Attachment 2_Specifications.pdf
PDF 8 MB Posted
- Attached to
- HVAC Equipment Replacement, Millville, Utah
- Solicitation number
- 12639526Q0076
About this file
This is a project submittal document for HVAC equipment under federal contract 12639526Q0076, Attachment 2 (Lennox or equal). The submittal specifies equipment requirements for 11 split systems with zero roof-top units, including seven 1-ton mini-split heat pumps, two 1.5-ton mini-split heat pumps, and two 2.5-ton split systems. The 1-ton and 1.5-ton systems are wall-mounted, single-zone mini-split heat pumps utilizing R-32 refrigerant with inverter-driven compressors and built-in Wi-Fi connectivity. The 1-ton units (MWHD012S6S/MWHD012S6) deliver 12,000 BTU cooling/heating capacity with SEER2 of 24.00 and EER2 of 13.25, while the 1.5-ton units (MWHD018S6S/MWHD018S6) provide 18,000/21,000 BTU with SEER2 of 21.50 and EER2 of 12.85. Field-installed accessories for the mini-split systems include duct cable strips, interconnect cable assemblies, and wall brackets totaling 7 units each.
The 2.5-ton split systems utilize a condenser (ML13KC1-030-230), R454B evaporator coil (CK40CT-30/36B), and gas furnace (ML196UH070XE36BK RDS) with AHRI certification 215586576, delivering 28.0 MBH gross cooling and 63.9 MBH heating output at 208-volt single-phase operation. The submittal includes detailed specifications, dimensional drawings, performance data, product features, and warranty information for all equipment. Additionally, three condensate pumps (X86-003 MicroBlue 110-230V) are specified as miscellaneous items. The document references Revit BIM and AutoCAD template links for design integration, though specific response deadlines, award dates, and pricing information are not contained within this submittal package.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| RFIs and Responses.docx | DOCX document | |
| Site Visit Attendance-2.pdf | ||
| 12639526Q0076-0002.pdf | ||
| Site visit attendance.pdf | ||
| 12639526Q0076-0001.pdf | ||
| Attachment 3_Federal Construction Wage Rates_Cache County (1).txt | TXT text file | |
| 12639526Q0076.docx | DOCX document | |
| Attachment 1_Statement of Work_HVAC.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Page
Project Name:
Project Number:
Project Altitude:
Project Location:
Customer:
Date:
Quote:
Roof Top Units: 0 Split Systems: 11
Table of Contents Tag Qty Model Description
1 Ton
27K85 27K92
MWHD012S6S SZ HP 12K 208/230V
MWHD012S6 SZ IDU Wall 12K 208/230V
1.5 Ton
27K86 27K93
MWHD018S6S SZ HP 18K 208/230V
MWHD018S6 SZ IDU Wall 18K 208/230V
2.5 Ton Split System
25C67 25U77
ML196UH070XE36BK
ML13KC1-030 Condenser/2.5 Ton/230
CK40CT-30/36B COIL 2.5-3.0T R454B
ML196UH070XE36BK UH 70KBTU NOX 3T
Miscellaneous Items
Revit® Building Information Modeling (BIM) - Click here
AutoCAD® Templates - Click here
12639526Q0076, Attachment 2 (Lennox or equal)
Project Submittal https://www.lennoxcommercial.com/support/contractors/revit-bim-software https://www.lennoxcommercial.com/support/contractors/autocad-templates
Project Submittal
Field Installed Accessories Catalog Number Qty Description
29F41 7 Duct-Strip 5 Mini-Split Cable, 250 Pull
Y8171 7 L1 1/4 X 3/8 X 1/2 X 25 DL W/NUT EZ-PULL
Y3400 7 DI 230-B2LType 2 Wall Brackets Lg
SUBMITTAL DATA – WALL MOUNTED
MWHD012S6S-1P – MWHD012S6-1P
SINGLE ZONE MINI-SPLIT HEAT PUMP
Job: Engineer:
Location: Architect:
Schedule No.: Date:
System Designation: For: Reference Approval Review Construction
NOTE – Due to Lennox’ ongoing commitment to quality, Specifications, Ratings, and Dimensions are subject to change without notice and without incurring liability. Improper installation, adjustment, alteration, service or maintenance can cause property damage or personal injury. Installation and service must be performed by a qualified installer and servicing agency.
FEATURES
496374 (202412) ©2024 Lennox Industries, Inc.
▪ The indoor unit shall feature WindFree™* mode. When activated in cooling mode the unit will close its louver and will disperse air into the space through thousands of micro-holes on the front of the indoor unit preventing cold air drafts on occupants.
▪ The system shall have a built-in Wi-Fi adapter as standard to allow control and monitoring using the Samsung SmartThings app.
▪ Outdoor unit shall provide 208/230V power to the indoor unit via 14 AWG X 3 interconnect power cable.
Construction
▪ Indoor unit chassis shall be UL94 V0 with a galvanized steel mounting bracket
▪ The indoor unit shall have easy access to wire, pipe, and drain connections via the access panel on the bottom of the unit for simple installation and service
▪ The outdoor unit shall be galvanized steel with a baked-on powder coated finish for durability Heat Exchanger
▪ The heat exchangers shall be mechanically bonded fin to copper tube Refrigerant System
▪ The system shall utilize low-GWP R-32 refrigerant
The compressor shall be hermetically sealed, inverter controlled, BLDC Rotary Refrigerant flow shall be controlled by an electronic expansion valve at the outdoor unit
Indoor Fan
▪ The indoor fan shall be a single cross-flow type
▪ Three fan speed settings and auto setting
▪ Automatic (motorized) vertical swing (up/down) and horizontal swing (left/right) louvers Controls
▪ The indoor unit shall ship with a rechargeable, solar-cell wireless controller and holder. The wireless controller battery shall be charged with a USB C cable or the integral solar panel.
▪ The included wireless controller shall have a pixel display that is visible in low light conditions.
▪ Dual set temperature support when connected to supported wired controllers.
▪ The indoor unit shall include an integral humidity sensor for improved humidity control functions.
▪ The indoor unit shall have a simple connection for condensate overflow detec-tion devices or any normally closed contact for simple unit shutdown.
▪ Samsung central control compatible (accessory required)
▪ Interconnect control wire between the outdoor and indoor unit shall be 16AWG
X 2 External Heat Control
▪ External heat control functionality allows for configuration of fan operation during auxiliary heat operation, defrost, and emergency heat (VSTAT10P-1 accessory required).
▪ External heat control configuration settings includes outside ambient external heat lockout, outside ambient compressor lockout, and time delay options (VSTAT10P-1 accessory required).
▪ Emergency heat functionality allows the system to continue controlling the exter-nal heat source even when system errors prevent the heat pump from operating (VSTAT10P-1 accessory required).
Convenience
▪ 7-segment digital display on the front of the unit to display temperature and unit status
▪ Washable main filter as standard accessible from the top of the unit
▪ System energy consumption can be viewed using the Samsung SmartThings mobile app or on the indoor unit display using the included wireless controller (conditions apply).
▪ AI (artificial intelligence) Auto Mode technology monitors factors such as indoor temperature, outdoor temperature, set temperature, and operating time to learn the patterns within your home to automatically adjust system operation to maxi-mize occupant comfort and efficiency (Wi-Fi connection required).
▪ AI Energy mode technology enhances energy saving operation using advanced compressor control techniques
▪ Eco Mode to reduce energy consumption during low demand operation
▪ Smart install mode - Startup system diagnostics operation to ensure system readiness during initial operation
▪ Auto restart after power loss
▪ Other Features and functions: Auto changeover, Auto Clean Function, Freeze
Wash Function, MAX mode to quickly reach set temperature, Good’sleep mode, Quiet mode, Dry mode, Simple ON/OFF time function (activated with wireless controller), Filter cleaning reminder
Outdoor Unit: MWHD012S6S-1P
Indoor Unit: MWHD012S6-1P
VSTAT02P-1 Touch Screen Wired Controller* 37P79
VSTAT04P-1 Programmable Wired Controller* 37Y74
ACCESSORIES
VSTAT06P-1 Wall Mnt Mini-Splt Wired Cntrlr Sub PCB 37Y83
VCTRL11P-1 External Room Temp. Sensor 37Y77
VSTAT10P-1 External Contact Control 37Y69
VSTAT09P-1 24V Thermostat Adapter 37Y96
VCTRL06P-1 Interface Module Comm Adaptor ERV Kits 37Y82
*VSTAT06P-1 (37Y83) is REQUIRED with the selection of this accessory
PRODUCT WARRANTY
Compressor – Seven year warranty All other covered components - Five year warranty
SINGLE ZONE MINI-SPLIT HEAT PUMP
NOTE – Due to Lennox’ ongoing commitment to quality, Specifications, Ratings, and Dimensions are subject to change without notice and without incurring liability. Improper installation, adjustment, alteration, service or maintenance can cause property damage or personal injury. Installation and service must be performed by a qualified installer and servicing agency.
496374 (202412) ©2024 Lennox Industries, Inc.
SUBMITTAL DATA – WALL MOUNTED
MWHD012S6S-1P – MWHD012S6-1P
SPECIFICATIONS
Performance
Nominal Capacity Cooling / Heating (Btu/h) 12,000 / 12,000
Capacity Range Cooling (Btu/h) 3,000 - 15,500 Heating (Btu/h) 2,200 - 23,000
AHRI 210-240 2023
SEER2 24.00
EER2 13.25
HSPF2 (region IV) 9.00
5°F COP 1.76
Power
Voltage ø / V / Hz 1 / 208-230 / 60 Working Voltage Range (VAC) 187 - 253
Operating Current (min. / standard / max.)
Cooling (A) 1.1 / 4.8 / 6.2 Heating (A) 1 / 4.6 / 10
Max. Breaker Amps 20.0 Min. Circuit Ampacity Amps 12.0
Dimensions W X H X D (in.)
Indoor Unit 32 5/16 X 11 3/4 X 8 7/16 Outdoor Unit 31 1/8 X 21 9/16 X 11 1/4
Weight (lbs.)
Indoor Unit 20.30 Outdoor Unit 69.20
Sound Pressure Level Indoor Unit dB(A) Silent / High 22 / 39 Outdoor Unit dB(A) Cooling (high) 46
Operating Temperatures Outdoor
Cooling 14 - 115°F (-10 - 46°C) Heating -5 - 75°F (-20.6 - 24°C)
Indoor Cooling 64 ~ 90°F (16 ~ 32°C) Heating T ≤ 86°F (30°C)
Pipe Connections
Indoor & Outdoor High side (In.) 1/4 Low side (In.) 3/8
Maximum (ft.) 66 Maximum Vertical Separation (ft.) 49 Condensate Connection 11/16” OD
Refrigerant
Type R-32 A2L Leak Detection Not Included Factory Charge oz. 34.0 Charged for 24.6 ft.
Compressor Type Inverter Driven, Twin BLDC Rotary RLA Amps 9.2
Evaporator Fan Type BLDC motor with cross-flow fan FLA Amps 0.12 Output Watts 27.0
Airflow Air Volume (L/M/H/Turbo) Cooling (CFM) 297 / 328 / 364 / 378 Heating (CFM) 328 / 364 / 396 / 413
Condenser Fan Type BLDC With Axial Type Fan (1) FLA / Watts / CFM (max.) 0.42 / 40 / 1,589
496374 (202412) ©2024 Lennox Industries, Inc.
NOTE – Due to Lennox’ ongoing commitment to quality, Specifications, Ratings, and Dimensions are subject to change without notice and without incurring liability. Improper installation, adjustment, alteration, service or maintenance can cause property damage or personal injury. Installation and service must be performed by a qualified installer and servicing agency.
SUBMITTAL DATA – WALL MOUNTED
MWHD012S6S-1P – MWHD012S6-1P
OUTDOOR DIMENSIONS IN.
31 1/8
23 11/16
/4
/1
1 15/16 X 1/2
/1
3 1/2
20 1/16
/1
1/
11 1/4
1/
/1
INDOOR DIMENSIONS IN.
SUBMITTAL DATA – WALL MOUNTED
MWHD012S6S-1P – MWHD012S6-1P
496374 (202412) ©2024 Lennox Industries, Inc.
NOTE – Due to Lennox’ ongoing commitment to quality, Specifications, Ratings, and Dimensions are subject to change without notice and without incurring liability. Improper installation, adjustment, alteration, service or maintenance can cause property damage or personal injury. Installation and service must be performed by a qualified installer and servicing agency.
32 5/16
1 7/8
/4
9/
1/
/4
2 9/16
1/
3 5/16
2 9/16
6 15/16
1/
16 5/8
32 5/16
7/
2 1/2 2 1/2
15 5/8
15 11/16
8 7/16
Field Installed Accessories Catalog Number Qty Description
Y3400 2 DI 230-B2LType 2 Wall Brackets Lg
Y8174 2 L1 1/4 X 1/2 X 1/2 X 50 DL W/NUT EZ-PULL
SUBMITTAL DATA – WALL MOUNTED
MWHD018S6S-1P – MWHD018S6-1P
SINGLE ZONE MINI-SPLIT HEAT PUMP
Job: Engineer:
Location: Architect:
Schedule No.: Date:
System Designation: For: Reference Approval Review Construction
NOTE – Due to Lennox’ ongoing commitment to quality, Specifications, Ratings, and Dimensions are subject to change without notice and without incurring liability. Improper installation, adjustment, alteration, service or maintenance can cause property damage or personal injury. Installation and service must be performed by a qualified installer and servicing agency.
FEATURES
496376 (202412) ©2024 Lennox Industries, Inc.
▪ The indoor unit shall feature WindFree™* mode. When activated in cooling mode the unit will close its louver and will disperse air into the space through thousands of micro-holes on the front of the indoor unit preventing cold air drafts on occupants.
▪ The system shall have a built-in Wi-Fi adapter as standard to allow control and monitoring using the Samsung SmartThings app.
▪ Outdoor unit shall provide 208/230V power to the indoor unit via 14 AWG X 3 interconnect power cable.
Construction
▪ Indoor unit chassis shall be UL94 V0 with a galvanized steel mounting bracket
▪ The indoor unit shall have easy access to wire, pipe, and drain connections via the access panel on the bottom of the unit for simple installation and service
▪ The outdoor unit shall be galvanized steel with a baked-on powder coated finish for durability Heat Exchanger
▪ The heat exchangers shall be mechanically bonded fin to copper tube Refrigerant System
▪ The system shall utilize low-GWP R-32 refrigerant
The compressor shall be hermetically sealed, inverter controlled, BLDC Rotary Refrigerant flow shall be controlled by an electronic expansion valve at the outdoor unit
Indoor Fan
▪ The indoor fan shall be a single cross-flow type
▪ Three fan speed settings and auto setting
▪ Automatic (motorized) vertical swing (up/down) and horizontal swing (left/right) louvers Controls
▪ The indoor unit shall ship with a rechargeable, solar-cell wireless controller and holder. The wireless controller battery shall be charged with a USB C cable or the integral solar panel.
▪ The included wireless controller shall have a pixel display that is visible in low light conditions.
▪ Dual set temperature support when connected to supported wired controllers.
▪ The indoor unit shall include an integral humidity sensor for improved humidity control functions.
▪ The indoor unit shall have a simple connection for condensate overflow detec-tion devices or any normally closed contact for simple unit shutdown.
▪ Samsung central control compatible (accessory required)
▪ Interconnect control wire between the outdoor and indoor unit shall be 16AWG
X 2 External Heat Control
▪ External heat control functionality allows for configuration of fan operation during auxiliary heat operation, defrost, and emergency heat (VSTAT10P-1 accessory required).
▪ External heat control configuration settings includes outside ambient external heat lockout, outside ambient compressor lockout, and time delay options (VSTAT10P-1 accessory required).
▪ Emergency heat functionality allows the system to continue controlling the exter-nal heat source even when system errors prevent the heat pump from operating (VSTAT10P-1 accessory required).
Convenience
▪ 7-segment digital display on the front of the unit to display temperature and unit status
▪ Washable main filter as standard accessible from the top of the unit
▪ System energy consumption can be viewed using the Samsung SmartThings mobile app or on the indoor unit display using the included wireless controller (conditions apply).
▪ AI (artificial intelligence) Auto Mode technology monitors factors such as indoor temperature, outdoor temperature, set temperature, and operating time to learn the patterns within your home to automatically adjust system operation to maxi-mize occupant comfort and efficiency (Wi-Fi connection required).
▪ AI Energy mode technology enhances energy saving operation using advanced compressor control techniques
▪ Eco Mode to reduce energy consumption during low demand operation
▪ Smart install mode - Startup system diagnostics operation to ensure system readiness during initial operation
▪ Auto restart after power loss
▪ Other Features and functions: Auto changeover, Auto Clean Function, Freeze
Wash Function, MAX mode to quickly reach set temperature, Good’sleep mode, Quiet mode, Dry mode, Simple ON/OFF time function (activated with wireless controller), Filter cleaning reminder
Outdoor Unit: MWHD018S6S-1P
Indoor Unit: MWHD018S6-1P
PRODUCT WARRANTY
Compressor – Seven year warranty All other covered components - Five year warranty
VSTAT02P-1 Touch Screen Wired Controller* 37P79
VSTAT04P-1 Programmable Wired Controller* 37Y74
ACCESSORIES
VSTAT06P-1 Wall Mnt Mini-Splt Wired Cntrlr Sub PCB 37Y83
VCTRL11P-1 External Room Temp. Sensor 37Y77
VSTAT10P-1 External Contact Control 37Y69
VSTAT09P-1 24V Thermostat Adapter 37Y96
VCTRL06P-1 Interface Module Comm Adaptor ERV Kits 37Y82
*VSTAT06P-1 (37Y83) is REQUIRED with the selection of this accessory
NOTE – Due to Lennox’ ongoing commitment to quality, Specifications, Ratings, and Dimensions are subject to change without notice and without incurring liability. Improper installation, adjustment, alteration, service or maintenance can cause property damage or personal injury. Installation and service must be performed by a qualified installer and servicing agency.
496376 (202412) ©2024 Lennox Industries, Inc.
SUBMITTAL DATA – WALL MOUNTED
MWHD018S6S-1P – MWHD018S6-1P
SPECIFICATIONS
Performance
Nominal Capacity Cooling / Heating (Btu/h) 18,000 / 21,000
Capacity Range Cooling (Btu/h) 4,500 - 22,000 Heating (Btu/h) 4,000 - 27,500
AHRI 210-240 2023
SEER2 21.50
EER2 12.85
HSPF2 (region IV) 9.00
5°F COP 2.09
Power
Voltage ø / V / Hz 1 / 208-230 / 60 Working Voltage Range (VAC) 187 - 253
Operating Current (min. / standard / max.)
Cooling (A) 1.7 / 6.2 / 8.6 Heating (A) 1.6 / 8 / 10.1
Max. Breaker Amps 25.0 Min. Circuit Ampacity Amps 16.0
Dimensions W X H X D (in.)
Indoor Unit 41 9/16 X 11 3/4 X 8 7/16 Outdoor Unit 34 5/8 X 31 7/16 X 12 3/16
Weight (lbs.)
Indoor Unit 25.40 Outdoor Unit 108.00
Sound Pressure Level Indoor Unit dB(A) Silent / High 27 / 41 Outdoor Unit dB(A) Cooling (high) 51
Operating Temperatures Outdoor
Cooling 14 - 115°F (-10 - 46°C) Heating -5 - 75°F (-20.6 - 24°C)
Indoor Cooling 64 ~ 90°F (16 ~ 32°C) Heating T ≤ 86°F (30°C)
Pipe Connections
Indoor & Outdoor High side (In.) 1/4 Low side (In.) 1/2
Maximum (ft.) 98 Maximum Vertical Separation (ft.) 66 Condensate Connection 11/16” OD
Refrigerant
Type R-32 A2L Leak Detection Not Included Factory Charge oz. 52.9 Charged for 24.6 ft.
Compressor Type Inverter Driven, Twin BLDC Rotary RLA Amps 15.2
Evaporator Fan Type BLDC motor with cross-flow fan FLA Amps 0.12 Output Watts 27.0
Airflow Air Volume (L/M/H/Turbo) Cooling (CFM) 445 / 494 / 540 / 586 Heating (CFM) 445 / 494 / 540 / 586
Condenser Fan Type BLDC With Axial Type Fan (1) FLA / Watts / CFM (max.) 1.25 / 125 / 2,013
496376 (202412) ©2024 Lennox Industries, Inc.
NOTE – Due to Lennox’ ongoing commitment to quality, Specifications, Ratings, and Dimensions are subject to change without notice and without incurring liability. Improper installation, adjustment, alteration, service or maintenance can cause property damage or personal injury. Installation and service must be performed by a qualified installer and servicing agency.
SUBMITTAL DATA – WALL MOUNTED
MWHD018S6S-1P – MWHD018S6-1P
OUTDOOR DIMENSIONS IN.
/1
34 5/8 1 15/16
9/
26 1/164 5/16
9/
12 3/16
/8
7/
26 1 1/16
/1
9 3/16
9 9/16
/1
5/
/1
INDOOR DIMENSIONS IN.
496376 (202412)
NOTE – Due to Lennox’ ongoing commitment to quality, Specifications, Ratings, and Dimensions are subject to change without notice and without incurring liability. Improper installation, adjustment, alteration, service or maintenance can cause property damage or personal injury. Installation and service must be performed by a qualified installer and servicing agency.
SUBMITTAL DATA – WALL MOUNTED
MWHD018S6S-1P – MWHD018S6-1P
©2024 Lennox Industries, Inc.
41 1/2
-3
/4
21 1/820 3/8 2 7/
2 9/16 2 9/16
24 7/8
3 5/16
1/
2 1/22 1/26 15/16
1/
41 1/2 8 7/16
/4
9/
5/
2 7/16
Tag: 2.5 Ton Split System Condenser:
Evaporator Coil:
Furnace:
ML13KC1-030-230
CK40CT-30/36B (R454B)
ML196UH070XE36BK (RDS)
UNIT OVERVIEW AHRI Reference - 215586576
Voltage
AHRI
SEER2
EER2
Tons
Gross Cooling Ttl/Sens
(MBH)
Net Cooling Ttl/Sens
(MBH)
Supply Air Flow
(cfm)
ESP/TSP
(in.WC)
EAT
DB/WB
(°F)
LAT
DB/WB
(°F) 208 Volt 1 Phase / 60Hz
14.3
12.2 2.5 28.0 / 20.8 26.4 / 19.2 958 0.5 / 0.6 80.0 / 67.0 50.1 / 50.1
COOLING
Cooling Performance Temperatures (DB/WB °F)
Gross Cooling (Ttl/Sens) Net Cooling (Ttl/Sens) Coil Moisture Removal
28.0 / 20.8 MBH
26.4 / 19.2 MBH
6.77 lb/hr
Ambient Entering Total Leaving – (Coil) Total Leaving – (Unit)
95.0 80.0 50.1 52.5
67.0 50.1 52.5
ARI Performance Compressors Refrigerant Condensate Drain AHRI Cooling 28.0 MBH Cooling Stages
Compressor Qty Single
Type Cond Suction Line Cond Liquid Line Coil Suction Line Coil Liquid Line
R-454B 3/4 3/8 3/4 3/8
Qty Size Pipe Thread
0.75 in.
fpt
HEATING
Heating Performance Temperatures (DB/WB °F) Specifications
Output (High/Low) Input (High/Low)
63.9 / MBH
66.0 / MBH
Gas Heat Rise Total Leaving
61.8°F 61.8
Thermal Efficiency Gas Line Size Heat Exchange Type
96.0%
0.5 in.
Aluminum
VENTILATION
Air Flow (cfm) Supply Fan Air Resistance (in.WC)
Supply 958 Nominal Power Drive Type Speed Orientation
0.5hp ECM Multi Speed Constant Torque Medium-Low Upflow/Horizontal
Total Ext Supply Wet Coil
0.61 0.50 0.11
ELECTRICAL
Condenser Furnace
Voltage
MCA
MOCP
Condenser Oper Range-Nom Volt Oper Range-Nom Volt
208 Volt 1 Phase / 60Hz 17 amp 25 amp +/- 10% +/- 10%
Voltage
MCA
MOCP
120V / 1Ph / 60Hz
15.0 amp
ADDITIONAL DATA
Condenser Furnace Evaporator Coil
Dimensions Total Weight
28.25 in. x 28.25 in. x 29.25 in.
152 lb
Dimensions Total Weight
28.75 in. x 17.50 in. x 33.00 in.
129 lb
Dimensions Total Weight
21.00 in. x 17.50 in. x 24.50 in.
45 lb
Field Installed Accessories Catalog Number Qty Description
26P11 2 ML196UH070XE36BK Furnace-Gas/70Btuh/3Ton
Product Features
Cabinet Heavy gauge galvanized steel cabinet Non-corrosive drain pan Fully Insulated heavy gauge steel cabinet Heavy Gauge Cold Rolled Steel Cabinet
Cooling System High Pressure Switch (Manual Reset) Scroll Compressor Quantum Coil / Fortified aluminum allow tube/enhanced fin coil Hi-Capacity Drier factory installed in liquid line Low Pressure Switch Twin Coils assembled in an "A" configuration Check and Expansion Valve is factory installed
Heating System Aluminized Steel Inshot Burners Aluminized Steel Tubular Heat Exchanger SureLight(R) Hot Surface Ignition Furnace Liminted Warranty 10 Years Comm
Control System Indoor Refirgerant Detection System (RDS)
Approvals and Compliance Only refrigerants in compliance with New York State regulations can be used in the state of New York
Warranty Condenser Limited compressor warranty of 5 years for Residential Installations Condenser See Limited Warranty Certificate included with unit for detailsCondenser Limited compressor warranty of 5 years for Non-Residential InstallationsCondenser Limited warranty on all covered components of 1 year in Non-Residential InstallationsCoil See Limited Warranty Certificate included with unit for detailsCoil Limited warranty on all other covered components of 1 year (Comm Use)Furnace See Limited Warranty Certificate included with unit for detailsFurnace Limited warranty on heat exchanger of 20 yearsFurnace Limited warranty on all other covered components of 1 year (Comm Use)Furnace Limited warranty on Surelight ignition control system of 1 Year (Comm Use)
Tag: Miscellaneous Items
Miscellaneous Items Tag Catalog Number Qty Description Condensate Pump
14T74 3 X86-003 - MicroBlue & Reservoir 110-230V
File details come from the government source that posted it. Updated .