Attachment 11 - Drawing ZSE-20006240-E204 - Revised 5-24-2023.pdf
PDF 623 KB Posted
- Attached to
- Amendment 0004 to Replace Parking Lot Lighting at Seattle Air Traffic Facility Federal contract opportunity
- Solicitation number
- 697DCK-23-R-00332
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 697DCK-23-R-00332 Amendment 0004.pdf | ||
| 697DCK-23-R-00332 Amendment 0003.pdf | ||
| Attachment 10 - Grounding Grid Layout.pdf | ||
| 697DCK-23-R-00332 Amendment 0002.pdf | ||
| 697DCK-23-R-00332 Amendment 0001.pdf | ||
| Attachment 3 - REF FAA-C-1391e.pdf | ||
| Attachment 4 - REF FAA-STD-019f.pdf | ||
| RFO 697DCK-23-R-00332.pdf | ||
| Attachment 1 - Specifications.pdf | ||
| Attachment 1(a) - Drawings.pdf | ||
| Attachment 6 - REF FAA Order 3900.19b.pdf | ||
| Attachment 7 - COVID-19 Contractual Requirement.pdf | ||
| Attachment 2 - REF FAA-C-1217h.pdf | ||
| Attachment 5 - REF FAA Order 1600.69C.pdf | ||
| Attachment 8 - Customer Satisfaction Survey.doc | DOC document | |
| Attachment 9 - DB WD No. WA20230011 dated 2-3-2023.pdf |
Show all 16
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
H
G
F
E
D
C
B
A
10'H EXTERIOR
PERIMETER
SECURITY FENCE
9'H INTERIOR
PERIMETER
SECURITY FENCE
ZONE 4 ------=1
n
IA
OPERATIONS
SUPPORT
-WING------1---,---,----l
LP-1A
PARKING j
-- 0 ___________________________________________________ .✓•
6 5 a□ □□
,1lllllllll, n
CONTROL
WING
25' 0 25'
SCALE: 1" = 25'
50'
GENERAL NOTES
1. NO FIXTURES ARE TO BE OUT OF SERVICE BY THE TIME OF
SUNSET, EXCEPT WHERE NEW FEEDER IS REQUIRED OR APPROVED H BY COR. CONTRACTOR SHALL PLAN WORK TO ENSURE MINIMAL
IMPACT TO DAY TO DAY LIGHTING CONDITIONS. COORDINATE
OUT AGES WITH COR
2. ONLY FAA PERSONNEL CAN OPERATE CIRCUIT BREAKERS.
COORDINATE BREAKER SHUT-DOWN WITH COR.
.3. NEW LIGHT FIXTURES SHALL COMPLY WITH FCC CFR TITLE 4 7
PART 15 FOR ELECTROMAGNETIC INFERENCE.
4. FOR EACH LIGHT FIXTURE, CONTRACTOR SHALL PROVIDE 8, INSTALL
GLARING PLATE, DIFFUSER, OR EQUIV. TO PREVENT LIGHT SHINING
INTO NEIGHBORING PROPERTIES. ILLUMINATION LEVELS BEYOND THE
PERIMETER FENCING SHALL NOT EXCEED 1.0 FOOT-CANDLES PER
FAA ORDER 16OO.69C. G
5. CONTRACTOR SHALL FURNISH AND INST ALL NECESSARY CONDUITS,
CONDUCTORS, AND TIMERS WHERE NECESSARY.
6. ORIENT LIGHT FIXTURES AS SHOWN ON DRAWING. CONTRACTOR IS
TO PROVIDE NEW OR MODIFY EXISTING MOUNTING BRACKETS.
7. REFER TO SHEET E6O1 FOR LIGHT FIXTURE AND LIGHT POLE
SCHEDULES.
SHEET NOTES
/,'\. PROVIDE AND INST ALL NEW LP-1A SINGLE BLADE LIGHT FIXTURE
"'/ ON EXISTING LIGHT POLES. REUSE EXISTING CONDUIT AND
CONDUCTORS.
A PROVIDE AND INST ALL NEW LP-2 BLADE LIGHT FIXTURE ON
V EXISTING LIGHT POLES. REUSE EXISTING CONDUIT AND
CONDUCTORS.
,Ii\. PROVIDE AND INSTALL NEW LP-4 FOUR BLADE LIGHT FIXTURE
':;/ ON EXISTING LIGHT POLES. REUSE EXISTING CONDUIT AND
CONDUCTORS.
M ZONE 4, WEST LOT IS FED FROM PANEL EOB15A,8. TIMER FOR
"'/ ZONE IS FED FROM PANEL EOB15A.1O.
M PROVIDE AND INST ALL NEW 25' LIGHT POLE (P25), FOUNDATION,
"'/ AND BASE AT PRE-EXISTING GLOBE LIGHT LOCATION. INSTALL
NEW LP-1A FIXTURE. PROVIDE AND INST ALL NEW CONDUIT AND
CONDUCTORS BETWEEN NEW LIGHT POLE AND EXISTING ZONE 4
LIGHT POLE.FROM PANEL EOB15A.8. TIMER FOR ZONE IS FED
FROM PANEL EOB15A.1O.
LEGEND
E�ST�G CONDUCTORS
NEW CONDUCTORS
DESCRIPTION JCN
DEPARTMENT OF TRANSPORTATION
FEDERAL AVIATION ADMINISTRATION
ATO - TECHNICAL OPERATIONS WESTERN SERVICE AREA
SEATTLE
REVIEWED BY
ARTCC
UPGRADE PARKING LOT LIGHTING
ZONE 4 - WEST LOT
LIGHTING PLAN
PROJECT ENGINEER
AUBURN WA
MGR: ENGINEERING - SEATTLE
,-.-------,----,-:=�=s==:-e□ ___ J-----1w ENGIN����NE; ;;RVICES cc:=:=:,=No�N�o _01_11 _2,_2 0 _23�Jc_N ___ 2_ o_oo�s2=.'!v cc10
,_______, _ ___,_ _ _ _ _ _ =-,J• ENROUTE/FSS
CHECKED ZSE-20006240-E204
F
E
D
C
<ii :i' w
DRAWING PRODUCED ON WSA MICROSTATK>N SYSTEM
_5
File details come from the government source that posted it. Updated .