Attachment 7 - As Built Record EHRM_Part III (1).pdf
PDF 10 MB Posted
- Attached to
- 656-26-702 EHRM DDPO 2. 0 Federal contract opportunity
- Solicitation number
- 36C26326B0028
About this file
Summary of EHRM Infrastructure Upgrades - Building 49 Telecommunications Record Documents
This file comprises record documents for the EHRM Infrastructure Upgrades project at the St. Cloud VA Health Care System in St. Cloud, Minnesota, specifically for Building 49 telecommunications work. The project, numbered 656-21-235, involves upgrading telecommunications infrastructure including data cabling demolition, new cabling installation, and telecom room equipment. The documents are dated June 21, 2024, and serve as record drawings prepared based on Designer of Record drawings with contractor markups through the construction phase under VA direction. Key construction involves a primary telecom room (Room 001) in the basement and supporting existing rooms (139 and 241) on the first and second floors, with data cabling distribution throughout the facility's basement, first, and second floors.
The telecommunications scope includes demolishing existing data cabling limits on the second and third floors, installing new CAT6A copper cabling and OM4/OS2 fiber optic backbone infrastructure, provisioning two-rack and single-rack configurations with patch panels, fiber distribution panels, network switches (VA OIT-provided 1U 48-port units), 5KW rack-mounted UPS systems, vertical cable management, and bonding bus bars. The project specifies conduit sizing (2-inch to 4-inch), cable tray configurations (12"x2" to 18"x4"), and dedicated cooling, power (NEMA L21-20R receptacles), humidity, temperature monitoring, and sensor systems for equipment rooms. Construction infection control risk assessments classify the work as Class II with Groups 1 and 3 risk designations, requiring 1-hour fire-rated partitions and specialized containment procedures for occupied areas during day-shift construction.
View the file
Other files for this federal contract opportunity
Show all 13
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
A -O
-V
DN
UP
DN
UP
A200
TELECOM
ROOM
1-TN300
1-TN300
LIMITS OF DATA CABLING DEMOLITION
1-TN300
WAP
WAP
WAP
WAP
WAP
WAP
WAP
WAP
WAP
WAP WAP
WAP
WAP
WAP
4D
4D
4D
4D
4D
4D
4D
4D
4D
4D 4D
6D
1D6D
4D 4D
1D
4D
1D
4D
4D
4D
4D
4D 4D
1D6D
4D
4D
4D
4D
4D
3D/1V 4D
4D 2D 4D 2D
4D
4D
1V
4D
4D
1D 4D
4D
4D
4D
4D
4D
3D/1V
4D
4D 4D
4D
4D 4D 4D 4D 4D
4D
4D
4D
4D
4D
4D
4D
4D
4D
4D
4D
4D
4D
E
E E
E
E E
E
E
E
EE
EE
E
E
E
E
E
E E
E
E
E
E
E E
E
E E E E
E
E E
E
E E
E
E
E
E
E
E
E
E
E
E
E
E
E E
E
E
E
E
E
E
E E E
E
E
E
E
E
E
E
E
E
EE
E
E
E
E
E
E
E E EEE
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E E
E E E E E E
E EE
E E
E
E
E
E
E
E
E
WAP
WAP
WAP
WAP
WAP
WAP
WAP
WAP
WAP
4D
4D
4D
4D
D
4D
4D
3D
4D
4D
4D
4D
4D 4D 4D 4D
4D
4D 4D
4D
4D 4D
3D
4D 2D
1V
1V
1V
4D E
E
D
"x
2"
"x
2"
12"x2"
E E
E
D
"x
2"
12"x2" 12"x2"
E
E E E
12"x4"
"x
4"
D D
D
E
E
"x
4"
"x 4"
E E
EE
E E
12"x4"
"x
4"
"x
4"
12"x4"
12"x4"12"x4"
D
EE
E
"x
4"
12"x2"
D
D
D D
RECORD DOCUMENTS
No DATEREVISION
DRAWING TITLE
CHECKED BY
ST.CLOUD, MN 56303
VA MEDICAL CENTER
BUILDING No
LOCATION
DRAWING NO.DRAWN
DWG. OF
PROJECT TITLE
PLOT SCALE
PROJECT NO.
DATE:
CONSULTANT ARCHITECT/ENGINEER OF RECORD
FULLY
SPRINKLERED
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
-RECORD DOCUMENT-
June 21, 2024
This Record Document has been prepared based on
Designer of Record drawings with Contractor provided markups through the construction phase of the project at the direction of the VA.
While the construction information is believed to be reliable, Architect/Engineer cannot assure its accuracy, and is not responsible for the accuracy of this Record Document. Those relying on this Record
Document are advised to independently verify its accuracy before applying it for any purpose.
RECORD DOCUMENTS 06/21/24
B
IM
/2
.0
V A
S t C lo u d E
H R
M I n fr a s tr u c tu re U p g ra d e s /6
-2
.B
.T
R
.r v t
/4
/2
:2
:1
P
M
1-TD120
SECOND FLOOR PLAN -
TELECOM - DEMOLITION
EHRM INFRASTRUCTURE
UPGRADES
656‐21‐235
03/30/2022
KSB SSK
16305
1/8" = 1'-0"1
SECOND FLOOR PLAN - TELECOM - DEMOLITION
N
0 8' 16'4'
GENERAL NOTES:
A. REFER TO GENERAL DEMOLITION NOTES ON SHEET T000 FOR ADDITIONAL DEMOLITION SCOPE.
SHEET NOTES:
1. REMOVE AND REPLACE EXISTING DATA CABLE: REMOVE ALL EXISTING DATA CABLES AND JACKS THROUGHOUT THIS AREA. REPLACE CABLES AND JACKS 1 FOR 1, AS REQUIRED BY THE NEW WORK PLANS.
REFER TO NEW WORK PLANS FOR SERVING COMMUNICATIONS ROOM LOCATION AND NEW CABLING
ROUTES.
CONVECTORCONVECTOR
CONVECTOR CONVECTOR CONVECTOR CONVECTORCONVECTOR
ATTIC ROOF
OFFICE
PURPOSE
MULTI
STAIR
PHONE
OFFICE
OFFICE
OFFICE
BATH
HAC
OFFICE
MED. DIR.
ACCESS
ATTIC
C3C
CORRIDOR
OFFICE
DN
STAIR A
CONVECTOR CONVECTOR CONVECTOR CONVECTORCONVECTOR
ATTIC ROOF
OFFICE
PURPOSE
MULTI
STAIR
PHONE
OFFICE
OFFICE
OFFICE
BATH
HAC
OFFICE
MED. DIR.
ACCESS
ATTIC
C3C
CORRIDOR
OFFICE
DN
STAIR A
LIMITS OF DATA CABLING DEMOLITION
E EE E
8"x2"
8" x2
8"x2"
RECORD DOCUMENTS
No DATEREVISION
DRAWING TITLE
CHECKED BY
ST.CLOUD, MN 56303
VA MEDICAL CENTER
BUILDING No
LOCATION
DRAWING NO.DRAWN
DWG. OF
PROJECT TITLE
PLOT SCALE
PROJECT NO.
DATE:
CONSULTANT ARCHITECT/ENGINEER OF RECORD
FULLY
SPRINKLERED
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
-RECORD DOCUMENT-
June 21, 2024
This Record Document has been prepared based on
Designer of Record drawings with Contractor provided markups through the construction phase of the project at the direction of the VA.
While the construction information is believed to be reliable, Architect/Engineer cannot assure its accuracy, and is not responsible for the accuracy of this Record Document. Those relying on this Record
Document are advised to independently verify its accuracy before applying it for any purpose.
RECORD DOCUMENTS 06/21/24
B
IM
/2
.0
V A
S t C lo u d E
H R
M I n fr a s tr u c tu re U p g ra d e s /6
-2
.B
.T
R
.r v t
/4
/2
:2
:1
P
M
1-TD130
THIRD FLOOR PLAN -
TELECOM - DEMOLITION
EHRM INFRASTRUCTURE
UPGRADES
656‐21‐235
03/30/2022
KSB SSK
16305
1/8" = 1'-0"
THIRD FLOOR PLAN - TELECOM - DEMOLITION
N
0 8' 16'4'
GENERAL NOTES:
A. REFER TO GENERAL DEMOLITION NOTES ON SHEET T000 FOR ADDITIONAL DEMOLITION SCOPE.
SHEET NOTES:
1. REMOVE AND REPLACE EXISTING DATA CABLE: REMOVE ALL EXISTING DATA CABLES AND JACKS THROUGHOUT THIS AREA. REPLACE CABLES AND JACKS 1 FOR 1, AS REQUIRED BY THE NEW WORK PLANS.
REFER TO NEW WORK PLANS FOR SERVING COMMUNICATIONS ROOM LOCATION AND NEW CABLING
ROUTES.
52.1183
52.1183 36.0000
AEC
CB1
DACC
GAC
LCC
CR
4D
BATH 4C
LOCKER
MALE
C0C
CORRIDOR
PHONE
LOBBY
HAC
HEALTH
OCC.
HAC
LOCKER
4A
LOCKER
FEMALE
4B
BATH
STOR
STAIR
12A
ELECTRICAL
MECHANICAL
MECHANICAL
ELECTRICAL
C0N
CORR
18A
MECHANICAL
19A
MECH
ELEV
MECAHNICAL
HEATER
EXAM ROOM
RADIOLOGY
SOUND
ULTRA
EXAM
32A
BATH
STAIR
OFFICE
X-RAY 1
UNEXCAVATED35
MECH
PROCESSING
FILM
37A
EQUIP
X-RAY 2
WAITING
CHANGE 38A
BATH
CLOSET
33A
EQUIP
OFFICE29
STOR
C0W
CORR
30A
MECH
STAIR
OFFICE
5A
OFFICE
PHYSICIAN
5C
CORR
5B
MECH
OFFICE
5D
ROOM
MECH
C0-B2
CORR
A01
HAC
A02
EQUIP
ELEV
C0-B1
CORR
A06
ELECTRICAL
A05A
MECHANICAL
A05B
STORAGE
ASB
STAIR
C0-B4
CORR
C0-B3
CORR
A10
SPACE
MECH.
E-A1
ELEV
A03
PHONE
36D
CONTROL
36E
EQUIP
36C
CT SCAN
CORRIDOR
36B
TOILET
36A
CHANGE
IMAGING
RT CLINIC
ABG LAB/
PFT LAB
HAC
LAB CLASSROOM
APAP/CPAP
EKG LAB
EDUCATION
RT CLINIC/
SOILED
CP
WORKROOM
STAFF
STORAGE
PROSTHETICS
OFFICE
LINEN
CLEAN
A60
OFFICE
A61
OFFICE
A62
OFFICE
A59
STORAGE
SUPPLY
A63
HEMA/COAG
CHEM/URINE/
A67
LOUNGE
CONF./
A68
BANK
BLOOD
A64
MICROBIOLOGY
A56
RECEP.
A58A
PHLEB
A58B
PHLEB
A58C
PHLEB
A58H
PHLEB
A58I
PHLEB
A58J
PHLEB
A58G
PHLEB
A58D
PHLEB
A58K
PHLEB
A58F
PHLEB
A58E
PHLEB
A57A
TOILET
A57B
TOILET
A57C
TOILET
A57C
COLLECTION
A66
LOCKER
A65
TOILET
C0-B1
WAITING
C0-H1
CORR
C0-H5
CORR
C0-C2
CORR C0-H2
CORR
C0-H4
CORR
C0-H3
CORR
A58
PHLEB
A58
PHLEB
C0-H6
CORR
C0-H7
CORR
2C
RECEPTION
WAITING
2A
MEN 2B
WOMEN
53A
STOR
E-01
ELEV
E-02
ELEV
16A
ROOM
MG
10B
HEALTH
OCC.
10A
HEALTH
OCC.
HEALTH
OCC.
30B
OFFICE
30C
OFFICE
8D
EQUIP
8I
MECHANICAL
8A
MRI
7F
INTAKE
7E
INTAKE
7D
HAC
7C
TOILET
7B
CHANGING
7A
CHANGING
COE
CORRIDOR
7G
FOYER
8H
VESTIBULE
8B
CONTROL
8C
HALL
8E
LINEN
8F
SOIL
8G
CLEAN
52.1183
52.1183 36.0000
AEC
CB1
DACC
GAC
LCC
CR
4D
BATH 4C
LOCKER
MALE
C0C
CORRIDOR
PHONE
LOBBY
HAC
HEALTH
OCC.
HAC
LOCKER
4A
LOCKER
FEMALE
4B
BATH
STOR
STAIR
12A
ELECTRICAL
MECHANICAL
MECHANICAL
ELECTRICAL
C0N
CORR
18A
MECHANICAL
19A
MECH
ELEV
MECAHNICAL
HEATER
EXAM ROOM
RADIOLOGY
SOUND
ULTRA
EXAM
32A
BATH
STAIR
OFFICE
X-RAY 1
UNEXCAVATED35
MECH
PROCESSING
FILM
37A
EQUIP
X-RAY 2
WAITING
CHANGE 38A
BATH
CLOSET
33A
EQUIP
OFFICE29
STOR
C0W
CORR
30A
MECH
STAIR
OFFICE
5A
OFFICE
PHYSICIAN
5C
CORR
5B
MECH
OFFICE
5D
ROOM
MECH
C0-B2
CORR
A01
HAC
A02
EQUIP
ELEV
C0-B1
CORR
A06
ELECTRICAL
A05A
MECHANICAL
A05B
STORAGE
ASB
STAIR
C0-B4
CORR
C0-B3
CORR
A10
SPACE
MECH.
E-A1
ELEV
A03
PHONE
36D
CONTROL
36E
EQUIP
36C
CT SCAN
CORRIDOR
36B
TOILET
36A
CHANGE
IMAGING
RT CLINIC
ABG LAB/
PFT LAB
HAC
LAB CLASSROOM
APAP/CPAP
EKG LAB
EDUCATION
RT CLINIC/
SOILED
CP
WORKROOM
STAFF
STORAGE
PROSTHETICS
OFFICE
LINEN
CLEAN
A60
OFFICE
A61
OFFICE
A62
OFFICE
A59
STORAGE
SUPPLY
A63
HEMA/COAG
CHEM/URINE/
A67
LOUNGE
CONF./
A68
BANK
BLOOD
A64
MICROBIOLOGY
A56
RECEP.
A58A
PHLEB
A58B
PHLEB
A58C
PHLEB
A58H
PHLEB
A58I
PHLEB
A58J
PHLEB
A58G
PHLEB
A58D
PHLEB
A58K
PHLEB
A58F
PHLEB
A58E
PHLEB
A57A
TOILET
A57B
TOILET
A57C
TOILET
A57C
COLLECTION
A66
LOCKER
A65
TOILET
C0-B1
WAITING
C0-H1
CORR
C0-H5
CORR
C0-C2
CORR C0-H2
CORR
C0-H4
CORR
C0-H3
CORR
A58
PHLEB
A58
PHLEB
C0-H6
CORR
C0-H7
CORR
2C
RECEPTION
WAITING
2A
MEN 2B
WOMEN
53A
STOR
E-01
ELEV
E-02
ELEV
16A
ROOM
MG
10B
HEALTH
OCC.
10A
HEALTH
OCC.
HEALTH
OCC.
30B
OFFICE
30C
OFFICE
8D
EQUIP
8I
MECHANICAL
8A
MRI
7F
INTAKE
7E
INTAKE
7D
HAC
7C
TOILET
7B
CHANGING
7A
CHANGING
COE
CORRIDOR
7G
FOYER
8H
VESTIBULE
8B
CONTROL
8C
HALL
8E
LINEN
8F
SOIL
8G
CLEAN
1-TN400
1-TN401
A003
EXIST RM
005F
TELECOM ROOM
005D
MECH
005E
LOCKER
005C
CORRIDOR
A05C
TELECOM ROOM
A05A
MECH
LIMITS OF DATA CABLING
REPLACEMENT FROM
ROOM 005F
LIMITS OF DATA CABLING
REPLACEMENT FROM ROOM A05C
2V
2V
2D/2V
2V
E
E
E
E
4D
4D
E
E
2D/2V
2D/2V
4D
4D
E
E
E
E
WAP
WAP
E
E
WAP
WAP
E
E
4D
4D E
E 4D
4D
4D 4D
EE
E
E
WAP
E 4D 4D
2D/2V 2D/2V 2D/2V 3D/1V
E E
E E E E
4D
4D 4D
EE
E
E
WAP
C5 126"
2"
2"
WAP
WAP
WAP
WAP
WAP
WAP
E
E
E
E
E
E 4D 4D
4D
4D
4D 4D
4D 4D
4D 4D 4D 4D
4D4D
4D 4D
4D 4D 4D 4D 4D 4D 2D
2D
2D
4D4D
4D
4D
E E E E E E E E E
E
E
E
E E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
4D
4D
4D
4D
4D
4D 4D
4D
4D
4D
4D
6D 4D
4D
4D
4D
4D
4D
4D4D
E
E
E
E
E
E
E
E
E
E
E E
E E
E
E
E
EE E
2D/1V
2D/1V
2D/1V
2D/1V
2D
2D
2D
4D
4D
4D
6D
2D
4D4D
1V
4D
4D
4D
4D
4D 1V
E
E
E
E
E E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
4D E
WAP
WAP
WAP
WAP
WAP
WAP
E
E
E
E
E
E
2D
4D 2D
2D 1V
4D 2D
3D
E
E E
EE
E
E E
WAP
WAP
E
E
2D E
4D
4D
1V
4D
4D
1V
4D
4D
4D
4D
4D
4D
4D1V
4D
4D
4D
4D
4D
4D
4D
E
E
E
E
E
E
E
E
E
E
E
E
E
E E
E
E
E E
E E
4D 4D E E
4D
4D
3D/1V
3D/1V
2D/1V
2D/1V
2D/2V
E
E
E
E
E E
E
4D
4D
4D
4D
4D
4D
4D 4D
4D E
E E
E E
E
E
E
E
2"
2"
2"
2"
2"
2"
2"
2"2"
C5 126"
C4 126"
12"x4"
E E
"x
4"
12"x4"
"x 4"
"x
4"
"x
4"
"x
4"
12"x4" 12"x4"
12"x4"
"x
4"
12"x4"
"x
2"
E
2 2"
"x
4"
12"x4"
"x
4"
12"x4"
2"
2"
2"
C4
C4
C4
(2) 2" CONDUIT
1 A-SIDE, 1
SPARE
4" CONDUIT B-SIDE
(2) 2" CONDUIT TO A101
EMPTY 2" CONDUIT UP TO 2ND
FLOOR TR A216 (FOR A-SIDE)
NEED TO RUN A 2"
CONDUIT FOR A-SIDE.
2" 12"x4"
RECORD DOCUMENTS
No DATEREVISION
DRAWING TITLE
CHECKED BY
ST.CLOUD, MN 56303
VA MEDICAL CENTER
BUILDING No
LOCATION
DRAWING NO.DRAWN
DWG. OF
PROJECT TITLE
PLOT SCALE
PROJECT NO.
DATE:
CONSULTANT ARCHITECT/ENGINEER OF RECORD
FULLY
SPRINKLERED
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
-RECORD DOCUMENT-
June 21, 2024
This Record Document has been prepared based on
Designer of Record drawings with Contractor provided markups through the construction phase of the project at the direction of the VA.
While the construction information is believed to be reliable, Architect/Engineer cannot assure its accuracy, and is not responsible for the accuracy of this Record Document. Those relying on this Record
Document are advised to independently verify its accuracy before applying it for any purpose.
RECORD DOCUMENTS 06/21/24
B
IM
/2
.0
V A
S t C lo u d E
H R
M I n fr a s tr u c tu re U p g ra d e s /6
-2
.B
.T
R
.r v t
/4
/2
:2
:1
P
M
1-TN100
BASEMENT FLOOR PLAN -
TELECOMMUNICATIONS
EHRM INFRASTRUCTURE
UPGRADES
656‐21‐235
03/30/2022
KSB SSK
16305
SHEET NOTES:
1. CONTRACTOR TO PROVIDE NEW WIRE BASKET, AS NEEDED, TO MAINTAIN A 50% OR LESS FILL OF THE CABLE TRAY SYSTEM FOR THE FLOOR. THE NEW WIRE BASKET WILL MATCH THE SIZE AND DISTANCE, EITHER BESIDE OR BELOW THE EXISTING CABLE TRAY, TO MATCH THE EXISTING TELECOM CABLE TRAY.
2. PROVIDE JUNCTION BOX TO CONNECT FIBER CONDUIT ENTRY TO EXTEND CONDUIT PATHWAY TO THE NEW
TELECOM ROOM.
3. NEW B SIDE FIBER TO BE PULLED TO A03, USING CURRENT B SIDE ROUTE, THEN PULLED TO THE NEW TRS.
1/8" = 1'-0"1
BASEMENT FLOOR PLAN - TELECOMMUNICATIONS
N
0 8' 16'4'
GENERAL NOTES:
A. REFER TO GENERAL NOTES ON SHEET T000 FOR ADDITIONAL SCOPE.
FRIDGE
24X26
SCALE
COPIER
PRINTER
F R
O N
T
ENTRY
128A
RECEPTION
STAIR120
WAITING
STAIR
MAA
REGISTRATION
REGISTRATION168
EXAM
EXAM
STOR
WHCHR
LOBBY
ELEV
C1NC
CORR
127A
PHONE
MECH
128B
V.I.C.
128C
OUT
CHECK
STOR
C1WI
CORR
EXAM
EXAM
EXAM
EXAM
STATION
NURSE
173A
MED
EXAM
EXAM165
NURSING
EXAM
EXAM
NURSING
160B
BATH
INTAKE
PROCEDURE
SPECIAL
160A
UTILITY
CLEAN
173B
INTAKE
C1WH
CORR
C1WG
CORR
ELEC
MECH
EXAM
INT
C1WF
CORR
EXAM
INT
EXAM
INT
EXAM
INT
EXAM
INT
EXAM
INT
STAIR
C1WJ
CORR
COPY
CONSULT
PHARM.
STAIR
C1WA
CORR
MALE
FEMALE
CHASE
WAITING
BATH
UTILITY
CLEAN
EXAM
EXAM
CONSULT
PHARM.
C1WD
CORR
EXAM
EXAM
UTILITY
CLEAN
CHART
NURSE/
OFFICE
NURSE
EXAM
EXAM
C1WB
CORR
EXAM
EXAM
EXAM
NURSING
EXAM
WAITING
152A
MED
C1WE
CORR
C1WC
CORR
ROOF
A111
VEST
TRIAGE
A110
OFFICE A109
EXAM
E-A1
ELEV
A-1
STAIR A108
STAFF
A107A
DICTATION
A107B
CLOSET
C0-2
CORR
A106
HAC A105
CONSULT
PHARM
A104
NURSING
A103
NURSING
C0-1
CORRIDOR
A127A
CHECK-OUT
A126
INTAKE
A125
EXAM
CO-5
CORR
A124
EXAM
A123
EXAM
A122
EXAM
A121
OFFICE
A120
UTIL
SOILED
A118
ALCOVE
NURSE
A117
MED
CO-3
CORRIDOR
A112
EXAM
A113
EXAM
A116
UTILITY
SOILED
A119
EXAM
C0-4
CORRIDOR
A114
EXAM
A115
EXAM
AS1
STAIR
A141
STORAGE
EQUIP.
A140
EXAM
A139
EXAM
A138
EXAM
A137
DICTATION
A136
EXAM
A135
EXAM
A134
OUT
CHECK
A133
PASSAGE
STAFF A132
STORAGE
CO-7
CORRIDOR
A142
STORAGE
CLEAN
A143
EXAM
A144
EXAM
A145
EXAM CO-3
CORR
A146
EXAM
A147
STORAGE
A127D
ROOM
MED A127C
STATION
NURSE
A127B
IN
CHECKCO-6
CORR
A131
MEN A130
CHASE
A129
WAITING
A128
WAITING
A102B
CHASE
A102A
WOMEN
A101
COMM
TELE-
A112A
LINEN
REGISTRATION
INTAKE
INTAKE
STAFF
111A
M.O.D.
111C
EQUIPMENT
SUPPLY
111D
PURPOSE
MULTI
111B
TOILET
WAITING
101A
TOILET
UNISEX
HAC
UTILITIES
CLEAN
UTILITIES
SOILED
LOCKERS
MED
STATION
NURSE
108A
TELEMETRY
108B
TELEMETRY
108C
TOILET
108D
TELEMETRY
108E
TELEMETRY
109C
TELEMETRY
PROCEDURE/
109B
TELEMETRY
109A
TELEMETRY
109D
TOILET
AMBULANCE
C1EC
CORRIDOR
C1EA
CORRIDOR
NOUR
C1ED
CORRIDOR
111E
CAMERAS
HOLDING/
111F
ANTE
HOLDING/
TOILET
C1EB
CORRIDOR
TOILET
STAFF
E-01
ELEV
E-02
ELEV
A117A
UNISEX
ROOF
FLAT
DECONTAM
1-TN402
LIMITS OF DATA CABLING
REPLACEMENT FROM ROOM A101
3D
3D
3D
3D
3D
3D
3D
3D 3D
4D
3D
3D
3D 3D
3D
3D
3D
3D
3D
3D
3D3D 4D
3D
2D
4D
WAP
WAP
WAP
WAP
WAP
WAP
WAP
4D 3D
3D
3D
3D
3D4V
1D
2D/2V
2D/2V
2D
2D/2V2D/2V 2V
4D
2D/3V
WAP
WAP
WAP
4D4D5D
2D
2D
2D
2D/2V
3D
6D5D
3D3D3D 3D
3D
3D/1V1D/2V
4D
2V 2D
2D
3D
WAP
WAP
WAP
WAP
4D
4D 4D
4D
1D
4D
4D
4D
4D 4D
4D
4D
4D
4D 4D 4D
4D
4D
4D
4D
4D4D
4D
4D
4D
4D
5D4D
4D
4D
4D
4D
4D
4D
4D
4D
WAP
WAP
WAP
WAP
WAPWAP
3D 3D3D
3D
3D2D 3D
3D
3D
4D
3D
3D
3D 3D
3D
3D
2D
2D
2D
2V2V
2V
2V
2V
2V
1D1D 1D
1D
1D
1D
1D
1D 1D
1D
2D/2V
4D
4D
WAP
3D 3D
1D
1D
2D/2V
2D/2V2D/2V 4D4D
4D4D
4D
4D
4D
4D 4D
4D
4D
4D
3D
4D
4D
2V
D
2V 2V 2V
D
2V
3D
2V
D
2V 2V
D
2V
D
D
2V
2V
2V
D
D
2V
2D
3V
WAP
WAP
WAP
WAP
WAP
D
D
2V
2V
D 2V
2V
D
2V
D
D D
2V
2V
2D/V
2D
D
4D
2D
2V
2D
2V D
2V
D
2VD
D
D
D
2V D D 2V
D
4D 2V
2V
E
E E E E
E
E
E E
E
E
E
EE
E
E E
E E
E
E
E
E
EE
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E E
E
E E E
E
E
E
E
E E
E E E E E
E
E E
E
E
E
EE
E E E E
E
E
E
E
E
E
E
E E
E
E
E
E
E
E E E
E
E
E
E E
E
E
E
E
E
E
E
E
E E E
E
E
E
E E E
E
E
E
E
E
E
E
E
EE
E
EE
EE
E
E E
E
E E
EE
E
E E
E
EE
E E
E E
E
E
E E
E
E
E
E
E
E
E
E
E
E
E
E
EE
E
E
E
E
E
E
E
E E
E
E
E
E
E
E E
E
E
E
E E
E
E
E
E
E
E
E
E
E
E
E E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E
E E
E E
E E
E
E
E E
E
E
E
E
E
E
E EEE
E
E E
E
E E
E E
E
E
E
E
E E
E
2V
D
E
E
2V E
D 2V
2V E
EE
E
E
12"x4"
"x
4"
"x
4"
12"x4"
12"x4"
12"x4"
"x
4"12 "x
4"
12"x4"
6" x4
"x
2"
12"x2"
12"x2"
6" x4
"x
2"
12"x4"
12"x4"
"x
4"
12"x4"
12"x4"
"x
4"
2" C
DOWN
2" C
UP
1"
C4
C4
C4
B-SIDE TO A216
4"
E
E E
E E
E E
E
E
E
E
E
4"4"4"
E
E
E
2"
4"4"4"
12"x4"
RECORD DOCUMENTS
No DATEREVISION
DRAWING TITLE
CHECKED BY
ST.CLOUD, MN 56303
VA MEDICAL CENTER
BUILDING No
LOCATION
DRAWING NO.DRAWN
DWG. OF
PROJECT TITLE
PLOT SCALE
PROJECT NO.
DATE:
CONSULTANT ARCHITECT/ENGINEER OF RECORD
FULLY
SPRINKLERED
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
-RECORD DOCUMENT-
June 21, 2024
This Record Document has been prepared based on
Designer of Record drawings with Contractor provided markups through the construction phase of the project at the direction of the VA.
While the construction information is believed to be reliable, Architect/Engineer cannot assure its accuracy, and is not responsible for the accuracy of this Record Document. Those relying on this Record
Document are advised to independently verify its accuracy before applying it for any purpose.
RECORD DOCUMENTS 06/21/24
B
IM
/2
.0
V A
S t C lo u d E
H R
M I n fr a s tr u c tu re U p g ra d e s /6
-2
.B
.T
R
.r v t
/4
/2
:2
:1
P
M
1-TN110
FIRST FLOOR PLAN -
TELECOMMUNICATIONS
EHRM INFRASTRUCTURE
UPGRADES
656‐21‐235
03/30/2022
KSB SSK
16305
1/8" = 1'-0"
FIRST FLOOR PLAN - TELECOMMUNICATIONS
N
0 8' 16'4'
SHEET NOTES:
1. CONTRACTOR TO PROVIDE NEW WIRE BASKET, AS NEEDED, TO MAINTAIN A 50% OR LESS FILL OF THE CABLE TRAY SYSTEM FOR THE FLOOR. THE NEW WIRE BASKET WILL MATCH THE SIZE AND DISTANCE, EITHER BESIDE OR BELOW THE EXISTING CABLE TRAY, TO MATCH THE EXISTING TELECOM CABLE TRAY.
2. PROVIDE JUNCTION BOX TO CONNECT EXISTING FIBER CONDUIT TO EXTEND CONDUIT PATHWAY TO THE
NEW TELECOM ROOM.
3. NEW B SIDE FIBER TO BE PULLED TO 127, USING CURRENT B SIDE ROUTE, THEN PULLED TO THE NEW TRS.
INSIDE dgsf = 26,040 S.F.
-O
-V
DN
UP
DN
UP
INSIDE dgsf = 26,040 S.F.
A -O
-V
DN
UP
DN
UP
1-TN403
A216
EXIST RM
A200
TELECOM ROOM
EXIST RM
A225
EXIST RM
LIMITS OF DATA CABLING
REPLACEMENT FROM
ROOM A200
HORIZONTAL AND
VERTICAL CABLE ROUTES
TO A200
WAP
4D
4D
4D
4D
4D
4D 4D
4D 4D
4D
6D 1D
6D 1D
E
E E
E
E E
E
E
E
EE
EE
E
4D
4D
1D
E
E
E
4D
6D 1D
4D
4D
4D 4D
4D 4D
4D
4D
3D/1V 4D
4D
4D
4D
4D
4D
4D
2D4D2D4D
E
E E
E
E
E
E
E E
E
E E E E
E
E E
E
E E
E
E
E
E
E
E
E
E
E
E
E
E
E E
E
E
E
4D
4D
4D
1D 4D
1V E
E
E
E E E
4D
4D
4D
4D
4D E
E
E
E
E
3D/1V
4D
4D 4D
4D
4D
E
E
E
E
EE
4D
4D
4D
4D
4D
4D
E
E
E
E
E
E
4D
4D
4D
4D
4D
4D 4D 4D
4D
4D 4D
E E EEE
E
E
E
E
E
E
WAP
WAP
WAP
WAP
WAP
WAP
WAP
WAP
WAP
WAP
WAP
WAP
WAP
2"
2"
2"
4D
4D
4D
4D
E
E
E
E
WAP
E
WAP
WAP
WAP
WAP
WAP
WAP
WAP
E
E
E
E
E
E
E 4D
4D
4D
4D 4D
4D
D E
E
E
E
E
E E
3D
4D
4D 4D
4D
4D 4D 4D 4D 4D 4D E E E E E E
E EE
E E
4D
3D E
E
1V
2D
1V
1V
E
E
E
E
WAP
E
4D E
E
E E E
"x
4"
12"x4"
"x
4"
"x 4"
E
E
E
E E
EE
E E
12"x4" 12"x4"
12"x4"12"x4"
"x
4"
"x
4"
E
EE
E
"x
4"
E
E
12"x4"
"x
4"
12"x4"
"x
4"
12"x4"
"x
4"
C4 126"
C4
C4
C4
C4
C4 126"
RECORD DOCUMENTS
No DATEREVISION
DRAWING TITLE
CHECKED BY
ST.CLOUD, MN 56303
VA MEDICAL CENTER
BUILDING No
LOCATION
DRAWING NO.DRAWN
DWG. OF
PROJECT TITLE
PLOT SCALE
PROJECT NO.
DATE:
CONSULTANT ARCHITECT/ENGINEER OF RECORD
FULLY
SPRINKLERED
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
-RECORD DOCUMENT-
June 21, 2024
This Record Document has been prepared based on
Designer of Record drawings with Contractor provided markups through the construction phase of the project at the direction of the VA.
While the construction information is believed to be reliable, Architect/Engineer cannot assure its accuracy, and is not responsible for the accuracy of this Record Document. Those relying on this Record
Document are advised to independently verify its accuracy before applying it for any purpose.
RECORD DOCUMENTS 06/21/24
B
IM
/2
.0
V A
S t C lo u d E
H R
M I n fr a s tr u c tu re U p g ra d e s /6
-2
.B
.T
R
.r v t
/4
/2
:2
:1
P
M
1-TN120
SECOND FLOOR PLAN -
TELECOMMUNICATIONS
EHRM INFRASTRUCTURE
UPGRADES
656‐21‐235
03/30/2022
KSB SSK
16305
1/8" = 1'-0"1
SECOND FLOOR PLAN - TELECOMMUNICATIONS
N
0 8' 16'4'
SHEET NOTES:
1. CONTRACTOR TO PROVIDE NEW WIRE BASKET, AS NEEDED, TO MAINTAIN A 50% OR LESS FILL OF
THE CABLE TRAY SYSTEM FOR THE FLOOR. THE NEW WIRE BASKET WILL MATCH THE SIZE AND
DISTANCE, EITHER BESIDE OR BELOW THE EXISTING CABLE TRAY, TO MATCH THE EXISTING
TELECOM CABLE TRAY.
2. PROVIDE JUNCTION BOX TO CONNECT EXISTING FIBER CONDUIT TO EXTEND CONDUIT PATHWAY
TO THE NEW TELECOM ROOM.
3. NEW B SIDE FIBER TO BE PULLED TO 229, USING CURRENT B SIDE ROUTE, THEN PULLED TO THE
NEW TRS.
ATTIC ROOF
OFFICE
PURPOSE
MULTI
STAIR
PHONE
OFFICE
OFFICE
OFFICE
BATH
HAC
OFFICE
MED. DIR.
ACCESS
ATTIC
C3C
CORRIDOR
OFFICE
DN
STAIR A
CONVECTORCONVECTOR
CONVECTOR CONVECTOR CONVECTOR CONVECTORCONVECTOR
ATTIC ROOF
OFFICE
PURPOSE
MULTI
STAIR
PHONE
OFFICE
OFFICE
OFFICE
BATH
HAC
OFFICE
MED. DIR.
ACCESS
ATTIC
C3C
CORRIDOR
OFFICE
DN
STAIR A
LIMITS OF DATA CABLING
REPLACEMENT FROM
ROOM A200
HORIZONTAL AND
VERTICAL CABLE ROUTES
TO A200
C1 126"
F1
12" LADDER
E EE E
8"x2"8"x2"
8"x2"
RECORD DOCUMENTS
No DATEREVISION
DRAWING TITLE
CHECKED BY
ST.CLOUD, MN 56303
VA MEDICAL CENTER
BUILDING No
LOCATION
DRAWING NO.DRAWN
DWG. OF
PROJECT TITLE
PLOT SCALE
PROJECT NO.
DATE:
CONSULTANT ARCHITECT/ENGINEER OF RECORD
FULLY
SPRINKLERED
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
-RECORD DOCUMENT-
June 21, 2024
This Record Document has been prepared based on
Designer of Record drawings with Contractor provided markups through the construction phase of the project at the direction of the VA.
While the construction information is believed to be reliable, Architect/Engineer cannot assure its accuracy, and is not responsible for the accuracy of this Record Document. Those relying on this Record
Document are advised to independently verify its accuracy before applying it for any purpose.
RECORD DOCUMENTS 06/21/24
B
IM
/2
.0
V A
S t C lo u d E
H R
M I n fr a s tr u c tu re U p g ra d e s /6
-2
.B
.T
R
.r v t
/4
/2
:2
:1
P
M
1-TN130
THIRD FLOOR PLAN -
TELECOMMUNICATIONS
EHRM INFRASTRUCTURE
UPGRADES
656‐21‐235
03/30/2022
KSB SSK
16305
1/8" = 1'-0"
THIRD FLOOR PLAN - TELECOMMUNICATIONS
N
0 8' 16'4'
SHEET NOTES:
1. PROVIDE NEW FLOOR PENETRATION, VERTICAL CABLE TRAY, HORIZONTAL CABLE TRAY, AND WALL SLEEVE ASSEMBLY TO ACCOMMODATE ROUTING OF HORIZONTAL CABLING FROM SOURCE COMMUNICATIONS ROOM
LOCATED ON SECOND FLOOR.
5 2.1183 5 2.1183 3 6.0000
AEC
CB1
DACC
GAC
LCC
C R
4D
BATH 4C
LOCKER
MALE
C0C
CORRIDOR
PHONE
LOBBY
HAC
HEALTH
OCC.
HAC
LOCKER
4A
LOCKER
FEMALE
4B
BATH
STOR
STAIR
12A
ELECTRICAL
MECHANICAL
MECHANICAL
ELECTRICAL
C0N
CORR
18A
MECHANICAL
19A
MECH
ELEV
MECAHNICAL
HEATER
EXAM ROOM
RADIOLOGY
SOUND
ULTRA
EXAM
32A
BATH
STAIR
OFFICE
X-RAY 1
UNEXCAVATED35
MECH
PROCESSING
FILM
37A
EQUIP
X-RAY 2
WAITING
CHANGE 38A
BATH
CLOSET
33A
EQUIP
OFFICE29
STOR
C0W
CORR
30A
MECH
STAIR
OFFICE
5A
OFFICE
PHYSICIAN
5C
CORR
5B
MECH
OFFICE
5D
ROOM
MECH
C0-B2
CORR
A01
HAC
A02
EQUIP
ELEV
C0-B1
CORR
A06
ELECTRICAL
A05A
MECHANICAL
A05B
STORAGE
ASB
STAIR
C0-B4
CORR
C0-B3
CORR
A10
SPACE
MECH.
E-A1
ELEV
A03
PHONE
36D
CONTROL
36E
EQUIP
36C
CT SCAN
CORRIDOR
36B
TOILET
36A
CHANGE
IMAGING
RT CLINIC
ABG LAB/
PFT LAB
HAC
LAB CLASSROOM
APAP/CPAP
EKG LAB
EDUCATION
RT CLINIC/
SOILED
CP
WORKROOM
STAFF
STORAGE
PROSTHETICS
OFFICE
LINEN
CLEAN
A60
OFFICE
A61
OFFICE
A62
OFFICE
A59
STORAGE
SUPPLY
A63
HEMA/COAG
CHEM/URINE/
A67
LOUNGE
CONF./
A68
BANK
BLOOD
A64
MICROBIOLOGY
A56
RECEP.
A58A
PHLEB
A58B
PHLEB
A58C
PHLEB
A58H
PHLEB
A58I
PHLEB
A58J
PHLEB
A58G
PHLEB
A58D
PHLEB
A58K
PHLEB
A58F
PHLEB
A58E
PHLEB
A57A
TOILET
A57B
TOILET
A57C
TOILET
A57C
COLLECTION
A66
LOCKER
A65
TOILET
C0-B1
WAITING
C0-H1
CORR
C0-H5
CORR
C0-C2
CORR C0-H2
CORR
C0-H4
CORR
C0-H3
CORR
A58
PHLEB
A58
PHLEB
C0-H6
CORR
C0-H7
CORR
2C
RECEPTION
WAITING
2A
MEN 2B
WOMEN
53A
STOR
E-01
ELEV
E-02
ELEV
16A
ROOM
MG
10B
HEALTH
OCC.
10A
HEALTH
OCC.
HEALTH
OCC.
30B
OFFICE
30C
OFFICE
8D
EQUIP
8I
MECHANICAL
8A
MRI
7F
INTAKE
7E
INTAKE
7D
HAC
7C
TOILET
7B
CHANGING
7A
CHANGING
COE
CORRIDOR
7G
FOYER
8H
VESTIBULE
8B
CONTROL
8C
HALL
8E
LI NEN
8F
SOI L
8G
CL EA N
5 2.1183 5 2.1183 3 6.0000
AEC
CB1
DACC
GAC
LCC
C R
4D
BATH 4C
LOCKER
MALE
C0C
CORRIDOR
PHONE
LOBBY
HAC
HEALTH
OCC.
HAC
LOCKER
4A
LOCKER
FEMALE
4B
BATH
STOR
STAIR
12A
ELECTRICAL
MECHANICAL
MECHANICAL
ELECTRICAL
C0N
CORR
18A
MECHANICAL
19A
MECH
ELEV
MECAHNICAL
HEATER
EXAM ROOM
RADIOLOGY
SOUND
ULTRA
EXAM
32A
BATH
STAIR
OFFICE
X-RAY 1
UNEXCAVATED35
MECH
PROCESSING
FILM
37A
EQUIP
X-RAY 2
WAITING
CHANGE 38A
BATH
CLOSET
33A
EQUIP
OFFICE29
STOR
C0W
CORR
30A
MECH
STAIR
OFFICE
5A
OFFICE
PHYSICIAN
5C
CORR
5B
MECH
OFFICE
5D
ROOM
MECH
C0-B2
CORR
A01
HAC
A02
EQUIP
ELEV
C0-B1
CORR
A06
ELECTRICAL
A05A
MECHANICAL
A05B
STORAGE
ASB
STAIR
C0-B4
CORR
C0-B3
CORR
A10
SPACE
MECH.
E-A1
ELEV
A03
PHONE
36D
CONTROL
36E
EQUIP
36C
CT SCAN
CORRIDOR
36B
TOILET
36A
CHANGE
IMAGING
RT CLINIC
ABG LAB/
PFT LAB
HAC
LAB CLASSROOM
APAP/CPAP
EKG LAB
EDUCATION
RT CLINIC/
SOILED
CP
WORKROOM
STAFF
STORAGE
PROSTHETICS
OFFICE
LINEN
CLEAN
A60
OFFICE
A61
OFFICE
A62
OFFICE
A59
STORAGE
SUPPLY
A63
HEMA/COAG
CHEM/URINE/
A67
LOUNGE
CONF./
A68
BANK
BLOOD
A64
MICROBIOLOGY
A56
RECEP.
A58A
PHLEB
A58B
PHLEB
A58C
PHLEB
A58H
PHLEB
A58I
PHLEB
A58J
PHLEB
A58G
PHLEB
A58D
PHLEB
A58K
PHLEB
A58F
PHLEB
A58E
PHLEB
A57A
TOILET
A57B
TOILET
A57C
TOILET
A57C
COLLECTION
A66
LOCKER
A65
TOILET
C0-B1
WAITING
C0-H1
CORR
C0-H5
CORR
C0-C2
CORR C0-H2
CORR
C0-H4
CORR
C0-H3
CORR
A58
PHLEB
A58
PHLEB
C0-H6
CORR
C0-H7
CORR
2C
RECEPTION
WAITING
2A
MEN 2B
WOMEN
53A
STOR
E-01
ELEV
E-02
ELEV
16A
ROOM
MG
10B
HEALTH
OCC.
10A
HEALTH
OCC.
HEALTH
OCC.
30B
OFFICE
30C
OFFICE
8D
EQUIP
8I
MECHANICAL
8A
MRI
7F
INTAKE
7E
INTAKE
7D
HAC
7C
TOILET
7B
CHANGING
7A
CHANGING
COE
CORRIDOR
7G
FOYER
8H
VESTIBULE
8B
CONTROL
8C
HALL
8E
LI NEN
8F
SOI L
8G
CL EA N
RECORD DOCUMENTS
No DATEREVISION
DRAWING TITLE
CHECKED BY
ST.CLOUD, MN 56303
VA MEDICAL CENTER
BUILDING No
LOCATION
DRAWING NO.DRAWN
DWG. OF
PROJECT TITLE
PLOT SCALE
PROJECT NO.
DATE:
CONSULTANT ARCHITECT/ENGINEER OF RECORD
FULLY
SPRINKLERED
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
-RECORD DOCUMENT-
June 21, 2024
This Record Document has been prepared based on
Designer of Record drawings with Contractor provided markups through the construction phase of the project at the direction of the VA.
While the construction information is believed to be reliable, Architect/Engineer cannot assure its accuracy, and is not responsible for the accuracy of this Record Document. Those relying on this Record
Document are advised to independently verify its accuracy before applying it for any purpose.
RECORD DOCUMENTS 06/21/24
B
IM
/2
.0
V A
S t C lo u d E
H R
M I n fr a s tr u c tu re U p g ra d e s /6
-2
.B
.T
R
.r v t
/4
/2
:2
:1
P
M
1-TN200
BASEMENT FLOOR PLAN -
TELECOM - CABLE DISTANCE
EHRM INFRASTRUCTURE
UPGRADES
656‐21‐235
03/30/2022
KSB SSK
16305
1" = 30'-0"
BASEMENT FLOOR PLAN - TELECOMMUNICATIONS - CABLE DISTANCE
N
0 30' 60'15'
FRIDGE
24X26
SCALE
COPIER
PRINTER
F R
O N
T
ENTRY
128A
RECEPTION
STAIR120
WAITING
STAIR
MAA
REGISTRATION
REGISTRATION168
EXAM
EXAM
STOR
WHCHR
LOBBY
ELEV
C1NC
CORR
127A
PHONE
MECH
128B
V.I.C.
128C
OUT
CHECK
STOR
C1WI
CORR
EXAM
EXAM
EXAM
EXAM
STATION
NURSE
173A
MED
EXAM
EXAM165
NURSING
EXAM
EXAM
NURSING
160B
BATH
INTAKE
PROCEDURE
SPECIAL
160A
UTILITY
CLEAN
173B
INTAKE
C1WH
CORR
C1WG
CORR
ELEC
MECH
EXAM
INT
C1WF
CORR
EXAM
INT
EXAM
INT
EXAM
INT
EXAM
INT
EXAM
INT
STAIR
C1WJ
CORR
COPY
CONSULT
PHARM.
STAIR
C1WA
CORR
MALE
FEMALE
CHASE
WAITING
BATH
UTILITY
CLEAN
EXAM
EXAM
CONSULT
PHARM.
C1WD
CORR
EXAM
EXAM
UTILITY
CLEAN
CHART
NURSE/
OFFICE
NURSE
EXAM
EXAM
C1WB
CORR
EXAM
EXAM
EXAM
NURSING
EXAM
WAITING
152A
MED
C1WE
CORR
C1WC
CORR
ROOF
A111
VEST
TRIAGE
A110
OFFICE A109
EXAM
E-A1
ELEV
A-1
STAIR A108
STAFF
A107A
DICTATION
A107B
CLOSET
C0-2
CORR
A106
HAC A105
CONSULT
PHARM
A104
NURSING
A103
NURSING
C0-1
CORRIDOR
A127A
CHECK-OUT
A126
INTAKE
A125
EXAM
CO-5
CORR
A124
EXAM
A123
EXAM
A122
EXAM
A121
OFFICE
A120
UTIL
SOILED
A118
ALCOVE
NURSE
A117
MED
CO-3
CORRIDOR
A112
EXAM
A113
EXAM
A116
UTILITY
SOILED
A119
EXAM
C0-4
CORRIDOR
A114
EXAM
A115
EXAM
AS1
STAIR
A141
STORAGE
EQUIP.
A140
EXAM
A139
EXAM
A138
EXAM
A137
DICTATION
A136
EXAM
A135
EXAM
A134
OUT
CHECK
A133
PASSAGE
STAFF A132
STORAGE
CO-7
CORRIDOR
A142
STORAGE
CLEAN
A143
EXAM
A144
EXAM
A145
EXAM CO-3
CORR
A146
EXAM
A147
STORAGE
A127D
ROOM
MED A127C
STATION
NURSE
A127B
IN
CHECKCO-6
CORR
A131
MEN A130
CHASE
A129
WAITING
A128
WAITING
A102B
CHASE
A102A
WOMEN
A101
COMM
TELE-
A112A
LINEN
REGISTRATION
INTAKE
INTAKE
STAFF
111A
M.O.D.
111C
EQUIPMENT
SUPPLY
111D
PURPOSE
MULTI
111B
TOILET
WAITING
101A
TOILET
UNISEX
HAC
UTILITIES
CLEAN
UTILITIES
SOILED
LOCKERS
MED
STATION
NURSE
108A
TELEMETRY
108B
TELEMETRY
108C
TOILET
108D
TELEMETRY
108E
TELEMETRY
109C
TELEMETRY
PROCEDURE/
109B
TELEMETRY
109A
TELEMETRY
109D
TOILET
AMBULANCE
C1EC
CORRIDOR
C1EA
CORRIDOR
NOUR
C1ED
CORRIDOR
111E
CAMERAS
HOLDING/
111F
ANTE
HOLDING/
TOILET
C1EB
CORRIDOR
TOILET
STAFF
E-01
ELEV
E-02
ELEV
A117A
UNISEX
ROOF
FLAT
DECONTAM
RECORD DOCUMENTS
No DATEREVISION
DRAWING TITLE
CHECKED BY
ST.CLOUD, MN 56303
VA MEDICAL CENTER
BUILDING No
LOCATION
DRAWING NO.DRAWN
DWG. OF
PROJECT TITLE
PLOT SCALE
PROJECT NO.
DATE:
CONSULTANT ARCHITECT/ENGINEER OF RECORD
FULLY
SPRINKLERED
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
-RECORD DOCUMENT-
June 21, 2024
This Record Document has been prepared based on
Designer of Record drawings with Contractor provided markups through the construction phase of the project at the direction of the VA.
While the construction information is believed to be reliable, Architect/Engineer cannot assure its accuracy, and is not responsible for the accuracy of this Record Document. Those relying on this Record
Document are advised to independently verify its accuracy before applying it for any purpose.
RECORD DOCUMENTS 06/21/24
B
IM
/2
.0
V A
S t C lo u d E
H R
M I n fr a s tr u c tu re U p g ra d e s /6
-2
.B
.T
R
.r v t
/4
/2
:2
:1
P
M
1-TN210
FIRST FLOOR PLAN -
TELECOM - CABLE DISTANCE
EHRM INFRASTRUCTURE
UPGRADES
656‐21‐235
03/30/2022
KSB SSK
16305
1" = 30'-0"
FIRST FLOOR PLAN - TELECOMMUNICATIONS - CABLE DISTANCE
INSIDE dgsf = 26,040 S.F.
-O
-V
DN
UP
DN
UP
INSIDE dgsf = 26,040 S.F.
A -O
-V
DN
UP
DN
UP
RECORD DOCUMENTS
No DATEREVISION
DRAWING TITLE
CHECKED BY
ST.CLOUD, MN 56303
VA MEDICAL CENTER
BUILDING No
LOCATION
DRAWING NO.DRAWN
DWG. OF
PROJECT TITLE
PLOT SCALE
PROJECT NO.
DATE:
CONSULTANT ARCHITECT/ENGINEER OF RECORD
FULLY
SPRINKLERED
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
-RECORD DOCUMENT-
June 21, 2024
This Record Document has been prepared based on
Designer of Record drawings with Contractor provided markups through the construction phase of the project at the direction of the VA.
While the construction information is believed to be reliable, Architect/Engineer cannot assure its accuracy, and is not responsible for the accuracy of this Record Document. Those relying on this Record
Document are advised to independently verify its accuracy before applying it for any purpose.
RECORD DOCUMENTS 06/21/24
B
IM
/2
.0
V A
S t C lo u d E
H R
M I n fr a s tr u c tu re U p g ra d e s /6
-2
.B
.T
R
.r v t
/4
/2
:2
:2
P
M
1-TN220
SECOND FLOOR PLAN -
TELECOM - CABLE DISTANCE
EHRM INFRASTRUCTURE
UPGRADES
656‐21‐235
03/30/2022
KSB SSK
16305
1" = 30'-0"
SECOND FLOOR PLAN - TELECOMMUNICATIONS - CABLE DISTANCE
ATTIC ROOF
OFFICE
PURPOSE
MULTI
STAIR
PHONE
OFFICE
OFFICE
OFFICE
BATH
HAC
OFFICE
MED. DIR.
ACCESS
ATTIC
C3C
CORRIDOR
OFFICE
DN
STAIR A
CONVECTORCONVECTOR
CONVECTOR CONVECTOR CONVECTOR CONVECTORCONVECTOR
ATTIC ROOF
OFFICE
PURPOSE
MULTI
STAIR
PHONE
OFFICE
OFFICE
OFFICE
BATH
HAC
OFFICE
MED. DIR.
ACCESS
ATTIC
C3C
CORRIDOR
OFFICE
DN
STAIR A
RECORD DOCUMENTS
No DATEREVISION
DRAWING TITLE
CHECKED BY
ST.CLOUD, MN 56303
VA MEDICAL CENTER
BUILDING No
LOCATION
DRAWING NO.DRAWN
DWG. OF
PROJECT TITLE
PLOT SCALE
PROJECT NO.
DATE:
CONSULTANT ARCHITECT/ENGINEER OF RECORD
FULLY
SPRINKLERED
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
-RECORD DOCUMENT-
June 21, 2024
This Record Document has been prepared based on
Designer of Record drawings with Contractor provided markups through the construction phase of the project at the direction of the VA.
While the construction information is believed to be reliable, Architect/Engineer cannot assure its accuracy, and is not responsible for the accuracy of this Record Document. Those relying on this Record
Document are advised to independently verify its accuracy before applying it for any purpose.
RECORD DOCUMENTS 06/21/24
B
IM
/2
.0
V A
S t C lo u d E
H R
M I n fr a s tr u c tu re U p g ra d e s /6
-2
.B
.T
R
.r v t
/4
/2
:2
:2
P
M
1-TN230
THIRD FLOOR PLAN -
TELECOM - CABLE DISTANCE
EHRM INFRASTRUCTURE
UPGRADES
656‐21‐235
03/30/2022
KSB SSK
16305
1" = 30'-0"
THIRD FLOOR PLAN - TELECOMMUNICATIONS - CABLE DISTANCE
52. 1183
52. 1183
4B
5C
CORR
MECH
52. 1183
52. 1183
4B
5C
CORR
MECH
NURSING A102A
A101
COMM
TELE-
NURSING A102A
A101
COMM
TELE-
C
C
A C
C
A03
PHONE
A03
PHONE
C
AC
C
RECEPTION
127A
PHONE
MECH
BAS
E
TW
D
D
R
E
SP
E
DATA RACKS
E
A200
TELECOM
ROOM
E
R E
E
DDD
LOW V CABINET
DATA
RACKS
D
E
E
TW
TW
DATA
RACKS
CABLE
TRAY
R
R
E
A003
EXIST RM
E
R
D
E
R
E
D
E
LOW V
CABINET
TW
CABLE
TRAY
DATA
RACK
A225
EXIST RM
D
DATA RACK
D
D
E
E
R E
E
IL1-4
IL
1-
1A
TW
DATA
RACKS
CABLE
TRAY
RECORD DOCUMENTS
No DATEREVISION
DRAWING TITLE
CHECKED BY
ST.CLOUD, MN 56303
VA MEDICAL CENTER
BUILDING No
LOCATION
DRAWING NO.DRAWN
DWG. OF
PROJECT TITLE
PLOT SCALE
PROJECT NO.
DATE:
CONSULTANT ARCHITECT/ENGINEER OF RECORD
FULLY
SPRINKLERED
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
-RECORD DOCUMENT-
June 21, 2024
This Record Document has been prepared based on
Designer of Record drawings with Contractor provided markups through the construction phase of the project at the direction of the VA.
While the construction information is believed to be reliable, Architect/Engineer cannot assure its accuracy, and is not responsible for the accuracy of this Record Document. Those relying on this Record
Document are advised to independently verify its accuracy before applying it for any purpose.
RECORD DOCUMENTS 06/21/24
B
IM
/2
.0
V A
S t C lo u d E
H R
M I n fr a s tr u c tu re U p g ra d e s /6
-2
.B
.T
R
.r v t
/4
/2
:2
:2
P
M
1-TN300
ENLARGED PLANS -
TELECOMMUNICATIONS -
DEMO
EHRM INFRASTRUCTURE
UPGRADES
656‐21‐235
03/30/2022
KSB SSK
16305
1/4" = 1'-0"
ENLARGED PLAN - TR A05C - TELECOM - DEMO
1/4" = 1'-0"
ENLARGED PLAN - TR 005F - TELECOM - DEMO
1/4" = 1'-0"
ENLARGED PLAN - TR A101 - TELECOM - DEMO
0 4' 8'2'
0 4' 8'2'0 4' 8'2'
0 4' 8'2'
N
N N
N
1/4" = 1'-0"
ENLARGED PLAN - TR A200 & A216 - TELECOM - DEMO
N
N
N
0 4' 8'2'
0 4' 8'2'0 4' 8'2' 1/4" = 1'-0"
ENLARGED PLAN - RM 229 & 229A - TELECOM - DEMO
1/4" = 1'-0"1
ENLARGED PLAN - TR A03 - TELECOM - DEMO
1/4" = 1'-0"
ENLARGED PLAN - RM A225 - TELECOM - DEMO
1/4" = 1'-0"4
ENLARGED PLAN - RM 127 & 127A - TELECOM - DEMO
GENERAL NOTES:
A. REFER TO GENERAL DEMOLITION NOTES ON SHEET T000 FOR ADDITIONAL DEMOLITION SCOPE.
SHEET NOTES:
1. EXISTING TELECOMMUNICATIONS CAGE AND RACK SHALL BE INCLUDED WITHIN THE SCOPE OF DEMOLITION.
EXISTING CABLING AND ASSOCIATED OUTLETS SHALL BE REMOVED AND REPLACED 1 FOR 1 AND REFED FROM DISTRIBUTION EQUIPMENT LOCATED WITHIN THE NEW TELECOMMUNICATIONS ROOM. REFER TO GENERAL CABLING NOTES FOR APPROXIMATE QUANTITIES. REFER TO NEW WORK PLANS FOR SERVING
COMMUNICATIONS ROOM LOCATION AND NEW CABLING ROUTES.
2. EXISTING CABLE TRAY, SECURITY CAMERAS, GROUND BUS BARS, AND RACKS FROM DECOMMISSIONED
ROOMS ARE TO BE REUSED, WHEN POSSBILE, IN NEW CONSTRUCTION TRS.
CABLING NOTE:
CABLING NOTES:
A. THE EXISTING CABLE COUNT ARE THE CABLES CURRENTLY PRESENT IN THE SPACE. THE CABLE
RELOCATION COUNT ARE THE NEW OR RELOCATED CABLES TO BE FED FROM THE SPACE. THE FINAL CABLE COUNT ARE THE CABLES THAT WILL BE PRESENT IN THE SPACE AT THE COMPLETION OF THE
PROJECT.
1. ROOM A003
EXISTING CABLE COUNT
DATA (CAT6): 0
DATA (CAT5e): 299
DATA (CAT5): 0
DATA (CAT3): 0
CABLE RELOCATION COUNT
DATA (CAT6): 0
DATA (CAT5e): 0
DATA (CAT5): 0
DATA (CAT3): 0
EXISTING CABLE TO REMAIN
DATA (CAT6): 0
DATA (CAT5e): 0
DATA (CAT5): 0
DATA (CAT3): 0
FINAL CABLE COUNT
DATA (CAT6): 0
DATA (CAT5e): 0
DATA (CAT5): 0
DATA (CAT3): 0
2. ROOM A101
EXISTING CABLE COUNT
DATA (CAT6): 0
DATA (CAT5e): 212
DATA (CAT5): 0
DATA (CAT3): 0
CABLE RELOCATION COUNT
DATA (CAT6): 0
DATA (CAT5e): 0
DATA (CAT5): 0
DATA (CAT3): 0
EXISTING CABLE TO REMAIN
DATA (CAT6): 0
DATA (CAT5e): 0
DATA (CAT5): 0
DATA (CAT3): 0
FINAL CABLE COUNT
DATA (CAT6): 0
DATA (CAT5e): 0
DATA (CAT5): 0
DATA (CAT3): 0
3. ROOM 127
EXISTING CABLE COUNT
DATA (CAT6): 0
DATA (CAT5e): 650
DATA (CAT5): 0
DATA (CAT3): 0
CABLE RELOCATION COUNT
DATA (CAT6): 0
DATA (CAT5e): 0
DATA (CAT5): 0
DATA (CAT3): 0
EXISTING CABLE TO REMAIN
DATA (CAT6): 0
DATA (CAT5e): 0
DATA (CAT5): 0
DATA (CAT3): 0
FINAL CABLE COUNT
DATA (CAT6): 0
DATA (CAT5e): 0
DATA (CAT5): 0
DATA (CAT3): 0
4. ROOM A216
EXISTING CABLE COUNT
DATA (CAT6): 0
DATA (CAT5e): 215
DATA (CAT5): 0
DATA (CAT3): 0
CABLE RELOCATION COUNT
DATA (CAT6): 0
DATA (CAT5e): 0
DATA (CAT5): 0
DATA (CAT3): 0
EXISTING CABLE TO REMAIN
DATA (CAT6): 0
DATA (CAT5e): 0
DATA (CAT5): 0
DATA (CAT3): 0
FINAL CABLE COUNT
DATA (CAT6): 0
DATA (CAT5e): 0
DATA (CAT5): 0
DATA (CAT3): 0
5. ROOM A225
EXISTING CABLE COUNT
DATA (CAT6): 0
DATA (CAT5e): 30
DATA (CAT5): 0
DATA (CAT3): 0
CABLE RELOCATION COUNT
DATA (CAT6): 0
DATA (CAT5e): 0
DATA (CAT5): 0
DATA (CAT3): 0
EXISTING CABLE TO REMAIN
DATA (CAT6): 0
DATA (CAT5e): 0
DATA (CAT5): 0
DATA (CAT3): 0
FINAL CABLE COUNT
DATA (CAT6): 0
DATA (CAT5e): 0
DATA (CAT5): 0
DATA (CAT3): 0
6. ROOM 229
EXISTING CABLE COUNT
DATA (CAT6): 0
DATA (CAT5e): 295
DATA (CAT5): 0
DATA (CAT3): 0
CABLE RELOCATION COUNT
DATA (CAT6): 0
DATA (CAT5e): 0
DATA (CAT5): 0
DATA (CAT3): 0
EXISTING CABLE TO REMAIN
DATA (CAT6): 0
DATA (CAT5e): 0
DATA (CAT5): 0
DATA (CAT3): 0
FINAL CABLE COUNT
DATA (CAT6): 0
DATA (CAT5e): 0
DATA (CAT5): 0
DATA (CAT3): 0
0 4' 8'2'
C
R
A C
1-TN400
1 - a b
1 - c d
C5 126"
A05C
TELECOM ROOM
CABLE
TRAY
DATA
RACKS
W
KEYPAD
2"
CABLE
TRAY
E
AC1
R
12"x4"
CABLE
TRAY
2"
"x
4"
"x
4"
NEMA L21-20R (TYP)
RACK 1
RACK 1
V E
R T
IC
A
L R
A C
K P
D U
V E
R T
IC
A
L R
A C
K P
D U
1U CABLE MANAGEMENT
VA OIT PROVIDED 1U 48 PORT SWITCH
2U CABLE MANAGEMENT
VA OIT PROVIDED 1U 48 PORT SWITCH
2U CABLE MANAGEMENT
VA OIT PROVIDED 1U 48 PORT SWITCH
2U CABLE MANAGEMENT
VA OIT PROVIDED 1U 48 PORT SWITCH
2U CABLE MANAGEMENT
VA OIT PROVIDED 1U 48 PORT SWITCH
2U CABLE MANAGEMENT
1U CABLE MANAGEMENT
VA OIT PROVIDED 1U 48 PORT SWITCH
6U SPACE FOR FUTURE USE.
PROVIDE BLANK PANELS FOR UNUSED SPACES.
6U 5KW RACK MOUNT UPS
D
PROVIDE DATA CABLE TO RACK
MOUNTED UPS FOR CONNECTION
TO MONITORING SYSTEM
VERTICAL CABLE
MANAGEMENT (TYP)
NEMA L21-20R (TYP)
RACK 2
1U BONDING BUS BAR (BACK) 1U ANGLED BLANKING PANEL (FRONT)
1U 48 PORT CAT6A ANGLED DATA PATCH PANEL
RACK 2
V E
R T
IC
A
L R
A C
K P
D U
V E
R T
IC
A
L R
A C
K P
D U
1U 48 PORT CAT6A ANGLED DATA PATCH PANEL
1U 48 PORT CAT6A ANGLED DATA PATCH PANEL
1U 48 PORT CAT6A ANGLED DATA PATCH PANEL
1U 48 PORT CAT6A ANGLED DATA PATCH PANEL
1U 48 PORT CAT6A ANGLED DATA PATCH PANEL
VA OIT PROVIDED 1U 48 PORT SWITCH
2U CABLE MANAGEMENT
VA OIT PROVIDED 1U 48 PORT SWITCH
2U CABLE MANAGEMENT
1U CABLE MANAGEMENT
VA OIT PROVIDED 1U 48 PORT SWITCH
6U SPACE FOR OIT PROVIDED EQUIPMENT.
PROVIDE BLANKING PANELS FOR UNUSED SPACES.
6U 5KW RACK MOUNT UPS
D
1U CABLE MANAGEMENT
VA OIT PROVIDED 1U 48 PORT SWITCH
2U CABLE MANAGEMENT
VA OIT PROVIDED 1U 48 PORT SWITCH
2U CABLE MANAGEMENT
VA OIT PROVIDED 1U 48 PORT SWITCH
2U CABLE MANAGEMENT
1U BONDING BUS BAR (BACK) 1U ANGLED BLANKING PANEL (FRONT)
SPACE FOR FUTURE HORIZONTAL CABLE
DISTRIBUTION. PROVIDE ANGLED BLANKING PANELS
FOR UNUSED SPACES.
NOTES:
1. REFER TO NEW WORK PLAN FOR RACK LOCATIONS.
2. COORDINATE EXACT RACK LOCATION WITH OWNER PRIOR TO PERMANENT INSTALLATION.
3. SEE PROJECT SPECIFICATIONS FOR ADDITIONAL RACK COMPONENTS.
4. RACK ELEVATION SHOWS A FULLY CONFIGURED SAMPLE RACK. CONTRACTOR TO PROVIDE REQUIRED EQUIPMENT TO
SUPPORT THE FINAL DATA COUNT FROM THE ENLARGED NEW SHEET.
5. COORDINATE FINAL RACK COMPONENT LAYOUT WITH OWNER'S IS/IT REPRESENTATIVE.
6. CONTRACTOR IS RESPONSIBLE FOR FINAL CABLE COUNT, QUANTITY OF PATCH PANELS, SWITCHES, FIBER ENCLOSURES, BLANKING PANELS, CABLE MANAGEMENT, TR PATCH CABLES, AND MOUNTING HARDWARE NOT MARKED AS “OIT PROVIDED”.
7. PUNCH DOWN COPPER BACKBONE CABLE TO RACK MOUNT PATCH PANEL. TERMINATE ONE (1) PAIR PER PATCH PANEL PORT.
4 POST CHANNEL
RACK (TYP)
1U 144 STRAND OM4 AND OS2 DISTRIBUTION PANEL
1U 48 PORT CAT5E BACKBONE ANGLED PATCH PANEL
SPACE FOR FUTURE HORIZONTAL CABLE
DISTRIBUTION. PROVIDE ANGLED BLANKING PANELS
FOR UNUSED SPACES.
1U 48 PORT CAT6A ANGLED DATA PATCH PANEL
1U 48 PORT CAT6A ANGLED DATA PATCH PANEL
1U 48 PORT CAT6A ANGLED DATA PATCH PANEL
1U 48 PORT CAT6A ANGLED DATA PATCH PANEL
1U 48 PORT CAT6A ANGLED DATA PATCH PANEL
1U 48 PORT CAT6A ANGLED DATA PATCH PANEL
RECORD DOCUMENTS
No DATEREVISION
DRAWING TITLE
CHECKED BY
ST.CLOUD, MN 56303
VA MEDICAL CENTER
BUILDING No
LOCATION
DRAWING NO.DRAWN
DWG. OF
PROJECT TITLE
PLOT SCALE
PROJECT NO.
DATE:
CONSULTANT ARCHITECT/ENGINEER OF RECORD
FULLY
SPRINKLERED
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
-RECORD DOCUMENT-
June 21, 2024
This Record Document has been prepared based on
Designer of Record drawings with Contractor provided markups through the construction phase of the project at the direction of the VA.
While the construction information is believed to be reliable, Architect/Engineer cannot assure its accuracy, and is not responsible for the accuracy of this Record Document. Those relying on this Record
Document are advised to independently verify its accuracy before applying it for any purpose.
RECORD DOCUMENTS 06/21/24
B
IM
/2
.0
V A
S t C lo u d E
H R
M I n fr a s tr u c tu re U p g ra d e s /6
-2
.B
.T
R
.r v t
/4
/2
:2
:2
P
M
1-TN400
ENLARGED PLANS -
TELECOMMUNICATIONS
EHRM INFRASTRUCTURE
UPGRADES
656‐21‐235
03/30/2022
KSB SSK
16305
1/2" = 1'-0"
ENLARGED PLAN - TR A05C - TELECOM - CABLE TRAY AND DATA
N
0 2' 4'1'
1/4" = 1'-0"2 1 - a
1/4" = 1'-0"3 1 - b
1/4" = 1'-0"4 1 - c
1/4" = 1'-0"
1 - d 0 4' 8'2' 0 4' 8'2' 0 4' 8'2' 0 4' 8'2'
GENERAL NOTES:
A. REFER TO GENERAL DEMOLITION NOTES ON SHEET T000 FOR ADDITIONAL DEMOLITION SCOPE.
CABLING NOTE:
CABLING NOTES:
A. THE EXISTING CABLE COUNT ARE THE CABLES CURRENTLY PRESENT IN THE SPACE.
THE CABLE RELOCATION COUNT ARE THE NEW OR RELOCATED CABLES TO BE FED
FROM THE SPACE. THE FINAL CABLE COUNT ARE THE CABLES THAT WILL BE
PRESENT IN THE SPACE AT THE COMPLETION OF THE PROJECT.
1. ROOM A05C
EXISTING CABLE COUNT
DATA (CAT6): 0
DATA (CAT5e): 0
DATA (CAT5): 0
DATA (CAT3): 0
CABLE RELOCATION COUNT
DATA (CAT6): 0
DATA (CAT5e): 299 FROM A003
DATA (CAT5): 0
DATA (CAT3): 0
EXISTING CABLE TO REMAIN
DATA (CAT6): 0
DATA (CAT5e): 0
DATA (CAT5): 0
DATA (CAT3): 0
FINAL CABLE COUNT
DATA (CAT6A): 299
DATA (CAT6): 0
NOT TO SCALE6
COMMUNICATIONS - TYPICAL TWO RACK ELEVATION WITH RACK MOUNT UPS - TR A05C
SHEET NOTES:
1. PROVIDE A NEW ACCESS CONTROL PANEL TO BE INSTALLED IN THE TELECOM ROOM. THE CARD READER AND KEYPAD FOR THIS ROOM TO BE WIRED TO THE NEW ACCESS CONTROL PANEL. EXISTING CARD READERS AND
KEYPADS WILL BE MOVED TO THE NEW CONTROL PANEL UNDER A DIFFERENT PROJECT.
R
A C
1-TN401
2 - a b
2 - c
-d
C4 126"
W 005F
TELECOM ROOM
"x
4"
DATA RACKS
CABLE TRAY
KEYPAD
4D E
AC
R
12"x4"
2"
WAP
C4 126"
2"
NEMA L21-20R (TYP)
RACK 1
RACK 1
V E
R T
IC
A
L R
A C
K P
D U
V E
R T
IC
A
L R
A C
K P
D U
1U CABLE MANAGEMENT
VA OIT PROVIDED 1U 48 PORT SWITCH
2U CABLE MANAGEMENT
VA OIT PROVIDED 1U 48 PORT SWITCH
2U CABLE MANAGEMENT
VA OIT PROVIDED 1U 48 PORT SWITCH
2U CABLE MANAGEMENT
VA OIT PROVIDED 1U 48 PORT SWITCH
2U CABLE MANAGEMENT
VA OIT PROVIDED 1U 48 PORT SWITCH
2U CABLE MANAGEMENT
1U CABLE MANAGEMENT
VA OIT PROVIDED 1U 48 PORT SWITCH
6U SPACE FOR FUTURE USE.
PROVIDE BLANK PANELS FOR UNUSED SPACES.
6U 5KW RACK MOUNT UPS
D
PROVIDE DATA CABLE TO RACK
MOUNTED UPS FOR CONNECTION
TO MONITORING SYSTEM
VERTICAL CABLE
MANAGEMENT (TYP)
1U BONDING BUS BAR (BACK) 1U ANGLED BLANKING PANEL (FRONT)
NOTES:
1. REFER TO NEW WORK PLAN FOR RACK LOCATIONS.
2. COORDINATE EXACT RACK LOCATION WITH OWNER PRIOR TO PERMANENT INSTALLATION.
3. SEE PROJECT SPECIFICATIONS FOR ADDITIONAL RACK COMPONENTS.
4. RACK ELEVATION SHOWS A FULLY CONFIGURED SAMPLE RACK. CONTRACTOR TO PROVIDE REQUIRED EQUIPMENT TO
SUPPORT THE FINAL DATA COUNT FROM THE ENLARGED NEW SHEET.
5. COORDINATE FINAL RACK COMPONENT LAYOUT WITH OWNER'S IS/IT REPRESENTATIVE.
6. CONTRACTOR IS RESPONSIBLE FOR FINAL CABLE COUNT, QUANTITY OF PATCH PANELS, SWITCHES, FIBER ENCLOSURES, BLANKING PANELS, CABLE MANAGEMENT, TR PATCH CABLES, AND MOUNTING HARDWARE NOT MARKED AS “OIT PROVIDED”.
7. PUNCH DOWN COPPER BACKBONE CABLE TO RACK MOUNT PATCH PANEL. TERMINATE ONE (1) PAIR PER PATCH PANEL PORT.
4 POST CHANNEL
RACK (TYP)
1U 144 STRAND OM4 AND OS2 DISTRIBUTION PANEL
1U 48 PORT CAT5E BACKBONE ANGLED PATCH PANEL
SPACE FOR FUTURE HORIZONTAL CABLE
DISTRIBUTION. PROVIDE ANGLED BLANKING PANELS
FOR UNUSED SPACES.
1U 48 PORT CAT6A ANGLED DATA PATCH PANEL
1U 48 PORT CAT6A ANGLED DATA PATCH PANEL
1U 48 PORT CAT6A ANGLED DATA PATCH PANEL
1U 48 PORT CAT6A ANGLED DATA PATCH PANEL
1U 48 PORT CAT6A ANGLED DATA PATCH PANEL
1U 48 PORT CAT6A ANGLED DATA PATCH PANEL
RECORD DOCUMENTS
No DATEREVISION
DRAWING TITLE
CHECKED BY
ST.CLOUD, MN 56303
VA MEDICAL CENTER
BUILDING No
LOCATION
DRAWING NO.DRAWN
DWG. OF
PROJECT TITLE
PLOT SCALE
PROJECT NO.
DATE:
CONSULTANT ARCHITECT/ENGINEER OF RECORD
FULLY
SPRINKLERED
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
-RECORD DOCUMENT-
June 21, 2024
This Record Document has been prepared based on
Designer of Record drawings with Contractor provided markups through the construction phase of the project at the direction of the VA.
While the construction information is believed to be reliable, Architect/Engineer cannot assure its accuracy, and is not responsible for the accuracy of this Record Document. Those relying on this Record
Document are advised to independently verify its accuracy before applying it for any purpose.
RECORD DOCUMENTS 06/21/24
B
IM
/2
.0
V A
S t C lo u d E
H R
M I n fr a s tr u c tu re U p g ra d e s /6
-2
.B
.T
R
.r v t
/4
/2
:2
:2
P
M
1-TN401
ENLARGED PLANS -
TELECOMMUNICATIONS
EHRM INFRASTRUCTURE
UPGRADES
656‐21‐235
03/30/2022
KSB SSK
16305
N
0 2' 4'1'
0 4' 8'2' 0 4' 8'2' 0 4' 8'2' 0 4' 8'2'
GENERAL NOTES:
A. REFER TO GENERAL DEMOLITION NOTES ON SHEET T000 FOR ADDITIONAL DEMOLITION SCOPE.
CABLING NOTE:
CABLING NOTES:
A. THE EXISTING CABLE COUNT ARE THE CABLES CURRENTLY PRESENT IN THE SPACE.
THE CABLE RELOCATION COUNT ARE THE NEW OR RELOCATED CABLES TO BE FED
FROM THE SPACE. THE FINAL CABLE COUNT ARE THE CABLES THAT WILL BE
PRESENT IN THE SPACE AT THE COMPLETION OF THE PROJECT.
1. ROOM 005F
EXISTING CABLE COUNT
DATA (CAT6): 0
DATA (CAT5e): 0
DATA (CAT5): 0
DATA (CAT3): 0
CABLE RELOCATION COUNT
DATA (CAT6): 0
DATA (CAT5e): 325 FROM ROOM 127
DATA (CAT5): 0
DATA (CAT3): 0
EXISTING CABLE TO REMAIN
DATA (CAT6): 0
DATA (CAT5e): 0
DATA (CAT5): 0
DATA (CAT3): 0
FINAL CABLE COUNT
DATA (CAT6A): 325
DATA (CAT6): 0
1/2" = 1'-0"
ENLARGED PLAN - TR 005F - TELECOM - CABLE TRAY AND DATA
1/4" = 1'-0"
2 - a 1/4" = 1'-0"
2 - b
1/4" = 1'-0"
2 - c 1/4" = 1'-0"
2-d
NOT TO SCALE6
COMMUNICATIONS - TYPICAL ONE RACK ELEVATION WITH RACK MOUNT UPS - TR A005F
SHEET NOTES:
1. PROVIDE A NEW ACCESS CONTROL PANEL TO BE INSTALLED IN THE TELECOM ROOM. THE CARD READER AND
C R
C
NURSING A102A
A101
COMM
TELE-
1-TN402
3 - a b
3 - c d
TW
BAS
SP
E
E
E
12"x4"
DATA RACKS
CABLE TRAY
4"4"4"
E
W
R
2" C
DOWN
2" C
UP
12"x4"
12"x4"
AC
12"x4"
4"4"4"4"
E
"x
4"
12"x4"
2"
1"
CABLE TRAY
KEYPAD
NEMA L21-20R (TYP)
RACK 1
RACK 1
V E
R T
IC
A
L R
A C
K P
D U
V E
R T
IC
A
L R
A C
K P
D U
1U CABLE MANAGEMENT
VA OIT PROVIDED 1U 48 PORT SWITCH
2U CABLE MANAGEMENT
VA OIT PROVIDED 1U 48 PORT SWITCH
2U CABLE MANAGEMENT
VA OIT PROVIDED 1U 48 PORT SWITCH
2U CABLE MANAGEMENT
VA OIT PROVIDED 1U 48 PORT SWITCH
2U CABLE MANAGEMENT
VA OIT PROVIDED 1U 48 PORT SWITCH
2U CABLE MANAGEMENT
1U CABLE MANAGEMENT
VA OIT PROVIDED 1U 48 PORT SWITCH
6U SPACE FOR FUTURE USE.
PROVIDE BLANK PANELS FOR UNUSED SPACES.
6U 5KW RACK MOUNT UPS
D
PROVIDE DATA CABLE TO RACK
MOUNTED UPS FOR CONNECTION
TO MONITORING SYSTEM
VERTICAL CABLE
MANAGEMENT (TYP)
NEMA L21-20R (TYP)
RACK 2
1U BONDING BUS BAR (BACK) 1U ANGLED BLANKING PANEL (FRONT)
1U 48 PORT CAT6A ANGLED DATA PATCH PANEL
RACK 2
V E
R T
IC
A
L R
A C
K P
D U
V E
R T
IC
A
L R
A C
K P
D U
1U 48 PORT CAT6A ANGLED DATA PATCH PANEL
1U 48 PORT CAT6A ANGLED DATA PATCH PANEL
1U 48 PORT CAT6A ANGLED DATA PATCH PANEL
1U 48 PORT CAT6A ANGLED DATA PATCH PANEL
1U 48 PORT CAT6A ANGLED DATA PATCH PANEL
VA OIT PROVIDED 1U 48 PORT SWITCH
2U CABLE MANAGEMENT
VA OIT PROVIDED 1U 48 PORT SWITCH
2U CABLE MANAGEMENT
1U CABLE MANAGEMENT
VA OIT PROVIDED 1U 48 PORT SWITCH
6U SPACE FOR OIT PROVIDED EQUIPMENT.
PROVIDE BLANKING PANELS FOR UNUSED SPACES.
6U 5KW RACK MOUNT UPS
D
1U CABLE MANAGEMENT
VA OIT PROVIDED 1U 48 PORT SWITCH
2U CABLE MANAGEMENT
VA OIT PROVIDED 1U 48 PORT SWITCH
2U CABLE MANAGEMENT
VA OIT PROVIDED 1U 48 PORT SWITCH
2U CABLE MANAGEMENT
1U BONDING BUS BAR (BACK) 1U ANGLED BLANKING PANEL (FRONT)
SPACE FOR FUTURE HORIZONTAL CABLE
DISTRIBUTION. PROVIDE ANGLED BLANKING PANELS
FOR UNUSED SPACES.
NOTES:
1. REFER TO NEW WORK PLAN FOR RACK LOCATIONS.
2. COORDINATE EXACT RACK LOCATION WITH OWNER PRIOR TO PERMANENT INSTALLATION.
3. SEE PROJECT SPECIFICATIONS FOR ADDITIONAL RACK COMPONENTS.
4. RACK ELEVATION SHOWS A FULLY CONFIGURED SAMPLE RACK. CONTRACTOR TO PROVIDE REQUIRED EQUIPMENT TO
SUPPORT THE FINAL DATA COUNT FROM THE ENLARGED NEW SHEET.
5. COORDINATE FINAL RACK COMPONENT LAYOUT WITH OWNER'S IS/IT REPRESENTATIVE.
6. CONTRACTOR IS RESPONSIBLE FOR FINAL CABLE COUNT, QUANTITY OF PATCH PANELS, SWITCHES, FIBER ENCLOSURES, BLANKING PANELS, CABLE MANAGEMENT, TR PATCH CABLES, AND MOUNTING HARDWARE NOT MARKED AS “OIT PROVIDED”.
7. PUNCH DOWN COPPER BACKBONE CABLE TO RACK MOUNT PATCH PANEL. TERMINATE ONE (1) PAIR PER PATCH PANEL PORT.
4 POST CHANNEL
RACK (TYP)
1U 144 STRAND OM4 AND OS2 DISTRIBUTION PANEL
1U 48 PORT CAT5E BACKBONE ANGLED PATCH PANEL
SPACE FOR FUTURE HORIZONTAL CABLE
DISTRIBUTION. PROVIDE ANGLED BLANKING PANELS
FOR UNUSED SPACES.
1U 48 PORT CAT6A ANGLED DATA PATCH PANEL
1U 48 PORT CAT6A ANGLED DATA PATCH PANEL
1U 48 PORT CAT6A ANGLED DATA PATCH PANEL
1U 48 PORT CAT6A ANGLED DATA PATCH PANEL
1U 48 PORT CAT6A ANGLED DATA PATCH PANEL
1U 48 PORT CAT6A ANGLED DATA PATCH PANEL
RECORD DOCUMENTS
No DATEREVISION
DRAWING TITLE
CHECKED BY
ST.CLOUD, MN 56303
VA MEDICAL CENTER
BUILDING No
LOCATION
DRAWING NO.DRAWN
DWG. OF
PROJECT TITLE
PLOT SCALE
PROJECT NO.
DATE:
CONSULTANT ARCHITECT/ENGINEER OF RECORD
FULLY
SPRINKLERED
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
-RECORD DOCUMENT-
June 21, 2024
This Record Document has been prepared based on
Designer of Record drawings with Contractor provided markups through the construction phase of the project at the direction of the VA.
While the construction information is believed to be reliable, Architect/Engineer cannot assure its accuracy, and is not responsible for the accuracy of this Record Document. Those relying on this Record
Document are advised to independently verify its accuracy before applying it for any purpose.
RECORD DOCUMENTS 06/21/24
B
IM
/2
.0
V A
S t C lo u d E
H R
M I n fr a s tr u c tu re U p g ra d e s /6
-2
.B
.T
R
.r v t
/4
/2
:2
:2
P
M
1-TN402
ENLARGED PLANS -
TELECOMMUNICATIONS
EHRM INFRASTRUCTURE
UPGRADES
656‐21‐235
03/30/2022
KSB SSK
16305
N
0 2' 4'1'
0 4' 8'2' 0 4' 8'2' 0 4' 8'2' 0 4' 8'2'
GENERAL NOTES:
A. REFER TO GENERAL DEMOLITION NOTES ON SHEET T000 FOR ADDITIONAL DEMOLITION SCOPE.
CABLING NOTE:
CABLING NOTES:
A. THE EXISTING CABLE COUNT ARE THE CABLES CURRENTLY PRESENT IN THE SPACE.
THE CABLE RELOCATION COUNT ARE THE NEW OR RELOCATED CABLES TO BE FED
FROM THE SPACE. THE FINAL CABLE COUNT ARE THE CABLES THAT WILL BE
PRESENT IN THE SPACE AT THE COMPLETION OF THE PROJECT.
1. ROOM A101
EXISTING CABLE COUNT
DATA (CAT6): 0
DATA (CAT5e): 212
DATA (CAT5): 0
DATA (CAT3): 0
CABLE RELOCATION COUNT
DATA (CAT6): 0
DATA (CAT5e): 325 FROM ROOM 127
DATA (CAT5): 0
DATA (CAT3): 0
EXISTING CABLE TO REMAIN
DATA (CAT6): 0
DATA (CAT5e): 0
DATA (CAT5): 0
DATA (CAT3): 0
FINAL CABLE COUNT
DATA (CAT6A): 537
DATA (CAT6): 0
1/2" = 1'-0"
ENLARGED PLAN - TR A101 - TELECOM - CABLE TRAY AND DATA
1/4" = 1'-0"
3 - a 1/4" = 1'-0"
3 - b
1/4" = 1'-0"
3 - c 1/4" = 1'-0"
3 - d
NOT TO SCALE6
COMMUNICATIONS - TYPICAL TWO RACK ELEVATION WITH RACK MOUNT UPS - TR A101
SHEET NOTES:
1. PROVIDE A NEW ACCESS CONTROL PANEL TO BE INSTALLED IN THE TELECOM ROOM. THE CARD READER AND
C
C R
1-TN403
4 - a b
4 - c d
W
"x
4"
A200
TELECOM ROOM
2"
DATA RACKS
CABLE TRAY
E
K E
Y P
A D
2"
AC1
R
C4 126"
18"x4"
C4 126"
18"x4"
NEMA L21-20R (TYP)
RACK 1
RACK 1
V E
R T
IC
A
L R
A C
K P
D U
V E
R T
IC
A
L R
A C
K P
D U
1U CABLE MANAGEMENT
VA OIT PROVIDED 1U 48 PORT SWITCH
2U CABLE MANAGEMENT
VA OIT PROVIDED 1U 48 PORT SWITCH
2U CABLE MANAGEMENT
VA OIT PROVIDED 1U 48 PORT SWITCH
2U CABLE MANAGEMENT
VA OIT PROVIDED 1U 48 PORT SWITCH
2U CABLE MANAGEMENT
VA OIT PROVIDED 1U 48 PORT SWITCH
2U CABLE MANAGEMENT
1U CABLE MANAGEMENT
VA OIT PROVIDED 1U 48 PORT SWITCH
6U SPACE FOR FUTURE USE.
PROVIDE BLANK PANELS FOR UNUSED SPACES.
6U 5KW RACK MOUNT UPS
D
PROVIDE DATA CABLE TO RACK
MOUNTED UPS FOR CONNECTION
TO MONITORING SYSTEM
VERTICAL CABLE
MANAGEMENT (TYP)
NEMA L21-20R (TYP)
RACK 2
1U BONDING BUS BAR (BACK) 1U ANGLED BLANKING PANEL (FRONT)
1U 48 PORT CAT6A ANGLED DATA PATCH PANEL
RACK 2
V E
R T
IC
A
L R
A C
K P
D U
V E
R T
IC
A
L R
A C
K P
D U
1U 48 PORT CAT6A ANGLED DATA PATCH PANEL
1U 48 PORT CAT6A ANGLED DATA PATCH PANEL
1U 48 PORT CAT6A ANGLED DATA PATCH PANEL
1U 48 PORT CAT6A ANGLED DATA PATCH PANEL
1U 48 PORT CAT6A ANGLED DATA PATCH PANEL
VA OIT PROVIDED 1U 48 PORT SWITCH
2U CABLE MANAGEMENT
VA OIT PROVIDED 1U 48 PORT SWITCH
2U CABLE MANAGEMENT
1U CABLE MANAGEMENT
VA OIT PROVIDED 1U 48 PORT SWITCH
6U SPACE FOR OIT PROVIDED EQUIPMENT.
PROVIDE BLANKING PANELS FOR UNUSED SPACES.
6U 5KW RACK MOUNT UPS
D
1U CABLE MANAGEMENT
VA OIT PROVIDED 1U 48 PORT SWITCH
2U CABLE MANAGEMENT
VA OIT PROVIDED 1U 48 PORT SWITCH
2U CABLE MANAGEMENT
VA OIT PROVIDED 1U 48 PORT SWITCH
2U CABLE MANAGEMENT
1U BONDING BUS BAR (BACK) 1U ANGLED BLANKING PANEL (FRONT)
SPACE FOR FUTURE HORIZONTAL CABLE
DISTRIBUTION. PROVIDE ANGLED BLANKING PANELS
FOR UNUSED SPACES.
NOTES:
1. REFER TO NEW WORK PLAN FOR RACK LOCATIONS.
2. COORDINATE EXACT RACK LOCATION WITH OWNER PRIOR TO PERMANENT INSTALLATION.
3. SEE PROJECT SPECIFICATIONS FOR ADDITIONAL RACK COMPONENTS.
4. RACK ELEVATION SHOWS A FULLY CONFIGURED SAMPLE RACK. CONTRACTOR TO PROVIDE REQUIRED EQUIPMENT TO
SUPPORT THE FINAL DATA COUNT FROM THE ENLARGED NEW SHEET.
5. COORDINATE FINAL RACK COMPONENT LAYOUT WITH OWNER'S IS/IT REPRESENTATIVE.
6. CONTRACTOR IS RESPONSIBLE FOR FINAL CABLE COUNT, QUANTITY OF PATCH PANELS, SWITCHES, FIBER ENCLOSURES, BLANKING PANELS, CABLE MANAGEMENT, TR PATCH CABLES, AND MOUNTING HARDWARE NOT MARKED AS “OIT PROVIDED”.
7. PUNCH DOWN COPPER BACKBONE CABLE TO RACK MOUNT PATCH PANEL. TERMINATE ONE (1) PAIR PER PATCH PANEL PORT.
4 POST CHANNEL
RACK (TYP)
1U 144 STRAND OM4 AND OS2 DISTRIBUTION PANEL
1U 48 PORT CAT5E BACKBONE ANGLED PATCH PANEL
SPACE FOR FUTURE HORIZONTAL CABLE
DISTRIBUTION. PROVIDE ANGLED BLANKING PANELS
FOR UNUSED SPACES.
1U 48 PORT CAT6A ANGLED DATA PATCH PANEL
1U 48 PORT CAT6A ANGLED DATA PATCH PANEL
1U 48 PORT CAT6A ANGLED DATA PATCH PANEL
1U 48 PORT CAT6A ANGLED DATA PATCH PANEL
1U 48 PORT CAT6A ANGLED DATA PATCH PANEL
1U 48 PORT CAT6A ANGLED DATA PATCH PANEL
RECORD DOCUMENTS
No DATEREVISION
DRAWING TITLE
CHECKED BY
ST.CLOUD, MN 56303
VA MEDICAL CENTER
BUILDING No
LOCATION
DRAWING NO.DRAWN
DWG. OF
PROJECT TITLE
PLOT SCALE
PROJECT NO.
DATE:
CONSULTANT ARCHITECT/ENGINEER OF RECORD
FULLY
SPRINKLERED
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
-RECORD DOCUMENT-
June 21, 2024
This Record Document has been prepared based on
Designer of Record drawings with Contractor provided markups through the construction phase of the project at the direction of the VA.
While the construction information is believed to be reliable, Architect/Engineer cannot assure its accuracy, and is not responsible for the accuracy of this Record Document. Those relying on this Record
Document are advised to independently verify its accuracy before applying it for any purpose.
RECORD DOCUMENTS 06/21/24
B
IM
/2
.0
V A
S t C lo u d E
H R
M I n fr a s tr u c tu re U p g ra d e s /6
-2
.B
.T
R
.r v t
/4
/2
:2
:2
P
M
1-TN403
ENLARGED PLANS -
TELECOMMUNICATIONS
EHRM INFRASTRUCTURE
UPGRADES
656‐21‐235
03/30/2022
KSB SSK
16305
N
0 2' 4'1'
0 4' 8'2' 0 4' 8'2' 0 4' 8'2' 0 4' 8'2'
GENERAL NOTES:
A. REFER TO GENERAL DEMOLITION NOTES ON SHEET T000 FOR ADDITIONAL DEMOLITION SCOPE.
CABLING NOTE:
CABLING NOTES:
A. THE EXISTING CABLE COUNT ARE THE CABLES CURRENTLY PRESENT IN THE SPACE.
THE CABLE RELOCATION COUNT ARE THE NEW OR RELOCATED CABLES TO BE FED
FROM THE SPACE. THE FINAL CABLE COUNT ARE THE CABLES THAT WILL BE
PRESENT IN THE SPACE AT THE COMPLETION OF THE PROJECT.
1. ROOM A200
EXISTING CABLE COUNT
DATA (CAT6): 0
DATA (CAT5e): 0
DATA…