Attachment 6 WILSON BID DOCUMENT 20220429.pdf
PDF 27 MB Posted
- Solicitation number
- 36C77623B0033
About this file
This attachment is related to a federal contract solicitation from the Department of Veterans Affairs Technology Acquisition Center Austin to convert residential lots to a paved parking area in Reno, Nevada. The solicitation number is 36C77623B0033 and seeks bids to complete minor construction work under opportunity Y1PZ--654-823. Bids are due by April 29, 2022 and the award date will be determined. The work required includes paving existing residential lots to create additional parking spaces. Details on pricing, bonding, or other contractual requirements are not provided in this attachment.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Additional Technical Questions 2.docx | DOCX document | |
| 36C77623B0033 0002.docx | DOCX document | |
| Copy of Parking Lot Sign In.xlsx | XLSX spreadsheet | |
| 36C77623B0033 0001.docx | DOCX document | |
| S05 - Contractor Technical Questions - answers.pdf | ||
| Reno VAMC Asbestos Survey (Draft).pdf | ||
| Reno VAMC LBP Screening Report (Draft).pdf | ||
| Attachment 1 Statement of Work.pdf | ||
| Attachment 3 Site Visit.docx | DOCX document | |
| Attachment 2 Specifications Bid 20220429.pdf | ||
| 36C77623B0033_1.docx | DOCX document | |
| Attachment 9 - DBA Wage Rate.pdf | ||
| Attachment 5 LOCUST BID DOCUMENT 20220429.pdf | ||
| Attachment 7 TAYLOR BID DOCUMENT PART 1 20220429.pdf | ||
| Attachment 4 - Contractor Safety - Environmental Form.docx | DOCX document | |
| Attachment 8 TAYLOR BID DOCUMENT PART 2 20220429.pdf |
Show all 16
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
VA FORM 08 - 6231
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
Revisions: Date:
BID DOCUMENTS
A/E:
TRIPLE C THE A/E GROUP
1839 S. Alma School Rd., Ste 300 Mesa AZ, 85210 307-460-2054 Mat Perkins
654-823-A
975 Kirman Ave, Reno, NV 89502
CONVERT PROCURED RESIDENTIAL
LOTS TO SURFACE LEVEL
ASPHALT PAVED PARKING
COVER SHEET
1030 WILSON AVENUE
APN: 013-172-01
GI000
STRUBLEPERKINS04/29/2022
VA Sierra Nevada Health Care System
BID DOCUMENTS
APRIL 29, 2022
NORTH
PROJECT SCOPE
VICINITY MAP
LOCATION MAP
NORTH
SHEET INDEX
SHEET NUMBER SHEET DESCRIPTION
GI000 COVER SHEET
VF101 CIVIL SITE SURVEY PLAN
CD101 CIVIL DEMOLITION PLAN
CS101 CIVIL SITE PLAN
CG101 CIVIL GRADING PLAN
CG102 STORMWATER PROTECTION PLAN
CG501 CIVIL GRADING DETAILS 1
CG502 CIVIL GRADING DETAILS 2
CG503 CIVIL GRADING DETAILS 3
CG504 CIVIL GRADING DETAILS 4
CU101 CIVIL UTILITY AND SIGNAGE PLAN
LP100 PLANTING NOTES
LP101 PLANTING PLAN
LP501 PLANTING DETAILS
LI100 IRRIGATION NOTES
LI101 IRRIGATION PLAN
LI501 IRRIGATION DETAILS
A-001 SYMBOLS, AND GENERAL NOTES
AD101 SITE DEMOLITION DEMOLITION - 1030 WILSON
A-201 EXTERIOR ELEVATIONS - 1030 WILSON
ED101 ELECTRICAL DEMOLITION PLAN - 1030 WILSON AVENUE
E-101 ELECTRICAL SITE PLAN - 1030 WILSON AVENUE
E-102 LIGHTING PHOTOMETRIC PLAN
T101 BUILDING 10 - KEY CABINET AND CAMERA INSTALLATION
PROJECT LOCATION
PROJECT LOCATION
VISN 21 PROJECT NO.: 654-19-823
CONTRACT NO.: VA261-17-D-0088
CONVERT PROCURED RESIDENTIAL LOTS TO
SURFACE LEVEL ASPHALT PAVED PARKING
1030 WILSON AVENUE
U.S. Department of Veterans Affairs
LOCATION OF VAMC BLDG 1D
FOR INSTALLATION OF KEY
CABINET - SEE SHEET T-101
FOR ADDITIONAL
INFORMATION
CLIENT:
VA Sierra Nevada Health Care System - VISN 21
Contracting Officer (CO) - Charee Harris Contracting Officer's Representative (COR) - Mike Rowley
975 Kirman Avenue Reno, NV 89502
THIS SET OF CONSTRUCTION DOCUMENTS PERTAINS ONLY TO THE 1030 WILSON PROJECT SITE.
As described in the VA scope of work (SOW) document, the SOW shall include the following:
Description:
1. 1.a The project intent is to complete design documents (drawings, specifications and cost estimates) to allow for conversion of five(5) separate property lots currently housing approximately ten (10) separate structures (including one rental apartment four-plex) into paved asphalt surface parking lots. Priority is to provide the maximum number of new parking spaces. Construction shall include any associated new structures, sidewalks, curbs, foundations, pavement, driveways, signage, utilities, metering, ancillary equipment, etc.
1.b Given the age of some of the existing structures it's likely that asbestos abatement, lead paint elimination, PCB removal and other similar remediation efforts will be necessary at some, if not all, of the structures procured by the facility. Therefore, the design project scope shall include a hazardous material abatement portion to assure these items are removed from the structures and properly disposed of. Additionally, it must be assumed that some if not all of the properties to be covered within the design scope contain underground fuel tanks which served furnaces to heat the structures. The design documents shall include all information necessary to allow for removal and proper disposal of any underground fuel tanks and piping systems.
1.c The design package shall include complete demolition documents to assure complete removal of the existing structures, substructures, foundations, slabs, sidewalks, driveways, utilities, metering, etc. which served the structures to be removed as part of this design scope. All new drive approaches, sidewalks, signage and drainage shall conform to City of Reno design standards where applicable.
1.d All recent projects on facility grounds which have required below surface work have resulted in a stoppage of the project when the contractor encountered unforeseen below surface conditions. The design scope shall include a geotechnical report for the areas under consideration as necessary to reduce the probability that, once below surface work begins, unforeseen conditions will result in project delays.
1.e The design package shall include all documents necessary to allow for the conversion of all the lots to asphalt paved surface level parking sloped to drain with storm water pollution prevention plan per local requirements. The parcels are federal property and shall comply with all Veterans Affairs (DVA) standards for Surface Level Parking including the Parking Design Manual, Parking Lot and Exterior Signage, Physical Security Design Manual, Telecommunications and Special Telecommunications and other DVA design guides and manuals. City of Reno design standards apply for public easement areas, i.e. driveways, sidewalk, curbs, etc.
Where DVA standards differ or conflict with City standards, the design shall follow the more stringent of the two standards. Lots are to be complete, asphalt paved, striped, lighted and sloped for proper drainage. Additionally, 1030 Wilson shall include:
Fully striped and marked lot, sloped to drain with storm-water pollution prevention per local requirements Parking bumpers at the head of each stall with adequate separation.
space to accommodate two DUV with approximate dimensions of 30'L x 9'W x 13'H each. Provide dedicated 120volt, 20amp GFI receptacles as shown on the electrical plans.
This lot shall be enclosed with CMU walls, vehicular gates and pedestrian doors with corresponding security access. Gates and operating motors shall have vehicle impact protection.
type II, charging stations to support PEV (plug-in electric vehicles) with designated signage for dedicated PEV parking only as shown on the plans Provide security camera system connecting to the VA police facility's existing main security control center on the main campus.
Scope of Work also includes installing a key-box off-site in the VA Medical Center Lobby, and a Security Camera for monitoring purposes. These devices shall be incorporated into the Existing Lenel Security System. Coordinate location, equipment requirements, and access with the COR. See utility and electrical plans for additional information.
1.f Landscaping shall comply with local zoning ordinances and VA landscaping requirements, compatible with current neighborhood aesthetics per State Preservation Historic Office (e.g., landscaping, foliage, trees, lighting, etc.) and to minimize adverse effects on surrounding historic properties to the extent practicable. Landscaping irrigation shall have a dedicated water meter where applicable. The Landscape Architect shall have specific experience in landscape design with High Desert environments, similar to the design location or be able to demonstrate equivalent design experience. Lots shall be properly lighted, per ASHRAE
90.1 and applicable IES standards.
1.g The three locations where the work is to occur are the following resident lots in Reno, Nevada:
1. 1000-1040 Wilson Street (4-unit apartment complex)
2. 524 and 526 East Taylor(adjoined lots - four residential structures), 530 East Taylor Street and 925 Locust Street (adjoined lots - four residential structures)
3. 633 Eat Taylor, 635 and 635A East Taylor Street (three residential structures) The Wilson Street lot is the location that has been designated for use by Government Vehicles and DUV (dual use vehicle) only.
1.h The Government Vehicle Lot will be designed to incorporate the following features:
Fully striped and marked lot, with a minimum of two van accessible parking spaces.
Parking bumpers at the head of each stall with adequate separation.
One stall sized to accommodate a DUV with approximate dimensions of 30'L x 9'W x 13'H. Provide a dedicated 120volt, 20amp GFI receptacle with exact location
TBD.
This lot shall be walled to provide additional security for the vehicles located therein. Wall to consist of precast concrete or CMU or other rigid fencing TBD. A-E to provide a minimum of three options to prevent access by unauthorized persons. One access gate into the lot with keypad entry and one access gate out of the lot with sensor operation. Gates and operating motors shall have vehicle impact protection. KeyBank system, www.morsewatchmans.com (Brand Name or Equal)
A total of (16) type II, charging stations to support PEV (plug-in electric vehicles) with designated signage for dedicated PEV parking only.
ttps://avt.inl.gov/sites/default/files/pdf/presentations/InterfuelsDCJune2016.pdf
Provide security stored loop feed cameras or cameras connecting the VA police facility's existing main security control center on the main campus. Design shall incorporate wireless technology as much as feasible within VA requirements for physical security. Provide adequate separation between bumper stops and adjacent signage, charging station equipment and other appurtenances. Provide heavy duty or flexible posts, and/or bollards where required. Signage may be located on fencing or other structures, where appropriate to prevent damage from vehicular traffic.
1.i The other two lots will include the following features:
Fully striped, marked with ADA compliant parking including a minimum 3% of stalls for handicap parking per VA standards. Parking bumpers at the head of each stall with adequate separation.
CONTRACTOR NOTE
ALL WORK WITHIN CITY OF RENO RIGHT OF WAY TO MEET CITY OF
RENO STANDARDS AND SPECIFICATIONS. ALL WORK WITHIN VA
PROPERTY TO MEET VA STANDARDS AND SPECIFICATIONS
/29
/20
EX. GAS METERS
EX. WATER METER
EX
. W
AT
ER
EX
. G
AS
EX. GAS
EX. WATER
EX
. W
AT
ER
EX. SAN. SEWER
EX. OVERHEAD POWER
EX. OVERHEAD TELEPHONE
EX
. S
AN
. S
EW
ER
LA
TE
RA
L
CONSTRUCT SAFETY SIGN
EX. OVERHEAD POWER
N88° 56' 52.53"E 57.614'
N0 ° 1
5' 1 4.8
9"W
0.0
N0 ° 1
4' 5 5.9
7"W
9.7
N89° 11' 12.00"E 57.624'
1"=10'F1 CIVIL SITE SURVEY PLAN
VA FORM 08 - 6231
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
Revisions: Date:
BID DOCUMENTS
A/E:
TRIPLE C THE A/E GROUP
1839 S. Alma School Rd., Ste 300 Mesa AZ, 85210 307-460-2054 Mat Perkins
654-823-A
975 Kirman Ave, Reno, NV 89502
CONVERT PROCURED RESIDENTIAL
LOTS TO SURFACE LEVEL
ASPHALT PAVED PARKING
CIVIL SITE SURVEY PLAN
1030 WILSON AVENUE
APN: 013-172-01
VF101
STRUBLEPERKINS04/29/2022
010' 10' 20'5'
LEGEND
LIMITS OF CONSTRUCTION
WATERLINE
SANITARY SEWER LINE
STORM DRAIN LINE
UNDERGROUND ELECTRICAL LINE
EX. CONCRETE
STORM DRAIN MANHOLE
SANITARY SEWER MANHOLE
WATER VALVE
SIDEWALK
UNDERGROUND GAS LINE
EXISTING PROPOSED
CURB
SEWER CLEAN-OUT
STORM DRAIN INLET
UTILITY LINE CAP
CONSTRUCTION FENCING
F/F FACE TO FACE
FF EL FINISH FLOOR ELEVATION
FG FINISH GRADE
FH FIRE HYDRANT
FL FLOW LINE
FOC FACE OF CURB
FT FEET OR FOOT
FTG FOOTING
HC HANDICAP
HCP HANDICAPPED
HDPE HIGH DENSITY POLYETHYLENE
HNDRL HANDRAIL
HORIZ HORIZONTAL
ID INSIDE DIAMETER OR INSIDE
DIMENSION
INFO INFORMATION
INV INVERT
INV EL INVERT ELEVATION
LAT LATITUDE
LF LINEAR FEET (FOOT)
LOC LOCATION
LP LOW POINT
LS LUMP SUM
MATL MATERIAL
MH MANHOLE
MIN MINIMUM
MISC MISCELLANEOUS
MON MONUMENT
MTG MEETING
MULT MULTIPLE
N NORTH
NA NOT APPLICABLE
NO NUMBER
NTS NOT TO SCALE
OC ON CENTER
PC POINT OF CURVE
PCT PERCENT
PI POINT OF INTERSECTION
PL PROPERTY LINE
PRKG PARKING
PROJ PROJECT
PROP PROPOSED
PSI POUNDS PER SQUARE INCH
PVC POLYVINYL CHLORIDE (PLASTIC)
QTY QUANTITY
R RADIUS
RCB REINFORCED CONCRETE BOX
RCP REINFORCED CONCRETE PIPE
RD ROAD OR ROOF DRAIN
REQD REQUIRED
ROW RIGHT OF WAY
RT RIGHT
RW ROADWAY
ABBRV ABBREVIATION
ABC AGGREGATE BASE COURSE
AC ASPHALTIC CONCRETE
ACP ASPHALTIC CONCRETE PAVING
ADA AMERICANS WITH DISABILITIES ACT
AGGR AGGREGATE
APPROX APPROXIMATE
ASPH ASPHALT
ASSY ASSEMBLY
AVE AVENUE
BC BACK OF CURB
BDRY BOUNDARY
BITUM BITUMINOUS
BLDG BUILDING
BLVD BOULEVARD
BM BENCHMARK
BRG BEARING
CB CATCH BASIN
CFS CUBIC FEET PER SECOND
CL CENTER LINE
CLASS CLASSIFICATION
CMP CORRUGATED METAL PIPE
CMU CONCRETE MASONRY UNIT
CO SEWER CLEAN OUT
CONC CONCRETE
CONSTR CONSTRUCTION
COORD COORDINATE
CORR CORRIDOR
CU FT CUBIC FEET
CU YD CUBIC YARD
DA DRAINAGE AREA
DAT DATUM
DEG DEGREE
DEMO DEMOLITION
DEPT DEPARTMENT
DESCR DESCRIPTION
DET DETAIL
DI DROP INLET
DIA DIAMETER
DIFF DIFFERENCE
DIM DIMENSION
DIP DUCTILE IRON PIPE
DIR DIRECTION
DIST DISTANCE
DWG DRAWING
E EAST
EA EACH
EC EDGE OF CURB
EG EXISTING GRADE
EL ELEVATION
ENGR ENGINEER
ENTR ENTRANCE
EP EDGE OF PAVEMENT (PAVING)
EPA ENVIRONMENTAL PROTECTION
AGENCY
EQUIP EQUIPMENT
ERD EXISTING ROOF DRAIN
ES EDGE OF SHOULDER
ESMT EASEMENT
EST ESTIMATE
EX EXISTING
EXIST EXISTING
SD STORM DRAIN
SDMH STORM DRAIN MANHOLE
SECT SECTION
SF SQUARE FOOT (FEET)
SHLDR SHOULDER
SMH STEAM MANHOLE
SP EL SPOT ELEVATION
SPEC SPECIFICATION
SQ YD SQUARE YARD
SS SANITARY SEWER
SSMH SANITARY SEWER
MANHOLE
ST STREET
STLT STREETLIGHT
STA STATION
STD STANDARD
STM STEAM
SURF SURFACE
SURV SURVEY
SW SIDEWALK
SWR SEWER
SYM SYMBOL
TAN TANGENT
TC TOP OF CURB
TD TRENCH DRAIN
TE TOP ELEVATION
TEMP TEMPORARY
THK THICKNESS
THRU THROUGH
TMH TOP OF MANHOLE
TOC TOP OF CURB
TOC WALL TOP OF CONCRETE
WALL
TOF TOP OF FOOTING
TOP TOP OF WALL
TOPO TOPOGRAPHY
TOS TOP OF SLAB
TYP TYPICAL
UGND UNDERGROUND
UNPV RD UNPAVED ROAD
UON UNLESS OTHERWISE
NOTED
UTIL UTILITY
VAR VARIES
VC VERTICAL CURVE
VERT VERTICAL
VIC VICINITY
VOL VOLUME
W WEST
W/ WITH
W/O WITHOUT
CIVIL SHEET ABBREVIATIONS
SURVEY DISCLAIMER
SURVEY INFORMATION OF SITE DETERMINED CITY OF RENO
SUPPLIED AS-BUILT DRAWINGS AND SURFACE SCANS. CONDITION
OF THE SITE MAY VARY FROM THE SURVEYED CONDITION. UTILITY
LOCATIONS ARE IN APPROXIMATE LOCATION, CONTRACTOR TO
VERIFY LOCATION AND DEPTH OF ALL UTILITIES PRIOR TO
CONSTRUCTION TO PROVIDE NON-INTERRUPTION OF SERVICE, TO
ENSURE PROPER CLEARANCE/SEPARATION, AND TO AVOID DAMAGE
THERETO. UTILITIES DAMAGED THROUGH NEGLIGENCE OF THE
CONTRACTOR TO OBTAIN LOCATION OF SAME SHALL BE REPAIRED
OR REPLACED BY THE CONTRACTOR AT HIS EXPENSE.N.T.S.E7 REAR OF HOUSE
E7
VF101
N.T.S.F7 FRONT OF HOUSE
F7
VF101
/29
EX
. W
AT
ER
EX
. G
AS
EX. GAS
EX. WATER
EX
. W
AT
ER
EX. OVERHEAD POWER EX. OVERHEAD TELEPHONE
EX. SAN. SEWER
EX. OVERHEAD POWER
EX. OVERHEAD TELEPHONE
EX. GAS METERS
TO BE REMOVED
EX. WATER METER BOX TO BE
REPLACED WITH TRAFFIC RATED BOX
EX. WATER LATERAL
TO BE REMOVED
EX. FENCE
TO BE REMOVED
EX. CONCRETE DRIVEWAY
TO BE REMOVED
EX. CONCRETE SIDEWALK
TO BE REMOVED
EX. GAS LINE
TO BE REMOVED
EX. OVERHEARD POWERLINE
TO BE REMOVED
EX. SANITARY
SEWER LATERAL
TO BE REMOVED
EX. TREE
TO BE REMOVED
EX. TREE
TO BE REMOVED
EX. TREE
TO BE REMOVED
EX. TREE
TO BE REMOVED
STUB AD CAP
GAS LINE AT
PROPERTY LINE
STUB AND CAP
SEWER LATERAL AT
PROPERTY LINE
EX. BUILDING
TO BE REMOVED
EX. FENCE
TO BE REMOVED
EX.CONCRETE CURB
TO BE REMOVED
EX
. S
AN
. S
EW
ER
LA
TE
RA
L
EX.CONCRETE CURB
TO BE REMOVED
EX. SIDEWALK
TO BE REMOVED
EX. CONCRETE ALLEY
TO BE REMOVED
EX. OVERHEAD TELEPHONE LINE
TO BE REMOVED
EX. TREE
TO BE REMOVED
CONSTRUCT SAFETY SIGN
1"=10'F1 CIVIL DEMOLITION PLAN
VA FORM 08 - 6231
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
Revisions: Date:
BID DOCUMENTS
A/E:
TRIPLE C THE A/E GROUP
1839 S. Alma School Rd., Ste 300 Mesa AZ, 85210 307-460-2054 Mat Perkins
654-823-A
975 Kirman Ave, Reno, NV 89502
CONVERT PROCURED RESIDENTIAL
LOTS TO SURFACE LEVEL
ASPHALT PAVED PARKING
CIVIL DEMOLITION PLAN
1030 WILSON AVENUE
APN: 013-172-01
CD101
STRUBLEPERKINS04/29/2022
LEGEND
LIMITS OF CONSTRUCTION
BACK OF CURB
EDGE OF PAVEMENT
EX. CONCRETE
EX. A.C. PAVEMENT
SIDEWALK
EXISTING PROPOSED
CENTERLINE
SAW-CUT LINE
SLOPE AND FLOW DIRECTION
PROPERTY FENCING
CONSTRUCTION FENCING
1. ALL WORK DETAILED ON THESE PLANS AND PERFORMED UNDER THIS CONTRACT SHALL BE CONSTRUCTED IN ACCORDANCE WITH THE PROJECT SPECIFICATIONS AND THE GEOTECHNICAL REPORT. WHERE APPLICABLE, CITY OF RENO PUBLIC WORKS STANDARDS SHALL APPLY.
2. THE CONTRACTOR SHALL ABIDE BY ALL LOCAL, STATE, AND FEDERAL LAWS, RULES AND REGULATIONS WHICH APPLY TO THE CONSTRUCTION OF THESE IMPROVEMENTS, INCLUDING EPA REGULATIONS WITH RESPECT TO STORM WATER DISCHARGE.
3. PRIOR TO CONSTRUCTION, THE CONTRACTOR SHALL FIELD VERIFY THE HORIZONTAL AND VERTICAL LOCATIONS OF ALL POTENTIAL OBSTRUCTIONS INCLUDING ALL UNDERGROUND UTILITIES. THE CONTRACTOR'S SURVEYOR SHALL DOCUMENT THE HORIZONTAL LOCATION AND ELEVATION OF UTILITIES THAT ARE EXPOSED. SHOULD A CONFLICT EXIST, THE CONTRACTOR SHALL NOTIFY THE CONTRACTING OFFICER'S REPRESENTATIVE (COR) OR ENGINEER SO THE CONFLICT CAN BE RESOLVED WITH A MINIMUM AMOUNT OF DELAY.
4. ALL ELECTRICAL, TELEPHONE, CABLE TV, GAS AND OTHER UTILITY LINES, CABLES, AND APPURTENANCES ENCOUNTERED DURING CONSTRUCTION THAT REQUIRE RELOCATION, SHALL BE COORDINATED WITH THE COR. THE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATION OF ALL NECESSARY UTILITY ADJUSTMENTS. NO ADDITIONAL COMPENSATION WILL BE ALLOWED FOR DELAYS OR INCONVENIENCES CAUSED BY UTILITY COMPANY WORK CREWS. THE CONTRACTOR MAY BE REQUIRED TO RESCHEDULE HIS ACTIVITIES TO
ALLOW UTILITY CREWS TO PERFORM THEIR REQUIRED WORK.
5. THE CONTRACTOR IS RESPONSIBLE FOR PROTECTING ALL EXISTING UTILITY LINES WITHIN THE CONSTRUCTION AREA. ANY DAMAGE TO EXISTING FACILITIES CAUSED BY CONSTRUCTION ACTIVITY SHALL BE REPAIRED OR REPLACED AT THE CONTRACTOR'S EXPENSE AND
APPROVED BY THE COR.
6. CONSTRUCTION ACTIVITY SHALL BE LIMITED TO THE PROPERTY AND/OR PROJECT LIMITS. ANY DAMAGE TO ADJACENT PROPERTIES RESULTING FROM CONSTRUCTION PROCESS SHALL BE REPAIRED OR REPLACED AT THE CONTRACTOR'S EXPENSE.
7. OVERNIGHT PARKING OF CONSTRUCTION EQUIPMENT SHALL NOT OBSTRUCT DRIVEWAYS OR DESIGNATED TRAFFIC LANES. THE CONTRACTOR SHALL NOT STORE ANY EQUIPMENT OR MATERIAL WITHIN THE PUBLIC RIGHT-OF-WAY.
8. THE CONTRACTOR SHALL OBTAIN ALL NECESSARY PERMITS FOR THE PROJECT PRIOR TO COMMENCING CONSTRUCTION (I.E. BARRICADING, TOPSOIL DISTURBANCE, EXCAVATION PERMITS, EPA STORM WATER PERMITS, ETC.)
9. ALL PROPERTY CORNERS DESTROYED DURING CONSTRUCTION SHALL BE REPLACED AT THE CONTRACTOR'S EXPENSE. ALL PROPERTY
CORNERS MUST BE RESET BY A REGISTERED LAND SURVEYOR.
10. THE CONTRACTOR SHALL PREPARE A CONSTRUCTION TRAFFIC CONTROL AND SIGNING PLAN AND OBTAIN APPROVAL OF SUCH PLAN FROM THE CONTRACT OFFICER'S REPRESENTATIVE (COR), PRIOR TO BEGINNING ANY CONSTRUCTION WORK ON OR ADJACENT TO EXISTING
STREETS.
11. ALL BARRICADES AND CONSTRUCTION SIGNING SHALL CONFORM TO APPLICABLE SECTIONS OF THE "MANUAL ON UNIFORM TRAFFIC
CONTROL DEVICES" (MUTCD), US DEPARTMENT OF TRANSPORTATION, LATEST EDITION.
12. THE CONTRACTOR SHALL MAINTAIN ALL CONSTRUCTION BARRICADES AND SIGNING AT ALL TIMES. THE CONTRACTOR SHALL VERIFY THE
PROPER LOCATION OF ALL BARRICADING AT THE END AND BEGINNING OF EACH DAY.
13. THE CONTRACTOR SHALL TAKE ALL STEPS NECESSARY TO CONFORM WITH EPA REQUIREMENTS, INCLUDING COMPLIANCE WITH NPDES PHASE 2 REQUIREMENTS. THIS INCLUDES PREPARATION OF A STORM WATER POLLUTION PREVENTION PLAN (SWPPP), FILING THE NOTICE OF
INTENT AND MAINTENANCE OF SWPPP BEST MANAGEMENT PLANS (BMP'S).
GENERAL NOTES
APPROXIMATE DEMOLITION QUANTITIES
*CONTRACTOR TO FIELD VERIFY
30" CONCRETE CURB AND GUTTER REMOVAL
QUANTITY UNITS
LF
DESCRIPTION
EXISTING CONCRETE SIDEWALK REMOVAL
SAW-CUT LF
A.C. PAVEMENT REMOVAL SF
010' 10' 20'5'
EXISTING TREE REMOVAL
EXISTING CONCRETE DRIVEWAY REMOVAL SF
SF
EA
EXISTING WATER LINE LATERAL REMOVAL
REPLACE WATER METER BOX
EXISTING SEWER LATERAL REMOVAL
EXISTING GAS METER REMOVAL
EXISTING GAS LINE REMOVAL
EXISTING FENCE REMOVAL
EXISTING BUILDING REMOVAL
LF
LF
LF
LF
SF
EA
EA
2,710
1,305
DEMOLITION NOTE
SEE ARCHITECTURAL DEMOLITION AND ELECTRICAL DEMOLITION
SHEETS FOR ADDITIONAL INFORMATION ON BUILDING AND UTILITY
DEMOLITION.
EXISTING CONCRETE ALLEY REMOVAL SF134
CONTRACTOR NOTE
CONTRACTOR TO PROVIDE A MONTHLY CONSTRUCTION AND DEMO
WASTE REPORT (SPREADSHEET WILL BE PROVIDED) TO VA RENO
ENVIRONMENTAL PROTECTION, 775-7200 EXT 5850. (SIMILAR NOTE
FOR ALL DRAWING SETS)
EXISTING OVERHEAD POWER LINE REMOVAL LF125
EXISTING OVERHEAD TELEPHONE/COMM LINE REMOVAL LF250
/29
17.04'17.04'
9.00'
9.0 0'
16.75'
10.00' 5.00'
5.00'
9.05'
16.0'
16.0'
5.00'
4.00'
20.0'
STA:12+53.67
BEG. CONSTRUCTION
STA:5+22.88
BEG. CONSTRUCTION
STA:5+46.88
END CONSTRUCTION
STA:4+97.81
END CONSTRUCTION
10.90'
10.37'
4.50'
L1
L2
L3 C1 L4
L5
L7
L8
C3 L9
L1
L11 C4 L1
L13
L1
14.00'
2.50'
3.00'
47' DUV PARKING ZONE
PARALLEL PARK 2 DUV VEHICLES
4'
17.50'
L6
C5
10.00' R25.00'
L15C2
L1 6 L1
20.24'
4.59'
9.52'
6.58'
10.93'
9.00'
L18
L1
L2
L21
2.0'
STA:11+86.92
BEG. CONSTRUCTION
STA:11+75.39
BEG. CONSTRUCTION
STA:4+92.27
END CONSTRUCTION
STA:4+57.33
END CONSTRUCTION
CONSTRUCT SAFETY SIGN
70°
1"=10'F1 CIVIL SITE PLAN
VA FORM 08 - 6231
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
Revisions: Date:
BID DOCUMENTS
A/E:
TRIPLE C THE A/E GROUP
1839 S. Alma School Rd., Ste 300 Mesa AZ, 85210 307-460-2054 Mat Perkins
654-823-A
975 Kirman Ave, Reno, NV 89502
CONVERT PROCURED RESIDENTIAL
LOTS TO SURFACE LEVEL
ASPHALT PAVED PARKING
CIVIL SITE PLAN
1030 WILSON AVENUE
APN: 013-172-01
CS101
STRUBLEPERKINS04/29/2022
CONTRACTOR NOTE
"LIMITS OF CONSTRUCTION" IDENTIFIES AN IMAGINARY LINE AROUND ALL AREAS IN WHICH
CONSTRUCTION WILL OCCUR. SOME ADDITIONAL AREAS MY BE IMPACTED BY UTILITY
INFRASTRUCTURE TIE-INS. COORDINATE WITH COR.
"LIMITS OF CONTRACTOR FENCED AREA" IDENTIFIES THE CONTRACTOR'S FENCE (TO COMPLY
WITH VA STANDARDS) AROUND THE BUILDING CONSTRUCTION AREA. COORDINATE WITH COR.
"OPTIONAL TEMPORARY CONTRACTOR MATERIAL LAYDOWN AREA" IDENTIFIES AREAS FOR
CONTRACTOR TO TEMPORARILY STAGE MATERIALS.
LEGEND
EXISTING PROPOSED
LIMITS OF CONSTRUCTION
EX. CONCRETE
STORM DRAIN MANHOLE
SANITARY SEWER MANHOLE
WATER VALVE
SIDEWALK
FENCE
SEWER/STORM PVC CLEAN-OUT
STORM DRAIN INLET
SURVEY DISCLAIMER
SURVEY INFORMATION OF SITE DETERMINED CITY OF RENO SUPPLIED AS-BUILT DRAWINGS AND SURFACE SCANS.
CONDITION OF THE SITE MAY VARY FROM THE SURVEYED CONDITION. UTILITY LOCATIONS ARE IN APPROXIMATE LOCATION, CONTRACTOR TO VERIFY LOCATION AND DEPTH OF ALL UTILITIES PRIOR TO CONSTRUCTION TO PROVIDE NON-INTERRUPTION OF SERVICE, TO ENSURE PROPER CLEARANCE/SEPARATION, AND TO AVOID DAMAGE THERETO.
UTILITIES DAMAGED THROUGH NEGLIGENCE OF THE CONTRACTOR TO OBTAIN LOCATION OF SAME SHALL BE REPAIRED OR
REPLACED BY THE CONTRACTOR AT HIS EXPENSE.
010' 10' 20'5'
CONSTRUCTION FENCING
SAW-CUT LINE
/29
STA:12+53.67
BEG. CONSTRUCTION
STA:5+22.88
BEG. CONSTRUCTION
STA:5+46.88
END CONSTRUCTION
STA:4+97.81
END CONSTRUCTION
STA:11+86.92
BEG. CONSTRUCTION
STA:11+75.39
BEG. CONSTRUCTION
STA:4+92.27
END CONSTRUCTION
STA:4+57.33
END CONSTRUCTION
CONSTRUCT SAFETY SIGN
4471.99
TC
4471.74
TC
4471.74
TC
4471.46
TC
4470.19
TC
4472.12
TC
4472.45
TC
4471.21
TC
4470.41
TC
4470.57
TC
4470.41
TC
4470.99
TC
4470.57
TC
4471.27
TC
4471.53
TC
4470.73
EX SW
4471.32
EX SW
4470.80
EX TC
4471.24
EX TC
4471.36
TC
4470.88
TC
4470.35
TC
4470.66
EX SW
4470.77
EX SW
4470.21
EX GR
4472.23
TC
4471.96
TC
4471.70
TC
4471.43
TC
4471.20
TC
4470.93
TC
4470.67
TC
4470.40
TC
1"=10'F1 CIVIL GRADING PLAN
VA FORM 08 - 6231
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
Revisions: Date:
BID DOCUMENTS
A/E:
TRIPLE C THE A/E GROUP
1839 S. Alma School Rd., Ste 300 Mesa AZ, 85210 307-460-2054 Mat Perkins
654-823-A
975 Kirman Ave, Reno, NV 89502
CONVERT PROCURED RESIDENTIAL
LOTS TO SURFACE LEVEL
ASPHALT PAVED PARKING
CIVIL GRADING PLAN
1030 WILSON AVENUE
APN: 013-172-01
CG101
STRUBLEPERKINS04/29/2022
010' 10' 20'5'
LEGEND
LIMITS OF CONSTRUCTION
BACK OF CURB
CONCRETE
SIDEWALK
EXISTING PROPOSED
SLOPE AND FLOW DIRECTION
CONSTRUCTION NOTES LEGEND
1. EXCEPT AS PROVIDED HEREIN, GRADING SHALL BE PERFORMED AT THE ELEVATIONS SHOWN
AND IN ACCORDANCE WITH THE DETAILS SHOWN ON SHEET CG501.
2. THE COST FOR REQUIRED CONSTRUCTION DUST AND EROSION CONTROL MEASURES SHALL BE
INCIDENTAL TO THE PROJECT COST.
3. ALL WORK RELATIVE TO FOUNDATION CONSTRUCTION, SITE PREPARATION, AND PAVEMENT
INSTALLATION, AS SHOWN ON THIS PLAN, SHALL BE CONSTRUCTED IN ACCORDANCE WITH THE
PROJECT, (FIRST PRIORITY) SPECIFICATIONS, AND/OR THE CITY OF RENO CODE OF ORDINANCES
(SECOND PRIORITY, AND WITHIN CITY OF RENO RIGHT-OF-WAY).
4. EARTH SLOPES SHALL NOT EXCEED 3 HORIZONTAL TO 1 VERTICAL UNLESS SHOWN OTHERWISE.
5. IT IS THE INTENT OF THESE PLANS THAT THIS CONTRACTOR SHALL NOT PERFORM ANY WORK
OUTSIDE OF THE PROPERTY BOUNDARIES EXCEPT AS REQUIRED BY THIS PLAN.
6. THE CONTRACTOR IS TO ENSURE THAT NO SOIL ERODES FROM THE SITE ONTO ADJACENT
PROPERTY OR PUBLIC RIGHT-OF-WAY. THIS SHOULD BE ACHIEVED BY CONSTRUCTING
TEMPORARY BERMS OR SILT FENCE AT THE PROPERTY LINES AND WETTING THE SOIL TO PROTECT
IT FROM WIND EROSION.
7. A DISPOSAL SITE FOR ANY & ALL EXCAVATION MATERIAL, AND UNSUITABLE MATERIAL AND/OR A
BORROW SITE CONTAINING ACCEPTABLE FILL MATERIAL SHALL BE OBTAINED BY THE
CONTRACTOR IN COMPLIANCE WITH APPLICABLE ENVIRONMENTAL REGULATIONS AND APPROVED
BY THE COR. ALL COSTS INCURRED IN OBTAINING A DISPOSAL OR BORROW SITE AND HAUL TO OR
FROM SHALL BE CONSIDERED INCIDENTAL TO THE PROJECT AND NO SEPARATE MEASURE OR
PAYMENT SHALL BE MADE.
8. PAVING AND ROADWAY GRADES SHALL BE +/- 0.1' FROM PLAN ELEVATIONS. PAD ELEVATIONS
SHALL BE +/- 0.05' FROM BUILDING PLAN ELEVATION.
9. VERIFY ALL ELEVATIONS SHOWN ON PLAN FROM BASIS OF ELEVATION CONTROL STATION PRIOR
TO BEGINNING CONSTRUCTION. (SEE SITE PLAN SHEET CS101).
GRADING NOTES
APPROXIMATE GRADING AND PAVING QUANTITIES
*CONTRACTOR TO FIELD VERIFY
QUANTITY UNITSDESCRIPTION
STORM DRAIN MANHOLE
SANITARY SEWER MANHOLE
STREET LIGHT
STORM DRAIN INLET
SURVEY DISCLAIMER
SURVEY INFORMATION OF SITE DETERMINED CITY OF RENO
SUPPLIED AS-BUILT DRAWINGS AND SURFACE SCANS. CONDITION
OF THE SITE MAY VARY FROM THE SURVEYED CONDITION. UTILITY
LOCATIONS ARE IN APPROXIMATE LOCATION, CONTRACTOR TO
VERIFY LOCATION AND DEPTH OF ALL UTILITIES PRIOR TO
CONSTRUCTION TO PROVIDE NON-INTERRUPTION OF SERVICE, TO
ENSURE PROPER CLEARANCE/SEPARATION, AND TO AVOID DAMAGE
THERETO. UTILITIES DAMAGED THROUGH NEGLIGENCE OF THE
CONTRACTOR TO OBTAIN LOCATION OF SAME SHALL BE REPAIRED
OR REPLACED BY THE CONTRACTOR AT HIS EXPENSE.
NOTE:
THE CONTRACTOR SHALL PROVIDE A "QUALIFIED SWPPP DEVELOPER" (QSD) WHO WILL
BE RESPONSIBLE FOR DEVELOPING A STORMWATER POLLUTION PREVENTION PLAN
FOR THIS PROJECT. THE QSD WILL ACT AS A DATA SUBMITTER FOR THE VA, WITH THE
FILING OF THE NOTICE OF INTENT TO THE NEVADA STATE WATER RESOURCES
CONTROL BOARD FOR COVERAGE UNDER THE CONSTRUCTION GENERAL PERMIT. THE
CONTRACTOR SHALL BE RESPONSIBLE TO PAY ALL FEES ASSOCIATED WITH THIS
PERMIT, WHICH INCLUDE, BUT ARE NOT LIMITED TO, THE NOTICE OF INTENT FILING AND
ANNUAL FEES FOR MAINTAINING COVERAGE UNDER THIS PERMIT. THE CONTRACTOR
WILL BE RESPONSIBLE FOR REVIEWING AND IMPLEMENTING THE PROVISIONS
SPECIFIED IN THE SWPPP AND THE EROSION CONTROL PLANS. THE CONTRACTOR
SHALL ALSO PROVIDE A "QUALIFIED SWPPP PRACTITIONER" (QSP) WHO WILL BE
RESPONSIBLE FOR IMPLEMENTING THE SWPPP, AND WILL ASSIST THE VA IN THE FILING
OF A NOTICE OF TERMINATION TO THE STATE WATER RESOURCES CONTROL BOARD
AT THE END OF THE PROJECT.
CONSTRUCT TYPE 1A CONCRETE CURB PER DETAIL F7, SHEET CG501
CONSTRUCT 4" CONCRETE SIDEWALK PER DETAIL F1, SHEET CG501
CONSTRUCT UTILITY TRENCH PER DETAIL C7, SHEET CG501 & C6, SHEET CG504
FLOW LINE
CONSTRUCT CONSTRUCTION FENCING
CONSTRUCT CONSTRUCTION YARD ENTRANCE GATE - (2) 6' CENTER LOCKING
CONSTRUCTION FENCING
CONSTRUCT BOLLARD POLE PER DETAIL F7, SHEET CG502
CONSTRUCT SCREEN WALL PER DETAIL B9, SHEET CG501
CONSTRUCT PEDESTRIAN DOOR - AMERISTAR EXODUS
CONSTRUCT VEHICLE SECURITY GATE - AMERISTAR PASSPORT COMMERCIAL INVINCIBLE
CONSTRUCT VEHICLE BARRIER GATE KEY PEDESTAL
CONSTRUCT HEAVY DUTY ASPHALT PAVEMENT PER DETAIL A7, SHEET CG501
SAW-CUT LINE AT 2 LF OFFSET FROM PROPOSED CURB / DROP CURB
CONNECT TO EXISTING CONCRETE - MATCH GRADE PER DETAIL C5, SHEET CG502
CONNECT TO EXISTING CURB - MATCH GRADE PER DETAIL C5, SHEET CG502
SEE DETAIL F10, SHEET CG502
ROLL GATE, 3-RAIL OR APPROVED EQUAL - SEE DETAIL D1, SHEET CG503
COMMERCIAL SINGLE SWING OR APPROVED EQUAL - SEE DETAIL C1, SHEET CG502
53 LF
2 EA
2 EA
138 LF
6 EA
6 LF
6,560 SF
187 LF
600 SF
222 SF
CONSTRUCT TYPE 2 P.C.C. MEDIAN CURB PER DETAIL C1, SHEET CG501
CONSTRUCT P.C.C. DRIVEWAY APRON PER DETAIL F9, SHEET CG501
TYPE 1A CONCRETE CURB
4" CONCRETE SIDEWALK
3' CONCRETE SWALE
BOLLARD POLE
SCREEN WALL
6' PEDESTRIAN GATE - AMERISTAR EXODUS
CONSTRUCT VEHICLE SECURITY GATE - AMERISTAR PASSPORT
CONSTRUCT VEHICLE BARRIER GATE KEY PEDESTAL
HEAVY DUTY ASPHALT PAVEMENT
COMMERCIAL INVINCIBLE ROLL GATE, 3-RAIL OR APPROVED EQUAL
COMMERCIAL SINGLE SWING OR APPROVED EQUAL
TYPE 2 P.C.C. MEDIAN CURB
P.C.C. DRIVEWAY APRON
1 EA
SAW-CUT LINE
CONSTRUCT 3' CONCRETE DRAINAGE SWALE PER DETAIL E9, SHEET CG502
CONSTRUCT DECORATIVE WROUGHT IRON FENCE PER DETAIL F8, SHEET CG503
CONSTRUCT TYPE 1 CONCRETE CURB PER DETAIL F7, SHEET CG501
158 LFTYPE 1 CONCRETE CURB
EARTHWORK FILL
-NET, UNADJUSTED 126 CY
CONSTRUCT 1" LIP P.C.C. CURB PER DETAIL C3, SHEET CG502
34 LF1" LIP P.C.C. CURB
21 CONSTRUCT P.C.C. ALLEY PER DETAIL F1 & F4, SHEET CG502
134 SFP.C.C. ALLEY
CONSTRUCT SAFETY SIGN PER DETAIL F4, SHEET CG50122
197 LF
8' DECORATIVE WROUGHT IRON FENCE
AMERISTAR MONTAGE CLASSIC OR APPROVED EQUAL
23 CONSTRUCT STREETLIGHT FOUNDATION, SEE SHEET CU101 AND DETAIL C4, SHEET CG504
- CONTRACTOR TO REMOVE AT COMPLETION OF PROJECT
- CONTRACTOR TO REMOVE AT COMPLETION OF PROJECT
TOPOGRAPHY CONTOUR MAJOR (5')
TOPOGRAPHY CONTOUR MINOR (1')
- CONTRACTOR TO REMOVE AT COMPLETION OF PROJECT
/29
1"=20'F1 STORMWATER PROTECTION PLAN
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
Revisions: Date:
BID DOCUMENTS
A/E:
TRIPLE C THE A/E GROUP
1839 S. Alma School Rd., Ste 300 Mesa AZ, 85210 307-460-2054 Mat Perkins
654-823-A
975 Kirman Ave, Reno, NV 89502
CONVERT PROCURED RESIDENTIAL
LOTS TO SURFACE LEVEL
ASPHALT PAVED PARKING
STORMWATER PROTECTION PLAN
1030 WILSON AVENUE
APN: 013-172-01
CG102
STRUBLEPERKINS04/29/2022
020' 20' 40'10'
CONSTRUCTION NOTES LEGEND
APPROXIMATE SWPPP QUANTITIES
*CONTRACTOR TO FIELD VERIFY
QUANTITY UNITSDESCRIPTION
SURVEY DISCLAIMER
SURVEY INFORMATION OF SITE DETERMINED CITY OF RENO
SUPPLIED AS-BUILT DRAWINGS AND SURFACE SCANS. CONDITION
OF THE SITE MAY VARY FROM THE SURVEYED CONDITION. UTILITY
LOCATIONS ARE IN APPROXIMATE LOCATION, CONTRACTOR TO
VERIFY LOCATION AND DEPTH OF ALL UTILITIES PRIOR TO
CONSTRUCTION TO PROVIDE NON-INTERRUPTION OF SERVICE, TO
ENSURE PROPER CLEARANCE/SEPARATION, AND TO AVOID DAMAGE
THERETO. UTILITIES DAMAGED THROUGH NEGLIGENCE OF THE
CONTRACTOR TO OBTAIN LOCATION OF SAME SHALL BE REPAIRED
OR REPLACED BY THE CONTRACTOR AT HIS EXPENSE.
NOTE:
THE CONTRACTOR SHALL PROVIDE A "QUALIFIED SWPPP DEVELOPER" (QSD) WHO WILL
BE RESPONSIBLE FOR DEVELOPING A STORMWATER POLLUTION PREVENTION PLAN
FOR THIS PROJECT. THE QSD WILL ACT AS A DATA SUBMITTER FOR THE VA, WITH THE
FILING OF THE NOTICE OF INTENT TO THE NEVADA STATE WATER RESOURCES
CONTROL BOARD FOR COVERAGE UNDER THE CONSTRUCTION GENERAL PERMIT. THE
CONTRACTOR SHALL BE RESPONSIBLE TO PAY ALL FEES ASSOCIATED WITH THIS
PERMIT, WHICH INCLUDE, BUT ARE NOT LIMITED TO, THE NOTICE OF INTENT FILING AND
ANNUAL FEES FOR MAINTAINING COVERAGE UNDER THIS PERMIT. THE CONTRACTOR
WILL BE RESPONSIBLE FOR REVIEWING AND IMPLEMENTING THE PROVISIONS
SPECIFIED IN THE SWPPP AND THE EROSION CONTROL PLANS. THE CONTRACTOR
SHALL ALSO PROVIDE A "QUALIFIED SWPPP PRACTITIONER" (QSP) WHO WILL BE
RESPONSIBLE FOR IMPLEMENTING THE SWPPP, AND WILL ASSIST THE VA IN THE FILING
OF A NOTICE OF TERMINATION TO THE STATE WATER RESOURCES CONTROL BOARD
AT THE END OF THE PROJECT. CONTRACTOR TO COORDINATE WITH CITY OF RENO
FOR ANY ADDITIONAL BMP REQUIREMENTS.
CONSTRUCT GRAVEL BAG PROTECTION PER DETAIL C9, SHEET CG502
6 EAGRAVEL BAG
LEGEND
LIMITS OF CONSTRUCTION
BACK OF CURB
CONCRETE
SIDEWALK
EXISTING PROPOSED
SLOPE AND FLOW DIRECTION
STORM DRAIN MANHOLE
SANITARY SEWER MANHOLE
GRAVEL BAG
STORM DRAIN INLET
FLOW LINE
CONSTRUCTION FENCING
SAW-CUT LINE
1. EXCEPT AS PROVIDED HEREIN, GRADING SHALL BE PERFORMED AT THE ELEVATIONS SHOWN
AND IN ACCORDANCE WITH THE DETAILS SHOWN ON SHEET CG501.
2. THE COST FOR REQUIRED CONSTRUCTION DUST AND EROSION CONTROL MEASURES SHALL BE
INCIDENTAL TO THE PROJECT COST.
3. ALL WORK RELATIVE TO FOUNDATION CONSTRUCTION, SITE PREPARATION, AND PAVEMENT
INSTALLATION, AS SHOWN ON THIS PLAN, SHALL BE CONSTRUCTED IN ACCORDANCE WITH THE
PROJECT, (FIRST PRIORITY) SPECIFICATIONS, AND/OR THE CITY OF RENO CODE OF ORDINANCES
(SECOND PRIORITY, AND WITHIN CITY OF RENO RIGHT-OF-WAY).
4. EARTH SLOPES SHALL NOT EXCEED 3 HORIZONTAL TO 1 VERTICAL UNLESS SHOWN OTHERWISE.
5. IT IS THE INTENT OF THESE PLANS THAT THIS CONTRACTOR SHALL NOT PERFORM ANY WORK
OUTSIDE OF THE PROPERTY BOUNDARIES EXCEPT AS REQUIRED BY THIS PLAN.
6. THE CONTRACTOR IS TO ENSURE THAT NO SOIL ERODES FROM THE SITE ONTO ADJACENT
PROPERTY OR PUBLIC RIGHT-OF-WAY. THIS SHOULD BE ACHIEVED BY CONSTRUCTING
TEMPORARY BERMS OR SILT FENCE AT THE PROPERTY LINES AND WETTING THE SOIL TO PROTECT
IT FROM WIND EROSION.
7. A DISPOSAL SITE FOR ANY & ALL EXCAVATION MATERIAL, AND UNSUITABLE MATERIAL AND/OR A
BORROW SITE CONTAINING ACCEPTABLE FILL MATERIAL SHALL BE OBTAINED BY THE
CONTRACTOR IN COMPLIANCE WITH APPLICABLE ENVIRONMENTAL REGULATIONS AND APPROVED
BY THE COR. ALL COSTS INCURRED IN OBTAINING A DISPOSAL OR BORROW SITE AND HAUL TO OR
FROM SHALL BE CONSIDERED INCIDENTAL TO THE PROJECT AND NO SEPARATE MEASURE OR
PAYMENT SHALL BE MADE.
8. PAVING AND ROADWAY GRADES SHALL BE +/- 0.1' FROM PLAN ELEVATIONS. PAD ELEVATIONS
SHALL BE +/- 0.05' FROM BUILDING PLAN ELEVATION.
9. VERIFY ALL ELEVATIONS SHOWN ON PLAN FROM BASIS OF ELEVATION CONTROL STATION PRIOR
TO BEGINNING CONSTRUCTION. (SEE SITE PLAN SHEET CS101).
GRADING NOTES
/29
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
Revisions: Date:
BID DOCUMENTS
A/E:
TRIPLE C THE A/E GROUP
1839 S. Alma School Rd., Ste 300 Mesa AZ, 85210 307-460-2054 Mat Perkins
654-823-A
975 Kirman Ave, Reno, NV 89502
CONVERT PROCURED RESIDENTIAL
LOTS TO SURFACE LEVEL
ASPHALT PAVED PARKING
CIVIL GRADING DETAILS 1
1030 WILSON AVENUE
APN: 013-172-01
CG501
STRUBLEPERKINS04/29/2022
NOT TO SCALEB9
1"
8'
MI
NI
MU
M
8" CMU WALL, FULLY GROUTED,
INTEGRAL COLOR.
4'-0" MAX.
1'-0" MAX.1'-0" MAX.
NOT TO SCALE VA STD. SD010000-01F4
U.S. Department of Veterans Affairs
THIS PROJECT HAS WORKED
CL
.00
.00
3" 3"
4" 1"
1" 5"
1"
.00
8.0 0'
48.00'
000 DAYS
WITHOUT A LOST TIME ACCIDENT
THE LIFE YOU SAVE MAY BE YOUR OWN
GENERAL CONTRACTORS FIRM NAME
ZERO IN ON
SAFETY
ALL VISIBLE SURFACES TO BE
PRIMED AND PAINTED
SIGN ATTACHED TOGETHER WITH
WOOD SCREW & LAG BOLTS
CHANGEABLE NUMBERS
FACE PANEL TO BE AN EXTERIOR GRADE. MDO
SHEERT OR AN ALUMINU M SKIN LAMINATED TO
A WOOD OR PLASTIC CORE IS PREFERRED
WITH EDGES PHYSICALLY SEALED.
4" x 4" POSTS
DEPTH & TYPE OF FOOTING
DETERMINED BY EXISTING
SOIL CONDITIONS.
SECTION A-A
PLAN
A
A
NOT TO SCALEF9
TYPE 1
TYPE 1A
TYPE 2 P.C.C. MEDIAN CURB
P.C.C. MEDIAN CURB (ALTERNATE)
A
PLAN
SECTION A-A
A
NOT TO SCALEC1
NOT TO SCALEF1 NOT TO SCALEF7
" M
IN
" M
IN
3X #4 BARS, CONTINUOUS
3" FROM BOTTOM AND SIDES OF
FOOTING AND SPACED EQUALLY
#5 BAR, 16" ON CENTER, ALTERNATE
TURN DIRECTION AT BOTTOM OF FOOTING
2X #4 BARS, CONTINUOUS
30" MINIMUM
2" ASH FORK, OR APPROVED EQUAL,
SLOPED TOP STONE CAP,
GROUT TO WALL
9' MIN.
REGULAR SPACES
.04
' M
IN
TY
PE
CU
RB
GU
TT
ER
/W
HE
EL
S
TO
P
PE
R
DE
TA
IL
F7 , T
HI
S
SH
EE
T
4" PAINTED PARKING STALL
LINES
9' MIN.
9' MIN.
9' MIN.
TY
PE
CU
RB
W
HE
EL
S
TO
P
PE
R
DE
TA
IL
C1
, T
HI
S
SH
EE
T
6" 4'-0"
10'-0"TO TOP O
F LIGHT
4" ROUND STEEL POLE
7'-0"
SECURITY CAMERA WHERE
SHOWN ON PLANS
POST-MOUNT LED
LIGHT FIXTURE WHERE
SHOWN ON PLANS
CONCRETE FOUNDATION
SEE DETAIL C4, SHEET
CG504
GRADE
12 6
WEATHER-PROOF
MOUNTING BOX
UNDERGROUND CONDUIT -
COORDINATE WITH
ELECTRICAL
GOOSENECK PEDESTAL
ANCHOR BOLTS -
COORDINATE W/ PEDESTAL
MANUFACTURER
CONCRETE CURB -
SEE CIVIL PLANS
12" SQUARE X 30"
DEEP CONCRETE
FOUNDATION
UNDERGROUND CONDUIT -
COORDINATE WITH ELECTRICAL
12"
6"
4'-0"
10'-0"
7'-0"
30"
12" 6"
3'-6"
12"
VA FORM 08 - 6231
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
Revisions: Date:
BID DOCUMENTS
A/E:
TRIPLE C THE A/E GROUP
1839 S. Alma School Rd., Ste 300 Mesa AZ, 85210 307-460-2054 Mat Perkins
654-823-A
975 Kirman Ave, Reno, NV 89502
CONVERT PROCURED RESIDENTIAL
LOTS TO SURFACE LEVEL
ASPHALT PAVED PARKING
CIVIL GRADING DETAILS 2
1030 WILSON AVENUE
APN: 013-172-01
CG502
STRUBLEPERKINS04/29/2022
TYPE 4R CATCH BASIN
TYPE 1 CATCH BASIN
INLET TYPE CATCH BASIN
TYPE 1
TRANSVERSE LONGITUDINAL
DOWELS AT MATCH ISOLATION JOINT
JOINT SEALANT DETAIL
EXPANSION JOINT
NOT TO SCALEC5 NOT TO SCALEC9
NOT TO SCALEE9
LOCKING BAR SECTION A-A
A A
NOT TO SCALEF7
SECTION A-A
NOT TO SCALEC3
DETAIL B (CONSTRUCTION JOINT)DETAIL A (CONTROL JOINT)
A A
SECTION A-A
PLAN
PLAN
SECTION A-A
PCC PAVEMENT EDGE AT ASPHALT PAVEMENT
A A
NOT TO SCALEF4NOT TO SCALEF1
NOT TO SCALEC1
NOT TO SCALEF9 NOT TO SCALEF10
/29
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
Revisions: Date:
BID DOCUMENTS
A/E:
TRIPLE C THE A/E GROUP
1839 S. Alma School Rd., Ste 300 Mesa AZ, 85210 307-460-2054 Mat Perkins
654-823-A
975 Kirman Ave, Reno, NV 89502
CONVERT PROCURED RESIDENTIAL
LOTS TO SURFACE LEVEL
ASPHALT PAVED PARKING
CIVIL GRADING DETAILS 3
1030 WILSON AVENUE
APN: 013-172-01
CG503
STRUBLEPERKINS04/29/2022
NOT TO SCALED1
NOT TO SCALEB4 NOT TO SCALEB6
A.C.
PAVEMENT
DETAIL A7, CG501
24" CONCRETE
CURB & GUTTER
DETAIL F7, CG501
LANDSCAPE
ROCK
EXISTING GROUND
SCREEN WALL
DETAILB9, CG501
A.C.
PAVEMENT
DETAIL A7, CG501
6" CONCRETE
CURB
DETAIL C1, CG501
LANDSCAPE
ROCK
EXISTING GROUND
2.5' MIN.
SEE SHEET CS101
2' MIN.
SEE SHEET CS101
NOT TO SCALEF1
ATTACH TO WALL WITH
TAMPER-PROOF MASONRY ANCHORS -
COORDINATE WITH MANUFACTURER'S
INSTALLATION FOR QUANTITY
AND LOCATION
SE
E
MA
NU
FA
CT
UR
ER
'S
IN
ST
AL
LA
TI
ON
S
(3 6"
IF
N
ON
E
PR
OV
ID
ED
ELECTRICAL ENCLOSURE,
CHARGING PORT
7'- 0"
A
BO
VE
G
RA
DE
SECURITY CAMERA
PROVIDE CONDUIT AND WALL BRACKETS
AS REQUIRED TO ROUTE ELECTRICAL
AND DATA
8' 3.0
0'
PERIMETER FENCE
SEE DETAIL F8, THIS SHEET
F8 NOT TO SCALE
12" SQUARE
8"
2 1 /2"
12" SQUARE
2 1 /2"
2'- 2 1
/2"
2'- 8 1
/2"
2'- 9"
8" SQUARE
NOT TO SCALEF4
R5-1 30"x30"
NOT TO SCALE
PLAN
A A
SECTION A-A
TRAFFIC RATED PULL BOX MINIMUM DIMENSION TABLE
NOT TO SCALEC8
RESTRICTION SIGN
24"x30"
GOVT
PARKING
ONLY
NOT TO SCALE
Uniform Zinc Coating (Hot Dip Galvanized)
Base Material
Uniform Zinc Coating (Hot Dip Galvanized)
Zinc Phosphate & Conversion Coating
Epoxy base coat
4" [44.5mm]
4" [44.5mm]
OPTIONAL 45° SWIVEL BRACKET
PANEL BRACKET
Specially designed two -point connection ensures fixity of rail ends for increased strength.
INTERNAL RETAINING ROD
Variable pitch connection system for ease of installation, high angle bias ability and elimination of unsightly external fasteners.
FORERUNNER RAIL
Double-walled "U"-Channel Specially formed high strength architectural shape.
TM
FORERUNNER RAILTM
"No-Mar" Polyester Powder finish coat
8' [2438.4mm] O.C. Nom.
Varies with
Height 8' [2438.4mm]
1.50' Min.
Footing depth
2" [50.8mm] Nom
4" Typ.
8"
16"
Bracket Options
13 4" [44.5mm] FORERUNNER Rail (See Cross- Section Below)
1" [25.4mm] x 14ga. Picket
TM
Post size varies with Height (See AEGIS II Post-Sizing chart)TM 1
NOTES:
1.) Post size depends on fence height and wind loads.
See AEGIS II post sizing chart.
2.) Panels also available for 6' on center post spacing 3.) Additional heights available on request 4.) Third rail optional.
TM
Values shown are nominal and not to be used for installation purposes. See product specification for installation requirements.
GATE OPENING
6' THROUGH 32'
FENCE LINE
LATCHING POST
LATCH
ROLLER GUIDE POST
ROLLER GUIDE POST
FENCE LINE
V-TRACK
DETAIL B
GA
TE
HE
IG
HT
S
4', 5'
, 6 ', 7
', 8
DETAIL A
DETAIL C
PassPort Commercial Ornamental Roll Gate OR Approved Equal
Ornamental Pickets: 34" Square Top Rail(s), Uprights and Diagonals Braces: 2"Square
Bottom Rail: 2" x 4" (Notched & Plated for V-track Wheels) Roll Gate Hardware : Kit #PGKOD
Available in Profiles of 2-Rail, 3-Rail, & 3-Rail w/Rings
R
1/4" [6.75mm]
SAFETY
SHIELD
ISO VIEW ISO VIEW
DETAIL A DETAIL B
TOP VIEWSIDE VIEW
DETAIL C
/29
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
Revisions: Date:
BID DOCUMENTS
A/E:
TRIPLE C THE A/E GROUP
1839 S. Alma School Rd., Ste 300 Mesa AZ, 85210 307-460-2054 Mat Perkins
654-823-A
975 Kirman Ave, Reno, NV 89502
CONVERT PROCURED RESIDENTIAL
LOTS TO SURFACE LEVEL
ASPHALT PAVED PARKING
CIVIL GRADING DETAILS 4
1030 WILSON AVENUE
APN: 013-172-01
CG504
STRUBLEPERKINS04/29/2022
NOT TO SCALEC8
PLAN
A A
SECTION A-A
PULL BOX MINIMUM DIMENSION TABLE
NOT TO SCALE
MIN
6"
MI
N
EXIST GRADE
C6
TAMPED BACKFILL
3"
MIN
SEE SHEET CU101 FOR
NUMBER AND SIZE OF CONDUITS.
CONDUIT CENTERED IN TRENCH
WHEN SINGLE CONDUIT.
4" ROUND STEEL POLE
PVC CONDUIT ADAPTER
COUPLING
PVC CONDUIT
RIGID STEEL CONDUIT
FINISHED GRADE
1"
2'- 0"
M
IN
UNDISTURBED SOIL OR SELECT
BACKFILL COMPACTED.
UTILITY CONCRETE PER VA
SPECIFICATIONS
4' 6"
12"
NOT TO SCALEC4
/29
TYP.
CONSTRUCT SAFETY SIGN
1"=10'F1 CIVIL UTILITY AND SIGNAGE PLAN
VA FORM 08 - 6231
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
Revisions: Date:
BID DOCUMENTS
A/E:
TRIPLE C THE A/E GROUP
1839 S. Alma School Rd., Ste 300 Mesa AZ, 85210 307-460-2054 Mat Perkins
654-823-A
975 Kirman Ave, Reno, NV 89502
CONVERT PROCURED RESIDENTIAL
LOTS TO SURFACE LEVEL
ASPHALT PAVED PARKING
CIVIL UTILITY AND SIGNAGE PLAN
1030 WILSON AVENUE
APN: 013-172-01
CU101
STRUBLEPERKINS04/29/2022
010' 10' 20'5'
LEGEND
1. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE COMPLETE INSTALLATION OF ALL WORK RELATED TO MECHANICAL UTILITIES AS SHOWN ON THIS PLAN INCLUDING: TRENCHING, BACKFILL, SUPPORTS, CLEANOUT PADS, SERVICE STOPS AND BOXES, SERVICE LINES, TESTING, CLEANING, AND STERILIZING. ANY WORK NOT ACCEPTED BY THE ARCHITECT OR ENGINEER DUE TO IMPROPER WORKMANSHIP OR LACK OF PROPER COORDINATION SHALL BE REMOVED AND CORRECTLY INSTALLED AT THE CONTRACTOR'S EXPENSE, AS
DIRECTED.
2. MINIMUM DEPTHS OF COVER SHALL BE: 36" FOR WATERLINES AND 48" FOR SEWER, EXCEPT AT BUILDING
CONNECTION.
3. ALL WORK DETAILED ON THESE PLANS TO BE PERFORMED UNDER CONTRACT SHALL, EXCEPT AS OTHERWISE STATED OR PROVIDED OF HEREON, BE CONSTRUCTED IN ACCORDANCE WITH THE IAPMO
UNIFORM PLUMBING CODE & NFPA 24, LATEST EDITION.
4. UTILITY LINES SHALL BE INSTALLED PRIOR TO PAVEMENT, CURB AND GUTTER, AND/OR SIDEWALK, AS
APPLICABLE.
5. ROUGH GRADING OF SITE (+/- 0.5') SHALL BE COMPLETED PRIOR TO INSTALLATION OF UTILITY LINES.
6. CONTRACTOR WILL BE RESPONSIBLE FOR CONNECTIONS TO NEW AND EXISTING BUILDING DRAIN LINES AND
ALL NECESSARY FITTINGS.
7. FIRE LINES SHALL USE PIPE MATERIALS UNDERWRITERS LABORATORIES LISTED AND APPROVED FOR FIRE
SERVICE.
8. UTILITY LOCATIONS DETERMINED FROM VA MASTER UTILITY PLAN. CONTRACTOR SHALL VERIFY INVERTS AND LOCATIONS OF EXISTING UTILITY LINES PRIOR TO BEGINNING OF WORK. ALL CONFLICTS SHALL BE
BROUGHT TO ATTENTION OF THE C.O.R. AND RESOLVED PRIOR TO BEGINNING OF WORK.
9. CONTRACTOR SHALL NOTIFY THE AUTHORITY HAVING JURISDICTION PRIOR TO INSTALLATION OF FIRE SERVICE LINES, AND PRIOR TO TESTING OF ALL WATERLINES. CONTRACTOR SHALL COMPLETE, SIGN, AND SUBMIT THE "CONTRACTOR'S MATERIAL & TEST CERTIFICATE FOR UNDERGROUND PIPING" IN ACCORDANCE
WITH NFPA 24.
UTILITY NOTES
1. ALL ELECTRICAL CONDUIT SHOWN IS FOR REFERENCE ONLY. PLEASE SEE ELECTRICAL PLAN E101 FOR
DETAILED INFORMATION.
ELECTRICAL NOTES:
APPLICABLE NOTES FROM THE CURRENT IN-PLACE REQUIREMENTS FOR
DEPARTMENT OF VETERANS AFFAIRS FACILITIES: "SITE DEVELOPMENT DESIGN
MANUAL - FEBRUARY 2013"
5.2 GENERAL UTILITY DESIGN REQUIREMENTS
5.2.1 CLEARANCES AND CROSSINGS
THE A/E SHALL DESIGN THE SITE WITH THE FEWEST CROSSINGS OF UTILITIES POSSIBLE. THE A/E SHALL CONSIDER THE FOLLOWING
ORDER OF PRIORITY FOR UNDERGROUND FACILITIES:
● SANITARY SEWER
● STORM SEWER
● WATER MAIN
● OTHER UTILITIES
5.2.6 MINIMUM DEPTH OF COVER
INDICATE BY NOTES ON DRAWINGS OR DETAIL SECTION, THE MINIMUM DEPTH OF COVER REQUIRED OVER EACH SPECIFIC UTILITY SYSTEM. ALL BURIED UTILITIES SHALL HAVE UNDERGROUND DETECTABLE WARNING TAPE INSTALLED IN THE TRENCH.
● MINIMUM COVER FOR STORM SEWER LINES SHALL BE AT LEAST 2’-0” (600 MM) FROM FINISH GRADES.
● TOP OF POTABLE WATER, CHILLED WATER, FUEL AND APPURTENANCES SHALL BE AT LEAST 1’-0” (300 MM) BELOW FROST
PENETRATION.
● THE MINIMUM DEPTH OF SANITARY SEWER LINES AT THE TERMINUS POINT SHALL BE 4’-0” (1200MM). WHERE PRACTICAL, TOP OF SEWERS SHALL BE AT LEAST 1’-0” (300 MM) BELOW FROST PENETRATION. WHERE SUCH DEPTH BELOW IS NOT PRACTICAL, PROVIDE FREEZE PROTECTION AND/OR SUPPORTING FOUNDATIONS TO A DEPTH BELOW THE FROST LINE AND SECURELY
FASTEN SEWER TO FOUNDATION.
5.2.7 UTILITIES DISTRIBUTION TYPE
THE UTILITY DISTRIBUTION TYPE SHALL BE DETERMINED ON A PROJECT BY PROJECT BASIS. THE A/E MUST CONSIDER THE EXISTING SITE
CONDITIONS AND BUDGET WHEN DECIDING WHAT TYPE TO USE.
5.2.7.1 TRENCHES: GENERALLY, DO NOT INSTALL MORE THAN ONE UTILITY SYSTEM IN THE SAME TRENCH. HOWEVER, DUE TO SITE CONSTRAINTS AND VALUE ENGINEERING CONCEPTS, MULTIPLE UTILITIES IN THE SAME TRENCH WILL BE EVALUATED BY THE GOVERNMENT ON A PER CASE BASIS. PRIOR TO APPROVING ANY MULTIPLE LINE TRENCH, THE A/E SHALL DOCUMENT THAT THE USE OF THE MULTIPLE LINE TRENCH WILL NOT NEGATIVELY IMPACT THE UTILITY SYSTEM, ADEQUATE CLEARANCES ARE PROVIDED FOR THE OPERATION AND MAINTENANCE OF THE SYSTEMS, AND THAT THE JOINT TRENCH WILL NOT POSE ANY CONTRACTIBILITY CONSTRAINTS.
THERE MUST BE A MINIMUM OF 12” (300 MM) BETWEEN THE OUTSIDE DIAMETERS OF ALL PIPES TO OBTAIN THE REQUIRED COMPACTION.
5.2.8 HORIZONTAL CLEARANCE
THE HORIZONTAL CLEARANCE SHALL BE MEASURED BETWEEN THE OUTSIDE DIMENSION OF THE PIPE, DUCT BANK, OR STRUCTURE.
5.2.8.1 WATER AND SANITARY SEWER:
MAINTAIN A HORIZONTAL CLEARANCE BETWEEN POTABLE WATER MAINS AND GRAVITY FLOW SANITARY SEWER/SANITARY SEWER FORCE MAINS OF AT LEAST 10 FEET (3M). THE HORIZONTAL CLEARANCE BETWEEN POTABLE WATER MAINS AND SANITARY SEWER MAINS MAY BE REDUCED TO 6’-0” (1800 MM) WHEN: LOCAL CONDITIONS PREVENT A HORIZONTAL CLEARANCE OF 10’-0” (3 M), THE WATER MAIN INVERT IS A MINIMUM OF 18” (450 MM) ABOVE THE CROWN OF THE SEWER, AND THE WATER MAIN IS IN A TRENCH, SEPARATED BY UNDISTURBED SOIL. WHEN THE SPECIFIED HORIZONTAL CLEARANCE CANNOT BE MET, THE WATER MAIN SHALL BE CONSTRUCTED WITH MECHANICAL JOINT DUCTILE IRON PIPE PER SPECIFICATION 33 10 00 – WATER UTILITIES, AND THE SANITARY SEWER SHALL BE CONSTRUCTED WITH MECHANICAL JOINT PRESSURE RATED DUCTILE IRON PIPE PER SPECIFICATION 33 30 00 – SANITARY SEWAGE UTILITIES. HORIZONTAL CLEARANCES SHALL COMPLY WITH THE REQUIREMENTS OF THE STATE HEALTH DEPARTMENT, DEPARTMENT OF ENVIRONMENTAL
QUALITY, OR AGENCY GOVERNING THE FACILITY OF POTABLE WATER MAINS AND SYSTEMS.
5.2.8.2 WATER AND CHILLED WATER:
MAINTAIN A HORIZONTAL CLEARANCE OF AT LEAST 6’-0” (1800MM) BETWEEN POTABLE WATER MAINS AND RECLAIMED/REUSE AND
CHILLED WATER MAINS.
5.2.8.3 WATER AND STORM SEWER:
MAINTAIN A HORIZONTAL CLEARANCE OF AT LEAST 5’-0” (1500MM) BETWEEN POTABLE WATER MAINS AND STORM SEWERS.
5.2.8.4 DUCT BANKS AND PIPED UTILITIES:
MAINTAIN A HORIZONTAL CLEARANCE OF AT LEAST 3’-0” (900 MM) BETWEEN DUCT BANKS AND PIPED UTILITIES.
5.2.9 VERTICAL CLEARANCE
THE VERTICAL CLEARANCE SHALL BE MEASURED BETWEEN THE OUTSIDE DIMENSION OF THE PIPE, DUCT BANK, OR STRUCTURE. FOR INSULATED PIPING, THE CLEARANCE SHALL BE MEASURED TO THE OUTSIDE OF THE INSULATION. AT UTILITY CROSSINGS WHERE ADEQUATE COMPACTION OF THE BEDDING MATERIAL CANNOT BE OBTAINED, USE FLOWABLE FILL IN THE ZONES WERE COMPACTION IS
IMPOSSIBLE OR IMPRACTICAL.
● MAINTAIN A MINIMUM VERTICAL CLEARANCE OF AT LEAST 1’-0” (300 MM) BETWEEN ALL UTILITIES AT CROSSINGS UNLESS
OTHERWISE SPECIFIED BELOW.
● AT CROSSINGS OF POTABLE WATER MAINS AND SANITARY SEWERS, STORM SEWERS, FORCE MAINS, RECLAIMED/REUSE MAINS, OR CHILLED WATER MAINS, WHERE THE POTABLE WATER MAIN CROSSES ABOVE THE OTHER UTILITY, THE MINIMUM VERTICAL SEPARATION SHALL BE 18” (450 MM), OR AS REQUIRED BY THE STATE HEALTH DEPARTMENT, DEPARTMENT OF ENVIRONMENTAL QUALITY, OR AGENCY GOVERNING THE FACILITY OF POTABLE WATER, WHICHEVER IS GREATER.
● WHERE 18” (450 MM) CANNOT BE MAINTAINED OR WHERE POTABLE WATER LINES CROSS UNDER GRAVITY SEWERS, RECLAIMED/REUSE MAINS, OR CHILLED WATER MAINS, ADDITIONAL PROTECTION SHALL BE PROVIDED AS REQUIRED BY THE AGENCY GOVERNING THE FACILITY OF POTABLE WATER. ADDITIONAL PROTECTION SHALL CONSIST OF CONSTRUCTING BOTH PIPING SYSTEMS WITH DUCTILE IRON PIPE WITH RESTRAINED MECHANICAL JOINTS OR USE OF CONCRETE ENCASEMENT. THE ADDITIONAL PROTECTION SHALL EXTEND A MINIMUM DISTANCE OF 10’-0” (3 M) OUTSIDE THE LIMITS OF THE CROSSING.
● SANITARY SEWER FORCE MAINS SHALL ONLY CROSS UNDER POTABLE WATER MAINS WITH A MINIMUM VERTICAL CLEARANCE OF 18” (450 MM). WHEN THE VERTICAL CLEARANCE BETWEEN THE POTABLE WATER MAIN AND THE FORCE MAIN IS LESS THAN 18” (450 MM), BOTH THE WATER MAIN AND THE FORCE MAIN SHALL BE CONSTRUCTED WITH RESTRAINED MECHANICAL JOINT DUCTILE IRON PIPE AS
INDICATED ABOVE FOR ADDITIONAL PROTECTION.
● THE PREFERRED VERTICAL CLEARANCE BETWEEN DUCT BANKS AND PIPED UTILITIES SHALL BE 2’-0” (300 MM) AND THE MINIMUM
VERTICAL CLEARANCE SHALL BE 18” (450 MM).
● THE MINIMUM VERTICAL CLEARANCE TO ALL STEAM, PUMPED CONDENSATE, AND HOT WATER, AND OTHER UTILITIES SHALL BE AT LEAST 18” (450 MM).