REPAIR AIRCRAFT FIRE TRAINING FACILITY HOMESTEAD AIR RESERVE BASE (HARB) FL
Solicitation number
FA664825R0004
Issued by

About this file

This file contains Unified Facilities Guide Specifications (UFGS) for multiple technical sections related to construction, including fluid-applied waterproofing (07 14 00), joint sealants (07 92 00), stainless steel piping components and valves (22 15 13.16 40), and water utility distribution piping (33 11 00). The UFGS documents provide comprehensive technical specifications for materials, installation methods, quality control, testing requirements, and execution standards for various construction components.

Key details include technical requirements for fluid-applied membrane waterproofing, elastomeric sealants, stainless steel piping systems, and polyethylene water distribution pipes. The specifications cover material compositions, joint connection methods, installation procedures, surface preparation, testing protocols (such as hydrostatic and leakage tests), and quality assurance measures. Each section provides detailed guidance on acceptable materials, installation techniques, performance standards, and field quality control processes for different construction elements, ensuring consistent and high-quality implementation across federal construction projects.

View the file

Other files

File Type Posted
Solicitation Amendment FA664825R00040002 SF 30.pdf PDF
Attachment 17 - Consolidated Requests for Information Q-As (6-4-25).xlsx XLSX spreadsheet
Attachment 17 - Consolidated Requests for Information Q-As.xlsx XLSX spreadsheet
Attachment 19 - Site Visit Sign in Sheet REDACTED.pdf PDF
Solicitation Amendment FA664825R00040001 SF 30.pdf PDF
Attachment 18 - Site Visit Photos.pdf PDF
Attachment 1 - SOW KYJM 18-9007 rev.6 (5-21-25).pdf PDF
Attachment 7 - KYJM18-9007 DRAWINGS.pdf PDF
Attachment 12 - Base Access Form_Blank.pdf PDF
Attachment 5 - UFC 3 250 03.pdf PDF
Attachment 11 - DBA Wage Determination FL20250215 dated 4-11-25.pdf PDF
Attachment 10 - Template - AF 3064 - Progress Schedule.xlsx XLSX spreadsheet
Attachment 3 - UFC 3 230 02.pdf PDF
Attachment 14 - Past Performance Questionnaire.docx DOCX document
Solicitation - FA664825R0004.pdf PDF
Attachment 4 - UFC 3 250 01.pdf PDF
Attachment 8 - KYJM 18-9007_AF 66_Construction.xlsx XLSX spreadsheet
Attachment 1 - SOW KYJM 18-9007 rev.5 (4-24-25).pdf PDF
Attachment 15 - Section L FA664825R0004.pdf PDF
Attachment 2 - T.O. 35E1-2-13-1.pdf PDF
Attachment 16 - Section M FA664825R0004.pdf PDF
Attachment 9 - CONSTRUCTION COST ESTIMATE (BLANK).xlsx XLSX spreadsheet
Attachment 13 - Past Performance Fact Sheet - Fire Trainer (Offeror).docx DOCX document
Show all 23

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

UFGS

USACE / NAVFAC / AFCESA / NASA UFGS-07 14 00 (February 2012) Preparing Activity: NAVFAC Superseding UFGS-07 14 00 (April 2006) UFGS-07141 (December 2003)

UNIFIED FACILITIES GUIDE SPECIFICATIONS

References are in agreement with UMRL dated January 2012

SECTION TABLE OF CONTENTS

DIVISION 07 - THERMAL AND MOISTURE PROTECTION

SECTION 07 14 00

FLUID-APPLIED WATERPROOFING

02/12

PART 1 GENERAL

1.1 REFERENCES

1.2 SUBMITTALS

1.3 PREWATERPROOFING CONFERENCE

1.4 DELIVERY, STORAGE, AND HANDLING

1.5 ENVIRONMENTAL CONDITIONS

1.6 WARRANTY

1.6.1 Roof Membrane Manufacturer Warranty

1.6.2 Roofing System Installer Warranty

1.6.3 Continuance of Warranty

PART 2 PRODUCTS

2.1 FLUID-APPLIED MEMBRANE

2.2 MEMBRANE PRIMER

2.3 SEALANT

2.4 SEALANT PRIMER

2.5 BACKING MATERIAL

2.6 [JOINT FILLER

2.7 BOND BREAKER

2.8 ELASTOMERIC SHEET

2.9 ELASTOMERIC SHEET ADHESIVE

2.10 FLEXIBLE FOAM-BACKED ELASTOMERIC SHEET

2.11 PROTECTION BOARD

2.12 DRAINAGE COURSE AGGREGATE

2.13 INSULATION

PART 3 EXECUTION

3.1 PREPARATION

3.1.1 Flashings

3.1.1.1 Drains

3.1.1.2 Penetrations and Projections

3.1.1.3 Walls and Vertical Surfaces

SECTION 07 14 00 Page 1

3.1.2 Cracks and Joints

3.1.3 Priming

3.2 SPECIAL PRECAUTIONS

3.3 APPLICATION

3.3.1 Work Sequence

3.3.2 Protection Board

3.3.3 Drainage Course

3.3.4 Insulation

3.4 FIELD QUALITY CONTROL

3.4.1 Moisture Test

3.4.2 Film Thickness

3.4.3 Flood Test

3.5 INSTRUCTIONS TO GOVERNMENT PERSONNEL

3.6 INFORMATION CARD

-- End of Section Table of Contents --

SECTION 07 14 00 Page 2

USACE / NAVFAC / AFCESA / NASA UFGS-07 14 00 (February 2012) Preparing Activity: NAVFAC Superseding UFGS-07 14 00 (April 2006) UFGS-07141 (December 2003)

UNIFIED FACILITIES GUIDE SPECIFICATIONS

References are in agreement with UMRL dated January 2012

SECTION 07 14 00

FLUID-APPLIED WATERPROOFING

02/12

NOTE: This guide specification covers the requirements for fluid-applied elastomeric waterproofing systems for building decks over occupied space where membrane is protected of a separate wearing course.

Adhere to UFC 1-300-02 Unified Facilities Guide Specifications (UFGS) Format Standard when editing this guide specification or preparing new project specification sections. Edit this guide specification for project specific requirements by adding, deleting, or revising text. For bracketed items, choose applicable items(s) or insert appropriate information.

Remove information and requirements not required in respective project, whether or not brackets are present.

Comments, suggestions and recommended changes for this guide specification are welcome and should be submitted as a Criteria Change Request (CCR).

NOTE: This guide specification should not be used to specify waterproofing of structures subject to hydrostatic pressure. It includes the fluid-applied membrane, protection board, drainage layer, and insulation. It does not include structural deck, protection slab, or wearing course; these elements influence performance of the waterproofing system.

See UFC 3-110-03, "Roofing" for design recommendations.

Technical Reference: ASTM C898, "High Solids Content, Cold Liquid-Applied Elastomeric Waterproofing Membrane with Separate Wearing

SECTION 07 14 00 Page 3

Course." This document contains guidelines for design of the waterproofing system, and may be used as a source of supplementary information.

1. Slope: Provide slope toward drains (after deflections due to applied load and creep) of not less than one percent 10 mm per meter 1/8 inch per foot.

2. Wall Flashing: Extend wall flashing to at least 100 mm 4 inches above wearing surface and higher where exposure is more severe. If top of flashing is recessed under a concrete wall, counterflashing is not necessary. Metal counterflashing is necessary at masonry wall intersections. Flash right-angle intersection of deck and wall with an elastomeric sheet.

NOTE: This section contains both metric and inch-pound graphics.

NUMBER TITLE

1 Basic Components of Membrane with Separate Wearing Course 2 Flashing at Cracks and Nonmoving Joints in the Concrete 3 Expansion Joint Flashing 4 Expansion Joint Flashing at Wall 5 Terminal Condition with Masonry Above Finish Wearing Surface at Grade 6 Wall Flashing on Concrete Wall 7 Wall - Deck Flashing 8 Penetration Flashing 9 Drain Flashing

DO NOT INCLUDE THE SKETCHES OR LIST OF SKETCHES IN

THE PROJECT SPECIFICATIONS. USE SKETCHES FOR

PREPARING DETAILS ON THE DRAWINGS.

NOTE: TO DOWNLOAD UFGS GRAPHICS

Go to http://www.wbdg.org/ccb/NAVGRAPH/graphtoc.pdf.

PART 1 GENERAL

1.1 REFERENCES

NOTE: This paragraph is used to list the publications cited in the text of the guide specification. The publications are referred to in the text by basic designation only and listed in this paragraph by organization, designation, date, and title.

SECTION 07 14 00 Page 4

Use the Reference Wizard's Check Reference feature when you add a RID outside of the Section's Reference Article to automatically place the reference in the Reference Article. Also use the Reference Wizard's Check Reference feature to update the issue dates.

References not used in the text will automatically be deleted from this section of the project specification when you choose to reconcile references in the publish print process.

The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.

ASTM INTERNATIONAL (ASTM)

ASTM C33/C33M (2011a) Standard Specification for Concrete Aggregates

ASTM C578 (2011a) Standard Specification for Rigid, Cellular Polystyrene Thermal Insulation

ASTM C836/C836M (2011a) High Solids Content, Cold Liquid-Applied Elastomeric Waterproofing Membrane for Use With Separate Wearing Course

ASTM D1056 (2007) Standard Specification for Flexible Cellular Materials - Sponge or Expanded Rubber

ASTM D1751 (2004; R 2008) Standard Specification for Preformed Expansion Joint Filler for Concrete Paving and Structural Construction (Nonextruding and Resilient Bituminous Types)

ASTM D1752 (2004a; R 2008) Standard Specification for Preformed Sponge Rubber Cork and Recycled PVC Expansion

1.2 SUBMITTALS

NOTE: Review Submittal Description (SD) definitions in Section 01 33 00 SUBMITTAL PROCEDURES and edit the following list to reflect only the submittals required for the project.

The Guide Specification technical editors have designated those items that require Government approval, due to their complexity or criticality, with a "G". Generally, other submittal items can be reviewed by the Contractor's Quality Control System. Only add a “G” to an item, if the submittal is sufficiently important or complex in

SECTION 07 14 00 Page 5 context of the project.

For submittals requiring Government approval on Army projects, a code of up to three characters within the submittal tags may be used following the "G" designation to indicate the approving authority.

Codes for Army projects using the Resident Management System (RMS) are: "AE" for Architect-Engineer; "DO" for District Office (Engineering Division or other organization in the District Office); "AO" for Area Office; "RO" for Resident Office; and "PO" for Project Office. Codes following the "G" typically are not used for Navy, Air Force, and NASA projects.

Choose the first bracketed item for Navy, Air Force and NASA projects, or choose the second bracketed item for Army projects.

Government approval is required for submittals with a "G" designation;

submittals not having a "G" designation are [for Contractor Quality Control approval.][for information only. When used, a designation following the "G" designation identifies the office that will review the submittal for the Government.] The following shall be submitted in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:

SD-03 Product Data

Fluid-applied membrane

Membrane primer

Elastomeric sheet

Flexible foam-backed elastomeric sheet

Solvent

Moisture meter

Protection board

Bond breaker

Submit material description and physical properties, application details, and recommendations regarding shelf life, application procedures, and precautions on flammability and toxicity.

SD-11 Closeout Submittals

Warranty

Information Card

Instructions To Government Personnel

Include copies of Material Safety Data Sheets for maintenance/repair materials.

SECTION 07 14 00 Page 6

1.3 PREWATERPROOFING CONFERENCE

NOTE: Include the requirement for a prewaterproofing conference when the waterproofing system will be used on large areas, e.g., promenade decks over occupied space, and will require work by other trades, e.g., mechanical subcontractors, electrical subcontractor, or tile setters on the membrane.

Prior to starting application of waterproofing system, arrange and attend a prewaterproofing conference to ensure a clear understanding of drawings and specifications. Give the Contracting Officer 7 days advance written notice of the time and place of meeting. Ensure that the mechanical and electrical subcontractor, flashing and sheetmetal subcontractor, and other trades that may perform other types of work on or over the membrane after installation, attend this conference.

1.4 DELIVERY, STORAGE, AND HANDLING

Deliver waterproofing materials in manufacturer's original, unopened containers, with labels intact and legible. Containers of materials covered by a referenced specification number shall bear the specification number, type, and class of the contents. Deliver materials in sufficient quantity to continue work without interruption. Store and protect materials in accordance with manufacturer's instructions, and use within their indicated shelf life. When hazardous materials are involved, adhere to special precautions of the manufacturer, unless precautions conflict with local, state, and federal regulations. Promptly remove from the site materials or incomplete work adversely affected by exposure to moisture or freezing. Store materials on pallets and cover from top to bottom with canvas tarpaulins.

1.5 ENVIRONMENTAL CONDITIONS

Apply materials when ambient temperature is 4 degrees C 40 degrees F or above for a period of 24 hours prior to the application and when there is no ice, frost, surface moisture, or visible dampness on the substrate surface. Apply materials when air temperature is expected to remain above 4 degrees C 40 degrees F during the cure period recommended by the manufacturer. Moisture test for substrate is specified under paragraph entitled "Moisture Test." Work may be performed within heated enclosures, provided the surface temperature of the substrate is maintained at a minimum of 4 degrees C 40 degrees F for 24 hours prior to the application of the waterproofing, and remains above that temperature during the cure period recommended by the manufacturer.

1.6 WARRANTY

Provide roof system material and workmanship warranties meeting specified requirements. Provide revisions or amendment to standard membrane manufacturer warranty to comply with the specified requirements. Minimum manufacturer warranty shall have no dollar limit, cover full system water-tightness, and shall have a minimum duration of 20 years.

SECTION 07 14 00 Page 7

1.6.1 Roof Membrane Manufacturer Warranty

NOTE: Insulated and routinely occupied facilities or facilities containing sensitive equipment or operations require a warranty of not less than 15 years. Designer may specify 5 or 10 year manufacturer warranty on facilities of small roof area and of minor importance where interiors and contents are not severely impacted by potential water intrusion. Environmentally controlled interiors require minimum 10 year warranty regardless of small size.

Furnish the roof membrane manufacturer's 20-year no dollar limit roof system materials and installation workmanship warranty, including flashing, insulation, and accessories necessary for a watertight roof system construction. Write the warranty directly to the Government commencing at time of Government's acceptance of the roof work. Provide the the following statements for such warranty:

a. If within the warranty period the roof system, as installed for its intended use in the normal climatic and environmental conditions of the facility, becomes non-watertight, shows evidence of moisture intrusion within the assembly, blisters, splits, tears, cracks, delaminates, separates at the seams, or shows evidence of excessive weathering due to defective materials or installation workmanship, the repair or replacement of the defective and damaged materials of the roof system assembly and correction of defective workmanship are the responsibility of the roof membrane manufacturer. All cost associated with the repair or replacement work are the responsibility of the roof membrane manufacturer.

b. The warranty must remain in full force and effect, including emergency temporary repairs performed by others, when the manufacturer or his approved applicator fail to perform the repairs within 72 hours of notification.

1.6.2 Roofing System Installer Warranty

The roof system installer must warrant for a minimum period of two years that the roof system, as installed, is free from defects in installation workmanship, to include the roof membrane, flashing, insulation, accessories, attachments, and sheet metal installation integral to a complete watertight roof system assembly. Write the warranty directly to the Government. The roof system installer is responsible for correction of defective workmanship and replacement of damaged or affected materials.

The roof system installer is responsible for all costs associated with the repair or replacement work.

1.6.3 Continuance of Warranty

Approve repair or replacement work that becomes necessary within the warranty period and accomplished in a manner so as to restore the integrity of the roof system assembly and validity of the roof membrane manufacturer warranty for the remainder of the manufacturer warranty period.

SECTION 07 14 00 Page 8

PART 2 PRODUCTS

2.1 FLUID-APPLIED MEMBRANE

NOTE: ASTM C836/C836M is a materials performance specification; it does not specify any particular elastomer or elastomeric-extender combination.

ASTM C836/C836M.

2.2 MEMBRANE PRIMER

As recommended by the fluid-applied membrane manufacturer unless specifically prohibited by the manufacturer of the fluid-applied membrane.

2.3 SEALANT

NOTE: Specify sealant conforming to FS TT-S-227 or FS TT-S-230 in Section 07 92 00 JOINT SEALANTS. If no such section is required, specify sealant in this section.

As specified in Section 07 92 00 JOINT SEALANTS.

2.4 SEALANT PRIMER

As specified in Section 07 92 00 JOINT SEALANTS.

2.5 BACKING MATERIAL

NOTE: Include the following paragraph in Section

07 92 00 JOINT SEALANTS.

"Special Backing Material: Backing materials used for sealants in conjunction with fluid-applied waterproofing are specified in this section.

Premolded, closed-cell, polyethylene, or polyurethane foam rod having a diameter 25 percent larger than joint width before being compressed into joint. Provide bond breaker of polyethylene film or other suitable material between backing material and sealant.

2.6 [JOINT FILLER

As specified in [Section 03 30 00 CAST-IN-PLACE CONCRETE,] [ASTM D1751] [or] [ASTM D1752].]

2.7 BOND BREAKER

As recommended by the fluid-applied membrane manufacturer. Bond breaker shall not interfere with the curing process or other performance properties of the fluid-applied membrane.

SECTION 07 14 00 Page 9

2.8 ELASTOMERIC SHEET

Preformed; as recommended by the fluid-applied membrane manufacturer. Bond strength between the fluid-applied membrane and the preformed elastomeric sheet shall be a minimum of 7 kPa one psi when tested in accordance with

ASTM C836/C836M.

2.9 ELASTOMERIC SHEET ADHESIVE

As recommended by the elastomeric sheet manufacturer.

2.10 FLEXIBLE FOAM-BACKED ELASTOMERIC SHEET

Flexible foam-backed elastomeric sheet for protection over preformed elastomeric sheet at expansion joints shall be 13 mm 1/2 inch thick, minimum, closed cell foam conforming to ASTM D1056, Type 2, Class B, Grades 2 or 3, factory-bonded to 2 mm 1/16 inch thick, minimum, preformed elastomeric sheet.

2.11 PROTECTION BOARD

Premolded bitumen composition board, 3 mm 1/8 inch minimum thickness or other composition board compatible with the fluid-applied membrane.

2.12 DRAINAGE COURSE AGGREGATE

ASTM C33/C33M, size No. 8.

2.13 INSULATION

Polystyrene foam conforming to ASTM C578, Class IV, thickness as [indicated] [required by indicated R-value].

PART 3 EXECUTION

3.1 PREPARATION

Coordinate work with that of other trades to ensure that components to be incorporated into the waterproofing system are available when needed.

Inspect and approve surfaces immediately before application of waterproofing materials. Remove laitance, loose aggregate, sharp projections, grease, oil, dirt, curing compounds, and other contaminants which could adversely affect the complete bonding of the fluid-applied membrane to the concrete surface.

3.1.1 Flashings

Make penetrations through sleeves in concrete slab watertight before application of waterproofing. After flashing is completed, cover elastomeric sheet with fluid-applied waterproofing during waterproofing application.

3.1.1.1 Drains

Make drain flanges flush with surface of structural slab. Apply a full elastomeric sheet around the drain, with edges fully adhered to drain flange and to structural slab. Do not adhere elastomeric sheet over joint between drain and concrete slab. Do not plug drainage or weep holes. Cover elastomeric sheet with fluid-applied waterproofing during waterproofing

SECTION 07 14 00 Page 10 application. Lap elastomeric sheet a minimum of 100 mm 4 inches onto concrete slab.

3.1.1.2 Penetrations and Projections

Flash penetrations and projections through structural slab with an elastomeric sheet adhered to the concrete slab and the penetration. Leave elastomeric sheet unadhered for 25 mm one inch over joint between penetration and concrete slab. Adhere elastomeric sheet a minimum of 100 mm 4 inches onto horizontal deck.

3.1.1.3 Walls and Vertical Surfaces

Flash wall intersections which are not of monolithic pour or constructed with reinforced concrete joints with an elastomeric sheet adhered to both vertical wall surfaces and concrete slab. Flash intersections which are monolithically poured or constructed with reinforced concrete joints with either an elastomeric sheet or a vertical grade of fluid-applied waterproofing adhered to vertical wall surfaces and concrete slab. Leave sheet unadhered for a distance of 25 mm one inch from the corner on both vertical and horizontal surfaces.

3.1.2 Cracks and Joints

Prepare visible cracks and joints in substrate to receive fluid-applied waterproofing membrane by placing a bond breaker and an elastomeric slip sheet between membrane and substrate. Cracks that show movement shall receive a 50 mm 2 inch bond breaker followed by an elastomeric sheet adhered to the deck. Nonmoving cracks shall be double coated with fluid-applied waterproofing.

3.1.3 Priming

Prime surfaces to receive fluid-applied waterproofing membrane. Apply primer as required by membrane manufacturer's printed instructions.

3.2 SPECIAL PRECAUTIONS

Protect waterproofing materials during transport and application. Do not dilute primers and other materials, unless specifically recommended by materials manufacturer. Keep containers closed except when removing contents. Do not mix remains of unlike materials. Thoroughly remove residual materials before using application equipment for mixing and transporting materials. Do not permit equipment on the project site that has residue of materials used on previous projects. Use cleaners only for cleaning, not for thinning primers or membrane materials. Ensure that workers and others who walk on cured membrane wear clean, soft-soled shoes to avoid damaging the waterproofing materials.

3.3 APPLICATION

Over primed surfaces, provide a uniform, wet, monolithic coating of fluid-applied membrane, 1.5 mm 60 mils thick, plus or minus 0.125 mm 5 mils by following manufacturer's printed instructions. Apply material by trowel, squeegee, roller, brush, spray apparatus, or other method recommended by membrane manufacturer. Check wet film thickness as specified in paragraph entitled "Film Thickness" and adjust application rate as necessary to provide a uniform coating of the thickness specified.

Where possible, mark off surface to be coated in equal units to facilitate

SECTION 07 14 00 Page 11 proper coverage. At expansion joints, control joints, prepared cracks, flashing, and terminations, carry membrane over preformed elastomeric sheet in a uniform 1.5 mm 60 mil thick, plus or minus 0.125 mm 5 mils, wet thickness to provide a monolithic coating. If membrane cures before next application, wipe previously applied membrane with a solvent to remove dirt and dust that could inhibit adhesion of overlapping membrane coat. Use solvent recommended by the membrane manufacturer, as approved.

3.3.1 Work Sequence

Perform work so that protection board is installed prior to using the waterproofed surface. Do not permanently install protection board until the membrane has passed the flood test specified under paragraph entitled "Flood Test." Move material storage areas as work progresses to prevent abuse of membrane and overloading of structural deck.

3.3.2 Protection Board

Protect fluid-applied membrane by placing protection board over membrane at a time recommended by the membrane manufacturer. Protect membrane application when protection board is not placed immediately. Butt protection boards together and do not overlap.

3.3.3 Drainage Course

Place drainage course where shown after flood tests are completed and concrete protection slab or wearing course is ready to be installed.

3.3.4 Insulation

Place insulation of thickness indicated, on top of drainage course just prior to placement of concrete protection slab.

3.4 FIELD QUALITY CONTROL

3.4.1 Moisture Test

Prior to application of fluid-applied waterproofing, measure moisture content of substrate with a moisture meter in the presence of the Contracting Officer. An acceptable device is the Delmhorst Moisture Meter, Model BD7/2E/CS, Type 21 E. Similar meters by other manufacturers, which are suitable for the purpose, may be used as approved by the Contracting Officer. Do not begin application until meter reading indicates "dry" range.

3.4.2 Film Thickness

Measure wet film thickness every 10 square meters 100 square feetduring application by placing flat metal plates on the substrate or using a mil-thickness gage especially manufactured for the purpose.

3.4.3 Flood Test

After application and curing is complete, plug drains and fill waterproofed area with water to a depth of 50 mm 2 inches. A minimum 48 hour cure time, or longer cure time if recommended by the membrane manufacturer, shall be required prior to flood testing. Allow water to stand 24 hours. Test watertightness by measuring water level at beginning and end of the 24 hour period. If water level falls, drain water, allow installation to dry, and

SECTION 07 14 00 Page 12 inspect. Make repairs or replace as required and repeat the test. Work shall not proceed before approval of repairs or replacement.

3.5 INSTRUCTIONS TO GOVERNMENT PERSONNEL

Furnish written and verbal instructions on proper maintenance procedures to designated Government personnel. Furnish instructions by a competent representative of the roof membrane manufacturer and include a minimum of 4 hours on maintenance and emergency repair of the membrane. Include a demonstration of membrane repair, and give sources of required special tools. Furnish information on safety requirements during maintenance and emergency repair operations.

3.6 INFORMATION CARD

For each roof application, furnish a minimum 215 mm 8-1/2 inch by 11 inch information card for facility records and a card laminated in plastic and framed for interior display at roof access point, or a photoengraved 1 mm

0.032 inch thick aluminum card for exterior display. Identify facility name and number; location; contract number; approximate roof area; detailed roof system description, including deck type, membrane, number of plies, method of application, manufacturer, insulation and cover board system and thickness; presence of tapered insulation for primary drainage, presence of vapor retarder; date of completion; installing contractor identification and contract information; membrane manufacturer warranty expiration, warranty reference number, and contact information. Install card at roof top or access location as directed by the Contracting Officer and provide a paper copy to the Contracting Officer.

SECTION 07 14 00 Page 13

FORM 1

FLUID-APPLIED WATERPROOFING SYSTEM COMPONENTS

1. Contract Number

2. Date Work Completed

3. Project Specification Designation

4. Substrate Material

5. Slope of Substrate

6. Drains Type/Manufacturer

7. Waterproofing

a. Membrane

b. Sealant

c. Elastomeric Sheet

d. Materials Manufacturer(s)

8. Protection Board

a. Type

b. Thickness

c. Manufacturer's Name

9. Drainage Course Material Graduation

10. Insulation

a. Type

b. Thickness

c. Manufacturer's Name

11. Protection Slab

a. Material

b. Thickness

c. Support

d. Joint System

12. Wearing Course

a. Type

b. Slope

c. Joint System

d. Sealant/Gasket Type

13. Wearing Surface Type

SECTION 07 14 00 Page 14

Manufacturer's Name

14. Warranty

a. Manufacturer warranty expiration

b. Warranty reference number

15. Statement of Compliance or Exception

Contractor's Signature Date Signed

Inspector's Signature Date Signed

-- End of Section --

SECTION 07 14 00 Page 15

USACE / NAVFAC / AFCESA / NASA UFGS-07 92 00 (January 2007) Preparing Activity: NAVFAC Superseding UFGS-07 92 00 (April 2006) UFGS-07 92 00.00 40 (April 2006)

UNIFIED FACILITIES GUIDE SPECIFICATIONS

References are in agreement with UMRL dated January 2012

SECTION TABLE OF CONTENTS

DIVISION 07 - THERMAL AND MOISTURE PROTECTION

SECTION 07 92 00

JOINT SEALANTS

01/07

PART 1 GENERAL

1.1 REFERENCES

1.2 SUBMITTALS

1.3 ENVIRONMENTAL CONDITIONS

1.4 DELIVERY AND STORAGE

1.5 QUALITY ASSURANCE

1.5.1 Compatibility with Substrate

1.5.2 Joint Tolerance

1.5.3 Mock-Up

1.6 SPECIAL WARRANTY

PART 2 PRODUCTS

2.1 SEALANTS

2.1.1 Interior Sealant

2.1.2 Exterior Sealant

2.1.3 Floor Joint Sealant

2.1.4 Acoustical Sealant

2.1.5 Preformed Sealant

2.1.5.1 Tape

2.1.5.2 Bead

2.1.5.3 Foam Strip

2.2 PRIMERS

2.3 BOND BREAKERS

2.4 BACKSTOPS

2.4.1 Rubber

2.4.2 PVC

2.4.3 Synthetic Rubber

2.4.4 Neoprene

2.4.5 Butyl Rubber Based

2.4.6 Silicon Rubber Base

2.5 CAULKING

2.6 CLEANING SOLVENTS

SECTION 07 92 00 Page 1

PART 3 EXECUTION

3.1 SURFACE PREPARATION

3.1.1 Steel Surfaces

3.1.2 Aluminum or Bronze Surfaces

3.1.3 Concrete and Masonry Surfaces

3.1.4 Wood Surfaces

3.2 SEALANT PREPARATION

3.3 APPLICATION

3.3.1 Joint Width-To-Depth Ratios

3.3.2 Masking Tape

3.3.3 Backstops

3.3.4 Primer

3.3.5 Bond Breaker

3.3.6 Sealants

3.4 PROTECTION AND CLEANING

3.4.1 Protection

3.4.2 Final Cleaning

SECTION 07 92 00 Page 2

USACE / NAVFAC / AFCESA / NASA UFGS-07 92 00 (January 2007) Preparing Activity: NAVFAC Superseding UFGS-07 92 00 (April 2006) UFGS-07 92 00.00 40 (April 2006)

UNIFIED FACILITIES GUIDE SPECIFICATIONS

References are in agreement with UMRL dated January 2012

SECTION 07 92 00

JOINT SEALANTS

01/07

NOTE: This guide specification covers the requirements for sealants for normal building construction.

Adhere to UFC 1-300-02 Unified Facilities Guide Specifications (UFGS) Format Standard when editing this guide specification or preparing new project specification sections. Edit this guide specification for project specific requirements by adding, deleting, or revising text. For bracketed items, choose applicable items(s) or insert appropriate information.

Remove information and requirements not required in respective project, whether or not brackets are present.

Comments, suggestions and recommended changes for this guide specification are welcome and should be submitted as a Criteria Change Request (CCR).

NOTE: This guide specification must be carefully modified if resealing or sealing of an addition to an existing building is required or if conditions require use of special sealing materials and designs such as high-rise curtain wall systems.

NOTE: On the drawings, show:

1. Joints in which each type of sealant will be used.

2. Typical scale or full-size details of sealant joints, indicating joint symbol or designation.

SECTION 07 92 00 Page 3

PART 1 GENERAL

1.1 REFERENCES

NOTE: This paragraph is used to list the publications cited in the text of the guide specification. The publications are referred to in the text by basic designation only and listed in this paragraph by organization, designation, date, and title.

Use the Reference Wizard's Check Reference feature when you add a RID outside of the Section's Reference Article to automatically place the reference in the Reference Article. Also use the Reference Wizard's Check Reference feature to update the issue dates.

References not used in the text will automatically be deleted from this section of the project specification when you choose to reconcile references in the publish print process.

The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.

ASTM INTERNATIONAL (ASTM)

ASTM C1311 (2010) Standard Specification for Solvent Release Agents

ASTM C509 (2006; R 2011) Elastomeric Cellular Preformed Gasket and Sealing Material

ASTM C734 (2006) Low-Temperature Flexibility of Latex Sealants After Artificial Weathering

ASTM C834 (2010) Latex Sealants

ASTM C919 (2008) Use of Sealants in Acoustical Applications

ASTM C920 (2011) Standard Specification for Elastomeric Joint Sealants

ASTM D1056 (2007) Standard Specification for Flexible Cellular Materials - Sponge or Expanded Rubber

ASTM D1667 (2005; R 2011) Flexible Cellular Materials

- Poly (Vinyl Chloride) Foam (Closed-Cell)

ASTM D217 (2010) Cone Penetration of Lubricating Grease

ASTM D2452 (2003; R 2009) Standard Test Method for

SECTION 07 92 00 Page 4

Extrudability of Oil- and Resin-Base Caulking Compounds

ASTM D2453 (2003; R 2009) Standard Test Method for Shrinkage and Tenacity of Oil- and Resin-Base Caulking Compounds

ASTM E84 (2011b) Standard Test Method for Surface Burning Characteristics of Building Materials

1.2 SUBMITTALS

NOTE: Review Submittal Description (SD) definitions in Section 01 33 00 SUBMITTAL PROCEDURES and edit the following list to reflect only the submittals required for the project.

The Guide Specification technical editors have designated those items that require Government approval, due to their complexity or criticality, with a "G". Generally, other submittal items can be reviewed by the Contractor's Quality Control System. Only add a “G” to an item, if the submittal is sufficiently important or complex in context of the project.

For submittals requiring Government approval on Army projects, a code of up to three characters within the submittal tags may be used following the "G" designation to indicate the approving authority.

Codes for Army projects using the Resident Management System (RMS) are: "AE" for Architect-Engineer; "DO" for District Office (Engineering Division or other organization in the District Office); "AO" for Area Office; "RO" for Resident Office; and "PO" for Project Office. Codes following the "G" typically are not used for Navy, Air Force, and NASA projects.

Choose the first bracketed item for Navy, Air Force and NASA projects, or choose the second bracketed item for Army projects.

Government approval is required for submittals with a "G" designation;

submittals not having a "G" designation are [for Contractor Quality Control approval.][for information only. When used, a designation following the "G" designation identifies the office that will review the submittal for the Government.] Submit the following in accordance with Section 01 33 00

SUBMITTAL PROCEDURES:

SD-03 Product Data

Sealants

Primers

SECTION 07 92 00 Page 5

Bond breakers

Backstops

Manufacturer's descriptive data including storage requirements, shelf life, curing time, instructions for mixing and application, and primer data (if required). Provide a copy of the Material Safety Data Sheet for each solvent, primer or sealant material.

SD-07 Certificates

Sealant

Certificates of compliance stating that the materials conform to the specified requirements.

1.3 ENVIRONMENTAL CONDITIONS

Apply sealant when the ambient temperature is between 4 and 32 degrees C 40 and 90 degrees F.

1.4 DELIVERY AND STORAGE

Deliver materials to the job site in unopened manufacturers' external shipping containers, with brand names, date of manufacture, [color,] and material designation clearly marked thereon. Label elastomeric sealant containers to identify type, class, grade, and use. Carefully handle and store materials to prevent inclusion of foreign materials or subjection to sustained temperatures exceeding 32 degrees C 90 degrees F or less than 4 degrees C 0 degrees F.

1.5 QUALITY ASSURANCE

1.5.1 Compatibility with Substrate

Verify that each of the sealants are compatible for use with joint substrates.

1.5.2 Joint Tolerance

Provide joint tolerances in accordance with manufacturer's printed instructions.

1.5.3 Mock-Up

Project personnel is responsible for installing sealants in mock-up [prepared by other trades], using materials and techniques approved for use on the project.

1.6 SPECIAL WARRANTY

Guarantee sealant joint against failure of sealant and against water penetration through each sealed joint for [five] [_____] years.

PART 2 PRODUCTS

2.1 SEALANTS

SECTION 07 92 00 Page 6

NOTE: Use Latex Sealant (ASTM C834) for temporary, low budget construction; interior sealing of joints in wood or masonry, or in short joints between masonry, wood, or metal surfaces where maximum movement is anticipated not to exceed 15 percent of joint width.

Use elastomeric Sealants (ASTM C920) for interior and exterior applications where maximum joint movement is anticipated to be between 25 and 50 percent of joint width.

Chemically curing sealants should not be used adjacent to or above membrane surfaces of asphaltic or bituminous materials; a sealant based on asphalt or bituminous materials similar to those in the membrane should be used.

Since all sealants meeting this specification are not suitable for all applications and substrates, specify applicable type, grade, class, and use(s) for each intended purpose:

Type S: Single-component

Type M: Multicomponent

Grade P: Pourable or self-leveling sealant for horizontal applications

Grade NS: Nonsag for vertical applications

Class 25: Withstands increase and decrease of at least 25 percent of joint width

Class 12.5: Withstands increase and decrease of at least 12.5 percent of joint width

Use T: Pedestrian and vehicular traffic areas such as walkways, plazas, decks, and parking garages

Use NT: Nontraffic areas, horizontal and vertical surfaces

Use M: Meets this specification when tested on mortar

Use G: Meets this specification when tested on glass

Use A: Meets this specification when tested on aluminum

Use O: Meets this specification when tested on substrates other than above. Specify substrate types in project specification.

Provide sealant that has been tested and found suitable for the substrates to which it will be applied.

SECTION 07 92 00 Page 7

2.1.1 Interior Sealant

Provide [ASTM C834] [ASTM C920, Type S or M, Grade NS, Class 12.5, Use NT]. Location(s) and color(s) of sealant for the following:

LOCATION COLOR

a. Small voids between walls or partitions and [As selected] adjacent lockers, casework, shelving, [Gray] [White] door frames, built-in or surface-mounted [_____] equipment and fixtures, and similar items.

b. Perimeter of frames at doors, windows, [_____] and access panels which adjoin exposed interior concrete and masonry surfaces.

c. Joints of interior masonry walls and [_____] partitions which adjoin columns, pilasters, concrete walls, and exterior walls unless otherwise detailed.

d. Joints between edge members for acoustical [_____] tile and adjoining vertical surfaces.

e. Interior locations, not otherwise indicated [_____] or specified, where small voids exist between materials specified to be painted.

f. Joints between bathtubs and ceramic tile; [_____] joints between shower receptors and ceramic tile; joints formed where nonplaner tile surfaces meet.

g. Joints formed between tile floors and tile [_____] base cove; joints between tile and dissimilar materials; joints occurring where substrates change.

h. Behind escutcheon plates at valve pipe [_____] penetrations and showerheads in showers.

i. [_____] [_____]

2.1.2 Exterior Sealant

For joints in vertical surfaces, provide ASTM C920, Type S or M, Grade NS, Class 25, Use NT. For joints in horizontal surfaces, provide ASTM C920, Type S or M, Grade P, Class 25, Use T. Provide location(s) and color(s) of sealant as follows:

LOCATION COLOR

a. Joints and recesses formed where frames [Match adjacent and subsills of windows, doors, louvers, surface color] and vents adjoin masonry, concrete, or [As selected] metal frames. Use sealant at both exterior [Gray] [White] and interior surfaces of exterior wall [_____] penetrations.

SECTION 07 92 00 Page 8

LOCATION COLOR

b. Joints between new and existing exterior [_____] masonry walls.

c. Masonry joints where shelf angles occur. [_____]

d. Joints in wash surfaces of stonework. [_____]

e. Expansion and control joints. [_____]

f. Interior face of expansion joints in [_____] exterior concrete or masonry walls where metal expansion joint covers are not required.

g. Voids where items pass through exterior [_____] walls.

h. Metal reglets, where flashing is inserted [_____] into masonry joints, and where flashing is penetrated by coping dowels.

i. Metal-to-metal joints where sealant is [_____] indicated or specified.

j. Joints between ends of gravel stops, fascias, [_____] copings, and adjacent walls.

k. [_____] [_____]

2.1.3 Floor Joint Sealant

ASTM C920, Type S or M, Grade P, Class 25, Use T. Provide location(s) and color(s) of sealant as follows:

LOCATION COLOR

a. Seats of metal thresholds for [As selected] exterior doors. [Gray] [White]

b. Control and expansion joints in floors, [_____] slabs, ceramic tile, and walkways.

2.1.4 Acoustical Sealant

NOTE: See ASTM C919 for use of acoustical sealant.

The acoustical sealant described here is to be used only in non-moving joints protected from abuse.

Other specified sealants may be used in acoustical applications when appropriate.

[_____] Rubber or polymer-based acoustical sealant conforming to ASTM C919 must have a flame spread of 25 or less and a smoke developed rating of 50 or less when tested in accordance with ASTM E84. Acoustical sealant must have a consistency of 250 to 310 when tested in accordance with ASTM D217, and must remain flexible and adhesive after 500 hours of accelerated

SECTION 07 92 00 Page 9 weathering as specified in ASTM C734, and must be non-staining.

2.1.5 Preformed Sealant

Provide preformed sealant of polybutylene or isoprene-butylene based pressure sensitive weather resistant tape or bead sealant capable of sealing out moisture, air and dust when installed as recommended by the manufacturer. At temperatures from minus 34 to plus 71 degrees C 30 to plus 160 degrees F, the sealant must be non-bleeding and no loss of adhesion.

2.1.5.1 Tape

[_____] Tape sealant: Provide cross-section dimensions of [_____].

2.1.5.2 Bead

[_____] Bead sealant: Provide cross-section dimensions of [_____].

2.1.5.3 Foam Strip

NOTE: Untreated polyurethane foam can be used where exposed to view or where staining of adjacent surfaces is not acceptable.

Provide [_____] foam strip of polyurethane foam; with cross-section dimensions of [_____]. Provide foam strip capable of sealing out moisture, air, and dust when installed and compressed as recommended by the manufacturer. Service temperature must be minus 40 to plus 135 degrees C minus 40 to plus 275 degrees F. Furnish untreated strips with adhesive to hold them in place. Do not allow adhesive to stain or bleed into adjacent finishes. Saturate treated strips with butylene waterproofing or impregnated with asphalt.

2.2 PRIMERS

Provide a nonstaining, quick-drying type and consistency recommended by the sealant manufacturer for the particular application.

2.3 BOND BREAKERS

Provide the type and consistency recommended by the sealant manufacturer to prevent adhesion of the sealant to backing or to bottom of the joint.

2.4 BACKSTOPS

Provide glass fiber roving or neoprene, butyl, polyurethane, or polyethylene foams free from oil or other staining elements as recommended by sealant manufacturer. Provide 25 to 33 percent oversized backing for closed cell and 40 to 50 percent oversized backing for open cell material, unless otherwise indicated. Make backstop material compatible with sealant. Do not use oakum [, [_____]] and other types of absorptive materials as backstops.

2.4.1 Rubber

SECTION 07 92 00 Page 10

NOTE: Class A is adequate for most applications.

Select Class B for petroleum oil or fuel resistance.

Select Class D for temperatures of minus 75 to 175 degrees C minus 103 to 347 degrees F with no oil exposure.

Specify Type 2 closed cell when moisture may migrate to the backing.

Conform to ASTM D1056, [Type 1, open cell,] [or] [Type 2, closed cell,] Class [A] [B] [D], Grade [_____], [round] [_____] cross section for [_____] cellular rubber sponge backing.

2.4.2 PVC

NOTE: Do not use open cell vinyl foam in moist areas or below grade.

Conform to ASTM D1667, Grade [VO 12] [_____], open-cell foam, [round] [_____] cross section for [_____] Polyvinyl chloride (PVC) backing.

2.4.3 Synthetic Rubber

NOTE: Use Option I and Type I for most applications. Select Option II only if flame resistance is NOT required. Type II provides the highest ozone resistance.

Conform to ASTM C509, Option [I] [II], Type [I] [II] preformed [rods] [or] [tubes] for [_____] Synthetic rubber backing.

2.4.4 Neoprene

Conform to ASTM D1056, [closed cell expanded neoprene cord Type 2, Class C, Grade [2C2] [_____]] [open cell neoprene sponge Type 1, Class C, Grade [1C3] [_____]] for [_____] Neoprene backing.

2.4.5 Butyl Rubber Based

Provide Butyl Rubber Based Sealants of single component, solvent release, color [as selected] [_____], conforming to ASTM C1311.

2.4.6 Silicon Rubber Base

Provide Silicon Rubber Based Sealants of single component, solvent release, color [as selected] [_____], conforming to ASTM C920, Non-sag, Type [_____], Grade [_____], Class [25] [_____].

2.5 CAULKING

NOTE: The term "caulking" is limited herein to oil-and resin-based caulking which should be used only indoors and where there is little or no anticipated

SECTION 07 92 00 Page 11 joint movement. Use a sealant where joints may move.

Conform to ASTM D2452 and ASTM D2453, Type [_____], for [_____] Oil- and resin-based caulking.

2.6 CLEANING SOLVENTS

Provide type(s) recommended by the sealant manufacturer [except for aluminum and bronze surfaces that will be in contact with sealant].

PART 3 EXECUTION

3.1 SURFACE PREPARATION

Clean surfaces from dirt frost, moisture, grease, oil, wax, lacquer, paint, or other foreign matter that would tend to destroy or impair adhesion.

Remove oil and grease with solvent. Surfaces must be wiped dry with clean cloths. When resealing an existing joint, remove existing caulk or sealant prior to applying new sealant. For surface types not listed below, contact sealant manufacturer for specific recommendations.

3.1.1 Steel Surfaces

Remove loose mill scale by sandblasting or, if sandblasting is impractical or would damage finish work, scraping and wire brushing. Remove protective coatings by sandblasting or using a residue-free solvent.

3.1.2 Aluminum or Bronze Surfaces

Remove temporary protective coatings from surfaces that will be in contact with sealant. When masking tape is used as a protective coating, remove tape and any residual adhesive just prior to sealant application. For removing protective coatings and final cleaning, use nonstaining solvents recommended by the manufacturer of the item(s) containing aluminum or bronze surfaces.

3.1.3 Concrete and Masonry Surfaces

Where surfaces have been treated with curing compounds, oil, or other such materials, remove materials by sandblasting or wire brushing. Remove laitance, efflorescence and loose mortar from the joint cavity.

3.1.4 Wood Surfaces

Keep wood surfaces to be in contact with sealants free of splinters and sawdust or other loose particles.

3.2 SEALANT PREPARATION

Do not add liquids, solvents, or powders to the sealant. Mix multicomponent elastomeric sealants in accordance with manufacturer's instructions.

3.3 APPLICATION

3.3.1 Joint Width-To-Depth Ratios

a. Acceptable Ratios:

SECTION 07 92 00 Page 12

JOINT WIDTH JOINT DEPTH

Minimum Maximum

For metal, glass, or other nonporous surfaces:

6 mm (minimum) 6 mm 6 mm over 6 mm 1/2 of Equal to width width

For wood, concrete, masonry, stone, or [_____]:

6 mm (minimum) 6 mm 6 mm Over 6 mm to 13 mm 6 mm Equal to width

Over 13 mm to 50 mm 50 mm 16 mm Over 50 mm (As recommended by sealant manufacturer)

JOINT WIDTH JOINT DEPTH

Minimum Maximum

For metal, glass, or other nonporous surfaces:

1/4 inch (minimum) 1/4 inch 1/4 inch over 1/4 inch 1/2 of Equal to width width

For wood, concrete, masonry, stone, or [_____]:

1/4 inch (minimum) 1/4 inch 1/4 inch Over 1/4 inch to 1/2 inch 1/4 inch Equal to width

Over 1/2 inch to 2 inch 1/2 inch 5/8 inch Over 2 inch. (As recommended by sealant manufacturer)

b. Unacceptable Ratios: Where joints of acceptable width-to-depth ratios have not been provided, clean out joints to acceptable depths and grind or cut to acceptable widths without damage to the adjoining work.

Grinding is not required on metal surfaces.

3.3.2 Masking Tape

Place masking tape on the finish surface on one or both sides of a joint cavity to protect adjacent finish surfaces from primer or sealant smears.

Remove masking tape within 10 minutes after joint has been filled and tooled.

3.3.3 Backstops

Install backstops dry and free of tears or holes. Tightly pack the back or bottom of joint cavities with backstop material to provide a joint of the

SECTION 07 92 00 Page 13 depth specified. Install backstops in the following locations:

a. Where indicated.

b. Where backstop is not indicated but joint cavities exceed the acceptable maximum depths specified in paragraph entitled, "Joint Width-to-Depth Ratios".

3.3.4 Primer

Immediately prior to application of the sealant, clean out loose particles from joints. Where recommended by sealant manufacturer, apply primer to joints in concrete masonry units, wood, and other porous surfaces in accordance with sealant manufacturer's instructions. Do not apply primer to exposed finish surfaces.

3.3.5 Bond Breaker

Provide bond breakers to the back or bottom of joint cavities, as recommended by the sealant manufacturer for each type of joint and sealant used, to prevent sealant from adhering to these surfaces. Carefully apply the bond breaker to avoid contamination of adjoining surfaces or breaking bond with surfaces other than those covered by the bond breaker.

3.3.6 Sealants

Provide a sealant compatible with the material(s) to which it is applied.

Do not use a sealant that has exceeded shelf life or has jelled and can not be discharged in a continuous flow from the gun. Apply the sealant in accordance with the manufacturer's printed instructions with a gun having a nozzle that fits the joint width. Force sealant into joints to fill the joints solidly without air pockets. Tool sealant after application to ensure adhesion. Make sealant uniformly smooth and free of wrinkles. Upon completion of sealant application, roughen partially filled or unfilled joints, apply sealant, and tool smooth as specified. Apply sealer over the sealant when and as specified by the sealant manufacturer.

3.4 PROTECTION AND CLEANING

3.4.1 Protection

Protect areas adjacent to joints from sealant smears. Masking tape may be used for this purpose if removed 5 to 10 minutes after the joint is filled.

3.4.2 Final Cleaning

Upon completion of sealant application, remove remaining smears and stains and leave the work in a clean and neat condition.

a. Masonry and Other Porous Surfaces: Immediately scrape off fresh sealant that has been smeared on masonry and rub clean with a solvent as recommended by the sealant manufacturer. Allow excess sealant to cure for 24 hour then remove by wire brushing or sanding.

b. Metal and Other Non-Porous Surfaces: Remove excess sealant with a solvent-moistened cloth.

SECTION 07 92 00 Page 14

SECTION 22 15 13.16 40 Page 1

SECTION TABLE OF

CONTENTS DIVISION 22

- PLUMBING SECTION 22

15 13.16 40

STAINLESS STEEL, PIPING COMPONENTS, AND VALVES

1.1 REFERENCES

1.2 SUBMITTALS

2.1 COMPONENTS

2.2 MATERIALS

2.2.1 Piping

2.2.1.1 Propane and Nitrogen/Compressed Air

3.1 INSTALLATION

3.1.1 General

3.1.2 Underground Piping Systems

3.1.3 Aboveground Piping Systems

3.1.3.1 Pipe Bending

3.1.3.2 Joints

3.2 FIELD QUALITY CONTROL

3.2.1 System Pressure Test

3.2.1.1 Acceptance Pressure Testing

3.2.1.2 Test Report

3.2.2 Test Gages

SECTION 22 15 13.16 40 Page 2

SECTION 22 15 13.16 40

STAINLESS STEEL, PIPING COMPONENTS, AND VALVES

The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.

Manual AMERICAN WELDING SOCIETY (AWS)

AWS WHB-2.9 (2004) Welding Handbook; Volume 2, Welding Processes, Part 1

ASME INTERNATIONAL (ASME)

ASME B16.11 (2016) Forged Fittings, Socket-Welding and Threaded

ASME B16.25 (2012) Standard for Buttwelding Ends

ASME B31.3 (2016) Process Piping

ASME B36.19M (2004; R 2015) Stainless Steel Pipe

ASME B40.100 (2013) Pressure Gauges and Gauge

Attachments

ASME BPVC SEC II-C (2010) BPVC Section II-Materials Part

C-Specifications for Welding Rods

Electrodes and Filler Metals

ASME BPVC SEC IX (2010) BPVC Section IX-Welding and Brazing

Qualifications

ASME BPVC SEC VIII D1 (2015) BPVC Section VIII-Rules for

Construction of Pressure Vessels Division 1

ASTM INTERNATIONAL (ASTM)

ASTM A182/A182M (2017) Standard Specification for Forged or Rolled Alloy and Stainless Steel Pipe

Flanges, Forged Fittings, and Valves and

Parts for High-Temperature Service

ASTM A312/A312M (2017) Standard Specification for

Seamless, Welded, and Heavily Cold Worked

Austenitic Stainless Steel Pipes

ASTM A403/A403M (2016) Standard Specification for Wrought

Austenitic Stainless Steel Piping Fittings

SECTION 22 15 13.16 40 Page 3

1.2…