ATTACHMENT 7 - Drawings 6 of 7.pdf

PDF 14 MB Posted

Attached to
Y1DA--Expand Primary Care (Minor) Construction Iron Mountain
Solicitation number
36C77621B0005
Issued by

About this file

This document provides details regarding a federal contract solicitation for construction services. The Department of Veterans Affairs, through its Veterans Health Administration and Program Contracting Activity Central, will issue an Invitation for Bid for an expand primary care construction project at the Oscar G. Johnson VA Medical Center in Iron Mountain, Michigan. The project involves adding 10,000 square feet to the existing hospital and renovating 1,100 square feet of existing space on the first floor for primary care. The solicitation will be set aside as a total Service-Disabled Veteran-Owned Small Business set-aside, with a North American Industry Classification System code of 236220 and size standard of $39.5 million. The performance period is approximately 546 calendar days from notice to proceed, with a magnitude between $5,000,000 to $10,000,000. The solicitation is scheduled for release in early to mid-March 2021.

View the file

Other files

Show all 20

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

H

S

H #

S #

ER

H

DS (##)

DH

TS

FS

FACP

FAAP

FATP

DESCRIPTION (MOUNTING)SYMBOLDESCRIPTION (MOUNTING)SYMBOL DESCRIPTION (MOUNTING)SYMBOL

LIGHTING FIXTURES

WIRING DEVICES

POWER EQUIPMENT COMMUNICATIONS EQUIPMENT

SOUND SYSTEM DEVICES

FIRE ALARM AND DETECTOR DEVICES

SECURITY EQUIPMENT

NURSE CALL SYSTEM DEVICES

RESCUE ASSISTANCE

SYSTEMS CLOCKS

ELECTRICAL SYMBOLS LEGEND

SURFACE CEILING FIXTURE - 2X4, 2X2, 1X4

RECESSED CEILING FIXTURE - 2X4, 2X2, 1X4

SURFACE/PENDANT FIXTURE

EMERGENCY BATTERY PACK (WALL, CEILING)

EXIT SIGN - SINGLE FACE (CEILING, WALL)

FIXTURE CONNECTED TO EMERGENCY CRITICAL/EQUIP. BRANCH POWER

WALL MOUNTED

FIXTURE CONNECTED TO EMERGENCY LIFE SAFETY BRANCH POWER

POLE TOP MOUNTED LUMINAIRE

POLE ARM MOUNTED LUMINAIRE(S)

TRACK LIGHTING

WARNING LIGHT (CEILING, WALL)

UNDERCABINET LIGHT/NARROW STRIP LIGHT

BOLLARD

FLOOD LIGHT

WALL WASH DOWN LIGHT FIXTURE

SS K2 S SK K3 K4

R

EMERGENCY STOP PUSHBUTTON

SWITCH W/ PILOT LIGHT

SWITCH & DUPLEX RECPT. MOUNTED IN COMMON BOX

WALL BOX DIMMER SWITCH (FLUORESCENT)

WALL BOX DIMMER SWITCH (INCANDESCENT)

SEPARATELY SWITCHED BALLASTS (DUAL-LEVEL)

SWITCH - 1, 2 POLE; 3, 4 WAYS

S D

SP

DF

S

S

S

SS

2S 3S 4

KEY SWITCH - 1, 2 POLE; 3, 4 WAY

DIMMER SYSTEM COMPONENT

LOW VOLTAGE SWITCH/RELAY CONTROL SWITCH

D

(4)

(4)

(4)

(4,5,6)

(4)

(4)

(4)

PUSHBUTTON SWITCH (2-BUTTON, 3-BUTTON)

RT

SR

SINGLE RECPT. (FLOOR, CEILING)

GF

DUPLEX RECEPT. (FLOOR, CEILING)

DUPLEX RECEPT. W/ GROUND FAULT

DOUBLE DUPLEX RECEPT. (FLOOR, CEILING)

SPECIAL PURPOSE CONNECTION

SURFACE RACEWAY

DUPLEX RECEPT. W/ RAIN TIGHT COVER

DUPLEX RECEPT. W/ SAFETY TYPE (TAMPER-RESISTANT)

DIVIDED SURFACE RACEWAY

MULTI-OUTLET PLUGSTRIP ASSEMBLY

(5,6,7)

(5,6)

(5,6)

(5,6)

(5,6)

(5,6)

(5,6)

(5,6)

(5,6)

PANELBOARD (EXISTING, NEW)

DISCONNECT SWITCH - FUSED, NON-FUSED

ELECTRIC MOTOR

MANUAL STARTER

COMBINATION MAGNETIC STARTER/DISCONNECT

S

TRANSFORMER

POWER METER OR TRANSOCKET

AUTOMATIC TRANSFER SWITCH

MAGNETIC STARTER

RELAY CONTACTOR

OUTDOOR UTILITY POLE

FAN SPEED SWITCH

MS

VARIABLE FREQUENCY DRIVE

BUSWAY

M

#X

WALL TELEPHONE [VOICE/DATA] OUTLET

INTERCOM

INTERCOM (MASTER)

WIRELESS DATA ACCESS POINT (CEILING, WALL)

I

I

#X

#X

DATA/VOICE/CATV RACK

CATV OUTLET (WALL, CEILING)T T

PAAC

PAGING SPEAKER, CEILING MOUNTED (RECESSED, SURFACE)

SPEAKER VOLUME CONTROL

CLOCK SPEAKER ASSEMBLY

PUBLIC ADDRESS AMPLIFIER & CONTROL (PAAC HEAD-END)

P.A. HORN SPEAKER, WALL MOUNTED

PAGING SPEAKER, WALL MOUNTED

MIC JACK (WALL, FLOOR, CEILING MT.)

S

S

S

S

M

AMPLIFIERA

RECIEVERR

ANTENNA

SV

MM

MANUAL PULL STATION (NEW, EXISTING)

STROBE ONLY (NEW, EXISTING)

SMOKE DETECTOR (NEW, EXISTING)

DOOR HOLD OPEN (NEW, EXISTING)

DUCT SMOKE DETECTOR (NEW, EXISTING)(##)

SMOKE DETECTOR FOR ELEVATOR CONTROL (NEW, EXISTING)

SPRINKLER WATER FLOW SWITCH (NEW, EXISTING)

SPRINKLER TAMPER SWITCH (NEW, EXISTING)

HEAT/THERMAL DETECTOR (NEW, EXISTING)

REMOTE TEST SWITCH W/ INDICATOR (WALL , CEILING)

FIRE ALARM CONTROL PANEL (NEW, EXISTING)

FIRE ALARM ANNUNCIATOR PANEL (NEW, EXISTING)

FIRE ALARM TRANSPONDER PANEL (NEW, EXISTING)

(10)

(9)

S

MONITORING / CONTROL MODULE

H

S

HORN (NEW, EXISTING)

SPEAKER (NEW, EXISTING)

H #

S #

HORN/STROBE (NEW, EXISTING) (10)

SPEAKER/STROBE (NEW, EXISTING)(10)

H

S

HORN LOUDSPEAKER

# CEILING MOUNTED HORN/STROBE (10)

CEILING SPEAKER, RECESSED

ER

H

DS

DH

TS

FS

MM CM

RTS/I

FACP

FAAP

FATP

RTE

K

DS

ES

SECURITY CAMERA (WALL, CEILING)

REQUEST TO EXIT

DOOR ALARM KEY BY-PASS SWITCH

DOOR SWITCH / POSITION SWITCH

ELECTRIC STRIKE

AUDIO/VISUAL MONITOR/TV

INFANT SECURITY DEVICE

SECURITY SYSTEM CONTROL PANEL (SSCP)

CR CARD READER

M

ML MAGNETIC LOCK

ELR ELECTRIC LATCH RETRACTION

MD

MOTION DETECTOR

N

GB

Z

EPB

F

EMERGENCY STATION - CORD TYPE

CORRIDOR DOME LIGHT, FULL FEATURE (CEILING, WALL)

MASTER STATION

NURSE CALL CONTROL PANEL

M

N

E

IU BED INTERFACE UNIT

B

CODE BLUE STATION

GRAPHICAL ROOM STATION

G

ROOM BOX (MDRP)

C CALL CORD BUTTON

CORRIDOR ZONE LIGHT

CORRIDOR DOME LIGHT (CEILING, WALL)

GRAPHICAL ROOM STATION W/ CODE BLUE

EMERGENCY STATION - PUSH BUTTON

RESCUE ASSISTANCE CALL STATION

RESCUE ASSISTANCE ANNUNCIATOR PANEL (RAAP)

N

N

N

N

N

N

N

N

N

RA

STANDARD ROOM STATION SN

SB STANDARD ROOM STATION W/ CODE BLUE N

M

WALL CLOCK (RECESS, SURFACE)

12:00 DIGITAL WALL CLOCK

CLOCK, DOUBLE FACE (CEILING, WALL)

12:0012:00 DIGITAL CLOCK, DOUBLE FACE (CEILING, WALL)

MASTER CLOCK

NOTES:

(1) 1" CONDUIT STUBBED UP TO ACCESSIBLE SPACE ABOVE CEILING FROM 4" SQUARE JUNCTION BOX W/ SINGLE GANG DEVICE RING. ALL CONDUIT STUBS SHALL BE TERMINATED W/ BUSHINGS.

(2) FIXTURE TYPE: SEE LIGHT FIXTURE SCHEDULE (LOCATION AROUND SYMBOL MAY VARY)

XX

CIRCUIT NUMBER: SEE PLAN FOR PANEL BEING USED. (LOCATION AROUND SYMBOL MAY VARY)

(3) (XX) - INDICATES AUTOMATIC LIGHTING CONTROL DEVICE TYPE. REFERENCE SCHEDULE ON SHEET E602.

(4) REFERENCE SWITCH WIRING DETAIL ON SHEET E502.

(5) REFERENCE RECEPTACLE WIRING DETAIL ON SHEET E502.

(6) RECEPTACLE CIRCUIT NUMBER: SEE PLAN FOR PANEL BEING USED. (LOCATION AROUND SYMBOL MAY VARY)

DEVICE HEIGHT (ONLY USED FOR SPECIAL HEIGHT REQUIREMENTS)

(7) #X - INDICATES QUANTITY AND TYPE OF DROPS:

2D 2V/2D

TYPE OF DROPS: COMBINATION VOICE/DATA

D = DATA

V = VOICE

QUANTITY OF DROPS

(8) PROVIDE DATA DROP AT LOCATION. PROVIDE 15FT. OF COILED CABLE ABOVE FINISHED CEILING. 'G' INDICATES GUEST NETWORK.

(9) (##) DESIGNATION INDICATES DAMPER OR AIR UNIT SERVED BY THE DUCT DETECTOR. REFERENCE THE FIRE/SMOKE DAMPER SCHEDULE ON SHEET H600 FOR FULL DESIGNATION.

(10) (##) DESIGNATION INDICATES CANDELA OF VISUAL ALARM.

(11) OMITTED.

(12) REFERENCE THE SCHEDULE ON SHEET E601.

* THIS COMPRISES A COMPLETE LIST OF ITEMS. NOT ALL SYMBOLS MAY NECESSARILY BE REPRESENTED ON THIS PROJECT.

L

RK

NCCP

RAAP

M MONITOR DATA OUTLET (1 DROP) - ABOVE COUNTER

CATV OUTLET W/ PILLOW SPEAKER CONTROL JACK (WALL, CEILING)T TN N

TELEPHONE PEDESTALTP

BC

AUDIO STATION BED CONNECTOR N

DB

DUTY STATION

D

DUTY STATION W/ CODE BLUE

N

N

FIXTURE CONNECTED TO EMERGENCY AND NORMAL POWER

SECURITY BELL/ALARMB

POWER SUPPLY - WALL, CEILINGPS

HEAT LAMP FIXTURE, RECESSED CEILINGH

SS SOLID STATE, REDUCED VOLTAGE STARTER

RTS/I

(8)

2U DUPLEX RECEPT. W/ TWO USB PORTS (5,2)

PUSHBUTTON SWITCH/PUSH PAD

E

CC CHIME (NEW, EXISTING)

C #C # CHIME/STROBE (NEW, EXISTING) (10)

C # CEILING MOUNTED CHIME/STROBE (10)

DESCRIPTION (MOUNTING)SYMBOL

WALL MOUNTED DATA/VOICE CABINETRK

DATA, VOICE OR COMB. VOICE/DATA OUTLET(S) - STANDARD HEIGHT(1,7)

#X DATA, VOICE OR COMB. VOICE/DATA OUTLET(S) - ABOVE COUNTER (1,7)

DATA, VOICE OR COMB. VOICE/DATA OUTLET(S) (FLOOR, CEILING) (1,7)

W (1)

M MONITOR DATA OUTLET (1 DROP) - STANDARD HEIGHT (1)

(1)

(1)

SOUND SPEAKER, CEILING MOUNTED (RECESSED, SURFACE)SS SS

SOUND SPEAKER, WALL MOUNTEDSS

SECURITY CAMERA - DOME TYPE (WALL, CEILING)

FIRE SPRINKLER BELLF

ENCLOSED CIRCUIT BREAKER {ECB} (EXISTING, NEW) ECB-XX ECB-XX

GENERATOR ANNUNCIATOR PANEL {GAP} (EXISTING, NEW) GAP GAP

ATSA ATSA ATS ANNUNCIATOR PANEL {ATSA} (EXISTING, NEW)

F

PS

SINGLE RECPT. ( NORMAL, EMERG.) - STANDARD HEIGHT (5,6)

DUPLEX RECEPT. ( NORMAL, EMERG.) - STANDARD HEIGHT (5,6)

DUPLEX RECEPT. ( NORMAL, EMERG.) - AC OR HIGH MT. (5,6)

4U DUPLEX RECEPT. AND 4-PORT USB DEVICE IN COMMON BOX (5,6)

FOUR PORT USB DEVICE

GROUNDING INPUT (SINGLE INPUT, MULTIPLE INPUTS)

DOUBLE DUPLEX RECEPT. ( NORMAL, EMERG.) - AC OR HIGH MT.

DOUBLE DUPLEX RECEPT. (NORMAL, EMERG.) - STANDARD HEIGHT

(5,6)

(5,6)

RECESSED CEILING FIXTURE WITH CENTER ELEMENT - 2X4, 2X2, 1X4

S CEILING MOUNTED STROBE (10)#

S SPRING WOUND TIMER SWITCHT

LIM LINE ISOLATION MONITOR (REMOTE)

LIGHT SENSOR

PHOTOCELL

TIME CLOCK

LS

PC

TC

LOW VOLTAGE SWITCHING RELAY PANEL

OS

XX

XX

XX OCCUPANCY SENSOR, CEILING

OCCUPANCY SENSOR, CEILING

OCCUPANCY SENSOR, WALL MOUNT

SXX OCCUPANCY SENSOR, WALL SWITCH

AUTOMATIC LIGHTING CONTROLS

EXTERIOR LIGHTING

LOW VOLTAGE CONTROLLER / RELAYLVC

REMOTE LOCATOR RECIEVERX

STAFF CEILING LOCATORX

F

N N

EQ AUXILIARY 1/4" JACK(S) [EQUIPMENT RECEPTACLE]N

STAFF EMERGENCY

SEN

MINI MASTER STATIONMMN

S # CEILING MOUNTED SPEAKER/STROBE (10)

(3)

(3)

(3)

(3)

(12)

(12)

(12)

(12)

(12)

(12)

(12)

(12)

(12)

(12)

(12)

(12)

(12)

(12)

(12)

(12)

(12)

(12)

(12)

(12)

(12)

(12)

(12)

(12)

(12)

(12)

RECESSED LINEAR / RECESSED CONTINUOUS LINEAR FIXTURE

EL ELECTRIC LOCK

(AS-COM/TELLIGENCE)

EH ELECTRIC HINGE

CELL PHONE SIGNAL BOOST

RECESSED DOWN LIGHT FIXTURE

SCONCE/WALL MOUNT FIXTURE

EXIT SIGN - DOUBLE FACE (CEILING, WALL)

RACEWAYS

JUNCTION & PULL BOX

BLANK JUNCTION BOX

CONDUIT SLEEVES THRU WALL ABOVE ACCESSIBLE CEILING

UNSWITCHED CIRCUIT CONNECTION

CONDUIT STUBBED OR CAPPED

COMBINATION POWER/COMMUNICATION POLE

CABLE TRAY

(1)

CONDUIT RISING UP

CONDUIT DROPPIN DOWN

EXTERIOR RACEWAYS

ELECTRICAL MANHOLE

UGP UNDERGROUND POWER

F UNDERGROUND FIBER

T UNDERGROUND TELEPHONE

A LIGHTNING PROTECTION AIR TERMINAL

L LIGHTNING PROTECTION CABLE

ANTENNA (TELEMETRY)

MISCELLANEOUS HEALTHCARE SYSTEMS

GE WAP (TELEMETRY)

FOOT SWITCH (LIGHTING CONTROL)FT

(2)

(2)

(2)

(2)

(2)

(2)

(2)

(2)

(2)

(2)

(2)

(2)

(2)

(2)

(2)

GF

E

ABBREVIATIONS

A AMPER(S)

A/C AIR CONDITIONING UNIT

ADA AMERICANS WITH DISABILITIES ACT

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AHU AIR HANDLING UNIT

AIC ANTICIPATED INTERRUPTING CURRENT

ALT ALTERNATE

ATS AUTOMATIC TRANSFER SWITCH

AWG AMERICAN WIRE GAUGE

BKR BREAKER

BW BLANKET WARMER

C CONDUIT

CAPS CARD ACCESS POWER SUPPLY

CATV CABLE ANTENNA TELEVISION

CB CIRCUIT BREAKER

CKT CIRCUIT

CM CONSTRUCTION MANAGER

COFF COFFEE MACHINE

CT CURRENT TRANSFORMER

DIST DISTRITBUTION

DO DOOR OPERATOR

EC ELECTRICAL CONTRACTOR

ECB ENCLOSED CIRCUIT BREAKER

EM EMERGENCY

EMT ELECTRICAL METALLIC TUBING

ETR EXISTING TO REMAIN

EWC ELECTRIC WATER COOLER

EX EXISTING

FA FIRE ALARM

FDR FEEDER

FLA FULL LOAD AMPS

FPC FIRE PROTECTION CONTRACTOR

FSC FOOD SERVICE CONTRACTOR

GC GENERAL CONTRACTOR

GEN GENERATOR

GFI,GF GROUND FAULT INTERRUPTER

GND GROUND

HID HIGHT DENSITY DISCHARGE

HP HORSE POWER

HVAC HEATING, VENTILATING, A/C CONTRACTOR

HWR HEAVY WALL RIGID CONDUIT

ICE ICE MACHINE

IMC INTERMEDIATE METALLIC CONDUIT

J-BOX JUNCTION BOX

KEC KITCHEN EQUIPMENT CONTRACTOR

KV KILOVOLTS

KVA KILOVOLT AMPERE(S)

KW KILOWATT(S)

LCP LIGHTING CONTROL PANEL

MCA MAIN CIRCUIT AMPS

MCB MAIN CIRCUIT BREAKER

MCC MOTOR CONTROL CENTER

MCM THOUSAND CIRCULAR MIL(S)

MDP MAIN DISTRIBUTION PANEL

MGAP MEDICAL GAS ALARM PANEL

MLO MAIN LUG ONLY

MTS MANUAL TRANSFER SWITCH

MW MICROWAVE

NAP NITROGEN ALARM PANEL

N.E.C. NATIONAL ELECTRIC CODE

NIC NOT IN CONTRACT

NTS NOT TO SCALE

OH OVERHEAD

PLGC PLUMGING CONTRACTOR

PNL PANEL

PRESS PRESSURE MONITOR

PRI PRIMARY

PTZ PAN, TILT, ZOOM

PVC POLYVINYL CHLORIDE

(R) ROOF

REC RECEPTACLE

REF REFRIGERATOR

RT RAIN TIGHT

SCP SUMP PUMP CONTROL PANEL

SEC SECONDARY

SHPS SECURITY HARDWARE POWER SUPPLY

SPC SPECIAL PURPOSE CONNECTION

SWBD SWITCHBOARD

TC TIME CLOCK

TCC TEMPERATURE CONTROL CONTRACTOR

TCP TEMPERATURE CONTROL PANEL

TCPS TEMPERATURE CONTROL POWER SUPPLY

TELE TELEPHONE

TR TOASTER

TV TELEVISION

TVSS TRANSIENT VOLTAGE SURGE SUPPRESION

TYP TYPICAL

UC UNDERCABINET

UG UNDERGROUND

UH UNIT HEATER

U.N.O. UNLESS NOTED OTHERWISE

UPS UNINTERRUPTED POWER SYSTEM

V. VOLT(S)

VFD VARIABLE FREQUENCY DRIVE

W WATT(S)

WP WEATHERPROOF

XFMR TRANSFORMER

NOTE:

* THIS COMPRISES A COMPLETE LIST OF ITEMS. NOT ALL

ABBREVIATIONS MAY NECESSARILY BE REPRESENTED ON THIS

PROJECT.

DESCRIPTION MOUNTING HEIGHT

LEGEND NOTES:

1. THE ABOVE LIST OF MOUNTING HEIGHTS SHALL BE USED FOR

INSTALLATION OF DEVICES UNLESS NOTED OTHERWISE ON THE

DRAWINGS.

EXACT MOUNTING HEIGHTS OF DEVICES MAY BE SLIGHTLY ADJUSTED IN

THE FIELD TO ACCOMMODATE BLOCK COURSES AND UNIFORMITY OF THE

WALL. REFERENCE DEVICE MOUNTING DETAIL ---/E500.

THE ABOVE ITEMS COMPRISE A COMPLETE LIST AND NOT ALL ITEMS MAY

BE APPLICABLE TO THIS PROJECT.

LIGHT SWITCH

PUSHBUTTON SWITCH

BLANK BOX

45 5/8" CENTERED AFF.

42" CENTERED AFF.

PUSHBUTTON (EMERGENCY STOP) 48" CENTERED AFF.

RECEPTACLES - STANDARD HEIGHT 18" CENTERED AFF.

18" CENTERED AFF. OR AS NOTED ON PLAN

18" CENTERED AFF.DATA/VOICE OUTLET - STANDARD HEIGHT

WALL TELEPHONE 45 5/8" CENTERED AFF.

6" CENTERED ABOVE COUNTERTOP OR

4" CENTERED ABOVE BACKSPLASH

INTERCOM 45 5/8" CENTERED AFF.

CATV OUTLET 18" CENTERED AFF OR AS NOTED ON PLAN

FIRE ALARM PULL STATION 45 5/8" CENTERED AFF.

FIRE ALARM AUDIO/VISUAL DEVICES

FIRE ALARM VISUAL DEVICES

80" AFF TO BOTTOM OF UNIT MINIMUM,

MAXIMUM 96" AFF.

80" AFF TO BOTTOM OF UNIT MINIMUM,

MAXIMUM 96" AFF.

SPEAKER (WALL MOUNTED)

VOLUME CONTROL

MICROPHONE JACK

DIGITAL CLOCK

CLOCK/SPEAKER

WALL CLOCK

CARD READER

80" AFF TO BOTTOM OF DEVICE.

45 5/8" CENTERED AFF.

18" CENTERED AFF. OR AS NOTED ON PLAN

CENTERED 16" TO 8" BELOW CEILING.

CENTERED 18" TO 9" BELOW CEILING.

CENTERED 18" TO 9" BELOW CEILING.

45 5/8" CENTERED AFF.

NURSE CALL DOME LIGHT CENTERED ABOVE DOOR.

NURSE CALL (EM) PULL STATION (TOILET) 48" AFF WITH CORD 6" AFF.

(SHOWER) 84" AFF WITH CORD 6" AFF.

NURSE CALL CODE BLUE 54" CENTERED AFF.

NURSE CALL DUTY STATION 54" CENTERED AFF.

NURSE CALL CALL CORD 54" CENTERED AFF.

NURSE CALL MASTER STATION AT DESK, EXACT LOCATION TO BE FIELD

VERIFIED.

MONITOR DATA OUTLET 18" CENTERED AFF OR AS NOTED ON PLAN

CATV OUTLET W/ PILLOW SPKR CTRL JACK 18" CENTERED AFF OR AS NOTED ON PLAN

OCCUPANCY SENSOR WALL SWITCH 45 5/8" CENTERED AFF.

FAN SPEED SWITCH 45 5/8" CENTERED AFF.

FIRE ALARM REMOTE TEST SWITCH 48" CENTERED AFF.

NURSE CALL STANDARD STATION 54" CENTERED AFF.

NURSE CALL GRAPHICAL STATION 54" CENTERED AFF.

PA HORN WALL SPEAKER 80" AFF TO BOTTOM OF DEVICE. OR AS

NOTED OTHERWISE

RESCUE ASSISTANCE CALL STATION 45 5/8" CENTERED AFF.

DEVICE MOUNTING HEIGHT LEGEND

RECEPTACLES - ABOVE COUNTER

RECEPTACLES - HIGH MOUNT

6" CENTERED ABOVE COUNTER.

4" CENTERED ABOVE BACKSPLASH.

45 5/8" AFF MOUNTED ASIDE OF SINKS;

COORDINATE WITH MIRROR LOCATION.

OR AS NOTED ON PLAN

DATA/VOICE OUTLET - ABOVE COUNTER

2.

3.

ALL M.E.P. TRADES WILL BE REQUIRED TO ATTEND A

COORDINATION MEETING WITH APPROVED DRAWINGS, ALL TRADES

AND THE OWNER PRIOR TO M.E.P. WORK BEGINNING ON SITE.

CORE DRILLING OF NEW FLOORS WITHIN THE ADDITION WILL NOT

BE PERMITTED DUE TO THE STRUCTURAL REBAR REQUIRED.

PROVIDE RIGID CONDUIT SLEEVES PRIOR TO THE FLOORS BEING

POURED. THIS IS APPLICABLE TO POWER, DATA AND SYSTEMS

CONDUITS, FIBER AND CABLING. REFERENCE THE SPECIFICATIONS.

CORE DRILLING OF NEW FLOORS WITHIN THE ADDITION WILL NOT

BE PERMITTED DUE TO THE STRUCTURAL REBAR REQUIRED.

PROVIDE RIGID CONDUIT SLEEVES PRIOR TO THE FLOORS BEING

POURED.

GENERAL PROJECT NOTES:

1.

2.

3.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

321 4 5 6 7 8 9 10

EXPAND PRIMARY CARE

OSCAR G. JOHNSON VA MEDICAL CENTER

325 H STREET,

IRON MOUNTAIN, MI 49801

ARCHITECT/ENGINEER

310 Pine Street | Green Bay, WI 54301 920-432-4865 | www.bernersschober.com

FULLY SPRINKLERED

KEY PLAN

Comm. Number: 5700.16

DECEMBER 4, 2020

585-336

U.S. Department of Veterans Affairs

100% DESIGN SUBMITTAL

Revisions: Date:

CONSULTANT

Architecture | Planning | Interior Design

2224 S. Michigan Ave. | Suite 1400 Chicago, Illinois 60604-2595

(312)-554-1400

65% SUBMITTAL 04/28/2020

ZONE 1

ZONE 2

ZONE 3

ZONE 4

project number: 1180742

95% SUBMITTAL 07/24/2020

100% SUBMITTAL 12/04/2020

B

IM

/V

A G

L H

S E x p a n d

P ri m a ry

C a re /V

A E

L E

C .r v t

/8 /2

:1

:2

A

M

MLL NMP

E001

SYMBOLS & ABBREVATIONS

DWG. 119 OF 147

UGP

UGP

UGP

U G

P

U G

P

UGP

UGP

UGP

UGP U

G

P U

G P

U G

P

U G

P

U G

P

U G

P

E

E

E

E X U

G P

EX UGP

E X

U G

P

E X

U G

P

E X

U G

P

EX UGP

UGP

EX UGP

EX

A E

DISCONNECT, REMOVE

AND SALVAGE POLE & LUMINAIRE

EXISTING TRANSFORMERS

AND SECONDARY FEEDERS

TO REMAIN IN SERVICE

EXISTING METER AND FEEDER INTO THE BUILDING TO REMAIN.

THE ASSOCIATED TRANSFORMER, PRIMARY

AND SECONDARY FEEDERS TO BE REMOVED/RELOCATED

PRIMARY SERVICE TRANSFORMER AND

SERVICE TO BUILDING

TO BE DISCONNECTED/REMOVED

F

BUILDING #3

S1

S2

A D

A D

DISCONNECT/REMOVE

AND SALVAGE POLE &

LUMINAIRE

S2

BUILDING #2

DISCONNECT, REMOVE

AND SALVAGE POLE AND

LUMINAIRE

S2

A E

DISCONNECT, REMOVE

AND SALVAGE POLE AND

LUMINAIRE

A C

EMERGENCY PRIMARY SERVICE

TRANSFORMER AND

SERVICE TO BUILDING

TO BE DISCONNECTED/REMOVED

G

PRIMARY SERVICE

TO TRANSFORMER(S) TO

BE REMOVED/REPLACED

F

SERVICE TRANSFORMER

FOR BUILDING #2

TO REMAIN

EMERGENCY POWER

PRIMARY FROM MANHOLE

TO BUILDING '3' TO BE

REMOVED G

TUNNEL TO BE REMOVED

BY GENERAL TRADE

FIBER/INNERDUCT I

2-3" C. H

EXISTING METER/CAB.

TO REMAIN

EXISTING TO REMAIN

2-EX UGP TO REMAIN

EMERGENCY POWER

MANHOLE TO REMAIN

EMERGENCY POWER

MANHOLE TO REMAIN

EX. UGP TO BUILDING #11

TO REMAIN

EX. UGP

TO REMAIN

2-EX UGP TO BUILDING #2

TO REMAIN

DISCONNECT/REMOVE THE

EXISTING 13.8KV EMERGENCY

POWER FEEDER FROM BUILDING '2'

A D

S2

SERVICE LATERAL

TO BUILDING #2

TO REMAIN

B

EX

DISCONNECT, REMOVE

AND SALVAGE POLE AND

LUMINAIRE

A C

S2

S2J F

K F

L

J

F

F K

EXISTING UG FEEDER

FROM WEST TO REMAIN

PRIMARY SERVICE

TO TRANSFORMER(S) TO

BE REMOVED/REPLACED

F

N

MF

SALVAGE POLE AND LUMINAIRE FOR REUSE. REFERENCE THE

LIGHT FIXTURE SCHEDULE AND NEW WORK SITE PLAN.

MAINTAIN EXISTING POLE/LUMINAIRE IN SERVICE.

SALVAGE THE EXISTING EXTERIOR POLE LIGHT CIRCUIT (IN

SERVICE) FOR REUSE. REMOVE CONDUIT AND WIRING IN WAY OF

NEW CONSTRUCTION.

DISCONNECT AND REMOVE ASSOCIATED CONDUIT AND WIRING

BACK TO THE NEAREST EXISTING POLE LIGHT TO REMAIN.

DISCONNECT AND REMOVE ASSOCIATED CONDUIT AND WIRING

BACK TO SOURCE.

COORDINATE ALL DEMOLITION WORK WITH THE OWNER AND

LOCAL UTILITY CO. ELECTRICAL CONTRACTOR SHALL INCLUDE IN

THEIR BID ALL COSTS ASSOCIATED WITH UTILITY WORK, BOTH

DEMOLITION AND NEW WORK.

THE 13.8KV EMERGENCY POWER PRIMARY FEEDER TO THE

TRANSFORMER OUTSIDE OF BUILDING #3 ORIGINATES WITHIN THE

EMERGENCY POWER SWITCHGEAR WITHIN BUILDING #2. TURN OFF,

LOCK-OUT THE SWITCH AND RELABEL IT AS SPARE. REMOVE THE 4"

CONDUIT AND PRIMARY CONDUCTORS ALL THE WAY TO THE

BUILDING #2 SWITCHGEAR. REMOVE THE ASSOCAITED CONDUIT UP

TO THE POINT WHERE THE GROUND CONSTRUCTION STOPS, OR

WHERE THE CONDUIT IS CONCRETE ENCASED WITH OTHER

FEEDERS TO REMAIN. ABANDON THE REMAINING CONDUIT IN

PLACE WHICH RUNS TO BUILDING #2.

DISCONNECT/REMOVE THE TWO (2) 3" CONDUITS FROM THE

BASEMENT OF BUILDING #3 TO THE MAIN TUNNEL. REMOVE THE

ATS CONTROL WIRING BACK TO SOURCE. REFERENCE THE

BASEMENT DEMOLITION PLAN OF BUILDING #3 FOR ADDITIONAL

INFORMATION.

DISCONNECT/REMOVE THE INNERDUCT/FIBER FROM THE

BASEMENT OF BUILDING #3 TO THE MAIN TUNNEL. COIL UP THE

FIBER AND PLACE IT IN A NEW PULL BOX WITHIN THE TUNNEL.

IDENTIFY BOX AND FIBER PER SPECIFICATIONS.

THE TWO (2) EXISTING UTILITY TRANSFORMERS OUTSIDE OF

BUILDING #1 ARE TO REMAIN IN SERVICE. SHORT PERIOD OUTAGES

WILL BE ALLOWED WHEN SCHEDULED IN ADVANCE WITH THE

OWNER. THE EXISTING PRIMARY FROM THE EAST IS IN WAY OF

NEW CONSTRUCTION AND REQUIRES REMOVAL. THE PRIMARY

FEED FROM THE WEST SHALL REMAIN IN SERVICE.

THE EXISTING UTILITY TRANSFORMER SERVING BUILDING #2 SHALL

REMAIN IN SERVICE. SHORT PERIOD OUTAGES SHALL BE ALLOWED

FOR NEW PRIMARY FEEDER CONNECTIONS. COORDINATE ALL

OUTAGES WITH OWNER.

BUILDING #3 SHALL BE REMOVED IN ITS' ENTIRETY. REFERENCE

SHEET ED103 FOR ADDITONAL INFORMATION.

THE EXISTING SERVICE TRANSFORMER FARTHEST TO THE EAST IS

IN WAY OF NEW ADDITION. .THIS TRANSOFRMER SHALL BE

REPLACED/RELOCATED. THE PRIMARY AND SECONDARY FEEDERS

SHALL BE REVISED. REFERENCE THE NEW WORK SITE PLAN.

DISCONNECT AND REMOVE THE EMERGEENCY POWR SECONDARY

SERVICE.

KEYED PLAN NOTES

(THIS SHEET ONLY)

A

B

C

D

E

F

G

H

I

J

K

L

THE INTENT OF THE PROJECT WILL BE TO HAVE THE ELECTRICAL

SERVICE WORK RELOCATED/COMPLETED FIRST, AS A PART OF

PHASE 1A, ALONG WITH ACCESS TO THE NEW LOADING DOCK.

REFERENCE THE ARCHITECTURAL PHASING PLANS AND

SPECIFICATIONS FOR ADDITIONAL INFORMATION.

GENERAL PLAN NOTES

(THIS SHEET ONLY)

M

N

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

321 4 5 6 7 8 9 10

EXPAND PRIMARY CARE

OSCAR G. JOHNSON VA MEDICAL CENTER

325 H STREET,

IRON MOUNTAIN, MI 49801

ARCHITECT/ENGINEER

310 Pine Street | Green Bay, WI 54301 920-432-4865 | www.bernersschober.com

FULLY SPRINKLERED

Comm. Number: 5700.16

DECEMBER 4, 2020

585-336

U.S. Department of Veterans Affairs

100% DESIGN SUBMITTAL

Revisions: Date:

CONSULTANT

Architecture | Planning | Interior Design

2224 S. Michigan Ave. | Suite 1400 Chicago, Illinois 60604-2595

(312)-554-1400

65% SUBMITTAL 04/28/2020

project number: 1180742

95% SUBMITTAL 07/24/2020

100% SUBMITTAL 12/04/2020

B

IM

/V

A G

L H

S E x p a n d

P ri m a ry

C a re /V

A E

L E

C .r v t

/8 /2

:1

:1

A

M

MLL NMP

EZ101

SITE DEMOLITION

DWG. 120 OF 147

N

1" = 20'-0"EZ101

SITE DEMOLITION PLANF5

UGP UGP

UGP

U G

P

UGP

E

E

E

E X U

G P

EX UGP

E X

U G

P

E X

U G

P

E X

U G

P

EX UGP

UGP

EX UGP

EX

S T OR M R U N A

ST

O

RM

R

UN

A

S TO RM RU

N B

S T O R M R U N B

ST O R M R U N C

ST O R M R U N C

S A N I T A R Y R U N A S A N I T A R Y R U N A

ST O R M R U N D

S T O

RM RU N

D

FFE=1147.78

N O

P A

R K

IN

G

NO PARKING

NO PARKING NO PARKING

N O

P A R

KIN

G

S2

S2

OP1

OP1

OP1

OP1

S1

OP1

OP1

OP1

OP1

OP1

OP1

BUILDING #2

S2

EX

TO EX. SITE

LIGHTING CIRCUIT/

FIXTURES

2-#6 AND #8 GND

IN 1 1/4" C.

EX METER

NEW PRIMARY SERVICE

FROM UTILITY CO.

EX

TRANSFORMER

2-#6 AND #8 GND

IN 1 1/4" C.

EX

2-#6 AND #8 GND

IN 1 1/4" C.

(TYP.) 2

S2

S2 S2

EX MANHOLE

OP22-#6 AND #8 GND

IN 1 1/4" C.

(TYP.)

BUILDING #11

BUILDING #1

NEW ADDITION

2-#6 AND #8 GND

IN 1 1/4" C.

(TYP.)

2-#6 AND #8 GND

IN 1 1/4" C.

2-#6 AND #8 GND

IN 1 1/4" C.

POWERED

GATE W/

CARD READER

(EX CKT FROM PNL EBA)

TO EXISTING EXTERIOR

LIGHTING RELAY/

EX METERS

EX

TRANSFORMERS

TO BUILDING #2

POWERED

GATE W/

CARD READER

EX MANHOLE

EX MANHOLE

EXISTING UG

PRIMARY FROM

THE WEST

NEW UTILITY

TRANSFORMER AND

SECONDARY FEEDERS

1 5

TO BUILDING '11'

COORDINATE WITH OWNER AND LOCAL UTILITY CO. FOR NEW

SERVICE PRIMARY TO REFEED THE SERVICE TRANSFORMERS OF

BUILDINGS #1 & #2. ELECTRICAL CONTRACTOR TO INCLUDE ALL

COSTS ASSOCIATED WITH UTILITY WORK IN THEIR BID. DO NOT

INCLUDE ADDITIONAL CHARGES ASSOCIATED WITH GROUND

FROST. IT IS ASSUMED THAT CONSTRUCTION WILL OCCUR IN

SPRING OR SUMMER.

EXTEND THE EXISTING SITE LIGHTING CIRCUIT SALVAGED FROM

DEMOLITION WORK TO NEW OR SALVAGED FIXTURE(S). PROVIDE

NEW CONDUIT AND WIRING AS REQUIRED/SHOWN.

RECONNECT TO EXISTING DOWNSTREAM CIRCUIT/FIXTURE.

UTILIZE THE EXISTING CONTROLLED, EXTERIOR LIGHTING CIRCUIT

FROM PANEL EBA RELAY/CONTACTOR CABINET LOCATED IN

LOADING DOCK AREA. COORDINATE WITH OWNER FOR EXACT

LOCATION.

COORDINATE WITH UTILITY CO. FOR INSTALLATION OF NEW

TRANSFORMER, PRIMARY AND REVISED SECONDARY FEEDER TO

EXISTING METER.

KEYED PLAN NOTES

(THIS SHEET ONLY)

THE INTENT OF THE PROJECT WILL BE TO HAVE THE ELECTRICAL

SERVICE WORK RELOCATED/COMPLETED FIRST, AS A PART OF

PHASE 1A, ALONG WITH ACCESS TO THE NEW LOADING DOCK.

REFERENCE THE ARCHITECTURAL PHASING PLANS AND

SPECIFICATIONS FOR ADDITIONAL INFORMATION.

GENERAL PLAN NOTES

(THIS SHEET ONLY)

24"

GRADE

NOTE: ANCHOR BOLT AND CONDUIT PROJECTIONS PER

MANUFACTURERS RECOMMENDATIONS

NOTE: PROVIDE

A SPARE

CONDUIT STUB

FROM EACH

END-OF-CIRCUIT

POLE BASE

PROVIDE BOLT COVERS

TRANSITION TO RIGID CONDUIT

1-1/4" PVC CONDUIT

2#6, 1#8 GRND

1/2"x8' COPPER CLAD

GROUND ROD

#4 REBAR @ 9" OC

ROUND CONC. BASE

24"

GRADE

NOTE: ANCHOR BOLT AND CONDUIT PROJECTIONS PER

MANUFACTURERS RECOMMENDATIONS

NOTE: PROVIDE

A SPARE

CONDUIT STUB

FROM EACH

END-OF-CIRCUIT

POLE BASE

PROVIDE BOLT COVERS

TRANSITION TO RIGID CONDUIT

1-1/4" PVC CONDUIT

2#6, 1#8 GRND

1/2"x8' COPPER CLAD

GROUND ROD

#4 REBAR @ 9" OC

ROUND CONC. BASE

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

321 4 5 6 7 8 9 10

EXPAND PRIMARY CARE

OSCAR G. JOHNSON VA MEDICAL CENTER

325 H STREET,

IRON MOUNTAIN, MI 49801

ARCHITECT/ENGINEER

310 Pine Street | Green Bay, WI 54301 920-432-4865 | www.bernersschober.com

FULLY SPRINKLERED

Comm. Number: 5700.16

DECEMBER 4, 2020

585-336

U.S. Department of Veterans Affairs

100% DESIGN SUBMITTAL

Revisions: Date:

CONSULTANT

Architecture | Planning | Interior Design

2224 S. Michigan Ave. | Suite 1400 Chicago, Illinois 60604-2595

(312)-554-1400

65% SUBMITTAL 04/28/2020

project number: 1180742

95% SUBMITTAL 07/24/2020

100% SUBMITTAL 12/04/2020

B

IM

/V

A G

L H

S E x p a n d

P ri m a ry

C a re /V

A E

L E

C .r v t

/8 /2

:1

:3

A

M

MLL NMP

EZ102

SITE NEW WORK PLAN

DWG. 121 OF 147

N

1" = 20'-0"EZ102

SITE NEW WORK PLANF5

NO SCALE

C1

TYPICAL POLE BASE FOR TYPES S1 AND OP1

NO SCALE

E1

TYPICAL POLE BASE FOR TYPES S2 AND OP2

ROOM

PROCEDURE

ALCOVE

TOILET

PATIENT

1267B

WORK RM

NURSE

ROOM

EXAM

ROOM

EXAM

RM

EXAM

WORKER

SOCIAL

RM

EXAM

/CONSULTATION

PT. EDUCATION

RM

DECON

MEDICATION

UTILITY

SOILED

TOILET

PATIENT

RM

TREATMENT

RM

TREATMENT

ROOM

TREATMENT

MEDICATION

/SECURITY RM.

FIRE ALARM

DIABETES

TOILET

PATIENT

LOBBY

ELEVATOR

TOILET

TOILET

PATIENT

CLERKS

RM

EXAM

WORKRM

NURSE

RM

EXAM

ROOM

EXAM

RM

EXAM

DIABETES

SUPPLY

STERILE

ROOM

EXAM

STATION

NURSE

DICTATION

WORKRM

NURSE

RM

EXAM

RM

EXAM

LINEN

CLEAN

HOUSEKEEPING

TOILET

STAFF

TOILET

WOMENS

LAB/EKG

BLOOD DRAW

LAB/EKG

BLOOD DRAW

CLOSET

HSKPG

ELIGIBILITY

ENROLLMENT &

AREA

WAITING

AREA

CLERK

ELECTRICAL

DATA & PHONE

1218A

CONSULTING

1218C

ROOM

EXAM

TOILET

PATIENT

ALCOVE

SCALE

TOILET

MENS

ALCOVE

SCALE

STAIR4

ALCOVE

PYXIS

PASSENGER

ELEVATOR

D-4 D-5

FE FE

BASEMENT ROOF

ROOM

PROCEDURE

ALCOVE

TOILET

PATIENT

1267B

WORK RM

NURSE

ROOM

EXAM

ROOM

EXAM

RM

EXAM

WORKER

SOCIAL

RM

EXAM

/CONSULTATION

PT. EDUCATION

RM

DECON

MEDICATION

UTILITY

SOILED

TOILET

PATIENT

RM

TREATMENT

RM

TREATMENT

ROOM

TREATMENT

MEDICATION

/SECURITY RM.

FIRE ALARM

DIABETES

TOILET

PATIENT

LOBBY

ELEVATOR

TOILET

TOILET

PATIENT

CLERKS

RM

EXAM

WORKRM

NURSE

RM

EXAM

ROOM

EXAM

RM

EXAM

DIABETES

SUPPLY

STERILE

ROOM

EXAM

STATION

NURSE

DICTATION

WORKRM

NURSE

RM

EXAM

RM

EXAM

LINEN

CLEAN

HOUSEKEEPING

TOILET

STAFF

TOILET

WOMENS

LAB/EKG

BLOOD DRAW

LAB/EKG

BLOOD DRAW

CLOSET

HSKPG

ELIGIBILITY

ENROLLMENT &

AREA

WAITING

AREA

CLERK

ELECTRICAL

DATA & PHONE

1218A

CONSULTING

1218C

ROOM

EXAM

TOILET

PATIENT

ALCOVE

SCALE

TOILET

MENS

ALCOVE

SCALE

STAIR4

ALCOVE

PYXIS

PASSENGER

ELEVATOR

D-4 D-5

FE FE

BASEMENT ROOF

N

N N

N

N

N

OS OS

OS

OSS

S

N

SP

N N

SP

SP

N

N

S

S

S

S N

SP S

B

B B

WP

OS

D

D

D D

D

D

D

OPC NURSE CALL PNL

FIRE ALARM TRANSPONDER PNL

SECURITY SYSTEM

L1D

L1C

CR1A

ED NURSE CALL PNLFIRE ALARM AUX PNL

LIGHTING CONTROL "LCP1B"

LIGHTING CONTROL "LCP1A"

STACKED PNLS

SECURITY SYSTEM

CONTROL PANEL

CONTROL PANEL

M M1

L1A(R)

L1A(L)

CR1EQ1LS1

E1S

SECURITY SYSTEM

CONTROL PANEL

TOILET

1224A

ROOM

COAT

OFFICE

PHARMACY

DATA

VESTIBULE

STAIR3

LDRY

CHUT

TOILET

1224A

ROOM

COAT

OFFICE

PHARMACY

DATA

VESTIBULE

STAIR3

LDRY

CHUT

FS

TS

E1C-A

D H

B

D B

B

D

K

K

B

B

C

B

K

DC

A

A

B

B

B

K

K

D

B

K

K

B

E E

E E E

E

E

E

E

E

E

FAN

F

EX START/STOP

STATION TO REMAIN

F

F

MULTIPLE CONDUITS

IN WAY OF NEW

CONSTRUCTION

EX GAS DETECTION

SYSTEM PANELS

TO REMAIN

F

G

INFRA-RED

HEATER

CDE

NURSE

MANAGER

CLINICAL

PHARMACIST

MH

PSYCHOLOGIST

MH SOCIAL

WORKER

NURSE

WORKROOM

1271 EXAM

OFFICE

E

I

I

S3

S3

S3

S3 S3

E

S3 S4 S4

S4 S4

S3

S3

S3

S3

A

S3

S4

A

A

S3

E

E E

E

E

E

E

E

AMBULANCE

GARAGE

BREAK ROOM

/ LOCKERS

STAFF TOILET

1340A

EXAM

ALL ELECTRICAL EQUIPMENT/FIXTURES AND DEVICES SHOWN ON

THE DEMOLITION PLAN ARE INTENDED TO BE DISCONNECTED AND

REMOVED UNLESS NOTED OTHERWISE. ELECTRICAL ITEMS

REMOVED AND NOT RELOCATED REMAIN THE PROPERTY OF THE

OWNER. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE

DISPOSAL OF ANY MATERIAL THE OWNER DOES NOT WANT TO

REUSE OR RETAIN.

THE DRAWINGS ARE INTENDED TO INDICATE THE SCOPE OF WORK

REQUIRED AND DO NOT INDICATE EVERY J-BOX, CONDUIT, OR WIRE

THAT MUST BE REMOVED. THE CONTRACTOR SHALL VISIT THE SITE

TO DETERMINE THE SCOPE OF DEMOLITION NECESSARY TO

ACCOMMODATE THE ELECTRICAL WORK. REFER TO SPECS FOR

ADDITIONAL REQUIREMENTS.

GC SHALL REMOVE AND REPLACE ALL CEILING TILES AS REQUIRED

FOR FOR THE EXECUTION OF ELECTRICAL WORK OUTSIDE THE

LIMITS OF CONSTRUCTION. DAMAGED TILES SHALL BE REPLACED

BY THE GC WITH IDENTICAL MATERIAL.

EC TO RE-SUPPORT EXISTING CONDUITS TO REMAIN PER N.E.C. AS

REQUIRED. RE-SUPPORT EXISTING COMMUNICATION CABLING TO

REMAIN PER TIA/EIA STANDARDS AS REQUIRED.

DISCONNECT AND REMOVE ANY BOXES, CONDUIT, OR RACEWAY

DETERMINED TO BE ABANDONED THAT IS EXPOSED BY

DEMOLITION.

WHERE CONDUIT RUN IS EXPOSED, ALL ASSOCIATED SUPPORTS,

HANGERS, CLAMPS, ETC. SHALL ALSO BE REMOVED. WHERE

CONDUIT IS RUN IN CONCRETE SLAB, CUT OFF FLUSH WITH

CONCRETE, PULL OUT WIRE AND PLUG THE OPENING AS REQUIRED

BY FIRE RATING.

WHERE ELECTRICAL DEVICES (I.E. LIGHTS, RECEPTACLES,

SWITCHES, ETC.) ARE BEING REMOVED; ALL ASSOCIATED WIRE AND

CONDUIT BACK TO THE PANELBOARD OR FEEDER JUNCTION BOX

SERVING THE DEVICE SHALL BE REMOVED. WHERE WALLS ARE

BEING REMOVED; ALL CONDUIT SHALL BE REMOVED. WHERE WALLS

REMAIN; CONDUIT IS ALLOWED TO REMAIN IN WALL WHEN NOT

CONFLICTING WITH NEW DEVICE(S), BUT SHALL BE REMOVED

ABOVE CEILING BACK TO THE PANELBOARD.

DEMOLITION NOTES

1.

2.

3.

4.

5.

6.

7.

DISCONNECT AND REMOVE EXISTING LIGHT FIXTURE(S). SALVAGE

EXISTING CIRCUIT(S) FOR REUSE. REFERENCE THE LIGHTING PLAN.

DISCONNECT AND REMOVE EXISTING DEVICE(S). SALVAGE

EXISTING CIRCUIT(S) FOR REUSE. REFERENCE THE POWER PLAN.

TEMPORARILY SUPPORT EXISTING DEVICE(S) UNTIL NEW CEILING

IS INSTALLED. RE-INSTALL DEVICE(S) IN NEW CEILING. REFERENCE

THE SYSTEMS PLAN.

DISCONNECT AND REMOVE EXISTING DEVICE(S). TURN OVER TO

OWNER.

THE EXISTING CEILING TILES/GRID WITHIN THE AREAS NOTED WILL

BE TEMPORARILY REMOVED FOR MECHANICAL WORK. THE E.C.

SHALL TEMPORARILY SUPPORT OR REMOVE EXISTING LIGHT

FIXTURES AND CEILING DEVICES AS REQUIRED. REINSTALL

FIXTURES AND CEILING DEVICES AT THE COMPLETION OF

MECHANICAL WORK. COORDINATE WITH G.C.

DISCONNECT EXISTING GARAGE EXHAUST FAN AND GAS

DETECTION SYSTEM. SALVAGE CIRCUITS FOR REUSE/RELOCATION.

COORDINATE WITH TEMPERATURE CONTROLS CONTRACTOR FOR

ELECTRICAL WORK REQUIREMENTS. REFERENCE THE FIRST FLOOR

POWER PLAN.

DISCONNECT EXISTING HEATER CIRCUIT AND SALVAGE CIRCUIT

FOR REUSE/RELOCATION. REFERENCE THE FIRST FLOOR POWER

PLAN.

DISCONNECT/REMOVE EXISTING CAMERA AND ASSOCIATED

CONDUIT/CABLING BACK TO SOURCE. SALVAGE THE CAMERA FOR

RELOCATION/REINSTALLATION. REFERENCE THE FIRST FLOOR

SYSTEMS PLAN.

REROUTE/REVISE SIX (6) EXISTING 3/4" CONDUITS WITH #12

CONDUCTORS IN WAY OF NEW DUCTWORK PENERTRATION.

COORDINATE WITH HVAC CONTRACTOR. PROVIDE SPLICE BOX(ES),

CONDUIT AND WIRING AS REQUIRED.

DISCONNECT THE FLOW AND TAMPER SWITCH AT STAIR-3.

SALVAGE THE CONDUIT AND WIRING FOR REUSE AT SAME

LOCATION.

DISCONNECT, REMOVE AND SALVAGE THE FIXTURE(S) FOR REUSE.

SALVAGE THE CIRCUIT FOR REUSE. REEFERENCE THE NEW WORK

LIGHTING PLANS AND LIGHT FIXTURE SCHEDULE. TURN OVER

UNUSED FIXTURE(S) TO OWNER.

KEYED PLAN NOTES

(THIS SHEET ONLY)

A

B

C

D

E

F

G

H

I

J

K

J

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

321 4 5 6 7 8 9 10

EXPAND PRIMARY CARE

OSCAR G. JOHNSON VA MEDICAL CENTER

325 H STREET,

IRON MOUNTAIN, MI 49801

ARCHITECT/ENGINEER

310 Pine Street | Green Bay, WI 54301 920-432-4865 | www.bernersschober.com

FULLY SPRINKLERED

KEY PLAN

Comm. Number: 5700.16

DECEMBER 4, 2020

585-336

U.S. Department of Veterans Affairs

100% DESIGN SUBMITTAL

Revisions: Date:

CONSULTANT

Architecture | Planning | Interior Design

2224 S. Michigan Ave. | Suite 1400 Chicago, Illinois 60604-2595

(312)-554-1400

65% SUBMITTAL 04/28/2020

ZONE 1

ZONE 2

ZONE 3

ZONE 4

project number: 1180742

95% SUBMITTAL 07/24/2020

100% SUBMITTAL 12/04/2020

B

IM

/V

A G

L H

S E x p a n d

P ri m a ry

C a re /V

A E

L E

C .r v t

/8 /2

:1

:2

A

M

MLL NMP

ED101

FIRST FLOOR DEMOLITION PLAN

DWG. 122 OF 147

N

1/8" = 1'-0"ED101

FIRST FLOOR DEMOLITION PLANF3

4'0 8' 12'

N

1/8" = 1'-0"ED101

PRTIAL FIRST FLOOR DEMOLITION PLANB5

4'0 8' 12'

MECHANICAL

TRAINING ROOM

NURSE EDUCATION

2ND FLOOR ROOF

S

DS

GF/RT

TCP

P-18 P-20

P-19 P-21

P-5

EF-67

SP

NMo

SP

FIRST FLOOR ROOF

NEUROLOGY

EXAM RM.

CHASE

SP

N N N

NN

N

N

OFFICE

SOCIAL

WORKER

2335A

PATIENT

TOILET

CHEMOTHERAPY

MENTAL HEALTH

EXAM

LANE

ROOM

TELE-HEALTH

OFFICE

CORRIDOR

STAFF

TOILET

SUB-WAIT

AREA

WOMENS

HEALTH EXAM

TOILET

WOMENS

HEALTH EXAM

WOMENS

HEALTH EXAM

WOMENS

HEALTH EXAM

WOMENS

HEALTH EXAM

FAMILY

LOUNGE

2338A

FAMILY

RESTROOM

ONOCOLOGY

EXAM/OFFICE

ONOCOLOGY

EXAM/PROC.

SOILED

LINEN

CORRIDOR

SA

ROOM

TECH. WORK

CONTROL

CT SCAN

TOILET

PT.

CHUTE

LAUNDRY

UTILITY

CORRIDOR

2230P

2252P

CORRIDOR

STAIR 3

UP

DN

MECH

CHASE

FIRST FLOOR ROOF

FS TS

ROOM

TECH. WORK

CONTROL

CT SCAN

TOILET

PT.

CHUTE

LAUNDRY

UTILITY

CORRIDOR

2230P

2252P

CORRIDOR

A

D

B

C

124 3 2.7 1.57

A.3

E

F

H H

H H

G G

A

D

B

C

123 2.7 1.5 0.5

A.3

B.0

SUB-WAIT

AREA

A A

B C

D

DD

D

S3

S3

S3

D

D D D

EXAM

ALL ELECTRICAL EQUIPMENT/FIXTURES AND DEVICES SHOWN ON

THE DEMOLITION PLAN ARE INTENDED TO BE DISCONNECTED AND

REMOVED UNLESS NOTED OTHERWISE. ELECTRICAL ITEMS

REMOVED AND NOT RELOCATED REMAIN THE PROPERTY OF THE

OWNER. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE

DISPOSAL OF ANY MATERIAL THE OWNER DOES NOT WANT TO

REUSE OR RETAIN.

THE DRAWINGS ARE INTENDED TO INDICATE THE SCOPE OF WORK

REQUIRED AND DO NOT INDICATE EVERY J-BOX, CONDUIT, OR WIRE

THAT MUST BE REMOVED. THE CONTRACTOR SHALL VISIT THE SITE

TO DETERMINE THE SCOPE OF DEMOLITION NECESSARY TO

ACCOMMODATE THE ELECTRICAL WORK. REFER TO SPECS FOR

ADDITIONAL REQUIREMENTS.

GC SHALL REMOVE AND REPLACE ALL CEILING TILES AS REQUIRED

FOR FOR THE EXECUTION OF ELECTRICAL WORK OUTSIDE THE

LIMITS OF CONSTRUCTION. DAMAGED TILES SHALL BE REPLACED

BY THE GC WITH IDENTICAL MATERIAL.

EC TO RE-SUPPORT EXISTING CONDUITS TO REMAIN PER N.E.C. AS

REQUIRED. RE-SUPPORT EXISTING COMMUNICATION CABLING TO

REMAIN PER TIA/EIA STANDARDS AS REQUIRED.

DISCONNECT AND REMOVE ANY BOXES, CONDUIT, OR RACEWAY

DETERMINED TO BE ABANDONED THAT IS EXPOSED BY

DEMOLITION.

WHERE CONDUIT RUN IS EXPOSED, ALL ASSOCIATED SUPPORTS,

HANGERS, CLAMPS, ETC. SHALL ALSO BE REMOVED. WHERE

CONDUIT IS RUN IN CONCRETE SLAB, CUT OFF FLUSH WITH

CONCRETE, PULL OUT WIRE AND PLUG THE OPENING AS REQUIRED

BY FIRE RATING.

WHERE ELECTRICAL DEVICES (I.E. LIGHTS, RECEPTACLES,

SWITCHES, ETC.) ARE BEING REMOVED; ALL ASSOCIATED WIRE AND

CONDUIT BACK TO THE PANELBOARD OR FEEDER JUNCTION BOX

SERVING THE DEVICE SHALL BE REMOVED. WHERE WALLS ARE

BEING REMOVED; ALL CONDUIT SHALL BE REMOVED. WHERE WALLS

REMAIN; CONDUIT IS ALLOWED TO REMAIN IN WALL WHEN NOT

CONFLICTING WITH NEW DEVICE(S), BUT SHALL BE REMOVED

ABOVE CEILING BACK TO THE PANELBOARD.

DEMOLITION NOTES

1.

2.

3.

4.

5.

6.

7.

DISCONNECT, REMOVE AND SALVAGE THE FIXTURE(S) FOR REUSE.

SALVAGE THE CIRCUIT FOR REUSE. REEFERENCE THE NEW WORK

LIGHTING PLANS AND LIGHT FIXTURE SCHEDULE. TURN OVER

UNUSED FIXTURE(S) TO OWNER.

DISCONNECT AND REMOVE EXISTING DEVICE(S). SALVAGE

EXISTING CIRCUIT(S) FOR REUSE. REFERENCE THE POWER PLAN.

TEMPORARILY SUPPORT EXISTING DEVICE(S) UNTIL NEW CEILING

IS INSTALLED. RE-INSTALL DEVICE(S) IN NEW CEILING. REFERENCE

THE SYSTEMS PLAN.

THE EXISTING CEILING TILES/GRID WITHIN THE AREAS NOTED WILL

BE TEMPORARILY REMOVED FOR MECHANICAL WORK. THE E.C.

SHALL TEMPORARILY SUPPORT OR REMOVE EXISTING LIGHT

FIXTURES AND CEILING DEVICES AS REQUIRED. REINSTALL

FIXTURES AND CEILING DEVICES AT THE COMPLETION OF

MECHANICAL WORK. COORDINATE WITH G.C.

DISCONNECT EXISTING TEMPERATURE CONTROL PANEL. SALVAGE

THE EXISTING CIRCUIT FOR EXTENSION TO NEW LOCATION. DEMO

ANY DATA CABLING BACK TO SOURCE. REFERENCE THE

PENTHOUSE POWER/SYSTEMS PLAN.

DISCONNECT/REMOVE EXISTING DEVICE IN WAY OF NEW

CONSTRUCTION. SALVAGE THE DEVICE FOR

RELOCATION/REINSTALLATION. REFERENCE THE PENTHOUSE

POWER/SYSTEMS PLAN.

DISCONNECT/REMOVE DEVICE AND ASSOCIATED CONDUIT AND

WIRING. MAINTAIN SERVICE TO EXISTING DEVICES UP OR DOWN

STREAM.

DISCONNECT EXISTING MOTORS/PUMPS AND REMOVE ASSOCIATED

STARTERS/DISCONNECTS. SALVAGE THE CONDUIT AND WIRING

FOR EXTENSION TO NEW MOTORS. TURN THE COMBINATION

STARTERS OVER TO OWNER.

DISCONNECT THE FLOW AND TAMPER SWITCH AT STAIR-3.

SALVAGE THE CONDUIT AND WIRING FOR REUSE AT SAME

LOCATION.

KEYED PLAN NOTES

(THIS SHEET ONLY)

A

B

C

D

E

F

G

H

I

82825

E

F

I

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

321 4 5 6 7 8 9 10

EXPAND PRIMARY CARE

OSCAR G. JOHNSON VA MEDICAL CENTER

325 H STREET,

IRON MOUNTAIN, MI 49801

ARCHITECT/ENGINEER

310 Pine Street | Green Bay, WI 54301 920-432-4865 | www.bernersschober.com

FULLY SPRINKLERED

KEY PLAN

Comm. Number: 5700.16

DECEMBER 4, 2020

585-336

U.S. Department of Veterans Affairs

100% DESIGN SUBMITTAL

Revisions: Date:

CONSULTANT

Architecture | Planning | Interior Design

2224 S. Michigan Ave. | Suite 1400 Chicago, Illinois 60604-2595

(312)-554-1400

65% SUBMITTAL 04/28/2020

ZONE 1

ZONE 2

ZONE 3

ZONE 4

project number: 1180742

95% SUBMITTAL 07/24/2020

100% SUBMITTAL 12/04/2020

B

IM

/V

A G

L H

S E x p a n d

P ri m a ry

C a re /V

A E

L E

C .r v t

/8 /2

:1

:4

A

M

MLL NMP

ED102

2ND FLOOR & PENTHOUSE

DEMOLITION PLAN

DWG. 123 OF 147

N

1/8" = 1'-0"ED102

PENTHOUSE DEMOLITION PLANF7

N

1/8" = 1'-0"ED102

SECOND FLOOR DEMOLITION PLANF3

4'0 8' 12'4'0 8' 12'

N

1/8" = 1'-0"ED102

SECOND FLOOR DEMOLITION PLAN - STAIR #3C4

ECB

ATS

ECB TVSS

FIBER BOX

IDF CAB.

PATCH

PANEL

PANEL

PANEL

PANEL

2-3" C.

FIBER

TO MAIN TUNNEL

(SEE SITE PLAN - DEMOLITION)

PHONE/COMM

BOARD

POWER

LOGIC

METERING

PULL BOX

2-3" C.

FIBER/INNERDUCT

SOCIAL ROOM

BED

ROOM

BED

ROOMBED

ROOM

BED

ROOM

BED

ROOM

BED

ROOM

BED

ROOM

BED

ROOM

BED

ROOM

BED

ROOM

LINEN

TOILET

AND BATH

CORRIDOR

LOBBY

PHONE

JAN

STAIR

BS

S

S

A

A

CC

A

A

A

B

C

B

BUILDING #3 IS BEING DEMOLISHED/REMOVED IN ITS ENTIRETY.

REFERENCE THE DEMOLITION SITE PLAN FOR ADDITIONAL

INFORMATION.

SALVAGE AND TURN OVER TO OWNER ALL EQUIPMENT NOTED AS

SUCH ON THESE PLANS. REMOVE ALL OTHER FIXTURES, DEVICES,

EQUIPMENT AND ASSOCIATED CONDUIT AND WIRING (SHOWN OR

NOT SHOWN) FROM SITE.

GENERAL DEMOLITION NOTES

1.

2.

3.

DISCONNECT/REMOVE AND SALVAGE EXISTING EQUIPMENT AND

TURN OVER TO OWNER.

DISCONNECT/REMOVE 6-STRAND FIBER FROM BUILDING #3. PULL

FIBER BACK TO MAIN TUNNEL AND COIL UP WITHIN A NEW

12"x12"x4" PULL BOX. IDENTIFY FIBER AND BOX PER

SPECIFICATIONS.

DISCONNECT/REMOVE PULL BOX AND TWO 3" CONDUITS BACK TO

MAIN TUNNEL BETWEEN BUILDING #1 & BUILDING #2. REMOVE ALL

ATS CONTROL WIRING BETWEEN BUILDING #2 AND BUILDING #3.

KEYED PLAN NOTES

(THIS SHEET ONLY)

A

B

C

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

321 4 5 6 7 8 9 10

EXPAND PRIMARY CARE

OSCAR G. JOHNSON VA MEDICAL CENTER

325 H STREET,

IRON MOUNTAIN, MI 49801

ARCHITECT/ENGINEER

310 Pine Street | Green Bay, WI 54301 920-432-4865 | www.bernersschober.com

FULLY SPRINKLERED

KEY PLAN

Comm. Number: 5700.16

DECEMBER 4, 2020

585-336

U.S. Department of Veterans Affairs

100% DESIGN SUBMITTAL

Revisions: Date:

CONSULTANT

Architecture | Planning | Interior Design

2224 S. Michigan Ave. | Suite 1400 Chicago, Illinois 60604-2595

(312)-554-1400

65% SUBMITTAL 04/28/2020

ZONE 1

ZONE 2

ZONE 3

ZONE 4

project number: 1180742

95% SUBMITTAL 07/24/2020

100% SUBMITTAL 12/04/2020

B

IM

/V

A G

L H

S E x p a n d

P ri m a ry

C a re /V

A E

L E

C .r v t

/8 /2

:1

:3

A

M

MLL NMP

ED103

BUILDING #3 DEMOLITION PLANS

DWG. 124 OF 147

N

1/8" = 1'-0"ED103

BUILDING #3 - BASEMENT DEMOLITION PLANF5

N

1/8" = 1'-0"ED103

BUILDING #3 - FIRST FLOOR DEMOLITION PLAND5

A

122.7 0.01.5 0.5

D.0

C.0

A.3

B.0

STAIR

ST-1

PIPE

BASEMENT

B001

E 3

WL

WL

E

KL KL KL KL

KLKL

KLKL

KLKL

KL

2U 2U 2U 2U

2U 2U 2U

2U

KL KL

TO FIXTURES

ABOVE

LS2A2- 3

NPCA- 1

LS2A2- 8

VIA PHOTO-CELL

AND T.C. #1

OC

REFERENCE THE EXTERIOR LIGHTING CONTROL DETAIL.

UTILIZE A 20A/1P BREAKER IN NEW LIFE SAFETY LS2A2 (LOCATED

IN ROOM 1415) TO FEED NEW STAIR WAY LIGHTING.

KEYED PLAN NOTES

(THIS SHEET ONLY)

UTILIZE A 20A/1P BREAKER IN NEW LIFE SAFETY PANEL LS2A2

(LOCATED IN ROOM 1415) (CKT #3) TO FEED ALL EMERGENCY

LIGHTING FIXTURES AND EXIT SIGNS WITHIN THE PIPE BASEMENT

AND STAIT ST-1.

REFERENCE THE ARCHITECTURAL PHASING PLANS AND

SPECIFICATIONS.

GENERAL NOTES

(THIS SHEET ONLY)

1.

2.

0.0

D.0

WL

WL E

TO FIXTURES

ABOVE

TO FIXTURES

BELOW

LS2A2- 8

VIA PHOTO-CELL

AND T.C. #1

OC

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

321 4 5 6 7 8 9 10

EXPAND PRIMARY CARE

OSCAR G. JOHNSON VA MEDICAL CENTER

325 H STREET,

IRON MOUNTAIN, MI 49801

ARCHITECT/ENGINEER

310 Pine Street | Green Bay, WI 54301 920-432-4865 | www.bernersschober.com

FULLY SPRINKLERED

KEY PLAN

Comm. Number: 5700.16

DECEMBER 4, 2020

585-336

U.S. Department of Veterans Affairs

100% DESIGN SUBMITTAL

Revisions: Date:

CONSULTANT

Architecture | Planning | Interior Design

2224 S. Michigan Ave. | Suite 1400 Chicago, Illinois 60604-2595

(312)-554-1400

65% SUBMITTAL 04/28/2020

ZONE 1

ZONE 2

ZONE 3

ZONE 4

project number: 1180742

95% SUBMITTAL 07/24/2020

100% SUBMITTAL 12/04/2020

B

IM

/V

A G

L H

S E x p a n d

P ri m a ry

C a re /V

A E

L E

C .r v t

/8 /2

:1

:2

A

M

MLL NMP

EL101

BASEMENT & EGRESS LANDING

LIGHTING PLANS

DWG. 125 OF 147

N

1/8" = 1'-0"EL101

BASEMENT LIGHTING PLANF7

N

1/8" = 1'-0"EL101

EGRESS LANDING LIGHTING PLANF5

4'0 8' 12' 4'0 8' 12'

ALCOVE

TOILET

PATIENT

1267B

WORK RM

NURSE

ROOM

EXAM

ROOM

EXAM

RM

EXAM

WORKER

SOCIAL

RM

EXAM

/CONSULTATION

PT. EDUCATION

RM

DECON

MEDICATION

UTILITY

SOILED

TOILET

PATIENT

RM

TREATMENT

RM

TREATMENT

MEDICATION

/SECURITY RM.

FIRE ALARM

DIABETES

TOILET

PATIENT

LOBBY

ELEVATOR

TOILET

PATIENT

CLERKS

RM

EXAM

WORKRM

NURSE

RM

EXAM

ROOM

EXAM

RM

EXAM

DIABETES

SUPPLY

STERILE

ROOM

EXAM

STATION

NURSE

DICTATION

WORKRM

NURSE

RM

EXAM

RM

EXAM

LINEN

CLEAN

HOUSEKEEPING

TOILET

STAFF

TOILET

WOMENS

LAB/EKG

BLOOD DRAW

ELIGIBILITY

ENROLLMENT &

AREA

WAITING

AREA

CLERK

ELECTRICAL

ROOM

EXAM

TOILET

PATIENT

ALCOVE

SCALE

TOILET

MENS

ALCOVE

SCALE

STAIR4

ALCOVE

PYXIS

PASSENGER

ELEVATOR

DNUP

MECH

SHAFT

FE FE

BASEMENT ROOF

A

D

B

C

124 3

CONNECTION

NURSE

WORKROOM

MENTAL

HEALTH

GROUP ROOM

MENTAL

HEALTH

PSYCHOLOGIST

MENTAL

HEALTH

SOCIAL

WORKER

ALCOVE

CLINICAL

PHARM

MENTAL

HEALTH

OFFICE

CLINICAL

PHARM

CLINICAL

PHARM

H/W ALCOVE

TRIAGE

CORRIDOR

SUB-WAIT

EXAM

EXAM

EXAM

EXAM

CLEAN

UTILITY

SOILED

HOLDING

C O

R R

ID

O

R

CORRIDOR

IT ROOM (VA)

HSKP.

PATIENT

TOILET

PATIENT

TOILET

CONFERENCE

ROOM

HALLWAY

TEAMLET

WORKSTATIONS

MEDICAL

EQUIPMENT

STORAGE

REFRESHMENT

ALCOVE

EXAM

EXAM

C O

R R

ID

O

R

ELECTRICAL

ROOM

7 1

1 1

2.7 0.01.5 0.57

2625242321

D.0

C.0

A.3

B.0

ST-1

2U

2U VL2

VL2

VL2

VL2

VL2

G2 G2

G2G2

G2 G2

G2G2

G2

G2

E

NPCA

NPC

KL

KL

KL KL KLAF2

OSOS OS

VF VF

D1 D1

E VL2 E1 VL2 VL2 VL2 VL2

VL2 VL2

E

VL2

E

E1

VL2

VL2

G2 G2

G2G2

G2 G2

VL2

VL2

VL2

E G2

E

VL2

VL2

VL2

VL2

VL2

VL2 VL2

VL2 VL2

D3

D3

D3

D3

D3

3 3

D3

VL2 VL2

VL2VL2 VL2 VL2

VL2VL2 VL2 VL2

VL2VL2

VL2 VL2

VL2VL2

OS OS

AL2

AL2

AF2

AF2

D

3E

VL2

E

VL2

VL2 VL2

VL2

E E

D1

VF

OS

G2

E E1

VL2

VL2

VL2

VL2

AL

AL

2U 2D

2D

L16 L16 L16 L16

VL2

VL2

D

S3 S3 S3

D

D

2U

D

D

D

G2

G2 G2

G2 1D

1D G2 G2

G2G2

G2 G2

G2G2G2

2U

1D

D

D 1D

S3

S3

WL

G2

G2 VL2

VL2

E

E

D

D

NPCA- 3

LS2A2

CR2-UPS-2- 1

NPCA- 5

NPCA- 7

EX CKT

EX CKT

EX CKT

EX CKT

EX CKT

WL

TO FIXTURES

ABOVE

TO FIXTURES

BELOW

#1

PC

S3

S3

S3S3

S3 S3

S3 S3

BREAK

ROOM/

LOCKERS

1340A

EXAM ROOM

AMBULANCE

GARAGE

EX

EX

S5

S5

S3

OS

OS

EX

DD3

EX

OSEX

EX

S4

S3 S3

S4

S3

EX

EX S6

S6

S6 S6 S6

S6S6S6

EX

EX

EXEXEXEX

EXISTING LIGHT FIXTURE(S) AND LIGHT SWITCH(ES) TO REMAIN IN

SERVICE. NO CHANGE.

CUT NEW BACK BOX INTO EXISTING WALL. FISH WALL CAVITY WITH

CONDUIT TO FEED NEW DEVICE(S).

RE-INSTALL DEVICE SALVAGED FROM DEMOLITION.

UTILIZE EXISTING LIGHTING CIRCUIT SALVAGED FROM DEMOLITION

TO FEED NEW FIXTURE(S).

EXTEND CONDUIT AND WIRING TO EXISTING CORRIDOR LIGHT

FIXTURE AND CONNECT.

UTILIZE EXISTING BACK BOX TO PROVIDE NEW SWITCH. PROVIDE

NEW WIRING AS REQUIRED.

REINSTALL LIGHTS AND CEILING DEVICES SALVAGED FROM

DEMOLITION WORK.

PROVIDE TIME CLOCK NEAR PANEL LS2A2 AND PHOTO CELL NEAR

ROOF LINE. REFERENCE THE LIGHTING CONTROL DETAIL ON SHEET

E502.

KEYED PLAN NOTES

(THIS SHEET ONLY)

UTILIZE A 20A/1P BREAKER IN NEW LIFE SAFETY PANEL LS2A2

(LOCATED IN ROOM 1415) (CKT #5) TO FEED ALL EMERGENCY

LIGHTING FIXTURES AND EXIT SIGNS ON THIS FLOOR.

REFERENCE THE ARCHITECTURAL PHASING PLANS AND

SPECIFICATIONS.

GENERAL NOTES

(THIS SHEET ONLY)

1.

2.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

321 4 5 6 7 8 9 10

EXPAND PRIMARY CARE

OSCAR G. JOHNSON VA MEDICAL CENTER

325 H STREET,

IRON MOUNTAIN, MI 49801

ARCHITECT/ENGINEER

310 Pine Street | Green Bay, WI 54301 920-432-4865 | www.bernersschober.com

FULLY SPRINKLERED

KEY PLAN

Comm. Number: 5700.16

DECEMBER 4, 2020

585-336

U.S. Department of Veterans Affairs

100% DESIGN SUBMITTAL

Revisions: Date:

CONSULTANT

Architecture | Planning | Interior Design

2224 S. Michigan Ave. | Suite 1400 Chicago, Illinois 60604-2595

(312)-554-1400

65% SUBMITTAL 04/28/2020

ZONE 1

ZONE 2

ZONE 3

ZONE 4

project number: 1180742

95% SUBMITTAL 07/24/2020

100% SUBMITTAL 12/04/2020

B

IM

/V

A G

L H

S E x p a n d

P ri m a ry

C a re /V

A E

L E

C .r v t

/8 /2

:1

:4

A

M

MLL NMP

EL102

FIRST FLOOR LIGHTING PLAN

DWG. 126 OF 147

N

1/8" = 1'-0"EL102

FIRST FLOOR LIGHTING PLANF3

CT SCAN

MEDICINE

NUCLEAR

ACCUPUNCTURE

EXAM ROOM

EYE PRE-

TREATMENT

EYE PRE-

TREATMENT

OFFICE

STERILE

SUPPLY

CLEAN

SUPPLY

SOCIAL

WORKER

2335A

PATIENT

TOILET

CHEMOTHERAPY

MENTAL HEALTH

EXAM

ELECTRICAL

ROOM

LANE

ROOM

LANE

ROOM

LANE

ROOM

EYE

INSTRUMENTS

TELE-HEALTH

EXAM RM

TELE-HEALTH

EXAM RM

TELE-HEALTH

OFFICE

MENS

TOILET

WORK AREA

CORRIDOR

STAFF

TOILET

SUB-WAIT

AREA

WOMENS

HEALTH EXAM

TOILET

WOMENS

HEALTH EXAM

WOMENS

HEALTH EXAM

WOMENS

HEALTH EXAM

WOMENS

HEALTH EXAM

FAMILY

LOUNGE

2338A

FAMILY

RESTROOM

ONOCOLOGY

EXAM/OFFICE

ONOCOLOGY

EXAM/PROC.

SOILED

LINEN

CORRIDOR

M-2A

L1A-2A-B

LS-2A

PAGING AMP.

SIM

PLE

X

TC

P

LS-5

NURSE CALL

CR-13

TC

P

TC

P

TC

P

TC

P

L1A-2A-A

L1B-2A-2

L1B-2A-1

M1-2A

CR-2A

EQ-2A

CHASE

CHASE

A

D

B

C

124 3

CDE

CDE

CDE

SUB-WAIT

STAIR

ST-1

ELECTRICAL

ROOM

IT ROOM (VA)

OFFICE

(TELEHEALTH)

OFFICE

(HBPC)

RECEPTION

OFFICE

(NURSE

MANAGER)

OFFICE

(ACOS)

PATIENT

TOILET

TELEHEALTH

EXAM

TELEHEALTH

EXAM

TELEHEALTH

EXAM

TELEHEALTH

EXAM

TELEHEALTH

EXAM

TELEHEALTH

EXAM

HBPC

WORKROOM

TELEHEALTH

WORKROOM

SUB-WAIT

CORRIDOR

C O

R R

ID

O

R

HALLWAY

STAFF TOILET

STAFF TOILET

HALLWAY

WC ALCOVE

IT ROOM

(VENDOR)

1 1

1 1

2.7 0.01.5 0.57

D.0

C.0

A.3

B.0

E

VF E

OS

D1

NPCB

CRPC

KL KL KL KL KL KL

D1D1

VFVF

OS OS

E

VL2

G2G2G2

G2

VL2

VL2

VL2

G2

E

VL2

E E

VL VL2U

VL5 VL5

VL5 VL5

VL2

VL2

VL2

VL2

VL5 VL5

VL5 VL5

VL5 VL5

VL5 VL5

1D

1D D

D

2U D

S3 S3 S3

VL

VL

VL

VL

1D 1D

DD

VL

VL

VL

VL

L12 L12

L12L12

L12 L12

L12L12

VL2 E

VL2

VL2

VL2

VL2VL2

VL2

E

VL2VL2VL2

E

VL

VL VL VL

VL2

WL

WLD

D

D

D

D

D

D

D

G2

G2

D

D

G2

G2

D

G2 G2 D

G2 G2

G2 G2 D

G2G2

D

NPCB- 1

NPCB- 5

CR2-UPS-2- 3

D D D

G2 G2

G2G2

2D

2D

2D2D

2D 2D

NPCB- 3

TO FIXTURES

BELOW

CR2-UPS-2

EXISTING LIGHT FIXTURE(S) AND LIGHT SWITCH(ES) TO REMAIN IN

SERVICE. NO CHANGE.

REINSTALL LIGHTS AND CEILING DEVICES SALVAGED FROM

DEMOLITION WORK.

KEYED PLAN NOTES

(THIS SHEET ONLY)

UTILIZE A 20A/1P BREAKER IN NEW LIFE SAFETY PANEL LS2A2

(LOCATED IN ROOM 1415) (CKT #7) TO FEED ALL EMERGENCY

LIGHTING FIXTURES AND EXIT SIGNS ON THIS FLOOR.

REFERENCE THE ARCHITECTURAL PHASING PLANS AND

SPECIFICATIONS.

GENERAL NOTES

(THIS SHEET ONLY)

1.

2.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

321 4 5 6 7 8 9 10

EXPAND PRIMARY CARE

OSCAR G. JOHNSON VA MEDICAL CENTER

325 H STREET,

IRON MOUNTAIN, MI 49801

ARCHITECT/ENGINEER

310 Pine Street | Green Bay, WI 54301 920-432-4865 | www.bernersschober.com

FULLY SPRINKLERED

KEY PLAN

Comm. Number: 5700.16

DECEMBER 4, 2020

585-336

U.S. Department of Veterans Affairs

100% DESIGN SUBMITTAL

Revisions: Date:

CONSULTANT

Architecture | Planning | Interior Design

2224 S. Michigan Ave. | Suite 1400 Chicago, Illinois 60604-2595

(312)-554-1400

65% SUBMITTAL 04/28/2020

ZONE 1

ZONE 2

ZONE 3

ZONE 4

project number: 1180742

95% SUBMITTAL 07/24/2020

100% SUBMITTAL 12/04/2020

B

IM

/V

A G

L H

S E x p a n d

P ri m a ry

C a re /V

A E

L E

C .r v t

/8 /2

:1

:0

A

M

MLL NMP

EL103

SECOND FLOOR LIGHTING PLAN

DWG. 127 OF 147

N

1/8" = 1'-0"EL103

SECOND FLOOR LIGHTING PLANF5

B

124 3 2.7

0.0

1.5 0.57

D.0

C.0

A.3

B.0

OA

9'-6"

E

OA

10'-0"

KL

KL

KL

KL

KL

KL

9'-6"

9'-6"9'-6"

LS2A2- 7

VIA PHOTOCELL &

TC. #1

LS2A2- 8

CRPC- 1

PENTHOUSE

LS2A2- 7

REFERENCE THE PARTIAL EXTERIOR LIGHTING CONTROL DETAIL

ON SHEET E502.

KEYED PLAN NOTES

(THIS SHEET ONLY)

REFERENCE THE ARCHITECTURAL PHASING PLANS AND

SPECIFICATIONS.

GENERAL NOTES

(THIS SHEET ONLY)

1.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

321 4 5 6 7 8 9 10

EXPAND PRIMARY CARE

OSCAR G. JOHNSON VA MEDICAL CENTER

325 H STREET,

IRON MOUNTAIN, MI 49801

ARCHITECT/ENGINEER

310 Pine Street | Green Bay, WI 54301 920-432-4865 | www.bernersschober.com

FULLY SPRINKLERED

KEY PLAN

Comm. Number: 5700.16

DECEMBER 4, 2020

585-336

U.S. Department of Veterans Affairs

100% DESIGN SUBMITTAL

Revisions: Date:

CONSULTANT

Architecture | Planning | Interior Design

2224 S. Michigan Ave. | Suite 1400 Chicago, Illinois 60604-2595

(312)-554-1400

65% SUBMITTAL 04/28/2020

ZONE 1

ZONE 2

ZONE 3

ZONE 4

project number: 1180742

95% SUBMITTAL 07/24/2020

100% SUBMITTAL 12/04/2020

B

IM

/V

A G

L H

S E x p a n d

P ri m a ry

C a re /V

A E

L E

C .r v t

/8 /2

:1

:5

A

M

MLL NMP

EL104

ROOF LIGHTING PLAN

DWG. 128 OF 147

N

1/8" = 1'-0"EL104

ROOF LIGHTING PLANF5

122.7 0.01.5 0.5

D.0

C.0

A.3

B.0

STAIR

ST-1

ELECTRICAL

ROOM

IT ROOM (VA)

OFFICE

(TELEHEALTH)

OFFICE

(HBPC)

RECEPTION

OFFICE

(NURSE

MANAGER)

OFFICE

(ACOS)

PATIENT

TOILET

TELEHEALTH

EXAM

TELEHEALTH

EXAM

TELEHEALTH

EXAM

TELEHEALTH

EXAM

TELEHEALTH

EXAM

2403 HBPC

WORKROOM

TELEHEALTH

WORKROOM

SUB-WAIT

SUB-WAIT

CORRIDOR

HALLWAY

STAFF TOILET

STAFF TOILET

HALLWAY

WC ALCOVE

2329 IT ROOM

(VENDOR)

STAIR

ST-1

ELECTRICAL

ROOM

IT ROOM (VA)

OFFICE

(TELEHEALTH)

OFFICE

(HBPC)

RECEPTION

OFFICE

(NURSE

MANAGER)

OFFICE

(ACOS)

PATIENT

TOILET

TELEHEALTH

EXAM

TELEHEALTH

EXAM

TELEHEALTH

EXAM

TELEHEALTH

EXAM

TELEHEALTH

EXAM

TELEHEALTH

EXAM

2403 HBPC

WORKROOM

TELEHEALTH

WORKROOM

SUB-WAIT

SUB-WAIT

CORRIDOR

CORRIDOR

HALLWAY

STAFF TOILET

STAFF TOILET

HALLWAY

WC ALCOVE

2329 IT ROOM

(VENDOR)

EGRESS LIGHTING STATISTICS

ROOM NAME MIN fc. MAX fc. AVG fc. AVG / MIN fc. MAX / MIN fc.

SUBWAIT & CORR.

2328/2401/2499 0.53 12.1 5.81 11.01 22.87

HALLWAY 2496 2.09 5.58 4.3 2.06 2.67

CORR. 2497/2498 1.4 13.1 6.48 4.64 9.36

WORK RM 2412 1.49 22.9 8.94 6.01 15.38

STAIR ST-1 12.4 31.1 16.9 1.37 2.51

EGRESS LIGHTING STATISTICS

ROOM NAME MIN fc. MAX fc. AVG fc. AVG / MIN fc. MAX / MIN fc.

TEAMLET 1408 1.33 9.32 4.82 3.62 6.99

CORR. 1498, 1499 1.45 12.5 6.03 4.14 8.6

CORR. 1495, 1496, 1497 0.77 11.5 5.61 7.28 14.94

STAIR ST-1 13.0 34.9 21.9 1.68 2.67

A

122.7 0.01.5 0.5

D.0

C.0

A.3

B.0

ELECTRICAL

ROOM

IT ROOM (VA)

SOILED

HOLDING

STAFF TOILET

TEAMLET

WORKSTATIONS

EXAM

EXAM

EXAM

EXAM

EXAM

EXAM

HSKP.

STAIR

ST-1

CONFERENCE

ROOM

MEDICAL

EQUIPMENT

STORAGE

CLEAN

UTILITY

HALLWAY

CORRIDOR

CORRIDOR

CORRIDOR

CORRIDOR

PATIENT

TOILET

PATIENT

TOILET

CONNECTION

EXAM ROOM

STAFF TOILET

1340A

BREAK

ROOM/

LOCKERS

CORRIDOR

1328A

ELECTRICAL

ROOM

IT ROOM (VA)

SOILED

HOLDING

STAFF TOILET

TEAMLET

WORKSTATIONS

EXAM

EXAM

EXAM

EXAM

EXAM

EXAM

HSKP.

STAIR

ST-1

CONFERENCE

ROOM

MEDICAL

EQUIPMENT

STORAGE

CLEAN

UTILITY

CORRIDOR

SUB-WAIT

PATIENT

TOILET

PATIENT

TOILET

EXAM ROOM

STAFF TOILET

1340A

BREAK

ROOM/

LOCKERS

CORRIDOR

1328A

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

321 4 5 6 7 8 9 10

EXPAND PRIMARY CARE

OSCAR G. JOHNSON VA MEDICAL CENTER

325 H STREET,

IRON MOUNTAIN, MI 49801

ARCHITECT/ENGINEER

310 Pine Street | Green Bay, WI 54301 920-432-4865 | www.bernersschober.com

FULLY SPRINKLERED

KEY PLAN

Comm. Number: 5700.16

DECEMBER 4, 2020

585-336

U.S. Department of Veterans Affairs

100% DESIGN SUBMITTAL

Revisions: Date:

CONSULTANT

Architecture | Planning | Interior Design

2224 S. Michigan Ave. | Suite 1400 Chicago, Illinois 60604-2595

(312)-554-1400

65% SUBMITTAL 04/28/2020

ZONE 1

ZONE 2

ZONE 3

ZONE 4

project number: 1180742

95% SUBMITTAL 07/24/2020

100% SUBMITTAL 12/04/2020

B

IM

/V

A G

L H

S E x p a n d

P ri m a ry

C a re /V

A E

L E

C .r v t

/8 /2

:1

:1

A

M

MLL NMP

EC101

FIRST AND SECOND FLOOR EGRESS

CALCULATIONS

DWG. 129 OF 147

N

1/8" = 1'-0"EC101

SECOND FLOOR LIGHTING EGRESS1

N

1/8" = 1'-0"EC101

FIRST FLOOR LIGHTING EGRESS4

PASSENGER

ELEVATOR

COILING OH DOOR

COILING OH

DOOR

COILING OH

DOOR

LIFT

COILING OH FABRIC

DOOR

TA

PI

PE

CH

AS

E

FE

FE FIRE

EQUIP

MECH

SHAFT

FD

LOBBY

ELEVATOR

B224

RECEIVING

SHIPPING &

B274

SHREDDER RM.

RECYCLING &

B278

STORAGE