Additional_Questions_and_Answers_0002.pdf
PDF 119 KB Posted
- Attached to
- MACA-INSTALL HOTEL GENERATOR/UPGRADE ELE Federal contract opportunity
- Solicitation number
- 140P5325R0002
About this file
This document is an Amendment 2 to a federal contract opportunity, providing additional questions and answers regarding a generator replacement project. The Q&A clarifies details about a diesel generator with an integrated 1,001-gallon sub-base fuel tank, addressing vendor inquiries about the tank's configuration, weight, and fueling arrangements. The key details include confirmation that the "black frame" is actually the fuel tank, which will remain in place as part of the permanent installation, and the combined weight of the generator and sound-attenuated enclosure is approximately 15,311 lbs (6,945 kg). The tank meets UL-142 standards and includes necessary fittings and monitoring features for diesel operation, eliminating the need for separate fueling infrastructure.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Sol_140P5325R0002_Amd_0002.pdf | ||
| Questions_and_Answers_0001.pdf | ||
| Pre_Bid_Site_Visit_Sign_in_sheet_0001.pdf | ||
| Sol_140P5325R0002_Amd_0001.pdf | ||
| Generator_Cut_Sheets_0001.pdf | ||
| Attachment_8_-__Limitation_on_Subcontracting_Report_Template.xlsx | XLSX spreadsheet | |
| Attachment_2_-_(DRAWINGS)_MACA_Hotel_Gen_248840_4-7-2024.pdf | ||
| Attachment_3_-_PRICE_SCHEDULE_.pdf | ||
| Attachment_6_-_Wage_Determination_4-11-2025.pdf | ||
| Attachment_4_-_Past_Performance_Questionnaire.doc | DOC document | |
| Attachment_1_-_Specifications_4-7-2025.pdf | ||
| Attachment_7_-_Construction_Contract_Administration.docx | DOCX document | |
| Attachment_5_-_Relevant_Prior_Experience.docx | DOCX document | |
| Sol_140P5325R0002.pdf | ||
| Attachment_9_-_GFP_Listing_Generac_SD0500_Generator.pdf | ||
| Attachment_10_-_IT_Security_and_Facility_Access_Instructions.pdf |
Show all 16
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
140P5325R0002
MACA Replace Generator
Additional Questions and Answers
Amendment 2
1. Question: You have provided a cut sheet for the generator. It says fuel tank (if selected). The cut sheets are for a diesel generator but do not provide any additional information on a fuel tank. Was one selected ? We would think the "black frame" questioned in Question #11 of the Questions and Answers is probably the location of the fuel tank for this generator. However, the answer says it was solely for transport. Please advise.
a. Answer: Yes, a 1,001-gallon sub-base fuel tank was selected and is integrated into the generator assembly. The “black frame” referenced in Question #11 is not a transport frame — it is the fuel tank and is intended to remain in place as part of the permanent installation.
2. Question: If the black frame is actually the fuel tank, what is the weight of both components combined?
a. Answer: The combined weight of the generator integrated 1,001-gallon fuel tank, and aluminum Level 2 sound-attenuated enclosure is approximately 15,311 lbs. (6,945 kg).
3. Question: If the black frame is truly only for transport, what are the arrangements for fueling this diesel-powered generator?
a. Answer: Since the black base is the integrated fuel tank, no separate fueling infrastructure is required. The generator is fueled directly through the sub-base tank, which meets UL-142 standards and includes all necessary fittings and monitoring features for diesel operation.