Attachment 11 ITB 00221.pdf

PDF 3 MB Posted

Attached to
Fiber Optic Cable Install - Qty 6 Federal contract opportunity
Solicitation number
FA671223Q0014
Issued by
Department of the Air Force Reserve Command

About this file

This document is an as-built telecommunications system installation plan for the Pittsburgh Air Reserve Station in Pennsylvania. It provides detailed floor plans and equipment layouts for the fiber optic cable and network infrastructure installed throughout various buildings and rooms on the base. The installation included over 700 feet of fiber optic cable run through conduit and cable trays with connections to over 25 communications equipment rooms. Key equipment deployed included fiber optic distribution panels, patch panels, switches and routers. The related federal contract opportunity is a solicitation from the Department of the Air Force Reserve Command for the installation of additional fiber optic cable with a quantity of six. No further details are provided on the opportunity in the documents reviewed.

View the file

Other files for this federal contract opportunity

Other files attached to Fiber Optic Cable Install - Qty 6, newest first.
File Type Posted
Attachment 32 Additional Questions and answers.docx DOCX document
Attachment 30 Wage Determination 2015-4235 Rev 24 6 30 2023.pdf PDF
Attachment 29 Site Visit Questions and answers.docx DOCX document
Attachment 31 Davis Bacon Act WD PA20230001 Rev 7 Building 07 28 2023.pdf PDF
Attachment 25 List of Attachments r1.xlsx XLSX spreadsheet
Attachment 28 EB 00202.pdf PDF
Attachment 6 Offer Pricing Template r1.pdf PDF
Attachment 26 SOW FOC from B202 to Marquee.docx DOCX document
Attachment 27 GD11014od01CG (107 HH).pdf PDF
Attachment 5 SOW FOC from ITB 405 to B120 V5.docx DOCX document
Attachment 8 Silica Control Plan.pdf PDF
Attachment 12 GD13013od02CG (HH304A 306 306A 306B 403 MH301).pdf PDF
Attachment 21 GD12014od01CG (HH2-6 MH 121).pdf PDF
Attachment 3 SOW FOC from ITB 221 to B419 V2.docx DOCX document
Attachment 6 Offer Pricing Template.pdf PDF
Attachment 25 List of Attachments.xlsx XLSX spreadsheet
Attachment 15 GD13013od01(MH1A 2 4 5 6 HH20).pdf PDF
Attachment 1 SOW FOC from ITB 221 to B209 V6.docx DOCX document
Attachment 9 GD13014od01 (MH14 208 208A 210 HH21 220).pdf PDF
Attachment 10 GD13014od02CG (MH213 218 221 221A HH300).pdf PDF
Attachment 14 GD13013dd01 (419 411 306 316 316a 333).pdf PDF
Attachment 16 GD13013od03CG (MH316 316A 411 418 419A419B).pdf PDF
Attachment 18 GD13014od02CG (MH213 218 221 221A HH300).pdf PDF
Attachment 19 GD14014od01CG (MH4A 221 B324).pdf PDF
Attachment 24 AF FORM 103 Work Clearance.pdf PDF
Attachment 2 SOW FOC from ITB 221 to B317 V5.docx DOCX document
Attachment 4 SOW FOC from ITB 405 to ITB 221 v3.docx DOCX document
Attachment 7 AF1024 Confined Space Entry Permit.pdf PDF
Attachment 17 GD13014od01 (MH14 208 208A 210 HH21 220).pdf PDF
Attachment 20 ITB 00405.pdf PDF
Attachment 22 GD12014od02CG (MH 125).pdf PDF
Show all 31

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

As Built 15 February 2017

Telecommunications System Installation Plan - CDRL A002 – Pittsburgh ARS, Pennsylvania Page 1 of 6 Crawl Space Floor Plan

ITB 221

Last Edited: 14 February, 2017

POC: Security Forces 412-474-8250

W

E

N

S

12SM FOC to EB 220

A

144SM FOC w/ (36SM to ITB 405, 12SM ea to EB’s 300, 312, 333, 342, 306, 304, 301, CEB 316, & EB 307 (left dark in HH 306)

A 48SM FOC w/ (12SM ea to EB’s 213, 218, 325, & 320)

48SM FOC to ITB 300 ANG

24SM FOC w/ (12SM ea to CEB’s 418 & 419)

B

170' wall snake tray

Reuse Building entry

B

36SM FOC to ITB 405

36SM FOC w/ (12SM ea to CEB’s 125, 210 & 208)

10' #6 AWG ground wire to snake tray in Boiler Rm

B

A

Telecommunications System Installation Plan - CDRL A002 – Pittsburgh ARS, Pennsylvania Page 2 of 6 1st Floor Floor Plan

ITB 221

Last Edited: 14 February, 2017

POC: Security Forces 412-474-8250

Rm

Boiler Rm

(below ground)

W

E

N

S

Mech Rm

Power panel B-MDP .41ohms

Telecommunications System Installation Plan - CDRL A002 – Pittsburgh ARS, Pennsylvania Page 3 of 6 Mech Rm/Boiler Rm Room Plan

ITB 221

Last Edited: 14 February, 2017

POC: Security Forces 412-474-8250

W

E

N

S

Note:

1. Boiler Rm is below ground level and uses crawl space to route FOC.

(2ea) 4" conc core

24 sm FOC w/ (12sm ea to CEB’s418,419)

48sm FOCto ITB 300 ANG

144sm FOC w/ (36sm tp ITB 405, 12sm ea to EB’s 300,312,333,342,306,304,301, CEB’s 316,&EB 307(left dark in HH 306)

48sm FOC w/ (12sm ea to EB’s 213,218,325,320)

13' wall snake tray

Mech Rm Boiler Rm

#6 AWG ground wire to snake tray in crawlspace

20' #6 AWG ground wire to snake tray in Rm 120

(4ea) 4" conc coresCrawl space entrance

16' wall snake tray

4" conc core

A 4"X4" pull box

Power panel MDP Ckt #32, 34, 36, 38

25' #6 AWG ground wire to snake tray

.03ohms to service ground

70' ½” EMT to power panel MDP

1" conc core

36sm FOC w/ (12 ea to CEB’s 125,208,&210)

36sm FOC to ITB 405

Telecommunications System Installation Plan - CDRL A002 – Pittsburgh ARS, Pennsylvania Page 4 of 6 Rm 120 Room Plan

ITB 221

Last Edited: 14 February, 2017

POC: Security Forces 412-474-8250

W

E

N

S

10'-0"

'-0

.10ohms

7' rack CAT 6 panel

Power panel

(2ea) Dedicated power

20AMP/110V/L5-20R

Panel MDP, Ckt #27,29

70' ½” EMT to power panel MDP

1" conc core

13' #6 AWG ground wire to TGB

#6 AWG ground wire to snake tray in Mech Rm

24sm FOC w/(12sm ea to CEB’s 418,419)

48sm FOC to ITB 300 ANG

144sm FOC w/(36sm to ITB 405 12sm ea to EB’s 300,312,333, 342,306,304,301,CEB’s 316, & 307 (left in dark in HH 306)

A

TG

B

10' #6 AWG ground wire to TGB

Dedicated power

20AMP/110V/L5-20R

Panel MDP, Ckt #32, 34, 36, 38

7' cabinet

.41ohms

.41ohms to power panel

4" conc core

36sm FOC w/ (12 eash to CEB’s

15,208,&210)

36sm FOC to ITB 405

Telecommunications System Installation Plan - CDRL A002 – Pittsburgh ARS, Pennsylvania Page 5 of 6 Rm 120 Elevation

ITB 221

Last Edited: 14 February, 2017

POC: Security Forces 412-474-8250 Reuse 7' Rack

Pre-Installation Photo

2U FODP

2U 48 Port Patch Panel

SD

2U Wire Management

2U 48 Port Patch Panel

SD

2U Wire Management

2U 48 Port Patch Panel

SD

2U Wire Management

1U 24 Port Patch Panel

2U 24 Port Patch Panel

SD

1U Wire Management

WS-3850-48PT

SD

2U Wire Management

WS-3850-48PT

Load

AVR Boost

On Line

AVR Trim

Replace Battery

On Battery

Overload

Battery Charge

Test I

O www .apcc.com

Smart-UPS

3 0 0 0 2000 UPS

Surge ProtectorRESET

I MIN

R

BR

EA

K E

PR

ES

S

TO

Equipment

SD

1U Wire Management

No Post Installation Photo Allowed

Telecommunications System Installation Plan - CDRL A002 – Pittsburgh ARS, Pennsylvania Page 6 of 6 Rm 120 Elevation

ITB 221

Last Edited: 14 February, 2017

POC: Security Forces 412-474-8250 7' Rack

No Pre-Installation Photo Allowed

221/405 1-36, 37-48, 221/312, 49-60 221/316, 61-72, 221/333, 73-84, 221/342, 85-96 221/306, 97-108, 221/304, 109-120, 221/301, 121-132 221/HH316 Dark, 133-144

405/221, 1-36, 221/418, 1-12, 221/419, 13-24 221/220, 1-12, 221/125, 1-12, 221/210, 13-24 221/208, 25-36 221/213, 1-12 221/320, 13-24 221/325, 25-36 221/218, 37-48

221-ANG300, 1-48

SD

Cable Management

WS-3850-12S

SD

Cable Management

WS-3850-12S

SD

Cable Management

WS-3850-12S

SD

Cable Management

WS-3850-12S

SD

Cable Management

WS-3850-12S

SD

Cable Management

WS-3850-12S

SD

Cable Management

WS-3850-12S

Load

AVR Boost

On Line

AVR Trim

Replace Battery

On Battery

Overload

Battery Charge

Test I

O ww w.apcc.c om

Smart-UPS

3 0 0 0 2000 UPS

BatteryPack Battery

Surge ProtectorRESET

I MIN

R

BR

EA

K E

PR

ES

S

TO

Surge ProtectorRESET

I MIN

R

BR

EA

K E

PR

ES

S

TO

Pre-Installation Photo

File details come from the government source that posted it. Updated .