Attachment_2_-_Technical_Specifications_-_Standards.pdf
PDF 229 KB Posted
- Attached to
- 138 KV Oil Breaker Replacements Project
- Solicitation number
- RFP-2024-010
- Issued by
- Alachua County, Graceville City, Florida
About this file
The document is a portion of the Gainesville Regional Utilities (GRU) Electric System Approved Materials Manual, specifically focusing on technical specifications for various electrical hardware components. The pages detail precise technical specifications for items including hex head stainless steel bolts, control cables, overhead aluminum conductors, bronze hex nuts, Belleville washers, and stainless steel flat washers. Each specification page provides comprehensive details such as material composition, dimensional specifications, thread types, manufacturer catalog numbers, stock numbers, and revision dates.
The manual serves as a standardized reference for approved electrical materials, ensuring consistency and quality in GRU's electrical infrastructure components. Each item specification includes precise technical requirements, such as material standards (e.g., ASTM standards), dimensional tolerances, and acceptable manufacturer sources. The documents indicate ongoing maintenance and periodic updates to the manual, with revision dates ranging from the 1980s to the mid-2010s, suggesting a systematic approach to maintaining and upgrading technical standards for electrical equipment and materials used by Gainesville Regional Utilities.
View the file
Other files
Show all 13
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Page B - 23.00
5/16” BOLT LENGTH
I L
5/8” - — tl III 111III III If HI b 1/2
I T
1/2" - 13 Bolts
19/64" BOLT LENGTH
n L 5/8" - — II- til III Mil t i l l I b 7/16
1 T I
7/16" - 14 Bolts
Description Manufacturer Catalog No. Stock No.
FINISHED HEX HEAD BOLT OF U.S.S. 18-8 STAINLESS
STEEL. THREADS CONFORM TO ANSI/ASME B18.2.1
STANDARD CLASS 2A FIT.
SIZE: 1/2" - 13 THREADS/INCH (COURSE THREAD)
LENGTH: 1-1/2"
(T = 1-1/4")
"OPEN MARKET" 70375-3
2" (T = 1-1/4")
"OPEN MARKET" 61635-4
2-1/2" (T = 1-1/4")
"OPEN MARKET" 61645-1
[lb> 3"
(T = 1-1/4") "OPEN MARKET" 61650-8
SIZE: 7/16” - 14 THREADS/INCH (COURSE THREAD)
LENGTH: 1-3/4"
(T = 1-1/8") "OPEN MARKET" 53647-4
Revision Date:
2-12-98
8-14-08 KLC
■/5DII
M o r e t h a n E n e r g y ™
Gainesville Regional Utilities Electric System Approved Materials Manual t- 1 Z 4-8-13 tVLU
KLC
ITEM NAME
BOLT, HEX HEAD (STAINLESS STEEL)
Stock No.Catalog No.ManufacturerDescription
Revision Date: Gainesville Regional Utilities Electric System Approved Materials ManualM o r e t h a n E n e r g y
SM
TM
Page C - 8.00
70017-7
70022-3
70027-4
CONTROL CABLE, 600 VOLT UL APPROVED FOR
WET OR DRY LOCATIONS AT 90O C.
REEL SIZE: 1000 FT.
SIZES: 3-10 AWG
(0.169 LBS./ FT.)
5-10 AWG
(0.276 LBS./FT.)
12-10 AWG
(0.629 LBS./FT.)
CABLE, CONTROL
HOUSTON WIRE & CABLE
COMPANY (HWC)
SERVICE WIRE CO.
OMNI CABLE
LAKE CABLE, LLC.
HOUSTON WIRE & CABLE
COMPANY (HWC)
SERVICE WIRE CO.
OMNI CABLE
LAKE CABLE, LLC.
HOUSTON WIRE & CABLE
COMPANY (HWC)
SERVICE WIRE CO.
OMNI CABLE
LAKE CABLE, LLC.
4-12-00
1-8-09 KLC
1-13-09 KLC
3-4-11 KLC
6-25-12 KLC
Cond.
No.
Base Color Black Red Blue
Orange Yellow Brown
Red Blue
Orange Yellow Brown Black
Tracer
Black Black Black Black Black Red
Cond.
No.
Base Color Blue
Orange Yellow Brown Black Red
Orange Yellow Brown Black Red Blue
Tracer
Red Red Red Red Blue Blue Blue Blue Blue
Orange Orange Orange
Cond.
No.
Base Color Yellow Brown Black Red Blue
Orange Brown Black Red Blue
Orange Yellow
Tracer
Orange Orange Yellow Yellow Yellow Yellow Yellow Brown Brown Brown Brown Brown
* ICEA Table E2 or K2
There are no Green or White conductors.
*Reference ICEA S-73-532 or ICEA S-95-658/NEMA WC-70
HW156 01003
TCXHHW10/3
A51003
VX103/M1
HW156 01005
TCXHHW10/5
A51005
VX105/M1
HW156 01012
TCXHHW10/12
A51012
VX1012/M1
/SPECIFICATIONS:
CONDUCTORS: SOFT BARE ANNEALED COPPER PER ASTM B-3, CLASS B, STRANDING PER ASTM B-8.
INSULATION: FLAME-RETARDANT CROSS-LINK POLYETHYLENE (FR-XLP) AND UL STANDARD 44 FOR
TYPE XHHW-2, VW-1 CONDUCTORS
JACKET: SUNLIGHT-RESISTANT PVC PER UL STANDARD 1277
COLOR CODED: METHOD 1, PER ICEA S-73-352, USING COLOR CODE TABLE E-2 OR
METHOD 1, PER ICEA S-95-658/NEMA WC-70 USING COLOR CODE TABLE K2
| REV.^>
| REV.^>
| REV.^>
■/SDI1
Revision Date: Gainesville Regional Utilities Electric System Approved Materials ManualM o r e t h a n E n e r g y
SM
TM
CONDUCTOR, OVERHEAD (AAC)
Page C - 105.15
OVERHEAD CONDUCTOR ALL ALUMINUM (AAC)
CONCENTRIC LAY
NO. 795 KCMIL
CODE WORD: ARBUTUS
STRANDS: 37
WEIGHT: 746.3 LBS./1000 FT.
AMPACITY: 860
OUTSIDE DIAMETER: 1.026"
PACKAGING SHALL BE IN ACCORDANCE WITH
THE CABLE SUPPLEMENTARY CONDITIONS, ON
PAGES C-9.00 THRU C-9.02, THIS MANUAL.
MANUFACTURER TO BE
SELECTED BASED ON
CONFORMANCE TO
SPECIFICATIONS
20214-2
1-25-88 7-11-88
■/SDI f
Revision Date: Gainesville Regional Utilities Electric System Approved Materials ManualM o r e t h a n E n e r g y
SM
TM
NUT, BRONZE HEX
27539-5
53642-3
"OPEN"
"OPEN"
FINISHED, BRONZE HEX NUT. MUST COMPLY WITH
ASTM STANDARD F-467-93, MATRTILS USED IS
SILICON BRONZW ALLOY # 651, 655 OR 661. (FULL
HARD SILICON BRONZE).
CLASS: 2B FIT
SIZE: 1/2" - 13 THREADS/INCH
7/16" - 14 THREADS/INCH
Page N - 30.00
8-29-83 4-3-96
9-30-11 KLC
5-4-12 KLC
Revision Date: Gainesville Regional Utilities Electric System Approved Materials ManualM o r e t h a n E n e r g y
SM
TM
WASHER, BELLEVILLE
12162-2820125301
1NEK6
BW - 1/2 - AH
50050BW
SOLON MANUF. CO.
GRAINGER
* OPEN MARKET
DOSSERT
BLACKBURN
STAINLESS STEEL (302) BEVELLED SPRING WASHER
FOR USE AT NEMA PAD CONNECTIONS.
DIMENSIONS:
O.D. = 1.25" (1-1/8")
I.D. = 0.515" T0 0.531" (33/64" TO 17/32")
THICKNESS = 0.125" (1/8")
TO FIT: 1/2" BOLT SIZE
* MANUFACTURER MUST BE APPROVED AT TIME OF
QUOTE
Page W - 3.00
12-4-80 1-4-88 6-13-94
12-6-07 KLC
THIS ITEM IS OBSOLETE WITH THESE
MANUFACTURERS
Revision Date: Gainesville Regional Utilities Electric System Approved Materials ManualM o r e t h a n E n e r g y
SM
TM
WASHER, STAINLESS STEEL FLAT
43156-7
43161-3
63632-6
"OPEN MARKET"
"OPEN MARKET"
"OPEN MARKET"
FLAT 18-8 STAINLESS STEEL WASHER.
TO FIT:
1/2" BOLT SIZE
5/16" BOLT SIZE
7/16" BOLT SIZE
Page W - 8.00
8-29-83
5-4-12 KLC
4-18-13 KLC
9-11-14 KLC
| Page B-23.00_Bolts |
| Page C-8.00_control cable |
| Page C-105.15_795AAC |
| Page N-30.00_Nut |
| Page T-25.02_Swage single to 4 hole |
| Page W-3.00_Bevel Washer |
| Page W-8.00_Washer |