Attachment 7 - As Built Record EHRM_Part V (1).pdf

PDF 7 MB Posted

Attached to
656-26-702 EHRM DDPO 2. 0 Federal contract opportunity
Solicitation number
36C26326B0028
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 23

About this file

This document is a record drawing package for the EHRM Infrastructure Upgrades project at the St. Cloud VA Medical Center in St. Cloud, Minnesota. The project involves upgrading mechanical, electrical, and telecommunications infrastructure across Buildings 51 and 116, with primary focus on converting existing spaces into compliant telecom rooms meeting Electronic Health Record Modernization (EHRM) standards.

Building 51 (Basement) requires electrical panel upgrades including two new 100-amp, 3-phase panels (B51IT-1 and B51IT-1-CR) fed from existing distribution equipment at panels 51-MDP and 51-EDC. The telecom room installation includes new wall-mounted split-system air conditioning unit (AC-51-1), condensate handling (CP-51-1), fire sprinkler head relocation, and an air-cooled condensing unit (CU-51-1) positioned outside. Electrical requirements include L21-30R receptacles for rack PDU connections, UPS systems rated at 5 kW (120/208V, 3-phase), and specific rack-mounted power distribution units (APC#AP8861 RPDU with dual units per rack). Short-circuit current ratings range from 3.599 kA to 18.226 kA with 10 kA to 22 kA SCCR ratings across affected panels.

Building 116 (First Floor, Room 111) involves converting an existing data room into a compliant EHRM telecom room with similar electrical and mechanical requirements. The space requires new conduit runs (3/4" C-4#10, 1#12 GND), L21-20R and L21-30R receptacles, five 5 kW rack-mounted UPS units, and dual APC RPDU units per rack. Mechanical work includes installing a new split-system AC unit with refrigerant and condensate piping routed approximately 30 feet to an HAC mop sink, along with fire sprinkler line rerouting. Both buildings require 1-hour fire-rated construction barriers for ICRA (Infection Control Risk Assessment) classification as Type C Group 1 Class II spaces, with construction limited to nighttime hours to minimize disruption to occupied clinical areas. The project includes extensive cabling demolition and replacement, with existing CAT5e cabling (114 strands in Building 116) being replaced by new CAT6A infrastructure.

View the file

Other files for this federal contract opportunity

Show all 13

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

MECHANICAL

H

E

SD

EXISTING 51MDP 51-ATS

ES-ATS

EC-TS

51-MDP

51-EDC

8'-2"

'-2

/2

TELECOM

ROOM

8'-2"

'-2

/2

TELECOM

ROOM

A

B51IT-1-CR

a

A

B51IT-1

b a b

8'-2"

'-2

/2

TELECOM

ROOM

B51IT-1

B51IT-1-CR

AC-51-1

B51IT-1-1

B51IT-1-CR-1

B51IT-1-1

B51IT-1-CR-1

B51IT-1-1

B51IT-1-CR-1

B51IT-1-CR-2,4,6

B51IT-1-2,4,6

No DATEREVISION

DRAWING TITLE

CHECKED BY

ST.CLOUD, MN 56303

VA MEDICAL CENTER

BUILDING No

LOCATION

DRAWING NO.DRAWN

DWG. OF

PROJECT TITLE

PLOT SCALE

PROJECT NO.

DATE:

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP

FULLY

SPRINKLERED

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Engineer under the laws of the State of Minnesota.

Name:

Date: 03/30/2022

License Number: MN#

03/30/2022

B

IM

/2

.0

V A

S t C lo u d E

H R

M I n fr a s tr u c tu re U p g ra d e s /6

-2

.B

.E

R

.r v t

/1

/2

:3

:2

P

M

51-E300

ENLARGED PLANS -

ELECTRICAL

EHRM INFRASTRUCTURE

UPGRADES

656-21-235

TBD GJL

16305

N O R

HT

1/4" = 1'-0"

BASEMENT FLOOR PLAN ENLARGED - ELECTRICAL

N O R

HT

1/4" = 1'-0"

TELECOM ROOM - ELECTRICAL DEMOLITION

N O R

HT

1/4" = 1'-0"

TELECOM ROOM - LIGHTING

N O R

HT

1/4" = 1'-0"

TELECOM ROOM - POWER & SYSTEM

KEYNOTES:

1. INDOOR UNIT TO BE POWERED BY OUTDOOR

UNIT. COORDINATE EXACT LOCATION WITH

M.C.

2. CONNECT SMOKE DETECTOR TO NEAREST

EXISTING SLC.

3. DISCONNECT AND REMOVE EXISTING LIGHTS

AND RECEPTACLES IN ROOM. MAINTAIN

CIRCUIT CONTINUITY TO ADJOINING ROOMS.

4. COORDINATE FINAL LOCATION OF

RECEPTACLE L21-30R WITH TELECOM

CONTRACTOR. PROVIDE 3/4"C-4#10, 1#10 GND

TO PANEL FOR EACH RECEPTACLE.

5. PROVIDE EATON BLADEUPS, 5KW, 120/208V, 3-

PHASE,4-WIRE RACK MOUNTED UPS FOR EACH

RACK TOWER.

6. PROVIDE APC#AP8861 RPDU RACK PDU 2G

WITH L21-20P CORD. (120/208V, 3-PHASE, 20A,

ZERO U, 5.7 KW, 208V, (36) C13 (6) C19 (2) 5-20R

OUTLETS. PROVIDE TWO PER RACK, MOUNTED

PER MANUFACTURER'S REQUIREMENTS.

7. PROVIDE ONE RACK MOUNTED ZONE PDU

UNIT. 30 AMP 3 PHASE, 120/208V, 5-WIRE WITH

(4) L21-30R, (6) 5-20R AND TWO 10' POWER

CORDS. ZONIT#ZPDS-208V-30A-L21-4L21-20R-

CR.#

100% CD 03/30

reby certify that this plan, specification o ort was prepared by me or under my dire ervision and that I am a duly Licensed ineer under the laws of the State of Minn me:

e: 03/30/202205-06-2022

ALEXANDER S. QUAST

06/14/2024 53095

RECORD DOCUMENTS 06/14

RECORD

DRAWINGS

THIS IS A RECORD DRAWING BASED ON INFORMATION RECEIVED FROM THE

CONTRACTOR AND IS TO BE USED FOR THE SOLE PURPOSE OF MAINTENANCE OF

THE ORIGINAL FACILITY FOR WHICH THIS DRAWING WAS PREPARED AND NOT

FOR ADDITIONAL CONSTRUCTION.No DATEREVISION

100% CD 03/30

RECORD DOCUMENTS 06/14

No DATEREVISION

RECORD DOCUMENTS 06/21/24 06/21/2024

-RECORD DOCUMENT-

June 21, 2024 This Record Document has been prepared based on

Designer of Record drawings with Contractor provided markups through the construction phase of the project at the direction of the VA.

While the construction information is believed to be reliable, Architect/Engineer cannot assure its accuracy, and is not responsible for the accuracy of this Record Document. Those relying on this Record

Document are advised to independently verify its accuracy before applying it for any purpose.

eby certify that this plan, specification rt was prepared by me or under my dir ervision and that I am a duly Licensed neer under the laws of the State of Min me:

e: 03/30/202205-06-2022

RECORD DOCUMENTS

BASEMENT

FIRST FLOOR

B51IT-1

100Y

51MDP

B51IT-1-CR

100Y

51-EDC

ISC 14.318 kA SCCR 22 kA

ISC 3.599 kA SCCR 10 kA

ISC 5.159 kA SCCR 10 kA

ISC 18.226 kA SCCR 22 kA

No DATEREVISION

DRAWING TITLE

CHECKED BY

ST.CLOUD, MN 56303

VA MEDICAL CENTER

BUILDING No

LOCATION

DRAWING NO.DRAWN

DWG. OF

PROJECT TITLE

PLOT SCALE

PROJECT NO.

DATE:

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP

FULLY

SPRINKLERED

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Engineer under the laws of the State of Minnesota.

Name:

Date: 03/30/2022

License Number: MN#

03/30/2022

B

IM

/2

.0

V A

S t C lo u d E

H R

M I n fr a s tr u c tu re U p g ra d e s /6

-2

.B

.E

R

.r v t

/1

/2

:3

:2

P

M

51-E500

ELECTRICAL ONE-LINE

DIAGRAMS AND SCHEDULES

EHRM INFRASTRUCTURE

UPGRADES

656-21-235

TBD GJL

16305

NO SCALE

PARTIAL POWER RISER

KEYNOTES:

1. PROVIDE NEW 100A/3P CIRCUIT BREAKERS IN

EXISTING PANEL TO MATCH EXISTING TYPE

AND AIC RATING.

100% CD 03/30

CIRCUIT KEY NOTES:

*TOTAL DEMAND CALCS SUBTRACT ANY REDUNDANT LOAD AND THE SMALLER OF ANY NONCOINCIDENT HVAC LOADS. THIS CALC IS DONE AT EACH PANEL.

TOTAL ESTIMATED DEMAND AMPS: 18.7 A

TOTAL CONNECTED AMPS: 18.65 A

Receptacles 0.72 kVA 100.00% 0.72 kVA TOTAL ESTIMATED DEMAND LOAD: 6.72 kVA

Power 6 kVA 100.00% 6 kVA TOTAL CONNECTED LOAD: 6.72 kVA

Lighting 0 kVA 0.00% 0 kVA

LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND

TOTALS*

LOAD SUMMARY

Total Amps: 21.40 16.67 18.40

Total Load: 2.54 kVA 2.00 kVA 2.18 kVA

-- 29 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 30 --

-- 27 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 28 --

-- 25 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 26 --

-- 23 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 24 --

-- 21 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 22 --

-- 19 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 20 --

-- 17 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 18 --

-- 15 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 16 --

-- 13 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 14 --

-- 11 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 12 --

-- 9 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 10 --

-- 7 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 8 --

5 WP GFI RECEPTACLE 20 A 1 12 12 12 0.18 2 -- -- -- -- -- -- 6 --

3 TELECOM ROOM LIGHTING 20 A 1 12 12 12 0 2 -- -- -- -- -- -- 4 --

1 TELECOM ROOM RECEPTACLE 20 A 1 12 12 12 0.54 2 10 10 10 3 30 A L21-30R 2

K E Y

CKT

NO. LOAD DESCRIPTION

OCPD

AMPS P

WIRE

SIZE

H N G

A B C

WIRE

SIZE

G N H

OCPD

P AMPS LOAD DESCRIPTION

CKT

NO.

K E Y

NOTES:

ISC: 5.16 kA

SCCR: 10 kA

LOCATION: TELECOM ROOM 001 WIRE: 4

FED FROM: 100 A/3P @ 51-MDP GROUND BUS PHASE: 3

ENCLOSURE: NEMA PB 1 SOLID NEUTRAL VOLTS: 120/208 Wye

MOUNTING: SURFACE MAIN: 100 A MCB

PANEL B51IT-1

CIRCUIT KEY NOTES:

*TOTAL DEMAND CALCS SUBTRACT ANY REDUNDANT LOAD AND THE SMALLER OF ANY NONCOINCIDENT HVAC LOADS. THIS CALC IS DONE AT EACH PANEL.

TOTAL ESTIMATED DEMAND AMPS: 18.2 A

TOTAL CONNECTED AMPS: 18.15 A

Receptacles 0.54 kVA 100.00% 0.54 kVA TOTAL ESTIMATED DEMAND LOAD: 6.54 kVA

Power 6 kVA 100.00% 6 kVA TOTAL CONNECTED LOAD: 6.54 kVA

Lighting 0 kVA 0.00% 0 kVA

LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND

TOTALS*

LOAD SUMMARY

Total Amps: 21.17 16.67 16.67

Total Load: 2.54 kVA 2.00 kVA 2.00 kVA

-- 29 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 30 --

-- 27 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 28 --

-- 25 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 26 --

-- 23 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 24 --

-- 21 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 22 --

-- 19 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 20 --

-- 17 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 18 --

-- 15 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 16 --

-- 13 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 14 --

-- 11 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 12 --

-- 9 SPARE 20 A 1 -- -- -- 0 0 -- -- -- 1 20 A SPARE 10 --

-- 7 -- -- -- -- -- -- 0 0 -- -- -- 1 20 A SPARE 8 --

5 CU-51-1 0 A 2 0 2 -- -- -- -- -- -- 6 --

3 TELECOM ROOM LIGHTING 20 A 1 12 12 12 0 2 -- -- -- -- -- -- 4 --

1 TELECOM ROOM RECEPTACLE 20 A 1 12 12 12 0.54 2 10 10 10 3 30 A L21-30R 2

K E Y

CKT

NO. LOAD DESCRIPTION

OCPD

AMPS P

WIRE

SIZE

H N G

A B C

WIRE

SIZE

G N H

OCPD

P AMPS LOAD DESCRIPTION

CKT

NO.

K E Y

NOTES:

ISC: 3.60 kA

SCCR: 10 kA

LOCATION: TELECOM ROOM 001 WIRE: 4

FED FROM: 100 A/3P @ 51-EDC GROUND BUS PHASE: 3

ENCLOSURE: NEMA PB 1 SOLID NEUTRAL VOLTS: 120/208 Wye

MOUNTING: SURFACE MAIN: 100 A MCB

PANEL B51IT-1-CR

reby certify that this plan, specification o ort was prepared by me or under my dire ervision and that I am a duly Licensed ineer under the laws of the State of Minn me:

e: 03/30/202205-06-2022

ALEXANDER S. QUAST

06/14/2024 53095

RECORD DOCUMENTS 06/14

RECORD

DRAWINGS

THIS IS A RECORD DRAWING BASED ON INFORMATION RECEIVED FROM THE

CONTRACTOR AND IS TO BE USED FOR THE SOLE PURPOSE OF MAINTENANCE OF

THE ORIGINAL FACILITY FOR WHICH THIS DRAWING WAS PREPARED AND NOT

FOR ADDITIONAL CONSTRUCTION.No DATEREVISION

100% CD 03/30

RECORD DOCUMENTS 06/14

No DATEREVISION

RECORD DOCUMENTS 06/21/24 06/21/2024

-RECORD DOCUMENT-

June 21, 2024 This Record Document has been prepared based on

Designer of Record drawings with Contractor provided markups through the construction phase of the project at the direction of the VA.

While the construction information is believed to be reliable, Architect/Engineer cannot assure its accuracy, and is not responsible for the accuracy of this Record Document. Those relying on this Record

Document are advised to independently verify its accuracy before applying it for any purpose.

eby certify that this plan, specification rt was prepared by me or under my dir ervision and that I am a duly Licensed neer under the laws of the State of Min me:

TELECOM ROOM

EXAM

23C INTAKE

23C

PASSAGE

COCA

PHONE CLOSET

1B

CORRIDOR

C0C

No DATEREVISION

DRAWING TITLE

CHECKED BY

ST.CLOUD, MN 56303

VA MEDICAL CENTER

BUILDING No

LOCATION

DRAWING NO.DRAWN

DWG. OF

PROJECT TITLE

PLOT SCALE

PROJECT NO.

DATE:

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP

FULLY

SPRINKLERED

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Engineer under the laws of the State of Minnesota.

Name:

Date: 03/30/2022

License Number: MN#

03/30/2022

B

IM

/2

.0

V A

S t C lo u d

E H

R M

I n fr a s tr u c tu re U p g ra d e s /6

-2

.B

.M

R

.r v t

/1

/2

:5

:3

A

M

51-M100

BASEMENT DEMOLITION PLAN

- MECHANICAL

EHRM INFRASTRUCTURE

UPGRADES

656-21-235

RDL DJC

16305

1/4" = 1'-0"

BASEMENT LEVEL DEMOLITION PLAN - MECHANICAL - TELECOM 001

0 4' 8'2'

N

KEYNOTES 1/51-M100:

1. REMOVE AND DISPOSE OF EXISTING FIRE SPRINKLER HEADS AND

BRANCH LINE BACK TO LOCATION SHOWN. PREPARE FOR

RECONNECTION.

2. EXISTING 2" STEAM RISER TO REMAIN.

3. EXISTING 1" CONDENSATE RISER TO REMAIN.

4. EXISTING CRAWL SPACE ACCESS DOOR.

FIELD VERIFICATION NOTES

1. THE HVAC CONTRACTOR SHALL VISIT THE SITE PRIOR TO BID TO FIELD VERIFY ALL EXISTING CONDITIONS WHICH MAY AFFECT THEIR

BID. THE FOLLOWING ITEMS SHALL BE VERIFIED:

A. EXACT PLACEMENT, SIZE, CAPACITY, MANUFACTURER AND CONDITION OF ALL EXISTING HVAC EQUIPMENT WITHIN SCOPE OF

WORK, WHETHER EXPLICITLY SHOWN OR NOT.

B. SIZE AND LOCATION OF ALL EXISTING DUCTWORK.

C. SIZE AND LOCATION OF ALL EXISTING GRILLES, REGISTERS AND DIFFUSERS.

D. SIZE AND LOCATION OF ALL EXISTING THERMOSTATIC CONTROL DEVICES.

E. SIZE AND LOCATION OF ALL EXISTING PLUMBING AND HYDRONIC PIPING.

2. ALL REFERENCES ON THESE DRAWINGS TO EXISTING EQUIPMENT, DUCTWORK, DIFFUSERS, THERMOSTATS AND PIPING ARE FOR REFERENCE ONLY. IT IS THE RESPONSIBLITY OF THE CONTRACTOR TO VERIFY ALL THESE ITEMS PRIOR TO BID AND INCLUDE IN THEIR

BID ANY AND ALL AMOUNTS REQUIRED TO ACCOMMODATE EXISTING CONDITIONS.

3. NO ALLOWANCES WILL BE MADE AFTER THE PROJECT HAS BEEN AWARDED FOR FAILURE TO VERIFY EXISTING CONDITIONS.

4. ANY DISCREPANCIES WHICH MAY AFFECT THE CONTRACTORS BID SHALL BE BROUGHT TO THE ATTENTION OF THE ENGINEER AND

ARCHITECT FOR DIRECTION.

100% CD 03/30 06/14/2024

RECORD DOCUMENTS 06/14 Robert D. Lowe

24706

RECORD

DRAWINGS

THIS IS A RECORD DRAWING BASED ON INFORMATION RECEIVED FROM THE

CONTRACTOR AND IS TO BE USED FOR THE SOLE PURPOSE OF MAINTENANCE OF

THE ORIGINAL FACILITY FOR WHICH THIS DRAWING WAS PREPARED AND NOT

FOR ADDITIONAL CONSTRUCTION.

No DATEREVISION

RECORD DOCUMENTS 06/21/24 06/21/2024

-RECORD DOCUMENT-

June 21, 2024 This Record Document has been prepared based on

Designer of Record drawings with Contractor provided markups through the construction phase of the project at the direction of the VA.

While the construction information is believed to be reliable, Architect/Engineer cannot assure its accuracy, and is not responsible for the accuracy of this Record Document. Those relying on this Record

Document are advised to independently verify its accuracy before applying it for any purpose.

T

TELECOM ROOM

EXAM

23C INTAKE

23C

PASSAGE

COCA

PHONE CLOSET

1B

CORRIDOR

C0C

AC-51-1

CP-51-1

RACK PROVIDED

BY OTHERS

CU-51-1

S U

C

L

IQ

No DATEREVISION

DRAWING TITLE

CHECKED BY

ST.CLOUD, MN 56303

VA MEDICAL CENTER

BUILDING No

LOCATION

DRAWING NO.DRAWN

DWG. OF

PROJECT TITLE

PLOT SCALE

PROJECT NO.

DATE:

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP

FULLY

SPRINKLERED

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Engineer under the laws of the State of Minnesota.

Name:

Date: 03/30/2022

License Number: MN#

03/30/2022

B

IM

/2

.0

V A

S t C lo u d

E H

R M

I n fr a s tr u c tu re U p g ra d e s /6

-2

.B

.M

R

.r v t

/1

/2

:5

:4

A

M

51-M200

BASEMENT FLOOR PLAN -

MECHANICAL

EHRM INFRASTRUCTURE

UPGRADES

656-21-235

RDL DJC

16305

1/4" = 1'-0"

BASEMENT LEVEL PLAN - MECHANICAL - TELECOM 001

N

0 4' 8'2'

FIELD VERIFICATION NOTES

1. THE HVAC CONTRACTOR SHALL VISIT THE SITE PRIOR TO BID TO FIELD VERIFY ALL EXISTING CONDITIONS WHICH MAY AFFECT THEIR

BID. THE FOLLOWING ITEMS SHALL BE VERIFIED:

A. EXACT PLACEMENT, SIZE, CAPACITY, MANUFACTURER AND CONDITION OF ALL EXISTING HVAC EQUIPMENT WITHIN SCOPE OF

WORK, WHETHER EXPLICITLY SHOWN OR NOT.

B. SIZE AND LOCATION OF ALL EXISTING DUCTWORK.

C. SIZE AND LOCATION OF ALL EXISTING GRILLES, REGISTERS AND DIFFUSERS.

D. SIZE AND LOCATION OF ALL EXISTING THERMOSTATIC CONTROL DEVICES.

E. SIZE AND LOCATION OF ALL EXISTING PLUMBING AND HYDRONIC PIPING.

2. ALL REFERENCES ON THESE DRAWINGS TO EXISTING EQUIPMENT, DUCTWORK, DIFFUSERS, THERMOSTATS AND PIPING ARE FOR REFERENCE ONLY. IT IS THE RESPONSIBLITY OF THE CONTRACTOR TO VERIFY ALL THESE ITEMS PRIOR TO BID AND INCLUDE IN THEIR

BID ANY AND ALL AMOUNTS REQUIRED TO ACCOMMODATE EXISTING CONDITIONS.

3. NO ALLOWANCES WILL BE MADE AFTER THE PROJECT HAS BEEN AWARDED FOR FAILURE TO VERIFY EXISTING CONDITIONS.

4. ANY DISCREPANCIES WHICH MAY AFFECT THE CONTRACTORS BID SHALL BE BROUGHT TO THE ATTENTION OF THE ENGINEER AND

ARCHITECT FOR DIRECTION.

KEYNOTES 1/51-M200:

1. PROVIDE NEW WALL-MOUNTED SPLIT SYSTEM AC UNIT.

2. PROVIDE NEW THERMOSTAT.

3. ROUTE REFRIGERANT PIPING TO NEW AIR COOLED CONDENSING UNIT

LOCATED ON GRADE.

4. ROUTE 1" PUMPEDCONDENSATE PIPING TO MOP SINK IN HAC 14.

5. PROVIDE NEW CONDENSATE PUMP. DRIP PAN CONDENSATE PIPING IN

TR ROOM. SEE DETAIL FOR REQUIREMENTS.

6. PROVIDE DRIP PAN FOR CONDENSATE PIPING.

7. EXTEND FIRE SPRINKLER BRANCH LINE AND PROVIDE NEW FIRE

SPINKLER HEAD.

8. PROVIDE NEW AIR COOLED CONDENSING UNIT CU-51-1. PROVIDE

CONCRETE PAD. REFER TO REFRIGERANT PIPING DETAIL 1/0-GM400

AND PAD MOUNTING DETAIL 3/0-GM400.

9. REFER TO 2/0-GM401 FOR WALL PENETRATION SEALING DETAIL.

100% CD 03/30 06/14/2024

RECORD DOCUMENTS 06/14 Robert D. Lowe

24706

RECORD

DRAWINGS

THIS IS A RECORD DRAWING BASED ON INFORMATION RECEIVED FROM THE

CONTRACTOR AND IS TO BE USED FOR THE SOLE PURPOSE OF MAINTENANCE OF

THE ORIGINAL FACILITY FOR WHICH THIS DRAWING WAS PREPARED AND NOT

FOR ADDITIONAL CONSTRUCTION.

No DATEREVISION

RECORD DOCUMENTS 06/21/24 06/21/2024

-RECORD DOCUMENT-

June 21, 2024 This Record Document has been prepared based on

Designer of Record drawings with Contractor provided markups through the construction phase of the project at the direction of the VA.

While the construction information is believed to be reliable, Architect/Engineer cannot assure its accuracy, and is not responsible for the accuracy of this Record Document. Those relying on this Record

Document are advised to independently verify its

LEGEND

CORRIDOR OUTLINE

VFY EXIST

BUILDING OUTLINE

VFY EXIST

TO 8TH ST WEST ONLYTO 8TH ST EAST & WEST

44TH AVE.

TRAIL 1

TRAIL 2

TRANSFER

SWITCH

CAPACITOR

BANK (3)

SWITCH

(2)

15KV

MAIN

SW

BATT

35 KV

TO

15 KV

TRANSFORMER

35KV

FUSED

SWITCH

METER 35KV

SWITCH

GRAVEL

GRAVEL

GRAVEL

EXISTING

ROAD

CHAIN LINK FENCE

CHAIN LINK FENCE

16' GATE

GRAVEL

ELECTRICAL

SUBSTATION

G E N E R A T O R

FUEL LINES

CONDU ITS TO TU NNEL

M V

D U

C T

B A

N K

1 1 2 W

PHARMACY ADDITION

11 2 E

G E N E R A T O R

B

CORRIDOR LINK

A

C T

TR

A

IL

ER

174 s .f.

256 s .f.

185 s .f.

149 s ..f.

155 s .f.

104 s .f.

70 s. .f .

72 s .f.

110 s .f.

276 s .f.

112 s .f.

99 s .f.

57 s .f.

146 s .f.

434 s .f.

R A

MP

U P

1:

M A X

R A

MP

U P

1:

M A X

RA

M P

UP

1:2 0 M

AX

TRANSFER

SWITCH

CAPACITOR

BANK (3)

SWITCH

(2) 15KV

MAIN

SW

BATT

35 KV

TO

15 KV

TRANSFORMER

35KV

FUSED

SWITCH

METER 35KV

SWITCH

.3

TRANSFORMER

BUILD ING

#91

5,000 GAL.

UNDERGROUND

DIESEL FUEL TANK

EXISTIN G G AS SU P P LY EQ U IP M EN T TO R EM AIN

O P ER ATIO N AL DU R IN G D EM O LITIO N AN D N EW

C O N STR U C TIO N. P R O TEC T EQU IP M EN T AN D

P IP ELIN ES IN AC C O R D AN C E W ITH G AS SU P P LIER 'S

R EC O M M EN D ATIO N S

N EW G AS SU P P LY M AIN

IN TO B U ILD IN G

SP AR E

P H O N E LIN E

EXTEN D S TO

E XISTIN G

P H O N E IN

B O ILER R O O M

P ER P LAN .

SP AR E

P H O N E

LIN E TO

M ETER

TU N N EL

E XTEN D S

A D D ITIO N AL

2'- 0" U N D ER

B U ILD IN G

FUEL LINE

VENT LINE

1,000 GAL.

UNDERGROUND

DIESEL FUEL

TANK

1,000/5,000 GAL.

UNDERGROUND

DIESEL FUEL TANK

1,000 GAL.

UNDERGROUND

DIESEL FUEL TANK

1,000 GAL.

UNDERGROUND

DIESEL FUEL TANK

S 1

LIG H T

N EW G AS SU P P LY

(C O O R D IN ATE W ITH SU P P LIER )

12"D

10"D

"D

TP TP

EXIST. BUILDING

EXIST.

BUS STOP

CC

L O

O P

16"

20"

12"

3"

8"

DN

0.

0’

BIRDCAGE

B

IR

D C

A G

E

NSP ELECTRICAL

FOR HWY DEPT

T101

I.T.

CHILLER

C O

NC

. B

LO

CKS

PAT

I O

C O

NC

. B

LO

CKS

PAT

I O

C O

NC

. B

LO

CKS

PAT

I O

C O

NC

. B

LO

CKS

PAT

I O

C O

NC

. B

LO

CKS

PAT

I O

C O

NC

. B

LO

CKS

PAT

I O

C O

NC

. B

LO

CKS

PAT

I O

C O

NC

. B

LO

CKS

PAT

I O

VESTIBULE

DN

DN

DN

FD

DN

F B

F

B

F B

F

B

F B

F

B

PASS

THROUGH

LINK TO

BUILDI NG 51

6 3. 32 56

1 13 5. 35 78

PARKING

NO

PARKING

93 49

37 6

109 5

1A

S M

O K

E B

L D

G

SMOKE

BLDG

SMOKE

BLDG

S M

O K

E B

L D

G

SMOKE

BLDG

M.H.

STOR.

SMOKE

BLDG

SMOKE

BLDG

SMOKE

BLDG

SMOKE

BLDG

SMOKE

BLDG

STOR.

BIO-

HAZ.

SAUK RIVER

GP

HOLDING POND

OWNER AND

CONSULTANTS:

CONTACT:

ADDRESS:

JUSTIN LAPPIN

ST CLOUD VA MEDICAL CENTER

4801 VETERANS DRIVE

ST. CLOUD, MN 56303

NAME:

ADDRESS:

CONTACT:

ADVANCED STRUCTURAL TECHNOLOGIES

7301 OHMS LANE; SUITE 215

EDINA, MN 55439

JOHN LEVAR

PHONE:

NAME:

ADDRESS:

CONTACT:

SPECIALIZED ENGINEERING SOLUTIONS

10360 ELLISON CIRCLE

OMAHA, NE 68134

KRIS BURNHAM

PHONE: 402-991-5520

NAME:

ADDRESS:

CONTACT:

PHONE:

NAME:

ADDRESS:

CONTACT:

PHONE:

NAME:

ADDRESS:

CONTACT:

PHONE:

ANDERSON ENGINEERING OF MN, LLC

13605 1ST AVE NORTH, SUITE 100

PLYMOUTH, MN 55441

LEE KOPPY

763-412-4000

ARCHITECT:

ANDERSON ENGINEERING OF MN, LLC

13605 1ST AVE NORTH, SUITE 100

PLYMOUTH, MN 55441

EDWARD MARKFORT

763-412-4000

952-906-7196

SPECIALIZED ENGINEERING SOLUTIONS

10360 ELLISON CIRCLE

OMAHA, NE 68134

KRIS BURNHAM

402-991-5520

No DATEREVISION

DRAWING TITLE

CHECKED BY

ST.CLOUD, MN 56303

VA MEDICAL CENTER

BUILDING No

LOCATION

DRAWING NO.DRAWN

DWG. OF

PROJECT TITLE

PLOT SCALE

PROJECT NO.

COVER

DATE:

APPROVED: APPROVED: PROJECTS SECTION MANAGER

APPROVED: OIT MANAGER DATE: APPROVED: ASSISTANT CHIEF ENGINEER DATE:

APPROVED: SAFETY MANAGER

APPROVED: CHIEF OF POLICE

APPROVED: PATIENT SAFETY

DATE:

DATE:

DATE: APPROVED: EMS MANAGER

APPROVED: M/O MANAGER

DATE:

DATE:

DATE:DATE:

APPROVED: MEDICAL CENTER DIRECTOR

APPROVED: PROJECT COR DATE:

APPROVED: INFECTION CONTROL NURSE DATE:

APPROVED: SERVICE LINE DIRECTOR

APPROVED: GEMS COORDINATOR DATE:

DATE:

APPROVED: NURSE EXECUTIVE

APPROVED: CHIEF OF STAFF DATE:

APPROVED: DIRECTOR FMS

APPROVED: ASSOCIATE DIRECTOR

DATE:

DATE:

DATE:

DATE:APPROVED: DATE:

APPROVED: DATE:

APPROVED: DATE:

Main Campus, St. Cloud, Minnesota St. Cloud VA Health Care System

N

CONSULTANT ARCHITECT/ENGINEER OF RECORD

FULLY

SPRINKLERED

VICINITY MAP:

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PHONE: 320-255-6346 x7354

CIVIL ENGINEER:

VA PRIMARY COR:

TELECOMMUNICATIONS ENGINEER:

CONTACT:

ADDRESS: ST CLOUD VA MEDICAL CENTER

4801 VETERANS DRIVE

ST. CLOUD, MN 56303

ADDITIONAL CORs:

STRUCTURAL ENGINEER:

MECH/ELEC/PLUMB/FIRE ENGINEER:

RECORD DOCUMENTS

CONTACT: COREY SELF

BRAEDAN HINOJOSA

CONTACT:

-RECORD DOCUMENT-

June 21, 2024

This Record Document has been prepared based on

Designer of Record drawings with Contractor provided markups through the construction phase of the project at the direction of the VA.

While the construction information is believed to be reliable, Architect/Engineer cannot assure its accuracy, and is not responsible for the accuracy of this Record Document. Those relying on this Record

Document are advised to independently verify its accuracy before applying it for any purpose.

C

U s e rs

\P u b li c \D o c u m e n ts \R e v it

P ro je c ts

\1 -1

-R

E

M a rk fo rt

.r v t

/2

/2

:5 :1

P

M

116-GI000

BUILDING 116 COVER SHEET &

SHEET INDEX

EHRM INFRASTRUCTURE

UPGRADES

656‐21‐235

03/30/2022

EM EM

16305

BUILDING 116 - EHRM INFRASTRUCTURE UPGRADES

0APPROX 150' 300'75'

SHEET INDEX - BUILDING 116

SHEET NO. SHEET TITLE

116-GI000 BUILDING 116 COVER SHEET & SHEET INDEX

116-GI111 FIRST FLOOR - INFECTION CONTROL & PHASING PLAN

116-AS110 FIRST FLOOR PLANS

116-TD110 FIRST FLOOR PLAN - TELECOM - DEMOLITION

116-TN110 FIRST FLOOR PLAN - TELECOMMUNICATIONS

116-TN210 FIRST FLOOR PLAN - TELECOM - CABLE DISTANCE

116-TN400 ENLARGED PLANS - TELECOMMUNICATIONS

116-E201 FIRST FLOOR - ELECTRICAL

116-E300 ELECTRICAL ENLARGED PLANS

116-M101 FIRST FLOOR DEMOLITION - MECHANICAL

116-M201 FIRST FLOOR REMODEL - MECHANICAL

SEE GENERAL SHEETS FOR ADDITIONAL INFORMATION

ROOM SCHEDULE

NO. NAME C

A

B

LI

N G

P A

T C

H P

A N

E L

B A

C K

B O

N E

P O

W E

R

B O

N D

IN

G

U P

S

D E

D

IC

A T

E D

C O

O

LI

N G

T E

M P

E R

A T

U R

E

H U

M

ID

IT

Y

R A

C K

S E

N S

O R

S P

A C

E

AREA

WIDTH

(FT)

LENGTH

(FT)

HT TO

CLG

STRUCT REMARKS

FIRST FLOOR

111 TELECOM ROOM X X AC X X X X X 61 SF 6.6 9.3 15.00 UPDATE EXIST IT/DATA ROOM TO EHRM TELECOM ROOM

STANDARDS. SEE TELECOM DRAWINGS

OPENING SCHEDULE

VA Building Number

ASSOCIATED ROOMS OPENING PANEL INFORMATION FRAME INFORMATION

H D

W G

R O

U P

F

IR

E L

A B

E L

(M

IN

G A

S K

E T

E

LE

C T

R

IC

A L

S L

A B

E L

COMMENTSFROM ROOM NAME TO ROOM NAME NUMBER WIDTH HEIGHT

PANEL

TYPE

2ND

PANEL

TYPE

PANEL

GLAZING FRAME TYPE

FRAME

GLAZING

HAZARDOUS MATERIAL SCHEDULE

LEVEL

ROOM

NO. ROOM NAME

QUESTIONABLE HAZARDOUS

ELEMENT POSSIBLE ABATEMENT ACTION

FIRST FLOOR 111 TELECOM ROOM NONE NONE

HAZARDOUS MATERIALS MAY BE ENCOUNTERED THROUGHOUT THE DISTRIBUTION ROUTING THROUGH CEILING PLENUMS AND UTILITY TUNNELS. INSTALLATION OF DISTRIBUTION SHALL NOT

DISTURB QUESTIONABLE HAZARDOUS MATERIAL.

ICRA PHASE CONSTRUCTION ROOM SCHEDULE

LEVEL

ROOM

NO. ROOM NAME

CAI BLDG NAME /

FUNCTION

CONSTRUCTION

PROJECT ACTIVITY

INFECTION CONTROL

RISK GROUP

CONTROL

PROCEDURE CLASS SECTION

CONSTRUCTION ZONE /

OCCUPIED CONSTR

DAY /

NIGHT

FIRST FLOOR 111 TELECOM ROOM OUTPATIENT MENTAL

HEALTH

TYPE C GROUP 1 CLASS II WEST OCCUPIED CONSTRUCTION NIGHT

SEE GENERAL NOTES SHEET FOR CONSTRUCTION INFECTION CONTROL RISK ASSESSMENT (ICRA) DESCRIPTIONS. TYPE, GROUP AND CLASS SELECTED TO BEST OF DESIGN TEAM'S KNOWLEDGE.

FINAL DETERMINATION BY THE VA WILL BE MADE AT A LATER DATE.

RECORD DOCUMENTS 06/21/24

LOW VISION

CLINIC

NORTH

VESTIBULE

STAFF

SPEECH

THERAPY

TREATMENT

ROOM 1

TREATMENT

ROOM 2

TREATMENT

ROOM 3

TREATMENT

ROOM 4

TREATMENT

ROOM 5

TREATMENT

ROOM 7

TREATMENT

ROOM 6

MAILROOM

CORRIDOR

PT

CHARTING

GROUP

MTG ROOM

OP GYM

PT GYM

PROSTH.

STORAGE

EQUIP

STORAGE

PATIENT

TOILET

FEMALE

TOILET

MALE

TOILET

MECHANICAL

LOW

VOLTAGE

ELECTRICAL

ELECTRICAL

CORRIDOR

WAITING

WAITING

SOUTH

VESTIBULE

RECEPTION

HAC

SCHEDULING

CLEAN

UTILITY

WC

STOR.

BALANCE

CLINIC

EQUIP

STORAGE

SPEECH

THERAPY

VIST

COORDINATOR

PROVIDER

OFFICE

LPN

REHAB

SUPERVISOR

CONSULTATION

ROOM

PROCEDURE

ROOM

O.T.

CHARTING

O.T.

CLINIC

CORRIDOR

CORRIDOR

ADL

BATHROOM

T-9

T-8

PATIENT

TOILET

SPEECH

THERAPY

ADL

KITCHEN

ADL

BEDROOM

154 SOILED

DN

REF.

FDFD

FD

FD

FD

MALE TOILET

FEMALE

TOILET

SOILED LINEN

CLEAN LINEN

RECYCLING

HALLWAY

CL LINEN

FD

FD

DWREF.

154A

CLOSET

151A

CLOSET

DN

TELECOM

ROOM

INFECTION CONTROL RISK ASSESSMENT (ICRA) LEGEND

LIMITS OF CONSTRUCTION

1 HOUR FIRE RATED ICRA / CONSTRUCTION BARRIER

LOCATION, AND DOOR, WHERE SHOWN

TEMPORARY NON-RATED (PLASTIC SHEETING) CONSTRUCTION BARRIER

LOCATION, WHERE APPROVED BY THE VA FOR USE IN RISK TYPE B.

UPGRADE TO 1 HOUR RATED PARTITION WHEN DIRECTED BY THE VA

No DATEREVISION

DRAWING TITLE

CHECKED BY

ST.CLOUD, MN 56303

VA MEDICAL CENTER

BUILDING No

LOCATION

DRAWING NO.DRAWN

DWG. OF

PROJECT TITLE

PLOT SCALE

PROJECT NO.

DATE:

CONSULTANT ARCHITECT/ENGINEER OF RECORD

FULLY

SPRINKLERED

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

RECORD DOCUMENTS

-RECORD DOCUMENT-

June 21, 2024

This Record Document has been prepared based on

Designer of Record drawings with Contractor provided markups through the construction phase of the project at the direction of the VA.

While the construction information is believed to be reliable, Architect/Engineer cannot assure its accuracy, and is not responsible for the accuracy of this Record Document. Those relying on this Record

Document are advised to independently verify its accuracy before applying it for any purpose.

C

U s e rs

\P u b li c \D o c u m e n ts \R e v it

P ro je c ts

\1 -1

-R

E

M a rk fo rt

.r v t

/1

/2

:3

:4

A

M

116-GI111

FIRST FLOOR - INFECTION

CONTROL & PHASING PLAN

EHRM INFRASTRUCTURE

UPGRADES

656‐21‐235

03/30/2022

EM BMW

16305

1/8" = 1'-0"

FIRST FLOOR - CONST BARRIER PLAN

ROOM ICRA SCHEDULE

LEVEL

ROOM

NO. ROOM NAME CAI BLDG NAME / FUNCTION CONSTRUCTION PROJECT ACTIVITY INFECTION CONTROL RISK GROUP CONTROL PROCEDURE CLASS

FIRST FLOOR 111 TELECOM ROOM OUTPATIENT MENTAL HEALTH TYPE C GROUP 1 CLASS II

SEE GENERAL NOTES SHEET FOR CONSTRUCTION INFECTION CONTROL RISK ASSESSMENT (ICRA) DESCRIPTIONS. TYPE, GROUP AND CLASS SELECTED TO BEST OF DESIGN TEAM'S KNOWLEDGE.

FINAL DETERMINATION BY THE VA WILL BE MADE AT A LATER DATE.

N

0 8' 16'4'

NORTH

VESTIBULE

STAFF

SPEECH

THERAPY

TREATMENT

ROOM 1

TREATMENT

ROOM 2

TREATMENT

ROOM 3

TREATMENT

ROOM 4

TREATMENT

ROOM 5

TREATMENT

ROOM 7

TREATMENT

ROOM 6

MAILROOM

CORRIDOR

PT

CHARTING

GROUP

MTG ROOM

OP GYM

PT GYM

PROSTH.

STORAGE

EQUIP

STORAGE

PATIENT

TOILET

FEMALE

TOILET

MALE

TOILET

MECHANICAL

LOW

VOLTAGE

ELECTRICAL

ELECTRICAL

CORRIDOR

WAITING

WAITING

SOUTH

VESTIBULE

RECEPTION

HAC

SCHEDULING

CLEAN

UTILITY

WC

STOR.

BALANCE

CLINIC

EQUIP

STORAGE

SPEECH

THERAPY

VIST

COORDINATOR

PROVIDER

OFFICE

LPN

REHAB

SUPERVISOR

CONSULTATION

ROOM

PROCEDURE

ROOM

O.T.

CHARTING

O.T.

CLINIC

CORRIDOR

CORRIDOR

ADL

BATHROOM

T-9

T-8

PATIENT

TOILET

SPEECH

THERAPY

ADL

KITCHEN

ADL

BEDROOM

154 SOILED

DN

REF.

FDFD

FD

FD

FD

MALE TOILET

FEMALE

TOILET

SOILED LINEN

CLEAN LINEN

RECYCLING

HALLWAY

CL LINEN

FD

FD

DWREF.

154A

CLOSET

151A

CLOSET

DN

TELECOM

ROOM

6'-7 1/4"

9' -3

/4

116-AS110

TELECOM

ROOM

4' -7

2'

-6

2' -2

IN-03.01

TELECOM

ROOM

TELECOM

ROOM

No DATEREVISION

DRAWING TITLE

CHECKED BY

ST.CLOUD, MN 56303

VA MEDICAL CENTER

BUILDING No

LOCATION

DRAWING NO.DRAWN

DWG. OF

PROJECT TITLE

PLOT SCALE

PROJECT NO.

DATE:

CONSULTANT ARCHITECT/ENGINEER OF RECORD

FULLY

SPRINKLERED

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

RECORD DOCUMENTS

-RECORD DOCUMENT-

June 21, 2024

This Record Document has been prepared based on

Designer of Record drawings with Contractor provided markups through the construction phase of the project at the direction of the VA.

While the construction information is believed to be reliable, Architect/Engineer cannot assure its accuracy, and is not responsible for the accuracy of this Record Document. Those relying on this Record

Document are advised to independently verify its accuracy before applying it for any purpose.

C

U s e rs

\P u b li c \D o c u m e n ts \R e v it

P ro je c ts

\1 -1

-R

E

M a rk fo rt

.r v t

/1

/2

:3

:3

A

M

116-AS110

FIRST FLOOR PLANS

EHRM INFRASTRUCTURE

UPGRADES

656‐21‐235

03/30/2022

EM EM

16305

N

0 8' 16'4' 1/8" = 1'-0"

FIRST FLOOR - OVERALL PLAN

1/4" = 1'-0"

ENLARGED FLOOR PLAN

1/4" = 1'-0"

DEMOLITION PLAN

1/4" = 1'-0"

REFLECTED CEILING PLAN

DE1

RC1 RC2

_DEMOLITION PLAN KEYED NOTES

DE1 PREPARE WALL FOR PLYWOOD BACKBOARD INSTALLATION AND EHRM

REQUIREMENTS, SEE FLOOR PLAN AND TELECOM DRAWINGS

NOTE: NOT ALL KEYED NOTES MAY BE USED ON EACH PLAN

_FLOOR PLAN KEYED NOTES

FL1 ALL FOUR PERIMETER WALL PARTITIONS APPLY 4' BY 8' AC GRADE ¾”

TRADE SIZE FIRE RATED PLYWOOD BACKBOARD FINISHED WITH

HIGH-GLOSS WHITE PAINT OVER TWO COATS OF FIRE RESISTANT PAINT

FOR SERVICE PROVIDER / SECURITY / VIDEO / ET CETERA. DO NOT PAINT

OVER FIRE RATING STAMP.

FL3 UPGRADE PARTITION TO 1 HOUR FIRE AND SMOKE BARRIER. PROVIDE

TESTED HEAD OF PARTITION ASSEMBLY WITH MATERIALS THAT RESIST

THE PASSAGE OF SMOKE. SEAL JOINT AT HEAD AND ALL PENETRATIONS

WITH FIRE CAULK.

FL20 TELECOM EQUIPMENT, SEE TELECOM DRAWINGS.

NOTE: NOT ALL KEYED NOTES MAY BE USED ON EACH PLAN

_REFLECTED CEILING PLAN KEYED NOTES

RC1 LED LIGHTING, SEE ELECTRICAL. IN FRONT OF AND BEHIND CABINET

ROWS PROVIDE 500 LUMENS IN HORIZONTAL AND 200 LUMENS IN THE

VERTICAL AT 3 FT AFF. OPERATED BY MOTION SENSOR PER CABINET

ROW OR SECTION.

RC2 OPEN TO STRUCTURAL FLOOR ABOVE

NOTE: NOT ALL KEYED NOTES MAY BE USED ON EACH PLAN

N

0 4' 8'2'

N

0 4' 8'2'

N

0 4' 8'2'

DE1

DE1

FL1 FL20

_SHEET NOTES

1. SEE GENERAL NOTES AND CAMPUS DRAWINGS FOR GENERAL

INFORMATION, LIFE SAFETY, ICRA, AND PHASING

2. ALL EXISTING CONDITIONS MUST BE FIELD VERIFIED BY THE

CONTRACTOR PRIOR TO DEMOLITION OR CONSTRUCTION. EXISTING

CONDITIONS THAT DIFFER FROM THOSE SHOWN MUST BE BROUGHT TO

THE ATTENTION OF THE C.O.R. TO INFORM THE ARCHITECTS AND

ENGINEERS.

3. THE INFORMATION SHOWN ON THE DRAWINGS IS BASED ON DRAWINGS

AND PHOTOGRAPHS PROVIDED BY THE C.O.R. COMBINED WITH

OBSERVATIONS AND SURVEYED DATA FROM THE ARCHITECTS AND

ENGINEERS.

4. SEE CIVIL, STRUCTURAL, TELECOM, ELECTRICAL, MECHANICAL, AND

PLUMBING DRAWINGS AND SPECIFICATIONS FOR ADDITIONAL

DEMOLITION AND CONSTRUCTION REQUIREMENTS.

5. PORTABLE FIRE EXTINGUISHERS (CO2 OR HALOGENATED TYPE AS

DETERMINED BY THE VA) WITH WALL MOUNT BRACKET AND CODE

REQUIRED SIGNAGE SHALL BE PROVIDED BY THE CONTRACTOR WITHIN

TELECOM ROOMS.

FL3

FL3

FL3

FL3

29 55

114 56

140140

177179 179

CLINIC

LOW VISION

VESTIBULE

NORTH

STAFF

THERAPY

SPEECH

ROOM 1

TREATMENT

ROOM 2

TREATMENT

ROOM 3

TREATMENT

ROOM 4

TREATMENT

ROOM 5

TREATMENT

ROOM 7

TREATMENT

ROOM 6

TREATMENT

MAILROOM

CORRIDOR126

CHARTING

PT

MTG ROOM

GROUP

OP GYM

PT GYM 123

STORAGE

PROSTH.

STORAGE

EQUIP.

TOILET

PATIENT

TOILET

FEMALE

TOILET

MALE

MECHANICAL

VOLTAGE

LOW

ELECTRICAL

ELECTRICAL

CORRIDOR

WAITING

WAITING

VESTIBULE

SOUTH

RECEPTION

HAC

SCHEDULING

UTILITY

CLEAN

STOR.

WC

CLINIC

BALANCE

STORAGE

EQUIP.

THERAPY

SPEECH

COORDINATOR

VIST

OFFICE

PROVIDER

LPN

SUPERVISOR

REHAB

ROOM

CONSULTATION

ROOM

PROCEDURE

CHARTING

O.T. 156

CLINIC

O.T.

CORRIDOR

CORRIDOR

BATHROOM

ADL

T-9

T-8

TOILET

PATIENT

THERAPY

SPEECH

KITCHEN

ADL

BEDROOM

ADL

SOILED

REF.

FDFD

FD

FD

FD

MALE TOILET

FEMALE

TOILET

SOILED LINEN

CLEAN LINEN

RECYCLING

HALLWAY

CL LINEN

FD

FD

DWREF.

154A

CLOSET

151A

CLOSET

DN

29 55

114 56

140140

177179 179

CLINIC

LOW VISION

VESTIBULE

NORTH

STAFF

THERAPY

SPEECH

ROOM 1

TREATMENT

ROOM 2

TREATMENT

ROOM 3

TREATMENT

ROOM 4

TREATMENT

ROOM 5

TREATMENT

ROOM 7

TREATMENT

ROOM 6

TREATMENT

MAILROOM

CORRIDOR126

CHARTING

PT

MTG ROOM

GROUP

OP GYM

PT GYM 123

STORAGE

PROSTH.

STORAGE

EQUIP.

TOILET

PATIENT

TOILET

FEMALE

TOILET

MALE

MECHANICAL

VOLTAGE

LOW

ELECTRICAL

ELECTRICAL

CORRIDOR

WAITING

WAITING

VESTIBULE

SOUTH

RECEPTION

HAC

SCHEDULING

UTILITY

CLEAN

STOR.

WC

CLINIC

BALANCE

STORAGE

EQUIP.

THERAPY

SPEECH

COORDINATOR

VIST

OFFICE

PROVIDER

LPN

SUPERVISOR

REHAB

ROOM

CONSULTATION

ROOM

PROCEDURE

CHARTING

O.T. 156

CLINIC

O.T.

CORRIDOR

CORRIDOR

BATHROOM

ADL

T-9

T-8

TOILET

PATIENT

THERAPY

SPEECH

KITCHEN

ADL

BEDROOM

ADL

SOILED

REF.

FDFD

FD

FD

FD

MALE TOILET

FEMALE

TOILET

SOILED LINEN

CLEAN LINEN

RECYCLING

HALLWAY

CL LINEN

FD

FD

DWREF.

154A

CLOSET

151A

CLOSET

DN

C

C

C

C

C

MAILROOM

RECEPTION

MAILROOM

RECEPTION

C

116-TD110

LIMITS OF DATA CABLING DEMOLITION

1D

2D

2D 2D

1D

2D

2D 2D

2D

2D

2D

2D

2D

2D

WAP

WAP

WAP

WAP

2D

2D

2D

WAP

2D

2D

2D

2D

2D2D2D

2D 2D 2D

2D 2D 2D

2D2D2D

1D

2D

2D

2D

E E E

EEE

E

E

E

E

E

E

E

E

E

E

E

EEE

E E E

E

E

E E

EE

E

E

E

E

E

E

E

E

E

E

E

E

EE

E

2D

2D

2D

E

E

E

2D

E

2D

2D

2D

E

E

E

2D E

E

E

E

E

2D

2D

2D

2D

E

E

E

E

WAP

2D

2D2D

2D E

E

E

E

E

2D

2D

2D

2DE

E

E 2D

WAP

2D

E

E 2D

E

EE

2D 2D

E

6D

EWAP

E E E

E

E E

E

EEE

E

E

E

E E

E

12"x2"

"x

2"

12"x2"

"x

2"

12"x2"12"x2"

"x

2"

"x

2"

12"x2"

"x

2"

"x 2"

12"x2"

E

E

"x

2"

E

4"

DOWN

E

4"4"2"

DR

DR

SP R

D

D

E

DATA

RACKS

E

4" DOWN

E

4"4"2" E

RECORD DOCUMENTS

No DATEREVISION

DRAWING TITLE

CHECKED BY

ST.CLOUD, MN 56303

VA MEDICAL CENTER

BUILDING No

LOCATION

DRAWING NO.DRAWN

DWG. OF

PROJECT TITLE

PLOT SCALE

PROJECT NO.

DATE:

CONSULTANT ARCHITECT/ENGINEER OF RECORD

FULLY

SPRINKLERED

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

-RECORD DOCUMENT-

June 21, 2024

This Record Document has been prepared based on

Designer of Record drawings with Contractor provided markups through the construction phase of the project at the direction of the VA.

While the construction information is believed to be reliable, Architect/Engineer cannot assure its accuracy, and is not responsible for the accuracy of this Record Document. Those relying on this Record

Document are advised to independently verify its accuracy before applying it for any purpose.

RECORD DOCUMENTS 06/21/24

B

IM

/2

.0

V A

S t C lo u d E

H R

M I n fr a s tr u c tu re U p g ra d e s /6

-2

.B

.T

R

.r v t

/6

/2

:3

:0

P M

116-TD110

FIRST FLOOR PLAN -

TELECOM - DEMOLITION

EHRM INFRASTRUCTURE

UPGRADES

656‐21‐235

03/30/2022

KSB SSK

16305

SHEET NOTES:

1. EXISTING TELECOMMUNICATIONS CAGE AND RACK SHALL BE INCLUDED WITHIN THE SCOPE OF DEMOLITION. EXISTING CABLING AND ASSOCIATED OUTLETS SHALL BE REMOVED AND REPLACED 1 FOR 1 AND REFED FROM DISTRIBUTION EQUIPMENT LOCATED WITHIN THE NEW TELECOMMUNICATIONS ROOM. REFER TO GENERAL CABLING NOTES FOR APPROXIMATE QUANTITIES. REFER TO NEW WORK

PLANS FOR SERVING COMMUNICATIONS ROOM LOCATION AND NEW CABLING ROUTES.

2. EXISTING CABLE TRAY, SECURITY CAMERAS, GROUND BUS BARS, AND RACKS FROM DECOMMISSIONED

ROOMS ARE TO BE REUSED, WHEN POSSBILE, IN NEW CONSTRUCTION TRS.

N

0 8' 16'4' 1/8" = 1'-0"1

FIRST FLOOR PLAN - TELECOM - DEMOLITION

1/4" = 1'-0"2

ENLARGED PLAN - EXIST RM 111 - TELECOM - DEMO

0 4' 8'2'

N

GENERAL NOTES:

A. REFER TO GENERAL DEMOLITION NOTES ON SHEET T000 FOR ADDITIONAL DEMOLITION SCOPE.

CABLING NOTE:

CABLING NOTES:

A. THE EXISTING CABLE COUNT ARE THE CABLES CURRENTLY PRESENT IN THE SPACE. THE CABLE

RELOCATION COUNT ARE THE NEW OR RELOCATED CABLES TO BE FED FROM THE SPACE. THE FINAL CABLE COUNT ARE THE CABLES THAT WILL BE PRESENT IN THE SPACE AT THE COMPLETION OF THE

PROJECT.

1. ROOM 111

EXISTING CABLE COUNT

DATA (CAT6): 0

DATA (CAT5e): 114

DATA (CAT5): 0

DATA (CAT3): 0

CABLE RELOCATION COUNT

DATA (CAT6): 0

DATA (CAT5e): 0

DATA (CAT5): 0

DATA (CAT3): 0

EXISTING CABLE TO REMAIN

DATA (CAT6): 0

DATA (CAT5e): 0

DATA (CAT5): 0

DATA (CAT3): 0

FINAL CABLE COUNT

DATA (CAT6): 0

DATA (CAT5e): 0

DATA (CAT5): 0

DATA (CAT3): 0

NORTH

VESTIBULE

STAFF

SPEECH

THERAPY

TREATMENT

ROOM 1

TREATMENT

ROOM 2

TREATMENT

ROOM 3

TREATMENT

ROOM 4

TREATMENT

ROOM 5

TREATMENT

ROOM 7

TREATMENT

ROOM 6

MAILROOM

CORRIDOR

PT

CHARTING

GROUP

MTG ROOM

OP GYM

PT GYM

PROSTH.

STORAGE

EQUIP

STORAGE

PATIENT

TOILET

FEMALE

TOILET

MALE

TOILET

MECHANICAL

LOW

VOLTAGE

ELECTRICAL

ELECTRICAL

CORRIDOR

WAITING

WAITING

SOUTH

VESTIBULE

RECEPTION

HAC

SCHEDULING

CLEAN

UTILITY

WC

STOR.

BALANCE

CLINIC

EQUIP

STORAGE

SPEECH

THERAPY

VIST

COORDINATOR

PROVIDER

OFFICE

LPN

REHAB

SUPERVISOR

CONSULTATION

ROOM

PROCEDURE

ROOM

O.T.

CHARTING

O.T.

CLINIC

CORRIDOR

CORRIDOR

ADL

BATHROOM

T-9

T-8

PATIENT

TOILET

SPEECH

THERAPY

ADL

KITCHEN

ADL

BEDROOM

154 SOILED

REF.

FDFD

FD

FD

FD

MALE TOILET

FEMALE

TOILET

SOILED LINEN

CLEAN LINEN

RECYCLING

HALLWAY

CL LINEN

FD

FD

DWREF.

154A

CLOSET

151A

CLOSET

DN

LOW VISION

CLINIC

NORTH

VESTIBULE

STAFF

SPEECH

THERAPY

TREATMENT

ROOM 1

TREATMENT

ROOM 2

TREATMENT

ROOM 3

TREATMENT

ROOM 4

TREATMENT

ROOM 5

TREATMENT

ROOM 7

TREATMENT

ROOM 6

MAILROOM

CORRIDOR

PT

CHARTING

GROUP

MTG ROOM

OP GYM

PT GYM

PROSTH.

STORAGE

EQUIP

STORAGE

PATIENT

TOILET

FEMALE

TOILET

MALE

TOILET

MECHANICAL

LOW

VOLTAGE

ELECTRICAL

ELECTRICAL

CORRIDOR

WAITING

WAITING

SOUTH

VESTIBULE

RECEPTION

HAC

SCHEDULING

CLEAN

UTILITY

WC

STOR.

BALANCE

CLINIC

EQUIP

STORAGE

SPEECH

THERAPY

VIST

COORDINATOR

PROVIDER

OFFICE

LPN

REHAB

SUPERVISOR

CONSULTATION

ROOM

PROCEDURE

ROOM

O.T.

CHARTING

O.T.

CLINIC

CORRIDOR

CORRIDOR

ADL

BATHROOM

T-9

T-8

PATIENT

TOILET

SPEECH

THERAPY

ADL

KITCHEN

ADL

BEDROOM

154 SOILED

REF.

FDFD

FD

FD

FD

MALE TOILET

FEMALE

TOILET

SOILED LINEN

CLEAN LINEN

RECYCLING

HALLWAY

CL LINEN

FD

FD

DWREF.

154A

CLOSET

151A

CLOSET

DN

C

C

C

C

C

C

TELECOM ROOM

116-TN400

LIMITS OF DATA CABLING REPLACEMENT

FROM ROOM 111

1D

2D

2D

2D 2D

1D

2D

WAP

WAP

WAP

2D 2D

2D

2D

2D

2D

2D

2D

WAP

2D 2D 2D

2D2D2D 2D

2D 2D 2D

2D2D2D

1D

2D

2D

2D

2D

WAP

2D

2D

2D

2D

E E E

EEE

E

E

E

E

E

E

E

E

E

E

E

EEE

E E E

E

E

E E

EE

E

E

E

E

E

E

E

E

E

E

E

E

EE

E

2D

2D

2D

2D

2D

2D

2D

2D

E

E

E

E

E

E

E

E

E

E

2D

2D

2D E

E 2D

6D

E

E

E

E

E 2D

E

2D

E 2D

WAP

E

E 2D

2D

2D

2D

2D

E

E

E

E

E

2D

WAP

2D

E

E

2D E

2D 2D

EE

12"x2"

"x

2"

12"x2" 12"x2"

"x

2"

1 CABLE TRAY

E

WAP

4"

2"

2"

2"

2"

2"

2"

E E

E E

E

E

E E

E

EEE

E

E

E

E E

E

"x

2"

12"x2"

"x

2"

12"x2"

"x

2"

"x

2"

E

E

"x

2"

E

4"

RECORD DOCUMENTS

No DATEREVISION

DRAWING TITLE

CHECKED BY

ST.CLOUD, MN 56303

VA MEDICAL CENTER

BUILDING No

LOCATION

DRAWING NO.DRAWN

DWG. OF

PROJECT TITLE

PLOT SCALE

PROJECT NO.

DATE:

CONSULTANT ARCHITECT/ENGINEER OF RECORD

FULLY

SPRINKLERED

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

-RECORD DOCUMENT-

June 21, 2024

This Record Document has been prepared based on

Designer of Record drawings with Contractor provided markups through the construction phase of the project at the direction of the VA.

While the construction information is believed to be reliable, Architect/Engineer cannot assure its accuracy, and is not responsible for the accuracy of this Record Document. Those relying on this Record

Document are advised to independently verify its accuracy before applying it for any purpose.

RECORD DOCUMENTS 06/21/24

B

IM

/2

.0

V A

S t C lo u d E

H R

M I n fr a s tr u c tu re U p g ra d e s /6

-2

.B

.T

R

.r v t

/6

/2

:3

:0

P M

116-TN110

FIRST FLOOR PLAN -

TELECOMMUNICATIONS

EHRM INFRASTRUCTURE

UPGRADES

656‐21‐235

03/30/2022

KSB SSK

16305

SHEET NOTES:

1. CONTRACTOR TO PROVIDE NEW WIRE BASKET, AS NEEDED, TO MAINTAIN A 50% OR LESS FILL OF THE CABLE TRAY SYSTEM FOR THE FLOOR. THE NEW WIRE BASKET WILL MATCH THE SIZE AND DISTANCE, EITHER BESIDE OR BELOW THE EXISTING CABLE TRAY, TO MATCH THE EXISTING TELECOM CABLE

TRAY.

2. PROVIDE JUNCTION BOX TO CONNECT FIBER CONDUIT ENTRY TO EXTEND CONDUIT PATHWAY TO THE

NEW TELECOM ROOM.

3. NEW B SIDE FIBER TO BE PULLED UTILIZING THE EXISTING FIBER PATH. ONCE THE A SIDE FIBER IS ACTIVATED AND IN USE, THE EXISTING FIBER CAN BE REMOVED. THE NEW B SIDE FIBER CAN THEN BE

ACTIVATED.

N

0 8' 16'4' 1/8" = 1'-0"

FIRST FLOOR PLAN - TELECOMMUNICATIONS

GENERAL NOTES:

A. REFER TO GENERAL NOTES ON SHEET T000 FOR ADDITIONAL SCOPE.

NORTH

VESTIBULE

STAFF

SPEECH

THERAPY

TREATMENT

ROOM 1

TREATMENT

ROOM 2

TREATMENT

ROOM 3

TREATMENT

ROOM 4

TREATMENT

ROOM 5

TREATMENT

ROOM 7

TREATMENT

ROOM 6

MAILROOM

CORRI DOR

PT

CHARTING

GROUP

MTG ROOM

OP GYM

PT GYM

PROSTH.

STORAGE

EQUIP

STORAGE

PATIENT

TOILET

FEMALE

TOILET

MALE

TOILET

MECHANI CAL

LOW

VOLTAGE

ELECTRICAL

ELECTRICAL

CORRI DOR

WAITING

WAITING

SOUTH

VESTIBULE

RECEPTION

HAC

SCHEDULING

CLEAN

UTILITY

WC

STOR.

BALANCE

CLINIC

EQUIP

STORAGE

SPEECH

THERAPY

VIST

COORDINATOR

PROVI DER

OFFICE

LPN

REHAB

SUPERVI SOR

CONSULTATION

ROOM

PROCEDURE

ROOM

O.T.

CHARTING

O.T.

CLINIC

CORRI DOR

CORRI DOR

ADL

BATHROOM

T-9

T-8

PATIENT

TOILET

SPEECH

THERAPY

ADL

KITCHEN

ADL

BEDROOM

154 SOILED

REF.

FDFD

FD

FD

FD

MALE TOILET

FEMALE

TOILET

SOILED LINEN

CLEAN LINEN

RECYCLING

HALLWAY

CL LINEN

FD

FD

DWREF.

154A

CLOSET

151A

CLOSET

DN

LOW VISION

CLINIC

NORTH

VESTIBULE

STAFF

SPEECH

THERAPY

TREATMENT

ROOM 1

TREATMENT

ROOM 2

TREATMENT

ROOM 3

TREATMENT

ROOM 4

TREATMENT

ROOM 5

TREATMENT

ROOM 7

TREATMENT

ROOM 6

MAILROOM

CORRI DOR

PT

CHARTING

GROUP

MTG ROOM

OP GYM

PT GYM

PROSTH.

STORAGE

EQUIP

STORAGE

PATIENT

TOILET

FEMALE

TOILET

MALE

TOILET

MECHANI CAL

LOW

VOLTAGE

ELECTRICAL

ELECTRICAL

CORRI DOR

WAITING

WAITING

SOUTH

VESTIBULE

RECEPTION

HAC

SCHEDULING

CLEAN

UTILITY

WC

STOR.

BALANCE

CLINIC

EQUIP

STORAGE

SPEECH

THERAPY

VIST

COORDINATOR

PROVI DER

OFFICE

LPN

REHAB

SUPERVI SOR

CONSULTATION

ROOM

PROCEDURE

ROOM

O.T.

CHARTING

O.T.

CLINIC

CORRI DOR

CORRI DOR

ADL

BATHROOM

T-9

T-8

PATIENT

TOILET

SPEECH

THERAPY

ADL

KITCHEN

ADL

BEDROOM

154 SOILED

REF.

FDFD

FD

FD

FD

MALE TOILET

FEMALE

TOILET

SOILED LINEN

CLEAN LINEN

RECYCLING

HALLWAY

CL LINEN

FD

FD

DWREF.

154A

CLOSET

151A

CLOSET

DN

RECORD DOCUMENTS

No DATEREVISION

DRAWING TITLE

CHECKED BY

ST.CLOUD, MN 56303

VA MEDICAL CENTER

BUILDING No

LOCATION

DRAWING NO.DRAWN

DWG. OF

PROJECT TITLE

PLOT SCALE

PROJECT NO.

DATE:

CONSULTANT ARCHITECT/ENGINEER OF RECORD

FULLY

SPRINKLERED

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

-RECORD DOCUMENT-

June 21, 2024

This Record Document has been prepared based on

Designer of Record drawings with Contractor provided markups through the construction phase of the project at the direction of the VA.

While the construction information is believed to be reliable, Architect/Engineer cannot assure its accuracy, and is not responsible for the accuracy of this Record Document. Those relying on this Record

Document are advised to independently verify its accuracy before applying it for any purpose.

RECORD DOCUMENTS 06/21/24

B

IM

/2

.0

V A

S t C lo u d E

H R

M I n fr a s tr u c tu re U p g ra d e s /6

-2

.B

.T

R

.r v t

/6

/2

:3

:1

P M

116-TN210

FIRST FLOOR PLAN -

TELECOM - CABLE DISTANCE

EHRM INFRASTRUCTURE

UPGRADES

656‐21‐235

03/30/2022

KSB SSK

16305

N

0 30' 60'15' 1" = 30'-0"

FIRST FLOOR PLAN - TELECOM - CABLE DISTANCE

RECEPTIONRECEPTION

A C

C R

C

TELECOM ROOM

116-TN400

1 - a b

1 - c d

E

SP

12"x2"

DATA RACK

CABLE

TRAY

E

W

KEYPAD

2"

AC

R

"x

2"

4"4"2"

4" DOWN

E

12" LADDER

FIRST FLOOR

0' - 0"

SECOND FLOOR

12' - 0"

FIRST FLOOR

0"

SECOND FLOOR

12'-0"

FIRST FLOOR

0' - 0"

SECOND FLOOR

12' - 0"

FIRST FLOOR

0"

SECOND FLOOR

12'-0"

FIRST FLOOR

0' - 0"

SECOND FLOOR

12' - 0"

FIRST FLOOR

0"

SECOND FLOOR

12'-0"

FIRST FLOOR

0' - 0"

SECOND FLOOR

12' - 0"

FIRST FLOOR

0"

SECOND FLOOR

12'-0"

NEMA L21-20R (TYP)

RACK 1

1U 144 STRAND OM4 AND OS2 DISTRIBUTION PANEL

1U BONDING BUS BAR (BACK) 1U ANGLED BLANKING PANEL (FRONT)

1U 48 PORT CAT5E BACKBONE ANGLED PATCH PANEL

SPACE FOR FUTURE HORIZONTAL CABLE

DISTRIBUTION. PROVIDE ANGLED BLANKING PANELS

FOR UNUSED SPACES.

1U 48 PORT CAT6A ANGLED DATA PATCH PANEL

RACK 1

V E

R T

IC

A

L R

A C

K P

D U

V E

R T

IC

A

L R

A C

K P

D U

1U 48 PORT CAT6A ANGLED DATA PATCH PANEL

1U 48 PORT CAT6A ANGLED DATA PATCH PANEL

1U 48 PORT CAT6A ANGLED DATA PATCH PANEL

1U 48 PORT CAT6A ANGLED DATA PATCH PANEL

1U 48 PORT CAT6A ANGLED DATA PATCH PANEL

1U CABLE MANAGEMENT

VA OIT PROVIDED 1U 48 PORT SWITCH

2U CABLE MANAGEMENT

VA OIT PROVIDED 1U 48 PORT SWITCH

2U CABLE MANAGEMENT

VA OIT PROVIDED 1U 48 PORT SWITCH

2U CABLE MANAGEMENT

VA OIT PROVIDED 1U 48 PORT SWITCH

2U CABLE MANAGEMENT

VA OIT PROVIDED 1U 48 PORT SWITCH

2U CABLE MANAGEMENT

1U CABLE MANAGEMENT

VA OIT PROVIDED 1U 48 PORT SWITCH

6U SPACE FOR FUTURE USE.

PROVIDE BLANK PANELS FOR UNUSED SPACES.

6U 5KW RACK MOUNT UPS

D

PROVIDE DATA CABLE TO RACK

MOUNTED UPS FOR CONNECTION

TO MONITORING SYSTEM

4 POST CHANNEL

RACK (TYP)

VERTICAL CABLE

MANAGEMENT (TYP)

NOTES:

1. REFER TO NEW WORK PLAN FOR RACK LOCATIONS.

2. COORDINATE EXACT RACK LOCATION WITH OWNER PRIOR TO PERMANENT INSTALLATION.

3. SEE PROJECT SPECIFICATIONS FOR ADDITIONAL RACK COMPONENTS.

4. RACK ELEVATION SHOWS A FULLY CONFIGURED SAMPLE RACK. CONTRACTOR TO PROVIDE REQUIRED EQUIPMENT TO

SUPPORT THE FINAL DATA COUNT FROM THE ENLARGED NEW SHEET.

5. COORDINATE FINAL RACK COMPONENT LAYOUT WITH OWNER'S IS/IT REPRESENTATIVE.

6. CONTRACTOR IS RESPONSIBLE FOR FINAL CABLE COUNT, QUANTITY OF PATCH PANELS, SWITCHES, FIBER ENCLOSURES, BLANKING PANELS, CABLE MANAGEMENT, TR PATCH CABLES, AND MOUNTING HARDWARE NOT MARKED AS “OIT PROVIDED”.

7. PUNCH DOWN COPPER BACKBONE CABLE TO RACK MOUNT PATCH PANEL. TERMINATE ONE (1) PAIR PER PATCH PANEL PORT.

RECORD DOCUMENTS

No DATEREVISION

DRAWING TITLE

CHECKED BY

ST.CLOUD, MN 56303

VA MEDICAL CENTER

BUILDING No

LOCATION

DRAWING NO.DRAWN

DWG. OF

PROJECT TITLE

PLOT SCALE

PROJECT NO.

DATE:

CONSULTANT ARCHITECT/ENGINEER OF RECORD

FULLY

SPRINKLERED

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

-RECORD DOCUMENT-

June 21, 2024

This Record Document has been prepared based on

Designer of Record drawings with Contractor provided markups through the construction phase of the project at the direction of the VA.

While the construction information is believed to be reliable, Architect/Engineer cannot assure its accuracy, and is not responsible for the accuracy of this Record Document. Those relying on this Record

Document are advised to independently verify its accuracy before applying it for any purpose.

RECORD DOCUMENTS 06/21/24

B

IM

/2

.0

V A

S t C lo u d E

H R

M I n fr a s tr u c tu re U p g ra d e s /6

-2

.B

.T

R

.r v t

/6

/2

:3

:1

P M

116-TN400

ENLARGED PLANS -

TELECOMMUNICATIONS

EHRM INFRASTRUCTURE

UPGRADES

656‐21‐235

03/30/2022

KSB SSK

16305

N

0 2' 4'1'

0 4' 8'2' 0 4' 8'2' 0 4' 8'2' 0 4' 8'2'

GENERAL NOTES:

A. REFER TO GENERAL DEMOLITION NOTES ON SHEET T000 FOR ADDITIONAL DEMOLITION SCOPE.

CABLING NOTE:

CABLING NOTES:

A. THE EXISTING CABLE COUNT ARE THE CABLES CURRENTLY PRESENT IN THE SPACE.

THE CABLE RELOCATION COUNT ARE THE NEW OR RELOCATED CABLES TO BE FED

FROM THE SPACE. THE FINAL CABLE COUNT ARE THE CABLES THAT WILL BE

PRESENT IN THE SPACE AT THE COMPLETION OF THE PROJECT.

1. ROOM 111

EXISTING CABLE COUNT

DATA (CAT6): 0

DATA (CAT5e): 114

DATA (CAT5): 0

DATA (CAT3): 0

CABLE RELOCATION COUNT

DATA (CAT6): 0

DATA (CAT5e): 0

DATA (CAT5): 0

DATA (CAT3): 0

EXISTING CABLE TO REMAIN

DATA (CAT6): 0

DATA (CAT5e): 0

DATA (CAT5): 0

DATA (CAT3): 0

FINAL CABLE COUNT

DATA (CAT6A): 114

DATA (CAT6): 0

1/2" = 1'-0"

ENLARGED PLAN -EXIST TR 111 - TELECOM - CABLE TRAY AND DATA

1/4" = 1'-0"

1 - a 1/4" = 1'-0"

1 - b

1/4" = 1'-0"

1 - c 1/4" = 1'-0"

1 - d

NOT TO SCALE6

COMMUNICATIONS - TYPICAL ONE RACK ELEVATION WITH RACK MOUNT UPS - EXIST TR 111

SHEET NOTES:

1. IF NO ACCESS CONTROL PANEL IS PRESENT IN THE TR, PROVIDE A NEW ACCESS CONTROL PANEL TO BE INSTALLED IN THE TELECOM ROOM. THE CARD READER AND KEYPAD FOR THIS ROOM TO BE WIRED TO THE NEW ACCESS CONTROL PANEL. EXISTING CARD READERS AND KEYPADS WILL BE MOVED TO THE NEW

CONTROL PANEL UNDER A DIFFERENT PROJECT.

E

CLINIC

NORTH

VESTIBULE

STAFF

SPEECH

THERAPY

TREATMENT

ROOM 1

TREATMENT

ROOM 2

TREATMENT

ROOM 3

TREATMENT

ROOM 4

TREATMENT

ROOM 5

TREATMENT

ROOM 7

TREATMENT

ROOM 6

MAILROOM

CORRIDOR

PT

CHARTING

GROUP

MTG ROOM

OP GYM

PT GYM

PROSTH.

STORAGE

EQUIP

STORAGE

PATIENT

TOILET

FEMALE

TOILET

MALE

TOILET

MECHANICAL

LOW

VOLTAGE

ELECTRICAL

ELECTRICAL

CORRIDOR

WAITING

WAITING

SOUTH

VESTIBULE

RECEPTION

HAC

SCHEDULING

CLEAN

UTILITY

WC

STOR.

BALANCE

CLINIC

EQUIP

STORAGE

SPEECH

THERAPY

VIST

COORDINATOR

PROVIDER

OFFICE

LPN

REHAB

SUPERVISOR

CONSULTATION

ROOM

PROCEDURE

ROOM

O.T.

CHARTING

O.T.

CLINIC

CORRIDOR

CORRIDOR

ADL

BATHROOM

T-9

T-8

PATIENT

TOILET

SPEECH

THERAPY

ADL

KITCHEN

ADL

BEDROOM

154 SOILED

DN

REF.

FDFD

FD

FD

FD

MALE TOILET

FEMALE

TOILET

SOILED LINEN

CLEAN LINEN

RECYCLING

HALLWAY

CL LINEN

FD

FD

DWREF.

154A

CLOSET

151A

CLOSET

DN

TELECOM

ROOM

1 CU-116-1

116-E300

116-CR-8,10

116-L1-4

116-CR

116-L1-4-47

No DATEREVISION

DRAWING TITLE

CHECKED BY

ST.CLOUD, MN 56303

VA MEDICAL CENTER

BUILDING No

LOCATION

DRAWING NO.DRAWN

DWG. OF

PROJECT TITLE

PLOT SCALE

PROJECT NO.

DATE:

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP

FULLY

SPRINKLERED

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Engineer under the laws of the State of Minnesota.

Name:

Date: 03/30/2022

License Number: MN#

03/30/2022

B

IM

/2

.0

V A

S t C lo u d

E H

R M

I n fr a s tr u c tu re U p g ra d e s /6

-2

.B

.E

R

.r v t

/2

/2

:5

:4

P

M

116-E201

FIRST FLOOR - ELECTRICAL

EHRM INFRASTRUCTURE

UPGRADES

656-21-235

TBD GJL

16305

KEYNOTES:

1. PROVIDE ELECTRICAL CONNECTION TO

CONDENSING UNIT, AS REQUIRED.

COORDINATE FINAL LOCATION AND

CONNECTION REQUIREMENTS WITH

MECHANICAL.

1/8" = 1'-0"

FIRST FLOOR - ELECTRICAL

0 8' 16'4'

N

100% CD 03/30

53095

FOR CONSTRUCTION

No DATEREVISION

DRAWING TITLE

CHECKED BY

ST.CLOUD, MN 56303

VA MEDICAL CENTER

BUILDING No

LOCATION

DRAWING NO.DRAWN

DWG. OF

PROJECT TITLE

PLOT SCALE

PROJECT NO.

DATE:

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP

FULLY

SPRINKLERED

I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Engineer under the laws of the State of Minnesota.

Name:

Date: 03/30/2022

License Number: MN#

03/30/2022

0-GE000

ELECTRICAL COVERSHEET

EHRM INFRASTRUCTURE

UPGRADES

656-21-235

TBD GJL

16305

CAMPUS

100% CD 03/30

by certify that this plan, specification was prepared by me or under my dir vision and that I am a duly Licensed eer under the laws of the State of Min e:

03/30/202205-06-2022

ALEXANDER S. QUAST

53095No DATEREVISION

100% CD 03/30

RECORD DOCUMENTS 06/14

No DATEREVISION

RECORD DOCUMENTS 06/21/24 06/21/2024

-RECORD DOCUMENT-

June 21, 2024 This Record Document has been prepared based on

Designer of Record drawings with Contractor provided markups through the construction phase of the project at the direction of the VA.

While the construction information is believed to be reliable, Architect/Engineer cannot assure its accuracy, and is not responsible for the accuracy of this Record Document. Those relying on this Record

Document are advised to independently verify its accuracy before applying it for any purpose.

eby certify that this plan, specification rt was prepared by me or under my dir ervision and that I am a duly Licensed neer under the laws of the State of Min me:

GB

E

SD

MAILROOM

RECEPTION

UTILITY

TELECOM

ROOM

AC-116-1

116-CR-2,4,6

116-L1-4-49,51,53

No DATEREVISION

DRAWING TITLE

CHECKED BY

ST.CLOUD, MN 56303

VA MEDICAL CENTER

BUILDING No

LOCATION

DRAWING NO.DRAWN

DWG. OF

PROJECT TITLE

PLOT SCALE

PROJECT NO.

DATE:

CONSULTANT ARCHITECT/ENGINEER OF RECORD STAMP

FULLY

SPRINKLERED

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

I hereby certify that this plan, specification or report was prepared by me or under my direct supervision and that I am a duly Licensed Engineer under the laws of the State of Minnesota.

Name:

Date: 03/30/2022

License Number: MN#

03/30/2022

B

IM

/2

.0

V A

S t C lo u d

E H

R M

I n fr a s tr u c tu re U p g ra d e s /6

-2

.B

.E

R

.r v t

/2

/2

:5

:4

P

M

116-E300

ELECTRICAL ENLARGED

PLANS

EHRM INFRASTRUCTURE

UPGRADES

656-21-235

TBD GJL

16305

1/4" = 1'-0"

FIRST FLOOR ENLARGED -

ELECTRICAL - RM 111

KEYNOTES:

1. DISCONNECT AND REMOVE LIGHTS AND

RECEPTACLES IN AREA OF NEW IT ROOM.

MAINTAIN CIRCUIT CONTINUITY TO ADJOINING

SPACES.

2. INDOOR UNIT TO BE POWERED BY OUTDOOR

UNIT. COORDINATE EXACT LOCATION WITH

M.C.

3. CONNECT SMOKE DETECTOR TO NEAREST

EXISTING SLC.

4. COORDINATE FINAL LOCATION OF

RECEPTACLE L21-20R WITH TELECOM

CONTRACTOR. PROVIDE 3/4"C-4#10, 1#12 GND

TO PANEL FOR EACH RECEPTACLE.

5. PROVIDE EATON BLADEUPS, 5KW, 120/208V, 3-

PHASE,4-WIRE RACK MOUNTED UPS FOR

EACH RACK TOWER.

6. PROVIDE APC#AP8861 RPDU RACK PDU 2G

WITH L21-20P CORD. (120/208V, 3-PHASE, 20A,

ZERO U, 5.7 KW, 208V, (36) C13 (6) C19 (2) 5-20R

OUTLETS. PROVIDE TWO PER RACK, MOUNTED

PER MANUFACTURER'S REQUIREMENTS.

SHEET NOTES:

1. REFER TO TECHNOLOGY PLANS FOR IT ROOM

LAYOUT AND RACK LAYOUT/DETAILS.

2. REFER TO SHEET 0-GE400 DETAIL LAYOUT &

ONE-LINE OF RACK.

0 4' 8'2'

N

CIRCUIT KEY NOTES:

*TOTAL DEMAND CALCS SUBTRACT ANY REDUNDANT LOAD AND THE SMALLER OF ANY NONCOINCIDENT HVAC LOADS. THIS CALC IS DONE AT EACH PANEL.

TOTAL ESTIMATED DEMAND AMPS: 19.4 A

TOTAL CONNECTED AMPS: 19.43 A

TOTAL ESTIMATED DEMAND LOAD: 7 kVA

TOTAL CONNECTED LOAD: 7.00 kVA

Power 7 kVA 100.00% 7 kVA

LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND

TOTALS*

LOAD SUMMARY

Total Amps: 23.50 23.50 13.89

Total Load: 2.67 kVA 2.67 kVA 1.67 kVA

41 42

39 40

37 38

35 36

33 34

31 32

29 30

27 28

25 26

23 24

21 22

19 20

17 18

15 16

13 14

11 12

9 1 -- -- -- -- -- -- 10 --

7 1 2 20 A CU-116-1 8

5 1.67 -- -- -- -- -- -- 6 --

3 1.67 -- -- -- -- -- -- 4 --

1 1.67 3 30 A L21-30R 2

K E Y

CKT

NO. LOAD DESCRIPTION

OCPD

AMPS P

WIRE

SIZE

H N G

A B C

WIRE

SIZE

G N H

OCPD

P AMPS LOAD DESCRIPTION

CKT

NO.

K E Y

NOTES:

ISC UNKNOWN 0.00 kA

SCCR: 65 kA

LOCATION: WIRE: 4

FED FROM: 0 A/0P @ GROUND BUS PHASE: 3

ENCLOSURE: NEMA PB 1 SOLID NEUTRAL VOLTS: 120/208 Wye

MOUNTING: SURFACE MAIN: 100 A MCB

EXISTING PANEL 116-CR

CIRCUIT KEY NOTES:

*TOTAL DEMAND CALCS SUBTRACT ANY REDUNDANT LOAD AND THE SMALLER OF ANY NONCOINCIDENT HVAC LOADS. THIS CALC IS DONE AT EACH PANEL.

TOTAL ESTIMATED DEMAND AMPS: 14.4 A

TOTAL CONNECTED AMPS: 14.38 A

TOTAL ESTIMATED DEMAND LOAD: 5.18 kVA

Receptacles 0.18 kVA 100.00% 0.18 kVA TOTAL CONNECTED LOAD: 5.18 kVA

Power 5 kVA 100.00% 5 kVA

LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND

TOTALS*

LOAD SUMMARY

Total Amps: 13.89 13.89 15.39

Total Load: 1.67 kVA 1.67 kVA 1.85 kVA

-- 53 -- -- -- -- -- -- 1.67 -- -- -- -- 1 -- SPACE 54 --

-- 51 -- -- -- -- -- -- 1.67 -- -- -- -- 1 -- SPACE 52 --

49 L21-30R 30 A 3 1.67 -- -- --…