About this file

This document is a set of construction drawings for a federal contract to install dual parallel piping for domestic water and fire protection systems in Buildings 2, 4, and 4A at the Central Alabama Veteran's Health Care System East Campus in Tuskegee, Alabama. The contract number is 36C24723C0066, and the project number is 619A4-23-106. The drawings constitute the final submission dated November 6, 2023, and include comprehensive plumbing and fire protection designs with multiple sheets covering demolition plans, new work installations, details, schedules, and hazardous materials abatement plans.

The project scope includes installing new 4-inch reduced pressure principle backflow preventers (BFP-2, BFP-4, and BFP-4A) in service rooms across the three buildings, with new 4-inch cold water piping and associated drainage systems. Double check valve backflow preventers (DCV-2, DCV-4, and DCV-4A) are specified for fire protection systems in the building attics and upper floors. The drawings detail pipe support installations, fire-rated wall penetrations using 3M firestop systems, and modifications to existing dry pipe external resetting valves. Asbestos and lead-based paint abatement work is required in identified areas within the basements and attics, with sampling locations marked on separate hazardous materials abatement plans. The construction must comply with infection control protocols during renovation, operate after hours and weekends, and include seismic bracing for all piping 2.5 inches in diameter and larger, as well as proper vibration isolation for new equipment.

View the file

Other files

File Type Posted
36C24726R0070 0003.docx DOCX document
Attachment 10 - Revised RFI Answers.docx DOCX document
Attachment 11 - Hazmat Survey Report.pdf PDF
Attachment 10 - RFI Answers.docx DOCX document
36C24726R0070 0002.docx DOCX document
36C24726R0070 0001.docx DOCX document
Attachment 9 - Site Visit Attend.pdf PDF
Attachment 5 - Wage Determinations.txt TXT text file
Attachment 6 - INVOICING.pdf PDF
Attachment 4 - Itemized Cost Breakdown.xlsx XLSX spreadsheet
Attachment 1 - Experience Modification Rate Form.pdf PDF
Attachment 2 - SBA Vet SB Cert Program Class Dev.pdf PDF
Attachment 3 - PPQ.pdf PDF
Attachment 7 - SPECS - 619A4-23-106.pdf PDF
36C24726R0070_1.docx DOCX document
Show all 15

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

NOT TO SCALE

CAMPUS MAP

N

PROJECT SITE

PROJECT SITE

(BLDG. 2, 4 & 4A)

NOT TO SCALE

N

VICINITY MAP

PAGE

SHEET

TITLE

00-GENERAL

1 GI001 TITLE SHEET X

2 GI002 PROJECT INFORMATION X

3 GI003

SHEET INDEX

STANDARD ABBREVIATIONS

DD

SUBMISSION

CD1

SUBMISSION

CD2

SUBMISSION

X

X

PL001 PLUMBING LEGENDS AND ABBREVIATIONS

X

PD101 PLUMBING DEMOLITION PLAN BLDG. 4A

X

PL101 PLUMBING NEW WORK PLAN BLDG. 4A

X

X

FP101 FIRE RISER - BUILDING 2, ATTIC X

FIRE RISER - BUILDING 4A, 3RD FLOOR X

X

12 PL102 PLUMBING NEW WORK PLAN BLDG. 2

FP102

FIRE RISER - BUILDING 4, 3RD FLOORFP103

PL501 PLUMBING DETAILS AND SCHEDULE

GI004 INFECTION CONTROL, DEMOLITION & PHASING INFO

X

X

X

X

X

X

X

X

X

X

X

X

HA001

HA002

HA003

HAZARDOUS MATERIALS ABATEMENT PLAN

HAZARDOUS MATERIALS ABATEMENT PLAN

HAZARDOUS MATERIALS ABATEMENT PLAN

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

FIRE RISER DETAILSFP50117 X

FINAL

SUBMISSION

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

PD102 PLUMBING DEMOLITION PLAN BLDG. 2 X

TITLE SHEET

GI001

SD JL

CONTRACT NO.: 36C24723C0066

PROJECT NO.: 619A4-23-106

o n e e i g h t h i n c o e f o t t h r e e i n c h e s o t o n e a d a l f i n c h e o t o n e i n o t t h r e e q u a r t e r s i n o t o n e h a l f i n o t t h r e e e i g h t h s i n o t o n e q u a r t e r i n o t

VA FORM 08-6231, OCT 1978

A

123456789

123456789

B

C

D

A

B

C

D

E

F

Drawing Title Project Title

Checked

Building Number

Drawn

Revisions: Date

Date

Project No.

Drawing No.

Location

Sheet of

FINAL SUBMISSION

FULLY SPRINKLERED

V e t e r a n s

A f f a i r s

Approved: Associate Director

Approved: Chief of Staff

Approved: Service Chief

Approved: GEMS Coordinator

Approved: Infection Control Officer

Approved: Safety Manager

Approved: Chief of Mental Health Service

Approved: Chief of Police

Approved: Energy EngineerApproved: Patient Safety Nurse

Approved: Chief of Facility Management Svc.

Approved: Medical Center Director

TUSKEGEE, ALABAMA

2, 4 & 4A

2023.11.06

619A4-23-106

INSTALL DUAL PARALLEL PIPING

FOR DOMESTIC WATER AND FIRE

PROTECTION IN BUILDINGS 2, 4

AND 4A

D a

P l o t t e d

Rev. No.:

INCORPORATED

ENGINEERS

ARCHITECTS

CONSTRUCTORS

E

F

CENTRAL ALABAMA VETERAN'S HEALTH CARE SYSTEM, EAST CAMPUS

INSTALL DUAL PARALLEL PIPING FOR DOMESTIC

WATER AND FIRE PROTECTION IN BUILDINGS

2, 4 AND 4A

2023.10.26 e e i g h o t t h r e e i n c h e o t o n e a l f i n c h e o t o n e i n o t t h r e e q u a r t e r s i n o t o n e h a l f i n o t t h r e e e i g h t h s i n o t o n e q u a r t e r i n o t

VA FORM 08-6231, OCT 1978

A

123456789

123456789

B

C

D

A

B

C

D

E

F

Drawing Title Project Title

Checked

Building Number

Drawn

Revisions: Date

Date

Project No.

Drawing No.

Location

Sheet of

FINAL SUBMISSION

FULLY SPRINKLERED

V e t e r a n s

A f f a i r s

Approved: Associate Director

Approved: Chief of Staff

Approved: Service Chief

Approved: GEMS Coordinator

Approved: Infection Control Officer

Approved: Safety Manager

Approved: Chief of Mental Health Service

Approved: Chief of Police

Approved: Energy EngineerApproved: Patient Safety Nurse

Approved: Chief of Facility Management Svc.

Approved: Medical Center Director

TUSKEGEE, ALABAMA

2, 4 & 4A

2023.11.06

619A4-23-106

INSTALL DUAL PARALLEL PIPING

FOR DOMESTIC WATER AND FIRE

PROTECTION IN BUILDINGS 2, 4

AND 4A

D a t e

P l o t t e d

Rev. No.:

INCORPORATED

ENGINEERS

ARCHITECTS

CONSTRUCTORS

E

F

HAZARDOUS MATERIALS

HA001

SD JL

ABATEMENT PLAN

1/4" = 1'-0"

BULK SAMPLE LOCATION DRAWING - BLDG. 4A SUB-BASEMENT, WATER

1/4" = 1'-0"

BULK SAMPLE LOCATION DRAWING - BLDG. 2 BASEMENT, WATER

PLAN

NORTH

GENERAL

ABATEMENT NOTES

1. ALL ASBESTOS ABEATEMENT WORK SHALL COMPLY

WITH ALL FEDERAL, STATE AND LOCAL REGULATIONS.

2. REFER TO SPECIFICATION 028233 FOR REQUIREMENTS

PERTAINING TO THE REMOVAL AND DISPOSAL OF

ASBESTOS CONTAINING MATERIALS.

3. REFER TO "ASBESTOS CONTAINING MATERIALS

SURVEY REPORT" BUILDING 2, 4 AND 4A, TUSKEGEE

VAMC. PREPARED BY ENVIRONMENTAL HEALTH

CONSULTANTS, LLC, DATED AUGUST 21, 2023.

1. AT THE POINT OF THIS DESIGN ITERATION; THE SUPPLY

ROOM AND ABANDONED MEN'S RESTROOM IN THE

BASEMENT OF BUILDING 2 WERE NOT SURVEYED. AT

THE TIME OF CONSTRUCTION ONE OF THESE ROOMS

WILL BE INCLUDED IN THIS CONTRACT. THE

CONTRACTOR SHALL BE RESPONSIBLE TO CONDUCT

AN ASBESTOS AND LEAD SURVEY OF ANY/ALL AREAS

NOT COVERED BY THE REPORT PROVIDED WITH THIS

CONSTRUCTION DOCUMENTS THAT ARE IMPACTED BY

CONSTRUCTION. (“ASBESTOS CONTAINING MATERIALS

SURVEY REPORT ”BUILDING 2, 4 AND 4A. TUSKEGEE

VAMC. PREPARED BY ENVIRONMENTAL HEALTH

CONSULTANTS, LLC DATE AUGUST 21). WHERE

ASBESTOS OR LEAD CONTAINING MATERIALS ARE

FOUND; ABATEMENT SHALL CONDUCTED ACCORDING

TO THE SPECIFICATIONS 02 82 11 AND 02 83 33 13.

2. THE QUANTITIES AND AREAS SHOWN IN THE REPORT

ARE FOR INFORMATIONAL PURPOSES ONLY AND ARE

BASED ON THE BEST INFORMATION AVAILABLE AT THE

TIME OF THE SPECIFICATION PREPARATION. THE

CONTRACTOR SHALL SATISFY THEMSELVES OF THE

ACTUAL QUANTITIES TO BE ABATED. NOTHING MAY BE

INTERPRETED AS LIMITING THE EXTENT OF WORK

OTHERWISE REQUIRED BY THIS CONTRACT AND

RELATED DOCUMENTS.

SURVEY NOTES

SUPPLY ROOM

MEN'S ROOM

(ABANDONED)

FP-1 FIREPROOFING

FP-2 FIREPROOFING

FP-3 FIREPROOFING

FP-4 FIREPROOFING

FP-5 FIREPROOFING

EC-6 ENDCAP SEALANT

EC-7 ENDCAP SEALANT

PW-34 PIPE WRAP

PW-35 PIPE WRAP

SB-8 SADDLE BLOCK

SB-9 SADDLEBLOCK

SAMPLING

DESCRIPTION

BP-28 BASE PLASTER

BP-29 BASE PLASTER

FS-30 FIRESTOPPING - PATCH WHITE

FS-31 FIRESTOPPING - PATCH WHITE

FS-32 FIRESTOPPING - RED

FS-33 FIRESTOPPING - GRAY

SP-26 SKIM PLASTER

SP-27 SKIM PLASTER

SAMPLING

DESCRIPTION

DRAWING KEY

SAMPLE NUMBERS IN BLUE OR INDICATE NON-ACM

SAMPLE NUMBERS IN RED OR INDICATE ACM

N

A

N

N

N N N

NN

NN

N

N

N N

N N

N N

N

N e e i g h o t t h r e e i n c h e o t o n e a l f i n c h e o t o n e i n o t t h r e e q u a r t e r s i n o t o n e h a l f i n o t t h r e e e i g h t h s i n o t o n e q u a r t e r i n o t

VA FORM 08-6231, OCT 1978

A

123456789

123456789

B

C

D

A

B

C

D

E

F

Drawing Title Project Title

Checked

Building Number

Drawn

Revisions: Date

Date

Project No.

Drawing No.

Location

Sheet of

FINAL SUBMISSION

FULLY SPRINKLERED

V e t e r a n s

A f f a i r s

Approved: Associate Director

Approved: Chief of Staff

Approved: Service Chief

Approved: GEMS Coordinator

Approved: Infection Control Officer

Approved: Safety Manager

Approved: Chief of Mental Health Service

Approved: Chief of Police

Approved: Energy EngineerApproved: Patient Safety Nurse

Approved: Chief of Facility Management Svc.

Approved: Medical Center Director

TUSKEGEE, ALABAMA

2, 4 & 4A

2023.11.06

619A4-23-106

INSTALL DUAL PARALLEL PIPING

FOR DOMESTIC WATER AND FIRE

PROTECTION IN BUILDINGS 2, 4

AND 4A

D a t e

P l o t t e d

Rev. No.:

INCORPORATED

ENGINEERS

ARCHITECTS

CONSTRUCTORS

E

F

HAZARDOUS MATERIALS

HA002

SD JL

ABATEMENT PLAN

1/4" = 1'-0"

BULK SAMPLE LOCATION DRAWING - BLDG. 2 ATTIC

1/4" = 1'-0"

BULK SAMPLE LOCATION DRAWING - BLDG. 4A 3RD FLOOR

PLAN

NORTH

GENERAL

ABATEMENT NOTES

1. ALL ASBESTOS ABEATEMENT WORK SHALL COMPLY

WITH ALL FEDERAL, STATE AND LOCAL REGULATIONS.

2. REFER TO SPECIFICATION 028233 FOR REQUIREMENTS

PERTAINING TO THE REMOVAL AND DISPOSAL OF

ASBESTOS CONTAINING MATERIALS.

3. REFER TO "ASBESTOS CONTAINING MATERIALS

SURVEY REPORT" BUILDING 2, 4 AND 4A, TUSKEGEE

VAMC. PREPARED BY ENVIRONMENTAL HEALTH

CONSULTANTS, LLC, DATED AUGUST 21, 2023.

SAMPLING

DESCRIPTION

BP-13 BASE PLASTER

BP-14 BASE PLASTER

BP-15 BASE PLASTER

SP-10 SKIM PLASTER

SP-11 SKIM PLASTER

SP-12 SKIM PLASTER

SAMPLING

DESCRIPTION

FS-22 FIRESTOPPING - GRAY

FS-23 FIRESTOPPING - GRAY

FS-24 FIRESTOPPING - BLACK TAR

FS-25 FIRESTOPPING - BLACK TAR

DRAWING KEY

SAMPLE NUMBERS IN BLUE OR INDICATE NON-ACM

SAMPLE NUMBERS IN RED OR INDICATE ACM

N

A

AA

N N

N N N

N N N e e i g h o t t h r e e i n c h e o t o n e a l f i n c h e o t o n e i n o t t h r e e q u a r t e r s i n o t o n e h a l f i n o t t h r e e e i g h t h s i n o t o n e q u a r t e r i n o t

VA FORM 08-6231, OCT 1978

A

123456789

123456789

B

C

D

A

B

C

D

E

F

Drawing Title Project Title

Checked

Building Number

Drawn

Revisions: Date

Date

Project No.

Drawing No.

Location

Sheet of

FINAL SUBMISSION

FULLY SPRINKLERED

V e t e r a n s

A f f a i r s

Approved: Associate Director

Approved: Chief of Staff

Approved: Service Chief

Approved: GEMS Coordinator

Approved: Infection Control Officer

Approved: Safety Manager

Approved: Chief of Mental Health Service

Approved: Chief of Police

Approved: Energy EngineerApproved: Patient Safety Nurse

Approved: Chief of Facility Management Svc.

Approved: Medical Center Director

TUSKEGEE, ALABAMA

2, 4 & 4A

2023.11.06

619A4-23-106

INSTALL DUAL PARALLEL PIPING

FOR DOMESTIC WATER AND FIRE

PROTECTION IN BUILDINGS 2, 4

AND 4A

D a t e

P l o t t e d

Rev. No.:

INCORPORATED

ENGINEERS

ARCHITECTS

CONSTRUCTORS

E

F

HAZARDOUS MATERIALS

HA003

SD JL

ABATEMENT PLAN

1/4" = 1'-0"

BULK SAMPLE LOCATION DRAWING - BLDG. 4 3RD FLOOR

PLAN

NORTH

GENERAL

ABATEMENT NOTES

1. ALL ASBESTOS ABEATEMENT WORK SHALL COMPLY

WITH ALL FEDERAL, STATE AND LOCAL REGULATIONS.

2. REFER TO SPECIFICATION 028233 FOR REQUIREMENTS

PERTAINING TO THE REMOVAL AND DISPOSAL OF

ASBESTOS CONTAINING MATERIALS.

3. REFER TO "ASBESTOS CONTAINING MATERIALS

SURVEY REPORT" BUILDING 2, 4 AND 4A, TUSKEGEE

VAMC. PREPARED BY ENVIRONMENTAL HEALTH

CONSULTANTS, LLC, DATED AUGUST 21, 2023.

FT-16 FLOOR TILE

FT-17 FLOOR TILE

FM-18 FLOOR MASTIC

FM-19 FLOOR MASTIC

FS-20 FIRESTOPPING

FS-21 FIRESTOPPING

SAMPLING

DESCRIPTION

DRAWING KEY

SAMPLE NUMBERS IN BLUE OR INDICATE NON-ACM

SAMPLE NUMBERS IN RED OR INDICATE ACM

N

A

N N

N N

N N e e i g h o t t h r e e i n c h e o t o n e a l f i n c h e o t o n e i n o t t h r e e q u a r t e r s i n o t o n e h a l f i n o t t h r e e e i g h t h s i n o t o n e q u a r t e r i n o t

VA FORM 08-6231, OCT 1978

A

123456789

123456789

B

C

D

A

B

C

D

E

F

Drawing Title Project Title

Checked

Building Number

Drawn

Revisions: Date

Date

Project No.

Drawing No.

Location

Sheet of

FINAL SUBMISSION

FULLY SPRINKLERED

V e t e r a n s

A f f a i r s

Approved: Associate Director

Approved: Chief of Staff

Approved: Service Chief

Approved: GEMS Coordinator

Approved: Infection Control Officer

Approved: Safety Manager

Approved: Chief of Mental Health Service

Approved: Chief of Police

Approved: Energy EngineerApproved: Patient Safety Nurse

Approved: Chief of Facility Management Svc.

Approved: Medical Center Director

TUSKEGEE, ALABAMA

2, 4 & 4A

2023.11.06

619A4-23-106

INSTALL DUAL PARALLEL PIPING

FOR DOMESTIC WATER AND FIRE

PROTECTION IN BUILDINGS 2, 4

AND 4A

D a t e

P l o t t e d

Rev. No.:

INCORPORATED

ENGINEERS

ARCHITECTS

CONSTRUCTORS

E

F

JLWB

PL001

PLUMBING LEGENDS AND

ABBREVIATIONS

FE

CO

FD

SANITARY SEWER CLEANOUT (FLOOR)

FCO

EXISTING COLD WATER

EXISTING HOT WATER

EXISTING SS PIPING

NEW COLD WATER

SS

NEW SANITARY SEWER

NEW SS VENT PIPING

NEW HOT WATER

NEW HOT WATER RECIRCULATION

EXISTING HOT WATER RECIRCULATION

EXISTING SS VENT PIPING

(E) V

(E) HWR

(E) SAN

(E) DHW

(E) DCW

HWR

V

SAN

DHW

DCW

SANITARY SEWER CLEANOUT (WALL)

WCO

AV

WATER HAMMER ARRESTOR

ISOLATION VALVE

DEMO KEY NOTE (SEE SCHEDULE)

FLOOR DRAIN (INSTALL WITH TRAP SEAL)

HOSE BIB

CLEAN OUT

FLOW ELEMENT

PRESSURE GAGE

THERMOMETER

STRAINER

FLOAT & THERMOSTATIC TRAP SET INCLUDING PIPING

ACCESSORIES

INVERTED BUCKET TRAP SET INCLUDING PIPING ACCESSORIES

POINT OF CONNECTION BETWEEN NEW AND EXISTING WORK

POINT OF DISCONNECTION

PIPE DOWN

PIPE UP

UNION

RISE OR DROP IN PIPE

CAPPED OUTLET

SIDE CONNECTION

BOTTOM CONNECTION, 45° OR 90°

TOP CONNECTION, 45° OR 90°

ECCENTRIC REDUCER

REDUCER OR INCREASER

ANCHOR

DIRECTION OF FLOW

DIRECTION OF PIPE PITCH (DOWN)

GATE VALVE

GLOBE VALVE

GATE VALVE WITH 3/4 " HOSE ADAPTER

CHECK VALVE

ANGLE GLOBE VALVE

BUTTERFLY VALVE

BALL VALVE

SOLENOID VALVE (2 POSITION)

PRESSURE REGULATING VALVE

AUTOMATIC FLOW CONTROL VALVE

PRESSURE RELIEF VALVE

MANUAL AIR VENT

TEST PLUG (PRESSURE/TEMPERATURE)

AUTOMATIC AIR VENT

A/E ARCHITECT / ENGINEER

AD AREA DRAIN

AFF ABOVE FINISH FLOOR

AFG ABOVE FINISH GRADE

AG AIR GAP

AP ACCESS PANEL

ASHRAE AMERICAN SOCIETY HEATING,

REFRIGERATION, AIR CONDITIONING

ENGINEERS

ASME AMERICAN SOCIETY MECHANICAL

ENGINEERS

ASPE AMERICAN SOCIETY PLUMBING

ENGINEERS

BFP REDUCED PRESSURE BACKFLOW

PREVENTER

BHP BREAK HORSEPOWER

BSP BLACK STEEL PIPE

BTU BRITISH THERMAL UNIT

BTUH BRITISH THERMAL UNIT PER HOUR

C CELSIUS

CI CAST IRON

CO CLEANOUT

CRS CORROSION RESISTANT STEEL

CS CLINICAL SINK

CV CONTROL VALVE

CW COLD WATER (DOMESTIC)

DI DEIONIZED WATER

DN DOWN

DWG DRAWING

DWH DOMESTIC WATER HEATER

DWB DIALYSIS WALL BOX

DWV DRAIN WASTE VENT

EL ELEVATION

EMCS ENERGY MONOSERRAT AND CENTRAL

EPACT ENERGY POLICY ACT

ESC ESCUTCHEON

ESH EMERGENCY SHOWER

ET EXPANSION TANK

EWC ELECTRIC WATER COOLER

EWS EYE WASH STATION

EX OR E EXISTING

F FAHRENHEIT

FCO FLOOR CLEANOUT

FCU FAN COIL UNIT

FD FLOOR DRAIN

FDC FIRE DEPARTMENT

(HOSE) CONNECTION

FM FLOW METER

FS FLOOR SINK

FS FLOW SWITCH

FU FIXTURE UNITS

GAL GALLON

GCO GRADE CLEANOUT

GPD GALLONS PER DAY

GPH GALLONS PER HOUR

GPM GALLONS PER MINUTE

GVTR GAS VENT THROUGH ROOF

H&CW HOT AND COLD WATER

HB HOSE BIBHD HUB DRAIN

HEX HEAT EXCHANGER

HP HORSEPOWER

HS HAND SINK

HST HOT WATER STORAGE TANK

(DOMESTIC)

HW HOT WATER (DOMESTIC)

HWR HOT WATER RETURN (DOMESTIC)

HWS HOT WATER SUPPLY (DOMESTIC)

HWCP HOT WATER CIRCULATING PUMP

HWP HOT WATER PUMP

HYD HYDRANT

INV INVERT

IPC INTERNATIONAL PLUMBING CODE

KW KILOWATT

KWHR KILOWATT-HOUR

LAV LAVATORY

LBS/HR POUNDS PER HOUR

LW LOW WATER

M METER

MA MEDICAL AIR

MAV MANUAL AIR VENT

MBH 1000 BTUH

MED MEDICAL

MER MECHANICAL EQUIPMENT

ROOM

MH MANHOLE

MSB MOP SERVICE BASIN

NC NORMALLY CLOSED

NIC NOT IN CONTRACT

NO NORMALLY OPEN

NOM. NOMINAL

NPW NON POTABLE WATER

NTS NOT TO SCALE

OD OUTSIDE DIAMETER

OFD OVERFLOW DRAIN

OVFL OVERFLOW

PA PASCAL

PD PRESSURE DROP OR DIFFERENCE

PDI PLUMBING AND DRAINAGE INSTITUTE

PG PRESSURE GAGE

PPM PARTS PER MILLION

PRS PRESSURE REDUCING STATION

PRV PRESSURE REDUCING VALVE

PSI POUNDS PER SQUARE INCH

PSIA POUNDS PER SQUARE INCH ATMOSPHERE

PSIG POUNDS PER SQUARE INCH GAUGE

PTRV PRESSURE TEMPERATURE RELIEF VALVE

PW POTABLE WATER

RD ROOF DRAIN

RDC ROOF DRAIN CONDUCTOR

RDL ROOF DRAIN LEADER

RL ROOF LEADER

RO REVERSE OSMOSIS WATER

RWL RAIN WATER LEADER

SAN SANITARY SEWER

SCFM STANDARD CUBIC FOOT/MINUTE

SCW SOFTENED COLD WATER

SD STORM DRAIN

SDMH STORM DRAIN MANHOLE

SMACNA SHEET METAL AND AIR CONDITIONING

CONTRACTORS NATIONAL ASSOCIATION

SQFT SQUARE FEET

SSTL STAINLESS STEEL

SS SANITARY SEWER

ST STORM WATER

TCV TEMPERATURE CONTROL VALVE

TD TEMPERATURE DIFFERENCE

TD TRENCH DRAIN

TDH TOTAL DYNAMIC HEAD

TEMP TEMPERATURE

TVAC THERMOSTATIC MIXING VALVE

TP TRAP PRIMER

TSTAT THERMOSTAT

TYP TYPICAL

UNO UNLESS NOTED OTHERWISE

UPC UNIFORM PLUMBING CODE

V VENT

VAC MEDICAL VACUUM

VB VACUUM BREAKER

VS VENT STACK

VTR VENT THROUGH ROOF

W WASTE

WC WATER CLOSET

WCO WALL CLEANOUT

WG WATER GAGE

WH WALL HYDRANT

WH WATER HEATER

WHA WATER HAMMER ARRESTER

WL WATER LINE

WM WATER METER

WPD WATER PRESSURE DROP

WS WASTE STACK

YCO YARD CLEANOUT

YH YARD HYDRANT

PLUMBING ABBREVIATIONSPLUMBING LEGEND

NEW WORK NOTE (SEE SCHEDULE)

GENERAL FIRE PROTECTION NOTES

1. SLEEVE AND FIRE STOP ALL NEW PENETRATIONS THROUGH RATED WALLS, FLOORS AND CEILINGS IN

ACCORDANCE WITH APPLICABLE CODE REQUIREMENTS. SEE ARCHITECTURAL DRAWINGS FOR EXACT

LOCATIONS OF FIRE RATED ASSEMBLIES.

2. ALL EXISTING FIRE PENETRATIONS DISTURBED DURING CONSTRUCTION SHALL BE BROUGHT UP TO

APPLICABLE CODE REQUIREMENTS.

3. ALL PENETRATIONS CREATED BY REMOVAL OF DEMOLISHED ITEMS UNDER THIS CONTRACT THROUGH

RATED FLOOR/CEILING ASSEMBLIES AND THROUGH FIRE RATED WALL AND SMOKE BARRIER

ASSEMBLIES MUST BE SEALED AS PART OF THIS CONTRACT. SEAL ON BOTH SIDES WITH VA APPROVED

FIRE RATED CAULK. ALL RATED SEPARATIONS MUST MEET CURRENT CODE REQUIREMENTS.

LEGIONELLA MITIGATION NOTE

1. REFER TO VHA DIRECTIVE 1061, FEBRUARY 13, 2021 (AMENDED SEPT. 26, 2022) FOR INFORMATION ON THE

POLICY FOR THE PREVENTION AND CONTROL OF HEALTHCARE-ASSOCIATED LEGIONELLA DISEASE IN

VHA-OWNED BUILDINGS.

NOTES FOR SEISMIC BRACING (ALL P-SHEETS)

3. PROVIDE BRACING FOR RIGID SUPPORT ON ALL SIDES OF SUSPENDED EQUIPMENT, AND RESTRAINTS FOR

5. TRANSVERSE AND VERTICAL BRACING SHALL OCCUR AT 40 FOOT INTERVALS (MAX). LONGITUDINAL BRACING

FOR DUCTWORK OR PIPING.

OR OTHER SUPPORT.

OF SEISMICALLY BRACED MECHANICAL SYSTEMS.

RESILIENTLY SUPPORTED EQUIPMENT.

VERTICAL RESTRAINT ON ALL SIDES OF THE BASE TO RESTRICT DISPLACEMENT OF THE EQUIPMENT.

4. BRACE ALL PIPES 2 1/2" DIAMETER AND LARGER. RESTRAIN ALL PIPING IN MECHANICAL ROOMS THAT IS

2. FLOOR MOUNTED EQUIPMENT, WITH VIBRATION ISOLATORS, SHALL BE PROVIDED WITH LATERAL AND

1. FLOOR OR PAD MOUNTED EQUIPMENT, WITHOUT VIBRATION ISOLATORS, SHALL BE BOLTED TO THE FLOOR

D. SEE THE SPECIFICATIONS FOR MANUFACTURER'S RESPONSIBILITIES IN SUBMITTING THE PROPER DESIGN

7. DO NOT USE BRANCH LINES TO RESTRAIN MAIN LINES.

6. AT PIPE RISERS, WHEREVER POSSIBLE, SUPPORT THE WEIGHT OF THE RISER AT A POINT OR POINTS

RESPOND DIFFERENTLY DURING AN EARTHQUAKE; IE: A WALL AND A ROOF.

ABOVE THE CENTER OF GRAVITY OF THE RISER.

8. DO NOT FASTEN ONE RIGID PIPING SYSTEM TO TWO DISSIMILAR PARTS OF THE BUILDING THAT MAY

SHALL OCCUR AT 80 FOOT INTERVALS (MAX.).

1 1/4" DIAMETER AND LARGER.

PIPING

EQUIPMENT

WW-H-171 OR BE BOLTED/WELDED AS APPROVED BY THE ENGINEER.

C. WALLS, INCLUDING DRYWALL PARTITIONS, MAY REPLACE REQUIRED TRANSVERSE OR VERTICAL BRACING

B. ATTACHMENT TO STRUCTURAL MEMBERS SHALL USE DEVICES PROVIDED BY FEDERAL SPECIFICATION

A. BRACING IS NOT REQUIRED WHEN THE TOP OF DUCT OR PIPE IS SUSPENDED 12" OR LESS FROM THE

SUPPORTING STRUCTURAL MEMBER.

GENERAL

CONSTRUCTION WORKING HOURS NOTE

1. ALL CONSTRUCTION WORK TO BE PERFORMED AFTER HOURS AND ON WEEKENDS.

MV

O

MA

MV

MA

O

EXISTING MEDICAL VACUUM(E) VAC

EXISTING MEDICAL AIR(E) MA

EXISTING MEDICAL OXYGEN(E) O2

NEW MEDICAL VACUUMVAC

NEW MEDICAL AIRMA

NEW MEDICAL OXYGENO2

ST EXISTING STORM DRAIN(E) ST

O2 OXYGEN

N NEW

AREA NOT IN CONTRACT

DCW DOMESTIC COLD WATER

DHW DOMESTIC HOT WATER

WSFU WATER SUPPLY FIXTURE UNITS

DFU DRAINAGE FIXTURE UNITS

BALANCING VALVE

DEMO PIPE

DEMO FIXTURE

GENERAL PLUMBING NOTES

1 THE PLUMBING SYSTEM SHALL CONFORM TO THE INTERNATIONAL PLUMBING CODE (LATEST EDITION).

2 UNLESS OTHERWISE SPECIFIED OR DIRECTED, PROVIDE IN ACCORDANCE WITH ASHRAE STANDARD 90.1, AND THE ENERGY CONSERVATION REQUIREMENTS OF THE CONTRACT. SIZE AND PLACE EQUIPMENT SO

THAT IT IS EASILY ACCESSIBLE AND REMOVABLE FOR REPAIR OR REPLACEMENT.

4 ALL SANITARY DRAINAGE, WASTE AND VENT PIPING WILL BE LOCATED EITHER BELOW FLOOR, IN

SUSPENDED CEILINGS, IN PIPE CHASES, OR WITHIN WALLS AS INDICATED ON DRAWINGS. COMPLETE

ACCESSIBILITY WILL BE AVAILABLE TO ALL CLEANOUTS IN THE SANITARY DRAINAGE PIPING AND

INTERVALS WILL BE SPACED ACCORDING TO THE INTERNATIONAL PLUMBING CODE.

5 PROVIDE VALVES ON ALL BRANCH LINES SERVING TWO OR MORE FIXTURES OR EQUIPMENT ITEMS.

6 DRAINAGE PIPING LARGER THAN 2" DIAMETER SHALL BE SLOPED NO LESS THAN 1/8" / FT.

7 DRAINAGE PIPING 2" AND SMALLER DIAMETER SHALL BE SLOPED NO LESS THAN 1/4" / FT.

8 ROUGH IN WASTE AND SUPPLIES TO SPECIAL EQUIPMENT IN ACCORDANCE WITH MANUFACTURER'S

RECOMMENDATIONS AND MAKE FINAL CONNECTIONS. ALL SUPPLIES SHALL HAVE SHUT-OFF VALVES.

INSTALL VACUUM BREAKERS WHERE REQUIRED BY CODE.

9 VALVES LOCATED ABOVE THE CEILING SHALL BE EASILY ACCESSIBLE BY EITHER REMOVABLE CEILING

TILES OR 30" WIDE ACCESS PANELS. CONTRACTOR SHALL PROVIDE AND COORDINATE ALL NECESSARY

ACCESS PANELS. ALL ACCESS PANELS SHALL BE TAMPER PROOF. SEE ARCHITECTURAL DRAWINGS FOR

CEILING TYPES.

10 LEAVE NO DEAD END BRANCHES IN DOMESTIC PIPING SYSTEM. REMOVE PIPING TO WITHIN THREE PIPE

DIAMETERS OF HEADER.

11 DO NOT ROUTE ANY PLUMBING PIPING THROUGH AN ELECTRICAL OR TELECOMM ROOM AND DO NOT

ROUTE PIPING DIRECTLY ABOVE AN ELECTRICAL PANEL.

12 PLUMBING SYSTEMS SHALL BE LABELED AND PAINTED IN ACCORDANCE WITH SPECIFICATION 09 91 00.

13 WATER HAMMER ARRESTORS SHALL BE INSTALLED WITH INLET ISOLATION VALVES TO ALLOW FOR

MAINTENANCE. PROVIDE ACCESS (INCLUDING DOORS WHERE APPLICABLE) FOR EACH ARRESTOR.

14 ALL PLUMBING LINES THAT ARE CAPPED SHALL BE PROTECTED DURING DEMOLITION.

15 THE FIRE PROTECTION CONTRACTOR IS REQUIRED TO PERFORM A FLOW TEST AND PROVIDE THAT

INFORMATION TO THE VAMC.

PLUMBING PIPING SHALL BE COORDINATED WITH ALL TRADES TO AVOID CONFLICTS, IN ORDER TO PROVIDE

A CODE COMPLIANT INSTALLATION, THIS SHALL INCLUDE ALL PHASES OF WORK AND EQUIPMENT SPACES

AND INTERRUPTIONS OF SERVICES WITH COR.

WATER PIPING SHALL BE SLOPED FOR DRAINAGE WITH DRAIN VALVES INSTALLED AT LOW POINTS.

17 ALL VERTICAL SUPPLY, SANITARY WASTE AND VENT PIPING SHALL BE LOCATED IN WALLS OR PARTITIONS, UNLESS NOTED OTHERWISE.

19 SANITARY VENTS WILL BE COLLECTED ABOVE THE CEILING AND EXTENDED UP AND CONNECT TO EXISTING

VENT THRU ROOF (VTR).

18 SUPPLY PIPING SHALL BE LOCATED ABOVE THE CEILING, UNLESS NOTED OTHERWISE.

20 THESE ENGINEERING DRAWINGS ARE DIAGRAMMATIC. IT IS THE INTENTION OF THESE DRAWINGS TO COVER

ALL WORK AND MATERIAL FOR A COMPLETE INSTALLATION. MAKE PROPER HOT AND COLD WATER, WASTE, VENT, ETC. PIPING CONNECTIONS TO ALL FIXTURES AND EQUIPMENT. ALTHOUGH ALL FITTINGS AND

CONNECTIONS ARE NOT SHOWN, THE PLUMBING CONTRACTOR IS RESPONSIBLE FOR PROVIDING PIPE

ESCUTCHEONS, DIELECTRIC UNIONS, DRIP PANS, PIPE LABELS, VALVE TAGS, ANCHORS, SUPPORT SEALS, SLEEVE SEALS, ISOLATION VALVES, CLEANOUTS, ETC. IN QUANTITIES ADEQUATE TO SATISFY THE INTENT OF

THE ENGINEER'S DOCUMENTS. ANY EQUIPMENT, PLUMBING FIXTURES, TRIM HARDWARE AND/OR DEVICES

USUALLY UTILIZED IN THIS CLASS OF WORK, THOUGH NOT SPECIFICALLY MENTIONED OR SHOWN ON THESE

DRAWINGS, BUT WHICH MAY BE NECESSARY FOR THE SATISFACTORY COMPLETION OF THE WORK (AS

DETERMINED BY THE COR) SHALL BE FURNISHED AND INSTALLED BY THE CONTRACTOR AS PART OF HIS

TOTAL WORK.

21 PROVIDE INSULATION ON ALL NEW PIPING.

22 PIPE HANGERS, HANGERS, BRACES AND RESTRAINT SHALL ADEQUATELY SUPPORT THE SYSTEM

HORIZONTALLY AND VERTICALLY AND SHALL ALLOW FOR MOVEMENT WITHOUT TRANSMITTING STRESS OR

VIBRATION TO THE STRUCTURE. HANGERS SHALL BE EQUAL TO GRINNELL PRODUCTS. HANGERS ON

INSULATED PIPING SHALL BE PROVIDED WITH AND SHALL BE SIZED TO ACCOMMODATE HANGERS, SHIELDS

AND SADDLES. HORIZONTAL SOIL, WASTE AND VENT PIPING HUNG FROM BUILDING CONSTRUCTION SHALL

BE SUPPORTED AT NOT OVER 5 FEET NEXT TO FITTINGS. PROVIDE ADDITIONAL SUPPORT AT JOINTS, CHANGES IN DIRECTION AND ELSEWHERE AS REQUIRED TO MAINTAIN PROPER ALIGNMENT.

23 THE CONTRACTOR SHALL CLEAN ALL FIXTURES, ADJUST ALL VALVES AND LEAVE THE SYSTEM IN GOOD

WORKING ORDER. REMOVE ALL DEBRIS AND RUBBISH CAUSED BY HIS WORK AND REPAIR AND DAMAGE

CAUSED BY HIS WORKMANSHIP.

24 THE PLUMBING CONTRACTOR SHALL SEAL ALL OF HIS PENETRATIONS OF FIRE-RATED WALLS USING UL

LISTED PENETRATION MATERIALS.

25 THE PLUMBING CONTRACTOR SHALL PROVIDE ALL OPENINGS IN WALLS AND FLOORS REQUIRED TO

COMPLETE HIS WORK, UNLESS OTHERWISE NOTED. HE SHALL VERIFY THE LOCATION AND SIZE OF ALL

OPENINGS REQUIRED UNDER THIS CONTRACT WITH THE GENERAL CONTRACTOR.

26 WORK SHALL INCLUDE DEMOLITION ON THE PLUMBING DRAWINGS AND INSTALLATION OF DOMESTIC COLD

WATER, WASTE PIPING, ISOLATION VALVES AS INDICATED ON THE PLUMBING DRAWINGS. THE DOMESTIC

WATER SYSTEM COMPONENTS SHALL BE DESIGNED TO WITHSTAND THE MAXIMUM STATIC PRESSURE AND

FLOW, BUT IN NO CASE SHALL BE LESS THAN 125 POUND CLASS.

27 SANITARY CLEANOUTS SHALL BE LOCATED IN ACCORDANCE WITH SECTIONS 708.3.1 THROUGH 708.3.6 OF

THE INTERNATIONAL PLUMBING CODE. SPECIFICALLY, ALL HORIZONTAL DRAINS SHALL BE PROVIDED WITH

CLEANOUTS LOCATED NOT MORE THAN 100 FT. APART. CLEANOUTS SHALL BE INSTALLED AT EACH CHANGE

OF DIRECTION GREATER THAN 45 DEGREES IN THE BUILDING SEWER, BUILDING DRAIN AND HORIZONTAL

WASTE OR SOIL LINES. WHERE MORE THAN ONE CHANGE OF DIRECTION OCCURS IN A RUN OF PIPING, ONLY

ONE CLEANOUT SHALL BE REQUIRED FOR EACH 40 FEET OF DEVELOPED LENGTH.

DPV DRY PIPE VALVE

2023.10.26 jlogan Text Box

EPA ENVIRONMENTAL PROTECTION AGENCY

jlogan Text Box

SYSTEM

SERVICE ROOM SB-1

HW STG. TK.

EX. 6"Ø CW

EX. 2

"Ø

DN.

EX. 4"Ø CW

TO BLDG. 4

EX. 4"Ø CW

TO BLDG. 4A

PIT

3'-9"

(FIELD VERIFY)

BLDG. 4A

3A3244A

BUILDING KEY PLAN

4"Ø

EX. 4"Ø TO BLDG. 4

EX. 4"Ø TO BLDG. 4A

ELEVATION

EX. 6"Ø CW

FROM MAIN

EX. 2

"Ø

FIN. FLOOR EL. 453'-0"

C EL. 459'-6"

C EL. 461'-9"±

o n e e i g h o t t h r e e i n c h e o t o n e a l f i n c h e o t o n e i n o t t h r e e q u a r t e r s i n o t o n e h a l f i n o t t h r e e e i g h t h s i n o t o n e q u a r t e r i n o t

VA FORM 08-6231, OCT 1978

A

123456789

123456789

B

C

D

A

B

C

D

E

F

Drawing Title Project Title

Checked

Building Number

Drawn

Revisions: Date

Date

Project No.

Drawing No.

Location

Sheet of

FINAL SUBMISSION

FULLY SPRINKLERED

V e t e r a n s

A f f a i r s

Approved: Associate Director

Approved: Chief of Staff

Approved: Service Chief

Approved: GEMS Coordinator

Approved: Infection Control Officer

Approved: Safety Manager

Approved: Chief of Mental Health Service

Approved: Chief of Police

Approved: Energy EngineerApproved: Patient Safety Nurse

Approved: Chief of Facility Management Svc.

Approved: Medical Center Director

TUSKEGEE, ALABAMA

2, 4 & 4A

2023.11.06

619A4-23-106

INSTALL DUAL PARALLEL PIPING

FOR DOMESTIC WATER AND FIRE

PROTECTION IN BUILDINGS 2, 4

AND 4A

D a t e

P l o t t e d

Rev. No.:

INCORPORATED

ENGINEERS

ARCHITECTS

CONSTRUCTORS

E

F

JLWB

PD101

1/4" = 1'-0"

PLUMBING DEMOLITION PLAN - BLDG. 4A SUB-BASEMENT, WATER

PLUMBING DEMOLITION PLAN

BLDG. 4A

PLAN

NORTH

1/4"=1'-0"

4' 0' 4' 8'

DRAWING DEMO KEYED NOTES

DEMO APPROXIMATE 3'-9" EXISTING SECTION OF 4"Ø PIPE FOR

INSTALLATION OF NEW BACKFLOW PREVENTER AND FITTINGS.

GENERAL PLUMBING NOTES

FOR LEGEND, SEE DWG. PL001.

LEGEND

1. FOR GENERAL PLUMBING NOTES, SEE DWG. PL001.

2. EXISTING PLUMBING IS SHOWN FOR REFERENCE ONLY. LOCATION

AND ROUTING OF EXISTING PIPING SHOULD BE VERIFIED PRIOR TO

CONSTRUCTION.

3. FOR PLUMBING SCHEDULE, SEE DRAWING PL601.

4. ALL EXISTING DIMENSIONS WERE TAKEN FROM FIELD NOTES AND

SHOULD BE VERIFIED BEFORE CONSTRUCTION.

DEMO EXISTING 4" PRESSURE REDUCING CONTROL VALVE,

VALVES, PIPING AND SUPPORTS AS SHOWN.

1/2" = 1'-0"

BLDG. 4A BASEMENT PLUMBING ELEVATION (DEMO)

NOTE:

ELEVATION IS LOOKING NORTH.

DEMO EXISTING SECTION OF 4"Ø PIPE IN VERTICAL RUN IN ORDER

TO RAISE HORIZONTAL SECTION DUE TO ELEVATION CHANGE AT

TIE-IN NEAR CW SERVICE ENTRY INTO BUILDING. FIELD DETERMINE

LENGTH OF PIPE TO BE REMOVED, ACCOUNTING FOR ANY EXISTING

INTERFERENCES.

SERVICE ROOM SB-1

HW STG. TK.

EX. 6"Ø CW

EX. 2

"Ø

DN.

EX. 4"Ø CW

TO BLDG. 4

EX. 4"Ø CW

TO BLDG. 4A

BLDG. 4A

BFP

4"

BFP

4A

4"

PIT

3'-6"

MATCH CL ELEVATION OF

EXISTING PIPE OF

APPROXIMATELY 459'-1

3A3244A

BUILDING KEY PLAN

VENT

ZURN

4"

WILKINS

4" 4"

VENT

ZURN

4"

WILKINS

4" 4"

4"Ø CW TO BLDG. 4

4"Ø CW TO BLDG. 4A

EX. 6"Ø CW

FROM MAIN

EX. 2

"Ø

FIN. FLOOR EL. 453'-0"

ROTATE HANDWHEELS

OUT 45° (TYP.) IF NEEDED

BFP FOR BLDG. 4 ELEVATION - LOOKING NORTH

C EL.

C EL. 459'-6"

C EL. 461'-9"±

C EL. 461'-0"±

FIELD ROUTE DRAIN TO

NEAREST SS, INSTALL

AIR GAP FITTING

BASE ELL SUPPORT

TYP. 2 (EA. SIDE)

BRACE WITH NEW

PIPE SUPPORT

FROM WALL (TYP. 4)

NEW 4" REDUCED PRESSURE

PRINCIPLE BACKFLOW

PREVENTER WITH GATE

VALVES (TYP. 2 PLACES)

VENT

ZURN

4"

WILKINS

4" 4"

VENT

ZURN

4"

WILKINS

4" 4"

FIN. FLOOR EL. 453'-0"

NEW FLOOR

MOUNTED PIPE

SUPPORT (TYP. 2)

NEW 4" REDUCED PRESSURE

PRINCIPLE BACKFLOW

PREVENTER WITH GATE

VALVES (TYP. 2 PLACES)

ROTATE HANDWHEELS

OUT 45° (TYP.) IF NEEDED

BFP FOR BLDG. 4A ELEVATION - LOOKING EAST

NEW 4"Ø CW

C EL. 459'-1

"C EL. 459'-1

FIELD ROUTE DRAIN TO

NEAREST SS, INSTALL

AIR GAP FITTING

o n e e i g h o t t h r e e i n c h e o t o n e a l f i n c h e o t o n e i n o t t h r e e q u a r t e r s i n o t o n e h a l f i n o t t h r e e e i g h t h s i n o t o n e q u a r t e r i n o t

VA FORM 08-6231, OCT 1978

A

123456789

123456789

B

C

D

A

B

C

D

E

F

Drawing Title Project Title

Checked

Building Number

Drawn

Revisions: Date

Date

Project No.

Drawing No.

Location

Sheet of

FINAL SUBMISSION

FULLY SPRINKLERED

V e t e r a n s

A f f a i r s

Approved: Associate Director

Approved: Chief of Staff

Approved: Service Chief

Approved: GEMS Coordinator

Approved: Infection Control Officer

Approved: Safety Manager

Approved: Chief of Mental Health Service

Approved: Chief of Police

Approved: Energy EngineerApproved: Patient Safety Nurse

Approved: Chief of Facility Management Svc.

Approved: Medical Center Director

TUSKEGEE, ALABAMA

2, 4 & 4A

2023.11.06

619A4-23-106

INSTALL DUAL PARALLEL PIPING

FOR DOMESTIC WATER AND FIRE

PROTECTION IN BUILDINGS 2, 4

AND 4A

D a t e

P l o t t e d

Rev. No.:

INCORPORATED

ENGINEERS

ARCHITECTS

CONSTRUCTORS

E

F

JLWB

PL101

1/4" = 1'-0"

PLUMBING NEW WORK PLAN - BLDG. 4A SUB-BASEMENT, WATER

PLUMBING NEW WORK PLAN

BLDG. 4A

PLAN

NORTH

1/4"=1'-0"

4' 0' 4' 8'

DRAWING NEW WORK KEYED NOTES

INSTALL NEW WALL-MOUNTED PIPE SUPPORTS.

GENERAL PLUMBING NOTES

FOR LEGEND, SEE DWG. PL001.

LEGEND

1. FOR GENERAL PLUMBING NOTES, SEE DWG. PL001.

2. EXISTING PLUMBING IS SHOWN FOR REFERENCE ONLY. LOCATION

AND ROUTING OF EXISTING PIPING SHOULD BE VERIFIED PRIOR TO

CONSTRUCTION.

3. FOR BACKFLOW PREVENTER SCHEDULE, SEE DRAWING PL501.

4. CONTRACTOR SHALL PROVIDE ADEQUATE VIBRATION CONTROL FOR

NEW BACKFLOW PREVENTER ASSEMBLIES AND PIPING.

INSTALL NEW 4" REDUCED PRINCIPLE BACKFLOW PREVENTER WITH

GATE VALVES. BFP-4 SERVING BUILDING 4 WILL BE INSTALLED ON

NORTH WALL OF SERVICE ROOM SB-1. BFP-4A SERVING BUILDING

4A WILL BE INSTALLED ON THE EAST WALL OF SERVICE ROOM SB-1.

1/2" = 1'-0"

BLDG. 4A SUB-BASEMENT BFP-4A ELEVATION (NEW)

NOTE:

ELEVATION IS LOOKING EAST.

1/2" = 1'-0"

BLDG. 4A SUB-BASEMENT BFP-4 ELEVATION (NEW)

NOTE:

ELEVATION IS LOOKING NORTH.

LOCATION

INSTALL NEW FLOOR-MOUNTED PIPE SUPPORTS.

RAISE THIS SECTION OF EXISTING 4" PIPE TO MATCH ELEVATION TO

THE SOUTH OF APPROXIMATELY 459' 1

3A3244A

BUILDING KEY PLAN

4" CW (EXIST.)

ELEV.

ROOM

MEN'S ROOM

(NOT IN USE)

SUPPLY

ROOM

ELEVATOR

STAIRS

STORAGE

PUMP

ROOM

MECH.

ROOM

BFP

4"

(ALT. LOC.)

EX. DOM. WATER

TO UPPER FLOORS

1'-0"

(MIN.)

VENT

ZURN

4"

WILKINS

4" 4"

VENT

ZURN

4"

WILKINS

4" 4"

FIN. FLOOR EL. 453'-0"

NEW FLOOR

MOUNTED PIPE

SUPPORT (TYP. 2)

NEW 4" REDUCED PRESSURE

PRINCIPLE BACKFLOW

PREVENTER WITH GATE

VALVES (TYP. 2 PLACES)

ROTATE HANDWHEELS

OUT 45° (TYP.) IF NEEDED

BFP FOR BLDG. 2 ELEVATION - LOOKING SOUTH

NEW 4"Ø CW

C EL.C EL.

FIELD ROUTE DRAIN TO

NEAREST SS, INSTALL

AIR GAP FITTING

o n e e i g h o t t h r e e i n c h e o t o n e a l f i n c h e o t o n e i n o t t h r e e q u a r t e r s i n o t o n e h a l f i n o t t h r e e e i g h t h s i n o t o n e q u a r t e r i n o t

VA FORM 08-6231, OCT 1978

A

123456789

123456789

B

C

D

A

B

C

D

E

F

Drawing Title Project Title

Checked

Building Number

Drawn

Revisions: Date

Date

Project No.

Drawing No.

Location

Sheet of

FINAL SUBMISSION

FULLY SPRINKLERED

V e t e r a n s

A f f a i r s

Approved: Associate Director

Approved: Chief of Staff

Approved: Service Chief

Approved: GEMS Coordinator

Approved: Infection Control Officer

Approved: Safety Manager

Approved: Chief of Mental Health Service

Approved: Chief of Police

Approved: Energy EngineerApproved: Patient Safety Nurse

Approved: Chief of Facility Management Svc.

Approved: Medical Center Director

TUSKEGEE, ALABAMA

2, 4 & 4A

2023.11.06

619A4-23-106

INSTALL DUAL PARALLEL PIPING

FOR DOMESTIC WATER AND FIRE

PROTECTION IN BUILDINGS 2, 4

AND 4A

D a

P l o t t e d

Rev. No.:

INCORPORATED

ENGINEERS

ARCHITECTS

CONSTRUCTORS

E

F

JLWB

PL102

SCALE: 3/16" = 1'-0"

0 12' 16'8'4'

3/16" = 1'-0"

PLUMBING NEW WORK PLAN - BLDG. 2 BASEMENT, WATER

DRAWING KEYED NOTES

GENERAL PLUMBING NOTES

FOR LEGEND, SEE DWG. PL001.

LEGEND

1. FOR GENERAL PLUMBING NOTES, SEE DWG. PL001.

2. EXISTING PLUMBING IS SHOWN FOR REFERENCE ONLY. LOCATION

AND ROUTING OF EXISTING PIPING SHOULD BE VERIFIED PRIOR TO

CONSTRUCTION.

3. FOR BACKFLOW PREVENTER SCHEDULE, SEE DRAWING PL501.

4. CONTRACTOR SHALL PROVIDE ADEQUATE VIBRATION CONTROL FOR

NEW BACKFLOW PREVENTER ASSEMBLIES AND PIPING.

PLUMBING NEW WORK PLAN

BLDG. 2

PLAN

NORTH

INSTALL NEW 4" REDUCED PRINCIPLE BACKFLOW PREVENTER WITH

GATE VALVES. BFP-2 SERVING BUILDING 2 WILL BE INSTALLED ON

SOUTH WALL OF SUPPLY ROOM SB-1.

INSTALL NEW FLOOR-MOUNTED PIPE SUPPORTS.

TIE-IN FOR NEW POTABLE WATER PIPING TO BFP MUST BE MADE

BEFORE FIRST BRANCH OF 4" MAIN.

1/2" = 1'-0"

BLDG. 2 BASEMENT BFP-2 ELEVATION (NEW, ALT.)

e e i g h o t t h r e e i n c h e o t o n e a l f i n c h e o t o n e i n o t t h r e e q u a r t e r s i n o t o n e h a l f i n o t t h r e e e i g h t h s i n o t o n e q u a r t e r i n o t

VA FORM 08-6231, OCT 1978

A

123456789

123456789

B

C

D

A

B

C

D

E

F

Drawing Title Project Title

Checked

Building Number

Drawn

Revisions: Date

Date

Project No.

Drawing No.

Location

Sheet of

FINAL SUBMISSION

FULLY SPRINKLERED

V e t e r a n s

A f f a i r s

Approved: Associate Director

Approved: Chief of Staff

Approved: Service Chief

Approved: GEMS Coordinator

Approved: Infection Control Officer

Approved: Safety Manager

Approved: Chief of Mental Health Service

Approved: Chief of Police

Approved: Energy EngineerApproved: Patient Safety Nurse

Approved: Chief of Facility Management Svc.

Approved: Medical Center Director

TUSKEGEE, ALABAMA

2, 4 & 4A

2023.11.06

619A4-23-106

INSTALL DUAL PARALLEL PIPING

FOR DOMESTIC WATER AND FIRE

PROTECTION IN BUILDINGS 2, 4

AND 4A

D a t e

P l o t t e d

Rev. No.:

INCORPORATED

ENGINEERS

ARCHITECTS

CONSTRUCTORS

E

F

JLWB

PL501

PLUMBING DETAILS AND

SCHEDULE

NOT TO SCALE

9C

TYP. BACKFLOW PREVENTER PIPING DETAIL

DESCRIPTION SIZE NOTES

REDUCED PRESSURE PRINCIPLE BACKFLOW PREVENTER ASSEMBLY:

1. BASIS OF DESIGN IS ZURN-WILKINS BUT IS NOT INTENDED TO LIMIT SELECTION. PROVIDE INDICATED

EQUIPMENT OR EQUIPMENT OF EQUAL CAPACITY, QUALITY AND PERFORMANCE.

4"

SYM

BFP-4

NOTES:

ZURN-WILKINS MODEL 375 DUCTILE IRON ASTM A536 BODY AND ACCESS

COVERS, NRS SHUT-OFF VALVES (OS&Y), FLANGED CONNECTIONS

DRAIN

1"

14"

BFP-4A

ZURN-WILKINS MODEL 375 DUCTILE IRON ASTM A536 BODY AND ACCESS

1"

REDUCED PRESSURE PRINCIPLE BACKFLOW PREVENTER ASSEMBLY:

COVERS, NRS SHUT-OFF VALVES (OS&Y), FLANGED CONNECTIONS

BFP-2

m m

WALL LINE

REDUCED PRESSURE

PRINCIPLE BACKFLOW

PREVENTER WITH GATE

VALVES

PLAN

AIR GAP

FITTING

WATER LINE

FROM METER

PIPE TO DRAIN (TYPICAL)

FINISHED FLOOR

COLD WATER TO SYSTEM

PIPE SUPPORT

ELEVATION

M

I N m m

T O

B O

T T

O M

O F

R E

L I E

F

O P

E N

I N

G S

REDUCED PRESSURE PRINCIPLE BACKFLOW PREVENTER ASSEMBLY:

14"

ZURN-WILKINS MODEL 375 DUCTILE IRON ASTM A536 BODY AND ACCESS

COVERS, NRS SHUT-OFF VALVES (OS&Y), FLANGED CONNECTIONS

1"

ALL THREAD ROD

CLEVIS HANGER

INSULATION

SHEETMETAL SHIELD

INSULATION PROTECTIVE

WASHER (TOP & BOTTOM)

NUT (TOP & BOTTOM)

PIPE

6C

TYP. CLEVIS HANGER DETAIL

NTS

2.

1.

UL CLASSIFICATION SYSTEM #147

ON EACH SIDE OF METAL STUD)

(1 LAYER OF FIRE RATED GYPSUM

OR CONDUIT

INSULATED METAL PIPE

PANEL SURFACE.

TO EXTERIOR OF GYPSUM

2 HOUR RATING, FLUSH

3/4" THICKNESS FOR

1 HOUR RATING.

1/2" THICKNESS FOR

APPLY TO BOTH SIDES OF WALL

AT JUNCTION WITH GYPSUM PANEL.

AROUND PERIMETER OF PIPE SLEEVE

BACKER ROD

METAL SLEEVE

METAL PIPE, FIBERGLASS

CP-25 N/S CAULK

1/4" BEAD OF CP-25 N/S CAULK

1-HOUR FIRE RATED WALL SECTION.

FIRE CURVE AND 3M APPLICATIONS ENGINEERING.

PER ASTM E-814 (UL 1479) TIME TEMPERATURE

RECOMMENDATIONS BASED ON PRODUCT PERFORMANCE

INSTALL 3M FIRESTOP ON BOTH SIDES OF WALL

OF WALL

FIRE BARRIER.

PENETRATES THE WALL OR FLOOR WHEN USING 3M

IT IS NOT NECESSARY TO REMOVE INSULATION AS IT

EXPOSURE. UL CLASSIFIED PER SYSTEM 91

ASTM E-814 (UL 1479) TIME TEMPERATURE CURVE FIRE

RECOMMENDATIONS BASED ON PRODUCT PERFORMANCE PER

MAXIMUM ANNULAR SPACE TO BE FILLED IS 2-1/2"

MINIMUM ANNULAR SPACE TO BE FILLED IS 3/4".

2"-3" OF INSULATION - 2" DEPTH OF CP-25 N/S OR S/L

1" OF INSULATION - 1" DEPTH OF CP-25 N/S OR S/L

DEPTH OF CP-25 CAULK DEPENDS ON INSULATION THICKNESS:

B) FOR INSULATED METAL PIPE:

MAXIMUM ANNULAR SPACE TO BE FILLED IS 2-1/2"

ACCEPTABLE AFTER INITIAL WET DEPTH INSTALLATION.

UP TO 40% SHRINKAGE OF CP-25 N/S OR S/L CAULK IS

PER ASTM E-814 (UL 1479) FIRE TEST AND UL

CLASSIFICATION FIRE STOP SYSTEM 49.

RECOMMENDATIONS BASED ON PRODUCT PERFORMANCE

3-4 HOURS

1-2 HOURS

MAX 8"

MAX 8"

1"

1/2"

FIRE RATING PIPE SIZE WET DEPTH

ON TYPE AND SIZE OF PIPE: AND DESIRED FIRE RATING.

WET INSTALLED DEPTH OF CP-25 CAULKS DEPENDS

A) FOR UNINSULATED METAL PIPE:

2. DEPTH OF CP-25 CAULK:

WITHIN WALL WITH DAMMING MATERIAL ON ONE SIDE.

1. FOR SOLID CONCRETE WALLS, CENTER CP-25 N/S CAULK

CAULK ON EACH SIDE

WALLS SEE NOTE 1

FOR SOLID CONCRETE

CONCRETE BLOCK WALL.

DAMMING MATERIAL

METAL PIPE SLEEVE

DEPTH OF CP-25 N/S

1-2-3 HOUR FIRE RATED

INSULATED METAL PIPE

METAL PIPE OR

SURFACES WHEN FILLING GAPS FROM BELOW.

VERTICAL SURFACES AND ON HORIZONTAL

USE CP-25 N\S NO SAG CAULK ON

GAPS FROM ABOVE THE PENETRATION.

ON HORIZONTAL SURFACES WHEN FILLING

USE CP-25 S/L SELF-LEVELING CAULK

CONCRETE FLOOR SLAB

INSULATED METAL PIPE

ENOUGH TO SUPPORT WEIGHT OF CAULK

INSULATION, BACKER ROD OR SAFING)

OF SLAB (TYP. EA. SIDE)

(SEE NOTES) FLUSH TO SURFACE

PIPE WITH CP-25 S/L CAULK

DAMMING MATERIAL (FIBERGLASS

FILL GAP COMPLETELY AROUND

1-2-3 HOUR FIRE RATED

METAL PIPE SLEEVE

METAL PIPE OR

4F

PIPE PENETRATION THRU FIRE-RATED WALLS

NTS

EX. 4"Ø FP RISER

FROM BELOW

EX. 4"Ø FP PIPING

TO BLDG. 2

EX. 4"Ø DRY PIPE VALVE

(IN VERT.), TYCO DPV-1

EX. 2"Ø DRAIN

1'-0 1/2"

ACCESS HATCH

3A3244A

BUILDING KEY PLAN

DPV-1

4" EX.

EX. 2"Ø DRAIN

EX. 4"Ø FP PIPING

ENTERING THRU FLOOR

EX. 4"Ø FP PIPING

THRU WALL

ATTIC FL EL. 509'-2"

ATTIC FL EL. 509'-2"

EX. 2"Ø DRAIN

EX. 4"Ø FP PIPING

ENTERING THRU FLOOR

EX. 4"Ø FP PIPING

THRU WALL

DPV-1

4" EX.

4"

DCV

o n e e i g h o t t h r e e i n c h e o t o n e a l f i n c h e o t o n e i n o t t h r e e q u a r t e r s i n o t o n e h a l f i n o t t h r e e e i g h t h s i n o t o n e q u a r t e r i n o t

VA FORM 08-6231, OCT 1978

A

123456789

123456789

B

C

D

A

B

C

D

E

F

Drawing Title Project Title

Checked

Building Number

Drawn

Revisions: Date

Date

Project No.

Drawing No.

Location

Sheet of

FINAL SUBMISSION

FULLY SPRINKLERED

V e t e r a n s

A f f a i r s

Approved: Associate Director

Approved: Chief of Staff

Approved: Service Chief

Approved: GEMS Coordinator

Approved: Infection Control Officer

Approved: Safety Manager

Approved: Chief of Mental Health Service

Approved: Chief of Police

Approved: Energy EngineerApproved: Patient Safety Nurse

Approved: Chief of Facility Management Svc.

Approved: Medical Center Director

TUSKEGEE, ALABAMA

2, 4 & 4A

2023.11.06

619A4-23-106

INSTALL DUAL PARALLEL PIPING

FOR DOMESTIC WATER AND FIRE

PROTECTION IN BUILDINGS 2, 4

AND 4A

D a t e

P l o t t e d

Rev. No.:

INCORPORATED

ENGINEERS

ARCHITECTS

CONSTRUCTORS

E

F

JLWB

FP101

1/2" = 1'-0"

FIRE RISER PLAN - BUILDING 2 ATTIC

FIRE RISER - BUILDING 2

ATTIC

PLAN

NORTH

1/2"=1'-0"

2' 0' 2' 4'

DRAWING KEYED NOTES

GENERAL PLUMBING NOTES

FOR LEGEND, SEE DWG. PL001.

LEGEND

1. FOR GENERAL PLUMBING NOTES, SEE DWG. PL001.

2. EXISTING PLUMBING IS SHOWN FOR REFERENCE ONLY. LOCATION

AND ROUTING OF EXISTING PIPING SHOULD BE VERIFIED PRIOR TO

CONSTRUCTION.

3. CONTRACTOR SHALL VERIFY THAT THE WATER PRESSURE

DOWNSTREAM FROM THE NEW BACKFLOW PREVENTERS SHALL BE

NO LESS THAN THE DESIRED PER THE FIRE FLOW TEST.

CONTRACTOR SHALL REQUEST LATEST AVAILABLE FLOW TESTS FOR

THE RESPECTIVE HYDRANTS NEAREST TO BUILDINGS 2, 4 AND 4A.

1/2" = 1'-0"

ELEV. "A" - BLDG. 2 ATTIC FIRE RISER ELEVATION (DEMO)

NOTE:

ELEVATION IS LOOKING WEST.

NOTE:

ELEVATION IS LOOKING WEST.

1/2" = 1'-0"

ELEV. "A" - BLDG. 2 ATTIC FIRE RISER ELEVATION (PROP.)

INSTALL NEW 2" SECTION OF DRAIN PIPE TO CONNECT TO

RELOCATED DRAIN FROM DPV-1 AND EX. PIPE (APPROX. 1'-0").

EXISTING 4" DRY PIPE EXTERNAL RESETTING VALVE (MODEL TYCO

DPV-1). RELOCATE DPV UPWARDS IN RISER DUE TO THE ADDITION

OF THE NEW DOUBLE CHECK BACKFLOW PREVENTER.

DEMO EXISTING 4" GATE VALVE AND SECTION OF 4"Ø PIPE.

LOCATION

A

A

DESCRIPTION SIZE NOTES

DOUBLE CHECK VALVE BACKFLOW PREVENTER ASSEMBLY:

1. BASIS OF DESIGN IS AMES BUT IS NOT INTENDED TO LIMIT SELECTION. PROVIDE INDICATED

EQUIPMENT OR EQUIPMENT OF EQUAL CAPACITY, QUALITY AND PERFORMANCE.

4"

SYM

DCV-2

NOTES:

AMES FIRE & WATERWORKS SERIES 2000SS, STAINLESS STEEL BODY

OS&Y SHUT-OFF VALVES, FLANGED CONNECTIONS, AWWA C510-92

DRAIN

INSTALL NEW DOUBLE CHECK BACKFLOW PREVENTER WITH OSY

GATE VALVE ASSEMBLY IN VERTICAL (FLOW UP) POSITION.

4A-332

EX. 2"Ø DRAIN

EX. 4"Ø FP PIPING

THRU CEILING

EX. 4"Ø DRY PIPE VALVE

(IN VERT.), TYCO DPV-1

EX. 4"Ø FP PIPING

ENTERING

4AC-3N

ELEV.

4A-322

4A-301

1'-1"

1'-7"

4A-332A

3A3244A

BUILDING KEY PLAN

EX. 3"Ø

EX. 4"Ø

EX. 4"Ø

ATTIC FL

EX. 4"Ø FP PIPING

THRU CEILING

EX. 4"Ø FP PIPING

ENTERING

DPV-1

4" EX.

EX. 2"Ø DRAIN

3RD FL EL. 498'-5"

EX. 4"Ø

ATTIC FL

EX. 4"Ø FP PIPING

THRU CEILING

EX. 4"Ø FP PIPING

ENTERING

DPV-1

4" EX.

EX. 2"Ø DRAIN

EX. 4"Ø

EX. 4"Ø

DCV

4A

4"

3RD FL EL. 498'-5"

o n e e i g h o t t h r e e i n c h e o t o n e a l f i n c h e o t o n e i n o t t h r e e q u a r t e r s i n o t o n e h a l f i n o t t h r e e e i g h t h s i n o t o n e q u a r t e r i n o t

VA FORM 08-6231, OCT 1978

A

123456789

123456789

B

C

D

A

B

C

D

E

F

Drawing Title Project Title

Checked

Building Number

Drawn

Revisions: Date

Date

Project No.

Drawing No.

Location

Sheet of

FINAL SUBMISSION

FULLY SPRINKLERED

V e t e r a n s

A f f a i r s

Approved: Associate Director

Approved: Chief of Staff

Approved: Service Chief

Approved: GEMS Coordinator

Approved: Infection Control Officer

Approved: Safety Manager

Approved: Chief of Mental Health Service

Approved: Chief of Police

Approved: Energy EngineerApproved: Patient Safety Nurse

Approved: Chief of Facility Management Svc.

Approved: Medical Center Director

TUSKEGEE, ALABAMA

2, 4 & 4A

2023.11.06

619A4-23-106

INSTALL DUAL PARALLEL PIPING

FOR DOMESTIC WATER AND FIRE

PROTECTION IN BUILDINGS 2, 4

AND 4A

D a t e

P l o t t e d

Rev. No.:

INCORPORATED

ENGINEERS

ARCHITECTS

CONSTRUCTORS

E

F

JLWB

FP102

1/2" = 1'-0"

FIRE RISER PLAN - BUILDING 4A 3RD FLOOR

FIRE RISER - BUILDING 4A

3RD FLOOR

PLAN

NORTH

1/2"=1'-0"

2' 0' 2' 4'

DRAWING KEYED NOTES

INSTALL NEW SECTION OF 4"Ø PIPE AND CONNECTING FLANGES IN

VERTICAL AS MAKEUP FOR BFP INSTALLATION.

INSTALL NEW DOUBLE CHECK BACKFLOW PREVENTER WITH OSY

GATE VALVE ASSEMBLY IN VERTICAL (FLOW UP) POSITION.

1/2" = 1'-0"

ELEV. "B" - ROOM 4A-332A FIRE RISER ELEVATION (DEMO)

NOTE:

ELEVATION IS LOOKING EAST.

1/2" = 1'-0"

ELEV. "B" - ROOM 4A-332A FIRE RISER ELEVATION (PROP.)

NOTE:

ELEVATION IS LOOKING EAST.

MODIFY EXISTING PIPE SUPPORT AS REQUIRED FOR THE NEW

DESIGN. VERIFY SUPPORT IS CAPABLE OF SUPPORTING THE

ADDITIONAL LOAD.

EXISTING 4" DRY PIPE EXTERNAL RESETTING VALVE (MODEL TYCO

DPV-1). LOCATION UNCHANGED IN RISER.

DEMO EXISTING 3" GATE VALVE AND ASSOCIATED FLANGES.

LOCATION

B

B

DESCRIPTION SIZE NOTES

1. BASIS OF DESIGN IS AMES BUT IS NOT INTENDED TO LIMIT SELECTION. PROVIDE INDICATED

EQUIPMENT OR EQUIPMENT OF EQUAL CAPACITY, QUALITY AND PERFORMANCE.

4"

SYM

DCV-4A

NOTES:

AMES FIRE & WATERWORKS SERIES 2000SS, STAINLESS STEEL BODY

OS&Y SHUT-OFF VALVES, FLANGED CONNECTIONS, AWWA C510-92

DRAIN

DOUBLE CHECK VALVE BACKFLOW PREVENTER ASSEMBLY:

GENERAL PLUMBING NOTES

FOR LEGEND, SEE DWG. PL001.

LEGEND

1. FOR GENERAL PLUMBING NOTES, SEE DWG. PL001.

2. EXISTING PLUMBING IS SHOWN FOR REFERENCE ONLY. LOCATION

AND ROUTING OF EXISTING PIPING SHOULD BE VERIFIED PRIOR TO

CONSTRUCTION.

3. CONTRACTOR SHALL VERIFY THAT THE WATER PRESSURE

DOWNSTREAM FROM THE NEW BACKFLOW PREVENTERS SHALL BE

NO LESS THAN THE DESIRED PER THE FIRE FLOW TEST.

CONTRACTOR SHALL REQUEST LATEST AVAILABLE FLOW TESTS FOR

THE RESPECTIVE HYDRANTS NEAREST TO BUILDINGS 2, 4 AND 4A.

4-325

EX. 2"Ø DRAIN

EX. 4"Ø DRY PIPE VALVE

(IN VERT.), TYCO DPV-1

EX. 4"Ø FP PIPING

THRU CEILING

EX. 4"Ø FP PIPING

ENTERING

4-326

4-3224-323

1'-1"

5'-1 1/2"

3'-6"

4C-3

BLDG. 4A

3A3244A

BUILDING KEY PLAN

EX. 3"Ø

EX. 4"Ø

ATTIC FL

EX. 4"Ø FP PIPING

THRU CEILING

EX. 4"Ø FP PIPING

ENTERING

DPV-1

4" EX.

EX. 2"Ø DRAIN

3RD FL EL. 498'-5"

3RD FL EL. 498'-5"

ATTIC FL

EX. 4"Ø FP PIPING

THRU CEILING

EX. 4"Ø FP PIPING

ENTERING

DPV-1

4" EX.

EX. 2"Ø DRAIN

DCV

4"

EX. 4"Ø

o n e e i g h o t t h r e e i n c h e o t o n e a l f i n c h e o t o n e i n o t t h r e e q u a r t e r s i n o t o n e h a l f i n o t t h r e e e i g h t h s i n o t o n e q u a r t e r i n o t

VA FORM 08-6231, OCT 1978

A

123456789

123456789

B

C

D

A

B

C

D

E

F

Drawing Title Project Title

Checked

Building Number

Drawn

Revisions: Date

Date

Project No.

Drawing No.

Location

Sheet of

FINAL SUBMISSION

FULLY SPRINKLERED

V e t e r a n s

A f f a i r s

Approved: Associate Director

Approved: Chief of Staff

Approved: Service Chief

Approved: GEMS Coordinator

Approved: Infection Control Officer

Approved: Safety Manager

Approved: Chief of Mental Health Service

Approved: Chief of Police

Approved: Energy EngineerApproved: Patient Safety Nurse

Approved: Chief of Facility Management Svc.

Approved: Medical Center Director

TUSKEGEE, ALABAMA

2, 4 & 4A

2023.11.06

619A4-23-106

INSTALL DUAL PARALLEL PIPING

FOR DOMESTIC WATER AND FIRE

PROTECTION IN BUILDINGS 2, 4

AND 4A

D a t e

P l o t t e d

Rev. No.:

INCORPORATED

ENGINEERS

ARCHITECTS

CONSTRUCTORS

E

F

JLWB

FP103

1/2" = 1'-0"

FIRE RISER PLAN - BUILDING 4 3RD FLOOR

DRAWING KEYED NOTES

FIRE RISER - BUILDING 4

3RD FLOOR

PLAN

NORTH

1/2"=1'-0"

2' 0' 2' 4'

1/2" = 1'-0"

ELEV. "C" - ROOM 4-325 FIRE RISER ELEVATION (EX.)

NOTE:

ELEVATION IS LOOKING NORTH.

1/2" = 1'-0"

ELEV. "C" - ROOM 4-325 FIRE RISER ELEVATION (PROP.)

NOTE:

ELEVATION IS LOOKING NORTH.

INSTALL NEW 2" DRAIN PIPE TO CONNECT TO RELOCATED DRAIN

FROM DPV-1 AND EX. PIPE (APPROX. 4'-0").

VERIFY EXISTING PIPE SUPPORT IS CAPABLE OF SUPPORTING THE

ADDITIONAL LOAD. MODIFY IF NEEDED.

EXISTING 4" DRY PIPE EXTERNAL RESETTING VALVE (MODEL TYCO

DPV-1). RELOCATE DPV UPWARDS IN RISER DUE TO THE ADDITION

OF THE NEW DOUBLE CHECK BACKFLOW PREVENTER.

ADJUST VERTICAL LENGTH OF EXISTING 4" PIPE TO HOLD LOCATION

OF HORIZONTAL RUN OF 4" PIPE.

DEMO EXISTING 3" GATE VALVE AND ASSOCIATED FLANGES.

DEMO SECTION OF 4"Ø PIPE TO ALLOW FOR INSTALLATION OF NEW

DOUBLE CHECK BACKFLOW PREVENTER ASSEMBLY.

LOCATION

CC

INSTALL NEW 1 1/4" DRAIN PIPE TO CONNECT TO RELOCATED DRAIN

FROM DPV-1 AND EX. PIPE (APPROX. 2'-0").

DESCRIPTION SIZE NOTES

1. BASIS OF DESIGN IS AMES BUT IS NOT INTENDED TO LIMIT SELECTION. PROVIDE INDICATED

EQUIPMENT OR EQUIPMENT OF EQUAL CAPACITY, QUALITY AND PERFORMANCE.

4"

SYM

DCV-4

NOTES:

AMES FIRE & WATERWORKS SERIES 2000SS, STAINLESS STEEL BODY

OS&Y SHUT-OFF VALVES, FLANGED CONNECTIONS, AWWA C510-92

DRAIN

INSTALL NEW DOUBLE CHECK BACKFLOW PREVENTER WITH OSY

GATE VALVE ASSEMBLY IN VERTICAL (FLOW UP) POSITION.

DOUBLE CHECK VALVE BACKFLOW PREVENTER ASSEMBLY:

GENERAL PLUMBING NOTES

FOR LEGEND, SEE DWG. PL001.

LEGEND

1. FOR GENERAL PLUMBING NOTES, SEE DWG. PL001.

2. EXISTING PLUMBING IS SHOWN FOR REFERENCE ONLY. LOCATION

AND ROUTING OF EXISTING PIPING SHOULD BE VERIFIED PRIOR TO

CONSTRUCTION.

3. CONTRACTOR SHALL VERIFY THAT THE WATER PRESSURE

DOWNSTREAM FROM THE NEW BACKFLOW PREVENTERS SHALL BE

NO LESS THAN THE DESIRED PER THE FIRE FLOW TEST.

CONTRACTOR SHALL REQUEST LATEST AVAILABLE FLOW TESTS FOR

THE RESPECTIVE HYDRANTS NEAREST TO BUILDINGS 2, 4 AND 4A.

2" MAIN DRAIN. MODIFY PIPING

TO RECONNECT TO EXISTING

DRAIN PIPING.

EX. 4" DRY PIPE EXTERNAL RESETTING VALVE.

RELOCATE AS SHOWN ON THE PLANS TO

ALLOW FOR INSTALLATION OF NEW DOUBLE

CHECK BACKFLOW PREVENTER.

INSTALL NEW DOUBLE CHECK

VALVE BACKFLOW PREVENTER

WITH OSY GATE VALVE ASSEMBLY

IN VERTICAL (FLOW UP) POSITION.

LOCATE ASSEMBLY A MINIMUM OF

12" ABOVE THE FLOOR.

M I N

4" FIRE WATER TO BUILDING

SYSTEM

TOC

NOTE: BASIS OF DESIGN IS AMES SERIES 2000SS DOUBLE CHECK

VALVE ASSEMBLY BUT IS NOT INTENDED TO LIMIT

EQUIPMENT SELECTION. PROVIDE INDICATED EQUIPMENT

OF EQUIPMENT OF EQUAL PERFORMANCE AND QUALITY.

SOME ADJUSTMENT OF DIMENSIONS AND LAYOUT MAY BE

REQUIRED WHEN SPECIFYING DIFFERENT MODELS.

ENSURE PIPING AND EQUIPMENT

ARE ADEQUATELY SUPPORTED

" MAIN DRAIN. MODIFY PIPING

TO RECONNECT TO EXISTING

DRAIN PIPING.

o n e e i g h o t t h r e e i n c h e o t o n e a l f i n c h e o t o n e i n o t t h r e e q u a r t e r s i n o t o n e h a l f i n o t t h r e e e i g h t h s i n o t o n e q u a r t e r i n o t

VA FORM 08-6231, OCT 1978

A

123456789

123456789

B

C

D

A

B

C

D

E

F

Drawing Title Project Title

Checked

Building Number

Drawn

Revisions: Date

Date

Project No.

Drawing No.

Location

Sheet of

FINAL SUBMISSION

FULLY SPRINKLERED

V e t e r a n s

A f f a i r s

Approved: Associate Director

Approved: Chief of Staff

Approved: Service Chief

Approved: GEMS Coordinator

Approved: Infection Control Officer

Approved: Safety Manager

Approved: Chief of Mental Health Service

Approved: Chief of Police

Approved: Energy EngineerApproved: Patient Safety Nurse

Approved: Chief of Facility Management Svc.

Approved: Medical Center Director

TUSKEGEE, ALABAMA

2, 4 & 4A

2023.11.06

619A4-23-106

INSTALL DUAL PARALLEL PIPING

FOR DOMESTIC WATER AND FIRE

PROTECTION IN BUILDINGS 2, 4

AND 4A

D a t e

P l o t t e d

Rev. No.:

INCORPORATED

ENGINEERS

ARCHITECTS

CONSTRUCTORS

E

F

JLWB

FP501

FIRE RISER DETAILS

NOT TO SCALE

9C

TYP. DBL. CHECK BACKFLOW PREVENTER PIPING DETAIL

NOT TO SCALE

6C

TYP. DBL. CHECK BACKFLOW PREVENTER INSTALLATION DETAIL