Attachment 4 - Keesler Guidance for Premise Wiring Jan 2023.pdf

PDF 678 KB Posted

Attached to
Renovate B412 for DCSA Phase 2
Solicitation number
FA301023R0040
Issued by

About this file

This guidance document outlines standards for premise wiring installations and renovations at Keesler Air Force Base. It supplements Telecommunications Industry Association and Electronic Industry Alliance commercial standards. All premise wiring must be category 6 or above and terminate using the 568B standard. Cable must be independently supported with labels on both ends encoded per the identified standard. Grounding methods and labeling standards are also provided. Contractors must have BICSI-certified technicians on site and provide as-built drawings and test results. The related federal contract opportunity is for renovations to building B412 for the Defense Counterintelligence and Security Agency under solicitation number FA301023R0040 issued by the Department of the Air Force Air Education and Training Command.

View the file

Other files

File Type Posted
Attachment 16 - Fire Alarm Clarification.pdf PDF
Solicitation Amendment FA301023R00400002 SF 30.pdf PDF
Solicitation Amendment - FA301023R00400002.pdf PDF
Attachment 15 - MAHG21-1099 Reno B412 DCSA Phase 2 Questions and Answers.pdf PDF
Solicitation Amendment - FA301023R00400001.pdf PDF
Solicitation Amendment FA301023R00400001 SF 30.pdf PDF
FA301023R0040 Pre-Bid Site Visit Sign-in.pdf PDF
Mechanical Room Photos.pdf PDF
Attachment 10 - Manufacturer Carpet and Adhesive Pricing Sheet.pdf PDF
Attachment 5 - Appendix A AIR BALANCE DIAGRAM.pdf PDF
Attachment 6 - Appendix B MECH RM - DUCT DEMO.pdf PDF
Attachment 2 - Renovate B412 DCSA Phase 2 Specifications 8.10.2023.pdf PDF
Attachment 8 - MAHG 211099 Renovate B412 DCSA Ph-2 MSS.xls XLS spreadsheet
Attachment 3 - Renovate B412 DCSA Ph 2 Drawings 10.24.2022.pdf PDF
Attachment 9 - USAF Carpet Ordering Guide Jan2022.pdf PDF
Attachment 1 - Renovate B412 DCSA Phase 2 SOW 8.10.2023.pdf PDF
Attachment 12 - Past Performance Reference List.pdf PDF
Attachment 7 - Appendix C MECH RM - DUCT INSTALL.pdf PDF
Attachment 11 - Past Performance Questionnaire.pdf PDF
Attachment 14 - Submittal Procedures.pdf PDF
Attachment 13 - Wage Determination MS 20220050.pdf PDF
Solicitation - FA301023R0040.pdf PDF
Show all 22

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

This guide is supplemental in nature and not all inclusive.

PREMISE WIRING GUIDANCE

Revision D, January 2023

Attachment 4

FA301023R0040

81st COMMUNICATIONS SQUADRON PREMISE WIRING GUIDANCE

Revision D, January 2023 Page 2 of 12

GENERAL

1. The purpose of this document is to supplement Telecommunications Industry Association/Electronic Industry Alliance (TIA/EIA) commercial standards for premise wiring (Local Area Network cabling) on Keesler AFB.

2. New construction or renovations programming premise wiring work requires coordination with the 81 CS/SCXP Plans and Programs Office, contact # 377- 7500 prior to implementation.

3. All premise wiring installed on Keesler AFB will conform to TIA/EIA wiring standards listed at the end of this document and the supplemental guidance contained in the attachments within this document.

4. Any deviations from the attached standards and this supplement should be coordinated and approved by the 81 CS/SCXP.

5. Contractual responsibilities:

5.1 Contractors selected to complete premise wiring work must have at least one experienced\technically certified Building Industry Consulting Service International (BICSI) technician on site.

5.2 Provide as-built drawings for the premise wiring work accomplished identifying installation/relocation work.

5.3 Provide test results for new\relocated premise wiring work accomplished.

5.4 Contractors shall be responsible for restoring work areas to original condition.

5.5 81 CS quality assurance office 81 CS/SCQ will be the approving authority for premise wiring work accomplished in new construction or renovations.

Revision D, January 2023 Page 3 of 12

RACKS/CABINETS (If installed)

Cabinets/Racks will be labeled on the front and rear at the top and bottom on a permanent part of the cabinet/rack. Text on labels shall be machine printed without serifs, uppercase and large enough to be read while standing near the cabinet/rack. The label color will contrast with surface upon which it is affixed (white on a dark surface, black on a light surface)(ANSI/TIA/EIA-606-A-1 section 11).

RACK 1 RACK 1

RACK 1 RACK 1

Revision D, January 2023 Page 4 of 12

CABLING

All copper cables, connectors, ports, jacks, outlets, and patch panels shall be TIA/EIA Category 6 rated and must be compatible with Panduit Mini-Com UTP RJ45 TG Jack Modules.

Cat 5e UTP

Cat 6 UTP

Cat 6 FTP

Cat 6A UTP

CABLE COLOR CODING

All installations and renovations will use the following cable color code:

Alarms/Cameras – yellow Public Address (PA) Systems – gray Secure Comm (encrypted) – red Data/Voice - blue

Revision D, January 2023 Page 5 of 12

TERMINATIONS

All premise cabling supporting a Local Area Network will be terminated using 568B standards.

Pairs will not be untwisted more than .5 inch. Cable jacket will not be stripped back more than 1 inch. No nicks on the inner conductors.

Revision D, January 2023 Page 6 of 12

CABLE MANAGEMENT

The Contractor shall ensure a neat and orderly installation utilizing proper cable management IAW current applicable standards. Data drops shall be routed in a manner to ensure the cables are protected and aesthetically pleasing along the cable path. Metal raceways (cable ladder or wire basket) shall be installed and/or utilized in all communication rooms.

• Cable trays shall be installed and/or utilized in all communication rooms.

• Cables will be independently supported off the ceiling with supports no more than 60 inches apart.

• Cable route should avoid fluorescent light ballasts, electrical cables and motors.

Revision D, January 2023 Page 7 of 12

CABLE MANAGEMENT (continued)

• Cable jackets must not be distorted. Velcro or nylon are acceptable – Velcro is better at protecting cable geometry. Staples will not be used.

• Any building penetrations (to include wall, ceiling, or floor), shall be in compliance with National Fire Protection Agency (NFPA) regulations and coordinated with CSC’s structural office and fire department.

Revision D, January 2023 Page 8 of 12

LABELING

All labeling shall be machine generated, without serifs, uppercase and large enough to be easily read (ANSI/TIA/EIA-606-A-1 section 11).

The naming scheme shall also be coordinated with the 81st Communications Squadron (81 CS/SCXP).

• Outlet(s)

• Patch Panel(s)

Example of a single quad data outlet located in room 32 and terminating in TR 110, Rack 1, Panel 1 and starting in port #1 of the patch panel

Example of a second quad data outlet located in room 32 and terminating in TR 110, Rack 1, Panel 1 and starting in port #5 of the patch panel

32-1 A B C D

32-2 A B C D

Example of RACK 1 PANEL 1 located in TR 110 and connecting to Room 32 Outlets 1 and 2.

Revision D, January 2023 Page 9 of 12

LABELING (continued)

• Cables - All cables will be labeled on both ends with encoded identifiers per (ANSI/TIA/EIA-606-A-1 section 11).

(located within 12 inches of faceplate) (located within 12 inches of patch panel)

110-1-1-1

110-1-1-2

110-1-1-3

110-1-1-4

32-1-A

32-1-B

32-1-C

32-1-D

RACK 1

Example of a single quad data outlet located in room 32 and terminated in TR 110, Rack 1, Panel 1 and starting in port #1 of the patch panel

Revision D, January 2023 Page 10 of 12

GROUNDING (TIA-607-B) (If installed)

All grounds will be labeled (ANSI/TIA-607-B para 7.8) (if installed).

All ground connections will have a clear margin of bare metal-to-metal contact (ANSI/TIA-607-B para 7.6).

Cabinets, racks and other enclosures shall not be bonded serially, each shall have their own dedicated bonding conductor (ANSI/TIA-607-B para 7.1.4).

Revision D, January 2023 Page 11 of 12

Premise Wiring References

NUMBER TITLE WEBSITE OR LOCATION

BICSI TDM Manual Building Industries Consulting Services International (BICSI) Telecommunications Distribution Methods (TDM) Manual http://www.bicsi.org/

NFPA 70 (2008) National Fire Protection Association (NFPA), National Electric Code (NEC) http://www.nfpa.org/

29 CFR 1910.268 Occupational Safety and Health Standards, Telecommunications http://www.osha.gov

ANSI American National Standards Institute (ANSI) and Internet Standards Resources http://www.ansi.org/

TIA Telecommunications Industry Association (TIA): TIA Standards See Commodity Specific Appendices and Individual Task Orders https://tiaonline.org/

TIA-526-7 (Jul 2015) Measurement of Optical Power Loss of Installed Single-Mode Fiber Cable Plant https://global.ihs.com/csf_hom e.cfm?&csf=TIA

TIA-568.0

(Mar 2020)

Generic Telecommunications Cabling for Customer Premises https://global.ihs.com/csf_hom e.cfm?&csf=TIA

TIA-568 SET (Mar 2020)

Commercial Building Telecommunications Cabling Standard https://global.ihs.com/csf_hom e.cfm?&csf=TIA

TIA-568.2

(Sep 2018)

Balanced Twisted-Pair Telecommunications Cabling and Components Standard http://www.tiaonline.org/

TIA-568.3 (Oct 2016) Optical Fiber Cabling and Components Standard https://global.ihs.com/csf_hom e.cfm?&csf=TIA

ASTM D4566-20 Standard Test Methods for Electrical Performance Properties of Insulations and Jackets for Telecommunications Wire and Cable http://webstore.ansi.org/

TIA-569 (May 2019) Telecommunications Pathways and Spaces https://global.ihs.com/csf_hom e.cfm?&csf=TIA

TIA-570 (Jul 2018) Residential Telecommunications Cabling Standard https://global.ihs.com/csf_hom e.cfm?&csf=TIA

TIA-598 (Jul 2014) Optical Fiber Cable Color Coding https://global.ihs.com/csf_hom e.cfm?&csf=TIA

TIA-606 (Oct 2021) Administration Standard for Telecommunications Infrastructure https://global.ihs.com/csf_hom e.cfm?&csf=TIA http://www.bicsi.org/ http://www.nfpa.org/ http://www.osha.gov/ http://www.ansi.org/ https://tiaonline.org/ https://global.ihs.com/csf_home.cfm?&csf=TIA https://global.ihs.com/csf_home.cfm?&csf=TIA https://global.ihs.com/csf_home.cfm?&csf=TIA https://global.ihs.com/csf_home.cfm?&csf=TIA https://global.ihs.com/csf_home.cfm?&csf=TIA https://global.ihs.com/csf_home.cfm?&csf=TIA http://www.tiaonline.org/ https://global.ihs.com/csf_home.cfm?&csf=TIA https://global.ihs.com/csf_home.cfm?&csf=TIA http://webstore.ansi.org/ https://global.ihs.com/csf_home.cfm?&csf=TIA https://global.ihs.com/csf_home.cfm?&csf=TIA https://global.ihs.com/csf_home.cfm?&csf=TIA https://global.ihs.com/csf_home.cfm?&csf=TIA https://global.ihs.com/csf_home.cfm?&csf=TIA https://global.ihs.com/csf_home.cfm?&csf=TIA https://global.ihs.com/csf_home.cfm?&csf=TIA https://global.ihs.com/csf_home.cfm?&csf=TIA

Revision D, January 2023 Page 12 of 12

TIA-607

(Jul 2019)

Commercial Building Grounding and Bonding Requirements for Telecommunications https://global.ihs.com/csf_hom e.cfm?&csf=TIA

TIA/EIA-758 (Mar 2012)

Customer-Owned Outside Plant Telecommunications Infrastructure Standard https://global.ihs.com/csf_hom e.cfm?&csf=TIA

EIA/ECA-310 (Dec 2005)

Racks, Panels and Associated Equipment https://standards.globalspec.c om/std/195405/EIA/ECA-310

ICEA S-80-576 (2002) Category 1 & 2 Individually Unshielded Twisted Pair Indoor Cables for Use in Communications Wiring Systems https://www.techstreet.com/ice a/searches/33123596

ICEA S-83-596-2016 Fiber Optic Premises Distribution Cable https://www.techstreet.com/ice a/subgroups/54441

GR-409, Issue 2 (Nov 2008)

Generic Requirements for Indoor Fiber Optic Cable https://telecom-info.njdepot.ericsson.net/site-cgi/ido/docs.cgi?ID=21553131 5SEARCH&DOCUMENT=gr

GR-20, Issue 4 (July 2013)

Generic Requirements for Optical Fiber and Optical Fiber Cable https://telecom-info.njdepot.ericsson.net/site-cgi/ido/docs.cgi?ID=21553131 5SEARCH&DOCUMENT=gr

NEMA TC 2-2020 Electrical Polyvinyl Chloride (PVC) Conduit http://www.nema.org/stds/tc2.cfm

NEMA TC 6&8-2020 PVC Plastic Utilities Duct for Underground Installations http://www.nema.org/stds/tc6_8.c fm

NEMA TC 9-2020 Fittings for PVC Plastic Utilities Duct for Underground Installation http://www.nema.org/stds/tc9.cfm

RUS Bulletin 1751F-

Underground Plant Design https://www.rd.usda.gov/sites/ default/files/UTP_Bulletins_17 51F-643.pdf

RUS Bulletin 1751F-

Underground Plant Construction https://www.rd.usda.gov/sites/ default/files/UTP_Bulletins_17 51F-644.pdf

RUS Bulletin 1753F-

801(PC-5A)

RUS Standard for Service Installations at Customer Access Locations https://www.rd.usda.gov/sites/ default/files/UTP_Bulletins_17 53F-801.pdf

RUS Bulletin 1753F-

401 (PC-2)

RUS Standards for Splicing Copper and Fiber Optic Cable https://www.rd.usda.gov/sites/ default/files/UTP_Bulletins_17 53F-401.pdf

RUS Bulletin 1753F- 601a

RUS Specifications for Fiber Optic Cables (PE-90a) https://www.rd.usda.gov/files/ UTP_Bulletins_1753F- 601a.pdf https://global.ihs.com/csf_home.cfm?&csf=TIA https://global.ihs.com/csf_home.cfm?&csf=TIA https://global.ihs.com/csf_home.cfm?&csf=TIA https://global.ihs.com/csf_home.cfm?&csf=TIA https://standards.globalspec.com/std/195405/EIA/ECA-310 https://standards.globalspec.com/std/195405/EIA/ECA-310 https://www.techstreet.com/icea/searches/33123596 https://www.techstreet.com/icea/searches/33123596 https://www.techstreet.com/icea/subgroups/54441 https://www.techstreet.com/icea/subgroups/54441 https://telecom-info.njdepot.ericsson.net/site-cgi/ido/docs.cgi?ID=215531315SEARCH&DOCUMENT=gr https://telecom-info.njdepot.ericsson.net/site-cgi/ido/docs.cgi?ID=215531315SEARCH&DOCUMENT=gr https://telecom-info.njdepot.ericsson.net/site-cgi/ido/docs.cgi?ID=215531315SEARCH&DOCUMENT=gr https://telecom-info.njdepot.ericsson.net/site-cgi/ido/docs.cgi?ID=215531315SEARCH&DOCUMENT=gr https://telecom-info.njdepot.ericsson.net/site-cgi/ido/docs.cgi?ID=215531315SEARCH&DOCUMENT=gr https://telecom-info.njdepot.ericsson.net/site-cgi/ido/docs.cgi?ID=215531315SEARCH&DOCUMENT=gr https://telecom-info.njdepot.ericsson.net/site-cgi/ido/docs.cgi?ID=215531315SEARCH&DOCUMENT=gr https://telecom-info.njdepot.ericsson.net/site-cgi/ido/docs.cgi?ID=215531315SEARCH&DOCUMENT=gr http://www.nema.org/stds/tc2.cfm http://www.nema.org/stds/tc6_8.cfm http://www.nema.org/stds/tc6_8.cfm http://www.nema.org/stds/tc9.cfm https://www.rd.usda.gov/sites/default/files/UTP_Bulletins_1751F-643.pdf https://www.rd.usda.gov/sites/default/files/UTP_Bulletins_1751F-643.pdf https://www.rd.usda.gov/sites/default/files/UTP_Bulletins_1751F-643.pdf https://www.rd.usda.gov/sites/default/files/UTP_Bulletins_1751F-644.pdf https://www.rd.usda.gov/sites/default/files/UTP_Bulletins_1751F-644.pdf https://www.rd.usda.gov/sites/default/files/UTP_Bulletins_1751F-644.pdf https://www.rd.usda.gov/sites/default/files/UTP_Bulletins_1753F-801.pdf https://www.rd.usda.gov/sites/default/files/UTP_Bulletins_1753F-801.pdf https://www.rd.usda.gov/sites/default/files/UTP_Bulletins_1753F-801.pdf https://www.rd.usda.gov/sites/default/files/UTP_Bulletins_1753F-401.pdf https://www.rd.usda.gov/sites/default/files/UTP_Bulletins_1753F-401.pdf https://www.rd.usda.gov/sites/default/files/UTP_Bulletins_1753F-401.pdf https://www.rd.usda.gov/files/UTP_Bulletins_1753F-601a.pdf https://www.rd.usda.gov/files/UTP_Bulletins_1753F-601a.pdf https://www.rd.usda.gov/files/UTP_Bulletins_1753F-601a.pdf

PREMISE WIRING GUIDANCE
1. The purpose of this document is to supplement Telecommunications Industry Association/Electronic Industry Alliance (TIA/EIA) commercial standards for premise wiring (Local Area Network cabling) on Keesler AFB.
2. New construction or renovations programming premise wiring work requires coordination with the 81 CS/SCXP Plans and Programs Office, contact # 377-7500 prior to implementation.
3. All premise wiring installed on Keesler AFB will conform to TIA/EIA wiring standards listed at the end of this document and the supplemental guidance contained in the attachments within this document.
4. Any deviations from the attached standards and this supplement should be coordinated and approved by the 81 CS/SCXP.
5. Contractual responsibilities:
5.1 Contractors selected to complete premise wiring work must have at least one experienced\technically certified Building Industry Consulting Service International (BICSI) technician on site.
5.2 Provide as-built drawings for the premise wiring work accomplished identifying installation/relocation work.
5.3 Provide test results for new\relocated premise wiring work accomplished.
5.4 Contractors shall be responsible for restoring work areas to original condition.
5.5 81 CS quality assurance office 81 CS/SCQ will be the approving authority for premise wiring work accomplished in new construction or renovations.
All copper cables, connectors, ports, jacks, outlets, and patch panels shall be TIA/EIA Category 6 rated.
All premise cabling supporting a Local Area Network will be terminated using 568B standards.
Pairs will not be untwisted more than .5 inch. Cable jacket will not be stripped back more than 1 inch. No nicks on the inner conductors.
CABLE MANAGEMENT
The Contractor shall ensure a neat and orderly installation utilizing proper cable management IAW current applicable standards. Data drops shall be routed in a manner to ensure the cables are protected and aesthetically pleasing along the cable path. ...
Cable trays shall be installed and/or utilized in all communication rooms.
Cables will be independently supported off the ceiling with supports no more than 60 inches apart.
Cable route should avoid fluorescent light ballasts, electrical cables and motors.
Cable jackets must not be distorted. Velcro or nylon are acceptable – Velcro is better at protecting cable geometry. Staples will not be used.
Any building penetrations (to include wall, ceiling, or floor), shall be in compliance with National Fire Protection Agency (NFPA) regulations and coordinated with CSC’s structural office and fire department.
LABELING
All labeling shall be machine generated, without serifs, uppercase and large enough to be easily read (ANSI/TIA/EIA-606-A-1 section 11).
The naming scheme shall also be coordinated with the 81st Communications Squadron (81 CS/SCXP).
Outlet(s)
Patch Panel(s)
LABELING (continued)
Cables - All cables will be labeled on both ends with encoded identifiers per (ANSI/TIA/EIA-606-A-1 section 11).
All grounds will be labeled (ANSI/TIA-607-B para 7.8) (if installed).
All ground connections will have a clear margin of bare metal-to-metal contact (ANSI/TIA-607-B para 7.6).
Cabinets, racks and other enclosures shall not be bonded serially, each shall have their own dedicated bonding conductor (ANSI/TIA-607-B para 7.1.4).