These construction documents are detailed electrical drawings for the Mammoth Cave Hotel generator and electrical upgrade project at Mammoth Cave National Park. The drawings comprehensively illustrate the electrical system modifications, including replacing the existing visitor center generator, installing a new 450kW generator, replacing the service transformer, constructing new utility infrastructure, and upgrading electrical distribution equipment. Key technical elements include installing a new automatic transfer switch (ATS-1), a pad-mounted transformer (T-1), a new 120/208V electrical service, underground conduit routing, and modifications to existing electrical panels and utility connections. The drawings provide extensive technical details such as grounding methods, conduit specifications, transformer mounting details, and utility yard configurations, with multiple sheets covering site plans, demolition plans, electrical one-line diagrams, and specific equipment installation specifications.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Additional_Questions_and_Answers_0002.pdf | ||
| Sol_140P5325R0002_Amd_0002.pdf | ||
| Questions_and_Answers_0001.pdf | ||
| Pre_Bid_Site_Visit_Sign_in_sheet_0001.pdf | ||
| Sol_140P5325R0002_Amd_0001.pdf | ||
| Generator_Cut_Sheets_0001.pdf | ||
| Attachment_8_-__Limitation_on_Subcontracting_Report_Template.xlsx | XLSX spreadsheet | |
| Attachment_3_-_PRICE_SCHEDULE_.pdf | ||
| Attachment_6_-_Wage_Determination_4-11-2025.pdf | ||
| Attachment_4_-_Past_Performance_Questionnaire.doc | DOC document | |
| Attachment_1_-_Specifications_4-7-2025.pdf | ||
| Attachment_7_-_Construction_Contract_Administration.docx | DOCX document | |
| Attachment_5_-_Relevant_Prior_Experience.docx | DOCX document | |
| Sol_140P5325R0002.pdf | ||
| Attachment_9_-_GFP_Listing_Generac_SD0500_Generator.pdf | ||
| Attachment_10_-_IT_Security_and_Facility_Access_Instructions.pdf |
Show all 16
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FINAL CONSTRUCTION DOCUMENTS
X0.0
X0.0
F
B
M
J
J
J
J
J
TR
EGS
T
V
VS
A
AS
C
T
KK
H
PM
GEN
M
R
EQ
E UG
I
G
P
G
INDICATES GROUND CONDUCTOR
INDICATES NEUTRAL CONDUCTOR
INDICATES NUMBER OF CONDUCTORS
PNL. A1 INDICATES PANEL AND CIRCUIT
POLE MOUNTED METER E = ELECTRIC POWER
T = TELEPHONE
UG = UNDERGROUND (TRENCH)
OH = OVERHEAD
DD = UNDERGROUND
(DIRECTIONALLY DRILLED)
D = DATA
SITE SYMBOLS
PA PUBLIC ADDRESS
POWER UNIT
PULL BOX/PUSHBUTTONPB
PBPU PREFABRICATED BEDSIDE PATIENT
TRANSIENT VOLTAGE SURGE SUPPRESSION
REMOTE GROUND INDICATOR PANEL
UNLESS NOTED OTHERWISE
W
X
WT
WS
WP
W/
TVSS
RGIP
UNO
RECEP
VP
V
UC
UH
SS
STA
TEL
TV
SIG
WIRE
WALL SURFACE
WATER TIGHT
EXISTING
WEATHERPROOF
WITH
UNDER COUNTER
SAFETY SWITCH
TELEPHONE
RECEPTACLE
VAPOR PROOF
UNIT HEATER
TELEVISION
VOLTAGE
STATION
SIGNAL
POWER TYPE ROOF VENTILATOR
POWER OPERATED DAMPER
PLBG
PWR
PTRV
POD
PLUMBING
POWER
TRANSFORMER
EXPLOSION PROOF
XFMR
XP
PH PHASE
PDU POWER DISTRIBUTION UNIT
PC PLUMBING CONTRACTOR/PHOTOCELL
POTENTIAL TRANSFORMERPT
RECESSEDREC
REQUIRED
RELOCATEREL
REQD
REDUCED VOLTAGE AUTO TRANSFORMERRVAT
SWITCHBOARD
STARTER
SWITCH
SWITCHGEARSWGR
SWBD
STR
SW
SPECIFICATION
SIMILAR
SPEC
SIM
SHEETSHT
TO FLOOR ABOVE
TO FLOOR BELOW
TFA
TFB
TAMPER SWITCH/TIME SWITCHTS
TYPICAL
TELEVISION TERMINAL CABINET
TYP
TVTC
UNDERGROUNDUG
UNINTERRUPTED POWER SUPPLYUPS
VARIABLE FREQUENCY DRIVEVFD
PANELPNL
POWER FACTORPF
- ELECTRICAL METALLIC TUBINGEMT
-BATS BYPASS AUTOMATIC TRANSFER SWITCH
DIRECT CURRENTDC -
F/FC
FSCP
GEN
GTB
GFI
GND
F/FW
F/FF
FDS
FACP
FCU
FIXT
FSS
FLUOR
FS
FL
FI
FA
FLUSH WITH FINISHED WALL
FLUSH WITH FINISHED FLOOR
FLUSH WITH FINISHED CEILING
FUSED DISCONNECT SWITCH
FLAME SAFEGUARD CONTROL PANEL
FUSED SAFETY SWITCH
FIRE ALARM CONTROL PANEL
GROUND FAULT INTERRUPTER
GROUND TERMINAL BOX
GENERATOR
GROUND
FLOW SWITCH
AT FLOOR LINE
FLUORESCENT
FAN COIL UNIT
FIRE ALARM
FILM ILLUMINATOR
FIXTURE
ECP
ELL
ELP
EQUIP
ETR
EDB
ELEC
EWC
ESM
EMER
EG
EJ
BFL
BPIP
CCT
CCTV
CLG
ATS
CB
CCT BKR
ECL
DB
EC
C
BC
ADO
AFF
AT
AF
AC
BELOW FLOOR LEVEL
EMERGENCY LIFE SAFETY LIGHTING
EMERGENCY CRITICAL POWER
EMERGENCY LIFE SAFETY POWER
EMERGENCY CRITICAL LIGHTING
EXISTING TO REMAIN
CLOSED CIRCUIT TELEVISION
BOILER PLANT INSTRUMENTATION PANEL
AUTOMATIC TRANSFER SWITCH
ELECTRIC STRIP MOLD
ELECTRIC WATER COOLER
EQUIPMENT GROUND
ELECTRIC DUCT BANK
EQUIPMENT
ELECTRIC/ELECTRICAL
EMERGENCY
EXPANSION JOINT
DIRECT BURIAL
CONDUIT
BARE COPPER
CIRCUIT BREAKER
CIRCUIT BREAKER
EMPTY CONDUIT/ELECTRICAL CONTRACTOR
CEILING
CIRCUIT
ABOVE FINISHED FLOOR
AUTOMATIC DOOR OPENER
ABOVE CEILING/ALTERNATING CURRENT
AMPERE TRIP
AMPERE FRAME
CONTRACTING OFFICER FURNISHED
CONTRACTING OFFICER FURNISHED
NON-FUSED DISCONNECT
MUSIC & PAGE TERMINAL BOX
MAIN DISTRIBUTION PANEL
MOTOR CONTROL CENTER
MAIN CIRCUIT BREAKER
MASTER ANTENNA TELEVISION
LOCAL TEMPERATURE CONTROL PANEL
HAND OFF AUTOMATIC
NON-FUSED SAFETY SWITCH
MTG HGT
OFOI
OFCI
NFD
NFSS
P
MPTB
LTCP
MCB
MCC
MDP
MLO
MATV
MTD
MH
LTS
LV
LTG
MOUNTING HEIGHT
CONTRACTOR INSTALLED
POLE
LOW VOLTAGE
MAIN LUGS ONLY
MOUNTED
MANHOLE
LIGHTS
LIGHTING
HOA
INCAND
HP
HV
HH
INCANDESCENT
HIGH VOLTAGE
HORSE POWER
HANDHOLE
AMPERES-A
ALTERNATE
ABOVE SUSPENDED CEILING
ARCH
ASC
AIC
ALT
ARCHITECTURAL
AMP INTERRUPTING CAPACITY
AUTOMATICAUTO -
BFC BELOW FINISH CEILING-
BUILDINGBLDG -
BREAKERBRKR -
CONTRACTOR FURNISHED, CONTRACTORCFCI -
INSTALLED
CO CONDUIT ONLY-
CONTR CONTRACTOR-
CORR CORRIDOR-
DED DEDICATED-
DET DETAIL-
DIA DIAMETER-
DISC DISCONNECT-
DN DOWN-
DP DISTRIBUTION PANEL-
CT
CR
CURRENT TRANSFORMER
CONTROL RELAY
EMI ELECTROMAGNETIC INTERFERENCE-
ENGINE GENERATOR SETEGS -
FLEX
FLR
FLA
FLEXIBLE
FLOOR
FULL LOAD AMPERES-
FDR FEEDER--
FULL VOLTAGE NON-REVERSINGFVNR --
GROUND FAULT PROTECTION
GROUND FAULT CIRCUIT INTERRUPTER
GENERAL CONTRACTOR
GFP
GC
GFCI
HEIGHT/HEAT TRACEHT -
INTERMEDIATE METAL CONDUITIMC -
KILOVOLT-AMPERES
KILOWATT HOURS
KILOWATTS
KILOVOLT
KWH
KVA
KW
KV
LIGHT
LOCAL AREA NETWORK
LGT
LAN
MOUNTINGMTG
MECHANICAL CONTRACTORMC
MOTOR CIRCUIT PROTECTORMCP
MECHANICAL EQUIPMENT ROOMMER
MOTOR/METERMTR
NEW CONNECTION/NORMALLY CLOSED
NOT APPLICABLE
NC
NA
NOT IN CONTRACT
NORMALLY OPEN
NOT TO SCALE
NO
NTS
NIC
ON CENTEROC
- DISCONNECT SWITCHDS
ELECTRICAL ABBREVIATIONS
SYMBOLS INDICATED HERE AND NOT USED IN THE CONTRACT DOCUMENTS DO NOT APPLY TO
THIS PROJECT. ADDITIONAL SYMBOLS MAY BE INDICATED IN THE CONTRACT DOCUMENTS.
1.NOTES:
ELECTRICAL SYMBOLS AND ABBREVIATIONS
SHEET SYMBOLS
EQUIPMENT DESIGNATION
TOP DESIGNATES EQUIPMENT ABBREVIATION
BOTTOM DESIGNATES EQUIPMENT NUMBER
DETAIL REFERENCE TOP DESIGNATES
DETAIL NUMBER BOTTOM DESIGNATES
ON WHICH SHEET DETAIL APPEARS
ELEVATION DESIGNATION
PLAN CONTINUATION DESIGNATION
REVISION NUMBER DESIGNATION
LINE CONTINUE BREAK
NEW WORK CONNECTION TO EXISTING
WORK DESIGNATION
NOTE DESIGNATION
SECTION REFERENCE TOP DESIGNATES
SECTION NUMBER BOTTOM DESIGNATES
ON WHICH SHEET SECTION APPEARS
EQUIPMENT AND WIRING
MANUAL STARTER W/OVERLOAD PROTECTION
TRANSFORMER
TRANSFORMER - ONE LINE DIAGRAM
GROUND CONNECTION
NON FUSED DISCONNECT SWITCH
FUSED DISCONNECT SWITCH
BREAKER DISCONNECT SWITCH
MAGNETIC MOTOR STARTER
COMBINATION MOTOR STARTER
SURFACE JUNCTION BOX
SURFACE JUNCTION BOX - WALL
FLUSH JUNCTION BOX - CEILING
FLUSH JUNCTION BOX - WALL
FLUSH JUNCTION BOX - FLOOR
MOTOR
ELECTRIC HEATER
RELAY - TYPE AS NOTED
TIMING RELAY
PANELBOARD - NORMAL
SURFACE MOUNTED
PANELBOARD - NORMAL
FLUSH MOUNTED
PANELBOARD - EMERGENCY/LIFE SAFETY
SURFACE MOUNTED
PANELBOARD - EMERGENCY/LIFE SAFETY
FLUSH MOUNTED
PANELBOARD - CRITICAL
SURFACE MOUNTED
PANELBOARD - CRITICAL
FLUSH MOUNTED
LOW VOLTAGE LIGHTING CONTROL
PANEL - SURFACE MOUNTED
LOW VOLTAGE LIGHTING CONTROL
PANEL - FLUSH MOUNTED
DISTRIBUTION PANELBOARD
MOTOR CONTROL CENTER
CABLE TAP BOX
BUSWAY PLUG-IN UNIT
CURRENT TRANSFORMER
POTENTIAL TRANSFORMER
REVERSE POWER RELAY
REMOTE GENERATOR ANNUNCIATOR
PUSH BUTTON
KIRK KEY INTERLOCK
ENGINE GENERATOR SET
PANEL DIVISION ARROW
LINE VOLTAGE THERMOSTAT
GROUND CONNECTION - PLUG-IN
PHYSIOLOGICAL MONITOR OUTLET
REMOTE GROUND INDICATOR
ROOM REFERENCE GROUND POINT
AIR TERMINAL
VOLTMETER & SELECTOR SWITCH
AMMETER, SELECTOR SWITCH, & CT'S
REVENUE METER, kWh/D
METER WITH CURRENT TRANSFORMER
MOLDED CASE CIRCUIT BREAKER
LOW VOLTAGE DRAW-OUT AIR CIRCUIT BREAKER
SWITCH ONE LINE DIAGRAM
GROUNDED "Y" SYSTEM
AUTOMATIC TRANSFER SWITCH
PANEL DIVISION LINE
WIRING CONCEALED IN FLOOR
WIRING IN CEILING/WALLS
HOMERUN
ISOLATION TRANSFORMER -
ONE LINE DIAGRAM
A-1,3,5 - PANEL AND CIRCUITS; PANEL A, CIRCUITS 1,3,5
T
MCC
JUNCTION BOXJB -
KNOCK-OUTKO -
NATIONAL ELECTRICAL CODENEC
RIGID METAL CONDUITRMC
M
CONTRACTING OFFICER INSTALLED
PULL BOX
PB
EXISTING TO REMAIN ONE-LINE DIAGRAM SYMBOLS
05/30/2023
E5.1
E6.1
E6.1
ATS-1
DISC-1
MAIN DISTRIBUTION
BOARD 'MDP'
(ETR)
REFER TO SHEET
E1.2 FOR
CONTINUATION
T-1
PANEL 'N'
(ETR)
PB
PB
E E E E
E
E
E
E
E
E
E
E E E E E
E
E
EEEE
E
E
E
E
E
EE
E E E E E E UG E UG E UG E
MECHANICAL
EQUIP
E20
EQUIP
E22
SERVICE
E1
PB
(NEW)
(NEW)
(NEW)
FINAL CONSTRUCTION DOCUMENTS
FEET241240
1. PROVIDE AND INSTALL UNDERGROUND
TRENCHED POWER SERVICE DUCT PACKAGE
FROM DIRECTIONAL DRILLING PIT TO
LOW-VOLTAGE TRANSFORMER IN HOTEL
UTILITY YARD. REFER TO SHEET E1.2 FOR
CONTINUATION.
2. PROVIDE AND INSTALL NEW 120/208V
ELECTRICAL SERVICE IN CONDUIT FROM NEW
SERVICE TRANSFORMER TO NEW AUTOMATIC
TRANSFER SWITCH LOCATED IN THE HOTEL
UTILITY YARD. UTILIZE THE EXISTING HOTEL
BASEMENT UTILITY TUNNEL FOR CONDUIT
ROUTING. REFER TO SHEET E7.1 FOR FEEDER
QUANTITIES AND SIZES.
3. PROVIDE AND INSTALL NEW 120/208V
ELECTRICAL SERVICE IN CONDUIT FROM NEW
SERVICE AUTOMATIC TRANSFER SWITCH
LOCATED IN THE HOTEL UTILITY YARD TO
EXISTING MAIN DISTRIBUTION BOARD 'MDP'
LOCATED IN MECHANICAL ROOM 10. REFER
TO SHEET E7.1 FOR FEEDER QUANTITIES AND
SIZES.
1. REFER TO SHEET E0.1 FOR ELECTRICAL
SYMBOLS AND ABBREVIATIONS.
2. DIMENSIONS ARE APPROXIMATE. FIELD
VERIFY PRIOR TO INSTALLATION AND ADJUST
NEW WORK AS NECESSARY TO MEET DESIGN
INTENT.
3. FEATURES SHOWN ON ELECTRICAL PLANS
ARE INDICATED FOR GENERAL REFERENCE
ONLY. CONTRACTOR TO VERIFY EXISTING
CONDITIONS PRIOR TO START OF
UNDERGROUND WORK.
4. NOTIFY AND COORDINATE WITH
CONTRACTING OFFICER IF POWER OUTAGE IS
REQUIRED PRIOR TO OUTAGE.
5. REFER TO SHEET E7.1 FOR ELECTRICAL ONE
LINE DIAGRAM.
GENERAL NOTES
SHEET KEYNOTES
UTILITY BUILDING
DISCONNECT 'DS-1'
(ETR)
EMERGENCY BUILDING
DISCONNECT 'DS-2'
(ETR)
GENERATOR
TERMINATION BOX
450KW GENERATOR
(NEW)
REFER TO SHEET E1.2
FOR CONTINUATION
VISITOR CENTER
ATS
(ETR)
REFER TO SHEET E1.2
FOR CONTINUATION
EUGEUGEUG
E
UG
CHILLER (ETR)
E UG E UG
REFER TO SHEET
E1.2 FOR
CONTINUATION
REFER TO SHEET
E3.1 FOR
CONTINUATION
REFER TO SHEET
E1.2 FOR
CONTINUATION
ATS-1
(NEW)
T-1
(NEW)
DISC-1
(NEW)
EUGUGEUG
UG E UG E UG E UG
E
FINAL CONSTRUCTION DOCUMENTS
SCALE:
E5.1
NOT TO SCALE
VISITOR CENTER UTILITY YARD
SCALE:
E5.1
NOT TO SCALE
HOTEL UTILITY YARD
GENERAL NOTES
1. REFER TO SHEET E0.1 FOR ELECTRICAL
SYMBOLS AND ABBREVIATIONS.
2. DIMENSIONS ARE APPROXIMATE. FIELD
VERIFY PRIOR TO INSTALLATION AND ADJUST
NEW WORK AS NECESSARY TO MEET DESIGN
INTENT.
3. FEATURES SHOWN ON ELECTRICAL PLANS
ARE INDICATED FOR GENERAL REFERENCE
ONLY. CONTRACTOR TO VERIFY EXISTING
CONDITIONS PRIOR TO START OF
UNDERGROUND WORK.
4. NOTIFY AND COORDINATE WITH
CONTRACTING OFFICER IF POWER OUTAGE IS
REQUIRED PRIOR TO OUTAGE.
5. REFER TO SHEET E3.1 FOR HOTEL BASEMENT
POWER PLAN.
6. REFER TO SHEET E7.1 FOR ELECTRICAL ONE
LINE DIAGRAM.
7. REFER TO SHEET E1.1 FOR ELECTRICAL SITE
PLAN.
SHEET KEYNOTES
1. REPLACE EXISTING 275KW VISITOR CENTER
GENERATOR WITH A NEW 450KW
GENERATOR. REUSE EXISTING EQUIPMENT
AND COMPONENTS ASSOCIATED WITH THE
GENERATOR AS MUCH AS POSSIBLE FOR
NEW GENERATOR INSTALL. COORDINATE
WITH GENERATOR MANUFACTURER. REFER
TO SHEET E7.1 FOR ELECTRICAL ONE LINE
DIAGRAM.
2. EXISTING PROPANE TANK. CONTRACTOR TO
VERIFY LOCATION, UTILITY ROUTING AND
FUTURE TANK EXPANSION WITH
CONTRACTING OFFICER PRIOR TO
CONSTRUCTION.
3. EXISTING TO REMAIN CHILLER 'CH-1'.
CONTRACTOR TO VERIFY LOCATION PRIOR
TO CONSTRUCTION.
4. PROVIDE AND INSTALL CONCRETE PAD,
DISCONNECT 'DISC-1', TRANSFORMER 'T-1'
AND AUTOMATIC TRANSFER SWITCH 'ATS-1' IN
HOTEL UTILITY YARD. COORDINATE EXACT
LOCATION WITH CONTRACTING OFFICER AND
EQUIPMENT MANUFACTURER REQUIREMENTS
PRIOR TO INSTALL. REFER TO SHEET E8.1
FOR DETAILS.
5. EXISTING TO REMAIN CONDUIT SERVING THE
VISITOR CENTER ELECTRICAL EQUIPMENT.
6. EXISTING TO REMAIN VISITOR CENTER
CHILLER.
u w _J w u _J <[_ z
LL
co OCl / <C u o_ n" u f- :::i
<L
I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I 11 I I[ I I 11 I I I I I I
I I I I I I I I I I I I I I I I I I I I I I
I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I
J J J J J J J J J J J I �A��o� cl.lEI J J J J j j
I I I I I I I I I I I I I I I I HOTEL(ETR) I I I I I I
I I I 11 II I I I I I I I I I I I I I I I I I I I I
I' I' I I I' I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I
I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I I j I j I j I I I I I I I I
GRADE
MIN.
42" MIN.
COVER 7"
t.-_________ _, 8
.5
" ====--=---h--- ----r---+-
:' r .! . ') ::\::·:<-::+,:/.:::;:;:_ �6"MIN.
8.25"
#4 TIE BARS
@ 2'-6" ON CENTE
GENERAL NOTES
1. REFER TO SHEET E0.1 FOR ELECTRICAL
SYMBOLS AND ABBREVIATIONS.
2. REFER TO SHEET E1 .2 FOR SITE PLAN.
3. REFER TO SHEET E7.1 FOR ELECTRICAL ONE
LINE DIAGRAM.
I ,_ §l 1 1 _.JI, ll_iJ_U I L_i_ L -"-' • , L--, U- I_._LI c==----
12" MAX
#4REBAR
SEE NOTE 2
LOCAL UTILITY COMPANY
REQUIREMENTS
NOTES:
I I l===a===a=='----, I
I I
: .:-, �---�I� ; -- � .- �-
• , • ·-�----,,:1' " • � •. ,;
1. COORDINATE NEW CONDUIT ROUTING WITH CONTRACTING
OFFICER PRIOR TO INSTALLATION.
2. REFER TO CIVIL DRAWINGS FOR PHOTOS OF EXISTING UTILITY
TUNNEL.
3. NEW PULLBOX FOR (6 SETS) OF 4" CONDUITS FROM NEW UTILITY
SERVICE DISCONNECT SWITCH TO NEW AUTOMATIC TRANSFER
SWITCH 'ATS-1' IN HOTEL UTILITY YARD. REFER TO SHEETS El.2 &
E3.1 FOR CONTINUATION OF ROUTING,
�j ;!�����?
HOTEL UTILITY TUNNEL NODE - FACING NORTH
5'-9"
NOTES:
1. PRIOR TO CONSTRUCTION, VERIFY EXISTING CONDITIONS AND LOCATIONS ..
SEE NOTE 5
2, (2) EXISTING TO REMAIN PIPES ENTERING HOTEL BASEMENT SERVICE ROOM E-1
FROM EXISTING CHILLER 'CH-1'.
3. NEW (6 SETS) OF 4" CONDUITS FROM NEW UTILITY SERVICE DISCONNECT
SWITCH TO NEW AUTOMATIC TRANSFER SWITCH 'ATS-1' IN HOTEL UTILITY
YARD. REFER TO SHEET E8.1 FOR ELECTRICAL ONE LINE DIAGRAM, REFER TO
SHEET E3.1 FOR CONTINUATION OF ROUTING.
4. NEW (5 SETS) OF 3" CONDUITS FROM NEW AUTOMATIC TRANSFER SWITCH
'ATS-1' TO EXISTING TO REMAIN MAIN DISTRIBUTION PANEL 'MDP' LOCATED IN
HOTEL MECHANICAL ROOM 10. REFER TO SHEET E8.1 FOR ELECTRICAL ONE
LINE DIAGRAM. REFER TO SHEET E3.1 FOR CONTINUATION OF ROUTING,
5. (2) EXISTING TO REMAIN ELECTRICAL CONDUITS ENTERING HOTEL BASEMENT
SERVICE ROOM E-1 FROM EXISTING CHILLER 'CH-1' DISCONNECT.
6. REFER TO SHEET Cl FOR PHOTOS OF EXISTING CONDITIONS.
NOTES:
2H X 1V
1. PRIOR TO CONSTRUCTION, CONTACT
REPRESENTATIVE TO CONFIRM DUCT
2. PRIOR TO COVERING UTILITY DUCT BANK, CALL LOCAL UTILITIES TO SET
UP A DITCH INSPECTION 48 HOURS IN ADVANCE.
3. H • NUMBER OF DUCTS IN HORIZONTAL PLANE, V - NUMBER OF DUCTS IN
VERTICAL PLANE,
4, POWER DUCT BANKS SHALL BE MARKED WITH A 6" WIDE RED PLASTIC MARKER
STRIP LABELED TO INDICATE "HIGH VOLTAGE" AND PLACED IN THE BACKFILL
APPROXIMATELY 12" ABOVE THE ENTIRE LENGTH OF THE DUCT BANK.
5. UTILITY CONDUITS SHALL BE 4".
6. UTILITY DUCT BANK SHALL BE A MINIMUM OF 42" FROM TOP OF CONDUIT TO
FINISHED GRADE.
7. MINIMUM SWEEPS SHALL BE 36" AND UTILIZE PVC SCHEDULE 80 CONDUIT FOR
ELBOWS.
r 1
, UNDERGROUND DUCT SECTION - UTILITY POLE TO UTILITY TRANSFORMER
' SCALE: NONE
. ,1
MAINTAIN A MINIMUM OF 3 FEET--, ,---1---+ -�-t-t--;-+- EXISTING UTILITIES.
HOTEL UTILITY YARD SECTION - FACING WEST
SCALE, NONE
CLEARANCE WITHIN EXISTING '�
UTILITY TUNNEL.
NOTES:
CHILLER
CH-1
• PULLBOX . .
(ETR)
PULLBOX
(NEW)
NOTE3
PULLBOX
' (NEW) •
NOTE2
, 1. .
:�,�i�.' ,_• :-J��I-• _· __ ••�•�·•��-•-'�" .. •�
NOTES:
--...._ {NEW) 4" CONDUITS FROM
SERVICE TRANSFORMER
TO ATS-1.
DIAGRAMMATIC ONLY.
SEE E7.1 FOR MORE INFORMATION.
1. COORDINATE NEW CONDUIT ROUTING WITH CONTRACTING OFFICER PRIOR TO
INSTALLATION.
2. MAINTAIN EXISTING CLEARANCE IN UTILITY TUNNEL.
3. REFER TO SPECIFICATION SECTION 26 05 29 FOR HANGER AND SUPPORT
REQUIREMENTS.
4. REFER TO SPECIFICATION SECTION 26 05 33 FOR RACEWAY REQUIREMENTS .
5. REFER TO CIVIL DRAWINGS FOR PHOTOS OF EXISTING UTILITY TUNNEL,
1. PRIOR TO CONSTRUCTION, VERIFY EXISTING CONDITIONS AND LOCATIONS ..
2. NEW PULLBOX FOR (6 SETS) OF 4" CONDUITS FROM NEW UTILITY SERVICE
DISCONNECT SWITCH TO NEW AUTOMATIC TRANSFER SWITCH 'ATS-1' IN HOTEL
UTILITY YARD. REFER TO SHEET E8.1 FOR ELECTRICAL ONE LINE DIAGRAM.
REFER TO SHEET E3,1 FOR CONTINUATION OF ROUTING.
·, EXISTING HOTEL UTILITY TUNNEL SECTION - FACING WEST
1 SCALE: NONE
3. NEW PULLBOX FOR (5 SETS) OF 3" CONDUITS FROM NEW AUTOMATIC TRANSFER
SWITCH 'ATS-1' TO EXISTING TO REMAIN MAIN DISTRIBUTION PANEL 'MDP'
LOCATED IN HOTEL MECHANICAL ROOM 10. REFER TO SHEET E8.1 FOR
ELECTRICAL ONE LINE DIAGRAM. REFER TO SHEET E3.1 FOR CONTINUATION OF
ROUTING.
4. REFER TO SHEET Cl FOR PHOTOS OF EXISTING CONDITIONS, ( 4 '\ HOTEL SERVICE ROOM E-1 SECTION - FACING EASTV SCALE: NONE
FINAL CONSTRUCTION DOCUMENTS
</E FIRM DESIGNED, SUB SHEET NO TITLE OF SHEET DR.�_Wli'IG NO.
PRIME AP
VHB 1��E0
WILLI.AMSBURG, VA
SUB
AEI
MADISON, WI
l
TECH. REVIEW,
SE
DOTE.
\'AY 7023 _______J_
ELECTRIC,L,L SECTIONS
0 L\0 �RIM<RY ELECTRIC EQUIPMENT
xxxxxx
PMIS/PKG NO.
2 1188 110
SHEET
<.T M L.MMOTH CAVE HOTEL
lv'.'MMC'TH CAVE i!t TIO,\leL PARK 1 7 OF 2 0
- -- - -- - -- , _____ .'::_'_.':"_"'_ __ _ _J_==-=-====!
EGS
F
F
SCALE:
E7.1
NOT TO SCALE
ELECTRICAL ONE LINE DIAGRAM
F
F
(NEW) [6 SETS] 3#500KCMIL,
1#500KCMIL N, 1#350KCMIL G
IN 4" CONDUIT
L = 450FT, VD = 2.7%
(NEW) PROVIDE [3 SETS] 3#400KCMIL,
1#400KCMIL N, 1#1/0 G IN 3" CONDUIT.
L = 10FT, VD = 0.1%
(NEW) [5 SETS] 3#400KCMIL,
1#400KCMIL N, 1#4/0 G, 3"C.
L = 122FT, VD = 1.07%
(NEW) PROVIDE [2 SETS] 3#250KCMIL,
1#2G IN 2-1/2" CONDUIT.
L = 450FT, VD = 1.2%
(NEW) 500A, 3P BREAKER
IN GENERATOR
TERMINATION BOX
GENERAL NOTES
1. REFER TO SHEET E0.1 FOR ELECTRICAL
SYMBOLS AND ABBREVIATIONS.
2. REFER TO SHEET E1.2 FOR ELECTRICAL SITE
PLAN.
3. ELECTRICAL ONE LINES SHOW EXISTING TO
REMAIN ELECTRICAL DISTRIBUTION SYSTEM
(ETR). NEW WORK (NEW) AS INDICATED ON
DRAWINGS.
4. NO SERVICE SHALL BE INTERRUPTED OR
CHANGED WITHOUT WRITTEN PERMISSION
FROM CONTRACTING OFFICER.
5. ADJUST TRANSFORMER TAPS AS NECESSARY
TO ACHIEVE PROPER OPERATING VOLTAGE.
SHEET KEYNOTES
1. REPLACE EXISTING BREAKER IN
GENERATOR TERMINATION BOX WITH NEW
500A BREAKER. CONTRACTOR TO FIELD
VERIFY CONDITION AND AMPERAGE OF
EXISTING BREAKER. EXTEND EXISTING
FEEDERS TO NEW BREAKER.
2. PROVIDE AND INSTALL 2H X 1V CONCRETE
ENCASED POWER SERVICE PRIMARY DUCT
PACKAGE FROM EXISTING UTILITY POLE TO
NEW SERVICE TRANSFORMER. COORDINATE
DUCT REQUIREMENTS WITH LOCAL
UTILITIES REPRESENTATIVE PRIOR TO
CONSTRUCTION. REFER TO DUCTBANK
SECTION 1/E6.1 AND DETAILS ON SHEET
E8.1. CONDUCTORS SHALL BE PROVIDED
AND INSTALLED BY LOCAL UTILITY
COMPANY.
3. PROVIDE AND INSTALL AN EXTERNALLY
MOUNTED SURGE PROTECTION DEVICE
(SPD) AND SWITCH. COORDINATE
REQUIREMENTS WITH MANUFACTURER.
REFER TO SPECIFICATION SECTION 26 43 00
FOR SPD REQUIREMENTS.
4. UTILIZE EXISTING SPARE 20A, 1PH BREAKER
TO SERVE PAVILION B. PROVIDE AND
INSTALL CONDUIT AND WIRE FROM
EXISTING PANEL 'N' TO PAVILION B. REFER
TO DETAIL 1/E9.1 FOR PANEL SCHEDULE.
(NEW) 1600A
UTILITY RATED ATS
ATS-1 (NEMA 3R)
120/208V
4-POLE
M
(NEW) PAD MOUNTED
TRANSFORMER BY LOCAL
UTILITY COMPANY
12.5kV:208Y/120V
3PH, 4W, 500KVA
(NEW) SECONDARY METER
LOCAL UTILITIES
CONTRACTING
OFFICER
DEMARCATION
MAMMOTH CAVE
NATIONAL PARK
(NEW) DRY-TYPE
TRANSFORMER T-1
(NEMA 3R)
480/277V:208Y/120V
3PH, 4W, 300KVA
(NEW) 450KW, 480/277V
3PH, 4WIRE
GENERATOR TO REPLACE
EXISTING GENERATOR
TO EXISTING VISITOR
CENTER ELECTRICAL
ROOM
6. WHERE NEW WORK INTERFERES WITH
CONTRACTING OFFICER'S USE OF PREMISES,
SCHEDULE WORK THROUGH CONTRACTING
OFFICER TO MINIMIZE INCONVENIENCE TO
CONTRACTING OFFICER. CONTRACTING
OFFICER MUST APPROVE SCHEDULE IN
WRITING BEFORE CONTRACTOR BEGINS ANY
SUCH WORK.
SPD
(NEW)
GENERAL NOTES (CONT.)
1600AS
1600AF
(NEMA 3R)
(NEW)
DISC-1 (NEMA 3R)
600AS
500AF
(NEW)
500A/3P
(ETR)
VISITOR CENTER ATS
(NEMA 3R)
277/480V
(ETR)
VISITOR CENTER
'DS-2'
(ETR)
VISITOR CENTER
'DS-1'
VISITOR CENTER
UTILITY SOURCE
HOTEL
UTILITY SOURCE
SCALE:
TYPICAL DRY TYPE TRANSFORMER GROUNDING 1
NONE
SCALE:
MOUNTING AND CONNECTION DETAIL3
NONE
SCALE:
DISCONNECT SWITCH MOUNTING DETAIL2
NONE
SCALE:
2 HOUR FIRE RATED GYPSUM WALLBOARD WALL5
NONE
SCALE:
MULTIPLE CONDUITS SINGLE ARRAY THROUGH GYPSUM WALL ASSEMBLY (1 OR 2-HR.)4
NONE
GENERAL NOTES
1. REFER TO SHEET E0.1 FOR ELECTRICAL
SYMBOLS AND ABBREVIATIONS.
TYPICAL DRY TYPE TRANSFORMER 480V DELTA PRIMARY
208Y/120V SECONDARY - SEE SPECIFICATIONS.
L1
L2
L3
0A
0B
0C
N
LOAD
SIDE
LINE
SIDE
GND.
TRANSFORMER HOUSING
GROUND TO ELECTRICAL ROOM GROUND BUS.
FURNISH AND INSTALL A COPPER
EQUIPMENT GROUND BAR KIT WITH
INDIVIDUAL TERMINALS FOR EACH
GROUNDING CONDUCTOR.
SECURELY MOUNT IN ACCESSIBLE
SPACE AT TRANSFORMER TERMINAL
COMPARTMENT. SIZE GROUND BAR
KIT TO ACCOMMODATE MAXIMUM AND
MINIMUM GROUND CONDUCTOR SIZES
FOR EACH GROUND TERMINAL.
VIBRATION ISOLATORS
RUBBER IN-SHEAR
2'-0" MIN.
ALL CONNECTIONS
CONDUIT
FLEXIBLE
CONCRETE
XFMR
HOUSEKEEPING PAD
CONDUIT SIZED AND
ROUTED TO EQUIPMENT
PER NEC
G R
A D
E
M
A X
DISCONNECT SWITCH
UNISTRUT FRAME
GALVANIZED
CONCRETE (TYPICAL)
FEED PER NEC
ROUTED TO POWER
CONDUIT SIZED AND
A
B O
V E
F
I N
I S
H E
D
6" MIN. 6" MIN.
3/4" (19mm) THICKNESS OF FIRE-RATED
CAULK OR PUTTY FLUSH TO EXTERIOR OF
GYPSUM PANEL SURFACE
WALL OR STEEL STUD
CONDUIT
SECTION VIEW
NOTES:
INSTALL FIRESTOP ON BOTH SIDES
OF WALL.
RECOMMENDATIONS BASED ON PRODUCT
PERFORMANCE PER ASTM E-814 (UL 1479)
TIME TEMPERATURE FIRE ENCLOSURE CURVE.
OPTIONS FOR MASKING TAPE TO PREVENT
SAGGING:
INSTALL ADDITIONAL DAMMING MATERIAL INSIDE
WALL AND OVER PRODUCT TO HOLD WITHIN
OPENING.
REMOVE PRODUCT FROM CONTAINER AND ALLOW
TO AIR CURE IN SMALL BATCHES FOR 12 HOURS,
THEN HAND FORM INTO OPENING.
(1)
(2)
(3)
A.
B.
2 HOUR RATED WALL
2 LAYERS OF 5/8" (16mm)
THICK GYPSUM WALLBOARD
1/4" MIN.
1/2" MAX.
1/2" (13mm) THICKNESS OF
NON-COMBUSTIBLE MINERAL
WOOL OR BACKER ROD
(SEE NOTE 3)
OR CAULK IF IT OCCURS
TO PREVENT SAGGING,
CURED (24-72 HOURS)
OR BACKER ROD UNTIL
WITH MASKING TAPE
COVER CAULK SURFACE
SINGLE CONDUIT PENETRATION OF
A
ASECTION A-A
NOTES:
1. WALL ASSEMBLY — THE 1 OR 2 HR FIRE-RATED GYPSUM WALLBOARD/STUD WALL
ASSEMBLY SHALL BE CONSTRUCTED OF THE MATERIALS AND IN THE MANNER
SPECIFIED IN THE INDIVIDUAL U300 OR U400 SERIES WALL AND PARTITION DESIGNS
IN THE UL FIRE RESISTANCE DIRECTORY.
2. THROUGH PENETRANTS — ONE OR MORE PIPES OR CONDUITS INSTALLED IN
SINGLE LAYER ARRAY WITHIN THE FIRESTOP SYSTEM. THE ANNULAR SPACE AT
PERIMETER SHALL BE MAX. 1-1/4", THE SPACE BETWEEN CONDUITS OR TUBING
SHALL BE 1/4" TO MAX. 1".
1-HR OR 2-HR FIRE RATED GYPSUM
WALLBOARD/STUD WALL ASSEMBLY:
a. STEEL STUDS (MIN. 3-5/8" @ MAX. 24" O.C.)
b. GYPSUM BOARD - TYPE AND NO. OF
LAYERS PER FIRE RATING.
MAX OPENING AREA IS 62 SQ IN W/ MAX.
DIMENSION 22-1/2".
SEALANT - MIN 5/8" THICKNESS INSTALLED
TO COMPLETELY FILL ANNULAR SPACE
BETWEEN PIPES, CONDUITS AND GYPSUM,
FLUSH WITH EACH SURFACE OF WALL.
MIN 1/2" DIAM BEAD OF FILL MATERIAL
APPLIED TO THE THROUGH
PENETRANT/WALL INTERFACE AT THE
POINT CONTACT LOCATIONS ON BOTH
SIDES OF THE WALL.
METAL PIPE
TYPE MAX DIA.
STEEL CONDUIT 2"
EMT 2"
DRY TYPE TRANSFORMER
SCALE:
E9.1
NOT TO SCALE
PANEL 'N' SCHEDULE
SCALE:
E9.1
NOT TO SCALE
PANEL 'N' PHOTOS - EXISTING CONDITIONS