Attachment 2 - Sheet ES101 revised for EHRM.pdf
PDF 839 KB Posted
- Attached to
- Y1AZ--674A4-21-703 EHRM Training and Admin Support Space Construction Waco Texas (VA-22-00050768)
- Solicitation number
- 36C77622B0045
About this file
This document includes an electrical site plan and specifications for renovations to the EHRM Training and Admin Space at the Department of Veterans Affairs facility in Waco, Texas. Key work includes demolishing an existing transformer and associated wiring, installing new medium voltage transformers and secondary conductors in a new ductbank, providing new pole-mounted LED area lights, and making building penetrations for power. The solicitation is for construction services to complete this work per the specifications and drawings by August 2022.
View the file
Other files
Show all 25
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
E
E
PBA-19,21
PP3
PBA-16,18
PP2
PBA-20,22
PP2
xd/xe xh/xi xf/xg
A. DEMOLISH EXISTING TRANSFORMER CIRCUIT, ON PRIMARY SIDE TO
NEAREST MANHOLE. FIELD VERIFY LOCATION OF NEAREST MANHOLE.
B. REMOVE WIRING, REUSE EXISTING CONDUIT FOR NEW TRANSFORMER
WIRING.
C. REFER TO ELECTRICAL ONE LINE DIAGRAM ON SHEET E-601 FOR
TRANSFORMER DETAILS.
E-410
EXISTING
UNDERGROUND
CONDUCTORS
00KEYNOTES
GENERAL NOTES
Drawing Title
VA FORM 08 - 6231
F
CONSULTANTS:
750 W HAMPDEN AVE
SUITE 300
ENGLEWOOD, CO 80110
(720) 550-6307 WWW.VALHALLAENGINEERING.COMDate:Issued:
10987654321
10987654321
E
D
C
B
A
F
E
D
C
B
A
ARCHITECT/ENGINEERS: STAMP:
Approved: Project Director
Phase Project Title
Location
Issue Date Checked Drawn
Project Number
Drawing Number
Building Number
C :\U se rs
\V al ha lla
E ng in ee r 7 \D oc um en ts
\6
A 4-
-7
_B ld g.
_E le c_
R
_r th or nb ru gh
S 6J
X V
.rv t
2/
/2
2:
:4
P
M
ES101
ELECTRICAL SITE PLAN EHRM TRAINING AND ADMIN
SPACE SUPPORT
4800 MEMORIAL DRIVE, WACO, TX 76711
674A4-21-703
02/10/2022 RA MLS
100% CONSTRUCTION
DOCUMENTS
VEG 20.15
64'32'16'8'4'0'
P la n N o rt h
Tru e N orth
1/16" = 1'-0"
ELECTRICAL SITE PLAN
1. EXISTING ELECTRICAL MANHOLE F. DISCONNECT EXISTING
TRANSFORMER AND REMOVE PRIMARY SIDE CONDUCTORS BACK TO
EXISTING MANHOLE.
2. REMOVE EXISTING DISCONNECTS AND ASSOCIATED WIRING BACK TO
PANEL. CUT AND CAP CONDUIT AT GRADE.
3. REMOVE EXISTING TRANSFORMER AND TRANSFORMER PAD.
4. THE CONTRACTOR WILL PROVIDE LED AREA LIGHTS MOUNTED ON 30
FOOT POLE WITH CONCRETE BASE AS PER DETAIL 10 ON SHEET E-501.
THE POLE SHALL HAVE THREE ARMS AND THREE LUMINAIRES. THE
LUMINAIRES SHALL MATCH EXISTING POLE MOUNTED LUMINAIRES
LOCATED IN ADJACENT AREAS OR BE SIMILAR WITH THE SAME LUMEN
OUTPUT AND DISTRIBUTION PATTERN. THE POLE MOUNTED LUMINAIRES
SHALL BE POWERED FROM CIRCUIT SHOWN. FURNISH AND INSTALL LIGHT
POLE. REFER TO SPECIFICATION SECTION 01 00 00.
5. THE CONTRACTOR WILL PROVIDE LED AREA LIGHTS MOUNTED ON 30
FOOT POLE WITH CONCRETE BASE AS PER DETAIL 10 ON SHEET E-501.
THE POLE SHALL HAVE TWO ARMS AND TWO LUMINAIRES. THE
LUMINAIRES SHALL MATCH EXISTING POLE MOUNTED LUMINAIRES
LOCATED IN ADJACENT AREAS OR BE SIMILAR WITH THE SAME LUMEN
OUTPUT AND DISTRIBUTION PATTERN. THE POLE MOUNTED LUMINAIRES
SHALL BE POWERED FROM CIRCUITS SHOWN. FURNISH AND INSTALL
LIGHT POLES. REFER TO SITE DEMO ON SHEET ES101 FOR RELATED
WORK. REFER TO SPECIFICATION SECTION 01 00 00.
6. ELECTRICAL CONTRACTOR SHALL PROVIDE MEDIUM VOLTAGE
TRANSFORMER PER SPECIFICATION SECTION 26 12 19. REFER TO SHEET
E-504 AND E-601 FOR MORE INFORMATION.
7. NEW SECONDARY SIDE CONDUCTORS MAIN DISTRIBUTION ELECTRICAL
EQUIPMENT. SEE DETAIL 6 ON SHEET E-501 FOR DUCTBANK DETAILS.
REFER TO FEEDER SCHEDULE ON SHEET E-508 FOR MORE INFORMATION.
COORDINATE WITH CIVIL FOR PHASING ON INSTALLING PORTION OF
SIDEWALK AFTER DUCTBANK IS LAID IN. SCHEDULE INSTALLATION OF
DUCTBANK AND CONDUIT PRIOR TO INSTALL OF SIDEWALK.
8. PROVIDE CONNECTORS FOR TRANSITION OF CONDUIT INTO THE
BUILDING. MAKE PENETRATIONS INTO THE BUILDING AT NOT MORE THAN
12” ABOVE GRADE.
9. PROVIDE JUNCTION BOX ADJACENT TO CONCRETE PAD FOR STAIRWAY.
PROVIDE SURFACE MOUNTED CONDUIT UP ALONG VERTICAL BEAMS OF
STAIRWELL TO PROVIDE POWER FOR LIGHTING CIRCUIT.
10. PROVIDE NEW MEDIUM VOLTAGE CABLES TO MATCH EXISTING, THRU
DUCTBANK AND SPLICE IN MANHOLE TO CABLES PREVIOUSLY FEEDING
BLDG 12. PROVIDE DUCTBANK PER DETAIL 6 ON SHEET E-501 AND PER
SPECIFICATION SECTION 26 05 41.
32'16'8'4'2'0'
P la n N o rt h
Tru e N orth
1/16" = 1'-0"
ELECTRICAL SITE PLAN DEMO
9 9
File details come from the government source that posted it. Updated .