Attachment 3 - Renovate B412 DCSA Ph 2 Drawings 10.24.2022.pdf

PDF 7 MB Posted

Attached to
Renovate B412 for DCSA Phase 2
Solicitation number
FA301023R0040
Issued by

About this file

This package of construction documents outlines the scope of work for a renovation project at Keesler Air Force Base. The project involves renovating space B412 to accommodate the Defense Counterintelligence and Security Agency.

The renovation will update mechanical, electrical, communications, and fire alarm systems. It will also involve demolishing existing finishes and fixtures to install new flooring, walls, casework and plumbing fixtures. Architectural drawings show demolition plans, new layouts and construction details. Mechanical drawings cover HVAC modifications. Electrical drawings include power, lighting and low-voltage plans, panel schedules and details. Communications drawings provide data outlet locations. Fire alarm drawings show device locations and riser diagrams. Specifications are included for mechanical, electrical and communications scopes.

View the file

Other files

File Type Posted
Attachment 16 - Fire Alarm Clarification.pdf PDF
Solicitation Amendment FA301023R00400002 SF 30.pdf PDF
Solicitation Amendment - FA301023R00400002.pdf PDF
Solicitation Amendment FA301023R00400001 SF 30.pdf PDF
Attachment 15 - MAHG21-1099 Reno B412 DCSA Phase 2 Questions and Answers.pdf PDF
Solicitation Amendment - FA301023R00400001.pdf PDF
FA301023R0040 Pre-Bid Site Visit Sign-in.pdf PDF
Mechanical Room Photos.pdf PDF
Attachment 1 - Renovate B412 DCSA Phase 2 SOW 8.10.2023.pdf PDF
Attachment 7 - Appendix C MECH RM - DUCT INSTALL.pdf PDF
Attachment 8 - MAHG 211099 Renovate B412 DCSA Ph-2 MSS.xls XLS spreadsheet
Attachment 10 - Manufacturer Carpet and Adhesive Pricing Sheet.pdf PDF
Attachment 11 - Past Performance Questionnaire.pdf PDF
Attachment 12 - Past Performance Reference List.pdf PDF
Solicitation - FA301023R0040.pdf PDF
Attachment 5 - Appendix A AIR BALANCE DIAGRAM.pdf PDF
Attachment 6 - Appendix B MECH RM - DUCT DEMO.pdf PDF
Attachment 13 - Wage Determination MS 20220050.pdf PDF
Attachment 14 - Submittal Procedures.pdf PDF
Attachment 2 - Renovate B412 DCSA Phase 2 Specifications 8.10.2023.pdf PDF
Attachment 4 - Keesler Guidance for Premise Wiring Jan 2023.pdf PDF
Attachment 9 - USAF Carpet Ordering Guide Jan2022.pdf PDF
Show all 22

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

PROJECT LOCATION

Deer Island

Ship IslandCat Island

St. Louis Bay

Mis siss ipp i

Sou nd

Big Lake

Back Bay of Biloxi

Bernard Bayou

W olf

R iv er

Biloxi River

Little Biloxi River

Tchoutacabouffa

River

Tuxachanie

Creek

Tch out aca bou ffa

Riv er

Cedar Lake

S a u c ie r

C re e k

Miss issip pi

Soun d

INTERSTATE 10

U .S

. H W

Y

U.S. HWY 90

I-1

PROJECT SITE

1" = 100'-0"1 PROJECT LOCATION

INDEX OF DRAWINGS

RENOVATE B412 PHASE 2 DCSA

MAHG211099

KEESLER AFB, MISSISSIPPI

OCTOBER 24, 2022

R. HOYT

A. MARASCA G. REED

VARIES

876543

D

E

B

C

A

87654321

G

F

E

D

C

B

A

G

F

APPROVEDDRAWN

AIR EDUCATION AND TRAINING COMMAND

DATEREVISION

UNITED STATES AIR FORCE

MISSISSIPPI

FACILITY NUMBER:

SHEET OF

DRAWING NUMBER:

BILOXI

RECOMMENDED:

(Chief of Engineering)

SUBMITTED:

(Chief of Contracts Design)

SCALE:

PROJECT NUMBER:

CHECKED:

DATE:

DESIGNED:

DRAWN:

OFFICE OF CIVIL ENGINEERS

MAHG21109924 OCT 2022

J. KOCI

C. JODHAN

KEESLER AIR FORCE BASE

RENOVATE B412 PHASE 2 DCSA

G-001

TITLE SHEET

G-001 TITLE SHEET

A-001 GENERAL NOTES, ABBREVIATIONS AND LEGEND

AD-101 OVERALL DEMOLITION PLAN

AD-102 OVERALL DEMOLITON REFLECTED CEILING PLAN

A-103 OVERALL FLOOR PLAN

A-104 OVERALL REFLECTED CEILING PLAN

A-501 ARCHITECTURAL DETAILS

A-502 ARCHITECTURAL DETAILS II

A-503 ARCHITECTURAL DETAILS III

M-001 GENERAL NOTES, ABREVIATIONS AND LEGEND

M-101 OVERALL MECHANICAL FLOOR PLAN

MD-102 ENLARGED MECHANICAL DEMOLITION PLAN

M-103 ENLARGED MECHANICAL INSTALLATION PLAN

M-501 MECHANICAL DETAILS

M-601 MECHANICAL SCHEDULES

E-001 GENERAL NOTES, ABBREIVATIONS AND LEGEND

E-101 OVERALL ELECTRICAL FLOOR PLAN

ED-102 ENLARGED ELECTRICAL DEMOLITION PLAN

E-103 ENLARGED POWER PLAN

E-104 ENLARGED LIGHTING PLAN

E-701 ELECTRICAL PANEL SCHEDULES

T-001 GENERAL NOTES, ABBREVATIONS AND LEGEND

T-101 OVERALL COMMUNICATIONS FLOOR PLAN

TD-102 COMMUNICATIONS DEMOLITION PLAN

T-103 OVERALL COMMUNICATIONS PLAN

FA-001 GENERAL NOTES, ABBREVIATION AND LEGEND

FA-101 OVERALL FIRE ALARM FLOOR PLAN

FA-103 OVERALL FIRE ALARM PLAN

FA-601 FA RISER DIAGRAM

E-105 SECURITY PLAN FAD-102 ENLARGED FIRE ALARM DEMOLITION PLAN

Attachment 3

FA301023R0040

1557824398E Text Box

J.BERGERON

A-001

GENERAL NOTES,

ABBREVIATIONS AND LEGEND

ARCHITECTURAL SYMBOL LEGEND:CODES AND STANDARDS: ABBREVIATIONS:ARCHITECTURAL GENERAL NOTES:

R. HOYT

A. MARASCA G. REED

VARIES

C. JODHAN

876543

D

E

B

C

A

87654321

G

F

E

D

C

B

A

G

F

APPROVEDDRAWN

AIR EDUCATION AND TRAINING COMMAND

DATEREVISION

UNITED STATES AIR FORCE

MISSISSIPPI

FACILITY NUMBER:

SHEET OF

DRAWING NUMBER:

BILOXI

RECOMMENDED:

(Chief of Engineering)

SUBMITTED:

(Chief of Contracts Design)

SCALE:

PROJECT NUMBER:

CHECKED:

DATE:

DESIGNED:

DRAWN:

OFFICE OF CIVIL ENGINEERS

J. KOCI

KEESLER AIR FORCE BASE

MAHG21109924 OCT 2022

RENOVATE B412 PHASE 2 DCSA

ACT ACOUSTICAL CEILING TILE

ADJ ADJUSTABLE

AFF ABOVE FINISHED FLOOR

BD BOARD

BOT. BOTTOM

CO CONTRACTING OFFICER

COR CONTRACTING OFFICER REPRESENTATIVE

DWR DRAWER

EXIST. EXISTING

FIN FINISH

FL FLOOR

GWB GYPSUM WALLBOARD

GYP GYPSUM

HDWD HARDWOOD

MISC. MISCELLANEOUS

MTL METAL

OC ON CENTER

PLAM PLASTIC LAMINATE

PLYWD PLYWOOD

PTD PAINTED

SCHED SCHEDULED

STC SOUND TRANSMISSION CLASS

TR TRIM

TRTD TREATED

W/ WITH

WD WOOD

1. UNLESS OTHERWISE SPECIFIED, PERFORM ALL WORK CONSISTENT WITH THE RULES

AND REQUIREMENTS OF THE FOLLOWING:

KEESLER AIR FORCE BASE.

STATE OF MISSISSIPPI BUILDING CODES, PLUMBING CODES AND REGULATORY

REQUIREMENTS.

2. THE ASSOCIATED STATEMENT OF WORK AND SPECIFICATIONS DEVELOPED AS PART

OF THE DESIGN PACKAGE ARE A PART OF AND APPLY TO WORK SHOWN ON THESE

DRAWINGS.

3. LOCATIONS, ELEVATIONS AND DIMENSIONS OF EXISTING STRUCTURES, BUILDING

SYSTEMS AND OTHER FEATURES SHOWN ARE BASED ON THE BEST INFORMATION

AVAILABLE AT THE TIME OF PREPARATION OF THESE PLANS, BUT DO NOT PURPORT TO

BE ABSOLUTELY CORRECT. PRIOR TO CONSTRUCTION, VERIFY THE LOCATIONS,

ELEVATIONS AND DIMENSIONS OF ALL EXISTING FEATURES (WHETHER OR NOT SHOWN

ON THE PLANS) AFFECTING THE WORK. NOTIFY THE CONTRACTING OFFICER (CO) OF

ALL CONFLICTS PRIOR TO BEGINNING CONSTRUCTION.

4. WORK THE SCOPE CONTAINED IN ALL DISCIPLINE SHEETS IN COORDINATION WITH ONE

ANOTHER.

5. PROVIDE ADEQUATE BRACING, SHORING, AND OTHER TEMPORARY SUPPORTS AS

NECESSARY TO PROTECT THE EXISTING STRUCTURE AND SYSTEMS TO REMAIN AS

REQUIRED BY SITE CONDITIONS AND FOR SAFE WORK CONDITIONS.

6. ALL DETAILS AND SECTIONS SHOWN ON THE DRAWINGS ARE INTENDED TO BE TYPICAL

AND CONSTRUED TO APPLY TO ANY SIMILAR SITUATION ELSEWHERE ON THE PROJECT,

EXCEPT WHERE A DIFFERENT DETAIL IS SHOWN.

7. COORDINATE TRADE ELEMENTS IN SHOP DRAWINGS SUBMITTALS.

8. GIVE ALL NOTICES AND COMPLY WITH ALL LAWS, ORDINANCES, RULES, REGULATIONS

AND PERMIT CONDITIONS BEARING ON THE CONDUCT OF THE WORK AS DRAWN AND

SPECIFIED. IF THE CONTRACTOR OBSERVES THAT THE DRAWINGS AND

SPECIFICATIONS ARE AT VARIANCE, NOTIFY THE CO, IN WRITING, AND ANY NECESSARY

CHANGES TO BE ADJUSTED, AS PROVIDED IN THE AGREEMENT FOR CHANGES IN THE

WORK.

9. THE ACTS AND OMISSIONS OF CONTRACTOR EMPLOYEES AND ALL THEIR

SUBCONTRACTORS AND THEIR AGENTS AND EMPLOYEES AND OTHER PERSONS

PERFORMING ANY OF THE WORK UNDER CONTRACT WITH THE CONTRACTOR IS THE

RESPONSIBILITY OF THE CONTRACTOR.

10. IMMEDIATELY NOTIFY THE CO OF ANY ERRORS AND OMISSIONS IN THE PLANS OR

SPECIFICATIONS.

11. MAINTAIN ACCESS TO THE WORK AREA TO SUPPORT INSPECTION FOR ALL APPLICABLE

GOVERNMENT JURISDICTIONS AT ALL TIMES AND PROVIDE PROPER FACILITIES FOR

SUCH ACCESS AND INSPECTION.

12. COMPLY WITH ALL FEDERAL OCCUPATIONAL HEALTH AND SAFETY ACT RULES AND

REGULATIONS. COMPLY WITH ANY AND ALL APPLICABLE FEDERAL, STATE, AND LOCAL

LAWS AND REGULATIONS PERTAINING TO JOB SAFETY AND HEALTH.

13. ENSURE ALL WORK PERFORMED UNDER THIS CONTRACT, AND ALL EQUIPMENT,

APPLIANCES, TOOLS AND LIKE ITEMS USED IN THE WORK CONFORM TO APPLICABLE

SAFETY CODES AND REGULATIONS OF THE AUTHORITY HAVING JURISDICTION. IN THE

EVENT OF CONFLICTING REQUIREMENTS, THE MORE STRINGENT INTERPRETATION OR

REGULATION GOVERNS. TAKE ALL REASONABLE PRECAUTIONS FOR THE SAFETY OF,

AND PROVIDE ALL REASONABLE PROTECTION TO PREVENT DAMAGE, INJURY OR LOSS

TO ALL EMPLOYEES, MATERIALS, EQUIPMENT, AND PROPERTY.

14. ERECT AND MAINTAIN, AS REQUIRED BY SITE CONDITIONS AND WORK PROGRESS, ALL

REASONABLE SAFEGUARDS FOR SAFETY AND ENVIRONMENTAL PROTECTION,

INCLUDING POSTING DANGER SIGNS AND OTHER WARNINGS AGAINST HAZARDS,

PROMULGATING SAFETY REGULATIONS, AND NOTIFYING CO AND USERS OF THE

EXISTENCE OF HAZARDS AND OF THE SAFETY OR ENVIRONMENTAL REGULATIONS.

15. USE, HANDLE, TRANSPORT, AND DISPOSE OF ALL HAZARDOUS MATERIALS IN

COMPLIANCE WITH ALL FEDERAL, STATE AND LOCAL ENVIRONMENTAL, HEALTH AND

SAFETY LAWS AND REQUIREMENTS.

16. TAKE ALL PRECAUTIONS TO PREVENT THE DISCHARGE, RELEASE OR DISPOSAL OF ANY

HAZARDOUS MATERIALS CREATED BY THE WORK ON OR ABOUT THE JOB SITE. IN THE

EVENT OF ANY SPILL, RELEASE OR ANY OTHER REPORTABLE OCCURRENCE, NOTIFY

THE APPROPRIATE GOVERNMENTAL AGENCY AND TAKE ACTIONS NECESSARY TO

MINIMIZE THE DELETERIOUS EFFECT OF THE SPILL ON PERSONS AND PROPERTY.

17. UPON COMPLETION OF PERFORMANCE OF ALL DUTIES UNDER THIS CONTRACT,

REMOVE ALL SUPPLIES, MATERIALS, AND WASTE FROM THE JOB SITE.

18. FIELD VERIFY ALL DIMENSIONS, LOCATIONS, AND CONDITIONS PRIOR TO BID AND

START OF CONSTRUCTION. NOTIFY CONTRACTING OFFICER OF ANY CONDITIONS

DETRIMENTAL TO THE COMPLETION OF THE WORK AS DESIGNED.

CONSTRUCTION COORDINATION:

1. THE SPACES INCLUDED IN THE SCOPE OF WORK ARE ADJACENT TO ACTIVE OFFICE

SPACES. SCHEDULE WORK AND PROVIDE PROTECTION TO PRESERVE THE USE AND

FUNCTION OF THE SPACES, INCLUDING NOISE CONTROL. CERTAIN TYPES OF WORK

MAY REQUIRE SCHEDULING OUTSIDE OF NORMAL WORKING HOURS.

2. PRIOR TO CONSTRUCTION, SCHEDULE A CONSTRUCTION COORDINATION MEETING

WITH THE CO AND PROJECT STAKEHOLDERS TO REVIEW THE CONSTRUCTION

SCHEDULE, PROJECT MILESTONES, OUTAGE REQUIREMENTS, AND REVIEW / CLARIFY

REQUESTS FOR INFORMATION.

3. PROVIDE DUST BARRIERS AND A SEALED ENVELOPE AROUND THE WORK AREA

DURING DEMOLITION AND CONSTRUCTION PHASES TO PROTECT THE OFFICE.

EXHAUST FANS MAY BE USED AS NECESSARY TO PROVIDE AIRFLOW THROUGH THE

SPACE DURING CONSTRUCTION.

4. ADJACENT AREAS TO THE SPACE INCLUDE CARPETED FLOOR FINISHES. PROTECT

FLOORING FROM DAMAGE, DUST AND DIRT. CLEANING AND REPLACEMENT TO CO

SATISFACTION ARE AT THE CONTRACTOR'S OWN COST.

· 2018 INTERNATIONAL BUILDING CODE

· 2021 INTERNATIONAL ENERGY CONSERVATION CODE

2021 INTERNATIONAL MECHANICAL CODE

· 2021 INTERNATIONAL PLUMBING CODE

· 2020 NATIONAL ELECTRIC CODE 2021 NFPA 101 LIFE

SAFETY CODE

· 2021 NFPA NATIONAL FIRE CODE

· CONUS - KEESLER AFB IFS

· UFC 3-101-01 ARCHITECTURE, WITH CHANGE 1

· UFC 3-120-10 INTERIOR DESIGN, WITH CHANGE 2

· UFC 3-190-06 PROTECTIVE COATINGS AND PAINTS

TYPICAL NOTE, APPLICABLE TO

ALL OCCURENCES

SPECIFIC NOTE

A

FIXTURE A - REFER TO LIGHTING FIXTURE SCHEDULE ON E-001

B

FIXTURE B - REFER TO LIGHTING FIXTURE SCHEDULE ON E-001

C

FIXTURE C - REFER TO LIGHTING FIXTURE SCHEDULE ON E-001

ITEMS TO BE DEMOLISHED

AREA NOT IN SCOPE

D

FIXTURE D - REFER TO LIGHTING FIXTURE SCHEDULE ON E-001

RED LED EXIT LIGHT, WALL MOUNTED

(HATCHING DENOTES ILLUMINATED FACE DIRECTION)

(TYP)

WALL TAG

2X4 ACT CEILING

GYPSUM BOARD CEILING

1557824398E

1 2 3 4

A

B

C

D

CORRIDOR

CORRIDOR

MEN

WOMEN

VEST

INVEST. ASSIST.

121 SAC

CONFERENCE/TRAINING

GENERAL NOTES

AD-101

R. HOYT

A. MARASCA G. REED

VARIES

C. JODHAN

876543

D

E

B

C

A

87654321

G

F

E

D

C

B

A

G

F

APPROVEDDRAWN

AIR EDUCATION AND TRAINING COMMAND

DATEREVISION

UNITED STATES AIR FORCE

MISSISSIPPI

FACILITY NUMBER:

SHEET OF

DRAWING NUMBER:

BILOXI

RECOMMENDED:

(Chief of Engineering)

SUBMITTED:

(Chief of Contracts Design)

SCALE:

PROJECT NUMBER:

CHECKED:

DATE:

DESIGNED:

DRAWN:

OFFICE OF CIVIL ENGINEERS

J. KOCI

KEESLER AIR FORCE BASE

MAHG21109924 OCT 2022

RENOVATE B412 PHASE 2 DCSA

A. CONFINE ALL WORK TO SPECIFIC AREAS AS DESIGNATED IN THE

SCOPE OF WORK AND SCHEDULE.

B. REMOVE ALL MATERIALS TO BE DEMOLISHED FROM THE SITE AND

DISPOSED OF OFF-SITE IN A LEGAL LANDFILL. CONTRACTOR IS NOT

ALLOWED TO STOCKPILE DEMOLITION MATERIALS ON SITE; ALL

MATERIALS TO BE REMOVED DAILY.

SCALE:

OVERALL DEMOLITION PLAN

1/4" = 1'-0"

SCALE: 1/4" = 1'-0"

21 4 80

OVERALL DEMOLITION PLAN

KEY NOTES

A. REMOVE EXISTING ROLL UP WINDOW IN ITS ENTIRETY.

B. DECONSTRUCT AND REMOVE EXISTING ELECTRONIC FILING

MACHINE.

C. REMOVE EXISTING WATER FOUNTAIN , SINK AND ASSOCIATED

CASEWORK. PREPARE PLUMBING TO ACCEPT NEW FIXTURES.

D. REMOVE EXISTING CURTAIN PARTITION WALL AND THE ASSOCIATED

CEILING TRACK.

E. REMOVE EXISTING PROJECTOR SCREEN.

F. REMOVE ALL EXISTING OFFICE FURNITURE.

G. REMOVE EXISTING CARPET AND RUBBER WALL BASE IN ITS

ENTIRETY. PREPARE FOR INSTALLATION OF NEW CARPET AND

BASEBOARD.

H. REMOVE MISC. HOOKS, NAILS, INSERTS, ETC. FROM WALL. PATCH

WALL AND PREPARE TO PAINT.

I. REMOVE EXISTING RUBBER WALL BASE AND VINYL TILE FLOORING.

PREPARE FOR INSTALLATION OF NEW VINYL TILE FLOORING AND

BASE.

J. REMOVE EXISTING GLASS DOUBLE ENTRANCE DOORS AND FRAMES

IN THEIR ENTIRETY. PREPARE OPENING FOR INSTALLATION OF NEW

HURRICANE RATED ASSEMBLY AND HEAVY DUTY COMMERCIAL

NON-HOLD-OPEN SURFACE DOOR CLOSERS MOUNTED TO THE FACE

OF EACH DOOR AND FACE OF EACH DOORFRAME.

K. REMOVE EXISTING GLASS DOUBLE DOORS AND FRAMES IN THEIR

ENTIRETY. MODIFY OPENING TO ACCEPT A NEW, SINGLE DOOR.

REFER TO SHEET A-103 FOR MODIFICATION DETAILS.

L. REMOVE EXISTING DOOR IN ITS ENTIRETY. PREPARE OPENING FOR

INSTALLATION OF NEW DOOR AND HARDWARE.

NOT IN SCOPE

1557824398E

CONFERENCE/TRAINING

IR-1

119A

FILE/COPY

121A

SAC

IR-2

119B

CORRIDOR

IR-3

118A

IR-4

118B

INVEST. ASSIST.

MEN'S RR

WOMEN'S RR

1 2 3 4

A

B

C

D

CORRIDOR

CORRIDOR

MEN

WOMEN

VEST

INVEST. ASSIST.

121 SAC

CONFERENCE/TRAINING

R. HOYT

A. MARASCA G. REED

VARIES

C. JODHAN

876543

D

E

B

C

A

87654321

G

F

E

D

C

B

A

G

F

APPROVEDDRAWN

AIR EDUCATION AND TRAINING COMMAND

DATEREVISION

UNITED STATES AIR FORCE

MISSISSIPPI

FACILITY NUMBER:

SHEET OF

DRAWING NUMBER:

BILOXI

RECOMMENDED:

(Chief of Engineering)

SUBMITTED:

(Chief of Contracts Design)

SCALE:

PROJECT NUMBER:

CHECKED:

DATE:

DESIGNED:

DRAWN:

OFFICE OF CIVIL ENGINEERS

J. KOCI

KEESLER AIR FORCE BASE

MAHG21109924 OCT 2022

RENOVATE B412 PHASE 2 DCSA

GENERAL NOTES

A. CONFINE ALL WORK TO SPECIFIC AREAS AS DESIGNATED IN THE

SCOPE OF WORK AND SCHEDULE.

B. REMOVE ALL MATERIALS TO BE DEMOLISHED FROM THE SITE AND

DISPOSED OF OFF-SITE IN A LEGAL LANDFILL. CONTRACTOR IS NOT

ALLOWED TO STOCKPILE DEMOLITION MATERIALS ON SITE; ALL

MATERIALS TO BE REMOVED DAILY.

C. CEILING TILE GRID IS APPROXIMATE AND IS SHOWN FOR

ILLUSTRATIVE PURPOSES AND APPROXIMATE LOCATIONS OF OTHER

CEILING MOUNTED EQUIPMENT.

AD-102

SCALE:

OVERALL DEMOLITION REFLECTED CEILING PLAN

1/4" = 1'-0"

SCALE: 1/4" = 1'-0"

21 4 80

OVERALL DEMOLITON REFLECTED

CEILING PLAN

KEY NOTES

A. REMOVE EXISTING ACOUSTICAL CEILING SYSTEM, INCLUDING

CEILING TILES, GRID, LIGHT FIXTURES, HVAC SUPPLY AND RETURN.

SUPPORT ITEMS TO REMAIN UNTIL SECURELY MOUNTED IN

REPLACEMENT CEILING SYSTEM.

1557824398E

WH1

IR-1

119A

FILE/COPY

121A

SAC

1 2 3 4

A

B

C

D

IR-2

119B

CORRIDOR

WOMEN'S RR

IR-4

118B

INVEST. ASSIST.

CORRIDOR

MEN'S RR

IR-3

118A

CAPGCCAPDHCAPQTCAPPNCAPMCCAPMG

CAPGCCAPDHCAPQTCAPPNCAPMCCAPMG

CAPGCCAPDHCAPQTCAPPNCAPMCCAPMG CAPGCCAPDHCAPQTCAPPNCAPMCCAPMG

CAPGCCAPDHCAPQTCAPPNCAPMCCAPMG

CAPGCCAPDHCAPQTCAPPNCAPMCCAPMG

CAPGCCAPDHCAPQTCAPPNCAPMCCAPMG

CAPGCCAPDHCAPQTCAPPNCAPMCCAPMG CAPGCCAPDHCAPQTCAPPNCAPMCCAPMG

CAPGCCAPDHCAPQTCAPPNCAPMCCAPMG CAPGCCAPDHCAPQTCAPPNCAPMCCAPMG

CAPGCCAPDHCAPQTCAPPNCAPMCCAPMG CAPGCCAPDHCAPQTCAPPNCAPMCCAPMG

CAPGCCAPDHCAPQTCAPPNCAPMCCAPMG

R. HOYT

A. MARASCA G. REED

VARIES

C. JODHAN

876543

D

E

B

C

A

87654321

G

F

E

D

C

B

A

G

F

APPROVEDDRAWN

AIR EDUCATION AND TRAINING COMMAND

DATEREVISION

UNITED STATES AIR FORCE

MISSISSIPPI

FACILITY NUMBER:

SHEET OF

DRAWING NUMBER:

BILOXI

RECOMMENDED:

(Chief of Engineering)

SUBMITTED:

(Chief of Contracts Design)

SCALE:

PROJECT NUMBER:

CHECKED:

DATE:

DESIGNED:

DRAWN:

OFFICE OF CIVIL ENGINEERS

J. KOCI

KEESLER AIR FORCE BASE

MAHG21109924 OCT 2022

RENOVATE B412 PHASE 2 DCSA

GENERAL NOTES

A. FURNITURE AND EQUIPMENT SHOWN ARE FOR UNDERSTANDING OF

SPACE ALLOCATIONS AND FOR REFERENCE ONLY.

A-103

SCALE:

OVERALL FLOOR PLAN

1/4" = 1'-0"

SCALE: 1/4" = 1'-0"

21 4 80

OVERALL FLOOR PLAN

KEY NOTES

A. PRIME AND PAINT WALLS. COLOR BY CO.

B. INSTALL DOOR AND HARDWARE.

C. INSTALL METAL STUD WALL. REFER TO WALL DETAILS ON SHEET

A-501.

D. INSTALL KITCHENETTE CABINETS AND COUNTER TOP.

E. TIE NEW PLUMBING TO EXISTING AND PLUMB NEW FIXTURES. REFER

TO FIXTURE SCHEDULE ON A-501.

F. PROVIDE LEVEL 4 FINISH, ON ALL NEW GYPSUM BD. WALLS AND

PATCHES, SEAL ALL OPENINGS IN WALL AND BETWEEN WALL AND

ROOF DECK WITH SOUND ATTENUATION SEALANT ABOVE LAY-IN

CEILING.

G. INSTALL CARPET AND RUBBER WALL BASE.

H. INSTALL LUXURY VINYL TILE AND RUBBER WALL BASE.

I. INSTALL METAL STUD WALL AND GYPSUM BOARD SIMILAR TO TYPE 1A

WALL TO REPAIR VOID FROM REMOVAL OF EXISTING ROLL UP

WINDOW TO MATCH EXISTING ADJACENT WALL.

J. PREPARE NEW CARPET FOR TRACK RACEWAY. REFER TO

ELECTRICAL DRAWINGS.

K. INSTALLATION HURRICANE RATED DOUBLE GLASS DOOR, ASSEMBLY

AND HEAVY DUTY COMMERCIAL NON-HOLD-OPEN SURFACE DOOR

CLOSERS MOUNTED TO THE FACE OF EACH DOOR AND FACE OF EACH

DOORFRAME.

L. INSTALL METAL STUD PARTITION WALL IN EXISTING OPENING TO

ACCEPT SINGLE DOOR, CENTERED IN OPENING. INSTALL HOLLOW

METAL FRAME AND INSTALL SINGLE DOOR AND HEAVY DUTY

COMMERCIAL NON-HOLD-OPEN SURFACE DOOR CLOSER MOUNTED

TO THE FACE OF THE DOOR AND FACE OF DOORFRAME.

M. INSTALL METAL STUD WALL AND WATER RESISTANT GYPSUM BOARD

TO PROVIDE STRUCTURAL ATTACHMENT OF NEW DOOR AND FRAME.

MATCH WALL THICKNESS TO THICKNESS OF ADJACENT BRICK WALL.

PROVIDE FOIL FACED, FIBERGLASS INSULATION TO MATCH THE VOID

WIDTH. SEAL FLOOR TO WALL JOINT WITH EXTERIOR RATED,

PAINTABLE ASTM C920 CLASS 35 LATEX SEALANT.

N. INSTALL WATER RESISTANT GYPSUM BOARD OVER EXISTING BRICK

WALL. PROVIDE SMOOTH TRANSITION BETWEEN GYPSUM

WALLBOARD ON BRICK AND NEW STUDS.

O. REMOVE WINDOW LATCH HANDLE AND INSTALL SECURITY PLATE.

REFER TO DETAIL ON A-501.

P. INSTALL POINT OF USE HOT WATER HEATER IN CABINET UNDER SINK.

CONNECT TO EXISTING COLD WATER SUPPLY. REFER TO A502 FOR

WATER HEATER SCHEDULE AND REFER TO ELECTRICAL PLANS FOR

POWER CONNECTION.

Q. INSTALL WINDOW FILM SD1010 RF/IR/GLASS FRAGMENTATION

CONTROL FILM OR APPROVED EQUAL ON ALL WINDOWS IN THE

BUILDING.

D118BD118A

D119BD119AD121A

A A-503

D101A

D101B

D121 D120

1557824398E Text Box

J.BERGERON

1557824398E Polygon

1557824398E

F

A

B

C

D

C C C

D

A

B

B

B

B

AB

BA

B B

AB

BA

BA

B B

A

B

A

P

OS

P OS

OS

PP

PP

OS

P

P

OS

PP

P

OS

PP PP

OS

P

OS

P

PPP

OS

PP

OS

P P

OS

PP

PP

P

OSE

E

D

E

D

E

CONFERENCE/TRAINING

IR-1

119A

FILE/COPY

121A

SAC

IR-2

119B

CORRIDOR

IR-3

118A

IR-4

118B

INVEST. ASSIST.

MEN'S RR

WOMEN'S RR

R. HOYT

A. MARASCA G. REED

VARIES

C. JODHAN

876543

D

E

B

C

A

87654321

G

F

E

D

C

B

A

G

F

APPROVEDDRAWN

AIR EDUCATION AND TRAINING COMMAND

DATEREVISION

UNITED STATES AIR FORCE

MISSISSIPPI

FACILITY NUMBER:

SHEET OF

DRAWING NUMBER:

BILOXI

RECOMMENDED:

(Chief of Engineering)

SUBMITTED:

(Chief of Contracts Design)

SCALE:

PROJECT NUMBER:

CHECKED:

DATE:

DESIGNED:

DRAWN:

OFFICE OF CIVIL ENGINEERS

J. KOCI

KEESLER AIR FORCE BASE

MAHG21109924 OCT 2022

RENOVATE B412 PHASE 2 DCSA

GENERAL NOTES

A. FINAL CEILING TILE GRID LAYOUT IS THE RESPONSIBILITY OF THE

CONTRACTOR. COORDINATE THE NEW GRID WITH ITEMS TO REMAIN

AND CRITICAL EQUIPMENT LOCATIONS. CENTER GRID IN ROOM

WHERE PRACTICAL. DO NOT INSTALL CEILING PANELS NARROWER

THAN SIX (6) INCHES.

A-104

SCALE:

OVERALL REFLECTED CEILING PLAN

1/4" = 1'-0"

SCALE: 1/4" = 1'-0"

21 4 80

OVERALL REFLECTED CEILING

PLAN

S1

EWC-1

1557824398E

R. HOYT

A. MARASCA G. REED

VARIES

C. JODHAN

876543

D

E

B

C

A

87654321

G

F

E

D

C

B

A

G

F

APPROVEDDRAWN

AIR EDUCATION AND TRAINING COMMAND

DATEREVISION

UNITED STATES AIR FORCE

MISSISSIPPI

FACILITY NUMBER:

SHEET OF

DRAWING NUMBER:

BILOXI

RECOMMENDED:

(Chief of Engineering)

SUBMITTED:

(Chief of Contracts Design)

SCALE:

PROJECT NUMBER:

CHECKED:

DATE:

DESIGNED:

DRAWN:

OFFICE OF CIVIL ENGINEERS

J. KOCI

KEESLER AIR FORCE BASE

MAHG21109924 OCT 2022

RENOVATE B412 PHASE 2 DCSA

SCALE:

PARTITION TYPES

NTS

A-501

ARCHITECTURAL DETAILS

9'-0" AFF

8" MTL STUDS @ 16" OC WITH 58" TYPE 'X' GYP

BD BOTH SIDES, W/ 32

1" SOUND ATTENUATING

BATTS AND PROVIDE CLASS 4 FINISH, PRIME

AND PAINT. PARTITION TO UNDERSIDE OF

ROOF DECK ABOVE. WALLS SHALL BE

SEALED W/APPROPRIATE NON-DRYING

ACOUSTICAL SEALANT AT TOP AND BOTTOM

OF WALLS AS WELL AS AT ALL

PENETRATIONS.

8" GYP BD TYPE 'X'

WITH CLASS 4

FINISH

2" SOUND

ATTENUATING BATTS

9'-0" AFF

INTERIOR PERIMETER WALL:

(STC 50 RATING)

8" MTL STUDS @ 16" OC WITH 2 LAYERS

OF TYPE 'X' 5

8" GWB ON INTERIOR ROOM

SIDE, ONE LAYER OF TYPE 'X' 58" GWB ON

EXTERIOR ROOM SIDE, AND 32

1" SOUND

ATTENUATING INSULATION AND PROVIDE

CLASS 4 FINISH, PRIME AND PAINT.

SECURE INSULATION TO PREVENT

SAGGING.. WALLS SHALL BE SEALED WITH

ACOUSTICAL SEALANT AT TOP AND

BOTTOM OF WALLS AND AT ALL

PENETRATION. EXTEND PARTITION TO THE

BOTTOM OF THE ROOF DECK ABOVE.

8" MTL STUDS

@ 16" OC

4" WALL BASE

8" MTL STUDS @ 16"

OC

ACT.ACT.

PROVIDE SOUND

ATTENUATION SEALANT AT

WALL/DECK CONNECTION

AND ALL PENETRATIONS

EXIST. ROOF

DECK

SUITE SIDE

2 LAYERS OF 58" TYPE 'X' GWB TO

BOTTOM OF ROOF DECK.

PROVIDE CLASS 4 FINISH AND

PRIME AND PAINT FROM FLOOR

TO ROOF DECK.

2" SOUND

ATTENUATING

BATT INSLATION.

SECURE TO PREVENT

SAGGING

1 LAYER 5 8" TYPE 'X'

GWB TO UNDERSIDE

OF ROOF DECK

ABOVE

EXIST. ROOF

DECK

INTERIOR PERIMETER WALL:

(STC 50 RATING)

EXISTING WALL, SAME CONSTRUCTION

AS ABOVE. REMOVE SUITE SIDE/ROOM

107 SIDE GWB. REMOVE AND REPLACE

SOUND ATTENUATION INSULATION TO

DECK ABOVE. SECURE INSULATION TO

PREVENT SAGGING. INSTALL TWO (2)

LAYERS OF 58" TYPE 'X' GWB AND

PROVIDE CLASS 4 FINISH, PRIME AND

PAINT, AND SEAL ALL OPENINGS FROM

FLOOR TO ROOF DECK. SEAL

OPENINGS AT WALL/ROOF DECK .

6" SOUND

ATTENUATION BATT

INSULATION 4'-0"

FROM EITHER SIDE

OF WALL.

4" WALL BASE

SOUND ATTENUATION

SEALANT

PROVIDE CLASS 4 FINISH AND

PRIME AND PAINT FROM

FLOOR TO ROOF DECK

ABOVE.

1557824398E

WINDOW FRAME

WINDOW SASH

GLAZING

REMOVE WINDOW LATCH

HARDWARE

2" (TYP)

4"

(TYP)

INSTALL ALUMINUM Z-BRACKET,

1/4" THICK MIN TO PERMANENTLY

SHUT WINDOW - TWO (2)

PER WINDOW

PRE-DRILL 3/16"Ø HOLES IN

BRACKET AND WINDOW (TYP)

1/4"Ø STAINLESS STEEL, FULLY THREADED

UNDERCUT, TAMPER-RESISTANT

TORX FLAT HEAD SCREWS (TYP)

WINDOW SILL

SD1010 RF/IR/GLASS

FRAGMENTATION

CONTROL FILM OR

APPROVED EQUAL

R. HOYT

A. MARASCA G. REED

VARIES

C. JODHAN

876543

D

E

B

C

A

87654321

G

F

E

D

C

B

A

G

F

APPROVEDDRAWN

AIR EDUCATION AND TRAINING COMMAND

DATEREVISION

UNITED STATES AIR FORCE

MISSISSIPPI

FACILITY NUMBER:

SHEET OF

DRAWING NUMBER:

BILOXI

RECOMMENDED:

(Chief of Engineering)

SUBMITTED:

(Chief of Contracts Design)

SCALE:

PROJECT NUMBER:

CHECKED:

DATE:

DESIGNED:

DRAWN:

OFFICE OF CIVIL ENGINEERS

J. KOCI

KEESLER AIR FORCE BASE

MAHG21109924 OCT 2022

RENOVATE B412 PHASE 2 DCSA

SCALE:

HEAD/JAMB DETAIL

NTS

A-502

ARCHITECTURAL DETAILS II

DOOR & FRAME SCHEDULE

NUMBER

DOOR

WIDTH

NUMBER

DOOR

HEIGHT THICK.

SIZE

DOORS

TYPE

JAMB

TYPEFINISH FINISH

DETAILS

HEAD

FRAMES

HARDWARE

SET

DEPTH

FRAME RATING

FIRE NOTES

6'-0" D31 3/4" AL #1 -F27'-0"101A

3'-0" #4 -

3'-0" #4

119B 3'-0" #4

PAINTAL

3'-0"121A

PAINT

7'-0"

WRAP7'-0" 1 3/4" PAINTHM

WRAP7'-0" 1 3/4" PAINTHM

1 3/4" WD7'-0" PAINTHM

7'-0"7'-0"

STAIN

118B

119A

WRAP

F1

F1

F1

FRAME NOTES:

1. ALL HOLLOW METAL FRAME MEMBERS 2"

WIDE UNLESS NOTED OTHERWISE.

2. ALL HOLLOW METAL FRAMES ARE TO BE

PAINTED TO MATCH EXISTING FRAMES.

3. SEAL VOIDS WITHIN WALLS AT FRAMES

WITH INSULATION WHERE NEEDED.

DOOR NOTES:

1. ALL INTERIOR WOOD DOORS TO MATCH

EXISTING INTERIOR WOOD DOORS IN

FINISH AND COLOR

F1D1

MTL STUD WALL

FRAMING

MTL STUD WALL

FRAMING

SEALANT ALL

AROUND

FRAME AS SCHED

DOOR AS SCHED

GWB

FRAME AS SCHED

SEALANT ALL

AROUND

DOOR AS SCHED

GWB

HEAD DETAIL JAMB DETAIL

ROOM FINISH SCHEDULE

CORRIDOR

OFFICE

CLOSET

119B

119A

RM# ROOM NAME

C

AR

PE

T

FLOOR CLG.HT

R U

BB

ER

BASE WALLS CEILING RM#

RESTROOM113

INVESTIGATION ROOM

INVESTIGATION ROOM

NOTES

PT

D

. G

YP

. B D

121A

OFFICE

COPY / FILE

LA

Y-

IN

A

C C

O U

S

TI

LE

9'-0"

LU

XU

R Y

VI

N

YL

T

IL

E

INVESTIGATION ROOM

RESTROOM

CONFERENCE

118A

118B INVESTIGATION ROOM

9'-0"

9'-0" 9'-0" 9'-0" 9'-0"

9'-0"

9'-0"

9'-0"

CORRIDOR102 -9'-0" 102

MTL STUD WALL

FRAMING

MTL STUD WALL

FRAMING

SEALANT ALL

AROUND

FRAME AS SCHED

DOOR AS SCHED

GWB

FRAME AS SCHED

SEALANT ALL

AROUND

DOOR AS SCHED

GWB

HEAD DETAIL JAMB DETAIL

INTERIOR SIDE

2 LAYERS OF

GWB

INTERIOR SIDE

2 LAYERS OF

GWB

NOTE: THESE DETAILS ARE USED FOR

DOORS WHERE WALL TYPE 2 IS

LOCATED, VERIFY THROAT

-9'-0" -9'-0" -9'-0"

3'-0" #4PAINTHM7'-0" 1 3/4"118A WRAPF1 -D1

D1

D1

D1

J2 H2

J2 H2

J2 H2

J1 H1

OPENING SCHEDULE NOTES

1. SEE SPECIFICATION 087100 DOOR HARDWARE FOR GENERAL HARDWARE

SPECIFICATIONS.

HARDWARE NOTES

1. INSTALL AND USE TEMPORARY 'CONSTRUCTION CORES'. DO NOT INSTALL

PERMANENT CORES.

2. ALL PERMANENT LOCK CORES SHOULD BE SMALL FORMAT

INTERCHANGEABLE CORE (BASE STANDARD).

3. PROVIDE ALL PERMANENT BLANK CORES TO THE CONTRACTING OFFICER

FOR THE BASE LOCKSMITH TO KEY AND INSTALL.

4. PROVIDE ALL BLANK KEYS TO THE CONTRACTING OFFICER FOR THE BASE

LOCKSMITH FOR KEYING.

5. ALL CHARACTERISTICS:

A. EQUIP LOCKSETS WITH CORE CYLINDERS TO MATCH EXISTING BASE

STANDARD.

B. METALS: CONSTRUCT LOCK CYLINDER PARTS FROM BRASS OR

BRONZE, STAINLESS STEEL, OR NICKEL SILVER.

C. KEY MATERIAL: PROVIDE KEYS OF NICKEL SILVER ONLY.

D. KEY QUANTITY: FURNISH 3 BLANK KEYS FOR EACH LOCK.

#3

SCALE:

DOOR ELEVATIONS

NTS

3'-0"

7'-0" 7'-0"

2"

AS SCHEDULED

MATERIAL MATERIAL

PLUMBING FIXTURE SCHEDULE

TAG TYPE MOUNTING RIM HT. BASIS OF DESIGN MATERIAL FINISH CW HW TRAP DRAIN VENT TRIM / REMARKS

EWC-1 ABA WATER COOLER - DBL. W/

BOTTLE FILLER WALL HUNG 33" / 39.5" ELKAY - EZSTL8WSLK STEEL GRAY /

BEIGE 2 @ 3/8" 2 @ 1-1/4" 2 @ 1-1/2" 2 @ 1-1/4" DUAL HEIGHT UNIT, PROVIDE WITH SERVICE STOP. ELECTRICAL 120V/5A

S-1 KITCHEN SINK UNDERMOUNT 36" SINK: PLUMBER FRIENDLY - PFSSU31188

FAUCET: ZURN Z6920-XL-CP4-GC-N-HW6. STEEL STAINLESS 1/2" 1/2" 2 @ 1-1/2" 2-1/2" 1-1/4" FAUCET: EPA WATERSENSE FAUCET; MAX FLOW 0.5 GPM @ 60

PSI. PROVIDE SENSOR POWER CONVERTER, HARD WIRED.

119B 119A

121A

118A 118B

1 3/4"

PAINTHM WRAPF1D1 J2 H2

101A

119B

121A

118B

119A

118A

PT

D

. G

YP

. B D

3'-0" D21 3/4" HM #2 -F17'-0"101B PAINTHMPAINT7'-0"7'-0" J1 H1 101B

3'-0"121 1 3/4"7'-0" PAINTHM WRAPF1 -D1 J1 H1 #4 121

3'-0"120 1 3/4" WD7'-0" PAINTHMSTAIN WRAPF1 -D1 J1 H1 #3 STC-50. PROVIDE VINYL TRANSITION STRIP BETWEEN

CARPET AND LUXURY VINYL TILE.

SCALE:

WINDOW SECURITY BRACKETS

NTS

F2

SEE

DOOR

SCHEDULE

SEE

DOOR

SCHEDULE

SEE

DOOR

SCHEDULE

SEE

DOOR

SCHEDULE

6" 6"

6"

6"

5' - 0"

1' - 0"

1' - 0"

D3 D2

H1 J1 H2 J2

WRAP

WRAP

HARDWARE SET #1

SINGLE-CYLINDER DEADBOLT LOCK

EXTERIOR - ADA COMPLIANT DOOR HANDLES

HEAVY-DUTY AUTOMATIC DOOR CLOSER

INTERIOR - CRASH BAR WITH VERTICAL ROD

PANIC BARS

ASTRAGAL (OVERLAPPING MOLDING)

CAM-LIFT FULL MORTISE HINGE

SWEEP

HARDWARE SET #2

ADA COMPLIANT ACCESSIBLE DOOR HANDLES

CAM-LIFT FULL MORTISE HINGE

HEAVY DUTY CLOSER

ELECTRONIC STRIKE (COORDINATE WITH

SECURITY VENDOR)

STAINLESS STEEL KICK PLATE

SWEEP

HARDWARE SET #3

ADA COMPLIANT ACCESSIBLE DOOR HANDLES

HEAVY DUTY CLOSER

CAM-LIFT FULL MORTISE HINGE

FULL MORTISE ADJUSTABLE DOOR BOTTOM

ADA THRESHOLD

ASTRAGAL PLATE

ADA COMPLIANT KEYED CYLINDRICAL

LOCKSETS

HARDWARE SET #4

HARDWARE AS PROVIDED WITH

LOCKMASTERS STC50 3070 DOOR-IN-A-BOX KIT

NOTE:

ALL INTERIOR DOOR HARDWARE TO MATCH TYPE AND APPEARANCE OF PREVIOUS RENOVATION

STC-50.

STC-50.

STC-50.

STC-50.

STC-50. PROVIDE VINYL TRANSITION STRIP BETWEEN

CARPET AND LUXURY VINYL TILE.

WATER HEATER SCHEDULE

TAG TYPE FUEL MANUFACTURER MODEL NO. STORAGE (GAL)

FUEL

INPUT

1ST HR. RECOVERY

(GPH)

SUPPLY

VOLT

WH-1 POINT OF USE ELECTRIC AMERICAN STANDARD CE-2-1/2-AS 2.5 1.4 Kw 7.7 120V

DOUBLE GLASS, ASSOCIATED FRAME, VERTICAL ROD PANIC.

EQUIP DOOR WITH HEAVY DUTY AUTOMATIC DOOR CLOSER.

LOCKMASTER STC-50 3070 DOOR-IN-A-BOX KIT OR

APPROVED EQUAL.

WD STAIN

WD STAIN

WD STAIN

WD STAIN

WD STAIN

1557824398E

SOLID SURFACE

COUNTERROP AND

BACK-SPLASH

REFRIGERATOR

(NIC)

7' -0

3' -0

1'

-6

2' -6

3'-0"

2' -0

9' -0

A4.0

PLAM ON EXPOSED

CABINET SURFACES.

PLAM ON EXPOSED

CABINET SURFACES.

5'-41 2"

PLASTIC LAMINATE ON 3/4"

HARDWOOD FACE FRAME

7' -0

3' -0

4" PLYWD END PANEL & BOT. OUTSIDE FACE

OF EXPOSED END PANEL SHALL BE COVERED

W/ PLAM

4" TOE SPACE

4" PLYWD BACK

FIN FL AS SCHED

RUBBER BASE2 x 6 TRTD WD

1 x 4 WD

1 x 4 WOODEN CLEAT (TOP & BOT)

PLASTIC LAMINATE ON 3/4"

HARDWOOD FACE FRAME

PLASTIC LAMINATE ON 3/4" PLYWOOD DOOR

4" PLYWOOD ADJUSTABLE SHELF WITH

HARDWOOD EDGE AND TRIM FINISH

HANDLE AS SPEC

PLAM ON 3 4" PLYWD BOT

4" PLYWD END PANEL

4" PLYWD BACK

ADJ SHELF BRACKET

HANDLE AS SPEC

PLAM FINISH ON 3 4" PLYWD DOOR,

FALSE DWR FRONT AND BASE

CABINET

1 x 8 WD

2'-0"

1' -6

2'

-6

1'-0"

1X4 SOLID SURFACE

BACKSPLASH

2" SOLID SURFACE TOP

WITH RADIUS EDGE

PROVIDE 34" HDWD FRAME FOR

SOLID SURFACE SUPPORT

3"

5' -3

TO

T O

P O

F

SI

G N

TYP. DOOR

9"

9"

DCSA

2"

6" 3"

1-1/2" TACTILE ROOM NUMBER

WITH BRAILLE HELVETICA NEUE

55 ROMAN

PRINTED PAPER INSERT

WITH ROOM DESCRIPTION

4" PRINTED MESSAGE

HELVETICA NEUE 55 ROMAN

REMOVABLE END CAPS

NOTE: VERIFY WITH CONTRACTING

OFFICER EXACT VERBIAGE OF SIGNAGE

PROVIDE WHITE LETTERS AND MEDIUM

BRONZE BACKGROUND

R. HOYT

A. MARASCA G. REED

VARIES

C. JODHAN

876543

D

E

B

C

A

87654321

G

F

E

D

C

B

A

G

F

APPROVEDDRAWN

AIR EDUCATION AND TRAINING COMMAND

DATEREVISION

UNITED STATES AIR FORCE

MISSISSIPPI

FACILITY NUMBER:

SHEET OF

DRAWING NUMBER:

BILOXI

RECOMMENDED:

(Chief of Engineering)

SUBMITTED:

(Chief of Contracts Design)

SCALE:

PROJECT NUMBER:

CHECKED:

DATE:

DESIGNED:

DRAWN:

OFFICE OF CIVIL ENGINEERS

J. KOCI

KEESLER AIR FORCE BASE

MAHG21109924 OCT 2022

RENOVATE B412 PHASE 2 DCSA

SCALE:

KITCHENETTE CABINET ELEVATION

NTS

A-503

ARCHITECTURAL DETAILS III

SCALE:

INTERIOR SIGNAGE MOUNTING TYPES

NTS SCALE:

INTERIOR SIGNAGE

NTS

SCALE:

CABINET SECTION

NTS

1557824398E

G. REED

J. VERGERON G. REED

MAHG21109916 MAR 2023

G. REED

G. REED

RENOVATE B412 PH 2 DCSA

VARIES

FIBERGLASS PANEL. PRESSURE

WASH FRONT AND BACK OF

PANEL

PRESSURE WASH

BRICK

5'-4" TALL MECHANICAL YARD

BRICK FENCE. PRESSURE WASH

TOP, BOTH SIDES AND

FOOTING BELOW. (+/-1100 SF)

NO WORK THIS SIDE

NO WORK THIS SIDE

PRESSURE WASH

BRICK

FIBERGLASS PANEL. PRESSURE

WASH FRONT AND BACK OF

PANEL

PRESSURE WASH CONCRETE

SIDEWALK WITHIN THE LIMITS

SHOWN

EXTERIOR PRESSURE WASH

NO WORK

THIS AREA

NO WORK

THIS AREA

AutoCAD SHX Text A504

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text B

AutoCAD SHX Text C

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text A

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text G

AutoCAD SHX Text F

AutoCAD SHX Text E

AutoCAD SHX Text D

AutoCAD SHX Text C

AutoCAD SHX Text B

AutoCAD SHX Text

APPROVED

AutoCAD SHX Text

DRAWN

AutoCAD SHX Text

AIR EDUCATION AND TRAINING COMMAND

AutoCAD SHX Text

DATE

AutoCAD SHX Text

REVISION

AutoCAD SHX Text

UNITED STATES AIR FORCE

AutoCAD SHX Text A

AutoCAD SHX Text

MISSISSIPPI

AutoCAD SHX Text

FACILITY NUMBER:

AutoCAD SHX Text

AutoCAD SHX Text

SHEET OF

AutoCAD SHX Text

DRAWING NUMBER:

AutoCAD SHX Text

BILOXI

AutoCAD SHX Text

RECOMMENDED:

AutoCAD SHX Text (Chief of Engineering)

AutoCAD SHX Text

SUBMITTED:

AutoCAD SHX Text (Chief of Contracts Design)

AutoCAD SHX Text

SCALE:

AutoCAD SHX Text

PROJECT NUMBER:

AutoCAD SHX Text

CHECKED:

AutoCAD SHX Text

DATE:

AutoCAD SHX Text

DESIGNED:

AutoCAD SHX Text

DRAWN:

AutoCAD SHX Text

AutoCAD SHX Text

OFFICE OF CIVIL ENGINEERS

AutoCAD SHX Text

KEESLER AIR FORCE BASE

AutoCAD SHX Text G

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text F

AutoCAD SHX Text

AutoCAD SHX Text

SCALE

AutoCAD SHX Text

AutoCAD SHX Text

KEY PLAN

AutoCAD SHX Text A504

AutoCAD SHX Text

AutoCAD SHX Text 1/8"=1'-0"

AutoCAD SHX Text

SCALE

AutoCAD SHX Text

AutoCAD SHX Text

NORTH ELEVATION

AutoCAD SHX Text A504

AutoCAD SHX Text

AutoCAD SHX Text 1/8"=1'-0"

AutoCAD SHX Text

SCALE

AutoCAD SHX Text

AutoCAD SHX Text

SOUTH ELEVATION

AutoCAD SHX Text A504

AutoCAD SHX Text

AutoCAD SHX Text 1/8"=1'-0"

AutoCAD SHX Text

SCALE

AutoCAD SHX Text

AutoCAD SHX Text

WEST ELEVATION

AutoCAD SHX Text A504

AutoCAD SHX Text

AutoCAD SHX Text 1/8"=1'-0"

AutoCAD SHX Text

SCALE

AutoCAD SHX Text

AutoCAD SHX Text

EAST ELEVATION

AutoCAD SHX Text A504

AutoCAD SHX Text

AutoCAD SHX Text 1/8"=1'-0"

AutoCAD SHX Text

1. PRESSURE WASH THE MECHANICAL YARD MASONRY FENCE, ITS FOOTING PAD, PRESSURE WASH THE MECHANICAL YARD MASONRY FENCE, ITS FOOTING PAD, SIDEWALK AS HATCHED, AND FROM BUILDING'S NORTH AND SOUTH ELEVATIONS ONLY. REMOVE DIRT, MILDEW, MOLD, AND/OR ALGAE FROM (WALLS, WINDOWS, DOORS AND FRAMES, BUILDING TRIM, FRONT AND BACK OF FIBERGLASS FASCIA, ETC.). (SEAL CRACKS AND CREVICES AROUND DOORS TO PREVENT WATER PASSAGE INTO THE BUILDING). 2. CLEAN EXTERIOR SURFACES W/ WATER ONLY, NO DETERGENTS OR CHEMICALS. CLEAN EXTERIOR SURFACES W/ WATER ONLY, NO DETERGENTS OR CHEMICALS. 3. USE CARE TO PREVENT DAMAGE TO EXISTING SURFACES AND EXISTING USE CARE TO PREVENT DAMAGE TO EXISTING SURFACES AND EXISTING LANDSCAPING. 4. REMOVE AND REPLACE DAMAGED SEALANT IN CONTROL AND EXPANSION REMOVE AND REPLACE DAMAGED SEALANT IN CONTROL AND EXPANSION JOINTS ON MASONRY WALL. 5. USE A WATER PRESSURE THAT ADEQUATELY CLEANS THE BUILDING EXTERIOR USE A WATER PRESSURE THAT ADEQUATELY CLEANS THE BUILDING EXTERIOR WITHOUT DAMAGING THE EXTERIOR FINISH. 6. REPAIR/REPLACE DAMAGE ITEMS TO PRE-DAMAGED CONDITION.REPAIR/REPLACE DAMAGE ITEMS TO PRE-DAMAGED CONDITION.

AutoCAD SHX Text

CLEAN BUILDING EXTERIOR

B

C

D

CORRIDOR

CORRIDOR

MEN

WOMEN

VEST

INVEST. ASSIST.

121 SAC

CONFERENCE/TRAINING

M-101

J. MENZIES

A. MARASCA G. REED

VARIES

C. JODHAN

876543

D

E

B

C

A

87654321

G

F

E

D

C

B

A

G

F

APPROVEDDRAWN

AIR EDUCATION AND TRAINING COMMAND

DATEREVISION

UNITED STATES AIR FORCE

MISSISSIPPI

FACILITY NUMBER:

SHEET OF

DRAWING NUMBER:

BILOXI

RECOMMENDED:

(Chief of Engineering)

SUBMITTED:

(Chief of Contracts Design)

SCALE:

PROJECT NUMBER:

CHECKED:

DATE:

DESIGNED:

DRAWN:

OFFICE OF CIVIL ENGINEERS

P. BRULL

KEESLER AIR FORCE BASE

MAHG21109924 OCT 2022

RENOVATE B412 PHASE 2 DCSA

SCALE:

OVERALL MECHANICAL FLOOR PLAN

1/4" = 1'-0"

SCALE: 1/4" = 1'-0"

21 4 80

OVERALL MECHANICAL FLOOR PLAN

MD-102

A

M-103 B

1557824398E

J. MENZIES

VARIES

C. JODHAN

876543

D

E

B

C

A

87654321

G

F

E

D

C

B

A

G

F

APPROVEDDRAWN

AIR EDUCATION AND TRAINING COMMAND

DATEREVISION

UNITED STATES AIR FORCE

MISSISSIPPI

FACILITY NUMBER:

SHEET OF

DRAWING NUMBER:

BILOXI

RECOMMENDED:

(Chief of Engineering)

SUBMITTED:

(Chief of Contracts Design)

SCALE:

PROJECT NUMBER:

CHECKED:

DATE:

DESIGNED:

DRAWN:

OFFICE OF CIVIL ENGINEERS

P. BRULL

KEESLER AIR FORCE BASE

MAHG21109924 OCT 2022

RENOVATE B412 PHASE 2 DCSA

SCALE:

TYPICAL DUCT/DIFFUSER DETAIL

NTS

M-501

MECHANICAL DETAILS

SUPPLY AIR DUCT

SPIN - IN FITTING WITH VOLUME DAMPER

FLEX DUCT CLAMP

GALV. SADDLE

CEILING CEILING

AIR FLOW AIR FLOW

FLEXIBLE DUCT

5'-0" MAXIMUM

FLOW DIRECTION

SCALE:

TYPICAL FLEXIBLE DUCT SUPPORT DETAIL

NTS

DUCT SHALL EXTEND STRAIGHT

FOR SEVERAL INCHES FROM A

CONNECTION BEFORE BENDING

MIN. 1" WIDE HANGER

STRAP (TYP.)

MAX. SAG 1/2" PER

FOOT OF SUPPORT

SPACING

MIN. 1½" WIDE BAND CLAMP

(TYP.) SHALL NOT

CONSTRICT DUCT. WIRENOT

PERMITTED.

SUPPORT SYSTEM MUST NOT DAMAGE

DUCT OR CAUSE OUT OF ROUND

SHAPE.

CLOSER MAXIMUM INTERVALS MAY BE

SPECIFIED AS A CONDITION OF U.L.

LISTING, PARTICULARY IN FIRE RATED

FLOOR/CEILING ASSEMBLIES.

MAIN BRANCH

DUCT

INSULATE BACK OF

DIFFUSER OR

GRILLE (DO NOT

TAPE TO T-BAR)

INSULATE SPIN - IN WITH 2" THICK

INSULATION WITH VAPOR BARRIER

LEAVING DAMPER OPERATOR

ACCESSIBLE "PROVIDE 2" STANDOFF"

SUPPORT FROM

STRUCTURE ABOVE

WIRE SUSPENSION

SYSTEM

1557824398E

M. GONZALEZ

VARIES

C. JODHAN

876543

D

E

B

C

A

87654321

G

F

E

D

C

B

A

G

F

APPROVEDDRAWN

AIR EDUCATION AND TRAINING COMMAND

DATEREVISION

UNITED STATES AIR FORCE

MISSISSIPPI

FACILITY NUMBER:

SHEET OF

DRAWING NUMBER:

BILOXI

RECOMMENDED:

(Chief of Engineering)

SUBMITTED:

(Chief of Contracts Design)

SCALE:

PROJECT NUMBER:

CHECKED:

DATE:

DESIGNED:

DRAWN:

OFFICE OF CIVIL ENGINEERS

M. SMITH

KEESLER AIR FORCE BASE

MAHG21109924 OCT 2022

RENOVATE B412 PHASE 2 DCSA

E-001

GENERAL NOTES,

ABBREIVATIONS AND LEGEND

ELECTRICAL SYMBOL LEGEND:

(XX)-(XXX)

CODE COMPLIANCE CRITERIA:

1. DE-ENERGIZE ALL ITEMS TO BE DEMOLISHED OR REMOVED. PERFORM

LOCKOUT/TAGOUT IN ACCORDANCE WITH OSHA 29 CFR 1910.147 AND

NFPA 70E.

2. CONTRACTOR MUST TAKE NECESSARY PRECAUTIONS AND PROVIDE

PROTECTION AS REQUIRED TO PRESERVE CONDITION OF EXISTING

UTILITIES EQUIPMENT, FURNISHINGS, AND SURFACES NOT INDICATED

FOR REMOVAL. IT IS THE CONTRACTOR'S RESPONSIBILITY TO WORK

AROUND THE EXISTING CONDITIONS TO ACCOMPLISH THE WORK.

3. COVER ALL OPENINGS OR PENETRATIONS IN ELECTRICAL ENCLOSURES

RESULTING FROM DEMOLITION ACTIVITIES WITH METAL PLUGS

MANUFACTURED FOR THAT PURPOSE.

4. SEAL ALL WALL PENETRATIONS RESULTING FROM DEMOLITION

ACTIVITIES WITH UL RATED FIRE SEALANT TO MATCH EXISTING WALL

ASSEMBLY RATING.

1. ALL ELECTRICAL INSTALLATION MUST BE IN ACCORDANCE WITH CODES AND

STANDARDS LISTED ON THIS SHEET.

2. ALL CONSTRUCTION MUST BE GOVERNED BY THE PLANS, SPECIFICATIONS, AND

ALL APPLICABLE BUILDING AND SAFETY CODES.

3. CONTRACTOR MUST BE FAMILIAR WITH THE SITE, THE WORK REQUIRED, THE

CUSTOMER'S WORK PROCEDURES, AND ALL OTHER CONDITIONS THAT MAY

AFFECT THE SUCCESSFUL COMPLETION OF THE JOB PRIOR TO

COMMENCEMENT OF WORK.

4. FIELD LOCATE ALL EXISTING UTILITIES AS TO LOCATION AND ELEVATION.

NOTIFY THE CONTRACTING OFFICER OF ANY AND ALL CONFLICTS PRIOR TO

BEGINNING CONSTRUCTION.

5. IT IS THE CONTRACTOR'S RESPONSIBILITY TO WORK AROUND THE EXISTING

CONDITIONS TO ACCOMPLISH THE WORK.

6. LOCATIONS OF ALL ELECTRICAL EQUIPMENT ARE APPROXIMATE AND MAY BE

RELOCATED TO AN APPROVED LOCATION. CONTACT CONTRACTING OFFICER

PRIOR TO ANY FIELD CHANGES.

7. ALL SPECIFIC MATERIALS AND PRODUCTS IDENTIFIED IN THE PROJECT

DRAWINGS ARE INCLUDED AS THE BASIS OF DESIGN. CONTRACTOR MAY SUBMIT

EQUIVALENT PRODUCTS IN COMPLIANCE WITH THE PROJECT SPECIFICATIONS

FOR APPROVAL.

8. ALL NEW INTERIOR CONDUITS ROUTED ABOVE CEILING MUST BE EMT WHILE

INTERIOR CONDUITS ROUTED BELOW CEILING MUST BE WALL-MOUNTED

UNLESS OTHERWISE NOTED.

9. ALL NEW CONDUITS MUST BE MINIMUM 3/4-INCH.

10. ALL NEW ELECTRICAL CONDUCTORS INSTALLED MUST BE COPPER INSULATION

TYPE THHN-THWN-2 UNLESS OTHERWISE NOTED.

11. REFER TO PANEL SCHEDULES INCLUDED IN THIS DRAWING SET FOR BRANCH

CIRCUIT, BREAKER, CONDUCTOR, AND CONDUIT INFORMATION.

12. ENSURE ALL MODIFIED PANELBOARDS RECEIVE NEW, TYPED PANEL SCHEDULES

REFLECTING AS-BUILT CONDITIONS. INSTALL PANEL SCHEDULES ON THE INSIDE

OF THE PANEL DOOR OR IN A SIMILAR CONSPICUOUS LOCATION.

13. REPAIR ALL DAMAGE TO GALVANIZING ZINC COATINGS RESULTING FROM

CONSTRUCTION AND DEMOLITION ACTIVITIES USING COLD GALVANIZING

COMPOUND.

14. ALL NEW LIGHTING CONTROL CONDUCTORS MUST BE #22 AWG MINIMUM AND

CLASS 2 TEFLON COATED FOR UL2043 PLENUM RATED.

15. PROVIDE NYLON PULL STRINGS IN ALL EMPTY CONDUITS AND RACEWAYS

INSTALLED AS PART OF THIS PROJECT.

29 CFR 1926/1910 OSHA STANDARDS FOR CONSTRUCTION

NFPA 70 NATIONAL ELECTRIC CODE, 2020

NFPA 70E STANDARD FOR ELECTRICAL SAFETY IN THE WORKPLACE, 2021

UFC 3-501-01 ELECTRICAL ENGINEERING, CHANGE 1 2019

UFC 3-520-01 INTERIOR ELECTRICAL SYSTEMS, WITH CHANGE 2, 2021

UFC 3-530-01 INTERIOR AND EXTERIOR LIGHTING SYSTEMS AND CONTROLS, WITH CHANGE 4, 2019

UFC 4-021-02 ELECTRONIC SECURITY SYSTEMS, WITH CHANGE 1, 2019

ABBREVIATIONS:

A AMPERE

AFF ABOVE FINISHED FLOOR

AHU AIR HANDLING UNIT

BLDG BUILDING

CB CIRCUIT BREAKER

CH CHILLER

CKT CIRCUIT

CU CONDENSING UNIT

D/S DISCONNECT SWITCH

EF EXHAUST FAN

EMT ELECTRICAL METALLIC TUBING

ETR EXISTING TO REMAIN

FCU FAN COIL UNIT

GND GROUND

GWH GAS WATER HEATER

HZ HERTZ

KAIC THOUSAND AMPS INTERRUPTING CURRENT

KCMIL THOUSAND CIRCULAR MILLS

KV KILOVOLT

KVA KILOVOLT AMPERE

KW KILOWATT

MCB MAIN CIRCUIT BREAKER

MLO MAIN LUG ONLY

NEC NATIONAL ELECTRICAL CODE

NEMA NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION

NFPA NATIONAL FIRE PROTECTION ASSOCIATION

NTS NOT TO SCALE

OSHA OCCUPATIONAL SAFETY AND HEALTH ADMINISTRATION

PH PHASE

PNL PANEL

QTY QUANTITY

RCPT RECEPTACLE

SPD SURGE PROTECTION DEVICE

THNN THERMOPLASTIC HIGH HEAT RESISTANT NYLON

THWN-2 THERMOPLASTIC HEAT AND WATER RESISTANT NYLON

TP TELEPHONE

UFC UNIFIED FACILITIES CRITERIA

TYP TYPICAL

V VOLT

VAC VOLTS ALTERNATING CURRENT

VDC VOLTS DIRECT CURRENT

W WATT

ELECTRICAL GENERAL NOTES:

ELECTRICAL GENERAL NOTES - DEMOLITION:

TYPICAL NOTE, APPLICABLE TO

ALL OCCURENCES

SPECIFIC NOTE

CIRCUIT HOME RUN

(PANEL NAME) - (CIRCUIT NUMBER)

PNL XXX

A

FIXTURE A - REFER TO LIGHTING FIXTURE SCHEDULE ON THIS SHEET

B

FIXTURE B - REFER TO LIGHTING FIXTURE SCHEDULE ON THIS SHEET

C

FIXTURE C - REFER TO LIGHTING FIXTURE SCHEDULE ON THIS SHEET

EXISTING PANELBOARD

SINGLE POLE, 120V, 20 AMP LIGHT SWITCH

3 SINGLE POLE THREE-WAY, 20V, 20 AMP LIGHT SWITCH

DUPLEX RECEPTACLE, NEMA 5-20R, 120VAC, WALL MOUNTED

GFCI

GFCI DUPLEX RECEPTACLE, NEMA 5-20R, 120 VAC, WALL MOUNTED

QUADPLEX RECEPTACLE, NEMA 5-20R, 120VAC, FLOOR MOUNTED

ITEMS TO BE DEMOLISHED

AREA NOT IN SCOPE

D

FIXTURE D - REFER TO LIGHTING FIXTURE SCHEDULE ON THIS SHEET

RED LED EXIT LIGHT, WALL MOUNTED

(HATCHING DENOTES ILLUMINATED FACE DIRECTION)

(TYP)

LIGHTING CONTROL POWER PACK

LIGHTING CONTROL OCCUPANCY SENSOR, CEILING MOUNTED

M MOTOR RATED TOGGLE SWITCH

DISCONNECT SWITCH

PP

OS

LIGHTING CONTROL PHOTOCELL, CEILING MOUNTEDP

TYPICAL OCCUPANCY

SENSOR, SEE DRAWINGS FOR

COUNT

POWER PACK

TYPICAL WALLPOD SWITCH

ADDITIONAL DEVICES

120V CIRCUIT CONDUCTORS TO

LUMINAIRES

120V

120V 120V

120V CIRCUIT FROM SOURCE PANEL

TO

ADDITIONAL

OCCUPANCY

SENSORS

SCALE:

LIGHTING CONTROL OCCUPANCY SENSOR WIRING DETAIL

NTS

E

FIXTURE D - REFER TO LIGHTING FIXTURE SCHEDULE ON THIS SHEET

J JUNCTION BOX

LIGHTING FIXTURE SCHEDULE

FIXTURE ID MANUFACTURER MODEL # FIXTURE TYPE MOUNTING WATTAGE VOLTAGE LAMP TYPE

A METALUX 24RTC-48-UNV-L835-CD 2'X4' LED TROFFER RECESSED 36.8W UNV LED

B METALUX 24RTC-48-UNV-EL14W-L835-CD 2'X4' LED TROFFER WITH 14W BATTERY PACK RECESSED 36.8W UNV LED C PORTFOLIO LERSWM4B30D010P-EC4B30508035-4LBN1BSS3LI 4" LED DOWNLIGHT WALL MOUNTED 27.6W UNV LED D PORTFOLIO LERS4B30D010P-EC4B30508035-4LBN1BSS3LI 4" LED DOWNLIGHT SURFACE 27.6W UNV LED E PORTFOLIO LERS4B30D010RP-EC4B30508035-4LBSS3LIR2530EM14 4" LED DOWNLIGHT WITH 14W BATTERY PACK SURFACE 27.6W UNV LED

F SURE-LITES LPX6WGS11 LED EXIT LIGHT SURFACE 1.02W 120V LED

VD

C

24VDC

VD

C

VD

C

TO

ADDITIONAL

PHOTOSENSOR

TYPICAL PHOTOSENSOR, SEE

DRAWINGS FOR COUNT

24VDC

LIGHTING CONTROL DEVICES

DESCRIPTION VOLTAGE AMPERAGE BASIS OF

DESIGN BRAND

BASIS OF DESIGN

CATALOG

OCCUPANCY/VACANCY SENSOR 24V 35mA LEVITON OSC10-MAW

POWER PACK 120/24V 16A LEVITON OPP20-RD4

PHOTOCELL 24V 10mA LEVITON ODC0P-D0W

TP

WALL-MOUNTED AI TELEPHONE

1557824398E

B

C

D

CORRIDOR

CORRIDOR

MEN

WOMEN

VEST

INVEST. ASSIST.

121 SAC

CONFERENCE/TRAINING

E-101

M. GONZALEZ

A. MARASCA G. REED

VARIES

C. JODHAN

876543

D

E

B

C

A

87654321

G

F

E

D

C

B

A

G

F

APPROVEDDRAWN

AIR EDUCATION AND TRAINING COMMAND

DATEREVISION

UNITED STATES AIR FORCE

MISSISSIPPI

FACILITY NUMBER:

SHEET OF

DRAWING NUMBER:

BILOXI

RECOMMENDED:

(Chief of Engineering)

SUBMITTED:

(Chief of Contracts Design)

SCALE:

PROJECT NUMBER:

CHECKED:

DATE:

DESIGNED:

DRAWN:

OFFICE OF CIVIL ENGINEERS

M. SMITH

KEESLER AIR FORCE BASE

MAHG21109924 OCT 2022

RENOVATE B412 PHASE 2 DCSA

SCALE:

OVERALL ELECTRICAL FLOOR PLAN

1/4" = 1'-0"

SCALE: 1/4" = 1'-0"

21 4 80

OVERALL ELECTRICAL FLOOR PLAN

ED-102

A

E-103 C

E-104 D

E-105 E

OPEN OFFICE107

CONFERENCE

BREAK RM

TEAM

OFFICE

OFFICE

111A

COPY/FILE

111B

LAN

MECH

105B

SITTING

105A

OPEN

111C

PHONE

ED-102

B

1557824398E

2 3 4

B

C

D

CORRIDOR

CORRIDOR

MEN

WOMEN

VEST

INVEST. ASSIST.

121 SAC

CONFERENCE/TRAINING

114M

M. GONZALEZ

A. MARASCA G. REED

VARIES

C. JODHAN

876543

D

E

B

C

A

87654321

G

F

E

D

C

B

A

G

F

APPROVEDDRAWN

AIR EDUCATION AND TRAINING COMMAND

DATEREVISION

UNITED STATES AIR FORCE

MISSISSIPPI

FACILITY NUMBER:

SHEET OF

DRAWING NUMBER:

BILOXI

RECOMMENDED:

(Chief of Engineering)

SUBMITTED:

(Chief of Contracts Design)

SCALE:

PROJECT NUMBER:

CHECKED:

DATE:

DESIGNED:

DRAWN:

OFFICE OF CIVIL ENGINEERS

M. SMITH

KEESLER AIR FORCE BASE

MAHG21109924 OCT 2022

RENOVATE B412 PHASE 2 DCSA

GENERAL NOTES

A. REFER TO GENERAL DEMOLITION NOTES ON SHEET E-001 FOR

ADDITIONAL DEMOLITION INFORMATION.

B. REMOVE ALL MATERIALS TO BE DEMOLISHED FROM SITE AND

DISPOSE OFF-SITE IN A LEGAL LANDFILL. CONTRACTOR IS NOT

ALLOWED TO STOCKPILE DEMOLITION MATERIALS ON SITE. ALL

MATERIALS MUST BE REMOVED IN A TIMELY FASHION.

ED-102

SCALE:

ENLARGED ELECTRICAL DEMOLITION PLAN

1/4" = 1'-0"

SCALE: 1/4" = 1'-0"

21 4 80

ENLARGED ELECTRICAL

DEMOLITION PLAN

E-101 A

KEY NOTES

A. DEMOLISH AHU-2 MOTOR RATED TOGGLE SWITCH AND AHU-2

CONDUCTORS AND CONDUIT BACK TO SOURCE PANEL "MDP".

B. DEMOLISH CONDENSER UNIT CONDUCTORS AND CONDUIT BACK TO

SOURCE PANEL "MDP".

C. REMOVE AND RETAIN LIGHTING FIXTURES LOCATED IN BATHROOMS

AND TURN OVER TO THE GOVERNMENT. DEMOLISH CONDUCTORS

AND CONDUIT BACK TO SOURCE PANEL "MDP".

D. DEMOLISH ALL RECEPTACLE CIRCUITS INCLUDING RECEPTACLE,

CONDUCTORS, AND CONDUITS BACK TO SOURCE PANEL "LP".

E. DEMOLISH ALL LIGHTING CIRCUITS INCLUDING FIXTURES, SWITCHES,

CONDUCTORS, AND CONDUITS BACK TO SOURCE PANEL "MDP".

F. REMOVE WALL-MOUNTED AI PHONE AND TURN OVER TO DCSA

SECURITY. PULL AND RETAIN AI PHONE CONDUCTORS BACK TO

NEAREST JUNCTION BOX FOR FUTURE USE. PROVIDE EMPTY

JUNCTION BOX WITH COVER PLATE TO MATCH WALL FINISH.

GWH (ETR)

AHU-2

CU

A

B

C

AHU-2 TOGGLE SWITCH

PNL LP (ETR)

PNL MDP (ETR)

AHU-1 (ETR)

ED

CONFERENCE

SCALE:

ENLARGED ELECTRICAL DEMOLITION PLAN -

PHASE 1 CONFERENCE ROOM 107

1/4" = 1'-0"E-101 B

TP

F

1557824398E

IR-1

119A

FILE/COPY

121A

SAC

2 3 4

A

B

C

D

IR-2

119B

CORRIDOR

WOMEN'S RR

IR-4

118B

INVEST. ASSIST.

CORRIDOR

MEN'S RR

IR-3

118A

CAPGCCAPDHCAPQTCAPPNCAPMCCAPMG

CAPGCCAPDHCAPQTCAPPNCAPMCCAPMG

CAPGCCAPDHCAPQTCAPPNCAPMCCAPMG CAPGCCAPDHCAPQTCAPPNCAPMCCAPMG

CAPGCCAPDHCAPQTCAPPNCAPMCCAPMG

CAPGCCAPDHCAPQTCAPPNCAPMCCAPMG

CAPGCCAPDHCAPQTCAPPNCAPMCCAPMG

CAPGCCAPDHCAPQTCAPPNCAPMCCAPMG CAPGCCAPDHCAPQTCAPPNCAPMCCAPMG

CAPGCCAPDHCAPQTCAPPNCAPMCCAPMG CAPGCCAPDHCAPQTCAPPNCAPMCCAPMG

CAPGCCAPDHCAPQTCAPPNCAPMCCAPMG CAPGCCAPDHCAPQTCAPPNCAPMCCAPMG

CAPGCCAPDHCAPQTCAPPNCAPMCCAPMG

GFCI

GFCI GFCIGFCI

M. GONZALEZ

A. MARASCA G. REED

VARIES

C. JODHAN

876543

D

E

B

C

A

87654321

G

F

E

D

C

B

A

G

F

APPROVEDDRAWN

AIR EDUCATION AND TRAINING COMMAND

DATEREVISION

UNITED STATES AIR FORCE

MISSISSIPPI

FACILITY NUMBER:

SHEET OF

DRAWING NUMBER:

BILOXI

RECOMMENDED:

(Chief of Engineering)

SUBMITTED:

(Chief of Contracts Design)

SCALE:

PROJECT NUMBER:

CHECKED:

DATE:

DESIGNED:

DRAWN:

OFFICE OF CIVIL ENGINEERS

M. SMITH

KEESLER AIR FORCE BASE

MAHG21109924 OCT 2022

RENOVATE B412 PHASE 2 DCSA

GENERAL NOTES

A. REFER TO GENERAL NOTES ON SHEET E-001 FOR GENERAL PROJECT

INFORMATION.

B. REFER TO PANEL SCHEDULES ON SHEET E-701 FOR CIRCUIT

BREAKER, BRANCH CONDUCTOR, AND CONDUIT INFORMATION.

E-103

SCALE:

ENLARGED POWER PLAN

1/4" = 1'-0"

SCALE: 1/4" = 1'-0"

21 4 80

E-101 C

ENLARGED POWER PLAN

(LP)-(24)

(LP)-(26)

(LP)-(22)

(LP)-(20)

(LP)-(28)

(LP)-(30)

(LP)-(12)

(LP)-(17)

(LP)-(10)

(LP)-(41)

EXISTING PNL MDP

EXISTING PNL LP

(LP)-(18)

EXISTING GWH

KEY NOTES

A. INSTALL NEW GFCI RECEPTACLE TO POWER NEW WATER HEATER.

COORDINATE LOCATION WITH MECHANICAL CONTRACTOR.

B. INSTALL RECEPTACLES 6-INCHES ABOVE COUNTER TOP.

(LP)-(34)

(LP)-(14)

EXISTING AHU-1

B

(LP)-(32)

(LP)-(16)

(LP)-(36)

B A

1557824398E

B

C

D

C C C

D

A

B

B

B

B

AB

BA

B B

AB

BA

BA

B B

A

B

A

P

OS

P OS

OS

PP

PP

OS

P

P

OS

PP

P

OS

PP PP

OS

P

OS

P

PPP

OS

PP

OS

P P

OS

PP

PP

P

OSE

E

D

E

D

E

CONFERENCE/TRAINING

IR-1

119A

FILE/COPY

121A

SAC

IR-2

119B

CORRIDOR

IR-3

118A

IR-4

118B

INVEST. ASSIST.

CORRIDOR

WOMEN'S RR

MEN'S RR

J. MENZIES

A. MARASCA G. REED

VARIES

C. JODHAN

876543

D

E

B

C

A

87654321

G

F

E

D

C

B

A

G

F

APPROVEDDRAWN

AIR EDUCATION AND TRAINING COMMAND

DATEREVISION

UNITED STATES AIR FORCE

MISSISSIPPI

FACILITY NUMBER:

SHEET OF

DRAWING NUMBER:

BILOXI

RECOMMENDED:

(Chief of Engineering)

SUBMITTED:

(Chief of Contracts Design)

SCALE:

PROJECT NUMBER:

CHECKED:

DATE:

DESIGNED:

DRAWN:

OFFICE OF CIVIL ENGINEERS

P. BRULL

KEESLER AIR FORCE BASE

MAHG21109924 OCT 2022

RENOVATE B412 PHASE 2 DCSA

GENERAL NOTES

A. REFER TO PANEL SCHEDULES ON SHEET E-701 FOR CIRCUIT

BREAKER, BRANCH CONDUCTOR, AND CONDUIT INFORMATION.

B. LIGHT LEVELS ARE IN ACCORDANCE WITH UFC 3-530-01.

C. REFER TO LIGHTING FIXTURE SCHEDULE AND LIGHTING CONTROL

SCHEDULE ON SHEET E-001.

D. PROVIDE JUNCTION BOXES OR LINE SIDE CONNECTIONS TO ENSURE

INDEPENDENT SWITCHING FOR EACH LIGHTING CIRCUIT.

E. ENSURE THAT ALL EXIT LIGHTS ARE WIRED AHEAD OF ANY

SWITCHING DEVICES TO PROVIDE UNINTERRUPTED POWER. PROVIDE

BRANCH LIGHTING CIRCUITS WITH ADDITIONAL UN-SWITCHED PHASE

CONDUCTOR TO ALL EMERGENCY FIXTURES.

F. PROVIDE OCCUPANCY SENSOR CONTROLLED POWER CIRCUIT TO

LIGHTING FIXTURES AS INDICATED. REFER TO LIGHTING CONTROL

OCCUPANCY WIRING DETAIL ON SHEET E-001 FOR WIRING

INFORMATION.

E-104

SCALE:

ENLARGED LIGHTING PLAN

1/4" = 1'-0"

SCALE: 1/4" = 1'-0"

21 4 80

ENLARGED LIGHTING PLAN

E-101 D

(MDP)-(9)

(MDP)-(26)

(MDP)-(27)

(MDP)-(9)

(MDP)-(7)

(MDP)-(7)

(MDP)-(7)

(MDP)-(26)

(MDP)-(26)

(MDP)-(26) (MDP)-(26)

(MDP)-(27)(MDP)-(27)

(MDP)-(27)

(MDP)-(9)

(MDP)-(9)

(MDP)-(9)

ZONE 1

ZONE 2

ZONE 3 ZONE 5 ZONE 5

ZONE 4

ZONE 3

ZONE 5ZONE 5

ZONE 6

ZONE 6

ZONE 7

LIGHTING CONTROL SCHEDULE

LIGHTS SPACE TYPE FUNCTIONS

ZONE 1 CORRIDORS

OCCUPANCY SENSOR (AUTOMATIC OFF AFTER 20-MIN. DELAY), PHOTOSENSOR (50% TO 70%

LIGHTING POWER STEP AND ≤35% LIGHTING POWER STEP)

ZONE 2 COPY/PRINT ROOM

MANUAL ON, DIMMER, VACANCY SENSOR (AUTOMATIC OFF AFTER 20-MIN. DELAY),

PHOTOSENSOR (50% TO 70% LIGHTING POWER STEP AND ≤35% LIGHTING POWER STEP)

ZONE 3 CONFERENCE ROOM

MANUAL ON, VACANY SENSOR (AUTOMATIC OFF AFTER 15-MIN. DELAY), PHOTOSENSOR (50% TO

70% LIGHTING POWER STEP AND ≤35% LIGHTING POWER STEP)

ZONE 4 OFFICE SUPPORT

AREA

MANUAL ON, DIMMER, VACANCY SENSOR (AUTOMATIC OFF AFTER 20-MIN. DELAY)

ZONE 5 OFFICE

OCCUPANCY SENSOR (AUTOMATIC ON WHEN OCCUPANT IS DETECTED, AUTOMATIC OFF AFTER

15-MIN. DELAY), PHOTOSENSOR (50% TO 70% LIGHTING POWER STEP AND ≤35% LIGHTING

POWER STEP)

ZONE 6 BATHROOM

WALL-MOUNTED OCCUPANCY SENSOR (AUTOMATIC ON WHEN OCCUPANT IS DETECTED,

AUTOMATIC OFF AFTER 15-MIN. DELAY)

ZONE 7 JANITOR CLOSET MANUAL ON

NOTES:

1. LIGHTING CONTROLS MUST CONFORM TO ASHRAE 90.1 REQUIREMENTS.

1557824398E Text Box

J.BERGERON

1557824398E Text Box

PROVIDE COMBINATION EXIT AND EMERGENCY WITH BATTERY BACKUP

1557824398E Line

IR-1

119A

FILE/COPY

121A

SAC

2 3 4

A

B

C

D

IR-2

119B

CORRIDOR

WOMEN'S RR

IR-4

118B

INVEST. ASSIST.

CORRIDOR

MEN'S RR

IR-3

118A

CAPGCCAPDHCAPQTCAPPNCAPMCCAPMG

CAPGCCAPDHCAPQTCAPPNCAPMCCAPMG

CAPGCCAPDHCAPQTCAPPNCAPMCCAPMG CAPGCCAPDHCAPQTCAPPNCAPMCCAPMG

CAPGCCAPDHCAPQTCAPPNCAPMCCAPMG

CAPGCCAPDHCAPQTCAPPNCAPMCCAPMG

CAPGCCAPDHCAPQTCAPPNCAPMCCAPMG

CAPGCCAPDHCAPQTCAPPNCAPMCCAPMG CAPGCCAPDHCAPQTCAPPNCAPMCCAPMG

CAPGCCAPDHCAPQTCAPPNCAPMCCAPMG CAPGCCAPDHCAPQTCAPPNCAPMCCAPMG

CAPGCCAPDHCAPQTCAPPNCAPMCCAPMG CAPGCCAPDHCAPQTCAPPNCAPMCCAPMG

CAPGCCAPDHCAPQTCAPPNCAPMCCAPMG

J

J

M. GONZALEZ

A. MARASCA G. REED

VARIES

C. JODHAN

876543

D

E

B

C

A

87654321

G

F

E

D

C

B

A

G

F

APPROVEDDRAWN

AIR EDUCATION AND TRAINING COMMAND

DATEREVISION

UNITED STATES AIR FORCE

MISSISSIPPI

FACILITY NUMBER:

SHEET OF

DRAWING NUMBER:

BILOXI

RECOMMENDED:

(Chief of Engineering)

SUBMITTED:

(Chief of Contracts Design)

SCALE:

PROJECT NUMBER:

CHECKED:

DATE:

DESIGNED:

DRAWN:

OFFICE OF CIVIL ENGINEERS

M. SMITH

KEESLER AIR FORCE BASE

MAHG21109924 OCT 2022

RENOVATE B412 PHASE 2 DCSA

GENERAL NOTES

A. REFERENCE GENERAL NOTES ON SHEET E-001 FOR GENERAL

PROJECT INFORMATION.

B. ALL NEW SECURITY DEVICES TO BE INSTALLED BY GOVERNMENT'S

CONTRACTOR. CONTRACTOR TO PROVIDE JUNCTION BOXES,

CONDUITS, AND PULL STRINGS BACK TO SERVER ROOM 111B.

COORDINATE JUNCTION BOX MOUNTING REQUIREMENTS WITH

GOVERNMENT.

C. ENSURE NEW CONDUIT RUNS FROM LAN ROOM 111B TO ROOMS 118,

120, AND 121 EXTEND 3-INCHES PAST THE WALLS ON BOTH ENDS.

E-105

SCALE:

ENLARGED SECURITY PLAN

1/4" = 1'-0"

SCALE: 1/4" = 1'-0"

21 4 80

E-101 E

SECURITY PLAN

EXISTING PNL MDP

EXISTING PNL LP

EXISTING GWH

EXISTING AHU-1

KEY PAD

KEY PAD

KEY NOTES

A. INSTALL ONE (1) 3-INCH CONDUIT ABOVE CEILING FROM LAN ROOM

111B TO CONFERENCE ROOM 118.

B. INSTALL ONE (1) 1-INCH CONDUIT ABOVE CEILING FROM LAN ROOM

111B TO SAC ROOM 120.

C. INSTALL ONE (1) 1-INCH CONDUIT ABOVE CEILING FROM LAN ROOM

111B TO INVEST. ASSIST ROOM 121.

D. INSTALL ONE (1) 1-INCH CONDUIT ABOVE CEILING FROM LAN ROOM

111B TO MAIN SECONDARY ENTRY DOOR.

A

BC

D

TO LAN

ROOM 111B

1557824398E

VARIES

C. JODHAN

876543

D

E

B

C

A

87654321

G

F

E

D

C

B

A

G

F

APPROVEDDRAWN

AIR EDUCATION AND TRAINING COMMAND

DATEREVISION

UNITED STATES AIR FORCE

MISSISSIPPI

FACILITY NUMBER:

SHEET OF

DRAWING NUMBER:

BILOXI

RECOMMENDED:

(Chief of Engineering)

SUBMITTED:

(Chief of Contracts Design)

SCALE:

PROJECT NUMBER:

CHECKED:

DATE:

DESIGNED:

DRAWN:

OFFICE OF CIVIL ENGINEERS

M. SMITH

KEESLER AIR FORCE BASE

MAHG21109924 OCT 2022

RENOVATE B412 PHASE 2 DCSA

E-701

ELECTRICAL PANEL SCHEDULES

PANEL MDP SCHEDULE PANEL LP SCHEDULE

GENERAL NOTES

A. PROVIDE NEW CIRCUIT BREAKER, CONDUCTORS, AND CONDUITS AS

INDICATED IN PANEL SCHEDULES.

PANEL NAME MDP

TYPE MCB 225 AMP MECH/ELEC RM - 112

VOLTAGE 208/120 MINIMUM AIC RATING 10 KA FED FROM: T35-412

TR

IP

A M

PS

PO

LE

S

DESIGNATION WIRE

N

EU

TR

A

L

G N

D

C O

N D

K

VA

C A

TE

G

O R

Y

N O

PH

A

SE

A

PH

A

SE

B

PH

A

SE

C

N O

C A

TE

G

O R

Y

K

VA

C O

N D

G N

D

N

EU

TR

A

L

WIRE DESIGNATION

PO

LE

S

TR

IP

A M

PS

1 SPACE 1 0.0 2 SPACE 1

1 GFI EXTERIOR 3 0.0 4 SPACE 1

20 1 HVAC UNIT LAN RM 5 0.0 6 FIRE ALARM PANEL 1 20

20 1 LGTS 113, 114, & 115 #12 #12 #12 3/4" 0.2 L 7 0.2 8 FRIG - BREAK RM 1 20

20 1 EXIT LIGHTS #12 #12 #12 3/4" 0.1 L 9 0.1 10 RECPT - BREAK RM 1 20

20 1 SPARE 11 0.0 12 RECPT - BREAK RM 1 20

20 1 SPARE 13 0.0 14 RECPT - OFFICE 104 1 20

20 1 CONFERENCE BEHIND TV 15 0.0 16 CONFERENCE BEHIND TV 1 20

20 1 CONFERENCE BELOW TV 17 0.0 18 CONFERENCE BELOW TV 1 20

20 1 CONFERENCE DESK 19 0.0 20 CONFERENCE BEHIND TV 1 20

1 LGTS 104 & 111 21 0.0 22 LGTS 101, 103, 112, & 116 1

1 LGTS 105 & 106 23 0.0 24 LGTS EMERGENCY 1

1 LGTS 107, 108, 109, & 110 25 0.5 26 L 0.5 3/4" #12 #12 #12 LGTS 118,118A,118B,119A, 119B 1 20

20 1 LGTS 102, 103, 120, 121, &121A #12 #12 #12 3/4" 0.7 L 27 0.7 28 SPARE 1 20

25 1 AHU #1 HEAT EX. 29 0.0 30 RESTROOM AUTO FLUSH 1

20 3 AHU #1

31 0.0 32 FUTURE COMM CLOSET 1

33 0.0 34

LGTS EXTERIOR 235 0.0 36

3 SPARE

37 0.0 38

C.U. #1 EXTERIOR 3 5039 0.0 40

41 0.0 42

TOTAL 0.70 0.79 0.00 TOTAL CONNECTED LOAD 1.49 KVA

DEMAND KVA

R RECEPTACLE<10KW 100% 0.0 DEMAND 5.17 AMPS

R RECEPTACLE >10KW 50% 0.0

L LIGHTS 125% 1.9

G GENERAL EQUIPMENT 100% 0.0 NOTES: 1 NEW CIRCUITS NOTED IN BOLD TEXT.

H HEATER 125% 0.0

M MOTORS LESS LARGEST 100% 0.0 2 EXISTING CIRCUIT INFORMATION BASED ON PHASE 1 DESIGN

DOCUMENTATION. UNCLEAR OR CONFLICTING INFORMATION LEFT BLANK;

FIELD VERIFY.

M LARGEST MOTOR 125% 0.0

TOTAL 1.9

PANEL NAME LP

TYPE MLO 175 AMP MECH/ELEC RM - 112

VOLTAGE 208/120VAC MINIMUM AIC RATING 10 KA FED FROM: PANEL…

This is the start of the file's text. The full file is on GovTribe.