This document outlines a federal contract opportunity for construction services. The solicitation number is 36C77623B0031 and is being issued by the Department of Veterans Affairs Technology Acquisition Center Austin. It seeks bids for a Nutrition & Food Services and Eye/PT Clinic Addition project at the Louis A. Johnson VA Medical Center. Interested parties should submit responses by the date listed on SAM.gov. The opportunity is for construction services to expand medical center facilities, including additions for nutrition/food services and eye/physical therapy clinics. Pricing, terms, and conditions will be negotiated with the selected contractor once all bids are received and evaluated.
View the file
Other files
Show all 25
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
RELIEF
AIR
M
M
VFD
BI
AO
BO
(FAN STATUS)
(VFD SPEED CONTROL)
(FAN START/STOP)
RETURN
AIR
INDOORS
DPS
AI
M
OUTSIDE
AIR
AI-OUTDOOR AIRFLOW
M
T-3 AI
M
VFD
T-1
AI
H-1 AI
DP
D-3
D-1
SPS-2
BI- HIGH PRESSURE STATIC
DSD-1
B1 TO FIRE ALARM
T-2
AI
T-5 AI
AFMS
AO - RELIEF DAMPER
(OPEN/CLOSE)
AI - RELIEF DAMPER
(POSITION)
BI (VFD FAULT)
D-2
AO - OUTSIDE AIR DAMPER
(OPEN/CLOSE)
AI - OUTSIDE AIR DAMPER
(POSITION)
BI -FILTER STATUS
DP
BI - FILTER STATUS
FZ BI-TEMPERATURE TSL
T-4 AI
BI
AO
BO
(FAN STATUS)
(VFD SPEED CONTROL)
(FAN START/STOP)
BI (VFD FAULT)
NTS
C
AO - RETURN AIR DAMPER
(OPEN/CLOSE)
AI - RETURN AIR DAMPER
(POSITION)
LOCATED AT THE NORTH FACE OF BUILDING
WALL COORDINATE EXACT LOCATION WITH
COR/BUILDING ENGINEER.
LOCATED IN FIRST FLOOR
CORRIDOR. FIELD VERIFY
EXACT LOCATION
AO
V-2
SEQUENCE OF OPERATION
VARIABLE VOLUME AIR HANDLING UNIT
C
1. GENERAL
A. UNIT IS NORMALLY STARTED AND STOPPED REMOTELY AT THE DDC. H-O-A SWITCH
SHALL BE KEPT IN THE "AUTO" POSITION. "HAND" AND "OFF" POSITIONS SHALL BE USED
ONLY FOR MAINTENANCE. WHEN THE UNIT IS "OFF" D-1, D-2, & D-3, SHALL BE FULLY
CLOSED. WHEN THE UNIT IS "ON" D-1, D-2, & D-3 SHALL BE OPEN TO ITS MINIMUM
POSITION. DAMPER SHALL MODULATE IN ACCORDANCE WITH THE FOLLOWING
SEQUENCE.
2. RUN CONDITIONS
A. THE UNIT SHALL RUN BASED ON THE FOLLOWING TENTATIVE ADJUSTABLE SCHEDULE.
a. MORNING START-UP
· MONDAY - FRIDAY 6:00AM - 7:00AM (ADJ)
· SATURDAY - SUNDAY 6:00AM - 7:00AM (ADJ)
b. OCCUPIED MODE
· MONDAY - FRIDAY 7:00AM - 7:00PM (ADJ)
· SATURDAY - SUNDAY 7:00AM - 7:00PM (ADJ)
c. UNOCCUPIED MODE
· MONDAY - FRIDAY 7:00PM - 7:00AM (ADJ)
· SATURDAY - SUNDAY 7:00PM - 7:00AM (ADJ)
B. OPTIMAL START SHALL START PRIOR TO SCHEDULED OCCUPANCY BASED ON THE TIME
NECESSARY FOR THE ZONES TO REACH THEIR OCCUPIED SETPOINTS. THE START TIME
SHALL AUTOMATICALLY ADJUST BASED ON CHANGES IN OUTSIDE AIR TEMPERATURE
AND ZONE TEMPERATURES.
C. ZONE SPACE TEMPERATURE SETPOINTS SHALL BE AS FOLLOWS:
· UNOCCUPIED HEATING SPACE TEMPERATURE SETPOINT: 62°F (ADJ.)
· OCCUPIED HEATING SPACE TEMPERATURE SETPOINT: 70°F (ADJ.)
· OCCUPIED COOLING SPACE TEMPERATURE SETPOINT: 75°F (ADJ.)
· UNOCCUPIED COOLING SPACE TEMPERATURE SETPOINT: 80°F (ADJ.)
D. MORNING WARM-UP MODE:
IF THE AVERAGE SPACE TEMPERATURE IS BELOW THE OCCUPIED HEATING SETPOINT
DURING OPTIMAL START, THEN MORNING WARM-UP MODE SHALL BE ACTIVATED. WHEN
MORNING WARM-UP IS INITIATED, THE UNIT SHALL ENABLE HEATING AND THE FAN(S). THE
OUTSIDE AIR DAMPER SHALL REMAIN CLOSED. WHEN THE AVERAGE SPACE
TEMPERATURE REACHES THE OCCUPIED HEATING SETPOINT (ADJ.), THE UNIT SHALL
TRANSITION TO OCCUPIED MODE.
E. PRE-COOL MODE:
IF THE AVERAGE SPACE TEMPERATURE IS ABOVE THE OCCUPIED COOLING SETPOINT
DURING OPTIMAL START, THEN PRE-COOL MODE SHALL BE ACTIVATED. WHEN PRE-COOL
IS INITIATED, THE UNIT SHALL ENABLE THE FAN(S) AND COOLING OR ECONOMIZER. THE
OUTSIDE AIR DAMPER SHALL REMAIN CLOSED, UNLESS ECONOMIZING. WHEN THE SPACE
TEMPERATURE REACHES THE OCCUPIED COOLING SETPOINT (ADJ.), THE UNIT SHALL
TRANSITION TO OCCUPIED MODE.
F. OCCUPIED MODE:
DURING OCCUPIED PERIODS, THE SUPPLY FAN SHALL RUN CONTINUOUSLY, AND THE
MIXED AIR DAMPERS SHALL OPEN TO MAINTAIN MINIMUM VENTILATION REQUIREMENTS.
a. COOLING MODE: THE CHILLED WATER VALVE SHALL MODULATE TO MAINTAIN THE
ACTIVE DISCHARGE AIR TEMPERATURE SETPOINT. IF ECONOMIZING IS ENABLED,
THE OUTSIDE AIR OR MIXED AIR DAMPERS SHALL MODULATE TO MAINTAIN THE
DISCHARGE AIR TEMPERATURE SETPOINT, AND THE RELIEF AIR DAMPER SHALL
TRACK THE MIXED AIR DAMPERS. THE DISCHARGE AIR TEMPERATURE SETPOINT
SHALL BE DYNAMICALLY RESET BASED ON THE DEVIATION OF ACTUAL SPACE
TEMPERATURE FROM THE ACTIVE SPACE TEMPERATURE SETPOINT. IF THE
DISCHARGE AIR TEMPERATURE SENSOR FAILS, THE CHILLED WATER VALVE SHALL
CLOSE, AND AN ALARM SHALL ANNUNCIATE AT THE BAS.
b. HEATING MODE: THE STEAM VALVE SHALL MODULATE TO MAINTAIN THE ACTIVE
DISCHARGE AIR TEMPERATURE SETPOINT. THE DISCHARGE AIR TEMPERATURE
SETPOINT SHALL BE DYNAMICALLY RESET BASED ON THE DEVIATION OF ACTUAL
SPACE TEMPERATURE FROM THE ACTIVE SPACE TEMPERATURE SETPOINT. IF THE
DISCHARGE AIR TEMPERATURE SENSOR FAILS, THE STEAM VALVE SHALL CLOSE,
AND AN ALARM SHALL ANNUNCIATE AT THE BAS.
G. UNOCCUPIED MODE:
a. DURING UNOCCUPIED MODE, THE AIR HANDLING UNIT IS CYCLED ON AND OFF BY
POLLING THE VAV BOX TEMPERATURE SENSORS TO MAINTAIN THE AVERAGE
SPACE HEATING OR COOLING UNOCCUPIED TEMPERATURE SETPOINT.
· ONLY THE TEMPERATURE SENSORS IN THE FOLLOWING ROOMS SHALL BE
POLLED: B122AA DISHWASHING, B122Y SUPERV. 1, B122V DRY GOODS
STORAGE
b. IF THE AVERAGE SPACE TEMPERATURE IS 2°F (ADJ.) ABOVE UNOCCUPIED
COOLING SETPOINT OR BELOW UNOCCUPIED HEATING SETPOINT, THE AIR
HANDLING UNIT IS STARTED. THE OUTDOOR AND RELIEF AIR DAMPERS REMAIN
FULLY CLOSED AND THE RETURN AIR DAMPER IS FULLY OPENED. ALL OTHER
CONTROL ALGORITHMS REMAIN ACTIVE.
c. IF THE AVERAGE SPACE TEMPERATURE IS 2°F (ADJ.) BELOW UNOCCUPIED
HEATING SETPOINT, DDC MODULATES THE HEATING COIL CONTROL VALVE FROM
THE SUPPLY AIR TEMPERATURE SENSOR FOR 85°F (ADJ.). DDC LOCKS OUT
COOLING CONTROL. DDC SHALL OVERRIDE VAV BOX DAMPERS TO 50% OPEN. DDC
DOES NOT ALLOW SUPPLY FAN AIR FLOW TO EXCEED MAXIMUM DUCT STATIC
PRESSURE RATING AS DETERMINED BY SYSTEM AIR BALANCER.
d. IF AVERAGE SPACE TEMPERATURE IS ABOVE UNOCCUPIED COOLING SETPOINT, DDC MODULATES COOLING COIL CONTROL VALVE FROM THE SUPPLY AIR
TEMPERATURE SENSOR FOR 50°F (ADJ.). DDC LOCKS OUT HEATING CONTROL
FROM OPERATING. SUPPLY FAN AIR FLOW IS CONTROLLED FROM THE DUCT
STATIC PRESSURE CONTROLS.
e. WHEN THE AVERAGE SPACE TEMPERATURE IS 2°F (ADJ.) INSIDE THE UNOCCUPIED
HEATING AND COOLING SETPOINTS, THE UNIT SHALL SHUT DOWN.
3. TEMPERATURE CONTROL
A. SUPPLY AIR TEMPERATURE, SENSED BY T-1, SHALL BE MAINTAINED AT SETPOINT VIA DDC
BY MODULATING D-1, D-2 AND D-3 OR V-1 OR V-2 IN SEQUENCE.
B. DURING OCCUPIED MODE, THE SETPOINT IS RESET FROM Tmin (53°F ADJ.)
PROPORTIONALLY UP TO Tmax BASED ON THE ZONE WITH THE HIGHEST DEVIATION FROM
SETPOINT.
4. PREHEATING COIL STEAM VALVE:
A. THE CONTROLLER SHALL MODULATE THE STEAM PREHEAT COIL STEAM VALVE TO
MAINTAIN THE DISCHARGE AIR SETPOINT.
B. THE PREHEATING SHALL BE ENABLED WHENEVER:
a. OUTSIDE AIR TEMPERATURE IS LESS THAN 65°F (ADJ.).
b. AND THE ECONOMIZER (IF PRESENT) IS DISABLED.
c. AND THE HEATING IS ACTIVE.
d. AND COOLING IS NOT ACTIVE.
e. AND THE SUPPLY FAN STATUS IS ON.
5. COOLING VALVE:
A. THE CONTROLLER SHALL MAINTAIN THE DISCHARGE AIR TEMPERATURE SETPOINT.
B. THE COOLING SHALL BE ENABLED WHENEVER:
a. OUTSIDE AIR TEMPERATURE IS GREATER THAN 60°F (ADJ.).
b. AND THE ECONOMIZER IS DISABLED OR FULLY OPEN.
c. AND THE SUPPLY FAN STATUS IS ON.
d. AND THE HEATING IS NOT ACTIVE.
e. DISCHARGE AIR TEMPERATURE IS ABOVE DISCHARGE AIR TEMPERATURE
SETPOINT +1°F(ADJ.)
6. AIR FLOW CONTROL
A. THE RETURN FAN WILL RUN WHENEVER THE SUPPLY FAN IS RUNNING. THE RETURN FAN
SPEED SHALL LAG THE SUPPLY FAN SPEED BY THE %LAG SETPOINT (ADJ.) THE %LAG
SETPOINT WILL BE RESET BASED ON THE BUILDING STATIC PRESSURE (SEE 12.A)
B. THE DDC, USING HIGH PRESSURE SENSOR SPS-2 LOCATED AT THE SUPPLY FAN
DISCHARGE, SHALL PREVENT THE SUPPLY FAN FROM DEVELOPING OVER 5" OF STATIC
PRESSURE (FIELD ADJUSTABLE). IF STATIC PRESSURE AT SPS-2 DOES EXCEED 5",
THE SUPPLY FAN SHALL STOP. SPS-2 SHALL BE HARDWIRED TO THE SUPPLY FAN VSMC
AND UNIT SHALL BE SHUTDOWN IN HAND, AUTO OR BYPASS MODE. SPS-2 WILL REQUIRE
MANUAL RESET AT THE DEVICE.
C. THE STATIC PRESSURE SETPOINT OF 1.0" (ADJ.) OF DUCT STATIC PRESSURE SENSED BY
SPS-1 SHALL BE BASED UPON ON ACTUAL BUILDING LOAD. STATIC PRESSURE RESET
SHALL BE BASED ON THE POSITION OF 2-3 ZONE DAMPERS, WITH THE GOAL OF
REDUCING THE STATIC PRESSURE 0.1" WATER COLUMN UNTIL AT LEAST 2-3 ZONE
DAMPERS IS NEARLY WIDE OPEN. IF MORE DAMPERS NEAR THE WIDE OPEN POSITION
THE SETPOINT SHALL INCREMENTALLY INCREASE UP 0.1" WATER COLUMN. ONLY ONE
RESET OPTION SHALL BE ENABLED AT A TIME.
7. FREEZE PROTECTION
A. IF THE AIR TEMPERATURE AS SENSED BY T-4 FALLS BELOW 40°F, AN ALARM SIGNAL
SHALL INDICATE AT THE DDC. IF THIS TEMPERATURE FALLS BELOW 35°F, AS SENSED BY
THE TSL, THE SUPPLY AND RETURN FANS SHALL SHUT DOWN AND A CRITICAL ALARM
SHALL INDICATE AT THE DDC. TSL SHALL BE HARDWIRED TO THE SUPPLY FAN VFD AND
UNIT SHALL BE SHUTDOWN IN HAND, AUTO OR BYPASS MODE. TSL WILL REQUIRE
MANUAL RESET AT THE DEVICE. DURING FAN SHUTDOWN, T-4 (PREHEAT TEMP) SENSOR
MODULATE PREHEAT VALVE TO MAINTAIN 60°F (ADJ.).
8. AUTOMATIC SHUTDOWN/RESTART
A. WHEN SMOKE IS DETECTED BY DUCT SMOKE DETECTOR, DSD, THE SUPPLY FANS SHALL
SHUT "OFF" AND AN ALARM SIGNAL SHALL BE TRANSMITTED TO THE FIRE ALARM SYSTEM.
ALL SMOKE DAMPERS IN THE SUPPLY AND RETURN DUCTS SHALL CLOSE. (HARDWIRE
CONNECTION FROM FIRE RELAY AND THE VFD SAFETY CIRCUIT.)
B. SUPPLY AND RETURN FANS SHALL RESTART AND SMOKE DAMPERS SHALL OPEN WHEN
FIRE ALARM CIRCUIT IS RESET.
9. EMERGENCY CONSTANT SPEED OPERATION
A. UPON FAILURE OF THE VFD, THE SUPPLY AND RETURN FANS SHALL BE
STARTED/STOPPED MANUALLY AT THE DDC THROUGH THE BYPASS STARTER. FANS
SHALL THEN BE OPERATED AT CONSTANT SPEED.
B. ALL VAV BOXES WILL BE INDEXED TO MAXIMUM FLOW TO ACCOMMODATE THE MAXIMUM
SUPPLY FAN FLOW.
10. ALARMS
A. PROVIDE ALARMS FOR SUPPLY FAN VFD FAULT, SUPPLY FAN FAILURE, (COMMANDED ON
BUT "ON" BUT THE STATUS IS "OFF"; SUPPLY FAN RUNNING IN HAND (COMMANDED "OFF"
BUT THE STATUS IS "ON", AND HIGHER PRE FILTER AND FINAL FILTER DIFFERENTIAL
STATIC PRESSURES.
B. IF THE DISCHARGE AIR TEMPERATURE IS ABOVE DISCHARGE AIR SETPOINT +5°F (ADJ.)
FOR GREATER THAN 5 MINUTES, AN ALARM SHALL BE SIGNALED TO THE DDC SYSTEM.
11. ECONOMIZER CYCLE
A. PROVIDE THE UNIT WITH AN ECONOMIZER CYCLE. OPERATION SHALL BE SUCH THAT
WHEN
a. THE OUTSIDE AIR TEMPERATURE IS LESS THAN THE RETURN AIR TEMPERATURE
THE ECONOMIZER IS ENABLED. (DISABLE ECONOMIZER WHEN OUTSIDE AIR
TEMPERATURE IS GREATER THAN RETURN AIR TEMPERATURE BY 1° (ADJ) AND
OA-T< 60°F (ADJ))
b. AND THE SUPPLY FAN STATUS IS ON.
c. THE ECONOMIZER SHALL BE DISABLED ANYTIME THE MIXED AIR TEMPERATURE
DROPS LESS THAN 40°F (ADJ) OR THE FREEZESTAT IS ON.
12. BUILDING DIFFERENTIAL PRESSURE
A. PROVIDE BUILDING DIFFERENTIAL PRESSURE SENSORS AT EACH FLOOR SERVED BY THE
AHU. IN OCCUPIED MODE, ON A RISE IN BUILDING DIFFERENTIAL PRESSURE ABOVE
SETPOINT (0.05 W.C., ADJ), THE RETURN FAN %LAG SETPOINT WILL BE DECREASED,
INCREASING THE RETURN FAN SPEED. IF THE BUILDING DIFFERENTIAL PRESSURE DROPS
BELOW SETPOINT, THE %LAG SETPOINT WILL BE INCREASED, DECREASING THE RETURN
FAN SPEED. THE RESET SHALL BE ACTIVE WHENEVER THE AHU'S FANS ARE OPERATING.
13. MINIMUM OUTSIDE AIR VENTILATION
A. WHEN IN THE OCCUPIED MODE, THE CONTROLLER SHALL MEASURE THE OUTSIDE
AIRFLOW AND MODULATE THE OUTSIDE AIR DAMPERS TO MAINTAIN THE PROPER
MINIMUM OUTSIDE AIR VENTILATION, OVERRIDING NORMAL DAMPER CONTROL. ON
DROPPING OUTSIDE AIRFLOW, THE CONTROLLER SHALL MODULATE THE OUTSIDE AIR
DAMPERS OPEN TO MAINTAIN THE OUTSIDE AIRFLOW SETPOINTS (ADJ).
14. SUPPLY AIR SMOKE DETECTION:
A. THE UNIT SHALL SHUT DOWN AND GENERATE AN ALARM UPON RECEIVING A SUPPLY AIR
SMOKE DETECTOR STATUS.
REMARKS:
A. LOCATE OUTSIDE SENSOR ON THE EXTERIOR NORTH SIDE OF THE BUILDING. LOCATE
OUT OF ANY HEAT SOURCE RELATED EQUIPMENT. COORDINATE FINAL LOCATION WITH
COR/BUILDING ENGINEER AND ALL MANUFACTURER'S RECOMMENDATIONS.
AIR HANDLING UNIT POINTS LIST
HARDWARE POINTS SOFTWARE POINTS
POINT NAME AI AO BI BO AV BV SCHED TREND ALARM SHOW ON
GRAPHIC
SUPPLY FAN POINTS LIST
VFD START / STOP X X X X
VFD FAN STATUS X X X X
VFD FAULT / FAILURE X X X X X
SUPPLY FAN VFD SPEED X
VFD HOA STATUS X X X
DUCT HIGH PRESSURE SAFETY, SPS-2 X X X X
DOWNDUCT STATIC PRESSURE SENSOR, SPS-1 X X
SUPPLY DUCT SMOKE DETECTOR, STATUS (DSD-1) X X X X
RETURN FAN POINTS LIST
VFD START / STOP X X X X
VFD FAN STATUS X X X X
VFD FAULT / FAILURE X X X X X
RETURN FAN VFD SPEED X
VFD HOA STATUS X X X
SUPPLY AIR TEMP CONTROL
LOW TEMPERTURE DETECTION, T-4 X X X X
FREEZE PROTECTION X
SUPPLY AIR TEMPERATURE, T-1 X X X X
SUPPLY AIR TEMPERATURE SET POINT X X X
STEAM PREHEAT COIL VALVE (V-1) X X X
CHILLED WATER VALVE (V-2) X X X
DAMPER CONTROL
MIXED AIR TEMPERATURE, T-3 X X X X
OUTSIDE AIR DAMPER POSITION, D-1 X X X
OUTSIDE AIR DAMPER OPEN/CLOSE, D-1 X X X
OUTSIDE AIR FLOW SET POINT, D-1 X X X
RETURN AIR DAMPER POSITION, D-2 X X X
RETURN AIR DAMPER OPEN/CLOSE, D-2 X X X
RETURN AIR FLOW SET POINT, D-2 X X X
RELIEF AIR DAMPER POSITION, D-3 X X X
RELIEF AIR DAMPER OPEN/CLOSE, D-3 X X X
RELIEF AIR FLOW SET POINT, D-3 X X X
MISCELLANEOUS POINTS
RETURN AIR TEMPERATURE, T-2 X X X X
RETURN AIR HUMIDITY, H-1 X X X
OUTSIDE AIR FLOW MEASURING STATION X X X
SUPPLY AIR FLOW MEASURING STATION X X X
BUILDING STATIC PRESSURE X X X X
FILTER DIFFERENTIAL PRESSURE X X X X
FILTER DIFFERENTIAL PRESSURE X X X X
FILTER DIFFERENTIAL PRESSURE ALARM SET POINT X X X
OUTSIDE AIR DEW POINT TEMPERATURE, T-5 (NETWORK) X X X X
OUTSIDE AIR HUMIDITY SENSOR, H-3 (NETWORK) X X X
AI-SUPPLY AIRFLOW AFMS
COOLING
COIL
H
AO
V-1
C
STEAM
PREHEAT COIL
SUPPLY TO
VAV UNITS
SPS-1
AI
OUTDOORS
T-6 AI
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
CONSTRUCTION DOCUMENTS-
ISSUE FOR BID
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
STAMP NUTRITION & FOOD SERVICE
AND
EYE/ PT CLINIC ADDITION
1 MEDICAL CENTER DRIVE, CLARKSBURG, WV 26301
540-370
10-21-202225% DD1 SUBMISSION 06-14-21
50% DD2 SUBMISSION 08-23-21
75% CD1 SUBMISSION 11-01-21
www. bancroft-ae.com
BAE PROJECT NO. 20-109
3300 Dundee Rd.
Northbrook, IL 60062
T: 847.952.9362
VA CONTRACT NO. 36C24521C0034
75% CD1 SUBMISSION (RESUBMITTAL) 01-11-22
100% CD 2 SUBMISSION 07-29-22
100% CD 2 SUBMISSION (RESUBMITTAL) 09-23-22
CONSTRUCTION DOCUMENTS- ISSUED FOR BID 10-21-22
RUN CONDITIONS - REQUESTED:
THE MAKE UP AIR UNIT SHALL BE INTERLOCKED TO RUN WHEN THE KITCHEN HOOD EXHAUST FAN (EF-B3) RUNS, UNLESS SHUT DOWN ON SAFETIES.
EMERGENCY SHUTDOWN:
THE UNIT SHALL SHUT DOWN AND GENERATE AN ALARM UPON RECEIVING AN EMERGENCY SHUTDOWN SIGNAL.
FREEZE PROTECTION:
THE UNIT SHALL SHUT DOWN AND GENERATE AN ALARM UPON RECEIVING A FREEZESTAT STATUS.
OUTSIDE AIR DAMPER:
THE OUTSIDE AIR DAMPER SHALL OPEN ANY TIME THE UNIT RUNS AND SHALL CLOSE ANY TIME THE UNIT STOPS.
THE SUPPLY FAN SHALL START ONLY AFTER THE DAMPER STATUS HAS PROVEN THE DAMPER IS OPEN. THE
OUTSIDE AIR DAMPER SHALL CLOSE 4 SECONDS (ADJ.) AFTER THE SUPPLY FAN STOPS.
ALARMS SHALL BE PROVIDED AS FOLLOWS:
· OUTSIDE AIR DAMPER FAILURE: COMMANDED OPEN, BUT THE STATUS IS CLOSED.
· OUTSIDE AIR DAMPER IN HAND: COMMANDED CLOSED, BUT THE STATUS IS OPEN.
SUPPLY FAN:
THE SUPPLY FAN SHALL RUN ANY TIME THE UNIT IS COMMANDED TO RUN. TO PREVENT SHORT CYCLING, THE SUPPLY FAN SHALL HAVE A USER DEFINABLE (ADJ.) MINIMUM RUNTIME, UNLESS SHUTDOWN ON SAFETIES.
ALARMS SHALL BE PROVIDED AS FOLLOWS:
· SUPPLY FAN FAILURE: COMMANDED ON, BUT THE STATUS IS OFF.
· SUPPLY FAN IN HAND: COMMANDED OFF, BUT THE STATUS IS ON.
SUPPLY AIR DUCT STATIC PRESSURE CONTROL:
THE CONTROLLER SHALL MEASURE DUCT STATIC PRESSURE AND SHALL MODULATE THE SUPPLY FAN VFD SPEED TO MAINTAIN A DUCT STATIC PRESSURE SETPOINT OF 1.5" H2O (ADJ.). THE SUPPLY FAN VFD SPEED SHALL NOT
DROP BELOW 30% (ADJ.).
ALARMS SHALL BE PROVIDED AS FOLLOWS:
· HIGH SUPPLY AIR STATIC PRESSURE: IF THE SUPPLY AIR STATIC PRESSURE IS 25% (ADJ.) GREATER THAN
SETPOINT.
· LOW SUPPLY AIR STATIC PRESSURE: IF THE SUPPLY AIR STATIC PRESSURE IS 25% (ADJ.) LESS THAN
SETPOINT.
COOLING COIL VALVE:
THE CONTROLLER SHALL MEASURE THE SUPPLY AIR TEMPERATURE AND MODULATE THE COOLING COIL VALVE TO
MAINTAIN COOLING SETPOINT OF 75°F (ADJ.).
THE COOLING SHALL BE ENABLED WHENEVER:
· OUTSIDE AIR TEMPERATURE IS GREATER THAN 60°F (ADJ.).
· AND THE SUPPLY AIR TEMPERATURE IS ABOVE COOLING SETPOINT.
· AND THE FAN STATUS IS ON.
THE COOLING COIL VALVE SHALL OPEN TO 50% (ADJ.) WHENEVER THE FREEZESTAT IS ON.
STEAM HEATING COIL VALVE:
THE CONTROLLER SHALL MEASURE THE SUPPLY AIR TEMPERATURE AND MODULATE THE HEATING COIL VALVE TO
MAINTAIN HEATING SETPOINT OF 70°F (ADJ.).
THE HEATING SHALL BE ENABLED WHENEVER:
· OUTSIDE AIR TEMPERATURE IS LESS THAN 65°F (ADJ.).
· AND THE SUPPLY AIR TEMPERATURE IS BELOW HEATING SETPOINT.
· AND THE FAN STATUS IS ON.
THE HEATING COIL VALVE SHALL OPEN TO 100% (ADJ.) WHENEVER THE FREEZESTAT IS ON.
PREFILTER DIFFERENTIAL PRESSURE MONITOR:
THE CONTROLLER SHALL MONITOR THE DIFFERENTIAL PRESSURE ACROSS THE PREFILTER.
ALARMS SHALL BE PROVIDED AS FOLLOWS:
· PREFILTER CHANGE REQUIRED: PREFILTER DIFFERENTIAL PRESSURE EXCEEDS A USER DEFINABLE LIMIT
(ADJ.).
SUPPLY AIR TEMPERATURE:
THE CONTROLLER SHALL MONITOR THE SUPPLY AIR TEMPERATURE.
ALARMS SHALL BE PROVIDED AS FOLLOWS:
· HIGH SUPPLY AIR TEMP: IF THE SUPPLY AIR TEMPERATURE IS GREATER THAN 120°F (ADJ.).
· LOW SUPPLY AIR TEMP: IF THE SUPPLY AIR TEMPERATURE IS LESS THAN 45°F (ADJ.).
SEQUENCE OF OPERATION
EXISTING MAKE UP AIR UNIT 100% OA
NTS
D-1
TT
PR
E-F
ILT
ER
PR
E-F
ILT
ER
DPT
30 PSI
STEAM
V1
V2
F& B H
EA
TIN
G
TT
CO
IL
CO
OL
ING
AICWRT TT
V3
CHWR
CHWS
TT
FT
AI
AI
CWST
CWF
BTUH BACNET TO AHU
CONTROLLER
AFMD
SUPPLY FAN
FREEZE
STAT
FROM
SAFETIES
VSMC
AT
SST
SS
BACNET MSTP TO AHU
CONTROLLER
TT
DSD
TO KITCHEN
NOTES:
1. CONTRACTOR TO MODIFY EXISTING AIR HANDLING UNIT CONTROLS TO ACHIEVE THE
SEQUENCE OF OPERATION. ALL POINTS ARE EXISTING TO REMAIN.
NTS
BI - ZONE OVERRIDE
AI -ZONE TEMP
AI -ZONE SETPOINT ADJUST
SEQUENCE OF OPERATION
VARIABLE TERMINAL AIR BOX
1. GENERAL
A. THE VARIABLE TERMINAL AIR BOX SHALL ACCORDING TO USER DEFINABLE TIME
SCHEDULE IN THE FOLLOWING MODES:
2. TEMPERATURE CONTROL
A. OCCUPIED MODE: THE UNIT SHALL MAINTAIN
a. A 75°F (ADJ) COOLING SETPOINT
b. A 72°F (ADJ) HEATING SETPOINT
B. UNOCCUPIED MODE (NIGHT SETBACK): THE UNIT SHALL MAINTAIN
a. A 85°F (ADJ) COOLING SETPOINT
b. A 65°F (ADJ) HEATING SETPOINT
C. THE UNIT SHALL MAINTAIN ZONE SETPOINTS BY CONTROLLING THE AIRFLOW
THROUGH ONE OF THE FOLLOWING.
D. OCCUPIED:
a. WHEN THE ZONE TEMPERATURE IS GREATER THAN THE COOLING SETPOINT, THE ZONE DAMPER SHALL MODULATE BETWEEN THE MINIMUM OCCUPIED
AIRFLOW (ADJ) AND THE MAXIMUM COOLING AIRFLOW (ADJ) UNTIL THE ZONE IS
SATISFIED.
b. WHEN THE ZONE TEMPERATURE IS BETWEEN THE COOLING SETPOINT AND THE
HEATING SETPOINT, THE ZONE DAMPER SHALL MAINTAIN THE MINIMUM ZONE
AIRFLOW (ADJ).
c. WHEN THE ZONE TEMPERATURE IS LESS THAN THE HEATING SETPOINT, THE
CONTROLLER SHALL ENABLE HEATING VALVE
TO MODULATE TO MAINTAIN SETPOINT UNTIL THE SUPPLY AIR DISCHARGE
TEMPERATURE REACHES 90°F. UPON FURTHER DROP IN SPACE TEMPERATURE
THE ZONE DAMPER SHALL MODULATE BETWEEN THE MINIMUM AND MAXIMUM
HEATING CFM TO MAINTAIN THE ZONE TEMPERATURE AT THE HEATING
SETPOINT.
E. UNOCCUPIED:
a. WHEN THE ZONE IS UNOCCUPIED THE ZONE DAMPER SHALL CONTROL TO ITS
MINIMUM UNOCCUPIED AIRFLOW (ADJ). WHEN THE ZONE TEMPERATURE IS
GREATER THAN THE COOLING SETPOINT, THE ZONE DAMPER SHALL MODULATE
BETWEEN THE MINIMUM UNOCCUPIED AIRFLOW (ADJ) AND THE MAXIMUM
COOLING AIRFLOW (ADJ) UNTIL THE ZONE IS SATISFIED.
b. WHEN THE ZONE TEMPERATURE IS LESS THAN ITS UNOCCUPIED HEATING
SETPOINT, THE CONTROLLER SHALL ENABLE HEATING TO MAINTAIN THE ZONE
TEMPERATURE AT THE SETPOINT, THE ZONE DAMPER SHALL MODULATE
BETWEEN THE MINIMUM UNOCCUPIED AIRFLOW (ADJ) AND THE HEATING
AIRFLOW (ADJ) UNTIL THE ZONE IS SATISFIED.
3. ZONE OPTIMAL START
A. THE UNIT SHALL USE AN OPTIMAL START ALGORITHM FOR MORNING START-UP. THIS
ALGORITHM SHALL MINIMIZE THE UNOCCUPIED WARM-UP OR COOL-DOWN PERIOD
WHILE STILL ACHIEVING COMFORT CONDITIONS BY THE START OF SCHEDULED
OCCUPIED PERIOD.
4. ZONE UNOCCUPIED OVERRIDE
A. A TIMED LOCAL OVERRIDE CONTROL SHALL ALLOW AN OCCUPANT TO OVERRIDE THE
SCHEDULE AND PLACE THE UNIT INTO OCCUPIED MODE FOR AN ADJUSTABLE PERIOD
OF TIME. AT THE EXPIRATION OF THIS TIME, CONTROL OF THE UNIT SHALL
AUTOMATICALLY RETURN TO THE SCHEDULE.
A0 - REHEAT VALVE
AI - DISCHARGE AIR TEMPERATURE
DISCHARGE AIR
AO - ZONE DAMPER
AI - AIRFLOW
SUPPLY AIR
TM
HW
S
HW
R
NOTE:
1. PROVIDE CONTROL TRANSFORMER SERVING LOCAL
GROUPS OF AIR TERMINAL UNITS (5 VAV BOXES MAX PER
TRANSFORMER.)
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
CONSTRUCTION DOCUMENTS-
ISSUE FOR BID
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
STAMP NUTRITION & FOOD SERVICE
AND
EYE/ PT CLINIC ADDITION
1 MEDICAL CENTER DRIVE, CLARKSBURG, WV 26301
540-370
10-21-202225% DD1 SUBMISSION 06-14-21
50% DD2 SUBMISSION 08-23-21
75% CD1 SUBMISSION 11-01-21
www. bancroft-ae.com
BAE PROJECT NO. 20-109
3300 Dundee Rd.
Northbrook, IL 60062
T: 847.952.9362
VA CONTRACT NO. 36C24521C0034
75% CD1 SUBMISSION (RESUBMITTAL) 01-11-22
100% CD 2 SUBMISSION 07-29-22
RUN CONDITIONS - REQUESTED:
THE FAN SHALL BE ACTIVATED BY WALL MOUNTED SWITCH WHEN THE DISHWASHER IS IN USED. ONCE
WALL SWITCH IS DEACTIVATED FAN SHALL OPERATE FOR 5 MINUTES (ADJ.) .
FAN:
THE FAN SHALL HAVE A USER DEFINABLE (ADJ.) MINIMUM RUNTIME.
FAN STATUS:
THE CONTROLLER SHALL MONITOR THE FAN STATUS.
ALARMS SHALL BE PROVIDED AS FOLLOWS:
· FAN FAILURE: COMMANDED ON, BUT THE STATUS IS OFF.
· FAN IN HAND: COMMANDED OFF, BUT THE STATUS IS ON.
· FAN RUNTIME EXCEEDED: FAN STATUS RUNTIME EXCEEDS A USER DEFINABLE LIMIT (ADJ.).
NTS
M
BI - EXHAUST FAN STATUS
BO - EXHAUST FAN START/STOP
CT
EXHAUST
AIR
BACK DRAFT DAMPER
RUN CONDITIONS - REQUESTED:
THE FAN SHALL BE ACTIVATED BY WALL MOUNTED SWITCH WHEN CART WASHER IS IN USE. ONCE
WALL SWITCH IS DEACTIVATED FAN SHALL OPERATE FOR 5 MINUTES (ADJ.) .
FAN:
THE FAN SHALL HAVE A USER DEFINABLE (ADJ.) MINIMUM RUNTIME.
FAN STATUS:
THE CONTROLLER SHALL MONITOR THE FAN STATUS.
ALARMS SHALL BE PROVIDED AS FOLLOWS:
· FAN FAILURE: COMMANDED ON, BUT THE STATUS IS OFF.
· FAN IN HAND: COMMANDED OFF, BUT THE STATUS IS ON.
· FAN RUNTIME EXCEEDED: FAN STATUS RUNTIME EXCEEDS A USER DEFINABLE LIMIT (ADJ.).
NTS
M
BI - EXHAUST FAN STATUS
BO - EXHAUST FAN START/STOP
CT
EXHAUST
AIR
BACK DRAFT DAMPER
EXHAUST FAN POINTS LIST (EF-B1 & EF-B2)
HARDWARE POINTS SOFTWARE POINTS
POINT NAME AI AO BI BO AV BV SCHED TREND ALARM SHOW ON GRAPHIC
FAN STATUS X X X
FAN START/STOP X X X
SCHEDULE X
FAN FAILURE X
FAN IN HAND X
FAN RUN TIME EXCEEDED X
M
CT
EP
DSS EVAPORATOR FAN
BI-FAN STATUS CT
EP
BI-COMPRESSOR STATUS
AIR COOLED CONDENSING UNIT
T AI-SPACE TEMPERATURE
DUCTLESS SPLIT SYSTEM
DUCTLESS SPLIT SYSTEMS SHALL HAVE SYSTEM MANUFACTURER'S STANDARD
WALL-MOUNTED PROGRAMMABLE CONTROLLER. SYSTEM SHALL OPERATE UNDER ITS
BUILT-IN, FACTORY INSTALLED CONTROL SYSTEM TO MAINTAIN ROOM TEMPERATURE
SET POINT (72°F). AN INDEPENDENT, WALL-MOUNTED TEMPERATURE SENSOR SHALL
MONITOR ROOM TEMPERATURE AND SEND AN ALARM TO THE BMS PANEL IF ROOM
TEMPERATURE RISES ABOVE 85°F (ADJUSTABLE). HIGH TEMPERATURE ALARM SHALL
REQUIRE MANUAL RESET. THE BMS SHALL MONITOR COMPRESSOR STATUS.
THE THERMOSTAT SHALL ENERGIZE THE CONDENSING UNIT ON CALL FOR COOLING.
WALL MOUNTED SWITCH WALL MOUNTED SWITCH
NTS
RUN CONDITIONS - REQUESTED:
FAN SHALL ACTIVATE VIA SWITCH ON KITCHEN HOOD. WHEN SWITCH IS PUT IN THE ON POSITION, FAN SHALL ACTIVATE. WHEN SWITCH IS PUT IN THE OFF POSITION, FAN SHALL DEACTIVATE. MAKE UP AIR UNIT (AHU-16)
OPERATION SHALL BE INTERLOCKED WITH FAN OPERATION.
FAN:
A. THE FAN SHALL HAVE A USER DEFINABLE (ADJ.) MINIMUM RUNTIME AND SHALL SEND A SIGNAL TO BAS.
FAN STATUS:
A. THE CONTROLLER SHALL MONITOR THE FAN STATUS.
B. ALARMS SHALL BE PROVIDED AS FOLLOWS:
a. FAN FAILURE: COMMANDED ON, BUT THE STATUS IS OFF.
b. FAN IN HAND: COMMANDED OFF, BUT THE STATUS IS ON.
c. FAN RUNTIME EXCEEDED: FAN STATUS RUNTIME EXCEEDS A USER DEFINABLE LIMIT (ADJ.).
EXHAUST
AIR
M
BI - EXHAUST FAN STATUS
BO - EXHAUST FAN START/STOP
CT
EXHAUST FAN POINTS LIST
HARDWARE POINTS SOFTWARE POINTS
POINT NAME AI AO BI BO AV BV SCHED TREND ALARM SHOW ON GRAPHIC
FAN STATUS X X X
FAN START/STOP X X X
SCHEDULE X
FAN FAILURE X
FAN IN HAND X
FAN RUN TIME EXCEEDED X
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
CONSTRUCTION DOCUMENTS-
ISSUE FOR BID
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
Phase
STAMP NUTRITION & FOOD SERVICE
AND
EYE/ PT CLINIC ADDITION
1 MEDICAL CENTER DRIVE, CLARKSBURG, WV 26301
540-370
10-21-202225% DD1 SUBMISSION 06-14-21
50% DD2 SUBMISSION 08-23-21
75% CD1 SUBMISSION 11-01-21
www. bancroft-ae.com
BAE PROJECT NO. 20-109
3300 Dundee Rd.
Northbrook, IL 60062
T: 847.952.9362
VA CONTRACT NO. 36C24521C0034
75% CD1 SUBMISSION (RESUBMITTAL) 01-11-22
100% CD 2 SUBMISSION 07-29-22
1. SEE ALL PROJECT GENERAL NOTES AND OTHER
REQUIREMENTS THE LIFE SAFETY AND
INFECTION CONTROL REQUIREMENTS LOCATED
WITHIN GENERAL DRAWINGS SECTION. COMPLY
WITH ALL REQUIREMENT AS THEY ARE A DIRECT
PART OF THIS SECTION AND AS IF THEY WERE
DIRECTLY INCLUDED AND PROVIDED BELOW.
2. BASIS OF DESIGN PROTOCOLS:
DESIGN IS BASED ON LISTED MANUFACTURER
MENTIONED ON ALL ELECTRICAL AND ALL
SPECIAL SYSTEM DRAWINGS INCLUDING BUT
NOT LIMITED TO VARIOUS ELECTRICAL
EQUIPMENTS, DEVICES, LIGHT FIXTURES,
LIGHTING CONTROLS, AND ALL SPECIAL SYSTEM
DEVICES. CONTRACTOR SHALL BE RESPONSIBLE
TO ENSURE THAT ALL EQUAL PRODUCTS SHALL
MEETS OR EXCEEDS THE DESIGN INTENT,
PERFORMANCE, OUTLINE DIMENSION, WEIGHT
ETC. EQUAL PRODUCT SHOP SUBMITTALS SHALL
BE REJECTED UNLESS CONTRACTOR PROVIDES
WRITTEN STATEMENT INDICATING IT MATCHES
100% PERFORMANCE SPECS AND ALL ABOVE
CRITERIA. EQUAL PRODUCT SHOP SUBMITTAL
NOT MEETING ABOVE CRITERIA SHALL BE
REVIEWED AND/OR SELECTED EQUAL PRODUCTS
REQUIRES RE-DESIGN THAT WILL BE AT THE
COST TO THE CONTRACTOR INCLUDING DELAY
OF PROJECT DUE TO THIS PROCESS.
ALTERNATIVELY EQUAL PRODUCTS ALONG WITH
LETTER INDICATING CONTRACTOR IS
RESPONSIBLE FOR MEETING DESIGN
INTENT/CRITERA SHALL BE SUBMITTED AND
APPROVED FROM VA/COR BEFORE BID AND
VA/COR APPROVAL PROOF SHALL BE SUBMITTED
ALONG WITH SHOP SUBMITTAL FOR REVIEW.
EQUIVALENCY SUBSTITUTIONS: THE “BASIS OF
DESIGN (BOD) PROTOCOLS” ARE TO BE
FOLLOWED FOR ALL EQUIPMENT, MATERIALS
AND ASSEMBLIES SPECIFIED AND DETAILED
THROUGHOUT ALL DRAWINGS AND
SPECIFICATION SECTIONS, WHETHER THE BOD
DESIGNATE IS SPECIFICALLY REFERENCED
THEREIN OR NOT. SEE THE GENERAL DRAWINGS
SECTION FOR THE FULL BOD EQUIVALENCY
SUBSTITUTION REQUIREMENTS AND PROTOCOLS
TO BE FOLLOWED.
3. CODES:
THE WORK SHALL COMPLY WITH ALL
APPLICABLE, MUNICIPAL, STATE, NATIONAL
CODES, AND ALL VA APPLICABLE DESIGN
MANUALS STANDARDS REQUIREMENTS. WHERE
THE CONSTRUCTION DOCUMENTS INDICATE
MORE RESTRICTIVE REQUIREMENTS THE
CONSTRUCTION DOCUMENTS SHALL GOVERN.
HOWEVER, THE CONSTRUCTION DOCUMENTS
SHALL NOT BE INTERPRETED AS AUTHORITY TO
VIOLATE ANY CODE OR REGULATION.
ALL WORK, MATERIAL, AND EQUIPMENT SHALL
COMPLY WITH ALL REQUIREMENTS OF THE
LATEST EDITIONS AND INTERIM AMENDMENTS OF
THE NATIONAL ELECTRICAL CODE (N.E.C.),
NATIONAL ELECTRICAL SAFETY CODE, OSHA,
AND ALL APPLICABLE FEDERAL, STATE, AND
LOCAL LAWS AND ORDINANCES. ALL ELECTRICAL
EQUIPMENT PROVIDED UNDER THIS CONTRACT
SHALL BE NEW (EXCEPT WHERE OTHERWISE
NOTED) AND SHALL SHALL BEAR THE MARK OF
NATIONALLY RECOGNIZED TESTING
LABORATORY, WHEN APPLICABLE. ALL
EQUIPMENT OF THE SAME TYPE AND CAPACITY
SHALL BE BY THE SAME MANUFACTURER.
4. DRAWINGS AND SPECIFICATIONS:
THE CONTRACTOR SHALL BE RESPONSIBLE FOR
READING AND COMPLYING WITH BOTH THE
DRAWINGS AND SPECIFICATIONS. IN THE EVENT
OF A CONFLICT OR INCONSISTENCY BETWEEN
THE DRAWINGS, NOTES, SPECIFICATIONS, OR
CODES, THE REFERENCE WHICH PROVIDES THE
MORE COMPLETE OR HIGHER STANDARD SHALL
PREVAIL UNLESS OTHERWISE CLARIFIED BY
OWNER.
CONTRACTOR SHALL REVIEW ENTIRE SET OF
CONTRACT DOCUMENTS: INCLUDING BUT NOT
NECESSARILY LIMITED TO ALL ARCHITECTURAL,
ALL STRUCTURAL, ALL MECHANICAL, ALL
ELECTRICAL, ALL PLUMBING, AND ENTIRE
PROJECT MANUAL. CONTRACTOR SHALL
ACKNOWLEDGE AND INCLUDE IN THE SCOPE OF
WORK (CONTRACT) ALL CONDITIONS PERTINENT
TO THE COMPLETION OF THE ELECTRICAL WORK.
CONTRACTOR SHALL FULLY COORDINATE
ELECTRICAL WORK WITH THE INSTALLATION OF
WORK BY ALL OTHER TRADES AND MAKE
NECESSARY FIELD ADJUSTMENTS AS REQUIRED
TO ACCOMMODATE THE ELECTRICAL
INSTALLATION. ALL OF THE ABOVE SHALL BE
INCLUDED IN THE SCOPE OF WORK AT NO
ADDITIONAL COST TO THE VA.
5. INTERPRETATION OF THE DOCUMENTS:
CAREFULLY COMPARE THE DRAWINGS AND
SPECIFICATIONS, CHECKING MEASUREMENTS
AND CONDITIONS UNDER WHICH THIS
INSTALLATION IS TO BE MADE. FOR
CLARIFICATION BETWEEN VARIOUS DRAWINGS,
BETWEEN DRAWINGS OR SPECIFICATION, OR
BETWEEN SECTIONS OF THE SPECIFICATION,
THE MATTER SHALL BE REFERRED TO THE
VA/COR FOR CLARIFICATION AND APPROVAL
BEFORE ANY WORK IS EXECUTED. THE
CONTRACTOR SHALL STATE IN THEIR PROPOSAL
ANY EXCEPTIONS NECESSARY TO MAKE THIS A
COMPLETE, READY TO USE INSTALLATION. IF
NOT STATED IN THEIR BID, IT WILL NOT BE
CONSIDERED EXTRA.
ALL WORK SHALL BE DONE IN ACCORDANCE
WITH THE CONTRACT DOCUMENTS, IN A NEAT
AND WORKABLE MANNER CONSISTENT WITH
RECOGNIZED GOOD PRACTICE, AND SHALL BE
SUBJECT TO THE APPROVAL OF THE VA/CO.
ANY CHANGES TO THE CONTRACT
REQUIREMENTS MUST BE APPROVED PRIOR TO
CONSTRUCTION. THE CONTRACTOR SHALL KEEP
UP-TO-DATE AS-BUILT DRAWINGS, ON-SITE,
AVAILABLE FOR INSPECTION AT ANY TIME OF THE
EXACT NATURE OF WORK, INCLUDING
ALLOWABLE DEVIATIONS FROM THE CONTRACT
DRAWINGS, FOR THE PURPOSE OF RECORD
DOCUMENTS.
6. ELECTRICAL DRAWINGS
THE ELECTRICAL DRAWINGS ARE DIAGRAMMATIC
AND SHALL NOT BE SCALED. THE CONTRACTOR
SHALL DETERMINE THE EXACT LOCATION OF ALL
DOORS, WALLS, FURNITURE, EQUIPMENT, ETC..
THE LOCATION OF RACEWAY SYSTEM
COMPONENTS IS SCHEMATIC. THE EXACT
LOCATION OF RACEWAY SYSTEM COMPONENTS
SHALL BE DETERMINED BY THE CONTRACTOR IN
THE FIELD. THE CONTRACTOR SHALL CONFIRM
THE DIMENSIONS OF THE ACTUAL EQUIPMENT TO
BE SUPPLIED FOR THIS PROJECT, VERIFY
CLEARANCES AND ROUGH-INS, AND OBTAIN ALL
APPROVALS PRIOR TO STARTING WORK.
7. SITE EXAMINATION
BEFORE SUBMITTING A BID, THE CONTRACTOR
SHALL VISIT THE SITE, EXAMINE THE PREMISES,
AND MAKE A THOROUGH SURVEY OF THE
EXISTING CONDITIONS. THIS VISIT SHALL ONLY
BE ALLOWED AS PER THE VA SCHEDULED WALK
THROUGH. THE SUBMISSION OF A BID WILL BE
CONSTRUED AS EVIDENCE THAT SUCH A VISIT
HAS BEEN MADE. NO CONSIDERATION OR
ALLOWANCE WILL BE GRANTED FOR FAILURE TO
VISIT THE SITE OR FOR LATER CLAIMS FOR
LABOR, EQUIPMENT, MATERIALS REQUIRED, OR
FOR DIFFICULTIES ENCOUNTERED WHICH COULD
HAVE BEEN FORESEEN HAD SUCH VISIT BEEN
MADE.
CONTRACTOR SHALL CAREFULLY EXAMINE THE
DRAWINGS AND SPECIFICATIONS, VISIT THE SITE
OF THE WORK, AND FULLY INFORM THEM SELF
AS TO ALL CONDITIONS AND MATTERS THAT CAN,
IN ANY WAY, AFFECT THE WORK OR THE COST
THEREOF. SHOULD THIS CONTRACTOR FIND
DISCREPANCIES IN, OR OMISSIONS FROM, THE
DRAWINGS, SPECIFICATIONS OR OTHER
DOCUMENTS OR BE IN DOUBT AS TO THEIR
MEANING, NOTIFY THE VA/COR AT ONCE, IN
WRITING, OF ANY DISCREPANCIES BETWEEN
EXISTING CONDITIONS AND NEW WORK, OR
BETWEEN ELECTRICAL WORK AND THE WORK OF
OTHER TRADES. OBTAIN CLARIFICATION(S)
PRIOR TO SUBMITTING ANY BID. LACK OF SUCH
NOTIFICATION SHALL BE CONSTRUED TO
INDICATE NO DISCREPANCIES OR CONFLICTS
EXIST. ADDITIONAL COMPENSATION WILL NOT BE
GRANTED AFTER AWARD OF CONTRACT FOR
ANY WORK REQUIRED TO COMPLY WITH THESE
REQUIREMENTS.
8. COORDINATION WITH OTHER TRADES:
THE ELECTRICAL CONTRACTOR SHALL OBTAIN A
COMPLETE SET OF GENERAL, ARCHITECTURAL
AND ENGINEERING DOCUMENTS AND
COORDINATE WITH MECHANICAL, PLUMBING,
ARCHITECTURAL, AND OTHER TRADES FOR
EXACT DIMENSIONS, CLEARANCES, ROUGH-IN
LOCATIONS, AND OTHER ADDITIONAL SCOPES OF
WORK THAT MAY NOT BE SHOWN ON THE
ELECTRICAL PLANS. THE ELECTRICAL
CONTRACTOR SHALL BE RESPONSIBLE FOR ALL
120 VOLT (AND HIGHER) AC POWER TO OTHER
TRADES EQUIPMENT AND HARDWARE. THIS
SHALL INCLUDE, BUT NOT BE LIMITED TO,
CONTROLS, FIRE AND SECURITY SYSTEMS,
MOTORIZED DOORS, DAMPERS, LIFTS, AND
OTHER SYSTEMS. UNLESS SPECIFICALLY NOTED
OTHERWISE ON THE ELECTRICAL PLANS, THE
ELECTRICAL CONTRACTOR SHALL FURNISH ALL
SAFETY DISCONNECT SWITCHES TO
MECHANICAL EQUIPMENT UNLESS OTHERWISE
NOTED..
THE CONTRACTOR SHALL CHECK ALL
ARCHITECTURAL, STRUCTURAL, AND
MECHANICAL TRADES WORK FOR POSSIBLE
INTERFERENCE CAUSED BY CONDITIONS IN THE
FIELD, BEFORE THE BID IS MADE. NO
ALLOWANCE SHALL SUBSEQUENTLY BE MADE TO
THE CONTRACTOR BY REASON OF HIS FAILURE
TO HAVE MADE SUCH EXAMINATIONS OR OF ANY
ERROR OF THEIR PART.
9. THE ELECTRICAL CONTRACTOR IS: RESPONSIBLE
FOR SCHEDULING DELIVERY, RECEIVING,
UNLOADING, UNCRATING, STORING SETTING IN
PLACE, AND PROTECTING FROM DAMAGE,
VANDALISM, THEFT OR WEATHER DURING
CONSTRUCTION FOR ALL NEW EQUIPMENT
FURNISHED BY THE ELECTRICAL
CONTRACTOR.
CONTRACTOR SHALL PAY ALL PERMIT FEES, PLAN
REVIEW FEES, LICENSE FEES, INSPECTIONS AND
TAXES APPLICABLE TO THIS DIVISION IF
NECESSARY. (FEDERAL GOVERNMENT IS NOT
SUBJECT TO LOCAL PERMITS OR FEE FOR THE
PROJECT).
10. FIRE STOPPING:
ALL PENETRATIONS IN WALL, FLOOR OR
CEILINGS SHALL BE SUITABLY CLOSED UP AND
SEALED WITH AN INTUMESCENT FIRE STOPPING
COMPOUND LISTED IN THE MOST RECENT
FACTORY MUTUAL RESEARCH CORPORATION
(FMRC) APPROVAL GUIDE. WHEN NEW
CABLES/CONDUITS PENETRATE EXISTING FIRE
RATED WALL, PENETRATIONS SHALL BE SEALED
TO MATCH EXISTING RATING TO ENSURE IT
RETAIN EXISTING CONDITIONS. THE BOD FOR
FIRE STOPPING PRODUCTS SHALL BE AS
MANUFACTURED BY THE 3M CO.
11. PAINTING:
ALL NEWLY INSTALLED EXPOSED PIPING SHALL
BE PAINTED TO MATCH THE ADJACENT WALL OR
CEILING SURFACE UNLESS THE REQUIRED
COLOR CODING IS SPECIFIED.
12. VA FURNISHED EQUIPMENT:
EQUIPMENT THAT WILL BE FURNISHED BY THE
VA WILL BE INDICATED ON A SCHEDULE OR BE
INCLUDED IN SPECIFIC NOTES OR
SPECIFICATIONS. THE CONTRACTOR SHALL
COORDINATE WITH THE VA/COR FOR DELIVERY
SCHEDULES. THE CONTRACTOR IS TO ASSUME
THAT ON SITE STORAGE MAY NOT BE AVAILABLE
WHEN COORDINATING DELIVERY OF EQUIPMENT.
THE CONTRACTOR, IN COORDINATION WITH THE
VA/COR, WILL INSPECT THE DELIVERY FOR
ACCURACY AND SHIPMENT DAMAGE AND
ACCEPTING THE EQUIPMENT. THE CONTRACTOR
SHALL BE RESPONSIBLE TO STORE, PROTECT,
AND ULTIMATELY INSTALL THE EQUIPMENT.
13. ELECTRICAL SERVICE DISRUPTIONS:
ANY WORK INVOLVING A TASK WHICH EXPOSES
ACTIVE BUS SHALL BE PERFORMED AFTER
HOURS (11:00PM TO 5:00AM). THIS RESTRICTION
INCLUDES REMOVING THE COVER FROM ANY
PANEL BOARD, SWITCHBOARD, M.C.C. ETC.. ALL
WORK WHICH EXPOSES ACTIVE BUS REQUIRES A
WRITTEN NOTIFICATION TO THE VA/COR WHICH
WILL OUTLINE THE METHOD OF PROCEDURE FOR
THE WORK. THE CONTRACTOR SHALL PROVIDE
A MINIMUM OF 6 WEEKS NOTICE TO THE VA/COR
BEFORE WORKING ON ANY ENERGIZED
ELECTRICAL SYSTEM. ALL POWER DISRUPTION
SHALL OCCUR AT TIMES AND OF DURATIONS
ACCEPTABLE TO THE VA/COR.
14. EQUIPMENT:
ALL MATERIALS AND EQUIPMENT USED IN THIS
INSTALLATION SHALL BE NEW, BUY AMERICA
COMPLAINT, AND HAVE THE APPROPRIATE UL
LISTING AND LABEL.
THE CONTRACTOR SHALL FURNISH ALL LABOR,
MATERIAL, TOOLS, EQUIPMENT SERVICES, AND
ACCESSORIES FOR COMPLETE INSTALLATION OF
ALL ELECTRICAL WORK AS NOTED. ITEMS
OMITTED FROM EITHER THE SPECIFICATIONS OR
THE DRAWINGS, BUT SHOWN OR DESCRIBED IN
ONE OR THE OTHER, AND ITEMS NECESSARY TO
MAKE THE ELECTRICAL SYSTEM COMPLETE AND
WORKABLE SHALL FORM A PART OF THE WORK.
15. MISCELLANEOUS SUPPORTING MEMBERS:
ALL ANGLES CHANNELS, AND OTHER
MISCELLANEOUS STEEL, BOLTS, RODS, ETC..
REQUIRED TO SUPPORT LIGHT FIXTURE,
CONDUIT, RACEWAY, LADDER TRAY, OR OTHER
ELECTRICAL EQUIPMENT OR DEVICES SHALL BE
FURNISHED AND INSTALLED BY THE
CONTRACTOR.
ANY MENTION OF A SPECIFIC VOLTAGE ON THE
ELECTRICAL DRAWINGS SHALL NOT RELIEVE THE
ELECTRICAL CONTRACTOR OF THE
RESPONSIBILITY TO VERIFY THE VOLTAGE PRIOR
TO PURCHASING OR ROUGH-IN WORK.
16. DISTRIBUTION PANELS AND PANELS BOARDS:
ALL DISTRIBUTION PANELS AND PANEL BOARDS
SHALL BE PROVIDED WITH TYPEWRITTEN
DIRECTORIES. SEE PANEL SCHEDULES ON THE
DRAWINGS AND SPECIFICATION FOR COMPLETE
IDENTIFICATION AND LABELING REQUIREMENTS.
ALL DISTRIBUTION PANELS AND PANEL BOARDS
SHALL BE LABELED ON THE PANEL CABINET WITH
THE PANEL NAME AND THE POWER SOURCE
FEEDING THE PANEL AS PER THE ELECTRICAL
ONE LINE. ALL PANELS AND PANEL BOARDS
SHALL BE PROVIDED WITH HINGED DOOR WITH
LOCK AND KEY.
17. SAFETY:
CONTRACTOR SHALL TAKE ALL STEPS
NECESSARY TO ENSURE THE SAFETY OF THE
VA'S EMPLOYEES, BUILDING EMPLOYEES AND
GUESTS, AS WELL AS THEIR OWN FORCES, BY
ADEQUATELY PROVIDING APPROPRIATE PPE AND
PROTECTING ANY EXPOSED LIVE CONDUCTORS,
OR DEVICES THROUGHOUT THE COURSE OF THIS
WORK.
18. EQUIPMENT CONNECTIONS:
PROVIDE FINAL CONNECTIONS FOR ALL
EQUIPMENT FURNISHED UNDER OTHER
DIVISIONS AND FOR ALL VA FURNISHED
EQUIPMENT. PROVIDE A FLEXIBLE LIQUID TIGHT
CONNECTION TO ALL VIBRATION PRODUCING
EQUIPMENT.
19. TEMPORARY LIGHTING, POWER, FIRE, AND
SAFETY:
PROVIDE TEMPORARY LIGHTING AND POWER AS
REQUIRED IN AREAS UNDERGOING WORK
DURING CONSTRUCTION. FURNISH AND INSTALL
ONE OSHA APPROVED PIGTAIL SOCKET WITH
150-WATT LAMP FOR EVERY 500 SQUARE FEET
OF FLOOR SPACE AND A MINIMUM 1 PER ROOM.
THE TEMPORARY LIGHTING SHALL BE LEFT IN
PLACE UNTIL PERMANENT LIGHTING IS
COMPLETELY OPERATIONAL.
FURNISH AND INSTALL POWER OUTLETS TO A
TOTAL OF ONE FOR EVERY 2000 SQUARE FEET
OR PART THEREOF OF FLOOR AREA. THESE
SHALL BE 15 AMP, SINGLE PHASE RECEPTACLES
FOR EITHER 110 OR 220 VOLTS AS DIRECTED BY
THE GENERAL/PRIME CONTRACTOR.
COORDINATE FOR ADDITIONAL TEMPORARY
POWER REQUIREMENTS WITH OTHER TRADES
AND PROVIDE AN ADEQUATE INSTALLATION.
COMPLY WITH NFPA 241 FOR SAFEGUARDING
DURING CONSTRUCTION AND ALTERATION
OPERATIONS. IN ADDITION, ANY OPENINGS IN
FIRE RATED SEPARATIONS BETWEEN OCCUPIED
AND UNOCCUPIED (OR OPERATIONAL AND
NON-OPERATIONAL) AREAS SHALL BE SEALED AT
THE END OF EACH WORK DAY WITH AN
APPROPRIATE FIRE RATED ENCLOSURE OR
SEALANT. DO NOT COMPROMISE EXISTING
SECURITY OR FIRE ALARM SYSTEMS SERVING
THE OCCUPIED OR OPERATIONAL AREAS.
DURING CONSTRUCTION THE CONTRACTOR
SHALL AT ALL TIMES MAINTAIN ELECTRICAL
UTILITIES OF THE BUILDING WITHOUT
INTERRUPTION. SHOULD IT BE NECESSARY TO
INTERRUPT ANY ELECTRICAL SERVICE OR
UTILITY, THE CONTRACTOR SHALL SECURE
PERMISSION IN WRITING FROM THE VA/COR FOR
SUCH INTERRUPTION AT LEAST 6 WEEKS IN
ADVANCE. ANY INTERRUPTION SHALL BE MADE
WITH THE MINIMUM AMOUNT OF INCONVENIENCE
TO THE VA AND ANY SHUT-DOWN TIME SHALL
HAVE TO BE ON A PREMIUM TIME/AFTER HOURS
BASIS AND SUCH TIME TO BE INCLUDED IN THE
CONTRACTOR'S BID.
CONTRACTOR SHALL PROVIDE ALL NECESSARY
TEMPORARY LIGHTING AND POWER FOR ALL
TRADES DURING CONSTRUCTION AND REMOVE
IT AT COMPLETION OF WORK.
CONTRACTOR SHALL ESTABLISH SAFE WORKING
PROCEDURES FOR THE PROTECTION OF THE
WORKMEN IN ALL PHASES OF WORK, COMPLYING
WITH THE APPLICABLE PROVISIONS OF ALL CITY,
STATE, AND FEDERAL SAFETY LAWS (OSHA), AND
AS RECOMMENDED IN THE "MANUAL OF
ACCIDENT PREVENTION IN CONSTRUCTION" AS
ISSUED BY THE ASSOCIATION OF GENERAL
CONTRACTORS OF AMERICA, INC., 20TH AND E.
STREETS, N.W. WASHINGTON, D.C.
20. POWER COORDINATION:
THE CONTRACTOR SHALL PERFORM ALL
COORDINATION AND SCHEDULING OF LOCAL
POWER OUTAGES REQUIRED WITH THE VA/COR.
ALL NEEDED POWER OUTAGES TO BE
SCHEDULED WITH THE VA/COR SIX WEEKS IN
ADVANCE.
21. CABLING:
BRANCH CIRCUITS TO RECEPTACLES, LIGHTING
AND MISC. SMALL LOADS (15 OR 20 AMP
CIRCUITS), UNLESS SPECIFICALLY NOTED
OTHERWISE, SHALL BE 2 - #12, 1 - #12 GRD., 3/4"
C. A SEPARATE NEUTRAL SHALL BE RUN FOR
EACH CIRCUIT. SEE WIRE SIZING TABLE ON THIS
SHEET.
ALL WIRE SIZE #10 AND SMALLER SHALL BE OF
SOLID COPPER.
EACH BRANCH CIRCUIT HOMERUN SHALL HAVE
NO MORE THAN THREE CIRCUITS. EACH BRANCH
CIRCUIT HOMERUN SHALL HAVE A SEPARATE
GREEN INSULATED EQUIPMENT GROUNDING
CONDUCTOR. ALL CONDUCTORS SHALL BE
COPPER TYPE THWN / XHHW.
CABLE JACKET COLOR FOR VARIOUS SYSTEM
SHALL BE AS FOLLOW:
VOICE (VOiP) - WHITE
3 DATA - YELLOW/GREEN/GRAY
CLINICAL WIRELESS (OIT) - DARK GREEN
VIDEO SURVEILLANCE - VIOLET
NURSE CALL - BLUE
FIRE ALARM - RED
22. CABLING SIZES:
BRANCH CIRCUIT CABLE SIZING SHALL BE
ADJUSTED BASED ON THE VALUES INDICATED IN
THE WIRE SIZING TABLE PER THIS SHEET.
23. SPECIAL LUG REQUIREMENTS:
ANY CABLE WHICH TERMINATES DIRECTLY ON TO
A BUS BAR SHALL BE 2 BOLT LONG BARREL TYPE
WITH INSPECTION HOLES PRODUCED WITH NON
FLASHING TYPE DYES WITH THE BOD AS
MANUFACTURED BY THOMAS AND BETTS, OR
EQUIVALENT MINIMUM 10 TONS OF
COMPRESSION, HEX CRIMP. THE USE OF HEAT
SHRINK TUBING IS EXPLICITLY FORBIDDEN.
24. RACEWAYS:
ALL WIRE SHALL BE INSTALLED IN THIN WALL
(E.M.T.) CONDUIT UNLESS OTHERWISE NOTED.
MINIMUM SIZE SHALL BE 3/4" EXCEPT FOR DROPS
FOR DEVICES, SWITCH LEGS, TEMPERATURE
CONTROL CONDUITS, WHERE INDICATED OR AS
CALLED FOR ON DRAWINGS. ALL THINWALL
FITTINGS SHALL BE OF THE STEEL
COMPRESSION GLAND TYPE.
ALL UNDERFLOOR, UNDERGROUND OR
EXPOSED-TO-WEATHER CONDUIT SHALL BE
HEAVYWALL GALVANIZED RIGID STEEL. (G.R.S.),
MINIMUM 3/4". ALL BURIED CONDUITS AND 2" AND
ABOVE EXPOSED-TO-WEATHER CONDUIT SHALL
BE PVC COATED HEAVYWALL GALVANIZED RIGID
STEEL (G.R.S).
ALL CONDUIT FASTENERS, STRAPS, SUPPORTS
ETC. MUST BE "BOLT-ON" GALVANIZED STEEL ON
EXPOSED CONSTRUCTION AND IN WET AREAS.
SNAP-ON BLACK METAL "CADDY" CLIPS IN METAL
PARTITION WALLS AND ABOVE SUSPENDED
CEILINGS WILL BE PERMITTED. ALL FASTENERS,
STRAPS, CLIPS, ETC. SHALL BE UL LISTED FOR
THEIR USE.
SUPPORT CONDUIT WITH P1000 UNISTRUT AND
3/8" THREADED ROD 8'-0" O.C. MAX.
PROVIDE MYERS HUBS FOR ALL CONDUIT TO
ENCLOSURE CONNECTIONS.
ALL CONDUIT RACEWAYS SHALL BE CONCEALED
IN OR WITHIN: WALLS, CEILING CAVITY, ROOF
CONSTRUCTION (WHERE APPROVED), SLAB,
GRADE, ETC. UNLESS OTHERWISE NOTED. ANY
RACEWAY THAT IS TO BE ROUTED EXPOSED
SHALL BE APPROVED BY THE VA/COR AND
SUCCESSFULLY REVIEWED BY THE
ARCHITECT/ENGR. PRIOR TO INSTALLATION. ALL
CONDUIT SHALL BE ROUTED PARALLEL OR
PERPENDICULAR TO WALLS AND STRUCTURAL
MEMBERS WITH 90° BENDS WHERE REQUIRED
AND SHALL BE RACKED. PULL AND JUNCTION
BOXES SHALL BE HELD TO A MINIMUM.
CONTRACTOR SHALL INSTALL ALL WORK IN NEAT
& INDUSTRY RECOGNIZED MANNER OF BEST
PRACTICES.
GROUND ALL CONDUITS, MOTORS, AND EXPOSED
NON-CURRENT CARRYING METAL PARTS OF
ELECTRICAL EQUIPMENT IN ACCORDANCE WITH
ALL PROVISIONS WITH THE LATEST EDITION OF
THE NATIONAL ELECTRICAL CODE. VA
SPECIFICATION SECTION 26 05 26 "GROUNDING
AND BONDING ELECTRICAL SYSTEM".
CONTRACTOR SHALL PROVIDE PULL BOXES,
JUNCTION BOXES, SPLICE BOXES AND FITTINGS
WHERE NECESSARY OR REQUIRED BY THE NEC.
CONDUIT ROUTING SHOWN DIAGRAMMATIC AND
BASED ON CONDITIONS AT THE TIME THE FIELD
SURVEY. CONTRACTOR SHALL FIELD VERIFY
EXACT ROUTING AS FIELD CONDITION DICTATES
AT THE TIME OF CONSTRUCTION. PROVIDE PULL
BOXES SIZED AS PER NFPA-70 LATEST EDITION.
THERE SHALL NOT BE MORE THAN EQUIVALENT
OF THREE QUARTER BENDS (270° TOTAL)
BETWEEN PULL POINTS.
ALL ELECTRICAL CONDUITS TO A MINIMUM OF
3/4". MULTI-GANG BACKBOXES FOR DIFFERENT
VOLTAGES AND TYPES OF EMERGENCY AND
NORMAL BRANCH WIRING DEVICES SHALL HAVE
DIVIDERS BETWEEN DEVICES.
PROVIDE JUNCTION BOX AND CONDUIT COLOR
FOR VARIOUS SYSTEMS AS PER FOLLOWING
COLOR SCHEME.
POWER:
120/208 VOLT (NORMAL POWER): SILVER
120/208 VOLT (LIFE SAFETY/CRITICAL): ORANGE
277/480 VOLT (NORMAL & EMERGENCY): YELLOW
LIGHTING WHITE
GENERAL DATA/VOICE: BLUE
FIRE ALARM: RED
NURSE CALL/GET WELL NETWORK: GREEN
T-STAT: BLUE
SECURITY (CARD READER/VIDEO): PURPLE
FIBER OPTIC: ORANGE
WHERE CORE DRILLING AND CUTTING OF FLOORS
OR WALLS IS REQUIRED, X-RAY THE AREAS
PRIOR TO DRILLING. AVOID INTERFERENCE WITH
EXISTING CONCEALED ELECTRICAL, PLUMBING
INSTALLATIONS, AND REINFORCING STEEL.
REFINISH DAMAGED AND CUT SURFACES TO
MATCH ADJACENT FINISHES.
CONTRACTOR SHALL FIREPROOF ALL CONDUIT
OPENINGS BETWEEN FLOORS AND ANY
INTERSPACE FIRE SEPARATION BLOCK WALLS
WITH A VA/COR APPROVED U.L. LISTED FIRE
RETARDANT MATERIAL, AS SUCCESSFULLY
REVIEWED BY THE ARCHITECT/ENGINEER.
CONTRACTOR SHALL INSTALL PLASTIC BUSHING
ON CONDUIT BOX FITTINGS.
25. LIGHTING:
ALL FINAL LOCATIONS AND ARRANGEMENTS OF
LIGHTING FIXTURES SHALL BE OBTAINED FROM
THE ARCHITECTURAL REFLECTED CEILING PLAN.
COORDINATE LIGHT LOCATION WITH CABLE TRAY
AND CEILING MOUNTED MECHANICAL
EQUIPMENTS AND ENSURE THAT SERVICE
CLEARANCE AND ACCESS IS NOT RESTRICTED.
26. RECEPTACLES
CONTRACTOR SHALL VERIFY ALL OUTLET
MOUNTING ARRANGEMENTS, HEIGHTS AND
LOCATIONS WITH THE ARCHITECTURAL
DRAWINGS PRIOR TO ROUGH-IN. ANY MENTION
OF A SPECIFIC MOUNTING ARRANGEMENT,
HEIGHT OR LOCATION SHALL NOT RELIEVE THE
CONTRACTOR OF THE RESPONSIBILITY TO
VERIFY THE SPECIFIC REQUIREMENT WITH THE
EQUIPMENT FURNISHED OR THE OTHER TRADES
WORKING IN THE SAME AREA. NO ADDITIONS TO
THE CONTRACT SUM WILL BE PERMITTED FOR
OUTLETS IN WRONG LOCATIONS, IN CONFLICT
WITH OTHER WORK ETC. THE VA RESERVES THE
RIGHT TO RELOCATE ANY DEVICE 10'-0" PRIOR
TO ROUGH-IN WITHOUT ANY ADDITIONAL
CHARGES BY THE CONTRACTOR.
OUTLET BOXES MOUNTED BACK-TO-BACK IN THE
SAME WALL ARE PROHIBITED. A MINIMUM 24"
CENTER-TO-CENTER LATERAL SPACING SHALL
BE MAINTAINED BETWEEN BOXES.
ALL THE EMERGENCY POWER OUTLETS SHALL
BE HOSPITAL GRADE RED IN COLOR.
27. AS BUILT/RECORD DOCUMENTS:
ELECTRICAL CONTRACTOR SHALL FURNISH
CONTRACT AS-BUILT RECORD DOCUMENTS TO
THE VA/COR AND ARCHITECT/ENGINEER BEFORE
FINAL PAYMENT WILL BE ISSUED. THE CONTRACT
RECORD DOCUMENTS SHALL
DIAGRAMMATICALLY INDICATE THE ACTUAL
INSTALLED CONDITIONS THAT DEVIATE FROM
ORIGINAL DESIGN DRAWINGS.
28. GUARANTEE:
ALL EQUIPMENT FURNISHED AND WORK
PERFORMED UNDER THE CONTRACT
DOCUMENTS SHALL BE GUARANTEED AGAINST
DEFECTS IN MATERIALS OR WORKMANSHIP FOR
A PERIOD AS PER VA SPECIFICATION, UNLESS
OTHERWISE NOTED. ANY FAILURE OF
EQUIPMENT OR WORK DUE TO DEFECTS IN
MATERIALS OR WORKMANSHIP SHALL BE
CORRECTED BY THE CONTRACTOR AT NO COST
TO THE VA.
29. FINAL INSPECTION:
ALL THE ITEMS AND WORK SHALL BE TESTED
FOR SAFE AND PROPER OPERATIONS.
UPON COMPLETION OF THE WORK, THE
ELECTRICAL CONTRACTOR SHALL REVIEW AND
CHECK THE ENTIRE PORTION OF WORK, CLEAN
EQUIPMENT AND DEVICES, REMOVE SURPLUS
MATERIALS AND RUBBISH FROM THE OWNER'S
PROPERTY, LEAVING THE WORK IN NEAT AND
CLEAN ORDER AND IN COMPLETE WORKING
CONDITION. THE ELECTRICAL CONTRACTOR
SHALL BE RESPONSIBLE FOR REMOVAL OF ANY
CARTON, DEBRIS, ETC. FOR EQUIPMENT
INSTALLED BY THIS CONTRACTOR INCLUDING
EQUIPMENT FURNISHED BY THE OWNER. THE
ABOVE SHALL ALSO APPLY TO ALL EQUIPMENT
FURNISHED BY OTHERS AND UNPACKED OR
REMOVED FROM CARTON, BY THE CONTRACTOR.
ELECTRICAL GENERAL NOTES
1. EXAMINATION
CONTRACTOR SHALL SURVEY THE EXISTING SITE AND
EXAMINE AREAS UNDER WHICH THE WORK IS TO BE
PERFORMED PRIOR TO BIDDING AND DETERMINE THE EXTENT
OF NECESSARY RELOCATIONS, REMOVALS AND REPAIRS TO
THE EXISTING ELECTRICAL WORK REQUIRE AVOIDING
CONFLICTS WITH NEW CONSTRUCTION IN ORDER TO MEET
MINIMUM CODE REQUIREMENTS. NOTIFY THE VA/COR IN
WRITING OF ANY CONDITIONS DETRIMENTAL TO THE PROPER
AND TIMELY COMPLETION OF THE WORK. CONTRACTOR
SHALL NOT PROCEED WITH WORK UNTIL SATISFACTORY
CONDITIONS HAVE BEEN CORRECTED. A FIELD SURVEY
VERIFICATION IS MANDATORY IN ORDER TO SUBMIT AN
ELECTRICAL BID, FAILURE TO DO SO SHALL NOT RELIEVE THIS
CONTRACTOR FROM PERFORMING THE WORK OF THIS
CONTRACT.
DEMOLITION DRAWINGS ARE BASED ON FIELD OBSERVATION
AND EXISTING RECORD DRAWINGS. THE CONTRACTOR SHALL
INCLUDE IN HIS BID ALL COSTS ASSOCIATED WITH
RELOCATION AND REMOVAL OF ELECTRICAL WORK AS
DESCRIBED IN THE DRAWINGS AND SPECIFICATIONS WITH
ALLOWANCES FOR EXPECTED OR UNFORESEEN ISSUES
WHEN CONCEALED WORK HAS BEEN EXPOSED. NO
ADDITIONAL CLAIMS FOR WORK ASSOCIATED WITH
DEMOLITION WILL BE ACCEPTED, UNLESS, IN CERTAIN CASES,
CONSIDERED JUSTIFIABLE BY THE COR.
REVIEW MECHANICAL AND ARCHITECTURAL DEMOLITION
DRAWINGS FOR ANY OTHER ELECTRICAL DEMOLITION
REQUIREMENTS.
2. PREPARATION
ALL EXISTING EQUIPMENT IS TO REMAIN OPERATIONAL
DURING THE CONSTRUCTION PERIOD. ANY TEMPORARY
WIRING OR REROUTING OF CIRCUITRY TO ACHIEVE THIS IS BY
THE ELECTRICAL CONTRACTOR. SHUTDOWN OF EXISTING
SERVICES SHALL ONLY BE PERMITTED UPON WRITTEN
APPROVAL FROM THE OWNER AND THEN ONLY FOR THE DATE
AND DURATION AGREED UPON. INCLUDE ALL PREMIUM TIME
CHARGES IN THE BASE BID.
ANY UTILITY SHUT DOWN THAT AFFECT PATIENT CARE SHALL
BE COORDINATED A MINIMUM OF 45 DAYS IN ADVANCE AND
SHALL BE PERFORMED OFF HOUR PERIODS OR WEEKENDS AT
THE CONVENIENCE OF VA AS APPROVED THE BY VA COR.
IT IS MANDATORY THAT THE EXISTING ALL FIRE ALARM AND
COMPONENTS TO REMAIN FUNCTIONAL DURING
CONSTRUCTION.
BEFORE WORKING ON ANY EQUIPMENT THAT IS CONNECTED
TO SOURCE OF ENERGY, CONTRACTOR SHALL PROVIDE OSHA
MANDATED LOCK-OUT/TAG-OUT AT SOURCE LOCATION TO
SHUT OFF ENERGY SOURCE.
3. DEMOLITION AND EXTENSION OF EXISTING ELECTRICAL
WORK.
WHERE SOURCE OF SUPPLY IS A PANEL BOARD, RE-LABEL
PROTECTIVE DEVICE AS “SPARE” AND SET TO THE OFF
POSITION AFTER DEMOLITION IS COMPLETE. PROVIDE
REVISED CIRCUIT DIRECTORIES IN ALL PANEL BOARDS
AFFECTED BY NEW OR DEMOLITION WORK THAT INDICATES
ALL LOADS, NEW AND MODIFIED.
CIRCUIT NUMBER LABEL SHOWN ON EXISTING OUTLETS AND
SWITCHES IS AS PER FIELD SURVEY. CONTRACTOR SHALL BE
RESPONSIBLE TO TRACE CIRCUITS AND FIND OUT BREAKER
LOCATIONS AND DEMO THE CABLES AND UPDATE THE PANEL
DIRECTORY FOR VA RECORD.
WHERE CORE DRILLING AND CUTTING OF FLOORS/SLABS OR
WALLS IS REQUIRED CONTRACTOR IS TO EXERCISE EXTREME
CAUTION AND X-RAY THE AREAS PRIOR TO DRILLING/CUTTING
SLAB TO AVOID DAMAGE TO ANY EXISTING CONCEALED
ELECTRICAL, PLUMBING INSTALLATIONS, AND REINFORCING
STEEL ETC. THAT MAY BE CONCEALED IN OR BENEATH THE
SLAB/WALL. CONTRACTOR SHALL FIREPROOF ALL THE
OPENING WITH U.L. LISTED FIRE RETARDANT MATERIAL, TO
MATCH EXISTING CONDITIONS.
REMOVE EXPOSED ABANDONED CONDUIT ABOVE
ACCESSIBLE CEILING AND FINISHED WALL. CUT CONDUIT
FLUSH WITH WALLS AND FLOORS, AND PATCH THE SURFACE
TO MATCH EXISTING. CONDUIT MAY BE ABANDONED IN WALLS
AND FLOORS TO REMAIN BUT EXISTING WIRING WITHIN THESE
CONDUITS TO BE REMOVED COMPLETELY.
REPAIR ADJACENT CONSTRUCTION AND FINISHES DAMAGED
DURING DEMOLITION AND EXTENSION OF WORK.
4. DISPOSAL
OWNER SHALL HAVE RIGHT TO RETAIN ANY EQUIPMENT OR
MATERIALS THAT HAVE BEEN DEMOLISHED PRIOR TO
DISPOSAL OR REMOVAL FROM SITE. ANY EQUIPMENT OR
MATERIALS NOT WANTED BY THE OWNER SHALL BECOME THE
PROPERTY OF THE CONTRACTOR AND REMOVED FROM SITE.
CONTRACTOR SHALL COMPLY WITH ENVIRONMENTAL LAWS
AND REGULATIONS FOR DISPOSAL OF DEMOLISHED
MATERIALS AND EQUIPMENT.
ELECT DEMOLITION NOTES
NOTES:
1. ALL DIMENSIONS ARE CONSIDERED FROM FINISHED FLOOR AND, UNLESS NOTED OTHERWISE, SHALL NOT VARY.
RAISED FLOORS SHALL BE CONSIDERED FINISHED FLOOR.
2. ALL DIMENSIONS SHALL BE COORDINATED WITH ARCHITECTURAL DETAILS AND MAY BE ADJUSTED TO CONFORM WITH ARCHITECTURAL REQUIREMENTS AS LONG AS NO CODE RESTRICTION IS VIOLATED.
3. OUTLETS INSTALLED LOWER THAN 15" AFF (FORWARD REACH) AND 9" AFF (SIDE REACH) ARE IN
VIOLATION OF ADA.
SPECIAL NOTES:
1. EXIT SIGNS SHALL NOT BE INSTALLED IN A MANNER THAT THE SIGN WILL BLOCK FIRE ALARM VISUAL
DEVICES.
2. FOR LIGHTING FIXTURES MOUNTING HEIGHTS SEE SCHEDULE AND DRAWINGS.
48" TO HIGHEST OPERABLE PART (SIDE OR FORWARD
ACCESS).
48" TO CENTERLINE OF BOX MINIMUM (TOILETS).
66" TO CENTERLINE OF BOX MAXIMUM (SHOWERS -
LOCATED OUT OF SPRAY AREA).
80" TO CENTERLINE OF DEVICE OR 6" BELOW CEILING,
WHICHEVER IS LOWER.
80" TO BOTTOM OF DEVICE OR NOT MORE THAN 96" TO
TOP.
FIRE ALARM VISUAL ONLY DEVICE OR A COMBINATION
AUDIBLE AND VISUAL DEVICE
NOT LESS THAN 90" TO TOP OR 6" BELOW CEILING, WHICH
EVER IS HIGHER.
48" TO CENTERLINE OF BOX - NOT MORE THAN 5'-0"
FROM EXIT.
54" TO DIAL CENTER (NON-ACCESSIBLE).
48" TO HIGHEST OPERABLE PART (ACCESSIBLE).
12" CEILING TO CENTERLINE OR 7'-0" TO CENTERLINE IF
CEILING IS OVER 8'-0".
AS NOTED ON DRAWINGS.
EXCEPTION: 44" MAXIMUM TO TOP ABOVE COUNTERS
WHICH ARE 20"-25"D.
16" TO BOTTOM OF BOX OR AS NOTED ON DRAWINGS.
EXCEPTION: 44" MAXIMUM TO TOP ABOVE COUNTERS
WHICH ARE 20"-25"D.
16" TO BOTTOM OF BOX.
EXCEPTION: 44" MAXIMUM TO TOP ABOVE COUNTERS
WHICH ARE 20"-25"D.
90" TO CENTERLINE OF SIGN OR CENTERED IN WALL AREA
BETWEEN TOP OF DOOR AND CEILING.
DISCONNECT SWITCHES, MOTOR STARTERS, MOTOR PUSH
BUTTON STATIONS
48" TO CENTERLINE OF BOX.
EXCEPTION: 44" MAXIMUM TO TOP ABOVE COUNTERS
WHICH ARE 20"-25"D.
MOUNTING HEIGHTSDEVICE
MOUNTING HEIGHTS FOR ELECTRICAL…