Attachment 6- Asbestos Reports - Wilkes-Barre.pdf

PDF 3 MB Posted

Attached to
Z2DA--Expand Mental Health Clinic Construction Wilkes Barre (VA-24-00034565)
Solicitation number
36C77624R0079_1
Issued by

About this file

This document contains the asbestos survey findings for the 1st and 2nd floors of the main building at the VA Medical Center in Wilkes-Barre, PA. The survey identified the presence of asbestos-containing materials (ACMs) in various building components such as floor tiles, floor tile mastics, pipe insulation, transite panels, and duct insulation. The report provides detailed information on the location, condition, quantity, and asbestos content of the identified ACMs. This information would be important for planning any renovation or demolition activities at the facility to ensure proper handling and disposal of the ACMs.

The related federal contract opportunity is for a project to expand the mental health clinic at the Wilkes-Barre VA Medical Center. The solicitation is a competitive Service-Disabled Veteran-Owned Small Business (SDVOSB) set-aside. The contractor will be required to provide all labor, project management, materials, tools, supplies, and equipment necessary to complete the work as detailed in the drawings and specifications. The project location is the Wilkes-Barre VA Medical Center at 1111 East End Blvd, Wilkes-Barre, PA 18711.

View the file

Other files

File Type Posted
Amendment 0003 36C77624R0079.pdf PDF
Amendment 0002 Attachment 1 Additional RFIs 7 9 24.docx DOCX document
Amendment 0002 36C77624R0079.pdf PDF
Amendment 0002 Attachment 2 6007 Wilkes-Barre Geotechnical Report.pdf PDF
Amendment 0001 Attachment 3 -VA Signage Design Manual.pdf PDF
Amendment 0001 36C77624R0079.pdf PDF
Amendment 0001 Attachment 1 RFIs - Expand Mental Health Wilkes-Barre Final.docx DOCX document
Amendment 0001 Attachment 4 - Const Wage Determination Luzern 6.28.24.pdf PDF
Amendment 0001 Attachment 5 -Site Visit SIgn In Sheet.pdf PDF
Amendment 0001 Attachment 2 -Adendum 01.zip ZIP file
Attachment 9 -Site Visit Instructions Wilkes-Barre.docx DOCX document
36C77624R0079_1.pdf PDF
Attachment 11- Site Map.pdf PDF
Attachment 3- Drawings - EMHC - Part 2 of 4.pdf PDF
Attachment 12 - Limitations on Subcontracting - Construction.docx DOCX document
Attachment 2- Drawings - EMHC - Part 1 of 4.pdf PDF
Attachment 7- Construction Wage Determination 5.31.pdf PDF
Attachment 1- Specs - EMHC.pdf PDF
Attachment 4- Drawings - EMHC - Part 3 of 4.pdf PDF
Attachment 9 -Site Visit Instructions Wilkes-Barre.docx DOCX document
Attachment 5- Drawings - EMHC - Part 4 of 4.pdf PDF
Attachment 8- Service Wage Determination.pdf PDF
Attachment 10- Brand Name_Redacted.pdf PDF
Show all 23

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Building 1, Floor I - Specific Survey Findings Project No. VAMC: 10013.00-IN

VA Medical Center, Main Building, 1 st

Floor Adelaide Environmental Health Services, Inc. – Project No. VAMC:10013.00-IN

1511 Route 22, Suite C24, Brewster, NY 10509 Phone: 845.278.7710 Fax: 845.278.7750

Adelaide Environmental Health Associates, Inc.

Project: Main Building, 1 st

Floor Inspector(s): James Reber

VA Medical Center Thomas Ferro Wilkes-Barre, PA 18711 Date(s): 2/2010-3/2010

LOCATION MATERIAL QUANTITY CONDITION SAMPLE #

HOMOGENEOUS

WITH SAMPLE #

ASBESTOS CONTENT

st

Floor, W wing, room C1-01

Floor Rug over red brown 9” X9” floor tile 280 ft2 N/A 4/12-03 N/A 15% Chrysotile

Walls Sheetrock/plaster N/A N/A N/A N/A Non-suspect

Ceilings 2’ X 4’ ceiling tile N/A N/A N/A N/A Non-suspect

Univents Transite panels 32-64ft2 Damaged Assumed

1st Floor, W wing, room C1-02 (suite)

Floor Rug over floor tile 360 ft2 N/A 4/12-01 N/A 3% Chrysotile Mastic 360 ft2 N/A 4/12-02 N/A 10% Chrysotile

Walls Sheetrock/plaster N/A N/A N/A N/A Non-suspect

Ceilings 2’ X 4’ ceiling tiles N/A N/A N/A V Non-suspect

Plaster N/A N/A N/A N/A Non-suspect

1st Floor, room C1-03

Floor Rug over floor tile N/A N/A N/A N/A Non-suspect

12” X 12” floor tile 160 ft2 N/A N/A Prev. tested pos. >1%

Floor tile mastic 160 ft2 N/A N/A Prev. tested pos. >1%

SOL# 36C77624R0079 Project # 693-352 Expand Mental Health Clinic Construction- Wilkes-Barre, PA

VA Medical Center, Main Building, 1 st Floor

Adelaide Environmental Health Services, Inc. – Project No. VAMC:10013.00-IN

Adelaide

Walls Plaster/sheetrock N/A N/A N/A N/A Non-suspect

Ceilings 2’ X 4’ ceiling tile N/A N/A N/A N/A Non-suspect

12” X 12” ceiling tiles (above 2’ X 4’)

160 ft2 N/A N/A 1-195 None detected

Univents Transite panels 20-40 ft2 Damaged N/A N/A Assumed

1st Floor, room C-1-03A

Floor Rug over tile N/A N/A N/A N/A Non-suspect

12” x 12” floor tile and mastic 200 ft2 N/A N/A Previously tested positive >1%

12” X 12” ceiling tiles (off white w/ grainy surface) – above 2’ X 4’

N/A N/A 1-195 N/A None detected

Univents Transite panels 20-40 ft2 Damaged N/A N/A Assumed

1st Floor, W wing, room C1-05 (suite) – 05 , 06, 07, 08, 09, 10, 11, 12, 13

Floor Rug over concrete or platform N/A N/A N/A N/A Non-suspect

Walls Sheetrock N/A N/A N/A N/A Non-suspect

Ceilings 2’ X4’ ceiling tile N/A N/A N/A N/A Non-suspect

12” X 12” ceiling tiles ( white w/rows of holes) – above 2’ X 4’

N/A N/A N/A 1-187 None detected

Univents Transite panels (one front panel missing)

100-200 ft2 Damaged N/A N/A Assumed

Over ceiling, far S wall

Duct insulation (black mastic over cork)

Not found N/A N/A 6-96 Not found

Chases + over ceiling in room next to ladies room

Pipe insulation (C1-11) 12 LF Good N/A N/A Assumed

SOL# 36C77624R0079 Project # 693-352 Expand Mental Health Clinic Construction- Wilkes-Barre, PA

Floor

1st Floor, W wing, ladies’ (C1-14) and men’s (C1-15) rooms across from C1-05

In wall between mens/ladies rooms

Pipe insulation 5 LF Good N/A N/A Assumed

1st Floor, W wing, electrical closet (E of stair #1)

Pipe riser Pipe insulation (black mastic over cork)

10 LF Good N/A 6-96 8% Chrysotile

1st Floor, room C1-18

Floor 12” X 12” floor tile (light gray w/white dark gray mottles)

100 ft2 N/A N/A 6-105 None detected

Floor tile mastic 100 ft2 N/A N/A 6-106 5% Chrysotile

Ceilings 2’ X 2’ ceiling tiles N/A N/A N/A N/A Non-suspect

Univents Transite panels 24-48 ft2 Damaged N/A N/A Assumed

1st Floor, room C1-19

Floor Rug over leveling compound over black mastic Removed

N/A N/A N/A N/A N/A

Black mastic Removed 150 ft2 N/A N/A N/A N/A

Walls Plaster/sheetrock N/A N/A N/A N/A Non-suspect

Univents Transite panels 8-16 ft2 Damaged N/A N/A Assumed

1st Floor, rooms C1-21B and C1-21C and C1-20

Floor Rug over floor tile - Removed N/A N/A N/A N/A N/A

12” X 12” floor tile - Removed 150 ft2 N/A N/A N/A N/A

Walls Plaster/ sheetrock N/A N/A N/A N/A Non-suspect

Ceilings 2’ X 4’ ceiling tiles N/A N/A N/A N/A Non-suspect

Univents Transite panels 16-32 ft2 Damaged N/A N/A Assumed

Floor

1st Floor, W wing, room C1-21A - Removed and is part of C1-22A now

Floor 12” X 12” floor tile (white w/olive mottles) - Removed

525 ft2 N/A N/A N/A

Floor tile mastic - Removed 525ft2 N/A N/A N/A

Walls Sheetrock N/A N/A N/A N/A Non-suspect

Ceilings 2’ X 4’ ceiling tiles N/A N/A N/A N/A Non-suspect

1st Floor, room C1-22A (and also C1-21B and C1-21C)

Floor (raised floor;

tiles not found underneath)

12” X 12” floor tile (off-white w/tan & brown streaks) - Removed

N/A N/A N/A 6-103 5% Chrysotile

Floor tile mastic - Removed N/A N/A N/A 6-104 5% Chrysotile

Walls Sheetrock N/A N/A N/A Previously tested positive >1%

Ceilings 2’ X 4’ ceiling tiles - removed N/A N/A N/A Previously tested positive >1%

1st Floor, room C1-22

Floor 12” X 12” floor tile (white w/brown streaks) –E room (C1-22D

150 ft2 N/A N/A 6-103 5% Chrysotile

Floor tile mastic 150 ft2 N/A N/A 6-104 5% Chrysotile

12” x 12” floor tile (off white w/tan marks) –W room

150 ft2 N/A N/A 3-165 None detected

Floor tile mastic- W room 150 ft2 N/A N/A 3-166 5% Chrysotile

Ceilings 2’ X 4’ ceiling tiles N/A N/A N/A N/A Non-suspect

C1-22E has pipe insulation – 8 LF, good. Same floor tiles as C1-22 – 484 ft2. Has suspect drywall on S wall - 30ft2, damaged

Floor

1st Floor, mechanical room behind C1-22 (on drawings as C1-22C)

12” X 12” floor tile (off-white w/tan marks)

400 ft2 N/A N/A 3-165 None-detected

Floor tile mastic 400 ft2 N/A N/A 3-166 5% Chrysotile

1st Floor, room C1-23

Floor Rug N/A N/A N/A N/A Non-suspect

12” X12’ floor tile 400 ft2 N/A N/A N/A Assumed

Floor tile mastic 400 ft2 N/A N/A N/A Assumed

Walls Plaster/sheetrock N/A N/A N/A N/A Non-suspect

Ceilings 2’ X 4’ ceiling tile N/A N/A N/A N/A Non-suspect

Above ceiling tiles & plaster

Pipe insulation 10 LF Damaged N/A N/A Assumed

1st Floor, room C1-24 and C1-27 (Armory)

Floor 12” X 12” floor tile (off white w/tan & dark tan mottles)

N/A N/A N/A Non-suspect

Floor tile mastic N/A N/A N/A Non-suspect

Walls Plaster/sheetrock N/A N/A N/A N/A Non-suspect

Ceilings 2’ X 4’ ceiling tiles (worm markings) N/A N/A N/A N/A Non-suspect

Univents Transite panels ( front panels removed)

24-48 ft2 Damaged N/A N/A Assumed

Chases Pipe insulation N/A N/A N/A N/A Assumed

Floor

1st Floor, room C1-28

Floor Rug over concrete N/A N/A N/A N/A Non-suspect

12” x !2” floor tile and mastic - Removed

200 ft2 N/A N/A N/A Assumed

Walls Plaster/sheetrock N/A N/A N/A N/A Non-suspect

Ceilings 2’ X 4’ ceiling tile (off white w/random pock markings)

200 ft2 N/A N/A N/A Non-suspect

Univents Transite panels 24-48 ft2 Damaged N/A N/A Assumed

1st Floor, Room C1-32

Floor Rug over concrete N/A N/A N/A N/A Non-suspect

Walls Sheetrock N/A N/A N/A N/A Non-suspect

Ceilings 2’ X 2’ ceiling tile- new V V V V Non-suspect

Chases Pipe insulation – no view in chases indeterminate N/A N/A N/A Assumed

Univents Transite panels 16-32 ft2 Damaged N/A N/A Assumed

1st Floor, rooms C1-32-A and C1-32B – No suspect materials observed

Floor

1st Floor, E wing, room C1-30

Floor 9” X 9” floor tile (brown) 25 ft2 Good N/A N/A Assumed

Floor tile mastic 25 ft2 N/A N/A N/A Assumed

Walls Plaster/sheetrock N/A N/A N/A N/A Non-suspect

1st Floor, E wing, room C1-35A

Pipes Pipe insulation (black mastic over cork)

12 LF N/A N/A 6-96 8% Chrysotile

1st Floor, rooms C1-36 and C1-37

Ceilings 12” X 12” ceiling tiles (white, perforated)

20-30 ft2 N/A 1-187 N/A None detected

2’ X 2’ ceiling tiles N/A N/A N/A N/A Non-suspect

Ceiling tile mastic 20-30 ft2 N/A 1-188 N/A None detected

Univents Transite panels 32-64 ft2 Damaged N/A N/A Assumed

1st Floor, E wing, room C1-36A

S wall Pipe insulation 30 LF Significant damage

N/A N/A Assumed

Univents Transite panels 8-16 ft2 Damaged N/A N/A Assumed

Comments: Behind the plaster fascia, there is a pipe chase which runs E to W on the S wall. Suspect pipe insulation may exist within the chase, and this situation may exist in all rooms within this area

1st Floor, room C1-38

Floor Rug over concrete N/A N/A N/A N/A Non-suspect

Walls Sheetrock N/A N/A N/A N/A Non-suspect

Ceilings 2’ X 2’ ceiling tiles- new and 12” X 12”

N/A N/A N/A N/A Non-suspect

Univents Transite panels 40 – 80 ft2 Damaged N/A N/A Assumed

Floor

1st Floor, E wing, rooms C1-43,C1-44, C1-45, C1-51, C1-52, 56A – No exposed suspect asbestos materials observed

1st Floor, E wing, rooms C1-39, C1-40, C1-41, & C1-42

Univents Transite panels 50 ft Damaged N/A N/A Assumed

Comments: Except for C1-42, the front transite panels have been removed. The rear could not be observed at the time of this inspection and could be present.

1st Floor, room C1-53

Pipe in SW corner Pipe insulation in chase- can’t see condition

N/A N/A N/A N/A Assumed

1st Floor, room C1-54

Floor Rug over concrete N/A N/A N/A N/A Non-suspect

Walls Plaster/sheetrock N/A N/A N/A N/A Non-suspect

Ceilings 2’ X 4’ ceiling tile N/A N/A N/A N/A Non-suspect

Above ceiling tiles Pipe insulation (SE corner) 5 LF Good N/A N/A Assumed

Univents Transite panels 16-32 ft2 Damaged N/A N/A Assumed

1st Floor, room C1-56-B, C1-56C (Corridors)

Floors 12” X12” floor tile Terrazzo N/A N/A N/A N/A Non-suspect

Floor tile mastic N/A N/A N/A N/A N/A

Walls Plaster/ N/A N/A N/A N/A Non-suspect

Ceilings 2’ x 4’ ceiling tile over fireproofing N/A N/A N/A N/A Non-suspect

Floor

1st Floor, C1-56

12” X 12” floor tile (brown w/ white, gray and dark brown marble effect)

480 ft2 N/A N/A 1-01 None detected

Floor tile mastic 480 ft2 N/A N/A 1-02 3% Chrysotile

Walls Plaster/sheetrock N/A N/A N/A N/A Non-suspect

Ceilings 2’ X 4’ ceiling tiles (concrete deck) N/A N/A N/A N/A Non-suspect

Above ceiling Pipe insulation (runs down into SW wall)

15-20 LF

Significant damage

N/A N/A Assumed

Univents Transite panels 32-64 ft2 Damaged N/A N/A Assumed

1st Floor, room C1-55

Floor Rug over floor tile N/A N/A N/A N/A Non-suspect

12 X 12” floor tile 160 ft2 N/A N/A N/A Assumed

Floor tile mastic 160 ft2 N/A N/A N/A Assumed

Walls Plaster/sheetrock N/A N/A N/A N/A Non-suspect

Ceilings 12” X 12” ceiling tile N/A N/A N/A N/A Non-suspect

Univents Transite panels 16-32 ft2 Damaged N/A N/A Assumed

1st Floor, smoking area NOT FOUND – Non-existing

Floor 12” X 12” floor tile (off-white w/ tan & dark tan mottles)

625 ft2 N/A 8-281 N/A None detected

Floor tile mastic 625 ft2 N/A 8-282 N/A <1% Chrysotile

Walls Plaster N/A N/A N/A N/A Non-suspect

Ceilings 12” X 12” ceiling tile N/A N/A 8-283 N/A None detected

Floor

1st Floor, room C1-59

12” X 12” floor tile (off-white w/gray mottles) and mastic

115 ft2 N/A N/A Previously tested positive >1%

Walls Plaster/sheetrock N/A N/A N/A N/A Non-suspect

Ceilings 2’ X 4’ ceiling tile N/A N/A N/A N/A Non-suspect

Above & behind plaster

Pipe insulation 20-30 LF N/A N/A v N/A Assumed

1st Floor, ladies room (C1-60) & men’s room (C1-61) plus C1-58 (vestibule)

Above ceiling and in walls where it was partially removed and replaced w/ fiberglass

Pipe insulation N/A Damaged N/A N/A Assumed

Comment: C1-58 vestibule – 18 LF of pipe (aircell). Nothing above men’s room/no access to ladies room ceiling

1st Floor, room C1-62

Floor Ceramic Tile N/A N/A N/A N/A Non-suspect

Walls Tile N/A N/A N/A N/A Non-suspect

Ceilings 2’ X 4’ ceiling tile N/A N/A N/A N/A Non-suspect

1st Floor, room C1-63

Floor Rug over concrete N/A N/A N/A N/A Non-suspect

Walls Tile N/A N/A N/A N/A Non-suspect

Floor

1st Floor, C1-64

Walls Plaster/sheetrock N/A N/A N/A N/A Non-suspect

Ceilings 2’ X 4’ ceiling tile (white w/ striations)

N/A N/A N/A N/A Non-suspect

1st Floor, room C1-65, C1-66, C1-67, C1-68

Floor Rug over concrete N/A N/A N/A N/A Non-suspect

Walls Plaster/sheetrock N/A N/A N/A N/A Non-suspect

Ceilings 2’ X 4’ ceiling tile N/A N/A N/A Previously tested Non-suspect

Comments: In rooms C1-63 through C1-68, suspect asbestos insulation possible on pipes above plaster ceiling

1st Floor, W wing, room C1-70

Floor Rug over 12” X 12” floor tiles/mastic

185 ft2 N/A N/A N/A Assume

Walls Plaster/sheetrock N/A N/A N/A` N/A Non-suspect

Ceilings 2’ X 4’ ceiling tile N/A N/A N/A N/A Non-suspect

1st Floor, room C1-71 and C1-70-A

Floor Rug over brown 9X9 floor tile and mastic

360 ft2 N/A N/A N/A Assumed

12” X 12” ceiling tile (white w/rows of holes) – above 2’ X 4’

160 ft2 N/A N/A 1-187 None detected

Floor

1st Floor, W wing, room C1-72

Rug over leveling compound and brown 9X9 floor tile and mastic

180 ft2 N/A N/A N/A Assumed

Walls Plaster N/A N/A N/A N/A Non-suspect

Sheetrock joint material N/A N/A 1-196 N/A None detected

Ceilings 2’ X 4’ ceiling tiles N/A N/A N/A N/A Non-suspect

12” X 12” ceiling tiles (off-white w/ holes) – above 2’ X 4’

150 ft2 N/A N/A 1-187 None detected

1st Floor, W wing, rooms C1-74a, C1-74, & C1-73

Floor Rug over brown 9X9 floor tile and mastic

450 ft2 Good N/A N/A Assumed

Ceilings 2’ X 4’ Ceiling tile N/A N/A N/A N/A Non-suspect

12” X 12” ceiling tiles (white w/rows of holes) – above 2’X4’

380 ft2 N/A N/A 1-187 None detected

Comments: No access under rug at the time of this inspection –possible floor tile and mastic materials under rug. Checked - Floor tile found

1st Floor, room C1-76

Pipes Pipe / fitting insulation 4-6 LF N/A N/A N/A Assumed

1st Floor, room C1-77

Floor 9” X 9” floor tile (white w/ black flecks)

110 ft2 N/A N/A N/A Assumed

Walls Plaster/sheetrock N/A N/A N/A N/A Non-suspect

Floor

1st Floor, hall by main elevator

Floor Terrazzo tile N/A N/A N/A N/A Non-suspect

Walls Marble N/A N/A N/A N/A Non-suspect

Ceilings 2’ X 2’ ceiling tile N/A N/A N/A N/A Non-suspect

1st Floor, main hall (mental health to Chapel Hall) (C1-18)

Floor 12” X 12” floor tile (tan w/ white/dark tan mottles)

2696 ft2 N/A N/A 8-039 None detected

Floor tile mastic 2696 ft2 N/A N/A 8-040 2% Chrysotile

1st Floor, security locker room by stair # 3 (C1-78)

Floor

12” X 12” floor tile (chocolate w/ white/brown marble effect)

40 ft2 N/A N/A 7-86 None detected

Floor tile mastic

40 ft2 N/A N/A 7-87 5% Chrysotile

Walls Plaster N/A N/A N/A N/A Non-suspect

Ceilings Ceiling tile N/A N/A N/A N/A Non-suspect

Univents Transite panels 4 ft2 Damaged N/A N/A Assumed

1st Floor, N wing, N1-71 ( Not on plans or in field)

Floor Rug over leveling compound N/A N/A N/A N/A Non-suspect

Walls Plaster/carpeted panels N/A N/A N/A N/A Non-suspect

Ceilings 2’ X 4’ ceiling tile N/A N/A N/A N/A Non-suspect

Above ceiling tile Pipe insulation 8 LF Damaged N/A N/A Assumed

Univents Transite Panels 16-32 ft2 Damaged N/A N/A Assumed

Floor

1st Floor, N wing, room N1-80

12” X 12” floor tile ( off-white w/ light & dark olive mottles)

216 ft2 N/A N/A 1-286 5% Chrysotile

Floor tile mastic 216 ft2 N/A N/A 1-287 3% Chrysotile

Walls Plaster/sheetrock N/A N/A N/A N/A Non-suspect

Ceilings 2’ X 4’ ceiling tile N/A N/A N/A N/A Non-suspect

1st Floor, N wing, room N1-81 ( room N of N1-80)

Floor Rug over floor tile N/A N/A N/A N/A Non-suspect

12” X 12” floor tile (off-white w. light & dark olive mottles)

300 ft2 N/A N/A 1-286 5% Chrysotile

Floor tile mastic 300 ft2 N/A N/A 1-287 3% Chrysotile

Walls Plaster/Sheetrock N/A N/A N/A V Non-suspect

Ceilings 2’ X 4’ ceiling tile N/A N/A N/A N/A Non-suspect

Above ceiling tiles & above E wall & duct

Pipe insulation < 25 LF FN/A N/A N/A Assumed

1st Floor, N wing, room N1-86D

Floor Rug over tile N/A N/A N/A N/A Non- suspect

12” X 12” floor tile ( white w/ black streaks

560 ft 2 N/A N/A 8-028 10 % Chrysotile

Floor tile mastic 560 ft 2 N/A V 8-029 5% Chrysotile

Walls Plaster/ sheetrock N/A N/A N/A N/A Non- suspect

Ceilings 2’ X 4’ ceiling tile N/A N/A N/A N/A Non- suspect

Above ceiling tile Pipe insulation 20-25 LF Damaged N/A N/A Assumed

Univents Transite panels 64-128 ft2 Damaged N/A N/A Assumed

Floor

1st Floor, N wing, room just S of N1-81

Floor Rug over floor tile N/A N/A N/A N/A Non-Suspect

12’ x 12’ ( off-white w/ light and dark olive mottles)

160 ft2 N/A N/A 1-286 5% Chrysotile

Floor tile mastic 160 ft 2 N/A N/A 1-287 3% Chrysotile

Walls Plaster/sheetrock N/A N/A N/A N/A Non-suspect

Ceilings 2’ X 4’ ceiling tile N/A N/A N/A N/A Non-suspect

Above ceiling Pipe insulation 8-10 LF Damaged N/A N/A Assumed

1st Floor, N wing, room N 1-82

Floor 12” X12” Floor tile ( off-white w/ light & dark olive mottles)

80-100 ft2 N/A 1-286 N/A 5% Chrysotile

Floor tile mastic 80-100 ft2 N/A 1-287 N/A 3% Chrysotile

12” x 12” ceiling tile (white w/ rows of holes) –above 2’ X 4’

N/A N/A N/A Previously tested <1%

1st Floor, N wing, room N1-83

Floor Carpet over 12” X12” floor tile (tan w/ white/dark tan mottles)

250 ft 2 N/A N/A 8-039 None detected

Floor tile mastic 250 ft2 N/A N/A 8-040 2% Chrysotile

Walls Plaster/sheetrock N/A N/A N/A N/A Non-suspect

Ceilings 2’ X 4’ ceiling tile N/A N/A N/A N/A Non-suspect

12” X 12” ceiling tiles N/A N/A N/A N/A Non-suspect

Above ceiling tile/plaster ceiling

Pipe insulation (can’t see above plaster)

N/A N/A N/A N/A Assumed

Floor

1st Floor, N wing, room N1-85

Walls Marble/plaster N/A N/A N/A N/A Non-suspect

Ceilings 2’ X 4’ ceiling tile 216 ft2 Damaged N/A 2-121 5% Chrysotile

Comments: No access above ceiling tiles within this area due to the asbestos content of the ceiling tiles.

1st Floor, N wing, room N1-86 and Mechanical room Labeled N1-89 on drawings(which is labeled twice)

Floor 12” X 12” floor tile (white w/tan & dark tan mottles)

960 ft2 N/A N/A 5-69 None detected

Floor tile mastic 960 ft2 N/A N/A 5-70 5% Chrysotile

Walls Plaster/sheetrock N/A N/A N/A N/A Non-suspect

Ceilings 2’ X 4’ ceiling tile N/A N/A N/A N/A Non-suspect

Ceiling tile - Removed N/A

Above ceiling tile Pipe/fitting insulation (N1-86) 20-25 LF Damaged N/A N/A Assumed

Pipes in Mech N1-89 Valve Fitting Insualtion 1 LF Significant Damage

N/A N/A Assumed

Univents Transite panels 64-128 ft2 Damaged V N/A Assumed

1st Floor, N wing, room N1-89 (Room between N1-86D and N1-79)

Floor 12” X12” floor tile under rug 250 ft2 N/A N/A 1-286 5% Chrysotile Mastic

250 ft2 N/A N/A 1-287 3% Chrysotile

Ceilings 2’ X 4’ ceiling tile N/A N/A N/A N/A Non-suspect

In chase Pipe/fitting insulation 20-30 LF Good N/A N/A Assumed

Floor

1st Floor, N wing, room N1-91

Pipe riser Pipe insulation (black mastic over cork)

10 LF Good N/A 6-96 8% Chrysotile

1st Floor, N wing, room N1-92 and N1-93 (bathroom)

Floor 12” X 12” floor tile (gray/green w/ white & gray mottles) - Removed

160ft2 (N1-92) 50ft2 (N1-93)

N/A 1-190 N/A N/A

Floor tile mastic - Removed 160 ft2 N/A 1-191 N/A N/A

Walls Plaster/sheetrock N/A N/A N/A N/A Non-suspect

Ceilings 2’ X 4’ ceiling tile N/A N/A N/A N/A Non-suspect

Above ceiling tile and plaster

Pipe insulation >30 LF Good N/A N/A Assumed

Univents (N1-92 only) Transite panels 16-32 ft2 Significant damage

N/A N/A Assumed

1st Floor, N wing, room N1-95 and N1-94 (bathroom)

Floor 12” X 12” floor tile (gray/green w/ white & gray mottles)

150 ft2 Good N/A 1-190 5% Chrysotile

Floor tile mastic 150 ft2 N/A N/A 1-191 10% Chrysotile

Walls Plaster/sheetrock N/A N/A N/A N/A Non-suspect

Ceilings 2’ X 4’ ceiling tile N/A N/A N/A N/A Non-suspect

Above ceiling tile (over W wall)

Pipe insulation 20 LF Good N/A N/A Assumed

Floor

1st Floor, N wing, rooms N1-99, N1-100, N1-102A, N1-102, N1-103A, N1-103 and N1-104A

9” X9” floor tile (white w/blue marks)

~160 ft2 /area N/A N/A N/A Assumed

Floor tile mastic ~160 ft2 /area N/A N/A N/A Assumed

Ceilings 2’ X 4’ ceiling tile N/A N/A N/A N/A Non-suspect

In chases ( all rooms) & above ceiling tile in 99,102,103A-removed above ceilings

Pipe insulation – 103A No pipe above, 102 8in damage piece B4 chase, 99 can’t see/plaster ceiling

20-30 LF

each

Damaged N/A N/A Assumed

Univents Transite panels (103 & 103A 3 of 4 front panels gone)

16-32 ft2/area Damage N/A N/A Assumed

1st Floor, N wing, rooms N1-104B and N1-104

Floor 12” X 12” floor tile (gray w/ white and dark gray mottles)

160 ft2 /area N/A N/A 8-039 None detected

Floor tile mastic 160 ft2 /area N/A N/A 8-040 2% Chrysotile

9” X 9” floor tile (N1-104B) 4-5 ft2 N/A N/A N/A Assumed

Walls Sheetrock N/A N/A N/A N/A Non-suspect

Ceilings 2’ X 4’ ceiling tile N/A N/A N/A N/A Non-suspect

Univents Transite Panels 16-32ft2

(104B)

8-16ft2 (104) Damaged N/A N/A Assumed

1st Floor, N wing, room N1-108

Floor Terrazzo tile N/A N/A N/A N/A Non-suspect

Walls Tile/plaster N/A N/A N/A N/A Non-suspect

Ceilings 2’ X 4’ ceiling tile N/A N/A N/A N/A Non-suspect

Floor

1st Floor, corridor N1-101

12” X12” floor tile (off-white w/ light & dark tan mottles)

1400 ft2 N/A 1-224T N/A None detected

Floor tile mastic 1400 ft2 N/A 1-224M N/A 8% Chrysotile

9” X 9” floor tile (by 104B) 6-8 ft2 N/A N/A N/A Assumed

Walls Plaster/tile N/A N/A N/A N/A Non-suspect

Ceilings 2’ X 2’ ceiling tile N/A N/A N/A N/A Non-suspect

Univents Transite panels (front panels missing)

16 ft2 Damaged N/A N/A Assumed

Above E ceiling Pipe insulation in deck - Removed N/A N/A N/A N/A Assumed

1st Floor, N wing, room N1-96A

Floor 12” X 12” floor tile(over hard tile) 160 ft2 N/A 1-225T N/A None detected

Floor tile mastic 160 ft2 N/A 1-225M N/A None detected

Walls Plaster/tile N/A N/A N/A N/A Non-suspect

1st Floor, N wing, room N1-96

Floor 12” X12” floor tile (over hard tile) 50 ft2 N/A N/A 1-225T None detected

Floor tile mastic 50 ft2 N/A N/A 1-225M None detected

Floor

1st Floor, N wing, room N1-97

Floor 12” X 12” floor tile (over hard tile) 160 ft2 N/A N/A 1-225T None detected

Floor tile mastic 160 ft2 N/A N/A 1-225M None detected

Univents Transite panels 16-32 ft2 Damaged N/A N/A Assumed

1st Floor, N wing, room N1-98

Floor 12” X12” floor tile (over hard tile) 160 ft2 N/A N/A 1-225T None detected

Floor tile mastic 160 ft2 N/A N/A 1-225M None detected

Univents Transite panels 16-32 ft2 Damaged N/A N/A Assumed

1st Floor, N wing, rooms N1-105A and N1-105

Floor 12” X 12” floor tile 160 ft2 /area N/A N/A 1-225T None detected

Floor tile mastic 160 ft2 /area N/A N/A 1-225M None detected

9” X 9” floor tile (under 12” X 12” ) 160 ft2 /area N/A N/A N/A Assumed

Floor tile mastic 160 ft2 /area N/A N/A N/A Assumed

Univents Transite panels (N1-105 missing front panels)

16-32 ft2 Damaged N/A N/A Assumed

1st Floor, N wing, room N1-109

Floor 12” X12” floor tile(tan w/ white & dark tan mottles) - Removed

300 ft2 N/A N/A N/A N/A

Floor tile mastic - Removed 300 ft3 N/A N/A N/A N/A

Floor

Ceilings 2’ X4’ ceiling tiles N/A N/A N/A Previously tested <1%

Above ceiling tile (N wall)

Pipe insulation 3 LF Good N/A N/A Assumed

Univents Transite panels (front missing) 16 ft2 Damaged N/A N/A Assumed

Comments: The front of the panels have been removed. The rear panes could not be observed at the time of this inspection and could be present.

1st Floor, N wing, room N1-110

Floor 12” X12” floor tiles - Removed 150 ft2 N/A N/A N/A N/A

Floor tile mastic - Removed 150 ft2 N/A N/A N/A N/A

Walls Plaster N/A N/A N/A N/A Non-suspect

Ceilings 2’ X 4’ ceiling tile N/A N/A N/A N/A Non-suspect

1st Floor, N wing, rooms N1-111, N1-112, N1-113, N1-114, N1-115, N1-116, N1-119

Floor 12” X 12” floor tile (yellow/orange) - Removed

180 ft2 N/A N/A 8-039 N/A

Floor tile mastic - Removed 180 ft2 N/A N/A N/A N/A

Walls Plaster N/A N/A N/A N/A Non-suspect

Ceilings 2’ X 4’ ceiling tile N/A N/A N/A N/A Non-suspect

Univents Transite panels (front panels missing)

16 ft2 / Room Damaged N/A N/A Assumed

Chases Pipe insulation - Assume still there N/A N/A N/A N/A Assumed

Floor

1st Floor, N wing, room N1-120

Floor 12” X12” floor tile - Removed 200 ft2 N/A N/A N/A N/A

Floor tile mastic - Removed 200 ft2 N/A N/A N/A N/A

1st Floor, N wing, rooms N1-121, N1-122, N1-123, and N1-124 - Removed

Floor 12” X 12” floor tile 100 ft2/ area 50 ft2 N1-124

N/A N/A 8-039 None detected

Floor tile mastic 100 ft2/ area 50 ft2 N1-124

N/A N/A 8-040 2% Chrysotile

Walls Plaster/sheetrock N/A N/A N/A N/A Non-suspect

Ceilings 2’ X 4’ ceiling tile N/A N/A N/A N/A Non-suspect

1st Floor, N wing, room N1-125

Floor 12” X 12” floor tile - Removed 200 ft2 N/A N/A N/A N/A

Floor tile mastic - Removed 200 ft2 N/A N/A N/A N/A

Walls Plaster/sheetrock N/A N/A N/A N/A Non-suspect

Ceiling 2’ X 4’ ceiling tile N/A N/A N/A N/A Non-suspect

1st Floor, N wing, room N1-130

Floor 12” X 12” floor tile - Removed 100 ft2 N/A N/A N/A N/A

Floor tile mastic - Removed 100 ft2 N/A N/A N/A N/A

Walls Sheetrock N/A N/A N/A N/A Non-suspect

Floor

1st Floor, N wing, room N1-131

Floor 12” X 12” floor tile - Removed 50 ft2 N/A N/A N/A N/A

Floor tile mastic - Removed 50 ft2 N/A N/A N/A N/A

Walls Plaster/sheetrock N/A N/A N/A N/A Non-suspect

Ceilings 2’ X 4’ ceiling tile N/A N/A N/A N/A Non-suspect

1st Floor, N wing, telephone closet (off room N 1-136) and N1-128

Floor 12” X 12” floor ( telephone closet) 9 ft2 N/A N/A N/A Assumed

Floor tile mastic 9 ft2 N/A N/A N/A Assumed

12” X 12” floor tile(N1-128) -

25 ft 2 N/A N/A N/A Assumed

Floor tile mastic - Removed 25 ft2 N/A N/A N/A Assumed

1st Floor, N wing, room N1-32 – Not on prints or Field

Floor Rug over tile N/A N/A N/A N/A Non-suspect

12” X 12” floor tile 160 ft2 N/A N/A N/A Assumed

Floor tile mastic 160 ft2 N/A N/A N/A Assumed

Walls Plaster/sheetrock N/A N/A N/A N/A Non-suspect

Ceilings 2’ X 4’ ceiling tile N/A N/A N/A N/A Non-suspect

Above ceiling tiles (N wall)

Pipe insulation 5 LF Damaged N/A N/A Assumed

Floor

1ST Floor, N wing, rooms N1-134, N1-135, N1-136 ( dental area)

Floor Rug over concrete or terrazzo N/A N/A N/A N/A Non-suspect

Walls Sheetrock and joint material N/A N/A 1-189 N/A None detected

Above ceiling tiles (wall by nurse’ station)

Pipe insulation - Removed N/A N/A N/A N/A N/A

1st Floor, halls (in dental areas)

Floor 12” X12” floor tile - Removed N/A N/A N/A N/A N/A

Floor tile mastic - Removed N/A N/A N/A N/A N/A

Walls Plaster/tile N/A N/A N/A N/A Non-suspect

Ceilings 2’ X 4’ Ceiling tile N/A N/A N/A N/A Non-suspect

1st Floor, N wing, room N1-136A – Area not present

Floor 12” X 12” floor tile 320 ft2 N/A N/A 8-039 None detected

Floor tile mastic 320 ft2 N/A N/A 8-040 2% Chrysotile

Walls Sheetrock N/A N/A 1-189 N/A None detected

Ceilings 2’X4’ ceiling tile N/A N/A N/A N/A Non-suspect

1st Floor, N wing, room N1-137

Floor 12” X 12” floor tile (white w/tan & dark tan mottles)

20 ft2 N/A N/A 5-69 None detected

Floor tile mastic 20ft2 N/A N/A 5-70 5% Chrysotile

Floor

1st Floor, N wing, rooms N1-143, N1-142, N1-141, N1-140, N1-139 and N1-138

Floor Rug over terrazzo N/A N/A N/A N/A Non-suspect

Walls Plaster / sheetrock N/A N/A N/A N/A Non-suspect

Ceilings 2’ x 2’ ceiling tile N/A N/A N/A N/A Non-suspect

Main Chapel and Sacristy

Floor of main chapel Rug over concrete (main area) Altar – rug over concrete

N/A N/A N/A N/A Non-suspect

12” X 12” Floor tile (purple w/ white/dark purple markings)

940 ft2 N/A C-149 N/A None detected

Floor tile mastic 940 ft2 N/A C-159 N/A 2% Chrysotile

Floor of Sacristy 9” X 9“ Floor tile 300 ft2 N/A N/A N/A Assumed

Floor tile mastic 300 ft2 N/A N/A N/A Assumed

Walls Sheetrock/joints N/A N/A N/A Previously tested None detected

Ceiling 2’ X 2’ ceiling tile (tan, rough variegations w/foil backing)

N/A N/A N/A N/A Non-suspect

Sacristy Closet Pipe insulation 30-40 ft Significant damage

N/A N/A Assumed

Eucharist Room (21-3)

Floor Rug over wood underlayment over concrete

N/A N/A N/A N/A Non-suspect

Walls Sheetrock/ Joint N/A N/A N/A Previously tested None detected

Ceilings 2’ X 4’ ceiling tile (off-white, crater-like worm markings)

N/A Good C-148 N/A None detected

Floor

S Office (21-4)

Floor Rug over 9” X 9” floor tile 150 ft2 N/A N/A N/A Assumed

Mastic Assumed

Walls Sheetrock/Joints N/A N/A N/A N/A Non-suspect

Ceilings 2’ X 4’ ceiling tiles (Not fire rated) N/A N/A N/A N/A Non-suspect

Hall to Chapel (21-13)

Floor 12” X 12” floor tile/carpet N/A N/A N/A N/A Non-suspect, installed after

Pipes Pipe fitting insulation 1 fitting Good N/A N/A Assumed

NOTE: No suspect asbestos-containing material were observed in rooms C1-17, C1-31, C1-43, C1-44, C1-45,C1-51, C1-52, C1-104, C1-56A, N1-133, N1-132, main hallway in dental areas, and crawlspace behind room C1-22 (mechanical room). The halls within the East wing have been recently renovated – no suspect asbestos-containing materials observed. The Dental Wing was completely renovated since 2005 Inspection

Building 1, Floor 2 - Specific Survey Findings

VA Medical Center, Building No. 1, 2 nd

Floor

1511 Route 22, Suite C24, Brewster, NY 10509 Phone: 845.278.7710 Fax: 845.278.7750

Environmental Health Associates, Inc.

Project: Main Building, 2 nd Floor Inspector(s): James Reber

VA Medical Center Thomas Ferro Wilkes-Barre, PA Date(s): 2/2010-3/2010

LOCATION MATERIAL QUANTITY CONDITION SAMPLE #

HOMOGENEOUS

WITH SAMPLE #

ASBESTOS CONTENT

nd

Floor, Corridor – center/east (service elevator side and small hall to Nuclear Medicine)

Floor 12” X 12” floor tile(light green w/white & dark green mottles)

1100 ft2 good N/A 7-58 15% Chrysotile

Floor tile mastic 1100 ft2 N/A N/A 7-59 10% Chrysotile

Walls Block N/A N/A N/A N/A Non-suspect

Ceilings 2’ X 2’ ceiling tile N/A N/A N/A N/A Non-suspect

Above ceiling tile Pipe insulation – mastic and cork >100 LF Good N/A N/A Assumed

2nd Floor, room C2-02 (No access – Assume materials still present)

Floor Concrete N/A N/A N/A N/A Non-suspect

Walls Block N/A N/A N/A N/A Non-suspect

Ceilings Metal/concrete N/A N/A N/A N/A Non-suspect

NW Corner Pipe insulation 2 LF N/A N/A N/A Assumed

2nd Floor, room C2-3A and C2-3B

Floor Composite/ceramic tile N/A N/A N/A N/A Non-suspect

Walls Sheetrock N/A N/A N/A N/A Non-suspect

Ceilings 2’ x 4’ ceiling tile N/A N/A N/A N/A Non-suspect

VA Medical Center, Building No. 1, Floor 2

Small closet of NE corner of Liberty Hall, C2-21

Floor 12” X 12” floor tile 16 ft2 N/A N/A 6-103 Assumed

Floor tile mastic 16 ft2 N/A N/A 6-104 Assumed

Walls Plaster N/A N/A N/A N/A Non-suspect

Ceilings Plaster N/A N/A N/A N/A Non-suspect

2nd Floor, room C2-03

Floor 12” x 12” floor tile (light green w/ white & dark green mottles)

160 ft2 N/A N/A 7-58 15% Chrysotile

Floor tile mastic 160 ft2 N/A N/A 7-59 10% Chrysotile

Walls Plaster N/A N/A N/A N/A Non-suspect

Ceilings 2’ X 4’ ceiling tile N/A N/A N/A N/A Non-suspect

Univents Transite panels 8-16 ft2 Damaged N/A N/A Assumed

2nd Floor, room C2-04

Floor 12” X 12” floor tile – replaced w/carpet

N/A

Floor tile mastic –replaced w/carpet N/A

Walls Paneling over plaster N/A N/A N/A N/A Non-suspect

Ceilings 2’ X 4’ ceiling tiles (white w/worm markings)

N/A N/A N/A N/A Non-suspect

Univents Transite panels 8-16 ft2 Damaged N/A N/A Assumed

In walls Brown tissue paper- like material N/A N/A 2-116 N/A None detected

On walls Plaster (light/soft) N/A N/A 2-117 N/A None detected

Comment: Pipe insulation may be in chase

2nd Floor, room C2-05

12” X 12” floor tile(light green w/white & dark green mottles)

168 ft2 N/A N/A 7-58 15% Chrysotile

Floor tile mastic 168 ft2 N/A V 7-59 10% Chrysotile

Walls Tile/plaster/paneling N/A N/A N/A N/A Non-suspect

Ceilings 2’ X 4’ ceiling tile (off white w/ pinhole perforations & crater worm markings)

N/A N/A 2-120 N/A None detected

2’ X 4’ ceiling tile (off-white w/pinholes & pockmarks)

N/A N/A N/A 2-123 None detected

2nd Floor, room C2-05A

Floor 12” X 12” floor tile (off –white w/ white & brown streaks)

332 ft2 N/A 2-118 N/A <1% Chrysotile

Floor tile mastic 332 ft2 N/A 2-119 N/A 5% Chrysotile

Walls Plaster/sheetrock joint material N/A N/A N/A N/A Non-suspect

Ceilings 2’ X 4’ ceiling tile N/A N/A N/A N/A Non-suspect

Above ceiling tile Pipe insulation (aircell) 35-40 LF Damaged N/A N/A Assumed

2nd Floor, room C2-05B

Floor 12” X12” floor tile (white w/brown streaks)

192 ft2 N/A N/A 6-103 5% Chrysotile

Floor tile mastic 192 ft2 N/A N/A 6-104 5% Chrysotile

Walls Sheetrock joint material N/A N/A 2-118 N/A None detected

Ceilings 2’ X 4’ ceiling tile (pinhole perforations & worm markings)

N/A N/A N/A 2-123 None detected

Above ceiling tile Pipe insulation 28 LF Good N/A N/A Assumed

2nd Floor, hall by rooms C2-05A and 2-130

12” X12’ floor tile (light green w/white & dark green mottles)

385 ft2 N/A N/A 7-58 15% Chrysotile

Floor tile mastic 385 ft2 N/A N/A 7-59 10% Chrysotile

Walls Sheetrock joint material N/A N/A N/A N/A Non-suspect

Ceilings 2’ x 4’ ceiling tile (pinhole perforations & worm markings

N/A N/A N/A 2-123 None detected

Above ceiling tile Pipe insulation <10 LF Damaged N/A N/A Assumed

2nd Floor, room C2-06

Floor Ceramic tile N/A N/A N/A N/A Non-suspect

Walls Plaster/tile N/A N/A N/A N/A Non-suspect

Ceilings 2’ X 4’ ceiling tile 198 ft2 N/A N/A N/A Non-suspect

Univents Transite Panels 8-16 ft2 Damaged N/A N/A Assumed

Comment: Pipe insulation in chase - NE

2nd Floor, rooms C2-07 & C2-08

Floor Rug over floor tile N/A N/A N/A N/A Non-suspect

12” X 12” Floor tile 144 ft2 / area N/A N/A N/A Assumed

Floor tile mastic 144 ft2 / area N/A N/A N/A Assumed

Walls Plaster N/A N/A N/A N/A Non-suspect

Ceilings 2’ X4’ ceiling tile( pinhole perforations & worm markings)

N/A N/A N/A 2-123 None detected

Above plaster ceiling (room C2-08 & C2- 07)

Pipe insulation 30 – 35 LF Significant damage

N/A N/A Assumed

C2-09 and C2-10 – Probable asbestos pipe insulation in walls.

C2-11 (corridor) – 12” X 12” green floor tile (7-58: 15% Chrysotile) and mastic (7-59: 10% Chrysotile) – 300 ft2 - Good

2nd Floor, Liberty Hall, room C2-14

Floor Ceramic Tile N/A N/A N/A N/A Non-suspect

Walls Sheetrock joint material N/A N/A N/A N/A Non-suspect

Ceilings 2’ X 4’ ceiling tile (off-white w/ sparse pinhole perforations & worm markings)

3500 ft2 N/A 2-121 N/A 5% Chrysotile

Above ceiling tile (N wall)

Pipe insulation (black mastic over cork)

N/A Good N/A 6-96 8% Chrysotile

Pipe insulation (aircell) N/A Good N/A N/A Assumed

Comment: Cannot check above ceiling tiles because it will disturb ACM

2nd Floor, room C2-13 (Credit Union) and C2-12

Floor Rug over concrete N/A N/A N/A N/A Non-suspect

Walls Sheetrock joint material N/A N/A N/A Previously tested <1%

Ceilings 2’ X 4’ ceiling tile N/A N/A N/A N/A Non-suspect

Plaster N/A N/A N/A N/A Non-suspect

Vertical chase Pipe insulation N/A N/A N/A N/A Assumed

2nd Floor, rooms C2-14B, C2-14C, C2-14D, C2-14E, and C2-14F

Floor Rug over concrete/ceramic tile N/A N/A N/A N/A Non-suspect

Walls Plaster/sheetrock joint material N/A N/A N/A N/A Non-suspect

2nd Floor, room C2-15

Floor Rig over concrete N/A N/A N/A N/A Non-suspect

Walls Sheetrock joint material N/A N/A N/A N/A Non-suspect

Ceilings 2’ X 4’ ceiling tile (pinhole perforations & worm markings)

128 ft2 N/A N/A 2-123 None detected

Above ceiling tile (over N wall)

Pipe insulation 4 LF Good N/A N/A Assumed

2nd Floor, room C2-16

Floor Rug over ceramic tile N/A N/A N/A N/A Non-suspect

Walls Sheetrock joint material N/A N/A N/A N/A Non-suspect

Ceilings 2’ x 4’ ceiling tile (pinhole perforations & worm markings)

144 ft2 N/A N/A 2-123 None detected

Above ceiling tile (N side)

Pipe insulation 10 LF Good N/A N/A Assumed

2nd Floor, room C2-17, C2-18, C2-19 (C2-19 not found)

Floor Ceramic Tile N/A N/A N/A N/A Non-suspect

Walls Plaster/sheetrock joint material N/A N/A N/A N/A Non-suspect

Ceilings 2’ X 4’ ceiling tile (pinhole perforations & worm markings)

N/A N/A N/A 2-123 Non-suspect

Above ceiling and in chase( has cork pipe aircell)

Pipe insulation (aircell, mastic cork pipe)

>50 LF

aircell

>40 LF cork N/A N/A N/A Assumed

2nd Floor, pipe chase by C2-22 (electrical closet) (Room was not found)

Pipe Pipe insulation (black mastic over cork)

3 LF N/A N/A 6-96 8% Chrysotile

2nd Floor, room C2-22

Floor Ceramic tile N/A N/A N/A N/A Non-suspect

12” X 12” floor tile (tan w/white & dark tan mottles) – bathroom

40 ft2 N/A N/A 8-039 None detected

Floor tile mastic – bathroom 40 ft2 Good N/A 8-040 2% Chrysotile

Ceilings 2’ X4’ ceiling tile N/A N/A N/A N/A Non-suspect

2nd Floor, room C2-23

Floor 12” X 12” floor tile – new N/A N/A N/A N/A Non-suspect

Walls Plaster/sheetrock joint material N/A N/A N/A N/A Non-suspect

Ceilings 2’X4’ ceiling tile (pinhole perforations w/ worm markings)

N/A N/A N/A 2-123 None detected

Univents Transite panels 24-48 ft2 Damaged N/A N/A Assumed

Above ceiling tile Pipe insulation (aircell) 16 LF Good N/A N/A Assumed

Pipe insulation (black mastic over cork and MAG)

12 LF Damaged N/A 6-96 8% Chrysotile

Threshold of C2-24 and C2-25 – 3 ft2 - 12” X 12” Floor tile (blue green) and floor tile mastic.

2nd Floor, room C2-24

Floor Terrazzo tile N/A N/A N/A N/A Non-suspect

Walls Tile /plaster N/A N/A N/A N/A Non-suspect

Ceilings 2’X4’ ceiling tile (off-white w/perforations &worm markings)

648 ft2 N/A N/A 2-128 None detected

Univents Transite panels 40 – 80 ft2 Damaged N/A N/A Assumed

Above ceiling and in chase

Pipe insulation >20 LF Good N/A N/A Assumed

2nd Floor, room C2-25

Floor Rug 12” X 12’ pads (brown) 258 ft2 N/A N/A N/A Non-suspect

Mastic 258 ft2 N/A N/A N/A >1%

Walls Plaster N/A N/A N/A N/A Non-suspect

Ceilings 2’ X 4’ ceiling tile (pinhole perforations & worm markings)

N/A N/A N/A 2-123 None detected

2nd Floor, room C2-27A Mechanical

Pipes Pipe insulation (black mastic over cork)

12 LF Damaged N/A 6-96 8% Chrysotile

2nd Floor, room C2-28

Floor Tile N/A N/A N/A N/A Non-suspect

Walls Tile N/A N/A N/A N/A Non-suspect

Ceilings 2’ X 4’ ceiling tile N/A N/A N/A N/A Non-suspect

Above ceiling tile/plaster

Pipe insulation 25-30 LF Good N/A N/A Assumed

Univent Transite panels (front missing) 8 ft2 N/A N/A N/A Assumed

2nd Floor, rooms C2-29 and C2-30

Floor 12”X 12” floor tile under rug (room C2-29 & C2-30)

420 ft2 N/A N/A Previously tested positive >1%

Floor tile mastic (room C2-29)` 420 ft2 N/A N/A Previously tested positive >1%

Plaster N/A N/A N/A N/A Non-suspect

Univents Transite panels 32-64 ft2/area Damaged N/A N/A Assumed

Above plaster in C2-

Pipe insulation 16-20 LF Damaged N/A N/A Assumed

2nd Floor, rooms C2-33A

Floor 12” X 12” floor tile – new N/A N/A N/A N/A Non-suspect

Walls Plaster N/A N/A N/A N/A Non-suspect

Ceilings 2’ X 4’ –new N/A N/A N/A N/A Non-suspect

Plaster N/A N/A N/A N/A Non-suspect

Univents Transite panels (front panels missing)

16 ft2 N/A N/A N/A Assumed

2nd Floor, room C2-30A

Floor Rug over 12” X 12” floor tile/mastic N/A N/A N/A N/A >1%

Walls Plaster N/A N/A N/A N/A Non-suspect

Ceilings 2’ X 4’ ceiling tile N/A N/A N/A N/A Non-suspect

Univents Transite panels 8-16 ft2 Damaged N/A N/A Assumed

2nd floor, room C2-31

Floor Rug over floor tile N/A N/A N/A N/A Non-suspect

12” X 12” floor tile (off-white) 880 ft2 N/A 2-131 7-59 5% Chrysotile

Floor tile mastic 880 ft2 N/A N/A N/A Assumed

Walls Wood paneling N/A N/A N/A N/A Non-suspect

Ceilings 2’ X 4’ ceiling tile (off-white w/ perforations & worm markings)

N/A N/A N/A N/A Non-suspect

Univents Transite panels 24-48 ft2 Damaged N/A N/A Assumed

2nd Floor, room C2-33

Floor Rug over floor tile No rug N/A N/A N/A N/A Non-suspect

12” X 12” floor tile (off-white) 120 ft2 Good 2-132 N/A 3% Chrysotile

Floor tile mastic 120 ft2 N/A 2-133 N/A 3% Chrysotile

Walls Plaster N/A N/A N/A N/A Non-suspect

Ceilings 2’ X 4’ ceiling tile N/A N/A N/A N/A Non-suspect

Univents Transite panels 20 – 40 ft 2 Damaged N/A N/A Assumed

E Wall Pipe insulation 8 linear feet N/A N/A N/A Assumed

2nd floor, Room C2-33B through C2-43

Floor 12” X 12” floor tile N/A N/A N/A N/A Non-suspect

Walls Plaster N/A N/A N/A N/A Non-suspect

Ceilings 2’ X 2’ ceiling tile N/A N/A N/A N/A Non-suspect

2nd Floor, room C2-43A – No suspect material

2nd Floor, C2-44

Floor Terrazzo Tile N/A N/A N/A N/A Non-suspect

Walls Tile/sheetrock joint material N/A N/A N/A N/A Non-suspect

Ceilings 2’ X 4’ ceiling tile 9pinhole perforations & worn markings

N/A N/A N/A 2-123 None detected

2nd Floor, hall by service elevator

Floor 12’ X 12” floor tile (light green W/ white & dark green mottles)

200 ft2 N/A N/A 7-58 15% Chrysotile

Floor mastic 200 ft2 N/A N/A 7-59 10% Chrysotile

Walls Brick/sheetrock N/A N/A N/A N/A Non-suspect

Ceilings 2’ X 4’ ceiling tile (pinhole perforations & worm markings)

N/A N/A N/A 2-123 None detected

Pipe insulation in chase behind elevator #2 – 15LF - Damaged

2nd Floor, room C2-46 (Electrical closet)

Pipe Pipe insulation (black mastic over cork)

12 LF Good N/A 6-96 8% Chrysotile

Pipe Pipe/fitting insulation on fiberglass lines

4 fittings Good N/A N/A Assumed

C2-106A and B, Pipe Room to N of 106B, and C2-107 – No exposed suspect asbestos containing materials observed.

2nd Floor, room C2-47

Floor 12” X 12” floor tile (chocolate w/white & dk brown marble effect)

120 ft2 Good N/A 7-86 None detected

Floor tile mastic 120 ft2 N/A N/A 7-87 5% Chrysotile

Walls Plaster N/A N/A N/A N/A Non-suspect

Ceilings Plaster N/A N/A N/A N/A Non-suspect

Univents Transite panels 12-24 ft2 Damaged N/A N/A Assumed

2nd Floor, room C2-118 and C2-121 (Library area)

Floor` Rug over N/A N/A N/A Non-suspect

Mastic N/A N/A 2-112 None detected

Walls Plaster/sheetrock N/A N/A N/A N/A Non-suspect

Ceiling 2’ X 2’ ceiling tile N/A N/A N/A N/A Non-suspect

Univents Transite panels

32-64ft

(C2-118) 56-112 ft

(C2-121)

Damaged N/A N/A Assumed

C2-129 and C2-130 – No exposed suspect asbestos materials observed. (Not found)

Recreation Room

Floor 12” X 12” floor tile (off-white with brown mottles)

2000 ft2 N/A N/A

Previously tested positive

>1%

Mastic 2000 ft2 N/A N/A

Previously tested positive

>1%

Walls Plaster N/A N/A N/A N/A Non-suspect

Ceilings 2’ X 2’ ceiling tile N/A N/A N/A N/A Non-suspect

2nd Floor, N wing, room N2-48 ( Labeled N2-49A on drawings)

Floor 12” X 12” floor tile- green mottles) Not there – newer 12” X 12”

180-200 ft2 N/A N/A

Mastic 180-200 ft2 N/A N/A

Walls Plaster N/A N/A N/A N/A Non-suspect

Ceilings 2’ X 4’ ceiling tile N/A N/A N/A N/A Non-suspect

Univents Transite panels (front panels missing)

12-24 ft2 Damaged N/A N/A Assumed

Above ceiling tiles Pipe insulation (aircell) – removed

2nd Floor, room N2-49

Floor Ceramic Tile N/A N/A N/A N/A Non-suspect

Walls Plaster/sheetrock joint material/tile N/A N/A N/A N/A Non-suspect

Ceilings 2’ X 4’ ceiling tile (pinhole perforations & worm markings)

N/A N/A N/A 2-123 None detected

Concrete N/A N/A N/A N/A Non-suspect

Univents Transite panels (front panels missing)

36 ft2 N/A N/A N/A Assumed

Utility room off C49 9 (N2-49B)

Pipe insulation (aircell) 10 LF Good N/A N/A Assumed

2nd floor, N wing, room N2-50

Floor Ceramic Tile N/A N/A N/A N/A Non-suspect

Walls Plaster/sheetrock joint material/tile N/A N/A N/A N/A Non-suspect

Ceilings 2’X 4’ ceiling tile (pinhole perforations & worm markings)

N/A N/A N/A 2-123 None detected

Univents Transite panels (front panels missing)

20 ft2 N/A N/A N/A Assumed

SW Chase Pipe insulation >20 LF N/A N/A N/A Assumed

2nd Floor, N wing, N2-48A – Turned into mechanical room.

Floor 12” X 12” floor tile – green mottled)

Mastic -Removed

Ceilings 2’ X 4’ ceiling tile N/A N/A N/A N/A Non-suspect

Pipes in N wall Pipe insulation/fitting 12 LF Significant damage

2nd Floor, N wing, room N2-53

Floor Ceramic tile N/A N/A N/A N/A Non-suspect

Walls Plaster N/A N/A N/A N/A Non-suspect

Ceilings 2’ X 4’ ceiling tile N/A N/A N/A N/A Non-suspect

Univents Transite panels (front panels missing)

40 ft2 N/A N/A N/A Assumed

Chase – NE corner Pipe insulation >12 LF N/A N/A N/A Assumed

2nd Floor, N wing, room N2-55 & electrical room

Floor Ceramic tile N/A N/A N/A N/A Non-suspect

Walls Plaster/tile N/A N/A N/A N/A Non-suspect

Ceilings Plaster N/A N/A N/A N/A Non-suspect

2nd Floor, N wing, room N2-56 (Electrical room)

Floor Concrete/metal N/A N/A N/A N/A Non-suspect

Walls Block N/A N/A N/A N/A Non-suspect

Vertical Chase Pipe insulation 9black mastic over cork)

12 LF Good N/A 6-96 8% Chrysotile

Vertical Chase Duct insulation (black mastic over cork)

100 ft2 Good N/A 6-96 8% Chrysotile

2nd floor, N wing, room N2-58

Floor 12” X 12” and 2’ X 2’ N/A N/A N/A N/A Non-suspect

Walls Plaster N/A N/A N/A N/A Non-suspect

Univents Transite panels (front panels missing)

8 ft 2 N/A N/A N/A Assumed

2nd Floor, N wing, room N2-60 – No exposed suspect asbestos materials observed.

2nd Floor, N wing, room N2-59

Floor 12” X 12” Floor tile N/A N/A N/A N/A Non-suspect

Walls Plaster N/A N/A N/A N/A Non-suspect

Ceilings 2’ X 4’ ceiling tile (pinhole perforations & worm markings)

N/A N/A N/A 2-123 None detected

Univents Transite panels 32 ft2 N/A N/A N/A Assumed

Comments: The front transite panels have been removed. The rear panels could not be observed at the time of this inspection and could be present.

2nd Floor, N wing, rooms N2-64 and N2-64A

Floor 12” X 12” floor tile N/A N/A N/A N/A Non-suspect

Walls Plaster/tile N/A N/A N/A N/A Non-suspect

Ceilings 2’ X 4’ ceiling tile (pinhole perforations & worm markings) – N2-64

N/A N/A N/A 2-123 None detected

2’ X 4’ ceiling tile – N2-62 N/A N/A N/A N/A Non-suspect

Above ceiling tile Pipe fitting - Removed 1 N/A N/A N/A Assumed

Univents Transite panels (front panels missing)

36 ft2 N/A N/A N/A Assumed

2nd Floor, N wing, rooms N2-66 and bathroom N2-67

Bathroom - in chases Pipe insulation >40 LF Significant damage

N/A N/A Assumed

Univents Transite panels (N2-67) 8 ft2 N/A N/A N/A Assumed

Comments: The front transite panels have been removed. The rear panels could not be observed at the time of this inspection and could be present.

2nd Floor, N wing, room N2-68

12” X 12” floor tile (tan w/white & dark tan mottles)

250-300 ft2 N/A N/A 8-039 None detected

Floor tile mastic 250-300 ft2 N/A N/A 8-040 2% Chrysotile

Walls Plaster N/A N/A N/A N/A Non-suspect

Ceilings 2’ X 4’ ceiling tile N/A N/A N/A N/A Non-suspect

Univents Transite panels (front panels missing

24 ft2 N/A N/A N/A Assumed

NE Corner chase Pipe insulation – Same chase as N2-70

10-20 LF Good N/A N/A Assumed

2nd Floor, N wing, room N2-70

Floor 12” X 12” floor tile (tan w/white & dark tan mottles)

36 ft2 good N/A 8-039 None detected

Floor tile mastic 36 ft2 N/A N/A 8-040 2% Chrysotile

Ceilings 2’ X 4’ ceiling tile N/A N/A N/A N/A Non-suspect

Univents Transite panels (front panels missing)

16 ft2 N/A N/A N/A Assumed

S wall Pipe insulation 10-20 LF Good N/A N/A Assumed

2nd Floor, N wing, room N2-71

Floor 12” X 12” floor tile N/A N/A N/A N/A Non-suspect

Walls Plaster N/A N/A N/A N/A Non-suspect

Ceilings 2’ X 4’ ceiling tile N/A N/A N/A N/A Non-suspect

Univents Transite panels (front panels missing)

24 ft2 N/A N/A N/A Assumed

Comments: The front transite panels have been removed. The rear panels could not be observed at the time of this inspection and could be present.

2nd Floor, N wing, room N2-74

Floor Ceramic tile N/A N/A N/A 8-039 Non-suspect

Walls Plaster/tile N/A N/A N/A N/A Non-suspect

Ceilings 2’ X 4’ ceiling tile N/A N/A N/A N/A Non-suspect

Univents Transite panels ( front panels missing)

8 ft2 N/A N/A N/A Assumed

Above ceiling & in chase

Pipe insulation 45 LF Good N/A N/A Assumed

2nd floor, N wing, room N2-75

Floor 12” X 12’ floor tile N/A N/A N/A N/A Non-suspect

Walls Plaster N/A N/A N/A N/A Non-suspect

Ceilings 2’ X 44’ ceiling tile (pinhole perforations & worm markings

N/A N/A N/A 2-123 None detected

Univents Transite panels 32 ft2 N/A N/A N/A Assumed

Over ceiling tile Duct insulation – removed N/A N/A N/A N/A N/A

Comments: The front transite panels have been removed. The rear panels could not be observed at the time of this inspection and could be present.

2nd Floor, N wing, bathroom at E end of radiology hall (Labeled N2-66)

Floor 12” X 12” floor tile (tan w/white and dk tan mottles) –Removed Non-suspect concrete

Floor tile mastic - Removed

Walls Sheetrock N/A N/A N/A N/A Non-suspect

Ceilings 2” X 2’ ceiling tile (off-white w/pinhole perforations & small crater)

36 ft2 Good 2-127 N/A None detected

Above ceiling tile Duct insulation – removed N/A N/A N/A N/A N/A

2nd Floor, N wing, room N2-77 and N2-77A

Floor 12” X 12” floor tile N/A N/A N/A N/A Non-suspect

Walls Plaster/sheetrock N/A N/A N/A N/A Non-suspect

Ceilings 2’ X 4’ ceiling tile (pinhole perforations & worm markings)

N/A N/A N/A 2-123 Non-suspect

Univents Transite panels (front panels missing)

16 ft2 N/A N/A N/A Assumed

In walls Pipe insulation (Assume chases) N/A N/A N/A N/A Assumed

2nd Floor, N wing, rooms N2-79 and N2-80

Floor 12” X 12” floor tile (light green w/white & dk green mottles)

320 ft2 Good N/A 7-58 15% Chrysotile

Floor tile mastic 320 ft2 N/A N/A 7-59 10% Chrysotile

Walls Plaster/sheetrock N/A N/A N/A N/A Non-suspect

Ceilings 2’ X 4’ ceiling tile N/A N/A N/A N/A Non-suspect

Plaster N/A N/A N/A N/A Non-suspect

Univents Transite panels (front panels missing)

24 ft2 N/A N/A N/A Assumed

Chase in N2-79 Pipe insulation 20-30 LF N/A N/A N/A Assumed

2nd Floor, N wing, room N2-83A

Floor 12” X 12’ floor tile(light green w/white & dark green mottles)

240 ft2 N/A N/A 7-58 15% Chrysotile

Floor tile mastic 240 ft2 N/A N/A 7-59 10% Chrysotile

Walls Plaster/sheetrock joint material N/A N/A N/A N/A Non-suspect

Ceilings 2’X4’ ceiling tile (pinhole perforations & worm markings)

N/A N/A N/A 2-123 None detected

Concrete N/A N/A N/A N/A Non-suspect

Univents Transite panels 32 ft2 N/A N/A N/A Assumed

Comments: The front transite panels have been removed. The rear panels could not be observed at the time of this inspection and could be present.

2nd Floor, N wing, rooms N2-84 and N2-84A

Floor 12” X 12” floor tile 300 ft2 N/A N/A 7-58 15% Chrysotile

Floor tile mastic 300 ft2 N/A N/A 7-59 10 % Chrysotile

Ceilings 2’ X 4’ ceiling tile (pinhole perforation & worm markings)

N/A N/A N/A 2-123 None detected

Univents Transite panels 8 ft2 (N2-84) 16 ft2 (N2-

84A) N/A N/A N/A Assumed

Above ceiling tile Duct insulation (black mastic over cork)

7 LF N/A N/A 6-96 8%Chrysotile

Chase in N2-84 Pipe insulation >40 LF N/A N/A N/A Assumed

2nd Floor, N wing, main hall (radiology area)

12” X 12” floor tile (light green w/white and dk green mottles)

900 ft2 N/A N/A 7-58 15% Chrysotile

Floor tile mastic 900 ft2 N/A N/A 7-59 10% Chrysotile

Ceilings 2’ X 2’ ceiling tile N/A N/A N/A N/A Non-suspect

Concrete N/A N/A N/A N/A Non-suspect

Above ceiling tile Duct insulation – removed N/A N/A N/A N/A N/A

2nd Floor, N wing, room N2-85 (files)

Floor-most of floor tiles in this room are new

12” X 12” floor tile (chocolate w/white & dk brown marble effect)

126 ft2 N/A N/A 7-87T None Detected

Floor tile mastic 126 ft2 N/A N/A 7-87M 5% Chrysotile

Walls Plaster/sheetrock/tile N/A N/A N/A N/A Non-suspect

Ceilings 2’ X 4’ ceiling tile N/A N/A N/A N/A Non-suspect

Univents Transite panels (front panels missing on some, present on others)

64-100 ft2 Damaged N/A N/A Assumed

Pipe insulation 8 LF Damaged N/A N/A Assumed

Above ceiling tile Duct insulation – removed N/A N/A N/A N/A N/A

2nd Floor, N wing, room N2-95 and N2-96 – Newly renovated – no suspect asbestos materials observed

2nd Floor, N wing, room N2-97A and N2-97B

Floor 12” X 12” floor tile (green with mottles)

400 ft2 (97A) 220 ft2 (97B)

Good N/A 7-58 15% Chrysotile

Floor tile mastic 400 ft2 (97A) 220 ft2 (97B)

N/A N/A 7-59 10% Chrysotile

Walls Plaster/tile N/A N/A N/A N/A Non-suspect

Ceilings 2’ X 4’ ceiling tile N/A N/A N/A N/A Non-suspect

Univents Transite panels 36-72ft2 (97A) 24-48ft2 (97B)

Damaged N/A N/A Assumed

NW Chase in 97A Pipe insulation >30 LF N/A N/A N/A Assumed

2nd Floor, N wing, room N2-98 and N2-99

9” x 9” floor tile (brown w/white & burnt sienna) (N2-98 only)

175 ft2 Good N/A N/A Assumed

Floor tile mastic 175 ft2 N/A N/A N/A Assumed

Walls Plaster/tile N/A N/A N/A N/A Non-suspect

Ceilings 2’ X 4’ ceiling tile N/A N/A N/A N/A Non-suspect

Plaster N/A N/A N/A N/A Non-suspect

Univents Transite panels 8-16 ft2 Damaged N/A N/A Assumed

Above ceiling tile Pipe insulation (aircell) 25 LF Good N/A N/A Assumed

2nd Floor, N wing, room N2-100 and N2-101

Floor 9” X 9” floor tile (brown w/white marks and burnt sienna) - N2-101 only

175 ft2 Good N/A N/A Assumed

Floor tile mastic 175 ft2 N/A N/A…