Attachment 7 CLIN D Drawings.pdf
PDF 6 MB Posted
- Solicitation number
- 12805B24R0036
About this file
This document contains drawings and technical specifications for the "CLIN D - Perimeter Fence" as part of a site security improvements project at the National Bio and Agro Defense Facility (NBAF) in Manhattan, Kansas.
The drawings provide details on the installation of a K12 bollard backup system and an M30 security post and rail system to meet anti-ram requirements. Key specifications include the materials, dimensions, and installation details for the fencing and supporting infrastructure. The document also includes general notes, demolition requirements, and record drawing instructions for the contractor.
This is related to a pre-solicitation for a future Request for Proposal (RFP) for the construction of the site security improvements at the NBAF, which the U.S. Department of Agriculture (USDA) Agricultural Research Service plans to issue around July 2, 2024. The project is anticipated to be a Firm Fixed Price construction contract between $1,000,000 - $5,000,000 in value and set aside for small businesses under NAICS code 236220 Commercial and Institutional Building Construction.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
USDA
VICINITY MAP (1" = 0.4 MILES)
NATIONAL BIO AND AGRO DEFENSE FACILITY (NBAF)
1980 DENISON AVENUE
MANHATTAN, KS 66502
INDEX OF DRAWINGS
CLIN "D" - PERIMETER FENCE
TITLE SHEET
T-101
GENERAL NOTES:
1. THE CONTRACTOR SHALL FIELD VERIFY ALL DIMENSIONS AND EXISTING CONDITIONS PRIOR TO PERFORMING
WORK OR FABRICATION OR PURCHASE OF EQUIPMENT, MATERIALS, AND ASSEMBLIES. ANY DEVIATIONS SHALL BE BROUGHT TO THE CONTRACTING OFFICER'S ATTENTION FOR RESOLUTION BEFORE PROCEEDING WITH ANY
CONSTRUCTION, FABRICATION, OR EQUIPMENT PURCHASE.
2. THE FACILITY WILL REMAIN IN OPERATION DURING ALL PHASES OF CONSTRUCTION. ALL MEANS OF EGRESS
MUST REMAIN FREE AND CLEAR.
3. COORDINATE CONSTRUCTION ACCESS AND STAGING AREA(S) WITH CONTRACTING OFFICER PRIOR TO
COMMENCING WORK.
U.S. DEPARTMENT OF AGRICULTURE
AGRICULTURAL RESEARCH SERVICE
SITE SECURITY IMPROVEMENTS DESIGN
CONTRACT NO: 12805B23D0001
NATIONAL BIO AND AGRO DEFENSE FACILITY (NBAF)
MANHATTAN, KANSAS
SHEET NO. DRAWING NO. TITLE
T-101 1 OF 5 CLIN "D" - PERIMETER FENCE TITLE SHEET
T-102 2 OF 5 CLIN "D" - GENERAL NOTES
C-101 3 OF 5 SITE PLAN - CLIN "D"
C-501 4 OF 5 CLIN "D" - DETAILS
C-502 5 OF 5 CLIN "D" - DETAILS
U
D A
S
PROJECT LOCATION
PROJECT
LOCATION
PROJECT LOCATION
LOCATION MAP (1" = 60 MILES)
lhenderson Chip NBAF 8
CLIN "D" - GENERAL NOTES
T-102
U
D
SITE SECURITY DEVICE SCHEDULE
BASIS OF DESIGN OR APPROVED EQUAL
ITEM TYPE MANUFACTURER MODEL GENERAL DESCRIPTION ELECTRICAL REQUIREMENTS
1 BOLLARD FENCING BACKUP TYMETAL TCF-CR-50P1 CRASH CABLE WITH RAILS -
2 CABLE HARDENING N/A UFC-710 GALVANIZED CABLE ANTI-RAM SYSTEM -
3 M30 SECURITY POST & RAIL AMERISTAR STALWART M30-P1 M30 POST & RAIL -
DEMOLITION NOTES
D-1 PROTECT ASSETS AND FINISHES NOT SHOWN TO BE REMOVED. ANY DAMAGE CAUSED BY
CONSTRUCTION OPERATIONS SHALL BE REPAIRED TO MATCH THE EXISTING CONDITIONS AT NO
COST TO THE GOVERNMENT.
D-2 AT A MINIMUM, PROVIDE 4' TALL TEMPORARY ORANGE HIGH DENSITY POLYETHYLENE SAFETY
FENCE TO ISOLATE HAZARD AND CONSTRUCTION FROM UNAUTHORIZED ACCESS.
D-3 CARE SHALL BE TAKEN IN ALL OPEN SUBGRADES TO PREVENT DETERIORATION CAUSED BY
WEATHER. DEWATER ALL OPEN SUBGRADES AS REQUIRED TO MAINTAIN STABILITY.
D-4 AT A MINIMUM, PROVIDE TEMPORARY TRAFFIC CONTROL AS REQUIRED FOR PHASING AND
CONSTRUCTION. ALL WORK SHALL CONFORM TO THE REQUIREMENTS OF THE MANUAL OF
UNIFORM TRAFFIC CONTROL DEVICES (MUTCD).
D-5 THE CONTRACTOR SHALL CONTROL THE SPREAD OF DUST AND IRRITANTS TO OTHER SPACES, ADJACENT BUILDINGS AND OUTSIDE OF DESIGNATED WORK AREAS.
D-6 THE CONTRACTOR SHALL PROVIDE CLEAN, STRAIGHT, NEAT CUTS FOR DEMOLITION THAT MINIMIZE
IMPACTS AND ADVERSE EFFECTS ON EXISTING FINISHES. COORDINATE THE LOCATION OF THE
CUTS TO ACCOMMODATE FINAL FINISHES.
D-7 WHERE NEW WORK IMPACTS RIGID PAVEMENT, CURB, OR CONCRETE WALKS, THE CONCRETE
SHALL BE SAW-CUT AND REMOVED AND REPLACED TO THE NEAREST CONTROL OR EXPANSION
JOINT, BE REPLACED LIKE-IN-KIND AND HAVE THE JOINT SEALED.
GENERAL NOTES
GN-1 THESE GENERAL NOTES ARE NOT INTENDED TO REPLACE THE PROJECT SPECIFICATIONS.
REVIEW ALL PROJECT DOCUMENTS PRIOR TO START OF CONSTRUCTION. REPORT ANY
DISCREPANCIES TO CONTRACTING OFFICER PRIOR TO PROCEEDING WITH WORK. DIMENSIONS
RELATING TO EXISTING CONSTRUCTION ARE TO BE FIELD VERIFIED. THE CONTRACTOR SHALL
IMMEDIATELY COMMUNICATE, IN WRITING TO THE CONTRACTING OFFICER, CONCERNS WHERE
THEY BELIEVE DESIGN DOCUMENTS ARE INSUFFICIENT, INADEQUATE OR INCORRECT FOR
PERFORMING THE CONSTRUCTION WORK.
GN-2 EXISTING UTILITIES ARE SHOWN IN THEIR APPROXIMATE LOCATIONS AS LOCATED AT THE TIME
OF THE DESIGN SITE VISIT.
AT THE BEGINNING OF THE PROJECT AND PRIOR TO ORDERING MATERIALS:
· THE CONTRACTOR SHALL BE RESPONSIBLE FOR DETERMINING THE EXACT LOCATION
OF EXISTING UTILITIES ON SITE.
· WHERE NEW WORK IS INDICATED TO CROSS EXISTING UTILITIES, THE CONTRACTOR
SHALL ANTICIPATE RELOCATING THE EXISTING SERVICE TO ACCOMMODATE THE NEW
INSTALLATION.
· THE CONTRACTOR SHALL VERIFY THE LOCATION OF ALL UTILITIES AND DETERMINE THE
POINTS OF CONNECTIONS (SUCH AS WATER, SEWER, ELECTRIC, GAS, COMMUNICATION
AND STORM DRAINAGE).
· THE CONTRACTOR SHALL PERFORM A FULL LOCATION ALONG THE LENGTH OF ANY
GRAVITY UTILITY ALIGNMENT TO DETERMINE IF THERE ARE OBSTRUCTIONS THAT
PREVENT THE CONSTRUCTION OF THE PLANNED DESIGN.
DOCUMENT ALL FINDINGS AND PROVIDE TO THE CONTRACTING OFFICER PRIOR TO BEGINNING
CONSTRUCTION.
GN-3 COORDINATE CIVIL WORKS AND OTHER TRADES.
GN-4 ALL DETAILS AND SECTIONS ON THE DRAWINGS ARE INTENDED TO BE TYPICAL AND SHALL BE
CONSTRUED TO APPLY TO ANY SIMILAR SITUATION ELSEWHERE ON THE PROJECT EXCEPT
WHERE A SEPARATE DETAIL IS SHOWN.
GN-5 THE CONTRACTOR SHALL TAKE CARE, BY THE USE OF GRADING, DIVERSION AND DEWATERING, TO PREVENT PONDING OF WATER ON SITE IN AREAS OF OPEN TRENCHES AND
STRUCTURAL/PAVEMENT SUBGRADES.
GN-6 THE CONTRACTOR SHALL PROVIDE AS-BUILT DRAWINGS OF ALL OF THE NEW UTILITIES AND
SERVICE, SITE FEATURES AND CHANGES MADE DURING THE WORK.
GN-7 PRODUCTS SHALL BE INSTALLED PER MORE STRINGENT REQUIREMENTS OF THE DESIGN
DOCUMENTS OR THE MANUFACTURER'S PRINTED INSTRUCTIONS FOR THE INDICATED
APPLICATION. THESE INSTRUCTIONS SHALL BE MAINTAINED ON SITE FOR THE DURATION OF THE
INSTALLATION AT A MINIMUM.
GN-8 AT THE COMPLETION OF GRADING, THE CONTRACTOR SHALL RESPREAD 4" OF TOP SOIL ON ALL
DISTURBED UNIMPROVED LAWN AREAS, AS REQUIRED TO ESTABLISH VEGETATIVE COVER. AT
THE COMPLETION OF THE PROJECT, HAUL EXCESS SOIL OFF SITE.
GN-9 TEMPORARY SEED OR STABILIZE ALL AREAS OF EXPOSED EARTH THAT ARE PLANNED TO BE
UNFINISHED OR UNWORKED FOR A PERIOD EXCEEDING 14 DAYS.
GN-10 ALL DE-WATERING AND WASH-WATER SHALL BE PRE-TREATED WITH AN ACCEPTED MANAGEMENT
PRACTICE PRIOR TO BEING DISCHARGED INTO A STORMWATER CONVEYANCE.
PHASING NOTES
PH-1 THE CONTRACTOR SHALL PROVIDE A SCHEDULE OF CONSTRUCTION TO THE CONTRACTING
OFFICER PRIOR TO BEGINNING CONSTRUCTION. DETAILS SHALL BE PROVIDED NOTING WHERE
CONSTRUCTION WILL OCCUR, SEQUENTIAL PHASING AND THE DURATION OF THE WORK TO BE
PERFORMED. THE SCHEDULE SHALL ALSO DETAIL THE LENGTHS OF ANTICIPATED
INTERRUPTIONS AND HOW THE CONTRACTOR WILL MINIMIZE INTERRUPTIONS TO THE
GOVERNMENT'S NORMAL OPERATIONS.
RECORD DRAWING NOTES:
RD-1 CONTRACTOR SHALL MAINTAIN UPDATED RECORD DRAWINGS AT ALL TIMES THROUGH THE
DURATION OF THE PROJECT.
RD-2 DURING CONSTRUCTION OF THE PROJECT, CONTRACTOR SHALL BE RESPONSIBLE FOR
DOCUMENTING ANY CONTRACTING OFFICER APPROVED FIELD CONSTRUCTION REVISIONS TO
THE DESIGN DEPICTED ON APPROVED CONSTRUCTION DRAWINGS. THESE REVISIONS SHALL BE
USED TO PREPARE RECORD AS-BUILT DRAWINGS OF COMPLETED CONSTRUCTION.
RD-3 ALL VARIATIONS IN PROJECT CONDITIONS, LOCATIONS, AND CONFIGURATIONS, AND ANY
OTHER CHANGES OR DEVIATIONS FROM THE INFORMATION PRESENTED ON THE ORIGINAL,
APPROVED CONSTRUCTION DRAWINGS SHALL BE NOTED. THIS INCLUDES BURIED OR
CONCEALED CONSTRUCTION AND UTILITY FEATURES THAT WERE REVEALED DURING
CONSTRUCTION.
X X
X X
X X
X X
X X
X
XXXXXXXXXXXXXXXXXXXX
X
X X
X X
X X
X X
X X
X X
X
U
D
SITE PLAN - CLIN "D"1
SCALE: 1" = 20'C-101
SCALE: 1" =
060 60
60'
SITE PLAN - CLIN "D"
C-101
1. PROVIDE NEW K12 BOLLARD BACKUP.
(SEE DETAILS ON C-501).
2. PROVIDE NEW M30 SECURITY POST
AND RAIL. (SEE DETAILS ON C-502).
KEYED NOTES :#
ELECTRIC UTILITY
EASEMENT
NEW K12 BOLLARD BACKUP
LEGEND
ELECTRIC UTILITY
EASEMENT
NEW M30 SECURITY POST AND RAIL
END
1 2
BEG
BEG
END
BEG
END
BEG
END
1" CABLE (K12)
1" CABLE (K12)
1" CABLE (K12)
CORNER
BOLLARD
4'- 0"
3'- 5"
2'-
4"
BOLLARD SPACING
VARIES
K12 ANTI-CRASH CABLE RUN BACKUP - ELEVATION2
SCALE: NONEC-501
4'- 6"
8'-0"±
3'-0"
7'- 0"
2'-
3'-
5"4'- 0"
4"
TY
P
FILL WITH 6,000 # PSI CONC.
GALV. HSS 8X8X.25 STEEL BOLLARD
GALV. 2X2.5" STEEL RAIL, TYP.
1" WIRE CABLE (K12)
1" WIRE CABLE (K12)
1" WIRE CABLE (K12)
#4 TIES @ 6" O.C.
NOTE: SEE K12 ELEVATION FOR
CABLE RUNS
BOLLARD
12 #8 EQ. SP.
6,000 # PSI CONC. FOOTING
1" CABLE CLAMP.
(4) PER CABLE
FOOTING REINFORCING
BOLLARD BACKUP - DETAIL1
SCALE: 1/2" = 1'-0"C-501
TYPE K12 FENCE
4" THICK X 36" WIDE
CONCRETE APRON
NOTE: CONTRACTOR PROVIDED SYSTEM MUST
BE (K12) M50 RATED AND INSTALLED PER
VENDOR'S WRITTEN REQUIREMENTS FOR
THIS APPLICATION
4'- 6"
CABLE RAIL
A
SECTION A-A
RAIL
1"Ø WIDE
CABLE
THE CONTRACTOR SHALL VERIFY
SOILS CONDITIONS AND ANTICIPATE
HARD ROCK, UNLESS NOTED
OTHERWISE
3'-0"
1'-6" MIN. 1'-6" MIN.
TYPE K12 FENCE END BOLLARD 4
SCALE: 1/2" = 1'-0"C-501
FENCE BOLLARD - SEE
DETAILS, THIS SHEET
FOR ADD'L. INFO.
4" CONC. MAINT. STRIP
WITH 12" DEEP SCORED
JOINTS AT 6' O.C., ON ±6"
COMPACTED SUB-BASE
ADJACENT FINISHES
HOLD TOP POST
FOOTING BELOW
ADJACENT FINISHES
GRASSED
LAWN
AREAS
6" THICK
GRAVEL
ATTACH TO METAL
FENCE POST WITH
GROUND CLAMP
FENCE POST
'-0
1'-
0"
3 4" DIA COPPER-CLAD
STEEL GROUND ROD
MOLDED EXOTHERMIC
WELD OR APPROVED
CLAMP-TYPE FITTING
OF BRONZE
TYPICAL AT ALL CORNER POST,
END POST, AND GATE POST
GROUNDING DETAIL3
SCALE: 1" = 1'-0"C-501
#8 AWG SOLID COPPER
WIRE, ROUTE IN CONDUIT
TO PROTECT
CONCRETE MOW STRIP
TYPICAL ALONG ENTIRE ALIGNMENT
36" MINSTEEL TUBE (UPRIGHT)
CABLE AND POST
4" THICK CONCRETE
APRON WITH 12" DEEP
SCORED JOINTS AT 6'
O.C.
GRADE TO DRAIN
AND PROVIDE 1'-4"
WIDE SOLID
SODDING EACH SIDE
TYPICAL
ABUT EXISTING FENCING
(TYPICAL ALONG ALIGNMENT)
MOW STRIP STRIP AND ALIGNMENT5
SCALE: 1/2" = 1'-0"C-501
6" THICK GRAVEL
U
D
CLIN "D" - DETAILS
C-501 02' 2'
1'-0"SCALE: 1/2" =
08" 8"
1'-0'SCALE: 1-1/2" =
4"
BOLLARD BACKUP REQUIREMENTS:
THE MANUFACTURER SHALL SUPPLY A TOTAL ANTI-RAM CABLE BARRIER SYSTEM
RATED AND CERTIFIED TO A LEVEL M50/P1 COMPRISED ENGINEERED POST & RAIL
DESIGN.
THE MANUFACTURER SHALL SUPPLY A TOTAL ANTI-RAM TWIN CABLE BARRIER
SYSTEM OF THE AMERISTAR STALWART M50/P1 POST & RAIL DESIGN, WHICH HAS
BEEN TESTED AND MEETS AN M50/P1 DESIGNATION UNDER ASTM F2656. THE
SYSTEM SHALL INCLUDE ALL COMPONENTS (I.E., CABLES, BRACES, POSTS, AND
HARDWARE) REQUIRED.
STEEL MATERIAL FOR CABLE-SUPPORTING FRAMEWORK (I.E., RAILS, BRACES AND
POSTS) SHALL CONFORM TO THE REQUIREMENTS OF ASTM A36/A36M.
THE CROSS-SECTIONAL SHAPE OF THE CABLE GUIDE RAIL SHALL CONFORM TO THE
MANUFACTURER'S RAIL DESIGN, C8 X 11.5 CHANNEL WITH 5” X 3” X ½” ANGLE RAIL TO
POST ATTACHMENT TABS. TERMINAL POSTS SHALL CONFORM TO THE
MANUFACTURER'S BOLLARD DESIGN WITH A NOMINAL 8” X 16” X ½” WALL.
INTERMEDIATE POSTS SHALL CONFORM TO THE MANUFACTURER'S BOLLARD
DESIGN WITH A NOMINAL 8” X 8” X ½” WALL. TERMINAL BRACE SHALL CONFORM TO
THE MANUFACTURER'S DESIGN WITH A NOMINAL 4” X 4” X ½” WALL. TERMINAL POST
PLATE SHALL CONFORM TO THE MANUFACTURER'S DESIGN WITH A NOMINAL 6” X 1” X
30”.
THE CABLE MATERIAL SHALL BE INDEPENDENT WIRE-ROPE CORE (IWRC) WIRE ROPE
CONFORMING TO FEDERAL SPECIFICATION RR-W-410D, 6 X 37 WARRINGTON SEALE,
PREFORMED, RIGHT REGULAR LAY, DRY LUBRICATION, EXTRA IMPROVED PLOW
STEEL (EIPS), WITH A BREAKING STRENGTH OF 228,000 POUNDS (114 TONS). CABLE
DIAMETER SHALL BE 1-1/2 INCH.
SOIL STRENGTH SHALL BE EQUIVALENT TO SOIL STRENGTH RECORDED DURING THE
ASTM F2656 CERTIFICATION TEST OR THE FOOTER SIZE AND DEPTH MUST BE
ADJUSTED ACCORDINGLY BASED ON THE MANUFACTURER'S PROVIDED
PROFESSIONAL ENGINEERING ANALYSIS.
THE MANUFACTURED GALVANIZED FRAMEWORK SHALL RECEIVE A THERMAL
STRATIFICATION COATING PROCESS (HIGH-TEMPERATURE, IN-LINE, MULTI-STAGE,
MULTI-LAYER) INCLUDING, AS A MINIMUM, A SIX-STAGE PRETREATMENT/WASH (WITH
ZINC PHOSPHATE), AN ELECTROSTATIC SPRAY APPLICATION OF AN EPOXY BASE,
AND A SEPARATE ELECTROSTATIC SPRAY APPLICATION OF A POLYESTER FINISH.
THE BASE COAT SHALL BE A THERMOSETTING EPOXY POWDER COATING (GRAY IN
COLOR) WITH A MINIMUM THICKNESS OF 2 MILS (0.0508MM). THE TOPCOAT SHALL BE
A “NO-MAR” POLYESTER POWDER COAT FINISH WITH A MINIMUM THICKNESS OF 2
MILS (0.0508MM). THE COLOR OPTIONS SHALL CONSIST OF BLACK, BRONZE, WHITE
OR DESERT SAND AT A MINIMUM AND SELECTED BY THE CONTRACTING OFFICER
PRIOR TO PURCHASE BY THE CONTRACTOR.
8'
TYPICAL MAXIMUM8'
1'-8"
8'
4'-4"
9"
3'
2'-634" 3'-014" 3'-534"
RAIL AND 1"Ø CABLE
73'-4"
MAXIMUM
CONCRETE FOUNDATION
FACE OF I-BEAM TO BE FLUSH WITH FACE OF BOLLARD (CRASH SIDE)
(3) 1"Ø CABLE
I-BEAM (UPRIGHT
I-BEAM (UPRIGHT)
DRILLED CONCRETE SUPPORT
(6) 24" #8 HORIZONTALS
#3 TIES
KNEE BRACECROSS BRACE
CONCRETE
FOUNDATION
BOLLARD
#5 VERTICAL
1'-4"
8'
3'-6"
2' 2'-6"
4" SQ TUBE
CROSS BRACE 3'-6"
4'
I-BEAM
POST
#3 TIES
#5 VERT
LEFT END
LINE
RIGHT END
INSIDE
CORNER
OUTSIDE
CORNER#3 TIES
(6) 24" #8 HORIZONTALS
THE CONTRACTOR SHALL VERIFY
SOILS CONDITIONS AND ANTICIPATE
HARD ROCK
CABLE AND
RAIL SECTION
RAIL
1"Ø WIDE
CABLE
CONCRETE MOW STRIP
TYPICAL ALONG ENTIRE
ALIGNMENT
4'
I-BEAM (UPRIGHT)
CABLE AND POST
4" THICK CONCRETE
APRON WITH 12" DEEP
SCORED JOINTS AT 6'
O.C.
GRADE TO DRAIN
AND PROVIDE 1'-4"
WIDE SOLID
SODDING EACH SIDE
TYPICAL
U
D
CLIN "D" - DETAILS
C-502
04' 4'
1'-0"SCALE: 1/4" =
2'
04' 4'
1'-0"SCALE: 1/4" =
2'
TYPICAL M30 SECURITY POST AND RAIL2
SCALE: 1/2" = 1'-0"C-502
TYPICAL M30 SECURITY POST AND RAIL ELEVATION1
SCALE: 1/4" = 1'-0"C-502
POST AND RAIL SECURITY BARRIER REQUIREMENTS:
THE MANUFACTURER SHALL SUPPLY A TOTAL ANTI-RAM CABLE BARRIER SYSTEM RATED AND CERTIFIED TO
A LEVEL M30/P2 COMPRISED ENGINEERED POST & RAIL DESIGN.
THE SYSTEM SHALL INCLUDE ALL COMPONENTS (I.E., CABLES, SUPPORTS, POSTS, AND HARDWARE)
REQUIRED.
ENGINEERING ANALYSIS SHALL BE BASED UPON ASTM F2656, IMPACT CONDITION DESIGNATION M30, PENETRATION RATING P2, WITH CAPABILITY OF STOPPING A 15,000 LB VEHICLE TRAVELING AT SPEEDS UP
TO 30MPH.
STEEL MATERIAL FOR CABLE-SUPPORTING FRAMEWORK (I.E., RAILS AND POSTS) SHALL BE GALVANIZED PRIOR TO FORMING AND SHALL CONFORM TO THE REQUIREMENTS OF ASTM A653/A653M, WITH A MINIMUM YIELD STRENGTH OF 45,000 PSI (310 MPA). THE STEEL SHALL BE HOT-DIP GALVANIZED TO MEET THE REQUIREMENTS OF ASTM A653/A653M WITH A MINIMUM ZINC COATING WEIGHT OF 0.90 OZ/FT2/ (276 G/M2/), COATING DESIGNATION G-90.
THE CROSS-SECTIONAL SHAPE OF THE RAILS SHALL BE NOMINAL 2” X 2” X 11 GA. TAMPERPROOF FASTENERS SHALL BE USED TO FASTEN EACH POST TO RAIL CONNECTION. POSTS SHALL PROVIDE A
NOMINAL I-SHAPE 3” X 2.75” X 12 GA.
THE CABLE MATERIAL SHALL BE INDEPENDENT WIRE-ROPE CORE (IWRC) WIRE ROPE CONFORMING TO FEDERAL SPECIFICATION RR-W-410E, 6 X 36 WARRINGTON SEALE, PREFORMED, RIGHT REGULAR LAY, MEDIUM LUBRICATION, EXTRA IMPROVED PLOW STEEL (EIPS), WITH A BREAKING STRENGTH OF 103,400
POUNDS (51.7 TONS). CABLE DIAMETER SHALL BE 1 INCH.
THE MANUFACTURED GALVANIZED FRAMEWORK SHALL RECEIVE A THERMAL STRATIFICATION COATING PROCESS (HIGH-TEMPERATURE, IN-LINE, MULTI-STAGE, MULTI-LAYER) INCLUDING, AS A MINIMUM, A SIX-STAGE PRETREATMENT/WASH (WITH ZINC PHOSPHATE), AN ELECTROSTATIC SPRAY APPLICATION OF AN EPOXY BASE, AND A SEPARATE ELECTROSTATIC SPRAY APPLICATION OF A POLYESTER FINISH. THE BASE COAT SHALL BE A THERMOSETTING EPOXY POWDER COATING (GRAY IN COLOR) WITH A MINIMUM THICKNESS OF 2 MILS (0.0508MM). THE TOPCOAT SHALL BE A “NO-MAR” POLYESTER POWDER COAT FINISH WITH A MINIMUM THICKNESS OF 2 MILS (0.0508MM). THE COLOR OPTIONS SHALL CONSIST OF BLACK, BRONZE, WHITE OR DESERT SAND AT A MINIMUM AND SELECTED BY THE CONTRACTING OFFICER PRIOR TO
PURCHASE BY THE CONTRACTOR.
SOIL STRENGTH SHALL BE EQUIVALENT TO SOIL STRENGTH RECORDED DURING THE ASTM F2656 CERTIFICATION TEST OR THE FOOTER SIZE AND DEPTH MUST BE ADJUSTED ACCORDINGLY BASED ON THE
MANUFACTURER'S PROVIDED PROFESSIONAL ENGINEERING ANALYSIS.
| T-101 CLIN D-T-101 |
| T-101 CLIN D-T-102 |
| C-101 CLIN D-C-101 |
| C-501 CLIN D-C-501 |
| C-502 CLIN DM30-C-502 |