Attachment 1(a) - Drawings.pdf

PDF 6 MB Posted

Attached to
Amendment 0004 to Replace Parking Lot Lighting at Seattle Air Traffic Facility Federal contract opportunity
Solicitation number
697DCK-23-R-00332
Issued by
Department of Transportation Federal Aviation Administration Northwest Mountain Region

View the file

Other files for this federal contract opportunity

Other files attached to Amendment 0004 to Replace Parking Lot Lighting at Seattle Air Traffic Facility, newest first.
File Type Posted
697DCK-23-R-00332 Amendment 0004.pdf PDF
Attachment 11 - Drawing ZSE-20006240-E204 - Revised 5-24-2023.pdf PDF
697DCK-23-R-00332 Amendment 0003.pdf PDF
Attachment 10 - Grounding Grid Layout.pdf PDF
697DCK-23-R-00332 Amendment 0002.pdf PDF
697DCK-23-R-00332 Amendment 0001.pdf PDF
Attachment 2 - REF FAA-C-1217h.pdf PDF
RFO 697DCK-23-R-00332.pdf PDF
Attachment 1 - Specifications.pdf PDF
Attachment 6 - REF FAA Order 3900.19b.pdf PDF
Attachment 7 - COVID-19 Contractual Requirement.pdf PDF
Attachment 3 - REF FAA-C-1391e.pdf PDF
Attachment 4 - REF FAA-STD-019f.pdf PDF
Attachment 5 - REF FAA Order 1600.69C.pdf PDF
Attachment 8 - Customer Satisfaction Survey.doc DOC document
Attachment 9 - DB WD No. WA20230011 dated 2-3-2023.pdf PDF
Show all 16

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

For the best experience, open this PDF portfolio in

Acrobat X or Adobe Reader X, or later.

Get Adobe Reader Now!

http://www.adobe.com/go/reader

120/208 400

BUILDING SERVICE BSB2-B Position 37

B119 N Wall

MDP-2

-1

-3

-5

-7

-9

-11

-13

-15

-17

-19

-21

-23

-25

-27

-29

2-

4-

6-

8-

10-

12-

14-

16-

18-

20-

22-

24-

26-

28-

30-

LOAD SYSTEMAMPSAMPSLOADSYSTEM

3_____Wire3_____Phase

480 100

23,000

ESSENTIAL

Bus Rating _________ Amps

Panel No. _________ Service Voltage _______ Volts

Mounting _______________

Bus ______________ Feed __________________

Location ________________

CIRCUIT CIRCUIT

PP-MOV Circuit #20

PUMP HOUSE S Wall

FROM LP-CT)

(WIRES ON 22 & 24, NEUTRAL

SW LOT LIGHTING (ZONE 3)

BLANK

PP-CT

SPARE

PUMP HOUSE HOIST

UNIT HEATER PH-1

VFPH-1 VENT FAN, PUMP HOUSE

HEATER

PNL LP-CT FR 15kVA XFMR

PROPERTY DRIVEWAY

LCV-2 (@ TK-19) IN PIT SW

PUMP 4 (NO WIRES)

AIC Rating _________ Amps

LIGHTS-EXT

CTRB

SUB

HOIST

EQN

CHILR

4_____Wire3_____Phase

120/208 50

PP-CT VIA XFMR TR-CT

PUMP HOUSE S Wall

LP-CT

CHEM FEED PANEL

CONTROLLER, IN THE PSWT PNL

PUMP FILTER, GFCI

PNL LP-CT FR 15kVA XFMR

HEAT TRACE

FCV-6C

OUTLET

SUB

SFAS

EQC

LIGHTING CONTACTOR SW PARKING LOT

COOLING TOWER

FCV-9

OUTLETS ON CHEM FEED BENCH

FCV-6A

CAMERA PTZ IN HOFFMAN BOX W WALL

S CLG TOWER WALL SECURITY LIGHT

FCV-6B

FCV-6DCHILR

-31

32-

34-

36-

38-

40-

-41

-39

-37

-35

-33

4_____Wire3_____Phase 23,000

Wall MountMounting _______________

CONTACTOR D

SW LOT LIGHTS (ZONE 3) VIA SECURITY

SECURITY CONTACTOR C

NORTH MOON LIGHTS VIA

SW LOT LIGHTS (ZONE 5) &

42-

LOADING DOCK LIFT

MAIN LUGS

MAIN LUGS

LIGHT CONTACTOR B

PNL B (RM 104) VIA SECURITY

PANEL B-1003-A

PANEL Y RM B111

ELVTR

PANEL A

SECURITY LIGHTS CONTROL TIMER FOR

z s e -2

-e

.d g n

/1

/2

:1

P M

L o ri D iV a

A

B

C

E

F

G

H

8 7 6 5 4 3 2 1

12345678

REVDRAWING NO

DATE JCN

APPROVED BY

ISSUED BY

CHECKED

DRAWN

DESIGNED

SUBMITTED BY

REVIEWED BY

FEDERAL AVIATION ADMINISTRATION

DEPARTMENT OF TRANSPORTATION

REV

DATE

APPROVED

DESCRIPTION JCN

REDLINE

APVD

IS

S

U

O R

ENGINEERING SERVICES

ENROUTE/FSS

ARTCC

PANELS PP-CT, LP-CT & MDP-2

PANEL SCHEDULES - ZONE 3

UPGRADE PARKING LOT LIGHTING

WAAUBURNSEATTLE

JA

JW

PROJECT ENGINEER MGR: ENGINEERING - SEATTLE

01/12/2023 20006240

ZSE-20006240-E802

DRAWING PRODUCED ON WSA MICROSTATION SYSTEM

ATO - TECHNICAL OPERATIONS WESTERN SERVICE AREA

N

T

IO

ZONE 3 ZONE 3

ZONE 3 (DEMO'D GLOBE LIGHTS)

2023-01-19T09:19:12-0800

Joshua Chua Wu

2023-01-23T05:57:09-0800

CALLEN R COLLINS

-c

:2

VISITOR

PARKING

K

IN

PARKING PARKING

STORAGE

BUILDING

WAAUBURN

01/12/2023

SITE PLAN

SEATTLE

JW 20006240

ZSE-20006240-C001

-c

SCALE: 1" = 50'

50' 100'050'

GENERAL NOTES

ASSOCIATED POWER PANEL.

ZONE TIMER CONTROLLERS ARE CO-LOCATED WITH THE 10.

SCHEDULES.

REFER TO SHEET E601 FOR LIGHT FIXTURE AND LIGHT POLE 9.

BY COR.

POWER SERVICE BUILDING. EXACT LOCATION TO BE DETERMINED

STAGING AREA WILL BE PROVIDED ON THE SOUTH SIDE OF THE 8.

CONDUCTORS, AND TIMERS WHERE NECESSARY.

CONTRACTOR SHALL FURNISH AND INSTALL NECESSARY CONDUITS, 7.

CANDLES PER FAA ORDER 1600.69C.

BEYOND THE PERIMETER FENCING SHALL NOT EXCEED 1.0 FOOT-

SHINING INTO NEIGHBORING PROPERTIES. ILLUMINATION LEVELS

INSTALL GLARING PLATE, DIFFUSER, OR EQUIV. TO PREVENT LIGHT

FOR EACH LIGHT FIXTURE, CONTRACTOR SHALL PROVIDE AND 6.

PART 15 FOR ELECTROMAGNETIC INTERFERENCE.

NEW LIGHT FIXTURES SHALL COMPLY WITH FCC CFR TITLE 47 5.

SHUT-DOWN WITH COR.

ONLY FAA CAN OPERATE CIRCUIT BREAKER. COORDINATE BREAKER 4.

OUTAGES WITH COR.

IMPACT OF DAY TO DAY LIGHTING CONDITIONS. COORDINATE

BY COR. CONTRACTOR SHALL PLAN WORK TO ENSURE MINIMAL

SUNSET, EXCEPT WHERE NEW FEEDER IS REQUIRED OR APPROVED

NO FIXTURES ARE TO BE OUT OF SERVICE BY THE TIME OF 3.

CONTRACTOR SHALL FIELD VERIFY EXISTING CONDITION.

FOUNDATIONS ABOVE GRADE, ACTUAL HEIGHT MAY VARY.

POLES ARE APPROXIMATELY 25' HIGH ON 2' CONCRETE 2.

VERIFY EXISTING CONDITION.

POLE LOCATIONS ARE APPROXIMATE. CONTRACTOR SHALL FIELD 1.

AUBURN WAY SOUTH (WA ST RT. 164)

COOLING

TOWERS

POWER

SERVICE

AAS

CONTROL

WING

ADMIN

AUTO

OPERATIONS

SUPPORT

EMERGENCY GATE

(ABANDONED)

PERSONNEL GATE

CONSTRUCTION GATE

PERSONNEL

GATE

9'H INTERIOR

PERIMETER

SECURITY FENCE

10'H EXTERIOR

12'W SECURITY

FENCE GATE

TOWER

LOADING ZONE

NO PARKING

SECURITY

FENCE

ZONE 2

ZONE 3

ZONE 4

NOT IN SCOPE

LIGHTS PROVIDED UNDER

REPAVING PROJECT

ZONE 6

ADDITION

ZONE 1

ZONE 5

PANEL E-ANTFM

FEEDS ZONE 6

PANELS GH-H & GH-L

FEEDS ZONE 5

PANELS PP-CT & LP-CT

FEEDS ZONE 3

PANEL EOB15A

(IN BASEMENT)

FEEDS ZONE 4

PANEL MDP-2

(IN BASEMENT)

FEEDS GLOBE LIGHTS

PANELS DPE & GLB-1

FEEDS ZONE 1 & 2

LP-1A

LP-1B

LP-1ALP-1ALP-1ALP-1A

LP-1A LP-1A

zse-20006240-c001.dgn 1/18/2023 3:25:22 PM

2023-01-19T08:49:58-0800

Joshua Chua Wu

2023-01-20T13:11:53-0800

CALLEN R COLLINS

:4

LIGHTING DEMOLITION PLAN

ZONE 1 - EAST LOT

ZSE-20006240-E101

SHEET NOTES

BASES, CONDUIT AND CONDUCTORS TO REMAIN.

DISMANTLE LP-1 SINGLE BLADE LIGHT FIXTURES. LIGHT POLES,

FOR ZONE IS FED FROM PANEL GLB-1.15.

ZONE 1, EAST LOT IS FED FROM PANEL DPE.26, 28, 30. TIMER

COORDINATE BREAKER SHUT-DOWN WITH COR.

ONLY FAA PERSONNEL CAN OPERATE CIRCUIT BREAKERS. 2.

OUTAGES WITH COR

IMPACT TO DAY TO DAY LIGHTING CONDITIONS. COORDINATE

NO FIXTURES ARE TO BE OUT OF SERVICE BY THE TIME OF 1.

SCALE: 1" = 25'

25' 50'025'

EXISTING CONDUCTORS

LEGEND

LIGHT POLE SINGLE BLADE LIGHT FIXTURE

LP-1

DPE .26, 28, 30

2023-01-19T08:52:14-0800

Joshua Chua Wu

2023-01-20T13:22:14-0800

CALLEN R COLLINS

EMERGENCY EXIT

B15/RESTROOM

120/208 100

EOB15E Circuit #2

OSW B-15A N Wall

20 SPARE

RM B16C

EOB15A

B05, B06, B08

OSW PARKING (WEST) ZONE 4

TIMER OSW PARKING ZONE 4

RM B16D

LIGHTS

RM B16E

STAIRWELL

RM B04, B16B

RM B16A

BLANKBLANK

OUTLETS

120/208 200

XFMR ANTFM

ANTENNA FARM WEST

E-ANTFM

LIGHTING (ZONE 6)

EXTERIOR SECURITY

TIMER (ZONE 6)

ANTENNA GFI RECEPTICLE

PANELS EOB15A & E-ANTFM

PANEL SCHEDULES - ZONE 4 & 6

ZSE-20006240-E803

ZONE 4 ZONE 6

2023-01-19T09:19:36-0800

Joshua Chua Wu

2023-01-23T05:55:04-0800

CALLEN R COLLINS

:3

PUMP

HOUSE

ZONE 2 - SOUTH LOT

ZSE-20006240-E102

ZONE 2, SOUTH LOT IS FED FROM PANEL DPE.26, 28, 30. TIMER

LP-1LP-1LP-1

1 111

2023-01-19T08:55:45-0800

Joshua Chua Wu

2023-01-20T13:19:13-0800

CALLEN R COLLINS

& CONTACTOR

N. LOT (ZONE 5) LIGHTING

OUTER EXIT BARRIER ARM

OUTER EXIT SWING GATE

INNER ENTRY BARRIER ARM

INNER EXIT BARRIER ARM

3_____Wire3_____Phase

BUILDING SERVICE

BSB1-1 Circuit #19

GUARD HOUSE GH05

OUTER ENTRY SWING GATE

GH-H

OUTER ENTRY BARRIER ARM INNER EXIT SWING GATE

RM B16D

15 15

70 15

INNER ENTRY SWING GATE45kVA XFMR GH-H

120/208 150

XFMR GH-H

GUARD HOUSE GH05

GH-L

W & CENTRAL BLDG

HP-1 INDOOR HEATER

HP-1 OUTDOOR HEATER

OUTDOOR HEATER, WEST SIDE

ELEC RM (GH05)

RESERVED FOR SFAS POWER

E & S/E

CPDS

NEWORK SWITCH SW-5

ACP-1A

HVAC UNIT

NOT USED, SPARE WIRES IN

EWH-125

BUILDING SERVICE

VEHICLE INSPECTION LIGHTING

LIGHTING CONTACTOR

INSIDE LIGHTING

OUTSIDE LIGHTING

PS/ACP

RECPT IN WPNS STRM (GH07)

OUTSIDE MAINT RECPT/SPRINKLER CNTL BOX

REFRIGERATOR

MICROWAVE

COFFEE MACHINE

METAL DETECTOR

X-RAY MACHINE

SERVICE DESK

CONSOLE

RECPTICLE CCTV MONITOR

EF-115

EWH-2

FLAG LIGHTING

SIGN LIGHTING

TELCO CABINET/PAD-3

PANEL SCHEDULES - ZONE 5

ZSE-20006240-E804

ZONE 5 ZONE 5

2023-01-19T09:19:54-0800

Joshua Chua Wu

2023-01-23T05:56:02-0800

CALLEN R COLLINS

ZONE 3 - SOUTHWEST LOT

ZSE-20006240-E103

TIMER FOR ZONE IS FED FROM PANEL LP-CT.18.

ZONE 3, SOUTHWEST LOT IS FED FROM PANEL PP-CT.22,24.

DEMOLISH GLOBE LIGHT POLES, FIXTURES AND BASES.

DISMANTLE LP-1 SINGLE BLADE LIGHT FIXTURES. LIGHT POLES, 1

CHASE.

CONTROL WING ATTIC MECHANICAL ROOM (ROOM 3003) UTILITY

LIGHTS (GL) TO SECURITY PANEL "A", LOCATED IN THE

DEMOLISH EXISTING CONDUCTORS FROM SOUTHWEST GLOBE

5 DEMOLISH EXISTING CONDUCTORS BETWEEN GLOBE FIXTURES.

GLOBE LIGHT FIXTURE

DEMOLISH CONDUCTORS

GL GL

LP-1 LP-1

GL

PP-CT .22, 24

MDP-2.7

2023-01-19T08:56:55-0800

Joshua Chua Wu

2023-01-20T13:20:45-0800

CALLEN R COLLINS

-g

AVIA

I

TRAT

SI

NI

AUBURN, WA

AIR ROUTE TRAFFIC CONTROL CENTER (ARTCC)

T OF TRANSPO

T A

IC

OF

STATES

IT

TM

EN

JW 01/12/2023 20006240

ZSE-20006240-G001

VICINITY MAP AND DRAWING INDEX

COVER SHEET,

AUBURN

WHIT

I V

RIV

AUBURN

GENERAL

DEPOT

1 MILE0 0.5

BU

RL

ING

TO

NO

RT

HE

RN

BNSF RR

AUBURN WAY SO.

PROJECT

LOCATION

AUBURN WASHINGTON

VICINITY MAP

2023-01-19T09:20:16-0800

Joshua Chua Wu

2023-01-23T05:54:22-0800

CALLEN R COLLINS

ZONE 4 - WEST LOT

ZSE-20006240-E104

ZONE IS FED FROM PANEL EOB15A.10.

ZONE 4, WEST LOT IS FED FROM PANEL EOB15A.8. TIMER FOR

DISMANTLE LP-4 FOUR BLADE LIGHT FIXTURES. LIGHT POLES,

DISMANTLE LP-2 DOUBLE BLADE LIGHT FIXTURES. LIGHT POLES,

LIGHT POLE DOUBLE BLADE LIGHT FIXTURE

LIGHT POLE FOUR BLADE LIGHT FIXTURE

LP-2

LP-4

EOB15A.8

1 2

2023-01-19T08:58:20-0800

Joshua Chua Wu

2023-01-20T13:17:40-0800

CALLEN R COLLINS

JW 01/12/2023 20006240

ZSE-20006240-G002

GENERAL/ELECTRICAL NOTES

ABBREVIATIONS, LEGEND AND

BETWEEN BONDED COMPONENTS WITH A 4 TERMINAL MILLIOHMMETER.

GROUND BONDS SHALL HAVE A MAXIMUM DC RESISTANCE OF 1 MILLIOHM WHEN MEASURED 9.

ELECTRODES SHALL BE SPACED NO CLOSER THAN 10'-0" FROM EACH OTHER.

GROUND ELECTRODES SHALL BE 3/4"X10' COPPER CLAD GROUND ROD. GROUND 8.

BARE 4/0 AWG EES CONDUCTOR SHALL BE BURIED A MINIMUM OF 24" BELOW GRADE.7.

LIDS SHALL BE BONDED WITH 6 AWG STRANDED BARE COPPER.

FROM HANDHOLE ELECTRODE OR UFER GROUND STUD WITHIN THE HANDHOLE. METALLIC

AND BE GROUNDED WITH A 6 AWG STRANDED BARE COPPER GROUND. PROVIDE 4/0 AWG

RIGID STEEL CONDUITS TERMINATING IN HANDHOLES SHALL INCLUDE GROUND BUSHINGS 6.

CONDUITS WITH A 2 AWG MINIMUM.

FOR BELOW GRADE CONDUITS, OR TO THE MULTIPOINT SYSTEM FOR ABOVE GRADE

METALLIC CONDUITS PENETRATING FACILITY EXTERIOR WALLS SHALL BE BONDED TO EES 5.

SEE FAA-STD-019F FOR SIZE AND QUANTITY REQUIRED.

ALL MECHANICAL GROUND LUG BONDS SHALL INCLUDE SPRING DISC (BELLEVILLE) WASHERS. 4.

WITH A BARE 2 AWG MINIMUM COPPER CONDUCTOR.

EXOTHERMICALLY WELDED TO THE EARTH ELECTRODE SYSTEM AT THE CROSSING POINT

ALL BELOW GRADE RGS CONDUITS CROSSING EARTH ELECTRODE SYSTEMS SHALL BE 3.

TERMINAL MILLIOHMMETER.

JOINTS AND FITTINGS SHALL BE LESS THAN 5 MILLIOHMS RESISTANCE MEASURED WITH A 4

ENCLOSURES, AND HANDHOLES FOR CONNECTION TO BONDING CONDUCTORS. CONDUIT

RGS CONDUITS SHALL INCLUDE GROUND BUSHINGS AT ALL J-BOXES, EQUIPMENT 2.

BELOW GRADE GROUNDING, EES CONNECTIONS SHALL BE EXOTHERMICALLY WELDED.1.

SUBCONTRACTOR SHALL DOUBLE LOCK.

DISCONNECTS, NO EXCEPTIONS. FAA SHALL OPEN, APPLY LOCK OUT, AND THEN THE

ONLY FAA PERSONNEL MAY DE-ENERGIZE EQUIPMENT AND OPEN CIRCUIT BREAKERS AND 12.

CONDUCTORS SHALL BE 12AWG MINIMUM FOR ALL LIGHTING AND RECEPTACLES CIRCUITS.

POWER CONDUCTORS SHALL BE COPPER WITH THHN/THWN 90DEG INSULATION. 11.

AND RECOMMENDATIONS.

CABLES SHALL BE INSTALLED WITHOUT SPLICES PER MANUFACTURER'S INSTRUCTIONS

SWAB AND MANDREL PROOF ALL BURIED CONDUITS PRIOR TO CABLE INSTALLATION. 10.

OTHERWISE NOTED.

BURIED CONDUITS SHALL BE A MINIMUM OF 24" BELOW GRADE (TOP OF CONDUIT) UNLESS 9.

NECESSARY WITH RE APPROVAL.

ROUTING PATHS BASED ON FIELD VERIFICATION OF EQUIPMENT LOCATIONS. ADJUST AS

COMPLETE POWER SYSTEMS INSTALLED UNDER THIS CONTRACT. VERIFY CONDUIT

PROVIDE ALL CONDUIT, JUNCTION BOXES, CABLES, TERMINATIONS, ETC. AS REQUIRED TO 8.

CONDUITS.

SHALL BE PUMPED DRY AND KEPT DRY WHILE ACCESSING OR INSTALLING CABLES AND/OR

CONSTRUCTION IN ACCORDANCE WITH CONTRACT REQUIREMENTS. TRENCHES/VAULTS

PROVIDE DEWATERING OF ALL TRENCHES AND EXCAVATIONS IF WATER IS PRESENT DURING 7.

PHENOLIC LABELS IDENTIFYING EQUIPMENT.

ALL EQUIPMENT AND ENCLOSURES INSTALLED UNDER THIS CONTRACT SHALL INCLUDE 6.

GALVANIZED (HDG) STRUT. FASTENERS SHALL ALSO BE HDG.

UNDER THIS CONTRACT. EQUIPMENT SHALL BE SUPPORTED ON 1 5/8" HOT DIPPED

PROVIDE ADEQUATE FASTENING AND SUPPORT FOR ELECTRICAL EQUIPMENT INSTALLED 5.

SHALL BE UV RATED SCHEDULE 80.

PVC CONDUIT SHALL ONLY BE PERMITTED FOR GROUND CONDUCTORS. PVC CONDUIT 4.

CONDUIT.

SCREW OR COMPRESSION TYPE FITTINGS ARE ALLOWED WITH RGS or RGSC-PVC COATED

NOT ALLOWED. ALL RGSC CONDUIT SHALL USE THREADED TYPE FITTINGS ONLY. NO SET

BE RGSC-PVC COATED, INCLUDING THE FITTINGS. ALUMINUM RACEWAYS OR FITTINGS ARE

ABOVE GRADE CONDUIT SHALL BE RGSC. UNDER GROUND AND IN SLAB CONDUITS SHALL

PERMITTED CONDUIT TYPES ARE RGSC, RGSC-PVC COATED, AND PVC. ALL EXTERIOR 3.

CASE SHALL NEC ARTICLE 110-26 BE VIOLATED.

COORDINATE WITH EQUIPMENT TO AVOID SPACE CONFLICTS WHERE NECESSARY. IN NO

ALL EQUIPMENT DIMENSIONS SHOWN ARE NOMINAL. FIELD VERIFY ALL DIMENSIONS AND 2.

THE NEC (NFPA 70), FAA-STD-019F, AND FAA-C-1217H.

SPECIFICATIONS. ALL ELECTRICAL WORK SHALL COMPLY WITH THE CURRENT EDITION OF

ELECTRICAL INSTALLATION SHALL BE IN ACCORDANCE WITH DIVISION 26 OF CONTRACT 1.

GENERAL ELECTRICAL NOTESGENERAL GROUNDING NOTES

GFR

GEN

GND

BC BARE COPPER

GEC GROUND ELECTRODE CONDUCTOR

EES EARTH ELECTRODE SYSTEM

HD HEAVY DUTY

GALVANIZED RIGID STEEL

RECP

RMS

PWR

PVC

PRI

MTS

MPG

MLO

MCM

MBS

OL

NEC

NEMA

NO

TRANSFORMERXFMR

RECEPTACLE

ROOT MEAN SQUARE

TELEPHONE COMPANYTELCO

TERMINAL BLOCKTB

TVSS

SYM

SWBD

SW

STR

SPST

SHT

SEC

SYMMETRICAL

SWITCHBOARD

SWITCH

STARTER

SINGLE POLE SINGLE THROW

SHEET

SECONDARY

SURGE PROTECTION

VFD VARIABLE FREQUENCY DRIVE

UNDERWRITERS LABORATORYUL

WP

WHM

W

VA

V

UPS

UF

WEATHERPROOF

WATT HOUR METER

WIRE/WATTS

VOLTAMPERES

VOLT

UNINTERRUPTIBLE POWER SYSTEM

UNFUSED

POLYVINYL CHLORIDE

PRIMARY

PHASE

MANUAL TRANSFER SWITCH

MULTIPOINT GUARD

MAIN LUGS ONLY

THOUSAND CIRCULAR MILS

MAINTENANCE BY PASS SWITCH

MOTOR

OVERLOAD

MANUFACTURERS ASSOCIATION

NATIONAL ELECTRIC CODE

NATIONAL ELECTRIC

NORMALLY OPEN

TRANSIENT VOLTAGE

ELECTRICAL METALLIC TUBING

EXISTING

LMFC LIQUID TIGHT METALLIC FLEXIBLE CONDUIT

RGSC RIGID GALVANIZED STEEL CONDUIT

X

J

A-XX

, [PXX]P-X

X

AIR AMP INTERRUPTING RATING

EX

GFCI GROUND FAULT CIRCUIT INTERRUPTER

GFCI

LIGHTING CONTACTOR

EGC EQUIPMENT GROUND CONDUCTOR

TO BE DETERMINEDTBD

FUSED CUTOUT

CIRCUIT BREAKER

HOME RUN INDICATOR

JUNCTION BOX

LIGHT SWITCH

RECEPTACLE, GROUND FAULT CIRCUIT INTERRUPTER

RECEPTACLE

PHASE/DIAMETER

CONNECTION TO GROUND ROD

EARTH, SOIL

CONCRETE

SCHEDULE NUMBER

TRANSFORMER

FUSED DISCONNECT SWITCH

EQUIPMENT AS NOTED

DEMOLISHED EQUIPMENT AS NOTED

CABLE CALLOUT

BATTERY BANK

OR SPLICE

SCHEMATIC CONNECTION

CABLE AS NOTED

CONDUIT, WIREWAY,

NOTED OTHERWISE

NEW CONSTRUCTION UNLESS

HEAVY LINE WEIGHTS SHOW

REFERENCE NOTES

GROUND CONNECTION TO EES

(12 AWG THHN, COPPER, SOLID - TYPICAL)

HOOK SLASH INDICATES GROUND CONDUCTOR

LONG SLASH INDICATES NEUTRAL CONDUCTOR

SHORT SLASH INDICATES PHASE CONDUCTOR

BRANCH CIRCUIT CONDUCTOR IDENTIFICATION-

ELECTRICAL

SYMBOLS LEGEND

ABBREVIATIONS

ENCLOSURE

ENGINE GENERATOR SET

AMPERE (AMPS)

ALTERNATING CURRENT

AMPS-FRAME

AC

AF

EMT

ENCL

EGS

FULL LOAD AMPS

EQUIPMENT

FLEXIBLE METAL CONDUIT

FLUORESCENT

FUSE

FIXTURE

GENERATOR

GOVERNMENT FURNISHED MATERIAL

GROUND

HANDHOLE

INTERMEDIATE METAL TUBING

JUNCTION BOX

THOUSAND CIRCULAR MILS

KILOVOLT

KILOVOLT AMPERES

KILOWATT

KILOWATT HOURS

LIGHT POLE

LIGHTING

LOW VOLTAGE

GROUND FAULT RELAY

AMPS-TRIP

AUTOMATIC TRANSFER SWITCH

AUTOMATIC

AMERICAN WIRE GAUGE

AT

ATS

AWG

AUXILIARYAUX

BATT BATTERY

CONDUIT

CABINET

CIRCUIT BREAKER

COMMUNICATIONS

CURRENT TRANSFORMER

COPPER

CAB

CB

COMM

CT

CU

CND CONDUIT

COND CONDUCTOR

DISC

DP

DPDT

DPST

DC

DDC

DS

DISCONNECT

DOUBLE POLE

DOUBLE POLE DOUBLE THROW

DOUBLE POLE SINGLE THROW

DIRECT CURRENT

DIRECT DIGITAL CONTROL

DISCONNECT SWITCH

FLA

EQUIP

FLEX

FLUOR

FU

FIXT

GRS

GFM

HH

IMT

JB

KCM

KV

KVA

KW

KWH

LP

LTG

LV

LOCKED ROTOR AMPSLRA

x ; 1B, TYPE 5 DISTRIBUTION PATTERN x ; 1A, TYPE 3 DISTRIBUTION PATTERN

LP-1x - LIGHT POLE SINGLE BLADE LIGHT FIXTURE

(180 DEGREE ORIENTATION)

LP-2 - LIGHT POLE DOUBLE BLADE LIGHT FIXTURE

LP-4 - LIGHT POLE FOUR BLADE LIGHT FIXTURE

(90 DEGREE ORIENTATION)

LP-2 - LIGHT POLE DOUBLE BLADE LIGHT FIXTURE

LP-1x

2023-01-19T09:20:59-0800

Joshua Chua Wu

2023-01-23T05:57:52-0800

CALLEN R COLLINS

:5

ZONE 5 - NORTH LOT

ZSE-20006240-E105

FOR ZONE IS FED FROM PANEL GH-L.27.

ZONE 5, NORTH LOT IS FED FROM PANEL GH-H.26,28,30. TIMER

DISMANTLE LP-2 DOUBLE BLADE LIGHT FIXTURES. LIGHT POLES,

LIGHT POLE DOUBLE BLADE LIGHT FIXTURE

LIGHT POLE FOUR BLADE LIGHT FIXTURE

LP-2LP-2

GH-H .26, 28, 30GH-H .26, 28, 30

1 2

2023-01-19T08:59:40-0800

Joshua Chua Wu

2023-01-20T13:23:45-0800

CALLEN R COLLINS

LIGHTING PLAN

ZONE 1 - EAST LOT

ZSE-20006240-E201

CONDUCTORS.

ON EXISTING LIGHT POLES. REUSE EXISTING CONDUIT AND

PROVIDE AND INSTALL NEW LP-1A SINGLE BLADE LIGHT FIXTURE

ZONE 1, EAST LOT IS FED FROM PANEL DPE.26, 28, 30. TIMER

REFER TO SHEET E601 FOR LIGHT FIXTURE AND LIGHT POLE 7.

TO PROVIDE NEW OR MODIFY EXISTING MOUNTING BRACKETS.

ORIENT LIGHT FIXTURES AS SHOWN ON DRAWING. CONTRACTOR IS 6.

CONTRACTOR SHALL FURNISH AND INSTALL NECESSARY CONDUITS, 5.

FAA ORDER 1600.69C.

PERIMETER FENCING SHALL NOT EXCEED 1.0 FOOT-CANDLES PER

INTO NEIGHBORING PROPERTIES. ILLUMINATION LEVELS BEYOND THE

GLARING PLATE, DIFFUSER, OR EQUIV. TO PREVENT LIGHT SHINING

FOR EACH LIGHT FIXTURE, CONTRACTOR SHALL PROVIDE & INSTALL 4.

PART 15 FOR ELECTROMAGNETIC INFERENCE.

NEW LIGHT FIXTURES SHALL COMPLY WITH FCC CFR TITLE 47 3.

2023-01-19T09:02:50-0800

Joshua Chua Wu

2023-01-20T13:30:57-0800

CALLEN R COLLINS

ZONE 2 - SOUTH LOT

ZSE-20006240-E202

PROVIDE AND INSTALL NEW LP-1B SINGLE BLADE LIGHT FIXTURE

ZONE 2, SOUTH LOT IS FED FROM PANEL DPE.26, 28, 30. TIMER 3

1 11

LP-1A LP-1ALP-1ALP-1A

2023-01-19T09:09:04-0800

Joshua Chua Wu

2023-01-20T13:32:19-0800

CALLEN R COLLINS

ZONE 3 - SOUTHWEST LOT

ZSE-20006240-E203

PP-CT.22,24. TIMER FOR ZONE IS FED FROM PANEL LP-CT.18.

ZONE 3, SOUTHWEST LOT IS FED FROM PANEL

NEW CONDUCTORS

PROVIDE AND INSTALL NEW LP-1B SINGLE BLADE LIGHT FIXTURE 2

PP-CT .22, 24

LP-1A LP-1A

2023-01-19T09:11:49-0800

Joshua Chua Wu

2023-01-20T13:33:48-0800

CALLEN R COLLINS

ZONE 4 - WEST LOT

ZSE-20006240-E204

ZONE IS FED FROM PANEL EOB15A.10.

ZONE 4, WEST LOT IS FED FROM PANEL EOB15A.8. TIMER FOR

PROVIDE AND INSTALL NEW LP-4 FOUR BLADE LIGHT FIXTURE

EXISTING LIGHT POLES. REUSE EXISTING CONDUIT AND

PROVIDE AND INSTALL NEW LP-2 BLADE LIGHT FIXTURE ON

FROM PANEL EOB15A.10.

LIGHT POLE.FROM PANEL EOB15A.8. TIMER FOR ZONE IS FED

CONDUCTORS BETWEEN NEW LIGHT POLE AND EXISTING ZONE 4

NEW LP-1A FIXTURE. PROVIDE AND INSTALL NEW CONDUIT AND

AND BASE AT PRE-EXISTING GLOBE LIGHT LOCATION. INSTALL

PROVIDE AND INSTALL NEW 25' LIGHT POLE (P25), FOUNDATION, 4

EOB15A.8

(2) #12, (1) #12 GND

IN 3/4" RSC

2023-01-19T09:14:04-0800

Joshua Chua Wu

2023-01-20T13:28:41-0800

CALLEN R COLLINS

ZONE 5 - NORTH LOT

ZSE-20006240-E205

FOR ZONE IS FED FROM PANEL GH-L.27.

ZONE 5, NORTH LOT IS FED FROM PANEL GH-H.26,28,30. TIMER

PLAN. REUSE EXISTING CONDUIT AND CONDUCTORS.

ON EXISTING LIGHT POLES. NOTE ORIENTATION OF BLADES ON

PROVIDE AND INSTALL NEW LP-2 DOUBLE BLADE LIGHT FIXTURE

PROVIDE AND INSTALL NEW LP-1B SINGLE BLADE LIGHT FIXTURE

GH-H .26, 28, 30GH-H .26, 28, 30

2023-01-19T09:16:47-0800

Joshua Chua Wu

2023-01-20T13:26:55-0800

CALLEN R COLLINS

ZONE 6 - NORTHEAST ADDITION

ZSE-20006240-E206

NEW LIGHT POLES AND PANEL E-ANTFM.

PROVIDE AND INSTALL NEW CONDUIT AND CONDUCTORS BETWEEN

AND LP-1B SINGLE BLADE LIGHT FIXTURES.

PROVIDE AND INSTALL NEW 15' LIGHT POLE, LIGHT POLE BASE 1

FOR THIS ZONE.

POWER. INSTALL 20A BREAKER ON CKT #9 FOR TIMER CIRCUIT

E-ANTFM. INSTALL 20A 2 POLE BREAKER ON CKTS #13, 15 FOR

NEW ZONE 6, NORTHEAST ADDITION IS FED FROM PANEL

SCALE: 1" = 20'

20' 40'020'

PERSONNEL

GATE

ZONE 6

PANEL E-ANTFM .13, 15

65'-0" 15'-0"

(1) #12 GND

(2) #12AWG,

CL

CL CL

2023-01-19T09:17:12-0800

Joshua Chua Wu

2023-01-20T13:35:19-0800

CALLEN R COLLINS

:0

EQ.

Q

LIGHTING PLAN AND DETAIL

GUARD HOUSE KIOSK

ZSE-20006240-E301

GUARD HOUSE PLAN

SCALE: 3/16" = 1'-0"A301

GUARD HOUSE KIOSK FRONT ELEVATION

SCALE: 3/8" = 1'-0"A301

SCALE: 3/16" = 1'-0"

8' 12'4'04'

SCALE: 3/8" = 1'-0"

4' 6'2'02'

LANE ROADWAY.

BRACKET. ORIENT BRACKET TO APPROX. 45deg FACING DRIVE

PROVIDE AND INSTALL LUMINAIRE SL-1 ON MFG. OPTIONAL ANGLE 1

PNL GH-L .29

EXISTING CONDUIT

AND CONDUCTORS

NEW LOCAL

SWITCH

NEW LED LUMINAIRE SL-1

NEW CONDUIT AND

CONDUCTORS FOR LIGHT

AND SWITCH

(2) #12, (1) #12 GND

VEHICLE

INSPECTION

LIGHT

EXISTING WEATHER

PROTECTION KIOSK

NEW LED LUMINAIRE SL-1

CARD

READER

BOLLARD

NEW LOCAL

SWITCH ON

REAR POST

KIOSK ROOF FLASHING

2023-01-19T09:17:36-0800

Joshua Chua Wu

2023-01-20T13:39:30-0800

CALLEN R COLLINS

FAA-C-1391E

SAND BEDDING PER

OR NEW PAVEMENT

AT FINISHED GRADE

TOP SOIL

BACKFILL MATERIAL

COMPACTED

WARNING TAPE

CONDUIT 1" PVC COATED RGSC

(MINIMUM 2"x4")

IN POLE HANDHOLE

FINISHED GRADE

(WHERE APPLICABLE)

TO NEXT LIGHT POLE

1" PVC COATED RGSC

BASE PLATE COVER

STEEL GROUND ROD

LONG COPPER CLAD

3/4" DIA. X 10'-0"

(WHERE APPLICABLE)

TO NEXT LIGHT POLE

1" PVC COATED RGSC

(SEAL ALL PENETRATIONS)

FINISHED GRADE

GROUND SLEEVE BELOW

1" PVC SCH 80 CONDUIT

2AWG BARE COPPER

TO THE GROUND ROD

EXOTHERMICALLY WELDED

COPPER CONDUCTOR TO BE

GROUND LUG WITH 2AWG BARE

2'-0"

(T Y

IC

ALL EXPOSED EDGES

3/4" CHAMFER

1" SLOPE

SONOTUBE POLE

24" DIAMETER

(TYPICAL)

12 #5, EQUALLY SPACED

CENTER (TYPICAL)

#3 HOOP TIES, 12" ON

(TYPICAL ALL SIDES)

3" MIN CLEAR

1'-0"

TEMPLATE TO SET ANCHOR BOLTS

-SEE LIGHT POLE MANUFACTURE ANCHOR

FOUR (4) ANCHOR BOLTS

FOUNDATION DETAILS

ZSE-20006240-E501

CONSTRUCTION NOTES

NOTES.

SEE SHEET -E001 FOR ELECTRICAL GENERAL AND GROUNDING 2.

SEE SHEET -G002 FOR SYMBOLS AND ABBREVIATIONS.1.

INSTRUCTIONS.

POLE ANCHORING IN ACCORDANCE WITH MANUFACTURERS

WITH FIXTURE SCHEDULE. PROVIDE FIXTURE MOUNTING AND LIGHT

PROVIDE LIGHT POLES AND LIGHT FIXTURES IN ACCORDANCE

EGC SHALL ALSO BE BONDED TO IN POLE GROUND BUS.

EQUIPMENT GROUND CONDUCTORS ROUTED IN EACH CONDUIT.

BOND CONDUIT GROUND BUSHINGS TO GROUND BUS WITH THE

TERMINATED TO THE GROUND BUS IN THE LIGHT POLE BASE.

EXOTHERMICALLY WELDED TO THE GROUND ROD AND

A BARE 2AWG COPPER GROUNDING CONDUCTOR

GROUND EACH LIGHT POLE WITH A 3/4" X 10' GROUND ROD AND

ADJACENT TO THE POLE FOUNDATION.

FIBER EXPANSION JOINT WHERE CONCRETE SURFACE IS

REMOVE SONOTUBE ONCE CONCRETE HAS HARDENED. PROVIDE

NOT TO SCALEE501

LIGHTING POLE FOUNDATION DETAIL-TYPICAL

NOT TO SCALEE501

TYPICAL DIRECT BURIAL CONDUIT SECTION-TYPICAL

2023-01-19T09:18:03-0800

Joshua Chua Wu

2023-01-20T13:37:59-0800

CALLEN R COLLINS

LIGHTING SCHEDULE

ZSE-20006240-E601

2023-01-19T09:18:28-0800

Joshua Chua Wu

2023-01-20T13:41:06-0800

CALLEN R COLLINS

(ALT FEED)

TRANSFORMER GTA IN RM 110

MCC-C Circuit 6

PSB 110 W Wall

DPE

IN RM 110

E/G #6 IMMERSION HEATER

AHU-520 IN RM 201

(ZONE 1)

EAST SECURUTY LIGHT

FP-2 (AHU-510) RM 201

AHU-515 IN RM 201

BATTERY CHARGER 5DCB

FAB

BATT RM HYDROGEN MONITOR

ACP-6A NETWORK SW-4

120/208 125

GLB Circuit #32

PSB 110 W Wall

20 PCMS LIGHTING IN RM 109

20 SPARE

BATT CHARGER AC-3C RM 110

BATT MON. SYS. RM 108 (OFF)

GLB-1

BATTERY RM BEACON LIGHTS

DDCP-26 PSB EX FANS

DDCP-23,24,25 RM 201 (AHU 510,515,520)

BATTERY ROOM SF-19

BATTERY ROOM EF-9

LIGHTING CONTACTOR RM 110

ELD

IN RM 109

BATTERY CHARGER 4DCB

EXHAUST FAN 581B IN RM 110

PA-9 (CAMERA 303)20

PAD-2 IN RM 109

APMS INFONODE, APC, DC-LINK CURRENT

APMS UPMS 1-5

APMS SWITCHGEAR & PCMS (C-BUS)

OUTLETS RM 110(E), 104(W), 101(SW&UPS)

PANELS DPE & GLB-1

PANEL SCHEDULES - ZONE 1 & 2

ZSE-20006240-E801

ZONE 1 & 2 ZONE 1 & 2

2023-01-19T09:18:50-0800

Joshua Chua Wu

2023-01-23T05:53:36-0800

CALLEN R COLLINS