Attachment 5 - Drawings 100 Percent - Mathers VAMC - Part 5 - Final.pdf

PDF 315 KB Posted

Attached to
Y1DZ--Facility for Mental Health Primary Care Modalities - Minor Construction - Mather VAMC
Solicitation number
36C77624B0005
Issued by

About this file

This document contains drawings and specifications for a fire sprinkler system at the Mathers Veterans Affairs Medical Center in Mather, California. The drawings show the layout of sprinklers on level two and include notes specifying that upright sprinkler heads are to be provided in unfinished areas as indicated. Deductive alternates are shown for administrative offices, human resources offices, and a sleep study patient suite, with requirements to provide upright sprinkler heads in areas where ceilings are removed. The related federal contract opportunity is a solicitation for a minor construction project to construct a facility for mental health and primary care alternative modalities at the Mathers VAMC, to be awarded by the Department of Veterans Affairs Technology Acquisition Center in Austin, Texas.

View the file

Other files

Show all 19

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

GENERAL NOTES

A. THESE DOCUMENTS REPRESENT THE DESIGN INTENT AND COVERAGE AREA FOR THE

FIRE SPRINKLER SYSTEM WITHIN THE PROJECT SCOPE. THE CONTRACTOR IS

RESPONSIBLE FOR PROVIDING A COMPLETE FIRE SPRINKLER SYSTEM APPROVED PER

NFPA AND BY THE AUTHORITY HAVING JURISDICTION. PROVIDE HYDRAULIC

CALCULATIONS, SHOP DRAWINGS, AND ANY ADDITIONAL EQUIPMENT NECESSARY TO

COMPLETE THE INSTALLATION AND COMPLY WITH THE SPECIFICATIONS AND ALL

APPLICABLE CODES AND CRITERIA.

B. THE SPACING AND SIZES OF SPRINKLERS AND PIPES SHALL CONFORM TO THE

REQUIREMENTS OF NFPA 13. SPRINKLERS SHALL BE INSTALLED BY PERSONNEL WHO

HAVE ENGINEERING FACILITIES AND EXPERIENCE IN SUCH WORK AND WHO ARE

REGULARLY EMPLOYED TO DO SUCH WORK.

C. PROVIDE A UL AND FM LISTED SPRINKLER GUARD IN LOCATIONS WHERE SPRINKLERS

ARE SUBJECT TO MECHANICAL DAMAGE; INCLUDING IN MECHANICAL ROOMS,

ELECTRICAL ROOMS, STAIRWELL LANDINGS, ELEVATOR SHAFTS, AND ON ALL

SPRINKLERS INSTALLED BELOW 7'-0" AFF.

D. PROVIDE SEISMIC PROTECTION IN ACCORDANCE WITH NFPA 13. CONTRACTOR SHALL

SUBMIT LOAD CALCULATIONS FOR SIZING OF SWAY BRACING FOR SYSTEMS THAT ARE

REQUIRED TO BE PROTECTED AGAINST DAMAGE FROM EARTHQUAKES.

E. HAZARD CLASSIFICATION IS LIGHT HAZARD UNLESS NOTED OTHERWISE. REFER TO

PLAN.

SPRINKLER LEGEND

REFER TO SPECIFICATION 21 13 13 FOR RESPONSE TYPE AND TEMPERATURE

RATING FOR EACH APPLICATION.

SEMI-RECESSED SPINKLER HEAD

UPRIGHT SPINKLER HEAD

SIDEWALL SPRINKLER HEAD

1 2 3 4

J

H

G

F

E

A

B

C

A.4

61.5

D

2.5 3.5

HAC

2A-205

ELEC

2A-203

ELEVATOR

2A-201

VESTIBULE

2A-200

IDF

2E-263

ROOF BELOW

CLEAN UTILITY

& SUPPLY

2D-232

SHAFT

2D-227

EXAM

2D-224

SOILED

UTILITY

2D-236

EXAM

2D-222

OFFICE

2D-237

OFFICE

2D-235

OFFICE

2D-233

OFFICE

2D-231

OFFICE

2D-225

OFFICE

2E-265

CONFERENCE

ROOM

2E-261

LACTATION

ROOM

2B-207

CHECK-IN /

WAITING AREA

2B-206

CPAP

STORAGE

2D-234

FEMALE

2B-211

MALE

2B-209

OFFICE

2D-223

EWC3

CORRIDOR

2D-220

CORRIDOR

2E-260

CORRIDOR

2D-240

CORRIDOR4

simsim

DEDUCTIVE ALTERNATE 4 -

HUMAN RESOURCES

DEDUCTIVE ALTERNATE 5 -

SLEEP STUDY PATIENT SUITE

D E

D U

C T

IV

E

A L

T E

R N

A T

E

A D

M

IN

IS

T

R A

T

IV

E O

F F

IC

E

S

A8.20 / 04

A8.20 / 01

1050 E. Southern Ave, Suite #D, Tempe, Arizona 85282, (480) 751-9542 designgroup

Architecture, Engineering, and Sustainable DesignAESUS

KEY PLAN NTS

NORTH

Drawing Title: Project Title:

Date

Location

Checked

Building Number:

Project Number:

Drawing Number:

Drawn

Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management

Construct Facility for Mental Health and Primary Care Alternative Modalities

Location:

100% Bid Set Submittal

8/18/2023 o n e e ig h th in c h o n e fo o t

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM

08-6231

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

Dwg. of

612-908

VANCHCS

10535 HOSPITAL WAY MATHER, CA 95655

AESUS

PROJECT

AREA

MAIN

HOSPITAL

FP2.25

FIRE PROTECTION PLAN - SPRINKLERS

(DEDUCTIVE ALTERNATE 3, 4 & 5)

LEGEND NOTES

1 PROVIDE UPRIGHT SPINKLERS IN SHELLED AREAS, AS INDICATED.

1/8" = 1'-0"

FIRE PROTECTION LEVEL 2 (DEDUCT 3, 4 & 5)

DEDUCTIVE ALTERNATES NOTES:

A. REFER TO COST ESTIMATE FOR COMPLETE LIST OF DEDUCTIVE ALTERNATES

B. DEDUCTIVE ALTNERATES SHOWN ON THIS SHEET ARE RELATIVE TO PHASED

BUILD OUT OF LEVEL 02 ONLY

DEDUCTIVE ALTERNATE #3:

CEILINGS ARE REMOVED IN DEDUCT AREA. PROVIDE UPRIGHT SPINKLER HEADS AS

INDICATED.

DEDUCTIVE ALTERNATE #4:

CEILINGS ARE REMOVED IN DEDUCT AREA. PROVIDE UPRIGHT SPINKLER HEADS AS

INDICATED.

DEDUCTIVE ALTERNATE #5:

CEILINGS ARE REMOVED IN DEDUCT AREA. PROVIDE UPRIGHT SPINKLER HEADS AS

INDICATED.