Attachment 2 - EHRM Upgrade -Phase 2 Construction Drawings - Part 2.pdf
PDF 16 MB Posted
- Attached to
- Y1DA--578-21-706 EHRM Training and Admin Space Support - Phase 2 - Hines, IL (VA-22-00052631)
- Solicitation number
- 36C77622B0050
About this file
This federal contract opportunity solicitation seeks proposals for the EHRM Training and Admin Space Support - Phase 2 project located in Hines, IL. The Department of Veterans Affairs Technology Acquisition Center Austin is soliciting proposals to provide construction drawings as detailed in Attachment 2 for upgrading and expanding the EHRM facility. Proposals are due by January 31, 2022. The selected contractor will be awarded a firm fixed-price contract to complete the required drawings by June 30, 2022 to support renovations of the training and administration spaces at the Hines VA Medical Center. The scope of work involves preparing architectural, mechanical, electrical and civil drawings to plan for renovations and additions to the existing facility as outlined in the statement of work.
View the file
Other files
Show all 28
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
UP
C D E F G H I J K L M N O P
AE301
/A
I8
FREIGHT
ELEVATOR
OFFICE (1)
SLC-1 ACT-1
P-1B-2
OFFICE (1)
SLC-1 ACT-1
P-1B-2
TR
SLC-1 ETR
ETRETR
OFFICE (1)
SLC-1 ACT-1
P-1B-2
OFFICE (1)
SLC-1 ACT-1
P-1B-2
OFFICE (1)
SLC-1 ACT-1
P-1B-2
BREAK (6)
SLC-1 ACT-1
P-1B-2
CORRIDOR
C1
SLC-1 ACT-1
P-1B-2
/4
/4
110A
LOBBY
SLC-1 ACT-1
P-1B-2
ELEVATOR
E1-A
S2-A
STAIR
S2-A
SLC-1 P-3
P-1B-2
ELEVATOR EQUIPMENT
SLC-1 P-3
P-1-
UNISEX RESTROOM
CT-1 ACT-1
CTW-1CBT-1
UNISEX RESTROOM
CT-1 ACT-1
CTW-1CBT-1
MECHANICAL
ETR P-3
P-1- STAIR
S1-A
SLC-1 P-3
P-1B-2
SHELL SPACE
ELECTRICAL
B
112A
118A
FUTURE RESTROOMS
CPT-3
XXX
XXX
XX
XX
XX
XX
ROOM NUMBER
CEILING FINISH
WALL FINISH
ROOM NAME
FLOOR FINISH
WALL BASE FINISH
FINISH KEY
REFER TO SHEET AI800
F I N I S H N O T E S:
A. SEE ROOM FINISH SCHEDULE SHEET I800.
B. ALL FLOORING MATERIALS TO BE SLIP RESISTANT.
C. ALL FINISHES TO BE CLASS A OR B
02/23/2022
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS
321 4 5 6 7 8 9 10
B
IM
/H in e s E
H R
M T ra in in g
C e n te r/ F
F E
H in e s
T ra in in g C e n te r_
B rv t
/2
/2
:1
:3
P
M
AI801
ARCHITECTURAL FIRST FLOOR
FINISH PLAN
02/23/2022 PH TD
EHRM TRAINING AND ADMIN SPACE
SUPPORT
578-21-706
HINES, IL
BID DOCUMENTS
EDWARD HINES
JR. VAMC
N
1/8" = 1'-0"
FIRST FLOOR FINISH PLAN
KEYPLAN
D R A W I N G N O T E S :
1 LOCKERS - RELOCATED BY VA
2 INFILL WALL WITH TYPE 4A 6" CMU WALL.
3 SEMI RECESSED FIRE EXTINGUISHER CABINET
Revisions: Date:
BID DOCUMENTS 02/23/2022
UPDN
C D E F G H I J K L M N O P
6/AI810
5/AI810
CLASSROOM (17)
CPT-1 ACT-1
P-1B-1
CLASSROOM (17)
CPT-1 ACT-1
P-1B-1
CLASSROOM (17)
CPT-1 ACT-1
P-1B-1
CLASSROOM (17)
CPT-1 ACT-1
P-1B-1
CLASSROOM (17)
CPT-1 ACT-1
P-1B-1
CLASSROOM (17)
CPT-1 ACT-1
P-1B-1
CLASSROOM (17)
CPT-1 ACT-1
P-1B-1
CLASSROOM (17)
CPT-1 ACT-1
P-1B-1
CLASSROOM (17)
CPT-1 ACT-1
P-1B-1
CLASSROOM (17)
CPT-1 ACT-1
P-1B-1
CLASSROOM (17)
CT-1 ACT-1
P-1B-1
CLASSROOM (17)
CPT-1 ACT-1
P-1B-1
CLASSROOM (17)
CPT-1 ACT-1
P-1B-1
CLASSROOM (17)
CPT-1 ACT-1
P-1B-1
CLASSROOM (17)
CPT-1 ACT-1
P-1B-1
CLASSROOM (17)
CPT-1 ACT-1
P-1B-1
CLASSROOM (17)
CPT-1 ACT-1
P-1B-1
CLASSROOM (17)
CPT-1 ACT-1
P-1B-1
TR
SLC-1 P-3
P-1B-2
MECHANICAL ROOM
SLC-1 P-3
P-1B-2
BREAK ROOM
SLC-1 ACT-1
P-5B-2
STAIR
S2-B
SLC-1 P-3
P-1B-2
FREIGHT ELEVATOR
E2
CORRIDOR
C5
CPT-2 P-3
P-1B-2
ELEVATOR
E1-B
CERNER AND COMMAND
CENTER (30)
CPT-1 ACT-1
P-1B-1
PLANNING AND PREP
CPT-1 ACT-1
P-1B-1
CONFERENCE ROOM
CPT-1 ACT-1
P-4B-1
VENDING
SLC-1 ACT-1
P-5B-2
AE501
SIM
ELEVATOR LOBBY
CPT-2 P-3
P-1B-2
STAIR
S3-B
SLC-1 P-3
P-1B-2
CORRIDOR
C2
SLC-1 ACT-2
P-1B-2
CORRIDOR
C2
SLC-1 ACT-2
P-1B-2
CORRIDOR
C3
CPT-2 P-3
P-1B-2
CORRIDOR
C4
CPT-2 ACT-2
P-1B-2
WOMEN'S RESTROOM
CT-1 ACT-1
CTW-1CBT-1
MEN'S RESTROOM
CT-1 ACT-1
CTW-1CBT-1
ELEC.
SLC-1 P-3
P-1B-2
HAC
CT-1 P-3
P-1CBT-1
SLC-1
SLC-1
SLC-1
/Q
H
/Q
H
4/QH401
1/QH401
AE502
XXX
XXX
XX
XX
XX
XX
ROOM NUMBER
CEILING FINISH
WALL FINISH
ROOM NAME
FLOOR FINISH
WALL BASE FINISH
FINISH KEY
REFER TO SHEET AI800
F I N I S H N O T E S:
A. SEE ROOM FINISH SCHEDULE SHEET I800.
B. ALL FLOORING MATERIALS TO BE SLIP RESISTANT.
C. ALL FINISHES TO BE CLASS A OR B
02/23/2022
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS
321 4 5 6 7 8 9 10
B
IM
/H in e s E
H R
M T ra in in g
C e n te r/ F
F E
H in e s
T ra in in g C e n te r_
B rv t
/2
/2
:1
:3
P
M
AI802
ARCHITECTURAL SECOND FLOOR
FINISH PLAN
02/23/2022 PH TD
EHRM TRAINING AND ADMIN SPACE
SUPPORT
578-21-706
HINES, IL
BID DOCUMENTS
EDWARD HINES
JR. VAMC
N
1/8" = 1'-0"
SECOND FLOOR FINISH PLAN
KEYPLAN
24" 24" 24" 24" 24" 24"
24" 24" 24" 24" 24" 24"
36"36"
36" 36" 36" 36"
36"36"36"36"48"
48" 36" 36" 36" 36"
02/23/2022
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS
321 4 5 6 7 8 9 10
B
IM
/H in e s E
H R
M T ra in in g
C e n te r/ F
F E
H in e s
T ra in in g C e n te r_
B rv t
/2
/2
:1
:4
P
M
AI810
ARCHITECTURAL INTERIOR
ELEVATIONS
02/23/2022 PH TD
EHRM TRAINING AND ADMIN SPACE
SUPPORT
578-21-706
HINES, IL
BID DOCUMENTS
EDWARD HINES
JR. VAMC
1/4" = 1'-0"
BREAK ROOM 107 - EAST WALL
1/4" = 1'-0"
PLANNING AND PREP 242 - CASEWORK
1/4" = 1'-0"
BREAKROOM 229 - CASEWORK
DM
DM
DM
DM
TR/USB
TR/USB
TR/USB
D
D
D
WP1
2D
D4
D
D4
D
D
D
D
D
G E N E R A L N O T E S:
H I
/2
20' - 0"
EQ. 17' - 4" EQ.
/Q
H
/Q
H
4/QH401
1/QH401
6' - 0" 1' - 0"
1' - 0" 6' - 0"
02/23/2022
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS
321 4 5 6 7 8 9 10
B
IM
/H in e s E
H R
M T ra in in g
C e n te r/ F
F E
H in e s
T ra in in g C e n te r_
B rv t
/2
/2
:1
:1
P
M
QH401
ENLARGED CLASSROOM
FURNITURE PLANS
02/23/2022 PH JK
EHRM TRAINING AND ADMIN SPACE
SUPPORT
578-21-706
HINES, IL
BID DOCUMENTS
EDWARD HINES
JR. VAMC
D R A W I N G N O T E S :
1 4 X 6 MARKER BOARD.
2 MONITOR SEE TECHNOLOGY DRAWINGS - PROVIDE BLOCKING IN WALL.
3 SUPPLY SHELF (VV).
N
1/4" = 1'-0"
ENLARGED PLAN - TYPICAL INTERIOR CLASSROOM
A. ALL ITEMS CONTRACTOR SUPPLIED AND CONTRACTOR INSTALLED
(CC) UNLESS NOTED OTHERWISE.
B. VV = VA SUPPLIED AND INSTALLED
C. LECTERN, TABLES, AND CHAIRS ARE VV.
1/4" = 1'-0"
TYPICAL CLASSROOM 1
1/4" = 1'-0"
TYPICAL CLASSROOM 2
1/4" = 1'-0"
TYPICAL CLASSROOM 4
1/4" = 1'-0"
TYPICAL CLASSROOM 3
C D E F G H I J K L M N O P
AE301
FREIGHT
ELEVATOR
121 SF
OFFICE (1)
119 SF
OFFICE (1)
114 SF
TR
120 SF
OFFICE (1)
120 SF
OFFICE (1)
120 SF
OFFICE (1)
339 SF
BREAK (6)
608 SF
CORRIDOR
C1
/4
/4
404 SF
LOBBY
61 SF
ELEVATOR EQUIPMENT
75 SF
ELEVATOR
E1-A
86 SF
UNISEX RESTROOM
86 SF
UNISEX RESTROOM
129 SF
STAIR
S2-A
108 SF
ELECTRICAL
237 SF
STAIR
S1-A
4667 SF
SHELL SPACE
SS
/A
I8
G E N E R A L N O T E S:
02/23/2022
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS
321 4 5 6 7 8 9 10
B
IM
/H in e s E
H R
M T ra in in g
C e n te r/ F
F E
H in e s
T ra in in g C e n te r_
B rv t
/2
/2
:1
:5
P
M
QH101
FIRST FLOOR FURNITURE PLAN
02/23/2022 PH TD
EHRM TRAINING AND ADMIN SPACE
SUPPORT
578-21-706
HINES, IL
BID DOCUMENTS
EDWARD HINES
JR. VAMC
N
1/8" = 1'-0"
FIRST FLOOR FURNITURE PLAN
KEYPLAN
F U R N I T U R E N O T E S :
1 LOCKERS - RELOCATED BY VA
A. ALL TABLES, CHAIRS, WORKSTATIONS, AND DESKS SHOWN ON THIS PLAN ARE
FOR REFERENCE ONLY AND ARE VA FURNISHED AND INSTALLED.
B. WHERE EXISTING SURFACES ARE TO BE REFINISHED OR ARE TO SERVE AS
SUBSTRATE FOR THE ATTACHMENT OR APPLICATION OF NEW MATERIALS OR
CONSTRUCTION, PREPARE OR ALTER THE EXISTING SURFACES AS NECESSARY
TO PROPERLY ACCOMMODATE THE NEW MATERIALS.
UPDN
C D E F G H I J K L M N O P
729 SF
CLASSROOM (17)
604 SF
CLASSROOM (17)
604 SF
CLASSROOM (17)
604 SF
CLASSROOM (17)
591 SF
CLASSROOM (17)
625 SF
CLASSROOM (17)
605 SF
CLASSROOM (17)
605 SF
CLASSROOM (17)
606 SF
CLASSROOM (17)
606 SF
CLASSROOM (17)
605 SF
CLASSROOM (17)
600 SF
CLASSROOM (17)
599 SF
CLASSROOM (17)
904 SF
CLASSROOM (17)
603 SF
CLASSROOM (17)
603 SF
CLASSROOM (17)
866 SF
CORRIDOR
C4
599 SF
CLASSROOM (17)
602 SF
CLASSROOM (17)
118 SF
TR
1572 SF
MECHANICAL ROOM
445 SF
BREAK ROOM
218 SF
STAIR
S2-B
82 SF
FREIGHT ELEVATOR
E2
1657 SF
CORRIDOR
C5
75 SF
ELEVATOR
E1-B
216 SF
VENDING
264 SF
MEN'S RESTROOM
265 SF
WOMEN'S RESTROOM
146 SF
STAIR
S3-B
62 SF
HAC
563 SF
ELEVATOR LOBBY
1936 SF
CERNER AND COMMAND
CENTER (30)
580 SF
PLANNING AND PREP
1832 SF
CORRIDOR
C2
135 SF
STAIR
S1-B
6/AI810
5/AI810
3/AE401
/A
E
/A
E
6/AE401
/A
E
8/AE401
/A
E
10/AE401
QH401
3' - 9"
/4
/Q
H
/Q
H
4/QH401
1/QH401
6' - 0"
85'
99'-6"
G E N E R A L N O T E S:
02/23/2022
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS
321 4 5 6 7 8 9 10
B
IM
/H in e s E
H R
M T ra in in g
C e n te r/ F
F E
H in e s
T ra in in g C e n te r_
B rv t
/2
/2
:1
:0
P
M
QH102
SECOND FLOOR FURNITURE PLAN
02/23/2022 PH TD
EHRM TRAINING AND ADMIN SPACE
SUPPORT
578-21-706
HINES, IL
BID DOCUMENTS
EDWARD HINES
JR. VAMC
N
1/8" = 1'-0"
SECOND FLOOR FURNITURE PLAN
D R A W I N G N O T E S :
1 VENDING MACHINES BY OTHERS
KEYPLAN
A. ALL TABLES, CHAIRS, WORKSTATIONS, AND DESKS SHOWN ON THIS PLAN ARE
FOR REFERENCE ONLY AND ARE VA FURNISHED AND INSTALLED.
B. WHERE EXISTING SURFACES ARE TO BE REFINISHED OR ARE TO SERVE AS
SUBSTRATE FOR THE ATTACHMENT OR APPLICATION OF NEW MATERIALS OR
CONSTRUCTION, PREPARE OR ALTER THE EXISTING SURFACES AS NECESSARY
TO PROPERLY ACCOMMODATE THE NEW MATERIALS.
ABBREVIATIONS
AC - AIR COMPRESSOR
ACC - ACCESS
AD - ACCESS DOOR
ADB - ACID DILUTION BASIN
ADJ - ADJUSTABLE
AFF - ABOVE FINISHED FLOOR
AFG - ABOVE FINISHED GRADE
ALT - ALTERNATE
AP - ACCESS PANEL
APPROX - APPROXIMATE
ARCH - ARCHITECT OR ARCHITECTURAL
ASSY - ASSEMBLY
BFP - BACKFLOW PREVENTER
BLDG - BUILDING
BOB - BOTTOM OF BEAM
BOD - BOTTOM OF DUCT
BOE - BOTTOM OF EQUIPMENT
BOF - BOTTOM OF FOOTING
BOG - BOTTOM OF GRILLE
BOP - BOTTOM OF PIPE
BOT - BOTTOM
BTWN - BETWEEN
CA - COMPRESSED AIR
CFCI - CONTRACTOR FURNISHED CONTRACTOR
INSTALLED
CLG - CEILING
CONN - CONNECT OR CONNECTION
CONTR - CONTRACTOR
COR - CONTRACTING OFFICER'S REPRESENTATIVE
CORR - CORRIDOR
CTR - CENTER
CWS - COMBINATION WATER SERVICE
D - DEPTH
DET - DETAIL
DIA - DIAMETER
DIM - DIMENSION
DN - DOWN
DS - SPRINKLER (DRY)
DWG - DRAWING
EA - EACH
EC - ELECTRICAL (DIVISION 26)
EJ - EXPANSION JOINT
ELEC - ELECTRICAL
ELEV - ELEVATOR
EQ - EQUAL
EQUIP - EQUIPMENT
ETR - EXISTING TO REMAIN
EQS - EQUIPMENT SUPPLIER
EXP - EXPANSION
EXT - EXTERIOR
EX - EXISTING
F - FIRE SUPPRESSION (STANDPIPE/SPRINKLER MAIN)
FCE - FIRE CONTROL EQUIPMENT
FCO - FLOOR CLEANOUT
FD - FLOOR DRAIN
FDC - FIRE DEPARTMENT CONNECTION
FDV - FIRE DEPARTMENT VALVE
FF - FINISHED FLOOR ELEVATION
FHC - FIRE HOSE CABINET
FLR - FLOOR
FPM - FEET PER MINUTE
FR - FIRE RISER
FS - FIRE SERVICE
FSC - FIRE SUPPRESSION (DIVISION 21)
FT - FEET
FTG - FOOTING
GA - GAUGE
GAL - GALLON
GALV - GALVANIZED
GC - GENERAL TRADES
GPM - GALLONS PER MINUTE
HC - HVAC (DIVISION 23)
HD - HUB DRAIN
HP - HORSEPOWER OR HIGH POINT
HR - HOSE REEL
HT - HEAT TRACE
HVAC - HEATING, VENTILATING, AND AIR CONDITIONING
ID - INSIDE DIAMETER
INV - INVERT ELEVATION
IN - INCHES
JS - JANITOR SINK
L - LENGTH
LBS - POUNDS
MAX - MAXIMUM
MB - MOP BASIN
MC - MECHANICAL (DIVISION 23)
MEZZ - MEZZANINE
MFR - MANUFACTURER
MIN - MINIMUM
MISC - MISCELLANEOUS
MTD - MOUNTED
MTG - MOUNTING
N/C - NORMALLY CLOSED
NIC - NOT IN CONTRACT
N/O - NORMALLY OPEN
NOM - NOMINAL
NPT - NATIONAL PIPE THREAD
NTS - NOT TO SCALE
OA - OUTDOOR AIR
OD - OUTSIDE DIAMETER
OFCI - OWNER FURNISHED CONTRACTOR
INSTALLED
OFOI - OWNER FURNISHED OWNER INSTALLED
PC - PLUMBING (DIVISION 22)
OR PUMPED CONDENSATE RETURN
PIV - POST INDICATOR VALVE
PLBG - PLUMBING
PS - PRE-ACTION/DELUGE SPRINKLER
PRESS - PRESSURE
PRV - PRESSURE REGULATING VALVE
PSF - POUNDS PER SQUARE FOOT
PSI - POUNDS PER SQUARE INCH
PSV - PRESSURE SUSTAINING VALVE
PSIG - POUNDS PER SQUARE INCH GAUGE
RAD - RADIUS
REC - RECESSED
REQD - REQUIRED
RI - ROUGH IN
RPM - REVOLUTIONS PER MINUTE
S - SPRINKLER (WET)
SCH - SCHEDULE
SD - SPRINKLER DRAIN
SHT - SHEET
SK - SINK
SPEC - SPECIFICATIONS
SQ - SQUARE
STD - STANDARD
STRUC - STRUCTURAL OR STRUCTURE
SUC - SITE UTILITY CONTRACTOR
TEMP - TEMPERATURE
TOB - TOP OF BEAM
TOD - TOP OF DUCT
TOE - TOP OF EQUIPMENT
TOF - TOP OF FOOTING
TOJ - TOP OF JOIST
TOP - TOP OF PIPE
TOS - TOP OF SLAB OR TOP OF STEEL
TYP - TYPICAL
UNO - UNLESS NOTED OTHERWISE
VEL - VELOCITY
VIB - VALVE IN BOX
VOL - VOLUME
W/ - WITH
W/O - WITHOUT
WIV - WALL INDICATOR VALVE
WS - WATER SERVICE
VALVES AND FITTINGS
T
P
FOB
FOT
CONCENTRIC PIPE REDUCER
ECCENTRIC PIPE REDUCER
GAUGE - PRESSURE
GAUGE - TEMPERATURE OR THERMOMETER
UNION
CLEANOUT
STRAINER
STRAINER - WITH A BLOW DOWN VALVE AND HOSE
CONNECTION
VALVE - DRAIN WITH HOSE END CONNECTION
VALVE - PRESSURE REGULATING
VALVE - SAFETY RELIEF. PIPE DISCHARGE AIR
GAPPED TO FLOOR DRAIN UNLESS NOTED
OTHERWISE.
PLUG - PRESSURE AND TEMPERATURE TEST
TRAP PRIMER
GAUGE - VACUUM WITH STOP
CLEANOUT - TO GRADE OR FINISHED FLOOR
END CAP
MIXING FAUCET
PLUG
HOSE BIB
WALL HYDRANT
VALVE - PLUG
VALVE - SHUTOFF AND BOX
VALVE - SHUTOFF ON RISER
V
VB
TP
CO
VALVE - SOLENOID
S
P/T VALVE - PRESSURE AND TEMPERATURE SAFETY
RELIEF. PIPE DISCHARGE AIR GAPPED TO
FLOOR DRAIN UNLESS NOTED OTHERWISE.
VALVE - CHECK
VALVE - SHUTOFF: BALL, GATE, BUTTERFLY VALVE
(REFER TO SPECIFICATIONS FOR REQUIRED TYPE
BASED ON APPLICATIONS)
AUTOMATIC FLOW CONTROLLER WITH P/T PLUG IN
AND OUT
VALVE - COMBINATION SHUTOFF AND
BALANCING (REFER TO SPECIFICATIONS FOR
REQUIRED TYPE BASED ON APPLICATIONS)
A1
P1 P1OR
A1
OH
P2
B
P2
GENERAL FLOOR PLAN NOTES
RISER OR STACK NUMBER
DETAIL: B = DETAIL DESIGNATION
P2 = SHEET WHERE DETAIL IS LOCATED
FIRE SUPPRESSION HAZARD CLASSIFICATION AND
HAZARD CLASSIFICATION GROUP
SECTION: 1 = SECTION DESIGNATION
P2 = SHEET WHERE DETAIL IS LOCATED
EQUIPMENT REFERENCE. LETTER DESIGNATION
VARIES. REFER TO SCHEDULES.
EQUIPMENT, DEVICE, OR PLUMBING FIXTURE MARK.
LETTER DESIGNATIONS REFER TO SCHEDULES.
CONNECT TO EXISTING
PLAN NOTE. APPLIES ONLY TO THE SHEET WHICH
IT IS SHOWN UNLESS NOTED OTHERWISE.
DETAIL NOTE. APPLIES ONLY TO THE ASSOCIATED DETAIL.
"UP TO" SYMBOL (ITEM ON FLOOR ABOVE)
EXISTING PIPE TO REMAIN
EXISTING PIPE TO BE REMOVED
EXPANSION JOINT
WATER METERM
PIPING SYMBOLS
BOTTOM CONNECTION (45°)
BRANCH TEE CONNECTION (NOTE:
BULLHEAD TEE'S ARE NOT PERMITTED)
DIRECTION OF PITCH
DROP
ELBOW DOWN
ELBOW UP
FLOW DIRECTION DESIGNATION
PUMP
RISE
TOP CONNECTION (45°)
TOP CONNECTION (90°)
BOTTOM CONNECTION (90°)
D
R
PIPE RISER
BC
TC
FLEX PIPING
NOTE: ALL SYMBOLS AND ABBREVIATIONS ARE SUBJECT TO MODIFICATIONS ON OTHER DRAWINGS. ADDITIONALLY, ALL SYMBOLS OR ABBREVIATIONS MIGHT NOT NECESSARILY BE USED ON THIS PROJECT.
FIRE SUPPRESSION SYMBOLS
PIPING DESIGNATIONS
FS
PIV
S
CONCEALED PENDENT SPRINKLER
FIRE HYDRANT
FLOW SWITCH
GATE VALVE OS&Y
INSTITUTIONAL PENDENT SPRINKLER
PENDENT SPRINKLER
POST INDICATOR VALVE
RECESSED PENDENT SPRINKLER
SIDE WALL SPRINKLER
SUPERVISED VALVE
UPRIGHT SPRINKLER
FIRE DEPARTMENT VALVE
SPRINKLER PIPE (DRY)
FIRE SUPPRESSION (STANDPIPE/
SPRINKLER MAIN)
FIRE SERVICE
PRE-ACTION / DELUGE SPRINKLER PIPE
SPRINKLER PIPE (WET)
SPRINKLER DRAIN PIPE
DS
F
FS
PS
S
SD
COMMMMBINATION FIRE SUPPRESSION &
DOMESTIC WATER SERVICE
CWS
A PROVIDE A COMPLETE RENOVATION TO AN EXISTING FIRE SUPPRESSION
SPRINKLER SYSTEM IN THE RENOVATED AREA.
B COORDINATE WORK WITH VAMC, PHASING PLAN AND OTHER TRADES. OFFSET
AND/OR RELOCATE EXISTING SERVICES TO ACCOMMODATE NEW WORK OF
OTHER TRADES.
C DESIGN SERVICES SHALL FOLLOW ALL VA STANDARD DESIGN PRACTICES,
DETAILS, SPECIFICATIONS AND SITE SPECIFIC COR REQUIREMENTS AS WELL AS
WORK SHOWN ON THESE DOCUMENTS. ALL DEVIATIONS FROM
AFOREMENTIONED REQUIREMENTS SHALL BE APPROVED BY THE COR.
D VERIFY THAT THERE IS ADEQUATE SPACE TO INSTALL ALL NEW PIPING
REQUIRED TO COMPLETE THIS WORK.
E ALL SPRINKLER PIPING IS LOCATED ABOVE THE CEILING (AT THE BOTTOM OF
STRUCTURE IN EXPOSED STRUCTURAL AREAS), UNLESS OTHERWISE INDICATED.
F THE BASIS OF DESIGN OF SPACING AND SIZING FOR THE COMPLETE FIRE
SUPPRESSION SPRINKLER SYSTEM SHALL BE FOR A WET PIPE SYSTEM
HYDRAULICALLY CALCULATED FOR A:
1 LIGHT HAZARD AREA LIMITED TO A MAXIMUM OF 225 SQ. FT. PER SPRINKLER
WITH THE DENSITY OF 0.10 GPM/SQ. FT. OVER THE MOST REMOTE 1500 SQ.
FT. PROVIDE AN ADDITION OF 100 GPM HOSE ALLOWANCE.
2 ALL MECHANICAL, ELECTRICAL AND SIMILAR SPACE AREAS SHALL BE
ORDINARY HAZARD (GROUP 1) LIMITED TO A MAXIMUM OF 130 SQ. FT. PER
SPRINKLER WITH A DENSITY OF 0.15 GPM/SQ. FT. PROVIDE AN ADDITION OF
250 GPM HOSE ALLOWANCE.
3 ALL STORAGE, TRASH, FILE STORAGE AND SIMILAR SPACE AREAS SHALL BE
ORDINARY HAZARD (GROUP 2) LIMITED TO A MAXIMUM OF 130 SQ. FT. PER
SPRINKLER WITH A DENSITY OF 0.20 GPM/ SQ. FT. PROVIDE AN ADDITION OF
250 GPM HOSE ALLOWANCE.
G PROVIDE SPRINKLER LOCATIONS AND RELATED PIPING.
H THE ENTIRE SPRINKLER SYSTEM SHALL CONFORM TO VAMC STANDARDS, RULES
AND REGULATIONS. REFER TO VA FIRE PROTECTION DESIGN MANUAL.
I CAREFULLY COORDINATE THE LOCATION OF ALL SPRINKLERS AND PIPING WITH
ALL OTHER TRADES AND THE ARCHITECT.
J VERIFY THE LOCATION OF ALL LIGHTING FIXTURES AND AIR DEVICES BEFORE
INSTALLATION OF SPRINKLERS.
K PROVIDE SPRINKLER PIPING LAYOUT AND SIZING.
L ALL SPRINKLER LOCATIONS MUST BE COORDINATED WITH ALL EQUIPMENT
KINDRED TO OTHER TRADES. SPRINKLER LOCATIONS MUST BE APPROVED BY
THE ARCHITECT BEFORE WORK COMMENCES. REFER TO THE ARCHITECTURAL
AND REFLECTIVE CEILING PLANS FOR ADDITIONAL INFORMATION ON ALL CEILING
TYPES, HEIGHTS AND OTHER ARCHITECTURAL FEATURES.
M MAKE NECESSARY FLOW TESTS, LAYOUT SYSTEMS, OBTAIN APPROVALS FROM
THE AUTHORITIES HAVING JURISDICTION PRIOR TO BEGINNING ANY
FABRICATION OR INSTALLATION WORK.
N SPRINKLER PIPING SHALL BE 1" MINIMUM SIZE.
O SPRINKLERS (UNLESS OTHERWISE NOTED):
EXPOSED AREAS - UPRIGHT OR PENDENT TYPE - STANDARD BRASS
CEILING AREAS - RECESSED PENDENT TYPE
P ALL HEADS SHALL BE UL LISTED AND FM APPROVED.
Q SPRINKLERS SHALL BE "QUICK RESPONSE" TYPE IN ALL AREAS EXCEPT: HIGH
TEMPERATURE AREAS, TELECOMMUNICATION, ELECTRICAL SWITCHGEAR,
ELEVATOR EQUIPMENT ROOMS AND ELEVATOR SHAFTS.
R ALL PENDENT TYPE SPRINKLERS LOCATED IN SUSPENDED CEILING TILE AREAS
SHALL BE LOCATED IN THE CENTER OF THE CEILING TILE.
S ANNULAR SPACE AT PIPE AND OTHER SIMILAR PENETRATION OF FIRE RATED
ASSEMBLIES SHALL BE FIRE STOPPED. REFER TO SPECIFICATIONS FOR FIRE
STOPPING. REFER TO ARCHITECTURAL DRAWINGS FOR CONSTRUCTION, LAYOUT
AND FIRE RATING OF FLOORS, WALLS, PARTITIONS AND OTHER BUILDING
ELEMENTS.
T A FLOW TEST IS REQUIRED. REFER TO SPECIFICATION SECTION 21 13 13 FOR
FLOW TEST INFORMATION.
U ALL SPRINKLER ZONES SHALL MATCH SMOKE COMPARTMENTS.
V REFER TO ARCHITECTURAL DRAWINGS FOR INFORMATION ON SMOKE
COMPARTMENTS, SMOKE PARTITIONS AND FIRE BARRIERS.
W PHASING: REFER TO ARCHITECTURAL DRAWINGS FOR AN OUTLINE OF PROJECT
PHASING. ADDITIONAL NOTES DESCRIBING PHASING DETAILS MAY BE INCLUDED
THROUGHOUT THIS DRAWING SET. INCLUDE ALL LABOR AND MATERIAL TO
ACCOMMODATE PHASING.
X BID ITEMS: REFER TO ARCHITECTURAL DRAWING AND SPECIFICATION SECTION
01 00 00 FOR AN OUTLINE OF BID ITEMS. ADDITIONAL NOTES DESCRIBING BID
ITEM DETAILS MAY BE INCLUDED THROUGHOUT THIS DRAWING SET.
Y SPRINKLER SYSTEM PIPING AND FITTINGS SHALL BE IN ACCORDANCE WITH
NFPA 13.
1 PIPING SIZES 2" AND SMALLER SHALL BE BLACK STEEL SCHEDULE 40
WITH THREADED END CONNECTIONS.
2 PIPING SIZES 2.5" AND LARGER SHALL BE BLACK STEEL SCHEDULE 10
WITH GROOVED CONNECTIONS. GROOVES IN SCHEDULE 10 PIPING SHALL BE
ROLLED GROOVED ONLY.
FIRE SUPPRESSION DESIGN NOTES
LOCATION: EDWARD HINES, JR VA HOSPITAL
5000 S. 5th Ave., Hines, IL 60141
BLDG 20 (S. 1ST AVE & CEMARK)
STATIC PRESSURE: 72 PSI
RESIDUAL PRESSURE: 60 PSI
FLOW: 830 GPM
DATE: 12/16/2021
NOTE: PERFORM HYDRAULIC CALCULATIONS UTILIZING THE BASIS OF DESIGN FLOW
TEST DATA PROVIDED TO BID THE FIRE SUPPRESSION SPRINKLER SYSTEM. UPON
AWARD OF THE PROJECT, A HYDRANT FLOW TEST ALONG WITH CORRESPONDING
HYDRAULIC CALCULATIONS SHALL BE PERFORMED TO VERIFY ADEQUATE PRESSURE
AND FLOW.
BASIS OF DESIGN FLOW TEST DATA
S.
#062-073523
REGISTERED
PROFESSIONAL
ENGINEER
OF
SIGER DERET
WE
H
T T
A M
GRAH
A
M
NO I S
ILLI
2021-05099
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
PROJECT NO.
C
B
IM
\M o d e l\
-0
-P lu m b in g C e n tr a l_ rl c o n d y .r v t
/1
/2
:5
:0
A
M
F001
FIRE SUPPRESSION ABBREVIATIONS,
LEGEND & DRAWING INDEX
VAMC
02/23/2022 KMB RLC
EHRM TRAINING AND ADMIN SPACE 578-21-706
HINES, IL.
BID DOCUMENTS
EDWARD HINES
JR. VAMC
2021-05099
DRAWING INDEX - FIRE SUPPRESSION
SHEET NUMBER SHEET NAME
F001 FIRE SUPPRESSION ABBREVIATIONS, LEGEND & DRAWING INDEX
FX101 FIRE SUPPRESSION BASEMENT & FIRST FLOOR PLANS
FX102 FIRE SUPPRESSION SECOND FLOOR PLAN
BFP
S
C D E F G H I J K L M N O P
OH
2 2
OH
EXISTING FIRE
SERVICE ENTRANCE
OH
OH
OH
OH
FDC
LOBBY
E1-A
ELEVATOR
ELEVATOR
EQUIPMENT
UNISEX
RESTROOM
UNISEX
RESTROOM
MECHANICAL
BREAK (6)
C1
CORRIDOR
OFFICE (1)
OFFICE (1)
OFFICE (1)
TR
OFFICE (1)
OFFICE (1)
S2-A
STAIR
ELECTRICAL
CLOSET
SS
SHELL
SPACE
ELECTRICAL
C1
CORRIDOR
A. REFER TO SHEET F001 FOR ABBREVIATIONS, SYMBOLS & INDEX OF DRAWINGS.
B. EXISTING CORRIDORS AND/ OR ROOMS TO REMAIN OPERATIONAL AT ALL TIMES DURING
BUSINESS HOURS. AUTOMATIC SPRINKLER SYSTEM(S) SHALL BE MAINTAINED IN FULLY
OPERATIONAL CONDITION (PER NFPA 241, SPRINKLER SYSTEMS WILL BE OPERATIONAL,
BUT IMPAIRED WHILE CEILINGS ARE REMOVED). SPRINKLER SYSTEM MAY BE TAKEN
OFF-LINE FOR UP TO 8 HOURS, AS REQUIRED, TO MAKE MODIFICATIONS/ CONNECTIONS
TO EXISTING SYSTEM.
GENERAL NOTES
N O P
2 2
OH
BASEMENT
S.
#062-073523
REGISTERED
PROFESSIONAL
ENGINEER
OF
SIGER DERET
WE
H
T T
A M
GRAH
A
M
NO I S
ILLI
2021-05099
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
PROJECT NO.
C
B
IM
\M o d e l\
-0
-P lu m b in g C e n tr a l_ rl c o n d y .r v t
/1
/2
:5
:0
A
M
FX101
FIRE SUPPRESSION BASEMENT & FIRST
FLOOR PLANS
VAMC
02/23/2022 KMB RLC
EHRM TRAINING AND ADMIN SPACE 578-21-706
HINES, IL.
BID DOCUMENTS
EDWARD HINES
JR. VAMC
2021-05099
N
1/8" = 1'-0"
FIRST FLOOR PLAN - FIRE SUPPRESSION
PLAN NOTES
1. EXISTING AREA, PIPING OR PIECE OF EQUIPMENT (TYPE AS INDICATED) TO REMAIN.
2. LIMITS OF RENOVATED AREA REQUIRING EXISTING SPRINKLER SYSTEM MODIFICATIONS.
MODIFICATIONS INCLUDE, BUT ARE NOT LIMITED TO, REPLACING ALL SPRINKLERS,
PIPE BRANCHES AND MAINS TO CONFORM TO NEW ARCHITECTURAL LAYOUTS WHERE
NECESSARY.
3. ONLY SPRINKLER PIPING SERVING ROOM'S SPRINKLER(S) SHALL BE ALLOWED ABOVE
THIS ROOM.
4. OPEN TO DECK ABOVE.
5. PROVIDE SUPERVISED VALVE TO ISOLATE SPRINKLERS SERVING ELEVATOR
EQUIPMENT ROOM.
6. PROVIDE STANDARD RESPONSE, INTERMEDIATE TEMPERATURE SPRINKLERS IN THE
ELEVATOR MACHINE ROOM.
7. PROVIDE SIDEWALL SPRINKLER IN THE ELEVATOR PIT LOCATED NO MORE THAN
2 FEET ABOVE THE PIT.
KEYPLAN
N
1/8" = 1'-0"
BASEMENT PLAN - FIRE SUPPRESSION
SS
C D E F G H I J K L M N O P
OH
CLASSROOM
(17)
CLASSROOM
(17)
CLASSROOM
(17)
BREAK
ROOM
CLASSROOM
(17)
CLASSROOM
(17)
MECHANICAL
ROOM
CLASSROOM
(17)
CLASSROOM
(17)
CLASSROOM
(17)
CLASSROOM
(17)
CLASSROOM
(17)
C4
CORRIDOR
CLASSROOM
(17)
CLASSROOM
(17)
CLASSROOM
(17)
CLASSROOM
(17)
CLASSROOM
(17)
CLASSROOM
(17)
S1-B
STAIR
S2-B
STAIR
C3
CORRIDOR
CERNER
AND
COMMAND
CENTER
(30)
ELEVATOR
LOBBY
S3-B
STAIR
HAC
WOMEN'S
RESTROOM
MEN'S
RESTROOM
TR
C2
CORRIDOR
CLASSROOM
(17)
VENDING
E1-B
ELEVATOR
OH
OH
OH
ELEC.
OH
PLANNING
AND PREP
C5
CORRIDOR
C5
CORRIDOR
C5
CORRIDOR
CLASSROOM
(17)
5 5
C2
CORRIDOR
C3
CORRIDOR
5 5
E2
FREIGHT
ELEVATOR
227A
ELEV.
SERVICE
CONFERENCE
ROOM
A. REFER TO SHEET F001 FOR ABBREVIATIONS, SYMBOLS & INDEX OF DRAWINGS.
B. EXISTING CORRIDORS AND/ OR ROOMS TO REMAIN OPERATIONAL AT ALL TIMES DURING
BUSINESS HOURS. AUTOMATIC SPRINKLER SYSTEM(S) SHALL BE MAINTAINED IN FULLY
OPERATIONAL CONDITION (PER NFPA 241, SPRINKLER SYSTEMS WILL BE OPERATIONAL,
BUT IMPAIRED WHILE CEILINGS ARE REMOVED). SPRINKLER SYSTEM MAY BE TAKEN
OFF-LINE FOR UP TO 8 HOURS, AS REQUIRED, TO MAKE MODIFICATIONS/ CONNECTIONS
TO EXISTING SYSTEM.
GENERAL NOTES
S.
#062-073523
REGISTERED
PROFESSIONAL
ENGINEER
OF
SIGER DERET
WE
H
T T
A M
GRAH
A
M
NO I S
ILLI
2021-05099
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
PROJECT NO.
C
B
IM
\M o d e l\
-0
-P lu m b in g C e n tr a l_ rl c o n d y .r v t
/1
/2
:5
:1
A
M
FX102
FIRE SUPPRESSION SECOND FLOOR
PLAN
VAMC
02/23/2022 KMB RLC
EHRM TRAINING AND ADMIN SPACE 578-21-706
HINES, IL.
BID DOCUMENTS
EDWARD HINES
JR. VAMC
2021-05099
N
1/8" = 1'-0"
SECOND FLOOR PLAN - FIRE SUPPRESSION
PLAN NOTES
1. LIMITS OF RENOVATED AREA REQUIRING EXISTING SPRINKLER SYSTEM MODIFICATIONS.
MODIFICATIONS INCLUDE, REPLACING ALL SPRINKLERS, PIPE BRANCHES, HANGERS
AND MAINSTO CONFORM TO NEW ARCHITECTURAL LAYOUT.
NOTE: FLOOR HEIGHT IS LIMITED. CLOSE COORDINATION WITH OTHER DIVISIONS IS
CRITICAL.
2. ONLY SPRINKLER PIPING SERVING ROOM'S SPRINKLER(S) SHALL BE ALLOWED ABOVE
THIS ROOM.
3. PROVIDE SUPERVISED VALVE TO ISOLATE SPRINKLERS SERVING ELEVATOR
EQUIPMENT ROOM.
4. PROVIDE STANDARD RESPONSE, INTERMEDIATE TEMPERATURE SPRINKLERS IN THE
ELEVATOR MACHINE ROOM.
5. OPEN TO DECK ABOVE.
KEYPLAN
NOTE: ALL SYMBOLS AND ABBREVIATIONS ARE SUBJECT TO MODIFICATIONS ON OTHER DRAWINGS. ADDITIONALLY, ALL SYMBOLS OR ABBREVIATIONS MIGHT NOT NECESSARILY BE USED ON THIS PROJECT.
A1
P1 P1OR
A1
OH
P2
B
P2
GENERAL FLOOR PLAN NOTES
RISER OR STACK NUMBER
DETAIL: B = DETAIL DESIGNATION
P2 = SHEET WHERE DETAIL IS LOCATED
FIRE SUPPRESSION HAZARD CLASSIFICATION AND
HAZARD CLASSIFICATION GROUP
SECTION: 1 = SECTION DESIGNATION
P2 = SHEET WHERE DETAIL IS LOCATED
EQUIPMENT REFERENCE. LETTER DESIGNATION
VARIES. REFER TO SCHEDULES.
EQUIPMENT, DEVICE, OR PLUMBING FIXTURE MARK.
LETTER DESIGNATIONS REFER TO SCHEDULES.
CONNECT TO EXISTING
PLAN NOTE. APPLIES ONLY TO THE SHEET WHICH
IT IS SHOWN UNLESS NOTED OTHERWISE.
DETAIL NOTE. APPLIES ONLY TO THE ASSOCIATED DETAIL.
"UP TO" SYMBOL (ITEM ON FLOOR ABOVE)
PIPING DESIGNATIONS
DOMESTIC COLD WATER
DOMESTIC HOT WATER
DOMESTIC HOT WATER RETURN
EXISTING PIPE TO REMAIN
EXISTING PIPE TO BE REMOVED
HOT WATER PIPE (140 DEGS. F.)
HOT WATER RETURN PIPE (140 DEGS. F.)
HOT WATER RETURN PIPE (180 DEGS. F.)
140R
180R
EXPANSION JOINT
WATER METERM
PIPING SYMBOLS
BOTTOM CONNECTION (45°)
BRANCH TEE CONNECTION (NOTE:
BULLHEAD TEE'S ARE NOT PERMITTED)
DIRECTION OF PITCH
DROP
ELBOW DOWN
ELBOW UP
FLOW DIRECTION DESIGNATION
PUMP
RISE
TOP CONNECTION (45°)
TOP CONNECTION (90°)
BOTTOM CONNECTION (90°)
D
R
PIPE RISER
HOT WATER PIPE (180 DEGS. F.)
ARGON PIPE
COMPRESSED AIR PIPE
GARAGE DRAINAGE PIPE
HYDROGEN PIPE
HELIUM PIPE
KITCHEN WASTE PIPE
LABORATORY COMPRESSED AIR PIPE
LABORATORY VENT PIPE
LABORATORY VACUUM PIPE
LABORATORY WASTE PIPE
NON-POTABLE
(OVERFLOW) SECONDARY STORM DRAINAGE PIPE
PUMP DISCHARGE PIPE
PURE WATER PIPE
SANITARY DRAINAGE PIPE
SOFT COLD WATER
STORM DRAINAGE PIPE
TRAP PRIMER DISCHARGE PIPE
TEMPERED WATER PIPE
SANITARY SEWER VENT
WATER SERVICE
LV
AR
CA
GD
H2
HE
IV
IW
LA
LV
LW
NPW
OD
PD
PW
SAN
SCW
STM
TP
TW
V
WS
INDIRECT VENT PIPE
INDIRECT WASTE PIPE
K
ACID VENT PIPEAV
ACID WASTE PIPEAW
BC
TC
COMBINATION FIRE SUPPRESSION &
DOMESTIC WATER SERVICE
CWS
FLEX PIPING
VALVES AND FITTINGS
T
P
FOB
FOT
CONCENTRIC PIPE REDUCER
ECCENTRIC PIPE REDUCER
GAUGE - PRESSURE
GAUGE - TEMPERATURE OR THERMOMETER
UNION
CLEANOUT
STRAINER
STRAINER - WITH A BLOW DOWN VALVE AND HOSE
CONNECTION
VALVE - DRAIN WITH HOSE END CONNECTION
VALVE - PRESSURE REGULATING
VALVE - SAFETY RELIEF. PIPE DISCHARGE AIR
GAPPED TO FLOOR DRAIN UNLESS NOTED
OTHERWISE.
PLUG - PRESSURE AND TEMPERATURE TEST
TRAP PRIMER
GAUGE - VACUUM WITH STOP
CLEANOUT - TO GRADE OR FINISHED FLOOR
END CAP
MIXING FAUCET
PLUG
HOSE BIB
WALL HYDRANT
VALVE - PLUG
VALVE - SHUTOFF AND BOX
VALVE - SHUTOFF ON RISER
V
VB
TP
CO
VALVE - SOLENOID
S
P/T VALVE - PRESSURE AND TEMPERATURE SAFETY
RELIEF. PIPE DISCHARGE AIR GAPPED TO
FLOOR DRAIN UNLESS NOTED OTHERWISE.
VALVE - CHECK
VALVE - SHUTOFF: BALL, GATE, BUTTERFLY VALVE
(REFER TO SPECIFICATIONS FOR REQUIRED TYPE
BASED ON APPLICATIONS)
AUTOMATIC FLOW CONTROLLER WITH P/T PLUG IN
AND OUT
VALVE - COMBINATION SHUTOFF AND
BALANCING (REFER TO SPECIFICATIONS FOR
REQUIRED TYPE BASED ON APPLICATIONS)
ABBREVIATIONS
AAP - AREA ALARM PANEL (MEDICAL GAS)
AC - AIR COMPRESSOR OR AIR CONDITIONER
ACC - ACCESS
ACCU - AIR COOLED CONDENSING UNIT
AD - ACCESS DOOR OR AREA DRAIN
ADB - ACID DILUTION BASIN
ADJ - ADJUSTABLE
AFF - ABOVE FINISHED FLOOR
AFG - ABOVE FINISHED GRADE
ALT - ALTERNATE
AP - ACCESS PANEL
APPROX - APPROXIMATE
AR - AIR RECEIVER OR ARGON
ARCH - ARCHITECT OR ARCHITECTURAL
ASSY - ASSEMBLY
AV - ACID VENT
AW - ACID WASTE
BDD - BACK DRAFT DAMPER
BFP - BACKFLOW PREVENTER
BLDG - BUILDING
BOB - BOTTOM OF BEAM
BOD - BOTTOM OF DUCT
BOE - BOTTOM OF EQUIPMENT
BOF - BOTTOM OF FOOTING
BOG - BOTTOM OF GRILLE
BOP - BOTTOM OF PIPE
BOT - BOTTOM
BT - BATHTUB
BTU - BRITISH THERMAL UNIT
BTUH - BRITISH THERMAL UNIT PER HOUR
BTWN - BETWEEN
CA - COMPRESSED AIR
CB - CATCH BASIN
CBD - COUNTER BALANCED BACKDRAFT DAMPER
CFCI - CONTRACTOR FURNISHED CONTRACTOR
INSTALLED
CFM - CUBIC FEET PER MINUTE
CHS - CHILLED WATER SUPPLY
CHR - CHILLED WATER RETURN
CI - CAST IRON
CK - CLINICAL SINK
CLG - CEILING
CMU - CONCRETE MASONRY UNIT
CO - CLEAN OUT
CO2 - MEDICAL CARBON DIOXIDE
CONN - CONNECT OR CONNECTION
CONTR - CONTRACTOR
COR - CONTRACTING OFFICER'S REPRESENTATIVE
CORR - CORRIDOR
CS - CLINICAL SINK OR COLD SOFT WATER
CTR - CENTER
CU - COPPER
CW - COLD WATER
CWS - COMBINATION WATER SERVICE
OR CONDENSER WATER SUPPLY
CWR - CONDENSER WATER RETURN
D - DEPTH OR DRAIN LINE
DD - DECK DRAIN
DCW - DOMESTIC COLD WATER
DET - DETAIL
DF - DRINKING FOUNTAIN OR WATER COOLER
OR DIESEL FUEL
DFU - DRAINAGE FIXTURE UNIT
DHW - DOMESTIC HOT WATER
DHWR - DOMESTIC HOT WATER RETURN
DI - DEIONIZED WATER
DIA - DIAMETER
DIM - DIMENSION
DN - DOWN
DS - DOWN SPOUT OR SPRINKLER (DRY)
DT - PERFORATED DRAIN TILE
DWG - DRAWING
EA - EACH
EC - ELECTRICAL (DIVISION 26)
EEW - EMERGENCY EYE WASH
EJ - EXPANSION JOINT
ELEC - ELECTRICAL
ELEV - ELEVATOR
EQ - EQUAL
EQUIP - EQUIPMENT
ET - EXPANSION TANK
ETR - EXISTING TO REMAIN
ES - EMERGENCY SHOWER
EQS - EQUIPMENT SUPPLIER
EWC - ELECTRICAL WATER COOLER
EXH - EXHAUST AIR
EXP - EXPANSION
EXT - EXTERIOR
EX - EXISTING
F - FIRE SUPPRESSION (STANDPIPE/SPRINKLER
MAIN)
FCE - FIRE CONTROL EQUIPMENT
FCO - FLOOR CLEANOUT
FD - FLOOR DRAIN
FDC - FIRE DEPARTMENT CONNECTION
FDV - FIRE DEPARTMENT VALVE
FF - FINISHED FLOOR ELEVATION
FHC - FIRE HOSE CABINET
FLR - FLOOR
FM - FORCE MAIN
FOB - FLAT ON BOTTOM
FOF - FUEL OIL FLOW
FOG - FUEL OIL GAUGE
FOR - FUEL OIL RETURN
FOS - FUEL OIL SUPPLY
FOT - FLAT ON TOP
FPM - FEET PER MINUTE
FR - FIRE RISER
FS - FLOOR SINK OR FIRE SERVICE
FSC - FIRE SUPPRESSION (DIVISION 21)
FT - FEET
FTG - FOOTING
G - GAS OR NATURAL GAS
GA - GAUGE
GAL - GALLON
GALV - GALVANIZED
GC - GENERAL TRADES
GD - GARAGE DRAINAGE
GPM - GALLONS PER MINUTE
GS - GAS SERVICE
GW - GREASE WASTE
H2 - HYDROGEN
HB - HOSE BIBB
HC - HVAC (DIVISION 23)
HD - HUB DRAIN
HE - HELIUM
HG - REFRIGERANT HOT GAS
HP - HORSEPOWER OR HIGH POINT
HPC - HIGH PRESSURE CONDENSATE RETURN
HPS - HIGH PRESSURE STEAM SUPPLY
HPW - HIGH PURITY WATER
HPWR - HIGH PURITY WATER RETURN
HR - HOSE REEL
HT - HEAT TRACE
HTR - HEATER
HVAC - HEATING, VENTILATING, AND AIR
CONDITIONING
HW - HOT WATER
HWR - HEATING HOT WATER RETURN
HWS - HEATING HOT WATER SUPPLY
IA - MEDICAL INSTRUMENT AIR
ID - INSIDE DIAMETER
INV - INVERT ELEVATION
IN - INCHES
IV - INDIRECT VENT
IW - INDIRECT WASTE
JS - JANITOR SINK
K - KITCHEN WASTE
KEC - KITCHEN EQUIPMENT
L - LENGTH
LA - LABORATORY COMPRESSED AIR
LAV - LAVATORY
LBS - POUNDS
LCW - LABORATORY COLD WATER
LEC - LABORATORY EQUIPMENT
LHW - LABORATORY HOT WATER
LHWR - LABORATORY HOT WATER RETURN
LPC - LOW PRESSURE CONDENSATE RETURN
LPS - LOW PRESSURE STEAM SUPPLY
LV - LABORATORY VACUUM OR LABORATORY
VENT
LW - LABORATORY WASTE
MA - MEDICAL COMPRESSED AIR
MAP - MASTER ALARM PANEL (MEDICAL GAS)
MAX - MAXIMUM
MB - MOP BASIN
MC - MECHANICAL (DIVISION 23)
MEZZ - MEZZANINE
MFR - MANUFACTURER
MH - MANHOLE
MIN - MINIMUM OR MINUTE
MISC - MISCELLANEOUS
MTD - MOUNTED
MTG - MOUNTING
MPC - MEDIUM PRESSURE CONDENSATE RETURN
MPS - MEDIUM PRESSURE STEAM SUPPLY
MU - WATER MAKE-UP
MV - MEDICAL SURGICAL VACUUM
N2 - MEDICAL NITROGEN
N/C - NORMALLY CLOSED
NG - GASOLINE (NON-LEAD)
NIC - NOT IN CONTRACT
N/O - NORMALLY OPEN
NO - MEDICAL NITROUS OXIDE
NOM - NOMINAL
NPW - NON-POTABLE WATER
NPT - NATIONAL PIPE THREAD
NTS - NOT TO SCALE
O2 - MEDICAL OXYGEN
OA - OUTDOOR AIR
OD - OUTSIDE DIAMETER OR OVERFLOW
DRAIN
OFCI - OWNER FURNISHED CONTRACTOR
INSTALLED
OFOI - OWNER FURNISHED OWNER INSTALLED
P - PROPANE GAS
PC - PLUMBING (DIVISION 22) OR PUMPED
CONDENSATE RETURN
PD - PUMP DISCHARGE OR PARAPET DRAIN
PIV - POST INDICATOR VALVE
PLBG - PLUMBING
PS - PRE-ACTION/DELUGE SPRINKLER
PRESS - PRESSURE
PRV - PRESSURE REGULATING VALVE
PSF - POUNDS PER SQUARE FOOT
PSI - POUNDS PER SQUARE INCH
PSV - PRESSURE SUSTAINING VALVE
PSIG - POUNDS PER SQUARE INCH GAUGE
PW - PURE WATER
RA - RETURN AIR
RAD - RADIUS
RCP - REINFORCED CONCRETE PIPE
RD - ROOF DRAIN
REC - RECESSED
REQD - REQUIRED
RI - ROUGH IN
RL - REFRIGERANT LIQUID
ROS - REVERSE OSMOSIS WATER SUPPLY
ROR - REVERSE OSMOSIS WATER RETURN
RPM - REVOLUTIONS PER MINUTE
RS - REFRIGERANT SUCTION
RV - RELIEF VALVE
S - SPRINKLER (WET)
SA - SHOCK ARRESTOR OR SUPPLY AIR
SAN - SANITARY OR SANITARY DRAIN
SCH - SCHEDULE
SCW - SOFT COLD WATER
SD - SPRINKLER DRAIN OR SUBSOIL DRAIN
SH - SHOWER
SHT - SHEET
SK - SINK
SPEC - SPECIFICATIONS
SQ - SQUARE
SR - SUPPLY RISER
SS - SANITARY STACK (SOIL OR WASTE) OR
STAINLESS STEEL
STD - STANDARD
STM - STORM OR STORM DRAINAGE
STRUC - STRUCTURAL OR STRUCTURE
SUC - SITE UTILITY CONTRACTOR
T - FUEL TANK VENT
TD - TRENCH DRAIN
TEMP - TEMPERATURE
TOB - TOP OF BEAM
TOD - TOP OF DUCT
TOE - TOP OF EQUIPMENT
TOF - TOP OF FOOTING
TOJ - TOP OF JOIST
TOP - TOP OF PIPE
TOS - TOP OF SLAB OR TOP OF STEEL
TF - TRAP FILLER
TP - TRAP PRIMER OR TRAP PRIMER
DISCHARGE
TW - TEMPERED WATER
TYP - TYPICAL
UR - URINAL
UNO - UNLESS NOTED OTHERWISE
V - VENT OR SANITARY SEWER VENT
VAC - VACUUM
VC - VACUUM CLEANING
VCV - VACUUM CLEANING VALVE
VE - VACUUM EXHAUST
VEL - VELOCITY
VIB - VALVE IN BOX
VOL - VOLUME
VP - VACUUM PUMP
VS - VENT STACK
VTR - VENT THROUGH ROOF
VR - VENT RISER
W/ - WITH
W/O - WITHOUT
W - WASTE
WAGD - WASTE ANESTHESIA GAS DISPOSAL
WC - WATER CLOSET
WCO - WALL CLEANOUT
WH - WALL HYDRANT OR WATER HEATER
WIV - WALL INDICATOR VALVE
WS - WATER SERVICE
WV - WATER VALVE
YCO - YARD CLEANOUT
ZVC - ZONE VALVE CABINET
GENERAL NOTES
A ALL PIPING IS ABOVE THE CEILING (AT THE UNDERSIDE OF STRUCTURE IN
EXPOSED STRUCTURE AREAS), UNLESS OTHERWISE NOTED.
B REFER TO SCHEDULES, DETAILS AND DIAGRAMS FOR PIPING, PIPE SIZES AND
PIPELINE DEVICES NOT INDICATED ON THE FLOOR PLAN.
C ABOVE CEILING UTILITY SPACE IS LIMITED. COORDINATION WITH ALL TRADES IS
CRITICAL, PRIOR TO INSTALLATION OF ANY WORK.
D LOCATIONS AND SIZES OF EXISTING PIPING HAVE BEEN DETERMINED FROM A
REVIEW OF EXISTING DRAWINGS AND/OR SITE INSPECTION, WHERE POSSIBLE.
FIELD VERIFICATION OF EXACT LOCATIONS, ELEVATIONS, INVERTS, SIZES,
DIRECTION OF FLOW, ETC. SHALL BE REQUIRED PRIOR TO BEGINNING NEW
WORK.
E ALL PIPING SHALL BE REMOVED BACK TO WITHIN TWO PIPE DIAMETERS OF
ACTIVE MAINS AND CAPPED, OR REMOVED BACK TO POINTS OF CONNECTION
OF NEW WORK. INACCESSIBLE PIPING, WHERE SO NOTED, TO BE ABANDONED
SHALL BE DISCONNECTED FROM ACTIVE MAINS AND CAPPED OR PLUGGED IN
CONCEALED LOCATIONS.
F NEW CONNECTIONS TO EXISTING PIPING SHALL BE WITH THE SAME SIZE AS THE
EXISTING PIPING UNLESS OTHERWISE NOTED.
G ALL REMOVED MATERIAL AND EQUIPMENT SO DESIGNATED BY THE OWNER,
SHALL BE TURNED OVER AND PLACED WHERE DIRECTED. ALL MATERIAL AND
EQUIPMENT, WHICH THE OWNER DOES NOT WISH TO RETAIN, SHALL BECOME
THE PROPERTY OF THE CONTRACTOR RESPONSIBLE FOR THE REMOVAL.
H ANY RENOVATION WORK REQUIRED "OUTSIDE" OF THE BOUNDARIES/ EXTENTS
OF A SPECIFIC PHASE OF WORK OR TEMPORARY CONSTRUCTION WALLS
SHALL BE BID AS "NIGHT WORK" AND SHALL BE AS DIRECTED BY THE COR.
I ALL CORE DRILLS AND PIPE EXTENSIONS THRU THE EXISTING STRUCTURAL
FLOOR SLAB OR STRUCTURAL WALL SHALL BE X-RAYED TO DETERMINE THE
EXACT LOCATION OF THE REBAR IN THE STRUCTURAL SLAB. DO NOT CUT
THE LOWER (BOTTOM REBARS) IN THE STRUCTURAL FLOOR SLAB.
J WORKING ON EXISTING FLOORS WITH NO/ LIMITED ARCHITECTURAL SCOPE, THE
CONTRACTOR SHALL PROVIDE ALL REQUIRED FLOOR/ WALL PROTECTION (AS
REQUIRED) AND REPLACE ANY DAMAGED CEILING TILES WITH NEW. RETURN
AREA BACK TO ORIGINAL CONDITION UPON COMPLETION OF WORK.
K REFER TO ARCHITECTURAL FIRE RATED PARTITION PLAN(S) FOR LOCATIONS
AND FIRE RATINGS OF NEW AND EXISTING WALL ASSEMBLIES. ALL
PENETRATIONS THROUGH FIRE RATED ASSEMBLIES SHALL BE PROTECTED
AND/OR FIRE STOPPED AS REQUIRED TO MAINTAIN FIRE RATINGS INDICATED.
COORDINATE WITH ALL TRADES TO ENSURE FIRE RATED PENETRATION
REQUIREMENTS AND DETAILS ARE MET.
L ANNULAR SPACE OF ALL PIPE & OTHER SIMILAR PENETRATIONS OF FIRE RATED
ASSEMBLIES SHALL BE FIRE STOPPED. IN ADDITION, PENETRATIONS THROUGH
0-HOUR RATED WALLS & FLOOR SHALL BE SEALED TO RETARD THE PASSAGE
OF SMOKE.
M DOMESTIC WATER PIPING SYSTEM IN THE RENOVATED AREA SHALL BE
DISINFECTED AND TESTED IN ITS ENTIRETY. DISINFECTION AND TESTING
PROCEDURES SHALL FOLLOW VA WATER SAFETY PLAN, OTHER VA
DESIGN MANUALS, SPECIFICATIONS, AND LOCAL REQUIREMENTS.
S.
#062-073523
REGISTERED
PROFESSIONAL
ENGINEER
OF
SIGER DERET
WE
H
T T
A M
GRAH
A
M
NO I S
ILLI
2021-05099
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
PROJECT NO.
C
B
IM
\M o d e l\
-0
-P lu m b in g C e n tr a l_ rl c o n d y .r v t
/2
/2
:1
:2
P M
P001
PLUMBING ABBREVIATIONS, LEGEND &
DRAWING INDEX
VAMC
02/23/2022 KMB RLC
EHRM TRAINING AND ADMIN SPACE 578-21-706
HINES, IL.
BID DOCUMENTS
EDWARD HINES
JR. VAMC
2021-05099
DRAWING INDEX - PLUMBING
SHEET NUMBER SHEET NAME
P001 PLUMBING ABBREVIATIONS, LEGEND & DRAWING INDEX
PD100 PLUMBING BASEMENT PLAN - REMOVALS
PD101 PLUMBING FIRST FLOOR PLAN - REMOVALS
PD102 PLUMBING SECOND FLOOR PLAN - REMOVALS
PL100 PLUMBING BASEMENT PLAN - NEW WORK
PL101 PLUMBING FIRST FLOOR PLAN - NEW WORK
PL102 PLUMBING SECOND FLOOR PLAN - NEW WORK
P401 PLUMBING ENLARGED PLANS
P601 PLUMBING SCHEDULES & DETAILS
P901 PLUMBING SOIL, WASTE & VENT DIAGRAM
P902 PLUMBING SOIL, WASTE & VENT DIAGRAM
P903 PLUMBING DOMESTIC WATER DIAGRAM
P904 PLUMBING DOMESTIC WATER DIAGRAM
UP6" F
A
PD100
UP3" DCW
3"
3"
1.5"
6"
6"
2"
SAN
S A
N
S A
N
SP2
FD
CO
WC
LAV
WC
SH/FD
SAN SAN
4" S
AN
DN6" SAN 1
UP4" V 1
4"
PD
SLAB ON GRADE
SLAB ON GRADE
SLAB ON GRADE
BSMT
SLAB ON GRADE
12" SAN
SANITARY MH #2756
4" SAN
12" SAN
11 1
WV
PIV
WV
UP4" PD
Level 1 100' - 0"
Basement 87' - 9"
4" - V
CO
BASIN 1
4" - PD
S.
#062-073523
REGISTERED
PROFESSIONAL
ENGINEER
OF
SIGER DERET
WE
H
T T
A M
GRAH
A
M
NO I S
ILLI
2021-05099
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
PROJECT NO.
C
B
IM
\M o d e l\
-0
-P lu m b in g C e n tr a l_ rl c o n d y .r v t
/2
/2
:1
:3
P M
PD100
PLUMBING BASEMENT PLAN -
REMOVALS
VAMC
02/23/2022 KMB RLC
EHRM TRAINING AND ADMIN SPACE 578-21-706
HINES, IL.
BID DOCUMENTS
EDWARD HINES
JR. VAMC
2021-05099
N
1/8" = 1'-0"
BASEMENT PLAN - REMOVALS
PLAN NOTES
1. EXISTING AREA, PIPING OR PIECE OF EQUIPMENT (TYPE AS
INDICATED) TO REMAIN.
2. REMOVE ALL EXTRANEOUS SANITARY DRAIN AND VENT PIPING BACK TO
POINT OF NEW CONNECTION OR BACK TO ACTIVE MAIN AND CAP. CAP
PIPING IN WALLS WHERE WALLS ARE TO REMAIN OR ABOVE CEILING OR
BELOW FLOOR SLAB WHERE WALLS ARE TO BE REMOVED. NO PIPE
STUBS SHALL REMAIN VISIBLE IN FINISHED AREAS.
3. REMOVE DUPLEX SUMP PUMP, MOTORS, VALVES AND CONTROLLERS.
REMOVE SUMP PIPING BACK TO POINT OF NEW CONNECTION.
THOROUGHLY CLEAN SUMP BASIN. (BASIN TO REMAIN). REFER TO
DETAIL A, THIS SHEET.
4. CAREFUL EXCAVATION IS REQUIRED IN THIS LOCATION. VERIFY EXACT
LOCATION, INVERTS, SIZES, CONNECTIONS AND DIRECTION OF SANITARY
PIPING PRIOR TO ANY DEMOLITION. EXISTING CONDITIONS ARE
UNKNOWN.
KEYPLAN
SCALE: 1/4" = 1'-0"
SUMP PUMP - SP2
A
GENERAL NOTES:
A. REFER TO P001 FOR ABBREVIATIONS, LEGEND AND DRAWING INDEX.
B. MAINTAIN AND RESTORE, IF INTERRUPTED, THE DOMESTIC WATER SUPPLY
AND SANITARY & VENT SYSTEMS TO THE EXISTING PLUMBING FIXTURES
LOCATED IN UNDISTURBED AREA.
BFP
C D E F G H I J K L M N O P
EXISTING FIRE/ WATER
SERVICE ENTRANCE
LAV
WC
FD SH
LAV
WC 2
E-85
2 VENT STACK
FDC
VENT STACK
& VTR
DWH1
3"
FD
4"
PD
DN4" PD
HB
HB
SK 2
STORAGE ANNEX NIC
1DWH
C D E F G H I J K L M N O P
S.
#062-073523
REGISTERED
PROFESSIONAL
ENGINEER
OF
SIGER DERET
WE
H
T T
A M
GRAH
A
M
NO I S
ILLI
2021-05099
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
PROJECT NO.
C
B
IM
\M o d e l\
-0
-P lu m b in g C e n tr a l_ rl c o n d y .r v t
/2
/2
:1
:4
P M
PD101
PLUMBING FIRST FLOOR PLAN -
REMOVALS
VAMC
02/23/2022 KMB RLC
EHRM TRAINING AND ADMIN SPACE 578-21-706
HINES, IL.
BID DOCUMENTS
EDWARD HINES
JR. VAMC
2021-05099
N
1/8" = 1'-0"
FIRST FLOOR PLAN - REMOVALS
PLAN NOTES
1. EXISTING AREA, PIPING OR PIECE OF EQUIPMENT (TYPE AS INDICATED) TO REMAIN.
2. REMOVE EXISTING FIXTURE OR ITEM OF EQUIPMENT (TYPE AS INDICATED) AND ALL
EXTRANEOUS DOMESTIC WATER PIPING BACK TO POINT OF NEW CONNECTION OR
WITH-IN TWO (2) PIPE DIAMETERS OF ACTIVE MAIN. REMOVE ALL EXTRANEOUS
SANITARY DRAIN AND VENT PIPING BACK TO POINT OF NEW CONNECTION OR BACK
TO ACTIVE MAIN AND CAP. CAP PIPING IN WALLS WHERE WALLS ARE TO REMAIN OR
ABOVE CEILING OR BELOW FLOOR SLAB WHERE WALLS ARE TO BE REMOVED. NO
PIPE STUBS SHALL REMAIN VISIBLE IN FINISHED AREAS.
3. REMOVE EXISTING FLOOR DRAIN GRATE AND STRAINER, PLUG DRAIN OUTLET, AND
FILL DRAIN WITH CONCRETE FLUSH WITH EXISTING FLOOR SLAB. REMOVE
EXISTING PIPING SERVING FLOOR DRAIN BACK TO ACTIVE MAIN AND CAP OR POINT
OF NEW CONNECTION.
4. REMOVE ENTIRE EXISTING HALON SYSTEM AND ALL ASSOCIATED PIPING.
5. REMOVE ALL PLUMBING PIPING, LINE DEVICES AND ACCESSORIES REMAINING IN
THIS AREA UNLESS OTHERWISE NOTED TO REMAIN.
REMOVE EXISTING DOMESTIC WATER PIPING BACK TO POINT OF NEW CONNECTION
OR WITH-IN TWO (2) PIPE DIAMETERS OF ACTIVE MAIN AND CAP.
REMOVE ALL EXTRANEOUS SANITARY DRAIN AND VENT PIPING BACK TO POINT OF
NEW CONNECTION OR BACK TO ACTIVE MAIN AND CAP.
NO PIPE STUBS SHALL REMAIN VISIBLE IN FINISHED AREAS.
REMOVE ALL EXISTING PLUMBING PIPING PROTRUDING THRU FLOOR/ DECK TO
FLUSH WITH FLOOR/ DECK. FILL WITH CONCRETE TO FLUSH WITH EXISTING
FLOOR/ DECK .
6. EXISTING VEEDER ROOT (E-85) FUELING MANAGEMENT SYSTEM TO REMAIN.
7. CAREFUL EXCAVATION IS REQUIRED IN THIS LOCATION. VERIFY EXACT LOCATION,
INVERTS, SIZES, CONNECTIONS AND DIRECTION OF SANITARY PIPING PRIOR TO
DEMOLITION.
KEYPLAN
GENERAL NOTES:
A. REFER TO P001 FOR ABBREVIATIONS, LEGEND AND DRAWING INDEX.
B. MAINTAIN AND RESTORE, IF INTERRUPTED, THE DOMESTIC WATER SUPPLY
AND SANITARY & VENT SYSTEMS TO THE EXISTING PLUMBING FIXTURES LOCATED
IN UNDISTURBED AREA.
VTR
VENT STACK
VTR
VENT STACK
& VTR
VTR
3 1
2 VENT STACK
SK
A. REFER TO SHEET P001 FOR ABBREVIATIONS, SYMBOLS & INDEX OF DRAWINGS.
GENERAL NOTES
S.
#062-073523
REGISTERED
PROFESSIONAL
ENGINEER
OF
SIGER DERET
WE
H
T T
A M
GRAH
A
M
NO I S
ILLI
2021-05099
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
PROJECT NO.
C
B
IM
\M o d e l\
-0
-P lu m b in g C e n tr a l_ rl c o n d y .r v t
/2
/2
:1
:4
P M
PD102
PLUMBING SECOND FLOOR PLAN -
REMOVALS
VAMC
02/23/2022 KMB RLC
EHRM TRAINING AND ADMIN SPACE 578-21-706
HINES, IL.
BID DOCUMENTS
EDWARD HINES
JR. VAMC
2021-05099
N
1/8" = 1'-0"
SECOND FLOOR PLAN - REMOVALS
PLAN NOTES
KEYPLAN
1. EXISTING AREA, PIPING OR PIECE OF EQUIPMENT (TYPE AS INDICATED) TO REMAIN.
2. REMOVE EXISTING VENT STACK AND VENT THRU ROOF. PATCH TO MATCH EXISTING.
SEAL WATER-TIGHT.
3. REMOVE EXISTING FIXTURE OR ITEM OF EQUIPMENT (TYPE AS INDICATED) AND ALL
EXTRANEOUS DOMESTIC WATER PIPING BACK TO POINT OF NEW CONNECTION OR
WITH-IN TWO (2) PIPE DIAMETERS OF ACTIVE MAIN. REMOVE ALL EXTRANEOUS
SANITARY DRAIN AND VENT PIPING BACK TO POINT OF NEW CONNECTION OR BACK
TO ACTIVE MAIN AND CAP. CAP PIPING IN WALLS WHERE WALLS ARE TO REMAIN OR
ABOVE CEILING OR BELOW FLOOR SLAB WHERE WALLS ARE TO BE REMOVED. NO
PIPE STUBS SHALL REMAIN VISIBLE IN FINISHED AREAS.
4. REMOVE ALL PLUMBING PIPING, LINE DEVICES AND ACCESSORIES REMAINING IN
THIS AREA UNLESS OTHERWISE NOTED TO REMAIN.
REMOVE EXISTING DOMESTIC WATER PIPING BACK TO POINT OF NEW CONNECTION
OR WITH-IN TWO (2) PIPE DIAMETERS OF ACTIVE MAIN AND CAP.
REMOVE ALL EXTRANEOUS SANITARY DRAIN AND VENT PIPING BACK TO POINT OF
NEW CONNECTION OR BACK TO ACTIVE MAIN AND CAP.
NO PIPE STUBS SHALL REMAIN VISIBLE IN FINISHED AREAS.
REMOVE ALL EXISTING PLUMBING PIPING PROTRUDING THRU FLOOR/ DECK TO
FLUSH WITH FLOOR/ DECK. FILL WITH CONCRETE TO FLUSH WITH EXISTING
FLOOR/ DECK.
B. REMOVE ALL EXISTING PLUMBING PIPING PROTRUDING THRU FLOOR TO FLUSH
WITH FLOOR/ DECK. PROVIDE BACKING MATERIAL AND FILL WITH CONCRETE
FLUSH WITH EXISTING FLOOR/ DECK.
ELEVATOR
PIT
UP4" SAN
FD1 FD1
P-418
S A
N
SAN
SAN
SAN
3"
3"
6"
2"
S A
N
UP3" DCW
UP6" F1
UP2" SAN
CO
UP2" SAN
S A
N
FD3
SAN
2" VR
SAN
UP4" SAN
UP1.5" SAN
SAN
SAN
FD1FD1
P-418
SAN
D P601
TP
TP
P-524
TP
SP2
DN6" SAN
UP4" V
4"
PD
FD3
TP
SAN SAN
4" S
AN PIV
WV
12" SAN 12" SAN
SANITARY MH #2756
SLAB ON GRADE
SLAB ON GRADESLAB ON GRADE
BSMT
WV
4" SAN
B
PL100
A
PL100
UP4" SAN
CO
SP1
UP2" PD
CO
CO
TEST-Y & CO
UP4" PD
HD
A. REFER TO SHEET P001 FOR ABBREVIATIONS, SYMBOLS & INDEX OF DRAWINGS.
GENERAL NOTES
3"
FLOOR
3"
1. DUPLEX CONTROL PANEL. MOUNT 60" AFF TO
TOP OF PANEL.
2. INSTALL PIPE ACCESSORIES IN HORIZONTAL
PORTION OF PIPING.
3. POWER WIRING IN CONDUIT TO CONTROL
PANEL.
4. EXISTING VENT
5. EXISTING PUMPED DISCHARGE PIPING
6. BASIN LID
7. PUMP
8. PUMP REMOVAL RAIL SYSTEM.
9. EXISTING BASIN
2 2
7 7
P D
P D
NOTESV
CO
P D
4" 5
4"
S.
#062-073523
REGISTERED
PROFESSIONAL
ENGINEER
OF
SIGER DERET
WE
H
T T
A M
GRAH
A
M
NO I S
ILLI
2021-05099
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
PROJECT NO.
C
B
IM
\M o d e l\
-0
-P lu m b in g C e n tr a l_ rl c o n d y .r v t
/2
/2
:1
:4
P M
PL100
PLUMBING BASEMENT PLAN - NEW
WORK
VAMC
02/23/2022 KMB RLC
EHRM TRAINING AND ADMIN SPACE 578-21-706
HINES, IL.
BID DOCUMENTS
EDWARD HINES
JR. VAMC
2021-05099
N
1/8" = 1'-0"
BASEMENT PLAN - NEW WORK
PLAN NOTES
1. EXISTING AREA, PIPING OR PIECE OF EQUIPMENT (TYPE AS INDICATED) TO REMAIN.
2. PROVIDE SUMP PUMP ALARM AND CONTROL PANEL. COORDINATE LOCATION AND
REQUIREMENTS WITH DIVISION 26.
3. SANITARY ROUGH-INS FOR FUTURE FIT-OUT. RISE TO 24" ABOVE EXISTING FLOOR
SLAB AND CAP. SIZE AS INDICATED.
4. RUN PIPING AS HIGH AS POSSIBLE TO CONNECT TO EXISTING 6" SANITARY IN
BASEMENT.
5. VERIFY EXACT LOCATION, INVERTS, SIZES, CONNECTIONS AND DIRECTION OF
SANITARY PIPING PRIOR TO ANY CONSTRUCTION.
6. SUMP PUMP: SUBMERSIBLE DUPLEX SUMP SYSTEM (SP2)
CAPACITY: 75 GPM @ 46 FT. HEAD (EA)
MOTOR: 3 HP - 208V-3PH (EA)
DISCHARGE: 3" W/ CHECK & BALL VALVE. (EA)
PROVIDE NEW BASIN LID, CONTROLS AND RAIL SYSTEM.
7. PROVIDE ADAPTOR AND CONNECT TO STUB PROVIDED BY S.U.C.
KEYPLAN
SCALE: NONE
SUMP PUMP - SP2
A
SCALE: NONE
SANITARY MH# 2756
B
B F
P
BFP
TP
A. REFER TO SHEET P001 FOR ABBREVIATIONS, SYMBOLS & INDEX OF DRAWINGS.
GENERAL NOTESC D E F G H I J K L M N O P
ET1
FD2
FD1
FD1
FD1
FD1
P-502
P-418 (4)
P-418 (4)
P-524
P107
P-201
(3)
(2)
DWH1
TMV1
RP1
P-609
P-107
1.5" VR
P401
1"
0.5"
E-85
P-524
DN2" SANDN2" SAN
DN4" SAN
CO
TP
FD2
T P
DN4" SAN
UP2" V
FD3
V 3"2" VR
V
V
EXISTING WATER
SERVICE ENTRANCE
2" VR
P-804
1.5"3"
3"
2.5" 1.25" 2.5"
SAN
(5)
P-609
DN1.5" SAN
1.5" VR
1.5" VR
1.5" VR
TP
TP
SAN
SAN
S A
N
TP
UP1.25" DHW
UP2.5" DCW
UP2" V
DN4" SAN
SS
SHELL
SPACE
ELECTRICAL
CLOSET
S2-A
STAIR
FUT
FUTURE
RESTROOMS
MECHANICAL
LOBBY
ELEVATOR
EQUIPMENT
E1-A
ELEVATOR
TR
OFFICE (1)
OFFICE (1)
OFFICE (1)
OFFICE (1)
BREAK (6)
UP2" V
E P601
UP0.5" DCW
4" CONCRETE HOUSEKEEPING PAD
7 7
0.75"
TP
TP
TP
1.25"
DN4" PD 1
4"
PD
ELECTRICAL
HB
HB 1
1.5"1.5"
FD3
DWH 1
STORAGE ANNEX NIC
UP2" PD
8 8
DN2" PD
UP0.75" DHWR
0.5"
CO
CO
CO
TEST-Y & CO
1.5" HD
S.
#062-073523
REGISTERED
PROFESSIONAL
ENGINEER
OF
SIGER DERET
WE
H
T T
A M
GRAH
A
M
NO I S
ILLI
2021-05099
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
PROJECT NO.
C
B
IM
\M o d e l\
-0
-P lu m b in g C e n tr a l_ rl c o n d y .r v t
/2
/2
:1
:4
P M
PL101
PLUMBING FIRST FLOOR PLAN - NEW
WORK
VAMC
02/23/2022 KMB RLC
EHRM TRAINING AND ADMIN SPACE 578-21-706
HINES, IL.
BID DOCUMENTS
EDWARD HINES
JR. VAMC
2021-05099
PLAN NOTES
1. EXISTING AREA, PIPING OR PIECE OF EQUIPMENT (TYPE AS INDICATED) TO REMAIN.
2. PROVIDE 1" STUB FOR HVAC EQUIPMENT. PIPING TO BE CONTINUED/ COORDINATED
PER DIVISION 23.
3. SANITARY ROUGH-INS FOR FUTURE FIT-OUT. RISE TO 24" ABOVE EXISTING FLOOR
SLAB AND CAP. SIZE AS INDICATED.
4. 2" DCW, 0.75" DHW & 0.5" DHWR VALVED AND CAPPED WITH-IN TWO (2) PIPE
DIAMETERS OF ACTIVE MAIN STUBS FOR FUTURE EXTENSION. VALVES SHALL
BE LOCKED CLOSED.
5. SUMP PUMP, REFER TO DETIAL D/ P601. EXTEND PUMPED DRAINAGE PIPING UP TO
SECOND FLOOR, DISCHARGE INTO MOP BASIN.
6. SAW CUT AND TRENCH EXISTING FLOOR SLAB TO ACCOMMODATE NEW SANITARY
PIPING. PROVIDE BEDDING, BACKFILL AND COMPACTION PER SPECIFICATIONS. PATCH
CONCRETE FLUSH TO FINISHED FLOOR AND RESURFACE TO MATCH ADJACENT FLOOR
SLAB.
7. INSTALL BODY COMPLETE, INSTALL SOLID COVER & GASKET. TURNOVER STRAINER
TO COR.
8. FIXTURE SHALL BE VENTED BY A COMBINATION WASTE AND VENT SYSTEM PER IPC
SECTION 915. MAXIMUM SLOPE SHALL BE 1/2" PER FOOT BETWEEN FIXTURE AND
VENT CONNECTION OF SYSTEM.
9. PROVIDE SUMP PUMP ALARM AND CONTROL PANEL. COORDINATE LOCATION AND
REQUIREMENTS WITH DIVISION 26.
10. PROVIDE 0.75" SANITARY DRAIN FIXED AIR GAP FITTING FOR MECHANICAL
CONDENSATE DRAIN.
KEYPLAN
N
1/8" = 1'-0"
FIRST FLOOR PLAN - NEW WORK
TP
DN
C D E F G H I J K L M N O P
CLASSROOM
(17)
CLASSROOM
(17)
CLASSROOM
(17)
BREAK
ROOM
CLASSROOM
(17)
CLASSROOM
(17)
MECHANICAL
ROOM
CLASSROOM
(17)
CLASSROOM
(17)
CLASSROOM
(17)
CLASSROOM
(17)
CLASSROOM
(17)
C4
CORRIDOR
CLASSROOM
(17)
CLASSROOM
(17)
CLASSROOM
(17)
CLASSROOM
(17)
CLASSROOM
(17)
CLASSROOM
(17)
S1-B
STAIR
S2-B
STAIR
C3
CORRIDOR
P401
CERNER
AND
COMMAND
CENTER
(30)
PLANNING
AND PREP
ELEVATOR
LOBBY
S3-B
STAIR
HAC
ELEC.
WOMEN'S
RESTROOM
MEN'S
RESTROOM
C2
CORRIDOR
C5
CORRIDOR
C5
CORRIDOR
C5
CORRIDOR
TR
C2
CORRIDOR
VENDING
C4
CORRIDOR
CLASSROOM
(17)
P-609
FD2
VTR
1"
1"
FD2
P-804
2" VR
V
V
DN0.5" DCW
E2
FREIGHT
ELEVATOR
227A
ELEV.
SERVICE
CLASSROOM
(17)
2" VR
VTR
V
A P601
CONFERENCE
ROOM
A. REFER TO SHEET P001 FOR ABBREVIATIONS, SYMBOLS & INDEX OF DRAWINGS.
GENERAL NOTES
S.
#062-073523
REGISTERED
PROFESSIONAL
ENGINEER
OF
SIGER DERET
WE
H
T T
A M
GRAH
A
M
NO I S
ILLI
2021-05099
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
PROJECT NO.
C
B
IM
\M o d e l\
-0
-P lu m b in g C e n tr a l_ rl c o n d y .r v t
/2
/2
:1
:5
P M
PL102
PLUMBING SECOND FLOOR PLAN - NEW
WORK
VAMC
02/23/2022 KMB RLC
EHRM TRAINING AND ADMIN SPACE 578-21-706
HINES, IL.
BID DOCUMENTS
EDWARD HINES
JR. VAMC
2021-05099
N
1/8" = 1'-0"
SECOND FLOOR PLAN - NEW WORK
KEYPLAN
PLAN NOTES
1. PROVIDE 1" STUB FOR HVAC EQUIPMENT. PIPING TO BE CONTINUED/ COORDINATED
PER DIVISION 23.
2. PIPING LOCATED IN CHASE/ WALL ABOVE FLOOR SLAB.
F G
P-610
P-107
P-107
P-107
P-201
P-201
P-107
P-107
P-107
P-524
P-809
P-107
P-107
P-418
P-418
P-418
P-418
P-418
P-418
P-418
P-418
P-502
FD1
FD1
FD1
F…