ATTACHMENT 1: WORK AREAS
Bldg 1: Room 124
75 KVA transformer
480v primary
208Y/120v secondary
ACME Electric CAT #ME-1-53314-38
Located in Basement switchgear room
Panel Room 124
120-240V
200A
3 phase
W/ 200A main
4/0
1.1
.4
.3
Amp reading
Notes
• Replace transformer and electrical panel.
• Provide main circuit breaker for panel with main breaker not to exceed amp rating of the wire.
Bldg 1: Room 161
100KVA transformer
480V Primary
120/240 secondary
GE Model
9T23A2675
Panel PA
600A
120/240V
3 phase
Panel LA
225A
120/240V
1 phase
Basement Switchgear room
Panel LHA
225A
277/480V
3 phase
250A
200A
2/0
4 each
1/0
1/0
Notes
• Replace transformer.
• Replace panels, LHA, PA, LA.
• Provide main circuit breaker for each panel.
Bldg 1: Room 111
Junction box
Panel LL-1
225A
120/240v
1 phase
Panel LL-2
120/240v
1 phase
4/0
4/0 4/0
34.8
36.7
17.1
16.3
11.0
9.4
Notes
Replace Panels LL-1 and LL-2
Provide main circuit breaker for each panel, Bldg 1: Room 139
Note ** Panel PB is a 3 phase panel converted to single phase panel—replace with single phase panel
167 KVA
Transformer
240/120v secondary
Federal pacific
Model 16B
**Panel PB
800A
120/240v
1 phase
Panel LK
225A
120/1204v
1 phase
Basement switchgear room
Panel LHB
225A
277/480V
3 phase
LV1
Transformer
37.5 KVA
Panel LV1
100a
120/240V
Manual transfer
Emergency power
200A
400A
4/0
4 each
1/0
3/0
3AWG
Notes
Replace panel PB, LK, LHB
Provide main circuit breaker
All other equipment to remain
Bldg 1: Room A103E
Switchgear
Panel MP
50KVA Transformer
120/240v secondary
GE Model 9T2342673
Panel PC
400A
120/240V
3 phase
Panel LY
100A
120/240v
1 phase
Panel LZ
100A
120/240v
1 phase
Panel LHC
100A
277/480V
3 phase
1AWG
2.8
1.6
.0
4.7
6.3
2AWG
17.7
2.3
2AWG
350mcm 60
Notes
Replace transformer
Replace panels PC, LY, LZ, LHC
Provide main breaker for each panel
Bldg 2:
Panel PHA-1
277/480v
3 phase w/ 250A main
Panel PHA-2
400A
277/480v
3 phase w/ 250A main
Panel LHD
277/480v
3 phase
75KVA
Transformer
480v primary
120/240v sec.
GE 9T23A2674
Panel PD
120/240v
1 phase
Panel L2A
225A
120/240V
1 phase
Panel L2B
100A
120/240v
1 phase
Panel L2C
225A
120/240v
1 phase
Panel L3A
100A
120/240v
1 phase
7.3
5.5
6.5
3.3
6.5
.2
2AWG
2AWG
2AWG
2AWG
350MCM
2AWG
350MCM
350MCM
4/0
Notes
• Replace transformer
• Replace panels PHA-1, PHA-2, LHD, PD, L2A, L2B, L2C
• Provide main circuit breaker for each panel.
• Ensure proper clearance for panel doors to open.
• For Panel L2B, wooden shelfing will require modification