Attachment 14 - Mechanical Catalog Cuts of Equipment_100PCT.pdf

PDF 9 MB Posted

Attached to
Y1AZ--674A4-21-703 EHRM Training and Admin Support Space Construction Waco Texas (VA-22-00050768)
Solicitation number
36C77622B0045
Issued by

About this file

This solicitation is for construction services to support EHRM training and administrative space at the VA Medical Center in Waco, Texas. Key details include construction of new spaces for approximately 12,000 square feet to include classrooms, conference rooms, and administrative offices. The solicitation was issued by the Department of Veterans Affairs with responses due by January 2022 and work expected to be completed by February 2023. Pricing will be fixed price with payment terms of net 30. The opportunity is unrestricted with no set aside designations.

View the file

Other files

File Type Posted
36C77622B0045 0002.docx DOCX document
Attachment 2 - 18708 Asbestos Re-inspection Final Report Bldg 12.pdf PDF
36C77622B0045 0001.docx DOCX document
Attachment 3 - Site Visit Sign-In Sheet 36C77622B0045 EHRM Waco.pdf PDF
Attachment 1 - Technical Questions - Waco EHRM Training Admin Support Space.docx DOCX document
Attachment 9 - LAND.pdf PDF
Attachment 11 - ELEC.pdf PDF
Attachment 17 - Wage rates revised 6.17.22 - saved 7.7.22.pdf PDF
36C77622B0045.docx DOCX document
Attachment 4 - CIVIL.pdf PDF
Attachment 18 - VHA Suppl. Contract Rqmnts for Combatting COVID-19 Updated 12-14-2021.pdf PDF
Attachment 5 - COMB_Part1.pdf PDF
Attachment 2 - Sheet ES101 revised for EHRM.pdf PDF
Attachment 20 - Site Visit Map Denoting B221 location as Orange color.pdf PDF
Attachment 3 - ARCH.pdf PDF
Attachment 6 - COMB_Part2.pdf PDF
Attachment 19 - Contractor Safety and Environmental Record Evaluation Form.docx DOCX document
Attachment 16 - VA Notice of Limitations on Subcontracting-Certificate of Compliance.docx DOCX document
Attachment 12 - PLUB.pdf PDF
Attachment 8 - GEN.pdf PDF
Attachment 10 - Lighting Manufacturers Information.pdf PDF
Attachment 1 - 674A4-21-703 100PCT SPECIFICATIONS - COMBINED.pdf PDF
Attachment 15 - Mechanical Calculations.pdf PDF
Attachment 13 - MECH.pdf PDF
Attachment 7 - FIRE.pdf PDF
Show all 25

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Doris Miller Department of Veterans Affairs VA Medical Center

Waco, Texas

Project Number 674A4-22-703

(VEG 20.15)

EHRM TRAINING AND ADMIN SPACE

SUPPORT

100% Construction Documents

MECHANICAL CATALOG CUTS OF EQUIPMENT

February 10, 2022

750 W. HAMPDEN AVE. #300

ENGLEWOOD, CO 80110

Ph (720) 550-6307

JobName:TDI-3-20-315CutSheet
Tag:MK-1
Quantity:1
PrintedDate:February18,2021
Model:TDI-3-20-315
TubeAxialDirectDriveInlineFan
StandardConstructionFeatures:Tubularpaintedsteelhousing.Propeller,castaluminum.Directdriven
motorintheairstream.

Fan Configuration

Drive type Direct

Performance

RequestedVolume(CFM) 3,130
ActualVolume(CFM) 3,027
TotalExternalSP(in.wg) 0.47
FanRPM 1,725
OperatingPower(bhp) 0.39
StartupPower(bhp) 0.39
AirStreamTemp(F) 70
Start-upTemp(F) 70
AirDensity(lbs/ft^3) 0.073
Elevation(ft) 570
StaticEfficiency(%) 57
OutletVelocity(ft/min) 1,387

Motor

Size (hp) 1/2 V/C/P 208/60/3

NEC FLA (Amps) 2.4

Fancurve
Brakehorsepowercurve
OperatingPointSP
OperatingBhppoint
Maxsystemcurve
Systemcurve

1,725 FRPM

Sys tem

Volume (CFM) x 100 0 5 10 15 20 25 30 35 40 45 50

St at ic P re ss ur e (in

. w g)

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

Br ak e Ho rs ep ow er (B

HP

0.05

0.1

0.15

0.2

0.25

0.3

0.35

0.4

0.45

ExternalSP 0.5in.wg
DirectDriveRPMAdjustment -0.03in.wg
TotalExternalSP 0.47in.wg

Static Pressure Calculations

Sound Octave Bands (hz) LwA dBA Sones

62.5 125 250 500 1000 2000 4000 8000

Inlet 87 86 87 85 81 77 71 69 87 75 25

GreenheckFanCorporationcertifiesthatthemodelshownhereinislicensedtobear
theAMCASeal.Theratingsshownarebasedontestsandproceduresperformedin
accordancewithAMCAPublication211andcomplywiththerequirementsofthe
AMCACertifiedRatingsProgramTheAMCAcertifiedratingssealappliestoair
performanceratingsonly.PerformancecertifiedisforinstallationtypeD:Ducted
inlet,ductedoutlet.Powerratingdoesnotincludetransmissionlosses.Performance
ratingsdonotincludetheeffectsofappurtenances.

Page 1 of 2 Version 2.8.0, February 2021

JobName:TDI-3-20-315CutSheet
Tag:MK-1
Quantity:1
PrintedDate:February18,2021

Dimensions and Weights

Label Value Description

- 113 Weightw/oaccessories(lbs)
A 26 OverallHeight(in)
B 24 OverallWidth(in)
C 19 OverallLength(in)
- 20.38 InletDiameter(in)
- 20.38 OutletDiameter(in)
*Alldimensionsareininches.
Page2of2 Version2.8.0,February2021

Titus GRD Selection GRD Performance

355RL-SS

Return Grilles and Registers

Features:

Model:

Description:

Neck Shape:

Patttern:

Notes:

Data Notes:

Material: Steel

Terminal Velocity:

Throw Pattern:

Exhaust

Border Type:

1-Surface Mount

-Way

.5 Inch 35 Degree Fixed Defl.

RCT

fpm0.00

Performance

Neck Size: Module Size:

NC:

69 248 426 605 783 963 1142 1320 1499

- - - 23 42 48 54 59

Air Flow, CFM

Velocity FPM:

12x10 14x12

50 179 308 566 696 825 954 1083

0.640.49

0.37

0.26

0.17

0.10

0.05

0.02

0.00

Throw Feet:

Pressure, w.c.:

The results of this program are only an aid to the designer, and are not a substitute for professional design services.

Titus accepts no liability for the adequacy of any resulting design or installation.

All data subject to change without notice.

Printed: 11/18/2020 8:33:47AMVersion:

www.armstrongfluidtechnology.com Page 1 of 2

Submittal

Product: Shell & Tube Model: WS-0602-200E-1-CSSSSNN-20 Project name: undefined Representative:

Location: Phone number:

Date submitted: e-mail:

Engineer: Submitted by:

Process Conditions

Shell Side Tube Side

Fluid steam water

Flow Rate 917.94 lb/hr 67 USgpm

Inlet Temperature 273.98 °F 154 °F

Outlet Temperature 273.98 °F 180 °F

Operating Pressure 30.000 psi 125.00 psi

Density 0.11 lb/ft³ 60.84 lb/ft³

Viscosity 0.01 SSU 0.38 SSU

Specific Heat 0.52 Btu/lb•°F 1.00 Btu/lb•°F

Thermal Conductivity 0.10 Btu/hr•ft•°F 0.40 Btu/hr•ft•°F

Specified Limits

Maximum Velocity 4.00 ft/s 7.50 ft/s

Maximum Pressure Drop Not Specified Not Specified

Fouling Requested None None

Maximum Exchanger Length Not Specified

Required Tube Passes Not Specified

Shell Design Pressure N/A N/A

Performance

Total Surface Area 9.7 ft²

Velocity 0.00 ft/s 4.57 ft/s

Pressure Drop 0.00 psi 0.40 psi

Heat Transfer Coeff. 1,919.00 Btu/hr.ft².°F 1,814.00 Btu/hr.ft².°F

Heat Load 852798.3 Btu/hr

Corrected LMTD 106.00 °F

Overall Heat Transfer Coeff. 875.20 Btu/hr.ft².°F

Total Fouling Used 0.00006294348 hr.ft².°F/Btu

Required Heating Surface 9.2ft² dirty and9.2ft² clean

Design Details Shell Side Tube Side

Design Rating 150 psi at 375 °F 150 psi at 375 °F

Passes 1 2

Inlet Nozzle 1.5 inch NPT F 2 inch NPT F

Outlet Nozzle 1 inch NPT F 2 inch NPT F

Materials - Tubes copper -20ga

Materials - Tubesheets N/A Carbon Steel http://www.armstrongfluidtechnology.com/ www.armstrongfluidtechnology.com Page 2 of 2

Materials - Head Cast Iron

Materials - Shell Carbon Steel

Materials - Baffles Carbon Steel

Materials - Gasket Non-Asbestos Non-Asbestos

Materials - Studs/Nuts Carbon Steel

Shipping/Dry Weight (not including adjustable supports): 132 lb [59.87 kg]

Drawing Number: WS-6-2P-E1-(3)

Exchanger Size: WS-62-2*-1

Design, test, and fabrication in accordance with ASME Code Sect. VIII, Div. 1

Note: When the Manual Select mode for pricing shell & tube heat exchangers and bundles is chosen; the thermal performance is not inputted nor verified and therefore cannot be guaranteed by Armstrong.

Drawing

Note:- Standard model as shown. For models with Adjustable Supports contact factory.

www.armstrongfluidtechnology.com Page 1 of 2

Typical Specifications

Product: Shell & Tube Heat Exchanger Model: WS-0602-200E-1-CSSSSNN-20

Armstrong WS Heat Exchanger Engineering Specification: WS-0602-200E-1-CSSSSNN-20

Tag No: Service: Location:

Supply and install approximately where shown on plans and with the manufacturer's recommendations heat exchanger(s) as follows:

1.TYPE

Shell and tube, single wall tubes, u-bend removable bundle.

2. MATERIALS

Tubes copper -20ga Shell Carbon Steel

Tubesheet Carbon Steel Baffles Carbon Steel

Front Head Cast Iron Studs and Nuts Carbon Steel

Head Gasket Non-Asbestos Shell Gasket Non-Asbestos

Shell side Tubesheet N/A

3. CONSTRUCTION

Each heat exchanger is to be designed, built, and tested in accordance with the ASME Boiler and Pressure Vessel Code, Section VIII, Division 1 and certified with ASME UM certification designator. A manufacturer's data report for pressure vessels, form number U-1 or a manufacturer's certificate of compliance form number U-3 as required by the provisions of the ASME Code rules is to be furnished to the user or designated agent upon request. This form must be signed by a qualified inspector, holding a National Board Commission when required, certifying that construction conforms to the latest ASME Code for pressure vessels for a minimum design metal temperature of 35 F, a tube side working pressure of 150 psi at 375 °F and a shell side working pressure of 150 psi at 375 °F.

4. CAPACITY

To heat 67 USgpm of water in the tubes from 154 °F to 180 °F using 917.94 lb/hr of steam at [273.98 °F].

5. OPERATING CONDITIONS

The tube side velocity shall be no more than 4.57 ft/s. The tubeside pressure drop shall be no more than 0.40 psi. The shell side velocity shall be no more than 0.00 ft/s. The shell side pressure drop shall be no more than 0.00 ft. The maximum bundle length shall be no more than 2 ft. The fouling factor shall be no less than 0.00006294348 hr.ft².°F/Btu. The heat exchanger shall be capable of providing a heat load of no less than 852798.3 Btu/hr. Each heat exchanger shall contain a tube heating surface of no less than 9.7 ft².

6. MANUFACTURER and MODEL

The heat exchanger(s) shall be the Armstrong liquid to liquid model WS-0602-200E-1-CSSSSNN-20.

7. DOCUMENTATION

Each heat exchanger shall be shipped complete with one copy each of the ASME U-1 or U-3 form and the manufacturer's installation and operating instructions.

8. SHIPPING

www.armstrongfluidtechnology.com Page 2 of 2

Each heat exchanger shall be prepared for shipping firmly mounted on a wooden skid. The skid shall be designed so as to prevent damage to the vessel during transport. All vessel connections shall be capped so as to prevent contamination of the tube surfaces.

9. INSTALLATION

Each heat exchanger shall be connected to the proper relief valves, vent and/or vacuum breaker as required.

Performance Curve e-90-STOCK

1.5AAB

Pump Selection Summary Pump Capacity 67 US gpm RPM @ Duty Point 3450 Pump Head 40 ft Impeller Diameter 4 in Control Head 0 ft NPSHr 15.7 Duty Point Pump Efficiency 65.6 % Motor Power 3 hp Pump PLEVv Efficiency 0.0 % Motor Speed 3600 rpm Duty point Power 1.58 bhp Minimum Shutoff Head 63.5 ft Minimum Flow at RPM 14.6 US gpm Fluid Type Water Flow @ BEP 73.1 US gpm Fluid Temperature 180 ºF Weight (approx. - consult rep) 66 lb lbs Floor Space --- ft²

The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office.

Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2015 Johnson Controls, Inc. www.johnsoncontrols.com

M9220-xxx-RK Electric Spring-Return Actuators

Code No. LIT-1900997

Issued November 4, 2015

Description The M9220-xxx-RK Electric Spring-Return Actuators operate with these available power options:

• AC 24 V at 50/60 Hz or DC 24 V (BGx and GGx)

• AC 120 V at 60 Hz (BAx) These direct-mount, bidirectional actuators do not require a damper linkage, and are easily installed on dampers with 3/4 to 1-1/16 in. (19 to 27 mm) round shafts, or 5/8 and 3/4 in. (16, 18, and 19 mm) square shafts using the standard shaft clamp included with the actuator. An optional M9220-601 Coupler Kit is available for 1/2 to 3/4 in. (12 to 19 mm) round shafts, or 3/8 and 1/2 in. (10, 12, and 14 mm) square shafts.

A single M9220 Electric Spring-Return Actuator provides a running and spring-return torque of 177 lb·in (20 N·m). Two or three models mounted in tandem deliver twice or triple the torque. Integral line voltage auxiliary switches are available on the -xxC models to indicate end-stop position or to perform switching functions within the selected rotation range.

Refer to the M9220-xxx-3 Electric Spring-Return Actuators Product Bulletin (LIT-12011057) for important product application information.

Applications The M9220-xxx-RK Electric Spring-Return Actuators provide reliable control of dampers and valves in HVAC systems. The M9220-xxx-RK Actuators are available for use with on/off, floating, and proportional controllers.

Repair Information If the M9220-xxx-RK Electric Actuator fails to operate within its specifications, replace the unit. For a replacement actuator, contact the nearest Johnson Controls® representative.

Features

• Available torques of 177 lb·in (20 N·m) for single actuators, 354 lb·in (40 N·m) for two models, and 531 lb·in (60 N·m) for three models mounted in tandem—offer a selection that is most suitable for the application.

• Reversible mounting design—simplifies installation and enables the actuator to spring return in either direction.

• Electronic stall detection throughout entire rotation range—extends the life of the actuator by deactivating the actuator motor when an overload condition is detected.

• Removable coupler—adapts to a shorter damper shaft.

• Integral 36 in. (0.91 m) halogen-free cables with colored and numbered conductors—simplify field wiring.

• Integral auxiliary switches (xxC models)— provide one fixed and one adjustable switch point with line voltage capability.

• NEMA 2 (IP54) rated aluminum enclosure—protects the internal components of the actuator from dirt and moisture.

• Easy-to-use locking manual override with auto release and crank storage—allows for manual positioning of the actuator hub.

• Integral Connectors for 3/8 in. flexible metal conduit—simplify installation and field wiring.

• Microprocessor-controlled brushless DC motor (-GGx types)—provides constant run-time independent of torque.

Selection Chart Code Number Control Type Auxiliary

Switches Power Requirements

M9220-BAA-RK On/Off None AC 120 V at 60 Hz

M9220-BAC-RK On/Off Two AC 120 V at 60 Hz

M9220-BGA-RK On/Off None AC 24 V at 50/60 Hz or DC 24 V

M9220-BGC-RK On/Off Two AC 24 V at 50/60 Hz or DC 24 V

M9220-GGA-RK Proportional None AC 24 V at 50/60 Hz or DC 24 V

M9220-xxx-RK Electric Spring-Return Actuator

Robert Thornbrugh Highlight M9220-BGA-RK On/Off None AC 24 V at 50/60 Hz or DC 24 V

The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office.

Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2015 Johnson Controls, Inc. www.johnsoncontrols.com

M9220-xxx-RK Electric Spring-Return Actuators (Continued)

Accessories Code Number Description

DMPR-KC0031

1. Furnished with the damper and may be ordered separately

7 in. (178 mm) Blade Pin Extension (without bracket) for Johnson Controls direct-mount damper applications (quantity 5)

M9000-153 Crankarm (quantity 1)

M9000-158 Tandem Mounting Kit used to mount two models of M9220-xxx-RK Proportional Electric Spring-Return Actuators (quantity 1)

M9000-170 Remote Mounting Kit, horizontal. Kit includes mounting bracket, M9000-153 Crankarm, ball joint, and mounting bolts (quantity 1).

M9000-171 Remote Mounting Kit, vertical. Kit includes mounting bracket, M9000-153 Crankarm, ball joint, and mounting bolts (quantity 1).

M9000-200 Commissioning tool that provides a control signal to drive 24 V on/off, floating, proportional, and/or resistive electric actuators (quantity 1)

M9000-320 Weather Shield Enclosure - NEMA 3R Enclosure for protecting a single M9220 Actuator from rain, sleet, or snow (quantity 1)

M9000-400 Jackshaft Linkage Kit. Open-ended design enables clamping onto a jackshaft without requiring access to the ends of the jackshaft (quantity 1).

M9000-604 Replacement Anti-Rotation Bracket Kit (with screws) for M9220-xxx-RK Proportional Electric Spring-Return Actuators (quantity 1)

M9200-100 Threaded Conduit Adapter, 1/2 NPSM, for M9220 and M9208 Series Actuators (quantity 5)

M9220-601 Replacement Coupler Kit (with Locking Clip) for mounting M9220-xxx-RK Proportional Electric Spring-Return Actuators on dampers with 1/2 to 3/4 in. or 12 to 19 mm round shafts, or 3/8 and 1/2 in. or 10, 12, and 14 mm square shafts (quantity 1)

M9220-602 Replacement locking clips for M9220-xxx-RK Proportional Electric Spring-Return Actuators (five per bag)

M9220-603 Adjustable Stop Kit for M9220-xxx-RK Proportional Electric Spring-Return Actuators (quantity 1)

M9220-604 Replacement manual override cranks for M9220-xxx-RK Proportional Electric Spring-Return Actuators (five per bag)

M9220-610 Replacement Shaft Gripper, 10 mm square shaft with locking clip (quantity 1)

M9220-612 Replacement Shaft Gripper, 12 mm square shaft with locking clip (quantity 1)

M9220-614 Replacement Shaft Gripper, 14 mm square shaft with locking clip (quantity 1)

The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office.

Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2015 Johnson Controls, Inc. www.johnsoncontrols.com

Dimensions

M9220-xxx-RK Electric Spring-Return Actuator Dimensions, in. (mm)

A

(102)

10-5/16 (262)

2-3/16 (56)

FI

G

:d m ns 1-3/4 (44)

1/8 (3)

3-3/16 (81)

3/4 (19)

2-3/16 (56)

(25)

(51)

1-19/32 (40)

1-1/16 (27)

1/4 (6.5) Mounting Hole

(6 Locations)

1-19/32 (40)

1-19/32 (40)

6-15/16 (176)

(254)

The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office.

Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2015 Johnson Controls, Inc. www.johnsoncontrols.com

Technical Specifications M9220-xxx-RK Electric Spring-Return Actuators (Part 1 of 2)

Product Codes M9220-Bxx-RK Models: On/Off M9220-GGA-RK Models: Proportional

Power Requirements GGA Models AC 24 V (19.2 to 30 V) at 50/60 Hz: Class 2, 15.5 VA running,

7.7 VA holding position;

DC 24 V (21.6 to 26.4 V): Class 2, 6.7 W running, 2.9 W holding position

BAx Models AC 120 V (AC 102 to 132 V) at 60 Hz: 0.25 A running, 0.13 A holding position

BGx Models AC 24 V (19.2 to 30 V) at 50/60 Hz: Class 2, 24.6 VA running,

7.7 VA holding position;

DC 24 V (21.6 to 26.4 V): Class 2, 17.6 W running, 2.8 W holding position

Transformer Sizing Requirements GGA Models 20 VA minimum per actuator

Bxx Models 25 VA minimum per actuator

Input Signal/Adjustments GGA Models Factory set DC 0 to 10 V, CW rotation with signal increase;

Selectable DC 0 (2) to 10 V or 0 (4) to 20 mA with field furnished 500 Ohm, 0.25 W minimum resistor; switch selectable direct or reverse action with signal increase

Control Input Impedance GGA Models Voltage Input: 200,000 Ohms;

Current Input: 500 Ohms with field furnished 500 Ohm resistor

Feedback Signal GGA Models 0 (2) to 10 VDC for desired rotation range up to 90°;

Corresponds to rotation limits, 1 mA maximum

Auxiliary Switch Rating xxC Models Two single-pole, double-throw (SPDT), double-insulated switches with gold flash contacts:

AC 24 V, 50 VA Pilot Duty;

AC 120 V, 5.8 A Resistive, 1/4 hp, 275 VA Pilot Duty;

AC 240 V, 5.0 A Resistive, 1/4 hp, 275 VA Pilot Duty

Spring Return Direction is selectable with mounting position of actuator:

Side A, actuator face away from damper for CCW Spring Return;

Side B, actuator face away from damper for CW Spring Return

Running and Spring Return Torque 177 lb·in (20 N·m) for a single actuator;

354 lb·in (40 N·m) for two models mounted in tandem 531 lb·in (60 N·m) for three models mounted in tandem

Valid Tandem Combinations Two M9220-Bxx-RK One M9220-GGA-RK master with one or two M9220-GGA-RK slaves

Rotation Range Adjustable from 30 to 90° CW or CCW with optional M9220-603 Adjustable Stop Kit; mechanically limited to 90°

Rotation Time Power On (Running)

GGA Models 150 seconds for 0 to 177 lb·in (0 to 20 N·m) at all operating conditions; independent of load

BGx Models 24 to 57 seconds for 0 to 177 lb·in (0 to 20 N·m) at all operating conditions; 35 seconds nominal at full rated load

Rotation Time Power Off (Spring Returning)

GGA Models 20 seconds for 0 to 177 lb·in (0 to 20 N·m) at room temperature

BGx Models 11 to 15 seconds for 0 to 177 lb·in (0 to 20 N·m) at room temperature;

35 seconds maximum for 0 to 177 lb·in (0 to 20 N·m) at -22°F (-30°C) 130 seconds maximum for 0 to 177 lb·in (0 to 20 N·m) at -40°F (-40°C)

Cycles 60,000 full stroke cycles; 1,500,000 repositions

Audible Noise Rating (AGx, HGx, GGx Models)

Power On (Running) < 40 dBA at 39-13/32 in. (1 m)

Power On (Holding) < 20 dBA at 39-13/32 in. (1 m)

Power Off (Spring Returning)

< 55 dBA at 39-13/32 in. (1 m)

Audible Noise Rating (BGx Models)

Power On (Running) < 66 dBA at 39-13/32 in. (1 m)

Power On (Holding) < 18 dBA at 39-13/32 in. (1 m)

Power Off (Spring Returning)

< 66 dBA at 39-13/32 in. (1 m)

Electrical Connections Actuator (All Models) 3 ft (0.91 m) halogen-free cable with 18 AWG (0.75 mm2) wire leads

Auxiliary Switches (xxC Models)

3 ft (0.91 m) halogen-free cable with 18 AWG (0.75 mm2) wire leads

Conduit Connections Integral connectors for 3/8 in. (10 mm) flexible metal conduit

Mechanical Connections Standard Shaft Clamp Included with Actuator

3/4 to 1-1/16 in. (19 to 27 mm) diameter round shafts, or 5/8 and 3/4 in. (16, 18, and 19 mm) square shafts

Aluminum Enclosure NEMA 2 (IP54) for all mounting orientations

Ambient Conditions Operating -40 to 131°F (-40 to 55°C); 90% RH maximum, noncondensing

Storage -85 to 185°F (-65 to 85°C); 95% RH maximum, noncondensing

Dimensions See Dimensions.

The performance specifications are nominal and conform to acceptable industry standards. For applications at conditions beyond these specifications, consult the local Johnson Controls office.

Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products. © 2015 Johnson Controls, Inc. www.johnsoncontrols.com

Compliance United States UL Listed, CCN XAPX, File E27734; to UL 60730-1A: 2003-08, Ed. 3.1, Automatic Electrical Controls for Household and Similar Use; and UL 60730-2-14: 2002-02, Ed. 1, Part 2, Particular Requirements for Electric Actuators.

(Models: All)

Canada UL Listed, CCN XAPX7, File E27734; to UL 60730-1:02-CAN/CSA:

July 2002, 3rd Ed., Automatic Electrical Controls for Household and Similar Use; and CSA C22.2 No. 24-93 Temperature Indicating and Regulating Equipment (Models: All).

Europe CE Mark – Johnson Controls, Inc. declares that this product is in compliance with the essential requirements and other relevant provisions of the EMC Directive 2004/108/EC and Low Voltage Directive 2006/95/EC.

Australia and New Zealand

C-Tick Mark, Australia/NZ Emissions Compliant (Models: All)

Shipping Weight xGx Models 6.4 lb (2.9 kg)

BAx Models 7.6 lb (3.5 kg)

M9220-xxx-RK Electric Spring-Return Actuators (Part 2 of 2)

ALL STATED SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE OR OBLIGATION. Ruskin® December 2020EME3625-1220/Replaces EME3625-1219

• 46% Free Area.

• AMCA 550 Listed Louver.

• Closely spaced vertical blades prevent the penetration of wind-driven rain, reducing damage and additional operating expenses.

• Published performance ratings based on testing in accordance with AMCA Publication 511.

• Excellent pressure drop performance.

• Aluminum construction for low maintenance and high resistance to corrosion.

• All welded construction.

• Visible mullion construction. Hidden mullions and continuous blade construction are not available.

NOTE:

- Dimensions in inches, parenthesis ( ) indicate millimeters.

- *Units furnished 1/4” (6) smaller than given opening dimensions.

FEATURES

STANDARD CONSTRUCTION

Frame 3” (76) deep, 6063T6 extruded aluminum with .073” (1.9) nominal wall thickness.

Blades 6063T6 extruded aluminum .040” (1) nominal wall thickness. Blades are mounted vertically and spaced approximately 3/4” (19) center to center.

Screen 1/2” x .063” (13 x 1.6) square mesh aluminum bird screen in removable frame. Screen adds approximately 1/2” (13) to louver depth.

Extended Sill .080” (2.0) formed aluminum with end dams.

Finish Mill.

Minimum Size 12”w x 12”h (305 x 305).

Approximate Shipping Weight

5 lbs. per sq. ft. (24 kg/m2)

Maximum Single Section Size

Shall be 48” x 96” (1219 x 2438). Lifting lugs provided on louvers 48” x 72” (1219 x 1829) and larger.

Louvers larger than the maximum factory assembly size will require field assembly of smaller sections.

FRAME CONSTRUCTION

The EME3625 is a 3” deep extruded aluminum louver with closely spaced vertical blades that prevent the penetration of wind-driven rain. This louver is designed with exceptional protection against wind-driven rain under severe conditions.

APPLICATION

AUTHORITY IN AIR CONTROL

EME3625

Wind-Driven Rain Resistant Stationary Louver Extruded Aluminum

VARIATIONS

• Filter racks.

• A variety of bird and insect screens.

• Extended sill.

• Blank off panel.

• Selection of finishes: baked enamel (modified fluoropolymer), epoxy, PVDF, Pearledize 50 & 70, prime coat, clear and color anodize. (Some variation in anodize color consistency is possible).

All variations are available at additional cost.

Consult Ruskin for other special requirements.

3” (76)

A* Varies

Birdscreen

A* x B*

1 1/2” (38)

INTEGRAL FLANGE

A* x B*

Lifting Lug (removable)

STANDARD

A*

B*

ALL STATED SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE OR OBLIGATION. Ruskin® December 2020EME3625-1220/Replaces EME3625-1219

Width – Inches and Meters

Free Area Guide shows free area in ft2 and m2 for various sizes of EME3625.

FREE AREA GUIDE

H ei gh t

In ch es a nd

M et er s

0.30

0.45

0.60

0.75

0.90

1.05

1.20

0.30

0.22 0.02

0.37 0.03

0.52 0.05

0.67 0.06

0.82 0.08

0.97 0.09

1.12 0.10

0.45

0.43 0.04

0.72 0.07

1.00 0.09

1.29 0.12

1.57 0.15

1.86 0.17

2.15 0.20

0.60

0.64 0.06

1.06 0.10

1.48 0.14

1.91 0.18

2.33 0.22

2.75 0.26

3.18 0.30

0.75

0.84 0.08

1.40 0.13

1.96 0.18

2.52 0.23

3.08 0.29

3.64 0.34

4.20 0.39

0.90

1.05 0.10

1.74 0.16

2.44 0.23

3.14 0.29

3.84 0.36

4.54 0.42

5.23 0.49

1.05

1.25 0.12

2.09 0.19

2.92 0.27

3.76 0.35

4.59 0.43

5.43 0.50

6.26 0.58

1.20

1.46 0.14

2.43 0.23

3.40 0.32

4.38 0.41

5.35 0.50

6.32 0.59

7.29 0.68

1.35

1.66 0.15

2.77 0.26

3.88 0.36

4.99 0.46

6.10 0.57

7.21 0..67

8.32 0.77

1.50

1.87 0.17

3.12 0.29

4.36 0.41

5.61 0.52

6.86 0.64

8.11 0.75

9.35 0.87

1.65

2.08 0.19

3.46 0.32

4.85 0.45

6.23 0.58

7.61 0.71

9.00 0.84

10.38 0.97

1.00

2.28 0.21

3.80 0.35

5.33 0.50

6.85 0.64

8.37 0.70

9.89 0.92

11.41 1.06

1.95

2.49 0.23

4.15 0.39

5.81 0.54

7.47 0.69

9.12 0.85

10.78 1.00

12.44 1.16

2.10

2.69 0.25

4.49 0.42

6.29 0.58

8.08 0.75

9.88 0.92

11.68 1.09

13.47 1.25

2.25

2.90 0.27

4.83 0.45

6.77 0.63

8.70 0.81

10.64 0.99

12.57 1.17

14.50 1.35

2.40

3.11 0.29

5.18 0.48

7.25 0.67

9.32 0.87

11.39 1.06

13.46 1.25

15.53 1.44

ALL STATED SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE OR OBLIGATION. Ruskin® December 2020EME3625-1220/Replaces EME3625-1219

PRESSURE DROP

St at ic P re ss ur e

D ro p in

In ch es w

.g

Pa

Air Velocity in feet (meters) per minute through Free Area

Pressure Drop testing performed on 48” x 48” (1219 x 1219) unit.

Ratings do not include the effect of a bird screen.

(248.9)

(3 0)

(6 1)

(9 1)

(1

(1

(1

(2

(2

(2

(3

(6

(9

(1

9)

(1

4)

(1

9)

(2

4)

(2

8)

(2

3)

(3

8)

,0

1.00 .90 .80 .70 .60

.50

.40

.30

.20

.10

.09

.08

.07

.06

.05

.04

.03

.02

.01

(224.01) (199.12) (174.23) (149.34)

(124.45)

(99.56)

(74.67)

(49.78)

(24.89) (22.40) (19.91) (17.42)

(14.93)

(12.45)

(9.96)

(7.47)

(4.98)

(2.49)

EXHAUST

INTAKE

Ruskin Company certifies that the EME3625D shown herein is approved to bear the AMCA Listing Label. The ratings shown are based on tests and procedures performed in accordance with AMCA Publications and comply with the requirements of the AMCA Listing Label Program.

The AMCA Listing Label applies to High Velocity Rain Resistant Louvers.

PERFORMANCE DATA

ALL STATED SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE OR OBLIGATION. Ruskin® December 2020EME3625-1220/Replaces EME3625-1219

Test size is: 39” x 39” (.99 x .99) core area, 41” x 41” (1.04 x 1.04) nominal. Free Area of test louver is 5.18 ft.2 (.48m2).

WIND-DRIVEN RAIN PERFORMANCE

Wind Velocity mph (kph)

Rainfall Rate In./hr. (mm/hr.)

Core Velocity FPM (m/s1)

Airflow cfm (m3/min)

Free Area Velocity2 fpm (m/sec.)

Effectiveness Ratio Class3, 4

Discharge Loss Class5 Intake

29 (46.4) 3 (76) 967 (5) 10,412 (294) 2,010 (10.0) 100% A 1

50 (80.5) 8 (203) 974 (5) 10,484 (296) 2,024 (10.1) 100% A 1

NOTE:

1. Core area is the open area of the louver face (face area less louver frames).

Core Velocity is the airflow velocity through the Core Area of the louver. 5 m/s is the maximum core velocity utilized in this test.

2. Free Area of test size is calculated per AMCA standard 500-L.

3. Wind-Driven Rain Penetration Classes:

Class Effectiveness A 1 to .99 B 0.989 to 0.95 C 0.949 to 0.80 D Below 0.8

4. The EME3625 provides class A performance at all velocities up to and including 5 m/s core velocity.

5. Discharge Loss Coefficient is calculated by dividing a louvers’ actual airflow rate

vs. a theoretical airflow for the opening. It provides an indication of the louvers’ airflow characteristics.

Discharge Loss Classes:

Class Discharge Loss Coefficient 1 0.4 and above 2 0.3 to 0.399 3 0.2 to 0.299 4 0.199 and below

(The higher the coefficient, the less resistance to airflow.)

Ruskin Company certifies that the louver shown herein is licensed to bear the AMCA Seal. The ratings shown are based on tests and procedures performed in accordance with AMCA Publication 511 and comply with the requirements of the AMCA Certified Ratings Program. The AMCA Certified Ratings Seal applies to air performance ratings and wind driven rain ratings only.

SUGGESTED SPECIFICATION

Furnish and install louvers as hereinafter specified where shown on plans or as described in schedules. Louvers shall possess stationary vertical blades designed to prevent the penetration of wind-driven rain. Louver blades shall be contained within a 3” (76) frame. Louver components (heads, jambs, sill and blades) shall be factory assembled by the louver manufacturer. Louver sizes too large for shipping shall be built up by the contractor from factory assembled louver sections to provide overall sizes required. Louver design shall limit single section sizes to 48” x 96” (1219 x 2438) and shall withstand a wind load of 30 lbs. per sq. ft. (1.44 kPa) (equivalent of a 110 mph wind [177 kph] - specifier may substitute any loading required).

Louvers shall be Ruskin Model EME3625 extruded 6063T6 aluminum alloy construction as follows:

Frame: .073” (1.9) wall thickness, caulking surfaces provided.

Blades: .040” (1) wall thickness, installed vertically on approximately .75” (19) centers.

Screen: .050” x .063” (13 x 1.6) square mesh aluminum bird screen in removable frame.

Finish: Select finish specification from Ruskin Finishes Brochure.

AUTHORITY IN AIR CONTROL

3900 Doctor Greaves Road Grandview, MO 64030 Website: www.ruskin.com Phone: (816) 761-7476

Document Title

Paint Finishes and Color Guide

Limited Warranty Document

LINKS TO IMPORTANT DOCUMENTS

https://www.ruskin.com/doc/Id/6554 https://www.ruskin.com/doc/id/6710

JobName:TDI-3-24-316CutSheet
Tag:MK-1
Quantity:1
PrintedDate:February12,2021
Model:TDI-3-24-316
TubeAxialDirectDriveInlineFan
StandardConstructionFeatures:Tubularpaintedsteelhousing.Propeller,castaluminum.Directdriven
motorintheairstream.

Fan Configuration

Drive type Direct

Performance

RequestedVolume(CFM) 5,548
ActualVolume(CFM) 5,548
TotalExternalSP(in.wg) 0.5
Operatingfrequency(Hz) 59
FanRPM 1,702
OperatingPower(bhp) 0.85

Startup Power (bhp) 0.88

FEI 1.77

AirStreamTemp(F) 70
Start-upTemp(F) 70
AirDensity(lbs/ft^3) 0.073
Elevation(ft) 567
StaticEfficiency(%) 51
OutletVelocity(ft/min) 1,766

Motor

Size (hp) 1 V/C/P 208/60/3

NEC FLA (Amps) 4.6

Fancurve
Brakehorsepowercurve
OperatingPointSP
OperatingBhppoint
Maxsystemcurve
Systemcurve

1,702 FRPM

Syst em

Volume (CFM) x 1000 0 1 2 3 4 5 6 7 8 9

St at ic P re ss ur e (in

. w g)

0.2

0.4

0.6

0.8

1.2

Br ak e Ho rs ep ow er (B

HP

0.2

0.4

0.6

0.8

1.2

Sound Octave Bands (hz) LwA dBA Sones

62.5 125 250 500 1000 2000 4000 8000

Inlet 92 91 92 90 86 82 77 75 92 80 33

GreenheckFanCorporationcertifiesthatthemodelshownhereinislicensedtobear
theAMCASeal.Theratingsshownarebasedontestsandproceduresperformedin
accordancewithAMCAPublication211andcomplywiththerequirementsofthe
AMCACertifiedRatingsProgramTheAMCAcertifiedratingssealappliestoair
performanceandFEIratingsonly.PerformancecertifiedisforinstallationtypeD:
Ductedinlet,ductedoutlet.Powerratingdoesnotincludetransmission
losses.Performanceratingsdonotincludetheeffectsofappurtenances.TheAMCA
licensedairand/orsoundperformancedatahasbeenmodifiedforinstallation,
appurtenances,etc.notincludedinthecertifieddata.Themodifiedperformanceis
notAMCAlicensedbutisprovidedtoaidinselectionandapplicationsofthe

product.

Page 1 of 2 Version 2.8.0, February 2021

JobName:TDI-3-24-316CutSheet
Tag:MK-1
Quantity:1
PrintedDate:February12,2021
Model:TDI-3-24-316
TubeAxialDirectDriveInlineFan
StandardConstructionFeatures:Tubularpaintedsteelhousing.Propeller,castaluminum.Directdriven
motorintheairstream.

Fan Configuration

Drive type Direct

Performance

RequestedVolume(CFM) 5,600
ActualVolume(CFM) 5,600
TotalExternalSP(in.wg) 0.5
Operatingfrequency(Hz) 59
FanRPM 1,710
OperatingPower(bhp) 0.86

Startup Power (bhp) 0.88

FEI 1.76

AirStreamTemp(F) 70
Start-upTemp(F) 70
AirDensity(lbs/ft^3) 0.073
Elevation(ft) 567
StaticEfficiency(%) 51
OutletVelocity(ft/min) 1,782

Motor

Size (hp) 1 V/C/P 208/60/3

NEC FLA (Amps) 4.6

Fancurve
Brakehorsepowercurve
OperatingPointSP
OperatingBhppoint
Maxsystemcurve
Systemcurve

1,710 FRPM

Syste m

Volume (CFM) x 1000 0 1 2 3 4 5 6 7 8 9

St at ic P re ss ur e (in

. w g)

0.2

0.4

0.6

0.8

1.2

Br ak e Ho rs ep ow er (B

HP

0.2

0.4

0.6

0.8

1.2

Sound Octave Bands (hz) LwA dBA Sones

62.5 125 250 500 1000 2000 4000 8000

Inlet 92 91 92 90 86 82 77 75 92 80 33

GreenheckFanCorporationcertifiesthatthemodelshownhereinislicensedtobear
theAMCASeal.Theratingsshownarebasedontestsandproceduresperformedin
accordancewithAMCAPublication211andcomplywiththerequirementsofthe
AMCACertifiedRatingsProgramTheAMCAcertifiedratingssealappliestoair
performanceandFEIratingsonly.PerformancecertifiedisforinstallationtypeD:
Ductedinlet,ductedoutlet.Powerratingdoesnotincludetransmission
losses.Performanceratingsdonotincludetheeffectsofappurtenances.TheAMCA
licensedairand/orsoundperformancedatahasbeenmodifiedforinstallation,
appurtenances,etc.notincludedinthecertifieddata.Themodifiedperformanceis
notAMCAlicensedbutisprovidedtoaidinselectionandapplicationsofthe

Page 1 of 2 Version 2.8.0, February 2021

JobName:TDI-3-24-316CutSheet
Tag:MK-1
Quantity:1
PrintedDate:February12,2021
Model:TDI-3-24-316
TubeAxialDirectDriveInlineFan
StandardConstructionFeatures:Tubularpaintedsteelhousing.Propeller,castaluminum.Directdriven
motorintheairstream.

Fan Configuration

Drive type Direct

Performance

RequestedVolume(CFM) 5,680
ActualVolume(CFM) 5,680
TotalExternalSP(in.wg) 0.5
FanRPM 1,722
OperatingPower(bhp) 0.88
StartupPower(bhp) 0.89

FEI 1.75

AirStreamTemp(F) 70
Start-upTemp(F) 70
AirDensity(lbs/ft^3) 0.073
Elevation(ft) 567
StaticEfficiency(%) 51
OutletVelocity(ft/min) 1,808

Motor

Size (hp) 1 V/C/P 208/60/3

NEC FLA (Amps) 4.6

Fancurve
Brakehorsepowercurve
OperatingPointSP
OperatingBhppoint
Maxsystemcurve
Systemcurve

1,722 FRPM

Don
oto

per ate in sh ad ed ar ea

Sy ste m

Volume (CFM) x 1000 0 1 2 3 4 5 6 7 8 9

St at ic P re ss ur e (in

. w g)

0.2

0.4

0.6

0.8

1.2

Br ak e Ho rs ep ow er (B

HP

0.2

0.4

0.6

0.8

1.2

Sound Octave Bands (hz) LwA dBA Sones

62.5 125 250 500 1000 2000 4000 8000

Inlet 92 91 92 90 86 82 77 75 92 80 33

GreenheckFanCorporationcertifiesthatthemodelshownhereinislicensedtobear
theAMCASeal.Theratingsshownarebasedontestsandproceduresperformedin
accordancewithAMCAPublication211andcomplywiththerequirementsofthe
AMCACertifiedRatingsProgramTheAMCAcertifiedratingssealappliestoair
performanceandFEIratingsonly.PerformancecertifiedisforinstallationtypeD:
Ductedinlet,ductedoutlet.Powerratingdoesnotincludetransmission
losses.Performanceratingsdonotincludetheeffectsofappurtenances.TheAMCA
licensedairand/orsoundperformancedatahasbeenmodifiedforinstallation,
appurtenances,etc.notincludedinthecertifieddata.Themodifiedperformanceis
notAMCAlicensedbutisprovidedtoaidinselectionandapplicationsofthe

Page 1 of 2 Version 2.8.0, February 2021

JobName:TDI-3-24-316CutSheet
Tag:MK-1
Quantity:1
PrintedDate:February12,2021

Dimensions and Weights

Label Value Description

- 123 Weightw/oaccessories(lbs)
A 30 OverallHeight(in)
B 28 OverallWidth(in)
C 19 OverallLength(in)
- 24.38 InletDiameter(in)
- 24.38 OutletDiameter(in)
*Alldimensionsareininches.
Page2of2 Version2.8.0,February2021

355RL-SS

Return Grilles and Registers

Features:

Model:

Description:

Neck Shape:

Patttern:

Notes:

Data Notes:

Material: Steel

Terminal Velocity:

Throw Pattern:

Exhaust

Border Type:

1-Surface Mount

-Way

.5 Inch 35 Degree Fixed Defl.

RCT

fpm0.00

Performance

Neck Size: Module Size:

NC:

71 255 439 623 806 992 1176 1359 1543

- - 11 24 43 49 55 60

Air Flow, CFM

Velocity FPM:

20x6 22x8

50 179 308 566 696 825 954 1083

0.680.52

0.39

0.28

0.18

0.11

0.05

0.02

0.00

Throw Feet:

Pressure, w.c.:

The results of this program are only an aid to the designer, and are not a substitute for professional design services.

Titus accepts no liability for the adequacy of any resulting design or installation.

Printed: 11/12/2020 12:40:38PMVersion:

JobName:SE1-12-432-VGCutSheet
Tag:MK-1
Quantity:1
PrintedDate:November19,2020
Model:SE1-12-432-VG
SidewallDirectDriveExhaustFan
StandardConstructionFeatures:Galvanizedsteelpanelwithfabricatedgalvanizedsteeldriveframe
(optionalwallhousingorwallcollar).Propeller,aluminum.Directdrivenmotorintheairstream.

Fan Configuration

Drive type Direct

Performance

RequestedVolume(CFM) 571
ActualVolume(CFM) 571
TotalExternalSP(in.wg) 0.2
FanRPM 1,102
OperatingPower(bhp) 0.06
StartupPower(bhp) 0.06
AirStreamTemp(F) 70
Start-upTemp(F) 70
AirDensity(lbs/ft^3) 0.074
Elevation(ft) 471
StaticEfficiency(%) 33
OutletVelocity(ft/min) 696

Motor

Size (hp) 1/4 V/C/P 208/60/1

NEC FLA (Amps) 2.3

Fancurve
Brakehorsepowercurve
OperatingPointSP
OperatingBhppoint
Maxsystemcurve
Systemcurve

1,102 FRP

Do n ot o pe ra te

in
s

ha de d ar ea

Sy ste m

Volume (CFM) x 100 0 2 4 6 8 10 12

St at ic P re ss ur e (in . w g)

0.05

0.1

0.15

0.2

0.25

0.3

0.35

0.4

0.45

Br ak e Ho rs ep ow er (B

HP

0.01

0.02

0.03

0.04

0.05

0.06

0.07

0.08

0.09

Sound Octave Bands (hz) LwA dBA Sones

62.5 125 250 500 1000 2000 4000 8000

Inlet 74 69 51 49 51 49 43 36 58 46 4.6

GreenheckFanCorporationcertifiesthatthemodelshownhereinislicensedtobear
theAMCASeal.Theratingsshownarebasedontestsandproceduresperformedin
accordancewithAMCAPublication211andAMCAPublication311andcomplywith
therequirementsoftheAMCACertifiedRatingsProgram.TheAMCAcertifiedratings
sealappliestosoundandairperformanceratingsonly.Performancecertifiedisfor
installationtypeA:Freeinlet,freeoutlet.Powerratingdoesnotincludetransmission
losses.Performanceratingsdonotincludetheeffectsofappurtenances.Thesound
ratingsshownareloudnessvaluesinhemisphericalsonesat1.5m(5ft)ina
hemisphericalfreefieldcalculatedperANSI/AMCAStandard301.Valuesshownare
forInstallationTypeA:freeinlethemisphericalsonelevels.dBAlevelsarenot
licensedbyAMCAInternational.TheAMCACertifiedRatingsSealforSoundapplies
toinletsoneratingsonly.

Page 1 of 2 Version 2.7.1, November 2020

JobName:SE1-12-432-VGCutSheet
Tag:MK-1
Quantity:1
PrintedDate:November19,2020

Dimensions and Weights

Label Value Description

- 27 Weightw/oaccessories(lbs)
A 18 OverallHeight(in)
B 18 OverallWidth(in)
C 11 OverallLength(in)
- 14 WallOpeningWidth(in)
- 14 WallOpeningHeight(in)
*Alldimensionsareininches.
Page2of2 Version2.7.1,November2020

PAS

24x24 Perforated Clg. Diffuser

Features:

Model:

Description:

Neck Shape:

Patttern:

Notes:

Data Notes:

Material: Steel

Terminal Velocity:

Throw Pattern:

4 Way, Horiz

Border Type:

1-Surface Mount

-Way

Adj. Discharge Pattern

RND

fpm50.00

Performance

Neck Size: Module Size:

NC:

296 398 495 597 694 796 898 995 1097

- - - 16 25 29 32 35

Air Flow, CFM

Velocity FPM:

6 24x24

58 78 97 136 156 176 195 215

0.210.17

0.14

0.11

0.09

0.06

0.04

0.03

0.02

Throw Feet:

Pressure, w.c.:

0.

1.

1.

1.

1.

1.

1.

1.

1.

1.

1.

2.

2.

2.

2.

2.

2.

A D

P I

ADPI Information

Room Load

Throw Ratio

The results of this program are only an aid to the designer, and are not a substitute for professional design services.

Titus accepts no liability for the adequacy of any resulting design or installation.

Printed: 11/12/2020 12:44:32PMVersion:

PAS

24x24 Perforated Clg. Diffuser

Features:

Model:

Description:

Neck Shape:

Patttern:

Notes:

Data Notes:

Material: Steel

Terminal Velocity:

Throw Pattern:

4 Way, Horiz

Border Type:

1-Surface Mount

-Way

Adj. Discharge Pattern

RND

fpm50.00

Performance

Neck Size: Module Size:

NC:

298 398 499 599 699 799 897 997 1097

- - 16 22 31 35 38 41

Air Flow, CFM

Velocity FPM:

8 24x24

104 139 174 244 279 313 348 383

0.240.20

0.16

0.13

0.10

0.07

0.05

0.03

0.02

Throw Feet:

Pressure, w.c.:

0.

1.

1.

1.

1.

1.

1.

1.

1.

1.

1.

2.

2.

2.

2.

2.

2.

A D

P I

ADPI Information

Room Load

Throw Ratio

The results of this program are only an aid to the designer, and are not a substitute for professional design services.

Titus accepts no liability for the adequacy of any resulting design or installation.

Printed: 11/12/2020 12:45:33PMVersion:

PAS

24x24 Perforated Clg. Diffuser

Features:

Model:

Description:

Neck Shape:

Patttern:

Notes:

Data Notes:

Material: Steel

Terminal Velocity:

Throw Pattern:

4 Way, Horiz

Border Type:

1-Surface Mount

-Way

Adj. Discharge Pattern

RND

fpm50.00

Performance

Neck Size: Module Size:

NC:

299 400 499 600 699 800 899 1000 1099

- 14 21 27 36 39 43 46

Air Flow, CFM

Velocity FPM:

10 24x24

163 218 272 381 436 490 545 599

0.270.22

0.18

0.14

0.11

0.08

0.06

0.04

0.02

Throw Feet:

Pressure, w.c.:

0.

1.

1.

1.

1.

1.

1.

1.

1.

1.

1.

2.

2.

2.

2.

2.

2.

A D

P I

ADPI Information

Room Load

Throw Ratio

The results of this program are only an aid to the designer, and are not a substitute for professional design services.

Titus accepts no liability for the adequacy of any resulting design or installation.

Printed: 11/12/2020 12:46:25PMVersion:

PAS

24x24 Perforated Clg. Diffuser

Features:

Model:

Description:

Neck Shape:

Patttern:

Notes:

Data Notes:

Material: Steel

Terminal Velocity:

Throw Pattern:

4 Way, Horiz

Border Type:

1-Surface Mount

-Way

Adj. Discharge Pattern

RND

fpm50.00

Performance

Neck Size: Module Size:

NC:

299 400 499 600 699 800 899 1000 1099

- 18 25 30 40 43 47 50

Air Flow, CFM

Velocity FPM:

12 24x24

235 314 392 549 628 706 785 863

0.430.35

0.29

0.23

0.17

0.13

0.09

0.06

0.03

Throw Feet:

Pressure, w.c.:

0.

1.

1.

1.

1.

1.

1.

1.

1.

1.

1.

2.

2.

2.

2.

2.

2.

A D

P I

ADPI Information

Room Load

Throw Ratio

The results of this program are only an aid to the designer, and are not a substitute for professional design services.

Titus accepts no liability for the adequacy of any resulting design or installation.

Printed: 11/12/2020 12:46:44PMVersion:

PAS

12x12 Perforated Clg. Diffuser

Features:

Model:

Description:

Neck Shape:

Patttern:

Notes:

Data Notes:

Material:

Steel

Terminal Velocity:

Throw Pattern:

4 Way, Horiz

Border Type:

1-Surface Mount

-Way

Adj. Discharge Pattern

RCT

fpm 50.00

Performance

Neck Size: Module Size:

NC:

300 400 500 600 700 800 900 1000 1100

- - 13 19 28 31 35 38

Air Flow, CFM

Velocity FPM:

6x6 12x12

75 100 125 175 200 225 250 275

0.260.21

0.17

0.14

0.10

0.08

0.05

0.03

0.02

Throw Feet:

Pressure, w.c.:

ADPI Information

Room Load

Throw Ratio

The results of this program are only an aid to the designer, and are not a substitute for professional design services.

Titus accepts no liability for the adequacy of any resulting design or installation.

All data subject to change without notice.

Printed:

3/29/2021 11:26:00AM

Version:

Project: Tag: AHU-1

General

Model: TBM-H Horizontal Indoor Air-Handling Unit

Unit Size: 12 Total FLA: 14.20

Airflow (CFM): 5690 MCA: 17.75

Heat Airflow (CFM): 3090 MSCP: 30.00

OA (CFM): 1707 Fan Watts: 3211

TSP (in.wg): 2.64 Fan Type: FC

ESP (in.wg): 2 Static Eff: 0.64

Motor V/P/Hz 208/3/60 Filter Type: 2" 30% Pleated (MERV 8)

Motor HP: 5 Filter PD (in.wg): 0.22

Fan BHP: 3.68 Fan Size: 18-13-1

Fan RPM: 916 Weight:* 960

Motor FLA: 14.20 Fan Arr: Fan Arr. 2 (Upblast Front)

Titus TEAMS Selection Results

Project Location: Ship Cycle: Standard Shipment

User: Coil Version: 7.01d

Altitude: 470 ft Selection Date: 3/18/2021 8:55:30 AM

File: 20.15 Waco, TX.tw2 Configuration: MRM-FCM

*Weight does not include accessories.

Weights are calculated using Double Wall unit casing and coil wet weights (100% water).

If selected, Base Rail weight is added after pricing is complete.

Chilled Water Coil

EAT DB/WB (°F): 101.0/75.0

LAT DB/WB (°F): 61.3/57.7

Total Capacity (MBH): 321.5

Sensible Capacity (MBH): 231.6

EWT/LWT (°F): 45.0/55.0

Fluid Flow (gpm): 63.90

Fluid PD (ft.wg): 13.58

Fluid Velocity (fps): 5.50

Air PD (in.wg): 0.39

Rows: 4

FPI: 14

Circuits: 20

Tube Wall (in.):

Cond Conn (in.): 1.5

Fluid Type: Water

Pct Glycol: 0.00

Hot Water Coil

EAT DB (°F): 25.0

LAT DB (°F): 76.3

Total Capacity (MBH): 183.8

EWT/LWT (°F): 180.0/160.0

Coil Face Velocity (fpm): 450

Fluid Flow (gpm): 18.90

Fluid PD (ft.wg): 4.10

Fluid Velocity (fps): 4.10

Air PD (in.wg): 0.03

Rows: 1

FPI: 14

Circuits: 7

Tube Wall (in.):

Suction Conn (in.): 1.25

Fluid Type: Water

Pct Glycol: 0.00

Page:19:32 AMPrinted: 3/18/2021 :

The results of this program are only an aid to the designer, and are not a substitute for professional design services.

Titus accepts no liability for the adequacy of any resulting design or installation.

Notes:

Fan Size: 18-13-1

Project: Tag: AHU-1

Titus TEAMS Selection Results

Page:29:32 AMPrinted: 3/18/2021 :

The results of this program are only an aid to the designer, and are not a substitute for professional design services.

Project: Tag: AHU-2

Model: TBM-H Horizontal Indoor Air-Handling Unit

Unit Size: 12 Total FLA: 14.20

Airflow (CFM): 5787 MCA: 17.75

Heat Airflow (CFM): 2895 MSCP: 30.00

OA (CFM): 1736 Fan Watts: 3289

TSP (in.wg): 2.66 Fan Type: FC

ESP (in.wg): 2 Static Eff: 0.64

Motor V/P/Hz 208/3/60 Filter Type: 2" 30% Pleated (MERV 8)

Motor HP: 5 Filter PD (in.wg): 0.22

Fan BHP: 3.77 Fan Size: 18-13-1

Fan RPM: 918 Weight:* 960

Motor FLA: 14.20 Fan Arr: Fan Arr. 2 (Upblast Front)

Titus TEAMS Selection Results

Project Location: Ship Cycle: Standard Shipment

User: Coil Version: 7.01d

Altitude: 470 ft Selection Date: 3/18/2021 9:26:43 AM

File: 20.15 Waco, TX.tw2 Configuration: MRM-FCM

*Weight does not include accessories.

Weights are calculated using Double Wall unit casing and coil wet weights (100% water).

If selected, Base Rail weight is added after pricing is complete.

Chilled Water Coil

EAT DB/WB (°F): 101.0/75.0

LAT DB/WB (°F): 61.4/57.7

Total Capacity (MBH): 325.8

Sensible Capacity (MBH): 234.8

EWT/LWT (°F): 45.0/54.9

Fluid Flow (gpm): 65.30

Fluid PD (ft.wg): 14.17

Fluid Velocity (fps): 5.60

Air PD (in.wg): 0.40

Rows: 4

FPI: 14

Circuits: 20

Tube Wall (in.):

Cond Conn (in.): 1.5

Fluid Type: Water

Pct Glycol: 0.00

Hot Water Coil

EAT DB (°F): 25.0

LAT DB (°F): 77.8

Total Capacity (MBH): 177.3

EWT/LWT (°F): 180.0/160.1

Coil Face Velocity (fpm): 457

Fluid Flow (gpm): 18.30

Fluid PD (ft.wg): 3.87

Fluid Velocity (fps): 3.90

Air PD (in.wg): 0.03

Rows: 1

FPI: 14

Circuits: 7

Tube Wall (in.):

Suction Conn (in.): 1.25

Fluid Type: Water

Pct Glycol: 0.00

Page:39:32 AMPrinted: 3/18/2021 :

The results of this program are only an aid to the designer, and are not a substitute for professional design services.

Project: Tag: AHU-2

Titus TEAMS Selection Results

Page:49:32 AMPrinted: 3/18/2021 :

The results of this program are only an aid to the designer, and are not a substitute for professional design services.

Project: Tag: AHU-3

Model: TBM-H Horizontal Indoor Air-Handling Unit

Unit Size: 12 Total FLA: 14.20

Airflow (CFM): 5998 MCA: 17.75

Heat Airflow (CFM): 2732 MSCP: 30.00

OA (CFM): 1800 Fan Watts: 3481

TSP (in.wg): 2.68 Fan Type: FC

ESP (in.wg): 2 Static Eff: 0.63

Motor V/P/Hz 208/3/60 Filter Type: 2" 30% Pleated (MERV 8)

Motor HP: 5 Filter PD (in.wg): 0.24

Fan BHP: 3.99 Fan Size: 18-13-1

Fan RPM: 922 Weight:* 960

Motor FLA: 14.20 Fan Arr: Fan Arr. 2 (Upblast Front)

Titus TEAMS Selection Results

Project Location: Ship Cycle: Standard Shipment

User: Coil Version: 7.01d

Altitude: 470 ft Selection Date: 3/18/2021 9:30:17 AM

File: 20.15 Waco, TX.tw2 Configuration: MRM-FCM

*Weight does not include accessories.

Weights are calculated using Double Wall unit casing and coil wet weights (100% water).

If selected, Base Rail weight is added after pricing is complete.

Chilled Water Coil

EAT DB/WB (°F): 101.0/75.0

LAT DB/WB (°F): 61.8/58.0

Total Capacity (MBH): 333.8

Sensible Capacity (MBH): 241.0

EWT/LWT (°F): 45.0/55.0

Fluid Flow (gpm): 66.80

Fluid PD (ft.wg): 14.77

Fluid Velocity (fps): 5.70

Air PD (in.wg): 0.42

Rows: 4

FPI: 14

Circuits: 20

Tube Wall (in.):

Cond Conn (in.): 1.5

Fluid Type: Water

Pct Glycol: 0.00

Hot Water Coil

EAT DB (°F): 25.0

LAT DB (°F): 79.1

Total Capacity (MBH): 171.5

EWT/LWT (°F): 180.0/160.0

Coil Face Velocity (fpm): 474

Fluid Flow (gpm): 17.60

Fluid PD (ft.wg): 3.58

Fluid Velocity (fps): 3.80

Air PD (in.wg): 0.02

Rows: 1

FPI: 14

Circuits: 7

Tube Wall (in.):

Suction Conn (in.): 1.25

Fluid Type: Water

Pct Glycol: 0.00

Page:59:32 AMPrinted: 3/18/2021 :

The results of this program are only an aid to the designer, and are not a substitute for professional design services.

Project: Tag: AHU-3

Titus TEAMS Selection Results

Page:69:32 AMPrinted: 3/18/2021 :

The results of this program are only an aid to the designer, and are not a substitute for professional design services.

Project: Tag: FCU-01

Titus TEAMS Fan Coil Unit Selection

Project Location: Riser:

Altitude: 471 Feet Floor:

User:

File: 20.15 Waco, TX.tw2

Room:

Unit Information

Type: Horizontal High Output Length: 30 in

Quantity: 1 Width: 37 in

Model: HHE Height: 19 in

Size: 10 Weight: 135 lbs

Airflow: 1035 CFM

Piping Config: 4-Pipe System Unit Voltage: 208-1-60

OA Airflow: 0 CFM Motor: 1/4 HP - 1.5 Amps

ESP: 0.00 in.wg Motor Type: Standard PSC

Fan Speed: Medium Unit Total Amps: 1.5 Amps

Filter: 1" Standard Unit MCA / MOP: 1.9 / 15

Cooling Coil Performance

Total Capacity

Sensible Capacity

EAT DB /

WB

LAT DB /

WB A.P.D

Face Velocity Rows Fluid Flow EWT LWT WPD

(MBH) (MBH) (F) (F) (in.wg) (fpm) (gpm) (F) (F) (ft.wg)

29.6 23.7 85.0 / 70.0 64.0 / 61.8 0.41 514 3 6.00 45.0 55.1 20.90

Fluid Type: Water - Glycol Percentage: 0%

Heating Coil Performance

Total Capacity EAT DB LAT DB A.P.D

Face Velocity Rows Fluid Flow EWT LWT WPD

(MBH) (F) (F) (in.wg) (fpm) (gpm) (F) (F) (ft.wg)

45.6 50.0 89.4 0.14 514 1 4.60 180.0 160.0 21.00

Fluid Type: Water - Glycol Percentage: 0%

Notes: 1. Selections are based on Titus as Manufacturer.

2. All performance based on tests conducted in accordance with AHRI 440-2008.

3. All airflow, pressure losses and heating performance values have been corrected for altitude.

4. Units of measure: dimensions (in), airflow (cfm), water flow (gpm), air pressure (in wg), water head losses (ft) and temperatures (degF).

5. Water pressure drop (WPd) units is in ft. water.

6. The minimum supply circuit ampacity (MCA) and maximum overcurrent protection (MOP) ratings were calculated in accordance with UL standards based on motor and electric coil full load current ratings.

2:34 PMPrinted: 2/12/2021 :

The results of this program are only an aid to the designer, and are not a substitute for professional design services.

Single Duct Terminal Unit Schedule

Tag AHU Room Model Size CFM Static Pressure NC Levels Hot Water Heat Coil Unit Information

Tag Unit Outlet Max Min Inlet Down Min Rad Dis CFM MBH EAT EWT LAT APd GPM LWT WPd Rows FPI Hand

12-VAV-01 12-AHU-01 Zone - 001 DESV 06 12x8 439 199 1 0.5 0.26 23 24 199 5.2 55 180 78.8 0.11 0.3 145.1 0.08 1-RH 10 RH

12-VAV-02 12-AHU-01 Zone - 002 DESV 04 12x8 204 204 1 0.5 0.11 25 33 204 5.2 55…

This is the start of the file's text. The full file is on GovTribe.

File details come from the government source that posted it. Updated .