Attachment 5 - Drawings - Options 2 and 3.pdf

PDF 6 MB Posted

Attached to
Recirculating Aquaculture System Upgrades Federal contract opportunity
Solicitation number
1232SA26Q0302
Issued by
Department of Agriculture Agricultural Research Service

About this file

This file is a set of design and construction drawings for the Recirculating Aquaculture Upgrades project at the National Cold-Water Marine Aquaculture Center (NCWMAC) in Franklin, Maine, under USDA Agricultural Research Service contract number 12305B21D0013/12305B24F0110.

The project involves upgrading the facility's recirculating aquaculture system with three primary mechanical components: providing process water cooling and ozone injection for salmon broodstock production. The scope includes installation of three 15-20 ton air-cooled chillers (C-1, C-2, C-3) serving the Brood 3, Parr, and Smolt 2 treatment bays respectively; a 31.2 PPD ozone generator (OZ-1) with integrated 4.5-ton chiller, housed in a prefabricated fiberglass equipment building with electrical controls and safety systems; and associated piping, filtration, and distribution systems for ozone supply to existing low-head oxygenators. The electrical work requires establishing new 480V/277V three-phase power distribution through multiple panelboards (MDP-2, P-H1, P-H2) with branch circuits serving the new mechanical equipment, including a 1000 KVA transformer and automatic transfer switch for emergency backup power. Construction materials must comply with Buy American Act requirements, existing facility operations must be maintained throughout construction, and all work must meet IBC 2021 design standards with 20 PSF ground snow load and 117 MPH ultimate wind speed design criteria.

View the file

Other files for this federal contract opportunity

Other files attached to Recirculating Aquaculture System Upgrades, newest first.
File Type Posted
SF30 - Amendment 02.pdf PDF
RFI 2 - Clarification.pdf PDF
Site Visit Sign In Sheet - Mar 17.pdf PDF
SF30 - Amendment 01.pdf PDF
RFIs.pdf PDF
Site Visit Sign In Sheet - Mar 18.pdf PDF
Attachment 1 - Solicitation Terms and Conditions.pdf PDF
Attachment 2 - Drawings - Base.pdf PDF
Attachment 3 - Specifications - Base.pdf PDF
Attachment 4 - Drawing - Option 1.pdf PDF
Wage Determination.pdf PDF
Attachment 6 - Specifications - Options 2 and 3.pdf PDF
Show all 12

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

PPM

REVISIONS

Agricultural

Service Research

DESCRIPTION

SHEET

DATE

U

NO.

DEPM

SAFETY & HEALTH

REAL PROPERTY

A

DATE

PROJECT NO.

SUSDA

BY

AGRICULTURAL RESEARCH SERVICE

OF

DESIGNER

PROJECT MANAGER

JOB #

CHECKED BY

A-E FIRM USDA AGRICULTURAL RESEARCH SERVICE

NCWMAC

RECIRCULATING AQUACULTURE UPGRADES

FRANKLIN, ME

COVER SHEET

T-100 1 2204/18/2025

THT

JEH

AEJ NATIONAL COLD-WATER MARINE

AQUACULTURE CENTER

25 SALMON FARM RD.

FRANKLIN, ME 04634

XXX

3724-E

XXX

XXX

XXX

XXX

USDA

LOCATION MAPVICINITY MAP NO SCALE

N N

NO SCALE

NATIONAL COLD-WATER MARINE

AQUACULTURE CENTER (NCWMAC)

25 SALMON FARM ROAD

FRANKLIN, ME

PROJECT

LOCATION

GENERAL PROJECT DESCRIPTION

THE PURPOSE OF THIS PROJECT IS TO PROVIDE PROCESS WATER COOLING AND OZONE INJECTION FOR SALMON BROODSTOCK

PRODUCTION.

GENERAL SITE REQUIREMENTS

A. ALL NCWMAC BIOSECURITY PROTOCOLS SHALL BE FOLLOWED AT ALL TIMES. PRIOR TO COMMENCING WORK, THE CONTRACTOR SHALL

OBTAIN THESE REQUIREMENTS IN WRITING FROM USDA.

B. UNINTERRUPTED OPERATION OF THE FACILITY IS REQUIRED. THE CONTRACTOR IS RESPONSIBLE FOR ENSURING SAFE

UNINTERRUPTED OPERATION OF THE FACILITY THROUGHOUT THE PROGRESS OF CONSTRUCTION.

C. LAYDOWN SPACE INSIDE OF THE BUILDINGS IS NOT AVAILABLE. ALL CONSTRUCTION MATERIALS SHALL BE STORED OUTSIDE OF THE

BUILDINGS IN AN AREA IDENTIFIED BY THE GOVERNMENT.

U.S. DEPARTMENT OF AGRICULTURE

AGRICULTURAL RESEARCH SERVICE

RECIRCULATING AQUACULTURE UPGRADES

CONTRACT NO: 12305B21D0013/12305B24F0110

NATIONAL COLD-WATER MARINE AQUACULTURE CENTER (NCWMAC)

FRANKLIN, ME

SALMON

FARM RD.

NCWMAC

PROJECT

LOCATION.

TAUTON BAYSHORES RD.TAUTON BAY

PUMPHOUSE

S. BAY RD.

CCAR MAIN BUILDING

Emilie Oakes sam ME seal

Agricultural

Service Research

DESCRIPTION

SHEET

DATE

U

NO.

DEPM

SAFETY & HEALTH

REAL PROPERTY

A

DATE

PROJECT NO.

SUSDA

BY

AGRICULTURAL RESEARCH SERVICE

OF

DESIGNER

PROJECT MANAGER

JOB #

CHECKED BY

A-E FIRM USDA AGRICULTURAL RESEARCH SERVICE

NCWMAC

RECIRCULATING AQUACULTURE UPGRADES

FRANKLIN, ME

DRAWING INDEX

G-100 2 2204/18/2025

THT

JEH

AEJ NATIONAL COLD-WATER MARINE

AQUACULTURE CENTER

25 SALMON FARM RD.

FRANKLIN, ME 04634

XXX

3724-E

XXX

XXX

XXX

XXX

SHEET

INDEX OF DRAWINGS

DRAWING NO. TITLE

T-100 1 OF 22 COVER SHEET

G-100 2 OF 22 DRAWING INDEX

M-001 3 OF 22 GENERAL NOTES AND ABBREVIATIONS

M-101 4 OF 22 OVERALL MECHANICAL PLAN

M-102 5 OF 22 OVERALL OZONE DISTRIBUTION PLAN

M-103 6 OF 22 MECHANICAL ROOF PLAN

M-104 7 OF 22 OZONE GENERATOR BUILDING PLAN

M-401 8 OF 22 ENLARGED MECHANICAL PLAN

M-601 9 OF 22 MECHANICAL SCHEDULES

M-602 10 OF 22 MECHANICAL DETAILS

M-603 11 OF 22 MECHANICAL DETAILS

M-604 12 OF 22 MECHANICAL DETAILS

M-605 13 OF 22 MECHANICAL DETAILS

M-606 14 OF 22 OZONE GENERATOR PID

M-607 15 OF 22 OZONE GENERATOR DIAGRAMS

M-608 16 OF 22 MECHANICAL DIAGRAMS

E-001 17 OF 22 ELECTRICAL GENERAL NOTES

E-002 18 OF 22 ELECTRICAL LEGEND

E-101 19 OF 22 POWER PLAN

E-501 20 OF 22 SCHEDULES AND DETAILS

E-601 21 OF 22 POWER RISER

E-602 22 OF 22 PANEL SCHEDULES

GENERAL NOTES:

1. THE CONTRACTOR SHALL VERIFY ALL SITE CONDITIONS BEFORE COMMENCING WORK. THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS, CONDITIONS, AND EXISTING

STRUCTURES AND EQUIPMENT AT THE JOB SITE. THE CONTRACTOR SHALL NOTIFY THE CONTRACTING OFFICER OF ANY DISCREPANCIES FOUND PRIOR TO THE START OF

CONSTRUCTION.

2. THE CONTRACTOR IS REQUIRED TO TAKE PRECAUTIONARY MEASURES TO PROTECT ALL EXISTING UTILITY LINES, STRUCTURES, EQUIPMENT, ETC. IN THE AREAS OF WORK, WHETHER OR NOT SHOWN ON THESE PLANS. ALL DAMAGES CAUSED BY THE CONTRACTOR SHALL BE REPAIRED TO LIKE-NEW CONDITION AND AT THE EXPENSE OF THE CONTRACTOR. IN CASE OF EMERGENCY, IMMEDIATELY NOTIFY THE CONTRACTING OFFICER.

3. CONTRACTOR SHALL PROVIDE THEIR OWN PORTABLE SANITARY FACILITIES IN THE LOCATION APPROVED BY THE CONTRACTING OFFICER. PORTABLE SANITARY

FACILITIES SHALL BE MAINTAINED REGULARLY FOR ODOR CONTROL AND APPEARANCE.

PLUMBING ABBREVIATIONS:

' INCHES

" FEET

ABA ARCHITECTURAL BARIERS ACT

AC AIR COMPRESSOR

AD AIR DRYER

ADA AMERICANS WITH DISABILITIES ACT

AFF ABOVE FINISHED FLOOR

ARCH ARCHITECTURE, ARCHITECTURAL

AWWA AMERICAN WATER WORKS ASSOCIATION

BFP BACKFLOW PREVENTER

CA COMPRESSED AIR

CO CLEANOUT

CW COLD WATER (POTABLE / DOMESTIC)

DEG.,° DEGREES

DHWR DOMESTIC HOT WATER RETURN

DIA DIAMETER

DWG DRAWING

EDF ELECTRIC DRINKING FOUNTAIN

ET EXPANSION TANK

EWH ELECTRIC WATER HEATER

FCO FLOOR CLEANOUT

FD FLOOR DRAIN

FOG FAT OILS GREASE

GAL GALLON(S)

GCO GROUND CLEANOUT

GPF GALLONS PER FLUSH

GPH GALLONS PER HOUR

GPM GALLONS PER MINUTE

HR HOSE REEL

HP HORSEPOWER

HW HOT WATER (POTABLE / DOMESTIC)

HWT HOT WATER STORAGE TANK

HWCP HOT WATER CIRCULATION PUMP

IBC INTERNATIONAL BUILDING CODE

IMB ICE MAKER BOX

ID,I.D. INSIDE DIAMETER

IPC INTERNATIONAL PLUMBING CODE

KW,kW KILOWATT

LB POUNDS

LV LAVATORY

LHO LOW HEAD OXYGENATOR

MFR MANUFACTURER

MS MOP SINK

NPT NATIONAL PIPE THREAD

NTS NOT TO SCALE

02 OXYGEN

03 OZONE

P, PLBG PLUMBING

PDI PLUMBING DRAINAGE INSTITUTE

PH PHASE(S)

PSIG POUNDS PER SQUARE INCH (GAUGE)

RPZ REDUCED PRESSURE ZONE

S, SS SANITARY SEWERS,

SCFM STANDARD CUBIC FEET PER MINUTE

SH SHOWER

SK SINK

SSEW SAFETY SHOWER WITH EYE WASH

T&P TEMPERATURE AND PRESSURE RELIEF VALVE

TYP TYPICAL

U/G UNDERGROUND

UH UNIT HEATER

UR URINAL

V VENT PIPING, VOLTS

VTR VENT THROUGH ROOF

WC WATER CLOSET

WCO WALL CLEANOUT

WH WALL HYDRANT, WATER HAMMER

WHA WATER HAMMER ARRESTOR

WM WATER METER

NOTES:

1. UNDERLINED FIXTURE AND EQUIPMENT MARKS (SUCH AS WC) ARE NOT

ABBREVIATIONS. REFER TO THE PLUMBING SCHEDULE SHEETS, P601 -

P699 FOR FIXTURE AND EQUIPMENT DESCRIPTIONS. FIXTURE MARKS ARE

ALSO LISTED HERE FOR CLARITY.

2. ALL ABBREVIATIONS MAY NOT BE USED IN THIS PROJECT.

NO. DATE BY DESCRIPTION

REVISIONS

U

S

D

A

PROJECT NO.

DATE

Agricultural Research Service

USDA AGRICULTURAL RESEARCH SERVICE

NCWMAC

RECIRCULATING AQUACULTURE UPGRADES

FRANKLIN, ME

SHEET

AGRICULTURE RESEARCH SERVICE

NATIONAL COLD-WATER MARINE

AQUACULTURE CENTER

FRANKLIN, ME 04934

OF

A-E FIRM

PROJECT MANAGER EPM

DESIGNER PPM

CHECKED BY SAFETY & HEALTH

JOB # REAL PROPERTY

USDA

xxxxx xxxxx xxxxx xxxxx xxxxx

3724-M

M-001

GENERAL NOTES AND ABBREVIATIONS

04/18/25

TT

JH

FJ

3 21

1. IT IS THE CONTRACTOR'S RESPONSIBILITY TO FIELD VERIFY ALL DIMENSIONS PRIOR TO FABRICATION OR PURCHASE OF EQUIPMENT, MATERIALS, AND ASSEMBLIES. ANY DEVIATIONS SHALL BE BROUGHT TO THE CONTRACTING OFFICER'S ATTENTION FOR RESOLUTION BEFORE PROCEEDING

WITH ANY CONSTRUCTION, FABRICATION, OR EQUIPMENT PURCHASE.

2. THESE DRAWINGS ARE SCHEMATIC IN NATURE AND ARE NOT INTENDED TO SHOW ALL POSSIBLE CONDITIONS (DO NOT SCALE FOR LOCATIONS).

THE CONTRACTOR SHALL PROVIDE COMPLETE AND SYSTEM AS INDICATED WITH ALL NECESSARY EQUIPMENT, APPURTENANCES AND CONTROLS

REQUIRED.

3. THE CONTRACTOR SHALL REVIEW THE DRAWINGS OF OTHER TRADES AS PART OF THIS CONTRACT FOR ADDITIONAL WORK REQUIRED AND FOR

COORDINATION OF ALL WORK FOR OPERATIONS OF OR CONNECTIONS TO OTHER TRADES.

4. CONTRACTOR SHALL EMPLOY WORKMEN WHO ARE TRAINED AND EXPERIENCED IN NECESSARY SKILLS TO PERFORM INDICATED WORK.

5. MAKE OFFSETS AND TRANSITIONS TO COORDINATE WITH OTHER TRADES WITHOUT ANY ADDITIONAL EXPENSE TO THE OWNER.

6. CONTRACTOR SHALL PROVIDE COORDINATION/SHOP DRAWINGS OF ALL PIPING BEFORE FABIRCATION OR INSTALLATION OF PIPING.

7. CONTRACTOR SHALL FIELD VERIFY EXACT LOCATIONS AND POINTS OF CONNECTIONS TO ALL UTILITIES AND SHALL COORDINATE WITH OTHER

TRADES.

8. REFER TO SPECIFICATIONS, SHEET NOTES, DETAILS AND SCHEDULES FOR ADDITIONAL REQUIREMENTS PERTAINING TO THE WORK.

9. ALL WORK (MATERIALS, EQUIPMENT, DEVICES, COMPONENTS, SYSTEMS, SUPPORTS, ETC.) MUST COMPLY WITH THE REQUIREMENTS OF ALL CODES, CODE AMENDMENTS, AND ORDINANCES AS USED, ADOPTED AND/OR ENFORCED BY THE LOCAL JURISDICTION, COUNTY AND STATE IN WHICH THE PROJECT IS LOCATED. WHERE INSPECTIONS ARE REQUIRED BY C.O., WORK MUST NOT BE CONCEALED UNTIL INSPECTIONS AND

TESTS ARE COMPLETED AND ACCEPTED. REFER TO SPECIFICATIONS FOR APPLICABLE CODES.

10. SCHEDULES, NOTES OR SPECIFICATIONS MAY REFERENCE "BASIS OF DESIGN" INFORMATION REGARDING A SPECIFIC MANUFACTURER OR MODEL NUMBER. SUCH INFORMATION IS PROVIDED SO AS TO ESTABLISH A STANDARD OF PERFORMANCE, QUALITY, FEATURES AND OPTIONS (SEE SCHEDULES AND SPECIFICATIONS). THE INTENT IS NOT TO LIMIT COMPETITION. EQUIVALENT EQUIPMENT OF OTHER MANUFACTURERS SHALL BE ACCEPTABLE PROVIDED SUCH EQUIPMENT EQUALS OR EXCEEDS THE BASIS OF DESIGN EQUIPMENT IN PERFORMANCE, QUALITY, FEATURES AND

OPTIONS WHETHER SPECIFIED, SCHEDULED OR NOTED.

11. ALL EQUIPMENT FURNISHED FOR THIS PROJECT MUST COMPLY WITH THE "BUY AMERICAN ACT".

12. ALL WORK IS TO BE FABRICATED AND/OR ERECTED USING CONTRACTOR'S FIELD MEASUREMENTS FOR PROPER COORDINATION WITH WORK OF

OTHER TRADES.

13. INFORMATION AND COMPONENTS SHOWN ON DIAGRAMS OR DETAILS, BUT NOT SHOWN ON PLANS, AND VICE VERSA, MUST BE PROVIDED AS IF

EXPRESSLY REQUIRED BY BOTH.

14. EXCEPT WHERE INDICATED OTHERWISE, THE NOTATION OR DESCRIPTION OF ANY ITEM IN THE CONTRACT DOCUMENTS CARRIES WITH IT THE INSTRUCTION TO FURNISH AND INSTALL THE ITEM, WHETHER OR NOT THIS INSTRUCTION IS EXPLICITLY STATED.

15. ALL WORK SHALL BE INSTALLED SO AS MAINTAIN ANY "UL" ASSEMBLY RATINGS, FIRE RATINGS OR SMOKE BARRIER CAPABILITIES OF WALLS, PARTITIONS, FLOORS AND ROOF. SEAL AROUND AND PLACE UL RATED FIRE-STOP MATERIAL AT ANY PENETRATION OR DISTURBANCE OF SUCH

ASSEMBLIES. COORDINATE WITH ARCHITECTURAL PLANS AND CONTRACTOR.

16. COORDINATE PLACEMENT OF ALL WORK WITH OTHER TRADES. DO NOT LOCATE, POSITION OR INSTALL ANY WORK IN SUCH A WAY THAT SYSTEM COMPONENTS OR ACCESS DOORS SHALL BE INACCESSIBLE, UNUSABLE OR UN-MAINTAINABLE AFTER CONSTRUCTION IS COMPLETED. COMPLY

WITH MANUFACTURER'S MINIMUM RECOMMENDED SERVICE CLEARANCES.

17. UNLESS OTHERWISE INDICATED, ALL WORK SHALL FROM STRUCTURE ABOVE, FROM WALLS, FROM COLUMNS, OR FROM THE FLOOR. DO NOT USE THE INSTALLED WORK OF OTHER TRADES, OR WORK RELATED TO ANY SUPPORT SYSTEMS FOR SUPPORT FOR OTHER TRADES.

18. PROVIDE PIPE TRANSITIONS REQUIRED AT FIXTURE CONNECTIONS WHERE PIPE SIZES INDICATED DIFFER FROM THE FIXTURE CONNECTION SIZE.

GENERAL NOTES:

M-401

M-401

M-401

M-401

EXISTING 25 TON CHILLER

NO. DATE BY DESCRIPTION

REVISIONS

U

S

D

A

PROJECT NO.

DATE

Agricultural Research Service

USDA AGRICULTURAL RESEARCH SERVICE

NCWMAC

RECIRCULATING AQUACULTURE UPGRADES

FRANKLIN, ME

SHEET

AGRICULTURE RESEARCH SERVICE

NATIONAL COLD-WATER MARINE

AQUACULTURE CENTER

FRANKLIN, ME 04934

OF

A-E FIRM

PROJECT MANAGER EPM

DESIGNER PPM

CHECKED BY SAFETY & HEALTH

JOB # REAL PROPERTY

USDA

xxxxx xxxxx xxxxx xxxxx xxxxx

3724-M

M-101

OVERALL MECHANICAL PLAN

04/18/25

TT

JH

FJ

4 21

3/32" = 1'-0"M-101

OVERALL MECHANICAL PLAN1

N

SCALE: = 1'-0"3/32"

0 11 21 3211

EXISTING 02 SUPPLY LINE UP FROM SLAB. CONNECT

NEW 1" LINE AFTER SHUT OFF AND ROUTE 1" LINE TO

OZONE GENERATOR.

PROVIDE 3/4" O3 SUPPLY LINE TYPICAL

PROVIDE OZONE

DISTRIBUTION MANIFOLD

PROVIDE 02 FILTRATION AND

REGULATING ASSEMBLY SEE

DETAIL 2/M607

PROVIDE 3/4" STAINLESS STEEL O3 SUPPLY LINE ACROSS MEZZANINE TYPICAL

C-1

C-3

C-2

M-401

NO. DATE BY DESCRIPTION

REVISIONS

U

S

D

A

PROJECT NO.

DATE

Agricultural Research Service

USDA AGRICULTURAL RESEARCH SERVICE

NCWMAC

RECIRCULATING AQUACULTURE UPGRADES

FRANKLIN, ME

SHEET

AGRICULTURE RESEARCH SERVICE

NATIONAL COLD-WATER MARINE

AQUACULTURE CENTER

FRANKLIN, ME 04934

OF

A-E FIRM

PROJECT MANAGER EPM

DESIGNER PPM

CHECKED BY SAFETY & HEALTH

JOB # REAL PROPERTY

USDA

xxxxx xxxxx xxxxx xxxxx xxxxx

3724-M

M-102

OVERALL OZONE DISTRIBUTION PLAN

04/18/25

TT

JH

FJ

5 21

3/32" = 1'-0"M-102

OVERALL OZONE PLAN1

SCALE: = 1'-0"3/32"

0 11 21 3211

OZ

R1

R2

Z

R1

Z

R1

Z

R1

Z

R1

Z Z Z

R1 R1

NOTES

PROVIDE AMBIENT OXYGEN MONITOR WITH

AUDIBLE AND VISUAL ALARM.

R2

Z

O

R1

PROVIDE AMBIENT OZONE MONITOR WITH AUDIBLE

AND VISUAL ALARM. INTERLOCK WITH OZONE

GENERATOR.

PROVIDE OXIDATION REDUCTION POTENTIAL

SENSOR. MOUNT SENSOR IN LOW HEAD

OXYGENATOR HEAD BOX. INTERLOCK WITH OZONE

DOSING CONTROL SYSTEM FOR DOSING CONTROL.

PROVIDE OXIDATION REDUCTION POTENTIAL

SENSOR. MOUNT SENSOR IN TANK STAND BOX OF

THE USERS DISCRESSION. INTERLOCK WITH OZONE

DOSING CONTROL SYSTEM FOR DOSING CONTROL.

R2 R2

R2R2R2

EXISTING 25 TON CHILLER

Emilie Oakes sam ME seal

ChristopherG.Morris Line

ChristopherG.Morris Line

1 112 3 4 5 6 7 8 9 10

A

B

C

D

E

F

G

H

PLAN

NORTH

SCALE:

ROOF PLAN

3/32" = 1'-0"

M-103 PLAN

NORTH

GRAPHIC SCALE

KEYED NOTES:

1. PROVIDE SNOW / ICE GUARD AS INDICATED. LOCATED

1' BACK FROM ROOF EAVE. SEE DETAIL 4/M-605.

COORDINATE OVERALL LENGTH WITH MECHANICAL TO

PROTECT MECHANICAL EQUIPMENT AND MODULAR

BUILDING AT GRADE BELOW.

GENERAL DEMO NOTES:

A. CONTRACTOR SHALL FIELD VERIFY ALL DIMENSIONS

AND BRING ANY DISCREPANCIES TO THE ATTENTION OF

THE CONTRACTING OFFICER.

B. PROTECT EXISTING EQUIPMENT TO REMAIN DURING

CONSTRUCTION

C. THE BUILDING SHALL REMAIN WATERTIGHT

THROUGHOUT THE CONSTRUCTION PROCESS.

D. EXISTING ROOF PITCH IS 2:12 AND SHOULD REMAIN.

EXISTING DORMERS

U

D A

S

MECHANICAL ROOF PLAN

M-103

1 20' 20'

20'

EXISTING DORMERS

EXISTING DORMERSEXISTING DORMERS

Emilie Oakes sam ME seal

ChristopherG.Morris Line

OUTLINE OF FIBERGLASS BUILDING

VARIES

12"

6"

#4 @ 12" O.C., E.W.

2"

3"

#4 VERT. @ 12" O.C.

(6) #4 HORZ.

3/4" CHAMFER

PPM

REVISIONS

Agricultural

Service Research

DESCRIPTION

SHEET

DATE

U

NO.

DEPM

SAFETY & HEALTH

REAL PROPERTY

A

DATE

PROJECT NO.

SUSDA

BY

AGRICULTURAL RESEARCH SERVICE

OF

DESIGNER

PROJECT MANAGER

JOB #

CHECKED BY

A-E FIRM USDA AGRICULTURAL RESEARCH SERVICE

NCWMAC

RECIRCULATING AQUACULTURE UPGRADES

FRANKLIN, ME

OZONE GENERATOR BUILDING

M-104 7 2204/18/2025

THT

JEH

AEJ NATIONAL COLD-WATER MARINE

AQUACULTURE CENTER

25 SALMON FARM RD.

FRANKLIN, ME 04634

XXX

3724-E

XXX

XXX

XXX

XXX

'-0

13'-0"

KEYED NOTES

1 EQUIPMENT PAD, SEE 3/M-605 FOR DETAILS AND REINFORCING

2 18" X 18" EXHAUST LOUVER FOR EF-1

3 18" X 18" INTAKE LOUVER

4 LIFTING EYE , TYPE OF 4

5 PREFABRICATED FIBERGLASS EQUIPMENT BUILDING. PROVIDE COMPLETE WITH ELECTRICAL

DISTRIBUTION PANEL, WALL LOUVERS, CONVENIENCE OUTLETS, ELECTRICAL HEATER, DOORS

AND ALL OTHER MISCELLANEOUS EQUIPMENT AND DEVICES NECESSARY FOR AN OPERATIONAL

EQUIPMENT BUILDING. ADJUST SLAB DIMENSIONS TO COMPLY WITH PRE-FAB BUILDING

MANUFACTURER'S REQUIREMENTS. ALL ELECTRICAL COMPONENTS INSIDE AND WITHIN 5' OF

OPENING SHALL BE CLASS 1 DIVISION 1. PROVIDE 1/2" VERTICAL DROP AT BUILDING FOUNDATION

AND SLOPE TO DRAIN AWAY BUILDING AT 1/4" IN 12".

6 PROVIDE SUFFICIENT ANCHORAGE TO PREVENT UPLIFT OR MOVEMENT IN DESIGN WIND EVENT.

7 4' X 7' X 6" CONCRETE LANDING, REINFORCE WITH W 6X6, 2.4 X 2.4 WWF

8 STEEL SUPPORT FRAME

9 (2) 3' X 7'4" FIBERGLASS DOORS, D0012 FRAME AND HARDWARE BY BUILDING MANUFACTURER

10 SNOW AND ICE GUARD BY BUILDING MANUFACTURER

11 COORDINATE PAD LOCATION AND SIZE WITH TRANSFORMER SELECTION. PAD MUST EXTEND

MINIMUM 6-IN FROM ALL SIDES OF TRANSFORMER.

PLAN

NORTH

8'- 8"

A

PP

RO

X.

8'- 8"

, A

PP

RO

X.

9'-10" 13'- 5", APPROX.

7'-0"

4'- 0"

12'-0"

7'- 0"

SCALE:

FLOOR PLAN

NONE

M-104

SCALE:

NORTH ELEVATION

NONE

M-104

SCALE:

EAST ELEVATION

NONE

M-104

SCALE:

SOUTH ELEVATION

NONE

M-104

SCALE:

WEST ELEVATION

NONE

M-104

APPROX. FINISHED

GRADE

APPROX. FINISHED

GRADE

APPROX. FINISHED

GRADE

6"

6"

TOP OF SLAB

TOP OF SLAB

TOP OF SLAB

6"

6"

3 9

#MINIMUM DESIGN LOADS AND REQUIREMENTS IN ACCORDANCE WITH IBC 2021

LIVE FLOOR LOAD

COLLATERAL

ROOF LIVE LOAD

GROUND SNOW LOAD

ICE ACCUMULATION

WIND DESIGN DATA:

ULTIMATE WIND SPEED

WIND IMPORTANCE FACTOR

WIND EXPOSURE

EARTHQUAKE DESIGN DATA:

SEISMIC IMPORTANCE FACTOR

SS

S1

SDS

SD1

100 PSF

10 PSF

20 PSF

82 PSF

0.86 INCHES @ 55 MPH

117 MPH

1.0 C

1.0 0.25 0.06 0.2

0.09

OZ-1

UH-1

M-104

CH-1

2'-0"

2'-0"EXISTING BUILDING

EXISTING BUILDING

SCALE: 3/4"=1'-0"

0 1' 2' 4'

SCALE:

TYP. FOUNDATION DETAIL

3/4" = 1'-0"

M-104

1 11

EXISTING SUMP AND PUMPS

EXISTING BIOFILTER

EXISTING LHO

EXISTING DRUM

FILTER

CH-1

OZ-1 EF-1

UH-1

1" O2 SUPPLY LINE

PROVIDE OZONE DISTRIBUTION

MANIFOLD

02 FILTRATION AND

REGULATING ASSEMBLY SEE

DETAIL 2/M607

EXISTING 25 TON CHILLER

PROVIDE OZONE GENERATOR

BUILDING SEE SHEET M-104

C-1

EXISTING SUMP AND PUMPS

EXISTING BIOFILTER

EXISTING LHO

EXISTING DRUM

FILTER

CB-1

PROVIDE EQUIPMENT PAD,

ACOUSTAL MAT ON EXTERIOR

OF EXISTING BUILDING, AND 3

SIDED ACOUSTICAL SCREEN.

SEE SHEET M-605

C-2

EXISTING SUMP

AND PUMPS

EXISTING

BIOFILTER

EXISTING

LHO

EXISTING DRUM

FILTER

CB-2

PROVIDE EQUIPMENT PAD,

ACOUSTAL MAT ON EXTERIOR

OF EXISTING BUILDING, AND 3

SIDED ACOUSTICAL SCREEN.

SEE SHEET M-605

C-3

EXISTING SUMP

AND PUMPS

EXISTING

BIOFILTER

EXISTING

LHO

EXISTING DRUM

FILTER

PROVIDE EQUIPMENT PAD,

ACOUSTAL MAT ON

EXTERIOR OF EXISTING

BUILDING, AND 3 SIDED

ACOUSTICAL SCREEN. SEE

SHEET M-605

CB-3

NO. DATE BY DESCRIPTION

REVISIONS

U

S

D

A

PROJECT NO.

DATE

Agricultural Research Service

USDA AGRICULTURAL RESEARCH SERVICE

NCWMAC

RECIRCULATING AQUACULTURE UPGRADES

FRANKLIN, ME

SHEET

AGRICULTURE RESEARCH SERVICE

NATIONAL COLD-WATER MARINE

AQUACULTURE CENTER

FRANKLIN, ME 04934

OF

A-E FIRM

PROJECT MANAGER EPM

DESIGNER PPM

CHECKED BY SAFETY & HEALTH

JOB # REAL PROPERTY

USDA

xxxxx xxxxx xxxxx xxxxx xxxxx

3724-M

M-401

ENLARGED MECHANICAL PLAN

04/18/25

TT

JH

FJ

8 21

1/4" = 1'-0"M-401

ENLARGED OZONE GENERATOR PLAN1

1/4" = 1'-0"M-401

ENLARGED BROOD 3 MECHANICAL PLAN2

SCALE: = 1'-0"

0 4 84

1/4"

1/4" = 1'-0"M-401

ENLARGED PARR MECHANICAL PLAN3

1/4" = 1'-0"M-401

ENLARGED SMOLT 2 MECHANICAL PLAN4

KEYED NOTES

PROVIDE COOLING WATER PIPING FROM CH-1 TO

OZ-1 IN ACCORDANCE WITH MANUFACTURER'S

WRITTEN RECCOMENDATIONS AND 3/M-607. PROVIDE

ALL PIPING, VALVES, ADN ALUMINUM JACKETING.

Emilie Oakes sam ME seal

ChristopherG.Morris Line

ChristopherG.Morris Line

SamEngle Line

SamEngle

NO. DATE BY DESCRIPTION

U

S

D

A

PROJECT NO.

DATE

Agricultural Research Service

USDA AGRICULTURAL RESEARCH SERVICE

NCWMAC

RECIRCULATING AQUACULTURE UPGRADES

FRANKLIN, ME

SHEET

AGRICULTURE RESEARCH SERVICE

NATIONAL COLD-WATER MARINE

AQUACULTURE CENTER

FRANKLIN, ME 04934

OF

A-E FIRM

PROJECT MANAGER EPM

DESIGNER PPM

CHECKED BY SAFETY & HEALTH

JOB # REAL PROPERTY

USDA

xxxxx xxxxx xxxxx xxxxx xxxxx

3724-M

M-601

MECHANICAL SCHEDULES

04/18/25

TT

JH

FJ

9 21

C-3 15 SMOLT 2 R454B 115 50 460/3/60 29.9 40 87 x 46 x 51 11

C-2 20 PARR R454B 115 50 460/3/60 40.8 50 87 x 68 x 51 11

C-1 15 BROOD 3 R454B 115 50 460/3/60 29.9 40 87 x 46 x 51 11

MARK

NOMINAL

TONNAGE

AREA SERVED REFRIGERANT

AMBIENT

DESIGN TEMP

SUMMER (F DB)

AMBIENT

DESIGN TEMP

WINTER (F DB)

VOLTAGE/PHASE/

FREQUENCY

MCA MOCP DIMENSIONS (LxWxH) (INCH) EER

CONDENSER UNIT SCHEDULE

CB-3 15 C-3 SMOLT 2 42.8 70 50 1 150 3 18 x 16.56 x 60 <5 23.2

CB-2 20 C-2 PARR 50 70 50 1 120 3 18 x 16.56 x 80 <5 23.2

CB-1 15 C-1 BROOD 3 50 70 50 1 150 3 18 x 16.56 x 60 <5 23.2

MARK

NOMINAL

TONNAGE

ASSOCIATED

CONDENSING

UNIT

AREA SERVED

DESIGN WATER

TEMP (F)

AMBIENT INDOOR

DESIGN TEMP (F)

AMBIENT DESIGN

TEMP WINTER (F DB)

EVAPORATOR

QUANTITY

FLOW RATE PER

EVAPORATOR

(GPM)

AQUATIC

CONNECTION

(IN)

DIMENSIONS (LxWxH) (INCH)

PRESSURE

DROP AT MAX

FLOW (PSI)

IEER

CHILLER BARREL SCHEDULE

OZ-1 31.2 52.9 0-100% YES 4.5 30 50 480/3/60 49 70 42 x 37 x 83 1200 NEMA 12

MARK

OZONE OUTPUT 10%

CONCENTRATION

(PPD)

LOX SUPPLY AT 10%

CONCENTRATION PER

LB OF OZONE (SLPM)

MAX TURNDOWN

RANGE

INTEGRATED

CHILLER

COOLING LOAD

(TON)

COOLING WATER

GLYCOL %

AMBIENT DESIGN

TEMP WINTER (F DB)

VOLTAGE/PHASE/

FREQUENCY

MCA MOCP DIMENSIONS (LxWxH) (INCH)

WEIGHT

(LBS)

ENCLOSURE

OZONE GENERATOR SCHEDULE

UNIT HEATER SCHEDULE

MARK SERVES AIRFLOW CFM TEMPERATURE RISE KW FAN HP FUEL VOLT/PHASE WEIGHT (LBS) REMARKS

UH-1 OZONE GENERATOR BUILDING 530 45 °F 7.5 1/40 ELECTRIC 480/3 52 ALL

EXHAUST FAN SCHEDULE

MARK

SERVES

EXTERNAL STATIC

PRESSURE (IN. WC.)

AIRFLOW

(CFM)

FAN RPM FAN HP

ELECTRICAL

(V/C/P)

FLA

MAX

SONES

WEIGHT

(LBS)

REMARKS

EF-1 OZONE GENERATOR BUILDING .15 100 1332 .1 115/60/1 .1 3 15 SPARK B RATED

NOTES:

1. PROVIDE WITH FACTORY PROVIDED MOUNTING KIT.

2. PROVIDE WITH WALL MOUNTED THERMOSTAT SET TO 55 DEG. F.

NOTES:

1. PROVIDE WITH BACKDRAFT DAMPERS.

2. PROVIDE WITH MESH INSECT SCREEN.

3. EXHAUST FANS SHALL BE SUPPLIED WITH CORROSION PROTECTION SUITABLE FOR INSTALLATION IN DAMP ENVIRONMENTS.

4. FAN IS TO BE OF SPARK B RATED OR BETTER.

CH-1 4.5 54,000 R410A 95 10 45 55 460/3/60 14 50 x 27 x 55 800

MARK

NOMINAL

TONNAGE

CAPACITY REFRIGERANT

AMBIENT DESIGN

TEMP SUMMER (F DB)

GPM

ENTERING WATER

TEMP (F)

LEAVING WATER

TEMP (F)

VOLTAGE/PHASE/

FREQUENCY

FLA

DIMENSIONS

(LxWxH) (INCH)

WEIGHT

CHILLER SCHEDULE

NOTES:

1. PROVIDE WITH CIRCULATING PUMP, EXPANSION TANK, STRAINER, AND 30% GLYCOL..

2 SERVES OZ-1.

NOTES:

1. PROVIDE WITH TITANIUM TUBE HEAT EXCHANGERS.

2. PROVIDE WITH 316 STAINLESS STEEL BASE AND HARDWARE.

3. PROVIDE WITH MARINE GRADE ALUMINUM JACKET.

4. PROVIDE WITH THERMOWELL AND FLOW SWITCH INSTALLED ACCORDING TO MANUFACTURES INSTRUCTIONS .

5. PROVIDE WITH TEMPERATURE CONTROLLER.

NOTES:

1. PROVIDE WITH MARINE GRANDE CONDENSER COIL

2. PROVIDE WITH LOW AMBIENT MOTOMASTER KIT.

NOTES:

1. PROVIDE WITH MANUFACTURER SUPPLIED OIL FREE AIR COMPRESSER FOR VALVE ACTUATION.

2. PROVIDE WITH CLOSED LOOP GENERATOR COOLING SYSTEM (CH-1).

3. ENCLOSURE SHALL BE NEMA 4X CONSTRUCTION.

4. PROVIDE WITH AUTOMATED CONTROLLER AND PLC.

5. PROVIDE WITH AMBIENT O3 AN 02 SENSOR WITH ALARM AS INDICATED

6. PROVIDE WITH ORP SENSORS AS INDICATED FOR OZONE DOSING CONTROL.

7. PROVIDE WITH 02 FILTRATION AND REGULATING ASSEMBLY AS INDICATED.

8. PROVIDE WITH OZONE DISTRIBUTION MANIFOLD WITH 10 OUTLETS (7 FOR USE 3 SPARES).

Emilie Oakes sam ME seal

ChristopherG.Morris Line

PIPE

INSULATION

CLEVIS HANGER

WASHER (TOP & BOTTOM)

NUT (TOP & BOTTOM)

ALL THREAD ROD

INSULATION

PROTECTIVE

SHEET METAL SHIELD

PIPING

FOAM INSULATION -OR- FIRE STOP

MATERIAL (FOR FIRE RATED PARTITIONS)

PIPE INSULATION AS APPLICABLE

WALL

20 GA.

MIN.

METAL

SLEEVE

CAULK ALL JOINTS AND

SLEEVE ENDS WATERTIGHT

PIPE PENETRATION NOTES:

1. PROVIDE WITH PITCH POCKET CONSTRUCTION, ADDITIONAL FLASHING OR WEATHER CAP AS

REQUIRED FOR WATERPROOF CONSTRUCTION. DO NOT MECHANICALLY ATTACH PIPE TO

STRUCTURE IN ANY WAY.

2. SPACE BETWEEN PIPE AND SLEEVE SHALL BE FREE FROM ANY FOREIGN MATERIALS.

3. PIPE SHALL NOT CONTACT STRUCTURE AT ANY TIME. WEDGES ARE NOT TO BE USED TO MAINTAIN

PIPE POSITION.

4. PIPE MUST BE APPROXIMATELY CENTERED IN OPENING.

NOTE:

PROVIDE MIN

ANCHOR SUPPORT

SPACING EVERY 3'

VERTICALLY

FOR PIPES < 4"∅

FOR PIPES< 2"∅

TYP TO UNISTRUT

P2500 SERIES PIPE

STRAP

INSULATE AS REQD

SECURE W/APPROVED

ANCHOR TO MATCH BASE

MATERIAL AND LOAD

REQUIREMENTS

TYP TO UNISTRUT

P 1000 12 GA

CHANNEL

WALL

TYP TO UNISTRUT

P3400 SERIES PIPE

STRAP

INSULATE AS REQD

SECURE W/APPROVED

ANCHOR TO MATCH BASE

MATERIAL AND LOAD

REQUIREMENTS

TYP TO UNISTRUT

P 1000 12 GA

CHANNEL

WALL

NOTES:

PROVIDE MIN ANCHOR

SUPPORT SPACING

EVERY 3' VERTICALLY

AS REQD

PIPE

NON-INSULATED

INSULATED PIPE

HANGER RODS

NOTES:

REQUIREMENT W/SAFETY FACTOR OF 5

MEMBER APPROVED TO SATISFY LOAD

SIZE RODS, SPRING CUSHION, AND HORIZONTAL

W/OR W/OUT

PROTECTIVE

SADDLE OR SHIELD AS

REQD

UNISTRUT TYPE

SUPPORT

UNIT HEATER SHALL BE SECURED

TO WALL WITH A MINIUMIM OF TWO

BRACKETS PER MANUFACTURERS

RECOMMENDATIONS OF HEATER

AND PRE-FAB BUILDING.

TWO 5/8" BOLTS, EACH SIDE OF

FRAME WITH LOCK WASHERS

ELECTRIC UNIT HEATER

SECURED TO WALL PER

MANUFACTURER'S

GUIDELINES BASED ON WALL

TYPE

NO. DATE BY DESCRIPTION

REVISIONS

U

S

D

A

PROJECT NO.

DATE

Agricultural Research Service

USDA AGRICULTURAL RESEARCH SERVICE

NCWMAC

RECIRCULATING AQUACULTURE UPGRADES

FRANKLIN, ME

SHEET

AGRICULTURE RESEARCH SERVICE

NATIONAL COLD-WATER MARINE

AQUACULTURE CENTER

FRANKLIN, ME 04934

OF

A-E FIRM

PROJECT MANAGER EPM

DESIGNER PPM

CHECKED BY SAFETY & HEALTH

JOB # REAL PROPERTY

USDA

xxxxx xxxxx xxxxx xxxxx xxxxx

3724-M

M-602

MECHANICAL DETAILS

04/18/25

TT

JH

FJ

10 21

NOT TO SCALEM-602

CLEVIS HANGER DETAIL1

NOT TO SCALEM-602

PIPE WALL PENETRATION DETAIL2

NOT TO SCALEM-602

VERTICAL WALL MOUNTED PIPING DETAIL4

NOT TO SCALEM-602

TRAPEZE HANGER DETAIL3

NOT TO SCALEM-602

UNIT HEATER WALL MOUNT DETAIL5

PROCESS WATER SUPPLY FROM SUMP

PROCESS WATER DISCHARGE TO LHO

BALANCING VALVE

ISOLATION VALVE

PROVIDE CHILLER BARREL

CHILLER BARREL SUPPLY

CONNECTION POINT

CHILLER BARREL

RETURN CONNECTION

POINT

3"ø

"ø

EXISTING SUMP AND SUMP PUMPS

EXISTING BIO FILTER

EXISTING LHO

HEAD BOX

30.0000

CONNECT TO

EXISTING 3" ACCESS

PIPE AND VENT TO

ROOF

3" LHO VENT TO EXTERIOR

SIDEWALL

CONNECT NEW OZONE

SUPPLY LINES TO EXISTING

OZONE AND OXYGEN INTAKE

BEHIND SKIRT ACCESS

RETAIN OXYGEN SUPPLY

LINES AND INTAKE

PROVIDE 3/4" OZONE SUPPLY LINE

NO. DATE BY DESCRIPTION

REVISIONS

U

S

D

A

PROJECT NO.

DATE

Agricultural Research Service

USDA AGRICULTURAL RESEARCH SERVICE

NCWMAC

RECIRCULATING AQUACULTURE UPGRADES

FRANKLIN, ME

SHEET

AGRICULTURE RESEARCH SERVICE

NATIONAL COLD-WATER MARINE

AQUACULTURE CENTER

FRANKLIN, ME 04934

OF

A-E FIRM

PROJECT MANAGER EPM

DESIGNER PPM

CHECKED BY SAFETY & HEALTH

JOB # REAL PROPERTY

USDA

xxxxx xxxxx xxxxx xxxxx xxxxx

3724-M

M-603

MECHANICAL DETAILS

04/18/25

TT

JH

FJ

11 21

1/2" = 1'-0"M-603

TYPICAL SINGLE CHILLER BARREL SECTION1

SCALE: = 1'-0"

0 2 42

1/2"

KEYED NOTES

MODIFY EXISTING PIPING TO COMPLETE

INSTALLATION OF NEW EQUIPMENT.

NOT TO SCALEM-603

TYPICA LHO SECTION2

EXPOSED URETHANE SEALANT

3/8" (MIN) FILLET

PENETRATION PERIMETER SEAL

COVER PLATE ASSEMBLYWALL PANEL

PENETRANT

BOTTOM COVER PLATE

BOTTOM COVER PLATE INSTALLATION

URETHANE SEALANT

PENETRANT

RIVET OR SCREW

(TYP)

WALL PANEL

TOP COVER PLATE INSTALLATION

BOTTOM COVER PLATE

URETHANE SEALANT

TOP COVER PLATE

PENETRANT

WALL PANEL

RIVET OR SCREW

(TYP)

1/4" PANCAKE FASTENER

@ 8"O.C. TYP.

WALL PANEL

TRIM. CONT. @ OPENING

FRAME OPENING WITH GALV. ANGLE.

1/8" Ø RIVETS @ 8" O.C.

SEALANT TAPE CONT. BUTYL SEALANT. CONT.

CLOSED CELL SPRAY FOAM INSULATION:

TIGER FOAM E-84 FIRE RATED SPF CLASS 1

SPRAY FOAM SYSTEM. OR APPROVED EQUAL

PAINT EXTERIOR OF INSULATION WITH ACRYLIC

ELASTOMERIC PAINT EQUAL TO: SHERWIN-WILLIAMS:

1CT LOXON MASONRY PRIMER 1 CT CONFLEX HIGH

BUILD

BACKER SHEET EQUAL TO: INSULWEB POLYPROPYLENE

FABRIC AS MANUFACTURED BY HANES ENGINEERING

MATERIALS.

WRAP PENETRANT IN BACKER SHEET TO PREVENT

ADHESION OF INSULATION. THIS IS TO ALLOW FOR

MOVEMENT.

EXPOSED URETHANE SEALANT

3/8" (MIN) FILLET

PENETRATION PERIMETER SEAL

COVER PLATE ASSEMBLY

WALL PANEL

BOTTOM COVER PLATE

BOTTOM COVER PLATE INSTALLATION

URETHANE SEALANT

PENETRANT

RIVET OR SCREW

(TYP). @ 6"O.C.

WALL PANEL

TOP COVER PLATE INSTALLATION

BOTTOM COVER PLATE

URETHANE SEALANT

TOP COVER PLATE

PENETRANT

WALL PANEL

RIVET OR SCREW

(TYP)

SINGLE PENETRATION LIMITED IN-LINE PENETRATIONS

NOTE: SEE ELEVATION FOR NUMBER AND

APPROXIMATE SIZE OF PENETRATIONS.

NOTE: WATERTIGHT SEAL REQUIRED AT ALL

PENETRATIONS

PENETRANT. SEE ELEVATIONS FOR APPROXIMATE SIZE AND

TYPE. FIELD VERIFY

2"

5"@ 3" ANGLE GIRT.

10"@ 8" CHANNEL GIRT

NEW 1" 22GA Z FURRING, SPACED 16" O.C. MAX,

SECURE WITH MAXIMUM 2 ANCHORS

UNISTRUT FOR MOUNTING WALL ITEMS

(CONDUIT, ELECTRICAL BOXES,

CONTROL PANELS, ETC.)

INSIDEOUTSIDE

SCALE:

MULTIPLE PENETRATION THROUGH WALL DETAIL

NONE

M-604

PPM

REVISIONS

Agricultural

Service Research

DESCRIPTION

SHEET

DATE

U

NO.

DEPM

SAFETY & HEALTH

REAL PROPERTY

A

DATE

PROJECT NO.

SUSDA

BY

AGRICULTURAL RESEARCH SERVICE

OF

DESIGNER

PROJECT MANAGER

JOB #

CHECKED BY

A-E FIRM USDA AGRICULTURAL RESEARCH SERVICE

NCWMAC

RECIRCULATING AQUACULTURE UPGRADES

FRANKLIN, ME

MECHANICAL DETAILS

M-604 12 2204/18/2025

THT

JEH

AEJ NATIONAL COLD-WATER MARINE

AQUACULTURE CENTER

25 SALMON FARM RD.

FRANKLIN, ME 04634

XXX

3724-E

XXX

XXX

XXX

XXX

SCALE:

TYPICAL UNITSTRUT MOUNTING DETAIL

NONE

M-604

SCALE:

TYPICAL SINGLE OR LIMITED PENETRATION DETAIL

NONE

M-604

STANDING SEAM METAL ROOF

INSULATION

CLAMPING RING FASTENERS SET IN MASTIC

3" VENT

STAINLESS STEEL BAND CLAMP

PREFABRICATED ROOF PENETRATION BOOT

SEALANT

BED OF MASTIC

FACE OF EXISTING BUILDING

EQUIPMENT SLAB SEE

DETAIL THIS SHEET

OUTLINE OF MECH.

EQUIPMENT

SCALE:

MECHANICAL SCREEN PLAN

NONE

M-605

1'- 0"

4"

B 2'-

0"

4"

2'-0" A 2'-0"

A + 2'-0" OR B + 2'-0"

SCALE:

MECHANICAL SCREEN ELEVATION

NONE

M-605

6" 4'-

0" 1'-

0" 3'-

6"

1'-4"

APPROX FINISHED GRADE

PPM

REVISIONS

Agricultural

Service Research

DESCRIPTION

SHEET

DATE

U

NO.

DEPM

SAFETY & HEALTH

REAL PROPERTY

A

DATE

PROJECT NO.

SUSDA

BY

AGRICULTURAL RESEARCH SERVICE

OF

DESIGNER

PROJECT MANAGER

JOB #

CHECKED BY

A-E FIRM USDA AGRICULTURAL RESEARCH SERVICE

NCWMAC

RECIRCULATING AQUACULTURE UPGRADES

FRANKLIN, ME

MECHANICAL DETAILS

M-605 13 2204/18/2025

THT

JEH

AEJ NATIONAL COLD-WATER MARINE

AQUACULTURE CENTER

25 SALMON FARM RD.

FRANKLIN, ME 04634

XXX

3724-E

XXX

XXX

XXX

XXX

12" TYP

NON-SLIP 'BROOMED' FINISH

(4)#4 CONTINUOUS

#4 12" OC MAX E.W.

COMPACTED MATERIAL (95%

STANDARD PROTECTOR)

BROAD SWEEP CONDUIT

AS REQ'D

TURNDOWN ALL

SIDES, TYP.

#4 STIRRUP @ 12" O.C.

3/4" CHAMFER

6" THICK

PAD MINIMUM

1'

4"

KEYED NOTES

1. 4X4 COMPOSITE POST

2. COMPOSITE SCREEN PANEL

3. STAINLESS STEEL CLIP TO ALLOW REMOVAL OF PANEL, TYPICAL ALL

PANELS

4. COMPOSITE FINAL

5. 1" ACOUSTICAL MAT ATTACHED TO WALL PANELS AS RECOMMENDED

BY MANUFACTURER 135" X 54"

6. 16" X 42" CONCRETE FOOTING

7. SLOPE TO DRAIN

SCALE:

EQUIPMENT SLAB DETAIL

NONE

M-605

FINISHED GRADE

ANCHOR BARS AS

REQ'D BE EQUIPMENT

(4) #4 VERT

(4) #4 TIES

SNOW/ICE CLIP BETWEEN

ROOF RIBS (BEYOND)

CONTINUOUS CROSSMEMBER

SNOW/ICE GAURDS

PROVIDE COLOR STRIP

INSERT FROM METAL

ROOF COIL STOCK

METAL CLAMP

ONE PER ROOF RIB

STANDING SEAM

STANDING ROOF PANEL

SCALE:

SNOW AND ICE GAURD DETAIL

NONE

M-605

NOTE: SEE SCHEDULE FOR DIMENSION

2 TYP.

1"

SCALE:

ROOF VENT DETAIL

NONE

M-605

LEGEND

PID PROCESS INSTRUMENTATION DIAGRAM

V VALVE

AIT ANALYSIS INDICATING TRANSMIT

PRV PRESSURE REGULATING VALVE

PIT PRESSURE INDICATING TRANSMITTER

F FILTER

S SOLENOID VALVE

PSW PRESSURE SAFETY VALVE

PI PRESSURE INDICATOR

FI FLOW INDICATOR

ODU OZONE DESTRUCT

S SOLENOID VALVE

TT TEMPERATURE TRANSMIT

EX HEAT EXCHANGER

HMI HUMAN MACHINE INTERFACE

PT PRESSURE TRANMIT

FT FLOW TRANSMIT

M MASS FLOW METER

FI ROTOMETER

MFC MASS FLOW CONTROLLER

RAS RECIRCULATING AQUICULTURE SYSTEM

PDM PROCESS DEVICE MANAGER

CWS CHILL WATER SUPPLY

CWR CHILL WATER RETURN

SV SOLENOID VALVE

V

DRAIN

EX

FT

V

V

TT

PI

V

V

PRV

TT

PI

V V

HMI

TT

AIT

M

FT

V

PT

V

PT

F

FI

O3

AIT

ODU

WD

VWD

SW

S

PRV

PI PSW

S

S

O2

O3

CWR

CWS

DRAIN

AIT

S

SV

S

SV

FT

TT

CV

3/4" TUBE

CWS INLET

3/4" TUBE

CWR OUTLET

ENCLOSURE

TEMP

ENCLOSURE

AMBIENT O3

3/4" TUBE

O2 INLET

3/4" TUBE

OZONE OUTLET

1/4" TUBE

BMT VENT

DRAIN PAN

1/2" NPT

VENT

PDM COMMAND FROM RAS SYSTEMS

1/4" TUBE

OXYGEN

VENT

1/4" TUBE

OXYGEN

VENT

1/4"COMPRESSED AIR FROM

MANUFACTURER SUPPLIED

COMPRESSOR

1/2" HOSE CONDENSATE

DRAIN TO EXTERIOR OF

BUILDING

OZONE GENERATOR

(OZ-1)

PPM

REVISIONS

Agricultural

Service Research

DESCRIPTION

SHEET

DATE

U

NO.

DEPM

SAFETY & HEALTH

REAL PROPERTY

A

DATE

PROJECT NO.

SUSDA

BY

AGRICULTURAL RESEARCH SERVICE

OF

DESIGNER

PROJECT MANAGER

JOB #

CHECKED BY

A-E FIRM USDA AGRICULTURAL RESEARCH SERVICE

NCWMAC

RECIRCULATING AQUACULTURE UPGRADES

FRANKLIN, ME

OZONE GENERATOR PID

M-606 14 2204/18/2025

THT

JEH

AEJ NATIONAL COLD-WATER MARINE

AQUACULTURE CENTER

25 SALMON FARM RD.

FRANKLIN, ME 04634

XXX

3724-E

XXX

XXX

XXX

XXX

SCALE:

OZONE GENERATOR PID

N.T.S.

M-606

O2 CW

S CW

RLOX SUPPLY

FROM CUSTOMER

1" SS

FLANGE

1" SS

FLANGE

3/4" TUBE

CH-1

OZONE GENERATOR

OZONE

DISTRIBUTION

SYSTEM

3/4" O3

TUBEO2

COOLING WATER

COOLING WATER

1/2" HOSE CONDENSATE

DRAIN TO EXTERIOR OF

BUILDING

1/4" TUBE O2 PURGE

COMPRESSED AIR

FROM

MANUFACTURER

SUPPLIED

COMPRESSOR

1" PIPE

1" PIPE

1" P

IP

E

1" P

IP

E

3/4" TUBE

PRV BVBV F BVPIT PITPIT AIT

OXYGEN

FILTER

1" FLANGED OXYGEN

INLET FROM O2 MAIN

1" LOX SUPPLY

1" FLANGED OXYGEN

OUTLET TO OZONE

GENERATOR

1/4" DRAIN

LEGEND

BV BALL VALVE

AIT ANALYSIS INDICATING TRANSMIT

PRV PRESSURE REGULATING VALVE

PIT PRESSURE INDICATING TRANSMITTER

F FILTER

CV BV

BV

STR BV

BV

BV

BV

CH-1

DRAIN

FILL

1" FLANGED CHILLED WATER

RETURN FROM OZONE

GENERATOR

1" FLANGED CHILLED WATER

RETURN TO OZONE

GENERATOR

LEGEND

BV BALL VALVE

STR STRAINER

CV CHECK VALVE

V PRESSURE INDICATING TRANSMITTER

PPM

REVISIONS

Agricultural

Service Research

DESCRIPTION

SHEET

DATE

U

NO.

DEPM

SAFETY & HEALTH

REAL PROPERTY

A

DATE

PROJECT NO.

SUSDA

BY

AGRICULTURAL RESEARCH SERVICE

OF

DESIGNER

PROJECT MANAGER

JOB #

CHECKED BY

A-E FIRM USDA AGRICULTURAL RESEARCH SERVICE

NCWMAC

RECIRCULATING AQUACULTURE UPGRADES

FRANKLIN, ME

OZONE GENERATOR DIAGRAMS

M-607 15 2204/18/2025

THT

JEH

AEJ NATIONAL COLD-WATER MARINE

AQUACULTURE CENTER

25 SALMON FARM RD.

FRANKLIN, ME 04634

XXX

3724-E

XXX

XXX

XXX

XXX

SCALE:

OZONE GENERATOR DIAGRAM

N.T.S.

M-607 SCALE:

LOX FILTRATION AND REGULATING DIAGRAM

N.T.S.

M-607

SCALE:

OZONE CHILLER DIAGRAM

N.T.S.

M-607

Agricultural

Service Research

DESCRIPTION

SHEET

DATE

U

NO.

DEPM

SAFETY & HEALTH

REAL PROPERTY

A

DATE

PROJECT NO.

SUSDA

BY

AGRICULTURAL RESEARCH SERVICE

OF

DESIGNER

PROJECT MANAGER

JOB #

CHECKED BY

A-E FIRM USDA AGRICULTURAL RESEARCH SERVICE

NCWMAC

RECIRCULATING AQUACULTURE UPGRADES

FRANKLIN, ME

MECHANICAL DIAGRAMS

M-608 16 2204/18/2025

THT

JEH

FEJ NATIONAL COLD-WATER MARINE

AQUACULTURE CENTER

25 SALMON FARM RD.

FRANKLIN, ME 04634

XXX

3724-M

XXX

XXX

XXX

XXX

SCALE:

BROOD 3

CHILLING SYSTEM DIAGRAM

NTS

M-608 SCALE:

PARR

CHILLING SYSTEM DIAGRAM

NTS

M-608

SCALE:

SMOLT 2

CHILLING SYSTEM DIAGRAM

NTS

M-608

AIR COOLED

CHILLER (C-1)

OUTSIDEINSIDE WATER

TREATMENT BAY

EXISTING SUMP

EXISTING RECIRCULATING PUMP

EXISTING LHO

ISOLATION VALVE

(TYPICAL OF (2))

BALANCING VALVE

REFRIGERANT SUPPLY AND RETURN

DX CHILLER BARREL

WITH CONTROLLER

AIR COOLED

CHILLER (C-3)

OUTSIDEINSIDE WATER

TREATMENT BAY

EXISTING SUMP

EXISTING RECIRCULATING PUMP

EXISTING LHO

ISOLATION VALVE

(TYPICAL OF (2))

BALANCING VALVE

REFRIGERANT SUPPLY AND RETURN

DX CHILLER BARREL

WITH CONTROLLER

AIR COOLED

CHILLER (C-2)

OUTSIDEINSIDE WATER

TREATMENT BAY

EXISTING SUMP

EXISTING RECIRCULATING PUMP

EXISTING LHO

ISOLATION VALVE

(TYPICAL OF (2))

BALANCING VALVE

REFRIGERANT SUPPLY AND RETURN

DX CHILLER BARREL

WITH CONTROLLER

Emilie Oakes sam ME seal

ChristopherG.Morris Line

NOTE:

1. NOT ALL ABBREVIATIONS SHOWN WILL BE USED ON THIS PROJECT.

A OR AMP

ACC

AC

AC

AF

AFF

AFG

AHU

AIC

AL

AM

ASYM

AT

ATS

AUTO

AWG

B

BC

BCW

BFF

BFG

BLDG

BMGB

C

CAT

CB

CCT

CCTV

CFCI

CH

CHWCP

CHWP

CHWSP

CKT

CMH

CMS

CP

CPT

CRAC

CRI

CT

CT

CU

CWP

D

DC

DF

DH or DUH

DHWCP

DISC

DOAS

DPST

DPDT

DSCU

DSHP

DSS

DWBP

DX

EC

ECB

EF

ELEC

EMH

EMT

E or EMER

EPA

EQUIP

ERV

ERU

EXIST or EX

EUH

EXP

EWC

EWH

F

FACP

FCU

FLEX

FWE

G OR GND

GFGI

GFI

GRS

GUH

GWH

H or HT

HAC

HOA

HP

HP

HT

HVU

HWCP

HWP

HWRP

HWSP

AMPERE(S)

AIR COOLED CHILLER

ALTERNATING CURRENT

AIR COMPRESSOR / AIR CURTAIN

AMP FRAME

ABOVE FINISHED FLOOR

ABOVE FINISHED GRADE

AIR HANDLING UNIT

AMPERE INTERRUPTING CAPACITY

ALUMINUM

AMMETER

ASYMMETRICAL

AMP TRIP

AUTOMATIC TRANSFER SWITCH

AUTOMATIC

AMERICAN WIRE GAUGE

BOILER

BRANCH CONTROLLER

BARE COPPER WIRE

BELOW FINISHED FLOOR

BELOW FINISHED GRADE

BUILDING

BUILDING MASTER GROUNDING BUSBAR

CONDUIT

CATEGORY

CIRCUIT BREAKER

CORRELATED COLOR TEMPERATURE

CLOSED CIRCUIT TELEVISION

CONTRACTOR FURNISHED CONTRACTOR INSTALLED

CHILLER

CHILLED WATER CIRCULATING PUMP IN A PRIMARY-SECONDARY SYSTEM

CHILLED WATER PUMP

CHILLED WATER SUPPLY PUMP IN A PRIMARY-SECONDARY SYSTEM

CIRCUIT

COMMUNICATIONS MANHOLE

COMBINATION MOTOR STARTER

CONDENSATE PUMP

CONTROL POWER TRANSFORMER

COMPUTER ROOM AC UNIT

COLOR RENDERING INDEX

CURRENT TRANSFORMER

COOLING TOWER

COPPER OR CONDENSING UNIT

CONDENSER WATER PUMP

DEPTH

DIRECT CURRENT

DESTRATIFICATION FAN

DUCT HEATERS

DOMESTIC HOT WATER CIRCULATING PUMP

DISCONNECT SWITCH

DEDICATED OUTSIDE AIR SYSTEM (UNIT)

DOUBLE POLE SINGLE THROW

DOUBLE POLE DOUBLE THROW

DUCTLESS SPLIT CONDENSING UNIT (POWERS THE DSS INDOOR UNIT)

DUCTLESS SPLIT HEAT PUMP (POWERS THE DSS INDOOR UNIT)

DUCTLESS SPLIT SYSTEM (INDOOR UNIT)

DOMESTIC WATER BOOSTER PUMP

DIRECT EXPANSION (DX) COOLING COIL

EMPTY CONDUIT

ENCLOSED CIRCUIT BREAKER

EXHAUST FAN

ELECTRICAL

ELECTRICAL MANHOLE

ELECTRICAL METALLIC TUBING

EMERGENCY

EFFECTIVE PROJECTED AREA

EQUIPMENT

ENERGY RECOVERY VENTILATOR

ENERGY RECOVERY UNIT

EXISTING

ELECTRIC UNIT HEATER

EXPLOSION PROOF

ELECTRIC WATER COOLER

ELECTRIC WATER HEATER

FUSE

FIRE ALARM CONTROL PANEL

FAN COIL UNIT

FLEXIBLE

FURNISHED WITH EQUIPMENT

GROUND

GOVERNMENT FURNISHED GOVERNMENT INSTALLED

GROUND FAULT INTERRUPTER

GALVANIZED RIGID STEEL CONDUIT

GAS UNIT HEATER

GAS WATER HEATER

HEIGHT

HEATED AIR CURTAIN

HAND-OFF AUTOMATIC

HORSE POWER

HEAT PUMP (OUTDOOR PORTION OF SPLIT SYSTEM HEAT PUMP, USE CU FOR

STANDARD DX OUTDOOR UNIT)

HEAT TRACKING

HEATING/VENTILATING UNIT

HEATING WATER CIRCULATING PUMP IN A PRIMARY-SECONDARY SYSTEM

HEATING WATER SUPPLY IN A PRIMARY-ONLY SYSTEM

HOT WATER RECIRCULATION PUMP

HEATING WATER SUPPLY PUMP IN A PRIMARY-SECONDARY SYSTEM

ELECTRICAL ABBREVIATIONS

HWUH

HZ

IDS

IMC

IRH

J OR JB

K

KAIC

KCM OR KCMIL

KEF

KH

KV

KVA

KW

KWHR

L

LA

LAN

LAV

LM

LTG

MAU

MAX

MCA

MCB or MB

MCC

MGB

MH

MIN

MLO

MOD

MT or MTD

MRS

N

NEC

NEMA

NFPA

NC

NESC

NL

NO

NTS

P

PA

PBB

PDU

PF

PH

PIU

PMT

PNL

PTAC

PVC

RBB

RECEPT or RECP

RF

RH

RMC

RMS

RTU

RVNR

SA

SBB

SCCR

SD

SF

S/N

SP

SPD

SPDT

SPEC

SPST

SWBD

SWGR

TEBC

TMGB

TOL

TP

TYP

U

UH

UG

UIO

UL

UTP

V

VA

VAV

VEF

VM

VRF

W

WC

WEF

WH

WHDM

WSHP

WP

WPIU

XFMR

Z

HOT WATER UNIT HEATER

HERTZ

INTRUSION DETECTION SYSTEM

INTERMEDIATE METAL CONDUIT

INFRARED HEATER

JUNCTION BOX

KILO

THOUSAND AMPERE INTERRUPTING CAPACITY

THOUSAND OF CIRCULAR MILS

KITCHEN EXHAUST FAN

KITCHEN HOOD

KILOVOLT

KILOVOLT-AMPERES

KILOWATT

KILOWATT-HOUR

LENGTH

LIGHTNING ARRESTOR

LOCAL AREA NETWORK

LAVATORY

LOCKHEED MARTIN

LIGHTING

MAKE-UP AIR UNIT

MAXIMUM

MINIMUM CIRCUIT AMPACITY

MAIN CIRCUIT BREAKER

MOTOR CONTROL CENTER

MAIN GROUND BAR

MANHOLE or MOUNTING HEIGHT

MINIMUM

MAIN LUGS ONLY

MOTOR OPERATED DAMPER

MOUNT or MOUNTED

MOTOR RATED SWITCH

NEUTRAL

NATIONAL ELECTRICAL CODE

NATIONAL ELECTRICAL MANUFACTURER'S ASSOCIATION

NATIONAL FIRE PROTECTION ASSOCIATION

NORMALLY CLOSED

NATIONAL ELECTRICAL SAFETY CODE

NIGHT LIGHT

NORMALLY OPEN

NOT TO SCALE

POLE(S) or PUMP

PUBLIC ADDRESS

PRIMARY BONDING BUSBAR

POWER DISTRIBUTION UNIT

POWER FACTOR

PHASE

VAV TERMINAL UNIT WITH PARALLEL OR SERIES FAN (PRIMARY INDUCTION UNIT)

PAD MOUNTED TRANSFORMER

PANEL OR PANELBOARD

PACKAGED THRU-WALL AIR CONDITIONER

POLYVINYL CHLORIDE

RACK BONDING BUSBAR

RECEPTACLE

RETURN FAN

RADIANT HEATERS (ELECTRIC)

RIGID METAL CONDUIT

ROOT MEAN SQUARE

ROOF TOP UNIT

REDUCED VOLTAGE NON-REVERSING

SURGE ARRESTOR

SECONDARY BONDING BUSBAR

SHORT CIRCUIT CURRENT RATING

SMOKE DAMPER

SUPPLY FAN

SOLID NEUTRAL

SUMP PUMP

SURGE PROTECTIVE DEVICE

SINGLE POLE DOUBLE THROW

SPECIFICATIONS

SINGLE POLE SINGLE THROW

SWITCHBOARD

SWITCHGEAR

TELECOMMUNICATIONS EQUIPMENT BONDING CONDUCTOR

TELECOMMUNICATIONS MAIN GROUNDING BUSBAR

THERMAL OVERLOAD

TWISTED PAIR

TYPICAL

URINAL

UNIT HEATER

UNDERGROUND

UNLESS INDICATED OTHERWISE

UNDERWRITERS LABORATORY

UNSHIELDED TWISTED PAIR

VOLTS

VOLT AMPERES

VAV TERMINAL UNIT

VEHICLE EXHAUST FAN

VOLTMETER

VARIABLE REFRIGERANT FLOW SYSTEM

WATTS or WIRE or WIDTH

WATER CLOSET

WELDING EXHAUST FAN

WATER HEATER

WATTHOUR DEMAND METER

WATER SOURCE HEAT PUMP

WEATHERPROOF

WEATHERPROOF IN USE

TRANSFORMER

IMPEDANCE

1. THE WORK MUST CONFORM WITH ALL REQUIREMENTS OF:

• NFPA 70, NATIONAL ELECTRICAL CODE (NEC) (2023)

• NFPA 101, LIFE SAFETY CODE (2024)

• ARS 242.1M, ARS FACILITIES DESIGN STANDARDS (2024)

• ASHRAE 90.1, ENERGY STANDARD FOR BUILDINGS EXCEPT LOW-RISE RESIDENTIAL BUILDINGS (2019)

*CRITERIA AND STANDARDS LISTED ALSO INCLUDE SPECIFIED STANDARDS AND RELATED SECTIONS AS PART OF THE DESIGN.

2. MINIMUM RACEWAY SIZE MUST BE 3/4". INCREASE RACEWAY SIZE AS REQUIRED TO LIMIT RACEWAY FILL RATIO TO LESS THAN 40% FULL.

3. THE ELECTRICAL CONTRACTOR MUST CAREFULLY COORDINATE WORK WITH OTHER TRADES THROUGH THE GENERAL CONTRACTOR AND MUST BE RESPONSIBLE FOR SECURING SPACE REQUIREMENTS FOR ELECTRICAL EQUIPMENT CLEARANCE FOR RECESSED LUMINAIRES AND CORRECT ROUGH-IN

LOCATIONS OF ELECTRICAL CONNECTIONS.

4. ALL FEEDERS AND BRANCH CIRCUITS MUST INCLUDE A GREEN INSULATED GROUND CONDUCTOR, SIZE PER NATIONAL ELECTRICAL CODE, OR AS SHOWN, CONNECTED TO EACH DEVICE AND OUTLET BOX ON THE CIRCUIT AND TO THE PANELBOARD GROUND BUS. PROVIDE A DEDICATED NEUTRAL CONDUCTOR FOR EACH BRANCH CIRCUIT. MULTIPLE BRANCH CIRCUITS IN ONE RACEWAY REQUIRE ONLY ONE GROUND CONDUCTOR.

5. EXISTING ELECTRICAL WORK (NOT SHOWN) MUST REMAIN, UNLESS INDICATED OTHERWISE. SHOULD ANY EXISTING ELECTRICAL POWER, LIGHTING OR AUXILIARY CIRCUIT, FEEDER OR EQUIPMENT BE SEVERED, DISCONNECTED OR DELETED IN THE PROCESS OF CONSTRUCTION OR REMODELING WHICH IS DONE AS A RESULT OF CONTRACT PLANS AND SPECIFICATIONS, AND UNLESS SPECIFICALLY DESIGNATED BY THE DRAWINGS TO BE DELETED, THEN SAID CIRCUIT OR FEEDER MUST BE RESTORED TO WORKING CONDITION. THE RESTORATION MUST INCLUDE RE-ROUTING, RELOCATION, RECONNECTION OR REPLACEMENT AS MAY BE REQUIRED BY THE NEW WORK. ANY SUCH WORK REQUIRED MUST BE INCLUDED IN THE CONTRACT AND NO EXTRA COMPENSATION WILL BE GRANTED.

6. NEW WORK MUST BE MADE TO TIE INTO THE EXISTING IN A UNIFORM MANNER, SIMILAR ITEMS OF NEW WORK MUST BE CHECKED AGAINST EXISTING WORK.

7. REFER TO ONE-LINE DIAGRAMS, SCHEDULES AND RISER DIAGRAMS FOR CONDUCTOR AND CONDUIT SIZES NOT SHOWN ON PLANS.

8. PROVIDE IS AN INCLUSIVE TERM USED TO DESCRIBE ASPECTS OF THE WORK TO BE ACCOMPLISHED, AND IS HEREBY DEFINED TO REQUIRE TO STORE, FURNISH, INSTALL, MOUNT, CONNECT, CONTROL AND POWER EQUIPMENT INDICATED, AS WELL AS ALL APPURTENANCES REQUIRED TO MAKE ELECTRICAL SYSTEMS OPERATE AS INDICATED WITHIN THESE DRAWINGS AND SPECIFICATIONS AND TO FULFILL THE SCOPE OF WORK.

9. DEMOLISH IS AN INCLUSIVE TERM USED TO DESCRIBE ASPECTS OF THE WORK TO BE ACCOMPLISHED, AND IS HEREBY DEFINED TO REQUIRE CONTRACTOR TO DISCONNECT EQUIPMENT FROM ALL CONNECTIONS, REMOVE FROM THE OWNER'S SITE, AND DISPOSE OF IN ACCORDANCE WITH FEDERAL, STATE AND LOCAL LAWS AND ORDINANCES. COST OF DISPOSAL IS ENTIRELY THE CONTRACTOR'S RESPONSIBILITY.

10. ALL CONDUCTORS ARE COPPER UNLESS SPECIFICALLY NOTED AS ALUMINUM.

11. CONTRACTOR MUST FIELD VERIFY ALL EXISTING CONDITIONS, DIMENSIONS AND ELEVATIONS BEFORE PROCUREMENT OF ANY MATERIALS AND DEVELOPMENT

OF ANY SHOP DRAWINGS OR SUBMITTALS.

13. ALL EQUIPMENT PADS FOR INTERIOR ELECTRICAL EQUIPMENT MUST BE FLUSH WITH FRONT SIDE OF EQUIPMENT AND EXTEND AT LEAST 2” BEYOND THE

FOOTPRINT OF THE EQUIPMENT ON ALL OTHER SIDES.

ELECTRICAL GENERAL NOTES:

NO. DATE BY DESCRIPTION

REVISIONS

U S D A

PROJECT NO.

DATE

Agricultural Research Service

USDA AGRICULTURAL RESEARCH SERVICE

NCWMAC

RECIRCULATING AQUACULTURE UPGRADES

FRANKLIN, ME

SHEET

AGRICULTURE RESEARCH SERVICE

NATIONAL COLD-WATER MARINE

AQUACULTURE CENTER

FRANKLIN, ME 04934

OF

A-E FIRM

PROJECT MANAGER EPM

DESIGNER PPM

CHECKED BY SAFETY & HEALTH

JOB # REAL PROPERTY

USDA

xxxxx xxxxx xxxxx xxxxx xxxxx

3724-M

E-001

ELECTRICAL GENERAL NOTES

04/18/25

TT

EH

CG

david ME seal

LA-1

LA-1

ELECTRICAL LEGEND

1. ALL EQUIPMENT AND DEVICES ARE TO BE FLUSH MOUNTED UNLESS

OTHERWISE NOTED.

2. DEVICES NOTED AS "GFCI" MUST BE GROUND FAULT CIRCUIT

INTERRUPTING DEVICES.

3. DEVICES NOTED AS "WP" MUST BE GFI AND WEATHERPROOF.

4.

DEVICES NOTED AS "DL" MUST BE RATED FOR DAMP LOCATION.5.

DEVICES NOTED AS "NL" MUST BE NIGHT LIGHTS. PROVIDE

UNSWITCHED POWER TO FIXTURE.

6.

DEVICES NOTED AS "WG" MUST BE PROVIDED AND INSTALLED WITH

A WIRE GUARD.

7.

DEVICES NOTED AS "TR" MUST BE TAMPER RESISTANT.8.

PROVIDE UNSWITCHED POWER TO EMERGENCY BATTERY

PACKS.

PE

DUPLEX RECEPTACLE, NEMA 5-20R, MOUNTED 18" A.F.F. TO

CENTERLINE OF BOX UNLESS NOTED OTHERWISE.

CONTACTOR.

PHOTOCELL.

CEILING MOUNTED JUNCTION BOX.

WALL MOUNTED JUNCTION

BOX.

FLEXIBLE CONNECTION TO

EQUIPMENT.

CONDUIT AND WIRING RECEPTACLESLEGEND GENERAL NOTES MISCELLANEOUS

CONDUCTORS IN CONDUIT CONCEALED WITHIN WALL OR

CEILING. TIC MARKS INDICATE NUMBER OF

CONDUCTORS. THE EQUIPMENT GROUNDING CONDUCTOR

IS NOT SHOWN, BUT MUST BE PROVIDED. SIZE THE

EQUIPMENT GROUNDING CONDUCTOR AND THE CONDUIT

PER THE NEC. THE ABSENCE OF TIC MARKS SIGNIFIES

THAT TWO CONDUCTORS PLUS AN EQUIPMENT GROUNDING

CONDUCTOR SHOULD BE PROVIDED. FOR EXAMPLE, THE

MARKINGS TO THE LEFT SIGNIFY THAT THREE

CONDUCTORS PLUS AN EQUIPMENT GROUNDING

CONDUCTOR SHOULD BE PROVIDED.

CONDUCTORS IN CONDUIT CONCEALED BELOW GRADE OR

FLOOR. TIC MARKS INDICATE NUMBER OF CONDUCTORS.

THE EQUIPMENT GROUNDING CONDUCTOR IS NOT

SHOWN, BUT MUST BE PROVIDED. SIZE THE EQUIPMENT

GROUNDING CONDUCTOR AND THE CONDUIT PER THE

NEC. THE ABSENCE OF TIC MARKS SIGNIFIES THAT TWO

CONDUCTORS PLUS AN EQUIPMENT GROUNDING

CONDUCTOR SHOULD BE PROVIDED. THE MARKINGS TO

THE LEFT SIGNIFY THAT THREE CONDUCTORS PLUS AN

EQUIPMENT GROUNDING CONDUCTOR SHOULD BE

PROVIDED.

THE TEXT INSIDE THE ARC INDICATES THE AWG SIZE OF

THE CONDUCTORS THAT MUST BE RUN IN THE CONDUIT.

THE ABSENCE OF TEXT SIGNIFIES THAT THE

CONDUCTORS SHOULD BE #12 AWG.

CIRCUITRY RUN IN STRAIGHT LINE SEGMENTS SIGNIFIES

EXPOSED SURFACE-MOUNTED RACEWAY (SEE

SPECIFICATIONS).

HOMERUN TO PANELBOARD. ARC DENOTES CONCEALED

CIRCUITRY. TEXT DENOTES PANELBOARD NAME WITH

CIRCUIT NUMBER. DEVICES HAVING CIRCUIT NUMBERS

LOCATED BESIDE THEM MAY NOT SHOW THE CIRCUIT

NUMBERS AT THE HOMERUN ARROWS.

PARTIAL HOMERUN TO PANELBOARD. COMBINE ALL

PARTIAL HOMERUNS THAT ARE ON THE SAME CIRCUIT IN

A JUNCTION BOX PRIOR TO ENTERING THE PANELBOARD.

LOW VOLTAGE CONDUCTORS USED FOR MOTION DETECTOR

CIRCUITRY. SEE MANUFACTURER'S RECOMMENDATIONS

FOR CONDUCTOR REQUIREMENTS.

C

J

J

DEVICES NOTED AS "WPIU" MUST BE GFI AND WEATHERPROOF IN USE.

9.

LONG TIC MARK IDENTIFIES CONDUCTOR. SHORT TICK MARK

IDENTIFIES NEUTRAL. HOOKED TIC MARK IDENTIFIES GROUND.

MECHANICAL ELECTRICAL

CONNECTION. TOP VALUE

REPRESENTS VOLTAGE AND PHASE.

BOTTOM VALUE IS IDENTIFIER.

120 V 1P

M1

GROUND FAULT CIRCUIT INTERRUPTOR DUPLEX RECEPTACLE, NEMA

5-20R, MOUNTED 18" A.F.F. TO CENTERLINE OF BOX UNLESS NOTED

OTHERWISE.

GFCI

NO. DATE BY DESCRIPTION

REVISIONS

U S D A

PROJECT NO.

DATE

Agricultural Research Service

USDA AGRICULTURAL RESEARCH SERVICE

NCWMAC

RECIRCULATING AQUACULTURE UPGRADES

FRANKLIN, ME

SHEET

AGRICULTURE RESEARCH SERVICE

NATIONAL COLD-WATER MARINE

AQUACULTURE CENTER

FRANKLIN, ME 04934

OF

A-E FIRM

PROJECT MANAGER EPM

DESIGNER PPM

CHECKED BY SAFETY & HEALTH

JOB # REAL PROPERTY

USDA

xxxxx xxxxx xxxxx xxxxx xxxxx

3724-M

E-002

ELECTRICAL LEGEND

04/18/25

TT

EH

CG

C-2

480 V 3P C-3

480 V 3P

EX-C

480 V 3P

EX-C

480 V 3P

C-1

480 V 3P

CH-1

480 V 3P

UH-1

480 V 3P

EF-1

120 V 1P

OZ-1

480 V 3P

RPB

DP-4

P-D

P-G1

P-G2

P-C

P-MM

P-NM

P-H L-L

P-A2

P-A1

P-J1

P-J2

MDP

DT-1

DP-1

P-H1

MDP-2-7,9,11

MDP-2

ATS-2

GEN-1

P-H2-8,10,12

P-H2-7,9,11

P-H2

MDP-2-8,10,12

P-H1-1,3,5

P-H1-7,9,11

P-H2-13,15,17

P-H2-1,3,5

P-Q2 QT-1QT-1-1

MDP-2-2,4

P-H2-2,4,6

P-Q2-1

P-H2-14,16,18

NO. DATE BY DESCRIPTION

REVISIONS

U S D A

PROJECT NO.

DATE

Agricultural Research Service

USDA AGRICULTURAL RESEARCH SERVICE

NCWMAC

RECIRCULATING AQUACULTURE UPGRADES

FRANKLIN, ME

SHEET

AGRICULTURE RESEARCH SERVICE

NATIONAL COLD-WATER MARINE

AQUACULTURE CENTER

FRANKLIN, ME 04934

OF

A-E FIRM

PROJECT MANAGER EPM

DESIGNER PPM

CHECKED BY SAFETY & HEALTH

JOB # REAL PROPERTY

USDA

xxxxx xxxxx xxxxx xxxxx xxxxx

3724-M

E-101

POWER PLAN

04/18/25

TT

EH

CG

3/32" = 1'-0"E-101

POWER PLAN1

SCALE: = 1'-0"3/32"

0 11 21 3211

N

X

1. PANEL IS PROPOSED IN ANOTHER PROJECT. IT IS SHOWN

FOR LOAD AND PLANNING PURPOSES.

2. AN ADDITIONAL 100 AMPS OF LOAD IS ANTICIPATED TO BE

ADDED TO THIS PANEL IN ANOTHER PROJECT.

3. PROVIDE NEW ELECTRIC PANEL. SEE E-601 FOR MORE

DETAILS.

4. PREFABRICATED FIBERGLASS ENCLOSURE.

• PROVIDE 125A 120/240V SERVICE AND 16 CIRCUIT

BREAKER PANEL.

• INTERIOR AND EXTERIOR LIGHTING PROVIDED BY

ENCLOSURE MANUFACTURER. PROVIDE

CONDUIT/CONDUCTORS, SINGLE POLE SWITCH, AND

INSTALL LIGHT FIXTURES.

• NOTE: ENCLOSURE INTERIOR AND ALL AREAS WITHIN

5-FT OF ENCLOSURE OPENINGS ARE CLASS I DIV I.

COORDINATE MATERIALS AND INSTALLATION METHOD

WITH SPACE REQUIREMENTS.

5. LOCATE MINIMUM 5-FT FROM ANY OPENINGS IN CLASSIFIED

SPACE.

KEYED NOTES

1/4" = 1'-0"E-101

OZ-1 BUILDING DETAIL2

UT-1

SCALE: = 1'-0"

0 4 84

1/4"

Emilie Oakes david ME seal

ChristopherG.Morris Line

GRADE OR

SLAB ON GRADE

USE SCHEDULE 40

POLYVINYL CHLORIDE (PVC)

CONDUIT FOR CIRCUITS

UNDERGROUND. USE PVC-COATED

GALVANIZED RIGID STEEL

ELBOWS.

USE GALVANIZED RIGID

STEEL OR INTERMEDIATE

METAL CONDUITS WHERE

CIRCUITS ARE EXPOSED TO

ABRASION.

USE PVC-COATED GALVANIZED

RIGID STEEL CONDUIT FOR ALL

VERTICAL RUNS EXTENDING 6"

ABOVE GRADE.

USE INTERMEDIATE METAL

CONDUITS OR ELECTRICAL

METALLIC TUBING FOR ALL

BRANCH CIRCUITS, FEEDERS,

AND AUXILIARY CIRCUITS

REQUIRING 1-1/4" NOMINAL

TRADE SIZE OR LARGER IN

DRY LOCATIONS.

UNDERGROUND

CONDUIT.

24"

MINIMAL

USE GALVANIZED RIGID

STEEL CONDUITS WHERE

CIRCUITS ARE RUN ABOVE

GROUND EXPOSED TO

WEATHER.

SERVICES, CONDUITS FOR

PRIMARY CONDUCTORS, AND

CONDUITS RUN UNDER

ROADWAYS MUST BE

BURIED NO LESS THAN 24"

DEEP.

6"

USE PVC-COATED

GALVANIZED RIGID STEEL

ELBOWS.

USE PVC-COATED GALVANIZED

RIGID STEEL CONDUIT FOR ALL

VERTICAL RUNS EXTENDING 6"

ABOVE GRADE.

6"

NOTE: GRS & IMC CONDUIT

THREADS MUST BE

GALVANIZED AFER CUTTING.

NOTE: GALVANIZED RIGID STEEL CONDUIT

COATED WITH TWO COMPLETE COATS OF

ASPHALTIC OF BITUMINOUS PAINT MAY

BE USED IN LIEU OF PVC-COATED

GALVANIZED RIGID STEEL CONDUITS.

ELECTRICAL CIRCUIT SCHEDULE

LOAD NAME VOLTAGE PHASE PANEL CIRCUIT NUMBER APPARENT LOAD WIRE SIZE

C-1 480 V

C-2

C-3

C-4

BREAKER

C-6

CH-1

EF-1

MDP

MECHANICAL

P-Q2

QT-1

UH-1

480 V

480 V

480 V

480 V

480 V

120 V

480 V

480 V

240 V

480 V

480 V

P-H2

P-H2

P-H2

P-H1

P-H1

P-H2

P-Q2

MDP-2

P-H2

QT-1

MDP-2

P-H2

7,9,11

8,10,12

13,15,17

7,9,11

1,3,5

1,3,5

43231 VA

33919 VA

50547 VA

33919 VA

16627 VA

120 VA

798106 VA

40737 VA

1060 VA

1060 VA

9311 VA

70A

70A

60A

80A

60A

30A

20A

1000A

20A

3-#4, 1-#4, 1-#8

(3) 3-#400, 1-#400, 1-#3

2-#12, 1-#12, 1-#12

1,3,5

14,16,18

2,4

2,4,6

43231 VA

3-#4, 1-#4, 1-#8

3-#6, 1-#6, 1-#10

3-#6, 1-#6, 1-#10

3-#4, 1-#4, 1-#8

70A3-#4, 1-#4, 1-#8

20A2-#12, 1-#12, 1-#12

20A3-#12, 1-#12, 1-#12

3-#12, 1-#12, 1-#12

1-#12, 1-#12, 1-#12

ELECTRICAL CIRCUIT SCHEDULE

LOAD ID CIRCUIT VOLTAGE NUMBER OF

POLES

MCA MOCP

C-1

C-2

C-3

CH-1

APPARENT

POWER

EF-1

EX-C

EX-C

OZ-1

UH-1

480V 3

61A

41A

20A

1A

52A

52A

49A

11A

33919VA

50547VA

33919VA

16627VA

120VA

43231VA

43231VA

40737VA

50A

70A

41A

80A

50A

1A

30A

9311VA1A

70A

70A

DISCONNECT

3P60A

3P100A

3P60A

3P100A

3P100A

P-H2-13,15,17

P-H1-7,9,11

P-H1-1,3,5

P-H1-1,3,5

P-Q2-1

P-H2-8,10,12

P-H2-7,9,11

P-H2-14,16,18

P-H2-2,4,6

480V

480V

480V

120V

480V

480V

480V

480V

NO. DATE BY DESCRIPTION

REVISIONS

U S D A

PROJECT NO.

DATE

Agricultural Research Service

USDA AGRICULTURAL RESEARCH SERVICE

NCWMAC

RECIRCULATING AQUACULTURE UPGRADES

FRANKLIN, ME

SHEET

AGRICULTURE RESEARCH SERVICE

NATIONAL COLD-WATER MARINE

AQUACULTURE CENTER

FRANKLIN, ME 04934

OF

A-E FIRM

PROJECT MANAGER EPM

DESIGNER PPM

CHECKED BY SAFETY & HEALTH

JOB # REAL PROPERTY

USDA

xxxxx xxxxx xxxxx xxxxx xxxxx

3724-M

E-501

SCHEDULES AND DETAILS

04/18/25

TT

EH

CG

N.T.SE-501

1 CONDUIT DETAIL

Emilie Oakes david ME seal

ChristopherG.Morris Line

PANEL

P-NM

600A

MLO

480Y/277V 3P 4W

PANEL

P-H1 225A

MCB

480Y/277V 3P 4W

PANEL

P-H2 400A

MLO

480Y/277V 3P 4W

400225600

1000.A

1600S

1600S

400A 3P L

225A 3P L

600A 3P L

MDP-2

480Y/277V 3P 4W 1600A

ATS-2

XFMR UT-1

1,000 KVA

480Y/277V

GEN-1

480Y/277V 3P

500KW

400A 3P

225A 3P

225A 3P

100A 3P

125A 3P

200A 3P

PANEL

P-G2 225A

MLO

208Y/120V 3P 4W

PANEL

P-G1 225A

MLO

208Y/120V 3P 4W

PANEL

P-H

225A

MLO

208Y/120V 3P 4W

PANEL

P-J2 100A

MLO

208Y/120V 3P 4W

PANEL

P-J1 100A

MLO

208Y/120V 3P 4W

DP-1

208Y/120V 3P 4W 400A

XFMR DT-1

75 KVA

480V

TO 208Y/120V

PANEL

L-L

100A

MLO

480Y/277V 3P 4W

PANEL

P-A2 225A

MLO

480Y/277V 3P 4W

PANEL

P-A1 225A

MLO

480Y/277V 3P 4W

PANEL

P-C

100A

MLO

480Y/277V 3P 4W

PANEL

P-B

225A

MLO

480Y/277V 3P 4W

MDP

480Y/277V 3P 4W

1200AF

P-D 480Y/277V 3P 4W 400A

MLO

PANEL

DP-E

200A

MLO

480Y/277V 3P 4W

225 100

100125225

400J

225 100

400225225100

125D

70A 2P L

XFMR QT-1

45 KVA

480V 1Ø 120/240V 1Ø

PANEL

P-Q2 125A

MLO

240Y/120V 2P 3W

125/2D

1000A 3P

LS1

1600A 3P

LS1G

M

FEEDER SCHEDULE

ID FEEDER

AMPS

CONDUIT AND FEEDER

100 1-1/2"C,3#1,#1N,#8G

125 1-1/2"C,3#1/0,#1/0N,#6G

125 1-1/2"C,3#1/0,#6G

200 2"C,3#3/0,#3/0N,#6G

225 2-1/2"C,3#4/0,#4/0N,#4G

400 3-1/2"C,3#600kcmil,#600kcmil N,#2G

400 3-1/2"C,3#600kcmil,#600kcmil N,#1/0G

600 (2)3"C,3#350kcmil,#350kcmil N,#1G

1000 (3)3"C,3#400kcmil,#400kcmil N,#2/0G

SIZING METHOD: COPPER, 60°C #12 THROUGH #1, 75°C 1/0 AND ABOVE

1600S

1000.A

400J

125D

70 70 1-1/4"C,2#4,#4N,#8G

125 1-1/4"C,2#1/0,#6G125/2D

150 1-1/2"C,3#1/0,#6G150DJ

1600 (4)3-1/2"C,3#600kcmil,#600kcmil N,#4/0 G1600

(4)3-1/2"C,3#600kcmil,#600kcmil N

EXISTING TO REMAIN

NEW WORK

FAULT CURRENT SCHEDULE

DEVICE FAULT AIC RATING L-L VOLTS FEEDER

SIZE

FEEDER

LENGTH

RATING

P-H1

P-H2

QT-1

10,493

10,482

3,794

22,000

22,000

22,000

480V

480V

240V

#600KCMIL

#4/0

#4

292'

202'

233' 45 KVA

400 A

225 A

P-Q2 3,050 22,000 240V #1/0 12' 125 A

NO. DATE BY DESCRIPTION

REVISIONS

U

S

D

A

PROJECT NO.

DATE

Agricultural Research Service

USDA AGRICULTURAL RESEARCH SERVICE

NCWMAC

RECIRCULATING AQUACULTURE UPGRADES

FRANKLIN, ME

SHEET

AGRICULTURE RESEARCH SERVICE

NATIONAL COLD-WATER MARINE

AQUACULTURE CENTER

FRANKLIN, ME 04934

OF

A-E FIRM

PROJECT MANAGER EPM

DESIGNER PPM

CHECKED BY SAFETY & HEALTH

JOB # REAL PROPERTY

USDA

xxxxx xxxxx xxxxx xxxxx xxxxx

3724-M

E-601

POWER RISER

04/18/25

TT

EH

CGN.T.S.E-601

POWER RISER - PHASE 21

A. PANEL P-NM IS A PROPOSED PANEL FOR ANOTHER

PROJECT. SHOWN FOR LOAD CALCULATIONS.

GENERAL NOTES

NO. DATE BY DESCRIPTION

U S D A

PROJECT NO.

DATE

Agricultural Research Service

USDA AGRICULTURAL RESEARCH SERVICE

NCWMAC

RECIRCULATING AQUACULTURE UPGRADES

FRANKLIN, ME

SHEET

AGRICULTURE RESEARCH SERVICE

NATIONAL…