Attachment 20 ITB 00405.pdf

PDF 7 MB Posted

Attached to
Fiber Optic Cable Install - Qty 6 Federal contract opportunity
Solicitation number
FA671223Q0014
Issued by
Department of the Air Force Reserve Command

About this file

This document provides as-built drawings and specifications for a telecommunications system installation at the Pittsburgh ARS facility. Key details include fiber optic and copper cabling to be installed between a telephone frame room and server room, with detailed floor plans, elevations, and equipment specifications. The related federal contract opportunity is solicitation number FA671223Q0014 for the procurement of fiber optic cable installation quantities at six sites from the Department of the Air Force Reserve Command. Services required include installing fiber optic and copper cabling between two rooms according to the specifications provided in the as-built drawings, to be awarded under the listed solicitation number by the Air Force Reserve Command.

View the file

Other files for this federal contract opportunity

Other files attached to Fiber Optic Cable Install - Qty 6, newest first.
File Type Posted
Attachment 32 Additional Questions and answers.docx DOCX document
Attachment 30 Wage Determination 2015-4235 Rev 24 6 30 2023.pdf PDF
Attachment 29 Site Visit Questions and answers.docx DOCX document
Attachment 31 Davis Bacon Act WD PA20230001 Rev 7 Building 07 28 2023.pdf PDF
Attachment 25 List of Attachments r1.xlsx XLSX spreadsheet
Attachment 28 EB 00202.pdf PDF
Attachment 6 Offer Pricing Template r1.pdf PDF
Attachment 26 SOW FOC from B202 to Marquee.docx DOCX document
Attachment 27 GD11014od01CG (107 HH).pdf PDF
Attachment 5 SOW FOC from ITB 405 to B120 V5.docx DOCX document
Attachment 8 Silica Control Plan.pdf PDF
Attachment 12 GD13013od02CG (HH304A 306 306A 306B 403 MH301).pdf PDF
Attachment 21 GD12014od01CG (HH2-6 MH 121).pdf PDF
Attachment 3 SOW FOC from ITB 221 to B419 V2.docx DOCX document
Attachment 6 Offer Pricing Template.pdf PDF
Attachment 11 ITB 00221.pdf PDF
Attachment 25 List of Attachments.xlsx XLSX spreadsheet
Attachment 15 GD13013od01(MH1A 2 4 5 6 HH20).pdf PDF
Attachment 1 SOW FOC from ITB 221 to B209 V6.docx DOCX document
Attachment 9 GD13014od01 (MH14 208 208A 210 HH21 220).pdf PDF
Attachment 10 GD13014od02CG (MH213 218 221 221A HH300).pdf PDF
Attachment 14 GD13013dd01 (419 411 306 316 316a 333).pdf PDF
Attachment 16 GD13013od03CG (MH316 316A 411 418 419A419B).pdf PDF
Attachment 18 GD13014od02CG (MH213 218 221 221A HH300).pdf PDF
Attachment 19 GD14014od01CG (MH4A 221 B324).pdf PDF
Attachment 24 AF FORM 103 Work Clearance.pdf PDF
Attachment 2 SOW FOC from ITB 221 to B317 V5.docx DOCX document
Attachment 4 SOW FOC from ITB 405 to ITB 221 v3.docx DOCX document
Attachment 7 AF1024 Confined Space Entry Permit.pdf PDF
Attachment 17 GD13014od01 (MH14 208 208A 210 HH21 220).pdf PDF
Attachment 22 GD12014od02CG (MH 125).pdf PDF
Show all 31

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

As Built 15 February 2017

Telecommunications System Installation Plan - CDRL A002 – Pittsburgh ARS, Pennsylvania Page 1 of 8 1st Floor Floor Plan

ITB 405

Last Edited: 14 February, 2017

POC: Les Vish 412-474-8491

Telephone Frame Rm

Server Rm 25

W

E

N

S

Telecommunications System Installation Plan - CDRL A002 – Pittsburgh ARS, Pennsylvania Page 2 of 8 Telephone Frame Rm Room Plan

ITB 405

Last Edited: 14 February, 2017

POC: Les Vish 412-474-8491

A

W

E

N

S

Covered channel to vault

7' rack #1 w/ FODP

Reuse 7' rack #2 w/ FODP

FODP

Power panel 1.5ohms

100' (3ea) 48SM MIC in plenum innerduct to Server Rm 25

(2ea) 36SM FOC to ITB 221

72SM FOC w/ (12SM ea to EB's 417, 416, 102, 129, 130, & MH 129)

36SM FOC w/ (12SM ea to EB's 420, 408, 409)

(6ea) 12SM FOC to CEB's 419, 125, 210 & EB’s 401, 403, 411

36SM FOC w/ (12SM ea to EB's 111, 107, 202)

A

4" conc core

10' 6" ladder rack

Telecommunications System Installation Plan - CDRL A002 – Pittsburgh ARS, Pennsylvania Page 3 of 8 Telephone Frame Rm Elevation

ITB 405

Last Edited: 14 February, 2017

POC: Les Vish 412-474-8491 7' Rack 1

WIC

FODP

FODP

Splice Chamber

FODP

Splice Chamber

FODP

FODP

Splice Chamber

WIC

Pre-Installation Photo

No Post Installation Photo Allowed

Telecommunications System Installation Plan - CDRL A002 – Pittsburgh ARS, Pennsylvania Page 4 of 8 Telephone Frame Rm Elevation

ITB 405

Last Edited: 14 February, 2017

POC: Les Vish 412-474-8491 Reuse 7' Rack #2

Reuse FODP w/ 36SM FOC to EB 333

Reuse FODP w/ 48SM FOC to CEB 316 12SM FOC to CEB 418

FODP w/ 12MM FOC to EB 316 24MM FOC to EB 418

Reuse FODP w/ 24SM FOC to EB 108 12SM FOC to EB106

Reuse FODP w/ 12SM FOC to EB 110

Pre-Installation Photo

SD

Cable Management

144 Port FODP w/ (2ea) 36SM FOC to ITB 221 12SM FOC ea to CEB’s 125, 419, 403, EB’s 210, 401, & 411

SD

Cable Management 144 Port FODP w/ 72SM FOC w/ (12SM ea to EB’s 417, 416, 102, 129, 130, & MH 129) 36SM FOC w/ (12SM ea to 420 408, & 409) 36SM FOC w/ (12SM ea to 111, 107, & 202)

SD

Cable Management

144 Port FODP w/ (3ea) 48SM MIC to Server Rm

SD

Cable Management

Telecommunications System Installation Plan - CDRL A002 – Pittsburgh ARS, Pennsylvania Page 5 of 8 Server Rm 25 Room Plan

ITB 405

Last Edited: 14 February, 2017

POC: Les Vish 412-474-8491

7' cabinet #4

W

E

N

S

(3ea) 48SM MIC in plenum innerduct to Telephone Frame Rm

7' cabinet #3

TG

B

Power panel MPA-MP Ckt #22, 24, 38

2.0ohms

7' cabinet

FODP

Power panel NED/1 Ckt #29, 31, 10, 41

8' 12" ladder rack

.08ohms to TGB

.08ohms to TGB

2.0ohms to power panel

Dedicated power (2ea) 20AMP/110V/L5-20R

Panel NED/1, Ckt# 10, 41 in Flex PVC

Dedicated power

30AMP/220V/L1430

Panel NED/1, Ckt #29, 31 in Flex PVC

Dedicated power

30AMP/220V/L1430

Panel MPA-MP, Ckt #22, 24 in Flex PVC

Dedicated power (2ea) 20AMP/110V/L5-20R MPA-MP, Ckt# 38 in Flex PVC

Telecommunications System Installation Plan - CDRL A002 – Pittsburgh ARS, Pennsylvania Page 6 of 8 Server Rm 25 Elevation

ITB 405

Last Edited: 14 February, 2017

POC: Les Vish 412-474-8491

SD

SD

SD

7' Cabinet 3

24 Port Patch Panel

48 Port Patch Panel

48 Port Patch Panel

Cable Management

48 Port Patch Panel

48 Port Patch Panel

Cable Management

48 Port Patch Panel

24 Port Patch Panel

48 Port Patch Panel

Cable Management

24 Port Patch Panel

FODP

FODP

FODP

FODP

FODP

Pre-Installation Photo

Telecommunications System Installation Plan - CDRL A002 – Pittsburgh ARS, Pennsylvania Page 7 of 8 Server Rm 25 Elevation

ITB 405

Last Edited: 14 February, 2017

POC: Les Vish 412-474-8491

MODE

CONSOLE

SYST XPS STAT SPEED DUPLX

S-PWR MAST ST ACK Po EEN

37X

38X

38 40 42 44 46 4837 39 41 43 45 47

Catalyst 3750-X Series PoE +

25X

26X

35X

36X

26 28 30 32 34 3625 27 29 31 33 35

13X

14X

1X

2X

11X

12X 24X

23X

14 16 18 20 22 2413 15 17 19 21 232 4 6 8 10 121 3 5 7 9 11

C3KX-NM-1G

NETWORK

MODULE

G1 G2 G3 G4

MODE

CONSOLE

SYST XPS STAT SPEED DUPLX

S-PWR MAST ST ACK Po EEN

37X

38X

38 40 42 44 46 4837 39 41 43 45 47

Catalyst 3750-X Series PoE +

25X

26X

35X

36X

26 28 30 32 34 3625 27 29 31 33 35

13X

14X

1X

2X

11X

12X 24X

23X

14 16 18 20 22 2413 15 17 19 21 232 4 6 8 10 121 3 5 7 9 11

C3KX-NM-1G

NETWORK

MODULE

G1 G2 G3 G4

MODE

CONSOLE

SYST XPS STAT SPEED DUPLX

S-PWR MAST ST ACK Po EEN

37X

38X

38 40 42 44 46 4837 39 41 43 45 47

Catalyst 3750-X Series PoE +

25X

26X

35X

36X

26 28 30 32 34 3625 27 29 31 33 35

13X

14X

1X

2X

11X

12X 24X

23X

14 16 18 20 22 2413 15 17 19 21 232 4 6 8 10 121 3 5 7 9 11

C3KX-NM-1G

NETWORK

MODULE

G1 G2 G3 G4

SD

7' Cabinet 4

Cisco WS-C3750-48P

Cisco WS-C3750-48P

Cisco WS-C3750-48P

Cable Management

Equipment

Equipment

Equipment

Equipment

Equipment

Equipment

Equipment

Pre-Installation Photo

Telecommunications System Installation Plan - CDRL A002 – Pittsburgh ARS, Pennsylvania Page 8 of 8 Server Rm 25 Elevation

ITB 405

Last Edited: 14 February, 2017

POC: Les Vish 412-474-8491

No Pre-Installation Photo Allowed

Reuse 7' Cabinet

Equipment

Surge ProtectorRESET

I MIN

R

BR

EA

K E

PR

ES

S

TO

FAN

STATUS

Catalyst 4507R+E

SUPER

VISO

R

SUPERVISO

R

Cisco WS-C4507R+E

SD

Cable Management

144 Port FODP w/ (3ea) 48SM MIC to Telephone Frame Rm

FAN

STATUS

Catalyst 4507R+E

SUPER

VISO

R

SUPERVISO

R

Cisco WS-C4507R+E

File details come from the government source that posted it. Updated .