This document is a record drawing package for the EHRM Infrastructure Upgrades project at the St. Cloud VA Medical Center in St. Cloud, Minnesota. The project involves upgrading mechanical, electrical, and telecommunications infrastructure across Buildings 51 and 116, with primary focus on converting existing spaces into compliant telecom rooms meeting Electronic Health Record Modernization (EHRM) standards.
Building 51 (Basement) requires electrical panel upgrades including two new 100-amp, 3-phase panels (B51IT-1 and B51IT-1-CR) fed from existing distribution equipment at panels 51-MDP and 51-EDC. The telecom room installation includes new wall-mounted split-system air conditioning unit (AC-51-1), condensate handling (CP-51-1), fire sprinkler head relocation, and an air-cooled condensing unit (CU-51-1) positioned outside. Electrical requirements include L21-30R receptacles for rack PDU connections, UPS systems rated at 5 kW (120/208V, 3-phase), and specific rack-mounted power distribution units (APC#AP8861 RPDU with dual units per rack). Short-circuit current ratings range from 3.599 kA to 18.226 kA with 10 kA to 22 kA SCCR ratings across affected panels.
Building 116 (First Floor, Room 111) involves converting an existing data room into a compliant EHRM telecom room with similar electrical and mechanical requirements. The space requires new conduit runs (3/4" C-4#10, 1#12 GND), L21-20R and L21-30R receptacles, five 5 kW rack-mounted UPS units, and dual APC RPDU units per rack. Mechanical work includes installing a new split-system AC unit with refrigerant and condensate piping routed approximately 30 feet to an HAC mop sink, along with fire sprinkler line rerouting. Both buildings require 1-hour fire-rated construction barriers for ICRA (Infection Control Risk Assessment) classification as Type C Group 1 Class II spaces, with construction limited to nighttime hours to minimize disruption to occupied clinical areas. The project includes extensive cabling demolition and replacement, with existing CAT5e cabling (114 strands in Building 116) being replaced by new CAT6A infrastructure.
View the file
Other files for this federal contract opportunity
Show all 13
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
MECHANICAL
H
E
SD
EXISTING 51MDP 51-ATS
ES-ATS
EC-TS
51-MDP
51-EDC
8'-2"
'-2
/2
TELECOM
ROOM
8'-2"
'-2
/2
TELECOM
ROOM
A
B51IT-1-CR
a
A
B51IT-1
b a b
8'-2"
'-2
/2
TELECOM
ROOM
B51IT-1
B51IT-1-CR
AC-51-1
B51IT-1-1
B51IT-1-CR-1
B51IT-1-1
B51IT-1-CR-1
B51IT-1-1
B51IT-1-CR-1
B51IT-1-CR-2,4,6
B51IT-1-2,4,6
No DATEREVISION
DRAWING TITLE
CHECKED BY
ST.CLOUD, MN 56303
VA MEDICAL CENTER
BUILDING No
LOCATION
DRAWING NO.DRAWN
DWG. OF
PROJECT TITLE
PLOT SCALE
PROJECT NO.
DATE:
CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP
FULLY
SPRINKLERED
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Engineer under the laws of the State of Minnesota.
Name:
Date: 03/30/2022
License Number: MN#
03/30/2022
B
IM
/2
.0
V A
S t C lo u d E
H R
M I n fr a s tr u c tu re U p g ra d e s /6
-2
.B
.E
R
.r v t
/1
/2
:3
:2
P
M
51-E300
ENLARGED PLANS -
ELECTRICAL
EHRM INFRASTRUCTURE
UPGRADES
656-21-235
TBD GJL
16305
N O R
HT
1/4" = 1'-0"
BASEMENT FLOOR PLAN ENLARGED - ELECTRICAL
N O R
HT
1/4" = 1'-0"
TELECOM ROOM - ELECTRICAL DEMOLITION
N O R
HT
1/4" = 1'-0"
TELECOM ROOM - LIGHTING
N O R
HT
1/4" = 1'-0"
TELECOM ROOM - POWER & SYSTEM
KEYNOTES:
1. INDOOR UNIT TO BE POWERED BY OUTDOOR
UNIT. COORDINATE EXACT LOCATION WITH
M.C.
2. CONNECT SMOKE DETECTOR TO NEAREST
EXISTING SLC.
3. DISCONNECT AND REMOVE EXISTING LIGHTS
AND RECEPTACLES IN ROOM. MAINTAIN
CIRCUIT CONTINUITY TO ADJOINING ROOMS.
4. COORDINATE FINAL LOCATION OF
RECEPTACLE L21-30R WITH TELECOM
CONTRACTOR. PROVIDE 3/4"C-4#10, 1#10 GND
TO PANEL FOR EACH RECEPTACLE.
5. PROVIDE EATON BLADEUPS, 5KW, 120/208V, 3-
PHASE,4-WIRE RACK MOUNTED UPS FOR EACH
RACK TOWER.
6. PROVIDE APC#AP8861 RPDU RACK PDU 2G
WITH L21-20P CORD. (120/208V, 3-PHASE, 20A,
ZERO U, 5.7 KW, 208V, (36) C13 (6) C19 (2) 5-20R
OUTLETS. PROVIDE TWO PER RACK, MOUNTED
PER MANUFACTURER'S REQUIREMENTS.
7. PROVIDE ONE RACK MOUNTED ZONE PDU
UNIT. 30 AMP 3 PHASE, 120/208V, 5-WIRE WITH
(4) L21-30R, (6) 5-20R AND TWO 10' POWER
CORDS. ZONIT#ZPDS-208V-30A-L21-4L21-20R-
CR.#
100% CD 03/30
reby certify that this plan, specification o ort was prepared by me or under my dire ervision and that I am a duly Licensed ineer under the laws of the State of Minn me:
e: 03/30/202205-06-2022
ALEXANDER S. QUAST
06/14/2024 53095
RECORD DOCUMENTS 06/14
RECORD
DRAWINGS
THIS IS A RECORD DRAWING BASED ON INFORMATION RECEIVED FROM THE
CONTRACTOR AND IS TO BE USED FOR THE SOLE PURPOSE OF MAINTENANCE OF
THE ORIGINAL FACILITY FOR WHICH THIS DRAWING WAS PREPARED AND NOT
FOR ADDITIONAL CONSTRUCTION.No DATEREVISION
100% CD 03/30
RECORD DOCUMENTS 06/14
No DATEREVISION
RECORD DOCUMENTS 06/21/24 06/21/2024
-RECORD DOCUMENT-
June 21, 2024 This Record Document has been prepared based on
Designer of Record drawings with Contractor provided markups through the construction phase of the project at the direction of the VA.
While the construction information is believed to be reliable, Architect/Engineer cannot assure its accuracy, and is not responsible for the accuracy of this Record Document. Those relying on this Record
Document are advised to independently verify its accuracy before applying it for any purpose.
eby certify that this plan, specification rt was prepared by me or under my dir ervision and that I am a duly Licensed neer under the laws of the State of Min me:
e: 03/30/202205-06-2022
RECORD DOCUMENTS
BASEMENT
FIRST FLOOR
B51IT-1
100Y
51MDP
B51IT-1-CR
100Y
51-EDC
ISC 14.318 kA SCCR 22 kA
ISC 3.599 kA SCCR 10 kA
ISC 5.159 kA SCCR 10 kA
ISC 18.226 kA SCCR 22 kA
No DATEREVISION
DRAWING TITLE
CHECKED BY
ST.CLOUD, MN 56303
VA MEDICAL CENTER
BUILDING No
LOCATION
DRAWING NO.DRAWN
DWG. OF
PROJECT TITLE
PLOT SCALE
PROJECT NO.
DATE:
CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP
FULLY
SPRINKLERED
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Engineer under the laws of the State of Minnesota.
Name:
Date: 03/30/2022
License Number: MN#
03/30/2022
B
IM
/2
.0
V A
S t C lo u d E
H R
M I n fr a s tr u c tu re U p g ra d e s /6
-2
.B
.E
R
.r v t
/1
/2
:3
:2
P
M
51-E500
ELECTRICAL ONE-LINE
DIAGRAMS AND SCHEDULES
EHRM INFRASTRUCTURE
UPGRADES
656-21-235
TBD GJL
16305
NO SCALE
PARTIAL POWER RISER
KEYNOTES:
1. PROVIDE NEW 100A/3P CIRCUIT BREAKERS IN
EXISTING PANEL TO MATCH EXISTING TYPE
AND AIC RATING.
100% CD 03/30
CIRCUIT KEY NOTES:
*TOTAL DEMAND CALCS SUBTRACT ANY REDUNDANT LOAD AND THE SMALLER OF ANY NONCOINCIDENT HVAC LOADS. THIS CALC IS DONE AT EACH PANEL.
TOTAL ESTIMATED DEMAND AMPS: 18.7 A
TOTAL CONNECTED AMPS: 18.65 A
Receptacles 0.72 kVA 100.00% 0.72 kVA TOTAL ESTIMATED DEMAND LOAD: 6.72 kVA
Power 6 kVA 100.00% 6 kVA TOTAL CONNECTED LOAD: 6.72 kVA
Lighting 0 kVA 0.00% 0 kVA
LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND
TOTALS*
LOAD SUMMARY
Total Amps: 21.40 16.67 18.40
Total Load: 2.54 kVA 2.00 kVA 2.18 kVA
-- 29 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 30 --
-- 27 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 28 --
-- 25 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 26 --
-- 23 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 24 --
-- 21 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 22 --
-- 19 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 20 --
-- 17 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 18 --
-- 15 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 16 --
-- 13 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 14 --
-- 11 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 12 --
-- 9 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 10 --
-- 7 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 8 --
5 WP GFI RECEPTACLE 20 A 1 12 12 12 0.18 2 -- -- -- -- -- -- 6 --
3 TELECOM ROOM LIGHTING 20 A 1 12 12 12 0 2 -- -- -- -- -- -- 4 --
1 TELECOM ROOM RECEPTACLE 20 A 1 12 12 12 0.54 2 10 10 10 3 30 A L21-30R 2
K E Y
CKT
NO. LOAD DESCRIPTION
OCPD
AMPS P
WIRE
SIZE
H N G
A B C
WIRE
SIZE
G N H
OCPD
P AMPS LOAD DESCRIPTION
CKT
NO.
K E Y
NOTES:
ISC: 5.16 kA
SCCR: 10 kA
LOCATION: TELECOM ROOM 001 WIRE: 4
FED FROM: 100 A/3P @ 51-MDP GROUND BUS PHASE: 3
ENCLOSURE: NEMA PB 1 SOLID NEUTRAL VOLTS: 120/208 Wye
MOUNTING: SURFACE MAIN: 100 A MCB
PANEL B51IT-1
CIRCUIT KEY NOTES:
*TOTAL DEMAND CALCS SUBTRACT ANY REDUNDANT LOAD AND THE SMALLER OF ANY NONCOINCIDENT HVAC LOADS. THIS CALC IS DONE AT EACH PANEL.
TOTAL ESTIMATED DEMAND AMPS: 18.2 A
TOTAL CONNECTED AMPS: 18.15 A
Receptacles 0.54 kVA 100.00% 0.54 kVA TOTAL ESTIMATED DEMAND LOAD: 6.54 kVA
Power 6 kVA 100.00% 6 kVA TOTAL CONNECTED LOAD: 6.54 kVA
Lighting 0 kVA 0.00% 0 kVA
LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND
TOTALS*
LOAD SUMMARY
Total Amps: 21.17 16.67 16.67
Total Load: 2.54 kVA 2.00 kVA 2.00 kVA
-- 29 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 30 --
-- 27 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 28 --
-- 25 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 26 --
-- 23 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 24 --
-- 21 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 22 --
-- 19 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 20 --
-- 17 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 18 --
-- 15 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 16 --
-- 13 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 14 --
-- 11 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 12 --
-- 9 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 10 --
-- 7 -- -- -- -- -- -- 0 0 -- -- -- 1 20 A SPARE 8 --
5 CU-51-1 0 A 2 0 2 -- -- -- -- -- -- 6 --
3 TELECOM ROOM LIGHTING 20 A 1 12 12 12 0 2 -- -- -- -- -- -- 4 --
1 TELECOM ROOM RECEPTACLE 20 A 1 12 12 12 0.54 2 10 10 10 3 30 A L21-30R 2
K E Y
CKT
NO. LOAD DESCRIPTION
OCPD
AMPS P
WIRE
SIZE
H N G
A B C
WIRE
SIZE
G N H
OCPD
P AMPS LOAD DESCRIPTION
CKT
NO.
K E Y
NOTES:
ISC: 3.60 kA
SCCR: 10 kA
LOCATION: TELECOM ROOM 001 WIRE: 4
FED FROM: 100 A/3P @ 51-EDC GROUND BUS PHASE: 3
ENCLOSURE: NEMA PB 1 SOLID NEUTRAL VOLTS: 120/208 Wye
MOUNTING: SURFACE MAIN: 100 A MCB
PANEL B51IT-1-CR
reby certify that this plan, specification o ort was prepared by me or under my dire ervision and that I am a duly Licensed ineer under the laws of the State of Minn me:
e: 03/30/202205-06-2022
ALEXANDER S. QUAST
06/14/2024 53095
RECORD DOCUMENTS 06/14
RECORD
DRAWINGS
THIS IS A RECORD DRAWING BASED ON INFORMATION RECEIVED FROM THE
CONTRACTOR AND IS TO BE USED FOR THE SOLE PURPOSE OF MAINTENANCE OF
THE ORIGINAL FACILITY FOR WHICH THIS DRAWING WAS PREPARED AND NOT
FOR ADDITIONAL CONSTRUCTION.No DATEREVISION
100% CD 03/30
RECORD DOCUMENTS 06/14
No DATEREVISION
RECORD DOCUMENTS 06/21/24 06/21/2024
-RECORD DOCUMENT-
June 21, 2024 This Record Document has been prepared based on
Designer of Record drawings with Contractor provided markups through the construction phase of the project at the direction of the VA.
While the construction information is believed to be reliable, Architect/Engineer cannot assure its accuracy, and is not responsible for the accuracy of this Record Document. Those relying on this Record
Document are advised to independently verify its accuracy before applying it for any purpose.
eby certify that this plan, specification rt was prepared by me or under my dir ervision and that I am a duly Licensed neer under the laws of the State of Min me:
TELECOM ROOM
EXAM
23C INTAKE
23C
PASSAGE
COCA
PHONE CLOSET
1B
CORRIDOR
C0C
No DATEREVISION
DRAWING TITLE
CHECKED BY
ST.CLOUD, MN 56303
VA MEDICAL CENTER
BUILDING No
LOCATION
DRAWING NO.DRAWN
DWG. OF
PROJECT TITLE
PLOT SCALE
PROJECT NO.
DATE:
CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP
FULLY
SPRINKLERED
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Engineer under the laws of the State of Minnesota.
Name:
Date: 03/30/2022
License Number: MN#
03/30/2022
B
IM
/2
.0
V A
S t C lo u d
E H
R M
I n fr a s tr u c tu re U p g ra d e s /6
-2
.B
.M
R
.r v t
/1
/2
:5
:3
A
M
51-M100
BASEMENT DEMOLITION PLAN
- MECHANICAL
EHRM INFRASTRUCTURE
UPGRADES
656-21-235
RDL DJC
16305
1/4" = 1'-0"
BASEMENT LEVEL DEMOLITION PLAN - MECHANICAL - TELECOM 001
0 4' 8'2'
N
KEYNOTES 1/51-M100:
1. REMOVE AND DISPOSE OF EXISTING FIRE SPRINKLER HEADS AND
BRANCH LINE BACK TO LOCATION SHOWN. PREPARE FOR
RECONNECTION.
2. EXISTING 2" STEAM RISER TO REMAIN.
3. EXISTING 1" CONDENSATE RISER TO REMAIN.
4. EXISTING CRAWL SPACE ACCESS DOOR.
FIELD VERIFICATION NOTES
1. THE HVAC CONTRACTOR SHALL VISIT THE SITE PRIOR TO BID TO FIELD VERIFY ALL EXISTING CONDITIONS WHICH MAY AFFECT THEIR
BID. THE FOLLOWING ITEMS SHALL BE VERIFIED:
A. EXACT PLACEMENT, SIZE, CAPACITY, MANUFACTURER AND CONDITION OF ALL EXISTING HVAC EQUIPMENT WITHIN SCOPE OF
WORK, WHETHER EXPLICITLY SHOWN OR NOT.
B. SIZE AND LOCATION OF ALL EXISTING DUCTWORK.
C. SIZE AND LOCATION OF ALL EXISTING GRILLES, REGISTERS AND DIFFUSERS.
D. SIZE AND LOCATION OF ALL EXISTING THERMOSTATIC CONTROL DEVICES.
E. SIZE AND LOCATION OF ALL EXISTING PLUMBING AND HYDRONIC PIPING.
2. ALL REFERENCES ON THESE DRAWINGS TO EXISTING EQUIPMENT, DUCTWORK, DIFFUSERS, THERMOSTATS AND PIPING ARE FOR REFERENCE ONLY. IT IS THE RESPONSIBLITY OF THE CONTRACTOR TO VERIFY ALL THESE ITEMS PRIOR TO BID AND INCLUDE IN THEIR
BID ANY AND ALL AMOUNTS REQUIRED TO ACCOMMODATE EXISTING CONDITIONS.
3. NO ALLOWANCES WILL BE MADE AFTER THE PROJECT HAS BEEN AWARDED FOR FAILURE TO VERIFY EXISTING CONDITIONS.
4. ANY DISCREPANCIES WHICH MAY AFFECT THE CONTRACTORS BID SHALL BE BROUGHT TO THE ATTENTION OF THE ENGINEER AND
ARCHITECT FOR DIRECTION.
100% CD 03/30 06/14/2024
RECORD DOCUMENTS 06/14 Robert D. Lowe
24706
RECORD
DRAWINGS
THIS IS A RECORD DRAWING BASED ON INFORMATION RECEIVED FROM THE
CONTRACTOR AND IS TO BE USED FOR THE SOLE PURPOSE OF MAINTENANCE OF
THE ORIGINAL FACILITY FOR WHICH THIS DRAWING WAS PREPARED AND NOT
FOR ADDITIONAL CONSTRUCTION.
No DATEREVISION
RECORD DOCUMENTS 06/21/24 06/21/2024
-RECORD DOCUMENT-
June 21, 2024 This Record Document has been prepared based on
Designer of Record drawings with Contractor provided markups through the construction phase of the project at the direction of the VA.
While the construction information is believed to be reliable, Architect/Engineer cannot assure its accuracy, and is not responsible for the accuracy of this Record Document. Those relying on this Record
Document are advised to independently verify its accuracy before applying it for any purpose.
T
TELECOM ROOM
EXAM
23C INTAKE
23C
PASSAGE
COCA
PHONE CLOSET
1B
CORRIDOR
C0C
AC-51-1
CP-51-1
RACK PROVIDED
BY OTHERS
CU-51-1
S U
C
L
IQ
No DATEREVISION
DRAWING TITLE
CHECKED BY
ST.CLOUD, MN 56303
VA MEDICAL CENTER
BUILDING No
LOCATION
DRAWING NO.DRAWN
DWG. OF
PROJECT TITLE
PLOT SCALE
PROJECT NO.
DATE:
CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP
FULLY
SPRINKLERED
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Engineer under the laws of the State of Minnesota.
Name:
Date: 03/30/2022
License Number: MN#
03/30/2022
B
IM
/2
.0
V A
S t C lo u d
E H
R M
I n fr a s tr u c tu re U p g ra d e s /6
-2
.B
.M
R
.r v t
/1
/2
:5
:4
A
M
51-M200
BASEMENT FLOOR PLAN -
MECHANICAL
EHRM INFRASTRUCTURE
UPGRADES
656-21-235
RDL DJC
16305
1/4" = 1'-0"
BASEMENT LEVEL PLAN - MECHANICAL - TELECOM 001
N
0 4' 8'2'
FIELD VERIFICATION NOTES
1. THE HVAC CONTRACTOR SHALL VISIT THE SITE PRIOR TO BID TO FIELD VERIFY ALL EXISTING CONDITIONS WHICH MAY AFFECT THEIR
BID. THE FOLLOWING ITEMS SHALL BE VERIFIED:
A. EXACT PLACEMENT, SIZE, CAPACITY, MANUFACTURER AND CONDITION OF ALL EXISTING HVAC EQUIPMENT WITHIN SCOPE OF
WORK, WHETHER EXPLICITLY SHOWN OR NOT.
B. SIZE AND LOCATION OF ALL EXISTING DUCTWORK.
C. SIZE AND LOCATION OF ALL EXISTING GRILLES, REGISTERS AND DIFFUSERS.
D. SIZE AND LOCATION OF ALL EXISTING THERMOSTATIC CONTROL DEVICES.
E. SIZE AND LOCATION OF ALL EXISTING PLUMBING AND HYDRONIC PIPING.
2. ALL REFERENCES ON THESE DRAWINGS TO EXISTING EQUIPMENT, DUCTWORK, DIFFUSERS, THERMOSTATS AND PIPING ARE FOR REFERENCE ONLY. IT IS THE RESPONSIBLITY OF THE CONTRACTOR TO VERIFY ALL THESE ITEMS PRIOR TO BID AND INCLUDE IN THEIR
BID ANY AND ALL AMOUNTS REQUIRED TO ACCOMMODATE EXISTING CONDITIONS.
3. NO ALLOWANCES WILL BE MADE AFTER THE PROJECT HAS BEEN AWARDED FOR FAILURE TO VERIFY EXISTING CONDITIONS.
4. ANY DISCREPANCIES WHICH MAY AFFECT THE CONTRACTORS BID SHALL BE BROUGHT TO THE ATTENTION OF THE ENGINEER AND
ARCHITECT FOR DIRECTION.
KEYNOTES 1/51-M200:
1. PROVIDE NEW WALL-MOUNTED SPLIT SYSTEM AC UNIT.
2. PROVIDE NEW THERMOSTAT.
3. ROUTE REFRIGERANT PIPING TO NEW AIR COOLED CONDENSING UNIT
LOCATED ON GRADE.
4. ROUTE 1" PUMPEDCONDENSATE PIPING TO MOP SINK IN HAC 14.
5. PROVIDE NEW CONDENSATE PUMP. DRIP PAN CONDENSATE PIPING IN
TR ROOM. SEE DETAIL FOR REQUIREMENTS.
6. PROVIDE DRIP PAN FOR CONDENSATE PIPING.
7. EXTEND FIRE SPRINKLER BRANCH LINE AND PROVIDE NEW FIRE
SPINKLER HEAD.
8. PROVIDE NEW AIR COOLED CONDENSING UNIT CU-51-1. PROVIDE
CONCRETE PAD. REFER TO REFRIGERANT PIPING DETAIL 1/0-GM400
AND PAD MOUNTING DETAIL 3/0-GM400.
9. REFER TO 2/0-GM401 FOR WALL PENETRATION SEALING DETAIL.
100% CD 03/30 06/14/2024
RECORD DOCUMENTS 06/14 Robert D. Lowe
24706
RECORD
DRAWINGS
THIS IS A RECORD DRAWING BASED ON INFORMATION RECEIVED FROM THE
CONTRACTOR AND IS TO BE USED FOR THE SOLE PURPOSE OF MAINTENANCE OF
THE ORIGINAL FACILITY FOR WHICH THIS DRAWING WAS PREPARED AND NOT
FOR ADDITIONAL CONSTRUCTION.
No DATEREVISION
RECORD DOCUMENTS 06/21/24 06/21/2024
-RECORD DOCUMENT-
June 21, 2024 This Record Document has been prepared based on
Designer of Record drawings with Contractor provided markups through the construction phase of the project at the direction of the VA.
While the construction information is believed to be reliable, Architect/Engineer cannot assure its accuracy, and is not responsible for the accuracy of this Record Document. Those relying on this Record
Document are advised to independently verify its
LEGEND
CORRIDOR OUTLINE
VFY EXIST
BUILDING OUTLINE
VFY EXIST
TO 8TH ST WEST ONLYTO 8TH ST EAST & WEST
44TH AVE.
TRAIL 1
TRAIL 2
TRANSFER
SWITCH
CAPACITOR
BANK (3)
SWITCH
(2)
15KV
MAIN
SW
BATT
35 KV
TO
15 KV
TRANSFORMER
35KV
FUSED
SWITCH
METER 35KV
SWITCH
GRAVEL
GRAVEL
GRAVEL
EXISTING
ROAD
CHAIN LINK FENCE
CHAIN LINK FENCE
16' GATE
GRAVEL
ELECTRICAL
SUBSTATION
G E N E R A T O R
FUEL LINES
CONDU ITS TO TU NNEL
M V
D U
C T
B A
N K
1 1 2 W
PHARMACY ADDITION
11 2 E
G E N E R A T O R
B
CORRIDOR LINK
A
C T
TR
A
IL
ER
174 s .f.
256 s .f.
185 s .f.
149 s ..f.
155 s .f.
104 s .f.
70 s. .f .
72 s .f.
110 s .f.
276 s .f.
112 s .f.
99 s .f.
57 s .f.
146 s .f.
434 s .f.
R A
MP
U P
1:
M A X
R A
MP
U P
1:
M A X
RA
M P
UP
1:2 0 M
AX
TRANSFER
SWITCH
CAPACITOR
BANK (3)
SWITCH
(2) 15KV
MAIN
SW
BATT
35 KV
TO
15 KV
TRANSFORMER
35KV
FUSED
SWITCH
METER 35KV
SWITCH
.3
TRANSFORMER
BUILD ING
#91
5,000 GAL.
UNDERGROUND
DIESEL FUEL TANK
EXISTIN G G AS SU P P LY EQ U IP M EN T TO R EM AIN
O P ER ATIO N AL DU R IN G D EM O LITIO N AN D N EW
C O N STR U C TIO N. P R O TEC T EQU IP M EN T AN D
P IP ELIN ES IN AC C O R D AN C E W ITH G AS SU P P LIER 'S
R EC O M M EN D ATIO N S
N EW G AS SU P P LY M AIN
IN TO B U ILD IN G
SP AR E
P H O N E LIN E
EXTEN D S TO
E XISTIN G
P H O N E IN
B O ILER R O O M
P ER P LAN .
SP AR E
P H O N E
LIN E TO
M ETER
TU N N EL
E XTEN D S
A D D ITIO N AL
2'- 0" U N D ER
B U ILD IN G
FUEL LINE
VENT LINE
1,000 GAL.
UNDERGROUND
DIESEL FUEL
TANK
1,000/5,000 GAL.
UNDERGROUND
DIESEL FUEL TANK
1,000 GAL.
UNDERGROUND
DIESEL FUEL TANK
1,000 GAL.
UNDERGROUND
DIESEL FUEL TANK
S 1
LIG H T
N EW G AS SU P P LY
(C O O R D IN ATE W ITH SU P P LIER )
12"D
10"D
"D
TP TP
EXIST. BUILDING
EXIST.
BUS STOP
CC
L O
O P
16"
20"
12"
3"
8"
DN
0.
0’
BIRDCAGE
B
IR
D C
A G
E
NSP ELECTRICAL
FOR HWY DEPT
T101
I.T.
CHILLER
C O
NC
. B
LO
CKS
PAT
I O
C O
NC
. B
LO
CKS
PAT
I O
C O
NC
. B
LO
CKS
PAT
I O
C O
NC
. B
LO
CKS
PAT
I O
C O
NC
. B
LO
CKS
PAT
I O
C O
NC
. B
LO
CKS
PAT
I O
C O
NC
. B
LO
CKS
PAT
I O
C O
NC
. B
LO
CKS
PAT
I O
VESTIBULE
DN
DN
DN
FD
DN
F B
F
B
F B
F
B
F B
F
B
PASS
THROUGH
LINK TO
BUILDI NG 51
6 3. 32 56
1 13 5. 35 78
PARKING
NO
PARKING
93 49
37 6
109 5
1A
S M
O K
E B
L D
G
SMOKE
BLDG
SMOKE
BLDG
S M
O K
E B
L D
G
SMOKE
BLDG
M.H.
STOR.
SMOKE
BLDG
SMOKE
BLDG
SMOKE
BLDG
SMOKE
BLDG
SMOKE
BLDG
STOR.
BIO-
HAZ.
SAUK RIVER
GP
HOLDING POND
OWNER AND
CONSULTANTS:
CONTACT:
ADDRESS:
JUSTIN LAPPIN
ST CLOUD VA MEDICAL CENTER
4801 VETERANS DRIVE
ST. CLOUD, MN 56303
NAME:
ADDRESS:
CONTACT:
ADVANCED STRUCTURAL TECHNOLOGIES
7301 OHMS LANE; SUITE 215
EDINA, MN 55439
JOHN LEVAR
PHONE:
NAME:
ADDRESS:
CONTACT:
SPECIALIZED ENGINEERING SOLUTIONS
10360 ELLISON CIRCLE
OMAHA, NE 68134
KRIS BURNHAM
PHONE: 402-991-5520
NAME:
ADDRESS:
CONTACT:
PHONE:
NAME:
ADDRESS:
CONTACT:
PHONE:
NAME:
ADDRESS:
CONTACT:
PHONE:
ANDERSON ENGINEERING OF MN, LLC
13605 1ST AVE NORTH, SUITE 100
PLYMOUTH, MN 55441
LEE KOPPY
763-412-4000
ARCHITECT:
ANDERSON ENGINEERING OF MN, LLC
13605 1ST AVE NORTH, SUITE 100
PLYMOUTH, MN 55441
EDWARD MARKFORT
763-412-4000
952-906-7196
SPECIALIZED ENGINEERING SOLUTIONS
10360 ELLISON CIRCLE
OMAHA, NE 68134
KRIS BURNHAM
402-991-5520
No DATEREVISION
DRAWING TITLE
CHECKED BY
ST.CLOUD, MN 56303
VA MEDICAL CENTER
BUILDING No
LOCATION
DRAWING NO.DRAWN
DWG. OF
PROJECT TITLE
PLOT SCALE
PROJECT NO.
COVER
DATE:
APPROVED: APPROVED: PROJECTS SECTION MANAGER
APPROVED: OIT MANAGER DATE: APPROVED: ASSISTANT CHIEF ENGINEER DATE:
APPROVED: SAFETY MANAGER
APPROVED: CHIEF OF POLICE
APPROVED: PATIENT SAFETY
DATE:
DATE:
DATE: APPROVED: EMS MANAGER
APPROVED: M/O MANAGER
DATE:
DATE:
DATE:DATE:
APPROVED: MEDICAL CENTER DIRECTOR
APPROVED: PROJECT COR DATE:
APPROVED: INFECTION CONTROL NURSE DATE:
APPROVED: SERVICE LINE DIRECTOR
APPROVED: GEMS COORDINATOR DATE:
DATE:
APPROVED: NURSE EXECUTIVE
APPROVED: CHIEF OF STAFF DATE:
APPROVED: DIRECTOR FMS
APPROVED: ASSOCIATE DIRECTOR
DATE:
DATE:
DATE:
DATE:APPROVED: DATE:
APPROVED: DATE:
APPROVED: DATE:
Main Campus, St. Cloud, Minnesota St. Cloud VA Health Care System
N
CONSULTANT ARCHITECT/ENGINEER OF RECORD
FULLY
SPRINKLERED
VICINITY MAP:
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PHONE: 320-255-6346 x7354
CIVIL ENGINEER:
VA PRIMARY COR:
TELECOMMUNICATIONS ENGINEER:
CONTACT:
ADDRESS: ST CLOUD VA MEDICAL CENTER
4801 VETERANS DRIVE
ST. CLOUD, MN 56303
ADDITIONAL CORs:
STRUCTURAL ENGINEER:
MECH/ELEC/PLUMB/FIRE ENGINEER:
RECORD DOCUMENTS
CONTACT: COREY SELF
BRAEDAN HINOJOSA
CONTACT:
-RECORD DOCUMENT-
June 21, 2024
This Record Document has been prepared based on
Designer of Record drawings with Contractor provided markups through the construction phase of the project at the direction of the VA.
While the construction information is believed to be reliable, Architect/Engineer cannot assure its accuracy, and is not responsible for the accuracy of this Record Document. Those relying on this Record
Document are advised to independently verify its accuracy before applying it for any purpose.
C
U s e rs
\P u b li c \D o c u m e n ts \R e v it
P ro je c ts
\1 -1
-R
E
M a rk fo rt
.r v t
/2
/2
:5 :1
P
M
116-GI000
BUILDING 116 COVER SHEET &
SHEET INDEX
EHRM INFRASTRUCTURE
UPGRADES
656‐21‐235
03/30/2022
EM EM
16305
BUILDING 116 - EHRM INFRASTRUCTURE UPGRADES
0APPROX 150' 300'75'
SHEET INDEX - BUILDING 116
SHEET NO. SHEET TITLE
116-GI000 BUILDING 116 COVER SHEET & SHEET INDEX
116-GI111 FIRST FLOOR - INFECTION CONTROL & PHASING PLAN
116-AS110 FIRST FLOOR PLANS
116-TD110 FIRST FLOOR PLAN - TELECOM - DEMOLITION
116-TN110 FIRST FLOOR PLAN - TELECOMMUNICATIONS
116-TN210 FIRST FLOOR PLAN - TELECOM - CABLE DISTANCE
116-TN400 ENLARGED PLANS - TELECOMMUNICATIONS
116-E201 FIRST FLOOR - ELECTRICAL
116-E300 ELECTRICAL ENLARGED PLANS
116-M101 FIRST FLOOR DEMOLITION - MECHANICAL
116-M201 FIRST FLOOR REMODEL - MECHANICAL
SEE GENERAL SHEETS FOR ADDITIONAL INFORMATION
ROOM SCHEDULE
NO. NAME C
A
B
LI
N G
P A
T C
H P
A N
E L
B A
C K
B O
N E
P O
W E
R
B O
N D
IN
G
U P
S
D E
D
IC
A T
E D
C O
O
LI
N G
T E
M P
E R
A T
U R
E
H U
M
ID
IT
Y
R A
C K
S E
N S
O R
S P
A C
E
AREA
WIDTH
(FT)
LENGTH
(FT)
HT TO
CLG
STRUCT REMARKS
FIRST FLOOR
111 TELECOM ROOM X X AC X X X X X 61 SF 6.6 9.3 15.00 UPDATE EXIST IT/DATA ROOM TO EHRM TELECOM ROOM
STANDARDS. SEE TELECOM DRAWINGS
OPENING SCHEDULE
VA Building Number
ASSOCIATED ROOMS OPENING PANEL INFORMATION FRAME INFORMATION
H D
W G
R O
U P
F
IR
E L
A B
E L
(M
IN
G A
S K
E T
E
LE
C T
R
IC
A L
S L
A B
E L
COMMENTSFROM ROOM NAME TO ROOM NAME NUMBER WIDTH HEIGHT
PANEL
TYPE
2ND
PANEL
TYPE
PANEL
GLAZING FRAME TYPE
FRAME
GLAZING
HAZARDOUS MATERIAL SCHEDULE
LEVEL
ROOM
NO. ROOM NAME
QUESTIONABLE HAZARDOUS
ELEMENT POSSIBLE ABATEMENT ACTION
FIRST FLOOR 111 TELECOM ROOM NONE NONE
HAZARDOUS MATERIALS MAY BE ENCOUNTERED THROUGHOUT THE DISTRIBUTION ROUTING THROUGH CEILING PLENUMS AND UTILITY TUNNELS. INSTALLATION OF DISTRIBUTION SHALL NOT
DISTURB QUESTIONABLE HAZARDOUS MATERIAL.
ICRA PHASE CONSTRUCTION ROOM SCHEDULE
LEVEL
ROOM
NO. ROOM NAME
CAI BLDG NAME /
FUNCTION
CONSTRUCTION
PROJECT ACTIVITY
INFECTION CONTROL
RISK GROUP
CONTROL
PROCEDURE CLASS SECTION
CONSTRUCTION ZONE /
OCCUPIED CONSTR
DAY /
NIGHT
FIRST FLOOR 111 TELECOM ROOM OUTPATIENT MENTAL
HEALTH
TYPE C GROUP 1 CLASS II WEST OCCUPIED CONSTRUCTION NIGHT
SEE GENERAL NOTES SHEET FOR CONSTRUCTION INFECTION CONTROL RISK ASSESSMENT (ICRA) DESCRIPTIONS. TYPE, GROUP AND CLASS SELECTED TO BEST OF DESIGN TEAM'S KNOWLEDGE.
FINAL DETERMINATION BY THE VA WILL BE MADE AT A LATER DATE.
RECORD DOCUMENTS 06/21/24
LOW VISION
CLINIC
NORTH
VESTIBULE
STAFF
SPEECH
THERAPY
TREATMENT
ROOM 1
TREATMENT
ROOM 2
TREATMENT
ROOM 3
TREATMENT
ROOM 4
TREATMENT
ROOM 5
TREATMENT
ROOM 7
TREATMENT
ROOM 6
MAILROOM
CORRIDOR
PT
CHARTING
GROUP
MTG ROOM
OP GYM
PT GYM
PROSTH.
STORAGE
EQUIP
STORAGE
PATIENT
TOILET
FEMALE
TOILET
MALE
TOILET
MECHANICAL
LOW
VOLTAGE
ELECTRICAL
ELECTRICAL
CORRIDOR
WAITING
WAITING
SOUTH
VESTIBULE
RECEPTION
HAC
SCHEDULING
CLEAN
UTILITY
WC
STOR.
BALANCE
CLINIC
EQUIP
STORAGE
SPEECH
THERAPY
VIST
COORDINATOR
PROVIDER
OFFICE
LPN
REHAB
SUPERVISOR
CONSULTATION
ROOM
PROCEDURE
ROOM
O.T.
CHARTING
O.T.
CLINIC
CORRIDOR
CORRIDOR
ADL
BATHROOM
T-9
T-8
PATIENT
TOILET
SPEECH
THERAPY
ADL
KITCHEN
ADL
BEDROOM
154 SOILED
DN
REF.
FDFD
FD
FD
FD
MALE TOILET
FEMALE
TOILET
SOILED LINEN
CLEAN LINEN
RECYCLING
HALLWAY
CL LINEN
FD
FD
DWREF.
154A
CLOSET
151A
CLOSET
DN
TELECOM
ROOM
INFECTION CONTROL RISK ASSESSMENT (ICRA) LEGEND
LIMITS OF CONSTRUCTION
1 HOUR FIRE RATED ICRA / CONSTRUCTION BARRIER
LOCATION, AND DOOR, WHERE SHOWN
TEMPORARY NON-RATED (PLASTIC SHEETING) CONSTRUCTION BARRIER
LOCATION, WHERE APPROVED BY THE VA FOR USE IN RISK TYPE B.
UPGRADE TO 1 HOUR RATED PARTITION WHEN DIRECTED BY THE VA
No DATEREVISION
DRAWING TITLE
CHECKED BY
ST.CLOUD, MN 56303
VA MEDICAL CENTER
BUILDING No
LOCATION
DRAWING NO.DRAWN
DWG. OF
PROJECT TITLE
PLOT SCALE
PROJECT NO.
DATE:
CONSULTANT ARCHITECT/ENGINEER OF RECORD
FULLY
SPRINKLERED
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
RECORD DOCUMENTS
-RECORD DOCUMENT-
June 21, 2024
This Record Document has been prepared based on
Designer of Record drawings with Contractor provided markups through the construction phase of the project at the direction of the VA.
While the construction information is believed to be reliable, Architect/Engineer cannot assure its accuracy, and is not responsible for the accuracy of this Record Document. Those relying on this Record
Document are advised to independently verify its accuracy before applying it for any purpose.
C
U s e rs
\P u b li c \D o c u m e n ts \R e v it
P ro je c ts
\1 -1
-R
E
M a rk fo rt
.r v t
/1
/2
:3
:4
A
M
116-GI111
FIRST FLOOR - INFECTION
CONTROL & PHASING PLAN
EHRM INFRASTRUCTURE
UPGRADES
656‐21‐235
03/30/2022
EM BMW
16305
1/8" = 1'-0"
FIRST FLOOR - CONST BARRIER PLAN
ROOM ICRA SCHEDULE
LEVEL
ROOM
NO. ROOM NAME CAI BLDG NAME / FUNCTION CONSTRUCTION PROJECT ACTIVITY INFECTION CONTROL RISK GROUP CONTROL PROCEDURE CLASS
FIRST FLOOR 111 TELECOM ROOM OUTPATIENT MENTAL HEALTH TYPE C GROUP 1 CLASS II
SEE GENERAL NOTES SHEET FOR CONSTRUCTION INFECTION CONTROL RISK ASSESSMENT (ICRA) DESCRIPTIONS. TYPE, GROUP AND CLASS SELECTED TO BEST OF DESIGN TEAM'S KNOWLEDGE.
FINAL DETERMINATION BY THE VA WILL BE MADE AT A LATER DATE.
N
0 8' 16'4'
NORTH
VESTIBULE
STAFF
SPEECH
THERAPY
TREATMENT
ROOM 1
TREATMENT
ROOM 2
TREATMENT
ROOM 3
TREATMENT
ROOM 4
TREATMENT
ROOM 5
TREATMENT
ROOM 7
TREATMENT
ROOM 6
MAILROOM
CORRIDOR
PT
CHARTING
GROUP
MTG ROOM
OP GYM
PT GYM
PROSTH.
STORAGE
EQUIP
STORAGE
PATIENT
TOILET
FEMALE
TOILET
MALE
TOILET
MECHANICAL
LOW
VOLTAGE
ELECTRICAL
ELECTRICAL
CORRIDOR
WAITING
WAITING
SOUTH
VESTIBULE
RECEPTION
HAC
SCHEDULING
CLEAN
UTILITY
WC
STOR.
BALANCE
CLINIC
EQUIP
STORAGE
SPEECH
THERAPY
VIST
COORDINATOR
PROVIDER
OFFICE
LPN
REHAB
SUPERVISOR
CONSULTATION
ROOM
PROCEDURE
ROOM
O.T.
CHARTING
O.T.
CLINIC
CORRIDOR
CORRIDOR
ADL
BATHROOM
T-9
T-8
PATIENT
TOILET
SPEECH
THERAPY
ADL
KITCHEN
ADL
BEDROOM
154 SOILED
DN
REF.
FDFD
FD
FD
FD
MALE TOILET
FEMALE
TOILET
SOILED LINEN
CLEAN LINEN
RECYCLING
HALLWAY
CL LINEN
FD
FD
DWREF.
154A
CLOSET
151A
CLOSET
DN
TELECOM
ROOM
6'-7 1/4"
9' -3
/4
116-AS110
TELECOM
ROOM
4' -7
2'
-6
2' -2
IN-03.01
TELECOM
ROOM
TELECOM
ROOM
No DATEREVISION
DRAWING TITLE
CHECKED BY
ST.CLOUD, MN 56303
VA MEDICAL CENTER
BUILDING No
LOCATION
DRAWING NO.DRAWN
DWG. OF
PROJECT TITLE
PLOT SCALE
PROJECT NO.
DATE:
CONSULTANT ARCHITECT/ENGINEER OF RECORD
FULLY
SPRINKLERED
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
RECORD DOCUMENTS
-RECORD DOCUMENT-
June 21, 2024
This Record Document has been prepared based on
Designer of Record drawings with Contractor provided markups through the construction phase of the project at the direction of the VA.
While the construction information is believed to be reliable, Architect/Engineer cannot assure its accuracy, and is not responsible for the accuracy of this Record Document. Those relying on this Record
Document are advised to independently verify its accuracy before applying it for any purpose.
C
U s e rs
\P u b li c \D o c u m e n ts \R e v it
P ro je c ts
\1 -1
-R
E
M a rk fo rt
.r v t
/1
/2
:3
:3
A
M
116-AS110
FIRST FLOOR PLANS
EHRM INFRASTRUCTURE
UPGRADES
656‐21‐235
03/30/2022
EM EM
16305
N
0 8' 16'4' 1/8" = 1'-0"
FIRST FLOOR - OVERALL PLAN
1/4" = 1'-0"
ENLARGED FLOOR PLAN
1/4" = 1'-0"
DEMOLITION PLAN
1/4" = 1'-0"
REFLECTED CEILING PLAN
DE1
RC1 RC2
_DEMOLITION PLAN KEYED NOTES
DE1 PREPARE WALL FOR PLYWOOD BACKBOARD INSTALLATION AND EHRM
REQUIREMENTS, SEE FLOOR PLAN AND TELECOM DRAWINGS
NOTE: NOT ALL KEYED NOTES MAY BE USED ON EACH PLAN
_FLOOR PLAN KEYED NOTES
FL1 ALL FOUR PERIMETER WALL PARTITIONS APPLY 4' BY 8' AC GRADE ¾”
TRADE SIZE FIRE RATED PLYWOOD BACKBOARD FINISHED WITH
HIGH-GLOSS WHITE PAINT OVER TWO COATS OF FIRE RESISTANT PAINT
FOR SERVICE PROVIDER / SECURITY / VIDEO / ET CETERA. DO NOT PAINT
OVER FIRE RATING STAMP.
FL3 UPGRADE PARTITION TO 1 HOUR FIRE AND SMOKE BARRIER. PROVIDE
TESTED HEAD OF PARTITION ASSEMBLY WITH MATERIALS THAT RESIST
THE PASSAGE OF SMOKE. SEAL JOINT AT HEAD AND ALL PENETRATIONS
WITH FIRE CAULK.
FL20 TELECOM EQUIPMENT, SEE TELECOM DRAWINGS.
NOTE: NOT ALL KEYED NOTES MAY BE USED ON EACH PLAN
_REFLECTED CEILING PLAN KEYED NOTES
RC1 LED LIGHTING, SEE ELECTRICAL. IN FRONT OF AND BEHIND CABINET
ROWS PROVIDE 500 LUMENS IN HORIZONTAL AND 200 LUMENS IN THE
VERTICAL AT 3 FT AFF. OPERATED BY MOTION SENSOR PER CABINET
ROW OR SECTION.
RC2 OPEN TO STRUCTURAL FLOOR ABOVE
NOTE: NOT ALL KEYED NOTES MAY BE USED ON EACH PLAN
N
0 4' 8'2'
N
0 4' 8'2'
N
0 4' 8'2'
DE1
DE1
FL1 FL20
_SHEET NOTES
1. SEE GENERAL NOTES AND CAMPUS DRAWINGS FOR GENERAL
INFORMATION, LIFE SAFETY, ICRA, AND PHASING
2. ALL EXISTING CONDITIONS MUST BE FIELD VERIFIED BY THE
CONTRACTOR PRIOR TO DEMOLITION OR CONSTRUCTION. EXISTING
CONDITIONS THAT DIFFER FROM THOSE SHOWN MUST BE BROUGHT TO
THE ATTENTION OF THE C.O.R. TO INFORM THE ARCHITECTS AND
ENGINEERS.
3. THE INFORMATION SHOWN ON THE DRAWINGS IS BASED ON DRAWINGS
AND PHOTOGRAPHS PROVIDED BY THE C.O.R. COMBINED WITH
OBSERVATIONS AND SURVEYED DATA FROM THE ARCHITECTS AND
ENGINEERS.
4. SEE CIVIL, STRUCTURAL, TELECOM, ELECTRICAL, MECHANICAL, AND
PLUMBING DRAWINGS AND SPECIFICATIONS FOR ADDITIONAL
DEMOLITION AND CONSTRUCTION REQUIREMENTS.
5. PORTABLE FIRE EXTINGUISHERS (CO2 OR HALOGENATED TYPE AS
DETERMINED BY THE VA) WITH WALL MOUNT BRACKET AND CODE
REQUIRED SIGNAGE SHALL BE PROVIDED BY THE CONTRACTOR WITHIN
TELECOM ROOMS.
FL3
FL3
FL3
FL3
29 55
114 56
140140
177179 179
CLINIC
LOW VISION
VESTIBULE
NORTH
STAFF
THERAPY
SPEECH
ROOM 1
TREATMENT
ROOM 2
TREATMENT
ROOM 3
TREATMENT
ROOM 4
TREATMENT
ROOM 5
TREATMENT
ROOM 7
TREATMENT
ROOM 6
TREATMENT
MAILROOM
CORRIDOR126
CHARTING
PT
MTG ROOM
GROUP
OP GYM
PT GYM 123
STORAGE
PROSTH.
STORAGE
EQUIP.
TOILET
PATIENT
TOILET
FEMALE
TOILET
MALE
MECHANICAL
VOLTAGE
LOW
ELECTRICAL
ELECTRICAL
CORRIDOR
WAITING
WAITING
VESTIBULE
SOUTH
RECEPTION
HAC
SCHEDULING
UTILITY
CLEAN
STOR.
WC
CLINIC
BALANCE
STORAGE
EQUIP.
THERAPY
SPEECH
COORDINATOR
VIST
OFFICE
PROVIDER
LPN
SUPERVISOR
REHAB
ROOM
CONSULTATION
ROOM
PROCEDURE
CHARTING
O.T. 156
CLINIC
O.T.
CORRIDOR
CORRIDOR
BATHROOM
ADL
T-9
T-8
TOILET
PATIENT
THERAPY
SPEECH
KITCHEN
ADL
BEDROOM
ADL
SOILED
REF.
FDFD
FD
FD
FD
MALE TOILET
FEMALE
TOILET
SOILED LINEN
CLEAN LINEN
RECYCLING
HALLWAY
CL LINEN
FD
FD
DWREF.
154A
CLOSET
151A
CLOSET
DN
29 55
114 56
140140
177179 179
CLINIC
LOW VISION
VESTIBULE
NORTH
STAFF
THERAPY
SPEECH
ROOM 1
TREATMENT
ROOM 2
TREATMENT
ROOM 3
TREATMENT
ROOM 4
TREATMENT
ROOM 5
TREATMENT
ROOM 7
TREATMENT
ROOM 6
TREATMENT
MAILROOM
CORRIDOR126
CHARTING
PT
MTG ROOM
GROUP
OP GYM
PT GYM 123
STORAGE
PROSTH.
STORAGE
EQUIP.
TOILET
PATIENT
TOILET
FEMALE
TOILET
MALE
MECHANICAL
VOLTAGE
LOW
ELECTRICAL
ELECTRICAL
CORRIDOR
WAITING
WAITING
VESTIBULE
SOUTH
RECEPTION
HAC
SCHEDULING
UTILITY
CLEAN
STOR.
WC
CLINIC
BALANCE
STORAGE
EQUIP.
THERAPY
SPEECH
COORDINATOR
VIST
OFFICE
PROVIDER
LPN
SUPERVISOR
REHAB
ROOM
CONSULTATION
ROOM
PROCEDURE
CHARTING
O.T. 156
CLINIC
O.T.
CORRIDOR
CORRIDOR
BATHROOM
ADL
T-9
T-8
TOILET
PATIENT
THERAPY
SPEECH
KITCHEN
ADL
BEDROOM
ADL
SOILED
REF.
FDFD
FD
FD
FD
MALE TOILET
FEMALE
TOILET
SOILED LINEN
CLEAN LINEN
RECYCLING
HALLWAY
CL LINEN
FD
FD
DWREF.
154A
CLOSET
151A
CLOSET
DN
C
C
C
C
C
MAILROOM
RECEPTION
MAILROOM
RECEPTION
C
116-TD110
LIMITS OF DATA CABLING DEMOLITION
1D
2D
2D 2D
1D
2D
2D 2D
2D
2D
2D
2D
2D
2D
WAP
WAP
WAP
WAP
2D
2D
2D
WAP
2D
2D
2D
2D
2D2D2D
2D 2D 2D
2D 2D 2D
2D2D2D
1D
2D
2D
2D
E E E
EEE
E
E
E
E
E
E
E
E
E
E
E
EEE
E E E
E
E
E E
EE
E
E
E
E
E
E
E
E
E
E
E
E
EE
E
2D
2D
2D
E
E
E
2D
E
2D
2D
2D
E
E
E
2D E
E
E
E
E
2D
2D
2D
2D
E
E
E
E
WAP
2D
2D2D
2D E
E
E
E
E
2D
2D
2D
2DE
E
E 2D
WAP
2D
E
E 2D
E
EE
2D 2D
E
6D
EWAP
E E E
E
E E
E
EEE
E
E
E
E E
E
12"x2"
"x
2"
12"x2"
"x
2"
12"x2"12"x2"
"x
2"
"x
2"
12"x2"
"x
2"
"x 2"
12"x2"
E
E
"x
2"
E
4"
DOWN
E
4"4"2"
DR
DR
SP R
D
D
E
DATA
RACKS
E
4" DOWN
E
4"4"2" E
RECORD DOCUMENTS
No DATEREVISION
DRAWING TITLE
CHECKED BY
ST.CLOUD, MN 56303
VA MEDICAL CENTER
BUILDING No
LOCATION
DRAWING NO.DRAWN
DWG. OF
PROJECT TITLE
PLOT SCALE
PROJECT NO.
DATE:
CONSULTANT ARCHITECT/ENGINEER OF RECORD
FULLY
SPRINKLERED
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
-RECORD DOCUMENT-
June 21, 2024
This Record Document has been prepared based on
Designer of Record drawings with Contractor provided markups through the construction phase of the project at the direction of the VA.
While the construction information is believed to be reliable, Architect/Engineer cannot assure its accuracy, and is not responsible for the accuracy of this Record Document. Those relying on this Record
Document are advised to independently verify its accuracy before applying it for any purpose.
RECORD DOCUMENTS 06/21/24
B
IM
/2
.0
V A
S t C lo u d E
H R
M I n fr a s tr u c tu re U p g ra d e s /6
-2
.B
.T
R
.r v t
/6
/2
:3
:0
P M
116-TD110
FIRST FLOOR PLAN -
TELECOM - DEMOLITION
EHRM INFRASTRUCTURE
UPGRADES
656‐21‐235
03/30/2022
KSB SSK
16305
SHEET NOTES:
1. EXISTING TELECOMMUNICATIONS CAGE AND RACK SHALL BE INCLUDED WITHIN THE SCOPE OF DEMOLITION. EXISTING CABLING AND ASSOCIATED OUTLETS SHALL BE REMOVED AND REPLACED 1 FOR 1 AND REFED FROM DISTRIBUTION EQUIPMENT LOCATED WITHIN THE NEW TELECOMMUNICATIONS ROOM. REFER TO GENERAL CABLING NOTES FOR APPROXIMATE QUANTITIES. REFER TO NEW WORK
PLANS FOR SERVING COMMUNICATIONS ROOM LOCATION AND NEW CABLING ROUTES.
2. EXISTING CABLE TRAY, SECURITY CAMERAS, GROUND BUS BARS, AND RACKS FROM DECOMMISSIONED
ROOMS ARE TO BE REUSED, WHEN POSSBILE, IN NEW CONSTRUCTION TRS.
N
0 8' 16'4' 1/8" = 1'-0"1
FIRST FLOOR PLAN - TELECOM - DEMOLITION
1/4" = 1'-0"2
ENLARGED PLAN - EXIST RM 111 - TELECOM - DEMO
0 4' 8'2'
N
GENERAL NOTES:
A. REFER TO GENERAL DEMOLITION NOTES ON SHEET T000 FOR ADDITIONAL DEMOLITION SCOPE.
CABLING NOTE:
CABLING NOTES:
A. THE EXISTING CABLE COUNT ARE THE CABLES CURRENTLY PRESENT IN THE SPACE. THE CABLE
RELOCATION COUNT ARE THE NEW OR RELOCATED CABLES TO BE FED FROM THE SPACE. THE FINAL CABLE COUNT ARE THE CABLES THAT WILL BE PRESENT IN THE SPACE AT THE COMPLETION OF THE
PROJECT.
1. ROOM 111
EXISTING CABLE COUNT
DATA (CAT6): 0
DATA (CAT5e): 114
DATA (CAT5): 0
DATA (CAT3): 0
CABLE RELOCATION COUNT
DATA (CAT6): 0
DATA (CAT5e): 0
DATA (CAT5): 0
DATA (CAT3): 0
EXISTING CABLE TO REMAIN
DATA (CAT6): 0
DATA (CAT5e): 0
DATA (CAT5): 0
DATA (CAT3): 0
FINAL CABLE COUNT
DATA (CAT6): 0
DATA (CAT5e): 0
DATA (CAT5): 0
DATA (CAT3): 0
NORTH
VESTIBULE
STAFF
SPEECH
THERAPY
TREATMENT
ROOM 1
TREATMENT
ROOM 2
TREATMENT
ROOM 3
TREATMENT
ROOM 4
TREATMENT
ROOM 5
TREATMENT
ROOM 7
TREATMENT
ROOM 6
MAILROOM
CORRIDOR
PT
CHARTING
GROUP
MTG ROOM
OP GYM
PT GYM
PROSTH.
STORAGE
EQUIP
STORAGE
PATIENT
TOILET
FEMALE
TOILET
MALE
TOILET
MECHANICAL
LOW
VOLTAGE
ELECTRICAL
ELECTRICAL
CORRIDOR
WAITING
WAITING
SOUTH
VESTIBULE
RECEPTION
HAC
SCHEDULING
CLEAN
UTILITY
WC
STOR.
BALANCE
CLINIC
EQUIP
STORAGE
SPEECH
THERAPY
VIST
COORDINATOR
PROVIDER
OFFICE
LPN
REHAB
SUPERVISOR
CONSULTATION
ROOM
PROCEDURE
ROOM
O.T.
CHARTING
O.T.
CLINIC
CORRIDOR
CORRIDOR
ADL
BATHROOM
T-9
T-8
PATIENT
TOILET
SPEECH
THERAPY
ADL
KITCHEN
ADL
BEDROOM
154 SOILED
REF.
FDFD
FD
FD
FD
MALE TOILET
FEMALE
TOILET
SOILED LINEN
CLEAN LINEN
RECYCLING
HALLWAY
CL LINEN
FD
FD
DWREF.
154A
CLOSET
151A
CLOSET
DN
LOW VISION
CLINIC
NORTH
VESTIBULE
STAFF
SPEECH
THERAPY
TREATMENT
ROOM 1
TREATMENT
ROOM 2
TREATMENT
ROOM 3
TREATMENT
ROOM 4
TREATMENT
ROOM 5
TREATMENT
ROOM 7
TREATMENT
ROOM 6
MAILROOM
CORRIDOR
PT
CHARTING
GROUP
MTG ROOM
OP GYM
PT GYM
PROSTH.
STORAGE
EQUIP
STORAGE
PATIENT
TOILET
FEMALE
TOILET
MALE
TOILET
MECHANICAL
LOW
VOLTAGE
ELECTRICAL
ELECTRICAL
CORRIDOR
WAITING
WAITING
SOUTH
VESTIBULE
RECEPTION
HAC
SCHEDULING
CLEAN
UTILITY
WC
STOR.
BALANCE
CLINIC
EQUIP
STORAGE
SPEECH
THERAPY
VIST
COORDINATOR
PROVIDER
OFFICE
LPN
REHAB
SUPERVISOR
CONSULTATION
ROOM
PROCEDURE
ROOM
O.T.
CHARTING
O.T.
CLINIC
CORRIDOR
CORRIDOR
ADL
BATHROOM
T-9
T-8
PATIENT
TOILET
SPEECH
THERAPY
ADL
KITCHEN
ADL
BEDROOM
154 SOILED
REF.
FDFD
FD
FD
FD
MALE TOILET
FEMALE
TOILET
SOILED LINEN
CLEAN LINEN
RECYCLING
HALLWAY
CL LINEN
FD
FD
DWREF.
154A
CLOSET
151A
CLOSET
DN
C
C
C
C
C
C
TELECOM ROOM
116-TN400
LIMITS OF DATA CABLING REPLACEMENT
FROM ROOM 111
1D
2D
2D
2D 2D
1D
2D
WAP
WAP
WAP
2D 2D
2D
2D
2D
2D
2D
2D
WAP
2D 2D 2D
2D2D2D 2D
2D 2D 2D
2D2D2D
1D
2D
2D
2D
2D
WAP
2D
2D
2D
2D
E E E
EEE
E
E
E
E
E
E
E
E
E
E
E
EEE
E E E
E
E
E E
EE
E
E
E
E
E
E
E
E
E
E
E
E
EE
E
2D
2D
2D
2D
2D
2D
2D
2D
E
E
E
E
E
E
E
E
E
E
2D
2D
2D E
E 2D
6D
E
E
E
E
E 2D
E
2D
E 2D
WAP
E
E 2D
2D
2D
2D
2D
E
E
E
E
E
2D
WAP
2D
E
E
2D E
2D 2D
EE
12"x2"
"x
2"
12"x2" 12"x2"
"x
2"
1 CABLE TRAY
E
WAP
4"
2"
2"
2"
2"
2"
2"
E E
E E
E
E
E E
E
EEE
E
E
E
E E
E
"x
2"
12"x2"
"x
2"
12"x2"
"x
2"
"x
2"
E
E
"x
2"
E
4"
RECORD DOCUMENTS
No DATEREVISION
DRAWING TITLE
CHECKED BY
ST.CLOUD, MN 56303
VA MEDICAL CENTER
BUILDING No
LOCATION
DRAWING NO.DRAWN
DWG. OF
PROJECT TITLE
PLOT SCALE
PROJECT NO.
DATE:
CONSULTANT ARCHITECT/ENGINEER OF RECORD
FULLY
SPRINKLERED
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
-RECORD DOCUMENT-
June 21, 2024
This Record Document has been prepared based on
Designer of Record drawings with Contractor provided markups through the construction phase of the project at the direction of the VA.
While the construction information is believed to be reliable, Architect/Engineer cannot assure its accuracy, and is not responsible for the accuracy of this Record Document. Those relying on this Record
Document are advised to independently verify its accuracy before applying it for any purpose.
RECORD DOCUMENTS 06/21/24
B
IM
/2
.0
V A
S t C lo u d E
H R
M I n fr a s tr u c tu re U p g ra d e s /6
-2
.B
.T
R
.r v t
/6
/2
:3
:0
P M
116-TN110
FIRST FLOOR PLAN -
TELECOMMUNICATIONS
EHRM INFRASTRUCTURE
UPGRADES
656‐21‐235
03/30/2022
KSB SSK
16305
SHEET NOTES:
1. CONTRACTOR TO PROVIDE NEW WIRE BASKET, AS NEEDED, TO MAINTAIN A 50% OR LESS FILL OF THE CABLE TRAY SYSTEM FOR THE FLOOR. THE NEW WIRE BASKET WILL MATCH THE SIZE AND DISTANCE, EITHER BESIDE OR BELOW THE EXISTING CABLE TRAY, TO MATCH THE EXISTING TELECOM CABLE
TRAY.
2. PROVIDE JUNCTION BOX TO CONNECT FIBER CONDUIT ENTRY TO EXTEND CONDUIT PATHWAY TO THE
NEW TELECOM ROOM.
3. NEW B SIDE FIBER TO BE PULLED UTILIZING THE EXISTING FIBER PATH. ONCE THE A SIDE FIBER IS ACTIVATED AND IN USE, THE EXISTING FIBER CAN BE REMOVED. THE NEW B SIDE FIBER CAN THEN BE
ACTIVATED.
N
0 8' 16'4' 1/8" = 1'-0"
FIRST FLOOR PLAN - TELECOMMUNICATIONS
GENERAL NOTES:
A. REFER TO GENERAL NOTES ON SHEET T000 FOR ADDITIONAL SCOPE.
NORTH
VESTIBULE
STAFF
SPEECH
THERAPY
TREATMENT
ROOM 1
TREATMENT
ROOM 2
TREATMENT
ROOM 3
TREATMENT
ROOM 4
TREATMENT
ROOM 5
TREATMENT
ROOM 7
TREATMENT
ROOM 6
MAILROOM
CORRI DOR
PT
CHARTING
GROUP
MTG ROOM
OP GYM
PT GYM
PROSTH.
STORAGE
EQUIP
STORAGE
PATIENT
TOILET
FEMALE
TOILET
MALE
TOILET
MECHANI CAL
LOW
VOLTAGE
ELECTRICAL
ELECTRICAL
CORRI DOR
WAITING
WAITING
SOUTH
VESTIBULE
RECEPTION
HAC
SCHEDULING
CLEAN
UTILITY
WC
STOR.
BALANCE
CLINIC
EQUIP
STORAGE
SPEECH
THERAPY
VIST
COORDINATOR
PROVI DER
OFFICE
LPN
REHAB
SUPERVI SOR
CONSULTATION
ROOM
PROCEDURE
ROOM
O.T.
CHARTING
O.T.
CLINIC
CORRI DOR
CORRI DOR
ADL
BATHROOM
T-9
T-8
PATIENT
TOILET
SPEECH
THERAPY
ADL
KITCHEN
ADL
BEDROOM
154 SOILED
REF.
FDFD
FD
FD
FD
MALE TOILET
FEMALE
TOILET
SOILED LINEN
CLEAN LINEN
RECYCLING
HALLWAY
CL LINEN
FD
FD
DWREF.
154A
CLOSET
151A
CLOSET
DN
LOW VISION
CLINIC
NORTH
VESTIBULE
STAFF
SPEECH
THERAPY
TREATMENT
ROOM 1
TREATMENT
ROOM 2
TREATMENT
ROOM 3
TREATMENT
ROOM 4
TREATMENT
ROOM 5
TREATMENT
ROOM 7
TREATMENT
ROOM 6
MAILROOM
CORRI DOR
PT
CHARTING
GROUP
MTG ROOM
OP GYM
PT GYM
PROSTH.
STORAGE
EQUIP
STORAGE
PATIENT
TOILET
FEMALE
TOILET
MALE
TOILET
MECHANI CAL
LOW
VOLTAGE
ELECTRICAL
ELECTRICAL
CORRI DOR
WAITING
WAITING
SOUTH
VESTIBULE
RECEPTION
HAC
SCHEDULING
CLEAN
UTILITY
WC
STOR.
BALANCE
CLINIC
EQUIP
STORAGE
SPEECH
THERAPY
VIST
COORDINATOR
PROVI DER
OFFICE
LPN
REHAB
SUPERVI SOR
CONSULTATION
ROOM
PROCEDURE
ROOM
O.T.
CHARTING
O.T.
CLINIC
CORRI DOR
CORRI DOR
ADL
BATHROOM
T-9
T-8
PATIENT
TOILET
SPEECH
THERAPY
ADL
KITCHEN
ADL
BEDROOM
154 SOILED
REF.
FDFD
FD
FD
FD
MALE TOILET
FEMALE
TOILET
SOILED LINEN
CLEAN LINEN
RECYCLING
HALLWAY
CL LINEN
FD
FD
DWREF.
154A
CLOSET
151A
CLOSET
DN
RECORD DOCUMENTS
No DATEREVISION
DRAWING TITLE
CHECKED BY
ST.CLOUD, MN 56303
VA MEDICAL CENTER
BUILDING No
LOCATION
DRAWING NO.DRAWN
DWG. OF
PROJECT TITLE
PLOT SCALE
PROJECT NO.
DATE:
CONSULTANT ARCHITECT/ENGINEER OF RECORD
FULLY
SPRINKLERED
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
-RECORD DOCUMENT-
June 21, 2024
This Record Document has been prepared based on
Designer of Record drawings with Contractor provided markups through the construction phase of the project at the direction of the VA.
While the construction information is believed to be reliable, Architect/Engineer cannot assure its accuracy, and is not responsible for the accuracy of this Record Document. Those relying on this Record
Document are advised to independently verify its accuracy before applying it for any purpose.
RECORD DOCUMENTS 06/21/24
B
IM
/2
.0
V A
S t C lo u d E
H R
M I n fr a s tr u c tu re U p g ra d e s /6
-2
.B
.T
R
.r v t
/6
/2
:3
:1
P M
116-TN210
FIRST FLOOR PLAN -
TELECOM - CABLE DISTANCE
EHRM INFRASTRUCTURE
UPGRADES
656‐21‐235
03/30/2022
KSB SSK
16305
N
0 30' 60'15' 1" = 30'-0"
FIRST FLOOR PLAN - TELECOM - CABLE DISTANCE
RECEPTIONRECEPTION
A C
C R
C
TELECOM ROOM
116-TN400
1 - a b
1 - c d
E
SP
12"x2"
DATA RACK
CABLE
TRAY
E
W
KEYPAD
2"
AC
R
"x
2"
4"4"2"
4" DOWN
E
12" LADDER
FIRST FLOOR
0' - 0"
SECOND FLOOR
12' - 0"
FIRST FLOOR
0"
SECOND FLOOR
12'-0"
FIRST FLOOR
0' - 0"
SECOND FLOOR
12' - 0"
FIRST FLOOR
0"
SECOND FLOOR
12'-0"
FIRST FLOOR
0' - 0"
SECOND FLOOR
12' - 0"
FIRST FLOOR
0"
SECOND FLOOR
12'-0"
FIRST FLOOR
0' - 0"
SECOND FLOOR
12' - 0"
FIRST FLOOR
0"
SECOND FLOOR
12'-0"
NEMA L21-20R (TYP)
RACK 1
1U 144 STRAND OM4 AND OS2 DISTRIBUTION PANEL
1U BONDING BUS BAR (BACK) 1U ANGLED BLANKING PANEL (FRONT)
1U 48 PORT CAT5E BACKBONE ANGLED PATCH PANEL
SPACE FOR FUTURE HORIZONTAL CABLE
DISTRIBUTION. PROVIDE ANGLED BLANKING PANELS
FOR UNUSED SPACES.
1U 48 PORT CAT6A ANGLED DATA PATCH PANEL
RACK 1
V E
R T
IC
A
L R
A C
K P
D U
V E
R T
IC
A
L R
A C
K P
D U
1U 48 PORT CAT6A ANGLED DATA PATCH PANEL
1U 48 PORT CAT6A ANGLED DATA PATCH PANEL
1U 48 PORT CAT6A ANGLED DATA PATCH PANEL
1U 48 PORT CAT6A ANGLED DATA PATCH PANEL
1U 48 PORT CAT6A ANGLED DATA PATCH PANEL
1U CABLE MANAGEMENT
VA OIT PROVIDED 1U 48 PORT SWITCH
2U CABLE MANAGEMENT
VA OIT PROVIDED 1U 48 PORT SWITCH
2U CABLE MANAGEMENT
VA OIT PROVIDED 1U 48 PORT SWITCH
2U CABLE MANAGEMENT
VA OIT PROVIDED 1U 48 PORT SWITCH
2U CABLE MANAGEMENT
VA OIT PROVIDED 1U 48 PORT SWITCH
2U CABLE MANAGEMENT
1U CABLE MANAGEMENT
VA OIT PROVIDED 1U 48 PORT SWITCH
6U SPACE FOR FUTURE USE.
PROVIDE BLANK PANELS FOR UNUSED SPACES.
6U 5KW RACK MOUNT UPS
D
PROVIDE DATA CABLE TO RACK
MOUNTED UPS FOR CONNECTION
TO MONITORING SYSTEM
4 POST CHANNEL
RACK (TYP)
VERTICAL CABLE
MANAGEMENT (TYP)
NOTES:
1. REFER TO NEW WORK PLAN FOR RACK LOCATIONS.
2. COORDINATE EXACT RACK LOCATION WITH OWNER PRIOR TO PERMANENT INSTALLATION.
3. SEE PROJECT SPECIFICATIONS FOR ADDITIONAL RACK COMPONENTS.
4. RACK ELEVATION SHOWS A FULLY CONFIGURED SAMPLE RACK. CONTRACTOR TO PROVIDE REQUIRED EQUIPMENT TO
SUPPORT THE FINAL DATA COUNT FROM THE ENLARGED NEW SHEET.
5. COORDINATE FINAL RACK COMPONENT LAYOUT WITH OWNER'S IS/IT REPRESENTATIVE.
6. CONTRACTOR IS RESPONSIBLE FOR FINAL CABLE COUNT, QUANTITY OF PATCH PANELS, SWITCHES, FIBER ENCLOSURES, BLANKING PANELS, CABLE MANAGEMENT, TR PATCH CABLES, AND MOUNTING HARDWARE NOT MARKED AS “OIT PROVIDED”.
7. PUNCH DOWN COPPER BACKBONE CABLE TO RACK MOUNT PATCH PANEL. TERMINATE ONE (1) PAIR PER PATCH PANEL PORT.
RECORD DOCUMENTS
No DATEREVISION
DRAWING TITLE
CHECKED BY
ST.CLOUD, MN 56303
VA MEDICAL CENTER
BUILDING No
LOCATION
DRAWING NO.DRAWN
DWG. OF
PROJECT TITLE
PLOT SCALE
PROJECT NO.
DATE:
CONSULTANT ARCHITECT/ENGINEER OF RECORD
FULLY
SPRINKLERED
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
-RECORD DOCUMENT-
June 21, 2024
This Record Document has been prepared based on
Designer of Record drawings with Contractor provided markups through the construction phase of the project at the direction of the VA.
While the construction information is believed to be reliable, Architect/Engineer cannot assure its accuracy, and is not responsible for the accuracy of this Record Document. Those relying on this Record
Document are advised to independently verify its accuracy before applying it for any purpose.
RECORD DOCUMENTS 06/21/24
B
IM
/2
.0
V A
S t C lo u d E
H R
M I n fr a s tr u c tu re U p g ra d e s /6
-2
.B
.T
R
.r v t
/6
/2
:3
:1
P M
116-TN400
ENLARGED PLANS -
TELECOMMUNICATIONS
EHRM INFRASTRUCTURE
UPGRADES
656‐21‐235
03/30/2022
KSB SSK
16305
N
0 2' 4'1'
0 4' 8'2' 0 4' 8'2' 0 4' 8'2' 0 4' 8'2'
GENERAL NOTES:
A. REFER TO GENERAL DEMOLITION NOTES ON SHEET T000 FOR ADDITIONAL DEMOLITION SCOPE.
CABLING NOTE:
CABLING NOTES:
A. THE EXISTING CABLE COUNT ARE THE CABLES CURRENTLY PRESENT IN THE SPACE.
THE CABLE RELOCATION COUNT ARE THE NEW OR RELOCATED CABLES TO BE FED
FROM THE SPACE. THE FINAL CABLE COUNT ARE THE CABLES THAT WILL BE
PRESENT IN THE SPACE AT THE COMPLETION OF THE PROJECT.
1. ROOM 111
EXISTING CABLE COUNT
DATA (CAT6): 0
DATA (CAT5e): 114
DATA (CAT5): 0
DATA (CAT3): 0
CABLE RELOCATION COUNT
DATA (CAT6): 0
DATA (CAT5e): 0
DATA (CAT5): 0
DATA (CAT3): 0
EXISTING CABLE TO REMAIN
DATA (CAT6): 0
DATA (CAT5e): 0
DATA (CAT5): 0
DATA (CAT3): 0
FINAL CABLE COUNT
DATA (CAT6A): 114
DATA (CAT6): 0
1/2" = 1'-0"
ENLARGED PLAN -EXIST TR 111 - TELECOM - CABLE TRAY AND DATA
1/4" = 1'-0"
1 - a 1/4" = 1'-0"
1 - b
1/4" = 1'-0"
1 - c 1/4" = 1'-0"
1 - d
NOT TO SCALE6
COMMUNICATIONS - TYPICAL ONE RACK ELEVATION WITH RACK MOUNT UPS - EXIST TR 111
SHEET NOTES:
1. IF NO ACCESS CONTROL PANEL IS PRESENT IN THE TR, PROVIDE A NEW ACCESS CONTROL PANEL TO BE INSTALLED IN THE TELECOM ROOM. THE CARD READER AND KEYPAD FOR THIS ROOM TO BE WIRED TO THE NEW ACCESS CONTROL PANEL. EXISTING CARD READERS AND KEYPADS WILL BE MOVED TO THE NEW
CONTROL PANEL UNDER A DIFFERENT PROJECT.
E
CLINIC
NORTH
VESTIBULE
STAFF
SPEECH
THERAPY
TREATMENT
ROOM 1
TREATMENT
ROOM 2
TREATMENT
ROOM 3
TREATMENT
ROOM 4
TREATMENT
ROOM 5
TREATMENT
ROOM 7
TREATMENT
ROOM 6
MAILROOM
CORRIDOR
PT
CHARTING
GROUP
MTG ROOM
OP GYM
PT GYM
PROSTH.
STORAGE
EQUIP
STORAGE
PATIENT
TOILET
FEMALE
TOILET
MALE
TOILET
MECHANICAL
LOW
VOLTAGE
ELECTRICAL
ELECTRICAL
CORRIDOR
WAITING
WAITING
SOUTH
VESTIBULE
RECEPTION
HAC
SCHEDULING
CLEAN
UTILITY
WC
STOR.
BALANCE
CLINIC
EQUIP
STORAGE
SPEECH
THERAPY
VIST
COORDINATOR
PROVIDER
OFFICE
LPN
REHAB
SUPERVISOR
CONSULTATION
ROOM
PROCEDURE
ROOM
O.T.
CHARTING
O.T.
CLINIC
CORRIDOR
CORRIDOR
ADL
BATHROOM
T-9
T-8
PATIENT
TOILET
SPEECH
THERAPY
ADL
KITCHEN
ADL
BEDROOM
154 SOILED
DN
REF.
FDFD
FD
FD
FD
MALE TOILET
FEMALE
TOILET
SOILED LINEN
CLEAN LINEN
RECYCLING
HALLWAY
CL LINEN
FD
FD
DWREF.
154A
CLOSET
151A
CLOSET
DN
TELECOM
ROOM
1 CU-116-1
116-E300
116-CR-8,10
116-L1-4
116-CR
116-L1-4-47
No DATEREVISION
DRAWING TITLE
CHECKED BY
ST.CLOUD, MN 56303
VA MEDICAL CENTER
BUILDING No
LOCATION
DRAWING NO.DRAWN
DWG. OF
PROJECT TITLE
PLOT SCALE
PROJECT NO.
DATE:
CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP
FULLY
SPRINKLERED
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Engineer under the laws of the State of Minnesota.
Name:
Date: 03/30/2022
License Number: MN#
03/30/2022
B
IM
/2
.0
V A
S t C lo u d
E H
R M
I n fr a s tr u c tu re U p g ra d e s /6
-2
.B
.E
R
.r v t
/2
/2
:5
:4
P
M
116-E201
FIRST FLOOR - ELECTRICAL
EHRM INFRASTRUCTURE
UPGRADES
656-21-235
TBD GJL
16305
KEYNOTES:
1. PROVIDE ELECTRICAL CONNECTION TO
CONDENSING UNIT, AS REQUIRED.
COORDINATE FINAL LOCATION AND
CONNECTION REQUIREMENTS WITH
MECHANICAL.
1/8" = 1'-0"
FIRST FLOOR - ELECTRICAL
0 8' 16'4'
N
100% CD 03/30
53095
FOR CONSTRUCTION
No DATEREVISION
DRAWING TITLE
CHECKED BY
ST.CLOUD, MN 56303
VA MEDICAL CENTER
BUILDING No
LOCATION
DRAWING NO.DRAWN
DWG. OF
PROJECT TITLE
PLOT SCALE
PROJECT NO.
DATE:
CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP
FULLY
SPRINKLERED
I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Engineer under the laws of the State of Minnesota.
Name:
Date: 03/30/2022
License Number: MN#
03/30/2022
0-GE000
ELECTRICAL COVERSHEET
EHRM INFRASTRUCTURE
UPGRADES
656-21-235
TBD GJL
16305
CAMPUS
100% CD 03/30
by certify that this plan, specification was prepared by me or under my dir vision and that I am a duly Licensed eer under the laws of the State of Min e:
03/30/202205-06-2022
ALEXANDER S. QUAST
53095No DATEREVISION
100% CD 03/30
RECORD DOCUMENTS 06/14
No DATEREVISION
RECORD DOCUMENTS 06/21/24 06/21/2024
-RECORD DOCUMENT-
June 21, 2024 This Record Document has been prepared based on
Designer of Record drawings with Contractor provided markups through the construction phase of the project at the direction of the VA.
While the construction information is believed to be reliable, Architect/Engineer cannot assure its accuracy, and is not responsible for the accuracy of this Record Document. Those relying on this Record
Document are advised to independently verify its accuracy before applying it for any purpose.
eby certify that this plan, specification rt was prepared by me or under my dir ervision and that I am a duly Licensed neer under the laws of the State of Min me:
GB
E
SD
MAILROOM
RECEPTION
UTILITY
TELECOM
ROOM
AC-116-1
116-CR-2,4,6
116-L1-4-49,51,53
No DATEREVISION
DRAWING TITLE
CHECKED BY
ST.CLOUD, MN 56303
VA MEDICAL CENTER
BUILDING No
LOCATION
DRAWING NO.DRAWN
DWG. OF
PROJECT TITLE
PLOT SCALE
PROJECT NO.
DATE:
CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP
FULLY
SPRINKLERED
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Engineer under the laws of the State of Minnesota.
Name:
Date: 03/30/2022
License Number: MN#
03/30/2022
B
IM
/2
.0
V A
S t C lo u d
E H
R M
I n fr a s tr u c tu re U p g ra d e s /6
-2
.B
.E
R
.r v t
/2
/2
:5
:4
P
M
116-E300
ELECTRICAL ENLARGED
PLANS
EHRM INFRASTRUCTURE
UPGRADES
656-21-235
TBD GJL
16305
1/4" = 1'-0"
FIRST FLOOR ENLARGED -
ELECTRICAL - RM 111
KEYNOTES:
1. DISCONNECT AND REMOVE LIGHTS AND
RECEPTACLES IN AREA OF NEW IT ROOM.
MAINTAIN CIRCUIT CONTINUITY TO ADJOINING
SPACES.
2. INDOOR UNIT TO BE POWERED BY OUTDOOR
UNIT. COORDINATE EXACT LOCATION WITH
M.C.
3. CONNECT SMOKE DETECTOR TO NEAREST
EXISTING SLC.
4. COORDINATE FINAL LOCATION OF
RECEPTACLE L21-20R WITH TELECOM
CONTRACTOR. PROVIDE 3/4"C-4#10, 1#12 GND
TO PANEL FOR EACH RECEPTACLE.
5. PROVIDE EATON BLADEUPS, 5KW, 120/208V, 3-
PHASE,4-WIRE RACK MOUNTED UPS FOR
EACH RACK TOWER.
6. PROVIDE APC#AP8861 RPDU RACK PDU 2G
WITH L21-20P CORD. (120/208V, 3-PHASE, 20A,
ZERO U, 5.7 KW, 208V, (36) C13 (6) C19 (2) 5-20R
OUTLETS. PROVIDE TWO PER RACK, MOUNTED
PER MANUFACTURER'S REQUIREMENTS.
SHEET NOTES:
1. REFER TO TECHNOLOGY PLANS FOR IT ROOM
LAYOUT AND RACK LAYOUT/DETAILS.
2. REFER TO SHEET 0-GE400 DETAIL LAYOUT &
ONE-LINE OF RACK.
0 4' 8'2'
N
CIRCUIT KEY NOTES:
*TOTAL DEMAND CALCS SUBTRACT ANY REDUNDANT LOAD AND THE SMALLER OF ANY NONCOINCIDENT HVAC LOADS. THIS CALC IS DONE AT EACH PANEL.
TOTAL ESTIMATED DEMAND AMPS: 19.4 A
TOTAL CONNECTED AMPS: 19.43 A
TOTAL ESTIMATED DEMAND LOAD: 7 kVA
TOTAL CONNECTED LOAD: 7.00 kVA
Power 7 kVA 100.00% 7 kVA
LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND
TOTALS*
LOAD SUMMARY
Total Amps: 23.50 23.50 13.89
Total Load: 2.67 kVA 2.67 kVA 1.67 kVA
41 42
39 40
37 38
35 36
33 34
31 32
29 30
27 28
25 26
23 24
21 22
19 20
17 18
15 16
13 14
11 12
9 1 -- -- -- -- -- -- 10 --
7 1 2 20 A CU-116-1 8
5 1.67 -- -- -- -- -- -- 6 --
3 1.67 -- -- -- -- -- -- 4 --
1 1.67 3 30 A L21-30R 2
K E Y
CKT
NO. LOAD DESCRIPTION
OCPD
AMPS P
WIRE
SIZE
H N G
A B C
WIRE
SIZE
G N H
OCPD
P AMPS LOAD DESCRIPTION
CKT
NO.
K E Y
NOTES:
ISC UNKNOWN 0.00 kA
SCCR: 65 kA
LOCATION: WIRE: 4
FED FROM: 0 A/0P @ GROUND BUS PHASE: 3
ENCLOSURE: NEMA PB 1 SOLID NEUTRAL VOLTS: 120/208 Wye
MOUNTING: SURFACE MAIN: 100 A MCB
EXISTING PANEL 116-CR
CIRCUIT KEY NOTES:
*TOTAL DEMAND CALCS SUBTRACT ANY REDUNDANT LOAD AND THE SMALLER OF ANY NONCOINCIDENT HVAC LOADS. THIS CALC IS DONE AT EACH PANEL.
TOTAL ESTIMATED DEMAND AMPS: 14.4 A
TOTAL CONNECTED AMPS: 14.38 A
TOTAL ESTIMATED DEMAND LOAD: 5.18 kVA
Receptacles 0.18 kVA 100.00% 0.18 kVA TOTAL CONNECTED LOAD: 5.18 kVA
Power 5 kVA 100.00% 5 kVA
LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND
TOTALS*
LOAD SUMMARY
Total Amps: 13.89 13.89 15.39
Total Load: 1.67 kVA 1.67 kVA 1.85 kVA
-- 53 -- -- -- -- -- -- 1.67 -- -- -- -- 1 -- SPACE 54 --
-- 51 -- -- -- -- -- -- 1.67 -- -- -- -- 1 -- SPACE 52 --
49 L21-30R 30 A 3 1.67 -- -- --…