This is a Fire Alarm System Inspection and Test Report form used by the National Park Service Alaska Regional Office (AKRO) to document the inspection and testing of fire alarm systems at park facilities.
The form documents comprehensive testing of fire alarm system components in accordance with NFPA 72 standards. Key sections include: General conditions (panel accessibility, pull station visibility, key and instruction availability), Fire Alarm Control Panel (AC/battery/generator power operation, trouble signals, circuit breaker identification, fuse conditions), Initiating Devices and Notification Appliances (100% testing of manual pull stations, smoke detectors, heat detectors, sprinkler waterflow switches, duct smoke detectors, tamper switches, horns, strobes, speakers, and bells), Batteries (standby and alarm ratings, no-load and full-load voltage measurements), Interface Devices (emergency generators, sprinkler flow switches, supervisory switches, suppression systems, fire pumps, emergency lighting), and Other Equipment Controlled by FACP (fan controls, smoke dampers, elevator recall/shunt trip, door hold release, remote annunciator panels). The form requires identification of the system make/model, testing date/time, technician credentials (state certification and NICET numbers), and documentation of any deficiencies found with NFPA 72 code references and recommended resolutions. A separate deficiencies section allows for detailed documentation of up to four identified issues with location, description, recommended corrective action, and whether corrections have been completed. Off-site monitoring information and park-specific identifiers (Park Alpha Code, FMSS Location Number) are also recorded.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Sol_140P9726Q0017.pdf | ||
| Attachment_6__DC_-_Dry_Chemical_Test_Form_(1).pdf | ||
| B03_DOL_WD_2015-5683_Rev_25.pdf | ||
| B03_DOL_WD_2015-5685_Rev_27.pdf | ||
| B03_DOL_WD_2015-5687_Rev_27.pdf | ||
| Attachment_3__DENA_Coordination_Requirements_1-23-20_(1).pdf | ||
| Attachment_8__FP_-_Fire_Pump_Test_Form_(1).pdf | ||
| B08_Subcontracting___Worksheet.xlsx | XLSX spreadsheet | |
| Attachment_5__CA_-_Clean_Agent_and_CO2_Test_Form_(1).pdf | ||
| Attachment_9__SP_-_Fire_Sprinkler_Test_Form_(1).pdf | ||
| Attachment_10__NPS_FILLABLE_INVENTORY_FORM_Vez_(1).xlsx | XLSX spreadsheet | |
| Attachment_2_-_SOW.pdf | ||
| Attachment_1_Structural_Fire_Asset_Details.pdf | ||
| Attachment_4__BP_-_Backflow_Device_Test_Form.pdf | ||
| B03_DOL_WD_2015-5681_Rev_25.pdf |
Show all 15
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Fire Alarm Page 1 of 3 Revised 12/17/25
National Park Service / AKRO
Inspection and Test Report (complete a separate form for each system)
FIRE ALARM SYSTEM – ADDRESSABLE CONVENTIONAL
Park Alpha Code: ______________________ FMSS Location No.:___________________
Location Description: ______________________
Date of Test:_________________________
Time:_________________
System Make: ______________________ System Model: _____________________
Off Site Monitoring? Yes No Monitoring Company or Location
Name ________________________________
DEFICIENCIES FOUND? Yes No List items that were not corrected. Use the Deficiencies section or attach itemized sheet
REPAIRS: All deficiencies have been corrected N/A Yes No
This certifies that the fire and life safety system has been inspected and tested for functional operation in accordance with the current edition of NFPA 72, and has been properly tagged and/or labeled. Any discrepancies found are noted in this report with code references for corrective action by the Owner/Responsible Person.
Technician Name (printed): ______________________ Company: ______________________________
Signature: ___________________________________ Phone #: _______________________________
State Certification No.: _________________________
National/NICET No.: ___________________________
GENERAL
1. The key to the panel is available at the FACP. N/A Yes No
2. The operating instructions are available at the FACP. Yes No
3. Materials and equipment needed to restore pull stations are available at the main panel, e.g. glass rods, and plates; keys and allen wrenches, etc. N/A Yes No
4. FACP and/or remote annunciator are accessible and free of obstructions preventing access. Yes No
5. Manual pull stations are visible and accessible. Yes No
FIRE ALARM CONTROL PANEL
6. All signals on the FACP operate on AC power. Yes No
7. All signals on the FACP operate on battery power. Yes No
8. All signals on the FACP operate on emergency generator/standby power N/A Yes No
9. A trouble signal activates upon loss of power, ground fault, and open circuit. Yes No
10. Circuit breaker location is identified at the FACP and all booster panels. Yes No
11. Fuses are satisfactory. Yes No
Fire Alarm Page 2 of 3 Revised 12/17/25
INITIATING DEVICES AND NOTIFICATION APPLIANCES
12. All initiating and annunciating devices tested operate properly on AC power. Yes No
13. All initiating and annunciating devices tested operate properly on generator/standby power. Yes No
14. All initiating and annunciating devices tested operate properly on battery power. Yes No
15. Detectors and sampling tubes, are not obstructed and are free of dust, dirt, and debris. Yes No
16. 100% of the INITIATING DEVICES were tested per NFPA 72.
No. of Units Tested Manual Pull Stations ________________ Smoke Detectors ________________ Heat Detectors ________________ Sprinkler Waterflow ________________ Dry Sprinkler High/Low Air ________________ Duct Smoke Detectors ________________ Tamper Switches ________________ Suppression Systems ________________ Other ________________
Yes No
17. 100% of the NOTIFICATION APPLIANCES were tested per NFPA 72
No. of Units Tested Horns ________________ Horn/Strobes ________________ Speakers ________________ Speaker / Strobes ________________ Bells (interior) ________________ Exterior Horns/Bells ________________
18. The audible alarm appliances tested operate at the levels designed by the manufacturer. Yes No
19. The audible appliances tested in residential areas generate a minimum of 70 dBA in sleeping areas.
N/A
20. The visual alarm appliances tested operate as designed. Yes No
BATTERIES
21. The batteries are rated for: ____ hours standby and ____ minutes alarm
22. Battery voltage (no load) ________ volts
23. Battery voltage (full load) ________ volts (signals operating)
24. Charge circuit voltage ________ volts
INTERFACE DEVICES
The FACP received signals from the following Interface devices: Tested by: Simulation Operation
25. Emergency Generator(s) N/A Yes No
26. Sprinkler Flow Switch(es) N/A Yes No
27. Supervisory Switch(es) N/A Yes No
28. Kitchen Hood Suppression System(s) N/A Yes No
29. Spray Booth Suppression System(s) N/A Yes No
30. Clean Agent System(s) N/A Yes No
31. Fire Pump(s) N/A Yes No
32. Emergency Lighting N/A Yes No
OTHER EQUIPMENT CONTROLLED BY FACP
The following Fire Safety Functions responded to signals from the FACP. Tested by Simulation Operation
33. Fan controls N/A Yes No
34. Smoke Dampers N/A Yes No
35. Elevator Recall N/A Yes No
36. Elevator Shunt Trip N/A Yes No
Fire Alarm Page 3 of 3 Revised 12/17/25
37. Door hold release N/A Yes No
38. Fire Pump(s) N/A Yes No
39. Remote Annunciator Panels N/A Yes No
40. Other - N/A Yes No
MONITORING
41. Signals were received at the monitoring company or approved location. N/A Yes No
Deficiencies
Resolved
Location:
Deficiency:
Recommended Resolution:
NFPA 72 reference:
File details come from the government source that posted it. Updated .