| Attachment 5 - Wage Determinations.txt | TXT text file | |
| Attachment 6 - INVOICING.pdf | ||
| Attachment 4 - Itemized Cost Breakdown.xlsx | XLSX spreadsheet | |
| Attachment 1 - Experience Modification Rate Form.pdf | ||
| Attachment 2 - SBA Vet SB Cert Program Class Dev.pdf | ||
| Attachment 3 - PPQ.pdf | ||
| Attachment 7 - SPECS - 619A4-23-106.pdf | ||
| 36C24726R0070_1.docx | DOCX document |
Show all 15
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
NOT TO SCALE
CAMPUS MAP
N
PROJECT SITE
PROJECT SITE
(BLDG. 2, 4 & 4A)
NOT TO SCALE
N
VICINITY MAP
PAGE
SHEET
TITLE
00-GENERAL
1 GI001 TITLE SHEET X
2 GI002 PROJECT INFORMATION X
3 GI003
SHEET INDEX
STANDARD ABBREVIATIONS
DD
SUBMISSION
CD1
SUBMISSION
CD2
SUBMISSION
X
X
PL001 PLUMBING LEGENDS AND ABBREVIATIONS
X
PD101 PLUMBING DEMOLITION PLAN BLDG. 4A
X
PL101 PLUMBING NEW WORK PLAN BLDG. 4A
X
X
FP101 FIRE RISER - BUILDING 2, ATTIC X
FIRE RISER - BUILDING 4A, 3RD FLOOR X
X
12 PL102 PLUMBING NEW WORK PLAN BLDG. 2
FP102
FIRE RISER - BUILDING 4, 3RD FLOORFP103
PL501 PLUMBING DETAILS AND SCHEDULE
GI004 INFECTION CONTROL, DEMOLITION & PHASING INFO
X
X
X
X
X
X
X
X
X
X
X
X
HA001
HA002
HA003
HAZARDOUS MATERIALS ABATEMENT PLAN
HAZARDOUS MATERIALS ABATEMENT PLAN
HAZARDOUS MATERIALS ABATEMENT PLAN
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
FIRE RISER DETAILSFP50117 X
FINAL
SUBMISSION
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
PD102 PLUMBING DEMOLITION PLAN BLDG. 2 X
TITLE SHEET
GI001
SD JL
CONTRACT NO.: 36C24723C0066
PROJECT NO.: 619A4-23-106
o n e e i g h t h i n c o e f o t t h r e e i n c h e s o t o n e a d a l f i n c h e o t o n e i n o t t h r e e q u a r t e r s i n o t o n e h a l f i n o t t h r e e e i g h t h s i n o t o n e q u a r t e r i n o t
VA FORM 08-6231, OCT 1978
A
123456789
123456789
B
C
D
A
B
C
D
E
F
Drawing Title Project Title
Checked
Building Number
Drawn
Revisions: Date
Date
Project No.
Drawing No.
Location
Sheet of
FINAL SUBMISSION
FULLY SPRINKLERED
V e t e r a n s
A f f a i r s
Approved: Associate Director
Approved: Chief of Staff
Approved: Service Chief
Approved: GEMS Coordinator
Approved: Infection Control Officer
Approved: Safety Manager
Approved: Chief of Mental Health Service
Approved: Chief of Police
Approved: Energy EngineerApproved: Patient Safety Nurse
Approved: Chief of Facility Management Svc.
Approved: Medical Center Director
TUSKEGEE, ALABAMA
2, 4 & 4A
2023.11.06
619A4-23-106
INSTALL DUAL PARALLEL PIPING
FOR DOMESTIC WATER AND FIRE
PROTECTION IN BUILDINGS 2, 4
AND 4A
D a
P l o t t e d
Rev. No.:
INCORPORATED
ENGINEERS
ARCHITECTS
CONSTRUCTORS
E
F
CENTRAL ALABAMA VETERAN'S HEALTH CARE SYSTEM, EAST CAMPUS
INSTALL DUAL PARALLEL PIPING FOR DOMESTIC
WATER AND FIRE PROTECTION IN BUILDINGS
2, 4 AND 4A
2023.10.26 e e i g h o t t h r e e i n c h e o t o n e a l f i n c h e o t o n e i n o t t h r e e q u a r t e r s i n o t o n e h a l f i n o t t h r e e e i g h t h s i n o t o n e q u a r t e r i n o t
VA FORM 08-6231, OCT 1978
A
123456789
123456789
B
C
D
A
B
C
D
E
F
Drawing Title Project Title
Checked
Building Number
Drawn
Revisions: Date
Date
Project No.
Drawing No.
Location
Sheet of
FINAL SUBMISSION
FULLY SPRINKLERED
V e t e r a n s
A f f a i r s
Approved: Associate Director
Approved: Chief of Staff
Approved: Service Chief
Approved: GEMS Coordinator
Approved: Infection Control Officer
Approved: Safety Manager
Approved: Chief of Mental Health Service
Approved: Chief of Police
Approved: Energy EngineerApproved: Patient Safety Nurse
Approved: Chief of Facility Management Svc.
Approved: Medical Center Director
TUSKEGEE, ALABAMA
2, 4 & 4A
2023.11.06
619A4-23-106
INSTALL DUAL PARALLEL PIPING
FOR DOMESTIC WATER AND FIRE
PROTECTION IN BUILDINGS 2, 4
AND 4A
D a t e
P l o t t e d
Rev. No.:
INCORPORATED
ENGINEERS
ARCHITECTS
CONSTRUCTORS
E
F
HAZARDOUS MATERIALS
HA001
SD JL
ABATEMENT PLAN
1/4" = 1'-0"
BULK SAMPLE LOCATION DRAWING - BLDG. 4A SUB-BASEMENT, WATER
1/4" = 1'-0"
BULK SAMPLE LOCATION DRAWING - BLDG. 2 BASEMENT, WATER
PLAN
NORTH
GENERAL
ABATEMENT NOTES
1. ALL ASBESTOS ABEATEMENT WORK SHALL COMPLY
WITH ALL FEDERAL, STATE AND LOCAL REGULATIONS.
2. REFER TO SPECIFICATION 028233 FOR REQUIREMENTS
PERTAINING TO THE REMOVAL AND DISPOSAL OF
ASBESTOS CONTAINING MATERIALS.
3. REFER TO "ASBESTOS CONTAINING MATERIALS
SURVEY REPORT" BUILDING 2, 4 AND 4A, TUSKEGEE
VAMC. PREPARED BY ENVIRONMENTAL HEALTH
CONSULTANTS, LLC, DATED AUGUST 21, 2023.
1. AT THE POINT OF THIS DESIGN ITERATION; THE SUPPLY
ROOM AND ABANDONED MEN'S RESTROOM IN THE
BASEMENT OF BUILDING 2 WERE NOT SURVEYED. AT
THE TIME OF CONSTRUCTION ONE OF THESE ROOMS
WILL BE INCLUDED IN THIS CONTRACT. THE
CONTRACTOR SHALL BE RESPONSIBLE TO CONDUCT
AN ASBESTOS AND LEAD SURVEY OF ANY/ALL AREAS
NOT COVERED BY THE REPORT PROVIDED WITH THIS
CONSTRUCTION DOCUMENTS THAT ARE IMPACTED BY
CONSTRUCTION. (“ASBESTOS CONTAINING MATERIALS
SURVEY REPORT ”BUILDING 2, 4 AND 4A. TUSKEGEE
VAMC. PREPARED BY ENVIRONMENTAL HEALTH
CONSULTANTS, LLC DATE AUGUST 21). WHERE
ASBESTOS OR LEAD CONTAINING MATERIALS ARE
FOUND; ABATEMENT SHALL CONDUCTED ACCORDING
TO THE SPECIFICATIONS 02 82 11 AND 02 83 33 13.
2. THE QUANTITIES AND AREAS SHOWN IN THE REPORT
ARE FOR INFORMATIONAL PURPOSES ONLY AND ARE
BASED ON THE BEST INFORMATION AVAILABLE AT THE
TIME OF THE SPECIFICATION PREPARATION. THE
CONTRACTOR SHALL SATISFY THEMSELVES OF THE
ACTUAL QUANTITIES TO BE ABATED. NOTHING MAY BE
INTERPRETED AS LIMITING THE EXTENT OF WORK
OTHERWISE REQUIRED BY THIS CONTRACT AND
RELATED DOCUMENTS.
SURVEY NOTES
SUPPLY ROOM
MEN'S ROOM
(ABANDONED)
FP-1 FIREPROOFING
FP-2 FIREPROOFING
FP-3 FIREPROOFING
FP-4 FIREPROOFING
FP-5 FIREPROOFING
EC-6 ENDCAP SEALANT
EC-7 ENDCAP SEALANT
PW-34 PIPE WRAP
PW-35 PIPE WRAP
SB-8 SADDLE BLOCK
SB-9 SADDLEBLOCK
SAMPLING
DESCRIPTION
BP-28 BASE PLASTER
BP-29 BASE PLASTER
FS-30 FIRESTOPPING - PATCH WHITE
FS-31 FIRESTOPPING - PATCH WHITE
FS-32 FIRESTOPPING - RED
FS-33 FIRESTOPPING - GRAY
SP-26 SKIM PLASTER
SP-27 SKIM PLASTER
SAMPLING
DESCRIPTION
DRAWING KEY
SAMPLE NUMBERS IN BLUE OR INDICATE NON-ACM
SAMPLE NUMBERS IN RED OR INDICATE ACM
N
A
N
N
N N N
NN
NN
N
N
N N
N N
N N
N
N e e i g h o t t h r e e i n c h e o t o n e a l f i n c h e o t o n e i n o t t h r e e q u a r t e r s i n o t o n e h a l f i n o t t h r e e e i g h t h s i n o t o n e q u a r t e r i n o t
VA FORM 08-6231, OCT 1978
A
123456789
123456789
B
C
D
A
B
C
D
E
F
Drawing Title Project Title
Checked
Building Number
Drawn
Revisions: Date
Date
Project No.
Drawing No.
Location
Sheet of
FINAL SUBMISSION
FULLY SPRINKLERED
V e t e r a n s
A f f a i r s
Approved: Associate Director
Approved: Chief of Staff
Approved: Service Chief
Approved: GEMS Coordinator
Approved: Infection Control Officer
Approved: Safety Manager
Approved: Chief of Mental Health Service
Approved: Chief of Police
Approved: Energy EngineerApproved: Patient Safety Nurse
Approved: Chief of Facility Management Svc.
Approved: Medical Center Director
TUSKEGEE, ALABAMA
2, 4 & 4A
2023.11.06
619A4-23-106
INSTALL DUAL PARALLEL PIPING
FOR DOMESTIC WATER AND FIRE
PROTECTION IN BUILDINGS 2, 4
AND 4A
D a t e
P l o t t e d
Rev. No.:
INCORPORATED
ENGINEERS
ARCHITECTS
CONSTRUCTORS
E
F
HAZARDOUS MATERIALS
HA002
SD JL
ABATEMENT PLAN
1/4" = 1'-0"
BULK SAMPLE LOCATION DRAWING - BLDG. 2 ATTIC
1/4" = 1'-0"
BULK SAMPLE LOCATION DRAWING - BLDG. 4A 3RD FLOOR
PLAN
NORTH
GENERAL
ABATEMENT NOTES
1. ALL ASBESTOS ABEATEMENT WORK SHALL COMPLY
WITH ALL FEDERAL, STATE AND LOCAL REGULATIONS.
2. REFER TO SPECIFICATION 028233 FOR REQUIREMENTS
PERTAINING TO THE REMOVAL AND DISPOSAL OF
ASBESTOS CONTAINING MATERIALS.
3. REFER TO "ASBESTOS CONTAINING MATERIALS
SURVEY REPORT" BUILDING 2, 4 AND 4A, TUSKEGEE
VAMC. PREPARED BY ENVIRONMENTAL HEALTH
CONSULTANTS, LLC, DATED AUGUST 21, 2023.
SAMPLING
DESCRIPTION
BP-13 BASE PLASTER
BP-14 BASE PLASTER
BP-15 BASE PLASTER
SP-10 SKIM PLASTER
SP-11 SKIM PLASTER
SP-12 SKIM PLASTER
SAMPLING
DESCRIPTION
FS-22 FIRESTOPPING - GRAY
FS-23 FIRESTOPPING - GRAY
FS-24 FIRESTOPPING - BLACK TAR
FS-25 FIRESTOPPING - BLACK TAR
DRAWING KEY
SAMPLE NUMBERS IN BLUE OR INDICATE NON-ACM
SAMPLE NUMBERS IN RED OR INDICATE ACM
N
A
AA
N N
N N N
N N N e e i g h o t t h r e e i n c h e o t o n e a l f i n c h e o t o n e i n o t t h r e e q u a r t e r s i n o t o n e h a l f i n o t t h r e e e i g h t h s i n o t o n e q u a r t e r i n o t
VA FORM 08-6231, OCT 1978
A
123456789
123456789
B
C
D
A
B
C
D
E
F
Drawing Title Project Title
Checked
Building Number
Drawn
Revisions: Date
Date
Project No.
Drawing No.
Location
Sheet of
FINAL SUBMISSION
FULLY SPRINKLERED
V e t e r a n s
A f f a i r s
Approved: Associate Director
Approved: Chief of Staff
Approved: Service Chief
Approved: GEMS Coordinator
Approved: Infection Control Officer
Approved: Safety Manager
Approved: Chief of Mental Health Service
Approved: Chief of Police
Approved: Energy EngineerApproved: Patient Safety Nurse
Approved: Chief of Facility Management Svc.
Approved: Medical Center Director
TUSKEGEE, ALABAMA
2, 4 & 4A
2023.11.06
619A4-23-106
INSTALL DUAL PARALLEL PIPING
FOR DOMESTIC WATER AND FIRE
PROTECTION IN BUILDINGS 2, 4
AND 4A
D a t e
P l o t t e d
Rev. No.:
INCORPORATED
ENGINEERS
ARCHITECTS
CONSTRUCTORS
E
F
HAZARDOUS MATERIALS
HA003
SD JL
ABATEMENT PLAN
1/4" = 1'-0"
BULK SAMPLE LOCATION DRAWING - BLDG. 4 3RD FLOOR
PLAN
NORTH
GENERAL
ABATEMENT NOTES
1. ALL ASBESTOS ABEATEMENT WORK SHALL COMPLY
WITH ALL FEDERAL, STATE AND LOCAL REGULATIONS.
2. REFER TO SPECIFICATION 028233 FOR REQUIREMENTS
PERTAINING TO THE REMOVAL AND DISPOSAL OF
ASBESTOS CONTAINING MATERIALS.
3. REFER TO "ASBESTOS CONTAINING MATERIALS
SURVEY REPORT" BUILDING 2, 4 AND 4A, TUSKEGEE
VAMC. PREPARED BY ENVIRONMENTAL HEALTH
CONSULTANTS, LLC, DATED AUGUST 21, 2023.
FT-16 FLOOR TILE
FT-17 FLOOR TILE
FM-18 FLOOR MASTIC
FM-19 FLOOR MASTIC
FS-20 FIRESTOPPING
FS-21 FIRESTOPPING
SAMPLING
DESCRIPTION
DRAWING KEY
SAMPLE NUMBERS IN BLUE OR INDICATE NON-ACM
SAMPLE NUMBERS IN RED OR INDICATE ACM
N
A
N N
N N
N N e e i g h o t t h r e e i n c h e o t o n e a l f i n c h e o t o n e i n o t t h r e e q u a r t e r s i n o t o n e h a l f i n o t t h r e e e i g h t h s i n o t o n e q u a r t e r i n o t
VA FORM 08-6231, OCT 1978
A
123456789
123456789
B
C
D
A
B
C
D
E
F
Drawing Title Project Title
Checked
Building Number
Drawn
Revisions: Date
Date
Project No.
Drawing No.
Location
Sheet of
FINAL SUBMISSION
FULLY SPRINKLERED
V e t e r a n s
A f f a i r s
Approved: Associate Director
Approved: Chief of Staff
Approved: Service Chief
Approved: GEMS Coordinator
Approved: Infection Control Officer
Approved: Safety Manager
Approved: Chief of Mental Health Service
Approved: Chief of Police
Approved: Energy EngineerApproved: Patient Safety Nurse
Approved: Chief of Facility Management Svc.
Approved: Medical Center Director
TUSKEGEE, ALABAMA
2, 4 & 4A
2023.11.06
619A4-23-106
INSTALL DUAL PARALLEL PIPING
FOR DOMESTIC WATER AND FIRE
PROTECTION IN BUILDINGS 2, 4
AND 4A
D a t e
P l o t t e d
Rev. No.:
INCORPORATED
ENGINEERS
ARCHITECTS
CONSTRUCTORS
E
F
JLWB
PL001
PLUMBING LEGENDS AND
ABBREVIATIONS
FE
CO
FD
SANITARY SEWER CLEANOUT (FLOOR)
FCO
EXISTING COLD WATER
EXISTING HOT WATER
EXISTING SS PIPING
NEW COLD WATER
SS
NEW SANITARY SEWER
NEW SS VENT PIPING
NEW HOT WATER
NEW HOT WATER RECIRCULATION
EXISTING HOT WATER RECIRCULATION
EXISTING SS VENT PIPING
(E) V
(E) HWR
(E) SAN
(E) DHW
(E) DCW
HWR
V
SAN
DHW
DCW
SANITARY SEWER CLEANOUT (WALL)
WCO
AV
WATER HAMMER ARRESTOR
ISOLATION VALVE
DEMO KEY NOTE (SEE SCHEDULE)
FLOOR DRAIN (INSTALL WITH TRAP SEAL)
HOSE BIB
CLEAN OUT
FLOW ELEMENT
PRESSURE GAGE
THERMOMETER
STRAINER
FLOAT & THERMOSTATIC TRAP SET INCLUDING PIPING
ACCESSORIES
INVERTED BUCKET TRAP SET INCLUDING PIPING ACCESSORIES
POINT OF CONNECTION BETWEEN NEW AND EXISTING WORK
POINT OF DISCONNECTION
PIPE DOWN
PIPE UP
UNION
RISE OR DROP IN PIPE
CAPPED OUTLET
SIDE CONNECTION
BOTTOM CONNECTION, 45° OR 90°
TOP CONNECTION, 45° OR 90°
ECCENTRIC REDUCER
REDUCER OR INCREASER
ANCHOR
DIRECTION OF FLOW
DIRECTION OF PIPE PITCH (DOWN)
GATE VALVE
GLOBE VALVE
GATE VALVE WITH 3/4 " HOSE ADAPTER
CHECK VALVE
ANGLE GLOBE VALVE
BUTTERFLY VALVE
BALL VALVE
SOLENOID VALVE (2 POSITION)
PRESSURE REGULATING VALVE
AUTOMATIC FLOW CONTROL VALVE
PRESSURE RELIEF VALVE
MANUAL AIR VENT
TEST PLUG (PRESSURE/TEMPERATURE)
AUTOMATIC AIR VENT
A/E ARCHITECT / ENGINEER
AD AREA DRAIN
AFF ABOVE FINISH FLOOR
AFG ABOVE FINISH GRADE
AG AIR GAP
AP ACCESS PANEL
ASHRAE AMERICAN SOCIETY HEATING,
REFRIGERATION, AIR CONDITIONING
ENGINEERS
ASME AMERICAN SOCIETY MECHANICAL
ENGINEERS
ASPE AMERICAN SOCIETY PLUMBING
ENGINEERS
BFP REDUCED PRESSURE BACKFLOW
PREVENTER
BHP BREAK HORSEPOWER
BSP BLACK STEEL PIPE
BTU BRITISH THERMAL UNIT
BTUH BRITISH THERMAL UNIT PER HOUR
C CELSIUS
CI CAST IRON
CO CLEANOUT
CRS CORROSION RESISTANT STEEL
CS CLINICAL SINK
CV CONTROL VALVE
CW COLD WATER (DOMESTIC)
DI DEIONIZED WATER
DN DOWN
DWG DRAWING
DWH DOMESTIC WATER HEATER
DWB DIALYSIS WALL BOX
DWV DRAIN WASTE VENT
EL ELEVATION
EMCS ENERGY MONOSERRAT AND CENTRAL
EPACT ENERGY POLICY ACT
ESC ESCUTCHEON
ESH EMERGENCY SHOWER
ET EXPANSION TANK
EWC ELECTRIC WATER COOLER
EWS EYE WASH STATION
EX OR E EXISTING
F FAHRENHEIT
FCO FLOOR CLEANOUT
FCU FAN COIL UNIT
FD FLOOR DRAIN
FDC FIRE DEPARTMENT
(HOSE) CONNECTION
FM FLOW METER
FS FLOOR SINK
FS FLOW SWITCH
FU FIXTURE UNITS
GAL GALLON
GCO GRADE CLEANOUT
GPD GALLONS PER DAY
GPH GALLONS PER HOUR
GPM GALLONS PER MINUTE
GVTR GAS VENT THROUGH ROOF
H&CW HOT AND COLD WATER
HB HOSE BIBHD HUB DRAIN
HEX HEAT EXCHANGER
HP HORSEPOWER
HS HAND SINK
HST HOT WATER STORAGE TANK
(DOMESTIC)
HW HOT WATER (DOMESTIC)
HWR HOT WATER RETURN (DOMESTIC)
HWS HOT WATER SUPPLY (DOMESTIC)
HWCP HOT WATER CIRCULATING PUMP
HWP HOT WATER PUMP
HYD HYDRANT
INV INVERT
IPC INTERNATIONAL PLUMBING CODE
KW KILOWATT
KWHR KILOWATT-HOUR
LAV LAVATORY
LBS/HR POUNDS PER HOUR
LW LOW WATER
M METER
MA MEDICAL AIR
MAV MANUAL AIR VENT
MBH 1000 BTUH
MED MEDICAL
MER MECHANICAL EQUIPMENT
ROOM
MH MANHOLE
MSB MOP SERVICE BASIN
NC NORMALLY CLOSED
NIC NOT IN CONTRACT
NO NORMALLY OPEN
NOM. NOMINAL
NPW NON POTABLE WATER
NTS NOT TO SCALE
OD OUTSIDE DIAMETER
OFD OVERFLOW DRAIN
OVFL OVERFLOW
PA PASCAL
PD PRESSURE DROP OR DIFFERENCE
PDI PLUMBING AND DRAINAGE INSTITUTE
PG PRESSURE GAGE
PPM PARTS PER MILLION
PRS PRESSURE REDUCING STATION
PRV PRESSURE REDUCING VALVE
PSI POUNDS PER SQUARE INCH
PSIA POUNDS PER SQUARE INCH ATMOSPHERE
PSIG POUNDS PER SQUARE INCH GAUGE
PTRV PRESSURE TEMPERATURE RELIEF VALVE
PW POTABLE WATER
RD ROOF DRAIN
RDC ROOF DRAIN CONDUCTOR
RDL ROOF DRAIN LEADER
RL ROOF LEADER
RO REVERSE OSMOSIS WATER
RWL RAIN WATER LEADER
SAN SANITARY SEWER
SCFM STANDARD CUBIC FOOT/MINUTE
SCW SOFTENED COLD WATER
SD STORM DRAIN
SDMH STORM DRAIN MANHOLE
SMACNA SHEET METAL AND AIR CONDITIONING
CONTRACTORS NATIONAL ASSOCIATION
SQFT SQUARE FEET
SSTL STAINLESS STEEL
SS SANITARY SEWER
ST STORM WATER
TCV TEMPERATURE CONTROL VALVE
TD TEMPERATURE DIFFERENCE
TD TRENCH DRAIN
TDH TOTAL DYNAMIC HEAD
TEMP TEMPERATURE
TVAC THERMOSTATIC MIXING VALVE
TP TRAP PRIMER
TSTAT THERMOSTAT
TYP TYPICAL
UNO UNLESS NOTED OTHERWISE
UPC UNIFORM PLUMBING CODE
V VENT
VAC MEDICAL VACUUM
VB VACUUM BREAKER
VS VENT STACK
VTR VENT THROUGH ROOF
W WASTE
WC WATER CLOSET
WCO WALL CLEANOUT
WG WATER GAGE
WH WALL HYDRANT
WH WATER HEATER
WHA WATER HAMMER ARRESTER
WL WATER LINE
WM WATER METER
WPD WATER PRESSURE DROP
WS WASTE STACK
YCO YARD CLEANOUT
YH YARD HYDRANT
PLUMBING ABBREVIATIONSPLUMBING LEGEND
NEW WORK NOTE (SEE SCHEDULE)
GENERAL FIRE PROTECTION NOTES
1. SLEEVE AND FIRE STOP ALL NEW PENETRATIONS THROUGH RATED WALLS, FLOORS AND CEILINGS IN
ACCORDANCE WITH APPLICABLE CODE REQUIREMENTS. SEE ARCHITECTURAL DRAWINGS FOR EXACT
LOCATIONS OF FIRE RATED ASSEMBLIES.
2. ALL EXISTING FIRE PENETRATIONS DISTURBED DURING CONSTRUCTION SHALL BE BROUGHT UP TO
APPLICABLE CODE REQUIREMENTS.
3. ALL PENETRATIONS CREATED BY REMOVAL OF DEMOLISHED ITEMS UNDER THIS CONTRACT THROUGH
RATED FLOOR/CEILING ASSEMBLIES AND THROUGH FIRE RATED WALL AND SMOKE BARRIER
ASSEMBLIES MUST BE SEALED AS PART OF THIS CONTRACT. SEAL ON BOTH SIDES WITH VA APPROVED
FIRE RATED CAULK. ALL RATED SEPARATIONS MUST MEET CURRENT CODE REQUIREMENTS.
LEGIONELLA MITIGATION NOTE
1. REFER TO VHA DIRECTIVE 1061, FEBRUARY 13, 2021 (AMENDED SEPT. 26, 2022) FOR INFORMATION ON THE
POLICY FOR THE PREVENTION AND CONTROL OF HEALTHCARE-ASSOCIATED LEGIONELLA DISEASE IN
VHA-OWNED BUILDINGS.
NOTES FOR SEISMIC BRACING (ALL P-SHEETS)
3. PROVIDE BRACING FOR RIGID SUPPORT ON ALL SIDES OF SUSPENDED EQUIPMENT, AND RESTRAINTS FOR
5. TRANSVERSE AND VERTICAL BRACING SHALL OCCUR AT 40 FOOT INTERVALS (MAX). LONGITUDINAL BRACING
FOR DUCTWORK OR PIPING.
OR OTHER SUPPORT.
OF SEISMICALLY BRACED MECHANICAL SYSTEMS.
RESILIENTLY SUPPORTED EQUIPMENT.
VERTICAL RESTRAINT ON ALL SIDES OF THE BASE TO RESTRICT DISPLACEMENT OF THE EQUIPMENT.
4. BRACE ALL PIPES 2 1/2" DIAMETER AND LARGER. RESTRAIN ALL PIPING IN MECHANICAL ROOMS THAT IS
2. FLOOR MOUNTED EQUIPMENT, WITH VIBRATION ISOLATORS, SHALL BE PROVIDED WITH LATERAL AND
1. FLOOR OR PAD MOUNTED EQUIPMENT, WITHOUT VIBRATION ISOLATORS, SHALL BE BOLTED TO THE FLOOR
D. SEE THE SPECIFICATIONS FOR MANUFACTURER'S RESPONSIBILITIES IN SUBMITTING THE PROPER DESIGN
7. DO NOT USE BRANCH LINES TO RESTRAIN MAIN LINES.
6. AT PIPE RISERS, WHEREVER POSSIBLE, SUPPORT THE WEIGHT OF THE RISER AT A POINT OR POINTS
RESPOND DIFFERENTLY DURING AN EARTHQUAKE; IE: A WALL AND A ROOF.
ABOVE THE CENTER OF GRAVITY OF THE RISER.
8. DO NOT FASTEN ONE RIGID PIPING SYSTEM TO TWO DISSIMILAR PARTS OF THE BUILDING THAT MAY
SHALL OCCUR AT 80 FOOT INTERVALS (MAX.).
1 1/4" DIAMETER AND LARGER.
PIPING
EQUIPMENT
WW-H-171 OR BE BOLTED/WELDED AS APPROVED BY THE ENGINEER.
C. WALLS, INCLUDING DRYWALL PARTITIONS, MAY REPLACE REQUIRED TRANSVERSE OR VERTICAL BRACING
B. ATTACHMENT TO STRUCTURAL MEMBERS SHALL USE DEVICES PROVIDED BY FEDERAL SPECIFICATION
A. BRACING IS NOT REQUIRED WHEN THE TOP OF DUCT OR PIPE IS SUSPENDED 12" OR LESS FROM THE
SUPPORTING STRUCTURAL MEMBER.
GENERAL
CONSTRUCTION WORKING HOURS NOTE
1. ALL CONSTRUCTION WORK TO BE PERFORMED AFTER HOURS AND ON WEEKENDS.
MV
O
MA
MV
MA
O
EXISTING MEDICAL VACUUM(E) VAC
EXISTING MEDICAL AIR(E) MA
EXISTING MEDICAL OXYGEN(E) O2
NEW MEDICAL VACUUMVAC
NEW MEDICAL AIRMA
NEW MEDICAL OXYGENO2
ST EXISTING STORM DRAIN(E) ST
O2 OXYGEN
N NEW
AREA NOT IN CONTRACT
DCW DOMESTIC COLD WATER
DHW DOMESTIC HOT WATER
WSFU WATER SUPPLY FIXTURE UNITS
DFU DRAINAGE FIXTURE UNITS
BALANCING VALVE
DEMO PIPE
DEMO FIXTURE
GENERAL PLUMBING NOTES
1 THE PLUMBING SYSTEM SHALL CONFORM TO THE INTERNATIONAL PLUMBING CODE (LATEST EDITION).
2 UNLESS OTHERWISE SPECIFIED OR DIRECTED, PROVIDE IN ACCORDANCE WITH ASHRAE STANDARD 90.1, AND THE ENERGY CONSERVATION REQUIREMENTS OF THE CONTRACT. SIZE AND PLACE EQUIPMENT SO
THAT IT IS EASILY ACCESSIBLE AND REMOVABLE FOR REPAIR OR REPLACEMENT.
4 ALL SANITARY DRAINAGE, WASTE AND VENT PIPING WILL BE LOCATED EITHER BELOW FLOOR, IN
SUSPENDED CEILINGS, IN PIPE CHASES, OR WITHIN WALLS AS INDICATED ON DRAWINGS. COMPLETE
ACCESSIBILITY WILL BE AVAILABLE TO ALL CLEANOUTS IN THE SANITARY DRAINAGE PIPING AND
INTERVALS WILL BE SPACED ACCORDING TO THE INTERNATIONAL PLUMBING CODE.
5 PROVIDE VALVES ON ALL BRANCH LINES SERVING TWO OR MORE FIXTURES OR EQUIPMENT ITEMS.
6 DRAINAGE PIPING LARGER THAN 2" DIAMETER SHALL BE SLOPED NO LESS THAN 1/8" / FT.
7 DRAINAGE PIPING 2" AND SMALLER DIAMETER SHALL BE SLOPED NO LESS THAN 1/4" / FT.
8 ROUGH IN WASTE AND SUPPLIES TO SPECIAL EQUIPMENT IN ACCORDANCE WITH MANUFACTURER'S
RECOMMENDATIONS AND MAKE FINAL CONNECTIONS. ALL SUPPLIES SHALL HAVE SHUT-OFF VALVES.
INSTALL VACUUM BREAKERS WHERE REQUIRED BY CODE.
9 VALVES LOCATED ABOVE THE CEILING SHALL BE EASILY ACCESSIBLE BY EITHER REMOVABLE CEILING
TILES OR 30" WIDE ACCESS PANELS. CONTRACTOR SHALL PROVIDE AND COORDINATE ALL NECESSARY
ACCESS PANELS. ALL ACCESS PANELS SHALL BE TAMPER PROOF. SEE ARCHITECTURAL DRAWINGS FOR
CEILING TYPES.
10 LEAVE NO DEAD END BRANCHES IN DOMESTIC PIPING SYSTEM. REMOVE PIPING TO WITHIN THREE PIPE
DIAMETERS OF HEADER.
11 DO NOT ROUTE ANY PLUMBING PIPING THROUGH AN ELECTRICAL OR TELECOMM ROOM AND DO NOT
ROUTE PIPING DIRECTLY ABOVE AN ELECTRICAL PANEL.
12 PLUMBING SYSTEMS SHALL BE LABELED AND PAINTED IN ACCORDANCE WITH SPECIFICATION 09 91 00.
13 WATER HAMMER ARRESTORS SHALL BE INSTALLED WITH INLET ISOLATION VALVES TO ALLOW FOR
MAINTENANCE. PROVIDE ACCESS (INCLUDING DOORS WHERE APPLICABLE) FOR EACH ARRESTOR.
14 ALL PLUMBING LINES THAT ARE CAPPED SHALL BE PROTECTED DURING DEMOLITION.
15 THE FIRE PROTECTION CONTRACTOR IS REQUIRED TO PERFORM A FLOW TEST AND PROVIDE THAT
INFORMATION TO THE VAMC.
PLUMBING PIPING SHALL BE COORDINATED WITH ALL TRADES TO AVOID CONFLICTS, IN ORDER TO PROVIDE
A CODE COMPLIANT INSTALLATION, THIS SHALL INCLUDE ALL PHASES OF WORK AND EQUIPMENT SPACES
AND INTERRUPTIONS OF SERVICES WITH COR.
WATER PIPING SHALL BE SLOPED FOR DRAINAGE WITH DRAIN VALVES INSTALLED AT LOW POINTS.
17 ALL VERTICAL SUPPLY, SANITARY WASTE AND VENT PIPING SHALL BE LOCATED IN WALLS OR PARTITIONS, UNLESS NOTED OTHERWISE.
19 SANITARY VENTS WILL BE COLLECTED ABOVE THE CEILING AND EXTENDED UP AND CONNECT TO EXISTING
VENT THRU ROOF (VTR).
18 SUPPLY PIPING SHALL BE LOCATED ABOVE THE CEILING, UNLESS NOTED OTHERWISE.
20 THESE ENGINEERING DRAWINGS ARE DIAGRAMMATIC. IT IS THE INTENTION OF THESE DRAWINGS TO COVER
ALL WORK AND MATERIAL FOR A COMPLETE INSTALLATION. MAKE PROPER HOT AND COLD WATER, WASTE, VENT, ETC. PIPING CONNECTIONS TO ALL FIXTURES AND EQUIPMENT. ALTHOUGH ALL FITTINGS AND
CONNECTIONS ARE NOT SHOWN, THE PLUMBING CONTRACTOR IS RESPONSIBLE FOR PROVIDING PIPE
ESCUTCHEONS, DIELECTRIC UNIONS, DRIP PANS, PIPE LABELS, VALVE TAGS, ANCHORS, SUPPORT SEALS, SLEEVE SEALS, ISOLATION VALVES, CLEANOUTS, ETC. IN QUANTITIES ADEQUATE TO SATISFY THE INTENT OF
THE ENGINEER'S DOCUMENTS. ANY EQUIPMENT, PLUMBING FIXTURES, TRIM HARDWARE AND/OR DEVICES
USUALLY UTILIZED IN THIS CLASS OF WORK, THOUGH NOT SPECIFICALLY MENTIONED OR SHOWN ON THESE
DRAWINGS, BUT WHICH MAY BE NECESSARY FOR THE SATISFACTORY COMPLETION OF THE WORK (AS
DETERMINED BY THE COR) SHALL BE FURNISHED AND INSTALLED BY THE CONTRACTOR AS PART OF HIS
TOTAL WORK.
21 PROVIDE INSULATION ON ALL NEW PIPING.
22 PIPE HANGERS, HANGERS, BRACES AND RESTRAINT SHALL ADEQUATELY SUPPORT THE SYSTEM
HORIZONTALLY AND VERTICALLY AND SHALL ALLOW FOR MOVEMENT WITHOUT TRANSMITTING STRESS OR
VIBRATION TO THE STRUCTURE. HANGERS SHALL BE EQUAL TO GRINNELL PRODUCTS. HANGERS ON
INSULATED PIPING SHALL BE PROVIDED WITH AND SHALL BE SIZED TO ACCOMMODATE HANGERS, SHIELDS
AND SADDLES. HORIZONTAL SOIL, WASTE AND VENT PIPING HUNG FROM BUILDING CONSTRUCTION SHALL
BE SUPPORTED AT NOT OVER 5 FEET NEXT TO FITTINGS. PROVIDE ADDITIONAL SUPPORT AT JOINTS, CHANGES IN DIRECTION AND ELSEWHERE AS REQUIRED TO MAINTAIN PROPER ALIGNMENT.
23 THE CONTRACTOR SHALL CLEAN ALL FIXTURES, ADJUST ALL VALVES AND LEAVE THE SYSTEM IN GOOD
WORKING ORDER. REMOVE ALL DEBRIS AND RUBBISH CAUSED BY HIS WORK AND REPAIR AND DAMAGE
CAUSED BY HIS WORKMANSHIP.
24 THE PLUMBING CONTRACTOR SHALL SEAL ALL OF HIS PENETRATIONS OF FIRE-RATED WALLS USING UL
LISTED PENETRATION MATERIALS.
25 THE PLUMBING CONTRACTOR SHALL PROVIDE ALL OPENINGS IN WALLS AND FLOORS REQUIRED TO
COMPLETE HIS WORK, UNLESS OTHERWISE NOTED. HE SHALL VERIFY THE LOCATION AND SIZE OF ALL
OPENINGS REQUIRED UNDER THIS CONTRACT WITH THE GENERAL CONTRACTOR.
26 WORK SHALL INCLUDE DEMOLITION ON THE PLUMBING DRAWINGS AND INSTALLATION OF DOMESTIC COLD
WATER, WASTE PIPING, ISOLATION VALVES AS INDICATED ON THE PLUMBING DRAWINGS. THE DOMESTIC
WATER SYSTEM COMPONENTS SHALL BE DESIGNED TO WITHSTAND THE MAXIMUM STATIC PRESSURE AND
FLOW, BUT IN NO CASE SHALL BE LESS THAN 125 POUND CLASS.
27 SANITARY CLEANOUTS SHALL BE LOCATED IN ACCORDANCE WITH SECTIONS 708.3.1 THROUGH 708.3.6 OF
THE INTERNATIONAL PLUMBING CODE. SPECIFICALLY, ALL HORIZONTAL DRAINS SHALL BE PROVIDED WITH
CLEANOUTS LOCATED NOT MORE THAN 100 FT. APART. CLEANOUTS SHALL BE INSTALLED AT EACH CHANGE
OF DIRECTION GREATER THAN 45 DEGREES IN THE BUILDING SEWER, BUILDING DRAIN AND HORIZONTAL
WASTE OR SOIL LINES. WHERE MORE THAN ONE CHANGE OF DIRECTION OCCURS IN A RUN OF PIPING, ONLY
ONE CLEANOUT SHALL BE REQUIRED FOR EACH 40 FEET OF DEVELOPED LENGTH.
DPV DRY PIPE VALVE
2023.10.26 jlogan Text Box
EPA ENVIRONMENTAL PROTECTION AGENCY
jlogan Text Box
SYSTEM
SERVICE ROOM SB-1
HW STG. TK.
EX. 6"Ø CW
EX. 2
"Ø
DN.
EX. 4"Ø CW
TO BLDG. 4
EX. 4"Ø CW
TO BLDG. 4A
PIT
3'-9"
(FIELD VERIFY)
BLDG. 4A
3A3244A
BUILDING KEY PLAN
4"Ø
EX. 4"Ø TO BLDG. 4
EX. 4"Ø TO BLDG. 4A
ELEVATION
EX. 6"Ø CW
FROM MAIN
EX. 2
"Ø
FIN. FLOOR EL. 453'-0"
C EL. 459'-6"
C EL. 461'-9"±
o n e e i g h o t t h r e e i n c h e o t o n e a l f i n c h e o t o n e i n o t t h r e e q u a r t e r s i n o t o n e h a l f i n o t t h r e e e i g h t h s i n o t o n e q u a r t e r i n o t
VA FORM 08-6231, OCT 1978
A
123456789
123456789
B
C
D
A
B
C
D
E
F
Drawing Title Project Title
Checked
Building Number
Drawn
Revisions: Date
Date
Project No.
Drawing No.
Location
Sheet of
FINAL SUBMISSION
FULLY SPRINKLERED
V e t e r a n s
A f f a i r s
Approved: Associate Director
Approved: Chief of Staff
Approved: Service Chief
Approved: GEMS Coordinator
Approved: Infection Control Officer
Approved: Safety Manager
Approved: Chief of Mental Health Service
Approved: Chief of Police
Approved: Energy EngineerApproved: Patient Safety Nurse
Approved: Chief of Facility Management Svc.
Approved: Medical Center Director
TUSKEGEE, ALABAMA
2, 4 & 4A
2023.11.06
619A4-23-106
INSTALL DUAL PARALLEL PIPING
FOR DOMESTIC WATER AND FIRE
PROTECTION IN BUILDINGS 2, 4
AND 4A
D a t e
P l o t t e d
Rev. No.:
INCORPORATED
ENGINEERS
ARCHITECTS
CONSTRUCTORS
E
F
JLWB
PD101
1/4" = 1'-0"
PLUMBING DEMOLITION PLAN - BLDG. 4A SUB-BASEMENT, WATER
PLUMBING DEMOLITION PLAN
BLDG. 4A
PLAN
NORTH
1/4"=1'-0"
4' 0' 4' 8'
DRAWING DEMO KEYED NOTES
DEMO APPROXIMATE 3'-9" EXISTING SECTION OF 4"Ø PIPE FOR
INSTALLATION OF NEW BACKFLOW PREVENTER AND FITTINGS.
GENERAL PLUMBING NOTES
FOR LEGEND, SEE DWG. PL001.
LEGEND
1. FOR GENERAL PLUMBING NOTES, SEE DWG. PL001.
2. EXISTING PLUMBING IS SHOWN FOR REFERENCE ONLY. LOCATION
AND ROUTING OF EXISTING PIPING SHOULD BE VERIFIED PRIOR TO
CONSTRUCTION.
3. FOR PLUMBING SCHEDULE, SEE DRAWING PL601.
4. ALL EXISTING DIMENSIONS WERE TAKEN FROM FIELD NOTES AND
SHOULD BE VERIFIED BEFORE CONSTRUCTION.
DEMO EXISTING 4" PRESSURE REDUCING CONTROL VALVE,
VALVES, PIPING AND SUPPORTS AS SHOWN.
1/2" = 1'-0"
BLDG. 4A BASEMENT PLUMBING ELEVATION (DEMO)
NOTE:
ELEVATION IS LOOKING NORTH.
DEMO EXISTING SECTION OF 4"Ø PIPE IN VERTICAL RUN IN ORDER
TO RAISE HORIZONTAL SECTION DUE TO ELEVATION CHANGE AT
TIE-IN NEAR CW SERVICE ENTRY INTO BUILDING. FIELD DETERMINE
LENGTH OF PIPE TO BE REMOVED, ACCOUNTING FOR ANY EXISTING
INTERFERENCES.
SERVICE ROOM SB-1
HW STG. TK.
EX. 6"Ø CW
EX. 2
"Ø
DN.
EX. 4"Ø CW
TO BLDG. 4
EX. 4"Ø CW
TO BLDG. 4A
BLDG. 4A
BFP
4"
BFP
4A
4"
PIT
3'-6"
MATCH CL ELEVATION OF
EXISTING PIPE OF
APPROXIMATELY 459'-1
3A3244A
BUILDING KEY PLAN
VENT
ZURN
4"
WILKINS
4" 4"
VENT
ZURN
4"
WILKINS
4" 4"
4"Ø CW TO BLDG. 4
4"Ø CW TO BLDG. 4A
EX. 6"Ø CW
FROM MAIN
EX. 2
"Ø
FIN. FLOOR EL. 453'-0"
ROTATE HANDWHEELS
OUT 45° (TYP.) IF NEEDED
BFP FOR BLDG. 4 ELEVATION - LOOKING NORTH
C EL.
C EL. 459'-6"
C EL. 461'-9"±
C EL. 461'-0"±
FIELD ROUTE DRAIN TO
NEAREST SS, INSTALL
AIR GAP FITTING
BASE ELL SUPPORT
TYP. 2 (EA. SIDE)
BRACE WITH NEW
PIPE SUPPORT
FROM WALL (TYP. 4)
NEW 4" REDUCED PRESSURE
PRINCIPLE BACKFLOW
PREVENTER WITH GATE
VALVES (TYP. 2 PLACES)
VENT
ZURN
4"
WILKINS
4" 4"
VENT
ZURN
4"
WILKINS
4" 4"
FIN. FLOOR EL. 453'-0"
NEW FLOOR
MOUNTED PIPE
SUPPORT (TYP. 2)
NEW 4" REDUCED PRESSURE
PRINCIPLE BACKFLOW
PREVENTER WITH GATE
VALVES (TYP. 2 PLACES)
ROTATE HANDWHEELS
OUT 45° (TYP.) IF NEEDED
BFP FOR BLDG. 4A ELEVATION - LOOKING EAST
NEW 4"Ø CW
C EL. 459'-1
"C EL. 459'-1
FIELD ROUTE DRAIN TO
NEAREST SS, INSTALL
AIR GAP FITTING
o n e e i g h o t t h r e e i n c h e o t o n e a l f i n c h e o t o n e i n o t t h r e e q u a r t e r s i n o t o n e h a l f i n o t t h r e e e i g h t h s i n o t o n e q u a r t e r i n o t
VA FORM 08-6231, OCT 1978
A
123456789
123456789
B
C
D
A
B
C
D
E
F
Drawing Title Project Title
Checked
Building Number
Drawn
Revisions: Date
Date
Project No.
Drawing No.
Location
Sheet of
FINAL SUBMISSION
FULLY SPRINKLERED
V e t e r a n s
A f f a i r s
Approved: Associate Director
Approved: Chief of Staff
Approved: Service Chief
Approved: GEMS Coordinator
Approved: Infection Control Officer
Approved: Safety Manager
Approved: Chief of Mental Health Service
Approved: Chief of Police
Approved: Energy EngineerApproved: Patient Safety Nurse
Approved: Chief of Facility Management Svc.
Approved: Medical Center Director
TUSKEGEE, ALABAMA
2, 4 & 4A
2023.11.06
619A4-23-106
INSTALL DUAL PARALLEL PIPING
FOR DOMESTIC WATER AND FIRE
PROTECTION IN BUILDINGS 2, 4
AND 4A
D a t e
P l o t t e d
Rev. No.:
INCORPORATED
ENGINEERS
ARCHITECTS
CONSTRUCTORS
E
F
JLWB
PL101
1/4" = 1'-0"
PLUMBING NEW WORK PLAN - BLDG. 4A SUB-BASEMENT, WATER
PLUMBING NEW WORK PLAN
BLDG. 4A
PLAN
NORTH
1/4"=1'-0"
4' 0' 4' 8'
DRAWING NEW WORK KEYED NOTES
INSTALL NEW WALL-MOUNTED PIPE SUPPORTS.
GENERAL PLUMBING NOTES
FOR LEGEND, SEE DWG. PL001.
LEGEND
1. FOR GENERAL PLUMBING NOTES, SEE DWG. PL001.
2. EXISTING PLUMBING IS SHOWN FOR REFERENCE ONLY. LOCATION
AND ROUTING OF EXISTING PIPING SHOULD BE VERIFIED PRIOR TO
CONSTRUCTION.
3. FOR BACKFLOW PREVENTER SCHEDULE, SEE DRAWING PL501.
4. CONTRACTOR SHALL PROVIDE ADEQUATE VIBRATION CONTROL FOR
NEW BACKFLOW PREVENTER ASSEMBLIES AND PIPING.
INSTALL NEW 4" REDUCED PRINCIPLE BACKFLOW PREVENTER WITH
GATE VALVES. BFP-4 SERVING BUILDING 4 WILL BE INSTALLED ON
NORTH WALL OF SERVICE ROOM SB-1. BFP-4A SERVING BUILDING
4A WILL BE INSTALLED ON THE EAST WALL OF SERVICE ROOM SB-1.
1/2" = 1'-0"
BLDG. 4A SUB-BASEMENT BFP-4A ELEVATION (NEW)
NOTE:
ELEVATION IS LOOKING EAST.
1/2" = 1'-0"
BLDG. 4A SUB-BASEMENT BFP-4 ELEVATION (NEW)
NOTE:
ELEVATION IS LOOKING NORTH.
LOCATION
INSTALL NEW FLOOR-MOUNTED PIPE SUPPORTS.
RAISE THIS SECTION OF EXISTING 4" PIPE TO MATCH ELEVATION TO
THE SOUTH OF APPROXIMATELY 459' 1
3A3244A
BUILDING KEY PLAN
4" CW (EXIST.)
ELEV.
ROOM
MEN'S ROOM
(NOT IN USE)
SUPPLY
ROOM
ELEVATOR
STAIRS
STORAGE
PUMP
ROOM
MECH.
ROOM
BFP
4"
(ALT. LOC.)
EX. DOM. WATER
TO UPPER FLOORS
1'-0"
(MIN.)
VENT
ZURN
4"
WILKINS
4" 4"
VENT
ZURN
4"
WILKINS
4" 4"
FIN. FLOOR EL. 453'-0"
NEW FLOOR
MOUNTED PIPE
SUPPORT (TYP. 2)
NEW 4" REDUCED PRESSURE
PRINCIPLE BACKFLOW
PREVENTER WITH GATE
VALVES (TYP. 2 PLACES)
ROTATE HANDWHEELS
OUT 45° (TYP.) IF NEEDED
BFP FOR BLDG. 2 ELEVATION - LOOKING SOUTH
NEW 4"Ø CW
C EL.C EL.
FIELD ROUTE DRAIN TO
NEAREST SS, INSTALL
AIR GAP FITTING
o n e e i g h o t t h r e e i n c h e o t o n e a l f i n c h e o t o n e i n o t t h r e e q u a r t e r s i n o t o n e h a l f i n o t t h r e e e i g h t h s i n o t o n e q u a r t e r i n o t
VA FORM 08-6231, OCT 1978
A
123456789
123456789
B
C
D
A
B
C
D
E
F
Drawing Title Project Title
Checked
Building Number
Drawn
Revisions: Date
Date
Project No.
Drawing No.
Location
Sheet of
FINAL SUBMISSION
FULLY SPRINKLERED
V e t e r a n s
A f f a i r s
Approved: Associate Director
Approved: Chief of Staff
Approved: Service Chief
Approved: GEMS Coordinator
Approved: Infection Control Officer
Approved: Safety Manager
Approved: Chief of Mental Health Service
Approved: Chief of Police
Approved: Energy EngineerApproved: Patient Safety Nurse
Approved: Chief of Facility Management Svc.
Approved: Medical Center Director
TUSKEGEE, ALABAMA
2, 4 & 4A
2023.11.06
619A4-23-106
INSTALL DUAL PARALLEL PIPING
FOR DOMESTIC WATER AND FIRE
PROTECTION IN BUILDINGS 2, 4
AND 4A
D a
P l o t t e d
Rev. No.:
INCORPORATED
ENGINEERS
ARCHITECTS
CONSTRUCTORS
E
F
JLWB
PL102
SCALE: 3/16" = 1'-0"
0 12' 16'8'4'
3/16" = 1'-0"
PLUMBING NEW WORK PLAN - BLDG. 2 BASEMENT, WATER
DRAWING KEYED NOTES
GENERAL PLUMBING NOTES
FOR LEGEND, SEE DWG. PL001.
LEGEND
1. FOR GENERAL PLUMBING NOTES, SEE DWG. PL001.
2. EXISTING PLUMBING IS SHOWN FOR REFERENCE ONLY. LOCATION
AND ROUTING OF EXISTING PIPING SHOULD BE VERIFIED PRIOR TO
CONSTRUCTION.
3. FOR BACKFLOW PREVENTER SCHEDULE, SEE DRAWING PL501.
4. CONTRACTOR SHALL PROVIDE ADEQUATE VIBRATION CONTROL FOR
NEW BACKFLOW PREVENTER ASSEMBLIES AND PIPING.
PLUMBING NEW WORK PLAN
BLDG. 2
PLAN
NORTH
INSTALL NEW 4" REDUCED PRINCIPLE BACKFLOW PREVENTER WITH
GATE VALVES. BFP-2 SERVING BUILDING 2 WILL BE INSTALLED ON
SOUTH WALL OF SUPPLY ROOM SB-1.
INSTALL NEW FLOOR-MOUNTED PIPE SUPPORTS.
TIE-IN FOR NEW POTABLE WATER PIPING TO BFP MUST BE MADE
BEFORE FIRST BRANCH OF 4" MAIN.
1/2" = 1'-0"
BLDG. 2 BASEMENT BFP-2 ELEVATION (NEW, ALT.)
e e i g h o t t h r e e i n c h e o t o n e a l f i n c h e o t o n e i n o t t h r e e q u a r t e r s i n o t o n e h a l f i n o t t h r e e e i g h t h s i n o t o n e q u a r t e r i n o t
VA FORM 08-6231, OCT 1978
A
123456789
123456789
B
C
D
A
B
C
D
E
F
Drawing Title Project Title
Checked
Building Number
Drawn
Revisions: Date
Date
Project No.
Drawing No.
Location
Sheet of
FINAL SUBMISSION
FULLY SPRINKLERED
V e t e r a n s
A f f a i r s
Approved: Associate Director
Approved: Chief of Staff
Approved: Service Chief
Approved: GEMS Coordinator
Approved: Infection Control Officer
Approved: Safety Manager
Approved: Chief of Mental Health Service
Approved: Chief of Police
Approved: Energy EngineerApproved: Patient Safety Nurse
Approved: Chief of Facility Management Svc.
Approved: Medical Center Director
TUSKEGEE, ALABAMA
2, 4 & 4A
2023.11.06
619A4-23-106
INSTALL DUAL PARALLEL PIPING
FOR DOMESTIC WATER AND FIRE
PROTECTION IN BUILDINGS 2, 4
AND 4A
D a t e
P l o t t e d
Rev. No.:
INCORPORATED
ENGINEERS
ARCHITECTS
CONSTRUCTORS
E
F
JLWB
PL501
PLUMBING DETAILS AND
SCHEDULE
NOT TO SCALE
9C
TYP. BACKFLOW PREVENTER PIPING DETAIL
DESCRIPTION SIZE NOTES
REDUCED PRESSURE PRINCIPLE BACKFLOW PREVENTER ASSEMBLY:
1. BASIS OF DESIGN IS ZURN-WILKINS BUT IS NOT INTENDED TO LIMIT SELECTION. PROVIDE INDICATED
EQUIPMENT OR EQUIPMENT OF EQUAL CAPACITY, QUALITY AND PERFORMANCE.
4"
SYM
BFP-4
NOTES:
ZURN-WILKINS MODEL 375 DUCTILE IRON ASTM A536 BODY AND ACCESS
COVERS, NRS SHUT-OFF VALVES (OS&Y), FLANGED CONNECTIONS
DRAIN
1"
14"
BFP-4A
ZURN-WILKINS MODEL 375 DUCTILE IRON ASTM A536 BODY AND ACCESS
1"
REDUCED PRESSURE PRINCIPLE BACKFLOW PREVENTER ASSEMBLY:
COVERS, NRS SHUT-OFF VALVES (OS&Y), FLANGED CONNECTIONS
BFP-2
m m
WALL LINE
REDUCED PRESSURE
PRINCIPLE BACKFLOW
PREVENTER WITH GATE
VALVES
PLAN
AIR GAP
FITTING
WATER LINE
FROM METER
PIPE TO DRAIN (TYPICAL)
FINISHED FLOOR
COLD WATER TO SYSTEM
PIPE SUPPORT
ELEVATION
M
I N m m
T O
B O
T T
O M
O F
R E
L I E
F
O P
E N
I N
G S
REDUCED PRESSURE PRINCIPLE BACKFLOW PREVENTER ASSEMBLY:
14"
ZURN-WILKINS MODEL 375 DUCTILE IRON ASTM A536 BODY AND ACCESS
COVERS, NRS SHUT-OFF VALVES (OS&Y), FLANGED CONNECTIONS
1"
ALL THREAD ROD
CLEVIS HANGER
INSULATION
SHEETMETAL SHIELD
INSULATION PROTECTIVE
WASHER (TOP & BOTTOM)
NUT (TOP & BOTTOM)
PIPE
6C
TYP. CLEVIS HANGER DETAIL
NTS
2.
1.
UL CLASSIFICATION SYSTEM #147
ON EACH SIDE OF METAL STUD)
(1 LAYER OF FIRE RATED GYPSUM
OR CONDUIT
INSULATED METAL PIPE
PANEL SURFACE.
TO EXTERIOR OF GYPSUM
2 HOUR RATING, FLUSH
3/4" THICKNESS FOR
1 HOUR RATING.
1/2" THICKNESS FOR
APPLY TO BOTH SIDES OF WALL
AT JUNCTION WITH GYPSUM PANEL.
AROUND PERIMETER OF PIPE SLEEVE
BACKER ROD
METAL SLEEVE
METAL PIPE, FIBERGLASS
CP-25 N/S CAULK
1/4" BEAD OF CP-25 N/S CAULK
1-HOUR FIRE RATED WALL SECTION.
FIRE CURVE AND 3M APPLICATIONS ENGINEERING.
PER ASTM E-814 (UL 1479) TIME TEMPERATURE
RECOMMENDATIONS BASED ON PRODUCT PERFORMANCE
INSTALL 3M FIRESTOP ON BOTH SIDES OF WALL
OF WALL
FIRE BARRIER.
PENETRATES THE WALL OR FLOOR WHEN USING 3M
IT IS NOT NECESSARY TO REMOVE INSULATION AS IT
EXPOSURE. UL CLASSIFIED PER SYSTEM 91
ASTM E-814 (UL 1479) TIME TEMPERATURE CURVE FIRE
RECOMMENDATIONS BASED ON PRODUCT PERFORMANCE PER
MAXIMUM ANNULAR SPACE TO BE FILLED IS 2-1/2"
MINIMUM ANNULAR SPACE TO BE FILLED IS 3/4".
2"-3" OF INSULATION - 2" DEPTH OF CP-25 N/S OR S/L
1" OF INSULATION - 1" DEPTH OF CP-25 N/S OR S/L
DEPTH OF CP-25 CAULK DEPENDS ON INSULATION THICKNESS:
B) FOR INSULATED METAL PIPE:
MAXIMUM ANNULAR SPACE TO BE FILLED IS 2-1/2"
ACCEPTABLE AFTER INITIAL WET DEPTH INSTALLATION.
UP TO 40% SHRINKAGE OF CP-25 N/S OR S/L CAULK IS
PER ASTM E-814 (UL 1479) FIRE TEST AND UL
CLASSIFICATION FIRE STOP SYSTEM 49.
RECOMMENDATIONS BASED ON PRODUCT PERFORMANCE
3-4 HOURS
1-2 HOURS
MAX 8"
MAX 8"
1"
1/2"
FIRE RATING PIPE SIZE WET DEPTH
ON TYPE AND SIZE OF PIPE: AND DESIRED FIRE RATING.
WET INSTALLED DEPTH OF CP-25 CAULKS DEPENDS
A) FOR UNINSULATED METAL PIPE:
2. DEPTH OF CP-25 CAULK:
WITHIN WALL WITH DAMMING MATERIAL ON ONE SIDE.
1. FOR SOLID CONCRETE WALLS, CENTER CP-25 N/S CAULK
CAULK ON EACH SIDE
WALLS SEE NOTE 1
FOR SOLID CONCRETE
CONCRETE BLOCK WALL.
DAMMING MATERIAL
METAL PIPE SLEEVE
DEPTH OF CP-25 N/S
1-2-3 HOUR FIRE RATED
INSULATED METAL PIPE
METAL PIPE OR
SURFACES WHEN FILLING GAPS FROM BELOW.
VERTICAL SURFACES AND ON HORIZONTAL
USE CP-25 N\S NO SAG CAULK ON
GAPS FROM ABOVE THE PENETRATION.
ON HORIZONTAL SURFACES WHEN FILLING
USE CP-25 S/L SELF-LEVELING CAULK
CONCRETE FLOOR SLAB
INSULATED METAL PIPE
ENOUGH TO SUPPORT WEIGHT OF CAULK
INSULATION, BACKER ROD OR SAFING)
OF SLAB (TYP. EA. SIDE)
(SEE NOTES) FLUSH TO SURFACE
PIPE WITH CP-25 S/L CAULK
DAMMING MATERIAL (FIBERGLASS
FILL GAP COMPLETELY AROUND
1-2-3 HOUR FIRE RATED
METAL PIPE SLEEVE
METAL PIPE OR
4F
PIPE PENETRATION THRU FIRE-RATED WALLS
NTS
EX. 4"Ø FP RISER
FROM BELOW
EX. 4"Ø FP PIPING
TO BLDG. 2
EX. 4"Ø DRY PIPE VALVE
(IN VERT.), TYCO DPV-1
EX. 2"Ø DRAIN
1'-0 1/2"
ACCESS HATCH
3A3244A
BUILDING KEY PLAN
DPV-1
4" EX.
EX. 2"Ø DRAIN
EX. 4"Ø FP PIPING
ENTERING THRU FLOOR
EX. 4"Ø FP PIPING
THRU WALL
ATTIC FL EL. 509'-2"
ATTIC FL EL. 509'-2"
EX. 2"Ø DRAIN
EX. 4"Ø FP PIPING
ENTERING THRU FLOOR
EX. 4"Ø FP PIPING
THRU WALL
DPV-1
4" EX.
4"
DCV
o n e e i g h o t t h r e e i n c h e o t o n e a l f i n c h e o t o n e i n o t t h r e e q u a r t e r s i n o t o n e h a l f i n o t t h r e e e i g h t h s i n o t o n e q u a r t e r i n o t
VA FORM 08-6231, OCT 1978
A
123456789
123456789
B
C
D
A
B
C
D
E
F
Drawing Title Project Title
Checked
Building Number
Drawn
Revisions: Date
Date
Project No.
Drawing No.
Location
Sheet of
FINAL SUBMISSION
FULLY SPRINKLERED
V e t e r a n s
A f f a i r s
Approved: Associate Director
Approved: Chief of Staff
Approved: Service Chief
Approved: GEMS Coordinator
Approved: Infection Control Officer
Approved: Safety Manager
Approved: Chief of Mental Health Service
Approved: Chief of Police
Approved: Energy EngineerApproved: Patient Safety Nurse
Approved: Chief of Facility Management Svc.
Approved: Medical Center Director
TUSKEGEE, ALABAMA
2, 4 & 4A
2023.11.06
619A4-23-106
INSTALL DUAL PARALLEL PIPING
FOR DOMESTIC WATER AND FIRE
PROTECTION IN BUILDINGS 2, 4
AND 4A
D a t e
P l o t t e d
Rev. No.:
INCORPORATED
ENGINEERS
ARCHITECTS
CONSTRUCTORS
E
F
JLWB
FP101
1/2" = 1'-0"
FIRE RISER PLAN - BUILDING 2 ATTIC
FIRE RISER - BUILDING 2
ATTIC
PLAN
NORTH
1/2"=1'-0"
2' 0' 2' 4'
DRAWING KEYED NOTES
GENERAL PLUMBING NOTES
FOR LEGEND, SEE DWG. PL001.
LEGEND
1. FOR GENERAL PLUMBING NOTES, SEE DWG. PL001.
2. EXISTING PLUMBING IS SHOWN FOR REFERENCE ONLY. LOCATION
AND ROUTING OF EXISTING PIPING SHOULD BE VERIFIED PRIOR TO
CONSTRUCTION.
3. CONTRACTOR SHALL VERIFY THAT THE WATER PRESSURE
DOWNSTREAM FROM THE NEW BACKFLOW PREVENTERS SHALL BE
NO LESS THAN THE DESIRED PER THE FIRE FLOW TEST.
CONTRACTOR SHALL REQUEST LATEST AVAILABLE FLOW TESTS FOR
THE RESPECTIVE HYDRANTS NEAREST TO BUILDINGS 2, 4 AND 4A.
1/2" = 1'-0"
ELEV. "A" - BLDG. 2 ATTIC FIRE RISER ELEVATION (DEMO)
NOTE:
ELEVATION IS LOOKING WEST.
NOTE:
ELEVATION IS LOOKING WEST.
1/2" = 1'-0"
ELEV. "A" - BLDG. 2 ATTIC FIRE RISER ELEVATION (PROP.)
INSTALL NEW 2" SECTION OF DRAIN PIPE TO CONNECT TO
RELOCATED DRAIN FROM DPV-1 AND EX. PIPE (APPROX. 1'-0").
EXISTING 4" DRY PIPE EXTERNAL RESETTING VALVE (MODEL TYCO
DPV-1). RELOCATE DPV UPWARDS IN RISER DUE TO THE ADDITION
OF THE NEW DOUBLE CHECK BACKFLOW PREVENTER.
DEMO EXISTING 4" GATE VALVE AND SECTION OF 4"Ø PIPE.
LOCATION
A
A
DESCRIPTION SIZE NOTES
DOUBLE CHECK VALVE BACKFLOW PREVENTER ASSEMBLY:
1. BASIS OF DESIGN IS AMES BUT IS NOT INTENDED TO LIMIT SELECTION. PROVIDE INDICATED
EQUIPMENT OR EQUIPMENT OF EQUAL CAPACITY, QUALITY AND PERFORMANCE.
4"
SYM
DCV-2
NOTES:
AMES FIRE & WATERWORKS SERIES 2000SS, STAINLESS STEEL BODY
OS&Y SHUT-OFF VALVES, FLANGED CONNECTIONS, AWWA C510-92
DRAIN
INSTALL NEW DOUBLE CHECK BACKFLOW PREVENTER WITH OSY
GATE VALVE ASSEMBLY IN VERTICAL (FLOW UP) POSITION.
4A-332
EX. 2"Ø DRAIN
EX. 4"Ø FP PIPING
THRU CEILING
EX. 4"Ø DRY PIPE VALVE
(IN VERT.), TYCO DPV-1
EX. 4"Ø FP PIPING
ENTERING
4AC-3N
ELEV.
4A-322
4A-301
1'-1"
1'-7"
4A-332A
3A3244A
BUILDING KEY PLAN
EX. 3"Ø
EX. 4"Ø
EX. 4"Ø
ATTIC FL
EX. 4"Ø FP PIPING
THRU CEILING
EX. 4"Ø FP PIPING
ENTERING
DPV-1
4" EX.
EX. 2"Ø DRAIN
3RD FL EL. 498'-5"
EX. 4"Ø
ATTIC FL
EX. 4"Ø FP PIPING
THRU CEILING
EX. 4"Ø FP PIPING
ENTERING
DPV-1
4" EX.
EX. 2"Ø DRAIN
EX. 4"Ø
EX. 4"Ø
DCV
4A
4"
3RD FL EL. 498'-5"
o n e e i g h o t t h r e e i n c h e o t o n e a l f i n c h e o t o n e i n o t t h r e e q u a r t e r s i n o t o n e h a l f i n o t t h r e e e i g h t h s i n o t o n e q u a r t e r i n o t
VA FORM 08-6231, OCT 1978
A
123456789
123456789
B
C
D
A
B
C
D
E
F
Drawing Title Project Title
Checked
Building Number
Drawn
Revisions: Date
Date
Project No.
Drawing No.
Location
Sheet of
FINAL SUBMISSION
FULLY SPRINKLERED
V e t e r a n s
A f f a i r s
Approved: Associate Director
Approved: Chief of Staff
Approved: Service Chief
Approved: GEMS Coordinator
Approved: Infection Control Officer
Approved: Safety Manager
Approved: Chief of Mental Health Service
Approved: Chief of Police
Approved: Energy EngineerApproved: Patient Safety Nurse
Approved: Chief of Facility Management Svc.
Approved: Medical Center Director
TUSKEGEE, ALABAMA
2, 4 & 4A
2023.11.06
619A4-23-106
INSTALL DUAL PARALLEL PIPING
FOR DOMESTIC WATER AND FIRE
PROTECTION IN BUILDINGS 2, 4
AND 4A
D a t e
P l o t t e d
Rev. No.:
INCORPORATED
ENGINEERS
ARCHITECTS
CONSTRUCTORS
E
F
JLWB
FP102
1/2" = 1'-0"
FIRE RISER PLAN - BUILDING 4A 3RD FLOOR
FIRE RISER - BUILDING 4A
3RD FLOOR
PLAN
NORTH
1/2"=1'-0"
2' 0' 2' 4'
DRAWING KEYED NOTES
INSTALL NEW SECTION OF 4"Ø PIPE AND CONNECTING FLANGES IN
VERTICAL AS MAKEUP FOR BFP INSTALLATION.
INSTALL NEW DOUBLE CHECK BACKFLOW PREVENTER WITH OSY
GATE VALVE ASSEMBLY IN VERTICAL (FLOW UP) POSITION.
1/2" = 1'-0"
ELEV. "B" - ROOM 4A-332A FIRE RISER ELEVATION (DEMO)
NOTE:
ELEVATION IS LOOKING EAST.
1/2" = 1'-0"
ELEV. "B" - ROOM 4A-332A FIRE RISER ELEVATION (PROP.)
NOTE:
ELEVATION IS LOOKING EAST.
MODIFY EXISTING PIPE SUPPORT AS REQUIRED FOR THE NEW
DESIGN. VERIFY SUPPORT IS CAPABLE OF SUPPORTING THE
ADDITIONAL LOAD.
EXISTING 4" DRY PIPE EXTERNAL RESETTING VALVE (MODEL TYCO
DPV-1). LOCATION UNCHANGED IN RISER.
DEMO EXISTING 3" GATE VALVE AND ASSOCIATED FLANGES.
LOCATION
B
B
DESCRIPTION SIZE NOTES
1. BASIS OF DESIGN IS AMES BUT IS NOT INTENDED TO LIMIT SELECTION. PROVIDE INDICATED
EQUIPMENT OR EQUIPMENT OF EQUAL CAPACITY, QUALITY AND PERFORMANCE.
4"
SYM
DCV-4A
NOTES:
AMES FIRE & WATERWORKS SERIES 2000SS, STAINLESS STEEL BODY
OS&Y SHUT-OFF VALVES, FLANGED CONNECTIONS, AWWA C510-92
DRAIN
DOUBLE CHECK VALVE BACKFLOW PREVENTER ASSEMBLY:
GENERAL PLUMBING NOTES
FOR LEGEND, SEE DWG. PL001.
LEGEND
1. FOR GENERAL PLUMBING NOTES, SEE DWG. PL001.
2. EXISTING PLUMBING IS SHOWN FOR REFERENCE ONLY. LOCATION
AND ROUTING OF EXISTING PIPING SHOULD BE VERIFIED PRIOR TO
CONSTRUCTION.
3. CONTRACTOR SHALL VERIFY THAT THE WATER PRESSURE
DOWNSTREAM FROM THE NEW BACKFLOW PREVENTERS SHALL BE
NO LESS THAN THE DESIRED PER THE FIRE FLOW TEST.
CONTRACTOR SHALL REQUEST LATEST AVAILABLE FLOW TESTS FOR
THE RESPECTIVE HYDRANTS NEAREST TO BUILDINGS 2, 4 AND 4A.
4-325
EX. 2"Ø DRAIN
EX. 4"Ø DRY PIPE VALVE
(IN VERT.), TYCO DPV-1
EX. 4"Ø FP PIPING
THRU CEILING
EX. 4"Ø FP PIPING
ENTERING
4-326
4-3224-323
1'-1"
5'-1 1/2"
3'-6"
4C-3
BLDG. 4A
3A3244A
BUILDING KEY PLAN
EX. 3"Ø
EX. 4"Ø
ATTIC FL
EX. 4"Ø FP PIPING
THRU CEILING
EX. 4"Ø FP PIPING
ENTERING
DPV-1
4" EX.
EX. 2"Ø DRAIN
3RD FL EL. 498'-5"
3RD FL EL. 498'-5"
ATTIC FL
EX. 4"Ø FP PIPING
THRU CEILING
EX. 4"Ø FP PIPING
ENTERING
DPV-1
4" EX.
EX. 2"Ø DRAIN
DCV
4"
EX. 4"Ø
o n e e i g h o t t h r e e i n c h e o t o n e a l f i n c h e o t o n e i n o t t h r e e q u a r t e r s i n o t o n e h a l f i n o t t h r e e e i g h t h s i n o t o n e q u a r t e r i n o t
VA FORM 08-6231, OCT 1978
A
123456789
123456789
B
C
D
A
B
C
D
E
F
Drawing Title Project Title
Checked
Building Number
Drawn
Revisions: Date
Date
Project No.
Drawing No.
Location
Sheet of
FINAL SUBMISSION
FULLY SPRINKLERED
V e t e r a n s
A f f a i r s
Approved: Associate Director
Approved: Chief of Staff
Approved: Service Chief
Approved: GEMS Coordinator
Approved: Infection Control Officer
Approved: Safety Manager
Approved: Chief of Mental Health Service
Approved: Chief of Police
Approved: Energy EngineerApproved: Patient Safety Nurse
Approved: Chief of Facility Management Svc.
Approved: Medical Center Director
TUSKEGEE, ALABAMA
2, 4 & 4A
2023.11.06
619A4-23-106
INSTALL DUAL PARALLEL PIPING
FOR DOMESTIC WATER AND FIRE
PROTECTION IN BUILDINGS 2, 4
AND 4A
D a t e
P l o t t e d
Rev. No.:
INCORPORATED
ENGINEERS
ARCHITECTS
CONSTRUCTORS
E
F
JLWB
FP103
1/2" = 1'-0"
FIRE RISER PLAN - BUILDING 4 3RD FLOOR
DRAWING KEYED NOTES
FIRE RISER - BUILDING 4
3RD FLOOR
PLAN
NORTH
1/2"=1'-0"
2' 0' 2' 4'
1/2" = 1'-0"
ELEV. "C" - ROOM 4-325 FIRE RISER ELEVATION (EX.)
NOTE:
ELEVATION IS LOOKING NORTH.
1/2" = 1'-0"
ELEV. "C" - ROOM 4-325 FIRE RISER ELEVATION (PROP.)
NOTE:
ELEVATION IS LOOKING NORTH.
INSTALL NEW 2" DRAIN PIPE TO CONNECT TO RELOCATED DRAIN
FROM DPV-1 AND EX. PIPE (APPROX. 4'-0").
VERIFY EXISTING PIPE SUPPORT IS CAPABLE OF SUPPORTING THE
ADDITIONAL LOAD. MODIFY IF NEEDED.
EXISTING 4" DRY PIPE EXTERNAL RESETTING VALVE (MODEL TYCO
DPV-1). RELOCATE DPV UPWARDS IN RISER DUE TO THE ADDITION
OF THE NEW DOUBLE CHECK BACKFLOW PREVENTER.
ADJUST VERTICAL LENGTH OF EXISTING 4" PIPE TO HOLD LOCATION
OF HORIZONTAL RUN OF 4" PIPE.
DEMO EXISTING 3" GATE VALVE AND ASSOCIATED FLANGES.
DEMO SECTION OF 4"Ø PIPE TO ALLOW FOR INSTALLATION OF NEW
DOUBLE CHECK BACKFLOW PREVENTER ASSEMBLY.
LOCATION
CC
INSTALL NEW 1 1/4" DRAIN PIPE TO CONNECT TO RELOCATED DRAIN
FROM DPV-1 AND EX. PIPE (APPROX. 2'-0").
DESCRIPTION SIZE NOTES
1. BASIS OF DESIGN IS AMES BUT IS NOT INTENDED TO LIMIT SELECTION. PROVIDE INDICATED
EQUIPMENT OR EQUIPMENT OF EQUAL CAPACITY, QUALITY AND PERFORMANCE.
4"
SYM
DCV-4
NOTES:
AMES FIRE & WATERWORKS SERIES 2000SS, STAINLESS STEEL BODY
OS&Y SHUT-OFF VALVES, FLANGED CONNECTIONS, AWWA C510-92
DRAIN
INSTALL NEW DOUBLE CHECK BACKFLOW PREVENTER WITH OSY
GATE VALVE ASSEMBLY IN VERTICAL (FLOW UP) POSITION.
DOUBLE CHECK VALVE BACKFLOW PREVENTER ASSEMBLY:
GENERAL PLUMBING NOTES
FOR LEGEND, SEE DWG. PL001.
LEGEND
1. FOR GENERAL PLUMBING NOTES, SEE DWG. PL001.
2. EXISTING PLUMBING IS SHOWN FOR REFERENCE ONLY. LOCATION
AND ROUTING OF EXISTING PIPING SHOULD BE VERIFIED PRIOR TO
CONSTRUCTION.
3. CONTRACTOR SHALL VERIFY THAT THE WATER PRESSURE
DOWNSTREAM FROM THE NEW BACKFLOW PREVENTERS SHALL BE
NO LESS THAN THE DESIRED PER THE FIRE FLOW TEST.
CONTRACTOR SHALL REQUEST LATEST AVAILABLE FLOW TESTS FOR
THE RESPECTIVE HYDRANTS NEAREST TO BUILDINGS 2, 4 AND 4A.
2" MAIN DRAIN. MODIFY PIPING
TO RECONNECT TO EXISTING
DRAIN PIPING.
EX. 4" DRY PIPE EXTERNAL RESETTING VALVE.
RELOCATE AS SHOWN ON THE PLANS TO
ALLOW FOR INSTALLATION OF NEW DOUBLE
CHECK BACKFLOW PREVENTER.
INSTALL NEW DOUBLE CHECK
VALVE BACKFLOW PREVENTER
WITH OSY GATE VALVE ASSEMBLY
IN VERTICAL (FLOW UP) POSITION.
LOCATE ASSEMBLY A MINIMUM OF
12" ABOVE THE FLOOR.
M I N
4" FIRE WATER TO BUILDING
SYSTEM
TOC
NOTE: BASIS OF DESIGN IS AMES SERIES 2000SS DOUBLE CHECK
VALVE ASSEMBLY BUT IS NOT INTENDED TO LIMIT
EQUIPMENT SELECTION. PROVIDE INDICATED EQUIPMENT
OF EQUIPMENT OF EQUAL PERFORMANCE AND QUALITY.
SOME ADJUSTMENT OF DIMENSIONS AND LAYOUT MAY BE
REQUIRED WHEN SPECIFYING DIFFERENT MODELS.
ENSURE PIPING AND EQUIPMENT
ARE ADEQUATELY SUPPORTED
" MAIN DRAIN. MODIFY PIPING
TO RECONNECT TO EXISTING
DRAIN PIPING.
o n e e i g h o t t h r e e i n c h e o t o n e a l f i n c h e o t o n e i n o t t h r e e q u a r t e r s i n o t o n e h a l f i n o t t h r e e e i g h t h s i n o t o n e q u a r t e r i n o t
VA FORM 08-6231, OCT 1978
A
123456789
123456789
B
C
D
A
B
C
D
E
F
Drawing Title Project Title
Checked
Building Number
Drawn
Revisions: Date
Date
Project No.
Drawing No.
Location
Sheet of
FINAL SUBMISSION
FULLY SPRINKLERED
V e t e r a n s
A f f a i r s
Approved: Associate Director
Approved: Chief of Staff
Approved: Service Chief
Approved: GEMS Coordinator
Approved: Infection Control Officer
Approved: Safety Manager
Approved: Chief of Mental Health Service
Approved: Chief of Police
Approved: Energy EngineerApproved: Patient Safety Nurse
Approved: Chief of Facility Management Svc.
Approved: Medical Center Director
TUSKEGEE, ALABAMA
2, 4 & 4A
2023.11.06
619A4-23-106
INSTALL DUAL PARALLEL PIPING
FOR DOMESTIC WATER AND FIRE
PROTECTION IN BUILDINGS 2, 4
AND 4A
D a t e
P l o t t e d
Rev. No.:
INCORPORATED
ENGINEERS
ARCHITECTS
CONSTRUCTORS
E
F
JLWB
FP501
FIRE RISER DETAILS
NOT TO SCALE
9C
TYP. DBL. CHECK BACKFLOW PREVENTER PIPING DETAIL
NOT TO SCALE
6C
TYP. DBL. CHECK BACKFLOW PREVENTER INSTALLATION DETAIL
File details come from the government source that posted it. Updated .