ATTACHMENT 3 - Drawings 2 of 7.pdf

PDF 17 MB Posted

Attached to
Y1DA--Expand Primary Care (Minor) Construction Iron Mountain
Solicitation number
36C77621B0005
Issued by

About this file

This notice provides details for a federal construction contract opportunity for the Department of Veterans Affairs. The solicitation will be for a single firm-fixed-price contract to complete an addition and renovation project at the Oscar G. Johnson VA Medical Center in Iron Mountain, Michigan. Work will include expanding primary care facilities by 10,000 square feet as well as renovating approximately 1,100 square feet of existing space on the first floor. The project scope encompasses architectural, site, structural, fire protection, HVAC, plumbing, electrical, earthwork, exterior utilities, and other construction aspects. The solicitation will be issued as an Invitation for Bid evaluated according to procedures in the solicitation. It is a total Service-Disabled Veteran-Owned Small Business set-aside with a North American Industry Classification System code of 236220 and size standard of $39.5 million. The performance period is approximately 546 calendar days from the notice to proceed. The magnitude of construction is between $5 million and $10 million. The solicitation will be issued in March 2021.

View the file

Other files

Show all 20

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

/F1 AE150-1/F1 AE150-1

F A E -1

F A E -1

EXPOSED

STRUCTURE

B001

ST-1

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

321 4 5 6 7 8 9 10

EXPAND PRIMARY CARE

OSCAR G. JOHNSON VA MEDICAL CENTER

325 H STREET,

IRON MOUNTAIN, MI 49801

ARCHITECT/ENGINEER

310 Pine Street | Green Bay, WI 54301 920-432-4865 | www.bernersschober.com

FULLY SPRINKLERED

KEY PLAN

Comm. Number: 5700.16

DECEMBER 4, 2020

585-336

U.S. Department of Veterans Affairs

100% DESIGN SUBMITTAL

Revisions: Date:

CONSULTANT

Architecture | Planning | Interior Design

2224 S. Michigan Ave. | Suite 1400 Chicago, Illinois 60604-2595

(312)-554-1400

65% SUBMITTAL 04/28/2020

ZONE 1

ZONE 2

ZONE 3

ZONE 4

project number: 1180742

95% SUBMITTAL 07/24/2020

100% SUBMITTAL 12/04/2020

B

IM

/V

A G

L H

S E x p a n d P ri m a ry

C a re /V

A A

R C

H .r v t

/1 /2

:2

:4

P M

DPD JAP

AE150

PIPE BASEMENT REFLECTED CEILING

PLAN

DWG. 29 OF 147

N

1/8" = 1'-0"AE150

BASEMENT REFLECTED CEILING PLANF2

4'0 8' 12'2'

1415 1414

1402 1403 1404 1405

ST-1

1418 1417

1358 1352

/F1 AE151-1/F1 AE151-1/F1 AE151-3/F1 AE151-3

/F1 AE151-2/F1 AE151-2/F1 AE151-4/F1 AE151-4

F A E -2

F A E -4

F A E -2

F A E -4

F A E -1

F A E -3

F A E -1

F A E -3

(NO WORK)

(NO WORK)

(NO WORK)(NO WORK)

(NO WORK)

(NO WORK)

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

321 4 5 6 7 8 9 10

EXPAND PRIMARY CARE

OSCAR G. JOHNSON VA MEDICAL CENTER

325 H STREET,

IRON MOUNTAIN, MI 49801

ARCHITECT/ENGINEER

310 Pine Street | Green Bay, WI 54301 920-432-4865 | www.bernersschober.com

FULLY SPRINKLERED

KEY PLAN

Comm. Number: 5700.16

DECEMBER 4, 2020

585-336

U.S. Department of Veterans Affairs

100% DESIGN SUBMITTAL

Revisions: Date:

CONSULTANT

Architecture | Planning | Interior Design

2224 S. Michigan Ave. | Suite 1400 Chicago, Illinois 60604-2595

(312)-554-1400

65% SUBMITTAL 04/28/2020

ZONE 1

ZONE 2

ZONE 3

ZONE 4

project number: 1180742

95% SUBMITTAL 07/24/2020

100% SUBMITTAL 12/04/2020

B

IM

/V

A G

L H

S E x p a n d P ri m a ry

C a re /V

A A

R C

H .r v t

/1 /2

:2

:0

P M

DPD JAP

AE151

1ST FLOOR REFLECTED CEILING PLAN

DWG. 30 OF 147

N

1/8" = 1'-0"AE151

1ST FLOOR REFLECTED CEILING PLANF2

ST-1

2419 2418

2416 2417

2413 2414

24062405

23642362

24202421

(NO WORK)(NO WORK)

(NO WORK)

/F1 AE152-1/F1 AE152-1

F A E -1

F A E -1

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

321 4 5 6 7 8 9 10

EXPAND PRIMARY CARE

OSCAR G. JOHNSON VA MEDICAL CENTER

325 H STREET,

IRON MOUNTAIN, MI 49801

ARCHITECT/ENGINEER

310 Pine Street | Green Bay, WI 54301 920-432-4865 | www.bernersschober.com

FULLY SPRINKLERED

KEY PLAN

Comm. Number: 5700.16

DECEMBER 4, 2020

585-336

U.S. Department of Veterans Affairs

100% DESIGN SUBMITTAL

Revisions: Date:

CONSULTANT

Architecture | Planning | Interior Design

2224 S. Michigan Ave. | Suite 1400 Chicago, Illinois 60604-2595

(312)-554-1400

65% SUBMITTAL 04/28/2020

ZONE 1

ZONE 2

ZONE 3

ZONE 4

project number: 1180742

95% SUBMITTAL 07/24/2020

100% SUBMITTAL 12/04/2020

B

IM

/V

A G

L H

S E x p a n d P ri m a ry

C a re /V

A A

R C

H .r v t

/1 /2

:2

:0

P M

DPD JAP

AE152

2ND FLOOR REFLECTED CEILING PLAN

DWG. 31 OF 147

N

1/8" = 1'-0"AE152

2ND FLOOR REFLECTED CEILING PLANF2

EXPOSED STRUCTURE

ST-1

B001

C2

AE502

C2

AE502

STAIR, SHAFT, OR HAZARDOUS AREA SEPARATION

WALLS: 2 HOUR FIRE

DOORS: 90 MINUTE FIRE

OPENINGS: NOT PERMITTED

DAMPERS: 90 MINUTE FIRE

FIRE COMPARTMENT DIVISON

WALLS: 2 HOUR FIRE AND SMOKE RESISTANT

DOORS: 90 MINUTE FIRE AND SMOKE RESISTANT

OPENINGS: NOT PERMITTED

DAMPERS: 90 MINUTE FIRE AND SMOKE RESISTANT

STAIR, SHAFT, OR HAZARDOUS AREA SEPARATION

WALLS: 1 HOUR FIRE

DOORS: 45 MINUTE FIRE

OPENINGS: 45 MINUTE PROTECTION

DAMPERS: 90 MINUTE FIRE AT NON-SPRINKLED

SMOKE COMPARTMENT DIVISON

WALLS: 1 HOUR FIRE AND SMOKE RESISTANT

DOORS: 20 MINUTE CONSTRUCTION AND SMOKE RESISTANT

OPENINGS: 20 MINUTE PROTECTION,

45 MINUTE AT 1 HOUR RATED ROOMS

DAMPERS: SMOKE RESISTANT

(IN NEW CONSTRUCTION REQUIRED BY IBC)

ONE HOUR SMOKE RESISTANT PARTITION

(NON-SPRINKLED COMPARTEMENT)

WALLS: 1 HOUR FIRE AND SMOKE RESISTANT

DOORS: 20 MINUTE CONSTRUCTION AND SMOKE RESISTANT

OPENINGS: 20 MINUTE PROTECTION

SMOKE RESISTANT PARTITION (SPRINKLED COMPARTMENT)

WALLS: SMOKE RESISTANT

DOORS: SMOKE RESISTANT AND POSITIVE LATCHING,

(EXCEPT TOILET ROOMS, ECT.)

OPENINGS: CANNOT EXCEED 80 SQ. IN. WITHOUT PROTECTION

FIRE SEPARATION LEGEND

1. UNLESS DIMENSIONED OTHERWISE ON THIS PLAN, CEILINGS

GRIDS ARE CENTERED IN ROOM IN BOTH DIRECTIONS.

2. SEE I001 FOR CEILING FINISH TYPE

3. COORDINATE/VERIFY LOCATION OF CEILING MOUNTED LIGHTS

WITH OWNER PRIOR TO INSTALLATION OF SUPPORT STRUCTURE.

4. WHERE EXISTING PARTITIONS ARE SHOWN TO HAVE A FIRE OR

SMOKE RATING, THE CONTRACTOR SHALL PROVIDE THE

REQUIRED PENETRATION PROTECTION FOR ALL NEW

PENETRATIONS THROUGH THE PARTITION. REPORT ANY

EXISTING VOIDS WHICH REQUIRE PATCHING, UNDER ADDITIONAL

SCOPE OF WORK.

5. CONTRACT WORK INCLUDES ALL CEILING MOUNTED ITEMS OR

DEVICES SHOWN ON THIS PLAN AND AS SHOWN ON THE PLANS

OF OTHER TRADES. THIS DRAWING DOES NOT RELIEVE

CONTRACTOR'S RESPONSIBILITY TO INDIVIDUALLY COORDINATE

THEIR WORK WITH OTHER TRADES.

GENERAL CEILING PLAN NOTES:

ARCHITECTURAL REFLECTED

CEILING PLAN NOTES

ACOUSTICAL TILE CEILINGS

GYPSUM BOARD CEILINGS

CEILING HEIGHT (PARENTHESIS INDICATES

EXISTING CEILING HEIGHT)

CEILING TYPE/FINISH

CEILING MATERIAL

ACT: ACOUSTICAL TILE CEILING

ESA: EXPOSED STRUCTURE ABOVE

GYP: GYPSUM BOARD

SMP: PAINTABLE SHEET METAL PANELS BY

MECHANICAL TRADE

CEILING HEIGHT (PARENTHESIS

INDICATES EXISTING CEILING HEIGHT)

8'-0"

8'-0"

MATERIAL AND SYMBOLS LEGEND:

INDICATES LOCATION OF CUT CEILING TILES

REQUIRED TO CENTER GRID PATTERNS IN

CORRIDORS

CUBICLE TRACK

SYMBOLS KEY

HVAC

FIRE PROTECTION

ARCHITECTURAL

ACCESS PANEL

RETURN GRILLE

SUPPLY DIFFUSER

RETURN GRILLE

SUPPLY DIFFUSER

GYPSUM BOARD CEILING

AP

PAINTED SHEET METAL PANELP.

CONCEALED PENDENT SPRINKLER HEAD

CEILING COORDINATION

PLAN LEGEND

EXHAUST GRILLE

SUPPLY DIFFUSER

PENDENT SPRINKLER HEAD

OS

S

S

S

N

2X4 LIGHT FIXTURE -

RECESSED / SURFACE

RECESSED DOWNLIGHT,

SURFACE / PENDANT

1X4 LIGHT FIXTURE -

RECESSED / SURFACE

EXIT SIGN - SINGLE / DOUBLE FACE

OCCUPANCY SENSOR

CEILING MOUNTED SPEAKER / STROBE

SMOKE DETECTOR

SPEAKER RECESSED

SPEAKER SURFACE

WIRELESS DATA ACCESS POINT

CORRIDOR DOME LIGHT

ELECTRICAL

2X2 LIGHT FIXTURE -

RECESSED / SURFACE

CEILING MOUNTED SECURITY CAMERA

(DOME TYPE)

S

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

321 4 5 6 7 8 9 10

EXPAND PRIMARY CARE

OSCAR G. JOHNSON VA MEDICAL CENTER

325 H STREET,

IRON MOUNTAIN, MI 49801

ARCHITECT/ENGINEER

310 Pine Street | Green Bay, WI 54301 920-432-4865 | www.bernersschober.com

FULLY SPRINKLERED

KEY PLAN

Comm. Number: 5700.16

DECEMBER 4, 2020

585-336

U.S. Department of Veterans Affairs

100% DESIGN SUBMITTAL

Revisions: Date:

CONSULTANT

Architecture | Planning | Interior Design

2224 S. Michigan Ave. | Suite 1400 Chicago, Illinois 60604-2595

(312)-554-1400

65% SUBMITTAL 04/28/2020

ZONE 1

ZONE 2

ZONE 3

ZONE 4

project number: 1180742

95% SUBMITTAL 07/24/2020

100% SUBMITTAL 12/04/2020

B

IM

/V

A G

L H

S E x p a n d P ri m a ry

C a re /V

A A

R C

H .r v t

/1 /2

:2

:5

P M

DPD JAP

AE150-1

PIPE BASEMENT REFLECTED CEILING

PLAN - ZONE 1

DWG. 32 OF 147

N

1/4" = 1'-0"AE150-1

BASEMENT REFLECTED CEILING PLAN - ZONE 1F1

0 2' 4' 6'1'

2'-0"

GYP

8' - 4"

EP2

ST-1

1402 1403 1404 1405

1418 1417

GYP

8' - 4"

EP2 GYP

8' - 4"

EP2

GYP

8' - 4"

EP2

GYP

8' - 4"

EP2

ACT

8' - 4"

ACT

8' - 10"

2ACT

8' - 10"

2ACT

8' - 10"

2ACT

8' - 10"

ACT

9' - 0"

ACT

9' - 0"

ACT

9' - 0"

ACT

9' - 0"

ACT

8' - 2"

1415 1414

EXPOSED

CEILING

EXPOSED

CEILING

ACT

9' - 0"

GYP

8' - 0" P1

ACT

9' - 0"

GYP

8' - 10"

P8

ACT

9' - 0"

ACT

8' - 4"

GYP

7' - 11"

P1

GYP

8' - 10"

P8

GYP

8' - 3"

P8

GYP

8' - 0" P1

GYP

8' - 0" P1

/F1 AE151-3

/F1 AE151-2/F1 AE151-2/F1 AE151-4

F

A

E

-2

F

A

E

-4

F

A

E

-3

F

A

E

-3

EXPANSION

JOINT COVER

2'-0"

BACKING ABOVE TILE

FOR CUBICLE TRACK

SUPPORT, TYP.

ACT

8' - 0"

ACT

7' - 10"

EX

REMOVE, SALVAGE AND

RE-INSTALL CEILINGS AT

NEW SPECIFIED HEIGHT.

REPLACE ANY DAMAGED

MATERIALS

ACT

8' - 0"

EX

1340A

ACT

9' - 0"

F1

AE501

ACT

8' - 10"

E3

AE501

E3

AE501

E2

AE501

E2

AE501

E3

AE501

E2

AE501

E3

AE501

E2

AE501

E2

AE501

ACT

8' - 4"

GYP

8' - 3"

GYP

8' - 9 1/4"

ACT

8' - 10"

/8

E1

AE501

GYP

8' - 3"

P8

GYP

8' - 9" P8

OPERABLE

PARTITION

D1

AE501

E2

AE505

D9

AE505

E2

AE505

D9

AE505

B9

AE505

PROVIDE CONTROL JOINT

AT ALL FACES OF SOFFIT

PROVIDE CONTROL JOINT

AT ALL FACES OF SOFFIT

PROVIDE CONTROL JOINT

AT ALL FACES OF SOFFIT

E3

AE501

1. UNLESS DIMENSIONED OTHERWISE ON THIS PLAN, CEILINGS

GRIDS ARE CENTERED IN ROOM IN BOTH DIRECTIONS.

2. SEE I001 FOR CEILING FINISH TYPE

3. COORDINATE/VERIFY LOCATION OF CEILING MOUNTED LIGHTS

WITH OWNER PRIOR TO INSTALLATION OF SUPPORT STRUCTURE.

4. WHERE EXISTING PARTITIONS ARE SHOWN TO HAVE A FIRE OR

SMOKE RATING, THE CONTRACTOR SHALL PROVIDE THE

REQUIRED PENETRATION PROTECTION FOR ALL NEW

PENETRATIONS THROUGH THE PARTITION. REPORT ANY

EXISTING VOIDS WHICH REQUIRE PATCHING, UNDER ADDITIONAL

SCOPE OF WORK.

5. CONTRACT WORK INCLUDES ALL CEILING MOUNTED ITEMS OR

DEVICES SHOWN ON THIS PLAN AND AS SHOWN ON THE PLANS

OF OTHER TRADES. THIS DRAWING DOES NOT RELIEVE

CONTRACTOR'S RESPONSIBILITY TO INDIVIDUALLY COORDINATE

THEIR WORK WITH OTHER TRADES.

GENERAL CEILING PLAN NOTES:

ARCHITECTURAL REFLECTED

CEILING PLAN NOTES

ACOUSTICAL TILE CEILINGS

GYPSUM BOARD CEILINGS

CEILING HEIGHT (PARENTHESIS INDICATES

EXISTING CEILING HEIGHT)

CEILING TYPE/FINISH

CEILING MATERIAL

ACT: ACOUSTICAL TILE CEILING

ESA: EXPOSED STRUCTURE ABOVE

GYP: GYPSUM BOARD

SMP: PAINTABLE SHEET METAL PANELS BY

MECHANICAL TRADE

CEILING HEIGHT (PARENTHESIS

INDICATES EXISTING CEILING HEIGHT)

8'-0"

8'-0"

MATERIAL AND SYMBOLS LEGEND:

INDICATES LOCATION OF CUT CEILING TILES

REQUIRED TO CENTER GRID PATTERNS IN

CORRIDORS

CUBICLE TRACK

STAIR, SHAFT, OR HAZARDOUS AREA SEPARATION

WALLS: 2 HOUR FIRE

DOORS: 90 MINUTE FIRE

OPENINGS: NOT PERMITTED

DAMPERS: 90 MINUTE FIRE

FIRE COMPARTMENT DIVISON

WALLS: 2 HOUR FIRE AND SMOKE RESISTANT

DOORS: 90 MINUTE FIRE AND SMOKE RESISTANT

OPENINGS: NOT PERMITTED

DAMPERS: 90 MINUTE FIRE AND SMOKE RESISTANT

STAIR, SHAFT, OR HAZARDOUS AREA SEPARATION

WALLS: 1 HOUR FIRE

DOORS: 45 MINUTE FIRE

OPENINGS: 45 MINUTE PROTECTION

DAMPERS: 90 MINUTE FIRE AT NON-SPRINKLED

SMOKE COMPARTMENT DIVISON

WALLS: 1 HOUR FIRE AND SMOKE RESISTANT

DOORS: 20 MINUTE CONSTRUCTION AND SMOKE RESISTANT

OPENINGS: 20 MINUTE PROTECTION,

45 MINUTE AT 1 HOUR RATED ROOMS

DAMPERS: SMOKE RESISTANT

(IN NEW CONSTRUCTION REQUIRED BY IBC)

ONE HOUR SMOKE RESISTANT PARTITION

(NON-SPRINKLED COMPARTEMENT)

WALLS: 1 HOUR FIRE AND SMOKE RESISTANT

DOORS: 20 MINUTE CONSTRUCTION AND SMOKE RESISTANT

OPENINGS: 20 MINUTE PROTECTION

SMOKE RESISTANT PARTITION (SPRINKLED COMPARTMENT)

WALLS: SMOKE RESISTANT

DOORS: SMOKE RESISTANT AND POSITIVE LATCHING,

(EXCEPT TOILET ROOMS, ECT.)

OPENINGS: CANNOT EXCEED 80 SQ. IN. WITHOUT PROTECTION

FIRE SEPARATION LEGEND

SYMBOLS KEY

HVAC

FIRE PROTECTION

ARCHITECTURAL

ACCESS PANEL

RETURN GRILLE

SUPPLY DIFFUSER

RETURN GRILLE

SUPPLY DIFFUSER

GYPSUM BOARD CEILING

AP

PAINTED SHEET METAL PANELP.

CONCEALED PENDENT SPRINKLER HEAD

CEILING COORDINATION

PLAN LEGEND

EXHAUST GRILLE

SUPPLY DIFFUSER

PENDENT SPRINKLER HEAD

OS

S

S

S

N

2X4 LIGHT FIXTURE -

RECESSED / SURFACE

RECESSED DOWNLIGHT,

SURFACE / PENDANT

1X4 LIGHT FIXTURE -

RECESSED / SURFACE

EXIT SIGN - SINGLE / DOUBLE FACE

OCCUPANCY SENSOR

CEILING MOUNTED SPEAKER / STROBE

SMOKE DETECTOR

SPEAKER RECESSED

SPEAKER SURFACE

WIRELESS DATA ACCESS POINT

CORRIDOR DOME LIGHT

ELECTRICAL

2X2 LIGHT FIXTURE -

RECESSED / SURFACE

CEILING MOUNTED SECURITY CAMERA

(DOME TYPE)

S

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

321 4 5 6 7 8 9 10

EXPAND PRIMARY CARE

OSCAR G. JOHNSON VA MEDICAL CENTER

325 H STREET,

IRON MOUNTAIN, MI 49801

ARCHITECT/ENGINEER

310 Pine Street | Green Bay, WI 54301 920-432-4865 | www.bernersschober.com

FULLY SPRINKLERED

KEY PLAN

Comm. Number: 5700.16

DECEMBER 4, 2020

585-336

U.S. Department of Veterans Affairs

100% DESIGN SUBMITTAL

Revisions: Date:

CONSULTANT

Architecture | Planning | Interior Design

2224 S. Michigan Ave. | Suite 1400 Chicago, Illinois 60604-2595

(312)-554-1400

65% SUBMITTAL 04/28/2020

ZONE 1

ZONE 2

ZONE 3

ZONE 4

project number: 1180742

95% SUBMITTAL 07/24/2020

100% SUBMITTAL 12/04/2020

B

IM

/V

A G

L H

S E x p a n d P ri m a ry

C a re /V

A A

R C

H .r v t

/1 /2

:2

:1

P M

DPD JAP

AE151-1

1ST FLOOR REFLECTED CEILING PLAN

- ZONE 1

DWG. 33 OF 147

N

1/4" = 1'-0"AE151-1

1ST FLOOR REFLECTED CEILING PLAN - ZONE 1F1

GYP

8' - 10"

P8

ACT

9' - 0"

2x2

ACT

9' - 0"

2x2

/F1 AE151-1/F1 AE151-1/F1 AE151-3

/F1 AE151-4

F

A

E

-4

F

A

E

-4

F

A

E

-1

F

A

E

-3

E3

AE501

1. UNLESS DIMENSIONED OTHERWISE ON THIS PLAN, CEILINGS

GRIDS ARE CENTERED IN ROOM IN BOTH DIRECTIONS.

2. SEE I001 FOR CEILING FINISH TYPE

3. COORDINATE/VERIFY LOCATION OF CEILING MOUNTED LIGHTS

WITH OWNER PRIOR TO INSTALLATION OF SUPPORT STRUCTURE.

4. WHERE EXISTING PARTITIONS ARE SHOWN TO HAVE A FIRE OR

SMOKE RATING, THE CONTRACTOR SHALL PROVIDE THE

REQUIRED PENETRATION PROTECTION FOR ALL NEW

PENETRATIONS THROUGH THE PARTITION. REPORT ANY

EXISTING VOIDS WHICH REQUIRE PATCHING, UNDER ADDITIONAL

SCOPE OF WORK.

5. CONTRACT WORK INCLUDES ALL CEILING MOUNTED ITEMS OR

DEVICES SHOWN ON THIS PLAN AND AS SHOWN ON THE PLANS

OF OTHER TRADES. THIS DRAWING DOES NOT RELIEVE

CONTRACTOR'S RESPONSIBILITY TO INDIVIDUALLY COORDINATE

THEIR WORK WITH OTHER TRADES.

GENERAL CEILING PLAN NOTES:

ARCHITECTURAL REFLECTED

CEILING PLAN NOTES

ACOUSTICAL TILE CEILINGS

GYPSUM BOARD CEILINGS

CEILING HEIGHT (PARENTHESIS INDICATES

EXISTING CEILING HEIGHT)

CEILING TYPE/FINISH

CEILING MATERIAL

ACT: ACOUSTICAL TILE CEILING

ESA: EXPOSED STRUCTURE ABOVE

GYP: GYPSUM BOARD

SMP: PAINTABLE SHEET METAL PANELS BY

MECHANICAL TRADE

CEILING HEIGHT (PARENTHESIS

INDICATES EXISTING CEILING HEIGHT)

8'-0"

8'-0"

MATERIAL AND SYMBOLS LEGEND:

INDICATES LOCATION OF CUT CEILING TILES

REQUIRED TO CENTER GRID PATTERNS IN

CORRIDORS

CUBICLE TRACK

STAIR, SHAFT, OR HAZARDOUS AREA SEPARATION

WALLS: 2 HOUR FIRE

DOORS: 90 MINUTE FIRE

OPENINGS: NOT PERMITTED

DAMPERS: 90 MINUTE FIRE

FIRE COMPARTMENT DIVISON

WALLS: 2 HOUR FIRE AND SMOKE RESISTANT

DOORS: 90 MINUTE FIRE AND SMOKE RESISTANT

OPENINGS: NOT PERMITTED

DAMPERS: 90 MINUTE FIRE AND SMOKE RESISTANT

STAIR, SHAFT, OR HAZARDOUS AREA SEPARATION

WALLS: 1 HOUR FIRE

DOORS: 45 MINUTE FIRE

OPENINGS: 45 MINUTE PROTECTION

DAMPERS: 90 MINUTE FIRE AT NON-SPRINKLED

SMOKE COMPARTMENT DIVISON

WALLS: 1 HOUR FIRE AND SMOKE RESISTANT

DOORS: 20 MINUTE CONSTRUCTION AND SMOKE RESISTANT

OPENINGS: 20 MINUTE PROTECTION,

45 MINUTE AT 1 HOUR RATED ROOMS

DAMPERS: SMOKE RESISTANT

(IN NEW CONSTRUCTION REQUIRED BY IBC)

ONE HOUR SMOKE RESISTANT PARTITION

(NON-SPRINKLED COMPARTEMENT)

WALLS: 1 HOUR FIRE AND SMOKE RESISTANT

DOORS: 20 MINUTE CONSTRUCTION AND SMOKE RESISTANT

OPENINGS: 20 MINUTE PROTECTION

SMOKE RESISTANT PARTITION (SPRINKLED COMPARTMENT)

WALLS: SMOKE RESISTANT

DOORS: SMOKE RESISTANT AND POSITIVE LATCHING,

(EXCEPT TOILET ROOMS, ECT.)

OPENINGS: CANNOT EXCEED 80 SQ. IN. WITHOUT PROTECTION

FIRE SEPARATION LEGEND

SYMBOLS KEY

HVAC

FIRE PROTECTION

ARCHITECTURAL

ACCESS PANEL

RETURN GRILLE

SUPPLY DIFFUSER

RETURN GRILLE

SUPPLY DIFFUSER

GYPSUM BOARD CEILING

AP

PAINTED SHEET METAL PANELP.

CONCEALED PENDENT SPRINKLER HEAD

CEILING COORDINATION

PLAN LEGEND

EXHAUST GRILLE

SUPPLY DIFFUSER

PENDENT SPRINKLER HEAD

OS

S

S

S

N

2X4 LIGHT FIXTURE -

RECESSED / SURFACE

RECESSED DOWNLIGHT,

SURFACE / PENDANT

1X4 LIGHT FIXTURE -

RECESSED / SURFACE

EXIT SIGN - SINGLE / DOUBLE FACE

OCCUPANCY SENSOR

CEILING MOUNTED SPEAKER / STROBE

SMOKE DETECTOR

SPEAKER RECESSED

SPEAKER SURFACE

WIRELESS DATA ACCESS POINT

CORRIDOR DOME LIGHT

ELECTRICAL

2X2 LIGHT FIXTURE -

RECESSED / SURFACE

CEILING MOUNTED SECURITY CAMERA

(DOME TYPE)

S

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

321 4 5 6 7 8 9 10

EXPAND PRIMARY CARE

OSCAR G. JOHNSON VA MEDICAL CENTER

325 H STREET,

IRON MOUNTAIN, MI 49801

ARCHITECT/ENGINEER

310 Pine Street | Green Bay, WI 54301 920-432-4865 | www.bernersschober.com

FULLY SPRINKLERED

KEY PLAN

Comm. Number: 5700.16

DECEMBER 4, 2020

585-336

U.S. Department of Veterans Affairs

100% DESIGN SUBMITTAL

Revisions: Date:

CONSULTANT

Architecture | Planning | Interior Design

2224 S. Michigan Ave. | Suite 1400 Chicago, Illinois 60604-2595

(312)-554-1400

65% SUBMITTAL 04/28/2020

ZONE 1

ZONE 2

ZONE 3

ZONE 4

project number: 1180742

95% SUBMITTAL 07/24/2020

100% SUBMITTAL 12/04/2020

B

IM

/V

A G

L H

S E x p a n d P ri m a ry

C a re /V

A A

R C

H .r v t

/1 /2

:2

:2

P M

DPD JAP

AE151-2

1ST FLOOR REFLECTED CEILING PLAN

- ZONE 2

DWG. 34 OF 147

N

1/4" = 1'-0"AE151-2

1ST FLOOR REFLECTED CEILING PLAN - ZONE 2F1

13521358

ACT

9' - 0" 2x2

ACT

9' - 0"

2x2

/F1 AE151-1

/F1 AE151-2/F1 AE151-4/F1 AE151-4

F

A

E

-2

F

A

E

-4

F

A

E

-1

(NO WORK)(NO WORK)

(NO WORK)

1. UNLESS DIMENSIONED OTHERWISE ON THIS PLAN, CEILINGS

GRIDS ARE CENTERED IN ROOM IN BOTH DIRECTIONS.

2. SEE I001 FOR CEILING FINISH TYPE

3. COORDINATE/VERIFY LOCATION OF CEILING MOUNTED LIGHTS

WITH OWNER PRIOR TO INSTALLATION OF SUPPORT STRUCTURE.

4. WHERE EXISTING PARTITIONS ARE SHOWN TO HAVE A FIRE OR

SMOKE RATING, THE CONTRACTOR SHALL PROVIDE THE

REQUIRED PENETRATION PROTECTION FOR ALL NEW

PENETRATIONS THROUGH THE PARTITION. REPORT ANY

EXISTING VOIDS WHICH REQUIRE PATCHING, UNDER ADDITIONAL

SCOPE OF WORK.

5. CONTRACT WORK INCLUDES ALL CEILING MOUNTED ITEMS OR

DEVICES SHOWN ON THIS PLAN AND AS SHOWN ON THE PLANS

OF OTHER TRADES. THIS DRAWING DOES NOT RELIEVE

CONTRACTOR'S RESPONSIBILITY TO INDIVIDUALLY COORDINATE

THEIR WORK WITH OTHER TRADES.

GENERAL CEILING PLAN NOTES:

ARCHITECTURAL REFLECTED

CEILING PLAN NOTES

ACOUSTICAL TILE CEILINGS

GYPSUM BOARD CEILINGS

CEILING HEIGHT (PARENTHESIS INDICATES

EXISTING CEILING HEIGHT)

CEILING TYPE/FINISH

CEILING MATERIAL

ACT: ACOUSTICAL TILE CEILING

ESA: EXPOSED STRUCTURE ABOVE

GYP: GYPSUM BOARD

SMP: PAINTABLE SHEET METAL PANELS BY

MECHANICAL TRADE

CEILING HEIGHT (PARENTHESIS

INDICATES EXISTING CEILING HEIGHT)

8'-0"

8'-0"

MATERIAL AND SYMBOLS LEGEND:

INDICATES LOCATION OF CUT CEILING TILES

REQUIRED TO CENTER GRID PATTERNS IN

CORRIDORS

CUBICLE TRACK

STAIR, SHAFT, OR HAZARDOUS AREA SEPARATION

WALLS: 2 HOUR FIRE

DOORS: 90 MINUTE FIRE

OPENINGS: NOT PERMITTED

DAMPERS: 90 MINUTE FIRE

FIRE COMPARTMENT DIVISON

WALLS: 2 HOUR FIRE AND SMOKE RESISTANT

DOORS: 90 MINUTE FIRE AND SMOKE RESISTANT

OPENINGS: NOT PERMITTED

DAMPERS: 90 MINUTE FIRE AND SMOKE RESISTANT

STAIR, SHAFT, OR HAZARDOUS AREA SEPARATION

WALLS: 1 HOUR FIRE

DOORS: 45 MINUTE FIRE

OPENINGS: 45 MINUTE PROTECTION

DAMPERS: 90 MINUTE FIRE AT NON-SPRINKLED

SMOKE COMPARTMENT DIVISON

WALLS: 1 HOUR FIRE AND SMOKE RESISTANT

DOORS: 20 MINUTE CONSTRUCTION AND SMOKE RESISTANT

OPENINGS: 20 MINUTE PROTECTION,

45 MINUTE AT 1 HOUR RATED ROOMS

DAMPERS: SMOKE RESISTANT

(IN NEW CONSTRUCTION REQUIRED BY IBC)

ONE HOUR SMOKE RESISTANT PARTITION

(NON-SPRINKLED COMPARTEMENT)

WALLS: 1 HOUR FIRE AND SMOKE RESISTANT

DOORS: 20 MINUTE CONSTRUCTION AND SMOKE RESISTANT

OPENINGS: 20 MINUTE PROTECTION

SMOKE RESISTANT PARTITION (SPRINKLED COMPARTMENT)

WALLS: SMOKE RESISTANT

DOORS: SMOKE RESISTANT AND POSITIVE LATCHING,

(EXCEPT TOILET ROOMS, ECT.)

OPENINGS: CANNOT EXCEED 80 SQ. IN. WITHOUT PROTECTION

FIRE SEPARATION LEGEND

SYMBOLS KEY

HVAC

FIRE PROTECTION

ARCHITECTURAL

ACCESS PANEL

RETURN GRILLE

SUPPLY DIFFUSER

RETURN GRILLE

SUPPLY DIFFUSER

GYPSUM BOARD CEILING

AP

PAINTED SHEET METAL PANELP.

CONCEALED PENDENT SPRINKLER HEAD

CEILING COORDINATION

PLAN LEGEND

EXHAUST GRILLE

SUPPLY DIFFUSER

PENDENT SPRINKLER HEAD

OS

S

S

S

N

2X4 LIGHT FIXTURE -

RECESSED / SURFACE

RECESSED DOWNLIGHT,

SURFACE / PENDANT

1X4 LIGHT FIXTURE -

RECESSED / SURFACE

EXIT SIGN - SINGLE / DOUBLE FACE

OCCUPANCY SENSOR

CEILING MOUNTED SPEAKER / STROBE

SMOKE DETECTOR

SPEAKER RECESSED

SPEAKER SURFACE

WIRELESS DATA ACCESS POINT

CORRIDOR DOME LIGHT

ELECTRICAL

2X2 LIGHT FIXTURE -

RECESSED / SURFACE

CEILING MOUNTED SECURITY CAMERA

(DOME TYPE)

S

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

321 4 5 6 7 8 9 10

EXPAND PRIMARY CARE

OSCAR G. JOHNSON VA MEDICAL CENTER

325 H STREET,

IRON MOUNTAIN, MI 49801

ARCHITECT/ENGINEER

310 Pine Street | Green Bay, WI 54301 920-432-4865 | www.bernersschober.com

FULLY SPRINKLERED

KEY PLAN

Comm. Number: 5700.16

DECEMBER 4, 2020

585-336

U.S. Department of Veterans Affairs

100% DESIGN SUBMITTAL

Revisions: Date:

CONSULTANT

Architecture | Planning | Interior Design

2224 S. Michigan Ave. | Suite 1400 Chicago, Illinois 60604-2595

(312)-554-1400

65% SUBMITTAL 04/28/2020

ZONE 1

ZONE 2

ZONE 3

ZONE 4

project number: 1180742

95% SUBMITTAL 07/24/2020

100% SUBMITTAL 12/04/2020

B

IM

/V

A G

L H

S E x p a n d P ri m a ry

C a re /V

A A

R C

H .r v t

/1 /2

:2

:3

P M

DPD JAP

AE151-3

1ST FLOOR REFLECTED CEILING PLAN

- ZONE 3

DWG. 35 OF 147

N

1/4" = 1'-0"AE151-3

1ST FLOOR REFLECTED CEILING PLAN - ZONE 3F1

GYP

8' - 0"

P1

ACT

9' - 0" 2x2

ACT

9' - 0"

2x2

ACT

9' - 0"

2x2

ACT

9' - 0" 2x2

/F1 AE151-1/F1 AE151-3/F1 AE151-3

/F1 AE151-2

F

A

E

-2

F

A

E

-2

F

A

E

-1

F

A

E

-3

(NO WORK)

(NO WORK)

(NO WORK)

(NO WORK)

E2

AE501

E2

AE501

D1

AE501

EXPANSION JOINT TO MATCH

LOCATION AND WIDTH OF

EXISTING FLOOR JOINT

MODIFY EXISTING 8'-4" CEILING

AND TRADES EQUIPMENT TO

ACCOMMODATE NEW SOFFIT

MODIFY EXISTING 8'-4" CEILING

AND TRADES EQUIPMENT TO

ACCOMMODATE NEW SOFFIT

W

IT

H F

P T

R A

D E

V

E R

IF

Y

E2

AE501

GYP

8' - 0"

PT

PAINT SOFFIT TO MATCH

ADJACENT SOFFIT

V

E R

IF

Y

W

IT

H P

L U

M B

IN

G

A

N D

F P

T R

A D

E S

1. UNLESS DIMENSIONED OTHERWISE ON THIS PLAN, CEILINGS

GRIDS ARE CENTERED IN ROOM IN BOTH DIRECTIONS.

2. SEE I001 FOR CEILING FINISH TYPE

3. COORDINATE/VERIFY LOCATION OF CEILING MOUNTED LIGHTS

WITH OWNER PRIOR TO INSTALLATION OF SUPPORT STRUCTURE.

4. WHERE EXISTING PARTITIONS ARE SHOWN TO HAVE A FIRE OR

SMOKE RATING, THE CONTRACTOR SHALL PROVIDE THE

REQUIRED PENETRATION PROTECTION FOR ALL NEW

PENETRATIONS THROUGH THE PARTITION. REPORT ANY

EXISTING VOIDS WHICH REQUIRE PATCHING, UNDER ADDITIONAL

SCOPE OF WORK.

5. CONTRACT WORK INCLUDES ALL CEILING MOUNTED ITEMS OR

DEVICES SHOWN ON THIS PLAN AND AS SHOWN ON THE PLANS

OF OTHER TRADES. THIS DRAWING DOES NOT RELIEVE

CONTRACTOR'S RESPONSIBILITY TO INDIVIDUALLY COORDINATE

THEIR WORK WITH OTHER TRADES.

GENERAL CEILING PLAN NOTES:

ARCHITECTURAL REFLECTED

CEILING PLAN NOTES

ACOUSTICAL TILE CEILINGS

GYPSUM BOARD CEILINGS

CEILING HEIGHT (PARENTHESIS INDICATES

EXISTING CEILING HEIGHT)

CEILING TYPE/FINISH

CEILING MATERIAL

ACT: ACOUSTICAL TILE CEILING

ESA: EXPOSED STRUCTURE ABOVE

GYP: GYPSUM BOARD

SMP: PAINTABLE SHEET METAL PANELS BY

MECHANICAL TRADE

CEILING HEIGHT (PARENTHESIS

INDICATES EXISTING CEILING HEIGHT)

8'-0"

8'-0"

MATERIAL AND SYMBOLS LEGEND:

INDICATES LOCATION OF CUT CEILING TILES

REQUIRED TO CENTER GRID PATTERNS IN

CORRIDORS

CUBICLE TRACK

STAIR, SHAFT, OR HAZARDOUS AREA SEPARATION

WALLS: 2 HOUR FIRE

DOORS: 90 MINUTE FIRE

OPENINGS: NOT PERMITTED

DAMPERS: 90 MINUTE FIRE

FIRE COMPARTMENT DIVISON

WALLS: 2 HOUR FIRE AND SMOKE RESISTANT

DOORS: 90 MINUTE FIRE AND SMOKE RESISTANT

OPENINGS: NOT PERMITTED

DAMPERS: 90 MINUTE FIRE AND SMOKE RESISTANT

STAIR, SHAFT, OR HAZARDOUS AREA SEPARATION

WALLS: 1 HOUR FIRE

DOORS: 45 MINUTE FIRE

OPENINGS: 45 MINUTE PROTECTION

DAMPERS: 90 MINUTE FIRE AT NON-SPRINKLED

SMOKE COMPARTMENT DIVISON

WALLS: 1 HOUR FIRE AND SMOKE RESISTANT

DOORS: 20 MINUTE CONSTRUCTION AND SMOKE RESISTANT

OPENINGS: 20 MINUTE PROTECTION,

45 MINUTE AT 1 HOUR RATED ROOMS

DAMPERS: SMOKE RESISTANT

(IN NEW CONSTRUCTION REQUIRED BY IBC)

ONE HOUR SMOKE RESISTANT PARTITION

(NON-SPRINKLED COMPARTEMENT)

WALLS: 1 HOUR FIRE AND SMOKE RESISTANT

DOORS: 20 MINUTE CONSTRUCTION AND SMOKE RESISTANT

OPENINGS: 20 MINUTE PROTECTION

SMOKE RESISTANT PARTITION (SPRINKLED COMPARTMENT)

WALLS: SMOKE RESISTANT

DOORS: SMOKE RESISTANT AND POSITIVE LATCHING,

(EXCEPT TOILET ROOMS, ECT.)

OPENINGS: CANNOT EXCEED 80 SQ. IN. WITHOUT PROTECTION

FIRE SEPARATION LEGEND

SYMBOLS KEY

HVAC

FIRE PROTECTION

ARCHITECTURAL

ACCESS PANEL

RETURN GRILLE

SUPPLY DIFFUSER

RETURN GRILLE

SUPPLY DIFFUSER

GYPSUM BOARD CEILING

AP

PAINTED SHEET METAL PANELP.

CONCEALED PENDENT SPRINKLER HEAD

CEILING COORDINATION

PLAN LEGEND

EXHAUST GRILLE

SUPPLY DIFFUSER

PENDENT SPRINKLER HEAD

OS

S

S

S

N

2X4 LIGHT FIXTURE -

RECESSED / SURFACE

RECESSED DOWNLIGHT,

SURFACE / PENDANT

1X4 LIGHT FIXTURE -

RECESSED / SURFACE

EXIT SIGN - SINGLE / DOUBLE FACE

OCCUPANCY SENSOR

CEILING MOUNTED SPEAKER / STROBE

SMOKE DETECTOR

SPEAKER RECESSED

SPEAKER SURFACE

WIRELESS DATA ACCESS POINT

CORRIDOR DOME LIGHT

ELECTRICAL

2X2 LIGHT FIXTURE -

RECESSED / SURFACE

CEILING MOUNTED SECURITY CAMERA

(DOME TYPE)

S

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

321 4 5 6 7 8 9 10

EXPAND PRIMARY CARE

OSCAR G. JOHNSON VA MEDICAL CENTER

325 H STREET,

IRON MOUNTAIN, MI 49801

ARCHITECT/ENGINEER

310 Pine Street | Green Bay, WI 54301 920-432-4865 | www.bernersschober.com

FULLY SPRINKLERED

KEY PLAN

Comm. Number: 5700.16

DECEMBER 4, 2020

585-336

U.S. Department of Veterans Affairs

100% DESIGN SUBMITTAL

Revisions: Date:

CONSULTANT

Architecture | Planning | Interior Design

2224 S. Michigan Ave. | Suite 1400 Chicago, Illinois 60604-2595

(312)-554-1400

65% SUBMITTAL 04/28/2020

ZONE 1

ZONE 2

ZONE 3

ZONE 4

project number: 1180742

95% SUBMITTAL 07/24/2020

100% SUBMITTAL 12/04/2020

B

IM

/V

A G

L H

S E x p a n d P ri m a ry

C a re /V

A A

R C

H .r v t

/1 /2

:2

:4

P M

DPD JAP

AE151-4

1ST FLOOR REFLECTED CEILING PLAN

- ZONE 4

DWG. 36 OF 147

N

1/4" = 1'-0"AE151-4

1ST FLOOR REFLECTED CEILING PLAN - ZONE 4F1

EXPOSED

CEILING

EXPOSED

CEILING

GYP

7' - 10" P8

GYP

7' - 10"

P1

ACT

8' - 0"

ACT

9' - 0"

GYP

8' - 0" P1

GYP

9' - 0"

EP2

GYP

9' - 0"

EP2

ACT

9' - 0"

GYP

9' - 0"

PT8

ST-1

2413 2414

2499 2498

24972496

ACT

9' - 0"

ACT

9' - 0"

ACT

9' - 0"

ACT

9' - 0"

ACT

9' - 0"

ACT

9' - 0"

ACT

9' - 0"

ACT

8' - 6"

ACT

9' - 0"

ACT

9' - 0"

ACT

8' - 6"

ACT

9' - 0"

4ACT

9' - 0"

ACT

9' - 8"

EXPOSED

CEILING

GYP

9' - 0"

EP2

EXPANSION

JOINT COVER

GYP

8' - 0"

P1

SOFFIT ABOVE AT

PENTHOUSE ROOF

E2

AE501

E2

AE501

E2

AE501

E2

AE501

E2

AE501

E2

AE501

GYP

8' - 5"

GYP

8' - 9 3/4"

ACT

8' - 6"

GYP

8' - 5" P8

D1

AE501

E2

AE701

GYP

8' - 0"

P1

TYP.

2'-0"

E3

AE501

D9

AE505

E2

AE505

D2

AE505

D9

AE505

B9

AE505

C2

AE505

ALIGN GRID WITH

WALL CORNER

GYP

7' - 11"

P8

E3

AE501

/2

1. UNLESS DIMENSIONED OTHERWISE ON THIS PLAN, CEILINGS

GRIDS ARE CENTERED IN ROOM IN BOTH DIRECTIONS.

2. SEE I001 FOR CEILING FINISH TYPE

3. COORDINATE/VERIFY LOCATION OF CEILING MOUNTED LIGHTS

WITH OWNER PRIOR TO INSTALLATION OF SUPPORT STRUCTURE.

4. WHERE EXISTING PARTITIONS ARE SHOWN TO HAVE A FIRE OR

SMOKE RATING, THE CONTRACTOR SHALL PROVIDE THE

REQUIRED PENETRATION PROTECTION FOR ALL NEW

PENETRATIONS THROUGH THE PARTITION. REPORT ANY

EXISTING VOIDS WHICH REQUIRE PATCHING, UNDER ADDITIONAL

SCOPE OF WORK.

5. CONTRACT WORK INCLUDES ALL CEILING MOUNTED ITEMS OR

DEVICES SHOWN ON THIS PLAN AND AS SHOWN ON THE PLANS

OF OTHER TRADES. THIS DRAWING DOES NOT RELIEVE

CONTRACTOR'S RESPONSIBILITY TO INDIVIDUALLY COORDINATE

THEIR WORK WITH OTHER TRADES.

GENERAL CEILING PLAN NOTES:

ARCHITECTURAL REFLECTED

CEILING PLAN NOTES

ACOUSTICAL TILE CEILINGS

GYPSUM BOARD CEILINGS

CEILING HEIGHT (PARENTHESIS INDICATES

EXISTING CEILING HEIGHT)

CEILING TYPE/FINISH

CEILING MATERIAL

ACT: ACOUSTICAL TILE CEILING

ESA: EXPOSED STRUCTURE ABOVE

GYP: GYPSUM BOARD

SMP: PAINTABLE SHEET METAL PANELS BY

MECHANICAL TRADE

CEILING HEIGHT (PARENTHESIS

INDICATES EXISTING CEILING HEIGHT)

8'-0"

8'-0"

MATERIAL AND SYMBOLS LEGEND:

INDICATES LOCATION OF CUT CEILING TILES

REQUIRED TO CENTER GRID PATTERNS IN

CORRIDORS

CUBICLE TRACK

STAIR, SHAFT, OR HAZARDOUS AREA SEPARATION

WALLS: 2 HOUR FIRE

DOORS: 90 MINUTE FIRE

OPENINGS: NOT PERMITTED

DAMPERS: 90 MINUTE FIRE

FIRE COMPARTMENT DIVISON

WALLS: 2 HOUR FIRE AND SMOKE RESISTANT

DOORS: 90 MINUTE FIRE AND SMOKE RESISTANT

OPENINGS: NOT PERMITTED

DAMPERS: 90 MINUTE FIRE AND SMOKE RESISTANT

STAIR, SHAFT, OR HAZARDOUS AREA SEPARATION

WALLS: 1 HOUR FIRE

DOORS: 45 MINUTE FIRE

OPENINGS: 45 MINUTE PROTECTION

DAMPERS: 90 MINUTE FIRE AT NON-SPRINKLED

SMOKE COMPARTMENT DIVISON

WALLS: 1 HOUR FIRE AND SMOKE RESISTANT

DOORS: 20 MINUTE CONSTRUCTION AND SMOKE RESISTANT

OPENINGS: 20 MINUTE PROTECTION,

45 MINUTE AT 1 HOUR RATED ROOMS

DAMPERS: SMOKE RESISTANT

(IN NEW CONSTRUCTION REQUIRED BY IBC)

ONE HOUR SMOKE RESISTANT PARTITION

(NON-SPRINKLED COMPARTEMENT)

WALLS: 1 HOUR FIRE AND SMOKE RESISTANT

DOORS: 20 MINUTE CONSTRUCTION AND SMOKE RESISTANT

OPENINGS: 20 MINUTE PROTECTION

SMOKE RESISTANT PARTITION (SPRINKLED COMPARTMENT)

WALLS: SMOKE RESISTANT

DOORS: SMOKE RESISTANT AND POSITIVE LATCHING,

(EXCEPT TOILET ROOMS, ECT.)

OPENINGS: CANNOT EXCEED 80 SQ. IN. WITHOUT PROTECTION

FIRE SEPARATION LEGEND

SYMBOLS KEY

HVAC

FIRE PROTECTION

ARCHITECTURAL

ACCESS PANEL

RETURN GRILLE

SUPPLY DIFFUSER

RETURN GRILLE

SUPPLY DIFFUSER

GYPSUM BOARD CEILING

AP

PAINTED SHEET METAL PANELP.

CONCEALED PENDENT SPRINKLER HEAD

CEILING COORDINATION

PLAN LEGEND

EXHAUST GRILLE

SUPPLY DIFFUSER

PENDENT SPRINKLER HEAD

OS

S

S

S

N

2X4 LIGHT FIXTURE -

RECESSED / SURFACE

RECESSED DOWNLIGHT,

SURFACE / PENDANT

1X4 LIGHT FIXTURE -

RECESSED / SURFACE

EXIT SIGN - SINGLE / DOUBLE FACE

OCCUPANCY SENSOR

CEILING MOUNTED SPEAKER / STROBE

SMOKE DETECTOR

SPEAKER RECESSED

SPEAKER SURFACE

WIRELESS DATA ACCESS POINT

CORRIDOR DOME LIGHT

ELECTRICAL

2X2 LIGHT FIXTURE -

RECESSED / SURFACE

CEILING MOUNTED SECURITY CAMERA

(DOME TYPE)

S

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

321 4 5 6 7 8 9 10

EXPAND PRIMARY CARE

OSCAR G. JOHNSON VA MEDICAL CENTER

325 H STREET,

IRON MOUNTAIN, MI 49801

ARCHITECT/ENGINEER

310 Pine Street | Green Bay, WI 54301 920-432-4865 | www.bernersschober.com

FULLY SPRINKLERED

KEY PLAN

Comm. Number: 5700.16

DECEMBER 4, 2020

585-336

U.S. Department of Veterans Affairs

100% DESIGN SUBMITTAL

Revisions: Date:

CONSULTANT

Architecture | Planning | Interior Design

2224 S. Michigan Ave. | Suite 1400 Chicago, Illinois 60604-2595

(312)-554-1400

65% SUBMITTAL 04/28/2020

ZONE 1

ZONE 2

ZONE 3

ZONE 4

project number: 1180742

95% SUBMITTAL 07/24/2020

100% SUBMITTAL 12/04/2020

B

IM

/V

A G

L H

S E x p a n d P ri m a ry

C a re /V

A A

R C

H .r v t

/1 /2

:2

:1

P M

DPD JAP

AE152-1

2ND FLOOR REFLECTED CEILING PLAN

- ZONE 1

DWG. 37 OF 147

N

1/4" = 1'-0"AE152-1

2ND FLOOR REFLECTED CEILING PLAN - ZONE 1F1

FIRST FLOOR

1148' - 0"

SECOND FLOOR

1161' - 0"

ROOF DECK

1175' - 0"

D.0C.0

BASEMENT

1137' - 0"

B.0

PARAPET

1178' - 11 1/2"

C6

AE301

EXISTING -

PENTHOUSE

PARAPET

1189' - 8 3/4"

EGRESS

LANDING

1142' - 0"

PRECAST ARCHITECTURAL

CONCRETE TO MATCH EXISTING

BRICK TO MATCH EXISTING

NEW RETAINING

WALL - SEE

SHEET C100

F6

AE301

F3

AE351

F7

AE351

A B.4

22'-0" 4'-0"

C.J. C.J.

C.J.

BUILDING

SECTION

6'-0" W X 4'-0" H

BLAST RATED

LOUVER

C.J. SEE TYP.--------------

B5

AE503

BUILDING

SECTION

WALL

SECTION

WALL

SECTION

F6

AE503

F8

AE503

6'-0" W X 4'-0" H

BLAST RATED

LOUVER

B

B

A

GUARDRAIL -

SEE SHEET C100

GUARDRAIL -

SEE SHEET C100

EXISTING

(NOT SHOWN

FOR CLARITY) NEW WORK

6'-0" 4'-0" 7'-0" 4'-0" 4'-0" 4'-0"

1139' - 4"

C2

AE502

2'-0"

F8

AE602

F9

AE602

C9

AE502

B3

AE502

BRICK LEDGE RISE IS 8", TYP. UNO

1140' - 0"1

3" BLAST RESISTANT

INSULATED METAL

WALL PANEL

FIRST FLOOR

1148' - 0"

SECOND FLOOR

1161' - 0"

ROOF DECK

1175' - 0"

0.0

BASEMENT

1137' - 0"

C2

AE301

PARAPET

1178' - 11 1/2"

EXISTING -

PENTHOUSE

PARAPET

1189' - 8 3/4"

0.5

F9

AE351

PRECAST ARCHITECTURAL

CONCRETE TO MATCH EXISTING

BRICK TO MATCH EXISTING

REMOVE AND

REPLACE BOLLARD

EXISTING DRIVEWAY

TO REMAIN

EXISTING

GARAGE TO

REMAIN

0.80.7 F4

AE352

EXISTING

PRECAST

4'-0" 24'-0"

C.J. C.J.

BUILDING

SECTION WALL

SECTION

WALL

SECTION

NEW FLASHING

EXISTING

(NOT SHOWN

FOR CLARITY)NEW WORK

E5

AE502

LOCATION OF

MOVED LADDER

RELOCATED LOUVER IN

EXISTING WALL, MATCH

ELEVATION OF EXISTING

LOUVER, LINE WITH EDGE

OF EXISTING DOOR

C9

AE502

3" BLAST RESISTANT

INSULATED METAL

WALL PANEL

FIRST FLOOR

1148' - 0"

SECOND FLOOR

1161' - 0"

ROOF DECK

1175' - 0"

2.7 0.0

BASEMENT

1137' - 0"

C2

AE301

1.5

PARAPET

1178' - 11 1/2"

EXISTING -

PENTHOUSE

PARAPET

1189' - 8 3/4"

0.5

EGRESS

LANDING

1142' - 0"

F2

AE301

F5

AE351

12347 56 F1

AE352

PRECAST ARCHITECTURAL

CONCRETE TO MATCH EXISTING

BRICK TO MATCH EXISTING

19'-4" W X 5'-2" H

NEW LOUVER IN

EXISTING WALL

EXISTING

ELEVATION

EXISTING

TRANSFORMERS

TO REMAIN

INFILL

REMOVED

LOUVER

1.3 0.8 0.7

4'-0"16'-0"4'-0" 16'-0" 15'-8"

C.J. C.J. C.J.C.J.C.J.C.J.

5'-4" W X 4'-0" H

BLAST RATED

LOUVER

BUILDING

SECTION

WALL

SECTION

WALL

SECTION

BUILDING

SECTION

C

16'-0"19'-8"10'-0" 20'-0" 5'-8" 25'-0"

1139' - 4"

8"

F8

AE602

AE502

C2

AE502

C2

F6

AE602

F2

AE503

-------------- SIM.

TYP.

C2

AE505

C9

AE502

BRICK LEDGE RISE IS 8", TYP.

FIRST FLOOR

1148' - 0"

SECOND FLOOR

1161' - 0"

ROOF DECK

1175' - 0"

D.0 C.0 A.3

BASEMENT

1137' - 0"

PARAPET

1178' - 11 1/2"

C6

AE301

EXISTING -

PENTHOUSE

PARAPET

1189' - 8 3/4"

EGRESS

LANDING

1142' - 0"

F6

AE301

F7

AE351

B CR P O N

PRECAST ARCHITECTURAL

CONCRETE TO MATCH EXISTING

BRICK TO MATCH EXISTING

EXISTING

GARAGE TO

REMAIN

EXISTING

ELEVATION

EXISTING

MECHANICAL

LOUVER

B.4 A.9

E.J. EXISTING PRECAST

AND STONE STRING

COURSE

EXISTING

PRECAST

2'-4" 9'-8" 18'-0" 18'-4" 6'-8" 4'-0"

C.J. C.J. C.J.C.J. C.J.

BUILDING

SECTION

WALL

SECTION

BUILDING

SECTION

6'-0" W X 4'-0" H

BLAST RATED

LOUVER

E7

AE501

E7

AE501

E7

AE501

D

D

10'-0" 6'-0" 6'-0" 6'-0" 6'-0" 6'-0" 6'-0" 6'-0"

F9

AE602

C2

AE502

F3

AE352

WALL

SECTION

B3

AE502

C9

AE502

BRICK LEDGE RISE IS 8", TYP.

3" BLAST RESISTANT

INSULATED METAL

WALL PANEL

BOTTOM OF STUB WALL,

TYP. (DASHED LINE)

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

321 4 5 6 7 8 9 10

EXPAND PRIMARY CARE

OSCAR G. JOHNSON VA MEDICAL CENTER

325 H STREET,

IRON MOUNTAIN, MI 49801

ARCHITECT/ENGINEER

310 Pine Street | Green Bay, WI 54301 920-432-4865 | www.bernersschober.com

FULLY SPRINKLERED

Comm. Number: 5700.16

DECEMBER 4, 2020

585-336

U.S. Department of Veterans Affairs

100% DESIGN SUBMITTAL

Revisions: Date:

CONSULTANT

Architecture | Planning | Interior Design

2224 S. Michigan Ave. | Suite 1400 Chicago, Illinois 60604-2595

(312)-554-1400

65% SUBMITTAL 04/28/2020

project number: 1180742

95% SUBMITTAL 07/24/2020

100% SUBMITTAL 12/04/2020

B

IM

/V

A G

L H

S E x p a n d P ri m a ry

C a re /V

A A

R C

H .r v t

/1 /2

:2

:2

P M

DPD JAP

AE201

EXTERIOR ELEVATIONS

DWG. 38 OF 147

1/8" = 1'-0"AE201

C7 WEST BUILDING ELEVATION

1/8" = 1'-0"AE201

F7 NORTH BUILDING ELEVATION

1/8" = 1'-0"AE201

C1 SOUTH BUILDING ELEVATION

1/8" = 1'-0"AE201

F3 EAST BUILDING ELEVATION

4'0 8' 12'2' 4'0 8' 12'2'

4'0 8' 12'2'4'0 8' 12'2'

1'-6"1'-9"

3'-8"

HOOK (CC)

HOOK (CC)

HAND SANITIZER (VC)

HOOK (CC)

HOOK (CC)

1'-5" 8" 7"

F

1'-2"

PL1

SS1

PL1

SHARPS

CONTAINER (VC)

PAPER TOWEL

DISPENSER (VC)

SOAP

DISPENSER (VC)

CCB

SINK BY PLUMBING

TRADE

SA

C8

AE601

BLOCKING AT CUBICLE

TRACK ENDS, TYP. SEE

3'-5"

F3

AE701

GLOVES DISPENSER

(VC)

3'-0"

BACKING ABOVE TILE

FOR CUBICLE TRACK

SUPPORT, TYP.

BLOCKING AT CUBICLE

TRACK ENDS, TYP. SEE

C8

AE601

MIRROR, 18x60 (CC)

EQ EQ

C8

AE601

BLOCKING AT CUBICLE

TRACK ENDS, TYP. SEE

OPEN

BEYOND

2724 F

F

PL1

PL1

PL1

PL2

CG1

F

F

PL1

PL1

PL1

PL2

INTERIOR ELEVATION NOTES

1. REFER TO TYPICAL MOUNTING HEIGHTS SHEET G003

2. REFER TO ROOM FINISH SCHEDULE FOR ADDITIONAL FINISH

INFORMATION

3. FOR CASEWORK LEGEND, SEE SHEET AE701

4. EQUIPMENT DESIGNATION AS FOLLOWS (U.N.O.):

VV - VA PROVIDED / VA INSTALLED

VC - VA PROVIDED / CONTRACTOR INSTALLED

CC - CONTRACTOR PROVIDED / CONTRACTOR INSTALLED

SOAP DISPENSER (VC)

PAPER TOWEL

DISPENSER (VC)

1'-5" 9" 7"

F

PL1

SS1

SINK BY

PLUMBING TRADE

2734 2434

F3

AE701

2'-8"

1'-3" 1'-7" 2'-0"

STAINLESS STEEL SINK

W/ INTEGRAL

EYE-WASH

PAPER TOWEL

DISPENSER (VC)

SHARPS CONTAINER

(VC)

4'-0"

SA

CBKS

SS1

SINK BY

PLUMBING TRADEF3

AE701

3'-0"

GLOVES DISPENSER

(VC)

SOAP DISPENSER (VC)

1'-0"

MOP AND BROOM

HOLDER (CC)

EQ EQ

1'-9"

CHEMICAL DISPENSER

(VC)

10"1'-6"

MIRROR, 24x36 (CC)

TOILET SEAT COVER

DISPENSER (CC)

3-PIECE GRAB BAR

(CC)

PAPER TOWEL

DISPENSER (VC)

EQ EQ

FIXTURE WALL, SEE

INTERIOR SHEETS

1'-0"

SOAP DISPENSER (VC)

TILE WAINSCOT, SEE

INTERIOR SHEETS

1'-9"

2'-8"

HOOK (CC)

BABY CHANGING STATION (CC)

HOOK (CC)

(PATIENT TOILETS ONLY)

TILE WAINSCOT, SEE

INTERIOR SHEETS1'-6"

SANITARY NAPKIN

DISPOSAL (CC)

3-PIECE GRAB BAR

(CC)

SANITARY NAPKIN

DISPENSER (CC)

1'-8"

TILE WAINSCOT, SEE

INTERIOR SHEETS

TOILET TISSUE

DISPENSER (VC)

1'-5" 1'-8" 8"

GLOVES DISPENSER

(VC)

PAPER TOWEL

DISPENSER (VC)

SOAP DISPENSER (VC)

F

PL1

1'-3"

SHARPS CONTAINER

(VC)

C8

AE601

BLOCKING AT CUBICLE

TRACK ENDS, TYP. SEE

1'-6"

HOOK (CC)

HOOK (CC)

CG1

OPEN

BEYOND

6" 3'-0" 2'-6"

GRAB BAR, 36" VERT.

(CC)

GRAB BAR, 36" VERT.

(CC)

8"

GRAB BAR, 36" VERT.

(CC)

OPEN

BEYOND

CG1

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

321 4 5 6 7 8 9 10

EXPAND PRIMARY CARE

OSCAR G. JOHNSON VA MEDICAL CENTER

325 H STREET,

IRON MOUNTAIN, MI 49801

ARCHITECT/ENGINEER

310 Pine Street | Green Bay, WI 54301 920-432-4865 | www.bernersschober.com

FULLY SPRINKLERED

Comm. Number: 5700.16

DECEMBER 4, 2020

585-336

U.S. Department of Veterans Affairs

100% DESIGN SUBMITTAL

Revisions: Date:

CONSULTANT

Architecture | Planning | Interior Design

2224 S. Michigan Ave. | Suite 1400 Chicago, Illinois 60604-2595

(312)-554-1400

65% SUBMITTAL 04/28/2020

project number: 1180742

95% SUBMITTAL 07/24/2020

100% SUBMITTAL 12/04/2020

B

IM

/V

A G

L H

S E x p a n d P ri m a ry

C a re /V

A A

R C

H .r v t

/1 /2

:2

:4

P M

DPD JAP

AE251

INTERIOR ELEVATIONS

DWG. 39 OF 147

1/2" = 1'-0"AE251

F9 EXAM - NORTH

1/2" = 1'-0"AE251

F7 EXAM - EAST

1/2" = 1'-0"AE251

F5 EXAM - SOUTH

1/2" = 1'-0"AE251

F3 EXAM - WEST

1/2" = 1'-0"AE251

F1 TEAMLET WORKSTATIONS - SOUTH

1/2" = 1'-0"AE251

E8 TEAMLET WORKSTATIONS - EAST

1/2" = 1'-0"AE251

E7 REFRESHMENT ALCOVE - WEST

1/2" = 1'-0"AE251

E5 SOILED HOLDING - WEST

1/2" = 1'-0"AE251

E3 SOILED HOLDING - EAST

1/2" = 1'-0"AE251

E2 SOILED HOLDING - SOUTH

1/2" = 1'-0"AE251

C7 HOUSEKEEPING CLOSET - WEST

1/2" = 1'-0"AE251

C8 HOUSEKEEPING CLOSET - NORTH

1/2" = 1'-0"AE251

C5 TYPICAL TOILET - EAST

1/2" = 1'-0"AE251

C4 TYPICAL TOILET - SOUTH

1/2" = 1'-0"AE251

C2 TYPICAL TOILET - WEST

1/2" = 1'-0"AE251

C1 TYPICAL TOILET - NORTH

1/2" = 1'-0"AE251

B7 TRIAGE - WEST

1/2" = 1'-0"AE251

B6 TRIAGE - NORTH

1/2" = 1'-0"AE251

B4 H/W SCALE ALCOVE - NORTH

1/2" = 1'-0"AE251

B3 H/W SCALE ALCOVE - EAST

1/2" = 1'-0"AE251

B1 H/W SCALE ALCOVE - SOUTH

0 1' 2' 3'6" 0 1' 2' 3'6" 0 1' 2' 3'6" 0 1' 2' 3'6" 0 1' 2' 3'6"

0 1' 2' 3'6" 0 1' 2' 3'6" 0 1' 2' 3'6" 0 1' 2' 3'6" 0 1' 2' 3'6" 0 1' 2' 3'6"

0 1' 2' 3'6" 0 1' 2' 3'6" 0 1' 2' 3'6" 0 1' 2' 3'6" 0 1' 2' 3'6"

INTERIOR ELEVATION NOTES

1. REFER TO TYPICAL MOUNTING HEIGHTS SHEET G003

2. REFER TO ROOM FINISH SCHEDULE FOR ADDITIONAL FINISH

INFORMATION

3. FOR CASEWORK LEGEND, SEE SHEET AE701

4. EQUIPMENT DESIGNATION AS FOLLOWS (U.N.O.):

VV - VA PROVIDED / VA INSTALLED

VC - VA PROVIDED / CONTRACTOR INSTALLED

CC - CONTRACTOR PROVIDED / CONTRACTOR INSTALLED

HOOK (CC)

HOOK (CC)

HOOK (CC)

HOOK (CC)

MIRROR, 18x60 (CC)

1'-6" EQ EQ 1'-6"

1'-9"

PAPER TOWEL

DISPENSER (VC)

SOAP DISPENSER (VC)

HOOK (CC)

HOOK (CC)

F

8" 1'-8"

1'-3"

PL1

HAND SANITIZER (VC)

1'-2"

1'-5" 1'-6" 8"

SOAP DISPENSER (VC)

PAPER TOWEL

DISPENSER (VC)

SHARPS CONTAINER

(VC)

HOOK (CC)

HOOK (CC)

F

1'-6"

BLOCKING AT CUBICLE

TRACK ENDS, TYP. SEE

C8

AE601

PL1

1'-9"

3'-2"

GLOVES DISPENSER

(VC)

EQ EQ

HAND SANITIZER (VC)

MIRROR, 18x60 (CC)

BLOCKING AT CUBICLE

TRACK ENDS, TYP. SEE

C8

AE601

3'-10"

EQ 4'-0" EQ

SLIDESLIDE

EQ4'-0"EQ

SLIDESLIDE

SA

CB KS

1'-4" 3'-9"

G

WM

PL2

PL2

1'-4"3'-9"

CB

SA

G

SA SA

KS

WM

CB CB

F2

AE701

F2

AE701

AE701

E2

2'-1"

4'-0"

G

KS

CB

SA

WM

PL2

4'-2"

F

F

24243034

PL1

PL1

PL1

PL2

2'-1"

SA

CB KS

4'-0"

G

WM

PL2

4'-2"

8"

GRAB BAR, 36" VERT.

(CC)

OPEN

BEYOND

CG1

EQ EQ

HOOK (CC)

HOOK (CC)

1'-6"

MIRROR, 24x36 (CC)

3-PIECE GRAB BAR

(CC)

TOILET SEAT COVER

DISPENSER (CC)

PAPER TOWEL

DISPENSER (VC)

1'-10"1'-4"

FIXTURE WALL, SEE

INTERIOR SHEETS

7"8"1'-4"

PAPER TOWEL

DISPENSER (VC)

SOAP DISPENSER (VC)

2'-6"

KS

SA

PL1PL1 SS1

3034 3034 3034 3034

3024 3024 3024

F3

AE701

SINK BY

PLUMBING TRADE

A L

IG

N 1'-6"

HOOK (CC)

HOOK (CC)

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

321 4 5 6 7 8 9 10

EXPAND PRIMARY CARE

OSCAR G. JOHNSON VA MEDICAL CENTER

325 H STREET,

IRON MOUNTAIN, MI 49801

ARCHITECT/ENGINEER

310 Pine Street | Green Bay, WI 54301 920-432-4865 | www.bernersschober.com

FULLY SPRINKLERED

Comm. Number: 5700.16

DECEMBER 4, 2020

585-336

U.S. Department of Veterans Affairs

100% DESIGN SUBMITTAL

Revisions: Date:

CONSULTANT

Architecture | Planning | Interior Design

2224 S. Michigan Ave. | Suite 1400 Chicago, Illinois 60604-2595

(312)-554-1400

65% SUBMITTAL 04/28/2020

project number: 1180742

95% SUBMITTAL 07/24/2020

100% SUBMITTAL 12/04/2020

B

IM

/V

A G

L H

S E x p a n d P ri m a ry

C a re /V

A A

R C

H .r v t

/1 /2

:2

:0

P M

DPD JAP

AE252

INTERIOR ELEVATIONS

DWG. 40 OF 147

1/2" = 1'-0"AE252

F8 MH OFFICE - WEST

1/2" = 1'-0"AE252

F7 CLINICAL PHARM - EAST

1/2" = 1'-0"AE252

F5 CLINICAL PHARM - EAST

1/2" = 1'-0"AE252

F3 TELEHEALTH EXAM - NORTH

1/2" = 1'-0"AE252

F1 TELEHEALTH EXAM - EAST

1/2" = 1'-0"AE252

E9 TELEHEALTH EXAM - SOUTH

1/2" = 1'-0"AE252

E7 TELEHEALTH EXAM - WEST

1/2" = 1'-0"AE252

E6 TELEHEALTH WORKROOM - NORTH1

1/2" = 1'-0"AE252

E3 TELEHEALTH WORKROOM - EAST

1/2" = 1'-0"AE252

E1 TELEHEALTH WORKROOM - SOUTH

1/2" = 1'-0"AE252

C7 TELEHEALTH WORKROOM - WEST

1/2" = 1'-0"AE252

C6 H/W SCALE ALCOVE - SOUTH

1/2" = 1'-0"AE252

C5 H/W SCALE ALCOVE - WEST

1/2" = 1'-0"AE252

C3 PATIENT TOILET - SOUTH

1/2" = 1'-0"AE252

C1 HBPC WORKROOM - NORTH

1/2" = 1'-0"AE252

B7 TYPICAL OFFICE - EAST

0 1' 2' 3'6"

0 1' 2' 3'6" 0 1' 2' 3'6" 0 1' 2' 3'6" 0 1' 2' 3'6" 0 1' 2' 3'6"

SECOND FLOOR

1161' - 0"

ROOF DECK

1175' - 0"

D.0C.0A.3

BASEMENT

1137' - 0"

PARAPET

1178' - 11 1/2"

EGRESS

LANDING

1142' - 0"

OFFICE

(NURSE

MANAGER)

RECEPTION

OFFICE

(TELEHEALTH)

CORRIDOR

ELECTRICAL

ROOM

ELECTRICAL

ROOM

CORRIDOR

CORRIDOR

STAIR

ST-1

PIPE

BASEMENT

B001

B.4A.9

AE351

F9

3 1/2" SPRAY INSULATION AT

FIRST FLOOR DECK, APPLY

AFTER FIRE PROOFING

FIRST FLOOR

1148' - 0"

SECOND FLOOR

1161' - 0"

ROOF DECK

1175' - 0"

2.7 0.0

BASEMENT

1137' - 0"

1.5

PARAPET

1178' - 11 1/2"

EXISTING -

PENTHOUSE

PARAPET

1189' - 8 3/4"

0.5

EGRESS

LANDING

1142' - 0"

EXISTING -

PENTHOUSE

ROOF DECK

1186' - 0"

STAIR

ST-1

CORRIDOR

HBPC

WORKROOM

TELEHEALTH

EXAM

HALLWAY

TELEHEALTH

EXAM

EXAM

CORRIDOR

TEAMLET

WORKSTATIONS

MEDICAL

EQUIPMENT

STORAGE

PIPE

BASEMENT

B001

23 1.3 0.8 0.7

AE351

F5

AE352

F3

AE352

F3

12 2

FIRST FLOOR

1148' - 0"

SECOND FLOOR

1161' - 0"

ROOF DECK

1175' - 0"

D.0C.0

BASEMENT

1137' - 0"

B.0

PARAPET

1178' - 11 1/2"

EXISTING -

PENTHOUSE

PARAPET

1189' - 8 3/4"

EGRESS

LANDING

1142' - 0"

EXISTING -

PENTHOUSE

ROOF DECK

1186' - 0"

PIPE

BASEMENT

B001

CORRIDOR

CONNECTION

SUB-WAIT

HALLWAY

PATIENT

TOILET

TELEHEALTH

EXAM

TELEHEALTH

EXAM

TELEHEALTH

EXAM

A B.4

AE352

F8 ------------

AE351

F5

FIRST FLOOR

1148' - 0"

SECOND FLOOR

1161' - 0"

ROOF DECK

1175' - 0"

2.7 0.0

BASEMENT

1137' - 0"

1.5

PARAPET

1178' - 11 1/2"

EXISTING -

PENTHOUSE

PARAPET

1189' - 8 3/4"

0.5

EGRESS

LANDING

1142' - 0"

EXISTING -

PENTHOUSE

ROOF DECK

1186' - 0"

CORRIDOR

HBPC

WORKROOM

HALLWAY

TELEHEALTH

WORKROOM

CORRIDOR

EXAM

EXAM

EXAM

EXAM

CLEAN

UTILITY

SOILED

HOLDING

CORRIDOR

CONFERENCE

ROOM

PIPE

BASEMENT

B001

3 1.3 0.8 0.7

OFFICE

(TELEHEALTH)

OFFICE

(HBPC)

SUB-WAIT

AE351

F5

AE352

F3

AE352

F3

AE351

F7

12 2

PATIENT

TOILET

NEW WORK KEYED NOTES:

1 PROVIDE (2) HOUR FIRE PROTECTION ON ROOF/FLOOR

ASSEMBLY IN FULL COLUMN BAY, FULL DEPTH OF PENTHOUSE

2 PROVIDE (1) HOUR ROOF ASSEMBLY

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

321 4 5 6 7 8 9 10

EXPAND PRIMARY CARE

OSCAR G. JOHNSON VA MEDICAL CENTER

325 H STREET,

IRON MOUNTAIN, MI 49801

ARCHITECT/ENGINEER

310 Pine Street | Green Bay, WI 54301 920-432-4865 | www.bernersschober.com

FULLY SPRINKLERED

Comm. Number: 5700.16

DECEMBER 4, 2020

585-336

U.S. Department of Veterans Affairs

100% DESIGN SUBMITTAL

Revisions: Date:

CONSULTANT

Architecture | Planning | Interior Design

2224 S. Michigan Ave. | Suite 1400 Chicago, Illinois 60604-2595

(312)-554-1400

65% SUBMITTAL 04/28/2020

project number: 1180742

95% SUBMITTAL 07/24/2020

100% SUBMITTAL 12/04/2020

B

IM

/V

A G

L H

S E x p a n d P ri m a ry

C a re /V

A A

R C

H .r v t

/1 /2

:2

:1

P M

DPD JAP

AE301

BUILDING SECTIONS

DWG. 41 OF 147

1/8" = 1'-0"AE301

C2 BUILDING SECTION 1

1/8" = 1'-0"AE301

C6 BUILDING SECTION 2

1/8" = 1'-0"AE301

F2 BUILDING SECTION 3

1/8" = 1'-0"AE301

F6 BUILDING SECTION 4

4'0 8' 12'2' 4'0 8' 12'2'

4'0 8' 12'2'4'0 8' 12'2'

SECOND FLOOR

1161' - 0"

ROOF DECK

1175' - 0"

2.7

BASEMENT

1137' - 0"

EGRESS

LANDING

1142' - 0"

5/8" GYP BOARD OVER

2-1/2" METAL STUDS

BLAST RATED

CURTAIN WALL

SYSTEM

MEMBRANE ROOFING ON

TAPERED INSULATION

PRECAST ARCHITECTURAL

CONCRETE TO MATCH

EXISTING

FOUNDATION WALL -

SEE STRUCTURAL

SHEET

WATERPROOFING

/4

M A

T C

H E

X

IS

T

IN

G

/4

V

IF

M A

T C

H E

X

IS

T

IN

G

V

IF

/8

/4

/8

/2

/2

2 HOUR FIRE RATED

FLOOR ASSEMBLY PER

U.L. NO. CW-S-0002

2" PERIMETER

INSULATION

AE505

C5

AE505

B5

AE505

F5

SPANDREL GLASS

VISION GLASS

VISION GLASS

SPANDREL GLASS

SPANDREL GLASS

3" POLYISOCYANURATE

INSULATION

5/8" GYP BOARD OVER

6" METAL STUDS

PAN SHALL BE INSTALLED

FLUSH WITH BACK OF MULLION

AND EXTEND TO WITHIN 1/2"

OF TERMINATION OF BACK

MULLION TUBE AT GLASS

FACE. SEAL TO CURTAINWALL

MULLION WITH SILICONE

SEALANT AND NO. 8 SCREWS

8" O.C. MAX. COVER EXPOSED

FLANGE WITH 1"X4" WIDE

CURTAINWALL INSULATION,

TYP.

FILL BOX PAN TO WITHIN 1"

OF PAN DEPTH WITH

CURTAINWALL INSULATION.

INSULATION IMPALING PINS

SHALL BE WELDED IN PLACE

NOT LESS THAN (1) PER

SQUARE FOOT, TYP.

20 GAUGE GALVANIZED FULLY

WELDED STEEL BOX PAN BY

CURTAINWALL SUPPLIER

(SMOKE AND WATER TIGHT),

TYP.

SHADE POCKET BY

CEILING MANUFACTURER

5/8" GYPSUM BOARD

OVER 2" PERIMETER

INSULATION BETWEEN

Z-CHANNELS 24" O.C. -

8'-0" TOTAL HEIGHT

AE505

F2

AE505

F2

AE505

E2

SHADE POCKET BY

CEILING MANUFACTURER

AE505

E2

DRAINAGE BY

PLUMBING TRADE

(1) HOUR SPRAY

FIREPROOFING ON BEAMS

(2) HOUR SPRAY

FIREPROOFING ON BEAMS

(2) HOUR SPRAY

FIREPROOFING ON BEAMS

FIRST FLOOR

1148' - 0"

SECOND FLOOR

1161' - 0"

ROOF DECK

1175' - 0"

D.0

BASEMENT

1137' - 0"

PARAPET

1178' - 11 1/2"

EGRESS

LANDING

1142' - 0"

FACE BRICK AND

COURSING TO

MATCH EXISTING

AIRSPACE

3" POLYISOCYANURATE

INSULATION

AIR AND VAPOR BARRIER

8" BLAST RATED CMU WITH

INSULATED CAVITIES

(WHERE UNGROUTED)

PRECAST ARCHITECTURAL

CONCRETE TO MATCH

EXISTING

ALUMINUM PARAPET,

MATCH EXISTING FINISH

FOUNDATION WALL -

SEE STRUCTURAL

GRADE

SHEET

WATERPROOFING

MEMBRANE ROOFING ON

TAPERED INSULATION

PLYWOOD ON

ROOFING INSULATION

2'-0"

2" PERIMETER

INSULATION

AE502

F9

AE502

E9

AE502

C9

/4

/4

3 1/2" SPRAY INSULATION

AT FIRST FLOOR DECK

DRAINAGE BY

PLUMBING TRADE

DOVETAIL INSERTS

AT 16" O.C.

(1) HOUR SPRAY

FIREPROOFING ON BEAMS

(2) HOUR SPRAY

FIREPROOFING ON BEAMS

(2) HOUR SPRAY

FIREPROOFING ON BEAMS

ANY VOIDS BETWEEN

SLAB AND BLOCK MUST BE

FIRESTOPPED, TYPICAL

WALL TIES AT 16" O.C.,

TYPICAL

5/8" GYP BOARD OVER

2-1/2" METAL STUDS

5/8" GYP BOARD OVER

2-1/2" METAL STUDS

FIRST FLOOR

1148' - 0"

SECOND FLOOR

1161' - 0"

ROOF DECK

1175' - 0"

0.0

BASEMENT

1137' - 0"

PARAPET

1178' - 11 1/2"

FACE BRICK AND

COURSING TO

MATCH EXISTING

AIRSPACE

3" POLYISOCYANURATE

INSULATION

AIR AND VAPOR BARRIER

8" BLAST RATED CMU WITH

INSULATED CAVITIES

(WHERE UNGROUTED)

5/8" GYPSUM BOARD

OVER 2-1/2" METAL STUDS

PRECAST ARCHITECTURAL

CONCRETE TO MATCH

EXISTING

ALUMINUM PARAPET,

MATCH EXISTING FINISH

FOUNDATION WALL -

SEE STRUCTURAL

GRADE

SHEET

WATERPROOFING

BLAST RATED

WINDOW SYSTEM

BLAST RATED

WINDOW SYSTEM

LEDGE HEIGHT VARIES -

SEE STRUCTURAL

/4

/4

/4

M A

T C

H E

X

IS

T

IN

G

/4

V

IF

M A

T C

H E

X

IS

T

IN

G

V

IF

/8

M A

T C

H E

X

IS

T

IN

G

/4

M A

T C

H E

X

IS

T

IN

G

/8

2'-0"

5/8" GYPSUM BOARD

OVER 2-1/2" METAL STUDS

2" PERIMETER

INSULATION

AE502

F9

AE502

E9

AE502

C9

MEMBRANE ROOFING ON

TAPERED INSULATION

PLYWOOD ON

ROOFING INSULATION

3 1/2" SPRAY INSULATION

AT FIRST FLOOR DECK

DRAINAGE BY

PLUMBING TRADE

DOVETAIL INSERTS

AT 16" O.C.

(1) HOUR SPRAY

FIREPROOFING ON BEAMS

(2) HOUR SPRAY

FIREPROOFING ON BEAMS

(2) HOUR SPRAY

FIREPROOFING ON BEAMS

ANY VOIDS BETWEEN

SLAB AND BLOCK MUST BE

FIRESTOPPED, TYPICAL

FIRST FLOOR

1148' - 0"

SECOND FLOOR

1161' - 0"

ROOF DECK

1175' - 0"

A.3

PARAPET

1178' - 11 1/2"

FACE BRICK AND

COURSING TO

MATCH EXISTING

AIRSPACE

3" POLYISOCYANURATE

INSULATION

AIR AND VAPOR BARRIER

8" BLAST RATED CMU WITH

INSULATED CAVITIES

(WHERE UNGROUTED)

EXISTING

FOUNDATION

WALL

EXISTING STRUCTURE

TO REMAIN. PROTECT

EXISTING STRUCTURE

DURING CONSTRUCTION

REPLACE ALUMINUM

PARAPET CAP TO

MATCH EXISTING

FOUNDATION WALL -

SEE STRUCTURAL

AE502

D8

AE502

C9

PRECAST ARCHITECTURAL

CONCRETE TO MATCH

EXISTING

ALUMINUM PARAPET,

MATCH EXISTING FINISH

MEMBRANE ROOFING ON

TAPERED INSULATION

PLYWOOD ON

ROOFING INSULATION

2'-0"

(1) HOUR SPRAY

FIREPROOFING ON BEAMS

(2) HOUR SPRAY

FIREPROOFING ON BEAMS

(2) HOUR SPRAY

FIREPROOFING ON BEAMS

ANY VOIDS BETWEEN

SLAB AND BLOCK MUST BE

FIRESTOPPED, TYPICAL

CLSM FILL - SEE

SPECIFICATIONS

5/8" GYP BOARD OVER

2-1/2" METAL STUDS

5/8" GYP BOARD OVER

2-1/2" METAL STUDS

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMP

321 4 5 6 7 8 9 10

EXPAND PRIMARY CARE

OSCAR G. JOHNSON VA MEDICAL CENTER

325 H STREET,

IRON MOUNTAIN, MI 49801

ARCHITECT/ENGINEER

310 Pine Street | Green Bay, WI 54301 920-432-4865 | www.bernersschober.com

FULLY SPRINKLERED

Comm. Number: 5700.16

DECEMBER 4, 2020

585-336

U.S. Department of Veterans Affairs

100% DESIGN SUBMITTAL

Revisions: Date:

CONSULTANT

Architecture | Planning | Interior Design

2224 S. Michigan Ave. | Suite 1400 Chicago, Illinois 60604-2595

(312)-554-1400

65% SUBMITTAL 04/28/2020

project number: 1180742

95% SUBMITTAL 07/24/2020

100% SUBMITTAL 12/04/2020

B

IM

/V

A G

L H

S E x p a n d P ri m a ry

C a re /V

A A

R C

H .r v t

/1 /2

:2

:2

P M

DPD JAP

AE351

WALL SECTIONS

DWG. 42 OF 147

1/2" = 1'-0"AE351

F3 WALL SECTION AT WEST CURTAINWALL

1/2" = 1'-0"AE351

F5 TYPICAL WALL SECTION

1/2" = 1'-0"AE351

F7 WALL SECTION AT RIBBON WINDOWS

1/2" = 1'-0"AE351

F9 WALL SECTION AT AMBULANCE GARAGE

0 1' 2' 3'6" 0 1' 2' 3'6" 0 1' 2' 3'6" 0 1' 2' 3'6"

CURTAINWALL ANCHORAGE TO STRUCTURE TO

BE DESIGNED BY MANUFACTURER TO MEET

BLAST RESISTANCE REQUIREMENTS.

ANCHORAGE MUST NOT PENETRATE BACKPAN.

SECOND FLOOR

1161' - 0"

ROOF DECK

1175' - 0"

D.0

BASEMENT

1137' - 0"

EGRESS

LANDING

1142' - 0"

5/8" GYP BOARD OVER

2-1/2" METAL STUDS

BLAST RATED

CURTAIN WALL

SYSTEM

PRECAST ARCHITECTURAL

CONCRETE TO MATCH

EXISTING

/2

/1

/4

/1

/8

/4

/8

/2

/2

/4

2 HOUR FIRE RATED

FLOOR ASSEMBLY PER

U.L. NO. CW-S-0002

AE505

C5

AE505

C5

SIM.

AE505

F4

SPANDREL GLASS

VISION GLASS

VISION GLASS

SPANDREL GLASS

5/8" GYP BOARD OVER

6" METAL STUDS

SPANDREL GLASS

CONCRETE CURB -

SEE STRUCTURAL

PAN SHALL BE INSTALLED

FLUSH WITH BACK OF MULLION

AND EXTEND TO WITHIN 1/2"

OF TERMINATION OF BACK

MULLION TUBE AT GLASS

FACE. SEAL TO CURTAINWALL

MULLION WITH SILICONE

SEALANT AND NO. 8 SCREWS

8" O.C. MAX. COVER EXPOSED

FLANGE WITH 1"X4" WIDE

CURTAINWALL INSULATION,

TYP.

FILL BOX PAN TO WITHIN 1"

OF PAN DEPTH WITH

CURTAINWALL INSULATION.

INSULATION IMPALING PINS

SHALL BE WELDED IN…

This is the start of the file's text. The full file is on GovTribe.