Attachment 2 - Drawings - Base.pdf
PDF 2 MB Posted
- Attached to
- Recirculating Aquaculture System Upgrades Federal contract opportunity
- Solicitation number
- 1232SA26Q0302
About this file
This is a set of electrical design and construction drawings for a recirculating aquaculture electrical upgrades project at the National Cold-Water Marine Aquaculture Center (NCWMAC) in Franklin, Maine. The project, under Contract No. 12305B21D0013/12305B24F0110 with the U.S. Department of Agriculture Agricultural Research Service, involves upgrading the existing electrical distribution infrastructure to handle larger load demands for future projects. The contractor must maintain uninterrupted facility operations throughout construction, follow all NCWMAC biosecurity protocols, coordinate utility disconnections and outages with the utility company, and store all construction materials outside buildings in government-designated areas. A new utility transformer will be provided and installed by the utility, with the existing transformer removed by the utility.
The drawings comprise nine sheets detailing the complete electrical system design, including a title sheet, drawing index, electrical general notes, electrical legend, power plan (Phase 1), details, power riser diagram, panel schedules, and grounding diagram. The electrical system features a 1,000 kVA utility transformer (UT-1) supplying 480Y/277V power to a main distribution panel (MDP-2) rated at 1,200 amperes, with multiple branch panels (P-A1, P-A2, P-B, P-C, P-D, P-G1, P-G2, P-H, P-J1, P-J2, L-L) at both 480Y/277V and 208Y/120V. A 500 kW generator (GEN-1) is included with an automatic transfer switch (ATS-2) for backup power. All work must comply with the 2023 National Electrical Code (NEC), UFC electrical standards, and ASHRAE 90.1 energy standards. Minimum raceway size is 3/4 inch with fill ratios not to exceed 40 percent, and all grounding must include dedicated ground conductors sized per NEC requirements.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| SF30 - Amendment 02.pdf | ||
| RFI 2 - Clarification.pdf | ||
| Site Visit Sign In Sheet - Mar 17.pdf | ||
| Site Visit Sign In Sheet - Mar 18.pdf | ||
| RFIs.pdf | ||
| SF30 - Amendment 01.pdf | ||
| Attachment 1 - Solicitation Terms and Conditions.pdf | ||
| Attachment 6 - Specifications - Options 2 and 3.pdf | ||
| Attachment 3 - Specifications - Base.pdf | ||
| Attachment 4 - Drawing - Option 1.pdf | ||
| Attachment 5 - Drawings - Options 2 and 3.pdf | ||
| Wage Determination.pdf |
Show all 12
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
i j 5l 8.
.J.. ...-i �I
�(ci" 0 - �a.
N
U.S. DEPARTMENT OF AGRICULTURE
AGRICULTURAL RESEARCH SERVICE
RECIRCULATING AQUACULTURE ELECTRIC UPGRADES
CONTRACT NO: 12305B21D0013 12305B24F0110
NATIONAL COLD-WATER MARINE AQUACULTURE CENTER (NCWMAC)
FRANKLIN, ME
GENERAL PROJECT DESCRIPTION
VICINITY MAP NOSCALE CD LOCATION MAP NO SCALE EB
THE PURPOSE OF THIS PROJECT IS TO UPGRADE THE EXISTING ELECTRICAL DISTRIBUTION INFRASTRUCTURE TO BE CAPABLE OF HANDLING 1----------------------V-----1-------------------------------1
LARGER LOAD DEMANDS FOR FUTURE PROJECTS.
GENERAL SITE REQUIREMENTS
A. ALL NCWMAC BIOSECURITY PROTOCOLS SHALL BE FOLLOWED AT ALL TIMES. PRIOR TO COMMENCING WORK, THE CONTRACTOR SHALL
OBTAIN THESE REQUIREMENTS IN WRITING FROM USDA.
B. UNINTERRUPTED OPERATION OF THE FACILITY IS REQUIRED. THE CONTRACTOR IS RESPONSIBLE FOR ENSURING SAFE
UNINTERRUPTED OPERATION OF THE FACILITY THROUGHOUT THE PROGRESS OF CONSTRUCTION.
C. LAYDOWN SPACE INSIDE OF THE BUILDINGS IS NOT AVAILABLE. ALL CONSTRUCTION MATERIALS SHALL BE STORED OUTSIDE OF THE
BUILDINGS IN AN AREA IDENTIFIED BY THE GOVERNMENT.
D. NEW UTILITY TRANSFORMER. TRANSFORMER IS PROVIDED AND INSTALLED BY THE UTILITY. EXISTING TRANSFORMER WILL BE REMOVED BY THE UTILITY. CONTRACTOR MUST COORDINATE DISCONNECTION AND OUTAGES WITH UTILITY PRIOR TO WORK.
PROJECT
LOCATION
NATIONAL COLD-WATER MARINE
AQUACULTURE CENTER (NCWMAC)
25 SALMON FARM ROAD
FRANKLIN.ME
• Johnson• M<:Adams PA I-·- - ' - �-· Pl.NINI�• BUIVEYIN8, -
P.0.EIOX�ll,�MIIISIWPPl-((1112)-
A-E FIRM USDA
PROJECT MANAGER EPM
TT XXX
DESIGNER PPM
EH XXX
CHECKED BY SAFETY & HEAL TH
CG XXX
JOB# REAL PROPERTY
3724-E XXX
NO. DATE BY DESCRIPTION
REVISIONS
U USDA Agricultural � Research t I Service S ...,_ _ ___,l;;;......._;;;;;;;;;;;;;;; _____ _.
D A
PROJECT NO.
XXX
DATE
04/18/25
USDA AGRICULTURAL RESEARCH SERVICE
NCWMAC
RECIRCULATING AQUACULTURE ELECTRIC UPGRADES
FRANKLIN, ME
COVER SHEET
AGRICULTURAL RESEARCH SERVICE
NATIONAL COLD-WATER MARINE
AQUACULTURE CENTER
25 SALMON FARM RD.
FRANKLIN, ME 04634
SHEET
T-100
Emilie Oakes david ME seal
INDEX OF DRAWINGS
DRAWING NO. SHEET TITLE
DRAWING INDEXG-100
OF
ELECTRICAL GENERAL NOTES
ELECTRICAL LEGEND
POWER PLAN
DETAILS
POWER RISER
PANEL SCHEDULES
GROUNDING DIAGRAM
ES-002
ES-001
ES-501
ES-101
ES-601
ESG101
ES-602
2 OF
3 OF
4 OF
5 OF
6 OF
7 OF
8 OF
9 OF
GENERAL NOTES:
TITLE SHEETT-100
NO. DATE BY DESCRIPTION
REVISIONS
U S D A
PROJECT NO.
DATE
Agricultural Research Service
USDA AGRICULTURAL RESEARCH SERVICE
NCWMAC
RECIRCULATING AQUACULTURE ELECTRIC UPGRADES
FRANKLIN, ME
SHEET
AGRICULTURE RESEARCH SERVICE
NATIONAL COLD-WATER MARINE
AQUACULTURE CENTER
FRANKLIN, ME 04934
OF
A-E FIRM
PROJECT MANAGER EPM
DESIGNER PPM
CHECKED BY SAFETY & HEALTH
JOB # REAL PROPERTY
USDA
xxxxx xxxxx xxxxx xxxxx xxxxx
3724-M
G-100
DRAWING INDEX
04/18/25
Designer
Author
Checker
1. THE CONTRACTOR SHALL VERIFY ALL SITE CONDITIONS BEFORE COMMENCING WORK. THE CONTRACTOR SHALL VERIFY ALL DIMENSIONS, CONDTIONS, AND EXISTING STRUCTURES AND EQUIPMENT AT THE JOB SITE. THE CONTRACTOR SHALL NOTIFY THE CONTRACTING OFFICER OF ANY DISCREPANCIES FOUND PRIOR TO THE START
OF CONSTRUCTION.
2. THE CONTRACTOR IS REQUIRED TO TAKE PRECAUTIONARY MEASURES TO PROTECT ALL EXISTING UTILITY LINES, STRUCTURES, EQUIPMENT, ETC. IN THE AREAS OF WORK, WHETHER OR NOT SHOWN ON THESE PLANS. ALL DAMAGES CAUSED BY THE CONTRACTOR SHALL BE REPAIRED TO LIKE-NEW CONDITION AND AT THE EXPENSE OF THE CONTRACTOR. IN CASE OF EMERGENCY, IMMEDIATELY NOTIFY THE CONTRACTING OFFICER.
3. CONTRACTOR SHALL PROVIDE THEIR OWN PORTABLE SANITARY FACILITIES IN THE LOCATION APPROVED BY THE CONTRACTING OFFICER. PORTABLE SANITARY
FACILITIES SHALL BE MAINTAINED REGULARLY FOR ODOR CONTROL AND APPEARANCE.
NOTE:
1. NOT ALL ABBREVIATIONS SHOWN WILL BE USED ON THIS PROJECT.
A OR AMP
ACC
AC
AC
AF
AFF
AFG
AHU
AIC
AL
AM
ASYM
AT
ATS
AUTO
AWG
B
BC
BCW
BFF
BFG
BLDG
BMGB
C
CAT
CB
CCT
CCTV
CFCI
CH
CHWCP
CHWP
CHWSP
CKT
CMH
CMS
CP
CPT
CRAC
CRI
CT
CT
CU
CWP
D
DC
DF
DH or DUH
DHWCP
DISC
DOAS
DPST
DPDT
DSCU
DSHP
DSS
DWBP
DX
EC
ECB
EF
ELEC
EMH
EMT
E or EMER
EPA
EQUIP
ERV
ERU
EXIST or EX
EUH
EXP
EWC
EWH
F
FACP
FCU
FLEX
FWE
G OR GND
GFGI
GFI
GRS
GUH
GWH
H or HT
HAC
HOA
HP
HP
HT
HVU
HWCP
HWP
HWRP
HWSP
AMPERE(S)
AIR COOLED CHILLER
ALTERNATING CURRENT
AIR COMPRESSOR / AIR CURTAIN
AMP FRAME
ABOVE FINISHED FLOOR
ABOVE FINISHED GRADE
AIR HANDLING UNIT
AMPERE INTERRUPTING CAPACITY
ALUMINUM
AMMETER
ASYMMETRICAL
AMP TRIP
AUTOMATIC TRANSFER SWITCH
AUTOMATIC
AMERICAN WIRE GAUGE
BOILER
BRANCH CONTROLLER
BARE COPPER WIRE
BELOW FINISHED FLOOR
BELOW FINISHED GRADE
BUILDING
BUILDING MASTER GROUNDING BUSBAR
CONDUIT
CATEGORY
CIRCUIT BREAKER
CORRELATED COLOR TEMPERATURE
CLOSED CIRCUIT TELEVISION
CONTRACTOR FURNISHED CONTRACTOR INSTALLED
CHILLER
CHILLED WATER CIRCULATING PUMP IN A PRIMARY-SECONDARY SYSTEM
CHILLED WATER PUMP
CHILLED WATER SUPPLY PUMP IN A PRIMARY-SECONDARY SYSTEM
CIRCUIT
COMMUNICATIONS MANHOLE
COMBINATION MOTOR STARTER
CONDENSATE PUMP
CONTROL POWER TRANSFORMER
COMPUTER ROOM AC UNIT
COLOR RENDERING INDEX
CURRENT TRANSFORMER
COOLING TOWER
COPPER OR CONDENSING UNIT
CONDENSER WATER PUMP
DEPTH
DIRECT CURRENT
DESTRATIFICATION FAN
DUCT HEATERS
DOMESTIC HOT WATER CIRCULATING PUMP
DISCONNECT SWITCH
DEDICATED OUTSIDE AIR SYSTEM (UNIT)
DOUBLE POLE SINGLE THROW
DOUBLE POLE DOUBLE THROW
DUCTLESS SPLIT CONDENSING UNIT (POWERS THE DSS INDOOR UNIT)
DUCTLESS SPLIT HEAT PUMP (POWERS THE DSS INDOOR UNIT)
DUCTLESS SPLIT SYSTEM (INDOOR UNIT)
DOMESTIC WATER BOOSTER PUMP
DIRECT EXPANSION (DX) COOLING COIL
EMPTY CONDUIT
ENCLOSED CIRCUIT BREAKER
EXHAUST FAN
ELECTRICAL
ELECTRICAL MANHOLE
ELECTRICAL METALLIC TUBING
EMERGENCY
EFFECTIVE PROJECTED AREA
EQUIPMENT
ENERGY RECOVERY VENTILATOR
ENERGY RECOVERY UNIT
EXISTING
ELECTRIC UNIT HEATER
EXPLOSION PROOF
ELECTRIC WATER COOLER
ELECTRIC WATER HEATER
FUSE
FIRE ALARM CONTROL PANEL
FAN COIL UNIT
FLEXIBLE
FURNISHED WITH EQUIPMENT
GROUND
GOVERNMENT FURNISHED GOVERNMENT INSTALLED
GROUND FAULT INTERRUPTER
GALVANIZED RIGID STEEL CONDUIT
GAS UNIT HEATER
GAS WATER HEATER
HEIGHT
HEATED AIR CURTAIN
HAND-OFF AUTOMATIC
HORSE POWER
HEAT PUMP (OUTDOOR PORTION OF SPLIT SYSTEM HEAT PUMP, USE CU FOR
STANDARD DX OUTDOOR UNIT)
HEAT TRACKING
HEATING/VENTILATING UNIT
HEATING WATER CIRCULATING PUMP IN A PRIMARY-SECONDARY SYSTEM
HEATING WATER SUPPLY IN A PRIMARY-ONLY SYSTEM
HOT WATER RECIRCULATION PUMP
HEATING WATER SUPPLY PUMP IN A PRIMARY-SECONDARY SYSTEM
ELECTRICAL ABBREVIATIONS
HWUH
HZ
IDS
IMC
IRH
J OR JB
K
KAIC
KCM OR KCMIL
KEF
KH
KV
KVA
KW
KWHR
L
LA
LAN
LAV
LM
LTG
MAU
MAX
MCA
MCB or MB
MCC
MGB
MH
MIN
MLO
MOD
MT or MTD
MRS
N
NEC
NEMA
NFPA
NC
NESC
NL
NO
NTS
P
PA
PBB
PDU
PF
PH
PIU
PMT
PNL
PTAC
PVC
RBB
RECEPT or RECP
RF
RH
RMC
RMS
RTU
RVNR
SA
SBB
SCCR
SD
SF
S/N
SP
SPD
SPDT
SPEC
SPST
SWBD
SWGR
TEBC
TMGB
TOL
TP
TYP
U
UH
UG
UIO
UL
UTP
V
VA
VAV
VEF
VM
VRF
W
WC
WEF
WH
WHDM
WSHP
WP
WPIU
XFMR
Z
HOT WATER UNIT HEATER
HERTZ
INTRUSION DETECTION SYSTEM
INTERMEDIATE METAL CONDUIT
INFRARED HEATER
JUNCTION BOX
KILO
THOUSAND AMPERE INTERRUPTING CAPACITY
THOUSAND OF CIRCULAR MILS
KITCHEN EXHAUST FAN
KITCHEN HOOD
KILOVOLT
KILOVOLT-AMPERES
KILOWATT
KILOWATT-HOUR
LENGTH
LIGHTNING ARRESTOR
LOCAL AREA NETWORK
LAVATORY
LOCKHEED MARTIN
LIGHTING
MAKE-UP AIR UNIT
MAXIMUM
MINIMUM CIRCUIT AMPACITY
MAIN CIRCUIT BREAKER
MOTOR CONTROL CENTER
MAIN GROUND BAR
MANHOLE or MOUNTING HEIGHT
MINIMUM
MAIN LUGS ONLY
MOTOR OPERATED DAMPER
MOUNT or MOUNTED
MOTOR RATED SWITCH
NEUTRAL
NATIONAL ELECTRICAL CODE
NATIONAL ELECTRICAL MANUFACTURER'S ASSOCIATION
NATIONAL FIRE PROTECTION ASSOCIATION
NORMALLY CLOSED
NATIONAL ELECTRICAL SAFETY CODE
NIGHT LIGHT
NORMALLY OPEN
NOT TO SCALE
POLE(S) or PUMP
PUBLIC ADDRESS
PRIMARY BONDING BUSBAR
POWER DISTRIBUTION UNIT
POWER FACTOR
PHASE
VAV TERMINAL UNIT WITH PARALLEL OR SERIES FAN (PRIMARY INDUCTION UNIT)
PAD MOUNTED TRANSFORMER
PANEL OR PANELBOARD
PACKAGED THRU-WALL AIR CONDITIONER
POLYVINYL CHLORIDE
RACK BONDING BUSBAR
RECEPTACLE
RETURN FAN
RADIANT HEATERS (ELECTRIC)
RIGID METAL CONDUIT
ROOT MEAN SQUARE
ROOF TOP UNIT
REDUCED VOLTAGE NON-REVERSING
SURGE ARRESTOR
SECONDARY BONDING BUSBAR
SHORT CIRCUIT CURRENT RATING
SMOKE DAMPER
SUPPLY FAN
SOLID NEUTRAL
SUMP PUMP
SURGE PROTECTIVE DEVICE
SINGLE POLE DOUBLE THROW
SPECIFICATIONS
SINGLE POLE SINGLE THROW
SWITCHBOARD
SWITCHGEAR
TELECOMMUNICATIONS EQUIPMENT BONDING CONDUCTOR
TELECOMMUNICATIONS MAIN GROUNDING BUSBAR
THERMAL OVERLOAD
TWISTED PAIR
TYPICAL
URINAL
UNIT HEATER
UNDERGROUND
UNLESS INDICATED OTHERWISE
UNDERWRITERS LABORATORY
UNSHIELDED TWISTED PAIR
VOLTS
VOLT AMPERES
VAV TERMINAL UNIT
VEHICLE EXHAUST FAN
VOLTMETER
VARIABLE REFRIGERANT FLOW SYSTEM
WATTS or WIRE or WIDTH
WATER CLOSET
WELDING EXHAUST FAN
WATER HEATER
WATTHOUR DEMAND METER
WATER SOURCE HEAT PUMP
WEATHERPROOF
WEATHERPROOF IN USE
TRANSFORMER
IMPEDANCE
1. THE WORK MUST CONFORM WITH ALL REQUIREMENTS OF:
• NFPA 70, NATIONAL ELECTRICAL CODE (NEC) (2023)
• NFPA 101, LIFE SAFETY CODE (2024)
• UFC 1-200-01, DOD BUILDING CODE (GENERAL BUILDING REQUIREMENTS),
• UFC 1-200-02, HIGH PERFORMANCE AND SUSTAINABLE BUILDING REQUIREMENTS
• UFC 3-501-01, ELECTRICAL ENGINEERING
• UFC 3-520-01 INTERIOR ELECTRICAL SYSTEMS
• UFC 3-530-01, INTERIOR AND EXTERIOR LIGHTING AND CONTROLS
• UFC 3-560-01, OPERATION AND MAINTENANCE: ELECTRICAL SAFETY
• UFC 4-010-01, DOD ANTITERRORISM STANDARDS FOR BUILDINGS
• UFC 4-011-06, CYBERSECURITY FOR FACILITY-RELATED CONTROL SYSTEMS
• ASHRAE 90.1, ENERGY STANDARD FOR BUILDINGS EXCEPT LOW-RISE RESIDENTIAL BUILDINGS (2019)
*CRITERIA AND STANDARDS LISTED ALSO INCLUDE SPECIFIED STANDARDS AND RELATED SECTIONS AS PART OF THE DESIGN.
2. MINIMUM RACEWAY SIZE MUST BE 3/4". INCREASE RACEWAY SIZE AS REQUIRED TO LIMIT RACEWAY FILL RATIO TO LESS THAN 40% FULL.
3. THE ELECTRICAL CONTRACTOR MUST CAREFULLY COORDINATE WORK WITH OTHER TRADES THROUGH THE GENERAL CONTRACTOR AND MUST BE RESPONSIBLE FOR SECURING SPACE REQUIREMENTS FOR ELECTRICAL EQUIPMENT CLEARANCE FOR RECESSED LUMINAIRES AND CORRECT ROUGH-IN
LOCATIONS OF ELECTRICAL CONNECTIONS.
4. ALL FEEDERS AND BRANCH CIRCUITS MUST INCLUDE A GREEN INSULATED GROUND CONDUCTOR, SIZE PER NATIONAL ELECTRICAL CODE, OR AS SHOWN, CONNECTED TO EACH DEVICE AND OUTLET BOX ON THE CIRCUIT AND TO THE PANELBOARD GROUND BUS. PROVIDE A DEDICATED NEUTRAL CONDUCTOR FOR EACH BRANCH CIRCUIT. MULTIPLE BRANCH CIRCUITS IN ONE RACEWAY REQUIRE ONLY ONE GROUND CONDUCTOR.
5. EXISTING ELECTRICAL WORK (NOT SHOWN) MUST REMAIN, UNLESS INDICATED OTHERWISE. SHOULD ANY EXISTING ELECTRICAL POWER, LIGHTING OR AUXILIARY CIRCUIT, FEEDER OR EQUIPMENT BE SEVERED, DISCONNECTED OR DELETED IN THE PROCESS OF CONSTRUCTION OR REMODELING WHICH IS DONE AS A RESULT OF CONTRACT PLANS AND SPECIFICATIONS, AND UNLESS SPECIFICALLY DESIGNATED BY THE DRAWINGS TO BE DELETED, THEN SAID CIRCUIT OR FEEDER MUST BE RESTORED TO WORKING CONDITION. THE RESTORATION MUST INCLUDE RE-ROUTING, RELOCATION, RECONNECTION OR REPLACEMENT AS MAY BE REQUIRED BY THE NEW WORK. ANY SUCH WORK REQUIRED MUST BE INCLUDED IN THE CONTRACT AND NO EXTRA COMPENSATION WILL BE GRANTED.
6. NEW WORK MUST BE MADE TO TIE INTO THE EXISTING IN A UNIFORM MANNER, SIMILAR ITEMS OF NEW WORK MUST BE CHECKED AGAINST EXISTING WORK.
7. REFER TO ONE-LINE DIAGRAMS, SCHEDULES AND RISER DIAGRAMS FOR CONDUCTOR AND CONDUIT SIZES NOT SHOWN ON PLANS.
8. PROVIDE IS AN INCLUSIVE TERM USED TO DESCRIBE ASPECTS OF THE WORK TO BE ACCOMPLISHED, AND IS HEREBY DEFINED TO REQUIRE TO STORE, FURNISH, INSTALL, MOUNT, CONNECT, CONTROL AND POWER EQUIPMENT INDICATED, AS WELL AS ALL APPURTENANCES REQUIRED TO MAKE ELECTRICAL SYSTEMS OPERATE AS INDICATED WITHIN THESE DRAWINGS AND SPECIFICATIONS AND TO FULFILL THE SCOPE OF WORK.
9. DEMOLISH IS AN INCLUSIVE TERM USED TO DESCRIBE ASPECTS OF THE WORK TO BE ACCOMPLISHED, AND IS HEREBY DEFINED TO REQUIRE CONTRACTOR TO DISCONNECT EQUIPMENT FROM ALL CONNECTIONS, REMOVE FROM THE OWNER'S SITE, AND DISPOSE OF IN ACCORDANCE WITH FEDERAL, STATE AND LOCAL LAWS AND ORDINANCES. COST OF DISPOSAL IS ENTIRELY THE CONTRACTOR'S RESPONSIBILITY.
10. ALL CONDUCTORS ARE COPPER UNLESS SPECIFICALLY NOTED AS ALUMINUM.
11. CONTRACTOR MUST FIELD VERIFY ALL EXISTING CONDITIONS, DIMENSIONS AND ELEVATIONS BEFORE PROCUREMENT OF ANY MATERIALS AND DEVELOPMENT
OF ANY SHOP DRAWINGS OR SUBMITTALS.
13. ALL EQUIPMENT PADS FOR INTERIOR ELECTRICAL EQUIPMENT MUST BE FLUSH WITH FRONT SIDE OF EQUIPMENT AND EXTEND AT LEAST 2” BEYOND THE
FOOTPRINT OF THE EQUIPMENT ON ALL OTHER SIDES.
ELECTRICAL GENERAL NOTES:
NO. DATE BY DESCRIPTION
REVISIONS
U S D A
PROJECT NO.
DATE
Agricultural Research Service
USDA AGRICULTURAL RESEARCH SERVICE
NCWMAC
RECIRCULATING AQUACULTURE ELECTRIC UPGRADES
FRANKLIN, ME
SHEET
AGRICULTURE RESEARCH SERVICE
NATIONAL COLD-WATER MARINE
AQUACULTURE CENTER
FRANKLIN, ME 04934
OF
A-E FIRM
PROJECT MANAGER EPM
DESIGNER PPM
CHECKED BY SAFETY & HEALTH
JOB # REAL PROPERTY
USDA
xxxxx xxxxx xxxxx xxxxx xxxxx
3724-M
ES-001
ELECTRICAL GENERAL NOTES
04/18/25
TT
EH
CG
LA-1
LA-1
ELECTRICAL LEGEND
1. ALL EQUIPMENT AND DEVICES ARE TO BE FLUSH MOUNTED UNLESS
OTHERWISE NOTED.
2. DEVICES NOTED AS "GFCI" MUST BE GROUND FAULT CIRCUIT
INTERRUPTING DEVICES.
3. DEVICES NOTED AS "WP" MUST BE GFI AND WEATHERPROOF.
4.
DEVICES NOTED AS "DL" MUST BE RATED FOR DAMP LOCATION.5.
DEVICES NOTED AS "NL" MUST BE NIGHT LIGHTS. PROVIDE
UNSWITCHED POWER TO FIXTURE.
6.
DEVICES NOTED AS "WG" MUST BE PROVIDED AND INSTALLED WITH
A WIRE GUARD.
7.
DEVICES NOTED AS "TR" MUST BE TAMPER RESISTANT.8.
PROVIDE UNSWITCHED POWER TO EMERGENCY BATTERY
PACKS.
PE
DUPLEX RECEPTACLE, NEMA 5-20R, MOUNTED 18" A.F.F. TO
CENTERLINE OF BOX UNLESS NOTED OTHERWISE.
CONTACTOR.
PHOTOCELL.
CEILING MOUNTED JUNCTION BOX.
WALL MOUNTED JUNCTION
BOX.
FLEXIBLE CONNECTION TO
EQUIPMENT.
CONDUIT AND WIRING RECEPTACLESLEGEND GENERAL NOTES MISCELLANEOUS
CONDUCTORS IN CONDUIT CONCEALED WITHIN WALL OR
CEILING. TIC MARKS INDICATE NUMBER OF
CONDUCTORS. THE EQUIPMENT GROUNDING CONDUCTOR
IS NOT SHOWN, BUT MUST BE PROVIDED. SIZE THE
EQUIPMENT GROUNDING CONDUCTOR AND THE CONDUIT
PER THE NEC. THE ABSENCE OF TIC MARKS SIGNIFIES
THAT TWO CONDUCTORS PLUS AN EQUIPMENT GROUNDING
CONDUCTOR SHOULD BE PROVIDED. FOR EXAMPLE, THE
MARKINGS TO THE LEFT SIGNIFY THAT THREE
CONDUCTORS PLUS AN EQUIPMENT GROUNDING
CONDUCTOR SHOULD BE PROVIDED.
CONDUCTORS IN CONDUIT CONCEALED BELOW GRADE OR
FLOOR. TIC MARKS INDICATE NUMBER OF CONDUCTORS.
THE EQUIPMENT GROUNDING CONDUCTOR IS NOT
SHOWN, BUT MUST BE PROVIDED. SIZE THE EQUIPMENT
GROUNDING CONDUCTOR AND THE CONDUIT PER THE
NEC. THE ABSENCE OF TIC MARKS SIGNIFIES THAT TWO
CONDUCTORS PLUS AN EQUIPMENT GROUNDING
CONDUCTOR SHOULD BE PROVIDED. THE MARKINGS TO
THE LEFT SIGNIFY THAT THREE CONDUCTORS PLUS AN
EQUIPMENT GROUNDING CONDUCTOR SHOULD BE
PROVIDED.
THE TEXT INSIDE THE ARC INDICATES THE AWG SIZE OF
THE CONDUCTORS THAT MUST BE RUN IN THE CONDUIT.
THE ABSENCE OF TEXT SIGNIFIES THAT THE
CONDUCTORS SHOULD BE #12 AWG.
CIRCUITRY RUN IN STRAIGHT LINE SEGMENTS SIGNIFIES
EXPOSED SURFACE-MOUNTED RACEWAY (SEE
SPECIFICATIONS).
HOMERUN TO PANELBOARD. ARC DENOTES CONCEALED
CIRCUITRY. TEXT DENOTES PANELBOARD NAME WITH
CIRCUIT NUMBER. DEVICES HAVING CIRCUIT NUMBERS
LOCATED BESIDE THEM MAY NOT SHOW THE CIRCUIT
NUMBERS AT THE HOMERUN ARROWS.
PARTIAL HOMERUN TO PANELBOARD. COMBINE ALL
PARTIAL HOMERUNS THAT ARE ON THE SAME CIRCUIT IN
A JUNCTION BOX PRIOR TO ENTERING THE PANELBOARD.
LOW VOLTAGE CONDUCTORS USED FOR MOTION DETECTOR
CIRCUITRY. SEE MANUFACTURER'S RECOMMENDATIONS
FOR CONDUCTOR REQUIREMENTS.
C
J
J
DEVICES NOTED AS "WPIU" MUST BE GFI AND WEATHERPROOF IN USE.
9.
LONG TIC MARK IDENTIFIES CONDUCTOR. SHORT TICK MARK
IDENTIFIES NEUTRAL. HOOKED TIC MARK IDENTIFIES GROUND.
MECHANICAL ELECTRICAL
CONNECTION. TOP VALUE
REPRESENTS VOLTAGE AND PHASE.
BOTTOM VALUE IS IDENTIFIER.
120 V 1P
M1
GROUND FAULT CIRCUIT INTERRUPTOR DUPLEX RECEPTACLE, NEMA
5-20R, MOUNTED 18" A.F.F. TO CENTERLINE OF BOX UNLESS NOTED
OTHERWISE.
GFCI
NO. DATE BY DESCRIPTION
REVISIONS
U S D A
PROJECT NO.
DATE
Agricultural Research Service
USDA AGRICULTURAL RESEARCH SERVICE
NCWMAC
RECIRCULATING AQUACULTURE ELECTRIC UPGRADES
FRANKLIN, ME
SHEET
AGRICULTURE RESEARCH SERVICE
NATIONAL COLD-WATER MARINE
AQUACULTURE CENTER
FRANKLIN, ME 04934
OF
A-E FIRM
PROJECT MANAGER EPM
DESIGNER PPM
CHECKED BY SAFETY & HEALTH
JOB # REAL PROPERTY
USDA
xxxxx xxxxx xxxxx xxxxx xxxxx
3724-M
ES-002
ELECTRICAL LEGEND
04/18/25
TT
EH
CG
RPB
DP-4
P-D
P-G1
P-G2
P-C
P-H L-L
P-A2
P-A1
P-J1
P-J2
MDP
UT-1
ATS
DT-1
DP-1
UT-1
MDP-2
ATS-2
GEN-1
NO. DATE BY DESCRIPTION
REVISIONS
U S D A
PROJECT NO.
DATE
Agricultural Research Service
USDA AGRICULTURAL RESEARCH SERVICE
NCWMAC
RECIRCULATING AQUACULTURE ELECTRIC UPGRADES
FRANKLIN, ME
SHEET
AGRICULTURE RESEARCH SERVICE
NATIONAL COLD-WATER MARINE
AQUACULTURE CENTER
FRANKLIN, ME 04934
OF
A-E FIRM
PROJECT MANAGER EPM
DESIGNER PPM
CHECKED BY SAFETY & HEALTH
JOB # REAL PROPERTY
USDA
xxxxx xxxxx xxxxx xxxxx xxxxx
3724-M
ES-101
POWER PLAN
04/18/25
TT
EH
CG
3/32" = 1'-0"ES-101
POWER PLAN - PHASE 11
SCALE: = 1'-0"3/32"
0 11 21 3211
N
A. CONTRACTOR IS RESPONSIBLE FOR LOCATING ALL BELOW
GRADE UTILITIES BEFOR ANY EXCAVATION IS PERFORMED.
GENERAL NOTES
X
1. NEW UTILITY TRANSFORMER. TRANSFORMER IS PROVIDED
AND INSTALLED BY THE UTILITY. EXISTING TRANSFORMER
WILL BE REMOVED BY THE UTILITY. CONTRACTOR MUST
COORDINATE DISCONNECTION AND OUTAGES WITH UTILITY
PRIOR TO WORK. CONTRACTOR MUST REMOVE EXISTING
TRANSFORMER VAULT. THE NEW VAULT WILL BE PROVIDED
AND INSTALLED BY THE CONTRACTOR. SEE DETAIL 1/ES-501
FOR MORE DETAILS. PROPOSED NEW LOCATION SHOW BY
DASHED OUTLINE.
2. NEW PADMOUNTED EXTERIOR RATED AUTOMATIC
TRANSFER SWITCH RATED FOR 1600 AMPS. ATS MUST BE
SERVICE ENTRANCE RATED AND INCLUDE MAINTENANCE
BYPASS.
3. EXISTING 500KW GENERATOR. REMOVE EXISTING
CONDUCTOR AND CONDUIT GOING TO MDP.
4. NEW PADMOUNTED EXTERIOR RATED SWITCHBOARD. SEE
RISER FOR MORE DETAILS.
5. EQUIPMENT WITHIN DASHED LINES ARE EXISTING TO
REMAIN UNLESS OTHERWISE NOTED.
6. REMOVE EXISTING AUTOMATIC TRANSFER SWITCH. RE-
FEED MDP TO NEW MDP-2.
KEYED NOTES
GRADE OR
SLAB ON GRADE
USE SCHEDULE 40
POLYVINYL CHLORIDE (PVC)
CONDUIT FOR CIRCUITS
UNDERGROUND. USE PVC-COATED
GALVANIZED RIGID STEEL
ELBOWS.
USE GALVANIZED RIGID
STEEL OR INTERMEDIATE
METAL CONDUITS WHERE
CIRCUITS ARE EXPOSED TO
ABRASION.
USE PVC-COATED GALVANIZED
RIGID STEEL CONDUIT FOR ALL
VERTICAL RUNS EXTENDING 6"
ABOVE GRADE.
USE INTERMEDIATE METAL
CONDUITS OR ELECTRICAL
METALLIC TUBING FOR ALL
BRANCH CIRCUITS, FEEDERS,
AND AUXILIARY CIRCUITS
REQUIRING 1-1/4" NOMINAL
TRADE SIZE OR LARGER IN
DRY LOCATIONS.
UNDERGROUND
CONDUIT.
24"
MINIMAL
NOTE : GALVANIZED RIGID STEEL CONDUIT
COATED WITH TWO COMPLETE COATS OF
ASPHALTIC OR BITUMINOUS PAINT MAY BE
USED IN LIEU OF PVC-COATED GALVANIZED
RIGID STEEL CONDUITS.
USE GALVANIZED RIGID
STEEL CONDUITS WHERE
CIRCUITS ARE RUN ABOVE
GROUND EXPOSED TO
WEATHER.
SERVICES, CONDUITS FOR
PRIMARY CONDUCTORS, AND
CONDUITS RUN UNDER
ROADWAYS MUST BE
BURIED NO LESS THAN 24"
DEEP.
6"
NOTE : GRS & IMC CONDUIT THREADS
MUST BE GALVANIZED AFTER
CUTTING.
USE PVC-COATED
GALVANIZED RIGID STEEL
ELBOWS.
USE PVC-COATED GALVANIZED
RIGID STEEL CONDUIT FOR ALL
VERTICAL RUNS EXTENDING 6"
ABOVE GRADE.
6"
NO. DATE BY DESCRIPTION
REVISIONS
U S D A
PROJECT NO.
DATE
Agricultural Research Service
USDA AGRICULTURAL RESEARCH SERVICE
NCWMAC
RECIRCULATING AQUACULTURE ELECTRIC UPGRADES
FRANKLIN, ME
SHEET
AGRICULTURE RESEARCH SERVICE
NATIONAL COLD-WATER MARINE
AQUACULTURE CENTER
FRANKLIN, ME 04934
OF
A-E FIRM
PROJECT MANAGER EPM
DESIGNER PPM
CHECKED BY SAFETY & HEALTH
JOB # REAL PROPERTY
USDA
xxxxx xxxxx xxxxx xxxxx xxxxx
3724-M
ES-501
DETAILS
04/18/25
TT
EH
CG
N.T.S.ES-501
TRANSFORMER VAULT DETAIL1
NOT TO SCALEES-501
CONDUIT DETAIL2
CONTRACTOR MUST
N.T.S.
FEEDER SCHEDULE
ID FEEDER
AMPS
CONDUIT AND FEEDER
100 1-1/2"C,3#1,#1N,#8G
125 1-1/2"C,3#1/0,#1/0N,#6G
125 1-1/2"C,3#1/0,#6G
200 2"C,3#3/0,#3/0N,#6G
225 2-1/2"C,3#4/0,#4/0N,#4G
400 3-1/2"C,3#600kcmil,#600kcmil N,#2G
400 3-1/2"C,3#600kcmil,#600kcmil N,#1/0G
600 (2)3"C,3#350kcmil,#350kcmil N,#1G
1000 (3)3"C,3#400kcmil,#400kcmil N,#2/0G
SIZING METHOD: COPPER, 60°C #12 THROUGH #1, 75°C 1/0 AND ABOVE
1600S
1000.A
400J
125D
70 70 1-1/4"C,2#4,#4N,#8G
125 1-1/4"C,2#1/0,#6G125/2D
150 1-1/2"C,3#1/0,#6G150DJ
1600 (4)3-1/2"C,3#600kcmil,#600kcmil N,#4/0 G1600
(4)3-1/2"C,3#600kcmil,#600kcmil N
EXISTING TO REMAIN
NEW WORK
1000.A
1000A 3P
LS1
1600S
1600S
600A 3P L
225A 3P L
400A 3P L
MDP-2
480Y/277V 3P 4W 1600A
XFMR UT-1
1,000 KVA
480Y/277V
GEN-1
480Y/277V 3P
500KW
400A 3P
225A 3P
225A 3P
100A 3P
125A 3P
200A 3P
PANEL
P-G2 225A
MLO
208Y/120V 3P 4W
PANEL
P-G1 225A
MLO
208Y/120V 3P 4W
PANEL
P-H
225A
MLO
208Y/120V 3P 4W
PANEL
P-J2 100A
MLO
208Y/120V 3P 4W
PANEL
P-J1 100A
MLO
208Y/120V 3P 4W
DP-1
208Y/120V 3P 4W 400A
XFMR DT-1
75 KVA
480V
TO 208Y/120V
PANEL
L-L
100A
MLO
480Y/277V 3P 4W
PANEL
P-A2 225A
MLO
480Y/277V 3P 4W
PANEL
P-A1 225A
MLO
480Y/277V 3P 4W
PANEL
P-C
100A
MLO
480Y/277V 3P 4W
PANEL
P-B
225A
MLO
480Y/277V 3P 4W
MDP
480Y/277V 3P 4W
1200AF
P-D 480Y/277V 3P 4W 400A
MLO
PANEL
DP-E
200A
MLO
480Y/277V 3P 4W
225 100
100125225
400J
225 100
400225225100
125D
ATS-2
1600A
1600A 3P
LS1G
M
FAULT CURRENT SCHEDULE
DEVICE FAULT AIC RATING L-L VOLTS FEEDER
SIZE
FEEDER
LENGTH
RATING
GEN-1 12,000
(4)#600KCMIL
UT-1
ATS-2
MDP-2
20,928
20,723
20,438
22,000
22,000
22,000
480V
480V
480V
480V (4)#600KCMIL
15' / 27'
22'
1000 KVA
500 KW
1600 A
1200 A
NO. DATE BY DESCRIPTION
REVISIONS
U
S
D
A
PROJECT NO.
DATE
Agricultural Research Service
USDA AGRICULTURAL RESEARCH SERVICE
NCWMAC
RECIRCULATING AQUACULTURE ELECTRIC UPGRADES
FRANKLIN, ME
SHEET
AGRICULTURE RESEARCH SERVICE
NATIONAL COLD-WATER MARINE
AQUACULTURE CENTER
FRANKLIN, ME 04934
OF
A-E FIRM
PROJECT MANAGER EPM
DESIGNER PPM
CHECKED BY SAFETY & HEALTH
JOB # REAL PROPERTY
USDA
xxxxx xxxxx xxxxx xxxxx xxxxx
3724-M
ES-601
POWER RISER
04/18/25
TT
EH
CG
A. NEW PADMOUNTED EXTERIOR RATED AUTOMATIC
TRANSFER SWITCH. ATS-2 MUST BE SERVICE ENTRANCE
RATED AND INCLUDE MAINTENANCE BYPASS.
B. INTERCEPT AND EXTEND EXISTING FEED FROM ATS-2 TO
EXISTING UTILITY TRANSFORMER. ROUTE FEEDER TO NEW
EXTERIOR SWITCHBOARD "MDP-2" AS SHOW ON RISER.
PROVIDE NEW BREAKER, WIRE AND CONDUIT AS SHOWN.
C. NEW UTILITY TRANSFORMER. TRANSFORMER IS PROVIDED
AND INSTALLED BY THE UTILITY. EXISTING TRANSFORMER
WILL BE REMOVED BY THE UTILITY. CONTRACTOR MUST
COORDINATE DISCONNECTION AND OUTAGES WITH UTILITY
PRIOR TO WORK. CONTRACTOR MUST REMOVE EXISTING
TRANSFORMER VAULT. CONTRACTOR MUST INSTALL A
NEW TRANSFORMER VAULT. THE NEW VAULT WILL BE
PROVIDED AND INSTALLED BY THE CONTRACTOR. SEE
DETAIL 1/E-501 FOR MORE DETAILS.
D. NEW PADMOUNTED EXTERIOR RATED SERVICE ENTRANCE
RATED SWITCHBOARD.
E. 600A 3P BREAKER SHOWN EXISTING ON MDP-2 IS FOR
PANEL P-NM WHICH IS A PROPOSED PANEL FOR ANOTHER
PROJECT. SHOWN FOR CALCULATION PURPOSES.
GENERAL NOTES
N.T.S.ES-601
POWER RISER - PHASE 11
NO. DATE BY DESCRIPTION
REVISIONS
U S D A
PROJECT NO.
DATE
Agricultural Research Service
USDA AGRICULTURAL RESEARCH SERVICE
NCWMAC
RECIRCULATING AQUACULTURE ELECTRIC UPGRADES
FRANKLIN, ME
SHEET
AGRICULTURE RESEARCH SERVICE
NATIONAL COLD-WATER MARINE
AQUACULTURE CENTER
FRANKLIN, ME 04934
OF
A-E FIRM
PROJECT MANAGER EPM
DESIGNER PPM
CHECKED BY SAFETY & HEALTH
JOB # REAL PROPERTY
USDA
xxxxx xxxxx xxxxx xxxxx xxxxx
3724-M
ES-602
PANEL SCHEDULES
04/18/25
TT
EH
CG
Total Est. Demand: 1163 A
Total Conn.: 1288 A
Total Est. Demand: 967143 VA
Spare 552963 VA 100.00% 552963 VA Total Conn. Load: 1070688 VA
MECHANICAL 517725 VA 80.00% 414180 VA
Load Classification Connected Load Demand Factor Estimated... Panel Totals
Legend:
Total... 1289 A 1290 A 1287 A
Total Load: 357023 VA 357123 VA 356543 VA
41 42
39 40
37 38
35 36
33 34
31 32
29 30
27 28
25 26
23 24
21 22
19 20
17 18
15 16
13 14
11 -- -- 28155 62352 -- -- 12
9 -- -- 28155 62352 -- -- 10
7 P-H1 3P225 A 28155 62352 3P400 A P-H2 8
5 -- -- 266035 6
3 -- -- 266035 580 -- -- 4
1 MDP 3P20 A 266035 480 2P70 A QT-1 2
CKT Circuit Description Breaker A B C Breaker Circuit Description CKT
Notes:
Enclosure: Type 2 MCB Rating: 1600 A
Mounting: Recessed Wires: 4 Mains Rating: 1600 A
Supply From: ATS-2 Phases: 3 Mains Type: BREAKER
Location: Volts: 480/277 Wye A.I.C. Rating: SEE SCHEDULE
Branch Panel: MDP-2
P-H1 (ON CKT 7, 9, 11), P-H2 (ON CKT 8, 10, 12), AND QT-1 (ON CKT 2, 4) ARE PROPOSED FOR A FUTURE PROJECT.
THEY ARE SHOWN FOR LOAD AND PLANNING PURPOSES.
G
N
MAIN DISTRIBUTION PANEL (MDP-2)
N
G
N
G
TYPICAL 480V
PANELBOARD
N
G
SBJ
N
G
TYPICAL 208V
PANELBOARD
GEC
EBJ
EBJ
SSBJ
SSBJ
TYPICAL STEP-DOWN
TRANSFORMER
SEE DETAIL C4/E503
EBC
SSBJ
SSBJ
BMGB - MDP-2
SEE DETAIL A3/E507
TRANSFORMER (UT-1) WATER PIPE
(MAIN SERVICE)
BUILDING
STEEL
#4/0
GEC
#3/0 AWG BARE
COPPER GROUNDING
CONDUCTOR BURIED
30" BELOW GRADE.
TRANSFORMER
HOUSING
3/4" DIAMETER X 10' LONG COPPER
CLAD GROUND ROD. INSTALL TOP
OF GROUND ROD MINIMUM 24"
BELOW FINISHED GRADE.
(TYPICAL)
GROUND LOOP
AROUND SUPPLY
TRANSFORMER.
#3/0(G), 1" PVC C.
SERVICE PAD MOUNTED
TRANSFORMER. SEE
2/ES-501 FOR
GROUNDING DETAILS. #4(G), 3/4" PVC C.
#6(G), 3/4" PVC C.
MBJ
BOND GROUND TO
NEUTRAL IN MDP
SBJ
EXISTING
BUILDING
GROUNDING
NETWORK
NOTE: EXTEND ALL NON-
PANEL GROUNDS FROM
EXISTING MDP TO NEW
BMGB
G
N
GENERATOR (GEN-1)
#4/0
GEC
#3/0 AWG BARE
COPPER GROUNDING
CONDUCTOR BURIED
30" BELOW GRADE.
TRANSFORMER
HOUSING
3/4" DIAMETER X 10' LONG COPPER
CLAD GROUND ROD. INSTALL TOP
OF GROUND ROD MINIMUM 24"
BELOW FINISHED GRADE.
(TYPICAL)
GROUND LOOP
AROUND SUPPLY
TRANSFORMER.
PAD MOUNTED
GENERATOR. SEE
1/ES-501 FOR
GROUNDING DETAILS.
SBJ
NORMAL ALT
N-LOAD
G
(ATS-2)
NO. DATE BY DESCRIPTION
REVISIONS
U S D A
PROJECT NO.
DATE
Agricultural Research Service
USDA AGRICULTURAL RESEARCH SERVICE
NCWMAC
RECIRCULATING AQUACULTURE ELECTRIC UPGRADES
FRANKLIN, ME
SHEET
AGRICULTURE RESEARCH SERVICE
NATIONAL COLD-WATER MARINE
AQUACULTURE CENTER
FRANKLIN, ME 04934
OF
A-E FIRM
PROJECT MANAGER EPM
DESIGNER PPM
CHECKED BY SAFETY & HEALTH
JOB # REAL PROPERTY
USDA
xxxxx xxxxx xxxxx xxxxx xxxxx
3724-M
ESG101
GROUNDING DIAGRAM
04/18/25
TT
EH
CG
N. T. S.ESG101
Grounding Diagram1
A. GROUNDING COMPONENTS MUST BE TRANSFERED TO
MDP-2 FROM MDP AND TO ATS-2 FROM ATS.
GENERAL NOTES
File details come from the government source that posted it. Updated .