Attachment 3 - Drawings Part1 - Louis A. Johnson.pdf

PDF 47 MB Posted

Attached to
Y1DZ--Nutrition & Food Servicesand Eye/ PT Clinic Addition - - Construction - Louis A. Johnson VAMC
Solicitation number
36C77623B0031
Issued by

About this file

This document contains details of an attachment to a federal contract solicitation. The solicitation number is 36C77623B0031 for construction services for a Nutrition & Food Services and Eye/PT Clinic Addition at the Louis A. Johnson VA Medical Center. The opportunity was issued by the Department of Veterans Affairs Technology Acquisition Center located in Austin, Texas. The 47MB attachment includes drawings for the project. Responses to the solicitation are due based on the standard timeline and terms for a construction contract issued by the VA. The award is expected to be made to a contractor who can complete the clinic addition project at the specified medical center location.

View the file

Other files

File Type Posted
Amendment 8.docx DOCX document
Amendment 7.docx DOCX document
Amendment 6.docx DOCX document
Amendment 5.docx DOCX document
Sign In Sheet 10-2-23.pdf PDF
Amendment 4.docx DOCX document
Technical Question Answers.docx DOCX document
Amendment 3.docx DOCX document
Amendment 2.docx DOCX document
Sign In Sheet 9-7-23.pdf PDF
36C77623B0031 0001.docx DOCX document
36C77623B0031_1.docx DOCX document
Attachment 11 - Harrison County Wage Rates.pdf PDF
Attachment 12 - Site Visit Instructions.docx DOCX document
Attachment 8 - Geotech Report - Louis A. Johnson.pdf PDF
Attachment 6 - Drawings Part4 - Louis A. Johnson.pdf PDF
Attachment 14 - INS (Immigration) Certification.docx DOCX document
Attachment 10 - Contractor Safety - Environmental Form.docx DOCX document
Attachment 1 - Specifications - Volume 1 - FINAL.pdf PDF
Attachment 5 - Drawings Part3 - Louis A. Johnson.pdf PDF
Attachment 2 - Specifications - Volume 2 - FINAL.pdf PDF
Attachment 4 - Drawings Part2 - Louis A. Johnson.pdf PDF
Attachment 9 - Limitations on Subcontracting - Construction 02.docx DOCX document
Attachment 13 - Brand Name - Construct Nutrition.pdf PDF
Attachment 7 - Asbestos Report - Louis A. Johnson.pdf PDF
Show all 25

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

HySecurity M

50 BARRIER O

PEN - 12' CLEAR O

PENING

SHEET 7

ARCHITECTS + ENGINEERS:

1 MEDICAL CENTER DRIVE

CLARKSBURG, WV 26301-4199

PROJECT LOCATION:

LOUIS A. JOHNSON

VA MEDICAL CENTER

PROJECT TITLE:

NUTRITION & FOOD SERVICE

AND EYE / PT CLINIC ADDITION

BUILDING NUMBER:

700 NICHOLAS BLVD. SUITE 300

ELK GROVE VILLAGE, ILLINOIS 60007

847.952.9362 www.bancroft-ae.com

BANCROFT ARCHITECTS + ENGINEERS

VA CONTRACT NO. 36C24521C0034

VA PROJECT NO. 540-370

BANCROFT-AE PROJECT NO. 20-109

PROJECT NUMBERS:

U.S. Department of Veterans Affairs

OCTOBER 21, 2022

CONSTRUCTION DOCUMENTS- ISSUED FOR BID

ENVIRONMENTAL CONSULTANT:

3280 WILLIAM PITT WAY

PITTSBURGH, PA 15238

412.828.1412 www.skellyloy.com

SKELLY AND LOY CONSULTANTS, INC.

COMMERCIAL KITCHEN CONSULTANT:

615 SOUTH COLLEGE ST. 9TH FLOOR

CHARLOTTE, NC 28202

704.545.6151 www.foodesignassociates.com

FOOD DESIGN ASSOCIATES

STRUCTURAL CONSULTANT:

3750 N. KEDZIE AVENUE

CHICAGO, ILLINOIS 60618

312.544.1908 www.orionengineersllc.com

ORION ENGINEERS, PLLC

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

CONSTRUCTION DOCUMENTS-

ISSUE FOR BID

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

STAMP NUTRITION & FOOD SERVICE

AND

EYE/ PT CLINIC ADDITION

1 MEDICAL CENTER DRIVE, CLARKSBURG, WV 26301

540-370

10-21-202225% DD1 SUBMISSION 06-14-21

50% DD2 SUBMISSION 08-23-21

75% CD1 SUBMISSION 11-01-21

www. bancroft-ae.com

BAE PROJECT NO. 20-109

3300 Dundee Rd.

Northbrook, IL 60062

T: 847.952.9362

VA CONTRACT NO. 36C24521C0034

75% CD1 SUBMISSION (RESUBMITTAL) 01-11-22

100% CD 2 SUBMISSION 07-29-22

100% CD 2 SUBMISSION (RESUBMITTAL) 09-23-22

CONSTRUCTION DOCUMENTS- ISSUED FOR BID 10-21-22

CIVIL ENGINEERING CONSULTANT:

148 S. QUEEN STREET, SUITE 201

MARTINSBURG, WV 25401

304.725.8456 www.gordon-us.com

GORDON

KKolian Snapshot

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

CONSTRUCTION DOCUMENTS-

ISSUE FOR BID

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

STAMP NUTRITION & FOOD SERVICE

AND

EYE/ PT CLINIC ADDITION

1 MEDICAL CENTER DRIVE, CLARKSBURG, WV 26301

540-370

10-21-202225% DD1 SUBMISSION 06-14-21

50% DD2 SUBMISSION 08-23-21

75% CD1 SUBMISSION 11-01-21

www. bancroft-ae.com

BAE PROJECT NO. 20-109

3300 Dundee Rd.

Northbrook, IL 60062

T: 847.952.9362

VA CONTRACT NO. 36C24521C0034

75% CD1 SUBMISSION (RESUBMITTAL) 01-11-22

100% CD 2 SUBMISSION 07-29-22

100% CD 2 SUBMISSION (RESUBMITTAL) 09-23-22

CONSTRUCTION DOCUMENTS- ISSUED FOR BID 10-21-22

Drawing Number

Project Title

Location

Issue Date Checked Drawn

CONSTRUCTION DOCUMENTS-

ISSUE FOR BID

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

STAMP NUTRITION & FOOD SERVICE

AND

EYE/ PT CLINIC ADDITION

1 MEDICAL CENTER DRIVE, CLARKSBURG, WV 26301

540-370

10-21-202225% DD1 SUBMISSION 06-14-21

50% DD2 SUBMISSION 08-23-21

75% CD1 SUBMISSION 11-01-21

www. bancroft-ae.com

BAE PROJECT NO. 20-109

3300 Dundee Rd.

Northbrook, IL 60062

T: 847.952.9362

VA CONTRACT NO. 36C24521C0034

75% CD1 SUBMISSION (RESUBMITTAL) 01-11-22

100% CD 2 SUBMISSION 07-29-22

100% CD 2 SUBMISSION (RESUBMITTAL) 09-23-22

CONSTRUCTION DOCUMENTS- ISSUED FOR BID 10-21-22

Drawing Number

Project Title

Location

Issue Date Checked Drawn

CONSTRUCTION DOCUMENTS-

ISSUE FOR BID

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

STAMP NUTRITION & FOOD SERVICE

AND

EYE/ PT CLINIC ADDITION

1 MEDICAL CENTER DRIVE, CLARKSBURG, WV 26301

540-370

10-21-202225% DD1 SUBMISSION 06-14-21

50% DD2 SUBMISSION 08-23-21

75% CD1 SUBMISSION 11-01-21

www. bancroft-ae.com

BAE PROJECT NO. 20-109

3300 Dundee Rd.

Northbrook, IL 60062

T: 847.952.9362

VA CONTRACT NO. 36C24521C0034

75% CD1 SUBMISSION (RESUBMITTAL) 01-11-22

100% CD 2 SUBMISSION 07-29-22

100% CD 2 SUBMISSION (RESUBMITTAL) 09-23-22

CONSTRUCTION DOCUMENTS- ISSUED FOR BID 10-21-22

Drawing Number

Project Title

Location

Issue Date Checked Drawn

CONSTRUCTION DOCUMENTS-

ISSUE FOR BID

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

STAMP NUTRITION & FOOD SERVICE

AND

EYE/ PT CLINIC ADDITION

1 MEDICAL CENTER DRIVE, CLARKSBURG, WV 26301

540-370

10-21-202225% DD1 SUBMISSION 06-14-21

50% DD2 SUBMISSION 08-23-21

75% CD1 SUBMISSION 11-01-21

www. bancroft-ae.com

BAE PROJECT NO. 20-109

3300 Dundee Rd.

Northbrook, IL 60062

T: 847.952.9362

VA CONTRACT NO. 36C24521C0034

75% CD1 SUBMISSION (RESUBMITTAL) 01-11-22

100% CD 2 SUBMISSION 07-29-22

100% CD 2 SUBMISSION (RESUBMITTAL) 09-23-22

CONSTRUCTION DOCUMENTS- ISSUED FOR BID 10-21-22

Drawing Number

Project Title

Location

Issue Date Checked Drawn

CONSTRUCTION DOCUMENTS-

ISSUE FOR BID

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

STAMP NUTRITION & FOOD SERVICE

AND

EYE/ PT CLINIC ADDITION

1 MEDICAL CENTER DRIVE, CLARKSBURG, WV 26301

540-370

10-21-202225% DD1 SUBMISSION 06-14-21

50% DD2 SUBMISSION 08-23-21

75% CD1 SUBMISSION 11-01-21

www. bancroft-ae.com

BAE PROJECT NO. 20-109

3300 Dundee Rd.

Northbrook, IL 60062

T: 847.952.9362

VA CONTRACT NO. 36C24521C0034

75% CD1 SUBMISSION (RESUBMITTAL) 01-11-22

100% CD 2 SUBMISSION 07-29-22

100% CD 2 SUBMISSION (RESUBMITTAL) 09-23-22

CONSTRUCTION DOCUMENTS- ISSUED FOR BID 10-21-22

(E)ACSS-46(E)ACSS-47

36x24 SA36x30 RA x24

SA

(E) x20

SA

24x20 SA

36x30 RA (E)20x14 RA36x26 RA

(E)30x24 RA

(E)14x10 RA

22x18 RA

(E)8"Ø SA

(E)8"Ø SA 8"Ø

SA

6"Ø SA

8"Ø SA

(E)12"Ø SA

20x16 SA

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

CONSTRUCTION DOCUMENTS-

ISSUE FOR BID

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

STAMP NUTRITION & FOOD SERVICE

AND

EYE/ PT CLINIC ADDITION

1 MEDICAL CENTER DRIVE, CLARKSBURG, WV 26301

540-370

10-21-202225% DD1 SUBMISSION 06-14-21

50% DD2 SUBMISSION 08-23-21

75% CD1 SUBMISSION 11-01-21

www. bancroft-ae.com

BAE PROJECT NO. 20-109

3300 Dundee Rd.

Northbrook, IL 60062

T: 847.952.9362

VA CONTRACT NO. 36C24521C0034

75% CD1 SUBMISSION (RESUBMITTAL) 01-11-22

100% CD 2 SUBMISSION 07-29-22

100% CD 2 SUBMISSION (RESUBMITTAL) 09-23-22

CONSTRUCTION DOCUMENTS- ISSUED FOR BID 10-21-22

ALTERNATE NO. 2:

AHU-1 TO BE REMOVED FROM SCOPE OF WORK. PHYSICAL THERAPY CLINIC TO BE SERVED FROM EXISTING AHU

LOCATED ON THE SECOND FLOOR MECHANICAL RM. 2128, ACSS-46.

HATCH INDICATES WALLS/ AHU/ ROOF ENCLOSURE STRUCTURE TO BE REMOVED

FROM SCOPE OF WORK.

1. AHU-1 (SERVES PHYSICAL THERAPY CLINIC) TO BE REMOVED FROM SCOPE OF WORK. SEE PLAN DETAIL

1/GI004 FOR MECHANICAL DUCTWORK MODIFICATIONS REQUIRED.

2. ALL THE ELECTRICAL DEVICES AND THEIR CIRCUITING ALONG WITH LIGHTNING PROTECTION SHALL BE

ADJUSTED ACCORDINGLY.

3. MECHANICAL ENCLOSURE TO BE REDUCED IN SCOPE AS SHOWN ON DRAWINGS. EAST WALL OF THE ROOF MECHANICAL ENCLOSURE SHALL BE ON STRUCTURAL COLUMN GRID BB.5. SEE PLAN DETAIL 2/GI004.

4. TAPERED ROOFIING INSULATION SHALL BE MODIFIED AS REQUIRED.

1. REFER TO 2/GI004A FOR CONTINUATION.

2. REWORK DUCTWORK AS REQUIRED TO ACCOMMODATE VAV BOXES,

DIFFUSERS, REGISTERS, AND GRILLES AS SHOWN ON SHEET MH101.1.

3. REMOVE EXISTING DUCT CONNECTION TO ACSS-46 IN SECOND FLOOR

MECHANICAL ROOM AND PROVIDE NEW DUCT CONNECTION OF INDICATED

SIZE.

4. REFER TO 1/GI004A FOR CONTINUATION.

5. LOCATION OF EXTERIOR WALL.

X

A. MECHANICAL DEMOLITION WORK IS NOT SHOWN BUT SHALL BE PERFORMED

AS FOLLOWS:

A.A. REMOVE EXISTING MEDIUM PRESSURE SUPPLY DUCT CONNECTION TO

ACSS-46 IN SECOND FLOOR MECHANICAL ROOM AND PORTION OF DUCT

ABOVE CORRIDOR 116B. REMOVE DUCTWORK FROM CORRIDOR 116B

NORTH TO ACCOMMODATE FOR LARGER DUCTWORK.

A.B. REMOVE EXISTING RETURN DUCT CONNECTION TO ACSS-46 IN SECOND

FLOOR MECHANICAL ROOM AND PORTION OF DUCT ABOVE WAITING

1124. REMOVE DUCTWORK FROM WAITING 1124 NORTH TO

ACCOMMODATE FOR LARGER DUCTWORK.

NOTE: REFER TO SPECIFICATION SECTION 01 00 00 FOR ADDITIONAL INFORMATION OF EACH OF EACH ALTERNATE.

ALTERNATE NO. 1:

REPLACE CAST STONE BANDING WITH FACE BRICK AT EXTERIOR MASONRY WALLS. WINDOWS SILLS WILL

BE CAST STONE.

ALTERNATE NO. 2:

REMOVE AIR HANDLING UNIT AHU-37. REDUCE MECHANICAL ENCLOSURE ON ROOF. SEE PLAN DETAILS 1 &

2/GI004A FOR ALTERNATE NO. 2 DESCRIPTION.

ALTERNATE N0. 3:

REMOVE ALL WORK ASSOCIATED WITH CONFERENCE ROOM B132.

ALTERNATE NO. 4:

REMOVE PORTIONS OF WORK ASSOCIATED WITH GENERAL OFFICES ROOM B120 SERIES. SEE PLAN DETAIL

1/GI004A FOR ALTERNATE NO. 4 DESCRIPTION.

ALTERNATE NO. 5:

REMOVE PORTIONS OF WORK IN PHYSICAL THERAPY CLINIC (1122 STORAGE ALCOVE, 1122J TOILET AND 1122K

TOILET. SEE PLAN DETAIL 2/GI004A FOR ALTERNATE NO. 5 DESCRIPTION.

ALTERNATE NO. 6:

REPLACE FIBERGLASS REINFORCED PANELS (FRP) GRAPHIC PANELS (FRP-1, FRP-2, FRP-3) IN THE FOLLOWING

ROOMS:

B122 TRAY ASSEMBLY B122A CORRIDOR

B122 COOK/PREP

ALTERNATE NO. 7:

REPLACE SOLID SURFACE WALL PANELS WITH EPOXY PAINT (P-1) AND FIBERGLASS REINFORCED PANELS

(FRP-4) IN THE FOLLOWING ROOMS. BOTTOM 48 INCHES OF WALL TO RECEIVE FRP:

B122 TRAY ASSEMBLY B122A CORRIDOR

B122K CORRIDOR B122L CORRIDOR

B122O EQUIPMENT ALCOVE B122P BOX BREAKDOWN

B122U COOK/PREP B122W SMALL WARES STOR.

B122AA DISHWASHING B122BB CORRIDOR

B122EE CORRIDOR

ALTERNATE NO. 8:

REPLACE LUXURY VINYL TILE (LVT) WITH VINYL COMPOSITE TILE (VCT) IN THE FOLLOWING ROOMS:

B122E STAFF LOUNGE B122F SECRETARY

B122G CHIEF B122H ASST. CHIEF 2

B122J ASST. CHIEF 1

ALTERNATE NO. 9:

REPLACE SHEET VINYL/RUBBER BACKED FLOORING (SV-1) AND LUXURY VINYL TILE (LVT) WITH VINYL

COMPOSITE TILE (VCT) IN THE FOLLOWING ROOMS:

1122A CHECKOUT 1122B WAITING 2

1122C CONSULT 1122D CVORRIDOR

1122E OFFICE 1122F GYM

1122H STORAGE ALCOVE 1122L ADL

1122M TREATMENT 4 1122N TREATMENT 3

1122O TREATMENT 2 1122P TREATMENT 1

1122Q CHARTING

ALTERNATE NO. 10:

REMOVE CEILING SOFFITS IN FIRST FLOOR PHYSICAL THERAPY, AND REPLACE WITH ACOUSTICAL CEILING TILE (ACT-1) IN THE FOLLOWING ROOMS. RECESSED DOWNLIGHTS SHALL BE REPLACED WITH 2' X 2' LIGHTS:

1122F GYM 1122D CORRIDOR

16x10 x12 x14 x10 x12

VAV-1122L

810 CFM

14x14

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

CONSTRUCTION DOCUMENTS-

ISSUE FOR BID

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

STAMP NUTRITION & FOOD SERVICE

AND

EYE/ PT CLINIC ADDITION

1 MEDICAL CENTER DRIVE, CLARKSBURG, WV 26301

540-370

10-21-202225% DD1 SUBMISSION 06-14-21

50% DD2 SUBMISSION 08-23-21

75% CD1 SUBMISSION 11-01-21

www. bancroft-ae.com

BAE PROJECT NO. 20-109

3300 Dundee Rd.

Northbrook, IL 60062

T: 847.952.9362

VA CONTRACT NO. 36C24521C0034

75% CD1 SUBMISSION (RESUBMITTAL) 01-11-22

100% CD 2 SUBMISSION 07-29-22

100% CD 2 SUBMISSION (RESUBMITTAL) 09-23-22

CONSTRUCTION DOCUMENTS- ISSUED FOR BID 10-21-22

ALTERNATE NO. 4:

GENERAL OFFICE SPACE (B120 ROOM SERIES) TO BE REDUCED IN SCOPE OF WORK. SPACE TO BE SHELL OUT.

HATCH INDICATES WALLS TO BE REMOVED FROM SCOPE OF WORK.

1. DOORS B120 AND B120H (INCLUDING FRAME AND HARDWARE) SHALL REMAIN IN SCOPE OF WORK. SEE PLAN

DRAWINGS.

2. WALL TYPE 'C' (FURRING) AND WALL TYPE 'B1' FIRE RATED WALL (BETWEEN KITCHEN AND GENERAL OFFICE

SPACE) SHALL REMAIN AND BE PRIMED AND PAINTED.

3. FINISH CEILING AND FINISH FLOORING REMOVED FROM SCOPE OF WORK.

4. ELECTRICAL POWER/ DATA TO REMAIN ON FURRED OUT WALLS AND FIRE RATED WALL. REFER TO ELECTRICAL

DRAWINGS.

5. ELECTRICAL OUTLETS AND THEIR ASSOCIATED CIRCUITS ON HATCHED WALLS SHALL BE REMOVED FROM

SCOPE OF WORK.

6. COMMUNICATION OUTLETS ON HATCHED WALLS SHALL BE REMOVED FROM THE SCOPE OF WORK.

7. ALL EGRESS LIGHTS SHALL REMAIN. REMOVE ALL LIGHTS, ASSOCIATED SWITCHES AND CIRCUITS SHALL BE

REMOVED FROM THE SCOPE OF WORK. PROVIDE TWO (2) F3 LIGHTS AND INSTALL INTO SPACE THAT WILL

PROVIDE UNIFORM LIGHT DISTRIBUTION WITH SWITCH AT ENTRY.

8. ALL FIRE ALARM DEVICES SHALL REMAIN AS SHOWN ON EF100.

9. MECHANICAL SUPPLY AND RETURN SHALL TERMINATE AS INDICATED ON PLAN DRAWING 1/GI004A.

10. AUTOMATIC SPRINKLERS AND BRANCH PIPING SHALL BE INSTALLED IN THE UPRIGHT POSITION TO PROVIDE

ADEQUATE CODE REQUIRED COVERAGE.

ALTERNATE NO. 5:

PHYSICAL THERAPY CLINIC TO BE REDUCED IN SCOPE OF WORK. AREA CONTAINING STORAGE ALCOVE 1122H, TOILET 1

1122J, TOILET 2 1122K AND ADL 1122L WILL BECOME A SHELLED OUT SPACE.

HATCH INDICATES WORK REMOVED FROM SCOPE OF WORK.

1. EXTERIOR WALLS (INCLUDING FURRING) IN SHELLED OUT SPACE SHALL BE CONSTRUCTED AS DESIGNED, PRIMED AND PAINTED. PLUMBING CHASE WALL FRAMING FOR TOILET ROOM FIXTURES TO BE INSTALLED. DO

NOT INSTALL GYPSUM BOARD ON FINISH SIDE.

2. FINISH CEILING AND FLOORING SHALL BE REMOVED FROM SCOPE OF WORK.

3. MECHANICAL DUCTWORK TO BE MODIFIED AS INDICATED ON THE PLAN DRAWING GI004A.

4. ELECTRICAL POWER/DATA SHALL REMAIN ON BUILDING ADDITION EXTERIOR FURRED WALLS. SEE ELECTRICAL

DRAWINGS.

5. ELECTRICAL OUTLETS AND THEIR ASSOCIATED CIRCUITS ON HATCHED WALLS SHALL BE REMOVED FROM

SCOPE OF WORK.

6. ALL NURSE CALL DEVICES AND ASSOCIATED DOME LIGHTS FOR ROOMS 1122J AND 1122K SHALL BE REMOVED

FROM SCOPE OF WORK.

7. ALL EGRESS LIGHTS SHALL REMAIN. REMOVE ALL LIGHTS, ASSOCIATED SWITCHES AND CIRCUITS SHALL BE

REMOVED FROM THE SCOPE OF WORK. PROVIDE TWO (2) F3 LIGHTS AND INSTALL INTO SPACE THAT WILL

PROVIDE UNIFORM LIGHT DISTRIBUTION WITH SWITCH AT ENTRY.

8. REMOVE FIRE ALARM STROBE FROM ROOM 1122J AND 1122K. ALL OTHER FIRE ALARM DEVICES SHOWN SHALL

REMAIN.

9. TEMPORARY WALL (TYPE 'A') SHALL BE INSTALLED SEPARATING AREA FROM REMAINDER OF GYM. WALL SHALL

BE PRIMED AND PAINTED ON GYM SIDE. WALL SHALL BE PRIMED ON UNFINISHED AREA.

10. NEW 3'-0" X 7'-0" WOOD DOOR (INCLUDING H.M. FRAME AND HARDWARE) SHALL BE INSTALLED IN WALL.

HARDWARE SHALL MATCH HARDWARE SET NO. 10 IN SPECIFICATION SECTION 08 71 00.

11. SANITARY, VENT, AND DOMESTIC WATER PIPING SHALL BE INSTALLED AND SET FOR ROUGH-IN OF THE SCHEDULED FIXTURES AND TRIM, BASED ON THE FIXTURE / TRIM MANUFACTURER'S INSTALLATION SHEETS.

ROUGH-IN PIPING SHALL TERMINATE ON THE INSIDE OF THE CHASE DRYWALL LOCATION.

12. AUTOMATIC SPRINKLERS SHALL BE INSTALLED IN THE UPRIGHT POSITION TO PROVIDE ADEQUATE CODE

REQUIRED COVERAGE.

1. NEW TITUS DESV 10"Ø VAV BOX WITH HOT WATER REHEAT COIL (OR VA

APPROVED EQUAL) AT 950 CFM, 1.1 GPM. INSTALL NEW 3/4" HOT WATER

SUPPLY AND RETURN BRANCH PIPING AND CONNECT TO MAINS AS REQUIRED

TO SERVE VAV BOX. REFER TO SHEET MP100.2 FOR PIPING ROUTING.

2. NEW 18x10 TITUS 300RL GRILLE (OR VA APPROVED EQUAL) AT 475 CFM.

PROVIDE WITH BALANCING DAMPER.

3. NEW 18x10 TITUS 350RL GRILLE (OR VA APPROVED EQUAL) AT 475 CFM.

PROVIDE WITH BALANCING DAMPER.

4. THERMOSTAT FOR NEW 10"Ø VAV BOX.

X 1. NEW 12x8 TITUS 300RL GRILLE (OR VA APPROVED EQUAL) AT 270 CFM.

PROVIDE WITH BALANCING DAMPER.

2. NEW 24x12 TITUS 350RL GRILLE (OR VA APPROVED EQUAL) AT 810 CFM.

PROVIDE WITH BALANCING DAMPER.

3. CONNECT TO MAIN MEDIUM PRESSURE SUPPLY DUCTWORK.

4. CONNECT TO MAIN RETURN DUCTWORK.

5. TEMPORARY WALL. ALIGN WITH FURRED WALL IN TOILET ROOM 1122J.

X

A. MODIFICATIONS ARE ONLY TO SUPPLY AND RETURN DUCTWORK AND

EQUIPMENT. KITCHEN MAKE UP AIR DUCTWORK AND GENERAL EXHAUST

DUCTWORK SHALL REMAIN AS SHOWN ON SHEET MH100.2.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

CONSTRUCTION DOCUMENTS-

ISSUE FOR BID

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

STAMP NUTRITION & FOOD SERVICE

AND

EYE/ PT CLINIC ADDITION

1 MEDICAL CENTER DRIVE, CLARKSBURG, WV 26301

540-370

10-21-202225% DD1 SUBMISSION 06-14-21

50% DD2 SUBMISSION 08-23-21

75% CD1 SUBMISSION 11-01-21

www. bancroft-ae.com

BAE PROJECT NO. 20-109

3300 Dundee Rd.

Northbrook, IL 60062

T: 847.952.9362

VA CONTRACT NO. 36C24521C0034

75% CD1 SUBMISSION (RESUBMITTAL) 01-11-22

100% CD 2 SUBMISSION 07-29-22

100% CD 2 SUBMISSION (RESUBMITTAL) 09-23-22

CONSTRUCTION DOCUMENTS- ISSUED FOR BID 10-21-22

ALTERNATE NO. 11:

ELIMINATE RENOVATION IN THE FOLLOWING ROOMS IN THE EXISTING PHYSICAL THERAPY CLINIC:

WORK AREA 1119 BREAK ROOM 1120 PATIENT TOILET 1121

GYM 1122 TREATMENT 1122C TREATMENT 1122D

ADL 1122E CORRIDOR 1124Z

CORRIDOR LEADING TO PATIENT TOILET, BREAK ROOM AND WORK AREA.

HATCH INDICATES WORK REMOVED FROM SCOPE OF WORK.

1. AREAS WITHIN THE HATCHED LINES WILL REMAIN IN THEIR EXISTING CONDITION.

2. TEMPORARY WALL (TYPE 'A') SHALL BE INSTALLED SEPARATING AREA FROM REMAINDER OF EXISTING GYM.

WALL SHALL BE PRIMED (1 COAT) AND FINISH PAINTED (2 COATS) ON EACH SIDE OF WALL.

3. NEW 3'-0" X 7'-0" WOOD DOOR (INCLUDING H.M. FRAME AND HARDWARE) SHALL BE INSTALLED IN WALL.

HARDWARE SHALL MATCH HARDWARE SET NO. 10 IN SPECIFICATION SECTION 08 71 00. PAINT FRAMES.

4. IT ROOM 1124NN SHALL REMAIN IN SCOPE OF WORK. SEE ELECTRICAL AND MECHANICAL DRAWINGS FOR

ADDITIONAL INFORMATION.

5. CORRIDORS 1122 AND 1122D SHALL RECEIVE THE FOLLOWING:

5.1. SPRINKLER HEADS TO BE MODIFIED TO COVER AREAS REMAINING IN SCOPE OF WORK.

5.2. ACOUSTICAL CEILING TILE (ACT-2) THROUGHOUT. GYPSUM BOARD SOFFIT REMOVED FROM SCOPE OF

WORK.

5.3. RUBBER WALL BASE.

5.4. EGRESS LIGHTS SHALL REMAIN IN SCOPE OF WORK.

5.5. LUXURY VINYL TILE (LVT-2).

5.6. PROVIDE 2 X 2 LED LIGHTING, TYPE F3 (TOTAL OF 5).

5.7. EMERGENCY LIGHTS SHALL REMAIN IN SCOPE OF WORK..

5.8. RECESSED WALL WASH LIGHT FIXTURES SHALL BE REMOVED FROM SCOPE OF WORK.

1. TEMPORARY WALL. SEE GENERAL NOTES ABOVE FOR ADDITIONAL

INFORMATION.

2. REMOVE FLOOR AND CEILING FINISH AS REQUIRED FOR INSTALLATION OF

NEW IT CLOSET 1122NN. NEW IT CLOSET TO REMAIN IN SCOPE OF WORK.

3. TEMPORARY DOOR. SEE GENERAL NOTES ABOVE FOR ADDITIONAL

INFORMATION.

X

A. RECONNECT ALL EXISTING SUPPLY AND RETURN DUCTWORK WITHIN

HATCHED AREA TO NEW MAIN SUPPLY AND RETURN DUCTWORK SHOWN IN

BID ALTERNATE NO. 2 ON SHEET GI004 AS REQUIRED.

B. INSTALL NEW HEATING HOT WATER PIPING TO AVOID PIPING ABOVE 1124NN IT

ROOM AND TO SERVE EXPANSION AREA AS SHOWN ON BASE BID PLANS.

C. ROUTE COOLING COIL CONDENSATE DRAIN PIPING FROM DFSS-1124NN IN

1124NN IT ROOM TO NEAREST OPEN SIGHT DRAIN.

Drawing Number

Project Title

Location

Issue Date Checked Drawn

CONSTRUCTION DOCUMENTS-

ISSUE FOR BID

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

STAMP NUTRITION & FOOD SERVICE

AND

EYE/ PT CLINIC ADDITION

1 MEDICAL CENTER DRIVE, CLARKSBURG, WV 26301

540-370

10-21-202225% DD1 SUBMISSION 06-14-21

50% DD2 SUBMISSION 08-23-21

75% CD1 SUBMISSION 11-01-21

www. bancroft-ae.com

BAE PROJECT NO. 20-109

3300 Dundee Rd.

Northbrook, IL 60062

T: 847.952.9362

VA CONTRACT NO. 36C24521C0034

75% CD1 SUBMISSION (RESUBMITTAL) 01-11-22

100% CD 2 SUBMISSION 07-29-22

100% CD 2 SUBMISSION (RESUBMITTAL) 09-23-22

CONSTRUCTION DOCUMENTS- ISSUED FOR BID 10-21-22

1 HR FIRE BARRIER

SMOKE PARTITION

SMOKE BARRIER (FIRE RATED 1 HR.)

2 HR FIRE BARRIER

FEC

UP

UP

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

CONSTRUCTION DOCUMENTS-

ISSUE FOR BID

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

STAMP NUTRITION & FOOD SERVICE

AND

EYE/ PT CLINIC ADDITION

1 MEDICAL CENTER DRIVE, CLARKSBURG, WV 26301

540-370

10-21-202225% DD1 SUBMISSION 06-14-21

50% DD2 SUBMISSION 08-23-21

75% CD1 SUBMISSION 11-01-21

www. bancroft-ae.com

BAE PROJECT NO. 20-109

3300 Dundee Rd.

Northbrook, IL 60062

T: 847.952.9362

VA CONTRACT NO. 36C24521C0034

75% CD1 SUBMISSION (RESUBMITTAL) 01-11-22

100% CD 2 SUBMISSION 07-29-22

100% CD 2 SUBMISSION (RESUBMITTAL) 09-23-22

CONSTRUCTION DOCUMENTS- ISSUED FOR BID 10-21-22

1 HR FIRE BARRIER

SMOKE PARTITION

SMOKE BARRIER (FIRE RATED 1 HR.)

2 HR FIRE BARRIER

UP

DN

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

CONSTRUCTION DOCUMENTS-

ISSUE FOR BID

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

STAMP NUTRITION & FOOD SERVICE

AND

EYE/ PT CLINIC ADDITION

1 MEDICAL CENTER DRIVE, CLARKSBURG, WV 26301

540-370

10-21-202225% DD1 SUBMISSION 06-14-21

50% DD2 SUBMISSION 08-23-21

75% CD1 SUBMISSION 11-01-21

www. bancroft-ae.com

BAE PROJECT NO. 20-109

3300 Dundee Rd.

Northbrook, IL 60062

T: 847.952.9362

VA CONTRACT NO. 36C24521C0034

75% CD1 SUBMISSION (RESUBMITTAL) 01-11-22

100% CD 2 SUBMISSION 07-29-22

100% CD 2 SUBMISSION (RESUBMITTAL) 09-23-22

CONSTRUCTION DOCUMENTS- ISSUED FOR BID 10-21-22

POST ICRA, ILSM, FIRE

INSPECTION SHEETS

VISIBLE TO PUBLIC

SUSPENDED PLASTIC

ZIPPER WALL CURTAIN

BARRIER

INDICATOR MUST BE AT -0.01 OR MORE NEGATIVE

(VERIFY DAILY) - IF NOT, VERIFY ALL OPENINGS

(SUCH AS DOORS) ARE CLOSED AND/OR CHANGE

OUT NEGATIVE AIR PRE-FILTER.

ICRA, ILSM

FIRE WATCH

MISC. FORMS

PAPER

CADDY

INDICATOR (REFER TO

PLAN & ELEVATION)

FRAMED PICTURE

OF C.O.R.

WITH CONTACT

INFORMATION

CONST. SUPERVISOR

NAME AND

CELL PHONE

XXXX XXXX

XXXX XXXX

XXXX XXXX

CHILLER PLANT AFTER HOURS

CALL (VA PROVIDE PHONE #)

HOUSE PHONE (VA PROVIDED)

FIRE EMERGENCY DIAL 911

POST ICRA, ILSM, FIRE

INSPECTION SHEETS

VISIBLE TO PUBLIC

MONTHLY CHANGED

HEPA FILTER

HEPA NEGATIVE AIR UNIT

WEEKLY CHANGED (OR MORE AS

NEEDED) PRE-FILTER

SUPPLY DUCTS -

EITHER KEEP RUNNING OR COVER

WHEN RUNNING TO KEEP DUST

OUT

PROVIDE STICKY MATS (CHANGED

END OF SHIFT OR MORE IF

NECESSARY TO MAINTAIN

CLEANLINESS)

INDICATOR MUST BE AT -0.01 OR GREATER (VERIFY DAILY) - IF

NOT, VERIFY ALL OPENINGS (SUCH AS DOORS) ARE CLOSED

AND/OR CHANGE OUT NEGATIVE AIR PRE-FILTER

PROVIDE STICKY MATS (CHANGED END OF SHIFT OR MORE IF

NECESSARY TO MAINTAIN CLEANLINESS)

FIRE EXTINGUISHER ON

PORTABLE FLOOR BRACKET (ILSM

MAY REQUIRE MORE THAN ONE)

TAPE ALL SERVICES TO PROTECT

AGAINST CONTAMINATION

A

O

V

OPTIONAL EXHAUST DUCTS

(COVER THE GRATES AND

DIFFUSERS)

E

COVER ALL RETURNS AT THE

GRATE/ DIFFUSERS

OUTSIDE OF BUILDING

FIRE RATED PLYWOOD (REFER TO

ELEVATION)

FL

EX

DU

CT

A A

SUSPENDED ACOUSTICAL

CEILING AS SCHEDULED

ON FLOOR PLAN

QUICK SET FIRE STOP

BOTTOM OF METAL DECK

EXISTING FLOOR/ ROOF DECK

5/8" TYPE 'X' GYPSUM

BOARD EACH SIDE OVER

3-5/8" METAL STUDS (16

GA.) AT 16" O.C., WITH

3-1/2" BATT INSULATION-

EXTEND TO BOTTOM OF

STRUCTURE ABOVE

4" RUBBER COVE BASE TO

MATCH EXISTING AREA

BASE ON EACH SIDE OF

WALL

NOTE: ALL TEMPORARY CONSTRUCTION BARRIERS TO BE 1- HOUR RATED, U.N.O.

WALL CONST. TYPES (DETAILS)

TYPE A UL DESIGN NO. 419 TYPE B TYPE C UL DESIGN NO. V497

TYPICAL IDEAL CONSTRUCTION LAYOUT

CLASS III

SCALE: 1/2"= 1'-0"

ENTRANCE ELEVATION

MOBILE CONTAINMENT CART

(CONSTRUCTION BARRIER TYPES)

SCALE: 1/2"= 1'-0"

SWIVEL CASTERS

HARD SIDED MOBILE

CONTAINMENT CART

ZIPPER SIDE ENTRY

PLASTIC WINDOW

(ON ALL SIDES)

AD

JU

ST

AB

LE

HE

IGH

T

AD

JU

ST

AB

LE

HE

IGH

T

FLEX DUCT

FLEX DUCT

HEPA NEGATIVE AIR UNIT

SUSPENDED ACOUSTICAL

CEILING AS SCHEDULED

ON FLOOR PLAN

5/8" TYPE 'X' GYPSUM

BOARD EACH SIDE OVER

3-5/8" METAL STUDS (16

GA.) AT 16" O.C.- EXTEND

TO BOTTOM OF

STRUCTURE ABOVE

4" RUBBER COVE BASE TO

MATCH EXISTING AREA

BASE ON EACH SIDE OF

WALL

QUICK SET FIRE STOP

EXISTING FINISH CEILING

TO REMAIN

EXISTING WALL TO

REMAIN

TWO (2) LAYERS 5/8" TYPE

'X' GYPSUM BOARD ONE

SIDE (CONSTRUCTION

SIDE) OVER 3-5/8" METAL

STUDS (16 GA.) AT 16"

O.C.-WALL TO EXTEND TO

BOTTOM OF STRUCTURE

ABOVE

BOTTOM OF METAL DECK

EXIST. FLOOR/ ROOF

DECK

NOTE:

USE OF MOBILE CONTAINMENT CART OUTSIDE OF THE SCOPE OF WORK

AREAS SHALL BE APPRVOED BY THE VA COR

THIS IS A

RESTRICTED AREA

AREA UNDER

CONSTRUCTION

COMING SOON!!!

(DESCRIPTION OF NEWLY PROPOSED OCCUPANCY)

PERSONNEL ENTERING MUST HAVE: HARD HAT, SAFETY

GLASSES AND PROPER I.D.

BLUE CORE LOCKSET

(LOCKED AT ALL TIMES)

1. REMOVE OR ISOLATE H.V.A.C. SYSTEM IN AREA WHERE WORK IS BEING DONE TO PREVENT CONTAMINATION

OF DUCT SYSTEM.

2. COMPLETE ALL CRITICAL BARRIERS IE. SHEETROCK, PLYWOOD, PLASTIC, TO SEAL AREA FROM NON-WORK AREA OR IMPLEMENT CONTROL CUBE METHOD (CART WITH PLASTIC COVERING AND SEALED CONNECTION TO WORK SITE WITH HEPA VACUUM FOR VACUUMING PRIOR TO EXIT) BEFORE CONSTRUCTION BEGINS.

3. MAINTAIN NEGATIVE AIR PRESSURE WITHIN WORK SITE UTILIZING HEPA EQUIPPED AIR FILTRATION UNITS IF

INDICATED.

4. CONTAIN CONSTRUCTION WASTE BEFORE TRANSPORT IN TIGHTLY COVERED CONTAINERS.

5. COVER TRANSPORT RECEPTACLES OR CARTS. TAPE COVERING UNLESS SOLID LID.

6. DO NOT REMOVE BARRIERS FROM WORK AREA UNTIL COMPLETED PROJECT IS INSPECTED BY THE

OWNER'S SAFETY DEPARTMENT AND INFECTION CONTROL DEPARTMENT AND THOROUGHLY CLEANED BY

THE OWNER'S ENVIRONMENTAL SERVICES DEPARTMENT.

CLASS III WORK ITEM NOTES

PRIOR TO ANY CONSTRUCTION

POST CONSTRUCTION

1. REMOVE BARRIER MATERIALS CAREFULLY TO MINIMIZE SPREADING OF DIRT AND DEBRIS ASSOCIATED WITH

CONSTRUTION.

2. VACUUM WORK AREA WITH HEPA FILTERED VACUUM.

3. WET MOP AREA WITH DISINFECTANT.

4. REMOVE ISOLATION OF H.V.A.C. SYSTEM IN AREAS WHERE WORK IS BEING PERFORMED.

CL

AS

S

III

IC MATRIX - CLASS OF PRECAUTIONS:

CONSTRUCTION PROJECT BY PATIENT RISK BY

CONSTRUCTION PROJECT TYPE

LOW RISK GROUP

MEDIUM RISK GROUP

HIGH RISK GROUP

HIGHEST RISK GROUP

RISK RELATED GROUP TYPE A

I

I

I

II

TYPE B

II

II

II

III/IV

TYPE D

III/IV

IV

IV

IV

TYPE C

II

III

III/IV

III/IV

NOTE:

INFECTION CONTROL APPROVAL WILL BE REQUIRED WHEN THE CONSTRUCTION ACTIVITY AND RISK LEVEL

INDICATE THAT CLASS III OR CLASS IV CONTROL PROCEDURES ARE NECESSARY.

PATIENT RISK GROUPS

LOW RISK

OFFICE AREAS

MEDIUM RISK

CARDIOLOGY

ECHOCARDIOGRAPHY

ENDOSCOPY

NUCLEAR MEDICINE

PHYSICAL THERAPY

RADIOLOGY/ MRI

RESPIRATORY THERAPY

HIGH RISK

CCU

EMERGENCY ROOM

LABOR & DELIVERY

LABORATORY (SPECIMEN)

NEWBORN NURSERY

OUTPATIENT SURGERY

PEDIATRICS

POST ANESTHESIA

CARE UNIT

PHARMACY

SURGICAL UNITS

HIGHEST RISK

ANY AREA CARING FOR

IMMUNOCOMPROMISED PATIENTS

BURN UNIT

CARDIAC CATH LAB

CENTRAL STERILE SUPPLY

INTENSIVE CARE UNITS

MEDICAL UNIT

NEGATIVE PRESSURE ISOLATION ROOMS

OPERATING ROOMS INCLUDING C-SECTION

ROOMS

ONCOLOGY

CONSTRUCTION PROJECT TYPES

TYPE A

MINIMAL

FIRE RISK

TYPE B

LIMITED

FIRE RISK

TYPE C

MODERATE

FIRE RISK

TYPE D

SIGNIFICANT

FIRE RISK

INSPECTION AND NON-INVASIVE ACTIVITES.

INCLUDES, BUT IS NOT LIMITED TO:

- REMOVAL OF CEILING TILES FOR VISUAL INSPECTION LIMITED TO 1 TILE PER 50 SQUARE FEET.

- PAINTING (BUT NOT SANDING).

- WALL COVERING, ELECTRICAL TRIM WORK, MINOR PLUMBING, AND ACTIVITIES WHICH DO NOT GENERATE

DUST OR REQUIRE CUTTING OF WALLS OR ACCESS TO CEILINGS OTHER THAN FOR VISUAL INSPECTION.

- REMOVAL OF FLOOR TILE LESS THAN 25 SQUARE FEET, NON-ACM AND NO GRINDING OR DUST GENERATING

ACTIVITIES.

SMALL SCALE, SHORT DURATION ACTIVITIES WHICH CREATE MINIMAL DUST.

INCLUDES, BUT IS NOT LIMITED TO:

- INSTALLATION OF TELEPHONE AND COMPUTER CABLING.

- ACCESS TO CHASE SPACES.

- CUTTING OF WALLS OR CEILING WHERE DUST MIGRATION CAN BE CONTROLLED.

WORK THAT GENERATES A MODERATE TO HIGH LEVEL OF DUST OR REQUIRES DEMOLITION OR REMOVAL OF ANY

FIXED BUILDING OR ASSEMBLIES.

INCLUDES, BUT IS NOT LIMITED TO:

- SANDING OF WALLS FOR PAINTING OR WALL COVERING.

- REMOVAL OF FLOOR COVERINGS, CEILING TILES AND CASEWORK.

- NEW CONSTRUCTION OR RENOVATIONS OVER 3 DAYS DURATION.

- MAJOR DUCT WORK, PLUMBING, PIPING, OR ELECTRICAL WORK.

- SOLDERING OR BRAZING OPERATIONS.

- ANY ACTIVITY THAT REQUIRES A BURN PERMIT.

MAJOR DEMOLITION AND CONSTRUCTION PROJECTS.

INCLUDES, BUT IS NOT LIMITED TO:

- ACTIVITIES WHICH REQUIRE CONSECUTIVE WORK SHIFTS.

- REQUIRES HEAVY DEMOLITION OR REMOVAL OF A COMPLETE BUILDING SYSTEM.

- NEW CONSTRUCTION OR RENOVATIONS OVER 3 DAYS DURATION.

SEE SHEET GI002 FOR INFECTION CONTROL GENERAL NOTES

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

CONSTRUCTION DOCUMENTS-

ISSUE FOR BID

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

STAMP NUTRITION & FOOD SERVICE

AND

EYE/ PT CLINIC ADDITION

1 MEDICAL CENTER DRIVE, CLARKSBURG, WV 26301

540-370

10-21-202225% DD1 SUBMISSION 06-14-21

50% DD2 SUBMISSION 08-23-21

75% CD1 SUBMISSION 11-01-21

www. bancroft-ae.com

BAE PROJECT NO. 20-109

3300 Dundee Rd.

Northbrook, IL 60062

T: 847.952.9362

VA CONTRACT NO. 36C24521C0034

75% CD1 SUBMISSION (RESUBMITTAL) 01-11-22

100% CD 2 SUBMISSION 07-29-22

100% CD 2 SUBMISSION (RESUBMITTAL) 09-23-22

CONSTRUCTION DOCUMENTS- ISSUED FOR BID 10-21-22

TYPE B

POST ICRA, ILSM, FIRE

INSPECTION SHEETS

VISIBLE TO PUBLIC

INDICATOR MUST BE AT -0.01 OR MORE NEGATIVE (VERIFY DAILY)

- IF NOT, VERIFY ALL OPENINGS (SUCH AS DOORS) ARE CLOSED

AND/OR CHANGE OUT NEGATIVE AIR PRE-FILTER.

ICRA, ILSM

FIRE WATCH

MISC. FORMS

PAPER

CADDY INDICATOR (REFER TO

PLAN & ELEVATION)

FRAMED PICTURE

OF C.O.R.

WITH CONTACT

INFORMATION

CONST. SUPERVISOR

NAME AND

CELL PHONE

XXXX XXXX

XXXX XXXX

XXXX XXXX

CHILLER PLANT AFTER HOURS

CALL (VA PROVIDE PHONE #)

HOUSE PHONE (VA PROVIDED)

FIRE EMERGENCY DIAL 911

SUSPENDED ACOUSTICAL

CEILING AS SCHEDULED

ON FLOOR PLAN

QUICK SET FIRE STOP

BOTTOM OF METAL DECK

EXISTING FLOOR/ ROOF DECK

5/8" TYPE 'X' GYPSUM

BOARD EACH SIDE OVER

3-5/8" METAL STUDS (16

GA.) AT 16" O.C., WITH

3-1/2" BATT INSULATION-

EXTEND TO BOTTOM OF

STRUCTURE ABOVE

4" RUBBER COVE BASE TO

MATCH EXISTING AREA

BASE ON EACH SIDE OF

WALL

NOTE: ALL TEMPORARY CONSTRUCTION BARRIERS TO BE 1- HOUR RATED, U.N.O.

TYPE A UL DESIGN NO. 419 TYPE B TYPE C UL DESIGN NO. V497

(CONSTRUCTION BARRIER TYPES)

SCALE: 1/2"= 1'-0"

SWIVEL CASTERS

HARD SIDED MOBILE

CONTAINMENT CART

ZIPPER SIDE ENTRY

PLASTIC WINDOW

(ON ALL SIDES)

AD

JU

ST

AB

LE

HE

IGH

T

AD

JU

ST

AB

LE

HE

IGH

T

FLEX DUCT

FLEX DUCT

HEPA NEGATIVE AIR UNIT

SUSPENDED ACOUSTICAL

CEILING AS SCHEDULED

ON FLOOR PLAN

5/8" TYPE 'X' GYPSUM

BOARD EACH SIDE OVER

3-5/8" METAL STUDS (16

GA.) AT 16" O.C.- EXTEND

TO BOTTOM OF

STRUCTURE ABOVE

4" RUBBER COVE BASE TO

MATCH EXISTING AREA

BASE ON EACH SIDE OF

WALL

QUICK SET FIRE STOP

EXISTING FINISH CEILING

TO REMAIN

EXISTING WALL TO

REMAIN

TWO (2) LAYERS 5/8" TYPE

'X' GYPSUM BOARD ONE

SIDE (CONSTRUCTION

SIDE) OVER 3-5/8" METAL

STUDS (16 GA.) AT 16"

O.C.-WALL TO EXTEND TO

BOTTOM OF STRUCTURE

ABOVE

BOTTOM OF METAL DECK

EXIST. FLOOR/ ROOF

DECK

NOTE:

USE OF MOBILE CONTAINMENT CART OUTSIDE OF

THE SCOPE OF WORK AREAS SHALL BE APPRVOED

BY THE VA COR

THIS IS A

RESTRICTED AREA

AREA UNDER

CONSTRUCTION

COMING SOON!!!

(DESCRIPTION OF NEWLY PROPOSED OCCUPANCY)

PERSONNEL ENTERING MUST HAVE: HARD HAT, SAFETY

GLASSES AND PROPER I.D.

OUTSIDE OF BUILDING

HARD BARRIER

BLUE CORE LOCKSET

(LOCKED AT ALL TIMES)

MONTHLY CHANGED

HEPA FILTER

COVER ALL RETURNS AT THE

GRATE/ DIFFUSERS WITH FIRE

RATED PLASTIC SHEETING AND

SECURE WITH DUCT TAPE

FIRE RATED PLYWOOD (REFER TO

ELEVATION)

FL

EX

DU

CT

WEEKLY CHANGED (OR MORE AS

NEEDED) PRE-FILTER

SUPPLY DUCTS -

EITHER KEEP RUNNING OR COVER

WITH FIRE RATED PLASTIC

SHEETING AND SECURE WITH

DUCT TAPE TO KEEP DUST OUT

HEPA NEGATIVE AIR UNIT

ABC TYPE FIRE EXTINGUISHER ON

PORTABLE FLOOR BRACKET (ILSM

MAY REQUIRE MORE THAN ONE

OR WALL MOUNTED).

NEED INSPECTION TAG AND

MONTHLY INSPECTION

(INITIALS/DATED)

TAPE ALL SERVICES TO PROTECT

AGAINST CONTAMINATION

OPTIONAL EXHAUST DUCTS

(COVER THE GRATES AND

DIFFUSERS)

E

A

O

V

INDICATOR MUST BE AT -0.01 OR GREATER (VERIFY DAILY) - IF

NOT, VERIFY ALL OPENINGS (SUCH AS DOORS) ARE CLOSED

AND/OR CHANGE OUT NEGATIVE AIR PRE-FILTER (TYPICAL

REGULATOR INSTALLATION)

POST ICRA, ILSM, FIRE INSPECTION SHEETS VISIBLE TO PUBLIC

PROVIDE STICKY MATS (CHANGED END

OF SHIFT OR MORE IF NECESSARY TO

MAINTAIN CLEANLINESS)

A A

WALL CONST. TYPES (DETAILS)

ANTEROOM ENTRANCE - SIDE ELEVATION

MOBILE CONTAINMENT CART

TYPICAL IDEAL CONSTRUCTION LAYOUT

CLASS IV

SCALE: 1/2"= 1'-0"

EXISTING WALL

FINISHED FLOORING TO BE KEPT CLEAN. FLOORS

NOT BEING REPLACED TO BE PROTECTED OR

COVERED WITH ROSEN PAPER/ FIRE RATED

PLYWOOD.

HEPA NEGATIVE AIR UNIT

EXISTING WINDOW FRAME

FIRE RATED PLYWOOD (TEMP.

REMOVE GLASS PANEL)

FIRE/ U.L. RATED PLASTIC TO

PREVENT DUCT INFILTRATION

(INSTALL PRIOR TO

CONSTRUCTION).

EXISTING FIRE SPRINKLER

SYSTEM

EXISTING WALL

EXISTING CONCRETE SLAB

FLOORING

SCALE: 1/2"= 1'-0"

CROSS-SECTION 'A-A'

CLASS IV

TEMPORARY ANTEROOM

1. ISOLATE H.V.A.C. SYSTEM IN AREA WHERE WORK IS BEING DONE TO PREVENT CONTAMINATION OF DUCT

SYSTEM.

2. COMPLETE ALL CRITICAL BARRIERS IE. SHEETROCK, PLYWOOD, PLASTIC, TO SEAL AREA FROM NON-WORK AREA OR IMPLEMENT CONTROL CUBE METHOD (CART WITH PLASTIC COVERING AND SEALED CONNECTION TO WORK SITE WITH HEPA VACUUM FOR VACUUMING PRIOR TO EXIT) BEFORE CONSTRUCTION BEGINS.

3. MAINTAIN NEGATIVE AIR PRESSURE WITHIN WORK SITE UTILIZING HEPA EQUIPPED AIR FILTRATION UNITS IF

INDICATED.

4. SEAL HOLES, PIPES, CONDUITS, AND PUNCTURES APPROPRIATELY.

5. CONSTRUCT ANTEROOM AND REQUIRE ALL PERSONNEL TO PASS THROUGH THIS ROOM SO THEY CAN BE

VACUUMED USING HEPA VACUUM CLEANER BEFORE LEAVING WORK SITE OR THEY CAN WEAR CLOTH OR

PAPER COVERALLS THAT ARE REMOVED EACH TIME THEY LEAVE THE WORK SITE.

6. ALL PERSONNEL ENTERING WORK SITE ARE REQUIRED TO WEAR SHOE COVERS. SHOE COVERS MUST BE CHANGED EACH TIME THE WORKER EXITS THE WORK AREA SITE OR THEY CAN WEAR CLOTH OR PAPER

COVERALLS THAT ARE REMOVED EACH TIME THEY LEAVE THE WORK SITE.

7. DO NOT REMOVE BARRIERS FROM WORK AREA UNTIL COMPLETED PROJECT IS INSPECTED BY THE VA'S

SAFETY DEPARTMENT AND INFECTION CONTROL.

PRIOR TO ANY CONSTRUCTION

POST CONSTRUCTION

1. OBTAIN APPROVAL BY THE VA TO REMOVE BARRIERS.

2. REMOVE BARRIER MATERIALS CAREFULLY TO MINIMIZE SPREADING OF DIRT AND DEBRIS ASSOCIATED WITH

CONSTRUCTION.

3. CONTAIN CONSTRUCTION WASTE BEFORE TRANSPORT IN TIGHTLY COVERED CONTAINERS.

4. COVER TRANSPORT RECEPTACLES OR CARTS. TAPE COVERING UNLESS SOLID LIQUID.

5. VACUUM WORK AREA WITH HEPA FILTERED VACUUM.

6. WET MOP AREA WITH DISINFECTANT.

7. REMOVE ISOLATION OF H.V.A.C. SYSTEM IN AREAS WHERE WORK IS BEING PERFORMED.

8. ROOM AND/ OR AREA SHALL BE THOROUGHLY CLEANED BY THE VA'S ENVIRONMENTAL SERVICES

DEPARTMENT.

CL

AS

S

IV

IC MATRIX - CLASS OF PRECAUTIONS:

CONSTRUCTION PROJECT BY PATIENT RISK BY

CONSTRUCTION PROJECT TYPE

LOW RISK GROUP

MEDIUM RISK GROUP

HIGH RISK GROUP

HIGHEST RISK GROUP

RISK RELATED GROUP TYPE A

I

I

I

II

TYPE B

II

II

II

III/IV

TYPE D

III/IV

IV

IV

IV

TYPE C

II

III

III/IV

III/IV

NOTE:

INFECTION CONTROL APPROVAL WILL BE REQUIRED WHEN THE CONSTRUCTION ACTIVITY AND RISK LEVEL

INDICATE THAT CLASS III OR CLASS IV CONTROL PROCEDURES ARE NECESSARY.

PATIENT RISK GROUPS

LOW RISK

OFFICE AREAS

MEDIUM RISK

CARDIOLOGY

ECHOCARDIOGRAPHY

ENDOSCOPY

NUCLEAR MEDICINE

PHYSICAL THERAPY

RADIOLOGY/ MRI

RESPIRATORY THERAPY

HIGH RISK

CCU

EMERGENCY ROOM

LABOR & DELIVERY

LABORATORY (SPECIMEN)

NEWBORN NURSERY

OUTPATIENT SURGERY

PEDIATRICS

POST ANESTHESIA

CARE UNIT

PHARMACY

SURGICAL UNITS

HIGHEST RISK

ANY AREA CARING FOR

IMMUNOCOMPROMISED PATIENTS

BURN UNIT

CARDIAC CATH LAB

CENTRAL STERILE SUPPLY

INTENSIVE CARE UNITS

MEDICAL UNIT

NEGATIVE PRESSURE ISOLATION ROOMS

OPERATING ROOMS INCLUDING C-SECTION

ROOMS

ONCOLOGY

CONSTRUCTION PROJECT TYPES

TYPE A

MINIMAL

FIRE RISK

TYPE B

LIMITED

FIRE RISK

TYPE C

MODERATE

FIRE RISK

TYPE D

SIGNIFICANT

FIRE RISK

INSPECTION AND NON-INVASIVE ACTIVITES.

INCLUDES, BUT IS NOT LIMITED TO:

- REMOVAL OF CEILING TILES FOR VISUAL INSPECTION LIMITED TO 1 TILE PER 50 SQUARE FEET.

- PAINTING (BUT NOT SANDING).

- WALL COVERING, ELECTRICAL TRIM WORK, MINOR PLUMBING, AND ACTIVITIES WHICH DO NOT GENERATE

DUST OR REQUIRE CUTTING OF WALLS OR ACCESS TO CEILINGS OTHER THAN FOR VISUAL INSPECTION.

- REMOVAL OF FLOOR TILE LESS THAN 25 SQUARE FEET, NON-ACM AND NO GRINDING OR DUST GENERATING

ACTIVITIES.

SMALL SCALE, SHORT DURATION ACTIVITIES WHICH CREATE MINIMAL DUST.

INCLUDES, BUT IS NOT LIMITED TO:

- INSTALLATION OF TELEPHONE AND COMPUTER CABLING.

- ACCESS TO CHASE SPACES.

- CUTTING OF WALLS OR CEILING WHERE DUST MIGRATION CAN BE CONTROLLED.

WORK THAT GENERATES A MODERATE TO HIGH LEVEL OF DUST OR REQUIRES DEMOLITION OR REMOVAL OF ANY

FIXED BUILDING OR ASSEMBLIES.

INCLUDES, BUT IS NOT LIMITED TO:

- SANDING OF WALLS FOR PAINTING OR WALL COVERING.

- REMOVAL OF FLOOR COVERINGS, CEILING TILES AND CASEWORK.

- NEW CONSTRUCTION OR RENOVATIONS OVER 3 DAYS DURATION.

- MAJOR DUCT WORK, PLUMBING, PIPING, OR ELECTRICAL WORK.

- SOLDERING OR BRAZING OPERATIONS.

- ANY ACTIVITY THAT REQUIRES A BURN PERMIT.

MAJOR DEMOLITION AND CONSTRUCTION PROJECTS.

INCLUDES, BUT IS NOT LIMITED TO:

- ACTIVITIES WHICH REQUIRE CONSECUTIVE WORK SHIFTS.

- REQUIRES HEAVY DEMOLITION OR REMOVAL OF A COMPLETE BUILDING SYSTEM.

- NEW CONSTRUCTION OR RENOVATIONS OVER 3 DAYS DURATION.

CLASS IV WORK ITEM NOTES

SEE SHEET GI002 FOR INFECTION CONTROL GENERAL NOTES

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

CONSTRUCTION DOCUMENTS-

ISSUE FOR BID

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

STAMP NUTRITION & FOOD SERVICE

AND

EYE/ PT CLINIC ADDITION

1 MEDICAL CENTER DRIVE, CLARKSBURG, WV 26301

540-370

10-21-202225% DD1 SUBMISSION 06-14-21

50% DD2 SUBMISSION 08-23-21

75% CD1 SUBMISSION 11-01-21

www. bancroft-ae.com

BAE PROJECT NO. 20-109

3300 Dundee Rd.

Northbrook, IL 60062

T: 847.952.9362

VA CONTRACT NO. 36C24521C0034

75% CD1 SUBMISSION (RESUBMITTAL) 01-11-22

100% CD 2 SUBMISSION 07-29-22

100% CD 2 SUBMISSION (RESUBMITTAL) 09-23-22

CONSTRUCTION DOCUMENTS- ISSUED FOR BID 10-21-22

EXIST. BUILDING

EXIST. BUILDING

(VETERANS NURSING FACILITY) EXIST.

GENERATOR

EXIST.

A.C

EXIST.

BUILDING

(#5)

NEW

BUILDING

EXISTING

BUILDING (#7)

EXIST. CANOPY

EXISTING

PARKING LOT

EXISTING

BUILDING (#6)

EXIST.

BUILDING

DRIVE TO NURSING HOME

EXISTING PARKING

EXISTING PARKING

EXISTING

PARKING LOT

EXIST.

LOADING DOCK

EXIST.

LOADING

DOCK

EXIST.

BUILDING

(#1)

EXIST.

BUILDING

EXIST.

UNDERGROUND

FUEL STORAGE

EXISTING

BUILDING

(#20)

NEW BUILDING

PROPERTY LINE

DUMPSTER LOCATION - COORDINATE WITH VA COR

CONTRACTOR ENTRANCE INTO BUILDING

CONTRACTOR PARKING - COORDINATE WITH VA COR

TEMPORARY FOOD SERVICE COOLERS

CONSTRUCTION ENTRANCE

CRANE LOCATION - INDICATING GENERAL DIRECTION AND REACH

CRANE LOCATION TO BE COORDINATED WITH VA COR.

A. GENERAL CONTRACTOR TO COORDINATE CONSTRUCTION STAGING AND

ROUTING WITH VA COR. TO INCLUDE, BUT NOT LIMITED TO, CONTRACTOR

PARKING, CONTRACTOR ENTRANCE TO HOSPITAL, DUMPSTER LOCATIONS,

ETC.

B. EXISTING ROOFS SHALL BE PROTECTED DURING CONSTRUCTION.

C. POWER FOR SECURITY GATE SHALL BE CONNECTED IN BUILDINIG 20,

ELECTRICAL ROOM. COMMUNICATIONS SHALL BE CONNECTED TO THE

SECURITY OFFICE IN BUILDING 1, FIRST FLOOR. GATE SHALL BE CONTROLLED

FROM SECURITY OFFICE DURING NORMAL BUSINESS HOURS. GATE SHALL BE

CONTROLLED FROM ROOM AOD OFFICE IN BUILDING 1 DURING AFTER HOURS.

REFER TO ELECTRICAL DRAWINGS FOR ADDITIONAL INFORMATION.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

CONSTRUCTION DOCUMENTS-

ISSUE FOR BID

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

STAMP NUTRITION & FOOD SERVICE

AND

EYE/ PT CLINIC ADDITION

1 MEDICAL CENTER DRIVE, CLARKSBURG, WV 26301

540-370

10-21-202225% DD1 SUBMISSION 06-14-21

50% DD2 SUBMISSION 08-23-21

75% CD1 SUBMISSION 11-01-21

www. bancroft-ae.com

BAE PROJECT NO. 20-109

3300 Dundee Rd.

Northbrook, IL 60062

T: 847.952.9362

VA CONTRACT NO. 36C24521C0034

75% CD1 SUBMISSION (RESUBMITTAL) 01-11-22

100% CD 2 SUBMISSION 07-29-22

100% CD 2 SUBMISSION (RESUBMITTAL) 09-23-22

CONSTRUCTION DOCUMENTS- ISSUED FOR BID 10-21-22

AREA OF WORK -

PHYSICAL SECURITY GATE/ FENCE

SEE NOTE C.

AREA OF WORK-

BUILDING ADDITION AND

RENOVATION

AREA OF WORK -

ELECTRICAL ROOM (PHYSICAL SECURITY

GATE POWER CONNECTION)

SEE NOTE C.

SECURITY OFFICE

(FIRST FLOOR- RM. 1240)

SEE NOTE C.

ADMINISTRATIVE OFFICER ON

DUTY OFFICE

(FIRST FLOOR- RM. 1220B)

SEE NOTE C.

FEC

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

CONSTRUCTION DOCUMENTS-

ISSUE FOR BID

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

STAMP NUTRITION & FOOD SERVICE

AND

EYE/ PT CLINIC ADDITION

1 MEDICAL CENTER DRIVE, CLARKSBURG, WV 26301

540-370

10-21-202225% DD1 SUBMISSION 06-14-21

50% DD2 SUBMISSION 08-23-21

75% CD1 SUBMISSION 11-01-21

www. bancroft-ae.com

BAE PROJECT NO. 20-109

3300 Dundee Rd.

Northbrook, IL 60062

T: 847.952.9362

VA CONTRACT NO. 36C24521C0034

75% CD1 SUBMISSION (RESUBMITTAL) 01-11-22

100% CD 2 SUBMISSION 07-29-22

100% CD 2 SUBMISSION (RESUBMITTAL) 09-23-22

CONSTRUCTION DOCUMENTS- ISSUED FOR BID 10-21-22

SCOPE OF WORK:

NEW DISHWASHING AREA, COOLERS/ FREEZERS, NFS OFFICES AND NEW

ADDITION. EXISTING KITCHEN PREP, COOKING, TRAY ASSEMBLY, DRY FOOD

STORAGE, DISHWASHING AND NFS OFFICES TO REMAIN FULLY OPERATIONAL

DURING PHASE 1 WORK.

PERFORM ASBESTOS ABATEMENT FOR WORK AREAS IN THIS PHASE. REFER

TO HAZARDOUS MATERIALS DRAWINGS AND REPORT (IN SPECIFICATIONS

MANUAL) FOR EXTENT OF ACM ABATEMENT.

SEQUENCE OF WORK TO ALLOW FOR EXPEDITED CONSTRUCTION AND

TRANSITION INTO PHASE 1B AREAS.

PHASE 1A:

1. EXISTING OFFICE SUITE B117 AND STORAGE SUITE B120 TO BE

DEMOLISHED.

2. STEAM PIPING FOR NEW DISHWASHER AND CART WASHER TO BE

INSTALLED IN EXISTING AND NEW PIPE TRENCHES.

3. ELECTRICAL ROOM SHALL BE CONSTRUCTED DURING PHASE 1A.

PHASE 1B:

1. REROUTE EXHAUST FOR EXISTING DISHWASHING EQUIPMENT PRIOR

TO START OF DEMOLITION ON PHASE 1B. REFER TO MECHANICAL

DRAWINGS FOR PROPOSED ROUTING FOR TEMPORARY EXHAUST

DUCTWORK. WORK TO BE COMPLETED AFTER HOURS.

2. EXISTING COOLERS/ FREEZERS AND STORAGE AREAS TO BE

DEMOLISHED.

3. INSTALL TEMPORARY CONDENSING UNITS FOR COOLERS/ FREEZERS.

LOCATE UNITS ON ROOF ABOVE EXISTING PHYSICAL THERAPY CLINIC

(UNLESS PERMANENT CU'S HAVE BEEN INSTALLED ON ROOF OF

ADDITION).

4. TEMPORARY COOLERS/ FREEZERS SHALL BE LOCATED IN EXISTING

CART STORAGE AREA B122 DURING THIS PHASE.

5. PHASE 1B NEW WORK TO BE COMPLETED PRIOR TO REMOVAL OF

TEMPORARY COOLERS/ FREEZERS.

6. NEW GREASE TRAP AND UNDERGROUND UTILITIES TO BE INSTALLED

PRIOR TO START OF PHASE 1C. GREASE TRAP TO BE FULLY

OPERATIONAL PRIOR TO START OF PHASE 2.

PHASE 1A PHASE 1C

(ADDITION)

PHASE 1B

PHASE 2A

PHASE

SCOPE OF WORK:

MOVE KITCHEN TRAY ASSEMBLY TO NEW SPACE, GENERAL OFFICE SPACE,

AND REMODEL CONFERENCE ROOM B132.

PERFORM ASBESTOS ABATEMENT FOR WORK AREAS IN THIS PHASE. REFER

TO HAZARDOUS MATERIALS DRAWINGS AND REPORT (IN SPECIFICATIONS

MANUAL) FOR EXTENT OF ACM ABATEMENT.

1. MOVE KITCHEN TRAY ASSEMBLY TO NEW KITCHEN.

2. DEMOLISH EXISTING OFFICES, BREAK RM., FOOD STORAGE AREAS.

3. BUILD NEW GENERAL OFFICE SPACE.

4. RENOVATE CONFERENCE ROOM B132.

1. TEMPORARY WALL. SEE ICRA TYPE SHEETS GI403 AND GI404 FOR NOTES AND

DETAILS. COORDINATE WITH VA COR FOR FINAL REQUIREMENTS.

1A. TEMPORARY WALL TO BE CONSTRUCTED TOWARD END OF CONSTRUCTION FOR

INSTALLATION OF NEW DOOR AND WALL. SEE ICRA TYPE SHEETS GI403 AND

GI404 FOR NOTES AND DETAILS. COORDINATE WITH VA COR FOR FINAL

REQUIREMENTS.

1B. INFECTION CONTROL WALL TO BE CONSTRUCTED AS PERMANENT BARRIER

WALL.

2. TEMPORARY 42 INCH CONSTRUCTION DOOR WITH SELF CLOSING DEVICES WITH

RATED STOREROOM FUNCTION DOOR HARDWARE. GENERAL CONTRACTOR TO

PROVIDE CONSTRUCTION DOORS FOR THE PROJECT. SEE SPECIFICATION

SECTION 01 35 26, CH. 1.12 FOR BARRIER AND INFECTION CONTROL

PROCEDURES.

3. EXISTING DOORS TO REMAIN DURING CONSTRUCTION. TOWARD END OF PHASE,

BUILD TEMPORARY WALLS FOR CONSTRUCTION OF NEW WALL AND DOORS.

4. SINGLE LEAF OF PAIR OF DOORS TO BE RENDERED INOPERABLE DURING PHASE

1A CONSTRUCTION. ALLOW FOR INSTALLATION OF TEMPORARY WALL.

5. PROVIDE TEMPORARY DOOR FRAME, DOOR AND HARDWARE FOR ACCESS TO

OFFICE DURING PHASE 2 CONSTRUCTION. UPON COMPLETION OF WORK, INFILL

WALL TO MATCH EXISTING CONSTRUCTION AND FINIISH.

6. PROVIDE STICKY WALK-OFF MATS ON EACH SIDE OF DOOR, SIZED TO DOOR

OPENING. CHANGE MATS AS REQUIRED.

7. FULLY SEAL WINDOWS/ DOORS WITH 6 MIL HEAVY DUTY, REINFORCED,

FIRE-RETARDANT, POLY SHEETING (VISQUEEN). PLASTIC SHEET SHALL BE

FULLY SEALED AT PERIMETER .

8. FLOOR SLAB SHALL BE CUT AS REQUIRED FOR INSTALLATION OF GAS, WATER

AND STEAM PIPING. WORK WILL BE REQUIRED TO OCCUR AFTER HOURS. FOR

MULTIPLE SHIFT WORK, INSTALL STEEL PLATE OVER OPENINGS SO THAT

KITCHEN STAFF CAN CONTINUE WORK FOLLOWING DAY. EQUIPMENT ON EAST

WALL SHALL BE MOVED DURING AFTER HOURS WORK AND RETURNED IN PLACE

PRIOR TO START OF KITCHEN STAFF WORK DAY. REFER TO PLUMBING AND

MECHANICAL DRAWINGS FOR ADDITIONAL INFORMATION.

9. EXISTING SANITARY PIPING TO SINKS SHALL BE REROUTED TO TEMPORARY

SANITARY THROUGH WALL. REFER TO PLUMBING DRAWINGS FOR ADDITIONAL

INFORMATION.

10. WATER PIPING TO BE INSTALLED AFTER HOURS. REFER TO PLUMBING

DRAWINGS. REPLACE DAMAGED CEILING TILE AS REQUIRED.

11. DUCTWORK IN ROOM B122 TO BE DISCONNECTED. PORTABLE COOLING UNIT TO

BE PROVIDED DURING CONSTRUCTION. REFER TO MECHANICAL DRAWINGS.

WORK TO BE COMPLETED AFTER HOURS.

12. EXISTING ELECTRICAL PANEL LOCATED ON EAST WALL OF ROOM B122 TO BE

REMOVED AFTER INSTALLATION OF TEMPORARY ELECTRICAL PANEL IS PLACED

ON WEST WALL. RETHERM UNITS TO BE CONNECTED TO TEMPORARY PANEL.

REFER TO ELECTRICAL DRAWIINGS. WORK TO BE COMPLETED AFTER HOURS.

13. REMOVE EXISTING GATE AS PART OF PHASE 2A.

14. EXISTING DUCTWORK TO BE REPLACED DURING PHASE 2A. WORK TO BE

COMPLETED AFTER HOURS.

15. EXHAUST DUCT TO BE REROUTED DURING PHASE 1 AFTER HOURS. REFER TO

MECHANICAL DRAWINGS FOR ADDITIONAL INIFORMATION.

16. TEMPORARY WALL PARTITION TO BE INSTALLED PRIOR TO AFTER HOURS WORK

AND TO BE REMOVED FOLLOWING AFTER HOURS WORK. IN ADDITION, PROVIDE

PLASTIC SHEETING ON KITCHEN SIDE, FULLY SEALED AT PERIMETERS.

SCOPE OF WORK:

MOVE DISHWASHING OPERATIONS, COLD FOOD STORAGE AND PARTIAL NFS

OFFICES INTO RENOVATED SPACES FROM EXPEDITED PHASE 1A.

RENOVATED PHASE 2 TO INCLUDE DIET COMMUNICATIONS OFFICES, TOILET

ROOMS, SECRETARY, STAFF LOUNGE, KITCHEN COOK/ PREP AND

TEMPORARY TRAY ASSEMBLY.

CONSTRUCTION OF PHASE 2 SHALL BEGIN UPON COMPLETION OF PHASE 1C

WORK.

PERFORM ASBESTOS ABATEMENT FOR WORK AREAS IN THIS PHASE. REFER

TO HAZARDOUS MATERIALS DRAWINGS AND REPORT (IN SPECIFICAITONS

MANUAL) FOR EXTENT OF ACM ABATEMENT.

PHASE 2A:

1. EXISTING STEAM LINES TO BE DEMOLISHED, AND NEW STEAM LINES

TO BE INSTALLED PRIOR TO START UP OF DISHWASHING/ CART

WASHING EQUIPMENT.

2. EXISTING DISHWASHER TO BE REMOVED UPON START UP OF NEW

DISHWASHING EQUIPMENT.

3. MOVE DISHWASHING OPERATIONS INTO NEW SPACE.

4. MOVE COLD FOOD STORAGE INTO NEW COOLERS/FREEZERS.

5. MOVE PARTIAL NFS OFFICES INTO NEW OFFICES IN PHASE 1A.

6. DEMOLISH EXISTING PREP/ COOK, DISHWASHING.

7. TEMPORARY TRAY ASSEMBLY SHALL BE LOCATED IN VACATED FOOD

STORAGE AND OFFICES.

8. KEEP PASSAGE AVAILABLE FROM DISHWASHING CORRIDOR TO

TEMPORARY TRAY ASSEMBLY.

PHASE 2B:

1. UPON COMPLETION OF PHASE 2A, TOILET ROOMS AND CORRIDOR TO

BE COMPLETED.

A. CONTRACTOR SHALL BE RESPONSIBLE FOR SEQUENCING AND COORDINATION

OF CONSTRUCTION PHASING WITH THE VA'S SCHEDULE, INFECTION CONTROL,

AND INTERIM LIFE SAFETY REQUIREMENTS.

B. CONTRACTOR SHALL PROVIDE ALL SUB-PHASING ACTIVITIES AS REQUIRED FOR

WORK OCCURING BETWEEN VARIOUS PHASES.

C. THE PHASING PLAN IS SUBJECT TO THE CONTRACTORS MEANS AND METHODS,

SCHEDULING AND TO EXISTING CONDITIONS AND TIME RESTRAINTS.

D. CONTRACTOR SHALL REFER TO ALL DEMOLITION AND CONSTRUCTION

DRAWINGS FOR A COMPLETE UNDERSTANDING OF THE SPECIFIED SCOPE OF

WORK.

E. CONTRACTOR SHALL MAINTAIN EGRESS PASSAGE WAYS MAIN CORRIDOR,

ELEVATOR LOBBY AND STAIR EXITS DURING COMPLETE PROJECT DURATION.

ALSO MAINTAIN ALL EGRESS/EXIT DOORS OF THE FACILITY.

F. CONTRACTOR SHALL REFER TO DRAWING GI403 AND GI404 FOR INFECTION

CONTROL NOTES AND SUGGESTED LOCATION OF CONSTRUCTION BARRIERS

AND ENTRANCES. ICRA BARRIERS TO BE LOCATED AS REQUIRED FOR EACH

PHASE OF CONSTRUCTION. COORDINATE WITH VA COR.

G. CONTRACTOR SHALL NOTE ALL EXISTING PLUMBING, MECHANICAL AND

ELECRICAL SERVICES AND SYSTEMS THAT ARE SCHEDULED TO REMAIN FULLY

OPERATIONAL AND FUNCTIONAL FOR DURACTION OF SPECIFIC PHASES.

H. CONTRACTOR SHALL NOTE THAT BUILDING NO. 1 SHALL BE OCCUPIED DURING

CONSTRUCTION.

I. HOURS OF OPERATION FOR NOISE AND VIBRATION OPERATIONS ARE DURING

OFF NORMAL HOSPITAL OPERATION HOURS (6:00 PM TO 6:00 AM). SERVICE

INTERRUPTIONS DURING OFF NORMAL WORK HOURS AND SCHEDULED MINIMUM

(2) WEEK ADVANCED NOTICE.

J. WHERE TWO OR MORE SEQUENCES MEET IT IS THE RESPONSIBILITY OF THE

CONTRACTOR TO COORDINATE THE TRANSITION WORK BETWEEN PHASES.

K. CONTRACTOR TO HAVE ALL MATERIALS AND EQUIPMENT ON SITE FOR THE

COMPLETION OF ANY WORK THAT IS DESIGNATED FOR OFF HOURS PRIOR TO

THE START OF OFF HOURS WORK.

L. PHASES TO BE PERFORMED IN SEQUENCE.

M. NUTRITION AND FOOD SERVICES AFTER HOURS:

EVERY DAY INCLUDING WEEKENDS: 8:00 P.M. TO 4:00 A.M.

EXISTING KITCHEN SHALL REMAIN OPERATIONAL AND UNINTERRUPTED

DURING CONSTRUCTION. WORK REQUIRED TO BE PERFORMED AFTER HOURS

SHALL BE CLEANED UP AND LEFT IN CONDITION WHERE NORMAL KITCHEN

OPERATIONS CAN BE CONTINUED AT THE START OF THE FOLLOWING DAY.

N. PHYSICAL THERAPY AND EYE CLINICS AFTER HOURS:

WEEKDAYS: 5:00 P.M. TO 6:30 A.M.

WEEKENDS: ALL DAY

EXISTING CLINICS SHALL REMAIN OPERATIONAL AND UNINTERRUPTED DURING

CONSTRUCTION. WORK REQUIRED TO BE PERFORMED AFTER HOURS SHALL BE

CLEANED UP AND LEFT IN CONDITION WHERE NORMAL CLINIC OPERATIONS CAN

BE CONTINUED AT THE START OF THE FOLLOWING DAY.

PHASED AREA OF WORK

(SHADES VARY FOR CLARITY)

CONSTRUCTION ROUTING

PHASE 1C: DEMOLISH EXISTING SITE AREA IN SCOPE OF WORK AND BEGIN

CONSTRUTION ON ADDITION. NEW ADDITION WILL BECOME KITCHEN PREP,

COOKING AND DRY FOOD STORAGE.

1. PROVIDE ADDITIONAL TEMPORARY COLD FOOD STORAGE TO BE

LOCATED AT THE SOUTH LOADING DOCK. COORDINATE EXACT

LOCATION WITH VA COR.

2. COOK/ PREP AREAS TO BE COMPLETED BEFORE DEMOLITION BEGINS

IN PHASE 2.

3. GREASE BASIN AND ASSOCIATED PIPING TO BE INSTALLED PRIOR TO

REMOVAL OF EXISTING GREASE BASIN.

PHASE 2B

NOTE:

PRIOR TO START OF PHASE 2, STEAM

LINES FOR DISHWASHING AND CART

WASHING EQUIPMENT TO BE INSTALLED

AND CONNECTED. EQUIPMENT MUST

FULLY OPERATIONAL BEFORE EXISTING

DISHWASHING EQUIPMENT IS REMOVED.

Drawing Number

Project Title

Location

Issue Date Checked Drawn

CONSTRUCTION DOCUMENTS-

ISSUE FOR BID

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

Phase

STAMP NUTRITION & FOOD SERVICE

AND

EYE/ PT CLINIC ADDITION

1 MEDICAL CENTER DRIVE, CLARKSBURG, WV 26301

540-370

10-21-202225% DD1 SUBMISSION 06-14-21

50% DD2 SUBMISSION 08-23-21

75% CD1 SUBMISSION 11-01-21

www. bancroft-ae.com

BAE PROJECT NO. 20-109

3300 Dundee Rd.

Northbrook, IL 60062

T: 847.952.9362

VA CONTRACT NO. 36C24521C0034

75% CD1 SUBMISSION (RESUBMITTAL) 01-11-22

100% CD 2 SUBMISSION 07-29-22

100% CD 2 SUBMISSION (RESUBMITTAL) 09-23-22

CONSTRUCTION DOCUMENTS- ISSUED FOR BID 10-21-22

SCOPE OF WORK:

CONSTRUCTION OF NEW ADDITION AND PROVIDE NEW SECONDARY EXIT

FROM NEW ADDITION.

PERFORM ASBESTOS ABATEMENT FOR WORK AREAS IN THIS PHASE. REFER

TO HAZARDOUS MATERIALS DRAWINGS AND REPORT (IN SPECIFICATIONS

MANUAL) FOR EXTENT OF ACM ABATEMENT.

1. REMOVE EXISTING WINDOWS IN NORTH WING ADJACENT TO NEW

BUIDLING ADDITION. INFILL WALL OPENINGS.

2. PROVIDE NEW OPENING IN EXISTING WALL FOR SECONDARY EXIT TO

EXISTING STAIR.

3. MECHANICAL CHILLED WATER PIPING TO BE CONNECTED TO NEW

ADDITION.

SCOPE OF WORK:

COMPLETE CONSTRUCTION IN CORRIDOR. WORK SHALL BE DONE AFTER

HOURS.

1. FINISH FLOORING TO BE INSTALLED IN CORRIDOR.

2. PATCH FLOORIING IN EYE CLINIC WAITING ROOM TO MATCH EXISTING.

1. TEMPORARY WALL. SEE ICRA TYPE SHEETS GI403 AND GI404 FOR

NOTES AND DETAILS. COORDINATE WITH VA COR FOR FINAL

REQUIREMENTS.

1A. TEMPORARY WALL . WALL CAN BE USED AS PERMANENT WALL.

PATCH, SAND, PAINT WALL TO MATCH FINAL FINISHES.

1B. PORTION OF TEMPORARY WALL CAN BE USED AS PERMANENT WALL.

PATCH, SAND, PAINT WALL TO MATCH FINAL FINISHES. REFER TO

NEW PLANS FOR PERMANENT WALLS.

2. TEMPORARY 42 INCH CONSTRUCTION DOOR WITH SELF CLOSING

DEVICES WITH RATED STOREROOM FUNCTION DOOR HARDWARE.

GENERAL CONTRACTOR TO PROVIDE CONSTRUCTION DOORS FOR

THE PROJECT. SEE SPECIFICATION SECTION 01 35 26, CH. 1.12 FOR

BARRIER AND INFECTION CONTROL PROCEDURES.

3. EXISTING EMERGENCY EXIT TO REMAIN ACCESSIBLE DURING

CONSTRUCTION.

4. EXISTING WINDOW TO BE REMOVED. EXISTING PORTION OF WALL TO

BE REMOVED FOR NEW…

This is the start of the file's text. The full file is on GovTribe.