This is a project submittal document for HVAC equipment under federal contract 12639526Q0076, Attachment 2 (Lennox or equal). The submittal specifies equipment requirements for 11 split systems with zero roof-top units, including seven 1-ton mini-split heat pumps, two 1.5-ton mini-split heat pumps, and two 2.5-ton split systems. The 1-ton and 1.5-ton systems are wall-mounted, single-zone mini-split heat pumps utilizing R-32 refrigerant with inverter-driven compressors and built-in Wi-Fi connectivity. The 1-ton units (MWHD012S6S/MWHD012S6) deliver 12,000 BTU cooling/heating capacity with SEER2 of 24.00 and EER2 of 13.25, while the 1.5-ton units (MWHD018S6S/MWHD018S6) provide 18,000/21,000 BTU with SEER2 of 21.50 and EER2 of 12.85. Field-installed accessories for the mini-split systems include duct cable strips, interconnect cable assemblies, and wall brackets totaling 7 units each.

The 2.5-ton split systems utilize a condenser (ML13KC1-030-230), R454B evaporator coil (CK40CT-30/36B), and gas furnace (ML196UH070XE36BK RDS) with AHRI certification 215586576, delivering 28.0 MBH gross cooling and 63.9 MBH heating output at 208-volt single-phase operation. The submittal includes detailed specifications, dimensional drawings, performance data, product features, and warranty information for all equipment. Additionally, three condensate pumps (X86-003 MicroBlue 110-230V) are specified as miscellaneous items. The document references Revit BIM and AutoCAD template links for design integration, though specific response deadlines, award dates, and pricing information are not contained within this submittal package.

View the file

Other files

File Type Posted
RFIs and Responses.docx DOCX document
Site Visit Attendance-2.pdf PDF
12639526Q0076-0002.pdf PDF
Site visit attendance.pdf PDF
12639526Q0076-0001.pdf PDF
Attachment 3_Federal Construction Wage Rates_Cache County (1).txt TXT text file
12639526Q0076.docx DOCX document
Attachment 1_Statement of Work_HVAC.docx DOCX document

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Page

Project Name:

Project Number:

Project Altitude:

Project Location:

Customer:

Date:

Quote:

Roof Top Units: 0 Split Systems: 11

Table of Contents Tag Qty Model Description

1 Ton

27K85 27K92

MWHD012S6S SZ HP 12K 208/230V

MWHD012S6 SZ IDU Wall 12K 208/230V

1.5 Ton

27K86 27K93

MWHD018S6S SZ HP 18K 208/230V

MWHD018S6 SZ IDU Wall 18K 208/230V

2.5 Ton Split System

25C67 25U77

ML196UH070XE36BK

ML13KC1-030 Condenser/2.5 Ton/230

CK40CT-30/36B COIL 2.5-3.0T R454B

ML196UH070XE36BK UH 70KBTU NOX 3T

Miscellaneous Items

Revit® Building Information Modeling (BIM) - Click here

AutoCAD® Templates - Click here

12639526Q0076, Attachment 2 (Lennox or equal)

Project Submittal https://www.lennoxcommercial.com/support/contractors/revit-bim-software https://www.lennoxcommercial.com/support/contractors/autocad-templates

Project Submittal

Field Installed Accessories Catalog Number Qty Description

29F41 7 Duct-Strip 5 Mini-Split Cable, 250 Pull

Y8171 7 L1 1/4 X 3/8 X 1/2 X 25 DL W/NUT EZ-PULL

Y3400 7 DI 230-B2LType 2 Wall Brackets Lg

SUBMITTAL DATA – WALL MOUNTED

MWHD012S6S-1P – MWHD012S6-1P

SINGLE ZONE MINI-SPLIT HEAT PUMP

Job: Engineer:

Location: Architect:

Schedule No.: Date:

System Designation: For: Reference Approval Review Construction

NOTE – Due to Lennox’ ongoing commitment to quality, Specifications, Ratings, and Dimensions are subject to change without notice and without incurring liability. Improper installation, adjustment, alteration, service or maintenance can cause property damage or personal injury. Installation and service must be performed by a qualified installer and servicing agency.

FEATURES

496374 (202412) ©2024 Lennox Industries, Inc.

▪ The indoor unit shall feature WindFree™* mode. When activated in cooling mode the unit will close its louver and will disperse air into the space through thousands of micro-holes on the front of the indoor unit preventing cold air drafts on occupants.

▪ The system shall have a built-in Wi-Fi adapter as standard to allow control and monitoring using the Samsung SmartThings app.

▪ Outdoor unit shall provide 208/230V power to the indoor unit via 14 AWG X 3 interconnect power cable.

Construction

▪ Indoor unit chassis shall be UL94 V0 with a galvanized steel mounting bracket

▪ The indoor unit shall have easy access to wire, pipe, and drain connections via the access panel on the bottom of the unit for simple installation and service

▪ The outdoor unit shall be galvanized steel with a baked-on powder coated finish for durability Heat Exchanger

▪ The heat exchangers shall be mechanically bonded fin to copper tube Refrigerant System

▪ The system shall utilize low-GWP R-32 refrigerant

The compressor shall be hermetically sealed, inverter controlled, BLDC Rotary Refrigerant flow shall be controlled by an electronic expansion valve at the outdoor unit

Indoor Fan

▪ The indoor fan shall be a single cross-flow type

▪ Three fan speed settings and auto setting

▪ Automatic (motorized) vertical swing (up/down) and horizontal swing (left/right) louvers Controls

▪ The indoor unit shall ship with a rechargeable, solar-cell wireless controller and holder. The wireless controller battery shall be charged with a USB C cable or the integral solar panel.

▪ The included wireless controller shall have a pixel display that is visible in low light conditions.

▪ Dual set temperature support when connected to supported wired controllers.

▪ The indoor unit shall include an integral humidity sensor for improved humidity control functions.

▪ The indoor unit shall have a simple connection for condensate overflow detec-tion devices or any normally closed contact for simple unit shutdown.

▪ Samsung central control compatible (accessory required)

▪ Interconnect control wire between the outdoor and indoor unit shall be 16AWG

X 2 External Heat Control

▪ External heat control functionality allows for configuration of fan operation during auxiliary heat operation, defrost, and emergency heat (VSTAT10P-1 accessory required).

▪ External heat control configuration settings includes outside ambient external heat lockout, outside ambient compressor lockout, and time delay options (VSTAT10P-1 accessory required).

▪ Emergency heat functionality allows the system to continue controlling the exter-nal heat source even when system errors prevent the heat pump from operating (VSTAT10P-1 accessory required).

Convenience

▪ 7-segment digital display on the front of the unit to display temperature and unit status

▪ Washable main filter as standard accessible from the top of the unit

▪ System energy consumption can be viewed using the Samsung SmartThings mobile app or on the indoor unit display using the included wireless controller (conditions apply).

▪ AI (artificial intelligence) Auto Mode technology monitors factors such as indoor temperature, outdoor temperature, set temperature, and operating time to learn the patterns within your home to automatically adjust system operation to maxi-mize occupant comfort and efficiency (Wi-Fi connection required).

▪ AI Energy mode technology enhances energy saving operation using advanced compressor control techniques

▪ Eco Mode to reduce energy consumption during low demand operation

▪ Smart install mode - Startup system diagnostics operation to ensure system readiness during initial operation

▪ Auto restart after power loss

▪ Other Features and functions: Auto changeover, Auto Clean Function, Freeze

Wash Function, MAX mode to quickly reach set temperature, Good’sleep mode, Quiet mode, Dry mode, Simple ON/OFF time function (activated with wireless controller), Filter cleaning reminder

Outdoor Unit: MWHD012S6S-1P

Indoor Unit: MWHD012S6-1P

VSTAT02P-1 Touch Screen Wired Controller* 37P79

VSTAT04P-1 Programmable Wired Controller* 37Y74

ACCESSORIES

VSTAT06P-1 Wall Mnt Mini-Splt Wired Cntrlr Sub PCB 37Y83

VCTRL11P-1 External Room Temp. Sensor 37Y77

VSTAT10P-1 External Contact Control 37Y69

VSTAT09P-1 24V Thermostat Adapter 37Y96

VCTRL06P-1 Interface Module Comm Adaptor ERV Kits 37Y82

*VSTAT06P-1 (37Y83) is REQUIRED with the selection of this accessory

PRODUCT WARRANTY

Compressor – Seven year warranty All other covered components - Five year warranty

SINGLE ZONE MINI-SPLIT HEAT PUMP

NOTE – Due to Lennox’ ongoing commitment to quality, Specifications, Ratings, and Dimensions are subject to change without notice and without incurring liability. Improper installation, adjustment, alteration, service or maintenance can cause property damage or personal injury. Installation and service must be performed by a qualified installer and servicing agency.

496374 (202412) ©2024 Lennox Industries, Inc.

SUBMITTAL DATA – WALL MOUNTED

MWHD012S6S-1P – MWHD012S6-1P

SPECIFICATIONS

Performance

Nominal Capacity Cooling / Heating (Btu/h) 12,000 / 12,000

Capacity Range Cooling (Btu/h) 3,000 - 15,500 Heating (Btu/h) 2,200 - 23,000

AHRI 210-240 2023

SEER2 24.00

EER2 13.25

HSPF2 (region IV) 9.00

5°F COP 1.76

Power

Voltage ø / V / Hz 1 / 208-230 / 60 Working Voltage Range (VAC) 187 - 253

Operating Current (min. / standard / max.)

Cooling (A) 1.1 / 4.8 / 6.2 Heating (A) 1 / 4.6 / 10

Max. Breaker Amps 20.0 Min. Circuit Ampacity Amps 12.0

Dimensions W X H X D (in.)

Indoor Unit 32 5/16 X 11 3/4 X 8 7/16 Outdoor Unit 31 1/8 X 21 9/16 X 11 1/4

Weight (lbs.)

Indoor Unit 20.30 Outdoor Unit 69.20

Sound Pressure Level Indoor Unit dB(A) Silent / High 22 / 39 Outdoor Unit dB(A) Cooling (high) 46

Operating Temperatures Outdoor

Cooling 14 - 115°F (-10 - 46°C) Heating -5 - 75°F (-20.6 - 24°C)

Indoor Cooling 64 ~ 90°F (16 ~ 32°C) Heating T ≤ 86°F (30°C)

Pipe Connections

Indoor & Outdoor High side (In.) 1/4 Low side (In.) 3/8

Maximum (ft.) 66 Maximum Vertical Separation (ft.) 49 Condensate Connection 11/16” OD

Refrigerant

Type R-32 A2L Leak Detection Not Included Factory Charge oz. 34.0 Charged for 24.6 ft.

Compressor Type Inverter Driven, Twin BLDC Rotary RLA Amps 9.2

Evaporator Fan Type BLDC motor with cross-flow fan FLA Amps 0.12 Output Watts 27.0

Airflow Air Volume (L/M/H/Turbo) Cooling (CFM) 297 / 328 / 364 / 378 Heating (CFM) 328 / 364 / 396 / 413

Condenser Fan Type BLDC With Axial Type Fan (1) FLA / Watts / CFM (max.) 0.42 / 40 / 1,589

496374 (202412) ©2024 Lennox Industries, Inc.

NOTE – Due to Lennox’ ongoing commitment to quality, Specifications, Ratings, and Dimensions are subject to change without notice and without incurring liability. Improper installation, adjustment, alteration, service or maintenance can cause property damage or personal injury. Installation and service must be performed by a qualified installer and servicing agency.

SUBMITTAL DATA – WALL MOUNTED

MWHD012S6S-1P – MWHD012S6-1P

OUTDOOR DIMENSIONS IN.

31 1/8

23 11/16

/4

/1

1 15/16 X 1/2

/1

3 1/2

20 1/16

/1

1/

11 1/4

1/

/1

INDOOR DIMENSIONS IN.

SUBMITTAL DATA – WALL MOUNTED

MWHD012S6S-1P – MWHD012S6-1P

496374 (202412) ©2024 Lennox Industries, Inc.

NOTE – Due to Lennox’ ongoing commitment to quality, Specifications, Ratings, and Dimensions are subject to change without notice and without incurring liability. Improper installation, adjustment, alteration, service or maintenance can cause property damage or personal injury. Installation and service must be performed by a qualified installer and servicing agency.

32 5/16

1 7/8

/4

9/

1/

/4

2 9/16

1/

3 5/16

2 9/16

6 15/16

1/

16 5/8

32 5/16

7/

2 1/2 2 1/2

15 5/8

15 11/16

8 7/16

Field Installed Accessories Catalog Number Qty Description

Y3400 2 DI 230-B2LType 2 Wall Brackets Lg

Y8174 2 L1 1/4 X 1/2 X 1/2 X 50 DL W/NUT EZ-PULL

SUBMITTAL DATA – WALL MOUNTED

MWHD018S6S-1P – MWHD018S6-1P

SINGLE ZONE MINI-SPLIT HEAT PUMP

Job: Engineer:

Location: Architect:

Schedule No.: Date:

System Designation: For: Reference Approval Review Construction

NOTE – Due to Lennox’ ongoing commitment to quality, Specifications, Ratings, and Dimensions are subject to change without notice and without incurring liability. Improper installation, adjustment, alteration, service or maintenance can cause property damage or personal injury. Installation and service must be performed by a qualified installer and servicing agency.

FEATURES

496376 (202412) ©2024 Lennox Industries, Inc.

▪ The indoor unit shall feature WindFree™* mode. When activated in cooling mode the unit will close its louver and will disperse air into the space through thousands of micro-holes on the front of the indoor unit preventing cold air drafts on occupants.

▪ The system shall have a built-in Wi-Fi adapter as standard to allow control and monitoring using the Samsung SmartThings app.

▪ Outdoor unit shall provide 208/230V power to the indoor unit via 14 AWG X 3 interconnect power cable.

Construction

▪ Indoor unit chassis shall be UL94 V0 with a galvanized steel mounting bracket

▪ The indoor unit shall have easy access to wire, pipe, and drain connections via the access panel on the bottom of the unit for simple installation and service

▪ The outdoor unit shall be galvanized steel with a baked-on powder coated finish for durability Heat Exchanger

▪ The heat exchangers shall be mechanically bonded fin to copper tube Refrigerant System

▪ The system shall utilize low-GWP R-32 refrigerant

The compressor shall be hermetically sealed, inverter controlled, BLDC Rotary Refrigerant flow shall be controlled by an electronic expansion valve at the outdoor unit

Indoor Fan

▪ The indoor fan shall be a single cross-flow type

▪ Three fan speed settings and auto setting

▪ Automatic (motorized) vertical swing (up/down) and horizontal swing (left/right) louvers Controls

▪ The indoor unit shall ship with a rechargeable, solar-cell wireless controller and holder. The wireless controller battery shall be charged with a USB C cable or the integral solar panel.

▪ The included wireless controller shall have a pixel display that is visible in low light conditions.

▪ Dual set temperature support when connected to supported wired controllers.

▪ The indoor unit shall include an integral humidity sensor for improved humidity control functions.

▪ The indoor unit shall have a simple connection for condensate overflow detec-tion devices or any normally closed contact for simple unit shutdown.

▪ Samsung central control compatible (accessory required)

▪ Interconnect control wire between the outdoor and indoor unit shall be 16AWG

X 2 External Heat Control

▪ External heat control functionality allows for configuration of fan operation during auxiliary heat operation, defrost, and emergency heat (VSTAT10P-1 accessory required).

▪ External heat control configuration settings includes outside ambient external heat lockout, outside ambient compressor lockout, and time delay options (VSTAT10P-1 accessory required).

▪ Emergency heat functionality allows the system to continue controlling the exter-nal heat source even when system errors prevent the heat pump from operating (VSTAT10P-1 accessory required).

Convenience

▪ 7-segment digital display on the front of the unit to display temperature and unit status

▪ Washable main filter as standard accessible from the top of the unit

▪ System energy consumption can be viewed using the Samsung SmartThings mobile app or on the indoor unit display using the included wireless controller (conditions apply).

▪ AI (artificial intelligence) Auto Mode technology monitors factors such as indoor temperature, outdoor temperature, set temperature, and operating time to learn the patterns within your home to automatically adjust system operation to maxi-mize occupant comfort and efficiency (Wi-Fi connection required).

▪ AI Energy mode technology enhances energy saving operation using advanced compressor control techniques

▪ Eco Mode to reduce energy consumption during low demand operation

▪ Smart install mode - Startup system diagnostics operation to ensure system readiness during initial operation

▪ Auto restart after power loss

▪ Other Features and functions: Auto changeover, Auto Clean Function, Freeze

Wash Function, MAX mode to quickly reach set temperature, Good’sleep mode, Quiet mode, Dry mode, Simple ON/OFF time function (activated with wireless controller), Filter cleaning reminder

Outdoor Unit: MWHD018S6S-1P

Indoor Unit: MWHD018S6-1P

PRODUCT WARRANTY

Compressor – Seven year warranty All other covered components - Five year warranty

VSTAT02P-1 Touch Screen Wired Controller* 37P79

VSTAT04P-1 Programmable Wired Controller* 37Y74

ACCESSORIES

VSTAT06P-1 Wall Mnt Mini-Splt Wired Cntrlr Sub PCB 37Y83

VCTRL11P-1 External Room Temp. Sensor 37Y77

VSTAT10P-1 External Contact Control 37Y69

VSTAT09P-1 24V Thermostat Adapter 37Y96

VCTRL06P-1 Interface Module Comm Adaptor ERV Kits 37Y82

*VSTAT06P-1 (37Y83) is REQUIRED with the selection of this accessory

NOTE – Due to Lennox’ ongoing commitment to quality, Specifications, Ratings, and Dimensions are subject to change without notice and without incurring liability. Improper installation, adjustment, alteration, service or maintenance can cause property damage or personal injury. Installation and service must be performed by a qualified installer and servicing agency.

496376 (202412) ©2024 Lennox Industries, Inc.

SUBMITTAL DATA – WALL MOUNTED

MWHD018S6S-1P – MWHD018S6-1P

SPECIFICATIONS

Performance

Nominal Capacity Cooling / Heating (Btu/h) 18,000 / 21,000

Capacity Range Cooling (Btu/h) 4,500 - 22,000 Heating (Btu/h) 4,000 - 27,500

AHRI 210-240 2023

SEER2 21.50

EER2 12.85

HSPF2 (region IV) 9.00

5°F COP 2.09

Power

Voltage ø / V / Hz 1 / 208-230 / 60 Working Voltage Range (VAC) 187 - 253

Operating Current (min. / standard / max.)

Cooling (A) 1.7 / 6.2 / 8.6 Heating (A) 1.6 / 8 / 10.1

Max. Breaker Amps 25.0 Min. Circuit Ampacity Amps 16.0

Dimensions W X H X D (in.)

Indoor Unit 41 9/16 X 11 3/4 X 8 7/16 Outdoor Unit 34 5/8 X 31 7/16 X 12 3/16

Weight (lbs.)

Indoor Unit 25.40 Outdoor Unit 108.00

Sound Pressure Level Indoor Unit dB(A) Silent / High 27 / 41 Outdoor Unit dB(A) Cooling (high) 51

Operating Temperatures Outdoor

Cooling 14 - 115°F (-10 - 46°C) Heating -5 - 75°F (-20.6 - 24°C)

Indoor Cooling 64 ~ 90°F (16 ~ 32°C) Heating T ≤ 86°F (30°C)

Pipe Connections

Indoor & Outdoor High side (In.) 1/4 Low side (In.) 1/2

Maximum (ft.) 98 Maximum Vertical Separation (ft.) 66 Condensate Connection 11/16” OD

Refrigerant

Type R-32 A2L Leak Detection Not Included Factory Charge oz. 52.9 Charged for 24.6 ft.

Compressor Type Inverter Driven, Twin BLDC Rotary RLA Amps 15.2

Evaporator Fan Type BLDC motor with cross-flow fan FLA Amps 0.12 Output Watts 27.0

Airflow Air Volume (L/M/H/Turbo) Cooling (CFM) 445 / 494 / 540 / 586 Heating (CFM) 445 / 494 / 540 / 586

Condenser Fan Type BLDC With Axial Type Fan (1) FLA / Watts / CFM (max.) 1.25 / 125 / 2,013

496376 (202412) ©2024 Lennox Industries, Inc.

NOTE – Due to Lennox’ ongoing commitment to quality, Specifications, Ratings, and Dimensions are subject to change without notice and without incurring liability. Improper installation, adjustment, alteration, service or maintenance can cause property damage or personal injury. Installation and service must be performed by a qualified installer and servicing agency.

SUBMITTAL DATA – WALL MOUNTED

MWHD018S6S-1P – MWHD018S6-1P

OUTDOOR DIMENSIONS IN.

/1

34 5/8 1 15/16

9/

26 1/164 5/16

9/

12 3/16

/8

7/

26 1 1/16

/1

9 3/16

9 9/16

/1

5/

/1

INDOOR DIMENSIONS IN.

496376 (202412)

NOTE – Due to Lennox’ ongoing commitment to quality, Specifications, Ratings, and Dimensions are subject to change without notice and without incurring liability. Improper installation, adjustment, alteration, service or maintenance can cause property damage or personal injury. Installation and service must be performed by a qualified installer and servicing agency.

SUBMITTAL DATA – WALL MOUNTED

MWHD018S6S-1P – MWHD018S6-1P

©2024 Lennox Industries, Inc.

41 1/2

-3

/4

21 1/820 3/8 2 7/

2 9/16 2 9/16

24 7/8

3 5/16

1/

2 1/22 1/26 15/16

1/

41 1/2 8 7/16

/4

9/

5/

2 7/16

Tag: 2.5 Ton Split System Condenser:

Evaporator Coil:

Furnace:

ML13KC1-030-230

CK40CT-30/36B (R454B)

ML196UH070XE36BK (RDS)

UNIT OVERVIEW AHRI Reference - 215586576

Voltage

AHRI

SEER2

EER2

Tons

Gross Cooling Ttl/Sens

(MBH)

Net Cooling Ttl/Sens

(MBH)

Supply Air Flow

(cfm)

ESP/TSP

(in.WC)

EAT

DB/WB

(°F)

LAT

DB/WB

(°F) 208 Volt 1 Phase / 60Hz

14.3

12.2 2.5 28.0 / 20.8 26.4 / 19.2 958 0.5 / 0.6 80.0 / 67.0 50.1 / 50.1

COOLING

Cooling Performance Temperatures (DB/WB °F)

Gross Cooling (Ttl/Sens) Net Cooling (Ttl/Sens) Coil Moisture Removal

28.0 / 20.8 MBH

26.4 / 19.2 MBH

6.77 lb/hr

Ambient Entering Total Leaving – (Coil) Total Leaving – (Unit)

95.0 80.0 50.1 52.5

67.0 50.1 52.5

ARI Performance Compressors Refrigerant Condensate Drain AHRI Cooling 28.0 MBH Cooling Stages

Compressor Qty Single

Type Cond Suction Line Cond Liquid Line Coil Suction Line Coil Liquid Line

R-454B 3/4 3/8 3/4 3/8

Qty Size Pipe Thread

0.75 in.

fpt

HEATING

Heating Performance Temperatures (DB/WB °F) Specifications

Output (High/Low) Input (High/Low)

63.9 / MBH

66.0 / MBH

Gas Heat Rise Total Leaving

61.8°F 61.8

Thermal Efficiency Gas Line Size Heat Exchange Type

96.0%

0.5 in.

Aluminum

VENTILATION

Air Flow (cfm) Supply Fan Air Resistance (in.WC)

Supply 958 Nominal Power Drive Type Speed Orientation

0.5hp ECM Multi Speed Constant Torque Medium-Low Upflow/Horizontal

Total Ext Supply Wet Coil

0.61 0.50 0.11

ELECTRICAL

Condenser Furnace

Voltage

MCA

MOCP

Condenser Oper Range-Nom Volt Oper Range-Nom Volt

208 Volt 1 Phase / 60Hz 17 amp 25 amp +/- 10% +/- 10%

Voltage

MCA

MOCP

120V / 1Ph / 60Hz

15.0 amp

ADDITIONAL DATA

Condenser Furnace Evaporator Coil

Dimensions Total Weight

28.25 in. x 28.25 in. x 29.25 in.

152 lb

Dimensions Total Weight

28.75 in. x 17.50 in. x 33.00 in.

129 lb

Dimensions Total Weight

21.00 in. x 17.50 in. x 24.50 in.

45 lb

Field Installed Accessories Catalog Number Qty Description

26P11 2 ML196UH070XE36BK Furnace-Gas/70Btuh/3Ton

Product Features

Cabinet Heavy gauge galvanized steel cabinet Non-corrosive drain pan Fully Insulated heavy gauge steel cabinet Heavy Gauge Cold Rolled Steel Cabinet

Cooling System High Pressure Switch (Manual Reset) Scroll Compressor Quantum Coil / Fortified aluminum allow tube/enhanced fin coil Hi-Capacity Drier factory installed in liquid line Low Pressure Switch Twin Coils assembled in an "A" configuration Check and Expansion Valve is factory installed

Heating System Aluminized Steel Inshot Burners Aluminized Steel Tubular Heat Exchanger SureLight(R) Hot Surface Ignition Furnace Liminted Warranty 10 Years Comm

Control System Indoor Refirgerant Detection System (RDS)

Approvals and Compliance Only refrigerants in compliance with New York State regulations can be used in the state of New York

Warranty Condenser Limited compressor warranty of 5 years for Residential Installations Condenser See Limited Warranty Certificate included with unit for detailsCondenser Limited compressor warranty of 5 years for Non-Residential InstallationsCondenser Limited warranty on all covered components of 1 year in Non-Residential InstallationsCoil See Limited Warranty Certificate included with unit for detailsCoil Limited warranty on all other covered components of 1 year (Comm Use)Furnace See Limited Warranty Certificate included with unit for detailsFurnace Limited warranty on heat exchanger of 20 yearsFurnace Limited warranty on all other covered components of 1 year (Comm Use)Furnace Limited warranty on Surelight ignition control system of 1 Year (Comm Use)

Tag: Miscellaneous Items

Miscellaneous Items Tag Catalog Number Qty Description Condensate Pump

14T74 3 X86-003 - MicroBlue & Reservoir 110-230V