Attachment 3 Electr. Drawings & Calc.pdf
PDF 1 MB Posted
- Attached to
- Design, Engineering and Constructions Services for Photovoltaic (PV) Inverter and Communication Upgrades
- Solicitation number
- 19BY7024Q0007
- Issued by
-
Department of State
About this file
This document appears to be a set of electrical drawings and calculations for a 61.44 kW photovoltaic (PV) system to be installed at the UTL Building in Bujumbura, Central Africa. The system will use 192 Sunpower E19/320 (US) PV modules and 9 SMA inverters, including 6 SMC 7000HV-11 inverters and 3 SMC 5000A inverters. The drawings provide details on the system layout, wiring, conduit, overcurrent protection, and labeling requirements. Key technical details include the array configuration, inverter specifications, and estimated annual energy production. The document also includes conductor sizing calculations and overcurrent protection device ratings for the DC and AC circuits. This appears to be a shop drawing package intended to guide the installation of the PV system.
The related federal contract opportunity is a solicitation from the Department of State for design, engineering, and construction services for PV inverter and communication upgrades. Attachments 1 and 2 are required to view the full solicitation details, which cannot be uploaded at this time. Interested parties are instructed to email BujProcurmeent@state.gov to request those attachments.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 19BY7024Q0007_Contractor Questions.pdf | ||
| ReducerBox_Screen2.PNG | PNG image | |
| ReducerBox_Screen1.PNG | PNG image | |
| NOB_Screen1.PNG | PNG image | |
| Buj_SOW PV System Upgrade V 1.0 - May 2024.docx | DOCX document | |
| UTL_Screen3.PNG | PNG image | |
| UTL_Screen1.PNG | PNG image | |
| 19BY7024Q0007_0001.pdf | ||
| 19BY7024Q0007_Memo signed.pdf | ||
| 19BY7024Q0007-RFQ Final.pdf | ||
| PR12511777-SF1442.pdf |
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
NOB
Electrical Drawing and
Calculations
69.12 kW
PV
Array x 320W SunPower modules x
SMA
SMC
7000HV-‐11
Inverters
Michael P. Stangl, P.E.
Renewable Power Design Group
P.O. Box 967
54 Holly Hill Road (packages)
Averill Park, NY 12018
USA
Michael P. Stangl, P.E. • Renewable Power Design Group • P.O. Box 967 • 54
Caddell Construction, Cos.
Tel.: +01 518 674-3684
Fax: +01 518 514-1212
E-Mail: MStangl@rpdg.us.com
NOB
92937
NOB with 9 x SMC 7000HV11
Location: Central Africa / Bujumbura
Grid voltage: 3~400 V
Project name:
Project number:
Project file:
System overview Part project 1
216 x Sunpower E19/320 (US) (PV Arrays for Entire Building)
Azimuth angle: -135 °, Angle of inclination: 7 °, Mounting type: Roof, PV Peak power: 69.12 kW
Inverters:
9 x SMC 7000HV-11 (Inverter efficiency: 95.2 %)
Technical data
Total number of PV modules:
PV Peak power: 69.12 kWp
Number of inverters: 9
Nominal AC power: 59.85 kW
Annual energy yield (approx.)*:
102.79 MWh
Energy usability factor: 100.0 %
Performance ratio (approx.
83.5 %
Spec. energy yield (approx.
1487 kWh/kWp
Line losses (in % of PV energy):
Unbalanced load: 0.00 VA
Notes:
Important: The yield values displayed are estimates. They are determined mathematically. SMA Solar Technology AG accepts no responsibility for the real yield value which can deviate from the yield values displayed here. Reasons for deviations are various outside conditions, such as soiling of the PV Modules or fluctuations in the efficiency of the PV modules.
Signature
Version: 2.00.4.R
System overview
Inverter: 9 x SMC 7000HV-11
PV-module:
A: (PV Arrays for Entire Building)
Sunpower
E19/320 (US)
Azimuth angle: -135 °, Angle of inclination: 7 °Mounting type: Roof
Technical data
Number of strings:
Number of PV modules (input):
Peak power (input):
Min. PV voltage:
Typical PV voltage:
Min. DC voltage (Grid voltage 230 V):
Max. PV voltage:
Max. DC voltage (PV):
Max. current of PV array:
Max. DC current:
PV Peak power:
Total number of PV modules:
Number of inverters:
Max. DC power (cos φ = 1):
Max. AC active power (cos φ = 1):
Grid voltage:
Nominal power ratio:
Displacement power factor cos φ:
69.12 kWp
7.50 kW
7.00 kW
230 V
98.0 %
PV/Inverter compatible
PV array and type of inverter are compatible. The nominal power ratio (max. DC power of the inverter divided by the peak power) is within the recommended range (90% - 110%).
There are probably specific grounding recommendations stated by the manufacturer for the selected PV modules.
Consult the manufacturer regarding current grounding recommendations. Please note that the grounding of the PV array takes place via a separate grounding set in the inverter.
PV-array:
Input A:
PV Arrays for Entire Building
7.68 kWp
374 V
395 V
335 V
554 V
600 V
17.6 A
23.0 A
Project name: NOB
Project number: 92937
Project file: NOB with 9 x SMC 7000HV11
Location: Central Africa / Bujumbura
Record Low Temperature: 0.00 °C
Average High Temperature: 31.00 °C
Record High Temperature: 40.00 °CPart project 1
Ambient temperature:
Evaluation of design
PV Electrical One-Line
P ro je ct
A fr ic a
N O
B
DRAWING
S ys te m
T o ta l:
8.
kW
D C
S
T C
S un po w er S
P R
-3
E -W
H T
-D st rin gs o f 8 p er in ve rt er
S
M C
H V
-1 in ve rt er s
M ou nt ed o n
S ch uc o
M od ul e
T ilt
.5
C
TITLE
REV
None
DATE
C L
IE
N
T S
Y S
T E
M D
E S
C R
IP
T
IO
N
P R
O J
E C
T
R ev
B y
D at e C o m m en t
G
LB
-0
2-
In iti al D ra ft
C kd
2011-May-10 SCALE (11"x17")
PV-E01
SHOP DRAWING
Switchboard NOBSB-E
1000A, 400/230VAC
42kA Interrupt
(Existing)
80A, 3P
1000A
Sunny WebBox
Communication hub located inside Tower
A Internal power
Supply
PV Data Monitor Network
Array
DC
AC
DATA
AC
35'
141'
127'
127'
6-PV wire 4 mm2, #8G bare
¾” RGS, 6#10 THWN-2, #8 EGC
2" RGS, 4#1/0 THWN-2, 1#6 G
Shielded 4 conductor RS-485 cable in ¾”C
2" RGS, 4#1/0 THWN-2, 1#6 G
WIRING (Minimum Requirements)
Conduit & WireDescription ~LengthLabel
B
A
C
PAGE
144 Sunpower
SPR 320E-WHT-D
PV Modules
One array per inverter; Six arrays total;
Each array comprised of three strings of eight modules or 24 modules per inverter
Voc =518V , Isc = 6.24A
Location: rooftop Positive Ground
40A, 3P
A
B
D
C
E
Tower A – Breaker 22
Tower B – Breaker 23
B.01.1.08
INV
A.01.1.01
INV
A.06.3.01
TOWER.INVERTER.STRING.MODULE
INV
03 =
INV
Sunny Tower A
A.06.3.08
A
B
INV
B.01.1.01
INV
B.03.3.01
INV
B.03.3.08
Sunny Tower B
72 Sunpower
SPR 320E-WHT-D
PV Modules
One array per inverter; Three arrays total;
Each array comprised of three strings of eight modules or 24 modules per inverter
Voc = 518V , Isc = 6.24A
Location: rooftop Positive Ground
D E
NOBSG-E
2000A bus, CB#3, 1000A
NOBSG-E-U
„CBA‟
2000A
UTLSG-E
„CBA‟
3000A bus, CB#7, 2000A
UTLSG-E-U
„CB1‟
3000A
G
Transformer
15kVΔ :400/230Y
2MVA
A.01.1.08
Inverters are connected Phase to Neutral
Exterior AC
Disconnect
Square D HU363RB
100A, 600VAC,
isolated neutral, NEMA 3R
(provided by others)
Transition Boxes A.01 A.06 B.01 B.03
M
P S
-0 3-
S ho p
D ra w in g R ev ie w
C G
LB
-0
5-
U ps iz e
S T
B , A
C r un fo r fu tu re e xp an si on
Sunny Tower “A”
6 x SMC 7000HV -11 Inverters (all used)
Sunny Tower “B”
6 x SMC 7000HV -11 Inverters
(3 used / 3 spare)
Exterior AC
Disconnect
Square D HU363RB
100A, 600VAC,
isolated neutral, NEMA 3R
(provided by others)
KEY
TOWER.INVERTER.STRING.MODULE
Example A.01.02.07 Sunny Tower A, Inverter 01, String 2, Module 7
M
P S
-0 5-
S ho p
D ra w in g R ev ie w
SHOP DRAWING
1) System shall conform to 2008 NEC, state and local Code requirements, electric utility co. requirements and manufacturers' instructions.
2) RMC (RGS) conduit and copper conductors required unless otherwise noted.
3) All conductors shall have THWN-2 (90°C) rating to ensure Code compliance, including #10 conductors.
4) All conductors shall have continuous insulation color unless #4 AWG or larger.
5) DC color coding to be black for ungrounded conductor, white for grounded conductor, and green for grounding conductor.
6) AC disconnects located adjacent to respective Tower units.
7) All connections from wire troughs to PV combiners, PV disconnects or PV inverters shall be made through conduit nipples.
8) Connections to the top of NEMA 3R or NEMA 4/4X troughs and junction boxes shall be made with listed weathertight connectors to maintain the enclosure's rating.
9) All disconnects and other equipment shall be marked and labeled as required by the 2008 NEC and all applicable state and local Codes.
10) The conduit systems shall be laid out, designed, furnished and installed to compensate for thermal expansion and contraction in accordance with 2008 NEC Article 300.7. RGS raintight expansion & contraction fittings shall be provided as directed in the field. RGS conduits to be galvanized and installed in accordance with NEC 344. All fittings shall be raintight on roof.
11) Rooftop conduits shall be installed a minimum of 3½" above the roof surface (measured to bottom of raceway).
12) The Electrical Contractor shall perform insulation resistance testing on all conductors. All readings shall be documented and provided as a report to RESC.
13) Structural review of roof by others.
14) Locks or padlocks shall be installed to secure all equipment unless location is accessible to qualified persons only.
15) At point of penetration from exterior to interior, install raceway fittings at suitable and accessible locations and fill them with sealing compound.
16) All grounding electrode conductors shall be installed in single continuous lengths except where spliced by irreversible connector or exothermic weld.
17) Maximum DC voltage calculated using module temperature coefficient for VOC.
18) Inverters connected ph to N
GENERAL NOTES (APPLY TO ALL SHEETS)
All Tower A
All Tower B
18A
18A
438 VDC
438 VDC
19A
19A
572 VDC
572VDC
61A/ph
30.43A/ph
230/400
230/400
INVERTER LABELING
DC ImaxDC Iop DC VopInverter DC Vmax AC Iop AC Vop
PV Electrical One-Line
P ro je ct
A fr ic a
N O
B
DRAWING
S ys te m
T o ta l:
8.
kW
D C
S
T C
S un po w er S
P R
-3
E -W
H T
-D st rin gs o f 8 p er in ve rt er
S
M C
H V
-1 in ve rt er s
M ou nt ed o n
S ch uc o
M od ul e
T ilt
.5
C
TITLE
REV
None
DATE
C L
IE
N
T S
Y S
T E
M D
E S
C R
IP
T
IO
N
P R
O J
E C
T
R ev
B y
D at e C o m m en t
G
LB
-0
2-
In iti al D ra ft
C kd
2011-May-10 SCALE (11"x17")
PV-E01
PAGE
Wiley Electronics ACE Box
Transition box from module USE-2 conductors to THWN-2 insulated conductors One transition box per inverter
– three PV strings per transition box, labeled per drawing
TO PV
MODULES
TO
INVERTER
TRANSITION BOX DETAIL
M
P S
-0 3-
S ho p
D ra w in g R ev ie w
C G
LB
-0
5-
U ps iz e
S T
B , A
C r un fo r fu tu re e xp an si on
M
P S
-0 5-
S ho p
D ra w in g R ev
Project 92937 Prepared by RESC NOB Tower A Date 5/9/11
Conductor Sizing and Overcurrent Device Ratings = user input needed
Step 1 - Determine Continuous Circuit Voltage
Step 1A SOURCE CIRCUIT 1 Based on IAEI News Article Isc = 6.24 A Sunpower SPR-320E "Conductor Sizing and OverCurrent Device Ratings" Vmp 54.7 V x 8 = 437.60 V Isc = 6.24 A by John Wiles (Jan./Feb. 2011) Vms 69.215 V x 1 x 8 = 553.72 V Imp = 5.86 A Imp = 5.86 A Voc = 64.8 V Step 1 Determine the continuous current in the circuit NEC Isc 6.24 A x 1.56 = 9.73 A Vmp = 54.7 V A. PV DC Circuits
6.24 A x 1.25 = 7.8 A Fuse = 20 A B. AC Inverter Output Circuits OUTPUT CIRCUIT 1 Voltage Temp Coeff -176.6 mV Isc 6.24 A x 3 = 18.72 A Step 2 Calculate the rating of the overcurrent device where required Vmp = 437.60 V Operating Conditions A. Rating determined from Continuous Currents Vms = 553.72 V Record low temperature 0 deg C B. Operating Temperature Affects Rating Imp 5.86 A x 3 = 17.58 A Highest Avg Monthly Temperature 31 deg C NEC Isc 18.72 A x 1.56 = 29.20 A Step 3 Select Conductor Size
18.72 A x 1.25 = 23.40 A A. Ampacity Requirements
Step 1B INVERTER 1 B. 125% Requirement
7000 W / 230 x 1.25 = 38.04 A Low Temperature Voc Correction 7000 W / 230 = 30.43 A String Voc 518.4 VDC Step 4 Terminal Temperature Limits
SMA SMC7000HV-11 Temp coefficient -176.6 mV/C deg Record low 0 Deg C Step 5 Verify that the overcurrent device protects the Temp diff from STC -25 Deg C conductor selected under the conditions of use.
Step 1B ST6 21000 W 230 V = 91.304348 AAC String Calcs
91.304348 A / 3 ph = 30.43 A per ph Voltage increase 35.32 VDC
Voc (temp corrected) 553.72 VDC
30.43 A x 1.25 NEC = 38.04 Max inverter DC input 800 VDC
LABELING
230 AC Operating V
30.43 AC Operating I
69.215 Voc per mod, 2008 NEC temp corrected
553.72 Voc (temp corrected) per string
518.4 uncorrected Voc
553.72 DC Max V
7.8 DC max I
437.60 DC Operating V
5.86 DC Operating I
Module Information
NOB Tower A Date 5/11/11
DC Conductor Sizing and Verification of OCP Device AC Conductor Sizing and Verification of OCP Device
THWN-2 Conductor THWN-2 Conductor THWN-2 Conductor T310.16 Table 310.15 (B)(2)(c ) ACME Junction Box to Inverter Each Inverter inside Sunny Tower Sunny Tower to Solar Backfeed Breaker Distance above roof to bottom of Conduit Temp Adder
Initial Selection of Conductor Size Based on Target Voltage Drop (<1%) Source Initial Selection of Conductor Size Based on Target Voltage Drop (<1%) Initial Selection of Conductor Size Based on Target Voltage Drop (<1%) deg C deg C deg F Inverters connected ph to N 21-25 1.04 0 to 13 mm (1/2") 33 60
141 LF (maximum DC conductor length) Drawings AC run 2 Inverters per phase 26-30 1 Above 13 mm to 90 mm 1/2" to 3 1/2" 22 40
437.60 Vmps 5 127 ft 31-35 0.96 Above 90 mm to 300 mm 3 1/2" to 12" 17 30
5.86 Imp one string 230 VAC 230 VAC 36-40 0.91 Above 300 mm to 900 mm 12" to 36" 14 25
9.73 Isc NEC 38.04 AAC NEC 76.09 AAC NEC 41-45 0.87
7.80 Isc Continuous 30.43 AAC Continuous 60.87 AAC Continuous 46-50 0.82
Voltage drop Vmp * Imp Voltage Drop Vdrop combined 51-55 0.76 10 AWG Conductor Size User selected 8 AWG Conductor Size 1/0 AWG Conductor Size 56-60 0.71
141.00 DC run in feet 5.00 AC run in feet 127 AC run combiner to POC 61-70 0.58
5.86 Imp of source ckt 30.43 AC Imp 60.87 AC Imp 71-80 0.41
0.47% Vdrop Chosen from Voltage Drop DC worksheet Chap. 9, Table 8 0.10% Voltage drop AC 0.92% 0.82% AC Vdrop combined
Step 2 Step 2 Step 2
38.0 76.1
Table 310.15(B)(2)(a) - Conduit Fill Correction Factors Use 40 Amp Breaker Use 80 Amp Breaker # of current carrying conductors
4 to 6 80 7 to 9 70 10 to 20 50 21 to 30 45
Step 3A Select Conductor Size (Ampacity) Step 3A Select Conductor Size (Ampacity) Step 3A Select Conductor Size (Ampacity) 31 to 40 40 10 AWG Conductor Size 8 AWG Conductor Size 1/0 AWG Conductor Size 41 and above 35 40 amps Conductor rating at 90 deg C Table 310.16 55 amps Conductor rating at 90 deg C 170 amps Conductor rating at 90 deg C
31 31 31
22 Table 310.15 (B)(2)(c ) 22
53 53
0.76 Table 310.16 0.76
0.76
30.40 42 129.20
6 # current carrying conductors in conduit Three strings x 2 (plus, minus) and EG
2 # current carrying of conductors in conduit
L1 , N and EG 4 # of current carrying conductors in conduit
L1, L2, L3, N and EG
0.8 derate for conduit fill Table 310.15(B)(2)(a) 1 derate for conduit fill 0.8 derate for conduit fill
24.32 amps Conductor Operating Capacity 41.80 amps Conductor Operating Capacity 103.36 amps Conductor Operating Capacity
15.60 amps Continuous Current (Strings in parallel minus one) 30.43 amps Continuous Current 60.87 amps Continuous Current
Yes Is Conductor Operating Capacity > Continuous Current Yes Is Conductor Operating Capacity > Continuous Current Yes Is Conductor Operating Capacity > Continuous Current
Step 3B Select Conductor Size (125% Requirement) Step 3B Select Conductor Size (125% Requirement) Step 3B Select Conductor Size (125% Requirement) 10 AWG Conductor Size 8 AWG Conductor Size 1/0 AWG Conductor Size 40 amps Conductor Rating at 90 Deg C Table 310.16 55 amps Conductor Rating at 90 Deg C 170 amps Conductor Rating at 90 Deg C
19.5 38 76
Yes Yes Yes
Step 3 Final Conductor Selection Step 3 Final Conductor Selection Step 3 Final Conductor Selection 10 AWG Conductor Size (Ampacity Requirement) 8 AWG Conductor Size (Ampacity Requirement) 1/0 AWG Conductor Size (Ampacity Requirement) 10 AWG Conductor Size (125% Requirement) 8 AWG Conductor Size (125% Requirement) 1/0 AWG Conductor Size (125% Requirement) 10 AWG Use Larger Conductor Size 8 AWG Use Larger Conductor Size 1/0 AWG Use Larger Conductor Size
Step 4 Check Terminal Temperature Limits Step 4 Step 4
10 AWG Chosen Conductor Size from Step 3 8 AWG Chosen Conductor Size from Step 3 1/0 AWG Chosen Conductor Size from Step 3
35 amps Conductor Rating at 75 deg C Table 310.16 50 amps Conductor Rating at 75 deg C 150 amps Conductor Rating at 75 deg C
19.5 38.0 76.1
Yes Yes Yes
Step 5 Check for OCP Device Sizing to protect conductor under actual operating conditions Step 5 Check OCP Device Sizing Step 5 Check OCP Device Sizing A. Normal method for choosing OCP Device A. Normal Method for Choosing OCP Device
No OCP required. 38.0 amps 125% of Continuous Current 76.1 amps 125% of Continuous Current Round up to Breaker Size Round up to Breaker Size
40 amps Chosen Breaker 80 amps Chosen Breaker Conduit Fill Annex C, Table C.8 Need 6 current carrying #10 THWN-2 Max. number of conductors B. Checking OCP Device to protect conductor under actual operating conditions B. Checking OCP Device to protect conductor under actual operating conditions 3/4" RMC (RGS) is good for 10 in rigid metal conduct (RMC) Check Chosen Conductor Capacity under actual operating condiitons Check Chosen Conductor Capacity under actual operating condiitons
8 AWG Conductor Size 1/0 AWG Conductor Size 55 amps Conductor rating at 90 deg C 170 amps Conductor rating at 90 deg C
31 31 22 22 53 53
0.76 0.76 42 129
2 # current carrying of conductors in conduitL1 , N and EG 4 # current carrying of conductors in conduitL1 ,L2, L3 and N and EG 1 derate for conduit fill 0.8 derate for conduit fill
42 amps Conductor Operating Capacity 103 amps Conductor Operating Capacity
45 110
Yes Is Chosen Breaker in "A" smaller than Max possible breaker "B" Yes Is Chosen Breaker in "A" smaller than Max possible breaker in "B" If "NO", have to use a larger conductor size If "NO", have to use a larger conductor size
Conduit Fill Conduit fill Need 6 current carrying # 8 THWN-2 Need 4 #1/0 THWN-2 1" RMC (RGS) is good for 9 2" RMC (RGS) good for 7 deg C (Estimated Operating Temperature) on roof amps - Maximum possible breaker that could be used based on Conductor Operating Capacity
Ambient avg high temperature (deg C) deg C (Estimated Operating Temperature) on roof amps - Maximum possible breaker that could be used based on Conductor Operating Capacity
Temperature Added for operating conditions (deg C) assuming
Temperature correction factor amps (temperature adjusted ampacity of selected conductor)
Temperature Added for operating conditions (deg C)
Temperature correction factor amps (temperature adjusted ampacity of selected amps 125% of Continuous Current
Check Terminal Temperature Limits Check Terminal Temperature Limits amps 125% of Continuous Current
Ambient avg high temperature (deg C)
Is conductor rating (@75 deg C) capacity > 125% of Continuous Current
Is current rating (@75 deg C) capacity > 125% of Continuous Current
String fusing not necessary because continuos current of 2 strings in parallel (15.6 amps) is less than module module manufacturer OCP requirements (20 amps)
Calculate the Rating of the Overcurrent Protection Device, where requiredCalculate the Rating of the Overcurrent Protection Device, where required Calculate the Rating of the Overcurrent Protection Device, where required
125% of continuous current
Temperature Correction Factors
THWN-2, Cu
Ambient avg high temperature (deg C) deg C (Estimated Operating Temperature) on roof
Ambient avg high temperature (deg C) ft from inverter to Sunny Tower
% of values
125% of continuous current
See Step 2
Temperature Added for operating conditions (deg C) assuming conduit within 4 inches of roof surface amps (temperature adjusted ampacity of selected conductor) deg C (Estimated Operating Temperature) on roof
Temperature correction factor amps 125% of Continuous Current (strings in parallel minus one) Is conductor rating (90 deg C) >125% of continuous current amps 125% of Continuous Current (strings in parallel
Is conductor rating (@75 deg C) capacity > 125% of Continuous Current
Ambient avg high temperature (deg C) amps 125% of Continuous Current
Is conductor rating (90 deg C) >125% of continuous current amps 125% of Continuous Current
Is conductor rating (90 deg C) >125% of continuous current
Temperature Added for operating conditions (deg C) assuming conduit within 4 inches of roof surface deg C (Estimated Operating Temperature) on roof
Temperature correction factor amps (temperature adjusted ampacity of selected conductor)
Temperature Added for operating conditions (deg C) assuming conduit within 4 inches of roof surface
Temperature correction factor amps (temperature adjusted ampacity of selected conductor)
NOB Tower B Date 5/9/11
Conductor Sizing and Overcurrent Device Ratings = user input needed
Step 1 - Determine Continuous Circuit Voltage
Step 1A SOURCE CIRCUIT 1 Based on IAEI News Article Isc = 6.24 A Sunpower SPR-320E "Conductor Sizing and OverCurrent Device Ratings" Vmp 54.7 V x 8 = 437.60 V Isc = 6.24 A by John Wiles (Jan./Feb. 2011) Vms 69.215 V x 1 x 8 = 553.72 V Imp = 5.86 A Imp = 5.86 A Voc = 64.8 V Step 1 Determine the continuous current in the circuit NEC Isc 6.24 A x 1.56 = 9.73 A Vmp = 54.7 V A. PV DC Circuits
6.24 A x 1.25 = 7.8 A Fuse = 20 A B. AC Inverter Output Circuits OUTPUT CIRCUIT 1 Voltage Temp Coeff -176.6 mV Isc 6.24 A x 3 = 18.72 A Step 2 Calculate the rating of the overcurrent device where required Vmp = 437.60 V Operating Conditions A. Rating determined from Continuous Currents Vms = 553.72 V Record low temperature 0 deg C B. Operating Temperature Affects Rating Imp 5.86 A x 3 = 17.58 A Highest Avg Monthly Temperature 31 deg C NEC Isc 18.72 A x 1.56 = 29.20 A Step 3 Select Conductor Size
18.72 A x 1.25 = 23.40 A A. Ampacity Requirements
Step 1B INVERTER 1 B. 125% Requirement
7000 W / 230 x 1.25 = 38.04 A Low Temperature Voc Correction 7000 W / 230 = 30.43 A String Voc 518.4 VDC Step 4 Terminal Temperature Limits
SMA SMC7000HV-11 Temp coefficient -176.6 mV/C deg Record low 0 Deg C Step 5 Verify that the overcurrent device protects the Temp diff from STC -25 Deg C conductor selected under the conditions of use.
Step 1B ST6 21000 W 230 V = 91.304348 AAC String Calcs
91.304348 A / 3 ph = 30.43 A per ph Voltage increase 35.32 VDC
Voc (temp corrected) 553.72 VDC
30.43 A x 1.25 NEC = 38.04 Max inverter DC input 800 VDC
LABELING
230 AC Operating V
30.43 AC Operating I
69.215 Voc per mod, 2008 NEC temp corrected
553.72 Voc (temp corrected) per string
518.4 uncorrected Voc
553.72 DC Max V
7.8 DC max I
437.60 DC Operating V
NOB Tower B Date 5/11/11
DC Conductor Sizing and Verification of OCP Device AC Conductor Sizing and Verification of OCP Device
THWN-2 Conductor THWN-2 Conductor THWN-2 Conductor T310.16 Table 310.15 (B)(2)(c ) ACME Junction Box to Inverter Each Inverter inside Sunny Tower Sunny Tower to Solar Backfeed Breaker Distance above roof to bottom of Conduit Temp Adder
Initial Selection of Conductor Size Based on Target Voltage Drop (<1%) Source Initial Selection of Conductor Size Based on Target Voltage Drop (<1%) Initial Selection of Conductor Size Based on Target Voltage Drop (<1%) deg C deg C deg F Inverters connected ph to N 21-25 1.04 0 to 13 mm (1/2") 33 60
141 LF (maximum DC conductor length) Drawings AC run 2 Inverters per phase See Note 1 26-30 1 Above 13 mm to 90 mm 1/2" to 3 1/2" 22 40
437.60 Vmps 5 127 ft 31-35 0.96 Above 90 mm to 300 mm 3 1/2" to 12" 17 30
5.86 Imp one string 230 VAC 230 VAC 36-40 0.91 Above 300 mm to 900 mm 12" to 36" 14 25
9.73 Isc NEC 38.04 AAC NEC 76.09 AAC NEC 41-45 0.87
7.80 Isc Continuous 30.43 AAC Continuous 60.87 AAC Continuous 46-50 0.82
Voltage drop Vmp * Imp Voltage Drop Vdrop combined 51-55 0.76 10 AWG Conductor Size User selected 8 AWG Conductor Size 1/0 AWG Conductor Size 56-60 0.71
141.00 DC run in feet 5.00 AC run in feet 127 AC run combiner to POC 61-70 0.58
5.86 Imp of source ckt 30.43 AC Imp 60.87 AC Imp 71-80 0.41
0.47% Vdrop Chosen from Voltage Drop DC worksheet Chap. 9, Table 8 0.10% Voltage drop AC 0.92% 0.82% AC Vdrop combined
Step 2 Step 2 Step 2
38.0 76.1
Table 310.15(B)(2)(a) - Conduit Fill Correction Factors Use 40 Amp Breaker Use 80 Amp Breaker See Note 2 # of current carrying conductors
4 to 6 80 7 to 9 70 10 to 20 50 21 to 30 45
Step 3A Select Conductor Size (Ampacity) Step 3A Select Conductor Size (Ampacity) Step 3A Select Conductor Size (Ampacity) 31 to 40 40 10 AWG Conductor Size 8 AWG Conductor Size 1/0 AWG Conductor Size 41 and above 35 40 amps Conductor rating at 90 deg C Table 310.16 55 amps Conductor rating at 90 deg C 170 amps Conductor rating at 90 deg C
31 31 31
22 Table 310.15 (B)(2)(c ) 22
53 53
0.76 Table 310.16 0.76
0.76
30.40 42 129.20
6 # current carrying conductors in conduit Three strings x 2 (plus, minus) and EG
2 # current carrying of conductors in conduit
L1 , N and EG 4 # of current carrying conductors in conduit
L1, L2, L3, N and EG
0.8 derate for conduit fill Table 310.15(B)(2)(a) 1 derate for conduit fill 0.8 derate for conduit fill
24.32 amps Conductor Operating Capacity 41.80 amps Conductor Operating Capacity 103.36 amps Conductor Operating Capacity
15.60 amps Continuous Current (Strings in parallel minus one) 30.43 amps Continuous Current 60.87 amps Continuous Current
Yes Is Conductor Operating Capacity > Continuous Current Yes Is Conductor Operating Capacity > Continuous Current Yes Is Conductor Operating Capacity > Continuous Current
Step 3B Select Conductor Size (125% Requirement) Step 3B Select Conductor Size (125% Requirement) Step 3B Select Conductor Size (125% Requirement) 10 AWG Conductor Size 8 AWG Conductor Size 1/0 AWG Conductor Size 40 amps Conductor Rating at 90 Deg C Table 310.16 55 amps Conductor Rating at 90 Deg C 170 amps Conductor Rating at 90 Deg C
19.5 38 76
Yes Yes Yes
Step 3 Final Conductor Selection Step 3 Final Conductor Selection Step 3 Final Conductor Selection 10 AWG Conductor Size (Ampacity Requirement) 8 AWG Conductor Size (Ampacity Requirement) 1/0 AWG Conductor Size (Ampacity Requirement) 10 AWG Conductor Size (125% Requirement) 8 AWG Conductor Size (125% Requirement) 1/0 AWG Conductor Size (125% Requirement) 10 AWG Use Larger Conductor Size 8 AWG Use Larger Conductor Size 1/0 AWG Use Larger Conductor Size
Step 4 Check Terminal Temperature Limits Step 4 Step 4
10 AWG Chosen Conductor Size from Step 3 8 AWG Chosen Conductor Size from Step 3 1/0 AWG Chosen Conductor Size from Step 3
35 amps Conductor Rating at 75 deg C Table 310.16 50 amps Conductor Rating at 75 deg C 150 amps Conductor Rating at 75 deg C
19.5 38.0 76.1
Yes Yes Yes
Step 5 Check for OCP Device Sizing to protect conductor under actual operating conditions Step 5 Check OCP Device Sizing Step 5 Check OCP Device Sizing A. Normal method for choosing OCP Device A. Normal Method for Choosing OCP Device
No OCP required. 38.0 amps 125% of Continuous Current 76.1 amps 125% of Continuous Current Round up to Breaker Size Round up to Breaker Size
40 amps Chosen Breaker 80 amps Chosen Breaker Conduit Fill Annex C, Table C.8 Need 6 current carrying #10 THWN-2 Max. number of conductors B. Checking OCP Device to protect conductor under actual operating conditions B. Checking OCP Device to protect conductor under actual operating conditions 3/4" RMC (RGS) is good for 10 in rigid metal conduct (RMC) Check Chosen Conductor Capacity under actual operating condiitons Check Chosen Conductor Capacity under actual operating condiitons
8 AWG Conductor Size 1/0 AWG Conductor Size 55 amps Conductor rating at 90 deg C 170 amps Conductor rating at 90 deg C
31 31 22 22 53 53
0.76 0.76 42 129
2 # current carrying of conductors in conduitL1 , N and EG 4 # current carrying of conductors in conduitL1 ,L2, L3 and N and EG 1 derate for conduit fill 0.8 derate for conduit fill
42 amps Conductor Operating Capacity 103 amps Conductor Operating Capacity
45 110
Yes Is Chosen Breaker in "A" smaller than Max possible breaker "B" Yes Is Chosen Breaker in "A" smaller than Max possible breaker in "B" If "NO", have to use a larger conductor size If "NO", have to use a larger conductor size
Conduit Fill Conduit fill Need 6 current carrying # 8 THWN-2 Need 4 #1/0 THWN-2 1" RMC (RGS) is good for 9 2" RMC (RGS) good for 7 deg C (Estimated Operating Temperature) on roof amps - Maximum possible breaker that could be used based on Conductor Operating Capacity
Ambient avg high temperature (deg C) deg C (Estimated Operating Temperature) on roof amps - Maximum possible breaker that could be used based on Conductor Operating Capacity
Temperature Added for operating conditions (deg C) assuming
Temperature correction factor amps (temperature adjusted ampacity of selected conductor)
Temperature Added for operating conditions (deg C)
Temperature correction factor amps (temperature adjusted ampacity of selected amps 125% of Continuous Current
Check Terminal Temperature Limits Check Terminal Temperature Limits amps 125% of Continuous Current
Ambient avg high temperature (deg C)
Is conductor rating (@75 deg C) capacity > 125% of Continuous Current
Is current rating (@75 deg C) capacity > 125% of Continuous Current
String fusing not necessary because continuos current of 2 strings in parallel (15.6 amps) is less than module module manufacturer OCP requirements (20 amps)
Calculate the Rating of the Overcurrent Protection Device, where requiredCalculate the Rating of the Overcurrent Protection Device, where required Calculate the Rating of the Overcurrent Protection Device, where required
125% of continuous current
Temperature Correction Factors
THWN-2, Cu
Ambient avg high temperature (deg C) deg C (Estimated Operating Temperature) on roof
Ambient avg high temperature (deg C) Note 1 - Sunny Tower AC output conductors based on the assumption that three additional SMC 7000HV-11 inverters may be added to the tower at a later date
Note 2 - Will install 40 amp, 3 phase solar backfeed breaker on distribution panel. Only one inverter per phase will be used initially on Sunny Tower "B". Solar backfeed breaker will have to be increased to an 80 amps breaker if additional three inverters are added to Sunny Tower "B" at a later date.
ft from inverter to Sunny Tower
% of values
125% of continuous current
See Step 2
Temperature Added for operating conditions (deg C) assuming conduit within 4 inches of roof surface amps (temperature adjusted ampacity of selected conductor) deg C (Estimated Operating Temperature) on roof
Temperature correction factor amps 125% of Continuous Current (strings in parallel minus one) Is conductor rating (90 deg C) >125% of continuous current amps 125% of Continuous Current (strings in parallel
Is conductor rating (@75 deg C) capacity > 125% of Continuous Current
Ambient avg high temperature (deg C) amps 125% of Continuous Current
Is conductor rating (90 deg C) >125% of continuous current amps 125% of Continuous Current
Is conductor rating (90 deg C) >125% of continuous current
Temperature Added for operating conditions (deg C) assuming conduit within 4 inches of roof surface deg C (Estimated Operating Temperature) on roof
Temperature correction factor amps (temperature adjusted ampacity of selected conductor)
Temperature Added for operating conditions (deg C) assuming conduit within 4 inches of roof surface
Temperature correction factor
MSGQ
Building
Electrical Drawing and Calculations
15.36 kW
PV
Array x 320W SunPower modules x
SMA
SMC
5000A Inverters
P.O. Box 967
54 Holly Hill Road (packages)
Averill Park, NY 12018
USA
Michael P. Stangl, P.E. • Renewable Power Design Group • P.O. Box 967 • 54
Tel.: +01 518 674-3684
Fax: +01 518 514-1212
E-Mail: MStangl@rpdg.us.com
MSGQ - Burundi
92937
MSGQ with 3 x SMC 5000A
Location: Central Africa / Bujumbura
Grid voltage: 3~400 V
Project name:
Project number:
Project file:
System overview Part project 1
48 x Sunpower E19/320 (US) (MSGQ Buliding)
Azimuth angle: -135 °, Angle of inclination: 7 °, Mounting type: Roof, PV Peak power: 15.36 kW
Inverters:
3 x SMC 5000A (Inverter efficiency: 95.0 %)
Technical data
Total number of PV modules:
PV Peak power: 15.36 kWp
Number of inverters: 3
Nominal AC power: 15.00 kW
Annual energy yield (approx.)*:
22771.10 kWh
Energy usability factor: 100.0 %
Performance ratio (approx.
83.2 %
Spec. energy yield (approx.
1482 kWh/kWp
Line losses (in % of PV energy):
Unbalanced load: 0.00 VA
Notes:
Important: The yield values displayed are estimates. They are determined mathematically. SMA Solar Technology AG accepts no responsibility for the real yield value which can deviate from the yield values displayed here. Reasons for deviations are various outside conditions, such as soiling of the PV Modules or fluctuations in the efficiency of the PV modules.
Inverter: 3 x SMC 5000A
PV-module:
A: (MSGQ Buliding)
Sunpower
E19/320 (US)
Azimuth angle: -135 °, Angle of inclination: 7 °Mounting type: Roof
Technical data
Number of strings:
Number of PV modules (input):
Peak power (input):
Min. PV voltage:
Typical PV voltage:
Min. DC voltage (Grid voltage 230 V):
Max. PV voltage:
Max. DC voltage (PV):
Max. current of PV array:
Max. DC current:
PV Peak power:
Total number of PV modules:
Number of inverters:
Max. DC power:
Max. AC power:
Grid voltage:
Nominal power ratio:
15.36 kWp
5.75 kW
5.50 kW
230 V
112.0 %
PV/Inverter conditionally compatible
PV array and inverter type are only partly compatible since the inverter is over-dimensioned for this combination (> 110 %).
There are probably specific grounding recommendations stated by the manufacturer for the selected PV modules.
Consult the manufacturer regarding current grounding recommendations. Please note that the grounding of the PV array takes place via a separate grounding set in the inverter.
PV-array:
Input A:
MSGQ Buliding
5.12 kWp
374 V
395 V
246 V
554 V
600 V
11.7 A
26.0 A
Project name: MSGQ - Burundi
Project number: 92937
Project file: MSGQ with 3 x SMC 5000A
Location: Central Africa / Bujumbura
Record Low Temperature: 0.00 °C
Average High Temperature: 31.00 °C
Record High Temperature: 40.00 °CPart project 1
Ambient temperature:
ro je ct
A fr ic a
M S
G Q
DRAWING
S ys te m
T o ta l:
5.
kW D
C
S T
C
S un po w er
S P
R -3
E
-W H
T -D st rin gs o f 8 p er in ve rt er
S
M C
H V
-1 in ve rt er s
M ou nt ed o n
S ch uc o
M od ul e
T ilt
.5
A zi m ut h
N A
C
TITLE
REV
None
DATE
C L
IE
N
T S
Y S
T E
M D
E S
C R
IP
T
IO
N
P R
O J
E C
T
R ev
B y
D at e C o m m en t
G
LB
-0
2-
In iti al D ra ft
C kd
2011-May-10 SCALE (11"x17")
PV-E01
SHOP DRAWING
Panelboard MDP
?A, 400/230VAC
25kA Interrupt
(Existing)
30A, 3P
400A
Sunny WebBox
Communication hub mounted inside tower Power from Sunny Tower
PV Data Monitor Network
Array
DC
AC
DATA
30'
80'
105'
6- PV wire 4 mm2, #8G bare
¾” RGS, 6#10 THWN-2, #8 EGC
1 ¼” RGS, 4#4 THWN-2, 1#6 G
Shielded 4 conductor RS-485 cable in ¾”C
WIRING (Minimum Requirements)
Conduit & WireDescription ~LengthLabel
B
A
C
PAGE
48 Sunpower
SPR 320E-WHT-D
PV Modules
One array per inverter; Two arrays total;
Each array comprised of 2 strings of eight modules or 16 modules per inverter
Voc =518 , Isc = 6.24A
Location: rooftop Positive Ground
D
C
Inverter breakers 38, 40, 42
TOWER.INVERTER.STRING.MODULE
D
UTLSB-U
1600A bus, CB#1, 400A CB, 65kAIC
UTLSG-U
„CB#11‟
3000A bus, 1000A CB, 65kAIC
UTLSG-E-U
„CB#3‟
3000A bus, 3000A
G
Transformer
15kVΔ :400/230Y
2MVA
Room MQ110
M
P S
-0 2-
S ho p
D ra w in gs R ev ie w
C G
LB
-0
5-
C ha ng e in ve rt er s to
S T
M C
A
KEY
TOWER.INVERTER.STRING.MODULE
Example A.01.02.07 Sunny Tower A, Inverter 01, String 2, Module 7
A.01.1.08
A
B
INV
A.01.1.01
INV
A.02.3.01
INV
A.02.3.08
Sunny Tower A Located on rooftop
A.01 A.03
Exterior AC
Disconnect
Square D HU363RB
100A, 600VAC,
isolated neutral, NEMA 3R
(provided by others)
Sunny Tower “A”
6 x SMC 5000A Inverters (3 used/3 spare)
M
P S
-0 5-
S ho p
D ra w in gs R ev
1) System shall conform to 2008 NEC, state and local Code requirements, electric utility co. requirements and manufacturers' instructions.
2) RMC (RGS) conduit and copper conductors required unless otherwise noted.
3) All conductors shall have THWN-2 (90°C) rating to ensure Code compliance, including #10 conductors.
4) All conductors shall have continuous insulation color unless #4 AWG or larger.
5) DC color coding to be black for ungrounded conductor, white for grounded conductor, and green for grounding conductor.
6) Inverters connected phase to neutral.
7) All connections from wire troughs to PV combiners, PV disconnects or PV inverters shall be made through conduit nipples.
8) Connections to the top of NEMA 3R or NEMA 4/4X troughs and junction boxes shall be made with listed weathertight connectors to maintain the enclosure's rating.
9) All disconnects and other equipment shall be marked and labeled as required by the 2008 NEC and all applicable state and local Codes.
10) The conduit systems shall be laid out, designed, furnished and installed to compensate for thermal expansion and contraction in accordance with 2008 NEC Article 300.7. RMC raintight expansion & contraction fittings shall be provided as directed in the field. RMC conduits to be galvanized and installed in accordance with NEC 344. All fittings shall be raintight on roof.
11) Rooftop conduits shall be installed a minimum of 3 1/2" above the roof surface (measured to bottom of raceway).
12) The Electrical Contractor shall perform insulation resistance testing on all conductors. All readings shall be documented and provided as a report to RESC.
13) Structural review of roof by others.
14) Locks or padlocks shall be installed to secure all equipment unless location is accessible for qualified persons only.
15) At point of penetration from exterior to interior, install raceway fittings at suitable and accessible locations and fill them with sealing compound.
16) All grounding electrode conductors shall be installed in single continuous lengths except where spliced by irreversible connector or exothermic weld.
17) Maximum DC voltage calculated using module temperature coefficient for VOC.
GENERAL NOTES (APPLY TO ALL SHEETS)
A.01 - 03 12A 438V13A 571V 22A 230/400
INVERTER LABELING
DC ImaxDC Iop DC VopInverter DC Vmax AC Iop AC Vop
PV Electrical One-Line
P ro je ct
A fr ic a
M S
G Q
DRAWING
S ys te m
T o ta l:
5.
kW D
C
S T
C
S un po w er
S P
R -3
E
-W H
T -D st rin gs o f 8 p er in ve rt er
S
M C
H V
-1 in ve rt er s
M ou nt ed o n
S ch uc o
M od ul e
T ilt
.5
A zi m ut h
N A
C
TITLE
REV
None
DATE
C L
IE
N
T S
Y S
T E
M D
E S
C R
IP
T
IO
N
P R
O J
E C
T
R ev
B y
D at e C o m m en t
G
LB
-0
2-
In iti al D ra ft
C kd
2011-May-10 SCALE (11"x17")
PV-E01
PAGE
Wiley Electronics ACE Box
Transition box from module USE-2 conductors to THWN-2 insulated conductors One transition box per inverter
– three PV strings per transition box, labeled per drawing
TO PV
MODULES
TO
INVERTER
TRANSITION BOX DETAIL
M
P S
-0 5-
S ho p
D ra w in gs R ev
MSGQ 3 x SMC 5000A inverters Date 5/12/11
Conductor Sizing and Overcurrent Device Ratings = user input needed
Step 1 - Determine Continuous Circuit Voltage
Step 1A SOURCE CIRCUIT 1 Based on IAEI News Article Isc = 6.24 A Sunpower SPR-320E "Conductor Sizing and OverCurrent Device Ratings" Vmp 54.7 V x 8 = 437.60 V Isc = 6.24 A by John Wiles (Jan./Feb. 2011) Vms 69.215 V x 1 x 8 = 553.72 V Imp = 5.86 A Imp = 5.86 A Voc = 64.8 V Step 1 Determine the continuous current in the circuit NEC Isc 6.24 A x 1.56 = 9.73 A Vmp = 54.7 V A. PV DC Circuits
6.24 A x 1.25 = 7.8 A Fuse = 20 A B. AC Inverter Output Circuits OUTPUT CIRCUIT 1 Voltage Temp Coeff -176.6 mV Isc 6.24 A x 2 = 12.48 A Step 2 Calculate the rating of the overcurrent device where required Vmp = 437.60 V Operating Conditions A. Rating determined from Continuous Currents Vms = 553.72 V Record low temperature 0 deg C B. Operating Temperature Affects Rating Imp 5.86 A x 2 = 11.72 A Highest Avg Monthly Temperature 31 deg C NEC Isc 12.48 A x 1.56 = 19.47 A Step 3 Select Conductor Size
12.48 A x 1.25 = 15.60 A A. Ampacity Requirements
Step 1B INVERTER 1 B. 125% Requirement
5000 W / 230 x 1.25 = 27.17 A Low Temperature Voc Correction 5000 W / 230 = 21.74 A String Voc 518.4 VDC Step 4 Terminal Temperature Limits
SMA SMC7000HV-11 Temp coefficient -176.6 mV/C deg Record low 0 Deg C Step 5 Verify that the overcurrent device protects the Temp diff from STC -25 Deg C conductor selected under the conditions of use.
Step 1B ST6 15000 W 230 V = 65.217391 AAC String Calcs
65.217391 A / 3 ph = 21.74 A per ph Voltage increase 35.32 VDC
Voc (temp corrected) 553.72 VDC
21.74 A x 1.25 NEC = 27.17 Max inverter DC input 800 VDC
LABELING
230 AC Operating V
21.74 AC Operating I
69.215 Voc per mod, 2008 NEC temp corrected
553.72 Voc (temp corrected) per string
518.4 uncorrected Voc
553.72 DC Max V
7.8 DC max I
437.60 DC Operating V
MSGQ 3 x SMC 5000A inverters Date 5/11/11
DC Conductor Sizing and Verification of OCP Device AC Conductor Sizing and Verification of OCP Device
THWN-2 Conductor THWN-2 Conductor THWN-2 Conductor T310.16 Table 310.15 (B)(2)(c ) ACME Junction Box to Inverter Inside Sunny Tower Sunny Tower to Solar Backfeed Breaker Distance above roof to bottom of Conduit Temp Adder
Initial Selection of Conductor Size Based on Target Voltage Drop (<1%) Source Initial Selection of Conductor Size Based on Target Voltage Drop (<1%) Initial Selection of Conductor Size Based on Target Voltage Drop (<1%) deg C deg C deg F Inverters connected ph to N 21-25 1.04 0 to 13 mm (1/2") 33 60
112 LF (maximum DC conductor length) Drawings AC run 1 Inverters per phase 26-30 1 Above 13 mm to 90 mm 1/2" to 3 1/2" 22 40
437.60 Vmps 5 105 ft 31-35 0.96 Above 90 mm to 300 mm 3 1/2" to 12" 17 30
5.86 Imp one string 230 VAC 230 VAC 36-40 0.91 Above 300 mm to 900 mm 12" to 36" 14 25
9.73 Isc NEC 27.17 AAC NEC 27.17 AAC NEC 41-45 0.87
7.80 Isc Continuous 21.74 AAC Continuous 21.74 AAC Continuous 46-50 0.82
Voltage drop Vmp * Imp Voltage Drop Vdrop combined 51-55 0.76 10 AWG Conductor Size User selected 8 AWG Conductor Size 4 AWG Conductor Size 56-60 0.71
112.00 DC run in feet 5.00 AC run in feet 105 AC run combiner to POC 61-70 0.58
5.86 Imp of source ckt 21.74 AC Imp 21.74 AC Imp 71-80 0.41
0.37% Vdrop Chosen from Voltage Drop DC worksheet Chap. 9, Table 8 0.07% Voltage drop AC 0.68% 0.61% AC Vdrop combined
Upsized conductor size to match same conductors as used for Sunny Tower conductors
Step 2 Step 2 Step 2
27.2 27.2
Table 310.15(B)(2)(a) - Conduit Fill Correction Factors Use 30 Amp Breaker Use 30 Amp Breaker # of current carrying conductors
4 to 6 80 7 to 9 70 10 to 20 50 21 to 30 45
Step 3A Select Conductor Size (Ampacity) Step 3A Select Conductor Size (Ampacity) Step 3A Select Conductor Size (Ampacity) 31 to 40 40 10 AWG Conductor Size 8 AWG Conductor Size 4 AWG Conductor Size 41 and above 35 40 amps Conductor rating at 90 deg C Table 310.16 55 amps Conductor rating at 90 deg C 95 amps Conductor rating at 90 deg C
31 31 31
22 Table 310.15 (B)(2)(c ) 4
Sunny Tower on roof
53 35
0.76 Table 310.16 0.96 Inside
Tower
0.76
30.40 53 72.20
6 # current carrying conductors in conduit Three strings x 2 (plus, minus) and EG
2 # current carrying of conductors in conduit
L and N and EG 4 # of current carrying conductors in conduit
L1, L2, L3, N and EG
0.8 derate for conduit fill Table 310.15(B)(2)(a) 1 derate for conduit fill 0.8 derate for conduit fill
24.32 amps Conductor Operating Capacity 52.80 amps Conductor Operating Capacity 57.76 amps Conductor Operating Capacity
7.80 amps Continuous Current (Strings in parallel minus one) 21.74 amps Continuous Current 21.74 amps Continuous Current Yes Is Conductor Operating Capacity > Continuous Current Yes Is Conductor Operating Capacity > Continuous Current Yes Is Conductor Operating Capacity > Continuous Current
Step 3B Select Conductor Size (125% Requirement) Step 3B Select Conductor Size (125% Requirement) Step 3B Select Conductor Size (125% Requirement) 10 AWG Conductor Size 8 AWG Conductor Size 4 AWG Conductor Size 40 amps Conductor Rating at 90 Deg C Table 310.16 55 amps Conductor Rating at 90 Deg C 95 amps Conductor Rating at 90 Deg C
9.75 27 27
Yes Yes Yes
Step 3 Final Conductor Selection Step 3 Final Conductor Selection Step 3 Final Conductor Selection 10 AWG Conductor Size (Ampacity Requirement) 8 AWG Conductor Size (Ampacity Requirement) 4 AWG Conductor Size (Ampacity Requirement) 10 AWG Conductor Size (125% Requirement) 8 AWG Conductor Size (125% Requirement) 4 AWG Conductor Size (125% Requirement) 10 AWG Use Larger Conductor Size 8 AWG Use Larger Conductor Size 4 AWG Use Larger Conductor Size
Step 4 Check Terminal Temperature Limits Step 4 Step 4
10 AWG Chosen Conductor Size from Step 3 8 AWG Chosen Conductor Size from Step 3 4 AWG Chosen Conductor Size from Step 3
35 amps Conductor Rating at 75 deg C Table 310.16 50 amps Conductor Rating at 75 deg C 85 amps Conductor Rating at 75 deg C
9.75 27.2 27.2
Yes Yes Yes
Step 5 Check for OCP Device Sizing to protect conductor under actual operating conditions Step 5 Check OCP Device Sizing Step 5 Check OCP Device Sizing A. Normal method for choosing OCP Device A. Normal Method for Choosing OCP Device
No OCP required. 27.2 amps 125% of Continuous Current 27.2 amps 125% of Continuous Current Round up to Breaker Size Round up to Breaker Size
30 amps Chosen Breaker 30 amps Chosen Breaker Conduit Fill Annex C, Table C.8 Need 6 current carrying #10 THWN-2 Max. number of conductors B. Checking OCP Device to protect conductor under actual operating conditions B. Checking OCP Device to protect conductor under actual operating conditions 3/4" RMC (RGS) is good for 10 conductors max. in rigid metal conduct (RMC) Check Chosen Conductor Capacity under actual operating condiitons Check Chosen Conductor Capacity under actual operating condiitons
8 AWG Conductor Size 4 AWG Conductor Size 55 amps Conductor rating at 90 deg C 95 amps Conductor rating at 90 deg C
31 31 4 22
35 53
0.96 0.76
53 72 2 # current carrying of conductors in conduitL1 , N and EG 4 # current carrying of conductors in conduitL1 ,L2, L3 and N and EG 1 derate for conduit fill 0.8 derate for conduit fill
53 amps Conductor Operating Capacity 58 amps Conductor Operating Capacity
60 60
Yes Is Chosen Breaker in "A" smaller than Max possible breaker "B" Yes Is Chosen Breaker in "A" smaller than Max possible breaker in "B" If "NO", have to use a larger conductor size If "NO", have to use a larger conductor size
Conduit Fill Conduit fill Inside Sunny Tower Need 4 #4 THWN-2 and #6 EG No conduit required 1 1/4" RMC (RGS) good for 7 conductors max.
deg C (Estimated Operating Temperature) on roof amps - Maximum possible breaker that could be used based on Conductor Operating Capacity
Ambient avg high temperature (deg C) deg C (Estimated Operating Temperature) on roof amps - Maximum possible breaker that could be used based on Conductor Operating Capacity
Temperature Added for operating conditions (deg C) assuming
Temperature correction factor amps (temperature adjusted ampacity of selected conductor)
Temperature Added for operating conditions (deg C)
Temperature correction factor amps (temperature adjusted ampacity of selected amps 125% of Continuous Current
Check Terminal Temperature Limits Check Terminal Temperature Limits amps 125% of Continuous Current
Ambient avg high temperature (deg C)
Is conductor rating (@75 deg C) capacity > 125% of Continuous Current
Is current rating (@75 deg C) capacity > 125% of Continuous Current
String fusing not necessary because only two strings in parallel.
Calculate the Rating of the Overcurrent Protection Device, where requiredCalculate the Rating of the Overcurrent Protection Device, where required Calculate the Rating of the Overcurrent Protection Device, where required
125% of continuous current
Temperature Correction Factors
THWN-2, Cu
Ambient avg high temperature (deg C) deg C (Estimated Operating Temperature) on roof
Ambient avg high temperature (deg C) ft from inverter to Sunny Tower
% of values
125% of continuous current
See Step 2
Temperature Added for operating conditions (deg C) assuming conduit within 4 inches of roof surface amps (temperature adjusted ampacity of selected conductor) deg C (Estimated Operating Temperature) on roof
Temperature correction factor amps 125% of Continuous Current (strings in parallel minus one) Is conductor rating (90 deg C) >125% of continuous current amps 125% of Continuous Current (strings in parallel
Is conductor rating (@75 deg C) capacity > 125% of Continuous Current
Ambient avg high temperature (deg C) amps 125% of Continuous Current
Is conductor rating (90 deg C) >125% of continuous current amps 125% of Continuous Current
Is conductor rating (90 deg C) >125% of continuous current
Temperature Added for operating conditions (deg C) assuming conduit within 4 inches of roof surface deg C (Estimated Operating Temperature) on roof
Temperature correction factor amps (temperature adjusted ampacity of selected conductor)
Temperature Added for operating conditions (deg C) assuming conduit within 4 inches of roof surface
Temperature correction factor
WHE
and Parking Canopy
Electrical Drawing and Calculations
161.28 kW
PV
Array x 320W SunPower modules x
SMA
SMC
7000HV-‐11
Inverters
P.O. Box 967
54 Holly Hill Road (packages)
Averill Park, NY 12018
USA
Michael P. Stangl, P.E. • Renewable Power Design Group • P.O. Box 967 • 54
Caddell Construction, Cos.
Tel.: +01 518 674-3684
Fax: +01 518 514-1212
E-Mail: MStangl@rpdg.us.com
WHE Building
92937
WHE with 21 x SMC
Location: Central Africa / Bujumbura
Grid voltage: 3~400 V
Project name:
Project number:
Project file:
System overview Part project 1
504 x Sunpower E19/320 (US) (PV Arrays for Entire Building)
Azimuth angle: -135 °, Angle of inclination: 7 °, Mounting type: Roof, PV Peak power: 161.28 kW
Inverters:
21 x SMC 7000HV-11 (Inverter efficiency: 95.2 %)
Technical data
Total number of PV modules:
PV Peak power: 161.28 kWp
Number of inverters: 21
Nominal AC power: 139.65 kW
Annual energy yield (approx.)*:
239.84 MWh
Energy usability factor: 100.0 %
Performance ratio (approx.
83.5 %
Spec. energy yield (approx.
1487 kWh/kWp
Line losses (in % of PV energy):
Unbalanced load: 0.00 VA
Notes:
Important: The yield values displayed are estimates. They are determined mathematically. SMA Solar Technology AG accepts no responsibility for the real yield value which can deviate from the yield values displayed here. Reasons for deviations are various outside conditions, such as soiling of the PV Modules or fluctuations in the efficiency of the PV modules.
Inverter: 21 x SMC 7000HV-11
PV-module:
A: (PV Arrays for Entire Building)
Sunpower
E19/320 (US)
Azimuth angle: -135 °, Angle of inclination: 7 °Mounting type: Roof
Technical data
Number of strings:
Number of PV modules (input):
Peak power (input):
Min. PV voltage:
Typical PV voltage:
Min. DC voltage (Grid voltage 230 V):
Max. PV voltage:
Max. DC voltage (PV):
Max. current of PV array:
Max. DC current:
PV Peak power:
Total number of PV modules:
Number of inverters:
Max. DC power (cos φ = 1):
Max. AC active power (cos φ = 1):
Grid voltage:
Nominal power ratio:
Displacement power factor cos φ:
161.28 kWp
7.50 kW
7.00 kW
230 V
98.0 %
PV/Inverter compatible
PV array and type of inverter are compatible. The nominal power ratio (max. DC power of the inverter divided by the peak power) is within the recommended range (90% - 110%).
There are probably specific grounding recommendations stated by the manufacturer for the selected PV modules.
Consult the manufacturer regarding current grounding recommendations. Please note that the grounding of the PV array takes place via a separate grounding set in the inverter.
PV-array:
Input A:
PV Arrays for Entire Building
7.68 kWp
374 V
395 V
335 V
554 V
600 V
17.6 A
23.0 A
Project name: WHE Building
Project number: 92937
Project file: WHE with 21 x SMC 7000HV11
Location: Central Africa / Bujumbura
Record Low Temperature: 0.00 °C
Average High Temperature: 31.00 °C
Record High Temperature: 40.00 °CPart project 1
Ambient temperature:
ro je ct
A fr ic a
W H
E
DRAWING
S ys te m
T o ta l:
.0 kW D
C
S T
C
S un po w er S
P R
-3
E -W
H T
-D
T O
W E
R S st rin gs o f 8 p er in ve rt er
S
M C
H V
-1 in ve rt er s
D
IS
C R
E T
E st rin gs o f 8 p er in ve rt er
S
M C
A in ve rt er s
M ou nt ed o n
S ch uc o
M od ul e
T ilt
.5
B
TITLE
REV
None
DATE
C L
IE
N
T S
Y S
T E
M D
E S
C R
IP
T
IO
N
P R
O J
E C
T
R ev
B y
D at e C o m m en t
G
LB
-0
2-
In iti al D ra ft
C kd
2011-May-07 SCALE (11"x17")
PV-E01
SHOP DRAWING
Switchboard WHU SEC2
?A, 400/230VAC
42kA Interrupt
(Existing)
80A, 3P
800A fusing
Sunny WebBox
Communication hub located inside Tower
A Internal power supply
PV Data Monitor Network
Array
DC
AC
DATA
AC
AC
25'
251'
48'
48'
15'
6-PV Wire, 4mm2, #8G bare
¾” RGS, 6#10 THWN-2, #8 EGC
2” RGS, 4#1 THWN-2, #6 G
Shielded 4 conductor RS-485 cable in ¾”C
1 ¼” RGS, 4#4 THWN-2, #6 G
1" RGS, 6#8 THWN-2, #6 G
WIRING (Minimum Requirements)
Conduit & WireDescription ~LengthLabel
B
A
C
PAGE
144 Sunpower
SPR 320E-WHT-D
PV Modules
One array per inverter; Six arrays total;
Each array comprised of three strings of eight modules or 24 modules per inverter
Voc = 518V, Isc = 6.24A
Location: rooftop…