Attachment 7 - As Built Record EHRM_Part I (1).pdf
PDF 9 MB Posted
- Attached to
- 656-26-702 EHRM DDPO 2. 0 Federal contract opportunity
- Solicitation number
- 36C26326B0028
About this file
This document is a set of record architectural and structural drawings for the EHRM (Electronic Health Record Management) Infrastructure Upgrades project at St. Cloud VA Medical Center in St. Cloud, Minnesota. The project, numbered 656-21-235 with AST project number MN 1964, involves comprehensive upgrades to Building 1 across basement, first, second, and attic floor levels.
The scope includes construction of new EHRM-compliant telecom rooms (005F, A05C, A101, and A200), selective demolition and remodeling of existing spaces, installation of electrical and mechanical systems, telecommunications infrastructure upgrades including CAT 6A cabling and communication backbone installations, and modifications to support ongoing medical center operations. Key construction activities encompass infection control risk assessment (ICRA) protocols with designated construction zones (1A, 1B, 1C, 1D) operating on night shifts, installation of fire-rated partitions and smoke barriers, creation of new building additions with EIFS panel exterior systems, and coordination of existing gas supply and electrical equipment protection. The project includes detailed specifications for partition types, door schedules, hazardous material abatement procedures, life safety planning with emergency exits and travel distance limitations, and coordination among architectural, structural, mechanical, electrical, plumbing, and telecommunications engineering disciplines. Design and construction documentation identifies specific room modifications, finishes, equipment requirements, and phasing sequences to maintain building operations throughout the upgrade process.
View the file
Other files for this federal contract opportunity
Show all 13
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
LEGEND
CORRIDOR OUTLINE
VFY EXIST
BUILDING OUTLINE
VFY EXIST
TO 8TH ST WEST ONLYTO 8TH ST EAST & WEST
44TH AVE.
TRAIL 1
TRAIL 2
TRANSFER
SWITCH
CAPACITOR
BANK (3)
SWITCH
(2)
15KV
MAIN
SW
BATT
35 KV
TO
15 KV
TRANSFORMER
35KV
FUSED
SWITCH
METER 35KV
SWITCH
GRAVEL
GRAVEL
GRAVEL
EXISTING
ROAD
CHAIN LINK FENCE
CHAIN LINK FENCE
16' GATE
GRAVEL
ELECTRICAL
SUBSTATION
G E N E R A T O R
FUEL LINES
CONDU ITS TO TU NNEL
M V
D U
C T
B A
N K
1 1 2 W
PHARMACY ADDITION
11 2 E
G E N E R A T O R
B
CORRIDOR LINK
A
C T
TR
A
IL
ER
174 s .f.
256 s .f.
185 s .f.
149 s ..f.
155 s .f.
104 s .f.
70 s. .f .
72 s .f.
110 s .f.
276 s .f.
112 s .f.
99 s .f.
57 s .f.
146 s .f.
434 s .f.
R A
MP
U P
1:
M A X
R A
MP
U P
1:
M A X
RA
M P
UP
1:2 0 M
AX
TRANSFER
SWITCH
CAPACITOR
BANK (3)
SWITCH
(2) 15KV
MAIN
SW
BATT
35 KV
TO
15 KV
TRANSFORMER
35KV
FUSED
SWITCH
METER 35KV
SWITCH
.3
TRANSFORMER
BUILD ING
#91
5,000 GAL.
UNDERGROUND
DIESEL FUEL TANK
EXISTIN G G AS SU P P LY EQ U IP M EN T TO R EM AIN
O P ER ATIO N AL DU R IN G D EM O LITIO N AN D N EW
C O N STR U C TIO N. P R O TEC T EQU IP M EN T AN D
P IP ELIN ES IN AC C O R D AN C E W ITH G AS SU P P LIER 'S
R EC O M M EN D ATIO N S
N EW G AS SU P P LY M AIN
IN TO B U ILD IN G
SP AR E
P H O N E LIN E
EXTEN D S TO
E XISTIN G
P H O N E IN
B O ILER R O O M
P ER P LAN .
SP AR E
P H O N E
LIN E TO
M ETER
TU N N EL
E XTEN D S
A D D ITIO N AL
2'- 0" U N D ER
B U ILD IN G
FUEL LINE
VENT LINE
1,000 GAL.
UNDERGROUND
DIESEL FUEL
TANK
1,000/5,000 GAL.
UNDERGROUND
DIESEL FUEL TANK
1,000 GAL.
UNDERGROUND
DIESEL FUEL TANK
1,000 GAL.
UNDERGROUND
DIESEL FUEL TANK
S 1
LIG H T
N EW G AS SU P P LY
(C O O R D IN ATE W ITH SU P P LIER )
12"D
10"D
"D
TP TP
EXIST. BUILDING
EXIST.
BUS STOP
CC
L O
O P
16"
20"
12"
3"
8"
DN
0.
0’
BIRDCAGE
B
IR
D C
A G
E
NSP ELECTRICAL
FOR HWY DEPT
T101
I.T.
CHILLER
C O
NC
. B
LO
CKS
PAT
I O
C O
NC
. B
LO
CKS
PAT
I O
C O
NC
. B
LO
CKS
PAT
I O
C O
NC
. B
LO
CKS
PAT
I O
C O
NC
. B
LO
CKS
PAT
I O
C O
NC
. B
LO
CKS
PAT
I O
C O
NC
. B
LO
CKS
PAT
I O
C O
NC
. B
LO
CKS
PAT
I O
VESTIBULE
DN
DN
DN
FD
DN
F B
F
B
F B
F
B
F B
F
B
SOUTH
VESTIBULE
PASS
THROUGH
LINK TO
BUILDI NG 51
6 3. 32 56
1 13 5. 35 78
PARKING
NO
PARKING
93 49
37 6
109 5
S M
O K
E B
L D
G
SMOKE
BLDG
SMOKE
BLDG
S M
O K
E B
L D
G
SMOKE
BLDG
M.H.
STOR.
SMOKE
BLDG
SMOKE
BLDG
SMOKE
BLDG
SMOKE
BLDG
SMOKE
BLDG
STOR.
BIO-
HAZ.
SAUK RIVER
GP
HOLDING POND
OWNER AND
CONSULTANTS:
CONTACT:
ADDRESS:
JUSTIN LAPPIN
ST CLOUD VA MEDICAL CENTER
4801 VETERANS DRIVE
ST. CLOUD, MN 56303
NAME:
ADDRESS:
CONTACT:
ADVANCED STRUCTURAL TECHNOLOGIES
7301 OHMS LANE; SUITE 215
EDINA, MN 55439
JOHN LEVAR
PHONE:
NAME:
ADDRESS:
CONTACT:
SPECIALIZED ENGINEERING SOLUTIONS
10360 ELLISON CIRCLE
OMAHA, NE 68134
KRIS BURNHAM
PHONE: 402-991-5520
NAME:
ADDRESS:
CONTACT:
PHONE:
NAME:
ADDRESS:
CONTACT:
PHONE:
NAME:
ADDRESS:
CONTACT:
PHONE:
ANDERSON ENGINEERING OF MN, LLC
13605 1ST AVE NORTH, SUITE 100
PLYMOUTH, MN 55441
LEE KOPPY
763-412-4000
ARCHITECT:
ANDERSON ENGINEERING OF MN, LLC
13605 1ST AVE NORTH, SUITE 100
PLYMOUTH, MN 55441
EDWARD MARKFORT
763-412-4000
952-906-7196
SPECIALIZED ENGINEERING SOLUTIONS
10360 ELLISON CIRCLE
OMAHA, NE 68134
KRIS BURNHAM
402-991-5520
No DATEREVISION
DRAWING TITLE
CHECKED BY
ST.CLOUD, MN 56303
VA MEDICAL CENTER
BUILDING No
LOCATION
DRAWING NO.DRAWN
DWG. OF
PROJECT TITLE
PLOT SCALE
PROJECT NO.
COVER
DATE:
APPROVED: APPROVED: PROJECTS SECTION MANAGER
APPROVED: OIT MANAGER DATE: APPROVED: ASSISTANT CHIEF ENGINEER DATE:
APPROVED: SAFETY MANAGER
APPROVED: CHIEF OF POLICE
APPROVED: PATIENT SAFETY
DATE:
DATE:
DATE: APPROVED: EMS MANAGER
APPROVED: M/O MANAGER
DATE:
DATE:
DATE:DATE:
APPROVED: MEDICAL CENTER DIRECTOR
APPROVED: PROJECT COR DATE:
APPROVED: INFECTION CONTROL NURSE DATE:
APPROVED: SERVICE LINE DIRECTOR
APPROVED: GEMS COORDINATOR DATE:
DATE:
APPROVED: NURSE EXECUTIVE
APPROVED: CHIEF OF STAFF DATE:
APPROVED: DIRECTOR FMS
APPROVED: ASSOCIATE DIRECTOR
DATE:
DATE:
DATE:
DATE:APPROVED: DATE:
APPROVED: DATE:
APPROVED: DATE:
Main Campus, St. Cloud, Minnesota St. Cloud VA Health Care System
N
CONSULTANT ARCHITECT/ENGINEER OF RECORD
FULLY
SPRINKLERED
VICINITY MAP:
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PHONE: 320-255-6346 x7354
CIVIL ENGINEER:
VA PRIMARY COR:
TELECOMMUNICATIONS ENGINEER:
CONTACT:
ADDRESS: ST CLOUD VA MEDICAL CENTER
4801 VETERANS DRIVE
ST. CLOUD, MN 56303
ADDITIONAL CORs:
STRUCTURAL ENGINEER:
MECH/ELEC/PLUMB/FIRE ENGINEER:
RECORD DOCUMENTS
CONTACT: COREY SELF
BRAEDAN HINOJOSA
CONTACT:
-RECORD DOCUMENT-
June 21, 2024
This Record Document has been prepared based on
Designer of Record drawings with Contractor provided markups through the construction phase of the project at the direction of the VA.
While the construction information is believed to be reliable, Architect/Engineer cannot assure its accuracy, and is not responsible for the accuracy of this Record Document. Those relying on this Record
Document are advised to independently verify its accuracy before applying it for any purpose.
C
U s e rs
\P u b li c \D o c u m e n ts \R e v it
P ro je c ts
\1 -1
-R E
M a rk fo rt
.r v t
/2
/2
:4 :0
P
M
1-GI000
BUILDING 1 COVER SHEET &
SHEET INDEX
EHRM INFRASTRUCTURE
UPGRADES
656‐21‐235
03/30/2022
TO, EM PC, EM
16305
BUILDING 1 - EHRM INFRASTRUCTURE UPGRADES
0APPROX 150' 300'75'
PROPOSED ADDITION
SHEET INDEX - BUILDING 1 - SET 1 OF 2
SHEET NO. SHEET TITLE
1-GI000 BUILDING 1 COVER SHEET & SHEET INDEX
1-GI101 BASEMENT FLOOR - INFECTION CONTROL & PHASING PLAN
1-GI111 FIRST FLOOR - INFECTION CONTROL & PHASING PLAN
1-GI120 SECOND FLOOR LIFE SAFETY PLAN
1-GI121 SECOND FLOOR - INFECTION CONTROL & PHASING PLAN
1-AS100 BASEMENT FLOOR - OVERALL PLAN
1-AS110 FIRST FLOOR - OVERALL PLAN
1-AS120 SECOND FLOOR - OVERALL PLAN
1-AS130 ATTIC FLOOR - OVERALL PLAN
1-AS400 LARGE SCALE PLANS
1-AS430 BUILDING ADDITION AND ROOF PLAN
1-AS600 ELEVATIONS, DETAILS, SCHEDULES
1-AS601 INTERIOR PARTITION TYPES AND DETAILS
1-AS602 SECTION DETAILS
1-S120 SECOND FLOOR PLAN - OVERALL
1-S130 ATTIC FLOOR PLAN - OVERALL
1-S400 LARGE SCALE PLANS
01-E100 BASEMENT DEMOLITION - ELECTRICAL
01-E102 SECOND FLOOR DEMOLITION - ELECTRICAL
01-E200 BASEMENT - ELECTRICAL
01-E201 FIRST FLOOR - ELECTRICAL
01-E202 SECOND FLOOR - ELECTRICAL
01-E204 ROOF - ELECTRICAL
01-E300 ELECTRICAL ENLARGED PLANS
01-E301 ELECTRICAL ENLARGED PLANS
01-E400 ELECTRICAL ONE-LINE DIAGRAMS
01-E500 ELECTRICAL SCHEDULES
01-E501 ELECTRICAL SCHEDULES
01-M100 BASEMENT DEMOLITION - MECHANICAL
01-M101 FIRST FLOOR DEMOLITION - MECHANICAL
01-M102 SECOND FLOOR DEMOLITION - MECHANICAL
01-M200 BASEMENT REMODEL - MECHANICAL
01-M201 FIRST FLOOR REMODEL - MECHANICAL
01-M202 SECOND FLOOR REMODEL - MECHANICAL
01-M204 ROOF REMODEL - MECHANICAL
SEE GENERAL AND SET 2 SHEETS FOR ADDITIONAL INFORMATION
SHEET INDEX - BUILDING 1 - SET 2 OF 2
SHEET NO. SHEET TITLE
1-TD100 BASEMENT FLOOR PLAN - TELECOM - DEMOLITION
1-TD110 FIRST FLOOR PLAN - TELECOM - DEMOLITION
1-TD120 SECOND FLOOR PLAN - TELECOM - DEMOLITION
1-TD130 THIRD FLOOR PLAN - TELECOM - DEMOLITION
1-TN100 BASEMENT FLOOR PLAN - TELECOMMUNICATIONS
1-TN110 FIRST FLOOR PLAN - TELECOMMUNICATIONS
1-TN120 SECOND FLOOR PLAN - TELECOMMUNICATIONS
1-TN130 THIRD FLOOR PLAN - TELECOMMUNICATIONS
1-TN200 BASEMENT FLOOR PLAN - TELECOM - CABLE DISTANCE
1-TN210 FIRST FLOOR PLAN - TELECOM - CABLE DISTANCE
1-TN220 SECOND FLOOR PLAN - TELECOM - CABLE DISTANCE
1-TN230 THIRD FLOOR PLAN - TELECOM - CABLE DISTANCE
1-TN300 ENLARGED PLANS - TELECOMMUNICATIONS - DEMO
1-TN400 ENLARGED PLANS - TELECOMMUNICATIONS
1-TN401 ENLARGED PLANS - TELECOMMUNICATIONS
1-TN402 ENLARGED PLANS - TELECOMMUNICATIONS
1-TN403 ENLARGED PLANS - TELECOMMUNICATIONS
SEE GENERAL AND SET 1 SHEETS FOR ADDITIONAL INFORMATION
RECORD DOCUMENTS 06/21/24
52.1183
36.0000
AEC
CB1
DACC
GAC
LCC
CR
4D
BATH 4C
LOCKER
MALE
C0C
CORRIDOR
PHONE
LOBBY
HAC
HEALTH
OCC.
HAC
LOCKER
4A
LOCKER
FEMALE
4B
BATH
STOR
STAIR
12A
ELECTRICAL
MECHANICAL
MECHANICAL
ELECTRICAL
C0N
CORR
18A
MECHANICAL
19A
MECH
ELEV
MECAHNICAL
HEATER
EXAM ROOM
RADIOLOGY
SOUND
ULTRA
EXAM
32A
BATH
STAIR
OFFICE
X-RAY 1
UNEXCAVATED35
MECH
PROCESSING
FILM
37A
EQUIP
X-RAY 2
WAITING
CHANGE 38A
BATH
CLOSET
33A
EQUIP
OFFICE29
STOR
C0W
CORR
30A
MECH
STAIR
OFFICE
5A
OFFICE
PHYSICIAN
5C
CORR
5B
MECH
OFFICE
5D
ROOM
MECH
C0-B2
CORR
A01
HAC
A02
EQUIP
ELEV
C0-B1
CORR
A06
ELECTRICAL
A05A
MECHANICAL
A05B
STORAGE
ASB
STAIR
C0-B4
CORR
C0-B3
CORR
A10
SPACE
MECH.
E-A1
ELEV
A03
PHONE
36D
CONTROL
36E
EQUIP
36C
CT SCAN
CORRIDOR
36B
TOILET
36A
CHANGE
IMAGING
RT CLINIC
ABG LAB/
PFT LAB
HAC
LAB CLASSROOM
APAP/CPAP
EKG LAB
EDUCATION
RT CLINIC/
SOILED
CP
WORKROOM
STAFF
STORAGE
PROSTHETICS
OFFICE
LINEN
CLEAN
A60
OFFICE
A61
OFFICE
A62
OFFICE
A59
STORAGE
SUPPLY
A63
HEMA/COAG
CHEM/URINE/
A67
LOUNGE
CONF./
A68
BANK
BLOOD
A64
MICROBIOLOGY
A56
RECEP.
A58A
PHLEB
A58B
PHLEB
A58C
PHLEB
A58H
PHLEB
A58I
PHLEB
A58J
PHLEB
A58G
PHLEB
A58D
PHLEB
A58K
PHLEB
A58F
PHLEB
A58E
PHLEB
A57A
TOILET
A57B
TOILET
A57C
TOILET
A57C
COLLECTION
A66
LOCKER
A65
TOILET
C0-B1
WAITING
C0-H1
CORR
C0-H5
CORR
C0-C2
CORR C0-H2
CORR
C0-H4
CORR
C0-H3
CORR
A58
PHLEB
A58
PHLEB
C0-H6
CORR
C0-H7
CORR
2C
RECEPTION
WAITING
2A
MEN 2B
WOMEN
53A
STOR
E-01
ELEV
E-02
ELEV
16A
ROOM
MG
10B
HEALTH
OCC.
10A
HEALTH
OCC.
HEALTH
OCC.
30B
OFFICE
30C
OFFICE
8D
EQUIP
8I
MECHANICAL
8A
MRI
7F
INTAKE
7E
INTAKE
7D
HAC
7C
TOILET
7B
CHANGING
7A
CHANGING
COE
CORRIDOR
7G
FOYER
8H
VESTIBULE
8B
CONTROL
8C
HALL
8E
LINEN
8F
SOIL
8G
CLEAN
L
R
A05C
TELECOM
ROOM
005F
TELECOM
ROOM
8'-11 3/4"
005E
LOCKER
ZONE 1B
CONSTRUCTION / ICRA BARRIER
ZONE 1A
CONSTRUCTION / ICRA BARRIER
LIMITS OF CONSTRUCTION
RELOCATED FURNITURE
EXIST FURNITURE TO BE MOVED
EXIST FURNITURE TO BE MOVED
RELOCATED FURNITURE
DOOR FOR OWNER &
CONSTRUCTION USE
DOORS FOR OWNER USE
DOOR FOR CONSTRUCTION USE
INFECTION CONTROL RISK ASSESSMENT (ICRA) LEGEND
LIMITS OF CONSTRUCTION
1 HOUR FIRE RATED ICRA / CONSTRUCTION BARRIER
LOCATION, AND DOOR, WHERE SHOWN
TEMPORARY NON-RATED (PLASTIC SHEETING) CONSTRUCTION BARRIER
LOCATION, WHERE APPROVED BY THE VA FOR USE IN RISK TYPE B.
UPGRADE TO 1 HOUR RATED PARTITION WHEN DIRECTED BY THE VA
No DATEREVISION
DRAWING TITLE
CHECKED BY
ST.CLOUD, MN 56303
VA MEDICAL CENTER
BUILDING No
LOCATION
DRAWING NO.DRAWN
DWG. OF
PROJECT TITLE
PLOT SCALE
PROJECT NO.
DATE:
CONSULTANT ARCHITECT/ENGINEER OF RECORD
FULLY
SPRINKLERED
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
RECORD DOCUMENTS
-RECORD DOCUMENT-
June 21, 2024
This Record Document has been prepared based on
Designer of Record drawings with Contractor provided markups through the construction phase of the project at the direction of the VA.
While the construction information is believed to be reliable, Architect/Engineer cannot assure its accuracy, and is not responsible for the accuracy of this Record Document. Those relying on this Record
Document are advised to independently verify its accuracy before applying it for any purpose.
C
U s e rs
\P u b li c \D o c u m e n ts \R e v it
P ro je c ts
\1 -1
-R E
M a rk fo rt
.r v t
/1
/2
:0 :3
P
M
1-GI101
BASEMENT FLOOR -
INFECTION CONTROL &
PHASING PLAN
EHRM INFRASTRUCTURE
UPGRADES
656‐21‐235
03/30/2022
EM BMW
16305
1/8" = 1'-0"
BASEMENT FLOOR - CONST BARRIER PLAN
ROOM ICRA SCHEDULE
LEVEL
ROOM
NO. ROOM NAME CAI BLDG NAME / FUNCTION CONSTRUCTION PROJECT ACTIVITY INFECTION CONTROL RISK GROUP CONTROL PROCEDURE CLASS
BASEMENT 005C CORRIDOR AMB CARE / MEDICAL TYPE D GROUP 1 CLASS III/IV
BASEMENT 005D MECH AMB CARE / MEDICAL TYPE D GROUP 1 CLASS III/IV
BASEMENT 005E LOCKER AMB CARE / MEDICAL TYPE D GROUP 1 CLASS III/IV
BASEMENT 005F TELECOM ROOM AMB CARE / MEDICAL TYPE D GROUP 1 CLASS III/IV
BASEMENT A003 EXIST RM AMB CARE / MEDICAL TYPE B GROUP 2 CLASS II
BASEMENT A05A MECH AMB CARE / MEDICAL TYPE C GROUP 2 CLASS III
BASEMENT A05C TELECOM ROOM AMB CARE / MEDICAL TYPE C GROUP 1 CLASS II
FIRST FLOOR 127 EXIST RM AMB CARE / MEDICAL TYPE B GROUP 2 CLASS II
FIRST FLOOR A101 TELECOM ROOM AMB CARE / MEDICAL TYPE C GROUP 2 CLASS III
SECOND FLOOR 229 EXIST RM AMB CARE / MEDICAL TYPE B GROUP 2 CLASS II
SECOND FLOOR A200 TELECOM ROOM AMB CARE / MEDICAL TYPE D GROUP 2 CLASS IV
SECOND FLOOR A216 EXIST RM AMB CARE / MEDICAL TYPE B GROUP 2 CLASS II
SECOND FLOOR A225 EXIST RM AMB CARE / MEDICAL TYPE B GROUP 4 CLASS III/IV
SEE GENERAL NOTES SHEET FOR CONSTRUCTION INFECTION CONTROL RISK ASSESSMENT (ICRA) DESCRIPTIONS. TYPE, GROUP AND CLASS SELECTED TO BEST OF DESIGN TEAM'S KNOWLEDGE.
FINAL DETERMINATION BY THE VA WILL BE MADE AT A LATER DATE.
SEQUENCE OF EVENTS - ZONE 1A
• SELECTIVE UPGRADE TO EXISTING INFORMATION TECHNOLOGY TO ENABLE
BUILDING TOTAL UPGRADE PROCESS
• INITIAL ICRA AND ILSM
• CONSTRUCTION OF BARRIER IN ONE NIGHT SHIFT. BARRIER INCLUDES DOOR
AND PARTITION TO BECOME PERMANENT CONSTRUCTION OF ROOM
• CONSTRUCT ROOMS AS DIRECTED, SEE ASSOCIATED DRAWINGS FROM
STRUCTURAL, ELECTRICAL, MECHANICAL, TELECOM, AND FINISHES
• INSTALL TEMPORARY PROTECTION AND CONDUCT SELECTIVE DEMOLITION TO
ENABLE UPGRADES
• INSTALL COMMON CABLE INFRASTRUCTURE
• CONSTRUCT COMMUNICATION BACKBONE
• INSTALL CAT 6A
• DECOMMISSION EXISTING NON-EHRM INFORMATION TECHNOLOGY ROOMS
SEQUENCE OF EVENTS - ZONE 1B
• SELECTIVE UPGRADE TO EXISTING INFORMATION TECHNOLOGY TO ENABLE
BUILDING TOTAL UPGRADE PROCESS
• INITIAL ICRA AND ILSM
• CONSTRUCTION OF BARRIER IN ONE NIGHT SHIFT AT ENTRY TO CORRIDOR
AND NEXT TO MECH 5B
• DEMOLISH
• CONSTRUCT ROOMS AS DIRECTED, SEE ASSOCIATED DRAWINGS FROM
STRUCTURAL, ELECTRICAL, MECHANICAL, TELECOM, AND FINISHES
• INSTALL TEMPORARY PROTECTION AND CONDUCT SELECTIVE DEMOLITION TO
ENABLE UPGRADES
• INSTALL COMMON CABLE INFRASTRUCTURE
• CONSTRUCT COMMUNICATION BACKBONE
• INSTALL CAT 6A
• DECOMMISSION EXISTING NON-EHRM INFORMATION TECHNOLOGY ROOMS
SUGGESTED SEQUENCE. FINAL INSTALLATION SEQUENCE TO BE MADE AT A LATER DATE.
SUGGESTED SEQUENCE. FINAL INSTALLATION SEQUENCE TO BE MADE AT A LATER DATE.
FRIDGE
24X26
SCALE
COPIER
PRINTER
F R
O N
T
ENTRY
128A
RECEPTION
STAIR120
WAITING
STAIR
MAA
REGISTRATION
REGISTRATION168
EXAM
EXAM
STOR
WHCHR
LOBBY
ELEV
C1NC
CORR
127A
PHONE
MECH
128B
V.I.C.
128C
OUT
CHECK
STOR
C1WI
CORR
EXAM
EXAM
EXAM
EXAM
STATION
NURSE
173A
MED
EXAM
EXAM165
NURSING
EXAM
EXAM
NURSING
160B
BATH
INTAKE
PROCEDURE
SPECIAL
160A
UTILITY
CLEAN
173B
INTAKE
C1WH
CORR
C1WG
CORR
ELEC
MECH
EXAM
INT
C1WF
CORR
EXAM
INT
EXAM
INT
EXAM
INT
EXAM
INT
EXAM
INT
STAIR
C1WJ
CORR
COPY
CONSULT
PHARM.
STAIR
C1WA
CORR
MALE
FEMALE
CHASE
WAITING
BATH
UTILITY
CLEAN
EXAM
EXAM
CONSULT
PHARM.
C1WD
CORR
EXAM
EXAM
UTILITY
CLEAN
CHART
NURSE/
OFFICE
NURSE
EXAM
EXAM
C1WB
CORR
EXAM
EXAM
EXAM
NURSING
EXAM
WAITING
152A
MED
C1WE
CORR
C1WC
CORR
ROOF
A111
VEST
TRIAGE
A110
OFFICE A109
EXAM
E-A1
ELEV
A-1
STAIR A108
STAFF
A107A
DICTATION
A107B
CLOSET
C0-2
CORR
A106
HAC A105
CONSULT
PHARM
A104
NURSING
A103
NURSING
C0-1
CORRIDOR
A127A
CHECK-OUT
A126
INTAKE
A125
EXAM
CO-5
CORR
A124
EXAM
A123
EXAM
A122
EXAM
A121
OFFICE
A120
UTIL
SOILED
A118
ALCOVE
NURSE
A117
MED
CO-3
CORRIDOR
A112
EXAM
A113
EXAM
A116
UTILITY
SOILED
A119
EXAM
C0-4
CORRIDOR
A114
EXAM
A115
EXAM
AS1
STAIR
A141
STORAGE
EQUIP.
A140
EXAM
A139
EXAM
A138
EXAM
A137
DICTATION
A136
EXAM
A135
EXAM
A134
OUT
CHECK
A133
PASSAGE
STAFF A132
STORAGE
CO-7
CORRIDOR
A142
STORAGE
CLEAN
A143
EXAM
A144
EXAM
A145
EXAM CO-3
CORR
A146
EXAM
A147
STORAGE
A127D
ROOM
MED A127C
STATION
NURSE
A127B
IN
CHECKCO-6
CORR
A131
MEN A130
CHASE
A129
WAITING
A128
WAITING
A102B
CHASE
A102A
WOMEN
A101
COMM
TELE-
A112A
LINEN
REGISTRATION
INTAKE
INTAKE
STAFF
111A
M.O.D.
111C
EQUIPMENT
SUPPLY
111D
PURPOSE
MULTI
111B
TOILET
WAITING
101A
TOILET
UNISEX
HAC
UTILITIES
CLEAN
UTILITIES
SOILED
LOCKERS
MED
STATION
NURSE
108A
TELEMETRY
108B
TELEMETRY
108C
TOILET
108D
TELEMETRY
108E
TELEMETRY
109C
TELEMETRY
PROCEDURE/
109B
TELEMETRY
109A
TELEMETRY
109D
TOILET
AMBULANCE
C1EC
CORRIDOR
C1EA
CORRIDOR
NOUR
C1ED
CORRIDOR
111E
CAMERAS
HOLDING/
111F
ANTE
HOLDING/
TOILET
C1EB
CORRIDOR
TOILET
STAFF
E-01
ELEV
E-02
ELEV
A117A
UNISEX
ROOF
FLAT
DECONTAM
ZONE 1D
INFECTION CONTROL RISK ASSESSMENT (ICRA) LEGEND
LIMITS OF CONSTRUCTION
1 HOUR FIRE RATED ICRA / CONSTRUCTION BARRIER
LOCATION, AND DOOR, WHERE SHOWN
TEMPORARY NON-RATED (PLASTIC SHEETING) CONSTRUCTION BARRIER
LOCATION, WHERE APPROVED BY THE VA FOR USE IN RISK TYPE B.
UPGRADE TO 1 HOUR RATED PARTITION WHEN DIRECTED BY THE VA
No DATEREVISION
DRAWING TITLE
CHECKED BY
ST.CLOUD, MN 56303
VA MEDICAL CENTER
BUILDING No
LOCATION
DRAWING NO.DRAWN
DWG. OF
PROJECT TITLE
PLOT SCALE
PROJECT NO.
DATE:
CONSULTANT ARCHITECT/ENGINEER OF RECORD
FULLY
SPRINKLERED
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
RECORD DOCUMENTS
-RECORD DOCUMENT-
June 21, 2024
This Record Document has been prepared based on
Designer of Record drawings with Contractor provided markups through the construction phase of the project at the direction of the VA.
While the construction information is believed to be reliable, Architect/Engineer cannot assure its accuracy, and is not responsible for the accuracy of this Record Document. Those relying on this Record
Document are advised to independently verify its accuracy before applying it for any purpose.
C
U s e rs
\P u b li c \D o c u m e n ts \R e v it
P ro je c ts
\1 -1
-R E
M a rk fo rt
.r v t
/1
/2
:0 :3
P
M
1-GI111
FIRST FLOOR - INFECTION
CONTROL & PHASING PLAN
EHRM INFRASTRUCTURE
UPGRADES
656‐21‐235
03/30/2022
EM BMW
16305
1/8" = 1'-0"
FIRST FLOOR - CONST BARRIER PLAN
ROOM ICRA SCHEDULE
LEVEL
ROOM
NO. ROOM NAME CAI BLDG NAME / FUNCTION CONSTRUCTION PROJECT ACTIVITY INFECTION CONTROL RISK GROUP CONTROL PROCEDURE CLASS
BASEMENT 005C CORRIDOR AMB CARE / MEDICAL TYPE D GROUP 1 CLASS III/IV
BASEMENT 005D MECH AMB CARE / MEDICAL TYPE D GROUP 1 CLASS III/IV
BASEMENT 005E LOCKER AMB CARE / MEDICAL TYPE D GROUP 1 CLASS III/IV
BASEMENT 005F TELECOM ROOM AMB CARE / MEDICAL TYPE D GROUP 1 CLASS III/IV
BASEMENT A003 EXIST RM AMB CARE / MEDICAL TYPE B GROUP 2 CLASS II
BASEMENT A05A MECH AMB CARE / MEDICAL TYPE C GROUP 2 CLASS III
BASEMENT A05C TELECOM ROOM AMB CARE / MEDICAL TYPE C GROUP 1 CLASS II
FIRST FLOOR 127 EXIST RM AMB CARE / MEDICAL TYPE B GROUP 2 CLASS II
FIRST FLOOR A101 TELECOM ROOM AMB CARE / MEDICAL TYPE C GROUP 2 CLASS III
SECOND FLOOR 229 EXIST RM AMB CARE / MEDICAL TYPE B GROUP 2 CLASS II
SECOND FLOOR A200 TELECOM ROOM AMB CARE / MEDICAL TYPE D GROUP 2 CLASS IV
SECOND FLOOR A216 EXIST RM AMB CARE / MEDICAL TYPE B GROUP 2 CLASS II
SECOND FLOOR A225 EXIST RM AMB CARE / MEDICAL TYPE B GROUP 4 CLASS III/IV
SEE GENERAL NOTES SHEET FOR CONSTRUCTION INFECTION CONTROL RISK ASSESSMENT (ICRA) DESCRIPTIONS. TYPE, GROUP AND CLASS SELECTED TO BEST OF DESIGN TEAM'S KNOWLEDGE.
FINAL DETERMINATION BY THE VA WILL BE MADE AT A LATER DATE.
A -O
-V
DN
UP
DN
UP
A200
TELECOM
ROOM
6' -1
/4
16'-0"
9'-8" 7'
-6
E A
HE
TO EXIT ACCESS
FE
127' - 9"
E A
HE
LIFE SAFETY SYMBOLS
SMOKE TIGHT
ASSEMBLY
1 HOUR FIRE
BARRIER
2 HOUR FIRE
BARRIER
3 HOUR FIRE
BARRIER
1 HOUR FIRE &
SMOKE BARRIER
2 HOUR FIRE &
SMOKE BARRIER
3 HOUR FIRE &
SMOKE BARRIER
HE
TRAVEL DISTANCE
100'-10"
TRAVEL DISTANCE
EA
EDEXIT EXIT
HORIZONTAL EXIT
EXIT DISCHARGE
EXIT ACCESS
FIRE
EXTINGUISHER
FE
FIRE
EXTINGUISHER
CABINET
FEC
LIMITS OF
CONSTRUCTION
SMOKE
COMPARTMENT
BOUNDARY
HEALTH CARE
SUITE
NOTE: NOT ALL SYMBOLS MY BE USED ON EACH PLAN
OCCUPANCY
SEPARATION
SHAFT
ADJACENT SYMBOLS SHOW PARTITION RATING AND
DAMPER REQUIREMENTS
HAZARDOUS USE
ADJACENT SYMBOLS SHOW PARTITION RATING.
OPENINGS REQUIRE CLOSER & LATCH
EXIT PASSAGEWAY
RATE AS STAIR
ALL OPENINGS TO BE RATED AS STAIR SHAFT
CORRIDOR
WALLS TO LIMIT THE TRANSFER OF SMOKE
ADJUNCT CORRIDOR or PSYCHIATRIC AREA or CONSTRUCTED WITH MIN. 4'-0" CLEAR
WITH (PER CHAPTER 19)
AREA SEPARATIONS / FIRE WALLS
TYPE(S) OF CONSTRUCTION
CONSTRUCTION TYPE(S)
SEE LIFE SAFETY PLANS
(IBC CHAPTER 6) IBC II-A
No DATEREVISION
DRAWING TITLE
CHECKED BY
ST.CLOUD, MN 56303
VA MEDICAL CENTER
BUILDING No
LOCATION
DRAWING NO.DRAWN
DWG. OF
PROJECT TITLE
PLOT SCALE
PROJECT NO.
DATE:
CONSULTANT ARCHITECT/ENGINEER OF RECORD
FULLY
SPRINKLERED
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
RECORD DOCUMENTS
-RECORD DOCUMENT-
June 21, 2024
This Record Document has been prepared based on
Designer of Record drawings with Contractor provided markups through the construction phase of the project at the direction of the VA.
While the construction information is believed to be reliable, Architect/Engineer cannot assure its accuracy, and is not responsible for the accuracy of this Record Document. Those relying on this Record
Document are advised to independently verify its accuracy before applying it for any purpose.
C
U s e rs
\P u b li c \D o c u m e n ts \R e v it
P ro je c ts
\1 -1
-R E
M a rk fo rt
.r v t
/1
/2
:0 :4
P
M
1-GI120
SECOND FLOOR LIFE SAFETY
PLAN
EHRM INFRASTRUCTURE
UPGRADES
656‐21‐235
03/30/2022
EM BMW
16305
1/8" = 1'-0"
SECOND FLOOR LIFE SAFETY PLAN
N
0 8' 16'4'
VAO
VAO
VAO
VAO
OAV
O A V
O AV
OAV
O AV
O A V
O A V
OAV
DICT.
A -O
-V
STAIR
210A
CORRIDOR
C2EA
STAIR
EXAM
CORRIDOR
C2C
UTILITY
229A
PHONE
ELEVATOR
LOBBY
CORRIDOR
C2N
CORRIDOR
INTAKE
230A
INTAKE
230B
TOILET
230C
EXAM
CORRIDOR
C2W
CORRIDOR
C2CA
SCOPE
STORAGE
STAFF
LOCKER
NURSE
STATION
237A
RECOVERY
WHEELCHAIR
TOILET
MEDS
PATIENT
INSTR
TOILET
235A
PROCTO
PROCEDURE
HOLDING
SOILED
UTILITY
ENDOSCOPY
PROCEDURE
SOILED
LINEN
ENDOSCOPY
PROCEDURE
STORAGE
CORRIDOR
C2WC
CORRIDOR
C2WB
TOILET
UROLOGY
PROCEDURE
TEST/
TOILET
UROLOGY
PROCEDURE
CORRIDOR
C2WA
STAIR
MINOR
PROCEDURE
MINOR
PROCEDURE
HAC
243A
STAIR
243B
CALL
CENTER
NURSING
SKIN
INTEGRITY
210F
EXAM
210E
EXAM
210C
EXAM
210B
EXAM
210A
WAITING
LINEN
210D
CORRIDOR
C2EC
CORRIDOR
C2ED
CORRIDOR
C2EB
EXAM
215D
EXAM
215C
EXAM
215B
EXAM
215A
STORAGE
HAC
PAC
TEL-MED
INTAKE
STAFF
STAFF
LOCKERS
221A
CLEAN
SOILED
BCG
MANAGER
OFFICE
STOR.
WAITING
STAFF
221WAITING
202RECEPTION
PATIENT
TOILET
STAFF
TOILET
ANESTHESIA
OFFICE
A233
ANESTHESIA
WORKROOM
A232
EQUIPMENT
ROOM
A231
SOILED
A230
LOUNGE
A229
CORRIDOR
C2-A7
HALL
C2-A6
HALL
C2-A5
O.R.
A223 O.R.
A222 O.R.
A219
RECOVERY
A213A
CLEAN
A225
HALL
C2-A8
CORRIDOR
C2-A9
SUB
STERILE
A224
CLEAN
CORE
A218
SUB
STERILE
A220
STORAGE
A221
HALL
C2-A4
HALL
C2-A2
HAC
A226
HALL
C2-A11
RAMP
C2-A12
ELECT.
A216
ELEV.
LOBBY
C2-A12
STERILE
SUPPLIES
A217
RECOVERY
A214
RECOVERY
A213B
RECOVERY
A213C
RECOVERY
ISOLATION
A215
HAC
A203
INTAKE
A204
INTAKE
A205
INTAKE
A208
INTAKE
A207
NURSE
A210
HALL
C2-A3
SCHEDULING
A201
HEAD
NURSE
A202
WOMEN'S
LOCKER
A227
SOILED
A212
CLEAN
A211
STAFF
TOILET
A209
PATIENT
TOILET
A206
MEDS
A210A
NOUR
A210B
RAMP
C2-A1
SURGERY
RECEPTION
225A
SURGERY
WAITING
CONSULT
STAIRS
A234
DN
UP
DN
UP
A200
TELECOM
ROOM
ALIGN
(60" MIN CLR)
+/- 5' -3"
LIMITS OF CONSTRUCTION
ZONE 1C
CONSTRUCTION / ICRA BARRIER
INFECTION CONTROL RISK ASSESSMENT (ICRA) LEGEND
LIMITS OF CONSTRUCTION
1 HOUR FIRE RATED ICRA / CONSTRUCTION BARRIER
LOCATION, AND DOOR, WHERE SHOWN
TEMPORARY NON-RATED (PLASTIC SHEETING) CONSTRUCTION BARRIER
LOCATION, WHERE APPROVED BY THE VA FOR USE IN RISK TYPE B.
UPGRADE TO 1 HOUR RATED PARTITION WHEN DIRECTED BY THE VA
No DATEREVISION
DRAWING TITLE
CHECKED BY
ST.CLOUD, MN 56303
VA MEDICAL CENTER
BUILDING No
LOCATION
DRAWING NO.DRAWN
DWG. OF
PROJECT TITLE
PLOT SCALE
PROJECT NO.
DATE:
CONSULTANT ARCHITECT/ENGINEER OF RECORD
FULLY
SPRINKLERED
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
RECORD DOCUMENTS
-RECORD DOCUMENT-
June 21, 2024
This Record Document has been prepared based on
Designer of Record drawings with Contractor provided markups through the construction phase of the project at the direction of the VA.
While the construction information is believed to be reliable, Architect/Engineer cannot assure its accuracy, and is not responsible for the accuracy of this Record Document. Those relying on this Record
Document are advised to independently verify its accuracy before applying it for any purpose.
C
U s e rs
\P u b li c \D o c u m e n ts \R e v it
P ro je c ts
\1 -1
-R E
M a rk fo rt
.r v t
/1
/2
:0 :4
P
M
1-GI121
SECOND FLOOR - INFECTION
CONTROL & PHASING PLAN
EHRM INFRASTRUCTURE
UPGRADES
656‐21‐235
03/30/2022
EM BMW
16305
1/8" = 1'-0"
SECOND FLOOR - CONST BARRIER PLAN
ROOM ICRA SCHEDULE
LEVEL
ROOM
NO. ROOM NAME CAI BLDG NAME / FUNCTION CONSTRUCTION PROJECT ACTIVITY INFECTION CONTROL RISK GROUP CONTROL PROCEDURE CLASS
BASEMENT 005C CORRIDOR AMB CARE / MEDICAL TYPE D GROUP 1 CLASS III/IV
BASEMENT 005D MECH AMB CARE / MEDICAL TYPE D GROUP 1 CLASS III/IV
BASEMENT 005E LOCKER AMB CARE / MEDICAL TYPE D GROUP 1 CLASS III/IV
BASEMENT 005F TELECOM ROOM AMB CARE / MEDICAL TYPE D GROUP 1 CLASS III/IV
BASEMENT A003 EXIST RM AMB CARE / MEDICAL TYPE B GROUP 2 CLASS II
BASEMENT A05A MECH AMB CARE / MEDICAL TYPE C GROUP 2 CLASS III
BASEMENT A05C TELECOM ROOM AMB CARE / MEDICAL TYPE C GROUP 1 CLASS II
FIRST FLOOR 127 EXIST RM AMB CARE / MEDICAL TYPE B GROUP 2 CLASS II
FIRST FLOOR A101 TELECOM ROOM AMB CARE / MEDICAL TYPE C GROUP 2 CLASS III
SECOND FLOOR 229 EXIST RM AMB CARE / MEDICAL TYPE B GROUP 2 CLASS II
SECOND FLOOR A200 TELECOM ROOM AMB CARE / MEDICAL TYPE D GROUP 2 CLASS IV
SECOND FLOOR A216 EXIST RM AMB CARE / MEDICAL TYPE B GROUP 2 CLASS II
SECOND FLOOR A225 EXIST RM AMB CARE / MEDICAL TYPE B GROUP 4 CLASS III/IV
SEE GENERAL NOTES SHEET FOR CONSTRUCTION INFECTION CONTROL RISK ASSESSMENT (ICRA) DESCRIPTIONS. TYPE, GROUP AND CLASS SELECTED TO BEST OF DESIGN TEAM'S KNOWLEDGE.
FINAL DETERMINATION BY THE VA WILL BE MADE AT A LATER DATE.
SEQUENCE OF EVENTS - ZONE 1C
• SELECTIVE UPGRADE TO EXISTING INFORMATION TECHNOLOGY TO ENABLE
BUILDING TOTAL UPGRADE PROCESS
• INITIAL ICRA AND ILSM
• CONSTRUCTION OF BARRIER IN ONE NIGHT SHIFT. BARRIER INCLUDES DOOR
AND PARTITION TO BECOME PERMANENT CONSTRUCTION OF ROOM
• CONSTRUCT ROOMS AS DIRECTED, SEE ASSOCIATED DRAWINGS FROM
STRUCTURAL, ELECTRICAL, MECHANICAL, TELECOM, AND FINISHES
• INSTALL TEMPORARY PROTECTION AND CONDUCT SELECTIVE DEMOLITION TO
ENABLE UPGRADES
• INSTALL COMMON CABLE INFRASTRUCTURE
• CONSTRUCT COMMUNICATION BACKBONE
• INSTALL CAT 6A
• DECOMMISSION EXISTING NON-EHRM INFORMATION TECHNOLOGY ROOMS
SUGGESTED SEQUENCE. FINAL INSTALLATION SEQUENCE TO BE MADE AT A LATER DATE.
36.0000
AEC
CB1
DACC
GAC
LCC
CR
4D
BATH 4C
LOCKER
MALE
C0C
CORRIDOR
PHONE
LOBBY
HAC
HEALTH
OCC.
HAC
LOCKER
4A
LOCKER
FEMALE
4B
BATH
STOR
STAIR
12A
ELECTRICAL
MECHANICAL
MECHANICAL
ELECTRICAL
C0N
CORR
18A
MECHANICAL
19A
MECH
ELEV
MECAHNICAL
HEATER
EXAM ROOM
RADIOLOGY
SOUND
ULTRA
EXAM
32A
BATH
STAIR
OFFICE
X-RAY 1
UNEXCAVATED35
MECH
PROCESSING
FILM
37A
EQUIP
X-RAY 2
WAITING
CHANGE 38A
BATH
CLOSET
33A
EQUIP
OFFICE29
STOR
C0W
CORR
30A
MECH
STAIR
OFFICE
5A
OFFICE
PHYSICIAN
5C
CORR
5B
MECH
OFFICE
5D
ROOM
MECH
C0-B2
CORR
A01
HAC
A02
EQUIP
ELEV
C0-B1
CORR
A06
ELECTRICAL
A05A
MECHANICAL
A05B
STORAGE
ASB
STAIR
C0-B4
CORR
C0-B3
CORR
A10
SPACE
MECH.
E-A1
ELEV
A03
PHONE
36D
CONTROL
36E
EQUIP
36C
CT SCAN
CORRIDOR
36B
TOILET
36A
CHANGE
IMAGING
RT CLINIC
ABG LAB/
PFT LAB
HAC
LAB CLASSROOM
APAP/CPAP
EKG LAB
EDUCATION
RT CLINIC/
SOILED
CP
WORKROOM
STAFF
STORAGE
PROSTHETICS
OFFICE
LINEN
CLEAN
A60
OFFICE
A61
OFFICE
A62
OFFICE
A59
STORAGE
SUPPLY
A63
HEMA/COAG
CHEM/URINE/
A67
LOUNGE
CONF./
A68
BANK
BLOOD
A64
MICROBIOLOGY
A56
RECEP.
A58A
PHLEB
A58B
PHLEB
A58C
PHLEB
A58H
PHLEB
A58I
PHLEB
A58J
PHLEB
A58G
PHLEB
A58D
PHLEB
A58K
PHLEB
A58F
PHLEB
A58E
PHLEB
A57A
TOILET
A57B
TOILET
A57C
TOILET
A57C
COLLECTION
A66
LOCKER
A65
TOILET
C0-B1
WAITING
C0-H1
CORR
C0-H5
CORR
C0-C2
CORR C0-H2
CORR
C0-H4
CORR
C0-H3
CORR
A58
PHLEB
A58
PHLEB
C0-H6
CORR
C0-H7
CORR
2C
RECEPTION
WAITING
2A
MEN 2B
WOMEN
53A
STOR
E-01
ELEV
E-02
ELEV
16A
ROOM
MG
10B
HEALTH
OCC.
10A
HEALTH
OCC.
HEALTH
OCC.
30B
OFFICE
30C
OFFICE
8D
EQUIP
8I
MECHANICAL
8A
MRI
7F
INTAKE
7E
INTAKE
7D
HAC
7C
TOILET
7B
CHANGING
7A
CHANGING
COE
CORRIDOR
7G
FOYER
8H
VESTIBULE
8B
CONTROL
8C
HALL
8E
LINEN
8F
SOIL
8G
CLEAN
A05C
TELECOM
ROOM
005F
TELECOM
ROOM
'-0
10'-6"
'-8
/4
4'-9 1/4"
'-6
3'-3"
10'-0"
8'-11 3/4"
5'-0"
6' -4
2'-0"
3' -0
1-AS400
1-AS400
005E
LOCKER
A05C
005F
5E
No DATEREVISION
DRAWING TITLE
CHECKED BY
ST.CLOUD, MN 56303
VA MEDICAL CENTER
BUILDING No
LOCATION
DRAWING NO.DRAWN
DWG. OF
PROJECT TITLE
PLOT SCALE
PROJECT NO.
DATE:
CONSULTANT ARCHITECT/ENGINEER OF RECORD
FULLY
SPRINKLERED
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
RECORD DOCUMENTS
-RECORD DOCUMENT-
June 21, 2024
This Record Document has been prepared based on
Designer of Record drawings with Contractor provided markups through the construction phase of the project at the direction of the VA.
While the construction information is believed to be reliable, Architect/Engineer cannot assure its accuracy, and is not responsible for the accuracy of this Record Document. Those relying on this Record
Document are advised to independently verify its accuracy before applying it for any purpose.
C
U s e rs
\P u b li c \D o c u m e n ts \R e v it
P ro je c ts
\1 -1
-R E
M a rk fo rt
.r v t
/1
/2
:0 :2
P
M
1-AS100
BASEMENT FLOOR - OVERALL
PLAN
EHRM INFRASTRUCTURE
UPGRADES
656‐21‐235
03/30/2022
TO, EM PC, EM
16305
1/8" = 1'-0"
BASEMENT FLOOR - OVERALL PLAN
N
0 8' 16'4'
_SHEET NOTES
1. SEE GENERAL NOTES AND CAMPUS DRAWINGS FOR GENERAL
INFORMATION, LIFE SAFETY, ICRA, AND PHASING
2. ALL EXISTING CONDITIONS MUST BE FIELD VERIFIED BY THE
CONTRACTOR PRIOR TO DEMOLITION OR CONSTRUCTION. EXISTING
CONDITIONS THAT DIFFER FROM THOSE SHOWN MUST BE BROUGHT TO
THE ATTENTION OF THE C.O.R. TO INFORM THE ARCHITECTS AND
ENGINEERS.
3. THE INFORMATION SHOWN ON THE DRAWINGS IS BASED ON DRAWINGS
AND PHOTOGRAPHS PROVIDED BY THE C.O.R. COMBINED WITH
OBSERVATIONS AND SURVEYED DATA FROM THE ARCHITECTS AND
ENGINEERS.
4. SEE CIVIL, STRUCTURAL, TELECOM, ELECTRICAL, MECHANICAL, AND
PLUMBING DRAWINGS FOR ADDITIONAL DEMOLITION AND
CONSTRUCTION REQUIREMENTS.
5. PORTABLE FIRE EXTINGUISHERS (CO2 OR HALOGENATED TYPE) WITH
WALL MOUNT BRACKET AND CODE REQUIRED SIGNAGE SHALL BE
PROVIDED WITHIN TELECOM ROOMS.
FRIDGE
24X26
SCALE
UPDATED 9/1/06
BUILDING 1 FIRST FLOOR
COPIER
PRINTER
F R
O N
T
ENTRY
128A
RECEPTION
STAIR120
WAITING
STAIR
MAA
REGISTRATION
REGISTRATION168
EXAM
EXAM
STOR
WHCHR
LOBBY
ELEV
C1NC
CORR
127A
PHONE
MECH
128B
V.I.C.
128C
OUT
CHECK
STOR
C1WI
CORR
EXAM
EXAM
EXAM
EXAM
STATION
NURSE
173A
MED
EXAM
EXAM165
NURSING
EXAM
EXAM
NURSING
160B
BATH
INTAKE
PROCEDURE
SPECIAL
160A
UTILITY
CLEAN
173B
INTAKE
C1WH
CORR
C1WG
CORR
ELEC
MECH
EXAM
INT
C1WF
CORR
EXAM
INT
EXAM
INT
EXAM
INT
EXAM
INT
EXAM
INT
STAIR
C1WJ
CORR
COPY
CONSULT
PHARM.
STAIR
C1WA
CORR
MALE
FEMALE
CHASE
WAITING
BATH
UTILITY
CLEAN
EXAM
EXAM
CONSULT
PHARM.
C1WD
CORR
EXAM
EXAM
UTILITY
CLEAN
CHART
NURSE/
OFFICE
NURSE
EXAM
EXAM
C1WB
CORR
EXAM
EXAM
EXAM
NURSING
EXAM
WAITING
152A
MED
C1WE
CORR
C1WC
CORR
ROOF
A111
VEST
TRIAGE
A110
OFFICE A109
EXAM
E-A1
ELEV
A-1
STAIR A108
STAFF
A107A
DICTATION
A107B
CLOSET
C0-2
CORR
A106
HAC A105
CONSULT
PHARM
A104
NURSING
A103
NURSING
C0-1
CORRIDOR
A127A
CHECK-OUT
A126
INTAKE
A125
EXAM
CO-5
CORR
A124
EXAM
A123
EXAM
A122
EXAM
A121
OFFICE
A120
UTIL
SOILED
A118
ALCOVE
NURSE
A117
MED
CO-3
CORRIDOR
A112
EXAM
A113
EXAM
A116
UTILITY
SOILED
A119
EXAM
C0-4
CORRIDOR
A114
EXAM
A115
EXAM
AS1
STAIR
A141
STORAGE
EQUIP.
A140
EXAM
A139
EXAM
A138
EXAM
A137
DICTATION
A136
EXAM
A135
EXAM
A134
OUT
CHECK
A133
PASSAGE
STAFF A132
STORAGE
CO-7
CORRIDOR
A142
STORAGE
CLEAN
A143
EXAM
A144
EXAM
A145
EXAM CO-3
CORR
A146
EXAM
A147
STORAGE
A127D
ROOM
MED A127C
STATION
NURSE
A127B
IN
CHECKCO-6
CORR
A131
MEN A130
CHASE
A129
WAITING
A128
WAITING
A102B
CHASE
A102A
WOMEN
A101
COMM
TELE-
A112A
LINEN
REGISTRATION
INTAKE
INTAKE
STAFF
111A
M.O.D.
111C
EQUIPMENT
SUPPLY
111D
PURPOSE
MULTI
111B
TOILET
WAITING
101A
TOILET
UNISEX
HAC
UTILITIES
CLEAN
UTILITIES
SOILED
LOCKERS
MED
STATION
NURSE
108A
TELEMETRY
108B
TELEMETRY
108C
TOILET
108D
TELEMETRY
108E
TELEMETRY
109C
TELEMETRY
PROCEDURE/
109B
TELEMETRY
109A
TELEMETRY
109D
TOILET
AMBULANCE
C1EC
CORRIDOR
C1EA
CORRIDOR
NOUR
C1ED
CORRIDOR
111E
CAMERAS
HOLDING/
111F
ANTE
HOLDING/
TOILET
C1EB
CORRIDOR
TOILET
STAFF
E-01
ELEV
E-02
ELEV
A117A
UNISEX
ROOF
FLAT
DECONTAM
BUILDING 1 ANNEX LOCATION
BUILDING 1 MAIN ENTRANCE
KIOSK
KIOSK
9' -6
/4
14'-0 3/4"
'-1
3/
4"
5'-5 1/4"
'-6
1-AS400
No DATEREVISION
DRAWING TITLE
CHECKED BY
ST.CLOUD, MN 56303
VA MEDICAL CENTER
BUILDING No
LOCATION
DRAWING NO.DRAWN
DWG. OF
PROJECT TITLE
PLOT SCALE
PROJECT NO.
DATE:
CONSULTANT ARCHITECT/ENGINEER OF RECORD
FULLY
SPRINKLERED
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
RECORD DOCUMENTS
-RECORD DOCUMENT-
June 21, 2024
This Record Document has been prepared based on
Designer of Record drawings with Contractor provided markups through the construction phase of the project at the direction of the VA.
While the construction information is believed to be reliable, Architect/Engineer cannot assure its accuracy, and is not responsible for the accuracy of this Record Document. Those relying on this Record
Document are advised to independently verify its accuracy before applying it for any purpose.
C
U s e rs
\P u b li c \D o c u m e n ts \R e v it
P ro je c ts
\1 -1
-R E
M a rk fo rt
.r v t
/1
/2
:0 :2
P
M
1-AS110
FIRST FLOOR - OVERALL PLAN EHRM INFRASTRUCTURE
UPGRADES
656‐21‐235
03/30/2022
TO, EM PC, EM
16305
N
0 8' 16'4'
_SHEET NOTES
1. SEE GENERAL NOTES AND CAMPUS DRAWINGS FOR GENERAL
INFORMATION, LIFE SAFETY, ICRA, AND PHASING
2. ALL EXISTING CONDITIONS MUST BE FIELD VERIFIED BY THE
CONTRACTOR PRIOR TO DEMOLITION OR CONSTRUCTION. EXISTING
CONDITIONS THAT DIFFER FROM THOSE SHOWN MUST BE BROUGHT TO
THE ATTENTION OF THE C.O.R. TO INFORM THE ARCHITECTS AND
ENGINEERS.
3. THE INFORMATION SHOWN ON THE DRAWINGS IS BASED ON DRAWINGS
AND PHOTOGRAPHS PROVIDED BY THE C.O.R. COMBINED WITH
OBSERVATIONS AND SURVEYED DATA FROM THE ARCHITECTS AND
ENGINEERS.
4. SEE CIVIL, STRUCTURAL, TELECOM, ELECTRICAL, MECHANICAL, AND
PLUMBING DRAWINGS FOR ADDITIONAL DEMOLITION AND
CONSTRUCTION REQUIREMENTS.
5. PORTABLE FIRE EXTINGUISHERS (CO2 OR HALOGENATED TYPE) WITH
WALL MOUNT BRACKET AND CODE REQUIRED SIGNAGE SHALL BE
PROVIDED WITHIN TELECOM ROOMS.
1/8" = 1'-0"1
FIRST FLOOR - OVERALL PLAN
A -O
-V
DN
UP
DN
UP
A200
TELECOM
ROOM
6' -1
/4
16'-0"
9'-8"
7' -6
5'-6"
9' -5
1-AS430
ALIGN
1-AS600
1-AS600
A200
No DATEREVISION
DRAWING TITLE
CHECKED BY
ST.CLOUD, MN 56303
VA MEDICAL CENTER
BUILDING No
LOCATION
DRAWING NO.DRAWN
DWG. OF
PROJECT TITLE
PLOT SCALE
PROJECT NO.
DATE:
CONSULTANT ARCHITECT/ENGINEER OF RECORD
FULLY
SPRINKLERED
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
RECORD DOCUMENTS
-RECORD DOCUMENT-
June 21, 2024
This Record Document has been prepared based on
Designer of Record drawings with Contractor provided markups through the construction phase of the project at the direction of the VA.
While the construction information is believed to be reliable, Architect/Engineer cannot assure its accuracy, and is not responsible for the accuracy of this Record Document. Those relying on this Record
Document are advised to independently verify its accuracy before applying it for any purpose.
C
U s e rs
\P u b li c \D o c u m e n ts \R e v it
P ro je c ts
\1 -1
-R E
M a rk fo rt
.r v t
/1
/2
:0 :2
P
M
1-AS120
SECOND FLOOR - OVERALL
PLAN
EHRM INFRASTRUCTURE
UPGRADES
656‐21‐235
03/30/2022
TO, EM PC, EM
16305
1/8" = 1'-0"1
SECOND FLOOR - OVERALL PLAN
N
0 8' 16'4'
_SHEET NOTES
1. SEE GENERAL NOTES AND CAMPUS DRAWINGS FOR GENERAL
INFORMATION, LIFE SAFETY, ICRA, AND PHASING
2. ALL EXISTING CONDITIONS MUST BE FIELD VERIFIED BY THE
CONTRACTOR PRIOR TO DEMOLITION OR CONSTRUCTION. EXISTING
CONDITIONS THAT DIFFER FROM THOSE SHOWN MUST BE BROUGHT TO
THE ATTENTION OF THE C.O.R. TO INFORM THE ARCHITECTS AND
ENGINEERS.
3. THE INFORMATION SHOWN ON THE DRAWINGS IS BASED ON DRAWINGS
AND PHOTOGRAPHS PROVIDED BY THE C.O.R. COMBINED WITH
OBSERVATIONS AND SURVEYED DATA FROM THE ARCHITECTS AND
ENGINEERS.
4. SEE CIVIL, STRUCTURAL, TELECOM, ELECTRICAL, MECHANICAL, AND
PLUMBING DRAWINGS FOR ADDITIONAL DEMOLITION AND
CONSTRUCTION REQUIREMENTS.
5. PORTABLE FIRE EXTINGUISHERS (CO2 OR HALOGENATED TYPE) WITH
WALL MOUNT BRACKET AND CODE REQUIRED SIGNAGE SHALL BE
CONVECTORCONVECTOR
CONVECTOR CONVECTOR CONVECTOR CONVECTORCONVECTOR
OFFICE
PURPOSE
MULTI
STAIR
PHONE
OFFICE
OFFICE
OFFICE
BATH
HAC
OFFICE
MED. DIR.
ACCESS
ATTIC
C3C
CORRIDOR
OFFICE
DN
STAIR A
1-AS430
No DATEREVISION
DRAWING TITLE
CHECKED BY
ST.CLOUD, MN 56303
VA MEDICAL CENTER
BUILDING No
LOCATION
DRAWING NO.DRAWN
DWG. OF
PROJECT TITLE
PLOT SCALE
PROJECT NO.
DATE:
CONSULTANT ARCHITECT/ENGINEER OF RECORD
FULLY
SPRINKLERED
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
RECORD DOCUMENTS
-RECORD DOCUMENT-
June 21, 2024
This Record Document has been prepared based on
Designer of Record drawings with Contractor provided markups through the construction phase of the project at the direction of the VA.
While the construction information is believed to be reliable, Architect/Engineer cannot assure its accuracy, and is not responsible for the accuracy of this Record Document. Those relying on this Record
Document are advised to independently verify its accuracy before applying it for any purpose.
C
U s e rs
\P u b li c \D o c u m e n ts \R e v it
P ro je c ts
\1 -1
-R E
M a rk fo rt
.r v t
/1
/2
:0 :2
P
M
1-AS130
ATTIC FLOOR - OVERALL
PLAN
EHRM INFRASTRUCTURE
UPGRADES
656‐21‐235
03/30/2022
TO, EM PC, EM
16305
1/8" = 1'-0"
ATTIC FLOOR - OVERALL PLAN
N
0 8' 16'4'
_SHEET NOTES
1. SEE GENERAL NOTES AND CAMPUS DRAWINGS FOR GENERAL
INFORMATION, LIFE SAFETY, ICRA, AND PHASING
2. ALL EXISTING CONDITIONS MUST BE FIELD VERIFIED BY THE
CONTRACTOR PRIOR TO DEMOLITION OR CONSTRUCTION. EXISTING
CONDITIONS THAT DIFFER FROM THOSE SHOWN MUST BE BROUGHT TO
THE ATTENTION OF THE C.O.R. TO INFORM THE ARCHITECTS AND
ENGINEERS.
3. THE INFORMATION SHOWN ON THE DRAWINGS IS BASED ON DRAWINGS
AND PHOTOGRAPHS PROVIDED BY THE C.O.R. COMBINED WITH
OBSERVATIONS AND SURVEYED DATA FROM THE ARCHITECTS AND
ENGINEERS.
4. SEE CIVIL, STRUCTURAL, TELECOM, ELECTRICAL, MECHANICAL, AND
PLUMBING DRAWINGS FOR ADDITIONAL DEMOLITION AND
CONSTRUCTION REQUIREMENTS.
5. PORTABLE FIRE EXTINGUISHERS (CO2 OR HALOGENATED TYPE) WITH
WALL MOUNT BRACKET AND CODE REQUIRED SIGNAGE SHALL BE
5C
CORR
005F
TELECOM
ROOM
3'-3"
5'-0"
6' -4
2'-0"
3' -0
5E
005F 005D
MECH
005C
CORRIDOR
005E
LOCKER V
.I.
F
3' -6
E
X
IS
T
005B
EXIST
MECH
IN-04.01
IN-03.01
3'-10" 2'-6" 3'-8"
3' -1
B3b
B3b
B3b
XN3
3'-3"
3' -3
10'-0"
(6
LO
C
K E
R S
(3) LOCKERS
(6) LOCKERS
(5
LO
C
K E
R S
(3
LO
C
K E
R S
(3
LO
C
K E
R S
(3) LOCKERS
(9
LO
C
K E
R S
005E
LOCKER
(3) LOCKERS
HOLD
1'-0"
LOCKER UNIT. PREFIN
METAL, PUTTY, TO
MATCH EXIST
TENNSCO LOCKERS
(3) LOCKERS
6' -4
'-0
/4
V .I.
F
005F
TELECOM
ROOM
TELECOM
ROOM
LOCKER
LOCKER
A05C
TELECOM
ROOM
A05C
A6bsA6bs
A05A
MECH
IN-03.01
3'-1 3/4" 4'-8 1/2"
3' -7
/4
2'
-6
3' -1
0"
A6bs
11'-8 1/2"
'-7
/4
TELECOM
ROOM
TELECOM
ROOM
A101
TELECOM
ROOM
IN-03.01
2'-5 1/2" 11'-7 1/4"
3' -1
/4
2'
-6
3' -1
1/
2"
TELECOM
ROOM
TELECOM
ROOM
No DATEREVISION
DRAWING TITLE
CHECKED BY
ST.CLOUD, MN 56303
VA MEDICAL CENTER
BUILDING No
LOCATION
DRAWING NO.DRAWN
DWG. OF
PROJECT TITLE
PLOT SCALE
PROJECT NO.
DATE:
CONSULTANT ARCHITECT/ENGINEER OF RECORD
FULLY
SPRINKLERED
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
RECORD DOCUMENTS
-RECORD DOCUMENT-
June 21, 2024
This Record Document has been prepared based on
Designer of Record drawings with Contractor provided markups through the construction phase of the project at the direction of the VA.
While the construction information is believed to be reliable, Architect/Engineer cannot assure its accuracy, and is not responsible for the accuracy of this Record Document. Those relying on this Record
Document are advised to independently verify its accuracy before applying it for any purpose.
C
U s e rs
\P u b li c \D o c u m e n ts \R e v it
P ro je c ts
\1 -1
-R E
M a rk fo rt
.r v t
/1
/2
:0 :2
P
M
1-AS400
LARGE SCALE PLANS EHRM INFRASTRUCTURE
UPGRADES
656‐21‐235
03/30/2022
TO, EM PC, EM
16305
1/4" = 1'-0"
ENLARGED FLOOR PLAN - RM 5F
1/8" = 1'-0"
DEMOLITION PLAN - RM 5F
1/8" = 1'-0"
REFLECTED CEILING PLAN - RM 5F
1/4" = 1'-0"
ENLARGED FLOOR PLAN - RM A05C
1/8" = 1'-0"
DEMOLITION PLAN - RM A05A
1/8" = 1'-0"
REFLECTED CEILING PLAN - RM A05C
N
0 4' 8'2'
N
0 4' 8'2'
N
0 8' 16'4'
N
0 8' 16'4'
N
0 8' 16'4'
N
0 8' 16'4'
1/4" = 1'-0"
ENLARGED FLOOR PLAN - RM A101
1/8" = 1'-0"
DEMOLITION PLAN - RM A101
1/8" = 1'-0"
REFLECTED CEILING PLAN - RM A101
N
0 4' 8'2'
N
0 8' 16'4'
N
0 8' 16'4'
_DEMOLITION PLAN KEYED NOTES
DE26 REFER TO MECHANICAL FOR REMOVAL OF ROOFTOP UNIT
DE27 CAREFULLY REMOVE EXISTING ROOFTOP TILE AND SALVAGE FOR REINSTALLATION
NOTE: NOT ALL KEYED NOTES MAY BE USED ON EACH PLAN
_DEMOLITION PLAN KEYED NOTES
DE1 PREPARE WALL FOR PLYWOOD BACKBOARD INSTALLATION AND EHRM REQUIREMENTS,
SEE FLOOR PLAN AND TELECOM DRAWINGS
DE2 REMOVE AND SALVAGE DOOR AND PREPARE OPENING TO ACCOMMODATE PLAN. SEE
FLOOR PLAN AND DOOR SCHEDULE
DE5 REMOVE AND SALVAGE ROOM IDENTIFICATION SIGN FOR REINSTALLATION
DE6 REMOVE PARTITION TO THE EXTENTS SHOWN
DE7 PARTIALLY REMOVE WALL TO ACCOMMODATE PLAN AS REQUIRED. COORDINATE TEMP
SHORING WITH STRUCTURAL. SEE FLOOR PLAN
DE8 REMOVE EXISTING ROOF ASSEMBLY AS REQUIRED TO BUILD NEW ROOM, REFER TO
MECHANICAL AND ELECTRICAL FOR REMOVAL OF ROOFTOP EQUIPMENT
DE11 REMOVE EXISTING EXTERIOR PANEL SYSTEM BACK TO STRUCTURE TO THE EXTENTS
SHOWN. PREPARE FOR INSTALLATION OF NEW FURRING WALL.
DE14 REFER TO ELECTRICAL FOR REMOVAL OF DEVICES.
DE18 REMOVE AND SALVAGE LOCKERS FOR REINSTALLATION
DE20 RELOCATE CHILL WATER AND SNOW MELT SYSTEM, SEE MECHANICAL AND PLUMBING
DE21 PREPARE FLOOR FOR FINISH AND RATED PARTITIONS, SEE FLOOR PLAN
DE22 REMOVE EXISTING GUARD RAIL AS REQUIRED FOR NEW CONSTRUCTION AND PREPARE
END OF REMAINING RAIL FOR NEW ENDCAPS
_FLOOR PLAN KEYED NOTES_FLOOR PLAN KEYED NOTES
FL1 ALL FOUR PERIMETER WALL PARTITIONS APPLY 4' BY 8' AC GRADE ¾” TRADE
SIZE FIRE RATED PLYWOOD BACKBOARD FINISHED WITH HIGH-GLOSS WHITE
PAINT OVER TWO COATS OF FIRE RESISTANT PAINT FOR SERVICE PROVIDER
/ SECURITY / VIDEO / ET CETERA. DO NOT PAINT OVER FIRE RATING STAMP.
FL2 DOOR, SIZE AS SCHEDULED, FIRE RESISTANT AS SCHEDULED.
FL3 UPGRADE PARTITION TO 1 HOUR FIRE AND SMOKE BARRIER. PROVIDE
TESTED HEAD OF PARTITION ASSEMBLY WITH MATERIALS THAT RESIST THE
PASSAGE OF SMOKE. SEAL JOINT AT HEAD AND ALL PENETRATIONS WITH
FIRE CAULK.
FL5 FINISH PARTITION WITH P-2 & RB-1.
FL13 DRYWALL PENETRATION BARRIER MESH.
FL16 MOUNT 5/8" GYPSUM BOARD TO EXISTING STEEL STUDS. UPGRADE
PARTITION TO 1 HOUR FIRE AND SMOKE BARRIER. PROVIDE TESTED HEAD
OF PARTITION ASSEMBLY WITH MATERIALS THAT RESIST THE PASSAGE OF
SMOKE. SEAL JOINT AT HEAD AND ALL PENETRATIONS WITH FIRE CAULK.
FL17 PREFINISHED METAL DOWNSPOUT AND PRECAST CONCRETE SPLASH
BLOCK.
FL18 FULL HEIGHT PREFINISHED METAL LOCKERS. RECONFIGURE LAYOUT AS
SHOWN. PROVIDE ALL NECESSARY TRANSITION COMPONENTS. MATCH
EXISTING TYPE AND FINISH.
FL20 TELECOM EQUIPMENT, SEE TELECOM DRAWINGS.
NOTE: NOT ALL KEYED NOTES MAY BE USED ON EACH PLAN
DE1
FL1
FL2
RC1
RC2
FL2
_REFLECTED CEILING PLAN KEYED NOTES
RC1 LED LIGHTING, SEE ELECTRICAL. IN FRONT OF AND BEHIND CABINET
ROWS PROVIDE 500 LUMENS IN HORIZONTAL AND 200 LUMENS IN THE
VERTICAL AT 3 FT AFF. OPERATED BY MOTION SENSOR PER CABINET
ROW OR SECTION.
RC2 OPEN TO STRUCTURAL FLOOR ABOVE
RC3 ACT SYSTEM AND 2X4 LIGHT FIXTURE, MATCH EXIST ADJACENT CEILING.
SEE ELECTRICAL
RC4 PATCH AND ALIGN ACT WITH EXISTING
RC5 EXISTING CEILING TO REMAIN
RC6 GYP SOFFIT. 1/2" GYP BD ON MTL STUD AFFIXED TO OPENING LIMITS,
PAINT
NOTE: NOT ALL KEYED NOTES MAY BE USED ON EACH PLAN
RC1
RC1
DE1
FL5
RC3
RC3
RC4
RC5
RC5
RC5
DE1
FL5
DE5DE1
DE2
DE6
FL1
FL5
FL5
FL5
FL1
DE1
DE1
DE1DE18
FL18
FL18
FL20
FL20
FL20
DE20 DE21
DE21
DE21
FL3
FL3
FL3
FL3
FL3
_SHEET NOTES
1. SEE GENERAL NOTES AND CAMPUS DRAWINGS FOR GENERAL
INFORMATION, LIFE SAFETY, ICRA, AND PHASING
2. ALL EXISTING CONDITIONS MUST BE FIELD VERIFIED BY THE
CONTRACTOR PRIOR TO DEMOLITION OR CONSTRUCTION. EXISTING
CONDITIONS THAT DIFFER FROM THOSE SHOWN MUST BE BROUGHT TO
THE ATTENTION OF THE C.O.R. TO INFORM THE ARCHITECTS AND
ENGINEERS.
3. THE INFORMATION SHOWN ON THE DRAWINGS IS BASED ON DRAWINGS
AND PHOTOGRAPHS PROVIDED BY THE C.O.R. COMBINED WITH
OBSERVATIONS AND SURVEYED DATA FROM THE ARCHITECTS AND
ENGINEERS.
4. SEE CIVIL, STRUCTURAL, TELECOM, ELECTRICAL, MECHANICAL, AND
PLUMBING DRAWINGS FOR ADDITIONAL DEMOLITION AND
CONSTRUCTION REQUIREMENTS.
5. PORTABLE FIRE EXTINGUISHERS (CO2 OR HALOGENATED TYPE) WITH
WALL MOUNT BRACKET AND CODE REQUIRED SIGNAGE SHALL BE
PROVIDED WITHIN TELECOM ROOMS.
RC2
RC2
DE1
FL3
DE1
S
LO
P E
D O
W N
1/
4"
1' -0
1-AS602
1-AS602
1-AS602
1-AS602
30.00°
1-AS600
1-AS600
'-1
1/
2" 3'
-4
2' -0
V .I.
F
'-2
/2
E
X
IS
T 157 SF
A200
TELECOM
ROOM
A200
'-2
/2
11'-3 3/4"
C2-A1
RAMP
IN-03.01
1-AS601
1-AS601
1-AS601
1-AS601
3'-9" 2'-6" 3'-11 1/2"
3' -6
4'
-9
7' -5
1-AS601
1-AS600
1-AS600
1-AS601
1-AS601
TELECOM
ROOM
No DATEREVISION
DRAWING TITLE
CHECKED BY
ST.CLOUD, MN 56303
VA MEDICAL CENTER
BUILDING No
LOCATION
DRAWING NO.DRAWN
DWG. OF
PROJECT TITLE
PLOT SCALE
PROJECT NO.
DATE:
CONSULTANT ARCHITECT/ENGINEER OF RECORD
FULLY
SPRINKLERED
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
RECORD DOCUMENTS
-RECORD DOCUMENT-
June 21, 2024
This Record Document has been prepared based on
Designer of Record drawings with Contractor provided markups through the construction phase of the project at the direction of the VA.
While the construction information is believed to be reliable, Architect/Engineer cannot assure its accuracy, and is not responsible for the accuracy of this Record Document. Those relying on this Record
Document are advised to independently verify its accuracy before applying it for any purpose.
C
U s e rs
\P u b li c \D o c u m e n ts \R e v it
P ro je c ts
\1 -1
-R E
M a rk fo rt
.r v t
/1
/2
:0 :3
P
M
1-AS430
BUILDING ADDITION AND
ROOF PLAN
EHRM INFRASTRUCTURE
UPGRADES
656‐21‐235
03/30/2022
EM BMW
16305
1/4" = 1'-0"
ROOF PLAN - RM A200
N
0 4' 8'2'
RO1
N
0 4' 8'2'
DE7
DE8
DE11
DE11
DE14
1/4" = 1'-0"
DEMOLITION PLAN - RM A200
_ROOF PLAN KEYED NOTES
RO1 SLOPE ROOF TO DRAIN MINIMUM 1/4" PER FOOT
RO3 RELOCATE EXISTING ROOF TILES AROUND RELOCATED ROOFTOP UNIT.
NOTE: NOT ALL KEYED NOTES MAY BE USED ON EACH PLAN
N
0 4' 8'2'
FL1
FL2
FL13
FL1
FL16
FL17
FL20
FL16
1/4" = 1'-0"
ENLARGED FLOOR PLAN - RM A200
N
0 4' 8'2'
RC1
RC5
RC6
1/4" = 1'-0"
REFLECTED CEILING PLAN - RM A200
_REFLECTED CEILING PLAN KEYED NOTES
RC1 LED LIGHTING, SEE ELECTRICAL. IN FRONT OF AND BEHIND CABINET
ROWS PROVIDE 500 LUMENS IN HORIZONTAL AND 200 LUMENS IN THE
VERTICAL AT 3 FT AFF. OPERATED BY MOTION SENSOR PER CABINET
ROW OR SECTION.
RC2 OPEN TO STRUCTURAL FLOOR ABOVE
RC3 ACT SYSTEM AND 2X4 LIGHT FIXTURE, MATCH EXIST ADJACENT CEILING.
SEE ELECTRICAL
RC4 PATCH AND ALIGN ACT WITH EXISTING
RC5 EXISTING CEILING TO REMAIN
RC6 GYP SOFFIT. 1/2" GYP BD ON MTL STUD AFFIXED TO OPENING LIMITS,
PAINT
NOTE: NOT ALL KEYED NOTES MAY BE USED ON EACH PLAN
DE22
RO3
DE27
DE26
_SHEET NOTES
1. SEE GENERAL NOTES AND CAMPUS DRAWINGS FOR GENERAL
INFORMATION, LIFE SAFETY, ICRA, AND PHASING
2. ALL EXISTING CONDITIONS MUST BE FIELD VERIFIED BY THE
CONTRACTOR PRIOR TO DEMOLITION OR CONSTRUCTION. EXISTING
CONDITIONS THAT DIFFER FROM THOSE SHOWN MUST BE BROUGHT TO
THE ATTENTION OF THE C.O.R. TO INFORM THE ARCHITECTS AND
ENGINEERS.
3. THE INFORMATION SHOWN ON THE DRAWINGS IS BASED ON DRAWINGS
AND PHOTOGRAPHS PROVIDED BY THE C.O.R. COMBINED WITH
OBSERVATIONS AND SURVEYED DATA FROM THE ARCHITECTS AND
ENGINEERS.
4. SEE CIVIL, STRUCTURAL, TELECOM, ELECTRICAL, MECHANICAL, AND
PLUMBING DRAWINGS FOR ADDITIONAL DEMOLITION AND
CONSTRUCTION REQUIREMENTS.
5. PORTABLE FIRE EXTINGUISHERS (CO2 OR HALOGENATED TYPE) WITH
WALL MOUNT BRACKET AND CODE REQUIRED SIGNAGE SHALL BE
PROVIDED WITHIN TELECOM ROOMS.
DEMOLITION PLAN KEYED NOTES
DE1 PREPARE WALL FOR PLYWOOD BACKBOARD INSTALLATION AND EHRM REQUIREMENTS,
SEE FLOOR PLAN AND TELECOM DRAWINGS
DE2 REMOVE AND SALVAGE DOOR AND PREPARE OPENING TO ACCOMMODATE PLAN. SEE
FLOOR PLAN AND DOOR SCHEDULE
DE5 REMOVE AND SALVAGE ROOM IDENTIFICATION SIGN FOR REINSTALLATION
DE6 REMOVE PARTITION TO THE EXTENTS SHOWN
DE7 PARTIALLY REMOVE WALL TO ACCOMMODATE PLAN AS REQUIRED. COORDINATE TEMP
SHORING WITH STRUCTURAL. SEE FLOOR PLAN
DE8 REMOVE EXISTING ROOF ASSEMBLY AS REQUIRED TO BUILD NEW ROOM, REFER TO
MECHANICAL AND ELECTRICAL FOR REMOVAL OF ROOFTOP EQUIPMENT
DE11 REMOVE EXISTING EXTERIOR PANEL SYSTEM BACK TO STRUCTURE TO THE EXTENTS
SHOWN. PREPARE FOR INSTALLATION OF NEW FURRING WALL.
DE14 REFER TO ELECTRICAL FOR REMOVAL OF DEVICES.
DE18 REMOVE AND SALVAGE LOCKERS FOR REINSTALLATION
DE20 RELOCATE CHILL WATER AND SNOW MELT SYSTEM, SEE MECHANICAL AND PLUMBING
DE21 PREPARE FLOOR FOR FINISH AND RATED PARTITIONS, SEE FLOOR PLAN
DE22 REMOVE EXISTING GUARD RAIL AS REQUIRED FOR NEW CONSTRUCTION AND PREPARE
END OF REMAINING RAIL FOR NEW ENDCAPS
DE26 REFER TO MECHANICAL FOR REMOVAL OF ROOFTOP UNIT
DE27 CAREFULLY REMOVE EXISTING ROOFTOP TILE AND SALVAGE FOR REINSTALLATION
NOTE: NOT ALL KEYED NOTES MAY BE USED ON EACH PLAN
FLOOR PLAN KEYED NOTES
FL1 ALL FOUR PERIMETER WALL PARTITIONS APPLY 4' BY 8' AC GRADE ¾”
TRADE SIZE FIRE RATED PLYWOOD BACKBOARD FINISHED WITH
HIGH-GLOSS WHITE PAINT OVER TWO COATS OF FIRE RESISTANT PAINT
FOR SERVICE PROVIDER / SECURITY / VIDEO / ET CETERA. DO NOT PAINT
OVER FIRE RATING STAMP.
FL2 DOOR, SIZE AS SCHEDULED, FIRE RESISTANT AS SCHEDULED.
FL3 UPGRADE PARTITION TO 1 HOUR FIRE AND SMOKE BARRIER. PROVIDE
TESTED HEAD OF PARTITION ASSEMBLY WITH MATERIALS THAT RESIST
THE PASSAGE OF SMOKE. SEAL JOINT AT HEAD AND ALL PENETRATIONS
WITH FIRE CAULK.
FL5 FINISH PARTITION WITH P-2 & RB-1.
FL13 DRYWALL PENETRATION BARRIER MESH.
FL16 MOUNT 5/8" GYPSUM BOARD TO EXISTING STEEL STUDS. UPGRADE
PARTITION TO 1 HOUR FIRE AND SMOKE BARRIER. PROVIDE TESTED
HEAD OF PARTITION ASSEMBLY WITH MATERIALS THAT RESIST THE
PASSAGE OF SMOKE. SEAL JOINT AT HEAD AND ALL PENETRATIONS WITH
FIRE CAULK.
FL17 PREFINISHED METAL DOWNSPOUT AND PRECAST CONCRETE SPLASH
BLOCK.
FL18 FULL HEIGHT PREFINISHED METAL LOCKERS. RECONFIGURE LAYOUT AS
SHOWN. PROVIDE ALL NECESSARY TRANSITION COMPONENTS. MATCH
EXISTING TYPE AND FINISH.
FL20 TELECOM EQUIPMENT, SEE TELECOM DRAWINGS.
NOTE: NOT ALL KEYED NOTES MAY BE USED ON EACH PLAN
FL1
FL13
RC2
SM1
9 1/4" 3 3/8"
1'-0 5/8"
WALL ASSEMBLY
EIFS PANEL
3/8" DRAINAGE BOARD
BUILDING MEMBRANE
5/8" GYPSUM SHEATHING
8" METAL STUDS @ 16" OC
5/8" GPBD
STEEL WIRE MESH
XN3
(1 ) LAYER 5/8" GYPSUM
BOARD EACH SIDE
3 5/8" METAL STUD
FRAMING
3" SOUND ATTENUATING
INSULATION
(1 ) LAYER 5/8" GYPSUM
BOARD
3 5/8" METAL STUD
FRAMING
STC 49
4 7/8"4 1/4"
B3
(1 ) LAYER 5/8" GYPSUM
BOARD EACH SIDE
6" METAL STUD FRAMING
3" SOUND ATTENUATING
INSULATION
STC 49
7 1/4"
B6
VARIES
A S
S C
H E
D
METAL STUDS
GYP BD
HM FRAME
DOOR AS SCHED
2"
METAL RUNNER
NOTE:
1. FOR PARTITION THICKNESS SEE PLANS
AND PARTITION TYPES
VARIES
2"
A S
S C
H E
D
HM FRAME
DOOR AS SCHED
METAL STUDS
GYP BD
NOTE:
1. FOR PARTITION THICKNESS SEE PLANS
AND PARTITION TYPES
1-AS601
1-AS601
EIFS PANEL
EIFS REVEAL
PREFINISHED METAL FLASHING
1-AS601
1-AS601
EIFS PANEL
EIFS REVEAL
PREFINISHED METAL FLASHING
No DATEREVISION
DRAWING TITLE
CHECKED BY
ST.CLOUD, MN 56303
VA MEDICAL CENTER
BUILDING No
LOCATION
DRAWING NO.DRAWN
DWG. OF
PROJECT TITLE
PLOT SCALE
PROJECT NO.
DATE:
CONSULTANT ARCHITECT/ENGINEER OF RECORD
FULLY
SPRINKLERED
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
RECORD DOCUMENTS
-RECORD DOCUMENT-
June 21, 2024
This Record Document has been prepared based on
Designer of Record drawings with Contractor provided markups through the construction phase of the project at the direction of the VA.
While the construction information is believed to be reliable, Architect/Engineer cannot assure its accuracy, and is not responsible for the accuracy of this Record Document. Those relying on this Record
Document are advised to independently verify its accuracy before applying it for any purpose.
C
U s e rs
\P u b li c \D o c u m e n ts \R e v it
P ro je c ts
\1 -1
-R E
M a rk fo rt
.r v t
/1
/2
:0 :3
P
M
1-AS600
ELEVATIONS, DETAILS,
SCHEDULES
EHRM INFRASTRUCTURE
UPGRADES
656‐21‐235
03/30/2022
TO, EM PC, EM
16305
OPENING SCHEDULE
VA Building Number
ASSOCIATED ROOMS OPENING PANEL INFORMATION FRAME INFORMATION
H D
W G
R O
U P
F
IR
E L
A B
E L
(M
IN
G A
S K
E T
E
LE
C T
R
IC
A L
S L
A B
E L
COMMENTSFROM ROOM NAME TO ROOM NAME NUMBER WIDTH HEIGHT
PANEL
TYPE
2ND
PANEL
TYPE
PANEL
GLAZING FRAME TYPE
FRAME
GLAZING
1 CORRIDOR LOCKER 005E 3'-0" 7'-0" WD-F NONE HMS-1 NONE HW-5 -- -- -- -- LOCKER ROOM DOOR
1 LOCKER TELECOM ROOM 005F 3'-0" 7'-0" WD-F NONE HMS-1 NONE HW-3.2B 45 Y Y Y
1 MECH TELECOM ROOM A05C 3'-0" 7'-0" HM-F NONE HMS-1 NONE HW-3.2B 45 Y Y Y
1 TELECOM ROOM A200 3'-0" 7'-0" WD-F NONE HMS-1 NONE HW-3.2B 45 Y Y Y
ROOM SCHEDULE
NO. NAME C
A
B
LI
N G
P A
T C
H P
A N
E L
B A
C K
B O
N E
P O
W E
R
B O
N D
IN
G
U P
S
D E
D
IC
A T
E D
C O
O
LI
N G
T E
M P
E R
A T
U R
E
H U
M
ID
IT
Y
R A
C K
S E
N S
O R
S P
A C
E
AREA
WIDTH
(FT)
LENGTH
(FT)
HT TO
CLG
STRUCT REMARKS
BASEMENT
005C CORRIDOR 54 SF 7.17 MODIFIED FOR LOCKER ROOM EXPANSION, MATCH
EXIST
005D MECH 264 SF 9.17 MODIFIED FOR LOCKER ROOM EXPANSION, SEE MECH
DRAWINGS FOR ADDITIONAL REMARKS
005E LOCKER 243 SF 7.17 MATCH EXIST LOCKER ROOM FINISHES, PROVIDE 54
LOCKERS IN AREA ADJACENT TO TR.
005F TELECOM ROOM X X ABC X X X X X X X X 137 SF 10.0 13.7 9.17 CONSTRUCT TO EHRM TELECOM ROOM STANDARDS.
SEE TELECOM DRAWINGS
A003 EXIST RM 64 SF 4.8 13.5 9.00 DECOMMISSION EXIST IT/DATA ROOM. SEE TELECOM
DRAWINGS
A05A MECH 1693 SF 9.58 MODIFIED FOR TELECOM ROOM, SEE MECH DRAWINGS
FOR ADDITIONAL REMARKS
A05C TELECOM ROOM X X ABC X X X X X X X X 103 SF 10.5 10.0 9.58 CONSTRUCT TO EHRM TELECOM ROOM STANDARDS.
SEE TELECOM DRAWINGS. RELOCATE CHILLED WATER
PUMPS AND SNOW MELT SYSTEM. SEE MECH
DRAWINGS
FIRST FLOOR
127 EXIST RM 74 SF 5.4 12.5 DECOMMISSION EXIST IT/DATA ROOM. SEE TELECOM
DRAWINGS
A101 TELECOM ROOM ABC X X X X X X 142 SF 9.6 14.1 8.17 UPDATE EXIST IT/DATA ROOM TO EHRM TELECOM
ROOM STANDARDS. SEE TELECOM DRAWINGS
SECOND FLOOR
229 EXIST RM 52 SF 5.5 9.4 DECOMMISSION EXIST IT/DATA ROOM. SEE TELECOM
DRAWINGS
A200 TELECOM ROOM X X ABC X X X X X X X X 157 SF 10.0 15.4 10.00 CONSTRUCT ADDITION. CONSTRUCT TO EHRM
TELECOM ROOM STANDARDS. SEE TELECOM
DRAWINGS. TELECOM ROOM ON ROOF FOR FIRST
FLOOR, TR SERVES 2ND AND 3RD FLOORS
A216 EXIST RM 98 SF 6.1 16.0 DECOMMISSION EXIST…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .