Attachment 3b - EHRM_Moutain Home_EHRM_IFB_Dwgs VOL 1b.pdf
PDF 34 MB Posted
- Attached to
- Y1DA--EHRM Infrastructure Upgrade Construction - Mountain Home Federal contract opportunity
- Solicitation number
- 36C77624B0024
About this file
I apologize, but the file you have referenced appears to be an engineering drawing file (PDF with .pdf extension) for an EHRM Infrastructure Upgrade Construction project at Mountain Home VA Medical Center. Without the actual document contents being displayed, I cannot provide a detailed summary. The filename suggests it is a technical drawing or blueprint (Volume 1b) related to the infrastructure upgrade project, but no specific details are visible in the provided information. To generate a comprehensive summary, I would need the actual contents of the drawing or document.
View the file
Other files for this federal contract opportunity
Show all 40
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
K:
\C
C G
_P R
O
JE
C
TS
\2
2\
-1
_6
-2 2-
0_
M t H om e, T N
_E H
R M
In fra st ru ct ur e U pg ra de s\
0-
D es
D oc s\
2- D ra w in gs
\W O
R
KI
N G
\E -7
.d w g
6/ 6/
0:
:1
AM
ISSUE FOR BIDOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
EHRM INFRASTRUCTURE
UPGRADES DESIGN
JAMES H. QUILLEN VA
MEDICAL CENTER
621-22-700
Revisions: Date:
www. bancroft-ae.com
1471 E. Business Center Dr. Suite 900, Mt. Prospect, IL 60056
T: 847.952.9362
ISSUED FOR BID
05/22/2025
05/22/2025 Bancroft Project No: 22-114
ELECTRICAL - SINGLE LINE, BLDG 200
WG BX
E-706
BLDG 200 MERGENCY AND NORMAL POWER FOR EHRM
EMERGENCY POWER TO EHRM NORMAL POWER TO EHRM
EXISTING PNL MEQ2
480.0 V
ComponentName EXISTING PNL MEQ2 BusLibDesc
PD-0046Manufacturer CUTLER-HAMMER Type HKB Sensor/Trip 225.0 A Plug 225.0 A Settings Thermal Curve (Fixed) INST (5-10 x Trip) 5 (1125A)
CBL-0036
(1) Size 3/0 AWG Copper 3-1/C+G
THHN, PVC
60.0 ft Ampacity 225.0 A
S
P
XF2-0005
Size 150 kVA Pri Delta Sec Wye-Ground %Z 4.5087 % X/R 2.1
CBL-0037
(2) Size 3/0 AWG Copper 3-1/C+G
THHN, PVC
20.0 ft Ampacity 450.0 A
PD-200 01 E
Manufacturer SQUARE D Type LA Sensor/Trip 400.0 A Plug 400.0 A Settings Thermal Curve (Fixed) INST (5-10 x Trip) 5.0 (2000A)
PNL 200 01 E EHRM
208.0 V
ComponentName PNL 200 01 E EHRM BusLibDesc 100-400A
PD-200-1-1 E
Manufacturer SQUARE D Type HJ Sensor/Trip 150.0 A Plug 150.0 A Settings Fixed CBL-0038
(1) Size 500 kcmil Copper 4-1/C+G
THHN, PVC
400.0 ft Ampacity 430.0 A
PNL 200 1-1 E EHRM
208.0 V
ComponentName PNL 200 1-1 E EHRM BusLibDesc 250A
PD-200 1-1 E EHRM
Manufacturer SQUARE D Type HJ Sensor/Trip 150.0 A Plug 150.0 A Settings Fixed
PNL 200 02 E EHRM
208.0 V
ComponentName PNL 200 02 E EHRM BusLibDesc 800A
PD-200-2-2 EManufacturer SQUARE D Type HJ Sensor/Trip 150.0 A Plug 150.0 A Settings Fixed CBL-0040
(1) Size 250 kcmil Copper 4-1/C+G
THHN, PVC
240.0 ft Ampacity 290.0 A
PNL 200 2-2 E EHRM
208.0 V
ComponentName PNL 200 2-2 E EHRM BusLibDesc 225A
PD-200 2-2 E EHRM
Manufacturer SQUARE D Type HJ Sensor/Trip 150.0 A Plug 150.0 A Settings Fixed
EXISTING PNL MSG 200
480.0 V
ComponentName EXISTING PNL MSG 200 BusLibDesc
PD-200-1-2 EManufacturer SQUARE D Type HJ Sensor/Trip 150.0 A Plug 150.0 A Settings Fixed CBL-0039
(1) Size 500 kcmil Copper 4-1/C+G
THHN, PVC
400.0 ft Ampacity 430.0 A
PNL 200 1-2 E EHRM
208.0 V
ComponentName PNL 200 1-2 E EHRM BusLibDesc 250A
PD-200 1-2 E EHRM
Manufacturer SQUARE D Type HJ Sensor/Trip 150.0 A Plug 150.0 A Settings Fixed
PD-0048Manufacturer CUTLER-HAMMER Type HKB Sensor/Trip 225.0 A Plug 225.0 A Settings Thermal Curve (Fixed) INST (5-10 x Trip) 5 (1125A)
CBL-0041
(1) Size 3/0 AWG Copper 3-1/C+G
THHN, PVC
320.0 ft Ampacity 225.0 A
S
P
XF2-0006
Size 150 kVA Pri Delta Sec Wye-Ground %Z 4.5087 %
X/R 2.1 CBL-0042
(2) Size 3/0 AWG Copper 3-1/C+G
THHN, PVC
20.0 ft Ampacity 450.0 A
PD-200 01 E1
Manufacturer SQUARE D Type LC Sensor/Trip 600.0 A Plug 600.0 A Settings Thermal Curve
INST LO (3000A)
PD-0136
Manufacturer SCHNEIDER Type INS250
PD-200-1-2 E1Manufacturer SQUARE D Type HJ Sensor/Trip 150.0 A Plug 150.0 A Settings Fixed CBL-0050
(1) Size 500 kcmil Copper 4-1/C+G
THHN, PVC
208.0 ft Ampacity 430.0 A
PNL 200 2 1 E EHRM
208.0 V
ComponentName PNL 200 2 1 E EHRM BusLibDesc 400A
PD-200 1-2 E EHRM1
Manufacturer SQUARE D Type KA Sensor/Trip 250.0 A Plug 250.0 A Settings Thermal Curve
INST LO (1250A)
PD-0047Manufacturer CUTLER-HAMMER Type HKB Sensor/Trip 225.0 A Plug 225.0 A Settings Thermal Curve (Fixed) INST (5-10 x Trip) 5 (1125A)
CBL-0043
(1) Size 3/0 AWG Copper 3-1/C+G
THHN, PVC
60.0 ft Ampacity 225.0 A
S
P
XF2-0007
Size 150 kVA Pri Delta Sec Wye-Ground %Z 4.5087 % X/R 2.1
CBL-0044
(2) Size 3/0 AWG Copper 3-1/C+G
THHN, PVC
20.0 ft Ampacity 450.0 A
PD-200 01 E0
Manufacturer SQUARE D Type LC Sensor/Trip 600.0 A Plug 600.0 A Settings Thermal Curve
INST LO (3000A)
PNL 200 01 N EHRM
208.0 V
ComponentName PNL 200 01 N EHRM BusLibDesc 800A
PD-200-1-1 E0
Manufacturer SQUARE D Type HJ Sensor/Trip 150.0 A Plug 150.0 A Settings Fixed
CBL-0045
(1) Size 500 kcmil Copper 4-1/C+G
THHN, PVC
400.0 ft Ampacity 430.0 A
PNL 200 1-1 N EHRM
208.0 V
ComponentName PNL 200 1-1 N EHRM BusLibDesc 250A
PD-200 1-1 E EHRM0
Manufacturer SQUARE D Type HJ Sensor/Trip 150.0 A Plug 150.0 A Settings Fixed
PD-200-1-2 E0Manufacturer SQUARE D Type HJ Sensor/Trip 150.0 A Plug 150.0 A Settings Fixed CBL-0048
(1) Size 500 kcmil Copper 4-1/C+G
THHN, PVC
400.0 ft Ampacity 430.0 A
PNL 200 1-2 N EHRM0
208.0 V
ComponentName PNL 200 1-2 N EHRM0 BusLibDesc 250A
PD-200 1-2 E EHRM0
Manufacturer SQUARE D Type HJ Sensor/Trip 150.0 A Plug 150.0 A Settings Fixed
PD-0049Manufacturer CUTLER-HAMMER Type HKB Sensor/Trip 225.0 A Plug 225.0 A Settings
Thermal Curve (Fixed) INST (5-10 x Trip) 5 (1125A)
CBL-0046
(1) Size 3/0 AWG Copper 3-1/C+G
THHN, PVC
304.0 ft Ampacity 225.0 A
S
P
XF2-0008
Size 150 kVA Pri Delta Sec Wye-Ground %Z 4.5087 %
X/R 2.1 CBL-0047
(2) Size 3/0 AWG Copper 3-1/C+G
THHN, PVC
20.0 ft Ampacity 450.0 A
PD-200 01 E2
Manufacturer CUTLER-HAMMER Type HLB Sensor/Trip 400.0 A Plug 400.0 A Settings Thermal Curve (Fixed) INST (5-10 x Trip) 5 (2000A)
PNL 200 02 N EHRM
208.0 V
ComponentName PNL 200 02 N EHRM BusLibDesc 100-400A
PD-200-1-1 E1
Manufacturer SQUARE D Type HJ Sensor/Trip 150.0 A Plug 150.0 A Settings Fixed CBL-0049
(1) Size 3/0 AWG Copper 4-1/C+G
THHN, PVC
180.0 ft Ampacity 225.0 A
PNL 200 2-1 N EHRM
208.0 V
ComponentName PNL 200 2-1 N EHRM BusLibDesc 250A
PD-200 1-1 E EHRM1
Manufacturer SQUARE D Type HJ Sensor/Trip 150.0 A Plug 150.0 A Settings Fixed
PD-200-1-2 E2Manufacturer SQUARE D Type HJ Sensor/Trip 150.0 A Plug 150.0 A Settings Fixed CBL-0051
(1) Size 500 kcmil Copper 4-1/C+G
THHN, PVC
240.0 ft Ampacity 430.0 A
PNL 200 2-2 N EHRM
208.0 V
ComponentName PNL 200 2-2 N EHRM BusLibDesc 250A
PD-200 1-2 E EHRM2
Manufacturer SQUARE D Type HJ Sensor/Trip 150.0 A Plug 150.0 A Settings Fixed
PD-0137
Manufacturer SCHNEIDER Type INS250
INDUSTRY STANDARDS
1.8.2.8 TELECOMMUNICATIONS INDUSTRY ASSOCIATION (TIA):
(A) TIA-120 SERIES -TELECOMMUNICATIONS LAND MOBILE COMMUNICATIONS (APCO/PROJECT 25).
(B) TIA-155- GUIDELINES FOR THE ASSESMENT AND MITIGATION OF INSTALLED CATEGORY 6 CABLING TO SUPPORT 10GBASE-T.
(C) TIA TSB - 162 - A - TELECOMMUNICATIONS CABLING GUIDELINES FOR WIRELESS ACCESS POINTS.
(D) TIIA - 222 - STRUCTURAL STANDARD FOR ANTENNA SUPPORTING STRUCTURES AND ANTENNAS.
(E) TIA - 472DOOO - B - FIBER OPTIC COMMUNICATIONS CABLE FOR OUTSIDE PLANT USE.
(F) TIA - 568 - REVISION/EDITION: C COMMERCIAL BUILDING TELECOMMUNICATIONS CABLING STANDARD SET:
a. TIA - 568 .0 (REV. E) GENERIC TELECOMMUNICATIONS CABLING FOR CUSTOMER PREMISES,
b. TIA - 568 .1 (REV. E) COMMERCIAL BUILDING TELECOMMUNICATIONS CABLING
STANDARD PART 1: GENERAL REQUIREMENTS,
c. TIA - 568 .2 (REV. D) COMMERCIAL BUILDING TELECOMMUNICATIONS CABLING STANDARD - PART 2: BALANCED
TWISTED PAIR CABLING COMPONENTS,
d. TIA - 568.3 (REV. D) OPTICAL FIBER CABLING COMPONENTS STANDARD, AND
e. TIA - 568.4 (REV. D) BROADBAND COAXIAL CABLING AND COMPONENTS STANDARD (WITH ADDENDUMS AND ERRATA).
f. TIA - 568.2-D PERFORMANCE CRITERIA FOR CATEGORY 6A TWISTED PAIR SYSTEM
(G) TIA - 569 (REV. E)- TELECOMMUNICATIONS PATHWAYS AND SPACES.
(H) TIA/EIE - 590 (REV. A) - STANDARD FOR PHYSICAL LOCATION AND PROTECTION OF BELOW GROUND FIBER OPTIC CABLE PLANT.
(I) ANSI/TIA - 606 (REV. D) - ADMINISTRATION STANDARD FOR TELECOMMUNICATIONS INFRASTRUCTURE.
(J) TIA - 607 (REV. D) - GENERIC TELECOMMUNICATIONS BONDING AND GROUNDING (EARTHING) FOR CUSTOMER PREMISES.
(K) ANSI/TIA - 758 (REV. B) - CUSTOMER-OWNED OUTSIDE PLANT TELECOMMUNICATION INFRASTRUCTURE STANDARD.
(L) ANSI/TIA - 862 (REV. B)- BUILDING AUTOMATION SYSTEMS CABLING STANDARD.
(M) TIA - 942 (REV. B) - TELECOMMUNICATIONS INFRASTRUCTURE STANDARD FOR DATA CENTERS.
(N) TIA - 1179 (REV. A)- HEALTHCARE FACILITY TELECOMMUNICATIONS INFRASTRUCTURE STANDARD.
GENERAL TELECOMMUNICATIONS NOTES
1. FOR GENERAL TELECOMMUNICATION INFORMATION AND SOW SEE DESIGN NARRATIVE/BASIS OF DESIGN
NARRATIVE.
2. SCOPE INCLUDES MODIFICATIONS AND ADDITIONS TO EXISTING ACCESS CONTROL AND VIDEO SURVEILLANCE SYSTEMS. CONTRACTORS TO PROVIDE ALL LABOR AND MATERIALS, INCLUDING COMPONENTS, REQUIRE TO
ACHIEVE A FULLY FUNCTIONAL SYSTEM.
3. PROJECT COORDINATION- NO SYSTEMS OR COMPONENTS SHALL BE DISRUPTED OUT OF PROJECT SEQUENCE;
COORDINATE ALL SERVICES DISRUPTIONS WITH THE PROJECT COR.
4. CARE SHALL BE TAKEN AS TO NOT DISRUPT OR DAMAGE EXISTING SYSTEMS INCLUDING BUT NOT LIMITED TO CATV, ACCESS CONTROL, NURSE CALL, BUILDING AUTOMATION, DISTRIBUTED ANTENNA, PAGING.
5. CONTRACTOR SHALL VERIFY ALL COMPONENTS CONNECTED TO EXISTING TELECOMMUNICATION GROUNDING BUSBARS HAVE BEEN TAKEN OUT OF SERVICE OR HAS BEEN BONDED TO THE NEW TELECOMMUNICATION
GROUNDING/BONDING SYSTEM PRIOR TO REMOVING EXISTING GROUNDING COMPONENTS.
6. CONTRACTOR SHALL VERIFY EXISTING CONDITION AND PROMPTLY REPORT ANY DRAWING DISCREPANCIES TO
THE PROJECT COR AND ARCHITECT.
7. IN ADDITION TO PRIMARY PATHWAYS, CABLE TRAY SHALL BE PROVIDED WITH CABLE BUNDLES EXCEED 24
CABLES.
8. FIRE RATED MECHANICAL SLEEVE ASSEMBLES SHALL BE PROVIDED WHEN PASSING THROUGH FIRE RATED
PARTITIONS ASSUMING 40% FILL AND 50% SPARE CAPACITY
9. CONTRACTOR SHALL ENSURE THAT ALL PENETRATIONS BE SEALED AS REQUIRED TO MEET EXISTING RATINGS.
REFER TO SPECIFICATION 07 84 00.
10. EXISTING ROUTING FOR TELECOM DROPS SHALL BE MAINTAINED TO THE FULLEST EXTENT POSSIBLE. IT IS UNDERSTOOD THAT SOME OF THE NEW CABLE WILL BE PLACED WITHIN NEW CABLE TRAY, HOWEVER THE
EXISTING CONDUIT TO THE DATA DROP SHALL BE REUSED.
11. THE INDUSTRY STANDARD OF 295 FEET MAXIMUM HORIZONTAL CABLE LENGTH SHALL STRICTLY ADHERED TO. IF
THIS REQUIREMENT CAN NOT BE MET, CONTACT TO PROJECT COR IMMEDIATELY.
12. ALL CABLE TO WIRELESS ACCESS POINTS (WAPS) SHALL BE REPLACED WITH CAT 6A CABLES. PROVIDE A NEW CAT 6A SINGLE JACK SURFACE MOUNTED BOX ABOVE THE CEILING WHERE EXISTING WAPS ARE LOCATED. ALL
EXISTING WIRELESS ACCESS POINT DEVICES SHALL REMAIN IN PLACE.
13. REFERENCE THE U.S. DEPARTMENT OF VETERAN AFFAIRS OFFICE OF INFORMATION AND TECHNOLOGY INFRASTRUCTURE STANDARD FOR TELECOMMUNICATIONS SPACES VERSION 3.1 (ISTSv3.1) FOR ADDITIONAL
INFORMATION.
ICT GENERAL NOTES
TT-000
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
G :\B uh ol tz P ro fe ss io na l E ng , I nc \B
PE
P ro je ct s\
BP
E
Pr oj ec ts
3\
5-
Ba nc ro ft
- T
N V
A H os pi ta l\B
PE
R
EV
IS
IO
N
3\
TT
-0
.d w g
5/
/2
8:
:1
AM
ISSUE FOR BIDOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
EHRM INFRASTRUCTURE
UPGRADES DESIGN
JAMES H. QUILLEN VA
MEDICAL CENTER
621-22-700
Revisions: Date:
www. bancroft-ae.com
3300 Dundee RD.
Northbrook, IL 60062
T: 847.952.9362
Bancroft Project No: 22-114
UHOLTZ ROFESSIONAL B P
ENGINEERING, INC.
154 Tuskawilla Rd., Ste. 1380 Winter Springs FL 32708 Ph 407-327-3300
CA 00009600 05/22/2025
ISSUED FOR BID 05/22/2025
BB BA,GM
R
R M
S RADIO CHANNEL SELECTOR FACILITIES, MTD. 4'-6" (1372 mm) AFF
UNLESS OTHERWISE NOTED.
SPEAKER PROGRAM SELECTOR SWITCH & VOLUME CONTROL MTD.
4'-6" (1372 mm) AFF UNLESS OTHERWISE NOTED.
INTERCOM STATION (REFER TO SPECS. FOR FUNCTIONAL
OPERATION OF INSTRUMENT & TYPE REQUIRED)
INTERCOM STAFF STATION.
ADO AUTOMATIC DOOR OPENER
DB DURESS BUTTON
DAS ANTENNA CELLULAR
DAP
DAC
CR
AIP
CR/K
REX
KP
RX
ES
ML
CCP
MID
GB
DC
WS
DIVERSITY PATCH ANTENNA
ELECTRONIC SAFETY AND SECURITY SYMBOLS
WALL MOUNTED CARD READER
AIPHONE
KEYPAD LOCK
ACCESS CONTROL PANEL
ROOF POLE MOUNTED SECURITY CAMERA
CAMERA CONTROL PANEL
WALL MOUNTED CARD READER WITH KEYPAD
REQUEST TO EXIT MOTION
DOOR LOCKING MECHANISM/ELECT STRIKE
DOOR LOCKING MECHANISM/MAG LOCK
ACCESS CONTROL POWER SUPPLY
REQUEST TO EXIT PUSH BUTTON
MOTION INTRUSION DETECTOR
GLASS BREAK SENSOR
DOOR CONTACT
DOOR OPENER WAVE SENSOR FOR MOTORIZED DOOR
ESSEX ELECTORNICS #32NF3X.
RFID WALL MOUNTED PATIENT WRISTBAND READER
OVER THE DOOR ALARM SENSOR PERVENTIVEDS
ACP
ACPS
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
G :\B uh ol tz P ro fe ss io na l E ng , I nc \B
PE
P ro je ct s\
BP
E
Pr oj ec ts
3\
5-
Ba nc ro ft
- T
N V
A H os pi ta l\B
PE
R
EV
IS
IO
N
3\
TT
-1
.0 1.
dw g
3/
/2
:0 1:
A
M
ISSUE FOR BIDOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
EHRM INFRASTRUCTURE
UPGRADES DESIGN
JAMES H. QUILLEN VA
MEDICAL CENTER
621-22-700
Revisions: Date:
www. bancroft-ae.com
3300 Dundee RD.
Northbrook, IL 60062
T: 847.952.9362
Bancroft Project No: 22-114
UHOLTZ ROFESSIONAL B P
ENGINEERING, INC.
154 Tuskawilla Rd., Ste. 1380 Winter Springs FL 32708 Ph 407-327-3300
CA 00009600 05/22/2025
ISSUED FOR BID 05/22/2025 TT-1.01
COMMUNICATIONS
PATHWAY SITE PLAN
BB BA,GM
PATHWAY, RACK, BONDING CONDUCTOR JOIN REQUIREMENTS
NOTES: ALL GROUNDING SHALL BE DONE IN ACCORDANCE WITH ANSI/TIA-607-D “COMMERCIAL
BUILDING GROUNDING (EARTHING) AND BONDING REQUIREMENTS FOR
TELECOMMUNICATIONS”, NFPA 70, AND IN COMPLIANCE WITH LOCAL CODES.
ALL EQUIPMENT SHALL BE GROUNDED PER MANUFACTURER’S INSTRUCTIONS.
EXAMPLE
“A”
EXAMPLE
“B”
RACK BONDING
CONDUCTORS –
ALL
CONDUCTORS
ROUTED TO
PBB/SBB
IRREVERSIBLE CRIMP
CONNECTOR
TO PBB/SBB
TOP-MOUNTED
RBB
RACK BONDING
CONDUCTOR
(6 AWG)
TEBC
(TELECOMMUNICATIONS
EQUIPMENT BONDING
CONDUCTOR – 6 AWG)
IRREVERSIBLE
COMPRESSION
CONNECTION
UNIT BONDING CONDUCTOR (6 AWG)
RACK BONDING CONDUCTOR (6 AWG)
INDIVIDUAL EQUIPMENT BONDING
CONDUCTORS FROM EACH PIECE OF
EQUIPMENT AND RACK TO THE RACK
BONDING CONDUCTOR
RACK ISOLATION PADS (IF
APPLICABLE)
RACK BONDING CONDUCTOR
EXTENDED TO BOTTOM OF RACK
TO ACCOMMODATE FUTURE
GROWTH
TWO-HOLE COMPRESSION
LUGS (RACKS SHALL NOT BE
MODIFIED IF ONLY
ONE-HOLE IS PROVIDED; USE
ONE-HOLE COMPRESSION
LUGS IN THIS CASE)
TWO HOLE STRAP OR
CADWELD CONNECTION TYPE
''LK'', TYPICAL
4"
MIN.
MOUNTING BRACKETS
FIBERGLASS INSULATORS
INSULATED COPPER GROUND
CONDUCTOR TO BUILDING GROUNDING
ELECTRODE CONDUCTOR
NOTES:
1. PREDRILLED BOLT HOLE SIZE AND SPACING AS REQUIRED FOR INDICATED TERMINATIONS.
2. PROVIDE LENGTH SUFFICIENT FOR ALL INDICATED TERMINATIONS AND 20% SPARE MOUNTING SPACE.
3. GROUND BAR SHALL BE MOUNTED MINIMUM 2" OFF WALL AND 12" AFF.
4. FIBERGLASS INSULATORS SHALL HAVE A MINIMUM DIELECTRIC STRENGTH OF 15kV.
1 GROUND BUS DETAIL NTS 2 DATA PORT NTS
CAT 6A DATA CABLE WITH
WHITE KEYSTONE
CAT 6A DATA CABLE WITH
RED KEYSTONE
CAT 6A
BLDG#-SECTION#
-FLOOR#-JACKID#
LABEL
SPARE WITH BLANK COVER
FOR FUTURE USE
CAT 6A VOICE CABLE
WITH BLUE KEYSTONE
NOTE:
- PROVIDE NYLON PULLING
ROPE FOR FUTURE CABLE
INSERTION
- PORT COVER SHALL BE
IVORY
- LABELING SHALL BE PER
EIA/TIA 606 STANDARD.
LABELING SCHEME SHALL
BE IN ACCORDANCE WITH
THE FOLLOWING: 'ROOM
NUMBER'- 'RECEPTACLE
NUMBER'- 'PORT NUMBER '.
1 1/4" EMT CONDUIT STUBBED TO
THE NEAREST CABLE
TRAY AND GROMMET
3 CABLE TRAY BONDING DETAIL NTS
#6 COPPER CABLE
TRAY BONDING
CONDUCTOR. TYPICAL
AT EACH SECTION
CONNECTION POINT
ALL BASKET TRAY SHALL
BE 6” DEEP & 12” WIDE
TO SSP OR SSB
IRREVERSIBLE CRIMP
CONNECTOR (TYPICAL)
TELECOMMUNICATIONS
EQUIPMENT BONDING
CONDUCTOR (TEBC)
DIRECTLY BONDED TO RBB
#6 COPPER.
BASKET TRAY GROUNDING
LUG (TYPICAL)
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
G :\B uh ol tz P ro fe ss io na l E ng , I nc \B
PE
P ro je ct s\
BP
E
Pr oj ec ts
3\
5-
Ba nc ro ft
- T
N V
A H os pi ta l\B
PE
R
EV
IS
IO
N
3\
TT
-5
.0 1.
dw g
5/
/2
9:
:5
AM
ISSUE FOR BIDOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
EHRM INFRASTRUCTURE
UPGRADES DESIGN
JAMES H. QUILLEN VA
MEDICAL CENTER
621-22-700
Revisions: Date:
www. bancroft-ae.com
3300 Dundee RD.
Northbrook, IL 60062
T: 847.952.9362
Bancroft Project No: 22-114
UHOLTZ ROFESSIONAL B P
ENGINEERING, INC.
154 Tuskawilla Rd., Ste. 1380 Winter Springs FL 32708 Ph 407-327-3300
CA 00009600 05/22/2025
ISSUED FOR BID 05/22/2025 TT-5.01
BB BA,GM
ICT - DETAILS
GRID FRAME
FIRE STOP
SEALANT
TE
LE
CO
M
R
OO
M
CO
M
M
ON
A
RE
A
RE-ENTERABLE FIRE RATED PATHWAY
GRID FOR BACKBONE FIBER, CATEGORY
6A, HORIZONTAL OM4, AND SECURITY
CABLING CONNECTIVITY BETWEEN
TELECOM ROOM AND COMMON AREAS.
SEE PLAN VIEW THIS SHEET.
6" W
AL
L
OP
EN
IN
G
NOTE:
SPECIFIED TECHNOLOGIES INC. EZ PATH
SERIES 44+ (OR COMPARABLE)
OPENING IN WALL. SEE
SECTION VIEW THIS SHEET.
SEE TELECOM ENLARGED PLAN
SHEETS FOR LOCATIONS
FOUR RE-ENTERABLE FIRE RATED
SLEEVES FOR CAT6A, FIBER AND
SECURITY CABLING. CABLE FILL
CAPACITY PER CODE STANDARD.
6"
18"
FLANGE OVERLAP
NOTE:
SPECIFIED TECHNOLOGIES
INC. EZ PATH SERIES 44+
(OR COMPARABLE)
1 2"
18"
EIGHT RE-ENTERABLE FIRE RATED
SLEEVES FOR CAT6A, FIBER AND
SECURITY CABLING. CABLE FILL
CAPACITY PER CODE STANDARD.
OPENING IN WALL. SEE
SECTION VIEW THIS SHEET.
SEE TELECOM ENLARGED PLAN
SHEETS FOR LOCATIONS
NOTE:
SPECIFIED TECHNOLOGIES
INC. EZ PATH SERIES 44+
(OR COMPARABLE)
OPENING IN WALL. SEE
SECTION VIEW THIS SHEET.
SEE TELECOM ENLARGED PLAN
SHEETS FOR LOCATIONS
TWO RE-ENTERABLE FIRE RATED
SLEEVES FOR CAT6A, FIBER AND
SECURITY CABLING. CABLE FILL
CAPACITY PER CODE STANDARD.
6"
10"
FLANGE OVERLAP
NOTE:
SPECIFIED TECHNOLOGIES
INC. EZ PATH SERIES 44+
(OR COMPARABLE)
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
G :\B uh ol tz P ro fe ss io na l E ng , I nc \B
PE
P ro je ct s\
BP
E
Pr oj ec ts
3\
5-
Ba nc ro ft
- T
N V
A H os pi ta l\B
PE
R
EV
IS
IO
N
3\
TT
-5
.0 2.
dw g
5/
/2
8:
:2
AM
ISSUE FOR BIDOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
EHRM INFRASTRUCTURE
UPGRADES DESIGN
JAMES H. QUILLEN VA
MEDICAL CENTER
621-22-700
Revisions: Date:
www. bancroft-ae.com
3300 Dundee RD.
Northbrook, IL 60062
T: 847.952.9362
Bancroft Project No: 22-114
UHOLTZ ROFESSIONAL B P
ENGINEERING, INC.
154 Tuskawilla Rd., Ste. 1380 Winter Springs FL 32708 Ph 407-327-3300
CA 00009600 05/22/2025
ISSUED FOR BID 05/22/2025 TT-5.02
BB BA,GM
FIRE PENETRATION - DETAILS
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
G :\B uh ol tz P ro fe ss io na l E ng , I nc \B
PE
P ro je ct s\
BP
E
Pr oj ec ts
3\
5-
Ba nc ro ft
- T
N V
A H os pi ta l\B
PE
R
EV
IS
IO
N
3\
TT
-6
.0 0-
SE
R
IE
S.
dw g
5/ 6/
:5
1:
P M
ISSUE FOR BIDOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
EHRM INFRASTRUCTURE
UPGRADES DESIGN
JAMES H. QUILLEN VA
MEDICAL CENTER
621-22-700
Revisions: Date:
www. bancroft-ae.com
3300 Dundee RD.
Northbrook, IL 60062
T: 847.952.9362
Bancroft Project No: 22-114
UHOLTZ ROFESSIONAL B P
ENGINEERING, INC.
154 Tuskawilla Rd., Ste. 1380 Winter Springs FL 32708 Ph 407-327-3300
CA 00009600 05/22/2025
ISSUED FOR BID 05/22/2025 TT-6.01
BB BA,GM
OVERALL SITE
RISER DIAGRAM
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
G :\B uh ol tz P ro fe ss io na l E ng , I nc \B
PE
P ro je ct s\
BP
E
Pr oj ec ts
3\
5-
Ba nc ro ft
- T
N V
A H os pi ta l\B
PE
R
EV
IS
IO
N
3\
TT
-6
.0 0-
SE
R
IE
S.
dw g
5/ 6/
:5
1:
P M
ISSUE FOR BIDOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
EHRM INFRASTRUCTURE
UPGRADES DESIGN
JAMES H. QUILLEN VA
MEDICAL CENTER
621-22-700
Revisions: Date:
www. bancroft-ae.com
3300 Dundee RD.
Northbrook, IL 60062
T: 847.952.9362
Bancroft Project No: 22-114
UHOLTZ ROFESSIONAL B P
ENGINEERING, INC.
154 Tuskawilla Rd., Ste. 1380 Winter Springs FL 32708 Ph 407-327-3300
CA 00009600 05/22/2025
ISSUED FOR BID 05/22/2025 TT-6.02
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
G :\B uh ol tz P ro fe ss io na l E ng , I nc \B
PE
P ro je ct s\
BP
E
Pr oj ec ts
3\
5-
Ba nc ro ft
- T
N V
A H os pi ta l\B
PE
R
EV
IS
IO
N
3\
TT
-6
.0 0-
SE
R
IE
S.
dw g
5/ 6/
:5
1:
P M
ISSUE FOR BIDOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
EHRM INFRASTRUCTURE
UPGRADES DESIGN
JAMES H. QUILLEN VA
MEDICAL CENTER
621-22-700
Revisions: Date:
www. bancroft-ae.com
3300 Dundee RD.
Northbrook, IL 60062
T: 847.952.9362
Bancroft Project No: 22-114
UHOLTZ ROFESSIONAL B P
ENGINEERING, INC.
154 Tuskawilla Rd., Ste. 1380 Winter Springs FL 32708 Ph 407-327-3300
CA 00009600 05/22/2025
ISSUED FOR BID 05/22/2025 TT-6.03
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
G :\B uh ol tz P ro fe ss io na l E ng , I nc \B
PE
P ro je ct s\
BP
E
Pr oj ec ts
3\
5-
Ba nc ro ft
- T
N V
A H os pi ta l\B
PE
R
EV
IS
IO
N
3\
TT
-6
.0 0-
SE
R
IE
S.
dw g
5/ 6/
:5
1:
P M
ISSUE FOR BIDOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
EHRM INFRASTRUCTURE
UPGRADES DESIGN
JAMES H. QUILLEN VA
MEDICAL CENTER
621-22-700
Revisions: Date:
www. bancroft-ae.com
3300 Dundee RD.
Northbrook, IL 60062
T: 847.952.9362
Bancroft Project No: 22-114
UHOLTZ ROFESSIONAL B P
ENGINEERING, INC.
154 Tuskawilla Rd., Ste. 1380 Winter Springs FL 32708 Ph 407-327-3300
CA 00009600 05/22/2025
ISSUED FOR BID 05/22/2025 TT-6.04
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
G :\B uh ol tz P ro fe ss io na l E ng , I nc \B
PE
P ro je ct s\
BP
E
Pr oj ec ts
3\
5-
Ba nc ro ft
- T
N V
A H os pi ta l\B
PE
R
EV
IS
IO
N
3\
TT
-7
.0 0-
SE
R
IE
S.
dw g
5/ 6/
:5
3:
P M
ISSUE FOR BIDOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
EHRM INFRASTRUCTURE
UPGRADES DESIGN
JAMES H. QUILLEN VA
MEDICAL CENTER
621-22-700
Revisions: Date:
www. bancroft-ae.com
3300 Dundee RD.
Northbrook, IL 60062
T: 847.952.9362
Bancroft Project No: 22-114
UHOLTZ ROFESSIONAL B P
ENGINEERING, INC.
154 Tuskawilla Rd., Ste. 1380 Winter Springs FL 32708 Ph 407-327-3300
CA 00009600 05/22/2025
ISSUED FOR BID 05/22/2025 TT-7.01
BB BA,GM
SPLICING DIAGRAM
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
G :\B uh ol tz P ro fe ss io na l E ng , I nc \B
PE
P ro je ct s\
BP
E
Pr oj ec ts
3\
5-
Ba nc ro ft
- T
N V
A H os pi ta l\B
PE
R
EV
IS
IO
N
3\
TT
-7
.0 0-
SE
R
IE
S.
dw g
5/ 6/
:5
3:
P M
ISSUE FOR BIDOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
EHRM INFRASTRUCTURE
UPGRADES DESIGN
JAMES H. QUILLEN VA
MEDICAL CENTER
621-22-700
Revisions: Date:
www. bancroft-ae.com
3300 Dundee RD.
Northbrook, IL 60062
T: 847.952.9362
Bancroft Project No: 22-114
UHOLTZ ROFESSIONAL B P
ENGINEERING, INC.
154 Tuskawilla Rd., Ste. 1380 Winter Springs FL 32708 Ph 407-327-3300
CA 00009600 05/22/2025
ISSUED FOR BID 05/22/2025 TT-7.02
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
G :\B uh ol tz P ro fe ss io na l E ng , I nc \B
PE
P ro je ct s\
BP
E
Pr oj ec ts
3\
5-
Ba nc ro ft
- T
N V
A H os pi ta l\B
PE
R
EV
IS
IO
N
3\
TT
-7
.0 0-
SE
R
IE
S.
dw g
5/ 6/
:5
3:
P M
ISSUE FOR BIDOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
EHRM INFRASTRUCTURE
UPGRADES DESIGN
JAMES H. QUILLEN VA
MEDICAL CENTER
621-22-700
Revisions: Date:
www. bancroft-ae.com
3300 Dundee RD.
Northbrook, IL 60062
T: 847.952.9362
Bancroft Project No: 22-114
UHOLTZ ROFESSIONAL B P
ENGINEERING, INC.
154 Tuskawilla Rd., Ste. 1380 Winter Springs FL 32708 Ph 407-327-3300
CA 00009600 05/22/2025
ISSUED FOR BID 05/22/2025 TT-7.03
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
G :\B uh ol tz P ro fe ss io na l E ng , I nc \B
PE
P ro je ct s\
BP
E
Pr oj ec ts
3\
5-
Ba nc ro ft
- T
N V
A H os pi ta l\B
PE
R
EV
IS
IO
N
3\
TT
-7
.0 0-
SE
R
IE
S.
dw g
5/ 6/
:5
3:
P M
ISSUE FOR BIDOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
EHRM INFRASTRUCTURE
UPGRADES DESIGN
JAMES H. QUILLEN VA
MEDICAL CENTER
621-22-700
Revisions: Date:
www. bancroft-ae.com
3300 Dundee RD.
Northbrook, IL 60062
T: 847.952.9362
Bancroft Project No: 22-114
UHOLTZ ROFESSIONAL B P
ENGINEERING, INC.
154 Tuskawilla Rd., Ste. 1380 Winter Springs FL 32708 Ph 407-327-3300
CA 00009600 05/22/2025
ISSUED FOR BID 05/22/2025 TT-7.04
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
G :\B uh ol tz P ro fe ss io na l E ng , I nc \B
PE
P ro je ct s\
BP
E
Pr oj ec ts
3\
5-
Ba nc ro ft
- T
N V
A H os pi ta l\B
PE
R
EV
IS
IO
N
3\
TT
-7
.0 0-
SE
R
IE
S.
dw g
5/ 6/
:5
3:
P M
ISSUE FOR BIDOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
EHRM INFRASTRUCTURE
UPGRADES DESIGN
JAMES H. QUILLEN VA
MEDICAL CENTER
621-22-700
Revisions: Date:
www. bancroft-ae.com
3300 Dundee RD.
Northbrook, IL 60062
T: 847.952.9362
Bancroft Project No: 22-114
UHOLTZ ROFESSIONAL B P
ENGINEERING, INC.
154 Tuskawilla Rd., Ste. 1380 Winter Springs FL 32708 Ph 407-327-3300
CA 00009600 05/22/2025
ISSUED FOR BID 05/22/2025 TT-7.05
TYP
DC
ES
CR/KREX
MID
7'- 3"
4'-3"
TYP
TYP
4'-3"
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
G :\B uh ol tz P ro fe ss io na l E ng , I nc \B
PE
P ro je ct s\
BP
E
Pr oj ec ts
3\
5-
Ba nc ro ft
- T
N V
A H os pi ta l\B
PE
R
EV
IS
IO
N
3\
TT
-B
-1
0B .d w g
5/
/2
8:
:0
AM
ISSUE FOR BIDOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
EHRM INFRASTRUCTURE
UPGRADES DESIGN
JAMES H. QUILLEN VA
MEDICAL CENTER
621-22-700
Revisions: Date:
www. bancroft-ae.com
3300 Dundee RD.
Northbrook, IL 60062
T: 847.952.9362
Bancroft Project No: 22-114
UHOLTZ ROFESSIONAL B P
ENGINEERING, INC.
154 Tuskawilla Rd., Ste. 1380 Winter Springs FL 32708 Ph 407-327-3300
CA 00009600 05/22/2025
ISSUED FOR BID 05/22/2025
GENERAL NOTES
A. FOR GENERAL NOTES AND LEGENDS REFER TO SHEET TT-000.
B. EXISTING IT/TR/OI&T ROOMS TO REMAIN ACTIVE DURING CONSTRUCTION. G.C. TO PROTECT EQUIPMENT
DURING CONSTRUCTION WITH VISQUEEN. CONTRACTOR TO ENSURE CONTINUOUS OPERATION OF EQUIPMENT.
C. NOT ALL KEY NOTES APPLY TO ALL PLAN SHEETS. G.C. TO APPLY ONLY AS INDICATED PER EACH SHEET.
D. APPLY FIRE RATED SEALANT TO ALL EXISTING AND NEW PENETRATIONS IN EXISTING WALLS TO MAKE EXISTING
WALLS A 1 HR ASSEMBLY. FOR ALL NEW PENETRATIONS REFERENCE DETAILS ON SHEET TT-5.02.
D. ALL LEGACY SYSTEMS CONNECTIONS THAT ARE NON-OIT (TELEMETRY, NURSE CALL, SECURITY, ETC.) THAT ARE NOT BEING REPLACED AND/OR RELOCATED SHALL REMAIN IN SERVICE IN THEIR CURRENT LOCATION AFTER OIT
RELATED CONNECTIONS HAVE BEEN REPLACES AND/OR RELOCATED.
FLOOR PLAN KEYNOTESX
FLOOR PLAN LEGEND
4'X8' AC GRADE 3/4" TRADE SIZE FIRE RATED PLYWOOD BACKBOARD
PAINTED HIGH GLOSS WHITE WITH (2) COATS OF FIRE RESISTANT PAINT
FOR SERVICE PROVIDER/SECURITY/VIDEO/ETC. AROUND PERIMETER
WALLS OF TRS AND ENTRANCE ROOMS AS SHOWN. ENSURE THAT FIRE
RATING STAMP IS TO REMAIN UNCOVERED BY PAINT.
1. PROVIDE MIGHTY MO 20 RACK, OR-MM20730B (OR EQUIVALENT)
2. PROVIDE 6" VERTICAL WIRE MANAGER, OR-MM20VMD706 (OR EQUIVALENT)
3. PROVIDE 4'X8' AC GRADE 3/4" TRADE SIZE FIRE RATED PLYWOOD BACKBOARD PAINTED HIGH GLOSS
WHITE WITH (2) COATS OF PAINT FOR SERVICE PROVIDER/SECURITY/VIDEO/ETC. AROUND
PERIMETER WALLS OF TR"s AND ENTRANCE ROOMS AS SHOWN. ENSURE THAT FIRE RATING STAMP
IS TO REMAIN UNCOVERED BY PAINT.
4. PROVIDE FIXED CAMERA WITH PASSIVE INFRARED(PIR) SUPPLEMENTAL LIGHTING ON TELECOM
ROOM CORNER.
5. PROVIDE ACCESS CONTROL DEVICES ON SECURITY DOOR.
6. PROVIDE COPPER GROUNDING BUSBAR AT 5' AFF IN LOCATION SHOWN. SEE GROUNDING BAR
DETAIL FOR ADDITIONAL REQUIREMENTS.
7. BASKET STYLE CABLE TRAY MINIMUM 4"X18" SHALL BE USED. ALL TRAY MUST BE INSTALLED AT 7'8"
AFF, SUPPORTED PER MANUFACTURER REQUIREMENTS, AND PROPERLY BONDED TO GROUND.
DEMO PLAN GENERAL NOTES
1. REMOVE EXISTING WALL MOUNTED SERVER RACK.
2. RELOCATE EXISTING UTILITY PIPING AS REQUIRED TO ACCOMMODATE NEW
SERVER RACK. COORDINATE FINAL LOCATIONS WITH VA/COR.
3. PROVIDE AND INSTALL VISQUEEN TYPE PLASTIC SHEET AND ZIPPER DOOR AS
REQUIRED TO MAINTAIN TYPE V INFECTION CONTROL PRECAUTIONS. EXTEND
AND SEAL TO ROOF DECK/STRUCTURE ABOVE. CONTRACTOR IS REQUIRED TO
ENSURE THAT PROPER HEAT MANAGEMENT WILL BE MAINTAINED FOR ANY
ACTIVE EQUIPMENT.
4. SUPPLY AND INSTALL WALK OFF MATS.
5. PROTECT EXISTING FINISHES FROM DUST AND DAMAGE.
ICT - BUILDING 3 -BASEMENT PLAN
OVERALL
BB BA,GM
TT-B03-10B
TYP
DC
ES
CR/K
MID
REX7'-
3"
4'-4"4'-4"
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
G :\B uh ol tz P ro fe ss io na l E ng , I nc \B
PE
P ro je ct s\
BP
E
Pr oj ec ts
3\
5-
Ba nc ro ft
- T
N V
A H os pi ta l\B
PE
R
EV
IS
IO
N
3\
TT
-B
-1
.d w g
4/ 1/
:5
3:
P M
ISSUE FOR BIDOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
EHRM INFRASTRUCTURE
UPGRADES DESIGN
JAMES H. QUILLEN VA
MEDICAL CENTER
621-22-700
Revisions: Date:
www. bancroft-ae.com
3300 Dundee RD.
Northbrook, IL 60062
T: 847.952.9362
Bancroft Project No: 22-114
UHOLTZ ROFESSIONAL B P
ENGINEERING, INC.
154 Tuskawilla Rd., Ste. 1380 Winter Springs FL 32708 Ph 407-327-3300
CA 00009600 05/22/2025
ISSUED FOR BID 05/22/2025
GENERAL NOTES
A. FOR GENERAL NOTES AND LEGENDS REFER TO SHEET TT-000.
B. EXISTING IT/TR/OI&T ROOMS TO REMAIN ACTIVE DURING CONSTRUCTION. G.C. TO PROTECT EQUIPMENT
DURING CONSTRUCTION WITH VISQUEEN. CONTRACTOR TO ENSURE CONTINUOUS OPERATION OF EQUIPMENT.
C. NOT ALL KEY NOTES APPLY TO ALL PLAN SHEETS. G.C. TO APPLY ONLY AS INDICATED PER EACH SHEET.
D. APPLY FIRE RATED SEALANT TO ALL EXISTING AND NEW PENETRATIONS IN EXISTING WALLS TO MAKE EXISTING
WALLS A 1 HR ASSEMBLY. FOR ALL NEW PENETRATIONS REFERENCE DETAILS ON SHEET TT-5.02.
D. ALL LEGACY SYSTEMS CONNECTIONS THAT ARE NON-OIT (TELEMETRY, NURSE CALL, SECURITY, ETC.) THAT ARE NOT BEING REPLACED AND/OR RELOCATED SHALL REMAIN IN SERVICE IN THEIR CURRENT LOCATION AFTER OIT
RELATED CONNECTIONS HAVE BEEN REPLACES AND/OR RELOCATED.
FLOOR PLAN KEYNOTESX
FLOOR PLAN LEGEND
4'X8' AC GRADE 3/4" TRADE SIZE FIRE RATED PLYWOOD BACKBOARD
PAINTED HIGH GLOSS WHITE WITH (2) COATS OF FIRE RESISTANT PAINT
FOR SERVICE PROVIDER/SECURITY/VIDEO/ETC. AROUND PERIMETER
WALLS OF TRS AND ENTRANCE ROOMS AS SHOWN. ENSURE THAT FIRE
RATING STAMP IS TO REMAIN UNCOVERED BY PAINT.
1. PROVIDE MIGHTY MO 20 RACK, OR-MM20730B (OR EQUIVALENT)
2. PROVIDE 6" VERTICAL WIRE MANAGER, OR-MM20VMD706 (OR EQUIVALENT)
3. PROVIDE 4'X8' AC GRADE 3/4" TRADE SIZE FIRE RATED PLYWOOD BACKBOARD PAINTED HIGH GLOSS
WHITE WITH (2) COATS OF PAINT FOR SERVICE PROVIDER/SECURITY/VIDEO/ETC. AROUND
PERIMETER WALLS OF TR"s AND ENTRANCE ROOMS AS SHOWN. ENSURE THAT FIRE RATING STAMP
IS TO REMAIN UNCOVERED BY PAINT.
4. PROVIDE FIXED CAMERA WITH PASSIVE INFRARED(PIR) SUPPLEMENTAL LIGHTING ON TELECOM
ROOM CORNER.
5. PROVIDE ACCESS CONTROL DEVICES ON SECURITY DOOR.
6. PROVIDE COPPER GROUNDING BUSBAR AT 5' AFF IN LOCATION SHOWN. SEE GROUNDING BAR
DETAIL FOR ADDITIONAL REQUIREMENTS.
7. BASKET STYLE CABLE TRAY MINIMUM 4"X18" SHALL BE USED. ALL TRAY MUST BE INSTALLED AT 7'8"
AFF, SUPPORTED PER MANUFACTURER REQUIREMENTS, AND PROPERLY BONDED TO GROUND.
DEMO PLAN GENERAL NOTES
1. REMOVE EXISTING WALL MOUNTED SERVER RACK.
2. RELOCATE EXISTING UTILITY PIPING AS REQUIRED TO ACCOMMODATE NEW
SERVER RACK. COORDINATE FINAL LOCATIONS WITH VA/COR.
3. PROVIDE AND INSTALL VISQUEEN TYPE PLASTIC SHEET AND ZIPPER DOOR AS
REQUIRED TO MAINTAIN TYPE V INFECTION CONTROL PRECAUTIONS. EXTEND
AND SEAL TO ROOF DECK/STRUCTURE ABOVE. CONTRACTOR IS REQUIRED TO
ENSURE THAT PROPER HEAT MANAGEMENT WILL BE MAINTAINED FOR ANY
ACTIVE EQUIPMENT.
4. SUPPLY AND INSTALL WALK OFF MATS.
5. PROTECT EXISTING FINISHES FROM DUST AND DAMAGE.
BB BA,GM
TT-B03-101
ICT - BUILDING 3 - LEVEL 1 PLAN
OVERALL
DC
ES
TYP
CR/K
MID
REX
7'- 3"
4'-4"4'-4"
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
G :\B uh ol tz P ro fe ss io na l E ng , I nc \B
PE
P ro je ct s\
BP
E
Pr oj ec ts
3\
5-
Ba nc ro ft
- T
N V
A H os pi ta l\B
PE
R
EV
IS
IO
N
3\
TT
-B
-1
.d w g
4/ 1/
:5
8:
P M
ISSUE FOR BIDOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
EHRM INFRASTRUCTURE
UPGRADES DESIGN
JAMES H. QUILLEN VA
MEDICAL CENTER
621-22-700
Revisions: Date:
www. bancroft-ae.com
3300 Dundee RD.
Northbrook, IL 60062
T: 847.952.9362
Bancroft Project No: 22-114
UHOLTZ ROFESSIONAL B P
ENGINEERING, INC.
154 Tuskawilla Rd., Ste. 1380 Winter Springs FL 32708 Ph 407-327-3300
CA 00009600 05/22/2025
ISSUED FOR BID 05/22/2025
GENERAL NOTES
A. FOR GENERAL NOTES AND LEGENDS REFER TO SHEET TT-000.
B. EXISTING IT/TR/OI&T ROOMS TO REMAIN ACTIVE DURING CONSTRUCTION. G.C. TO PROTECT EQUIPMENT
DURING CONSTRUCTION WITH VISQUEEN. CONTRACTOR TO ENSURE CONTINUOUS OPERATION OF EQUIPMENT.
C. NOT ALL KEY NOTES APPLY TO ALL PLAN SHEETS. G.C. TO APPLY ONLY AS INDICATED PER EACH SHEET.
D. APPLY FIRE RATED SEALANT TO ALL EXISTING AND NEW PENETRATIONS IN EXISTING WALLS TO MAKE EXISTING
WALLS A 1 HR ASSEMBLY. FOR ALL NEW PENETRATIONS REFERENCE DETAILS ON SHEET TT-5.02.
D. ALL LEGACY SYSTEMS CONNECTIONS THAT ARE NON-OIT (TELEMETRY, NURSE CALL, SECURITY, ETC.) THAT ARE NOT BEING REPLACED AND/OR RELOCATED SHALL REMAIN IN SERVICE IN THEIR CURRENT LOCATION AFTER OIT
RELATED CONNECTIONS HAVE BEEN REPLACES AND/OR RELOCATED.
FLOOR PLAN KEYNOTESX
FLOOR PLAN LEGEND
4'X8' AC GRADE 3/4" TRADE SIZE FIRE RATED PLYWOOD BACKBOARD
PAINTED HIGH GLOSS WHITE WITH (2) COATS OF FIRE RESISTANT PAINT
FOR SERVICE PROVIDER/SECURITY/VIDEO/ETC. AROUND PERIMETER
WALLS OF TRS AND ENTRANCE ROOMS AS SHOWN. ENSURE THAT FIRE
RATING STAMP IS TO REMAIN UNCOVERED BY PAINT.
1. PROVIDE MIGHTY MO 20 RACK, OR-MM20730B (OR EQUIVALENT)
2. PROVIDE 6" VERTICAL WIRE MANAGER, OR-MM20VMD706 (OR EQUIVALENT)
3. PROVIDE 4'X8' AC GRADE 3/4" TRADE SIZE FIRE RATED PLYWOOD BACKBOARD PAINTED HIGH GLOSS
WHITE WITH (2) COATS OF PAINT FOR SERVICE PROVIDER/SECURITY/VIDEO/ETC. AROUND
PERIMETER WALLS OF TR"s AND ENTRANCE ROOMS AS SHOWN. ENSURE THAT FIRE RATING STAMP
IS TO REMAIN UNCOVERED BY PAINT.
4. PROVIDE FIXED CAMERA WITH PASSIVE INFRARED(PIR) SUPPLEMENTAL LIGHTING ON TELECOM
ROOM CORNER.
5. PROVIDE ACCESS CONTROL DEVICES ON SECURITY DOOR.
6. PROVIDE COPPER GROUNDING BUSBAR AT 5' AFF IN LOCATION SHOWN. SEE GROUNDING BAR
DETAIL FOR ADDITIONAL REQUIREMENTS.
7. BASKET STYLE CABLE TRAY MINIMUM 4"X18" SHALL BE USED. ALL TRAY MUST BE INSTALLED AT 7'8"
AFF, SUPPORTED PER MANUFACTURER REQUIREMENTS, AND PROPERLY BONDED TO GROUND.
DEMO PLAN GENERAL NOTES
1. REMOVE EXISTING WALL MOUNTED SERVER RACK.
2. RELOCATE EXISTING UTILITY PIPING AS REQUIRED TO ACCOMMODATE NEW
SERVER RACK. COORDINATE FINAL LOCATIONS WITH VA/COR.
3. PROVIDE AND INSTALL VISQUEEN TYPE PLASTIC SHEET AND ZIPPER DOOR AS
REQUIRED TO MAINTAIN TYPE V INFECTION CONTROL PRECAUTIONS. EXTEND
AND SEAL TO ROOF DECK/STRUCTURE ABOVE. CONTRACTOR IS REQUIRED TO
ENSURE THAT PROPER HEAT MANAGEMENT WILL BE MAINTAINED FOR ANY
ACTIVE EQUIPMENT.
4. SUPPLY AND INSTALL WALK OFF MATS.
5. PROTECT EXISTING FINISHES FROM DUST AND DAMAGE.
BB BA,GM
TT-B03-102
ICT - BUILDING 3 - LEVEL 2 PLAN
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
G :\B uh ol tz P ro fe ss io na l E ng , I nc \B
PE
P ro je ct s\
BP
E
Pr oj ec ts
3\
5-
Ba nc ro ft
- T
N V
A H os pi ta l\B
PE
R
EV
IS
IO
N
3\
TT
-B
-2
-S
ER
IE
S.
dw g 3/
/2
3:
:3
PM
ISSUE FOR BIDOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
EHRM INFRASTRUCTURE
UPGRADES DESIGN
JAMES H. QUILLEN VA
MEDICAL CENTER
621-22-700
Revisions: Date:
www. bancroft-ae.com
3300 Dundee RD.
Northbrook, IL 60062
T: 847.952.9362
Bancroft Project No: 22-114
UHOLTZ ROFESSIONAL B P
ENGINEERING, INC.
154 Tuskawilla Rd., Ste. 1380 Winter Springs FL 32708 Ph 407-327-3300
CA 00009600 05/22/2025
ISSUED FOR BID 05/22/2025
ICT - BUILDING 3
RACK ELEVATIONS
BB BA,GM
TT-B3-201
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
G :\B uh ol tz P ro fe ss io na l E ng , I nc \B
PE
P ro je ct s\
BP
E
Pr oj ec ts
3\
5-
Ba nc ro ft
- T
N V
A H os pi ta l\B
PE
R
EV
IS
IO
N
3\
TT
-B
-2
-S
ER
IE
S.
dw g 3/
/2
3:
:3
PM
ISSUE FOR BIDOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
EHRM INFRASTRUCTURE
UPGRADES DESIGN
JAMES H. QUILLEN VA
MEDICAL CENTER
621-22-700
Revisions: Date:
www. bancroft-ae.com
3300 Dundee RD.
Northbrook, IL 60062
T: 847.952.9362
Bancroft Project No: 22-114
UHOLTZ ROFESSIONAL B P
ENGINEERING, INC.
154 Tuskawilla Rd., Ste. 1380 Winter Springs FL 32708 Ph 407-327-3300
CA 00009600 05/22/2025
ISSUED FOR BID 05/22/2025
ICT - BUILDING 3
RACK ELEVATIONS
BB BA,GM
TT-B3-202
TYP DC
ES
CR/K
MID
REX
3'- 9"
3'-1"
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
G :\B uh ol tz P ro fe ss io na l E ng , I nc \B
PE
P ro je ct s\
BP
E
Pr oj ec ts
3\
5-
Ba nc ro ft
- T
N V
A H os pi ta l\B
PE
R
EV
IS
IO
N
3\
TT
-B
-1
0B .d w g
4/ 1/
2:
:3
PM
ISSUE FOR BIDOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
EHRM INFRASTRUCTURE
UPGRADES DESIGN
JAMES H. QUILLEN VA
MEDICAL CENTER
621-22-700
Revisions: Date:
www. bancroft-ae.com
3300 Dundee RD.
Northbrook, IL 60062
T: 847.952.9362
Bancroft Project No: 22-114
UHOLTZ ROFESSIONAL B P
ENGINEERING, INC.
154 Tuskawilla Rd., Ste. 1380 Winter Springs FL 32708 Ph 407-327-3300
CA 00009600 05/22/2025
ISSUED FOR BID 05/22/2025
GENERAL NOTES
A. FOR GENERAL NOTES AND LEGENDS REFER TO SHEET TT-000.
B. EXISTING IT/TR/OI&T ROOMS TO REMAIN ACTIVE DURING CONSTRUCTION. G.C. TO PROTECT EQUIPMENT
DURING CONSTRUCTION WITH VISQUEEN. CONTRACTOR TO ENSURE CONTINUOUS OPERATION OF EQUIPMENT.
C. NOT ALL KEY NOTES APPLY TO ALL PLAN SHEETS. G.C. TO APPLY ONLY AS INDICATED PER EACH SHEET.
D. APPLY FIRE RATED SEALANT TO ALL EXISTING AND NEW PENETRATIONS IN EXISTING WALLS TO MAKE EXISTING
WALLS A 1 HR ASSEMBLY. FOR ALL NEW PENETRATIONS REFERENCE DETAILS ON SHEET TT-5.02.
D. ALL LEGACY SYSTEMS CONNECTIONS THAT ARE NON-OIT (TELEMETRY, NURSE CALL, SECURITY, ETC.) THAT ARE NOT BEING REPLACED AND/OR RELOCATED SHALL REMAIN IN SERVICE IN THEIR CURRENT LOCATION AFTER OIT
RELATED CONNECTIONS HAVE BEEN REPLACES AND/OR RELOCATED.
FLOOR PLAN KEYNOTESX
FLOOR PLAN LEGEND
4'X8' AC GRADE 3/4" TRADE SIZE FIRE RATED PLYWOOD BACKBOARD
PAINTED HIGH GLOSS WHITE WITH (2) COATS OF FIRE RESISTANT PAINT
FOR SERVICE PROVIDER/SECURITY/VIDEO/ETC. AROUND PERIMETER
WALLS OF TRS AND ENTRANCE ROOMS AS SHOWN. ENSURE THAT FIRE
RATING STAMP IS TO REMAIN UNCOVERED BY PAINT.
1. PROVIDE MIGHTY MO 20 RACK, OR-MM20730B (OR EQUIVALENT)
2. PROVIDE 6" VERTICAL WIRE MANAGER, OR-MM20VMD706 (OR EQUIVALENT)
3. PROVIDE 4'X8' AC GRADE 3/4" TRADE SIZE FIRE RATED PLYWOOD BACKBOARD PAINTED HIGH GLOSS
WHITE WITH (2) COATS OF PAINT FOR SERVICE PROVIDER/SECURITY/VIDEO/ETC. AROUND
PERIMETER WALLS OF TR"s AND ENTRANCE ROOMS AS SHOWN. ENSURE THAT FIRE RATING STAMP
IS TO REMAIN UNCOVERED BY PAINT.
4. PROVIDE FIXED CAMERA WITH PASSIVE INFRARED(PIR) SUPPLEMENTAL LIGHTING ON TELECOM
ROOM CORNER.
5. PROVIDE ACCESS CONTROL DEVICES ON SECURITY DOOR.
6. PROVIDE COPPER GROUNDING BUSBAR AT 5' AFF IN LOCATION SHOWN. SEE GROUNDING BAR
DETAIL FOR ADDITIONAL REQUIREMENTS.
7. BASKET STYLE CABLE TRAY MINIMUM 4"X18" SHALL BE USED. ALL TRAY MUST BE INSTALLED AT 7'8"
AFF, SUPPORTED PER MANUFACTURER REQUIREMENTS, AND PROPERLY BONDED TO GROUND.
DEMO PLAN GENERAL NOTES
1. REMOVE EXISTING WALL MOUNTED SERVER RACK.
2. RELOCATE EXISTING UTILITY PIPING AS REQUIRED TO ACCOMMODATE NEW
SERVER RACK. COORDINATE FINAL LOCATIONS WITH VA/COR.
3. PROVIDE AND INSTALL VISQUEEN TYPE PLASTIC SHEET AND ZIPPER DOOR AS
REQUIRED TO MAINTAIN TYPE V INFECTION CONTROL PRECAUTIONS. EXTEND
AND SEAL TO ROOF DECK/STRUCTURE ABOVE. CONTRACTOR IS REQUIRED TO
ENSURE THAT PROPER HEAT MANAGEMENT WILL BE MAINTAINED FOR ANY
ACTIVE EQUIPMENT.
4. SUPPLY AND INSTALL WALK OFF MATS.
5. PROTECT EXISTING FINISHES FROM DUST AND DAMAGE.
BB BA,GM
TT-B05-10B
ICT - BUILDING 3 - BUILDING 5 PLAN
ES
TYP
TYP
TYP
CR/K
MID
REX
8'- 3"
FUTURE
4'-1" 4'-1"
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
G :\B uh ol tz P ro fe ss io na l E ng , I nc \B
PE
P ro je ct s\
BP
E
Pr oj ec ts
3\
5-
Ba nc ro ft
- T
N V
A H os pi ta l\B
PE
R
EV
IS
IO
N
3\
TT
-B
-1
.d w g
4/ 1/
:5
6:
P M
ISSUE FOR BIDOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
EHRM INFRASTRUCTURE
UPGRADES DESIGN
JAMES H. QUILLEN VA
MEDICAL CENTER
621-22-700
Revisions: Date:
www. bancroft-ae.com
3300 Dundee RD.
Northbrook, IL 60062
T: 847.952.9362
Bancroft Project No: 22-114
UHOLTZ ROFESSIONAL B P
ENGINEERING, INC.
154 Tuskawilla Rd., Ste. 1380 Winter Springs FL 32708 Ph 407-327-3300
CA 00009600 05/22/2025
ISSUED FOR BID 05/22/2025
GENERAL NOTES
A. FOR GENERAL NOTES AND LEGENDS REFER TO SHEET TT-000.
B. EXISTING IT/TR/OI&T ROOMS TO REMAIN ACTIVE DURING CONSTRUCTION. G.C. TO PROTECT EQUIPMENT
DURING CONSTRUCTION WITH VISQUEEN. CONTRACTOR TO ENSURE CONTINUOUS OPERATION OF EQUIPMENT.
C. NOT ALL KEY NOTES APPLY TO ALL PLAN SHEETS. G.C. TO APPLY ONLY AS INDICATED PER EACH SHEET.
D. APPLY FIRE RATED SEALANT TO ALL EXISTING AND NEW PENETRATIONS IN EXISTING WALLS TO MAKE EXISTING
WALLS A 1 HR ASSEMBLY. FOR ALL NEW PENETRATIONS REFERENCE DETAILS ON SHEET TT-5.02.
D. ALL LEGACY SYSTEMS CONNECTIONS THAT ARE NON-OIT (TELEMETRY, NURSE CALL, SECURITY, ETC.) THAT ARE NOT BEING REPLACED AND/OR RELOCATED SHALL REMAIN IN SERVICE IN THEIR CURRENT LOCATION AFTER OIT
RELATED CONNECTIONS HAVE BEEN REPLACES AND/OR RELOCATED.
FLOOR PLAN KEYNOTESX
FLOOR PLAN LEGEND
4'X8' AC GRADE 3/4" TRADE SIZE FIRE RATED PLYWOOD BACKBOARD
PAINTED HIGH GLOSS WHITE WITH (2) COATS OF FIRE RESISTANT PAINT
FOR SERVICE PROVIDER/SECURITY/VIDEO/ETC. AROUND PERIMETER
WALLS OF TRS AND ENTRANCE ROOMS AS SHOWN. ENSURE THAT FIRE
RATING STAMP IS TO REMAIN UNCOVERED BY PAINT.
1. PROVIDE MIGHTY MO 20 RACK, OR-MM20730B (OR EQUIVALENT)
2. PROVIDE 6" VERTICAL WIRE MANAGER, OR-MM20VMD706 (OR EQUIVALENT)
3. PROVIDE 4'X8' AC GRADE 3/4" TRADE SIZE FIRE RATED PLYWOOD BACKBOARD PAINTED HIGH GLOSS
WHITE WITH (2) COATS OF PAINT FOR SERVICE PROVIDER/SECURITY/VIDEO/ETC. AROUND
PERIMETER WALLS OF TR"s AND ENTRANCE ROOMS AS SHOWN. ENSURE THAT FIRE RATING STAMP
IS TO REMAIN UNCOVERED BY PAINT.
4. PROVIDE FIXED CAMERA WITH PASSIVE INFRARED(PIR) SUPPLEMENTAL LIGHTING ON TELECOM
ROOM CORNER.
5. PROVIDE ACCESS CONTROL DEVICES ON SECURITY DOOR.
6. PROVIDE COPPER GROUNDING BUSBAR AT 5' AFF IN LOCATION SHOWN. SEE GROUNDING BAR
DETAIL FOR ADDITIONAL REQUIREMENTS.
7. BASKET STYLE CABLE TRAY MINIMUM 4"X18" SHALL BE USED. ALL TRAY MUST BE INSTALLED AT 7'8"
AFF, SUPPORTED PER MANUFACTURER REQUIREMENTS, AND PROPERLY BONDED TO GROUND.
DEMO PLAN GENERAL NOTES
1. REMOVE EXISTING WALL MOUNTED SERVER RACK.
2. RELOCATE EXISTING UTILITY PIPING AS REQUIRED TO ACCOMMODATE NEW
SERVER RACK. COORDINATE FINAL LOCATIONS WITH VA/COR.
3. PROVIDE AND INSTALL VISQUEEN TYPE PLASTIC SHEET AND ZIPPER DOOR AS
REQUIRED TO MAINTAIN TYPE V INFECTION CONTROL PRECAUTIONS. EXTEND
AND SEAL TO ROOF DECK/STRUCTURE ABOVE. CONTRACTOR IS REQUIRED TO
ENSURE THAT PROPER HEAT MANAGEMENT WILL BE MAINTAINED FOR ANY
ACTIVE EQUIPMENT.
4. SUPPLY AND INSTALL WALK OFF MATS.
5. PROTECT EXISTING FINISHES FROM DUST AND DAMAGE.
ICT - BUILDING 5 - FIRST FLOOR PLAN
OVERALL
BB BA,GM
TT-B05-101
TYP
TYP
TYP
CR/K
MID
REX
3'- 9"
3'-1" 3'-4"
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
G :\B uh ol tz P ro fe ss io na l E ng , I nc \B
PE
P ro je ct s\
BP
E
Pr oj ec ts
3\
5-
Ba nc ro ft
- T
N V
A H os pi ta l\B
PE
R
EV
IS
IO
N
3\
TT
-B
-1
.d w g
4/ 1/
:1
3:
P M
ISSUE FOR BIDOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
EHRM INFRASTRUCTURE
UPGRADES DESIGN
JAMES H. QUILLEN VA
MEDICAL CENTER
621-22-700
Revisions: Date:
www. bancroft-ae.com
3300 Dundee RD.
Northbrook, IL 60062
T: 847.952.9362
Bancroft Project No: 22-114
UHOLTZ ROFESSIONAL B P
ENGINEERING, INC.
154 Tuskawilla Rd., Ste. 1380 Winter Springs FL 32708 Ph 407-327-3300
CA 00009600 05/22/2025
ISSUED FOR BID 05/22/2025
GENERAL NOTES
A. FOR GENERAL NOTES AND LEGENDS REFER TO SHEET TT-000.
B. EXISTING IT/TR/OI&T ROOMS TO REMAIN ACTIVE DURING CONSTRUCTION. G.C. TO PROTECT EQUIPMENT
DURING CONSTRUCTION WITH VISQUEEN. CONTRACTOR TO ENSURE CONTINUOUS OPERATION OF EQUIPMENT.
C. NOT ALL KEY NOTES APPLY TO ALL PLAN SHEETS. G.C. TO APPLY ONLY AS INDICATED PER EACH SHEET.
D. APPLY FIRE RATED SEALANT TO ALL EXISTING AND NEW PENETRATIONS IN EXISTING WALLS TO MAKE EXISTING
WALLS A 1 HR ASSEMBLY. FOR ALL NEW PENETRATIONS REFERENCE DETAILS ON SHEET TT-5.02.
D. ALL LEGACY SYSTEMS CONNECTIONS THAT ARE NON-OIT (TELEMETRY, NURSE CALL, SECURITY, ETC.) THAT ARE NOT BEING REPLACED AND/OR RELOCATED SHALL REMAIN IN SERVICE IN THEIR CURRENT LOCATION AFTER OIT
RELATED CONNECTIONS HAVE BEEN REPLACES AND/OR RELOCATED.
FLOOR PLAN KEYNOTESX
FLOOR PLAN LEGEND
4'X8' AC GRADE 3/4" TRADE SIZE FIRE RATED PLYWOOD BACKBOARD
PAINTED HIGH GLOSS WHITE WITH (2) COATS OF FIRE RESISTANT PAINT
FOR SERVICE PROVIDER/SECURITY/VIDEO/ETC. AROUND PERIMETER
WALLS OF TRS AND ENTRANCE ROOMS AS SHOWN. ENSURE THAT FIRE
RATING STAMP IS TO REMAIN UNCOVERED BY PAINT.
1. PROVIDE MIGHTY MO 20 RACK, OR-MM20730B (OR EQUIVALENT)
2. PROVIDE 6" VERTICAL WIRE MANAGER, OR-MM20VMD706 (OR EQUIVALENT)
3. PROVIDE 4'X8' AC GRADE 3/4" TRADE SIZE FIRE RATED PLYWOOD BACKBOARD PAINTED HIGH GLOSS
WHITE WITH (2) COATS OF PAINT FOR SERVICE PROVIDER/SECURITY/VIDEO/ETC. AROUND
PERIMETER WALLS OF TR"s AND ENTRANCE ROOMS AS SHOWN. ENSURE THAT FIRE RATING STAMP
IS TO REMAIN UNCOVERED BY PAINT.
4. PROVIDE FIXED CAMERA WITH PASSIVE INFRARED(PIR) SUPPLEMENTAL LIGHTING ON TELECOM
ROOM CORNER.
5. PROVIDE ACCESS CONTROL DEVICES ON SECURITY DOOR.
6. PROVIDE COPPER GROUNDING BUSBAR AT 5' AFF IN LOCATION SHOWN. SEE GROUNDING BAR
DETAIL FOR ADDITIONAL REQUIREMENTS.
7. BASKET STYLE CABLE TRAY MINIMUM 4"X18" SHALL BE USED. ALL TRAY MUST BE INSTALLED AT 7'8"
AFF, SUPPORTED PER MANUFACTURER REQUIREMENTS, AND PROPERLY BONDED TO GROUND.
DEMO PLAN GENERAL NOTES
1. REMOVE EXISTING WALL MOUNTED SERVER RACK.
2. RELOCATE EXISTING UTILITY PIPING AS REQUIRED TO ACCOMMODATE NEW
SERVER RACK. COORDINATE FINAL LOCATIONS WITH VA/COR.
3. PROVIDE AND INSTALL VISQUEEN TYPE PLASTIC SHEET AND ZIPPER DOOR AS
REQUIRED TO MAINTAIN TYPE V INFECTION CONTROL PRECAUTIONS. EXTEND
AND SEAL TO ROOF DECK/STRUCTURE ABOVE. CONTRACTOR IS REQUIRED TO
ENSURE THAT PROPER HEAT MANAGEMENT WILL BE MAINTAINED FOR ANY
ACTIVE EQUIPMENT.
4. SUPPLY AND INSTALL WALK OFF MATS.
5. PROTECT EXISTING FINISHES FROM DUST AND DAMAGE.
ICT - BUILDING 5 - SECOND FLOOR
PLAN OVERALL
BB BA,GM
TT-B05-102
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
G :\B uh ol tz P ro fe ss io na l E ng , I nc \B
PE
P ro je ct s\
BP
E
Pr oj ec ts
3\
5-
Ba nc ro ft
- T
N V
A H os pi ta l\B
PE
R
EV
IS
IO
N
3\
TT
-B
-2
-S
ER
IE
S.
dw g 3/
/2
4:
:3
PM
ISSUE FOR BIDOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
EHRM INFRASTRUCTURE
UPGRADES DESIGN
JAMES H. QUILLEN VA
MEDICAL CENTER
621-22-700
Revisions: Date:
www. bancroft-ae.com
3300 Dundee RD.
Northbrook, IL 60062
T: 847.952.9362
Bancroft Project No: 22-114
UHOLTZ ROFESSIONAL B P
ENGINEERING, INC.
154 Tuskawilla Rd., Ste. 1380 Winter Springs FL 32708 Ph 407-327-3300
CA 00009600 05/22/2025
ISSUED FOR BID 05/22/2025
ICT - BUILDING 5
RACK ELEVATIONS
BB BA,GM
TT-B5-201
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
G :\B uh ol tz P ro fe ss io na l E ng , I nc \B
PE
P ro je ct s\
BP
E
Pr oj ec ts
3\
5-
Ba nc ro ft
- T
N V
A H os pi ta l\B
PE
R
EV
IS
IO
N
3\
TT
-B
-2
-S
ER
IE
S.
dw g 3/
/2
4:
:3
PM
ISSUE FOR BIDOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
EHRM INFRASTRUCTURE
UPGRADES DESIGN
JAMES H. QUILLEN VA
MEDICAL CENTER
621-22-700
Revisions: Date:
www. bancroft-ae.com
3300 Dundee RD.
Northbrook, IL 60062
T: 847.952.9362
Bancroft Project No: 22-114
UHOLTZ ROFESSIONAL B P
ENGINEERING, INC.
154 Tuskawilla Rd., Ste. 1380 Winter Springs FL 32708 Ph 407-327-3300
CA 00009600 05/22/2025
ISSUED FOR BID 05/22/2025
ICT - BUILDING 5
RACK ELEVATIONS
BB BA,GM
TT-B5-202
TYP
TYP
CR/K
MID
REX
FUTURE
5'-8" 5'-8" 3'-
1"
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
G :\B uh ol tz P ro fe ss io na l E ng , I nc \B
PE
P ro je ct s\
BP
E
Pr oj ec ts
3\
5-
Ba nc ro ft
- T
N V
A H os pi ta l\B
PE
R
EV
IS
IO
N
3\
TT
-B
-1
0B .d w g
4/ 1/
:0
0:
P M
ISSUE FOR BIDOffice of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
EHRM INFRASTRUCTURE
UPGRADES DESIGN
JAMES H. QUILLEN VA
MEDICAL CENTER
621-22-700
Revisions: Date:
www. bancroft-ae.com
3300 Dundee RD.
Northbrook, IL 60062
T: 847.952.9362
Bancroft Project No: 22-114
UHOLTZ ROFESSIONAL B P
ENGINEERING, INC.
154 Tuskawilla Rd., Ste. 1380 Winter Springs FL 32708 Ph 407-327-3300
CA 00009600 05/22/2025
ISSUED FOR BID 05/22/2025
GENERAL NOTES
A. FOR GENERAL NOTES AND LEGENDS REFER TO SHEET TT-000.
B. EXISTING IT/TR/OI&T ROOMS TO REMAIN ACTIVE DURING CONSTRUCTION. G.C. TO PROTECT EQUIPMENT
DURING CONSTRUCTION WITH VISQUEEN. CONTRACTOR TO ENSURE CONTINUOUS OPERATION OF EQUIPMENT.
C. NOT ALL KEY NOTES APPLY TO ALL PLAN SHEETS. G.C. TO APPLY ONLY AS INDICATED PER EACH SHEET.
D. APPLY FIRE RATED SEALANT TO ALL EXISTING AND NEW PENETRATIONS IN EXISTING WALLS TO MAKE EXISTING
WALLS A 1 HR ASSEMBLY. FOR ALL NEW PENETRATIONS REFERENCE DETAILS ON SHEET TT-5.02.
D. ALL LEGACY SYSTEMS CONNECTIONS THAT ARE NON-OIT (TELEMETRY, NURSE CALL,…