Attachment 4 Drawings.pdf
PDF 9 MB Posted
- Solicitation number
- 1232SA25R0038
About this file
These engineering design documents detail the cooling tower replacement project for the National Agricultural Library (NAL) located in Beltsville, Maryland. The 30-page set of technical drawings, prepared by Summer Consultants Incorporated on July 11, 2024, comprehensively illustrates the mechanical, electrical, structural, and site planning aspects of replacing two existing cooling towers. The drawings specify replacement of the cooling towers with two new cross-flow, two-cell cooling towers, each capable of cooling 1,000 gallons per minute from 95°F to 83°F, featuring 30 HP premium efficiency motors, variable frequency drives, electronic water level controllers, basin heaters, and integrated building automation system controls.
Key technical details include vibration isolation framing, detailed piping and electrical connection specifications, demolition plans for existing infrastructure, temporary cooling tower provisions, and comprehensive schedules for equipment, panels, and electrical systems. The project involves removing existing cooling tower infrastructure, installing new structural supports, providing new condenser water pumps, implementing a basin filtration skid, and integrating new control systems. The drawings indicate careful consideration of mechanical integration, electrical requirements, lightning protection, and site logistics, with professional engineering certification by a Maryland-licensed professional engineer.
View the file
Other files
Show all 14
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
7/1 1/2
4 9
:45 :25
A M
2.0
G
-0
.D W
G
G-001COVER SHEET
FI
LE
N
AM
E:
OU
R
RE
F:
PL
OT
D
AT
E:
2.0
NATIONAL AGRICULTURAL LIBRARY COOLING TOWER
REPLACEMENT
7900 Westpark Dr. | Suite A405 | McLean, VA 22102
(703) 556-8820 | www.summerconsultants.com
SUMMER
CONSULTANTS
I N C O R P O R A T E D
BELTSVILLE, MARYLAND
11 JULY 2024
SEE LOCATION MAP
LOCATION OF WORK
N
N
N
JURAN, A.
BENZEL, L.
HYMANSON, J.
JURAN, A.
Sheet Number Sheet Title
G-001 COVER SHEET
S-001 STRUCTURAL NOTES, ABBREVIATIONS, AND LEGEND
S-401 COOLING TOWER FRAMING PLAN
S-402 COOLING TOWER VIBRATION ISOLATION FRAME
S-502 SECTIONS & DETAILS
M-001 SYMBOLS & ABBREVIATIONS
MS101T SITE PLAN - TEMPORARY
M-101 BASEMENT - MECHANICAL
M-102 LOWER ROOF & PENTHOUSE - MECHANICAL
MD401 BASEMENT - MECHANICAL DEMOLITION
MD402 LOWER ROOF & PENTHOUSE - MECHANICAL DEMOLITION
M-401T BASEMENT - MECHANICAL TEMPORARY
M-401 BASEMENT - MECHANICAL
M-402 LOWER ROOF & PENTHOUSE - MECHANICAL
M-403 DETAILS
M-601 SCHEDULES
M-700 CONTROLS COVER SHEET
M-701 CONTROLS
M-702 COOLING TOWER POINT LIST
E-001 SYMBOLS & ABBREVIATIONS
ED401 BASEMENT - ELECTRICAL DEMOLITION
ED402 LOWER ROOF & PENTHOUSE - ELECTRICAL DEMOLITION
E-401 BASEMENT - ELECTRICAL
E-401T TEMPORARY COOLING TOWER
E-402 LOWER ROOF & PENTHOUSE - ELECTRICAL
E-501 LIGHTNING PROTECTION DETAIL
E-601 PANEL SCHEDULES
E-602 PANEL SCHEDULES
E-603 SWITCHGEAR SCHEDULE
E-701 RISER DIAGRAM
HAZARDOUS MATERIALS SUMMARY
NO ASBESTOS CONTAINING MATERIAL WAS IDENTIFIED
PAINT WITH LEAD CONCENTRATIONS LESS THAN 0.7 MG/CM2 COVER
ALL SURFACES NOT IDENTIFIED AS LEAD BASED PAINT.
FIBERGLASS PIPE INSULATION, PAINTED
METAL PIPES
METAL COVER PLATE
METAL CHILLER COMPRESSORS
METAL PIPE SUPPORTS
CONCRETE WALL BLOCK
METAL MOUNT
METAL VALVE
METAL COOLING TOWER HOUSING
CONCRETE PLATFORM
METAL PUMP
METAL COOLING TOWER STAND
METAL SWITCH
PROFESSIONAL CERTIFICATION. I HEREBY
CERTIFY THAT THESE DOCUMENTS WERE
PREPARED OR APPROVED BY ME, AND
THAT I AM A DULY LICENSED
PROFESSIONAL ENGINEER UNDER THE
LAWS OF THE STATE OF MARYLAND,
LICENSE NO. 38731, WITH EXPIRATION DATE
OF 05/16/2026.
AutoCAD SHX Text
SAFETY & HEALTH
AutoCAD SHX Text
DESIGNER
AutoCAD SHX Text
CHECKED BY
AutoCAD SHX Text
PROJECT MANAGER
AutoCAD SHX Text
PPM
AutoCAD SHX Text
EPM
AutoCAD SHX Text
A-E FIRM
AutoCAD SHX Text
AutoCAD SHX Text
SOLICITATION NO.
AutoCAD SHX Text
DATE
AutoCAD SHX Text A
AutoCAD SHX Text D
AutoCAD SHX Text
USDA
AutoCAD SHX Text S
AutoCAD SHX Text U
AutoCAD SHX Text
NO.
AutoCAD SHX Text
DATE
AutoCAD SHX Text
BY
AutoCAD SHX Text
DWG. NO.
AutoCAD SHX Text Service
AutoCAD SHX Text Research
AutoCAD SHX Text Agricultural
AutoCAD SHX Text
REVISIONS
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
DRAWN BY
AutoCAD SHX Text
SHEET OF
AutoCAD SHX Text
REAL PROPERTY
AutoCAD SHX Text
VICINITY MAP
AutoCAD SHX Text
LOCATION MAP
AutoCAD SHX Text
SITE KEY PLAN
AutoCAD SHX Text
NOTICES
AutoCAD SHX Text
INDEX OF DRAWINGS
AutoCAD SHX Text
AGRICULTURAL RESEARCH SERVICE
AutoCAD SHX Text
FACILITIES DIVISION, BELTSVILLE, MARYLAND
AutoCAD SHX Text
NATIONAL AGRICULTURAL LIBRARY COOLING TOWER REPLACEMENT
AutoCAD SHX Text
U.S. DEPARTMENT OF AGRICULTURE
AutoCAD SHX Text
CWS
(E)
LC
ABBREVIATIONS CONT. SYMBOLS CONT. SYMBOLS CONT. GENERAL SYMBOLS
ABBREVIATIONS
SYMBOLS
R
PRIMARY CHILLED WATER RETURNPCWR
PCWS PRIMARY CHILLED WATER SUPPLY
RL
RS
SCWR
SCWS
SP SPRINKLER PIPING
PIPE TURN UP
PIPE TURN DOWN
CONCENTRIC PIPE REDUCER
ECCENTRIC PIPE REDUCER
DIRECTION OF FLOW
PIPE CAP
PIPE CLEANOUT
WALL PIPE CLEANOUT
FLOOR CLEANOUT
FLOOR DRAIN
C.O.
W.C.O.
F.C.O.
FL.D.
DOUBLE LINE PIPE TURN UP
DOUBLE LINE PIPE TURN DOWN
FORGED BRANCH PIPE FITTING
PROVIDE FULL LUG BUTTERFLY
ISOLATION VALVES
PROVIDE MOTORIZED, FULL LUG
BUTTERFLY ISOLATION VALVES
PIPE CAP
PROVIDE OS&Y
ISOLATION VALVES
GATE VALVE
GLOBE VALVE
SWING CHECK VALVE
TWO-WAY CONTROL VALVE
THREE-WAY CONTROL VALVE
STRAINER
UNION
PRESSURE REDUCING VALVE
SAFETY RELIEF VALVE
O.S.&Y VALVE
MOTORIZED O.S.&Y VALVE
FLOW MEASURING VALVE
COMBINATION FLOW MEASURING
AND BALANCING VALVE
BALANCING VALVE
BALL VALVE
BUTTERFLY VALVE
MOTORIZED BUTTERFLY VALVE
BACKFLOW PREVENTER
MANUAL AIR VENT 3/8" BALL VALVEM.A.V.
THERMOMETER AND WELL
PRESSURE GAUGE
FLEXIBLE PIPING CONNECTION
PIPE EXPANSION JOINT
FLEXIBLE DUCTWORK. 5 FEET MAXIMUM
LENGTH, SIZE AS INDICATED OR SCHEDULED
CENTRIFUGAL FAN OR
PUMP BY APPLICATION
DOOR LOUVER
3/4" DOOR UNDERCUT
RETURN AIR SYMBOL
NUMBER INDICATES CFM
SUPPLY AIR SYMBOL
NUMBER INDICATES CFM
THERMOSTAT
U
L
HUMIDITY SENSOR
COMPRESSED AIR PIPINGA
BBD BOILER BLOWDOWN
BFS BOILER FEEDWATER SUCTION
BOILER FEEDWATERBFW
BFWA BOILER FEEDWATER AUXILIARY
C CONDENSER WATER SUPPLY
CHILLED GLYCOL RETURN
(30% PROPYLENE GLYCOL)CGR
CGS (30% PROPYLENE GLYCOL)
CONDENSER WATER RETURNCR
DOMESTIC COLD WATERCW
CWR CHILLED WATER RETURN
CHILLED WATER SUPPLY
CONDENSATE DRAIND
FIRE LINE PIPINGF
FOR FUEL/OIL RETURN
FUEL/OIL SUPPLYFOS
G GAS PIPING
DUAL TEMPERATURE WATER RETURNHCR
DUAL TEMPERATURE WATER SUPPLYHCS
HPR HIGH PRESSURE STEAM RETURN
(CONDENSATE)
HPS HIGH PRESSURE STEAM SUPPLY
(ABOVE 50 PSIG)
HTWR HIGH TEMP. HOT WATER RETURN
HIGH TEMP. HOT WATER SUPPLYHTWS
HW DOMESTIC HOT WATER
HWC HOT WATER CIRCULATING
HWR HEATING WATER RETURN
HEATING WATER SUPPLYHWS
LOW PRESSURE STEAM RETURN
(CONDENSATE)LPR
LOW PRESSURE STEAM SUPPLY
(LESS THAN 15 PSIG)LPS
MPR MEDIUM PRESSURE STEAM RETURN
(CONDENSATE)
MPS MEDIUM PRESSURE STEAM SUPPLY
(BETWEEN 15 & 50 PSIG)
MAKE-UP WATERMU
PC PUMPED CONDENSATE
PUMPED CONDENSATE RETURNPCR
NORTH ARROW
COLUMN BUBBLE
DESIGNATION
REVISION CLOUD WITH REVISION
NUMBER DESIGNATION
BREAKLINE
MATCHLINE DESIGNATIONM A T C H L I N E A-A
DEMOLITION LINETYPE
CENTERLINE
CENTERLINE SYMBOL
EXISTING
POINT OF CONNECTION TO EXISTING
POINT OF TERMINATION OF REMOVAL
NOTE NUMBER
T
H
M
CHILLED GLYCOL SUPPLY
M
M
GAL. GALLON
GPM GALLONS PER MINUTE
H.C. HEATING COIL
HP HORSEPOWER
HW DOMESTIC HOT WATER
HWR HEATING WATER RETURN
HWS HEATING WATER SUPPLY
HX HEAT EXCHANGER
Hz HERTZ
IN. INCHES
JC JANITORS CLOSET
L.A.T. LEAVING AIR TEMPERATURE
LBS. POUNDS
LBS./HR POUNDS PER HOUR
L.D.B. LEAVING DRY BULB
L.W.T. LEAVING WATER TEMPERATURE
MAX. MAXIMUM
M.B.D. MANUAL BALANCING DAMPER
MER MECHANICAL EQUIPMENT ROOM
MIN. MINIMUM
M.O.D. MOTOR OPERATED DAMPER
NC NOISE CRITERIA
N.C. NORMALLY CLOSED
N.I.C. NOT IN CONTRACT
N.O. NORMALLY OPEN
O.A. OUTSIDE AIR
O.C. ON CENTER
O.S.D. OPEN SITE DRAIN
O.F.D OVERFLOW DRAIN
P.D. PRESSURE DROP
PDWS PRESSURIZED DEIONIZED WATER SUPPLY
PH PHASE
PRV PRESSURE RELIEF VALVE
PSI POUNDS PER SQUARE INCH
PSIG POUNDS PER SQUARE INCH GAUGE
PVC POLYVINYL CHLORIDE
R.A. RETURN AIR
R.G. RETURN GRILLE
RHG REFRIGERANT HOT GAS
RL REFRIGERANT LIQUID
RLA RUNNING LOAD AMPS
RPM REVOLUTIONS PER MINUTE
S.A. SUPPLY AIR
SD SMOKE DETECTOR
S.P. STATIC PRESSURE
S.S. STAINLESS STEEL
T.G. TOP GRILLE
T.O.C. TOP OF CONCRETE
T.O.G. TOP OF GRADE
T.O.S. TOP OF STEEL
T.R. TOP REGISTER
TYP. TYPICAL
UH UNIT HEATER
V VOLTS
VAV VARIABLE AIR VOLUME
VOL. VOLUME
W.B. WET BULB
W.C. WATERCOLUMN
W.G. WATER GAUGE
MECHANICAL PIPE
RISER DESIGNATION
RISER NUMBER
ARROW INDICATES
TRUE NORTH AND/OR
PROJECT NORTH
N
M101
N
8'0 1/8"=1'-0"
UNIQUE PLAN OR
DETAIL NUMBER
ON THIS DRAWING NORTH ARROW
NAME OF PLAN OR DETAIL
ALL DRAWINGS WHERE
DETAIL IS REFERENCED
GRAPHIC SCALE OF
PLAN OR DETAIL
SECTION IDENTIFICATION
INDICATES DIRECTION
OF CUTTING PLANE
NUMBER INDICATES SECTION
SHEET NUMBER WHERE
SECTION IS DRAWN
2-PART REFERENCE DETAIL IDENTIFICATION:
SHEET NUMBER WHERE
DETAIL/SECTION IS DRAWN
NUMBER INDICATES
DETAIL/SECTION
FLOOR PLAN
M101, M1022
FLOOR PLAN AND DETAIL TITLES:
M101
SECONDARY CHILLED WATER RETURN
SECONDARY CHILLED WATER SUPPLY
REFRIGERANT LIQUID
REFRIGERANT SUCTION
ROOM NUMBER DESIGNATION.1234
A.D. ACCESS DOOR
A.F.F. ABOVE FINISHED FLOOR
AHU AIR HANDLING UNIT
ARCH. ARCHITECTURAL
A.P. ACCESS PANEL
APPROX. APPROXIMATELY
BHP BRAKE HORSEPOWER
BTU BRITISH THERMAL UNITS
BTUH BRITISH THERMAL UNITS PER HOUR
C COMMON
C.C. COOLING COIL
C.D. CEILING DIFFUSER
CFM CUBIC FEET PER MINUTE
C.G. CEILING GRILLE
CGR CHILLED GLYCOL RETURN
CGS CHILLED GLYCOL SUPPLY
C.O. CLEANOUT
C.R. CEILING REGISTER
CW DOMESTIC COLD WATER
D.B. DRY BULB
db DECIBEL
DDC DIRECT DIGITAL CONTROL
DESIG. DESIGNATION
DIA DIAMETER
DN. DOWN
(E) EXISTING
E.A.T. ENTERING AIR TEMPERATURE
E.D.B. ENTERING DRY BULB
EFF. EFFICIENCY
E.G. EXHAUST GRILLE
ELEV. ELEVATION/ELEVATOR
ENT. ENTERING
E.S.P. EXTERNAL STATIC PRESSURE
E.W.B. ENTERING WET BULB
E.W.T. ENTERING WATER TEMPERATURE
EXIST. EXISTING
°F DEGREES FAHRENHEIT
FCU FAN COIL UNIT
F.D. FIRE DAMPER
FLA FULL LOAD AMPS
FL.D. FLOOR DRAIN
FLR. FLOOR
FPM FEET PER MINUTE
FT. FEET
F.V. FACE VELOCITY
PROJECT SEQUENCING
1.1. PERMANENT TOWERS MUST BE IN OPERATION DURING PERIOD: JUNE 1 -
AUGUST 30.
1.2. PROVIDE TEMPORARY PIPING CONNECTION PER DRAWING M-401T.
1.3. PROVIDE "HEAVY DUTY CONSTRUCTION MAT" FOR TEMPORARY COOLING
TOWER AND VEHICLE ACCESS. SEE DRAWING MS101T.
1.4. PROVIDE TEMPORARY COOLING TOWER PER SCHEDULE ON M-601 FOR
THE DURATION OF CONSTRUCTION.
1.5. COOLING TOWER MUST BE LOCATED 25' FROM AIR INTAKES AND
OPERABLE WINDOWS PER ASHRAE STANDARD 62.1.
1.6. DO NOT BEGIN DEMOLITION OF COOLING TOWERS UNTIL TEMPORARY
COOLING TOWERS ARE OPERATIONAL AND CONTRACTING OFFICER HAS
APPROVED.
1.7. TEMPORARY COOLING TOWERS CAN OPERATE WITH EXISTING PUMPS
OR PUMPS PROVIDED UNDER THIS CONTRACT. TAB PUMPS WITH
INSTALLATION OF TEMPORARY COOLING TOWER. BALANCE FLOW TO
1,200 GPM.
1.8. TEMPORARY COOLING TOWERS MUST REMAIN ON SITE UNTIL THE
PERMANENT COOLING TOWERS HAVE BEEN FULLY COMMISSIONED AND
14 DAYS OF TREND DATA ON THE CHILLER PLANT HAVE BEEN REVIEWED
AND APPROVED BY THE GOVERNMENT. ALLOW ONE WEEK FOR TREND
REVIEW.
1.9. PROCURE ALL PERMITS AND ROAD CLOSURES TO PERFORM WORK FOR
CRANE.
FREIGHT ELEVATOR: SEE DRAWING M-101 FOR LOCATION.
4500 POUND CAPACITY.
CABIN DIMENSIONS 8'-8"L x 5'-10"D x 7'-0"H CABIN DOORS: 6'-1"W x 7'-0"H
FREIGHT ELEVATOR GOES FROM MECHANICAL BASEMENT TO 14TH FLOOR.
EXISTING 70"x 52" HATCH TO LIFT ITEMS FROM 14TH FLOOR TO THE PENTHOUSE.
OUTAGES
ELECTRICAL OUTAGES - 3 HOURS MAX ON MCC. SEE DRAWING E-601 AND E-602
FOR MCCs AND EQUIPMENT IMPACTED FROM SHUTDOWNS:
OUTAGE ON MCC 6-CH TO CONNECT TEMPORARY COOLING TOWER.
OUTAGE ON MCC 5A TO DEMOLISH AND CONNECT COOLING TOWER MOTORS.
MECHANICAL OUTAGES - 8-HOUR MAX FOR CHILLER PLANT OUTAGE:
OUTAGE ON CHILLED WATER PLANT FOR TEMPORARY PIPING CONNECTIONS
AND TEMPORARY COOLING TOWER. FREEZING OR OTHER ACCEPTABLE
MEANS TO ENSURE THAT THE OUTAGE IS LIMITED TO NO MORE THAN 8
HOURS.
7/1 1/2
4 9
:45 :32
A M
2.0
M
-0
.D W
G
M-001SYMBOLS & ABBREVIATIONS
FI
LE
N
RE
F:
PL
OT
D
AT
E:
2.0
NATIONAL AGRICULTURAL LIBRARY COOLING TOWER
REPLACEMENT
7900 Westpark Dr. | Suite A405 | McLean, VA 22102
(703) 556-8820 | www.summerconsultants.com
SUMMER
CONSULTANTS
I N C O R P O R A T E D
BELTSVILLE, MARYLAND
11 JULY 2024
PROFESSIONAL CERTIFICATION. I HEREBY
CERTIFY THAT THESE DOCUMENTS WERE
PREPARED OR APPROVED BY ME, AND
THAT I AM A DULY LICENSED
PROFESSIONAL ENGINEER UNDER THE
LAWS OF THE STATE OF MARYLAND,
LICENSE NO. 38731, WITH EXPIRATION DATE
OF 05/16/2026.
JURAN, A.
BENZEL, L.
HYMANSON, J.
JURAN, A.
HANGER LOCATION
AutoCAD SHX Text
SAFETY & HEALTH
AutoCAD SHX Text
DESIGNER
AutoCAD SHX Text
CHECKED BY
AutoCAD SHX Text
PROJECT MANAGER
AutoCAD SHX Text
PPM
AutoCAD SHX Text
EPM
AutoCAD SHX Text
A-E FIRM
AutoCAD SHX Text
AutoCAD SHX Text
SOLICITATION NO.
AutoCAD SHX Text
DATE
AutoCAD SHX Text A
AutoCAD SHX Text D
AutoCAD SHX Text
USDA
AutoCAD SHX Text S
AutoCAD SHX Text U
AutoCAD SHX Text
NO.
AutoCAD SHX Text
DATE
AutoCAD SHX Text
BY
AutoCAD SHX Text
DWG. NO.
AutoCAD SHX Text Service
AutoCAD SHX Text Research
AutoCAD SHX Text Agricultural
AutoCAD SHX Text
REVISIONS
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
DRAWN BY
AutoCAD SHX Text
SHEET OF
AutoCAD SHX Text
REAL PROPERTY
EQUIPMENT PAD
M-401T
(E)TREE
(E)TREE
(E)TREE
(E)HEDGES
(E)TREE
(E)TREE (E)TREE
(E)TREE
(E)GARDEN
(E)TREE
(E)TREE
(E)TREE
(E)TREE
(E)TREE
(E)TREE
(E)TREE
(E)GARDEN
(E)TREE
(E)TREE (E)TREE
7/1 1/2
4 9
:45 :38
A M
2.0
M
S1
T.
DW
G
MS101TSITE PLAN - TEMPORARY
FI
LE
N
RE
F:
PL
OT
D
AT
E:
2.0
NATIONAL AGRICULTURAL LIBRARY COOLING TOWER
REPLACEMENT
7900 Westpark Dr. | Suite A405 | McLean, VA 22102
(703) 556-8820 | www.summerconsultants.com
SUMMER
CONSULTANTS
I N C O R P O R A T E D
BELTSVILLE, MARYLAND
11 JULY 2024
PROFESSIONAL CERTIFICATION. I HEREBY
CERTIFY THAT THESE DOCUMENTS WERE
PREPARED OR APPROVED BY ME, AND
THAT I AM A DULY LICENSED
PROFESSIONAL ENGINEER UNDER THE
LAWS OF THE STATE OF MARYLAND,
LICENSE NO. 38731, WITH EXPIRATION DATE
OF 05/16/2026.
JURAN, A.
BENZEL, L.
HYMANSON, J.
JURAN, A.
GENERAL NOTES
G1. VERIFY LOCATION AND DIMENSIONS OF EXISTING
EQUIPMENT AND COORDINATE ALL WORK PRIOR TO THE
START OF CONSTRUCTION.
G2. ALL WORK SHALL BE NEW AND PROVIDED UNDER THIS
CONTRACT UNLESS SPECIFICALLY MARKED "EXISTING",
"EXIST", OR "(E)".
NOTES
1. PROVIDE DRIVEABLE SURFACE, SUCH AS HEAVY DUTY
CONSTRUCTION MAT, FROM DRIVEWAY TO
TEMPORARY COOLING TOWER LOCATION FOR
DURATION OF TEMPORARY TOWER USAGE. SURFACE
MUST BE RATED FOR VEHICLE AND COOLING TOWER
WEIGHT.
2. RESTORE LANDSCAPING IN IMPACTED AREAS FROM
TEMPORARY CONDITIONS AND RIGGING.
3. DEMOLISH WALKING PATH RAILING BETWEEN POINTS
INDICATED. ONCE TEMPORARY COOLING TOWERS
REMOVED, PROVIDE METAL TUBE, HAND RAILING AND
PAINT TO MATCH EXISTING CONDITIONS.
N
0 32' 64' 1/32"=1'-0"
SITE PLAN - TEMPORARY
AutoCAD SHX Text
SAFETY & HEALTH
AutoCAD SHX Text
DESIGNER
AutoCAD SHX Text
CHECKED BY
AutoCAD SHX Text
PROJECT MANAGER
AutoCAD SHX Text
PPM
AutoCAD SHX Text
EPM
AutoCAD SHX Text
A-E FIRM
AutoCAD SHX Text
AutoCAD SHX Text
SOLICITATION NO.
AutoCAD SHX Text
DATE
AutoCAD SHX Text A
AutoCAD SHX Text D
AutoCAD SHX Text
USDA
AutoCAD SHX Text S
AutoCAD SHX Text U
AutoCAD SHX Text
NO.
AutoCAD SHX Text
DATE
AutoCAD SHX Text
BY
AutoCAD SHX Text
DWG. NO.
AutoCAD SHX Text Service
AutoCAD SHX Text Research
AutoCAD SHX Text Agricultural
AutoCAD SHX Text
REVISIONS
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
DRAWN BY
AutoCAD SHX Text
SHEET OF
AutoCAD SHX Text
REAL PROPERTY
5 4
9 8 7 6
3 2 1
A
B
C
D
121314151617
A
B
C
D
17 16 15 14 13 12
E
3 2 1
F
G
J
K
L
M
F
G
H
J
K
L
M
9 8 7 61011 5 4
P P
E
N
H
UP
MD401
M-401
ED401
E-401
7/1 1/2
4 9
:45 :45
A M
2.0
M
-1
.D W
G
M-101BASEMENT - MECHANICAL
FI
LE
N
RE
F:
PL
OT
D
AT
E:
2.0
NATIONAL AGRICULTURAL LIBRARY COOLING TOWER
REPLACEMENT
7900 Westpark Dr. | Suite A405 | McLean, VA 22102
(703) 556-8820 | www.summerconsultants.com
SUMMER
CONSULTANTS
I N C O R P O R A T E D
BELTSVILLE, MARYLAND
11 JULY 2024
PROFESSIONAL CERTIFICATION. I HEREBY
CERTIFY THAT THESE DOCUMENTS WERE
PREPARED OR APPROVED BY ME, AND
THAT I AM A DULY LICENSED
PROFESSIONAL ENGINEER UNDER THE
LAWS OF THE STATE OF MARYLAND,
LICENSE NO. 38731, WITH EXPIRATION DATE
OF 05/16/2026.
N
32'0 16' 1/16"=1'-0"
BASEMENT - MECHANICAL
JURAN, A.
BENZEL, L.
HYMANSON, J.
JURAN, A.
GENERAL NOTES
G1. VERIFY LOCATION AND DIMENSIONS OF EXISTING EQUIPMENT AND
COORDINATE ALL WORK PRIOR TO THE START OF CONSTRUCTION.
NOTES
1. FREIGHT ELEVATOR. SEE M-001 PROJECT SEQUENCING FOR DETAILS.
AutoCAD SHX Text
SAFETY & HEALTH
AutoCAD SHX Text
DESIGNER
AutoCAD SHX Text
CHECKED BY
AutoCAD SHX Text
PROJECT MANAGER
AutoCAD SHX Text
PPM
AutoCAD SHX Text
EPM
AutoCAD SHX Text
A-E FIRM
AutoCAD SHX Text
AutoCAD SHX Text
SOLICITATION NO.
AutoCAD SHX Text
DATE
AutoCAD SHX Text A
AutoCAD SHX Text D
AutoCAD SHX Text
USDA
AutoCAD SHX Text S
AutoCAD SHX Text U
AutoCAD SHX Text
NO.
AutoCAD SHX Text
DATE
AutoCAD SHX Text
BY
AutoCAD SHX Text
DWG. NO.
AutoCAD SHX Text Service
AutoCAD SHX Text Research
AutoCAD SHX Text Agricultural
AutoCAD SHX Text
REVISIONS
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
DRAWN BY
AutoCAD SHX Text
SHEET OF
AutoCAD SHX Text
REAL PROPERTY
DN.
STAIR NO. 4
ELEV. 3
ELEV. 2
STAIR NO. 2
ELEV. 4
ELEV. 1
5 4
9 8 7 6
3 2 1
A
B
C
D
121314151617
A
B
C
D
17 16 15 14 13 12
E
3 2 1
F
G
H
J
K
L
M
N
F
G
H
J
K
L
M
9 8 7 6
1011 5 4
P P
E
MD402
1,2
M-402
7/1 1/2
4 9
:45 :52
A M
2.0
M
-1
.D W
G
M-102LOWER ROOF & PENTHOUSE -
MECHANICAL
FI
LE
N
RE
F:
PL
OT
D
AT
E:
2.0
NATIONAL AGRICULTURAL LIBRARY COOLING TOWER
REPLACEMENT
7900 Westpark Dr. | Suite A405 | McLean, VA 22102
(703) 556-8820 | www.summerconsultants.com
SUMMER
CONSULTANTS
I N C O R P O R A T E D
BELTSVILLE, MARYLAND
11 JULY 2024
PROFESSIONAL CERTIFICATION. I HEREBY
CERTIFY THAT THESE DOCUMENTS WERE
PREPARED OR APPROVED BY ME, AND
THAT I AM A DULY LICENSED
PROFESSIONAL ENGINEER UNDER THE
LAWS OF THE STATE OF MARYLAND,
LICENSE NO. 38731, WITH EXPIRATION DATE
OF 05/16/2026.
GENERAL NOTES
G1. VERIFY LOCATION AND DIMENSIONS OF EXISTING
EQUIPMENT AND COORDINATE ALL WORK PRIOR TO THE
START OF CONSTRUCTION.
N
32'0 16' 1/16"=1'-0"
LOWER ROOF & PENTHOUSE - MECHANICAL
JURAN, A.
BENZEL, L.
HYMANSON, J.
JURAN, A.
AutoCAD SHX Text
SAFETY & HEALTH
AutoCAD SHX Text
DESIGNER
AutoCAD SHX Text
CHECKED BY
AutoCAD SHX Text
PROJECT MANAGER
AutoCAD SHX Text
PPM
AutoCAD SHX Text
EPM
AutoCAD SHX Text
A-E FIRM
AutoCAD SHX Text
AutoCAD SHX Text
SOLICITATION NO.
AutoCAD SHX Text
DATE
AutoCAD SHX Text A
AutoCAD SHX Text D
AutoCAD SHX Text
USDA
AutoCAD SHX Text S
AutoCAD SHX Text U
AutoCAD SHX Text
NO.
AutoCAD SHX Text
DATE
AutoCAD SHX Text
BY
AutoCAD SHX Text
DWG. NO.
AutoCAD SHX Text Service
AutoCAD SHX Text Research
AutoCAD SHX Text Agricultural
AutoCAD SHX Text
REVISIONS
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
DRAWN BY
AutoCAD SHX Text
SHEET OF
AutoCAD SHX Text
REAL PROPERTY
UP
FAN ROOM
BOILER ROOM
AREAWAY
(E)CH-1
STAIR NO. 2
BOOK
CONVEYOR
PIT
(E)FL.D.
(E)6"CWR
(E)HX
(E)6"CS
(E)6"CR
(E)10"CR
(E)10"CS
(E)8"CR
(E)8"CS
(E)8"CS
(E )M
CC
-1
23 23 23
CWP-11 CWP-31
CWP-21
(E)CHP1D
(E)CHP-2(E)CHP-3(E)CHP-1
(E)CWP2D
(E)10"CR UP TO CT
(E)10"CS UP TO CT
(E)CH-2
(E)MCC-6
(E)8"CS
(E)8"CR
(E)
(E)
(E)V-4
M
(E)8"CR
(E)10"CR
(E)OPENING IN GRATING
(E)FL.D.
(E)FL.D.
(E)FL.D.
(E)PAD
(E)PAD(E)PAD
J
K
9 8 71011
7/1 1/2
4 9
:45 :59
A M
2.0
M
D4
.D W
G
MD401BASEMENT - MECHANICAL
DEMOLITION
FI
LE
N
RE
F:
PL
OT
D
AT
E:
2.0
NATIONAL AGRICULTURAL LIBRARY COOLING TOWER
REPLACEMENT
7900 Westpark Dr. | Suite A405 | McLean, VA 22102
(703) 556-8820 | www.summerconsultants.com
SUMMER
CONSULTANTS
I N C O R P O R A T E D
BELTSVILLE, MARYLAND
11 JULY 2024
PROFESSIONAL CERTIFICATION. I HEREBY
CERTIFY THAT THESE DOCUMENTS WERE
PREPARED OR APPROVED BY ME, AND
THAT I AM A DULY LICENSED
PROFESSIONAL ENGINEER UNDER THE
LAWS OF THE STATE OF MARYLAND,
LICENSE NO. 38731, WITH EXPIRATION DATE
OF 05/16/2026.
JURAN, A.
BENZEL, L.
HYMANSON, J.
JURAN, A.
N
8'0 4' 1/4"=1'-0"
BASEMENT - MECHANICAL DEMOLITION
M-1011
GENERAL NOTES
G1. VERIFY LOCATION AND DIMENSIONS OF EXISTING
EQUIPMENT AND COORDINATE ALL WORK PRIOR TO THE
START OF CONSTRUCTION.
NOTES
1. DEMOLISH EQUIPMENT, ASSOCIATED SUPPORTS,
CONTROLS WIRING, INSULATION, AND ALL
APPURTENANCES COMPLETE.
2. DEMOLISH PIPING, INSULATION, HANGERS, AND ALL
APPURTENANCES COMPLETE. SEE DETAIL 1, M-601.
3. (E)SHUTOFF VALVE IN VERTICAL.
N
AutoCAD SHX Text
SAFETY & HEALTH
AutoCAD SHX Text
DESIGNER
AutoCAD SHX Text
CHECKED BY
AutoCAD SHX Text
PROJECT MANAGER
AutoCAD SHX Text
PPM
AutoCAD SHX Text
EPM
AutoCAD SHX Text
A-E FIRM
AutoCAD SHX Text
AutoCAD SHX Text
SOLICITATION NO.
AutoCAD SHX Text
DATE
AutoCAD SHX Text A
AutoCAD SHX Text D
AutoCAD SHX Text
USDA
AutoCAD SHX Text S
AutoCAD SHX Text U
AutoCAD SHX Text
NO.
AutoCAD SHX Text
DATE
AutoCAD SHX Text
BY
AutoCAD SHX Text
DWG. NO.
AutoCAD SHX Text Service
AutoCAD SHX Text Research
AutoCAD SHX Text Agricultural
AutoCAD SHX Text
REVISIONS
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
DRAWN BY
AutoCAD SHX Text
SHEET OF
AutoCAD SHX Text
REAL PROPERTY
AutoCAD SHX Text
SITE KEY PLAN
2"D
2"D
CT-1
(E)R.D.
3"CS
2"D2"D
3"CS
2-1/2"CW
2 2-1/2"CW
2"D2
2 10"CS & 10"CR
(E)10"CR DN. TO
BASEMENT
(E)10"CS DN. TO
BASEMENT
2 10"CR
10"CS2
2 10"CS
10"CR2
2 3"CS
(E)2-1/2"CW
TO MAIN
(E)FLOW METER &
BACK-FLOW PREVENTER
FILTRATION PUMP
FILTRATION SYSTEM
(E)3"FL.D. WITH 12"FUNNEL
2 2"CS
2"CSABANDONED
FILTRATION SKID
1 3
(E)R.D.(E)R.D.
(E)WATER TREATMENT
9 8 7 610
G
J
7/1 1/2
4 9
:46 :07
A M
2.0
M
D4
.D W
G
MD402LOWER ROOF & PENTHOUSE -
MECHANICAL DEMOLITION
FI
LE
N
RE
F:
PL
OT
D
AT
E:
2.0
NATIONAL AGRICULTURAL LIBRARY COOLING TOWER
REPLACEMENT
7900 Westpark Dr. | Suite A405 | McLean, VA 22102
(703) 556-8820 | www.summerconsultants.com
SUMMER
CONSULTANTS
I N C O R P O R A T E D
BELTSVILLE, MARYLAND
11 JULY 2024
PROFESSIONAL CERTIFICATION. I HEREBY
CERTIFY THAT THESE DOCUMENTS WERE
PREPARED OR APPROVED BY ME, AND
THAT I AM A DULY LICENSED
PROFESSIONAL ENGINEER UNDER THE
LAWS OF THE STATE OF MARYLAND,
LICENSE NO. 38731, WITH EXPIRATION DATE
OF 05/16/2026.
GENERAL NOTES
G1. VERIFY LOCATION AND DIMENSIONS OF EXISTING
EQUIPMENT AND COORDINATE ALL WORK PRIOR TO THE
START OF CONSTRUCTION.
JURAN, A.
BENZEL, L.
HYMANSON, J.
JURAN, A.
N
1. DEMOLISH EQUIPMENT, ASSOCIATED SUPPORTS,
CONTROLS WIRING, INSULATION, AND ALL
APPURTENANCES COMPLETE.
2. DEMOLISH PIPING, INSULATION, HANGERS, AND ALL
APPURTENANCES COMPLETE BETWEEN POINTS
INDICATED.
3. EQUIPMENT HAS ALREADY BEEN DISCONNECTED
FROM POWER.
NOTES
N
8'0 4' 1/4"=1'-0"
LOWER ROOF & PENTHOUSE - MECHANICAL DEMOLITION
M-1021
AutoCAD SHX Text
SAFETY & HEALTH
AutoCAD SHX Text
DESIGNER
AutoCAD SHX Text
CHECKED BY
AutoCAD SHX Text
PROJECT MANAGER
AutoCAD SHX Text
PPM
AutoCAD SHX Text
EPM
AutoCAD SHX Text
A-E FIRM
AutoCAD SHX Text
AutoCAD SHX Text
SOLICITATION NO.
AutoCAD SHX Text
DATE
AutoCAD SHX Text A
AutoCAD SHX Text D
AutoCAD SHX Text
USDA
AutoCAD SHX Text S
AutoCAD SHX Text U
AutoCAD SHX Text
NO.
AutoCAD SHX Text
DATE
AutoCAD SHX Text
BY
AutoCAD SHX Text
DWG. NO.
AutoCAD SHX Text Service
AutoCAD SHX Text Research
AutoCAD SHX Text Agricultural
AutoCAD SHX Text
REVISIONS
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
DRAWN BY
AutoCAD SHX Text
SHEET OF
AutoCAD SHX Text
REAL PROPERTY
AutoCAD SHX Text
SITE KEY PLAN
9 8 71011
J
K
UP
PUMP ROOM
FAN ROOM
BOILER ROOM
(E)CH-1
STAIR NO. 2
BOOK
CONVEYOR
PIT
(E)CH-2
(E)FL.D.
ELEV. 4
(E)MCC-6
(E)CHP1D
(E)6"CWR
(E)HX
(E)6"CS
(E)6"CR
(E)10"CR
(E)10"CS
(E)8"CR
(E)8"CS
(E)8"CS
(E)8"CR
(E)8"CS
(E)10"CR UP TO CT
(E)10"CS UP TO CT
(E)CWP-12 (E)CWP-3 (E)CWP-2
TEMPORARY
COOLING
TOWER
(E)OPENING IN GRATING
(E)3"CW
2"CW
6"CR
6"CS
2"CW
(E)CHP-2(E)CHP-3(E)CHP-1
(E)CWP2D
(E)GENERATOR
EXHAUST
(E)SIDEWALK
2 2
(E)3"FL.D.
(E )M
CC
-1
(E)
(E)
(E)V-4 M
(E)8"CR
(E)10"CR
(E)FL.D.
TEMPORARY WATER
TREATMENT
(E)FL.D.
20'L x 8'W x 12'-6"H
10"CR
10"CS
(E)SHRUBS
G
J
K
H
4"D TO (E)FL.D
4"D
M
6"CR
6"CS4
(E)FENCING
(E)BOILER FLUE
(E)AREAWAY
2"CW
G
7/1 1/2
4 9
:46 :15
A M
2.0
M
-4
T.
DW
G
M-401TBASEMENT - MECHANICAL
TEMPORARY
FI
LE
N
RE
F:
PL
OT
D
AT
E:
2.0
NATIONAL AGRICULTURAL LIBRARY COOLING TOWER
REPLACEMENT
7900 Westpark Dr. | Suite A405 | McLean, VA 22102
(703) 556-8820 | www.summerconsultants.com
SUMMER
CONSULTANTS
I N C O R P O R A T E D
BELTSVILLE, MARYLAND
11 JULY 2024
PROFESSIONAL CERTIFICATION. I HEREBY
CERTIFY THAT THESE DOCUMENTS WERE
PREPARED OR APPROVED BY ME, AND
THAT I AM A DULY LICENSED
PROFESSIONAL ENGINEER UNDER THE
LAWS OF THE STATE OF MARYLAND,
LICENSE NO. 38731, WITH EXPIRATION DATE
OF 05/16/2026.
N
8'0 4' 1/4"=1'-0"
BASEMENT - MECHANICAL TEMPORARY
M-1021
N
GENERAL NOTES
G1. VERIFY LOCATION AND DIMENSIONS OF EXISTING
EQUIPMENT AND COORDINATE ALL WORK PRIOR TO THE
START OF CONSTRUCTION.
G2. ALL WORK SHALL BE NEW AND PROVIDED UNDER THIS
CONTRACT UNLESS SPECIFICALLY MARKED "EXISTING",
"EXIST", OR "(E)".
NOTES
1. CUT PIPING AND PROVIDE TEES AND SHUTOFF VALVES
BETWEEN INDICATED POINTS.
2. TAB PUMPS WITH INSTALLATION OF TEMPORARY
COOLING TOWER. BALANCE FLOW TO 1,200 GPM.
3. CLOSE DOOR OPENING WITH PLYWOOD. CUT
OPENINGS FOR CONDENSER WATER PIPING.
4. TEMPORARY FLEXIBLE PIPING.
5. PROVIDE PER DETAIL 3 ON DRAWING M-601.
6. MOTORIZED BYPASS VALVE WITH ISOLATION VALVES.
7. DEMOLISH EXISTING MOTORIZED VALVES, CONTROLS,
AND ALL APPURTENANCES COMPLETE.
8. COORDINATE WITH GOVERNMENTS EXISTING WATER
TREATMENT CONTRACT.
9. PROVIDE HEAT TRACE AND AND ABOVE GROUND COLD
PIPE LINE INSULATION ON ALL TEMPORARY OUTDOOR
HYDRONIC PIPING, DOMESTIC COLD WATER,
FILTRATION AND DRAIN PIPING. SEE HEAT TRACE
SCHEDULE ON M-601.
GRADE LEVEL MECHANICAL BASEMENT LEVEL
JURAN, A.
BENZEL, L.
HYMANSON, J.
JURAN, A.
GRADE LEVEL MECHANICAL BASEMENT LEVEL
AutoCAD SHX Text
SAFETY & HEALTH
AutoCAD SHX Text
DESIGNER
AutoCAD SHX Text
CHECKED BY
AutoCAD SHX Text
PROJECT MANAGER
AutoCAD SHX Text
PPM
AutoCAD SHX Text
EPM
AutoCAD SHX Text
A-E FIRM
AutoCAD SHX Text
AutoCAD SHX Text
SOLICITATION NO.
AutoCAD SHX Text
DATE
AutoCAD SHX Text A
AutoCAD SHX Text D
AutoCAD SHX Text
USDA
AutoCAD SHX Text S
AutoCAD SHX Text U
AutoCAD SHX Text
NO.
AutoCAD SHX Text
DATE
AutoCAD SHX Text
BY
AutoCAD SHX Text
DWG. NO.
AutoCAD SHX Text Service
AutoCAD SHX Text Research
AutoCAD SHX Text Agricultural
AutoCAD SHX Text
REVISIONS
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
DRAWN BY
AutoCAD SHX Text
SHEET OF
AutoCAD SHX Text
REAL PROPERTY
AutoCAD SHX Text
SITE KEY PLAN
FAN ROOM
BOILER ROOM
AREAWAY
(E)CH-1
STAIR NO. 2
BOOK
CONVEYOR
PIT
(E)FL.D.
CWP-1
(E)6"CWR
(E)HX
(E)6"CS
(E)6"CR
(E)10"CR
(E)10"CS
(E)8"CR
(E)8"CS
(E)8"CS
(E)8"CR
(E)FL.D.
CWP-3
CWP-2
(E)CHP1D
(E)CHP-2(E)CHP-3(E)CHP-1
(E)CWP2D
(E)10"CR UP TO CT
(E)10"CS UP TO CT
(E)3"CW
(E )M
CC
-1
(E)CH-2
(E)MCC-6
(E)
(E) M
(E)V-4
(E)8"CR
(E)10"CR
CAP
(E)FL.D.
(E)OPENING IN GRATING
3/4"D
3/4"D 3/4"D
(E)8"CS
CAP
(E)
(E) (E)
(E)
1 1 1
(E)PAD
(E)PAD(E)PAD
J
K
9 8 71011
7/1 1/2
4 9
:46 :23
A M
2.0
M
-4
.D W
G
M-401BASEMENT - MECHANICAL
FI
LE
N
RE
F:
PL
OT
D
AT
E:
2.0
NATIONAL AGRICULTURAL LIBRARY COOLING TOWER
REPLACEMENT
7900 Westpark Dr. | Suite A405 | McLean, VA 22102
(703) 556-8820 | www.summerconsultants.com
SUMMER
CONSULTANTS
I N C O R P O R A T E D
BELTSVILLE, MARYLAND
11 JULY 2024
PROFESSIONAL CERTIFICATION. I HEREBY
CERTIFY THAT THESE DOCUMENTS WERE
PREPARED OR APPROVED BY ME, AND
THAT I AM A DULY LICENSED
PROFESSIONAL ENGINEER UNDER THE
LAWS OF THE STATE OF MARYLAND,
LICENSE NO. 38731, WITH EXPIRATION DATE
OF 05/16/2026.
N
8'0 4' 1/4"=1'-0"
BASEMENT - MECHANICAL
M-1011
N
JURAN, A.
BENZEL, L.
HYMANSON, J.
JURAN, A.
GENERAL NOTES
G1. VERIFY LOCATION AND DIMENSIONS OF EXISTING
EQUIPMENT AND COORDINATE ALL WORK PRIOR TO THE
START OF CONSTRUCTION.
G2. ALL WORK SHALL BE NEW AND PROVIDED UNDER THIS
CONTRACT UNLESS SPECIFICALLY MARKED "EXISTING",
"EXIST", OR "(E)".
1. EXTEND EXISTING PAD PER DETAIL 4/M601.
NOTES
AutoCAD SHX Text
SAFETY & HEALTH
AutoCAD SHX Text
DESIGNER
AutoCAD SHX Text
CHECKED BY
AutoCAD SHX Text
PROJECT MANAGER
AutoCAD SHX Text
PPM
AutoCAD SHX Text
EPM
AutoCAD SHX Text
A-E FIRM
AutoCAD SHX Text
AutoCAD SHX Text
SOLICITATION NO.
AutoCAD SHX Text
DATE
AutoCAD SHX Text A
AutoCAD SHX Text D
AutoCAD SHX Text
USDA
AutoCAD SHX Text S
AutoCAD SHX Text U
AutoCAD SHX Text
NO.
AutoCAD SHX Text
DATE
AutoCAD SHX Text
BY
AutoCAD SHX Text
DWG. NO.
AutoCAD SHX Text Service
AutoCAD SHX Text Research
AutoCAD SHX Text Agricultural
AutoCAD SHX Text
REVISIONS
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
DRAWN BY
AutoCAD SHX Text
SHEET OF
AutoCAD SHX Text
REAL PROPERTY
AutoCAD SHX Text
SITE KEY PLAN
W14X43
(E)R.D.
3"D
EQUALIZER
2"D 3"O.F.D
ACCESS LADDER
(E)2-1/2"CW
TO MAIN
EWL-1A/B
BASIN FILTRATION SKID
(E)3"FL.D. WITH
12"FUNNEL
(E)FLOW METER &
BACK-FLOW
PREVENTER
12"CR
10"CS
4 ACCESS LADDER4
(E)R.D.
(E)R.D.(E)R.D.
3"FILTRATION
M-403
M-403
2"D 3"O.F.D
10"CS
2-1/2"CW
2-1/2"CW
10"CS
(E)10"CR DN. TO
BASEMENT
(E)10"CS DN. TO
BASEMENT
2-1/2"CW
2"D
W18X50
12"CR UP
5 W14X43
5 W18X505
W14X435W14X435 W14X435
V-6
(E)SHELVES
10"CS
ACCESS LADDER4
SPRING ISOLATORS SPRING ISOLATORS
5 W14X43
3/4"
12"CS
SPRING ISOLATORS
V-2B
V-2A
(E)WATER TREATMENT
D8
V-3
M
V-3
G
J
J
G
10 9 8 7 6
ACCESS
LADDER
CT-1A CT-1B
ACCESS LADDER
& ACCESS DOOR
PLATFORM
ACCESS LADDER & ACCESS
DOOR PLATFORM
M-403
ACCESS
PLATFORM
12"CR DN.
10"CR 10"CR
M-403
V-1A M
V-1B M
9 8 7 6
7/1 1/2
4 9
:46 :33
A M
2.0
M
-4
.D W
G
M-402LOWER ROOF & PENTHOUSE -
MECHANICAL
FI
LE
N
RE
F:
PL
OT
D
AT
E:
2.0
NATIONAL AGRICULTURAL LIBRARY COOLING TOWER
REPLACEMENT
7900 Westpark Dr. | Suite A405 | McLean, VA 22102
(703) 556-8820 | www.summerconsultants.com
SUMMER
CONSULTANTS
I N C O R P O R A T E D
BELTSVILLE, MARYLAND
11 JULY 2024
N
JURAN, A.
BENZEL, L.
HYMANSON, J.
JURAN, A.
GENERAL NOTES
G1. VERIFY LOCATION AND DIMENSIONS OF EXISTING
EQUIPMENT AND COORDINATE ALL WORK PRIOR TO THE
START OF CONSTRUCTION.
G2. ALL WORK SHALL BE NEW AND PROVIDED UNDER THIS
CONTRACT UNLESS SPECIFICALLY MARKED "EXISTING",
"EXIST", OR "(E)".
N
1. PROVIDE VIBRATION CUTOFF RESET SWITCHES AT
OPERATOR HEIGHT. LOCATE SWITCH FOR EACH OF
THE TOWERS IN THE SAME LOCATION WITH LABELS.
2. PROVIDE HEAT TRACE AND ABOVE GROUND COLD PIPE
LINE INSULATION ON ALL OUTDOOR HYDRONIC PIPING,
DOMESTIC COLD WATER, FILTRATION AND DRAIN
PIPING. SEE HEAT TRACE SCHEDULE ON M-601.
3. PROVIDE FLEXIBLE PIPE CONNECTION. INSTALL
FLEXIBLE CONNECTION STRAIGHT WITH CAPABILITY OF
3/4" LATERAL OFFSET.
4. MANUFACTURER PROVIDED. EXTEND LADDER TO
ROOF DECK.
5. SHOWN FOR REFERENCE. COORDINATE WITH
STRUCTURAL DRAWINGS.
6. PIPE SIZE VARIES BY MANUFACTURER. MATCH OUTLET
DIMENSION.
7. SEE STRUCTURAL FOR PIPING SUPPORT DETAIL.
8. BYPASS CONNECTION BETWEEN CS AND CR. VALVE
PROVIDE ISOLATION VALVES FOR V-3.
NOTES
N
8'0 4' 1/4"=1'-0"
COOLING TOWERS LOWER PLAN
M-1022
N
8'0 4' 1/4"=1'-0"
COOLING TOWERS UPPER PLAN
M-1021
PROFESSIONAL CERTIFICATION. I HEREBY
CERTIFY THAT THESE DOCUMENTS WERE
PREPARED OR APPROVED BY ME, AND
THAT I AM A DULY LICENSED
PROFESSIONAL ENGINEER UNDER THE
LAWS OF THE STATE OF MARYLAND,
LICENSE NO. 38731, WITH EXPIRATION DATE
OF 05/16/2026.
AutoCAD SHX Text
SAFETY & HEALTH
AutoCAD SHX Text
DESIGNER
AutoCAD SHX Text
CHECKED BY
AutoCAD SHX Text
PROJECT MANAGER
AutoCAD SHX Text
PPM
AutoCAD SHX Text
EPM
AutoCAD SHX Text
A-E FIRM
AutoCAD SHX Text
AutoCAD SHX Text
SOLICITATION NO.
AutoCAD SHX Text
DATE
AutoCAD SHX Text A
AutoCAD SHX Text D
AutoCAD SHX Text
USDA
AutoCAD SHX Text S
AutoCAD SHX Text U
AutoCAD SHX Text
NO.
AutoCAD SHX Text
DATE
AutoCAD SHX Text
BY
AutoCAD SHX Text
DWG. NO.
AutoCAD SHX Text Service
AutoCAD SHX Text Research
AutoCAD SHX Text Agricultural
AutoCAD SHX Text
REVISIONS
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
DRAWN BY
AutoCAD SHX Text
SHEET OF
AutoCAD SHX Text
REAL PROPERTY
AutoCAD SHX Text
SITE KEY PLAN
AutoCAD SHX Text
SITE KEY PLAN
G
TOP OF ROOFING
MATERIALS
8'0 4' 1/4"=1'-0"
SECTION COOLING TOWERS
M-4022
V-5
EQUILIZER
2-1/2"CW
EWL-1A
10"CS
12"CS
10"CR
3"D
EWL-1B
(E)WALL
ACCESS DOOR
8'0 4' 1/4"=1'-0"
SECTION COOLING TOWERS
M-4021
TOP OF ROOFING
MATERIALS
CT-1B
7 8
2-1/2"CW
3"D
CT-1A
EQUILIZER
12"CS10"CS
10"CS
10"CS
10"CR
M
V-5B M
V-5A
10"CR
V-2A
10"CR
10"CS
M
M
2-1/2"CW
10"CR
V-2B 5
3"FILTRATION
V-2B
SPRING
ISOLATOR
V-1B
ACCESS PLATFORM
RAILINGS RAILINGS
RAILINGS
7/1 1/2
4 9
:46 :39
A M
M-
3 D
ET
AI
LS
.D W
G
M-403DETAILS
FI
LE
N
RE
F:
PL
OT
D
AT
E:
2.0
NATIONAL AGRICULTURAL LIBRARY COOLING TOWER
REPLACEMENT
7900 Westpark Dr. | Suite A405 | McLean, VA 22102
(703) 556-8820 | www.summerconsultants.com
SUMMER
CONSULTANTS
I N C O R P O R A T E D
BELTSVILLE, MARYLAND
11 JULY 2024
PROFESSIONAL CERTIFICATION. I HEREBY
CERTIFY THAT THESE DOCUMENTS WERE
PREPARED OR APPROVED BY ME, AND
THAT I AM A DULY LICENSED
PROFESSIONAL ENGINEER UNDER THE
LAWS OF THE STATE OF MARYLAND,
LICENSE NO. 38731, WITH EXPIRATION DATE
OF 05/16/2026.
JURAN, A.
BENZEL, L.
HYMANSON, J.
JURAN, A.
GENERAL NOTES
G1. VERIFY LOCATION AND DIMENSIONS OF EXISTING
EQUIPMENT AND COORDINATE ALL WORK PRIOR TO THE
START OF CONSTRUCTION.
G2. ALL WORK SHALL BE NEW AND PROVIDED UNDER THIS
CONTRACT UNLESS SPECIFICALLY MARKED "EXISTING",
"EXIST", OR "(E)".
1. PROVIDE FLEXIBLE PIPE CONNECTION. INSTALL
FLEXIBLE CONNECTION STRAIGHT WITH CAPABILITY OF
3/4" LATERAL OFFSET.
2. SEE STRUCTURAL DRAWINGS FOR SUPPORT DETAILS.
3. PROVIDE HEAT TRACE AND AND ABOVE GROUND COLD
PIPE LINE INSULATION ON ALL OUTDOOR HYDRONIC
PIPING, DOMESTIC COLD WATER, FILTRATION AND
DRAIN PIPING. SEE HEAT TRACE SCHEDULE ON M-601.
4. PROVIDE WELDED CONNECTION FOR PIPE STAND TO
THE ELBOW. COORDINATE WITH THE STRUCTURAL
DRAWINGS.
5. BASIN SWEEPER CONNECTIONS.
NOTES
3" FILTRATION S/R
AutoCAD SHX Text
SAFETY & HEALTH
AutoCAD SHX Text
DESIGNER
AutoCAD SHX Text
CHECKED BY
AutoCAD SHX Text
PROJECT MANAGER
AutoCAD SHX Text
PPM
AutoCAD SHX Text
EPM
AutoCAD SHX Text
A-E FIRM
AutoCAD SHX Text
AutoCAD SHX Text
SOLICITATION NO.
AutoCAD SHX Text
DATE
AutoCAD SHX Text A
AutoCAD SHX Text D
AutoCAD SHX Text
USDA
AutoCAD SHX Text S
AutoCAD SHX Text U
AutoCAD SHX Text
NO.
AutoCAD SHX Text
DATE
AutoCAD SHX Text
BY
AutoCAD SHX Text
DWG. NO.
AutoCAD SHX Text Service
AutoCAD SHX Text Research
AutoCAD SHX Text Agricultural
AutoCAD SHX Text
REVISIONS
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
DRAWN BY
AutoCAD SHX Text
SHEET OF
AutoCAD SHX Text
REAL PROPERTY
DRILL & GROUT # 4 @ 12" O.C.
W/ STD. HOOK (MIN. 4" EMBED)
MA
TC
H (E
#4 @ 12" O.C. E.W.
DRILL & EPOXY (MIN. 6"
EMBED)
2" MI
N.
(E) PAD
7/1 1/2
4 9
:46 :46
A M
2.0
M
-6
.D W
G
M-601SCHEDULES
FI
LE
N
RE
F:
PL
OT
D
AT
E:
2.0
NATIONAL AGRICULTURAL LIBRARY COOLING TOWER
REPLACEMENT
7900 Westpark Dr. | Suite A405 | McLean, VA 22102
(703) 556-8820 | www.summerconsultants.com
SUMMER
CONSULTANTS
I N C O R P O R A T E D
BELTSVILLE, MARYLAND
11 JULY 2024
PROFESSIONAL CERTIFICATION. I HEREBY
CERTIFY THAT THESE DOCUMENTS WERE
PREPARED OR APPROVED BY ME, AND
THAT I AM A DULY LICENSED
PROFESSIONAL ENGINEER UNDER THE
LAWS OF THE STATE OF MARYLAND,
LICENSE NO. 38731, WITH EXPIRATION DATE
OF 05/16/2026.
PUMP SCHEDULE
UNIT NO.
TYPE
FLUID GPM
HEAD
(FT.) RPM
EFF.
BHP
MAX.
MOTOR
HP
ELEC.
DATA
(V/PH/HZ)
SERVICE LOCATION NOTES
CWP-1 ES WATER 1,000 90 1770 85 27.30 40 460/3/60 CONDENSER WATER -
CH-1
MB-07 PUMP
ROOM B,C,D,E
CWP-2 ES WATER 1,000 90 1770 85 27.30 40 460/3/60 CONDENSER WATER -
CH-2 2B5 - MECH B,C,D,E
CWP-3 ES WATER 1,000 90 1770 85 27.30 40 460/3/60 CONDENSER WATER -
STANDBY 2B5 - MECH B,C,D,E
NOTES
A
A. ES - END SUCTION
B. PROVIDE WITH FLANGED CONNECTIONS.
C. PROVIDE PREMIUM EFFICIENCY MOTOR AND VARIABLE
FREQUENCY DRIVE.
D. CWP - CONDENSER WATER PUMP
E. INSTALL PER DETAIL 1/M-601.
F. PROVIDE SUCTION DIFFUSER TO MATCH PUMP FLANGE AND
EXISTING PIPING.
COOLING TOWER SCHEDULE
CT-1A,B
CROSS-FLOW 2-CELL COOLING TOWER TO EACH COOL 1,000 GPM OF WATER FROM 95°F
TO 83°F AT 78°F AMBIENT WET-BULB.
FAN HP: 30 HP PER CELL, PROVIDE PREMIUM EFFICIENCY, CLASS F INSULATION
PROVIDE WITH BELT DRIVE MOTOR.
PROVIDE BASIN HEATERS - 12 KW PER CELL.
460 VOLT / 3 PHASE / 60 HZ.
PROVIDE REVERSIBLE VFD WITH INTERNAL BYPASS.
PROVIDE WITH TWO ELECTRONIC WATER LEVEL CONTROLLER. HIGH AND LOW ALARMS.
MAX SHIPPING WEIGHT: 5,550 LBS
MAXIMUM OPERATING WEIGHT OF 19,000 LB PER COOLING TOWER CELL INCLUDING
ACCESSORIES.
MAXIMUM DIMENSIONS TWO CELLS - 24'-5.75" L x 11'-11"Wx18'-2.25"H
COOLING TOWER SHALL GALVANIZED STEEL WITH A STAINLESS STEEL BASIN.
PROVIDE FACTORY MUTUAL APPROVAL.
PROVIDE OSHA COMPLIANT TOP RAILING, MID RAILING, AND TOW BOARD AT TOP OF
TOWERS. PROVIDE OSHA COMPLIANT RAILING AT TOP OF TOWERS AND LADDERS WITH
SAFETY CAGE.
PROVIDE INTERNAL ACCESS WALKWAY AND MECHANICAL ACCESS PLATFORM.
PROVIDE BASIN SWEEPER.
BASIS OF DESIGN, FOR REFERENCE ONLY:
BALTIMORE AIRCOIL COMPANY; SERIES 1500
SPX COOLING TECH, LLC; MODEL AV SERIES
HEAT TRACE
PIPE SIZE WATTS/LF NOTES
< 3" DIA 3 B,C
3"-6" DIA 5 B,C
8"-12" DIA 10 B,C
NOTES
A. PROVIDE ON ALL OUTDOOR HYDRONIC
PIPING AND DRAINS.
B. SELF REGULATING.
C. ELECTRICAL: 120V/1PH/60PH
A
VIBRATION SPRING ISOLATORS
PROVIDE 4" DEFLECTION ISOLATOR FOR COOLING TOWER ISOLATION. COORDINATE WITH
STRUCTURAL AND MECHANICAL DRAWINGS.
VERTICALLY AND LATERALLY RESTRAINED SPRING ISOLATOR WITH CONSTANT FREE
AND OPERATING HEIGHT AND REPLACEABLE NEOPRENE SNUBBING ELEMENTS.
VERTICAL RESTRAINT BOLT
PROVIDE TOP PLATE IF ISOLATORS IF EQUIP SUPPORT STEEL IS 90° TO THE LONG
ISOLATOR AXIS
MAX DIMENSIONS : 25.50"L x 8.0"W x 17.5"H
JURAN, A.
BENZEL, L.
HYMANSON, J.
JURAN, A.
TEMPORARY COOLING TOWER
400 NOMINAL TON, TEMPORARY COOLING TOWER 1,000 GPM OF WATER
FROM 95°F TO 83°F AT 78°F AMBIENT WET-BULB.
PROVIDE INTEGRAL CONTROLS WITH TEMPORARY TOWERS AND
TEMPERATURE SENSORS.
PROVIDE TOWER WITH INTEGRAL WATER LEVEL CONTROLLER AND MAKEUP
WATER CONTROL.
PROVIDE VARIABLE SPEED DRIVES FOR FAN MOTORS.
PROVIDE CONTROLS WITH FREE COOLING MODE. MINIMUM CONDENSER
FLOW TO MEET FREE COOLING IS 480 GPM. PROVIDE VIBRATION SWITCH
WITH AUTOMATIC SHUTDOWN.
ELECTRICAL
460 VOLT / 3 PHASE / 60 HZ.
MAIN DISCONNECT - 100 A
FLA - 56 A
SINGLE POINT OF CONNECTION
PROVIDE MANUFACTURER COMMISSIONING AND STARTUP AND CONTINUED
MAINTENANCE THROUGHOUT RENTAL PERIOD.
NO SCALE
END SUCTION PUMP
DETAIL
M-6011
FLOW ALL GAGE PIPING AND
BALL VALVES TO BE 3/8"
RANGE 0-100 PSI
3/4" SEAL BASIN DRAIN
PIPE TO FLOOR DRAIN
BALL VALVE TYP.
4" CONCRETE PAD. DOWEL
TO CONCRETE FLOOR SLAB
BOLT BASE TO
INERTIA BASE
3/8" BALL VALVE
ABRASIVE
SEPARATOR
PROVIDE SPRING HANGER ON
PIPE OR FLEXIBLE CONNECTORS
MANUAL AIR VENT
SPRING LOADED
SILENT CHECK VALVE
BALANCING VALVE
SEE FLOOR PLANS FOR
PIPE SIZES. ALL VALVES
ARE FULL SIZE OF PIPE
8"x8"x1/2" BASE PLATE
BOLT TO INERTIA BASE
2" PIPE WELDED TO
SUCTION DIFFUSER AND BASE PLATE
FLEXIBLE PIPE CONNECTION, WITH ELONGATION
AND COMPRESSION CONTROL RODS, TYP.
3/4" GATE VALVE WITH
HOSE CONNECTION
SUCTION DIFFUSER
FL
OW
(E)BUTTERFLY
VALVE
(E)BUTTERFLY
VALVE
BASIN FILTRATION SKID
PROVIDE SKID MOUNTED SOLID SEPARATOR CONSISTING OF CENTRIFUGAL
VORTEX SEPARATOR, CENTRIFUGAL CIRCULATING PUMP, STEEL STRAINER,
SOLIDS RECOVERY VESSEL, AND SELF CONTAINED CONTROLS WITH BAS
CONNECTION. PROVIDE END SUCTION CENTRIFUGAL PUMP WITH CAST IRON
HOUSING AND IMPELLER, BRONZE SHAFT SLEEVE AND MECHANICAL SHAFT
SEAL. PROVIDE STARTER, DISCONNECT AND HOA SWITCH.
PROVIDE PURGE PACKAGE AS RECOMMENDED BY MANUFACTURER. BAS
CONNECTION FOR STATUS AND START/STOP.
FLOW - 200 GPM TOTAL
PROVIDE SKID PER DETAIL 2 ON M-601
MOTOR - 7.5 HP
460 VOLT/ 3 PHASE/ 60 HZ
PRESSURE GAUGE
SEE FLOOR PLANS
FOR PIPE SIZES
PUMP
CENTRIFUGAL
SEPARATOR
PRESSURE GAUGE
PROVIDE 3/8" PIPING
AND BALL VALVES
FLUID RECOVERY FILTER
NO SCALE
CENTRIFUGAL SOLID FROM LIQUID SEPERATOR
DETAIL
M-6012
NO SCALE
MAKEUP WATER CONNECTION
DETAIL
M-401T3
REDUCED PRESSURE
BACKFLOW PREVENTER
3/4" CW
MAKE-UP
INDIRECT WASTE
CONNECTION
TO FLOOR DRAIN
TO COOLING TOWER BASIN
FROM COOLING TOWER BASIN
STRAINER
TO FL.D
AUTOMATIC PURGE
CONTROL VALVE
MANUFACTURER
PROVIDED SKID
NO SCALE
(E) EQUIP. PAD EXTENSION
DETAIL
M-4014
AutoCAD SHX Text
SAFETY & HEALTH
AutoCAD SHX Text
DESIGNER
AutoCAD SHX Text
CHECKED BY
AutoCAD SHX Text
PROJECT MANAGER
AutoCAD SHX Text
PPM
AutoCAD SHX Text
EPM
AutoCAD SHX Text
A-E FIRM
AutoCAD SHX Text
AutoCAD SHX Text
SOLICITATION NO.
AutoCAD SHX Text
DATE
AutoCAD SHX Text A
AutoCAD SHX Text D
AutoCAD SHX Text
USDA
AutoCAD SHX Text S
AutoCAD SHX Text U
AutoCAD SHX Text
NO.
AutoCAD SHX Text
DATE
AutoCAD SHX Text
BY
AutoCAD SHX Text
DWG. NO.
AutoCAD SHX Text Service
AutoCAD SHX Text Research
AutoCAD SHX Text Agricultural
AutoCAD SHX Text
REVISIONS
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
DRAWN BY
AutoCAD SHX Text
SHEET OF
AutoCAD SHX Text
REAL PROPERTY
G
M
ES-#
FLOW METER
(TURBINE-STYLE)
AIR OR WATER DIFFERENTIAL PRESSURE SWITCH, BY APPLICATION.
PROVIDE AIR SWITCH PER DETAIL 4/M-701/M-701. PROVIDE WATER
SWITCH PER DETAIL 6/M-701/M-701.
DIFFERENTIAL PRESSURE GAUGE, CONNECT TO STATIC
PRESSURE TAPS IN ACCORDANCE WITH DETAIL 3/M-701/M-701.
AIR OR WATER DIFFERENTIAL PRESSURE TRANSMITTER, BY APPLICATION.
PROVIDE AIR TRANSMITTER PER DETAIL 4/M-701/M-701. PROVIDE WATER
TRANSMITTER PER DETAIL 6/M-701/M-701.
PIPE MOUNTED INSERTION TYPE ELECTRONIC
TEMPERATURE SENSOR WITH WELL.
CURRENT SWITCH
END SWITCH
BINARY INPUT OR OUTPUT POINT
ANALOG INPUT OR OUTPUT POINT
NETWORK CONNECTION
THERMOMETER.
ELECTRIC TO PNEUMATIC SOLENOID VALVE
MOUNTED IN INSTRUMENTATION PANEL,
COIL VOLTAGES AS INDICATED ON WIRING
DIAGRAMS.
GENERAL REQUIREMENTS
SYMBOLS & ABREVIATIONS
AI ANALOG INPUT
ANALOG OUTPUTAO
BI BINARY INPUT
BINARY OUTPUTBO
CLG COOLING
CHANGE OF VALUECOV
Cx COMMISSIONING
HEATINGHTG
I/O INPUT/OUTPUT
NETWORK VARIABLE INPUTNVI
NVO NETWORK VARIABLE OUTPUT
SETPOINTSP
HAND-OFF-AUTO SWITCH
MOTOR
NORMALLY OPEN CONTACTS
NORMALLY CLOSED CONTACTS
RELAY COIL
STARTER HOLDING COIL
THERMAL MOTOR SWITCH
PNEUMATIC TUBING
EXISTING PNEUMATIC TUBING
MOTOR STARTER
NC
NOEP#
C
FAN OR PUMP, BY APPLICATION
EMERGENCY HVAC OFF (SYSTEM VARIABLE)
OUTSIDE AIR TEMPERATURE SENSOR (SYSTEM VARIABLE)
OUTSIDE AIR ENTHALPY TRANSMITTER (SYSTEM VARIABLE)
VARIABLE FREQUENCY DRIVE
R#
SYMBOLS & ABBREVIATIONS
CONTROL AIR MAIN CONNECTION
OPPOSED BLADE DAMPER.D-#
D-# PARALLEL BLADE DAMPER.
A-#
DAMPER OR VALVE ACTUATOR.
2 WAY CONTROL VALVE (BALL OR GLOBE AS SPECIFIED).
V-#
3 WAY CONTROL VALVE (BALL OR GLOBE AS SPECIFIED).
V-#
HYDRONIC PIPING
AIR OR WATER FLOW PATH
FILTER OR COIL (AS LABELED)
M
A O
H
VFD-#
DP-#
DP-#
TS-#
CS-#
EHO
TS-OA
EN-OA
BUTTERFLY VALVE.
2 WAY CONTROL VALVE (BALL OR GLOBE AS SPECIFIED) WITH
PILOT POSITIONER.
3 WAY CONTROL VALVE (BALL OR GLOBE AS SPECIFIED).
WITH PILOT POSITIONER.
V-#
V-#
1. PROVIDE THE FOLLOWING AUTOMATIC ALARM AT OWS EVERY MARCH 1ST AND
SEPTEMBER 1ST: "IN CONFORMANCE WITH THE LOCAL BUILDING CODES AND IN
ORDER TO SAVE ENERGY, BUILDING SENSORS MUST BE CALIBRATED AND CLEANED
AT REGULAR INTERVALS. OUTSIDE AIR, HUMIDITY, AND ENTHALPY SENSORS
SHOULD BE CALIBRATED ANNUALLY"
7/1 1/2
4 9
:46 :53
A M
2.0
M
-7
.D W
G
M-700CONTROLS COVER SHEET
FI
LE
N
RE
F:
PL
OT
D
AT
E:
2.0
NATIONAL AGRICULTURAL LIBRARY COOLING TOWER
REPLACEMENT
7900 Westpark Dr. | Suite A405 | McLean, VA 22102
(703) 556-8820 | www.summerconsultants.com
SUMMER
CONSULTANTS
I N C O R P O R A T E D
BELTSVILLE, MARYLAND
11 JULY 2024
PROFESSIONAL CERTIFICATION. I HEREBY
CERTIFY THAT THESE DOCUMENTS WERE
PREPARED OR APPROVED BY ME, AND
THAT I AM A DULY LICENSED
PROFESSIONAL ENGINEER UNDER THE
LAWS OF THE STATE OF MARYLAND,
LICENSE NO. 38731, WITH EXPIRATION DATE
OF 05/16/2026.
JURAN, A.
BENZEL, L.
BENZEL, L.
JURAN, A.
AutoCAD SHX Text
XXXX
AutoCAD SHX Text M B
AutoCAD SHX Text
SAFETY & HEALTH
AutoCAD SHX Text
DESIGNER
AutoCAD SHX Text
CHECKED BY
AutoCAD SHX Text
PROJECT MANAGER
AutoCAD SHX Text
PPM
AutoCAD SHX Text
EPM
AutoCAD SHX Text
A-E FIRM
AutoCAD SHX Text
AutoCAD SHX Text
SOLICITATION NO.
AutoCAD SHX Text
DATE
AutoCAD SHX Text A
AutoCAD SHX Text D
AutoCAD SHX Text
USDA
AutoCAD SHX Text S
AutoCAD SHX Text U
AutoCAD SHX Text
NO.
AutoCAD SHX Text
DATE
AutoCAD SHX Text
BY
AutoCAD SHX Text
DWG. NO.
AutoCAD SHX Text Service
AutoCAD SHX Text Research
AutoCAD SHX Text Agricultural
AutoCAD SHX Text
REVISIONS
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
DRAWN BY
AutoCAD SHX Text
SHEET OF
AutoCAD SHX Text
REAL PROPERTY
GENERAL NOTES
G1. VERIFY LOCATION AND DIMENSIONS OF EXISTING EQUIPMENT AND
COORDINATE ALL WORK PRIOR TO THE START OF CONSTRUCTION.
G2. ALL WORK SHALL BE NEW AND PROVIDED UNDER THIS CONTRACT
UNLESS SPECIFICALLY MARKED "EXISTING", "EXIST", OR "(E)".
NOTES
1. DEMOLISH ELECTRONIC CONTROL DEVICE. RETAIN WIRING, CONDUIT,
HANGERS, AND ALL APPURTENANCES COMPLETE BACK TO CONTROL
CABINET.
2. PROVIDE SENSOR IN EXISTING WELL. REUSE WIRING, ETC. BACK TO
CONTROL CABINET.
3. SET INTERNAL CHILLER CONTROLS FOR A MINIMUM CONDENSER
WATER FLOW OF LESS THAN 900 GPM.
4. CONTROLS CONTRACTOR MUST COORDINATE WITH TAB
CONTRACTOR FOR BALANCING.
COOLING TOWERS
CWP-1
N.C.
VFD-1B
CT-1B
VFD-1A
WATER LEVEL
CONTROLLERS
CT-1A
(E)
(E)
(E)
(E)
(E)
TS
VFD
EXTERNAL ENABLE
VS-1
BACnet MS/TP
CONNECTION FOR:
START/STOP,
STATUS, FAULT,
SPEED,
FREQUENCY,
CURRENT, kW
COOLING TOWER FANS
V-1A V-1B V-3
V-2A V-2B
(E)
TS
(E)
VFD-2A
VFD-2C
EWL-1A EWL-1B
CW
V-6
CS
(E)CH-1
PUMPS
BACnet MS/TP
CONNECTION FOR:
START/STOP,
STATUS, FAULT,
SPEED,
FREQUENCY,
CURRENT
VFD
TS
(E)
TS
(E)CR ASSOCAITED
WITH CHILLER
(E)CS ASSOCAITED
WITH CHILLER
(E)CHWR ASSOCAITED
WITH CHILLER
(E)CHWS ASSOCAITED
WITH CHILLER
(E)
(E)
VFD-2B
(E)
N.C.
(E)
(E)
CWP-3
CWP-2
CR
(E)
(E)
TS
(E)
TS
(E)
(E)CH-2
TS
(E)
TS
(E)CR ASSOCAITED
WITH CHILLER
(E)CS ASSOCAITED
WITH CHILLER
(E)CHWR ASSOCAITED
WITH CHILLER
(E)CHWS ASSOCAITED
WITH CHILLER
(E)HX-1
CHWS
(E)CWP2D
(FREE COOLING)
(E) (E)
(E)
CS
(E)CS(E)
(E)CHP1D
(FREE COOLING)
(E) (E)
(E)CS (E)
CHWR(E)(E)V-4
N.C
(E)V-5 N.C
TS
-2
TS
-1
TS-3
21 21
(E)WATER METER
DESIGN INTENT
1. TWO CHILLERS, TWO COOLING TOWER, TWO PRIMARY CHILLED WATER PUMPS, TWO CONDENSER
WATER PUMPS ARE REQUIRED TO MEET THE BLOCK LOAD.
1.1. ONE CHILLER REQUIRES ONE COOLING TOWER AND ONE CONDENSER WATER PUMP. HOWEVER, THE MOST EFFICIENT SINGLE CHILLER OPERATION USES 2 COOLING TOWERS AND ONE
CONDENSER WATER PUMP.
1.2. TWO CHILLERS REQUIRES TWO COOLING TOWER AND TWO CONDENSER WATER PUMPS,
1.3. THEREFORE THIS DESIGN RUNS TWO COOLING TOWERS WITH THE EXISTING TWO 400 TON
CHILLERS.
2. TO REDUCE ENERGY USE, ALL COOLING TOWERS SHOULD OPERATE WITH A SINGLE CHILLER AND SINGLE CONDENSER WATER PUMP WHEN THE OUTSIDE AIR TEMPERATURE IS ABOVE 55°F. IN ORDER TO REDUCE THE COOLING TOWER APPROACH AND INCREASE CHILLER EFFICIENCY, THIS DESIGN OPERATES ALL TOWERS AT 70% SPEED THAT RESULTS IN TOTAL TOWER BHP OF 34% OF A SINGLE
TOWER MOTOR.
3. FREE COOLING - REQUIRES ONE COOLING TOWER, ONE FREE-COOLING CONDENSER WATER PUMP, ONE FREE COOLING CHILLED WATER PUMP, ONE 200 TON PLATE FRAME HEAT EXCHANGER. FREE
COOLING IS ACTIVE WHEN OUTDOOR AMBIENT TEMPERATURE IS BELOW 47°F AND OFF ONCE
TEMPERATURE RISES ABOVE 54°F.
2. EQUIPMENT PAIRINGS FOR LEAD/LAG: (CHILLER), (CONDENSER PUMP), (PRIMARY PUMP)
2.1. CH-1, CWP-1, CHP-1
2.2. CH-2, CWP-2, CHP-2
2.3. CWP-3 = STANDBY PUMP FOR EITHER CH-1 OR CH-2
2.4. IN THE EVENT OF EQUIPMENT FAILURE, THERE ARE MANUAL VALVES TO CHANGE EQUIPMENT
PAIRINGS. PROVIDE MANUAL OVERRIDES ON THE OWS.
3. EQUIPMENT FOR FREE COOLING
3.1. LEAD COOLING TOWER
3.2. CHILLED WATER PUMP - CHP1D
3.3. CONDENSER WATER PUMP - CWP2D
3.4. HEAT EXCHANGER - HX-1
LEAD/LAG SELECTION
1. PRIOR TO STARTING THE CHILLED WATER SYSTEM THE OPERATOR SHALL SELECT THE EQUIPMENT
LEAD AND LAG ORDER.
2. PUMPS, AND COOLING TOWERS INPUT AS "OUT OF SERVICE" WILL BE SKIPPED OVER IN THE STARTING
AND STOPPING SEQUENCE
EQUIPMENT ROTATION: AUTOMATICALLY ALTERNATE THE FOLLOWING TO EQUIPMENT PAIRINGS TO EQUALIZE THE RUN TIMES, WITH A MINIMUM OF ONCE PER WEEK. THE LIST BELOW SHOWS TYPICAL
EQUIPMENT PAIRINGS:
CH-1, CWP-1, CHP-1,
CH-2, CWP-2, CHP-2
CT-1A, CT-1B
CWP-3 = STANDBY EQUIPMENT
COOLING
1. EXISTING CHILLER START UP SEQUENCE IS TO BE MAINTAINED.
2. CHILLER HEAD PRESSURE CONTROL SHALL MODULATE CONDENSER WATER BYPASS VALVE V-3
OUTSIDE OF THE BAS. PROVIDE VALVE PILOT POSITIONER ON VALVE V-3 AND INDICATE VALVE
POSITION ON OWS GRAPHIC.
3. CONDENSER PUMP VFD: LEAD CONDENSER PUMP VFD BALANCED TO PROVIDE 1,000 GPM.
4. CONDENSER WATER SUPPLY TEMPERATURE, AS SENSED BY SENSOR TS-2, FLOATS BETWEEN HIGH LIMIT OF 83°F AND LOW LIMIT OF 60°F. PROVIDE A TIME DELAY, INITIALLY SET FOR 1 MINUTE, BETWEEN
COOLING TOWER STARTS.
5. WHEN OUTSIDE AIR TEMPERATURE RISES ABOVE 55°F, OPEN BOTH LAG TOWER VALVES V-1 AND V-2 AND EQUALIZER VALVE V-5 AND ENABLE BOTH TOWER CONTROLS. OPERATE ALL TOWER FAN VFDS AT 70% SPEED PROVIDED THAT CONDENSER WATER TEMPERATURE AT TS-2 IS BETWEEN HIGH AND LOW LIMITS. UPON A FALL IN TEMPERATURE AT TS-2 BELOW LOW LIMIT SETPOINT, TOWER VFDS SHALL
DECREASE SPEED.
6. WHEN FANS ARE AT MINIMUM SPEED FOR 15 MINUTES AND CONDENSER WATER RETURN
TEMPERATURE AT TS-2 FALLS TO 55°F, DISABLE ONE TOWER.
7. WHEN OUTSIDE AIR TEMPERATURE FALLS BELOW 55°F, A SINGLE COOLING TOWER FAN IS OPERATING, CLOSE LAG VALVE V-1, V-2, AND V-5. LEAD TOWER VFD SHALL OPERATE 20% HIGHER SPEED THAN
OPERATING CHILLER KW PERCENTAGE, SUBJECT TO CONDENSER WATER TEMPERATURE SENSOR
TS-2 HIGH AND LOW LIMITS. OPERATING TOWER VFD SHALL BE AT 100% SPEED WHEN OPERATING CHILLER KW PERCENTAGE IS BETWEEN 80 AND 100%. PROVIDE A TIME DELAY, INITIALLY SET 1 MINUTE, BETWEEN STARTS.
8. WHEN BOTH TOWERS OPERATE, CONTROL ALL VFDS AT THE SAME SPEED UNLESS OTHERWISE
NOTED.
WATER SIDE ECONOMIZER
1. FREE COOLING MODE: ON A FALL IN OUTSIDE TEMPERATURE BELOW 47°F AND A CALL FOR CHILLED WATER, VALVE V-1, V-2, V-4 AND V-5 SHALL OPEN. UPON CONFIRMATION THAT VALVES V-4 AND V-5 ARE OPEN, START ASSOCIATED PUMPS. FREE COOLING MODE SHALL BE ACTIVE UNTIL OUTSIDE AIR TEMPERATURE EXCEEDS 54°F. IF THERE IS NO CHILLED WATER DEMAND, BASED ON AHU CHILLED WATER VALVE POSITION, OR OUTSIDE TEMPERATURE IS ABOVE 54°F, THE REVERSE SHALL OCCUR.
2. LEAD COOLING TOWER CELL FAN SPEED SHALL MODULATE TO MAINTAIN SETPOINT OF CONDENSER WATER TEMPERATURE TRANSMITTER TS-2, INITIALLY SET 43 DEGREES F. PROVIDE A TIME DELAY, INITIALLY SET 10 MINUTE, BETWEEN STARTS OF COOLING TOWER MOTORS, SO THAT THERE ARE
MAXIMUM 6 STARTS PER HOUR.
FREEZE PROTECTION
1. BASIN HEATERS, SET TO MAINTAIN 38 °F, SHALL OPERATE WITH SELF CONTAINED CONTROLS.
2. FILL FREEZE PROTECTION: WHEN OUTSIDE AIR TEMPERATURE FALLS BELOW 40 °F, STOP OPERATING TOWER FAN EVERY TWO HOURS. AFTER A 1 MINUTE DELAY, OPERATE FAN IN REVERSE AT HALF
SPEED FOR 15 MINUTES. AFTER A 1 MINUTE TIME DELAY, ENABLE LEAD TOWER TO START.
COOLING TOWER MAKE-UP
1. ON A FALL IN TOWER WATER LEVEL, AS SENSED BY ASSOCIATED ELECTRIC WATER LEVEL
CONTROLLER EWL-1, MAKEUP VALVE V-6 SHALL OPEN. ON A RISE IN WATER LEVEL, THE REVERSE
SHALL OCCUR. EWL-1 SHALL BE IN CONTROL FOR ALL TWO CELLS.
POWER FAILURE - AUTOMATIC RESTART
1. LOSS AND RESTORATION OF POWER TO PLANT SHALL BE DETECTED BY THE BAS THROUGH LOSS OF
LOCAL FIELD PANEL OPERATION.
2. UPON RESTORATION OF POWER, DRIVE ALL VALVES TO NORMAL POSITIONS. THE BAS SHALL AUTOMATICALLY RESTART EQUIPMENT THAT WAS IN OPERATION PRIOR TO THE POWER FAILURE.
IMPLEMENT SEQUENCE FOR THE MODE MOST RECENTLY SELECTED. IF THE EQUIPMENT DOES NOT
START, IMPLEMENT PROCEDURE FOR EQUIPMENT FAILURE.
PLANT OPERATION - EQUIPMENT FAILURE
1. IF ANY PIECE OF EQUIPMENT FAILS TO START FOR WHATEVER REASON, THE BAS SHALL
AUTOMATICALLY IMPLEMENT THE NORMAL SEQUENCE TO START THE LAG EQUIPMENT. ADDITIONALLY, AN ALARM SHALL BE INDICATED AT THE OWS.
BASIN SWEEPER FILTRATION SKID
1. PUMP SHALL OPERATE WITH OPERATION OF CONDENSER WATER PUMPS AND FREE COOLING PUMP
CWP-1, CWP-2, CWP-3, OR CWP2D.
2. MOTOR RUN TIME: INDICATE TOTAL PUMP MOTOR RUN TIME.
3. MOTOR STARTS: THE NUMBER OF MOTOR STARTS, AS INDICATED BY PUMP PROOF, SHALL BE
TOTALIZED.
4. EMERGENCY HVAC OFF: ON ACTIVATION OF THE EMERGENCY HVAC OFF SWITCH (EHO), THE PUMP
SHALL STOP.
SAFETIES
1. COOLING TOWER VIBRATION SWITCH: UPON SENSING EXCESS VIBRATION THE COOLING TOWER FAN SHALL STOP AND AN ALARM SHALL BE INDICATED AT THE OWS. THE CHILLER STOP SEQUENCE FOR THE ASSOCIATED CHILLER SHALL BE INITIATED. THE COOLING TOWER SHALL REMAIN LOCKED OUT
FROM FURTHER OPERATION UNTIL THE ALARM IS MANUALLY CLEARED AT THE OWS.
2. UPON ACTUATION OF LOCAL COOLING TOWER DISCONNECT, LDL SHALL DISABLE VFD THROUGH
HARDWIRE INTERLOCK.
COMMISSIONING
1. ALL SETPOINTS, PERCENTAGES, TIME DELAYS, ETC. SHALL BE ADJUSTABLE.
SCHEMATIC
SEQUENCE OF OPERATIONS
WIRING DIAGRAMS
VS-1A VS-1B
V-5A V-5B
P-FILTRATION
TO
BASIN
SWEEPERS
FROM
BASIN
SWEEPERS
BAS
A
O H
X1
120 VAC
OVERLOADS
X2
M
EHO
P-FILTRATION
FILTRATION SKID SELF
CONTAINED CONTROLS
7/1 1/2
4 9
:47 :00
A M
2.0
M
-7
.D W
G
M-701CONTROLS
FI
LE
N
RE
F:
PL
OT
D
AT
E:
2.0
NATIONAL AGRICULTURAL LIBRARY COOLING TOWER
REPLACEMENT
7900 Westpark Dr. | Suite A405 | McLean, VA 22102
(703) 556-8820 | www.summerconsultants.com
SUMMER
CONSULTANTS
I N C O R P O R A T E D
BELTSVILLE, MARYLAND
11 JULY 2024
PROFESSIONAL CERTIFICATION. I HEREBY
CERTIFY THAT THESE DOCUMENTS WERE
PREPARED OR APPROVED BY ME, AND
THAT I AM A DULY LICENSED
PROFESSIONAL ENGINEER UNDER THE
LAWS OF THE STATE OF MARYLAND,
LICENSE NO. 38731, WITH EXPIRATION DATE
OF 05/16/2026.
JURAN, A.
BENZEL, L.
BENZEL, L.
JURAN, A.
AutoCAD SHX Text
SAFETY & HEALTH
AutoCAD SHX Text
DESIGNER
AutoCAD SHX Text
CHECKED BY
AutoCAD SHX Text
PROJECT MANAGER
AutoCAD SHX Text
PPM
AutoCAD SHX Text
EPM
AutoCAD SHX Text
A-E FIRM
AutoCAD SHX Text
AutoCAD SHX Text
SOLICITATION NO.
AutoCAD SHX Text
DATE
AutoCAD SHX Text A
AutoCAD SHX Text D
AutoCAD SHX Text
USDA
AutoCAD SHX Text S
AutoCAD SHX Text U
AutoCAD SHX Text
NO.
AutoCAD SHX Text
DATE
AutoCAD SHX Text
BY
AutoCAD SHX Text
DWG. NO.
AutoCAD SHX Text Service
AutoCAD SHX Text Research
AutoCAD SHX Text Agricultural
AutoCAD SHX Text
REVISIONS
AutoCAD SHX Text
DESCRIPTION
AutoCAD SHX Text
DRAWN BY
AutoCAD SHX Text
SHEET OF
AutoCAD SHX Text
REAL PROPERTY
4 9
:47 :05
A M
2.0
M
-7
.D W
G
M-702COOLING TOWER POINT LIST
18 November 2022
FI
LE
N
RE
F:
PL
OT
D
AT
E:
2.0
NATIONAL AGRICULTURAL LIBRARY COOLING TOWER
REPLACEMENT
7900 Westpark Dr. | Suite A405 | McLean, VA 22102
(703) 556-8820 | www.summerconsultants.com
SUMMER
CONSULTANTS
I N C O R P O R A T E D
BELTSVILLE, MARYLAND
11 JULY 2024
PROFESSIONAL CERTIFICATION. I HEREBY
CERTIFY THAT THESE DOCUMENTS WERE
PREPARED OR APPROVED BY ME, AND
THAT I AM A DULY LICENSED
PROFESSIONAL ENGINEER UNDER THE
LAWS OF THE STATE OF MARYLAND,
LICENSE NO. 38731, WITH EXPIRATION DATE
OF 05/16/2026.
POINTS LIST
POINT NAME DESCRIPTION NETWORK
CONNECTION I/O TYPE
ALARMS TRENDING
FAIL
WARNING LIMIT Cx
FREQUENCY
OPERATING
FREQUENCYLOW HIGH LOW HIGH
VFD-1A
COOLING TOWER FAN X
START/STOP COV COV
SPEED REFERENCE 5min 15min
MOTOR OPERATION X COV COV
VFD FAULT X COV COV
kW 5min 15min
VFD-1B
COOLING TOWER FAN X
START/STOP COV…
This is the start of the file's text. The full file is on GovTribe.